CH2M HILL 610 Anacapa Street Santa Barbara, CA 93101 Tel 605-566-0650 Fax 714-424-2016 CH2M January 16, 2009 Mr. Ron Yasny, Compliance Project Manager California Energy Commission 1516 Ninth Street, MS-2000 Sacramento, CA 95814-5512 Mr. Mathew Trask, Amendment Project Manager Energy Facility Siting Division California Energy Commission 1516 Ninth Street Sacramento, CA 95814-5512 DOCKET \- JAN 16 mos DATE. --- , 16 RECO:-:: --- Subject: Data Responses Set 1 (Responses to Data Requests 1 through 11 GWF Henrietta Combined Cycle Power Plant Project (Ol-AFC-18C) On behalf of the GWF Energy LLC., attached please find six hard copies and three CD copies of the GWF Hernietta Data Responses, Set I, in response to CEC Staff's Data Requests dated December 8, 2008. As part of this submittal, we are also providing two hard copies and five CD copies of the GWF enrietta System Impact Study (Attachments DR8-I), per CEC Data Request umber 8. Please contact me should you have any questions. Sincerely, CH2MHILL . Jennifer L. Scholl Senior Project Manager/Regulatory Specialist

To determine the system impacts caused by the Project

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: To determine the system impacts caused by the Project

CH2M HILL

610 Anacapa Street

Santa Barbara, CA 93101

Tel 605-566-0650

Fax 714-424-2016 CH2M

January 16, 2009

Mr. Ron Yasny, Compliance Project Manager California Energy Commission 1516 Ninth Street, MS-2000 Sacramento, CA 95814-5512

Mr. Mathew Trask, Amendment Project Manager Energy Facility Siting Division California Energy Commission 1516 Ninth Street Sacramento, CA 95814-5512

DOCKET \- C-\~C

JAN 1 6 mos DATE. --­

, 16 RECO:-:: --­

Subject: Data Responses Set 1 (Responses to Data Requests 1 through 11 GWF Henrietta Combined Cycle Power Plant Project (Ol-AFC-18C)

On behalf of the GWF Energy LLC., attached please find six hard copies and three CD copies of the GWF Hernietta Data Responses, Set I, in response to CEC Staff's Data Requests dated December 8, 2008. As part of this submittal, we are also providing two hard copies and five CD copies of the GWF enrietta System Impact Study (Attachments DR8-I), per CEC Data Request umber 8.

Please contact me should you have any questions.

Sincerely,

CH2MHILL

. /~;d ~.

Jennifer L. Scholl Senior Project Manager/Regulatory Specialist

Page 2: To determine the system impacts caused by the Project

Petition for License Amendment

System Impact StudySubmitted in Support of

GWF Henrietta Peaker Plant (01-AFC-18)

GWF Henrietta Combined-Cycle GWF Henrietta Combined-Cycle Power PlantPower Plant

EY072008002SAC

January 2009

With Technical Assistance by

Submitted by

Page 3: To determine the system impacts caused by the Project

System Impact Study Generation Interconnection 

GWF Energy LLC 

GWF Henrietta Combined Cycle Power Plant 

December 10, 2008 

 

Page 4: To determine the system impacts caused by the Project

Table of Contents  1. Executive Summary ........................................................................................................ 1

2. Project and Interconnection Information ..................................................................... 2

3. Study Assumptions ......................................................................................................... 3

4. Powerflow Study Base Cases......................................................................................... 4

5. Study Criteria Summary................................................................................................. 6

6. Steady State Power Flow Study and Results ............................................................... 7

7. Reactive Power Deficiency Analysis............................................................................. 9

8. Transient Stability Results............................................................................................ 11

9. Short Circuit Study Results .......................................................................................... 12

10. Mitigation ....................................................................................................................... 13

11. Cost  Estimates............................................................................................................... 13

12. Environmental Evaluation / Permitting ..................................................................... 14

13. Study Updates................................................................................................................ 15

 i

Page 5: To determine the system impacts caused by the Project

 ii

Appendices   

A. Contingency Lists for Outages  B. Governor Power flow Outages C. Steady State Power Flow Results D. Steady State Power Flow Plots E. Transient Stability Plots F. Generator Machine Dynamic Data 

Page 6: To determine the system impacts caused by the Project

1. Executive Summary 

GWF Energy, LLC (GWF), proposes to interconnect a 25 MW Steam Turbine (Project) to the existing GWF Henrietta  facility consisting of  two 50 MW Combustion Turbines  (CT).   The interconnection point will be at the 70‐kV bus at Pacific Gas & Electric Company’s (PG&E) Henrietta  Substation,  in Kings County, California.      The  planned  operation  date  for  the proposed Project is May 1, 2012. 

In  order  for  the  Project  to  proceed  through  the  California  Energy  Commission’s  (CEC) License Amendment process a system impact study for the Project must be completed.  The CEC has  stated  that  it will  accept  a  “third party”  impact  study  and,  therefore, GWF has requested that Navigant Consulting Inc. (NCI) perform a System Impact Study (SIS) for the Project.  This SIS: 

• Identifies  the  transmission  system  impacts  caused  solely  by  the  addition  of  the proposed Project,  

• Identifies the system reinforcements necessary to mitigate the adverse impacts of the proposed Project under various system conditions, and  

• Provides preliminary cost estimates for the above system reinforcements.  To  determine  the  system  impacts  caused  by  the  addition  of  the  Project,  studies  were performed using the following full loop base cases: 1) 2013 Summer Peak, 2) 2013 Summer Off‐Peak, and 3) 2013 Spring Peak.  The studies performed included: 

• Steady State Power Flow • Governor Power Flow • Dynamic Stability Analysis • Short Circuit Analysis • Reactive Margin Analysis 

 This evaluation, which was performed using data provided by PG&E and in a manner similar to that used by PG&E in performing generation interconnection system impact studies in accordance with existing CAISO/PG&E tariff rules, concludes that the addition of the Project would cause a number of pre‐existing normal and/or emergency overloads to increase.  However, the addition of the Project did not result in new overloads.   The power flow analysis also indicated that the Project causes no reactive power deficiencies. Dynamic Stability Study and Reactive Margin Study results indicated that the transmission system’s performance, relative to the applicable reliability guidelines, would not be impacted by the GWF Project following selected disturbances. 

 1

Page 7: To determine the system impacts caused by the Project

The preliminary cost estimate of the Interconnection Facilities1 to interconnect the Project is approximately $1.1 million, exclusive of ITCC2.   

2. Project and Interconnection Information 

As discussed above  the Project will be  located at  the  existing GWF Henrietta  site  located directly adjacent to PG&E’s Henrietta Substation.   Figure 2‐1 provides a map of the Project area and of the transmission facilities in the proximity of the Project. 

The Project will be an addition of a steam turbine generator, along with the steam turbine’s associated  generator  step‐up  transformer  (GSU),  to  the  existing  two  combustion  turbine generators  which  will  establish  a  combined  cycle  power  plant.    Specific  information regarding the Project Expansion configuration is as follows: 

• Steam turbine generator ‐ 27 MW (gross) • Auxiliary load – 2.0 MW • Total  maximum net output of 25 MW • STG step‐up transformer – Rated at 13.8/70‐kV and 35 MVA. 

JACOBS CORNERON 18TH AVE, 5 MILES S/O LEMOOAVENAL9324560 kvOwner: PGEGIS_ID: 72265SAP Funct Loc #: ETS.08.12518

JACOBS CORNERON 18TH AVE, 5 MILES S/O LEMOOAVENAL9324560 kvOwner: PGEGIS_ID: 72265SAP Funct Loc #: ETS.08.12518

JACOBS CORNERON 18TH AVE, 5 MILES S/O LEMOOAVENAL9324560 kvOwner: PGEGIS_ID: 72265SAP Funct Loc #: ETS.08.12518

JACOBS CORNERON 18TH AVE, 5 MILES S/O LEMOOAVENAL9324560 kvOwner: PGEGIS_ID: 72265SAP Funct Loc #: ETS.08.12518

JACOBS CORNERON 18TH AVE, 5 MILES S/O LEMOOAVENAL9324560 kvOwner: PGEGIS_ID: 72265SAP Funct Loc #: ETS.08.12518

LEMOORE N.A.S.LEMORE AIRBASE, NR LEMOORELEMOORE STATION9324570 kvOwner: PGEGIS_ID: 71463SAP Funct Loc #:

LEMOORE N.A.S.LEMORE AIRBASE, NR LEMOORELEMOORE STATION9324570 kvOwner: PGEGIS_ID: 71463SAP Funct Loc #:

LEMOORE N.A.S.LEMORE AIRBASE, NR LEMOORELEMOORE STATION9324570 kvOwner: PGEGIS_ID: 71463SAP Funct Loc #:

LEMOORE N.A.S.LEMORE AIRBASE, NR LEMOORELEMOORE STATION9324570 kvOwner: PGEGIS_ID: 71463SAP Funct Loc #:

LEMOORE N.A.S.LEMORE AIRBASE, NR LEMOORELEMOORE STATION9324570 kvOwner: PGEGIS_ID: 71463SAP Funct Loc #:

LEPRINO FOODS (LEMOORE)200 N 19 1/2 AVE

LEMOORE93245

No Voltage DataOwner: nonPGEGIS_ID: 72463

SAP Funct Loc #:

LEPRINO FOODS (LEMOORE)200 N 19 1/2 AVE

LEMOORE93245

No Voltage DataOwner: nonPGEGIS_ID: 72463

SAP Funct Loc #:

LEPRINO FOODS (LEMOORE)200 N 19 1/2 AVE

LEMOORE93245

No Voltage DataOwner: nonPGEGIS_ID: 72463

SAP Funct Loc #:

LEPRINO FOODS (LEMOORE)200 N 19 1/2 AVE

LEMOORE93245

No Voltage DataOwner: nonPGEGIS_ID: 72463

SAP Funct Loc #:

LEPRINO FOODS (LEMOORE)200 N 19 1/2 AVE

LEMOORE93245

No Voltage DataOwner: nonPGEGIS_ID: 72463

SAP Funct Loc #:

GWF HENRIETTA CO-GEN25TH STREET S/O HWY 198

AVENAL93245

Owner: nonPGEGIS_ID: 72472

SAP Funct Loc #:

GWF HENRIETTA CO-GEN25TH STREET S/O HWY 198

AVENAL93245

Owner: nonPGEGIS_ID: 72472

SAP Funct Loc #:

GWF HENRIETTA CO-GEN25TH STREET S/O HWY 198

AVENAL93245

Owner: nonPGEGIS_ID: 72472

SAP Funct Loc #:

GWF HENRIETTA CO-GEN25TH STREET S/O HWY 198

AVENAL93245

Owner: nonPGEGIS_ID: 72472

SAP Funct Loc #:

GWF HENRIETTA CO-GEN25TH STREET S/O HWY 198

AVENAL93245

Owner: nonPGEGIS_ID: 72472

SAP Funct Loc #:

LEMOORE SC11239 19TH AVENUELEMOORE93245Owner: PGEGIS_ID: 70298SAP Funct Loc #:

LEMOORE SC11239 19TH AVENUELEMOORE93245Owner: PGEGIS_ID: 70298SAP Funct Loc #:

LEMOORE SC11239 19TH AVENUELEMOORE93245Owner: PGEGIS_ID: 70298SAP Funct Loc #:

LEMOORE SC11239 19TH AVENUELEMOORE93245Owner: PGEGIS_ID: 70298SAP Funct Loc #:

LEMOORE SC11239 19TH AVENUELEMOORE93245Owner: PGEGIS_ID: 70298SAP Funct Loc #:

LEMOORE CSO208 WEST D STREETLEMOORE93245Owner: PGEGIS_ID: 70297SAP Funct Loc #:

LEMOORE CSO208 WEST D STREETLEMOORE93245Owner: PGEGIS_ID: 70297SAP Funct Loc #:

LEMOORE CSO208 WEST D STREETLEMOORE93245Owner: PGEGIS_ID: 70297SAP Funct Loc #:

LEMOORE CSO208 WEST D STREETLEMOORE93245Owner: PGEGIS_ID: 70297SAP Funct Loc #:

LEMOORE CSO208 WEST D STREETLEMOORE93245Owner: PGEGIS_ID: 70297SAP Funct Loc #:

Sw. #27Sw. #27Sw. #27Sw. #27Sw. #27

Sw. #29Sw. #29Sw. #29Sw. #29Sw. #29

Sw. #65Sw. #65Sw. #65Sw. #65Sw. #65

Sw. #129Sw. #129Sw. #129Sw. #129Sw. #129Sw. #127Sw. #127Sw. #127Sw. #127Sw. #127Sw. #125Sw. #125Sw. #125Sw. #125Sw. #125

19 1/ 2(HW

Y 41)1 9 1/2(H

WY 41)

19 1 /2(HW

Y 41)19 1 /2(H

WY 41)

19 1 /2(HW

Y 41)H

WY 41)

HW

Y 41)H

WY 41)

HW

Y 41)H

WY 41)

2 0TH20T H2 0TH2 0TH2 0TH

20TH20TH20TH20TH20TH

HWY 198

HWY 198

HWY 198HWY 198

HWY 198

HWY 198

HWY 198

HWY 198HWY 198

HWY 198

HWY 198HWY 198HWY 198HWY 198HWY 198

HW

Y 41H

WY 41

HW

Y 41H

WY 41

HW

Y 41H

WY 41

HW

Y 4 1H

WY 41

HW

Y 41H

WY 41

HWY

41

HWY

41HW

Y 41

HWY

41HW

Y 41

HWY

41

HWY

41HW

Y 41

HWY

41HW

Y 41

HWY

41

HWY

41HW

Y 41

HWY

41HW

Y 41

HWY

41

HWY

41HW

Y 41

HWY

41

HWY

41HWY 198HWY 198HWY 198HWY 198HWY 198HWY 198HWY 198HWY 198HWY 198HWY 198

1 8TH18T H1 8TH1 8TH1 8TH

8TH8TH8TH8TH8TH

18TH18TH18TH18TH18TH

AVENAL CUT-O

FF

AVENAL C

UT-OFF

AVENAL C

UT-OFF

AVENAL C

UT-OFF

AVENAL C

UT-OFF

AVENAL C

UTOFF

AVENAL CUTOFF

AVENAL C

UTOFF

AVENAL C

UTOFF

AVENAL C

UTOFF

BUSHBUSHBUSHBUSHBUSH

EM

PIR

EE

MP

IRE

EM

PIR

EE

MP

IRE

EM

PIR

E

HANFORD AHANFORD AHANFORD AHANFORD AHANFORD A

JACKSONJACKSONJACKSONJACKSONJACKSON

LAURELLAURELLAURELLAURELLAUREL LAURELLAURELLAURELLAURELLAUREL

GWF Henrietta Project

Gates-Gregg 230 kV Line

Henrietta-LemoorNAS 70 kV Line

Henrietta-Lemoor70 kV Line

Guernsey-Henrietta 70 kV Line

Henrietta Substation

  1 The transmission facilities necessary to physically and electrically interconnect the Project to the CAISO Controlled Grid. 2 Income Tax Component of Contribution. 

 2

Page 8: To determine the system impacts caused by the Project

Figure 2‐1:  Project Location Map 

Figure 2‐2  is a conceptual one‐line diagram  for  the Project and  the related  interconnection facilities. 

 

 

 

Figure 2‐2:  Conceptual One‐Line Diagram 

  

3. Study Assumptions 

NCI conducted this SIS using the following assumptions: 

1. The Project will be a steam  turbine generator rated  for 27 MW.     The maximum  total gross output  from  the Project  is 27 MW with an expected  total plant  load of 2.0 MW.  Therefore, the maximum net output to the grid will be 25 MW.   

2. The expected commercial operation date is May 2012. 3. The  step‐up  transformer  for  the  STG,  will  be  a  three‐phase,  13.8/70‐kV  delta/wye 

grounded transformer, rated at 35 MVA @ 65 degree C rise with an impedance of 9% @ 35 MVA base.   

Point of Interconnection

Henrietta Substation

32

Existing Tie Line

48 MW 48 MW 25 MW25 MWHenrietta Peaker Plant Existing New

 3

Page 9: To determine the system impacts caused by the Project

4. The generator will tie in to the existing GWF Henrietta substation. 5. The  planned  generating  facilities  in  PG&E’s  Greater  Fresno  service  area  whose 

schedules are concurrent with or precede the Project’s schedule will be modeled on‐line.  

4. Powerflow Study Base Cases 

Six power flow base cases (three pre‐Project and three post‐Project) were used to evaluate the transmission system impacts of the Project.  While it is impossible to study all combinations of system load and generation levels during all seasons and at all times of the day, these base cases will represent extreme loading and generation conditions for the study area.  However, there is no guarantee that: 

• The  Project  can  operate  at maximum  rated  output  24  hours  a  day,  year  round, without system impacts, or 

• The Project will not cause system impacts during the times and seasons not studied in this SIS. 

 The power flow analysis was performed using the following WECC full‐loop base cases (all in General Electric Power Flow format).  These base cases were provided by PG&E: 

• A 2013 Summer Peak Base Case which was developed from PG&E’s 2007 base case series and has a 1‐in‐10 year extreme weather load level for the Greater Fresno Area. 

• A  2013  Spring  Peak  Base  Case  which  was  developed  to  evaluate  potential transmission  congestion with  typical Spring  season  load  conditions and very high hydro‐generation levels (as is typical during the Spring season).  

• A  2013  Summer Off‐Peak  Base  Case which was  developed  to  evaluate  potential transmission congestion during off‐peak system conditions.  The load in the Greater Fresno area was modeled at 50% of  the summer peak  load  level and  two units at Helms PGP (620 MW total) were assumed in pumping mode. 

 Table 4‐1 summarizes information regarding critical path flows and northern California area loads and generation for each of the above cases.    According  to  the  IFS  study  plan  the  above  base  cases  modeled  all  approved  CAISO transmission  reliability projects  that will  be  operational  by  2013.   They  also modeled  the proposed  queued  generation  projects  that  are  ahead  of  the  Project  in  the CAISO  queue.  However, some generation projects that are electrically far from the proposed Project were either turned off or modeled with reduced generation to balance the loads and resources in the power flow model.  The major queued generation projects in the southern portion of the PG&E system modeled in the above base cases are summarized in Table 4‐2. 

 

 4

Page 10: To determine the system impacts caused by the Project

 

 

Table 4‐1:  Key Base Case Parameters 

Powerflow Case  

Summer Peak 

Spring Peak 

Summer Off‐Peak 

Critical Path Flows (North‐to‐South, MW) Path 15 (Los Banos ‐ Midway)  (1,968)  (966)  (5,000) 

Path 26 (Midway‐Vincent)  3,945  2,889  (591) Path 65 (PDCI)  2,500  3,091  (1,846) Path 66 (COI)  4,742  4,501  (3,647) 

Northern California Data (MW) Area Loads  28,155  22,833  14,029 Area Losses  1,244  1,012  721 

Area Generation  28,518  22,170  18,651  The base cases and the most recent CAISO generation interconnection queue (dated July 25, 2008) were  reviewed by NCI  to determine  if  the base cases contained projects with  lower numbered queue positions  than  the Project which may have withdrawn  from  the CAISO generation  interconnection queue  since  the cases were prepared.     All Queued generation modeled in the base cases remain in the queue and are summarized in Table 4‐2 below. 

Table 4‐2:  Modeling of Queued Projects in Henrietta  SIS 

Queue Position 

Interconnection Point 

Capacity (MW) 

9  Morro Bay 230‐kV bus  1,200 16  Lompoc area 115‐kV lines  120 42  McCall 115‐kV bus  300 52  Panoche 230‐kV bus  401 54  Panoche 115‐kV bus  120 60  Kern Oil 115‐kV bus  94 128  McCall 230‐kV bus  565 152  Mesa‐Divide #1 and #2 115‐kV lines  105 166  Morro Bay‐Midway 230‐kV line  210 194  230‐kV lines near Carrizo Plains sub.  190 196  Borden 230‐kV bus  508 238  Temblor‐San Luis Obispo 115‐kV line  45 239  Morro Bay‐Midway 230‐kV line  250 242  Morro Bay‐Midway 230‐kV line  390 

 5

Page 11: To determine the system impacts caused by the Project

Queue  Interconnection  Capacity Position  Point  (MW) 

253  Cabrillo substation  40 254  Gates Substation 230‐kV Bus  600 261  Mendota‐San Joaquin‐Helm 70‐kV Line  5 272  Henrietta 70‐kV Bus  27 

 

5. Study Criteria Summary 

5.1 Powerflow Studies 

Criteria applied during the powerflow analysis were as follows: 

• Normal (Category A) conditions: 

° All line and transformer loadings shall be below normal rating. 

