1) PFEER Standard Tones2) NORSOK Standard Tones3) IMO Standard Tones4) DNV Standard Tones
The mandatory tones that make up these alarm sets are as follows:1) PFEER
PAPA (Prepare to Abandon Platform Alarm) Alarm ToneWarble tone; frequency 1200Hz ramping down to 500Hz within 1 second.
GA (General Alarm) Alarm ToneIntermittent tone 1 second on, 1 second off at 1 KHz.
Toxic Gas Alarm Tone
2) NORSOK
Muster/Prepare to Abandon Platform Alarm ToneWarble tone: frequency 1200Hz ramping down to 500Hz within 1 second.
GA (General Alarm) Alarm ToneIntermittent tone 1 second on, 1 second off at 1 kHz.
Toxic Gas Alarm ToneIntermittent tone 1kHz, 0.1 second on, 0.1 second off, in bursts of duration 1 second alternating with 1 second silence.
3) IMOMuster Alarm Tone
Fire Alarm Tone
7x short blasts of 1kHz followed by 1 x continuous 1kHz for 7 seconds then the cycle repeats.
Toxic Gas Alarm ToneInterrupted 1KHZ tone
4) DNVGA (General Alarm) Alarm Tone7x short blasts of 1kHz followed by 1 x continuous 1kHz for 7 seconds then the cycle repeats.
Muster and Toxic gas alarm tones are equipped as above
Muster Alarm Tone
Toxic Gas Alarm Tone
Interrupted 1KHZ tone