    Continuous Current rating Three Core Dimensional Details Single Core Dimensional Details

    11 kv Cable|Home|Enquiry|Sitemap|Contact Us

    Go to product category Next

    Continuous Current Rat ing for Single/ Three Core Cableswith Aluminium / Copper Conductor

    Aluminium

    Copper

    NominalCross

    SectionalArea of

    Conductor

    Continuous Current Rating forThree Core Cable

    Continuous Current Rating forSingle Core Cable

    (Single End bonding)

    When Laid inGround

    When Laid inAir

    When Laid inGround

    When Laid inAir

    Sq.mm. amps amps amps amps

    35115 125 115 140

    145 165 150 180

    50130 150 140 170

    170 195 175 215

    70160 190 170 210

    210 240 215 270

    95190 230 200 255

    250 295 260 325

    120220 260 230 295

    280 335 295 375

    150 245 295 255 335310 380 320 425

    185275 335 290 385

    350 430 370 495

    240315 395 330 455

    400 500 425 580

    300355 450 375 520

    450 570 475 670

    400400 520 425 610

    500 650 540 760

    500455 600 485 720

    550 740 600 900

    630-- -- 550 830

    -- -- 670 1010

    800-- -- 620 950

    -- -- 730 1140

    1000-- -- 670 1070

    -- -- 790 1250

    Ambient Air Temperature: 400 C

    Ground temperature : 300 C

    Thermal Resistivity of Soil : 1500 C cm/ w

    Maximum Continuous Conductor tempera ture : 900 CSingle Core Cable laid in TrefoilThree Core Cable laid SinglyMaximum Conductor Temperature

    after Short Circuit : 250

    0

    C

    Depth of Laying

    3.3 kv to 11 kv Above 11 kv

    900 mm 1050 mm

    Tips:3.Key Manufacturing P rocess in HT Cable

    Manufacturing.

    XLPE Screenings and Insulation by Extrusion

    Conductors made through stranding process aresubjected to this operation to form cores. Theprocess requires three extrusion operations, whichare done simultaneously using three extruders buta common head.

    The core consists of three concentric layers o fextruded material. The first is a layer of black semi

    conducting compound formed over the strandedcompacted conductor using the first extruder. Juston top of this a layer of white insulation compoundis extruded to form the second layer and finallythrough another extruder a layer o f black semiconducting compound is extruded over insulationlayer. The semi conducting layer formed overconductor is called conductor screen and the oneover insulation is called insulation screen. The threelayers i.e .conductor screen, insulation andinsulation screen are formed through a commonhead known as triple head.

    Search

    Go to product category Next

    | About Us | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|Contact Us

    nt Cables Ltd http://www.torrentcables.com/11kv_ht_

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    2/12

    PVC pow er cables with aluminium conductors

    1.1kv Power Cables(Un Armoured)

    |Home|Enquiry|Sitemap|Contact Us

    Go to product category Constructional details aluminium

    Pvc pow er cables w ith aluminum conductors (unarmourded cables)

    Sr.no

    Nominal

    conductor

    area sq.mm.

    Minimum

    nos.of w ires in

    conductor

    Nominal

    thickness of

    insulation in

    mm

    Minimum thickness

    of innersheath in

    mm

    Nominal thickneness of

    outer sheath in mm

    Approximate overall

    diameter in mm

    Approximate weight of

    cable in kg/ kms.

    Main

    coreE

    Half

    coreM ain Neu tral M ain Neutral

    Nos. of cores Nos. of cores Nos. of cores Nos. of cores

    2 3 3.5 4 2 3 3.5 4 2 3 3.5 4 2 3 3.5 4

    1 4 $ - 1 - 1 - 0.3 0.3 0.3 1.80 1.80 1.80 14.3 15.0 16.1 232 256 298

    # 3 - 1 - 0.3 0.3 0.3 1.80 1.80 1.80 14.8 15.6 16.8 250 250 318

    2 6 $ - 1 - 1 - 0.3 0.3 0.3 1.80 1.80 1.80 15.5 16.3 17.7 280 315 371

    # 3 - 1 - 0.3 0.3 0.3 1.80 1.80 1.80 16.3 17.2 18.5 305 340 400

    3 10 $ - 1 - 1 - 0.3 0.3 0.3 1.80 1.80 1.80 16.8 17.8 19.2 307 360 425

    # 3 - 1 - 0.3 0.3 0.3 1.80 1.80 1.80 18.0 19.0 20.6 335 390 460

    4 16 $ - 3 - 1 - 0.3 0.3 0.3 1.80 1.80 2.00 20.0 21.2 23.5 415 491 612

    # - -

    5 25 # - 3 1.2 0.3 0.3 0.3 2.00 2.00 2.00 24.1 25.5 28.0 592 732 848

    6 25 @ 16 # 6 7 1.2 1.0 0.3 0.3 0.3 0.3 2.00 2.00 2.00 2.00 20.0 23.4 25.4 25.9 461 600 695 760