° Bus voltages will not exceed the minimum or maximum limits established. 

• Contingency (Category B and C) conditions: 

° No transmission element will be loaded above the emergency rating. 

° Bus voltage deviations  shall not exceed 5%  for Category B and 10%  for Category C outages. 

° There will be no loss of load for Category B outages. 

 5.2 Transient Stability Analysis 

Transient stability studies were performed to assess the impact of the Project on the system.   Each  contingency was simulated  for 20  seconds  in order  to demonstrate that it complies with NERC/WECC Planning criteria.   

Criteria applied in these studies will be as follows: 

• All machines  in  the system shall  remain  in synchronism as demonstrated by their relative rotor angles. 

• System stability is evaluated based on the damping of the relative rotor angles and the damping of the voltage magnitude swings. 

• Transient voltage dips  and  frequency dips must meet  the WECC Reliability Criteria summarized in Table 5‐1. 

 6

Page 12: To determine the system impacts caused by the Project

Table 5‐1:  WECC Reliability Criteria 

Performance Level 

Disturbance  Transient Voltage Dip Criteria 

Transient Frequency Dip 

Criteria 

Post Transient Voltage  Deviation 

B N‐1 

(Single Contingency) 

Max V Dip at Load Buses‐25% 

Max Duration of V Dip > 20% ‐ 20 cycles 

Duration of Frequency Below 59.6 Hz  ‐ 6 cycles 

Not to exceed 5% 

C N‐2 

(Double Contingency) 

Max V Dip – 30% Max Duration of V Dip > 20% 

‐ 40 cycles 

Duration of Frequency Below 59.4 Hz  ‐ 6 cycles 

Not to exceed 10% 

5.3 Reactive Margin Analysis 

In order to meet planning standards, the system must have positive reactive margin with the Path flow increased by 5% for Category B outages and increased by 2.5% for Category C outages.  Positive reactive margin with rated Path flows is all that is required for outages involving two nuclear units at the Palo Verde, San Onofre, or Diablo Canyon nuclear plants.  

6. Steady State Power Flow Study and Results  

This SIS investigated the Project’s impact on the CAISO Controlled Grid.  The study utilized three seasonal base cases to simulate the impact of interconnecting the Project during normal operating conditions as well as during Category B and Category C contingency conditions (described below in section 6.1). 

It cannot be guaranteed that the GWF Project can operate at maximum rated output 24 hours a day, year round, without system  impacts, nor can  it be guaranteed that the GWF Project would not have system impacts during the times and seasons not studied in the SIS. 

6.1 Contingencies 

The  Category  “B”  and  “C”  contingencies  used  in  this  analysis  are  provided  in Appendix  A.    The  single  (Category  “B”)  and  selected multiple  (Category  “C”) contingencies include the following outages: 

6.1.1 Category “B” 

• All single (60 – 500‐kV) generator outages within the study area • All single (60 – 500‐kV) transmission circuit outages within the study area • All single (60 – 500‐kV) transformer outages within the study area • Selected overlapping single generator and transmission circuit outages for 

the transmission lines and generators within the study area 

 7

Page 13: To determine the system impacts caused by the Project

• 500‐kV  facility  outages  were  simulated  using  a  governor  power  flow program. 

6.1.2 Category “C” 

• Selected bus (60‐230‐kV) outages within the study area • Selected outages caused by selected breaker failures (excluding bus tie and 

sectionalizing breakers) at the same above bus section • Selected  combination  of  any  two‐generator/transmission  line/transformer 

outages (except ones included above in Category “B”) within the study area • Selected outages of double circuit tower lines (60‐500‐kV) within the study 

area. • 500‐kV  facility  outages  were  simulated  using  a  governor  power  flow 

program.    Path  15  Internal  Remedial  Action  Scheme  (IRAS)  was  also simulated for the relevant outages during the Summer Off‐Peak base case in which there are high south‐to‐north flows across Path 15. 

6.2 Power Flow Study Results 

Appendix A provides a list of the contingencies studied.  Appendix B provides the switching sequences for those 500‐kV outages simulated with the governor power flow program.   Appendix C shows  the power  flow analysis results.   Appendix D includes power flow plots of those new overloads and overloads that had the most significant increase due to the Project coming on‐line. 

6.2.1 Normal Overloads (CAISO Category A) 

The Project causes no new normal overloads.  It did result in slight increases in existing overloads on fourteen (14) facilities during the 2013 Summer Peak, two (2)  facilities  during  the  2013  Summer  Off‐Peak,  and  thirteen  (13)  facilities during  the  2013  Spring  Peak.    The  mitigation  of  these  overloads  is  the responsibility of projects earlier in the CAISO Generation Queue. 

 6.2.2 Emergency Overloads (CAISO Category B) 

The Project results in new Category B overloads occurring on three (3) facilities during the 2013 Summer Peak, two (2) facilities during the 2013 Summer Off‐Peak,  and  twelve  (12)  facilities  during  the  2013  Spring  Peak  conditions.   However,  these  facilities  experienced    greater  overloads  in  the  pre‐Project studies.  Therefore,  the  mitigation  of  those  pre‐Project  overloads  is  the responsibility of projects earlier in the CAISO Generator  

 8

Page 14: To determine the system impacts caused by the Project

In  addition,  the  Project  exacerbated  existing  overloads  on  twenty‐one  (21) facilities  during  the  2013  Summer  Peak,  seven  (7)  facilities  during  the  2013 Summer Off‐Peak, and twenty‐one (21) facilities during the 2013 Spring Peak.  The mitigation of  those pre‐Project overloads  is  the  responsibility of projects earlier in the CAISO Generator Queue.. 

All facility overloads are shown in Appendix C with the pre‐Project overloads shown as shaded in the table. 

6.2.3 Emergency Overloads (CAISO Category C) 

The Project results in  new Category C overloads occurring on five (5) facilities during the 2013 Summer Peak,  two (2) facilities during the 2013 Summer Off‐Peak, and  seven  (7)  facilities during 2013 Spring Peak conditions.   However, these facilities experienced overloads during the pre‐Project studies.  Therefore, the mitigation  of  those pre‐Project  overloads  is  the  responsibility  of projects earlier in the CAISO Generator Queue. Table 6‐2 below summarizes the three impacted facilities that did not overload for any of the pre‐Project scenarios and are a result of the addition of the Project.   

In  addition,  the  Project  exacerbated  existing  overloads  on  forty‐nine  (49) facilities during  the 2013 Summer Peak,  twenty‐four  (24)  facilities during  the Summer Off‐Peak, and  forty‐nine  (49)  facilities during  the 2013 Spring Peak. The mitigation of  those pre‐Project overloads  is  the  responsibility of projects earlier in the CAISO Generator Queue 

All facility overloads are shown in Appendix C with the pre‐Project overloads shown as shaded in the table.     

7. Reactive Power Deficiency Analysis 

The power flow studies of Category “B” and “C” contingencies indicated that the Project did not cause voltage drops of 5% or more from the pre‐Project levels, or cause the PG&E system to fail to meet applicable voltage criteria. 

Post‐transient  reactive margin  studies were performed  on  the  Summer Off‐Peak  base cases because of  the high south‐to‐north  flow conditions on  the Los Banos‐North Path modeled in these cases.  Reactive Margins were calculated for the following outages: 

Category B 

• Diablo‐Midway 500‐kV • Gates‐Midway 500‐kV • Los Banos‐Gates #1 500‐kV 

 9

Page 15: To determine the system impacts caused by the Project

• Los Banos‐Gates #3 500‐kV • Los Banos‐Midway 500‐kV • Moss Landing‐Los Banos 500‐kV • Tracy‐Los Banos 500‐kV • Tesla‐Los Banos 500‐kV  Category C 

• Diablo‐Midway #1 & #2 500‐kV DLO • Los Banos‐Tesla & Los Banos‐Tracy 500‐kV DLO w/ Path 15 IRAS • Los Banos‐Midway & Los Banos‐Gates 500‐kV DLO w/ Path 15 IRAS • Midway‐Gates & Midway‐Los Banos 500‐kV DLO w/ Path 15 IRAS  2‐Nuclear Unit Trip 

• Diablo 2‐Unit Trip 

As shown in Table 7‐1 below, the addition of the Project has no negative impact to the reactive margins on the system. 

Table 7‐1:  Reactive Margin Results 

Reactive Margin (MVAR) 2013 Summer Off‐Peak Case Contingency 

 

Bus with smallest  

Reactive Margin   Pre‐Project  Post‐Project  Difference 

Category B – Path 15 Flows Increased by 5%       

Diablo‐Midway 500‐kV  Arco 230‐kV  529  529  0 

Gates‐Midway 500‐kV  Arco 230‐kV  506  506  0 

Los Banos‐Gates #1 500‐kV  Arco 230‐kV  509  509  0 

Los Banos‐Gates #3 500‐kV  Arco 230‐kV  520  520  0 

Los Banos ‐ Midway 500‐kV  Arco 230‐kV  498  498  0 

Moss Landing‐Los Banos 500‐kV  Arco 230‐kV  519  519  0 

Tracy‐Los Banos 500‐kV  Arco 230‐kV  512  512  0 

Tesla‐Los Banos 500‐kV  Arco 230‐kV  511  511  0 

Category C – Path 15 Flows Increased by 2.5%       

Diablo‐Midway #1 & #2 500‐kV DLO  Arco 230‐kV  517  517  0 Los Banos‐Tesla & Los Banos‐Tracy 500‐kV DLO  w/ Path 15 RAS 

Arco 230‐kV  501  501  0 

Los Banos‐Midway & Los Banos‐Gates 500‐kV DLO  w/ Path 15 RAS 

Arco 230‐kV  475  475  0 

Midway‐Gates & Midway‐Los Banos 500‐kV DLO  w/ Path 15 RAS 

Arco 230‐kV  496  496  0 

Two Unit Outage – No Increase in Path 15 Flows       

Diablo 2‐Unit Trip  Arco 230‐kV  592  591  ‐1 

 10

Page 16: To determine the system impacts caused by the Project

 

8. Transient Stability Results 

Transient stability simulations were performed on the 2013 Summer Peak base case for a period of 20 seconds to determine whether the addition of the Project would create any system instability during the following line and generator outages.  

8.1 CAISO Category “B” 

• Full load rejection (127 MW) of the proposed Project. 

• A  three‐phase  close‐in  fault  on  the  Henrietta‐Guernsey  70‐kV  line  at  the Henrietta  70‐kV  bus with  normal  clearing  time  followed  by  the  loss  of  the Henrietta‐Guernsey 70‐kV line. 

• A  three‐phase close‐in  fault on  the Henrietta‐Lemoore NAS 70‐kV  line at  the Henrietta  70‐kV  bus with  normal  clearing  time  followed  by  the  loss  of  the Henrietta‐Lemoore NAS 70‐kV line. 

• A  three‐phase  close‐in  fault  on  the  Henrietta‐Lemoore  70‐kV  line  at  the Henrietta  70‐kV  bus with  normal  clearing  time  followed  by  the  loss  of  the Henrietta‐Lemoore 70‐kV line. 

• A three‐phase close‐in fault on the Henrietta 230/70‐kV Transformer #2 at the Henrietta  70‐kV  bus with  normal  clearing  time  followed  by  the  loss  of  the Henrietta 230/70‐kV Transformer #2. 

• A three‐phase close‐in fault on the Henrietta 230/70‐kV Transformer #4 at the Henrietta  70‐kV  bus with  normal  clearing  time  followed  by  the  loss  of  the Henrietta 230/70‐kV Transformer #4. 

 8.2 CAISO Category “C” 

• A three‐phase fault on the Gates‐Gregg and Gates‐McCall 230‐kV  lines at the Henrietta  230‐kV bus with normal  clearing  time  followed by  the  loss of  the Gates‐Gregg and Gates‐McCall 230‐kV lines. 

 These dynamic  stability  studies  indicated  that  there would be no  system performance issues caused by the GWF Project.  Transient stability plots are given in Appendix E.  

 11

Page 17: To determine the system impacts caused by the Project

Table 8‐1: Transient Stability Bus Voltages that dip below 59.6 Hz 

         Pre‐Project  Post‐Project   

Outage Bus No.  Bus  Duration 

Min. Freq. 

  @ time  Duration 

Min. Freq. 

 @ time 

Change in  Freq Dip 

34460  Guernsey 70‐kV  9  59.319  0.44  11.2  59.326  0.48  0.007 

34532  Armstrong 70‐kV  9  59.284  0.48  11.2  59.279  0.48  ‐0.005 34534  Reserve 70‐kV  9  59.284  0.48  11.2  59.279  0.48  ‐0.005 

Henrietta 230/115‐kV Bk#4  (8 cycle clearing)  34540  Henrietta 70‐kV  ‐‐  ‐‐  ‐‐  6.7  59.457  0.44  ‐‐ 

 

9. Short Circuit Study Results 

Short circuit studies were performed  to determine  the  impact of adding  the Project  to  the transmission system.  The 3‐phase fault duties at busses in the proximity of the Project were calculated before and after the Project.  The dynamic data supplied by GWF and summarized in Appendix F was used  in  the analysis of  these short circuit studies.   The Project step‐up transformer was modeled as follows in these studies. 

STG:   One,  three‐phase, 13.8/70kV and  rated  for 35 MVA at 65 degree C  temperature rise with 9.0% impedance at 35 MVA base. 

 9.1 Results 

Table 9‐1  lists the available pre‐ and post‐Project short circuit duty at the buses electrically adjacent  to  the Project.   As shown  in Table 9‐1  the only appreciable increase  in short circuit duty due  to  the addition of  the Project occurred at  the Lemoore NAS 70‐kV bus and the Henrietta 70‐kV bus. 

Table 9‐1:  Short Circuit Study Results (Amps) 

Pre‐Project 

Post‐Project 

Fault Location  3Ø  3Ø %  

Increase  

Henrietta 230‐KV Bus  14,457  14,653  1.36% Henrietta 115‐KV Bus  9,468  9,495  0.28% Henrietta 70‐KV Bus  19,131  20,062  4.86% Lemoore 70‐kV Bus  4,890  4,948  1.18% Lemoore NAS 70‐kV Bus  12857  13,272  3.23% Leprino 70‐kV Bus  4,604  4,655  1.11% Jacobs Corner 70‐kV Bus  6,002  6,065  1.05% Guernsey 70‐kV Bus  4,264  4,286  0.54% Reserve 70‐kV Bus  3,686  3,701  0.39% 

 12

Page 18: To determine the system impacts caused by the Project

 

10. Mitigation 

As described  in  the  sub‐section  below  the Project did not  create  any new  overloads  that hadn’t already been overloaded for under pre‐Project conditions.  

10.1 Category “A” Normal Overload Mitigation 

The power flow results  indicated that the Project caused no new Category “A” normal overloads and only slightly increased overloads that existed on the Pre‐Project  case.    Therefore,  there  is  no  mitigation  needed  for  Category  “A” conditions.  

10.2 Category “B” Emergency Overload Mitigation 

The power flow results indicated that the Project did not result in overloads on any facilities which were greater than the overloads noted in the Pre‐Project studies.  Therefore, there is no mitigation needed for Category “B” conditions.  

10.3 Category “C” Emergency Overload Mitigation 

The power flow results indicate that the Project did not result in overloads on any facilities which were greater than the overloads noted in the pre‐Project studies.  Therefore, there is no mitigation needed for Category “C” conditions. 

 

11. Cost  Estimates  

The preliminary cost estimate for the Project interconnection to the CAISO Controlled Grid is $1.1 million, exclusive of ITCC.  The cost responsibility breakdown is provided below. 

Substation Work   Provide general support at generation site  $1,000,000 Subtotal Substation Work  $1,000,000 

   Building & Land Work   Land engineering support and permitting activities  $100,000 Subtotal Building & Land Work  $100,000 

   Total Interconnection Facilities Cost before ITCC 3  $1,100,000 

 

3 Based on information in the Project IFS 

 13

Page 19: To determine the system impacts caused by the Project

12. Environmental Evaluation / Permitting 

12.1 CPUC General Order 131‐D 

As discussed in the Interconnection Feasibility Study (IFS), Pacific Gas and Electric Company  (PG&E)  is  subject  to  the  jurisdiction  of  the  California  Public Utilities Commission (CPUC) and must comply with CPUC General Order 131‐D (Order) on the  construction, modification,  alteration,  or  addition  of  all  electric  transmission facilities  (i.e.,  lines,  substations, etc.).   This  includes  facilities  to be  constructed by others and deeded  to PG&E.   The Order exempts PG&E  from obtaining a  formal permit  from  the  CPUC  on  facilities  over  200‐kV  provided  the  planned  facilities involve  the  replacement  of  existing  facilities  or  supporting  structures  with equivalent  facilities  or  structures,  the  minor  relocation  of  existing  facilities,  the conversion of existing facilities to underground or the placing of new or additional conductors,  insulators, or their accessories on or replacement of structures already built.  These exemptions do not apply under certain circumstances when significant environmental impacts may be caused by the work.  If the project does not qualify for an  exemption, PG&E will need  to  seek  formal approval  from  the CPUC  (i.e., Certificate of Public Convenience and Necessity)  taking as much as 18 months or more since the CPUC may decide to conduct its own environmental evaluation (i.e., Negative Declaration or Environmental Impact Report).   

For cases where PG&E can claim a valid exemption, PG&E would  file an Advice Letter with the CPUC and publish public notice of the proposed construction of the facilities.  The noticing process takes about 90 days if no protests are filed, but should be done as early as possible so that a protest does not delay construction.  PG&E has no  control over  the  time  it  takes  the CPUC  to  respond when  issues arise.    If  the protest is granted, PG&E will then need to apply for a formal permit to construct the project (i.e., Certificate of Public Convenience and Necessity). 

Facilities built or modified under this procedure must also be designed  to  include electric and magnetic  field  (EMF) mitigation measures pursuant  to PG&E   “EMF Design  Guidelines  of  New  Electrical  Facilities:    Transmission,  Substation  and Distribution”. 

Please see Section III, B.1 (f) in General Order 131‐D.  This document can be found in the CPUC’s web page at: 

http://www.cpuc.ca.gov/PUBLISHED/GENERAL_ORDER/589.htm 

12.2 CPUC Section 851 

In addition, and as noted  in  the  IFS, Pacific Gas and Electric Company  (PG&E)  is subject to the jurisdiction of the California Public Utilities Commission (CPUC) and 

 14

Page 20: To determine the system impacts caused by the Project

 15

must  comply with  Public Utilities Code  Section  851, which  among  other  things requires CPUC approval of leases and licenses to use PG&E property.  This includes rights‐of‐way granted to third parties for interconnection facilities.  Obtaining CPUC approval  for  a  Section  851  application  can  take  several  months,  and  requires compliance  with  the  California  Environmental  Quality  Act  (CEQA).    PG&E recommends  that Section  851  issues be  identified  as  early  as possible  so  that  the necessary application can be prepared and processed. 

