51
Toronto Catholic District School Board Asbestos Survey Type of Document Final Project Name Father Henry Carr Catholic Secondary School 1760 Martin Grove Road Etobicoke, Ontario Project Number BRM00205804A0 Prepared By: exp 1595 Clark Boulevard Brampton, ON L6T 4V1 Canada Date Submitted 19.07.11

Toronto Catholic District School Board · PDF fileFinal Project Name ... Project Number: BRM 00205804 A0 Prepared ... Exp was retained by the Toronto Catholic District School Board

  • Upload
    vucong

  • View
    218

  • Download
    4

Embed Size (px)

Citation preview

Toronto Catholic District

School Board

Asbestos Survey

Type of Document Final

Project Name Father Henry Carr Catholic Secondary School 1760 Martin Grove Road Etobicoke, Ontario

Project Number BRM 00205804 A0

Prepared By:

exp 1595 Clark Boulevard Brampton, ON L6T 4V1 Canada

Date Submitted 19.07.11

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

i

Toronto Catholic District School Board

Asbestos Survey

Type of Document: Final

Project Name: Father Henry Carr Catholic Secondary School 1760 Martin Grove Road Etobicoke, Ontario

Project Number: BRM 00205804 A0

Prepared By: exp 1595 Clark Boulevard Brampton, ON L6T 4V1 Canada T: +1.905.793.9800 F: +1.905.793.0641 www.exp.com

___________________________________ Calvin Cathcart, B.A.Sc. Environmental Scientist Environmental Division

___________________________________ Manjinder Athwal, A.Sc.T. Team Leader, Hazardous Materials Services Environmental Division

Date Submitted: 19/07/12

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

ii

Table of Contents Page

Chapter 1 –Introduction 1

1. Introduction 2

1.1 Regulatory Requirements.........................................................................................2

1.2 Purpose .....................................................................................................................2

1.3 Scope of Work .........................................................................................................3

1.4 Background Information on Asbestos .....................................................................3

Chapter 2 – Approach to Work 4

2 Approach to Work 5

2.1 Survey Methodology ................................................................................................5

2.2 Sample Analysis.......................................................................................................6

Chapter 3 – Results and Findings 7

3 Results and Findings 8

3.1 Property Description ................................................................................................8

3.2 Asbestos Survey .......................................................................................................8

3.2.1 Friable Asbestos .........................................................................................11

3.2.2 Non , Friable Asbestos...............................................................................11

3.2.3 Hazard Assessment of ACMs ....................................................................11

Chapter 4 – Conclusions and Recommendations 12

4 Conclusions & Recommendations 13

4.1 Asbestos .................................................................................................................13

4.1.1 Friable Asbestos .........................................................................................13

4.1.2 Non , Friable Asbestos...............................................................................13

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

iii

Chapter 5 – General Limitations 14

5 General Limitations 14

Appendix A – Laboratory Analytical Results 14

Appendix B – Asbestos Location and Quantity Tables (Asbestos Only) 14

Appendix C – Photographs 14

Appendix D – Figures 1

Appendix E – Hazard Ranking Decision Tree 14

List of Distribution 14

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

1

Chapter 1 – Introduction

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

2

1. Introduction

Exp was retained by the Toronto Catholic District School Board to carry out an Asbestos Survey of Father

Henry Carr Catholic Secondary School located at 1760 Martin Grove Road in Etobicoke, Ontario.

It is our understanding that the purpose of the survey was to bring the building into compliance with

current regulations.

Regulatory Requirements 1.1

The Occupational Health and Safety Act, R.S.O. 1990, c.0.1, s.30 (1) requires:

“Before beginning a project, the owner shall determine whether any Designated Substances are present

at the project site and shall prepare a list of all Designated Substances that are present at the site”.

Designated Substances are defined as any biological, chemical, or physical agent or combination thereof

prescribed as a Designated Substance to which exposure of a worker is prohibited, regulated, restricted,

limited or controlled.

Section 30 of the Act requires that the list of Designated Substances be provided to prospective

contractors and subcontractors working on the site.

The Ministry of Labor Designated Substances are the following:

Acrylonitrile Isocyanates

Arsenic Lead

Asbestos Mercury

Benzene Silica

Coke Oven Emissions Vinyl Chloride

Ethylene Oxide

Ontario Regulation 278/05 (O. Reg. 278/05), the Regulation respecting Asbestos on Construction

Projects and in Buildings and Repair Operations, made under the Occupational Health and Safety Act

(OHSA), requires owners of a building to identify ACMs prior to potential disturbance of the materials. In

addition, an owner of a building is required to have an Asbestos Management Plan (AMP) if ACMs (friable

or non>friable) have been used in the building and are to remain in place. An inventory of ACMs must be

kept on site. All ACMs must be routinely inspected to ensure no damage has occurred, and the inventory

must be updated once in each 12>month period and as may be required based on expected changing site

conditions, abatement and/or renovation activities.