    7 35 @ 16 # 6 7 1.2 1.0 0.3 0.3 0.3 0.3 2.00 2.00 2.00 2.00 21.5 25.3 27.5 28.2 552 725 825 920

    8 50 @ 25 @ 6 6 1.4 1.2 0.3 0.3 0.3 0.4 2.00 2.00 2.00 2.20 23.9 28.5 31.2 33.0 700 928 1070 1250

    9 70 @ 35 @ 12 6 1.4 1.2 0.3 0.4 0.4 0.4 2.00 2.20 2.20 2.20 26.7 32.0 34.8 35.8 871 1230 1415 1570

    10 95 @ 50 @ 15 6 1.6 1.4 0.4 0.4 0.4 0.4 2.20 2.20 2.20 2.40 30.4 35.7 38.9 40.5 1180 1577 1818 2065

    11 120 @ 70 @ 15 12 1.6 1.4 0.4 0.4 0.5 0.5 2.20 2.20 2.40 2.40 32.4 38.2 42.2 43.2 1384 1860 2262 2485

    12 150 @ 70 @ 15 12 1.8 1.4 0.4 0.5 0.5 0.5 2.40 2.40 2.40 2.60 35.6 42.5 46.2 47.8 1688 2322 2642 3030

    13 185 @ 95 @ 30 15 2.0 1.6 0.5 0.5 0.5 0.6 2.40 2.60 2.60 2.80 39.0 46.7 50.8 53.0 2066 2840 3270 3760

    14 240 @ 120 @ 30 15 2.2 1.6 0.5 0.6 0.6 0.6 2.60 2.80 3.00 3.00 43.5 52.3 57.2 58.8 2605 3640 4225 4736

    15 300 @ 150 @ 30 15 2.4 1.8 0.6 0.6 0.6 0.7 2.80 3.00 3.20 3.40 48.0 57.5 62.9 65.0 3222 4430 5135 5902

    16 400 @ 185 @ 53 30 2.6 2.0 0.7 0.7 0.7 0.7 3.20 3.40 3.40 3.60 54.5 65.0 70.5 73.0 4165 5818 6515 7422

    -Extruded Pvc Inner Sheath $ = Solid Circular Aluminium Conductor-Standard drum length for all sizes : 500mtrs. 5% # = Stranded Circular Alumimium Conductor

    @ =Standard Sector Shaped Aluminum Conductor

    Go to product category

    Search

    | Company | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|Contact

    nt Cables Ltd http://www.torrentcables.com/PVC_power_cables_unarmou

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    3/12

    Control cables w ith stranded circular copper conductor Control cables with solid circular copper conductor

    1.1kv Control Cables(Armoured)

    |Home|Enquiry|Sitemap|Contact Us

    Go to product category NextControl cables wi th stranded circular copper conductor (armoured)

    Sr.no.

    No.of cores

    and

    conductor

    area sq.mm.

    Copper

    conductor

    minimum

    no.of wires

    Thickness of

    insulation

    (mm)

    Thickness of innersheath

    in mm

    Armou r size in mm

    & type Minimum

    thickness o f

    outer sheath

    (mm)

    Approximate

    overall d iameter

    (mm)

    Approximate

    weight of cables

    (kg./ km)Extruded W rapped

    Round

    wireFlat strip

    1 2 X 1.5 3 0.8 0.3 - 1.4 - 1.24 14.2 420

    2 3 X 1.5 3 0.8 0.3 - 1.4 - 1.24 14.5 460

    3 4 X 1.5 3 0.8 0.3 - 1.4 - 1.24 15.5 510

    4 5 X 1.5 3 0.8 0.3 - 1.4 - 1.24 16.5 562

    5 7 X 1.5 3 0.8 - 0.3 1.4 - 1.24 17.1 605

    6 10 X 1.5 3 0.8 - 0.3 1.4 - 1.40 20.9 820

    7 12 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.24 20.0 700

    8 14 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.40 21.1 785

    9 16 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.40 22.0 865

    10 19 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.40 23.1 955

    11 24 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.40 26.3 117512 27 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.40 27.0 1240

    13 30 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.40 27.9 1340

    14 37 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.40 29.7 1545

    15 44 X 1.5 3 0.8 - 0.3 - 4 X 0.8 1.56 33.0 1840

    16 52 X 1.5 3 0.8 - 0.4 - 4 X 0.8 1.56 35.0 2070

    17 61 X 1.5 3 0.8 - 0.4 - 4 X 0.8 1.56 37.0 2340

    Sr.no.

