To, THE DIRECTOR OF BOILERS, WEST BENGAL New Secretariat Building (8th floor) 1, K.S. Roy Road, KOLKATA - 700001 Sir, Name of the Owner: Shaktigarh Textile and Industries Ltd. Locality: Railway Station Shaktigarh, Burdwan ( North ), Purba Bardhaman, P.O : Barshul, Pin : 713124 Boiler Registration No: WBL4555, Boiler Type: Lancashire, Date of Inspection: 15-12-2018 Sub: i) Steam Test With reference to above and subsequent visit by the undersigned this is to report that the steam test was carried out keeping the main steam stop valve in closed condition and the observations were as below: Item Seat Dia. (mm) Boiler W.P. (KG/CM2) SET PR. (KG/CM2) RESET PR. (KG/CM2) BLOW DOWN (%) REMARKS SV-1 2.5 inch 5.0 5.0 4.8 4.0 Satisfactory SV-2 2 inch 4.9 4.7 4.08 Satisfactory During the steam test all the mountings and fittings had performed satisfactorily. Your’s faithfully Sri Dasarathi Saren, Assistant Director of Boilers, W.B. No. WB/R/2018/1427.date 18-12-2018 Copy forwarded for information and necessary action to:- i) Shaktigarh Textile and Industries Ltd., Village : Railway Station Shaktigarh, Subdivision : Burdwan ( North ), P.O. : Barshul District : Purba Bardhaman, PIN : 713124 ii) Sri Dasarathi Saren, Assistant Director of Boilers, W.B. Joint Director of Boilers, W.B. Powered by TCPDF (www.tcpdf.org)

To, THE DIRECTOR OF BOILERS, WEST BENGAL New Secretariat

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: To, THE DIRECTOR OF BOILERS, WEST BENGAL New Secretariat

To,THE DIRECTOR OF BOILERS, WEST BENGAL

New Secretariat Building (8th floor)1, K.S. Roy Road, KOLKATA - 700001

Sir,Name of the Owner: Shaktigarh Textile and Industries Ltd.

Locality: Railway Station Shaktigarh, Burdwan ( North ), Purba Bardhaman, P.O : Barshul, Pin : 713124

Boiler Registration No: WBL4555, Boiler Type: Lancashire, Date of Inspection: 15-12-2018

Sub: i) Steam Test

With reference to above and subsequent visit by the undersigned this is to report that the steam test was carried outkeeping the main steam stop valve in closed condition and the observations were as below:

Item Seat Dia.

(mm)

Boiler W.P.

(KG/CM2)

SET PR.

(KG/CM2)

RESET PR.

(KG/CM2)

BLOW DOWN

(%)

REMARKS

SV-1 2.5 inch 5.0 5.0 4.8 4.0 SatisfactorySV-2 2 inch 4.9 4.7 4.08 SatisfactoryDuring the steam test all the mountings and fittings had performed satisfactorily.

Your’s faithfully

Sri Dasarathi Saren, Assistant Director of Boilers, W.B.

No. WB/R/2018/1427.date 18-12-2018Copy forwarded for information and necessary action to:-i) Shaktigarh Textile and Industries Ltd., Village : Railway Station Shaktigarh, Subdivision : Burdwan ( North ),P.O. : Barshul District : Purba Bardhaman, PIN : 713124ii) Sri Dasarathi Saren, Assistant Director of Boilers, W.B.

Joint Director of Boilers, W.B.