Purpose 1.2

The purpose of the survey was to:

1. Determine the presence or absence of ACMs;

2. Establish the type, location, condition and approximate quantities of ACMs; and,

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

3

3. Conduct a hazard assessment of any identified ACMs.

This asbestos survey report complies with the requirements of the Occupational Health & Safety Act, Regulation 278/05: Asbestos on Construction Projects and in Buildings and Repair Operations, with respect to identifying ACMs in the specified areas of the subject building

Scope of Work 1.3

The asbestos survey entailed:

• Visual review of accessible specific areas of the building to identify materials which could

contain asbestos;

• Representative bulk sampling and analysis of materials suspected of containing asbestos

This assessment did not involve any destructive sampling (i.e. sampling within wall cavities,

bulkheads or above plastered [false] ceilings);

• Assessment of the condition of the asbestos>containing materials (hazard assessment); and,

• Recommendations for appropriate corrective action where required.

Background Information on Asbestos 1.4

Asbestos is a generic name that has been given to a group of naturally occurring fibrous minerals. In the

past, asbestos was commonly used as a component in building materials such as insulation, fireproofing

and acoustic or decorative panels. Although there are many types of asbestos, the three main forms of

commercial importance in Ontario are chrysotile, amosite and crocidolite.

An Asbestos>Containing Material (ACM) is defined by O. Reg. 278/05 as a material that contains 0.5 % or

more asbestos by dry weight. ACMs are placed into two general classes, “friable” and “non>friable”

ACMs. Friable ACMs are those materials that when dry can be crumbled, pulverized and reduced to

powder by hand pressure. Typical friable ACMs include acoustical or decorative texture coats,

fireproofing, some ceiling tiles and thermal insulation. Non>friable ACMs are much more durable as they

are held together by a binder such as cement, vinyl or asphalt. Typical non>friable ACMs include floor

tiles, fire blankets, roofing materials and cementations products such as wallboards, pipes or siding.

It has been recognized that hazardous situations may exist in buildings where asbestos>containing

materials are found. This is especially true where asbestos fibres may become airborne as a result of

material aging, physical damage, water damage or air movement. In contrast, there is little reason for

concern if the asbestos is in good condition, has not been damaged and is not in a location where it is

likely to be disturbed.

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

4

Chapter 2 –

Approach to Work

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

5

Approach to Work 2The asbestos survey included a visual assessment as well as sampling and analysis of materials

suspected of containing asbestos. The site work was carried out by Mr. Calvin Cathcart from June 19 to

June 21, 2012. The following subsections present a description of the methodologies used for the

asbestos survey as well as sample analysis.

Survey Methodology 2.1

The asbestos survey included the identification of potential friable and non#friable asbestos#containing

materials within the building. All accessible friable and non#friable materials suspected of containing

asbestos were sampled. In addition, the condition, accessibility and friability of the suspected materials

were noted.

No destructive investigations were performed as part of this survey. The likelihood of ACMs being

present in inaccessible areas such as above plaster ceilings, behind drywall, within bulkheads or under

carpeting was determined by assessing the potential for asbestos#containing systems in adjacent areas.

Certain materials which may contain asbestos were not sampled to avoid damage and compromising the

integrity of building systems. For instance, caulking materials were not sampled to ensure that the

integrity of the window seals remains intact. To avoid possible damage to the roof, nullifying any roofing

warranty and compromising the building envelope, the survey did not include sampling of exterior roofing

materials. These materials noted are non#friable and should be considered to contain asbestos until

sampling confirms otherwise.

Building materials suspected of containing asbestos were identified and representative sampling and

laboratory testing of these materials was conducted. O.Reg. 278/05 outlines requirements for the

collection of multiple samples of each homogeneous material suspected of containing asbestos, as

presented in Table 1. O.Reg. 278/05 s. 3 (3).

Table 2�1: O. Reg. 278/05 s. 3(3) # Minimum Asbestos Bulk Material Sample Requirements

Item Type of material Size of area of homogeneous

material

Minimum

number of

bulk material

samples to

be collected

1.

Surfacing material, including without limitation,

material that is applied to surfaces by spraying, by

troweling or otherwise, such as acoustical plaster on

ceilings and fireproofing materials on structural

members

Less than 90 square meters 3

90 or more square meters, but less

than 450 square meters

5

450 or more square meters 7

2. Thermal insulation, except as described in item 3 any size 3

3. Thermal insulation patch Less than 2 linear meters or 0.5

square meters 1

4. Other material Any size 3

The number of bulk material samples collected from a homogeneous area were taken in accordance with

Table 1 O. Reg. 278/05 s. 3 (3).