13. Study Updates 

This SIS was performed according  to  the assumptions shown  in  the Sections  titled “Study Assumptions” and “Power Flow Study Base Cases”.   If these assumptions are changed, an updated study may be required to re‐evaluate the project’s impact on the CAISO Controlled Grid.  Examples of changes that might prompt such a study are: 

• Change in interconnection date • Change in Interconnection Queue position • Change in Project’s MW size beyond the provisions set forth in the LGIP • Change in interconnection plan • Withdrawal of a higher queued project  from the CAISO queue 

Page 21: To determine the system impacts caused by the Project

Appendix A Category B and C Contingency Lists

Table of Content Summer Peak Category B Contingencies ........................................................................... 1 Summer Peak Category C Contingencies ......................................................................... 66 Summer Off-Peak Category B Contingencies .................................................................. 88 Summer Off-Peak Category C Contingencies ................................................................ 154 Spring Peak Category B Contingencies.......................................................................... 177 Spring Peak Category C Contingencies.......................................................................... 242

Page 22: To determine the system impacts caused by the Project

A-1 GWF Henrietta SISAppendix A

Summer Peak Category B Contingencies # Q272 2013 sumpk category b contingency list # Yosemite and Fresno Divisions Zones 313 and 314 # # 2013 sumpk category b contingency list # Yosemite Zone 313 # # # (1) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (2) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 0 # # # (3) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (4) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (5) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (6) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (7) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 0 # # # (8) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (9) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 23: To determine the system impacts caused by the Project

A-2 GWF Henrietta SISAppendix A

1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (10) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30793 "1 " 0 # line from PANOCHE 230.00 BRKR to (3) PANO_EC 230.00 2 30793 34326 "1 " 0 # TRAN from PANO_EC 230.00 (3) to (1) PANO_BS1 13.80 2 30793 34327 "1 " 0 # TRAN from PANO_EC 230.00 (3) to (1) PANO_BS2 13.80 4 34326 0 "ss" 0 # LOAD-DROP PANO_BS1 13.80 LOAD==4.50(2.49) 4 34327 0 "ss" 0 # LOAD-DROP PANO_BS2 13.80 LOAD==4.50(2.49) 3 34326 0 "1 " 0 # GEN-DROP PANO_BS1 13.80 GEN==102.50(20.25) 3 34326 0 "2 " 0 # GEN-DROP PANO_BS1 13.80 GEN==102.50(20.25) 3 34327 0 "3 " 0 # GEN-DROP PANO_BS2 13.80 GEN==102.50(20.25) 3 34327 0 "4 " 0 # GEN-DROP PANO_BS2 13.80 GEN==102.50(20.25) 0 # # # (11) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 0 # # # (12) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 0 # # # (13) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (14) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (15) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) 0 # # # (16) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69)

Page 24: To determine the system impacts caused by the Project

A-3 GWF Henrietta SISAppendix A

0 # # # (17) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30806 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR Q196 230.00 0 # # # (18) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30806 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR Q196 230.00 0 # # # (19) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line 0 # # # (20) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line 0 # # # (21) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34017 34010 "1 " 0 # line from CRWS LDG 60.00 (1) to (3) CRWS LDJ 60.00 1 34010 34006 "1 " 0 # line from CRWS LDJ 60.00 (3) to BRKR PATTERSN 60.00 1 34010 34012 "1 " 0 # line from CRWS LDJ 60.00 (3) to (2) GUSTN JT 60.00 1 34012 34014 "1 " 0 # line from GUSTN JT 60.00 (2) to BRKR NEWMAN 60.00 4 34017 0 "1 " 0 # LOAD-DROP CRWS LDG 60.00 LOAD==3.73(0.17) 1 34016 34017 "1 " 1 # Switches in Crows Landing SW 57 to transfer load 4 34017 0 "**" 1 # Restore Load at Crows Landing 0 # # # (22) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00 2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80 2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94)

Page 25: To determine the system impacts caused by the Project

A-4 GWF Henrietta SISAppendix A

4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11) 3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) 0 # # # (23) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 0 # # # (24) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34104 34108 "1 " 0 # line from ATWATER 115.00 BRKR to (3) CRESEY T 115.00 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (1) ATWATR J 115.00 1 34108 34114 "1 " 0 # line from CRESEY T 115.00 (3) to (3) JRWD GEN 115.00 1 34114 34124 "1 " 0 # line from JRWD GEN 115.00 (3) to (2) JR WOOD 115.00 2 34114 34332 "1 " 0 # TRAN from JRWD GEN 115.00 (3) to (1) JRWCOGEN 9.11 1 34124 34140 "1 " 0 # line from JR WOOD 115.00 (2) to (1) CRESSEY 115.00 4 34124 0 "1 " 0 # LOAD-DROP JR WOOD 115.00 LOAD==11.70(10.32) 4 34140 0 "1 " 0 # LOAD-DROP CRESSEY 115.00 LOAD==19.02(3.86) 3 34332 0 "1 " 0 # GEN-DROP JRWCOGEN 9.11 GEN==3.80(5.40) 0 # # # (25) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34105 34121 "1 " 0 # line from CERTANJ1 115.00 (2) to (3) SHARON T 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34121 34128 "1 " 0 # line from SHARON T 115.00 (3) to (3) OAKH_JCT 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34128 34123 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) K1-JCT 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) 0 # # # (26) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (3) ATWATR J 115.00 1 34110 34130 "1 " 0 # line from ATWATR J 115.00 (3) to (2) LIVNGSTN 115.00 1 34110 34144 "1 " 0 # line from ATWATR J 115.00 (3) to BRKR MERCED 115.00

Page 26: To determine the system impacts caused by the Project

A-5 GWF Henrietta SISAppendix A

1 34130 34132 "1 " 0 # line from LIVNGSTN 115.00 (2) to (1) GALLO 115.00 4 34130 0 "3 " 0 # LOAD-DROP LIVNGSTN 115.00 LOAD==24.58(5.00) 4 34132 0 "1 " 0 # LOAD-DROP GALLO 115.00 LOAD==4.30(3.68) 0 # # # (27) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34112 34116 "1 " 0 # line from EXCHEQUR 115.00 BRKR to BRKR LE GRAND 115.00 3 34306 0 "1 " 0 # Exchequer Unit will trip for this outage 4 34228 0 "**" 0 # Mariposa Loads will drop if bus is below 64 kV, this is anticipate 0 # # # (28) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34116 34134 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR WILSON A 115.00 0 # # # (29) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 0 # # # (30) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) 0 # # # (31) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 0 # # # (32) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34136 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR WILSON B 115.00 0 # # # (33) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34144 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR MERCED 115.00 0 # # # (34) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 0

Page 27: To determine the system impacts caused by the Project

A-6 GWF Henrietta SISAppendix A

# # # (35) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34136 34144 "2 " 0 # line from WILSON B 115.00 BRKR to BRKR MERCED 115.00 0 # # # (36) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34141 34148 "1 " 0 # line from PAN2_TAP 115.00 (2) to (2) CHENY 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80 1 34148 34149 "1 " 0 # line from CHENY 115.00 (2) to (3) CHENYT 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (37) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34150 34154 "1 " 0 # line from NEWHALL 115.00 (2) to BRKR DAIRYLND 115.00 1 34150 34178 "1 " 0 # line from NEWHALL 115.00 (2) to (3) MADERAPR 115.00 1 34178 34156 "1 " 0 # line from MADERAPR 115.00 (3) to BRKR MENDOTA 115.00 2 34178 34179 "1 " 0 # TRAN from MADERAPR 115.00 (3) to (1) MADERA_G 13.80 4 34150 0 "2 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==8.55(1.73) 4 34150 0 "3 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==10.62(2.16) 4 34179 0 "ss" 0 # LOAD-DROP MADERA_G 13.80 LOAD==3.60(0.85) 3 34179 0 "1 " 0 # GEN-DROP MADERA_G 13.80 GEN==28.60(6.34) 0 # # # (38) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34157 34156 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR MENDOTA 115.00 1 34157 34158 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR PANOCHE 115.00 3 34186 0 "1 " 0 # DG_PAN Unit trips for Panoche - Mendota 115 kV outage 0 # # # (39) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34158 34189 "1 " 0 # line from PANOCHE 115.00 BRKR to (3) STARWOOD 115.00 2 34189 34328 "1 " 0 # TRAN from STARWOOD 115.00 (3) to (1) STARGT1 13.80 2 34189 34329 "1 " 0 # TRAN from STARWOOD 115.00 (3) to (1) STARGT2 13.80 4 34328 0 "ss" 0 # LOAD-DROP STARGT1 13.80 LOAD==1.00(0.55) 4 34329 0 "ss" 0 # LOAD-DROP STARGT2 13.80 LOAD==1.00(0.55) 3 34328 0 "1 " 0 # GEN-DROP STARGT1 13.80 GEN==60.94(9.59) 3 34329 0 "2 " 0 # GEN-DROP STARGT2 13.80 GEN==60.94(9.59) 0 # # # (40) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 28: To determine the system impacts caused by the Project

A-7 GWF Henrietta SISAppendix A

1 34158 34350 "1 " 0 # line from PANOCHE 115.00 BRKR to (2) KAMM 115.00 1 34350 34352 "1 " 0 # line from KAMM 115.00 (2) to (2) CANTUA 115.00 1 34352 34432 "1 " 0 # line from CANTUA 115.00 (2) to (2) WESTLNDS 115.00 1 34432 34354 "1 " 0 # line from WESTLNDS 115.00 (2) to BRKR SCHINDLR 115.00 4 34350 0 "1 " 0 # LOAD-DROP KAMM 115.00 LOAD==3.85(1.75) 4 34352 0 "1 " 0 # LOAD-DROP CANTUA 115.00 LOAD==16.79(3.41) 4 34432 0 "16" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==0.94(0.23) 4 34432 0 "18" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==1.21(0.32) 0 # # # (41) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34159 34158 "1 " 0 # line from PANOCHEJ 115.00 (3) to BRKR PANOCHE 115.00 1 34159 34160 "1 " 0 # line from PANOCHEJ 115.00 (3) to (2) HAMMONDS 115.00 1 34159 34180 "1 " 0 # line from PANOCHEJ 115.00 (3) to (3) OXFRDJCT 115.00 1 34160 34161 "1 " 0 # line from HAMMONDS 115.00 (2) to (3) DFSTP 115.00 1 34161 34162 "1 " 0 # line from DFSTP 115.00 (3) to BRKR ORO LOMA 115.00 1 34161 34164 "1 " 0 # line from DFSTP 115.00 (3) to (1) DFS 115.00 1 34180 34166 "1 " 0 # line from OXFRDJCT 115.00 (3) to (1) OXFORD 115.00 1 34180 34181 "1 " 0 # line from OXFRDJCT 115.00 (3) to (3) WSTLDJCT 115.00 1 34181 34182 "1 " 0 # line from WSTLDJCT 115.00 (3) to (1) WSTLD1RA 115.00 1 34181 34183 "1 " 0 # line from WSTLDJCT 115.00 (3) to (3) LUISJCT 115.00 1 34183 34163 "1 " 0 # line from LUISJCT 115.00 (3) to (1) LUIS_#3 115.00 1 34183 34165 "1 " 0 # line from LUISJCT 115.00 (3) to (1) LUIS_#5 115.00 4 34160 0 "1 " 0 # LOAD-DROP HAMMONDS 115.00 LOAD==10.00(2.03) 4 34164 0 "1 " 0 # LOAD-DROP DFS 115.00 LOAD==1.37(1.06) 4 34166 0 "1 " 0 # LOAD-DROP OXFORD 115.00 LOAD==3.87(1.76) 4 34182 0 "1 " 0 # LOAD-DROP WSTLD1RA 115.00 LOAD==2.98(0.71) 4 34163 0 "1 " 0 # LOAD-DROP LUIS_#3 115.00 LOAD==3.30(0.78) 4 34165 0 "1 " 0 # LOAD-DROP LUIS_#5 115.00 LOAD==3.40(0.81) 0 # # # (42) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34172 34170 "1 " 0 # line from WESTLAND 70.00 (2) to (1) WESIX 70.00 1 34172 34271 "1 " 0 # line from WESTLAND 70.00 (2) to (3) WSTLDJCT 70.00 1 34271 34269 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) BIOMSJCT 70.00 1 34271 34469 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) GFFNJCT 70.00 1 34269 34268 "1 " 0 # line from BIOMSJCT 70.00 (3) to BRKR MENDOTA 70.00 1 34269 34270 "1 " 0 # line from BIOMSJCT 70.00 (3) to (2) BIOMASS 70.00 2 34270 34334 "1 " 0 # TRAN from BIOMASS 70.00 (2) to (1) BIO PWR 9.11 1 34469 34470 "1 " 0 # line from GFFNJCT 70.00 (3) to (1) GIFFEN 70.00 1 34469 34471 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) SNJQJCT 70.00

Page 29: To determine the system impacts caused by the Project

A-8 GWF Henrietta SISAppendix A

1 34471 34472 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR SAN JOQN 70.00 1 34471 34474 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR HELM 70.00 4 34172 0 "1 " 0 # LOAD-DROP WESTLAND 70.00 LOAD==3.20(0.76) 4 34170 0 "1 " 0 # LOAD-DROP WESIX 70.00 LOAD==1.60(0.38) 4 34470 0 "1 " 0 # LOAD-DROP GIFFEN 70.00 LOAD==9.59(1.95) 3 34334 0 "1 " 0 # GEN-DROP BIO PWR 9.11 GEN==21.80(10.99) 1 34472 34473 "1 " 1 # Switches in San Joaquin CB22 to transfer load 4 34472 0 "**" 1 # Restore Load at San Joaquin 0 # # # (43) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34218 "1 " 0 # line from ORO LOMA 70.00 BRKR to (2) DOS PALS 70.00 1 34218 34216 "1 " 0 # line from DOS PALS 70.00 (2) to BRKR SNTA RTA 70.00 4 34218 0 "1 " 0 # LOAD-DROP DOS PALS 70.00 LOAD==10.29(2.09) 0 # # # (44) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00 1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93) 0 # # # (45) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34234 "1 " 0 # line from ORO LOMA 70.00 BRKR to (2) POSO J1 70.00 1 34234 34266 "1 " 0 # line from POSO J1 70.00 (2) to (2) FIREBAGH 70.00 1 34266 34267 "1 " 0 # line from FIREBAGH 70.00 (2) to (2) TOMATAK 70.00 1 34267 34268 "1 " 0 # line from TOMATAK 70.00 (2) to BRKR MENDOTA 70.00 4 34266 0 "1 " 0 # LOAD-DROP FIREBAGH 70.00 LOAD==11.13(2.26) 4 34267 0 "1 " 0 # LOAD-DROP TOMATAK 70.00 LOAD==6.40(4.97) 0 # # # (46) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34202 34203 "1 " 0 # line from MERCED 70.00 BRKR to (3) ELNIDOTP 70.00 1 34203 34205 "1 " 0 # line from ELNIDOTP 70.00 (3) to (2) ELNIDO 70.00 1 34203 34236 "1 " 0 # line from ELNIDOTP 70.00 (3) to (1) POSO J2 70.00 2 34205 34330 "1 " 0 # TRAN from ELNIDO 70.00 (2) to (1) ELNIDO 13.80 4 34330 0 "ss" 0 # LOAD-DROP ELNIDO 13.80 LOAD==2.00(1.11) 3 34330 0 "1 " 0 # GEN-DROP ELNIDO 13.80 GEN==12.50(5.69)

Page 30: To determine the system impacts caused by the Project

A-9 GWF Henrietta SISAppendix A

0 # # # (47) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34202 34230 "1 " 0 # line from MERCED 70.00 BRKR to BRKR MRCDFLLS 70.00 0 # # # (48) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34204 34212 "1 " 0 # line from LIVNGSTN 70.00 (1) to (3) LVNGSTNT 70.00 1 34212 34206 "1 " 0 # line from LVNGSTNT 70.00 (3) to BRKR CANAL 70.00 1 34212 34210 "1 " 0 # line from LVNGSTNT 70.00 (3) to (2) SNTA NLA 70.00 1 34210 34208 "1 " 0 # line from SNTA NLA 70.00 (2) to (2) CHEVPIPE 70.00 1 34208 34214 "1 " 0 # line from CHEVPIPE 70.00 (2) to BRKR LOS BANS 70.00 4 34204 0 "2 " 0 # LOAD-DROP LIVNGSTN 70.00 LOAD==5.51(1.12) 4 34210 0 "1 " 0 # LOAD-DROP SNTA NLA 70.00 LOAD==6.75(1.37) 4 34210 0 "2 " 0 # LOAD-DROP SNTA NLA 70.00 LOAD==9.50(1.93) 4 34208 0 "1 " 0 # LOAD-DROP CHEVPIPE 70.00 LOAD==0.63(0.42) 0 # # # (49) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34206 34216 "1 " 0 # line from CANAL 70.00 BRKR to BRKR SNTA RTA 70.00 0 # # # (50) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34214 34278 "1 " 0 # line from LOS BANS 70.00 BRKR to (2) PCHCO PP 70.00 1 34278 34280 "1 " 0 # line from PCHCO PP 70.00 (2) to (2) INTL TUR 70.00 2 34280 34342 "1 " 0 # TRAN from INTL TUR 70.00 (2) to (1) INT.TURB 9.11 4 34278 0 "1 " 0 # LOAD-DROP PCHCO PP 70.00 LOAD==18.00(4.10) 3 34342 0 "1 " 0 # GEN-DROP INT.TURB 9.11 GEN==1.10(0.00) 0 # # # (51) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34214 34282 "1 " 0 # line from LOS BANS 70.00 BRKR to (2) ONLL PMP 69.00 2 34282 34316 "1 " 0 # TRAN from ONLL PMP 69.00 (2) to (1) ONEILPMP 9.11 4 34282 0 "1 " 0 # LOAD-DROP ONLL PMP 69.00 LOAD==6.00(1.20) 3 34316 0 "1 " 0 # GEN-DROP ONEILPMP 9.11 GEN==0.50(0.00) 0 # # # (52) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34228 34232 "1 " 0 # line from MARIPOS2 70.00 (1) to BRKR EXCHEQUR 70.00 4 34228 0 "1 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.01(1.83) 4 34228 0 "2 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.37(1.90) 1 34228 34244 "1 " 1 # Switches in Mariposa SW 39 to transfer load 4 34228 0 "**" 1 # Restore Load at Mariposa 0 #

Page 31: To determine the system impacts caused by the Project

A-10 GWF Henrietta SISAppendix A

# # (53) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34232 34242 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (2) BER VLLY 70.00 1 34242 34244 "1 " 0 # line from BER VLLY 70.00 (2) to (2) BRCEBG J 70.00 1 34244 34246 "1 " 0 # line from BRCEBG J 70.00 (2) to (3) SAXONCRK 70.00 1 34246 34248 "1 " 0 # line from SAXONCRK 70.00 (3) to (2) INDN FLT 70.00 2 34246 34346 "1 " 0 # TRAN from SAXONCRK 70.00 (3) to (1) SAXNCK L 4.16 1 34248 34250 "1 " 0 # line from INDN FLT 70.00 (2) to (1) YOSEMITE 70.00 4 34242 0 "1 " 0 # LOAD-DROP BER VLLY 70.00 LOAD==5.91(1.20) 4 34246 0 "1 " 0 # LOAD-DROP SAXONCRK 70.00 LOAD==0.03(0.02) 4 34248 0 "1 " 0 # LOAD-DROP INDN FLT 70.00 LOAD==2.02(0.41) 4 34250 0 "1 " 0 # LOAD-DROP YOSEMITE 70.00 LOAD==2.90(0.00) 0 # # # (54) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita 0 # # # (55) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34252 34256 "1 " 0 # line from MADERA 70.00 BRKR to BRKR BORDEN 70.00 0 # # # (56) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34252 34256 "2 " 0 # line from MADERA 70.00 BRKR to BRKR BORDEN 70.00 0 # # # (57) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34256 34240 "1 " 0 # line from BORDEN 70.00 BRKR to BRKR GLASS 70.00 0 # # # (58) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34256 34262 "1 " 0 # line from BORDEN 70.00 BRKR to (2) CASSIDY 70.00

Page 32: To determine the system impacts caused by the Project

A-11 GWF Henrietta SISAppendix A

1 34262 34454 "1 " 0 # line from CASSIDY 70.00 (2) to (2) RIVERROC 70.00 1 34454 34464 "1 " 0 # line from RIVERROC 70.00 (2) to BRKR COPPRMNE 70.00 4 34262 0 "1 " 0 # LOAD-DROP CASSIDY 70.00 LOAD==14.31(2.90) 4 34454 0 "1 " 0 # LOAD-DROP RIVERROC 70.00 LOAD==2.01(1.83) 0 # # # (59) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34259 34261 "1 " 0 # line from NRTHFORK 70.00 (3) to (2) SJNO3 70.00 1 34259 34260 "1 " 0 # line from NRTHFORK 70.00 (3) to (3) SJNO2 70.00 2 34259 34340 "1 " 0 # TRAN from NRTHFORK 70.00 (3) to (1) N.FORK E 9.11 2 34261 34633 "1 " 0 # TRAN from SJNO3 70.00 (2) to (1) SJ3GEN 9.11 1 34260 34452 "1 " 0 # line from SJNO2 70.00 (3) to BRKR WISHON 70.00 2 34260 34631 "1 " 0 # TRAN from SJNO2 70.00 (3) to (1) SJ2GEN 9.11 4 34261 0 "2 " 0 # LOAD-DROP SJNO3 70.00 LOAD==6.95(1.41) 4 34260 0 "2 " 0 # LOAD-DROP SJNO2 70.00 LOAD==3.22(0.66) 4 34340 0 "1 " 0 # LOAD-DROP N.FORK E 9.11 LOAD==1.21(0.25) 3 34633 0 "1 " 0 # GEN-DROP SJ3GEN 9.11 GEN==1.00(0.00) 3 34631 0 "1 " 0 # GEN-DROP SJ2GEN 9.11 GEN==2.00(0.00) 0 # # # (60) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34321 34226 "1 " 0 # line from MCSWAINJ 70.00 (3) to (2) MC SWAIN 70.00 1 34321 34230 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR MRCDFLLS 70.00 1 34321 34232 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR EXCHEQUR 70.00 2 34226 34320 "1 " 0 # TRAN from MC SWAIN 70.00 (2) to (1) MCSWAIN 9.11 3 34320 0 "1 " 0 # GEN-DROP MCSWAIN 9.11 GEN==10.00(2.00) 0 # # # (61) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Melones - Wilson line 0 # # # (62) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (63) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30765 (30069) 30050 34302 : 2 30765 30050 "1 " 0 # TRAN from LOSBANOS 230.00 BRKR to (1) LOSBANOS 500.00 0 # # # (64) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) #