    No.of cores

    and conductor

    area sq.mm.

    Copper

    conductor

    minimum

    no.of wires

    Thickness of

    insulation

    (mm)

    Thickness of innersheath

    in mm

    Armou r size in mm

    & typeMinimum

    thickness of

    outer sheath

    (mm)

    Approximate

    overall d iameter

    (mm)

    Approximate

    weight of cables

    (kg./km)Extruded W rapped Round

    wireFlat strip

    1 2 X 2.5 3 0.9 0.3 - 1.4 - 1.24 15.5 500

    2 3 X 2.5 3 0.9 0.3 - 1.4 - 1.24 16.1 550

    3 4 X 2.5 3 0.9 0.3 - 1.4 - 1.24 17.0 625

    4 5 X 2.5 3 0.9 0.3 - 1.4 - 1.24 18.2 686

    5 7 X 2.5 3 0.9 - 0.3 1.4 - 1.24 19.0 751

    6 10 X 2.5 3 0.9 - 0.3 - 4 X 0.8 1.24 22.3 861

    7 12 X 2.5 3 0.9 - 0.3 - 4 X 0.8 1.40 22.9 935

    8 14 X 2.5 3 0.9 - 0.3 - 4 X 0.8 1.40 24.0 1030

    9 16 X 2.5 3 0.9 - 0.3 - 4 X 0.8 1.40 25.0 1140

    10 19 X 2.5 3 0.9 - 0.3 - 4 X 0.8 1.40 26.1 1270

    11 24 X 2.5 3 0.9 - 0.3 - 4 X 0.8 1.40 30.1 1566

    12 27 X 2.5 3 0.9 - 0.3 - 4 X 0.8 1.40 30.8 1675

    13 30 X 2.5 3 0.9 - 0.3 - 4 X 0.8 1.40 32.3 1845

    14 37 X 2.5 3 0.9 - 0.4 - 4 X 0.8 1.56 34.6 2170

    15 44 X 2.5 3 0.9 - 0.4 - 4 X 0.8 1.56 38.5 2545

    16 52 X 2.5 3 0.9 - 0.4 - 4 X 0.8 1.56 40.5 2860

    17 61 X 2.5 3 0.9 - 0.4 - 4 X 0.8 1.56 42.5 3240

    Go to product category Next

    Search

    | About Us | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|Contact Us

    nt Cables Ltd http://www.torrentcables.com/control_cables_armou

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    4/12

    Standard Operating Parameters Current Rating Short Circuit Rating Rating Factors

    PVC Common design details |Home|Enquiry|Sitemap|Contact Us

    Go to product category Next

    Standard OperatingParameters

    Maximum ConductorTemperature

    70 C (85 C for HR Cable)

    Thermal resistivity of soil 150 C.cm./w

    Thermal resistivity of PVC 650 C.cm./w

    Ground temperature 30 C

    Ambient air temperature 40 C

    Depth of laying in Cms (Cableslaid in ground)

    75 cm

    Type o f installation

    Twin, Three & Multicore Cables Laid singly

    Single core Cable3 Cores in close trefoilformation

    Current Rating (ac) for Three Single Core 650/ 1100 VOLTSUnarmoured / Non- Magnetic Armoured Cables according to is : 1554(Part I) 1988

    SR.NO.

    NOMINALCROSS

    SECTIONAL

    AREA

    (sq.mm.)

    LAID DIRECT IN

    GROUNDLAID IN DUCT LAID IN AIR

    COPPER

    (Amps)

    ALUMINIUM

    (Amps)

    COPPER

    (Amps)

    ALUMINIUM

    (Amps)

    COPPER

    (Amps)

    ALUMINIUM

    (Amps)

    1 1.5 22 17 21 17 20 15

    2 2.5 30 24 29 24 27 21

    3 4 39 31 38 30 35 27

    4 6 49 39 48 37 44 35

    5 10 65 51 64 51 60 47

    6 16 85 66 83 65 82 64

    7 25 110 86 110 84 110 84

    8 35 130 100 125 100 130 105

    9 50 155 120 150 115 165 130

    10 70 190 140 175 135 205 155

    11 95 220 175 200 155 245 190

    12 120 250 195 220 170 280 220

    13 150 280 220 245 190 320 250

    14 185 305 240 260 210 370 290

    15 240 345 270 285 225 425 335

    16 300 375 295 310 245 475 380

    17 400 400 325 335 275 550 435

    18 500 425 345 355 295 590 480

    19 625 470 390 375 320 660 550

    20 800 540 440 405 345 765 640

    21 1000 600 490 435 370 860 720

    Tips:

    9.Follow ing care should be taken wh ilelaying the Cable Across Roads, Railway

    Tracks or Water Pipe Lines :

    Steel, Castlron, Plastics, Cement or earthenwareducts or cable ducting blocks should be usedwhere cables cross roads and railways tracks.