Materials suspected of containing asbestos were collected using wetting techniques and hand sampling

tools. These materials (approximately one teaspoon full in quantity) were placed in sealable plastic bags

and labeled for QA/QC review by Trow’s Hazardous Materials Manager. 64 samples of 18 potentially

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

6

asbestos#containing materials were collected from the subject building and were sent to an accredited

laboratory for analysis. A summary of potential asbestos#containing samples collected and the locations

where these samples were taken are presented in Table 2, Section 3.2.

A hazard assessment of identified ACMs was also carried out as part of this survey. The rankings of

potential hazard range from 1#most hazardous to 4#least hazardous. A decision tree to assist in the

Hazard Ranking of the ACM is attached to this report in Appendix D.

A hazard assessment of identified ACMs was also carried out as part of this survey. The rankings of

potential hazard range from 1#most hazardous, to 4#least hazardous. The hazard rankings help

determine what asbestos#containing materials need immediate abatement and which can remain in place

and be monitored as part of the surveillance program under an Asbestos Management Plan. A decision

tree to assist in the Hazard Ranking of the ACM is attached to this report in Appendix E.

Sample Analysis 2.2

All bulk samples were analyzed for asbestos content by International Asbestos Testing Laboratories

(IATL), an independent laboratory that participates in the American Industrial Hygiene Association (AIHA)

Industrial Hygiene Program (identification #100188) and the National Voluntary Laboratory Accreditation

Program (NVLAP) for asbestos fiber analysis (NVLAP code #101165#0).A chain of custody form

containing relevant information accompanied all submissions.

Bulk samples were analyzed by Polarized Light Microscopy (PLM). The method and procedures used for

establishing whether material is asbestos#containing is in accordance with the U.S. Environmental

Protection Agency Method for the Determination of Asbestos in Bulk Building Materials (Test Method

EPA/600/R#93/116). In accordance with the O.Reg. 278/05, if a material was found to contain greater

than 0.5% asbestos, additional bulk material samples taken from the same homogeneous material were

not analyzed.

Survey Limitations 2.3

This report reflects only the observations, findings, and analysis of materials sampled at the time of the

survey. Analytical results reflect the sampled materials at the specific sampling locations. Visually similar

materials were referenced to specific analyzed samples.

It should be noted caulking and roofing materials were not sampled to ensure that the integrity of the

window seals and roof remains intact.

Fibreglass insulation was not submitted for analysis as it can be identified visually and was never

manufactured with asbestos.

The baby blue, pink, green, and grey 12”x12” vinyl floor tiles observed in Room 234 were not sampled for

aesthetic reasons.

There was limited access to the ceiling space in Room 121; based on the findings in adjacent areas it is

assumed that asbestos#containing cement parging is present on pipe fittings in the ceiling space.

In general, the survey was limited to accessible areas of the subject building. Some intrusive sampling

was conducted during the Site visit, however, it is possible asbestos#containing materials may be present

in inaccessible areas such as underneath carpet or multiple layers of flooring, behind walls, above

ceilings or within bulkheads. Exp’s survey of the building was based on clear, unobstructed visual

identification of suspect Designated Substances. Where possible the areas above suspended ceiling tiles

were assessed.

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

7

Chapter 3 – Results and Findings

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

8

Results and Findings 3

Property Description 3.1

The building located at the afore�mentioned property is a two storey secondary school.

The building’s original date of construction is unknown. The building was occupied at the time of the

survey.

The building was observed to be constructed with a concrete slab floor, steel framing. Interior walls were

either plaster or gypsum wallboard and ceilings were gypsum wallboard, or ceiling tiles. Floors were

covered with wood, carpet, ceramic or vinyl floor tiles.

The majority of domestic hot and cold water lines appeared to be either un�insulated or wrapped with

fibreglass insulation.

Asbestos Survey 3.2

A summary of the analytical results from the current representative sampling program is summarized in

Table 2 below.