Page 33: To determine the system impacts caused by the Project

A-12 GWF Henrietta SISAppendix A

# **** 3-WINDING TRANSFORMER 30790 (30791) 34158 34310 : 2 30790 34158 "1 " 0 # TRAN from PANOCHE 230.00 BRKR to (1) PANOCHE 115.00 0 # # # (65) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 30790 34158 "2 " 0 # TRAN from PANOCHE 230.00 BRKR to BRKR PANOCHE 115.00 0 # # # (66) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 34112 (34176) 34232 34306 : 2 34112 34232 "1 " 0 # TRAN from EXCHEQUR 115.00 BRKR to (4) EXCHEQUR 70.00 1 34232 34228 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) MARIPOS2 70.00 1 34232 34242 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) BER VLLY 70.00 1 34232 34321 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) MCSWAINJ 70.00 4 34228 0 "1 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.01(1.83) 4 34228 0 "2 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.37(1.90) 1 34228 34244 "1 " 1 # Switches in Mariposa SW 39 to transfer load 4 34228 0 "**" 1 # Restore Load at Mariposa 0 # # # (67) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34134 30800 "1 " 0 # TRAN from WILSON A 115.00 BRKR to BRKR WILSON 230.00 0 # # # (68) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34136 30800 "2 " 0 # TRAN from WILSON B 115.00 BRKR to BRKR WILSON 230.00 0 # # # (69) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 34144 (34146) 34202 34312 : 2 34144 34202 "2 " 0 # TRAN from MERCED 115.00 BRKR to (1) MERCED 70.00 0 # # # (70) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34200 34162 "2 " 0 # TRAN from ORO LOMA 70.00 BRKR to (3) ORO LOMA 115.00 1 34162 34161 "1 " 0 # line from ORO LOMA 115.00 BRKR to (1) DFSTP 115.00 1 34162 34168 "1 " 0 # line from ORO LOMA 115.00 BRKR to (1) EL NIDO 115.00 0 # # # (71) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34214 30765 "3 " 0 # TRAN from LOS BANS 70.00 BRKR to BRKR LOSBANOS 230.00 0 #

Page 34: To determine the system impacts caused by the Project

A-13 GWF Henrietta SISAppendix A

# # (72) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34214 30765 "4 " 0 # TRAN from LOS BANS 70.00 BRKR to BRKR LOSBANOS 230.00 0 # # # (73) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34256 30805 "1 " 0 # TRAN from BORDEN 70.00 BRKR to BRKR BORDEN 230.00 0 # # # (74) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34256 30805 "2 " 0 # TRAN from BORDEN 70.00 BRKR to BRKR BORDEN 230.00 0 # # # (75) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34268 34156 "1 " 0 # TRAN from MENDOTA 70.00 BRKR to (3) MENDOTA 115.00 1 34156 34178 "1 " 0 # line from MENDOTA 115.00 BRKR to (1) MADERAPR 115.00 1 34156 34157 "1 " 0 # line from MENDOTA 115.00 BRKR to (1) PANOCHET 115.00 4 34156 0 "1 " 0 # LOAD-DROP MENDOTA 115.00 LOAD==24.55(4.99) 0 # # # (76) B1 GENERATOR OUTAGE # 3 34142 0 "1" 0 # WHD_PAN2 13.80 PGEN=49.00 QGEN=-22.43 0 # # # (77) B1 GENERATOR OUTAGE # 3 34179 0 "1" 0 # MADERA_G 13.80 PGEN=28.60 QGEN=3.67 0 # # # (78) B1 GENERATOR OUTAGE # 3 34186 0 "1" 0 # DG_PAN1 13.80 PGEN=49.00 QGEN=-17.22 0 # # # (79) B1 GENERATOR OUTAGE # 3 34301 0 "1" 0 # CHOWCOGN 13.80 PGEN=50.00 QGEN=0.72 0 # # # (80) B1 GENERATOR OUTAGE # 3 34305 0 "1" 0 # CHWCHLA2 13.80 PGEN=12.50 QGEN=7.35 0 # # # (81) B1 GENERATOR OUTAGE # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # #

Page 35: To determine the system impacts caused by the Project

A-14 GWF Henrietta SISAppendix A

# (82) B1 GENERATOR OUTAGE # 3 34316 0 "1" 0 # ONEILPMP 9.11 PGEN=0.52 QGEN=0.00 0 # # # (83) B1 GENERATOR OUTAGE # 3 34320 0 "1" 0 # MCSWAIN 9.11 PGEN=10.00 QGEN=0.00 0 # # # (84) B1 GENERATOR OUTAGE # 3 34322 0 "1" 0 # MERCEDFL 9.11 PGEN=3.50 QGEN=2.00 0 # # # (85) B1 GENERATOR OUTAGE # 3 34326 0 "1" 0 # PANO_BS1 13.80 PGEN=102.50 QGEN=25.42 0 # # # (86) B1 GENERATOR OUTAGE # 3 34326 0 "2" 0 # PANO_BS1 13.80 PGEN=102.50 QGEN=25.42 0 # # # (87) B1 GENERATOR OUTAGE # 3 34327 0 "3" 0 # PANO_BS2 13.80 PGEN=102.50 QGEN=25.42 0 # # # (88) B1 GENERATOR OUTAGE # 3 34327 0 "4" 0 # PANO_BS2 13.80 PGEN=102.50 QGEN=25.42 0 # # # (89) B1 GENERATOR OUTAGE # 3 34328 0 "1" 0 # STARGT1 13.80 PGEN=60.94 QGEN=13.94 0 # # # (90) B1 GENERATOR OUTAGE # 3 34329 0 "2" 0 # STARGT2 13.80 PGEN=60.94 QGEN=13.94 0 # # # (91) B1 GENERATOR OUTAGE # 3 34330 0 "1" 0 # ELNIDO 13.80 PGEN=12.50 QGEN=4.15 0 # # # (92) B1 GENERATOR OUTAGE # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=3.80 QGEN=5.40 0 # # # (93) B1 GENERATOR OUTAGE # 3 34334 0 "1" 0 # BIO PWR 9.11 PGEN=21.80 QGEN=8.92 0

Page 36: To determine the system impacts caused by the Project

A-15 GWF Henrietta SISAppendix A

# # # (94) B1 GENERATOR OUTAGE # 3 34342 0 "1" 0 # INT.TURB 9.11 PGEN=1.10 QGEN=0.00 0 # # # (95) B1 GENERATOR OUTAGE # 3 34631 0 "1" 0 # SJ2GEN 9.11 PGEN=2.00 QGEN=0.00 0 # # # (96) B1 GENERATOR OUTAGE # 3 34633 0 "1" 0 # SJ3GEN 9.11 PGEN=1.00 QGEN=0.00 0 # # # (97) B1 GENERATOR OUTAGE # 3 34335 0 "1" 0 # Q196GT1 16.50 PGEN=192.50 QGEN=31.08 0 # # # (98) B1 GENERATOR OUTAGE # 3 34336 0 "2" 0 # Q196GT2 16.50 PGEN=192.50 QGEN=31.08 0 # # # (99) B1 GENERATOR OUTAGE # 3 34337 0 "3" 0 # Q196ST1 13.80 PGEN=68.50 QGEN=11.04 0 # # # (100) B1 GENERATOR OUTAGE # 3 34338 0 "4" 0 # Q196ST2 13.80 PGEN=68.50 QGEN=11.04 0 # # # (101) B CAPACITOR OUTAGE # 6 30765 0 "v" 0 # LOSBANOS 230.0 SVD 0 # # # (102) B CAPACITOR OUTAGE # 6 30796 0 "v" 0 # STOREY 1 230.0 SVD 0 # # # (103) B CAPACITOR OUTAGE # 6 34134 0 "v" 0 # WILSON A 115.0 SVD 0 # # # (104) B CAPACITOR OUTAGE # 6 34252 0 "v" 0 # MADERA 70.0 SVD 0 # # # (105) B CAPACITOR OUTAGE #

Page 37: To determine the system impacts caused by the Project

A-16 GWF Henrietta SISAppendix A

6 34302 0 "v" 0 # L.BANS T 13.8 SVD 0 # # # (106) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Chowchilla 115 kV Line and Exchequer 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00 2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80 2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94) 4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11) 3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (107) L-1/G-1 OVERLAPPING OUTAGE # Chowchilla - Kerckhoff #2 115 kV Line and Exchequer 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34105 34121 "1 " 0 # line from CERTANJ1 115.00 (2) to (3) SHARON T 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34121 34128 "1 " 0 # line from SHARON T 115.00 (3) to (3) OAKH_JCT 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34128 34123 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) K1-JCT 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (108) L-1/G-1 OVERLAPPING OUTAGE # Atwater - El Capitan 115 kV Line and Exchequer 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0

Page 38: To determine the system impacts caused by the Project

A-17 GWF Henrietta SISAppendix A

# # # (109) L-1/G-1 OVERLAPPING OUTAGE # Atwater - Merced 115 kV Line and Exchequer 1 34104 34108 "1 " 0 # line from ATWATER 115.00 BRKR to (3) CRESEY T 115.00 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (1) ATWATR J 115.00 1 34108 34114 "1 " 0 # line from CRESEY T 115.00 (3) to (3) JRWD GEN 115.00 1 34114 34124 "1 " 0 # line from JRWD GEN 115.00 (3) to (2) JR WOOD 115.00 2 34114 34332 "1 " 0 # TRAN from JRWD GEN 115.00 (3) to (1) JRWCOGEN 9.11 1 34124 34140 "1 " 0 # line from JR WOOD 115.00 (2) to (1) CRESSEY 115.00 4 34124 0 "1 " 0 # LOAD-DROP JR WOOD 115.00 LOAD==11.70(10.32) 4 34140 0 "1 " 0 # LOAD-DROP CRESSEY 115.00 LOAD==19.02(3.86) 3 34332 0 "1 " 0 # GEN-DROP JRWCOGEN 9.11 GEN==3.80(5.40) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (110) L-1/G-1 OVERLAPPING OUTAGE # Cressy Tap 115 kV Line and Exchequer 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (3) ATWATR J 115.00 1 34110 34130 "1 " 0 # line from ATWATR J 115.00 (3) to (2) LIVNGSTN 115.00 1 34110 34144 "1 " 0 # line from ATWATR J 115.00 (3) to BRKR MERCED 115.00 1 34130 34132 "1 " 0 # line from LIVNGSTN 115.00 (2) to (1) GALLO 115.00 4 34130 0 "3 " 0 # LOAD-DROP LIVNGSTN 115.00 LOAD==24.58(5.00) 4 34132 0 "1 " 0 # LOAD-DROP GALLO 115.00 LOAD==4.30(3.68) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (111) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Dairyland 115 kV Line and Exchequer 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (112) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Oro Loma 115 kV Line and Exchequer 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (113) L-1/G-1 OVERLAPPING OUTAGE # El Capitan - Wilson 115 kV Line and Exchequer 1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 #

Page 39: To determine the system impacts caused by the Project

A-18 GWF Henrietta SISAppendix A

3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (114) L-1/G-1 OVERLAPPING OUTAGE # Dairyland - Mendota 115 kV Line and Exchequer 1 34150 34154 "1 " 0 # line from NEWHALL 115.00 (2) to BRKR DAIRYLND 115.00 1 34150 34178 "1 " 0 # line from NEWHALL 115.00 (2) to (3) MADERAPR 115.00 1 34178 34156 "1 " 0 # line from MADERAPR 115.00 (3) to BRKR MENDOTA 115.00 2 34178 34179 "1 " 0 # TRAN from MADERAPR 115.00 (3) to (1) MADERA_G 13.80 4 34150 0 "2 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==8.55(1.73) 4 34150 0 "3 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==10.62(2.16) 4 34179 0 "ss" 0 # LOAD-DROP MADERA_G 13.80 LOAD==3.60(0.85) 3 34179 0 "1 " 0 # GEN-DROP MADERA_G 13.80 GEN==28.60(6.34) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (115) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Mendota 115 kV Line and Exchequer 1 34157 34156 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR MENDOTA 115.00 1 34157 34158 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR PANOCHE 115.00 3 34186 0 "1 " 0 # DG_PAN Unit trips for Panoche - Mendota 115 kV outage # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (116) L-1/G-1 OVERLAPPING OUTAGE # Glass - Biola - Madera 70 kV Line and Exchequer 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (117) L-1/G-1 OVERLAPPING OUTAGE # Merced Falls - Exchequer 70 kV Line and Exchequer 1 34321 34226 "1 " 0 # line from MCSWAINJ 70.00 (3) to (2) MC SWAIN 70.00 1 34321 34230 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR MRCDFLLS 70.00 1 34321 34232 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR EXCHEQUR 70.00 2 34226 34320 "1 " 0 # TRAN from MC SWAIN 70.00 (2) to (1) MCSWAIN 9.11

Page 40: To determine the system impacts caused by the Project

A-19 GWF Henrietta SISAppendix A

3 34320 0 "1 " 0 # GEN-DROP MCSWAIN 9.11 GEN==10.00(2.00) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (118) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Canal - Oro Loma 70 kV Line and Exchequer 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00 1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (119) L-1/G-1 OVERLAPPING OUTAGE # Atwater - El Capitan 115 kV Line and JR Wood Cogen 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=4.00 QGEN=5.40 0 # # # (120) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Atwater #2 115 kV Line and JR Wood Cogen 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=4.00 QGEN=5.40 0 # # # (121) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Chowchilla 115 kV Line and Kerckhoff 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00 2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80 2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94) 4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11)

Page 41: To determine the system impacts caused by the Project

A-20 GWF Henrietta SISAppendix A

3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (122) L-1/G-1 OVERLAPPING OUTAGE # Exchequer - Le Grand 115 kV Line and Kerckhoff 1 34112 34116 "1 " 0 # line from EXCHEQUR 115.00 BRKR to BRKR LE GRAND 115.00 3 34306 0 "1 " 0 # Exchequer Unit will trip for this outage 4 34228 0 "**" 0 # Mariposa Loads will drop if bus is below 64 kV, this is anticipate # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (123) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # Le Grand - Dairyland 115 kV Line and Kerckhoff 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (124) L-1/G-1 OVERLAPPING OUTAGE # Glass - Biola - Madera 70 kV Line and Kerckhoff 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (125) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Canal - Oro Loma 70 kV Line and Oneil Pump 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00 1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93)

Page 42: To determine the system impacts caused by the Project

A-21 GWF Henrietta SISAppendix A

# 3 34316 0 "1" 0 # ONEILPMP 9.11 PGEN=0.52 QGEN=0.00 0 # # # (126) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Melones Unit 1 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (127) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Melones Unit 1 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (128) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Melones Unit 1 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (129) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Melones Unit 1 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (130) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Melones Unit 1 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (131) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Melones Unit 1 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (132) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Helms Unit 1 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00

Page 43: To determine the system impacts caused by the Project

A-22 GWF Henrietta SISAppendix A

# 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (133) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Helms Unit 1 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (134) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Helms Unit 1 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (135) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Helms Unit 1 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (136) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Helms Unit 1 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (137) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Helms Unit 1 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (138) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Helms Unit 1 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (139) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Helms Unit 1 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (140) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Helms Unit 1

Page 44: To determine the system impacts caused by the Project

A-23 GWF Henrietta SISAppendix A

1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (141) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Helms Unit 1 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (142) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Helms Unit 1 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (143) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Helms Unit 1 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (144) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Helms Unit 1 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (145) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Helms Unit 1 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (146) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Helms Unit 1 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # #

Page 45: To determine the system impacts caused by the Project

A-24 GWF Henrietta SISAppendix A

# (147) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Helms Unit 1 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (148) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Helms Unit 1 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (149) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Helms Unit 1 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (150) L-1/G-1 OVERLAPPING OUTAGE # Dos Amigos - Panoche 230 kV Line and Helms Unit 1 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (151) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Exchequer 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (152) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Exchequer 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (153) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Exchequer 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (154) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Exchequer 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77

Page 46: To determine the system impacts caused by the Project

A-25 GWF Henrietta SISAppendix A

0 # # # (155) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Exchequer 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (156) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Exchequer 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (157) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Exchequer 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (158) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Exchequer 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (159) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Exchequer 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (160) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Exchequer 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (161) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Exchequer 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (162) L-1/G-1 OVERLAPPING OUTAGE

Page 47: To determine the system impacts caused by the Project

A-26 GWF Henrietta SISAppendix A

# Gates - Panoche #1 230 kV Line and Exchequer 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (163) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Exchequer 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (164) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Exchequer 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (165) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Exchequer 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (166) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Exchequer 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (167) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Exchequer 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (168) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Exchequer 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (169) L-1/G-1 OVERLAPPING OUTAGE

Page 48: To determine the system impacts caused by the Project

A-27 GWF Henrietta SISAppendix A

# Dos Amigos - Panoche 230 kV Line and Exchequer 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (170) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Kerckhoff 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (171) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Kerckhoff 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (172) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Kerckhoff 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (173) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Kerckhoff 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (174) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Kerckhoff 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (175) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Kerckhoff 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (176) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Kerckhoff 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 #

Page 49: To determine the system impacts caused by the Project

A-28 GWF Henrietta SISAppendix A

# # (177) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Kerckhoff 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (178) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Kerckhoff 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (179) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Kerckhoff 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (180) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Kerckhoff 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (181) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Kerckhoff 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (182) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Kerckhoff 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (183) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Kerckhoff 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # #

Page 50: To determine the system impacts caused by the Project

A-29 GWF Henrietta SISAppendix A

# (184) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Kerckhoff 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (185) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Kerckhoff 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (186) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Kerckhoff 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (187) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Kerckhoff 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (188) L-1/G-1 OVERLAPPING OUTAGE # Dos Amigos - Panoche 230 kV Line and Kerckhoff 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # 2013 sumpk category b contingency list # Fresno Zone 314 # # # (189) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 0 # # # (190) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line 0 # # # (191) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 51: To determine the system impacts caused by the Project

A-30 GWF Henrietta SISAppendix A

1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line 0 # # # (192) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line 0 # # # (193) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line 0 # # # (194) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (195) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 0 # # # (196) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 0 # # # (197) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 0

Page 52: To determine the system impacts caused by the Project

A-31 GWF Henrietta SISAppendix A

# # # (198) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) 0 # # # (199) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) 0 # # # (200) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30875 30874 "1 " 0 # line from MC CALL 230.00 BRKR to BRKR P0615STN 230.00 0 # # # (201) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30875 30874 "2 " 0 # line from MC CALL 230.00 BRKR to BRKR P0615STN 230.00 0 # # # (202) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 # # # (203) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 0 # # # (204) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 0 # #

Page 53: To determine the system impacts caused by the Project

A-32 GWF Henrietta SISAppendix A

# (205) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 0 # # # (206) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 0 # # # (207) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 1 34123 34128 "1 " 0 # line from K1-JCT 115.00 (2) to (3) OAKH_JCT 115.00 1 34128 34121 "1 " 0 # line from OAKH_JCT 115.00 (3) to (3) SHARON T 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34121 34105 "1 " 0 # line from SHARON T 115.00 (3) to (2) CERTANJ1 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) 0 # # # (208) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 1 34149 34148 "1 " 0 # line from CHENYT 115.00 (3) to (2) CHENY 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00 1 34148 34141 "1 " 0 # line from CHENY 115.00 (2) to (2) PAN2_TAP 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (209) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00 2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) 0 # # # (210) B2 LINE OUTAGE (BREAKER-TO-BREAKER)