    Spare ducts for future extension should beprovided & sealed at both ends.

    Ensure smooth entry of cable without undue

    bending.

    The duct/pipe joints should be covered by collarsto prevent settlement in between pipes.

    The diameter of the cable conduit or pipe or ductshould be atleast 1.5 times the outer diameterof cable. The pipe/duct should be mechanicallystrong enough to withstand forces due to heavytraffic when laid across road/railway tracks.

    The cable entry and exit should be through bellmouth or padding.

    The bending radii of steel or plastic ducts shouldnot be less than 1.5 m.

    Single core cables should not be laid individually

    in ducts, butall3 cables of the same systemshould be laid in one duct.

    Search

    Go to product category Next

    | About Us | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|Contact Us

    nt Cables Ltd http://www.torrentcables.com/PVC_common_design_de

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    5/12

    Standard Operating Parameters Continuous Current RatingMaximum short circuit rating of conductor for a duration of one second Rating Factor

    LT-XLPE Common Design Details |Home|Enquiry|Sitemap|Contact Us

    Go to product category Next

    Standard Operating Parameters PVC XLPE

    Maximum conductor temperature for continuous operations ( C) 70 90

    Ambient air temperature ( C) 40 40

    Ground temperature ( C) 30 30

    Thermal resistivity of soil ( C cm/watt) 150 150

    Thermal resistivity ( C cm/w) 650 350

    Depth of laying 75 cm 75cm

    Cables are installed singly

    Minimum bending radious ( for Multi core cables) times cable diameter. 12 12

    Maximum conductor temperature During short circuit ( C) 160 250

    Continuous current rating of 3 or 4 core cables armoured and unarmoured laid direct inthe ground or in air 1100 volts grade with Aluminium conductor.

    3, 3.5 or 4 core cables toIS : 1554 (Pt.1)

    (PVC)

    3, 3.5 or 4 core cables toIS : 7098 (Pt. 1)

    (XLPE)

    Sizesq. mm.

    When Laid inApprox.Voltage

    drop

    v/km/A

    Sizesq. mm.

    When Laid inApprox.Voltage

    drop

    v/km/A

    Groundamps

    Airamps

    Groundamps

    Airamps

    25 76 70 2.50 25 94 96 2.68

    35 92 86 1.80 35 114 117 1.95

    50 110 105 1.30 50 133 142 1.44

    70 135 130 0.94 70 164 179 0.99

    95 165 155 0.68 95 196 221 0.78

    120 185 180 0.55 120 223 257 0.58

    150 210 205 0.46 150 249 292 0.47

    185 235 240 0.37 185 282 337 0.40

    240 275 280 0.30 240 327 400 0.31

    300 305 315 0.27 300 368 455 0.26

    400 335 375 0.22 400 418 511 0.22

    Tips:6.Type of Tests conducted on Finished

    Cables

    Routine TestsRoutine tests are tests conducted on each andevery finished length o f a cable. Routine testsmean tests conducted on a cable to assess itssuitability during routine service condition.

    Type TestsType tests consist of a number of testsconducted on a piece of cable (not on the entiredrum length) cut from a finished cable drumlength. The purpose of these tests is to confirmthe suitability of a cable against the type, whichhas been constructed for a particular application.The sample taken for type tests represents theentire lot of cable manufactured of a particulartype.

    Acceptance TestsAcceptance tests also consist of a number oftests conducted on few pieces of cables drawnfrom a manufactured lot. These tests areconducted during client's witness of testprogramme on a manufactured lot in order todecide about the lotto be shipped for usage ornot.

    Special Tests

    Special tests are those tests which do not getcovered under routine o r type o r acceptancetests. Generally special tests are conducted toassess a particular property or a set ofproperties, which have been built in the cable toexhibit desired requirement during its operation.

    Search

    Go to product category Next

    nt Cables Ltd http://www.torrentcables.com/LT_common_design_de

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    6/12

    Single core Two core Three Core Three & Half Core Four Core

    LT-XLPE UnArmoured Cables |Home|Enquiry|Sitemap|Contact Us

    Go to product category NextSINGLE CORE UNARMOURED CABLES - 1100 VOLTS ALUMINIU M CONDUCTOR WITH XLPE I NSULATION

    NominalArea of

    Conductor

    Single Core unarmoured Cables

    Deliverylength with

    +/- 5%tolerance

    StandardMax DC

    resistanceat 20C

    ACresistance

    at

    OperatingTemp90C

    Nominal

    Thicknessof

    Insulation

    Nominal

    diameterof roundAlu. Wire

    Approx.