Table 3�1: Asbestos Sampling Locations and Laboratory Results

Sample ID Location Material Asbestos Type and

Content Friability

BS-1.1 Room 131

White Plaster None Detected N/A

Grey Plaster None Detected N/A

BS-1.2 Room 146

White Plaster None Detected N/A

Grey Plaster None Detected N/A

BS-1.3 Room 219

White Plaster None Detected N/A

Grey Plaster None Detected N/A

BS-1.4 Room 202

White Plaster None Detected N/A

Grey Plaster None Detected N/A

BS-1.5 Room 235

White Plaster None Detected N/A

Grey Plaster None Detected N/A

BS-1.6 Room 225

White Plaster None Detected N/A

Grey Plaster None Detected N/A

BS-1.7 Room 224 Grey Plaster None Detected N/A

BS-2.1 Room 108 Drywall Joint Compound None Detected N/A

BS-2.2 Room 156 Drywall Joint Compound None Detected N/A

BS-2.3 Room 149 Drywall Joint Compound None Detected N/A

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

9

Sample ID Location Material Asbestos Type and

Content Friability

BS-2.4 Stairwell B Drywall Joint Compound None Detected N/A

BS-2.5 Room 131 Drywall Joint Compound None Detected N/A

BS-2.6 207 – Corridor Drywall Joint Compound None Detected N/A

BS-2.7 Room 233 Drywall Joint Compound None Detected N/A

BS-3.1 Room 131 Sprayed Fireproofing None Detected N/A

BS-3.2 Room 121 Sprayed Fireproofing None Detected N/A

BS-3.3 Room 152 Sprayed Fireproofing None Detected N/A

BS-3.4 Room 149 Sprayed Fireproofing None Detected N/A

BS-3.5 135 – Corridor Sprayed Fireproofing None Detected N/A

BS-3.6 207 – Corridor Sprayed Fireproofing None Detected N/A

BS-3.7 Room 217 Sprayed Fireproofing None Detected N/A

BS-4.1 Room 111 Suspended Ceiling Tile – 4’x2’ Small and

Large Pinholes None Detected N/A

BS-4.2 Room 111 Suspended Ceiling Tile – 4’x2’ Small and

Large Pinholes None Detected N/A

BS-4.3 Room 111 Suspended Ceiling Tile – 4’x2’ Small and

Large Pinholes None Detected N/A

BS-5.1 Room 111 Cement Parging on Pipe Fittings 95% Chrysotile Friable

BS-5.2 Room 111 Cement Parging on Pipe Fittings Sample Not Analyzed

due to Positive Stop Friable

BS-5.3 Room 111 Cement Parging on Pipe Fittings Sample Not Analyzed

due to Positive Stop Friable

BS-6.1 Room 156

Vinyl Floor Tile – 12”x12” Cream w/ Light

and Dark Tan None Detected N/A

Yellow Mastic None Detected N/A

BS-6.2 Room 156

Vinyl Floor Tile – 12”x12” Cream w/ Light

and Dark Tan None Detected N/A

Yellow Mastic None Detected N/A

BS-6.3 Room 156

Vinyl Floor Tile – 12”x12” Cream w/ Light

and Dark Tan None Detected N/A

Yellow Mastic None Detected N/A

BS-11.1 Stairwell C

Vinyl Floor Tile – 12”x12” Dark and Light

Pink None Detected N/A

Black Mastic None Detected N/A

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

10

Sample ID Location Material Asbestos Type and

Content Friability

BS-11.2 Stairwell C

Vinyl Floor Tile – 12”x12” Dark and Light

Pink None Detected N/A

Black Mastic None Detected N/A

BS-11.3 Stairwell C

Vinyl Floor Tile – 12”x12” Dark and Light

Pink None Detected N/A

Black Mastic None Detected N/A

BS-12.1 207 - Corridor

Vinyl Floor Tile – 12”x12” Royal Blue None Detected N/A

Black Mastic None Detected N/A

BS-12.2 207 – Corridor

Vinyl Floor Tile – 12”x12” Royal Blue None Detected N/A

Black Mastic None Detected N/A

BS-12.3 207 - Corridor

Vinyl Floor Tile – 12”x12” Royal Blue None Detected N/A

Black Mastic None Detected N/A

BS-13.1 Room 156 Vinyl Floor Tile – 12”x12” Light Grey, Dark

Grey and White Speck None Detected N/A

BS-13.2 Room 156 Vinyl Floor Tile – 12”x12” Light Grey, Dark

Grey and White Speck None Detected N/A

BS-13.3 Room 156 Vinyl Floor Tile – 12”x12” Light Grey, Dark

Grey and White Speck None Detected N/A

BS-14.1 Room 123

Vinyl Floor Tile – 12”x12” Tan w/ Black Dots None Detected N/A

Black Mastic None Detected N/A

BS-14.2 Room 123

Vinyl Floor Tile – 12”x12” Tan w/ Black Dots None Detected N/A

Black Mastic None Detected N/A

BS-14.3 Room 123

Vinyl Floor Tile – 12”x12” Tan w/ Black Dots None Detected N/A

Black Mastic None Detected N/A

BS-15.1 Room 123

Vinyl Floor Tile – 12”x12” White w/ Black

Dots None Detected N/A

Tan Mastic None Detected N/A

BS-15.2 Room 123

Vinyl Floor Tile – 12”x12” White w/ Black

Dots None Detected N/A

Tan Mastic None Detected N/A

BS-15.3 Room 123

Vinyl Floor Tile – 12”x12” White w/ Black

Dots None Detected N/A

Tan Mastic None Detected N/A

BS-16.1 Room 123 Vinyl Floor Tile – 12”x12” Grey w/ Black

Dots None Detected N/A

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

11

Sample ID Location Material Asbestos Type and