Page 54: To determine the system impacts caused by the Project

A-33 GWF Henrietta SISAppendix A

# 1 34356 34358 "1 " 0 # line from KERCKHF1 115.00 BRKR to BRKR KERCKHF2 115.00 0 # # # (211) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (212) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34358 34360 "1 " 0 # line from KERCKHF2 115.00 BRKR to (3) WWARD JT 115.00 1 34360 34414 "1 " 0 # line from WWARD JT 115.00 (3) to BRKR WOODWARD 115.00 1 34360 34363 "1 " 0 # line from WWARD JT 115.00 (3) to (3) CLOVISJ1 115.00 1 34363 34362 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR CLOVIS-1 115.00 1 34363 34366 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR SANGER 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36) 4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34362 0 "**" 1 # Restore Load at Clovis 1 0 # # # (213) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34359 34361 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR AIRWAYS 115.00 1 34359 34408 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR BARTON 115.00 1 34359 34366 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR SANGER 115.00 0 # # # (214) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34364 34365 "1 " 0 # line from CLOVIS-2 115.00 BRKR to (3) CLOVISJ2 115.00 1 34365 34358 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR KERCKHF2 115.00 1 34365 34366 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR SANGER 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34364 0 "**" 1 # Restore Load at Clovis 2 0 # # # (215) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 #

Page 55: To determine the system impacts caused by the Project

A-34 GWF Henrietta SISAppendix A

# # (216) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "2 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (217) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "3 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (218) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34372 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MALAGA 115.00 0 # # # (219) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34389 "1 " 0 # line from SANGER 115.00 BRKR to (3) RAINBWTP 115.00 1 34389 34388 "1 " 0 # line from RAINBWTP 115.00 (3) to (1) RAINBW 115.00 1 34389 34394 "1 " 0 # line from RAINBWTP 115.00 (3) to (3) PIEDRA 1 115.00 1 34394 34380 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR REEDLEY 115.00 1 34394 34400 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR KNGSRVR1 115.00 4 34388 0 "1 " 0 # LOAD-DROP RAINBW 115.00 LOAD==16.20(3.29) 0 # # # (220) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34396 "1 " 0 # line from SANGER 115.00 BRKR to (2) PIEDRA 2 115.00 1 34396 34398 "1 " 0 # line from PIEDRA 2 115.00 (2) to (2) BALCH 115.00 2 34398 34624 "1 " 0 # TRAN from BALCH 115.00 (2) to (1) BALCH 1 13.20 4 34624 0 "1 " 0 # LOAD-DROP BALCH 1 13.20 LOAD==0.26(0.00) 3 34624 0 "1 " 0 # GEN-DROP BALCH 1 13.20 GEN==27.00(8.33) 0 # # # (221) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34369 34370 "1 " 0 # line from P0418 115.00 (5) to BRKR MC CALL 115.00 2 34369 34661 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT1 13.80 2 34369 34663 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT2 13.80 2 34369 34665 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT3 13.80 2 34369 34667 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT4 13.80 4 34661 0 "ss" 0 # LOAD-DROP P0418GT1 13.80 LOAD==3.00(1.66) 4 34663 0 "ss" 0 # LOAD-DROP P0418GT2 13.80 LOAD==3.00(1.66) 4 34665 0 "ss" 0 # LOAD-DROP P0418GT3 13.80 LOAD==3.00(1.66) 4 34667 0 "ss" 0 # LOAD-DROP P0418GT4 13.80 LOAD==3.00(1.66) 3 34661 0 "1 " 0 # GEN-DROP P0418GT1 13.80 GEN==78.80(13.93) 3 34663 0 "2 " 0 # GEN-DROP P0418GT2 13.80 GEN==78.80(13.93) 3 34665 0 "3 " 0 # GEN-DROP P0418GT3 13.80 GEN==78.80(13.93)

Page 56: To determine the system impacts caused by the Project

A-35 GWF Henrietta SISAppendix A

3 34667 0 "4 " 0 # GEN-DROP P0418GT4 13.80 GEN==78.80(13.93) 0 # # # (222) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 0 # # # (223) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34370 34385 "1 " 0 # line from MC CALL 115.00 BRKR to (3) KINGS J1 115.00 1 34385 34417 "1 " 0 # line from KINGS J1 115.00 (3) to (2) KINGS J2 115.00 1 34385 34425 "1 " 0 # line from KINGS J1 115.00 (3) to (3) KCOGNJCT 115.00 1 34417 34418 "1 " 0 # line from KINGS J2 115.00 (2) to BRKR KINGSBRG 115.00 1 34425 34387 "1 " 0 # line from KCOGNJCT 115.00 (3) to (1) SUNMAID 115.00 1 34425 34427 "1 " 0 # line from KCOGNJCT 115.00 (3) to (2) GRDNGLS2 115.00 1 34427 34386 "1 " 0 # line from GRDNGLS2 115.00 (2) to (2) KNGSCOGN 115.00 2 34386 34642 "1 " 0 # TRAN from KNGSCOGN 115.00 (2) to BRKR KINGSBUR 9.11 4 34387 0 "1 " 0 # LOAD-DROP SUNMAID 115.00 LOAD==3.40(3.28) 3 34642 0 "1 " 0 # GEN-DROP KINGSBUR 9.11 GEN==34.00(17.30) 0 # # # (224) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34402 34404 "1 " 0 # line from CAL AVE 115.00 BRKR to BRKR WST FRSO 115.00 0 # # # (225) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34376 "1 " 0 # line from MALAGA 115.00 BRKR to (1) PPG 115.00 4 34376 0 "1 " 0 # LOAD-DROP PPG 115.00 LOAD==6.25(3.87) 0 # # # (226) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34379 "1 " 0 # line from MALAGA 115.00 BRKR to (3) MALAGATP 115.00 1 34379 34373 "1 " 0 # line from MALAGATP 115.00 (3) to (3) SCWAXJCT 115.00 1 34379 34375 "1 " 0 # line from MALAGATP 115.00 (3) to (3) ULTPWRJ 115.00 1 34373 34371 "1 " 0 # line from SCWAXJCT 115.00 (3) to (1) SCWAX 115.00 1 34373 34374 "1 " 0 # line from SCWAXJCT 115.00 (3) to (1) RANCHRS 115.00 1 34375 34377 "1 " 0 # line from ULTPWRJ 115.00 (3) to (2) AIRPROD 115.00 2 34375 34640 "1 " 0 # TRAN from ULTPWRJ 115.00 (3) to (1) ULTR.PWR 9.11 1 34377 34370 "1 " 0 # line from AIRPROD 115.00 (2) to BRKR MC CALL 115.00 4 34371 0 "1 " 0 # LOAD-DROP SCWAX 115.00 LOAD==2.70(1.53) 4 34374 0 "1 " 0 # LOAD-DROP RANCHRS 115.00 LOAD==9.16(1.86) 4 34377 0 "1 " 0 # LOAD-DROP AIRPROD 115.00 LOAD==5.10(2.02)

Page 57: To determine the system impacts caused by the Project

A-36 GWF Henrietta SISAppendix A

3 34640 0 "1 " 0 # GEN-DROP ULTR.PWR 9.11 GEN==14.50(13.00) 0 # # # (227) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34381 "1 " 0 # line from MALAGA 115.00 BRKR to (3) KRCDP 115.00 2 34381 34671 "1 " 0 # TRAN from KRCDP 115.00 (3) to (1) KRCDPCT1 13.80 2 34381 34672 "1 " 0 # TRAN from KRCDP 115.00 (3) to (1) KRCDPCT2 13.80 4 34671 0 "ss" 0 # LOAD-DROP KRCDPCT1 13.80 LOAD==1.05(0.65) 4 34672 0 "ss" 0 # LOAD-DROP KRCDPCT2 13.80 LOAD==1.05(0.65) 3 34671 0 "1 " 0 # GEN-DROP KRCDPCT1 13.80 GEN==50.00(7.14) 3 34672 0 "1 " 0 # GEN-DROP KRCDPCT2 13.80 GEN==50.00(7.14) 0 # # # (228) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34380 34384 "1 " 0 # line from REEDLEY 115.00 BRKR to (2) GERAWAN 115.00 1 34384 34382 "1 " 0 # line from GERAWAN 115.00 (2) to BRKR WAHTOKE 115.00 0 # # # (229) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34390 34370 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR MC CALL 115.00 1 34390 34402 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR CAL AVE 115.00 4 34390 0 "1 " 0 # LOAD-DROP DANISHCM 115.00 LOAD==4.10(3.51) 0 # # # (230) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34391 34392 "1 " 0 # line from QUEBECTP 115.00 (2) to (1) QUEBEC 115.00 1 34391 34426 "1 " 0 # line from QUEBECTP 115.00 (2) to BRKR ALPAUGH 115.00 4 34392 0 "1 " 0 # LOAD-DROP QUEBEC 115.00 LOAD==11.20(7.82) 0 # # # (231) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (232) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (233) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34409 34413 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR PNEDLE 115.00 1 34409 34416 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR BULLARD 115.00 1 34409 34412 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR HERNDON 115.00

Page 58: To determine the system impacts caused by the Project

A-37 GWF Henrietta SISAppendix A

4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25) 4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 1 34411 34413 "1 " 1 # Switches in Pindale CB#12 to transfer load 4 34413 0 "**" 1 # Restore load at Pindale 0 # # # (234) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34410 34412 "1 " 0 # line from MANCHSTR 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (235) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34411 34416 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR BULLARD 115.00 1 34411 34412 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR HERNDON 115.00 0 # # # (236) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34412 34422 "1 " 0 # line from HERNDON 115.00 BRKR to (2) CHLDHOSP 115.00 1 34422 34414 "1 " 0 # line from CHLDHOSP 115.00 (2) to BRKR WOODWARD 115.00 4 34422 0 "1 " 0 # LOAD-DROP CHLDHOSP 115.00 LOAD==3.50(1.60) 0 # # # (237) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34420 "1 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (238) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34420 "2 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (239) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34423 "1 " 0 # line from KINGSBRG 115.00 BRKR to (3) GAURD J1 115.00 1 34423 34370 "1 " 0 # line from GAURD J1 115.00 (3) to BRKR MC CALL 115.00 1 34423 34421 "1 " 0 # line from GAURD J1 115.00 (3) to (2) GAURD J2 115.00 1 34421 34424 "1 " 0 # line from GAURD J2 115.00 (2) to (1) GRDN GLS 115.00 4 34424 0 "1 " 0 # LOAD-DROP GRDN GLS 115.00 LOAD==3.50(1.15) 4 34418 0 "3 " 0 # Kingsburg Bank #3 will also be dropped on this outage 0 # # # (240) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34428 "1 " 0 # line from KINGSBRG 115.00 BRKR to (2) CONTADNA 115.00 1 34428 34429 "1 " 0 # line from CONTADNA 115.00 (2) to (4) GWF_HEP 115.00 1 34429 34521 "1 " 0 # line from GWF_HEP 115.00 (4) to (2) LEPRNOFD 115.00

Page 59: To determine the system impacts caused by the Project

A-38 GWF Henrietta SISAppendix A

2 34429 34431 "1 " 0 # TRAN from GWF_HEP 115.00 (4) to (1) GWF_HEP1 13.80 2 34429 34433 "1 " 0 # TRAN from GWF_HEP 115.00 (4) to (1) GWF_HEP2 13.80 1 34521 34430 "1 " 0 # line from LEPRNOFD 115.00 (2) to BRKR HENRETTA 115.00 4 34428 0 "1 " 0 # LOAD-DROP CONTADNA 115.00 LOAD==7.60(5.70) 4 34429 0 "ss" 0 # LOAD-DROP GWF_HEP 115.00 LOAD==3.00(0.68) 4 34521 0 "1 " 0 # LOAD-DROP LEPRNOFD 115.00 LOAD==6.65(4.30) 3 34431 0 "1 " 0 # GEN-DROP GWF_HEP1 13.80 GEN==50.00(21.27) 3 34433 0 "1 " 0 # GEN-DROP GWF_HEP2 13.80 GEN==50.00(21.27) 0 # # # (241) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34426 34700 "1 " 0 # line from ALPAUGH 115.00 BRKR to BRKR SMYRNA 115.00 0 # # # (242) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34452 34260 "1 " 0 # line from WISHON 70.00 BRKR to (3) SJNO2 70.00 1 34260 34259 "1 " 0 # line from SJNO2 70.00 (3) to (3) NRTHFORK 70.00 2 34260 34631 "1 " 0 # TRAN from SJNO2 70.00 (3) to (1) SJ2GEN 9.11 1 34259 34261 "1 " 0 # line from NRTHFORK 70.00 (3) to (2) SJNO3 70.00 2 34259 34340 "1 " 0 # TRAN from NRTHFORK 70.00 (3) to (1) N.FORK E 9.11 2 34261 34633 "1 " 0 # TRAN from SJNO3 70.00 (2) to (1) SJ3GEN 9.11 4 34260 0 "2 " 0 # LOAD-DROP SJNO2 70.00 LOAD==3.22(0.66) 4 34261 0 "2 " 0 # LOAD-DROP SJNO3 70.00 LOAD==6.95(1.41) 4 34340 0 "1 " 0 # LOAD-DROP N.FORK E 9.11 LOAD==1.21(0.25) 3 34631 0 "1 " 0 # GEN-DROP SJ2GEN 9.11 GEN==2.00(0.00) 3 34633 0 "1 " 0 # GEN-DROP SJ3GEN 9.11 GEN==1.00(0.00) 0 # # # (243) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34452 34491 "1 " 0 # line from WISHON 70.00 BRKR to (3) AUBRYTP 70.00 1 34491 34464 "1 " 0 # line from AUBRYTP 70.00 (3) to BRKR COPPRMNE 70.00 1 34491 34493 "1 " 0 # line from AUBRYTP 70.00 (3) to (1) AUBERRY 70.00 4 34493 0 "1 " 0 # LOAD-DROP AUBERRY 70.00 LOAD==6.07(1.23) 4 34493 0 "2 " 0 # LOAD-DROP AUBERRY 70.00 LOAD==7.15(1.45) 0 # # # (244) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34456 34458 "1 " 0 # line from HRDWK TP 70.00 (3) to (1) HARDWICK 70.00 1 34456 34522 "1 " 0 # line from HRDWK TP 70.00 (3) to (1) HNFRD SW 70.00 1 34456 34576 "1 " 0 # line from HRDWK TP 70.00 (3) to BRKR KNGLOBUS 70.00 4 34458 0 "1 " 0 # LOAD-DROP HARDWICK 70.00 LOAD==12.86(2.61) 0 # # # (245) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 60: To determine the system impacts caused by the Project

A-39 GWF Henrietta SISAppendix A

1 34460 34462 "1 " 0 # line from GUERNSEY 70.00 BRKR to (3) GUR3TPT 70.00 1 34462 34542 "1 " 0 # line from GUR3TPT 70.00 (3) to (2) JCBSCRNR 70.00 1 34462 34554 "1 " 0 # line from GUR3TPT 70.00 (3) to BRKR AMSTG SW 70.00 1 34542 34540 "1 " 0 # line from JCBSCRNR 70.00 (2) to BRKR HENRITTA 70.00 4 34460 0 "1 " 0 # LOAD-DROP GUERNSEY 70.00 LOAD==10.51(2.13) 4 34542 0 "1 " 0 # LOAD-DROP JCBSCRNR 70.00 LOAD==12.05(2.45) 4 34542 0 "2 " 0 # LOAD-DROP JCBSCRNR 70.00 LOAD==9.54(1.94) 0 # # # (246) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34464 34478 "1 " 0 # line from COPPRMNE 70.00 BRKR to BRKR TVY VLLY 70.00 0 # # # (247) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34464 34638 "1 " 0 # line from COPPRMNE 70.00 BRKR to (2) FRANTDM 70.00 2 34638 34636 "1 " 0 # TRAN from FRANTDM 70.00 (2) to (1) FRIANTDM 6.60 3 34636 0 "2 " 0 # GEN-DROP FRIANTDM 6.60 GEN==14.70(5.86) 3 34636 0 "3 " 0 # GEN-DROP FRIANTDM 6.60 GEN==7.80(3.11) 3 34636 0 "4 " 0 # GEN-DROP FRIANTDM 6.60 GEN==2.30(0.92) 0 # # # (248) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34466 34482 "1 " 0 # line from BIOLA 70.00 BRKR to BRKR OLDKERN 70.00 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 0 # # # (249) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34468 34482 "1 " 0 # line from BOWLES 70.00 (1) to BRKR OLDKERN 70.00 4 34468 0 "1 " 0 # LOAD-DROP BOWLES 70.00 LOAD==18.29(3.72) 0 # # # (250) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34469 34271 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) WSTLDJCT 70.00 1 34469 34470 "1 " 0 # line from GFFNJCT 70.00 (3) to (1) GIFFEN 70.00 1 34469 34471 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) SNJQJCT 70.00 1 34271 34172 "1 " 0 # line from WSTLDJCT 70.00 (3) to (2) WESTLAND 70.00 1 34271 34269 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) BIOMSJCT 70.00 1 34471 34472 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR SAN JOQN 70.00 1 34471 34474 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR HELM 70.00 1 34172 34170 "1 " 0 # line from WESTLAND 70.00 (2) to (1) WESIX 70.00 1 34269 34268 "1 " 0 # line from BIOMSJCT 70.00 (3) to BRKR MENDOTA 70.00

Page 61: To determine the system impacts caused by the Project

A-40 GWF Henrietta SISAppendix A

1 34269 34270 "1 " 0 # line from BIOMSJCT 70.00 (3) to (2) BIOMASS 70.00 2 34270 34334 "1 " 0 # TRAN from BIOMASS 70.00 (2) to (1) BIO PWR 9.11 4 34470 0 "1 " 0 # LOAD-DROP GIFFEN 70.00 LOAD==9.59(1.95) 4 34172 0 "1 " 0 # LOAD-DROP WESTLAND 70.00 LOAD==3.20(0.76) 4 34170 0 "1 " 0 # LOAD-DROP WESIX 70.00 LOAD==1.60(0.38) 3 34334 0 "1 " 0 # GEN-DROP BIO PWR 9.11 GEN==21.80(10.99) 1 34472 34473 "1 " 1 # Switches in San Joaquin CB22 to transfer load 4 34472 0 "**" 1 # Restore Load at San Joaquin 0 # # # (251) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34473 34472 "1 " 0 # line from SNJQTP 70.00 (2) to BRKR SAN JOQN 70.00 1 34473 34475 "1 " 0 # line from SNJQTP 70.00 (2) to (3) AGRCJCT 70.00 1 34475 34476 "1 " 0 # line from AGRCJCT 70.00 (3) to (2) AGRICO 70.00 1 34475 34484 "1 " 0 # line from AGRCJCT 70.00 (3) to BRKR KERMAN 70.00 2 34476 34608 "1 " 0 # TRAN from AGRICO 70.00 (2) to (1) AGRICO 13.80 4 34484 0 "1 " 0 # LOAD-DROP KERMAN 70.00 LOAD==19.44(3.95) 4 34484 0 "2 " 0 # LOAD-DROP KERMAN 70.00 LOAD==11.78(2.39) 3 34608 0 "2 " 0 # GEN-DROP AGRICO 13.80 GEN==7.00(1.08) 3 34608 0 "3 " 0 # GEN-DROP AGRICO 13.80 GEN==18.10(2.80) 3 34608 0 "4 " 0 # GEN-DROP AGRICO 13.80 GEN==26.00(4.02) 0 # # # (252) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34474 34556 "1 " 0 # line from HELM 70.00 BRKR to BRKR STRD JCT 70.00 0 # # # (253) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34478 34492 "1 " 0 # line from TVY VLLY 70.00 BRKR to BRKR REEDLEY 70.00 0 # # # (254) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34480 34481 "1 " 0 # line from KEARNEY 70.00 BRKR to (3) FRWWTAP 70.00 1 34481 34483 "1 " 0 # line from FRWWTAP 70.00 (3) to (3) FRESNOWW 70.00 1 34481 34483 "2 " 0 # line from FRWWTAP 70.00 (3) to (3) FRESNOWW 70.00 2 34483 34485 "1 " 0 # TRAN from FRESNOWW 70.00 (3) to (1) FRESNOWW 12.47 4 34485 0 "1 " 0 # LOAD-DROP FRESNOWW 12.47 LOAD==7.91(0.00) 3 34485 0 "1 " 0 # GEN-DROP FRESNOWW 12.47 GEN==9.00(0.00) 0 # # # (255) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34480 34482 "1 " 0 # line from KEARNEY 70.00 BRKR to (3) OLDKERN 70.00 1 34482 34466 "1 " 0 # line from OLDKERN 70.00 BRKR to BRKR BIOLA 70.00 1 34482 34468 "1 " 0 # line from OLDKERN 70.00 BRKR to (1) BOWLES 70.00