    Overalldiameterof cable

    Approx

    weight offinishedcables

    sq.mm. mm. mm. mm. kg/ km meters ohms/ km ohms/ km

    25 0.9 1.8 13.0 177 1000 1.2000 1.536

    35 0.9 1.8 14.0 209 1000 0.8680 1.111

    50 1.0 1.8 15.0 258 1000 0.6410 0.820

    70 1.1 1.8 17.0 337 1000 0.4430 0.567

    95 1.1 1.8 17.0 401 1000 0.3200 0.410

    120 1.2 1.8 21.0 535 1000 0.2530 0.324

    150 1.4 2.0 23.0 642 1000 0.2060 0.264

    185 1.6 2.0 25.0 774 500 0.1640 0.210

    240 1.7 2.0 27.0 968 500 0.1250 0.160

    300 1.8 2.0 30.0 1162 500 0.1000 0.128

    400 2.0 2.2 33.0 1491 500 0.0778 0.100

    Conductor : Stranded Compacted Circular. ( Except 25 sq.mm. Stranded circular)

    | Top

    TWO / THREE CORE UNARMOURED CABLES - 1100 VOLTS ALUMINIUM CONDUCTOR WITH XLPE I NSULATION

    Nominal

    Area of

    Conductor

    Nominal

    Thickness

    of

    Insulation

    Tw o core unarmoured Cable

    (Shaped Cond.)

    3 core unarmoured C able

    (Shaped Cond.)Standard

    Delivery

    length

    with

    +/- 5 %

    tolerance

    Max DC

    resistance

    at 20C

    AC

    resistance

    at

    Operating

    Temp

    90C

    Minimum

    Thickness

    of inner

    sheath

    Nominal

    Thickness

    of outer

    sheath

    Approx.

    Overall

    diameter

    of cable

    Approx

    w eight

    of

    finished

    cables

    Minimum

    Thickness

    of inner

    sheath

    Nominal

    Thickness

    of outer

    sheath

    Approx.

    Overall

    diameter

    of cable

    Approx.

    Weight

    of

    finished

    cable

    sq.mm. mm. mm. mm. mm. kg/ km mm. mm. mm. kg/ km meters ohms/ km ohms/ km

    25 0.90 0.3 2.0 20.0 295 0.3 2.0 23.0 411 500 1.2000 1.536

    35 0.90 0.3 2.0 22.0 377 0.3 2.0 25.0 525 500 0.8680 1.111

    50 1.00 0.3 2.0 24.0 496 0.3 2.0 28.0 686 500 0.6410 0.820

    70 1.10 0.3 2.0 27.0 669 0.4 2.2 32.0 983 500 0.4430 0.567

    95 1.10 0.4 2.2 30.0 912 0.4 2.2 35.0 1253 500 0.3200 0.410

    120 1.20 0.4 2.2 32.0 1167 0.4 2.2 37.0 1587 500 0.2530 0.324

    150 1.40 0.4 2.2 36.0 1413 0.5 2.4 42.0 2001 500 0.2060 0.264

    185 1.60 0.5 2.4 40.0 1786 0.5 2.6 46.0 2467 500 0.1640 0.210

    240 1.70 0.5 2.6 44.0 2252 0.6 2.8 51.0 3163 500 0.1250 0.160

    300 1.80 0.6 2.8 48.0 2784 0.6 3.0 56.0 3841 500 0.1000 0.128

    400 2.00 0.6 3.0 54.0 3539 0.7 3.2 63.0 4948 500 0.0778 0.100

    nt Cables Ltd http://www.torrentcables.com/single_two_three_unarmoured_ca

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    7/12

    Go to product category Next

    Search

    | About Us | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|Contact Us

    nt Cables Ltd http://www.torrentcables.com/single_two_three_unarmoured_ca

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    8/12

    Single core Two core Three Core Three & Half Core Four Core

    LT-XLPE Armoured Cables

    |Home|Enquiry|Sitemap|Contact Us

    Go to product category NextSINGLE CORE ARMOURED CABLES - 1100 VOLTS ALUMINUM CONDUCTOR WITH XLP E INSULATION