Content Friability

Black Mastic None Detected N/A

BS-16.2 Room 123

Vinyl Floor Tile – 12”x12” Grey w/ Black

Dots None Detected N/A

Black Mastic None Detected N/A

BS-16.3 Room 123

Vinyl Floor Tile – 12”x12” Grey w/ Black

Dots None Detected N/A

Black Mastic None Detected N/A

BS-17.1 Room 111

Vinyl Floor Tile – 12”x12” Light Grey None Detected N/A

Black Mastic None Detected N/A

BS-17.2 Room 111

Vinyl Floor Tile – 12”x12” Light Grey None Detected N/A

Black Mastic None Detected N/A

BS-17.3 Room 111

Vinyl Floor Tile – 12”x12” Light Grey None Detected N/A

Black Mastic None Detected N/A

BS-18.1 Room 111

Vinyl Floor Tile – 12”x12” Dark Grey None Detected N/A

Black Mastic None Detected N/A

BS-18.2 Room 111 Vinyl Floor Tile – 12”x12” Dark Grey None Detected N/A

BS-18.3 Room 111 Vinyl Floor Tile – 12”x12” Dark Grey None Detected N/A

N/A = Not Applicable

Friable Asbestos 3.2.1

Friable asbestos�containing cement parging was identified on pipe fittings in several locations throughout

the subject building. The cement parging was found to contain 95% Chrysotile asbestos.

Refer to Appendix B for locations and quantities of friable asbestos�containing materials.

Non - Friable Asbestos 3.2.2

Suspect non�friable asbestos�containing cement (transite) pipe was observed in several locations

throughout the subject building. This material was not sampled to ensure that the integrity of the pipe

remains intact.

Refer to Appendix B for locations and quantities of non�friable asbestos�containing materials.

Hazard Assessment of ACMs 3.2.3

The friable cement parging on pipe fittings present in the building was observed to be in good condition.

This material was assigned a Hazard Rank of 4 (Low).

The suspect non�friable cement (transite) pipe was observed to be in good condition with a low potential

for disturbance. This material was assigned a Hazard Rank of 4 (Low Risk).

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

12

Chapter 4 –

Conclusions and Recommendations

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

13

Conclusions & Recommendations 4On the basis of our walk�through examination of the building, representative sampling and laboratory

analysis of suspected asbestos and lead containing materials, the following conclusions and

recommendations are presented.

Asbestos 4.1

Friable Asbestos 4.1.1

Friable asbestos�containing cement parging was identified on pipe fittings in several locations throughout

the subject building. The cement parging was found to contain 95% Chrysotile asbestos. The cement

parging present in the building was observed to be in good condition. This material was assigned a

Hazard Rank of 4 (Low Risk).

Refer to Appendix B for locations and quantities of friable asbestos�containing materials.

Non - Friable Asbestos 4.1.2

Non�friable asbestos�containing cement (transite) pipe was observed in several locations throughout the subject building. The non�friable cement (transite) pipe was observed to be in good condition with a low potential for disturbance. This material was assigned a Hazard Rank of 4 (Low Risk).

Refer to Appendix B for locations and quantities of non�friable asbestos�containing materials.

− Prior to renovation activities which may disturb asbestos#containing materials, these materials

must be removed following the appropriate asbestos abatement work procedures (Type

1/2/3) as detailed in O. Reg. 278/05 and disposed of as asbestos waste under O. Reg. 347;

− Prior to renovation activities which may disturb suspect asbestos#containing vinyl floor tiles in

Room 234, these materials shall be sampled to confirm the asbestos content. If confirmed as

ACM, this material shall be removed following appropriate asbestos abatement work

procedures (Type 1/2/3 – depending on the method of removal) as detailed in O. Reg. 278/05

and disposed of as asbestos waste under O. Reg. 347;

− Any suspect asbestos#containing material uncovered during the course of

renovation/demolition activities that is not mentioned in this report shall be considered

asbestos#containing until sampling and analysis indicates otherwise.

− Prior to the demolition of the building, roofing and window caulking material samples must be

collected in accordance with Ontario Regulation 278/05 to determine the presence or

absence of asbestos;

− Prior to the demolition of the building, all asbestos#containing materials must be removed

following appropriate asbestos abatement work procedures (Type 1/2/3) as detailed in O.