Page 62: To determine the system impacts caused by the Project

A-41 GWF Henrietta SISAppendix A

4 34482 0 "1 " 0 # LOAD-DROP OLDKERN 70.00 LOAD==18.75(3.81) 4 34482 0 "3 " 0 # LOAD-DROP OLDKERN 70.00 LOAD==7.57(1.54) 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 4 34468 0 "1 " 0 # LOAD-DROP BOWLES 70.00 LOAD==18.29(3.72) 0 # # # (256) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34480 34512 "1 " 0 # line from KEARNEY 70.00 BRKR to BRKR CARUTHRS 70.00 4 34512 0 "1 " 0 # LOAD-DROP CARUTHRS 70.00 LOAD==19.63(3.98) 0 # # # (257) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34487 34489 "1 " 0 # line from SNGRJCT 70.00 (3) to (2) SNGRCOGN 70.00 1 34487 34490 "1 " 0 # line from SNGRJCT 70.00 (3) to (2) PARLIER 70.00 1 34487 34488 "1 " 0 # line from SNGRJCT 70.00 (3) to BRKR SANGER 70.00 2 34489 34646 "1 " 0 # TRAN from SNGRCOGN 70.00 (2) to (1) SANGERCO 9.11 1 34490 34492 "1 " 0 # line from PARLIER 70.00 (2) to BRKR REEDLEY 70.00 4 34490 0 "1 " 0 # LOAD-DROP PARLIER 70.00 LOAD==20.24(4.11) 3 34646 0 "1 " 0 # GEN-DROP SANGERCO 9.11 GEN==37.50(1.40) 0 # # # (258) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34488 34366 "1 " 0 # line from SANGER 70.00 BRKR to BRKR SANGER 115.00 0 # # # (259) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34492 34497 "1 " 0 # line from REEDLEY 70.00 BRKR to (3) DNUBAJCT 70.00 1 34497 34499 "1 " 0 # line from DNUBAJCT 70.00 (3) to (2) DNUBAEGY 70.00 1 34497 34500 "1 " 0 # line from DNUBAJCT 70.00 (3) to BRKR DINUBA 70.00 2 34499 34648 "1 " 0 # TRAN from DNUBAEGY 70.00 (2) to (1) DINUBA E 13.80 4 34648 0 "ss" 0 # LOAD-DROP DINUBA E 13.80 LOAD==0.30(0.26) 3 34648 0 "1 " 0 # GEN-DROP DINUBA E 13.80 GEN==12.00(7.00) 0 # # # (260) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34492 34526 "1 " 0 # line from REEDLEY 70.00 BRKR to (3) ORSI JCT 70.00 1 34526 34495 "1 " 0 # line from ORSI JCT 70.00 (3) to (2) SANDCRK 70.00 1 34526 34502 "1 " 0 # line from ORSI JCT 70.00 (3) to BRKR OROSI 70.00 1 34495 34494 "1 " 0 # line from SANDCRK 70.00 (2) to (1) DUNLAP 70.00 4 34495 0 "1 " 0 # LOAD-DROP SANDCRK 70.00 LOAD==3.14(0.64) 4 34494 0 "1 " 0 # LOAD-DROP DUNLAP 70.00 LOAD==4.46(0.91) 0 # # # (261) B2 LINE OUTAGE (BREAKER-TO-BREAKER)

Page 63: To determine the system impacts caused by the Project

A-42 GWF Henrietta SISAppendix A

# 1 34496 34498 "1 " 0 # line from STCRRL J 70.00 (3) to (1) STONCRRL 70.00 1 34496 34500 "1 " 0 # line from STCRRL J 70.00 (3) to BRKR DINUBA 70.00 1 34496 34502 "1 " 0 # line from STCRRL J 70.00 (3) to (2) OROSI 70.00 1 34502 34526 "1 " 0 # line from OROSI 70.00 BRKR to (1) ORSI JCT 70.00 4 34498 0 "2 " 0 # LOAD-DROP STONCRRL 70.00 LOAD==3.37(0.68) 4 34498 0 "3 " 0 # LOAD-DROP STONCRRL 70.00 LOAD==2.68(0.54) 4 34502 0 "1 " 0 # LOAD-DROP OROSI 70.00 LOAD==8.38(1.70) 4 34502 0 "2 " 0 # LOAD-DROP OROSI 70.00 LOAD==7.43(1.51) 0 # # # (262) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34508 34510 "1 " 0 # line from CAMDEN 70.00 (2) to (1) CMDN JCT 70.00 1 34508 34576 "1 " 0 # line from CAMDEN 70.00 (2) to BRKR KNGLOBUS 70.00 4 34508 0 "1 " 0 # LOAD-DROP CAMDEN 70.00 LOAD==6.87(1.40) 4 34508 0 "2 " 0 # LOAD-DROP CAMDEN 70.00 LOAD==10.90(2.22) 0 # # # (263) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34514 34540 "1 " 0 # line from MUSLSLGH 70.00 (1) to BRKR HENRITTA 70.00 4 34514 0 "1 " 0 # LOAD-DROP MUSLSLGH 70.00 LOAD==22.00(13.60) 0 # # # (264) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) 0 # # # (265) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34528 34530 "1 " 0 # line from CORCORAN 70.00 BRKR to (3) BSWLL TP 70.00 1 34530 34531 "1 " 0 # line from BSWLL TP 70.00 (3) to (2) JGBSWLL 70.00 1 34530 34538 "1 " 0 # line from BSWLL TP 70.00 (3) to (1) BOSWELL 70.00 1 34531 34536 "1 " 0 # line from JGBSWLL 70.00 (2) to (1) ANGIOLA 70.00 4 34538 0 "1 " 0 # LOAD-DROP BOSWELL 70.00 LOAD==2.37(1.53) 4 34536 0 "1 " 0 # LOAD-DROP ANGIOLA 70.00 LOAD==7.24(1.47) 0 # # # (266) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34532 34554 "1 " 0 # line from ARMSTRNG 70.00 (1) to (4) AMSTG SW 70.00

Page 64: To determine the system impacts caused by the Project

A-43 GWF Henrietta SISAppendix A

1 34554 34462 "1 " 0 # line from AMSTG SW 70.00 BRKR to (1) GUR3TPT 70.00 1 34554 34534 "1 " 0 # line from AMSTG SW 70.00 (4) to (1) RESERVE 70.00 2 34554 34650 "1 " 0 # TRAN from AMSTG SW 70.00 BRKR to (1) GWF-PWR. 13.80 4 34534 0 "1 " 0 # LOAD-DROP RESERVE 70.00 LOAD==2.03(0.41) 3 34650 0 "1 " 0 # GEN-DROP GWF-PWR. 13.80 GEN==23.00(12.00) 0 # # # (267) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34537 34540 "1 " 0 # line from GWF_HENR 70.00 (5) to BRKR HENRITTA 70.00 2 34537 34539 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) GWF_GT1 13.80 2 34537 34541 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) GWF_GT2 13.80 2 34537 34691 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) Q272_ST1 13.80 2 34537 34692 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) Q272SLST 13.80 4 34539 0 "ss" 0 # LOAD-DROP GWF_GT1 13.80 LOAD==1.10(0.25) 4 34541 0 "ss" 0 # LOAD-DROP GWF_GT2 13.80 LOAD==1.10(0.25) 4 34691 0 "ss" 0 # LOAD-DROP Q272_ST1 13.80 LOAD==2.00(1.11) 4 34692 0 "ss" 0 # LOAD-DROP Q272SLST 13.80 LOAD==14.00(7.75) 3 34539 0 "1 " 0 # GEN-DROP GWF_GT1 13.80 GEN==50.00(4.51) 3 34541 0 "1 " 0 # GEN-DROP GWF_GT2 13.80 GEN==50.00(4.51) 3 34691 0 "1 " 0 # GEN-DROP Q272_ST1 13.80 GEN==27.00(1.87) 3 34692 0 "1 " 0 # GEN-DROP Q272SLST 13.80 GEN==139.00(35.74) 0 # # # (268) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34544 34550 "1 " 0 # line from TLRE LKE 70.00 BRKR to (2) CHEVPLIN 70.00 1 34550 34546 "1 " 0 # line from CHEVPLIN 70.00 (2) to (2) AVENAL 70.00 1 34546 34548 "1 " 0 # line from AVENAL 70.00 (2) to BRKR KETTLEMN 70.00 4 34544 0 "1 " 0 # LOAD-DROP TLRE LKE 70.00 LOAD==6.79(1.38) 4 34550 0 "1 " 0 # LOAD-DROP CHEVPLIN 70.00 LOAD==1.01(0.73) 4 34546 0 "1 " 0 # LOAD-DROP AVENAL 70.00 LOAD==7.72(1.57) 0 # # # (269) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34548 34552 "1 " 0 # line from KETTLEMN 70.00 (2) to BRKR GATES 70.00 1 34548 34546 "1 " 0 # line from KETTLEMN 70.00 BRKR to (1) AVENAL 70.00 4 34548 0 "1 " 0 # LOAD-DROP KETTLEMN 70.00 LOAD==6.32(1.29) 0 # # # (270) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34558 "1 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0 # # # (271) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34558 "2 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0

Page 65: To determine the system impacts caused by the Project

A-44 GWF Henrietta SISAppendix A

# # # (272) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.45(2.99) 0 # # # (273) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34556 34562 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR SCHLNDLR 70.00 0 # # # (274) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34556 34564 "1 " 0 # line from STRD JCT 70.00 (3) to BRKR STROUD 70.00 1 34556 34474 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR HELM 70.00 1 34556 34562 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR SCHLNDLR 70.00 4 34564 0 "1 " 0 # LOAD-DROP STROUD 70.00 LOAD==13.09(2.66) 0 # # # (275) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34558 34560 "1 " 0 # line from HURON 70.00 BRKR to (2) CALFLAX 70.00 1 34560 34562 "1 " 0 # line from CALFLAX 70.00 (2) to BRKR SCHLNDLR 70.00 4 34560 0 "1 " 0 # LOAD-DROP CALFLAX 70.00 LOAD==6.53(1.33) 1 34552 34558 "2 " 0 # Must include Gates - Huron #2 in this outage 0 # # # (276) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34562 34566 "1 " 0 # line from SCHLNDLR 70.00 BRKR to (2) PLSNTVLY 70.00 1 34566 34570 "1 " 0 # line from PLSNTVLY 70.00 (2) to BRKR COLNGA 2 70.00 4 34566 0 "1 " 0 # LOAD-DROP PLSNTVLY 70.00 LOAD==10.00(2.51) 0 # # # (277) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34570 34572 "1 " 0 # line from COLNGA 2 70.00 BRKR to (3) TORNADO 70.00 1 34572 34574 "1 " 0 # line from TORNADO 70.00 (3) to BRKR COLNGA 1 70.00 2 34572 34654 "1 " 0 # TRAN from TORNADO 70.00 (3) to (1) COLNGAGN 9.11 4 34572 0 "1 " 0 # LOAD-DROP TORNADO 70.00 LOAD==1.74(1.44) 3 34654 0 "1 " 0 # GEN-DROP COLNGAGN 9.11 GEN==34.00(5.40) 2 34570 34652 "1 " 0 # Must include Colinga2 - Chv.coal in this outage - modeled on bus, 3 34652 0 "**" 0 # Drops units on Derrick Sub 4 34652 0 "**" 0 # Drops load at Derrick Sub 0 # # # (278) B2 LINE OUTAGE (BREAKER-TO-BREAKER)

Page 66: To determine the system impacts caused by the Project

A-45 GWF Henrietta SISAppendix A

# 1 36354 34574 "1 " 0 # line from SAN MIGL 70.00 BRKR to BRKR COLNGA 1 70.00 0 # # # (279) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30835 (30882) 34412 34630 : 2 30835 34412 "1 " 0 # TRAN from HERNDON 230.00 BRKR to (1) HERNDON 115.00 0 # # # (280) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30835 (30883) 34412 34632 : 2 30835 34412 "2 " 0 # TRAN from HERNDON 230.00 BRKR to (1) HERNDON 115.00 0 # # # (281) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30876) 34370 34618 : 2 30875 34370 "1 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # # # (282) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30877) 34370 34620 : 2 30875 34370 "2 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # # # (283) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30878) 34370 34621 : 2 30875 34370 "3 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # # # (284) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 30881 34430 "3 " 0 # TRAN from HENRIETA 230.00 BRKR to BRKR HENRETTA 115.00 0 # # # (285) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30900 (34607) 30055 34606 : 2 30900 30055 "11" 0 # TRAN from GATES 230.00 BRKR to (1) GATES 500.00 0 # # # (286) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 30900 30901 "1 " 0 # TRAN from GATES 230.00 BRKR to (3) GATES 1M 230.00 2 30901 34378 "1 " 0 # TRAN from GATES 1M 230.00 (3) to BRKR GATES 115.00 2 30901 34622 "1 " 0 # TRAN from GATES 1M 230.00 (3) to (1) GATES 1T 13.20 4 34378 0 "3 " 0 # Drop Gates Bank #3

Page 67: To determine the system impacts caused by the Project

A-46 GWF Henrietta SISAppendix A

0 # # # (287) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34356 34344 "1 " 0 # TRAN from KERCKHF1 115.00 BRKR to (1) KERCKHOF 6.60 4 34344 0 "4 " 0 # LOAD-DROP KERCKHOF 6.60 LOAD==3.24(0.66) 3 34344 0 "2 " 0 # GEN-DROP KERCKHOF 6.60 GEN==6.80(-4.00) 0 # # # (288) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34366 34590 "1 " 0 # TRAN from SANGER 115.00 BRKR to (2) SANGR3T 115.00 2 34590 34488 "1 " 0 # TRAN from SANGR3T 115.00 (2) to BRKR SANGER 70.00 4 34590 0 "3 " 0 # LOAD-DROP SANGR3T 115.00 LOAD==20.55(4.17) 0 # # # (289) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34418 34576 "2 " 0 # TRAN from KINGSBRG 115.00 BRKR to BRKR KNGLOBUS 70.00 0 # # # (290) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34474 30873 "1 " 0 # TRAN from HELM 70.00 BRKR to BRKR HELM 230.00 0 # # # (291) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34480 30830 "2 " 0 # TRAN from KEARNEY 70.00 BRKR to BRKR KEARNEY 230.00 0 # # # (292) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34492 34380 "1 " 0 # TRAN from REEDLEY 70.00 BRKR to BRKR REEDLEY 115.00 0 # # # (293) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34492 34380 "2 " 0 # TRAN from REEDLEY 70.00 BRKR to BRKR REEDLEY 115.00 0 # # # (294) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34528 34420 "2 " 0 # TRAN from CORCORAN 70.00 BRKR to BRKR CORCORAN 115.00 1 34420 34391 "1 " 0 # Must include Corcoran - Quebec (Corcoran CB 142) in this outage 1 34420 34418 "2 " 0 # Must include Corcoran - Kingburg (Corcoran CB 162) in this outage 1 34528 34460 "1 " 0 # Must include Corcorna - Guernsey (Corcoran CB 42) in this outage 0 # #

Page 68: To determine the system impacts caused by the Project

A-47 GWF Henrietta SISAppendix A

# (295) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34540 30881 "2 " 0 # TRAN from HENRITTA 70.00 BRKR to BRKR HENRIETA 230.00 0 # # # (296) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34540 30881 "4 " 0 # TRAN from HENRITTA 70.00 BRKR to BRKR HENRIETA 230.00 0 # # # (297) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34552 34378 "2 " 0 # TRAN from GATES 70.00 BRKR to BRKR GATES 115.00 0 # # # (298) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34562 34354 "1 " 0 # TRAN from SCHLNDLR 70.00 BRKR to (3) SCHINDLR 115.00 1 34354 34149 "1 " 0 # line from SCHINDLR 115.00 BRKR to (1) CHENYT 115.00 1 34354 34432 "1 " 0 # line from SCHINDLR 115.00 BRKR to (1) WESTLNDS 115.00 4 34354 0 "1 " 0 # LOAD-DROP SCHINDLR 115.00 LOAD==11.22(2.28) 0 # # # (299) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34652 34570 "1 " 0 # TRAN from CHV.COAL 9.11 (1) to BRKR COLNGA 2 70.00 4 34652 0 "S1" 0 # LOAD-DROP CHV.COAL 9.11 LOAD==5.12(2.48) 4 34652 0 "SG" 0 # LOAD-DROP CHV.COAL 9.11 LOAD==0.94(0.46) 3 34652 0 "1 " 0 # GEN-DROP CHV.COAL 9.11 GEN==2.50(8.30) 3 34652 0 "2 " 0 # GEN-DROP CHV.COAL 9.11 GEN==8.00(4.00) 0 # # # (300) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34658 34452 "1 " 0 # TRAN from WISHON 2.30 (1) to BRKR WISHON 70.00 3 34658 0 "3 " 0 # GEN-DROP WISHON 2.30 GEN==4.50(1.00) 3 34658 0 "4 " 0 # GEN-DROP WISHON 2.30 GEN==4.50(1.00) 0 # # # (301) B1 GENERATOR OUTAGE # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (302) B1 GENERATOR OUTAGE # 3 34344 0 "2" 0 # KERCKHOF 6.60 PGEN=6.80 QGEN=-4.00 0 # # # (303) B1 GENERATOR OUTAGE # 3 34431 0 "1" 0 # GWF_HEP1 13.80 PGEN=50.00 QGEN=21.57 0 #

Page 69: To determine the system impacts caused by the Project

A-48 GWF Henrietta SISAppendix A

# # (304) B1 GENERATOR OUTAGE # 3 34433 0 "1" 0 # GWF_HEP2 13.80 PGEN=50.00 QGEN=21.57 0 # # # (305) B1 GENERATOR OUTAGE # 3 34485 0 "1" 0 # FRESNOWW 12.47 PGEN=9.00 QGEN=0.00 0 # # # (306) B1 GENERATOR OUTAGE # 3 34539 0 "1" 0 # GWF_GT1 13.80 PGEN=50.00 QGEN=1.23 0 # # # (307) B1 GENERATOR OUTAGE # 3 34541 0 "1" 0 # GWF_GT2 13.80 PGEN=50.00 QGEN=1.23 0 # # # (308) B1 GENERATOR OUTAGE # 3 34553 0 "1" 0 # WHD_GAT2 13.80 PGEN=49.00 QGEN=-25.30 0 # # # (309) B1 GENERATOR OUTAGE # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (310) B1 GENERATOR OUTAGE # 3 34602 0 "1" 0 # HELMS 2 18.00 PGEN=404.00 QGEN=66.06 0 # # # (311) B1 GENERATOR OUTAGE # 3 34604 0 "1" 0 # HELMS 3 18.00 PGEN=404.00 QGEN=66.12 0 # # # (312) B1 GENERATOR OUTAGE # 3 34608 0 "2" 0 # AGRICO 13.80 PGEN=7.00 QGEN=1.64 0 # # # (313) B1 GENERATOR OUTAGE # 3 34608 0 "3" 0 # AGRICO 13.80 PGEN=18.10 QGEN=4.24 0 # # # (314) B1 GENERATOR OUTAGE # 3 34608 0 "4" 0 # AGRICO 13.80 PGEN=26.00 QGEN=6.09 0 # # # (315) B1 GENERATOR OUTAGE # 3 34610 0 "1" 0 # HAAS 13.80 PGEN=70.00 QGEN=18.75