    NominalArea of

    Conductor

    Hard drawn A luminium round wire ArmouredStandardDelivery

    length with+/- 5 %

    tolerance

    Max DCresistanceat 20C

    ACresistance

    atOperating

    Temp 90C

    NominalThickness

    ofInsulation

    Nominaldiameter

    of roundAlu. Wire

    MinimumThickness

    of outersheat

    Approx.Overall

    diameterof cable

    Approx.Weight of

    finishedcable

    sq.mm. mm. mm mm. mm. kg/ km meters ohms/ km ohms/ km

    25 1.2 1.4 1.24 14.5 259 1000 1.2000 1.536

    35 1.2 1.4 1.24 15.0 295 1000 0.8680 1.111

    50 1.3 1.4 1.24 17.0 354 1000 0.6410 0.820

    70 1.4 1.4 1.24 18.0 445 1000 0.4430 0.567

    95 1.4 1.6 1.40 19.0 544 1000 0.3200 0.410

    120 1.5 1.6 1.40 23.0 694 1000 0.2530 0.324

    150 1.7 1.6 1.40 25.0 817 1000 0.2060 0.264

    185 1.9 1.6 1.40 26.0 965 500 0.1640 0.210

    240 2.0 1.6 1.40 29.0 1188 500 0.1250 0.160

    300 2.2 1.6 1.56 32.0 1428 500 0.1000 0.128

    400 2.4 2.0 1.56 36.0 1844 500 0.0778 0.100

    Conductor : Stranded Compacted Circular. (Except 25 sq. mm. Stranded circular)

    TWO CORE ARMOURED CABLES - 1100 VOLTS ALUMINI UM CONDUCTOR W ITH XLP E INSULATION

    Nominal

    Area of

    Conductor

    Nominal

    Thickness

    of

    Insulation

    Minimum

    Thickness

    of inner

    sheath

    Flat galvenised steel strip Armo ured

    ( shaped cond)

    Galvenised rou nd steel wire

    Armoured ( shaped cond)Standard

    Delivery

    length

    with

    +/- 5 %

    tolerance

    Max DC

    resistance

    at 20C

    AC

    resistance

    at

    Operating

    Temp

    90C

    Nominal

    dimension

    of flat

    strip

    Minimum

    Thickness

    of outer

    sheat

    Approx.

    Overall

    diameter

    of cable

    Approx

    w eight

    of

    finished

    cables

    Nominal

    diameter

    of round

    g.s.

    Wire

    Minimum

    Thickness

    of o uter

    sheath

    Approx.

    Overall

    diameter

    of cable

    Approx.

    Weight

    of

    finished

    cable

    sq.mm. mm. mm mm. mm. mm. kg/ km mm. mm. mm. kg/ km meters ohms/ km ohms/ km

    25 0.90 0.3 4 x 0.8 1.40 21.0 527 1.6 1.40 22.0 741 500 1.2000 1.536

    35 0.90 0.3 4 x 0.8 1.40 22.0 633 1.6 1.40 24.0 866 500 0.8680 1.111

    50 1.00 0.3 4 x 0.8 1.40 25.0 788 1.6 1.40 26.0 1050 500 0.6410 0.820

    70 1.10 0.3 4 x 0.8 1.56 28.0 1024 1.6 1.56 29.0 1318 500 0.4430 0.567

    95 1.10 0.4 4 x 0.8 1.56 31.0 1285 2.0 1.56 33.0 1822 500 0.3200 0.410

    120 1.20 0.4 4 x 0.8 1.56 33.0 1574 2.0 1.56 35.0 2156 500 0.2530 0.324

    150 1.40 0.4 4 x 0.8 1.72 37.0 1899 2.0 1.72 39.0 2546 500 0.2060 0.264

    185 1.60 0.5 4 x 0.8 1.72 40.0 2295 2.0 1.88 43.0 3047 500 0.1640 0.210

    240 1.70 0.5 4 x 0.8 1.88 44.0 2813 2.5 2.04 48.0 4031 500 0.1250 0.160

    300 1.80 0.6 4 x 0.8 2.04 49.0 3402 2.5 2.20 52.0 4741 500 0.1000 0.128

    400 2.00 0.6 4 x 0.8 2.36 55.0 4281 2.5 2.36 58.0 5738 500 0.0778 0.100

    Extruded PVC inner sheath

    nt Cables Ltd http://www.torrentcables.com/armoured_singlecore_twocore_ca

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    9/12

    Go to product category Next

    Search

    | About Us | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|About Us

    nt Cables Ltd http://www.torrentcables.com/armoured_singlecore_twocore_ca

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    10/12

    Conductor resistance and Short Circuit Carrying Capacity Group Rating Factor fo r Single and Multi Core CablesGroup Rating Factors for Single/Multicore Cables Rating Factor for Ambient Air/Ground Temperature variation

    HT Common design details

    |Home|Enquiry|Sitemap|Contact Us

    Go to product category NextConducto r Resistance and Short Circuit Current Carrying Capacity