Reg. 278/05 and disposed of as asbestos waste under O. Reg. 347;

− Sub#trades working with or in close proximity to asbestos#containing material must be

informed of its presence; and,

Ontario Regulation 278/05, made under the Occupational Health and Safety Act, specifies

that an Asbestos Management Plan (AMP) must be implemented if any asbestos#containing

materials (friable or non#friable) are known to be present in the building and are to remain in

place. An inventory of asbestos#containing materials must be kept on site. All materials must

be routinely inspected to ensure no damage has occurred and the inventory must be updated

once in each 12#month period and as may be required based on expected changing site

conditions, abatement and/or renovation activities.

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

14

Chapter 5 –

General Limitations

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

15

General Limitations 5The services performed and outlined herein were based in part, upon visual observations of the building.

Our opinion cannot be extended to portions of the building that were unavailable for direct observation by

objects or coverings at the time of our site visit.

Any of our observations relating to hazardous and toxic materials and asbestos in the environment at the

building are described in this report. Where testing was performed, it was executed in accordance with

our contract for these services. It should be noted that other compounds or materials not tested for may

be present in the environment.

The objective of this report was to audit the environmental conditions at the building within the context of

our contract with respect to existing Regulations and Guidelines within the applicable jurisdiction.

Compliance of past and current owners with applicable local, provincial and federal government laws and

regulations was not included in our contract for services.

The conclusions of this report are based, in part, on the information provided by others and any testing

and analyses described in the report. The possibility remains that unexpected environmental conditions

may be encountered at the building in locations not explored. Should such an event occur, exp should be

notified in order that we may determine if modifications to our conclusions are necessary.

This report has been prepared in accordance with generally accepted environmental study and/or

engineering practices. No other warranties, either expressed or implied, are made as to the professional

services provided under the terms of our contract and included in this report.

This report has been prepared for the exclusive use of the Toronto Catholic District School Board in

accordance with accepted environmental study and/or engineering practices for an Asbestos Survey. No

other warranties, either expressed or implied, are made as to the professional services provided under

the terms of the Survey and included in this report. Any use which a third party makes of this report, or

any part hereof, or any reliance on or decisions to be made based on it, are the responsibility of such third

parties. Exp accepts no responsibility for damages, if any, suffered by any third party as a result of

decisions made or actions based on this report.

We trust the above report meets with your approval. Should you have any questions, please do not

hesitate to contact us.

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

16

Appendix A – Laboratory Analytical Results

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.1

4704749 Description / Location:

Room 131

None Detected None Detected None Detected None Detected 100

White Plaster

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.1

4704749 Description / Location:

Room 131

None Detected None Detected None Detected None Detected 100

Grey PlasterLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.2

4704750 Description / Location:

Room 146

None Detected None Detected None Detected None Detected 100

White Plaster

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.2

4704750 Description / Location:

Room 146

None Detected None Detected None Detected None Detected 100

Grey PlasterLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date:

Approved By:

Frank E. Ehrenfeld, III

Laboratory Director

7/2/2012

Page 1 of 21

R. Caran

_____________________________

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.3

4704751 Description / Location:

Room 219

None Detected None Detected None Detected None Detected 100

White Plaster

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.3

4704751 Description / Location:

Room 219

None Detected None Detected None Detected None Detected 100

Grey PlasterLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.4

4704752 Description / Location:

Room 202

None Detected None Detected None Detected None Detected 100

White Plaster

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.4

4704752 Description / Location:

Room 202

None Detected None Detected None Detected None Detected 100

Grey PlasterLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 2 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.5

4704753 Description / Location:

Room 235

None Detected None Detected None Detected None Detected 100

White Plaster

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.5

4704753 Description / Location:

Room 235

None Detected None Detected None Detected None Detected 100

Grey PlasterLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.6

4704754 Description / Location:

Room 225

None Detected None Detected None Detected None Detected 100

White Plaster

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.6

4704754 Description / Location:

Room 225

None Detected None Detected None Detected None Detected 100

Grey PlasterLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 3 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-1.7

4704755 Description / Location:

Room 224

None Detected None Detected None Detected None Detected 100

Grey Plaster

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-2.1

4704756 Description / Location:

Room 108

None Detected None Detected None Detected None Detected 100

White Joint Compound

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-2.2

4704757 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

White Joint Compound

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-2.3

4704758 Description / Location:

Room 149

None Detected None Detected None Detected None Detected 100

White Joint Compound

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 4 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-2.4