Page 70: To determine the system impacts caused by the Project

A-49 GWF Henrietta SISAppendix A

0 # # # (316) B1 GENERATOR OUTAGE # 3 34610 0 "2" 0 # HAAS 13.80 PGEN=70.00 QGEN=18.75 0 # # # (317) B1 GENERATOR OUTAGE # 3 34612 0 "1" 0 # BLCH 2-2 13.80 PGEN=50.00 QGEN=9.61 0 # # # (318) B1 GENERATOR OUTAGE # 3 34614 0 "1" 0 # BLCH 2-3 13.80 PGEN=50.00 QGEN=13.00 0 # # # (319) B1 GENERATOR OUTAGE # 3 34616 0 "1" 0 # KINGSRIV 13.80 PGEN=47.00 QGEN=9.00 0 # # # (320) B1 GENERATOR OUTAGE # 3 34618 0 "1" 0 # MCCALL1T 13.20 PGEN=0.00 QGEN=36.40 0 # # # (321) B1 GENERATOR OUTAGE # 3 34621 0 "1" 0 # MCCALL3T 13.20 PGEN=0.00 QGEN=4.85 0 # # # (322) B1 GENERATOR OUTAGE # 3 34624 0 "1" 0 # BALCH 1 13.20 PGEN=27.00 QGEN=10.00 0 # # # (323) B1 GENERATOR OUTAGE # 3 34630 0 "1" 0 # HERNDN1T 13.20 PGEN=0.00 QGEN=20.26 0 # # # (324) B1 GENERATOR OUTAGE # 3 34632 0 "1" 0 # HERNDN2T 13.20 PGEN=0.00 QGEN=32.58 0 # # # (325) B1 GENERATOR OUTAGE # 3 34636 0 "2" 0 # FRIANTDM 6.60 PGEN=14.70 QGEN=6.14 0 # # # (326) B1 GENERATOR OUTAGE # 3 34636 0 "3" 0 # FRIANTDM 6.60 PGEN=7.80 QGEN=3.26 0 # # # (327) B1 GENERATOR OUTAGE

Page 71: To determine the system impacts caused by the Project

A-50 GWF Henrietta SISAppendix A

# 3 34636 0 "4" 0 # FRIANTDM 6.60 PGEN=2.30 QGEN=0.96 0 # # # (328) B1 GENERATOR OUTAGE # 3 34640 0 "1" 0 # ULTR.PWR 9.11 PGEN=14.50 QGEN=13.00 0 # # # (329) B1 GENERATOR OUTAGE # 3 34642 0 "1" 0 # KINGSBUR 9.11 PGEN=34.00 QGEN=17.30 0 # # # (330) B1 GENERATOR OUTAGE # 3 34646 0 "1" 0 # SANGERCO 9.11 PGEN=37.50 QGEN=4.31 0 # # # (331) B1 GENERATOR OUTAGE # 3 34648 0 "1" 0 # DINUBA E 13.80 PGEN=12.00 QGEN=7.00 0 # # # (332) B1 GENERATOR OUTAGE # 3 34650 0 "1" 0 # GWF-PWR. 13.80 PGEN=23.00 QGEN=12.00 0 # # # (333) B1 GENERATOR OUTAGE # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=2.50 QGEN=8.30 0 # # # (334) B1 GENERATOR OUTAGE # 3 34652 0 "2" 0 # CHV.COAL 9.11 PGEN=8.00 QGEN=4.00 0 # # # (335) B1 GENERATOR OUTAGE # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.00 QGEN=-3.48 0 # # # (336) B1 GENERATOR OUTAGE # 3 34658 0 "3" 0 # WISHON 2.30 PGEN=4.50 QGEN=1.00 0 # # # (337) B1 GENERATOR OUTAGE # 3 34658 0 "4" 0 # WISHON 2.30 PGEN=4.50 QGEN=1.00 0 # # # (338) B1 GENERATOR OUTAGE # 3 34671 0 "1" 0 # KRCDPCT1 13.80 PGEN=50.00 QGEN=10.75 0 #

Page 72: To determine the system impacts caused by the Project

A-51 GWF Henrietta SISAppendix A

# # (339) B1 GENERATOR OUTAGE # 3 34672 0 "1" 0 # KRCDPCT2 13.80 PGEN=50.00 QGEN=10.75 0 # # # (340) B1 GENERATOR OUTAGE # 3 38720 0 "1" 0 # PINE FLT 13.80 PGEN=57.00 QGEN=23.30 0 # # # (341) B1 GENERATOR OUTAGE # 3 34661 0 "1" 0 # P0418GT1 13.80 PGEN=78.80 QGEN=13.93 0 # # # (342) B1 GENERATOR OUTAGE # 3 34663 0 "2" 0 # P0418GT2 13.80 PGEN=78.80 QGEN=13.93 0 # # # (343) B1 GENERATOR OUTAGE # 3 34665 0 "3" 0 # P0418GT3 13.80 PGEN=78.80 QGEN=13.93 0 # # # (344) B1 GENERATOR OUTAGE # 3 34667 0 "4" 0 # P0418GT4 13.80 PGEN=78.80 QGEN=13.93 0 # # # (345) B1 GENERATOR OUTAGE # 3 34685 0 "1" 0 # P0615CT1 16.50 PGEN=192.00 QGEN=35.45 0 # # # (346) B1 GENERATOR OUTAGE # 3 34686 0 "1" 0 # P0615CT2 16.50 PGEN=192.00 QGEN=35.45 0 # # # (347) B1 GENERATOR OUTAGE # 3 34687 0 "1" 0 # P0615STG 16.50 PGEN=193.00 QGEN=35.57 0 # # # (348) B1 GENERATOR OUTAGE # 3 34688 0 "1" 0 # Q254CTG1 18.00 PGEN=172.40 QGEN=41.25 0 # # # (349) B1 GENERATOR OUTAGE # 3 34689 0 "2" 0 # Q254CTG2 18.00 PGEN=172.40 QGEN=41.25 0 # # # (350) B1 GENERATOR OUTAGE # 3 34690 0 "3" 0 # Q254STG1 18.00 PGEN=290.80 QGEN=67.53

Page 73: To determine the system impacts caused by the Project

A-52 GWF Henrietta SISAppendix A

0 # # # (351) B1 GENERATOR OUTAGE # 3 34691 0 "1" 0 # Q272_ST1 13.80 PGEN=27.00 QGEN=1.87 0 # # # (352) B1 GENERATOR OUTAGE # 3 34692 0 "1" 0 # Q272SLST 13.80 PGEN=139.00 QGEN=35.74 0 # # # (353) L-1/G-1 OVERLAPPING OUTAGE # Smyrna - Semitropic - Midway 115 kV Line and Exchequer 1 34700 34708 "1 " 0 # line from SMYRNA 115.00 BRKR to (2) MCKIBBEN 115.00 1 34708 34742 "1 " 0 # line from MCKIBBEN 115.00 (2) to (2) SEMITRPJ 115.00 1 34742 34746 "1 " 0 # line from SEMITRPJ 115.00 (2) to (2) GANSO 115.00 1 34746 34774 "1 " 0 # line from GANSO 115.00 (2) to BRKR MIDWAY 115.00 4 34746 0 "1 " 0 # LOAD-DROP GANSO 115.00 LOAD==5.34(1.22) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=89.95 QGEN=18.49 0 # # # (354) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #2 70 kV Line and Chevron Coalinga Unit 1 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00 2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=17.00 QGEN=8.30 0 # # # (355) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #1 70 kV Line and Chevron Coalinga Unit 1 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.03(2.5) 0 # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=17.00 QGEN=8.30 0 # # # (356) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #2 70 kV Line and Coalinga Cogen 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00 2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.22 QGEN=-13.50 0 #

Page 74: To determine the system impacts caused by the Project

A-53 GWF Henrietta SISAppendix A

# # (357) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #1 70 kV Line and Coalinga Cogen 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.03(2.5) 0 # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.22 QGEN=-13.50 0 # # # (358) L-1/G-1 OVERLAPPING OUTAGE # Borden - Coppermine 70 kV Line and Friant PP Unit 2 1 34262 34454 "1 " 0 # line from CASSIDY 70.00 (2) to (2) RIVERROC 70.00 1 34262 34256 "1 " 0 # line from CASSIDY 70.00 (2) to BRKR BORDEN 70.00 1 34454 34464 "1 " 0 # line from RIVERROC 70.00 (2) to BRKR COPPRMNE 70.00 4 34262 0 "1 " 0 # LOAD-DROP CASSIDY 70.00 LOAD==14.31(2.90) 4 34454 0 "1 " 0 # LOAD-DROP RIVERROC 70.00 LOAD==2.01(1.83) # 3 34636 0 "2" 0 # FRIANTDM 6.60 PGEN=14.70 QGEN=6.14 0 # # # (359) L-1/G-1 OVERLAPPING OUTAGE # Henrietta - Lemoore 70 kV Line and GWF Hanford 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) # 3 34650 0 "1" 0 # GWF-PWR. 13.80 PGEN=23.00 QGEN=12.00 0 # # # (360) L-1/G-1 OVERLAPPING OUTAGE # Henrietta - Lemoore 70 kV Line and GWF Henrietta Unit 1 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) # 3 34539 0 "1" 0 # GWF_GT1 13.80 PGEN=50.00 QGEN=1.23 0 # # # (361) L-1/G-1 OVERLAPPING OUTAGE # McCall - Wahtoke 115 kV Line and Sanger Cogen 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 # 3 34646 0 "1" 0 # SANGERCO 9.11 PGEN=37.50 QGEN=4.31

Page 75: To determine the system impacts caused by the Project

A-54 GWF Henrietta SISAppendix A

0 # # # (362) L-1/G-1 OVERLAPPING OUTAGE # McCall - Wahtoke 115 kV Line and Kings River Power House 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 # 3 34616 0 "1" 0 # KINGSRIV 13.80 PGEN=47.00 QGEN=9.00 0 # # # (363) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Exchequer 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (364) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Exchequer 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (365) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Exchequer 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (366) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Exchequer 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (367) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Exchequer 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (368) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Exchequer 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67)

Page 76: To determine the system impacts caused by the Project

A-55 GWF Henrietta SISAppendix A

4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (369) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Exchequer 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (370) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Exchequer 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (371) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Exchequer 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (372) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Exchequer 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (373) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Exchequer

Page 77: To determine the system impacts caused by the Project

A-56 GWF Henrietta SISAppendix A

1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (374) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Exchequer 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (375) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Exchequer 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (376) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Exchequer 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (377) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Exchequer 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (378) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Exchequer 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (379) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Kerckhoff 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 #

Page 78: To determine the system impacts caused by the Project

A-57 GWF Henrietta SISAppendix A

# # (380) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Kerckhoff 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (381) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Kerckhoff 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (382) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Kerckhoff 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (383) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Kerckhoff 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (384) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Kerckhoff 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (385) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Kerckhoff 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) #

Page 79: To determine the system impacts caused by the Project

A-58 GWF Henrietta SISAppendix A

3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (386) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Kerckhoff 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (387) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Kerckhoff 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (388) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Kerckhoff 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (389) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Kerckhoff 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (390) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Kerckhoff 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00

Page 80: To determine the system impacts caused by the Project

A-59 GWF Henrietta SISAppendix A

# 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (391) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Kerckhoff 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (392) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Kerckhoff 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (393) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Kerckhoff 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (394) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Kerckhoff 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (395) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Helms Unit 1 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (396) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Helms Unit 1 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (397) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Helms Unit 1 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # #

Page 81: To determine the system impacts caused by the Project

A-60 GWF Henrietta SISAppendix A

# (398) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Helms Unit 1 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (399) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Helms Unit 1 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (400) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Helms Unit 1 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (401) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Helms Unit 1 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (402) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Helms Unit 1 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (403) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Helms Unit 1 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00

Page 82: To determine the system impacts caused by the Project

A-61 GWF Henrietta SISAppendix A

4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (404) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Helms Unit 1 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (405) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Helms Unit 1 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (406) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Helms Unit 1 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (407) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Helms Unit 1 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (408) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Helms Unit 1 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0

Page 83: To determine the system impacts caused by the Project

A-62 GWF Henrietta SISAppendix A

# # # (409) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Helms Unit 1 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (410) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Helms Unit 1 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (411) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Melones Unit 1 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (412) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Melones Unit 1 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (413) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Melones Unit 1 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (414) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Melones Unit 1 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (415) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Melones Unit 1 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (416) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Melones Unit 1

Page 84: To determine the system impacts caused by the Project

A-63 GWF Henrietta SISAppendix A

1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (417) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Melones Unit 1 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (418) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Melones Unit 1 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (419) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Melones Unit 1 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (420) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Melones Unit 1 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (421) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Melones Unit 1 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 #

Page 85: To determine the system impacts caused by the Project

A-64 GWF Henrietta SISAppendix A

# # (422) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Melones Unit 1 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (423) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Melones Unit 1 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (424) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Melones Unit 1 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (425) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Melones Unit 1 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (426) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Melones Unit 1 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0

Page 86: To determine the system impacts caused by the Project

A-65 GWF Henrietta SISAppendix A

# # # (427) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Melones Unit 1 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (428) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Melones Unit 1 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (429) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Melones Unit 1 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (430) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Melones Unit 1 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # -1 # EOF

Page 87: To determine the system impacts caused by the Project

A-66 GWF Henrietta SISAppendix A

Summer Peak Category C Contingencies # Q272 2013 sumpk category c contingency list (dctl and bus outages) # Yosemite and Fresno Divisions Zones 313 and 314 # # 2013 sumpk category c contingency list # Yosemite Zone 313 # # # (1) C5 DCTL OUTAGE # Wilson - Atwater and El Capitan - Wilson 115 kV Lines 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 0 # # # (2) C5 DCTL OUTAGE # Wilson - Atwater and Atwater - El Capitan 115 kV Lines 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 0 # # # (3) C5 DCTL OUTAGE # Wilson - Merced #2 and Wilson - Oro Loma 115 kV Lines 1 34134 34144 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR MERCED 115.00 # 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) 0 # # # (4) C5 DCTL OUTAGE # Panoche - Schindler #1 and #2 115 kV Lines 1 34158 34350 "1 " 0 # line from PANOCHE 115.00 BRKR to (2) KAMM 115.00 1 34350 34352 "1 " 0 # line from KAMM 115.00 (2) to (2) CANTUA 115.00 1 34352 34432 "1 " 0 # line from CANTUA 115.00 (2) to (2) WESTLNDS 115.00 1 34432 34354 "1 " 0 # line from WESTLNDS 115.00 (2) to BRKR SCHINDLR 115.00 4 34350 0 "1 " 0 # LOAD-DROP KAMM 115.00 LOAD==3.85(1.75) 4 34352 0 "1 " 0 # LOAD-DROP CANTUA 115.00 LOAD==16.79(3.41) 4 34432 0 "16" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==0.94(0.23) 4 34432 0 "18" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==1.21(0.32) # 1 34141 34148 "1 " 0 # line from PAN2_TAP 115.00 (2) to (2) CHENY 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80

Page 88: To determine the system impacts caused by the Project

A-67 GWF Henrietta SISAppendix A

1 34148 34149 "1 " 0 # line from CHENY 115.00 (2) to (3) CHENYT 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (5) C5 DCTL OUTAGE # Gates - Panoche #1 and #2 230 kV Lines 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (6) C5 DCTL OUTAGE # Los Banos - Panoche #2 and Los Banos - Dos Amigos 230 kV Lines 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 0 # # # (7) C5 DCTL OUTAGE # Los Banos - Panoche #2 and Dos Amigos - Panoche 230 kV Lines 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (8) C5 DCTL OUTAGE # Los Banos - San Luis PGP #1 and #2 230 kV Lines 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (9) C5 DCTL OUTAGE # Bellota - Melones and Bellota - Warnerville 230 kV Lines 1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 30500 38208 "1 " 0 # line from BELLOTA 230.00 BRKR to (3) COTTLE B 230.00 1 38208 30515 "1 " 0 # line from COTTLE B 230.00 (3) to BRKR WARNERVL 230.00 4 38208 0 "2 " 0 # LOAD-DROP COTTLE B 230.00 LOAD==21.32(7.38) 0 # # # (10) C5 DCTL OUTAGE # Bellota - Melones and Warnerville - Wilson 230 kV Lines

Page 89: To determine the system impacts caused by the Project

A-68 GWF Henrietta SISAppendix A

1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (11) C5 DCTL OUTAGE # Bellota - Melones and Melones - Wilson 230 kV Lines 1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Melones - Wilson line 0 # # # (12) C5 DCTL OUTAGE # Melones - Wilson and Warnerville - Wilson 230 kV Lines 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Melones - Wilson line # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (13) C5 DCTL OUTAGE # Wilson - Borden #1 and #2 230 kV Lines 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) 0 # # # (14) C5 DCTL OUTAGE # Borden - Gregg #1 and #2 230 kV Lines 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line 0 # # # (15) C5 DCTL OUTAGE # Moss Landing - Panoche and Coburn - Panoche 230 kV Lines 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00

Page 90: To determine the system impacts caused by the Project

A-69 GWF Henrietta SISAppendix A

# 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (16) C5 DCTL OUTAGE # Panoche - Helm and Panoche - Kearney 230 kV Lines 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 0 # # # (17) BUS FAULT 30765 "LOSBANOS" Bus Section 1 # 1 30765 30670 "1" 0 # LINE from LOSBANOS 230.00 to WESTLEY 230.00 1 30765 30790 "2" 0 # LINE from LOSBANOS 230.00 to PANOCHE 230.00 1 30765 38625 "1" 0 # LINE from LOSBANOS 230.00 to SN LS PP 230.00 1 30765 38625 "2" 0 # LINE from LOSBANOS 230.00 to SN LS PP 230.00 2 30765 34214 "3" 0 # TRAN from LOSBANOS 230.00 to LOS BANS 70.00 6 30765 0 "v" 0 # drop Los Banos 230 kV shunt Caps 0 # # # (18) BUS FAULT 30765 "LOSBANOS" Bus Section 2 # 1 30765 30790 "1" 0 # LINE from LOSBANOS 230.00 to PANOCHE 230.00 1 30765 38615 "1" 0 # LINE from LOSBANOS 230.00 to DS AMIGO 230.00 2 30765 34214 "4" 0 # TRAN from LOSBANOS 230.00 to LOS BANS 70.00 0 # # # (19) BUS FAULT 30790 "PANOCHE" Bus Section 1 # 1 30790 30760 "1" 0 # LINE from PANOCHE 230.00 to COBURN 230.00 1 30790 30765 "1" 0 # LINE from PANOCHE 230.00 to LOSBANOS 230.00 1 30790 30765 "2" 0 # LINE from PANOCHE 230.00 to LOSBANOS 230.00 1 30790 30825 "1" 0 # LINE from PANOCHE 230.00 to MCMULLN1 230.00 1 30790 30900 "1" 0 # LINE from PANOCHE 230.00 to GATES 230.00 2 30790 30791 "1" 0 # TRAN from PANOCHE 230.00 to PNCHE 1M 230.00 0 # # # (20) BUS FAULT 30790 "PANOCHE" Bus Section 2 # 1 30790 30750 "1" 0 # LINE from PANOCHE 230.00 to MOSSLND2 230.00 1 30790 30793 "1" 0 # LINE from PANOCHE 230.00 to PANO_EC 230.00 1 30790 30873 "1" 0 # LINE from PANOCHE 230.00 to HELM 230.00 1 30790 30900 "2" 0 # LINE from PANOCHE 230.00 to GATES 230.00 1 30790 38615 "1" 0 # LINE from PANOCHE 230.00 to DS AMIGO 230.00 2 30790 34158 "2" 0 # TRAN from PANOCHE 230.00 to PANOCHE 115.00 0 # # # (21) BUS FAULT 34100 "CHWCHLLA" # 1 34100 34101 "1" 0 # LINE from CHWCHLLA 115.00 to CERTAN T 115.00 1 34100 34105 "1" 0 # LINE from CHWCHLLA 115.00 to CERTANJ1 115.00 4 34100 0 "1 " 0 # LOAD-DROP CHWCHLLA 115.00 LOAD==10.13(2.06) 4 34100 0 "2 " 0 # LOAD-DROP CHWCHLLA 115.00 LOAD==13.86(2.82) 0 # # # (22) BUS FAULT 34104 "ATWATER"