    NominalCross

    SectionalArea

    MaximumDC

    Resistance

    at 200 C

    Approx.ACResistance

    at 900 C

    MaximumDC

    Resistance

    at 200 C

    Approx.ACResistance

    at 900 C

    Short Circuit Currentfor Conductor

    Aluminium Conductor Copper Conductor Aluminium Coppersq.mm ohms/ km ohms/ km ohms/ km ohms/ km ka/ sec ka/ sec

    35 0.8680 1.137 0.5240 0.6864 3.29 5.01

    50 0.6410 0.840 0.3870 0.5070 4.70 7.15

    70 0.4430 0.580 0.2680 0.3511 6.58 10.01

    95 0.3200 0.419 0.1930 0.2528 8.93 13.58

    120 0.2530 0.331 0.1530 0.2004 11.28 17.16

    150 0.2060 0.270 0.1240 0.1624 14.10 21.45

    185 0.1640 0.215 0.0991 0.1298 17.39 26.46

    240 0.1250 0.164 0.0754 0.0988 22.56 34.32

    300 0.1000 0.131 0.0601 0.0787 28.20 42.90

    400 0.0778 0.102 0.0470 0.0616 37.60 57.20

    500 0.0605 0.079 0.0366 0.0479 47.00 71.50

    630 0.0467 0.061 0.0283 0.0371 59.22 90.09

    800 0.0367 0.048 0.0210 0.0280 75.20 114.40

    1000 0.0292 0.038 0.0176 0.0231 94.00 143.00

    Group Rating Facto r for Single and Mu lti Core Cables

    Single Core

    Multi Core

    Number of Cablesin Group

    Spacing between Cables in mm

    Touching 150 200 300 400 450 600 800

    20.76 0.81 0.83 0.85 0.87 0.88 0.90 0.92

    0.79 0.82 0.86 0.87 0.88 0.89 0.92 0.94

    30.64 0.72 0.72 0.77 0.79 0.81 0.83 0.86

    0.67 0.73 0.77 0.78 0.80 0.82 0.86 0.89

    40.58 0.65 0.67 0.72 0.75 0.76 0.80 0.84

    0.61 0.68 0.72 0.74 0.79 0.80 0.83 0.87

    50.53 0.61 0.63 0.68 0.71 0.73 0.77 0.81

    0.56 0.63 0.68 0.70 0.76 0.77 0.81 0.85

    60.50 0.56 0.60 0.66 0.69 0.72 0.76 0.80

    0.53 0.60 0.65 0.68 0.74 0.76 0.80 0.84

    SINGLE CORE:

    A. Group Rating facto rs for Circuit of three Single core cables in Trefoils laiddirect in Ground in Horizontal formation.

    MULTI CORE:

    B. Group Rating factors for cables laid in Horizontal formation.

    Go to product category Next

    Search

    | About Us | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|Contact Us

    nt Cables Ltd http://www.torrentcables.com/HT_common_design_de

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    11/12

    Continuous Current rating Three Core Dimensional Details Single Core Dimensional Details

    33 kv Cable|Home|Enquiry|Sitemap|Contact Us

    Go to product category Next

    Continuous Current Rating for Single/ Three Core Cableswith Aluminium / Copper Conductor

    Aluminium

    Copper

    NominalCross

    SectionalArea of

    Conductor

    Continuous Current Rating forThree Core Cable

    Continuous Current Rating forSingle Core Cable

    (Single End bonding)

    When Laid inGround

    When Laid inAir

    When Laid inGround

    When Laid inAir

    Sq.mm. amps amps amps amps

    35110 130 115 140

    145 165 150 185

    50130 155 135 170

    170 200 175 225

    70160 190 165 215

    205 245 215 275

    95190 230 195 255

    245 300 250 340

    12 0215 265 225 295

    275 340 290 390

    15 0 240 300 250 330305 385 325 440

    18 5270 340 280 380

    345 435 365 500

    24 0310 400 325 450

    395 510 420 590

    30 0350 455 370 520

    440 580 470 680

    40 0395 530 420 610

    495 660 530 780

    50 0445 610 480 710

    550 750 590 900

    63 0-- -- 550 820

    -- -- 660 1020

    80 0-- -- 610 950

    -- -- 730 1140

    1000-- -- 680 1080

    -- -- 790 1240

    Ambient Air Temperature: 400 C

    Ground temperature : 300 C

    Thermal Resistivity o f Soil : 1500 C cm/ w

    Maximum Continuous Conductor tempera ture : 900 CSingle Core Cable laid in TrefoilThree Core Cable laid SinglyMaximum Conductor Temperature

    after Short Circuit : 250

    0

    C

    Depth of Laying

    3.3 kv to 11 kv Above 11 kv

    900 mm 1050 mm

    Tips:5.Key Manufacturing P rocess in HT Cable

    Manufacturing.