4704759 Description / Location:

Stairwell B

None Detected None Detected None Detected None Detected 100

White Joint Compound

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-2.5

4704760 Description / Location:

Room 131

None Detected None Detected None Detected None Detected 100

White Joint Compound

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-2.6

4704761 Description / Location:

207-Corridor

None Detected None Detected None Detected None Detected 100

White Joint Compound

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-2.7

4704762 Description / Location:

Room 233

None Detected None Detected None Detected None Detected 100

White Joint Compound

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 5 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-3.1

4704763 Description / Location:

Room 131; Sprayed Fireproofing

None Detected None Detected 75 Fibrous Glass 25

White Insulation

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-3.2

4704764 Description / Location:

Room 121; Sprayed Fireproofing

None Detected None Detected 75 Fibrous Glass 25

White Insulation

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-3.3

4704765 Description / Location:

Room 152; Sprayed Fireproofing

None Detected None Detected 75 Fibrous Glass 25

White Insulation

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-3.4

4704766 Description / Location:

Room 149; Sprayed Fireproofing

None Detected None Detected 75 Fibrous Glass 25

Grey Insulation

Results from sample number 4704804 as per client request.

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 6 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-3.5

4704767 Description / Location:

135-Corridor; Sprayed Fireproofing

None Detected None Detected 75 Fibrous Glass 25

White Insulation

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-3.6

4704768 Description / Location:

207-Corridor; Sprayed Fireproofing

None Detected None Detected 75 Fibrous Glass 25

White Insulation

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-3.7

4704769 Description / Location:

Room 217; Sprayed Fireproofing

None Detected None Detected 75 Fibrous Glass 25

White Insulation

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-4.1

4704770 Description / Location:

Room 111

None Detected None Detected 60

20

Cellulose

Fibrous Glass

20

White Ceiling Tile; 4x2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 7 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-4.2

4704771 Description / Location:

Room 111

None Detected None Detected 60

20

Cellulose

Fibrous Glass

20

White Ceiling Tile; 4x2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-4.3

4704772 Description / Location:

Room 111

None Detected None Detected 60

20

Cellulose

Fibrous Glass

20

White Ceiling Tile; 4x2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-5.1

4704773 Description / Location:

Room 111; Parging On Fittings

95 Chrysotile None Detected None Detected 5

White Insulation

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-5.2

4704774 Description / Location:

Sample Not Analyzed Sample Not Analyzed

Sample Not Analyzed

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 8 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-5.3

4704775 Description / Location:

Sample Not Analyzed Sample Not Analyzed

Sample Not Analyzed

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-6.1

4704776 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-6.1

4704776 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

Yellow MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 9 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-6.2

4704777 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-6.2

4704777 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

Yellow MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-6.3

4704778 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-6.3

4704778 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

Yellow MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 10 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-11.1

4704779 Description / Location:

Stairwell C

None Detected None Detected None Detected None Detected 100

Lt.Pink Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-11.1

4704779 Description / Location:

Stairwell C

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-11.2

4704780 Description / Location:

Stairwell C

None Detected None Detected None Detected None Detected 100

Lt.Pink Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-11.2

4704780 Description / Location:

Stairwell C

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 11 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-11.3

4704781 Description / Location:

Stairwell C

None Detected None Detected None Detected None Detected 100

Lt.Pink Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-11.3

4704781 Description / Location:

Stairwell C

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-12.1

4704782 Description / Location:

207-Corridor

None Detected None Detected None Detected None Detected 100

Blue Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-12.1

4704782 Description / Location:

207-Corridor

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 12 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-12.2

4704783 Description / Location:

207-Corridor

None Detected None Detected None Detected None Detected 100

Blue Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-12.2

4704783 Description / Location:

207-Corridor

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-12.3

4704784 Description / Location:

207-Corridor

None Detected None Detected None Detected None Detected 100

Blue Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-12.3

4704784 Description / Location:

207-Corridor

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 13 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-13.1

4704785 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-13.2

4704786 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-13.3

4704787 Description / Location:

Room 156

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 14 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-14.1

4704788 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-14.1

4704788 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-14.2

4704789 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-14.2

4704789 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 15 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-14.3

4704790 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-14.3

4704790 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-15.1

4704791 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-15.1

4704791 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Tan MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 16 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-15.2

4704792 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-15.2

4704792 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Tan MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-15.3

4704793 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

White Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-15.3

4704793 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Tan MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 17 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-16.1

4704794 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-16.1

4704794 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-16.2

4704795 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-16.2

4704795 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 18 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-16.3

4704796 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-16.3

4704796 Description / Location:

Room 123

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-17.1

4704797 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-17.1

4704797 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 19 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-17.2

4704798 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-17.2

4704798 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-17.3

4704799 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-17.3

4704799 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 20 of 21

R. Caran

9000 Commerce Parkway Suite B Mt. Laurel, NJ 08054

Telephone: 856-231-9449 Fax: 856-231-9818

International Asbestos

Testing Laboratories

IATL

CERTIFICATE OF ANALYSIS

Client: Report Date:

Project No.:

Project:

BULK SAMPLE ANALYSIS SUMMARY

exp Services, Inc.

1595 Clark Blvd.

Brampton ON L6T 4VI

999-00205804-PA

7/2/2012

Report No.: 277798

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-18.1

4704800 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-18.1

4704800 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Black MasticLayer No.: 2

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-18.2

4704801 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material

Client No.:

Lab No.:

BS-18.3

4704802 Description / Location:

Room 111

None Detected None Detected None Detected None Detected 100

Grey Floor Tile; 12x12

NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government

This report shall not be reproduced except in full, without written approval of the laboratory.

Accreditations:

EPA 600/R-93/116, by Polarized Light Microscopy Analytical Method:

Comments:Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not

quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not

present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations

of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron

microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analysis Performed By:

Date: 7/2/2012

Page 21 of 21

R. Caran

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

17

Appendix B – Asbestos Location and Quantity Tables (Asbestos Only)

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

18

Location Type of

Material Sample #

Asbestos

Content

Approx.

Quantity

Hazard

Ranking

Type of

Removal as

per O. Reg.

278/05

Room 111 Cement Parging

on Fittings BS-5.1 95% Chrysotile 2 Fittings 4

Type 2/Glove

Bag

Room 121 Cement Parging

on Fittings VS-5.1 95% Chrysotile ** 4

Type 2/Glove

Bag or Type 3

Room 122 Cement Parging

on Fittings VS-5.1 95% Chrysotile 20 Fittings 4

Type 2/Glove

Bag or Type 3

Room 123 Cement Parging

on Fittings VS-5.1 95% Chrysotile 12 Fittings 4

Type 2/Glove

Bag or Type 3

Room 124

Cement

(Transite) Pipe N/A Assumed 20 ft. 4 Type 1

Cement Parging

on Fittings VS-5.1 95% Chrysotile 20 Fittings 4

Type 2/Glove

Bag or Type 3

Room 157 -

Gym

Suspect Cement

(Transite) Pipe

(inaccessible)

N/A Assumed 300 ft. 4 Type 1

Room 165 Cement Parging

on Fittings VS-5.1 95% Chrysotile 22 Fittings 4

Type 2/Glove

Bag or Type 3

Room 234

Vinyl Floor Tile

12”x12” Baby

Blue

N/A Assumed 400 ft2 4 Type 1

Vinyl Floor Tile

12”x12” Pink N/A Assumed 150 ft

2 4 Type 1

Vinyl Floor Tile

12”x12” Green N/A Assumed 150 ft

2 4 Type 1

Vinyl Floor Tile

12”x12” Grey N/A Assumed 150 ft

2 4 Type 1

Room 237 –

Mechanical

Room

Cement

(Transite) Pipe N/A Assumed 60 ft. 4 Type 1

N/A - Not Applicable

** There was limited access to the ceiling space in Room 121; based on the findings in adjacent areas it is assumed that

asbestos-containing cement parging is present on pipe fittings in the ceiling space.

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

19

Appendix C – Photographs

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

20

Photograph No. 1. Asbestos-containing cement (transite) pipe observed throughout the subject

building.

Photograph No. 2. Asbestos-containing cement parging identified on pipe fittings throughout

the subject building.

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

21

Appendix D – Figures

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

22

Appendix E – Hazard Ranking Decision Tree

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

23

CLASSIFICATION FOR ASBESTOS HAZARD POTENTIAL

(DECISION TREE DISPLAY)

ACM CONDITION

DAMAGED INTACT

POTENTIAL FOR DISTURBANCE

HIGH RISK

(REMOVE/REPAIR)

SIGNIFICANT POTENTIAL FOR LOW POTENTIAL POTENTIAL FOR DISTURBANCE FOR DISTURBANCE DISTURBANCE

MODERATE RISK LOW RISK

(MAY REMAIN IN PLACE IF NO RENOVATIONS/DEMOLITION)

HAZARD

RANK # 1

HAZARD

RANK # 2 HAZARD

RANK # 3 HAZARD

RANK # 4

Toronto Catholic District School Board Father Henry Carr Catholic Secondary School, 1760 Martin Grove Road, Etobicoke, Ontario

BRM#00205804#A0 19.07.12

24

List of Distribution Report Distributed To: Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Attention: Ms. Alexandra Collacott, MHSc Safety Officer, Occupational Health and Safety Department [email protected]