    Wet (Steam/ Hot Water) Cure Process

    The chemistry of cross linking leads toC-Si-O-Si-C linkage.

    The cores are cooled in water, post extrusion.

    The cross linking takes place in a wetenvironment.

    Curing is done by batch process.

    Because of batch process, there is a limitation todrum length of cable.

    The plant and machinery are not very expensive.

    Losses are less in case of equipment/process malfunctioning.

    This does not require very large factory space.

    The process requires an associated curingarrangement in the form of steam y chamber orwater tank etc.

    Curing is restricted to insulation only, semiconducting layers are of y thermoplasticcompound based.

    Because of batch curing, extremely difficult tocrossing cores.beyond 33 kV. Chances ofnon-uniform cross linking cannot be ruled out.

    Maintenance expenses are comparatively lower.

    Search

    Go to product category Next

    | About us | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|Contact Us

    nt Cables Ltd http://www.torrentcables.com/33kv_ht_

    22/10/2011

  • 8/3/2019 Torrent Cables Ltd

    12/12

    PVC pow er cables with aluminium sector shaped conductors PVC power cables with aluminium conductors

    1.1kv Power Cables(Armoured)

    |Home|Enquiry|Sitemap|Contact Us

    Go to product category NextConstructional details aluminium

    Pvc pow er cables w ith aluminum sector shaped conductors (armourded cables)

    Sr.no.

    Nominal

    conductor

    area

    sq.mm.

    Minimum

    nos. of

    w ires in

    conductor

    Nominal

    thickness of

    insulation in

    mm

    Minimum

    thickness of

    innersheath

    in mm

    Nominal

    diameter/dimension of

    G.I.armouring in mm

    Minimum thicknass of

    outer sheath in mm

    Approximate overall

    diameter in mm

    Approximate weight

    cable in kg/ kms.

    Main

    core

    Half

    coreMainNeutralL MainNeutral

    Nos.of cores Number.of cores Number.of cores Number.of cores Number.of cores

    2 3 3.5 4 2 3 3.5 4 2 3 3.5 4 2 3 3.5 4 2 3 3.5

    1 25 16 6 7 1.2 1.0 0.30.3 0.3 0.34.0 x

    0.8

    4.0 x

    0.8

    4.0 x

    0.8

    4.0 x

    0.8 1.40 1.40 1.40 1.40 20.4 23.8 25.8 27.0 675 855 975 1

    (1.6) (1.6) (1.6) (1.6) (1.40)(1.40)(1.40)(1.40)(21.8)(25.3)(27.2)(28.0) (901) (1125)(1265) (1

    2 35 16 6 7 1.2 1.0 0.30.3 0.3 0.34.0 x

    0.8

    4.0 x

    0.8

    4.0 x

    0.8

    4.0 x

    0.81.40 1.40 1.40 1.40 22.0 25.6 27.9 29.1 785 1005 1130 1

    (1.6) (1.6) (1.6) (1.6) (1.40)(1.40)(1.40)(1.56)(23.2)(27.3)(29.2)(30.7)(1030)(1295)(1445) (1

    3 50 25 6 6 1.4 1.2 0.30.3 0.3 0.44.0 x

    0.8

    4.0 x

    0.8

    4.0 x

    0.8

    4.0 x

    0.81.40 1.56 1.56 1.56 24.5 29.3 31.8 33.5 970 1275 1450 1

    (1.6) (1.6) (1.6) (2.0) (1.56)(1.56)(1.56)(1.56)(26.0)(30.9)(33.2)(35.2)(1275)(1605)(1805) (2

    4 70 35 12 6 1.4 1.2 0.30.4 0.4 0.44.0 x

    0.8

    4.0 x

    0.8

    4.0 x

    0.8

    4.0 x

    0.81.56 1.56 1.56 1.56 27.0 32.3 35.0 36.5 1195 1570 1780 1

    (1.6) (2.0) (2.0) (2.0) (1.56)(1.56)(1.56)(1.56)(28.3)(34.6)(37.4)(38.0)(1500)(2165)(2430) (2

    -Wrapped thermoplastic tape inner sheath

    -Standard drum length for all sizes : 500 mtrs. 5 %

    -Values written in bracket are for g.i. wire armoured cables

    Previous Go to product category Next

    Search

    | About Us | Market Segment | Product Range |For Investors| |Home|Enquiry|Sitemap|Contact Us

    nt Cables Ltd http://www.torrentcables.com/PVC_power_cables_armou