Page 91: To determine the system impacts caused by the Project

A-70 GWF Henrietta SISAppendix A

# 1 34104 34106 "1" 0 # LINE from ATWATER 115.00 to CASTLE 115.00 1 34104 34108 "1" 0 # LINE from ATWATER 115.00 to CRESEY T 115.00 1 34104 34134 "1" 0 # LINE from ATWATER 115.00 to WILSON A 115.00 4 34104 0 "1 " 0 # LOAD-DROP ATWATER 115.00 LOAD==32.40(6.57) 4 34104 0 "2 " 0 # LOAD-DROP ATWATER 115.00 LOAD==28.36(5.76) 0 # # # (23) BUS FAULT 34112 "EXCHEQUR" # 1 34112 34116 "1" 0 # LINE from EXCHEQUR 115.00 to LE GRAND 115.00 2 34112 34176 "1" 0 # TRAN from EXCHEQUR 115.00 to EXCHQRTP 115.00 0 # # # (24) BUS FAULT 34116 "LE GRAND" # 1 34116 34101 "1" 0 # LINE from LE GRAND 115.00 to CERTAN T 115.00 1 34116 34112 "1" 0 # LINE from LE GRAND 115.00 to EXCHEQUR 115.00 1 34116 34134 "1" 0 # LINE from LE GRAND 115.00 to WILSON A 115.00 1 34116 34154 "1" 0 # LINE from LE GRAND 115.00 to DAIRYLND 115.00 4 34116 0 "1 " 0 # LOAD-DROP LE GRAND 115.00 LOAD==13.41(2.72) 0 # # # (25) BUS FAULT 34134 "WILSON A" # 1 34134 34116 "1" 0 # LINE from WILSON A 115.00 to LE GRAND 115.00 1 34134 34104 "1" 0 # LINE from WILSON A 115.00 to ATWATER 115.00 1 34134 34136 "1" 0 # LINE from WILSON A 115.00 to WILSON B 115.00 1 34134 34144 "1" 0 # LINE from WILSON A 115.00 to MERCED 115.00 2 34134 30800 "1" 0 # TRAN from WILSON A 115.00 to WILSON 230.00 4 34134 0 "3 " 0 # LOAD-DROP WILSON A 115.00 LOAD==18.66(3.79) 6 34134 0 "v" 0 # drop Wilson A 115 kV shunt Caps 0 # # # (26) BUS FAULT 34136 "WILSON B" # 1 34136 34118 "1" 0 # LINE from WILSON B 115.00 to LE GRNDJ 115.00 1 34136 34134 "1" 0 # LINE from WILSON B 115.00 to WILSON A 115.00 1 34136 34138 "1" 0 # LINE from WILSON B 115.00 to EL CAPTN 115.00 1 34136 34144 "2" 0 # LINE from WILSON B 115.00 to MERCED 115.00 2 34136 30800 "2" 0 # TRAN from WILSON B 115.00 to WILSON 230.00 0 # # # (27) BUS FAULT 34138 "EL CAPTN" # 1 34138 34106 "1" 0 # LINE from EL CAPTN 115.00 to CASTLE 115.00 1 34138 34136 "1" 0 # LINE from EL CAPTN 115.00 to WILSON B 115.00 4 34138 0 "1 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==19.47(3.95) 4 34138 0 "2 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==25.91(5.26) 4 34138 0 "3 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==33.05(6.71) 0 # # # (28) BUS FAULT 34144 "MERCED" # 1 34144 34110 "1" 0 # LINE from MERCED 115.00 to ATWATR J 115.00 1 34144 34134 "1" 0 # LINE from MERCED 115.00 to WILSON A 115.00 1 34144 34136 "2" 0 # LINE from MERCED 115.00 to WILSON B 115.00 2 34144 34146 "2" 0 # TRAN from MERCED 115.00 to MERCED M 115.00 4 34144 0 "1 " 0 # LOAD-DROP MERCED 115.00 LOAD==37.10(7.53) 4 34144 0 "3 " 0 # LOAD-DROP MERCED 115.00 LOAD==19.45(3.95) 0 # # # (29) BUS FAULT 34154 "DAIRYLND"

Page 92: To determine the system impacts caused by the Project

A-71 GWF Henrietta SISAppendix A

# 1 34154 34116 "1" 0 # LINE from DAIRYLND 115.00 to LE GRAND 115.00 1 34154 34150 "1" 0 # LINE from DAIRYLND 115.00 to NEWHALL 115.00 4 34154 0 "1 " 0 # LOAD-DROP DAIRYLND 115.00 LOAD==25.82(5.24) 0 # # # (30) BUS FAULT 34158 "PANOCHE" Bus Section 1 # 1 34158 34149 "1" 0 # LINE from PANOCHE 115.00 to CHENYT 115.00 1 34158 34159 "1" 0 # LINE from PANOCHE 115.00 to PANOCHEJ 115.00 2 34158 30790 "2" 0 # TRAN from PANOCHE 115.00 to PANOCHE 230.00 2 34158 34186 "1" 0 # TRAN from PANOCHE 115.00 to DG_PAN1 13.80 0 # # # (31) BUS FAULT 34158 "PANOCHE" Bus Section 2 # 1 34158 34157 "1" 0 # LINE from PANOCHE 115.00 to PANOCHET 115.00 1 34158 34189 "1" 0 # LINE from PANOCHE 115.00 to STARWOOD 115.00 1 34158 34350 "1" 0 # LINE from PANOCHE 115.00 to KAMM 115.00 2 34158 30791 "1" 0 # TRAN from PANOCHE 115.00 to PNCHE 1M 230.00 0 # # # (32) BUS FAULT 34200 "ORO LOMA" # 1 34200 34218 "1" 0 # LINE from ORO LOMA 70.00 to DOS PALS 70.00 1 34200 34222 "1" 0 # LINE from ORO LOMA 70.00 to MRCYSPRS 70.00 1 34200 34234 "1" 0 # LINE from ORO LOMA 70.00 to POSO J1 70.00 2 34200 34162 "2" 0 # TRAN from ORO LOMA 70.00 to ORO LOMA 115.00 4 34200 0 "1 " 0 # LOAD-DROP ORO LOMA 70.00 LOAD==8.64(1.75) 0 # # # (33) BUS FAULT 34202 "MERCED" # 1 34202 34203 "1" 0 # LINE from MERCED 70.00 to ELNIDOTP 70.00 1 34202 34230 "1" 0 # LINE from MERCED 70.00 to MRCDFLLS 70.00 2 34202 34146 "2" 0 # TRAN from MERCED 70.00 to MERCED M 115.00 0 # # # (34) BUS FAULT 34206 "CANAL" # 1 34206 34212 "1" 0 # LINE from CANAL 70.00 to LVNGSTNT 70.00 1 34206 34216 "1" 0 # LINE from CANAL 70.00 to SNTA RTA 70.00 1 34206 34220 "1" 0 # LINE from CANAL 70.00 to ORTIGA 70.00 4 34206 0 "1 " 0 # LOAD-DROP CANAL 70.00 LOAD==30.56(6.21) 4 34206 0 "2 " 0 # LOAD-DROP CANAL 70.00 LOAD==31.27(6.35) 0 # # # (35) BUS FAULT 34214 "LOS BANS" # 1 34214 34208 "1" 0 # LINE from LOS BANS 70.00 to CHEVPIPE 70.00 1 34214 34272 "1" 0 # LINE from LOS BANS 70.00 to WRGHT PP 70.00 1 34214 34278 "1" 0 # LINE from LOS BANS 70.00 to PCHCO PP 70.00 1 34214 34282 "1" 0 # LINE from LOS BANS 70.00 to ONLL PMP 69.00 2 34214 30765 "3" 0 # TRAN from LOS BANS 70.00 to LOSBANOS 230.00 2 34214 30765 "4" 0 # TRAN from LOS BANS 70.00 to LOSBANOS 230.00 0 # # # (36) BUS FAULT 34216 "SNTA RTA" # 1 34216 34206 "1" 0 # LINE from SNTA RTA 70.00 to CANAL 70.00 1 34216 34218 "1" 0 # LINE from SNTA RTA 70.00 to DOS PALS 70.00 4 34216 0 "1 " 0 # LOAD-DROP SNTA RTA 70.00 LOAD==7.48(1.52) 0

Page 93: To determine the system impacts caused by the Project

A-72 GWF Henrietta SISAppendix A

# # # (37) BUS FAULT 34230 "MRCDFLLS" # 1 34230 34202 "1" 0 # LINE from MRCDFLLS 70.00 to MERCED 70.00 1 34230 34321 "1" 0 # LINE from MRCDFLLS 70.00 to MCSWAINJ 70.00 2 34230 34322 "1" 0 # TRAN from MRCDFLLS 70.00 to MERCEDFL 9.11 2 34230 34322 "2" 0 # TRAN from MRCDFLLS 70.00 to MERCEDFL 9.11 4 34230 0 "2 " 0 # LOAD-DROP MRCDFLLS 70.00 LOAD==8.94(1.82) 0 # # # (38) BUS FAULT 34238 "BONITA" # 1 34238 34236 "1" 0 # LINE from BONITA 70.00 to POSO J2 70.00 1 34238 34255 "1" 0 # LINE from BONITA 70.00 to TRIGO J 70.00 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 0 # # # (39) BUS FAULT 34240 "GLASS" # 1 34240 34237 "1" 0 # LINE from GLASS 70.00 to CANANDGA 70.00 1 34240 34256 "1" 0 # LINE from GLASS 70.00 to BORDEN 70.00 4 34240 0 "1 " 0 # LOAD-DROP GLASS 70.00 LOAD==9.05(4.89) 0 # # # (40) BUS FAULT 34252 "MADERA" # 1 34252 34254 "1" 0 # LINE from MADERA 70.00 to TRIGO 70.00 1 34252 34256 "1" 0 # LINE from MADERA 70.00 to BORDEN 70.00 1 34252 34256 "2" 0 # LINE from MADERA 70.00 to BORDEN 70.00 4 34252 0 "1 " 0 # LOAD-DROP MADERA 70.00 LOAD==17.99(3.65) 4 34252 0 "2 " 0 # LOAD-DROP MADERA 70.00 LOAD==23.16(4.71) 6 34252 0 "v" 0 # drop Madera 70 kV shunt Caps 0 # # # (41) BUS FAULT 34256 "BORDEN" # 1 34256 34252 "1" 0 # LINE from BORDEN 70.00 to MADERA 70.00 1 34256 34252 "2" 0 # LINE from BORDEN 70.00 to MADERA 70.00 1 34256 34240 "1" 0 # LINE from BORDEN 70.00 to GLASS 70.00 1 34256 34262 "1" 0 # LINE from BORDEN 70.00 to CASSIDY 70.00 2 34256 30805 "1" 0 # TRAN from BORDEN 70.00 to BORDEN 230.00 2 34256 30805 "2" 0 # TRAN from BORDEN 70.00 to BORDEN 230.00 0 # # # (42) BUS FAULT 34268 "MENDOTA" # 1 34268 34267 "1" 0 # LINE from MENDOTA 70.00 to TOMATAK 70.00 1 34268 34269 "1" 0 # LINE from MENDOTA 70.00 to BIOMSJCT 70.00 2 34268 34156 "1" 0 # TRAN from MENDOTA 70.00 to MENDOTA 115.00 0 # # # 2013 sumpk category c contingency list # Fresno Zone 314 # # # (43) C5 DCTL OUTAGE # Gates - Schindler and Gates - Huron #1 70 kV Lines 1 34558 34560 "1 " 0 # line from HURON 70.00 BRKR to (2) CALFLAX 70.00 1 34560 34562 "1 " 0 # line from CALFLAX 70.00 (2) to BRKR SCHLNDLR 70.00 4 34560 0 "1 " 0 # LOAD-DROP CALFLAX 70.00 LOAD==6.53(1.33) 1 34552 34558 "2 " 0 # Must include Gates - Huron #2 in this outage

Page 94: To determine the system impacts caused by the Project

A-73 GWF Henrietta SISAppendix A

# 1 34552 34558 "1 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0 # # # (44) C5 DCTL OUTAGE # Barton - Sanger and Manchester - Sanger 115 kV Lines 1 34359 34361 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR AIRWAYS 115.00 1 34359 34408 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR BARTON 115.00 1 34359 34366 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR SANGER 115.00 # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (45) C5 DCTL OUTAGE # Herndon - Barton and Herndon - Manchester 115 kV Lines 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 # 1 34410 34412 "1 " 0 # line from MANCHSTR 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (46) C5 DCTL OUTAGE # Herndon - Barton and Manchester - Sanger 115 kV Lines 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (47) C5 DCTL OUTAGE # Herndon - Bullard #1 and #2 115 kV Lines 1 34411 34416 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR BULLARD 115.00 1 34411 34412 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR HERNDON 115.00 # 1 34409 34413 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR PNEDLE 115.00 1 34409 34416 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR BULLARD 115.00 1 34409 34412 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR HERNDON 115.00 4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25) 4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 1 34411 34413 "1 " 1 # Switches in Pindale CB#12 to transfer load

Page 95: To determine the system impacts caused by the Project

A-74 GWF Henrietta SISAppendix A

4 34413 0 "**" 1 # Restore load at Pindale 0 # # # (48) C5 DCTL OUTAGE # Kerckhoff - Clovis - Sanger #1 and #2 115 kV Lines 1 34358 34360 "1 " 0 # line from KERCKHF2 115.00 BRKR to (3) WWARD JT 115.00 1 34360 34414 "1 " 0 # line from WWARD JT 115.00 (3) to BRKR WOODWARD 115.00 1 34360 34363 "1 " 0 # line from WWARD JT 115.00 (3) to (3) CLOVISJ1 115.00 1 34363 34362 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR CLOVIS-1 115.00 1 34363 34366 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR SANGER 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36) 4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34362 0 "**" 1 # Restore Load at Clovis 1 # 1 34364 34365 "1 " 0 # line from CLOVIS-2 115.00 BRKR to (3) CLOVISJ2 115.00 1 34365 34358 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR KERCKHF2 115.00 1 34365 34366 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR SANGER 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34364 0 "**" 1 # Restore Load at Clovis 2 0 # # # (49) C5 DCTL OUTAGE # Kingburg - Corcoran #1 and #2 115 kV Lines 1 34418 34420 "1 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 # 1 34418 34420 "2 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (50) C5 DCTL OUTAGE # Kings River - Sanger - Reedley and Balch - Sanger 115 kV Lines 1 34366 34389 "1 " 0 # line from SANGER 115.00 BRKR to (3) RAINBWTP 115.00 1 34389 34388 "1 " 0 # line from RAINBWTP 115.00 (3) to (1) RAINBW 115.00 1 34389 34394 "1 " 0 # line from RAINBWTP 115.00 (3) to (3) PIEDRA 1 115.00 1 34394 34380 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR REEDLEY 115.00 1 34394 34400 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR KNGSRVR1 115.00 4 34388 0 "1 " 0 # LOAD-DROP RAINBW 115.00 LOAD==16.20(3.29) # 1 34366 34396 "1 " 0 # line from SANGER 115.00 BRKR to (2) PIEDRA 2 115.00 1 34396 34398 "1 " 0 # line from PIEDRA 2 115.00 (2) to (2) BALCH 115.00 2 34398 34624 "1 " 0 # TRAN from BALCH 115.00 (2) to (1) BALCH 1 13.20 4 34624 0 "1 " 0 # LOAD-DROP BALCH 1 13.20 LOAD==0.26(0.00) 3 34624 0 "1 " 0 # GEN-DROP BALCH 1 13.20 GEN==27.00(8.33) 0 # # # (51) C5 DCTL OUTAGE # McCall - Kingsburg #1 and #2 115 kV Lines

Page 96: To determine the system impacts caused by the Project

A-75 GWF Henrietta SISAppendix A

1 34370 34385 "1 " 0 # line from MC CALL 115.00 BRKR to (3) KINGS J1 115.00 1 34385 34417 "1 " 0 # line from KINGS J1 115.00 (3) to (2) KINGS J2 115.00 1 34385 34425 "1 " 0 # line from KINGS J1 115.00 (3) to (3) KCOGNJCT 115.00 1 34417 34418 "1 " 0 # line from KINGS J2 115.00 (2) to BRKR KINGSBRG 115.00 1 34425 34387 "1 " 0 # line from KCOGNJCT 115.00 (3) to (1) SUNMAID 115.00 1 34425 34427 "1 " 0 # line from KCOGNJCT 115.00 (3) to (2) GRDNGLS2 115.00 1 34427 34386 "1 " 0 # line from GRDNGLS2 115.00 (2) to (2) KNGSCOGN 115.00 2 34386 34642 "1 " 0 # TRAN from KNGSCOGN 115.00 (2) to BRKR KINGSBUR 9.11 4 34387 0 "1 " 0 # LOAD-DROP SUNMAID 115.00 LOAD==3.40(3.28) 3 34642 0 "1 " 0 # GEN-DROP KINGSBUR 9.11 GEN==34.00(17.30) # 1 34418 34423 "1 " 0 # line from KINGSBRG 115.00 BRKR to (3) GAURD J1 115.00 1 34423 34370 "1 " 0 # line from GAURD J1 115.00 (3) to BRKR MC CALL 115.00 1 34423 34421 "1 " 0 # line from GAURD J1 115.00 (3) to (2) GAURD J2 115.00 1 34421 34424 "1 " 0 # line from GAURD J2 115.00 (2) to (1) GRDN GLS 115.00 4 34424 0 "1 " 0 # LOAD-DROP GRDN GLS 115.00 LOAD==3.50(1.15) 4 34418 0 "3 " 0 # Kingsburg Bank #3 will also be dropped on this outage 0 # # # (52) C5 DCTL OUTAGE # McCall - Sanger #1 and #2 115 kV Lines 1 34366 34370 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 # 1 34366 34370 "2 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (53) C5 DCTL OUTAGE # McCall - West Fresno and California Ave. - West Fresno 115 kV Lines 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 # 1 34402 34404 "1 " 0 # line from CAL AVE 115.00 BRKR to BRKR WST FRSO 115.00 0 # # # (54) C5 DCTL OUTAGE # McCall - West Fresno and California Ave. - McCall 115 kV Lines 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 # 1 34390 34370 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR MC CALL 115.00 1 34390 34402 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR CAL AVE 115.00 4 34390 0 "1 " 0 # LOAD-DROP DANISHCM 115.00 LOAD==4.10(3.51) 0 # # # (55) C5 DCTL OUTAGE # Gates - Gregg and Gates - McCall 230 kV Lines 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00

Page 97: To determine the system impacts caused by the Project

A-76 GWF Henrietta SISAppendix A

1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 # # # (56) C5 DCTL OUTAGE # Panoche - Kearney and Gates - Gregg 230 kV Lines 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 0 # # # (57) C5 DCTL OUTAGE # Panoche - Kearney and Panoche - Helm 230 kV Lines 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 0 # # # (58) C5 DCTL OUTAGE # Panoche - Kearney and Helm - McCall 230 kV Lines 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 0 # # # (59) C5 DCTL OUTAGE # Helm - McCall and Gates - McCall 230 kV Lines 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 #

Page 98: To determine the system impacts caused by the Project

A-77 GWF Henrietta SISAppendix A

# # (60) C5 DCTL OUTAGE # Helms - Gregg #1 and #2 230 kV Lines 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line 0 # # # (61) C5 DCTL OUTAGE # Gregg - Herndon #1 and #2 230 kV Lines 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line 0 # # # (62) C5 DCTL OUTAGE # Herndon - Kearney and Herndon - Ashlan 230 kV Lines 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 0 # # # (63) C5 DCTL OUTAGE # Herndon - Kearney and Gates - Gregg 230 kV Lines 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 0 # # # (64) C5 DCTL OUTAGE # Gates - Gregg and Gregg - Ashlan 230 kV Lines 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) #

Page 99: To determine the system impacts caused by the Project

A-78 GWF Henrietta SISAppendix A

1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (65) C5 DCTL OUTAGE # Herndon - Ashlan and Gregg - Ashlan 230 kV Lines 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (66) C5 DCTL OUTAGE # Haas - McCall and Balch - McCall 230 kV Lines 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) 0 # # # (67) C5 DCTL OUTAGE # Morro Bay - Gates and Templeton - Gates 230 kV Lines

Page 100: To determine the system impacts caused by the Project

A-79 GWF Henrietta SISAppendix A

1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 0 # # # (68) C5 DCTL OUTAGE # Gates - Midway and Gates - Arco 230 kV Lines 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 0 # # # (69) BUS FAULT 30820 "HELMS PP" # 1 30820 30810 "1" 0 # LINE from HELMS PP 230.00 to GREGG 230.00 1 30820 30810 "2" 0 # LINE from HELMS PP 230.00 to GREGG 230.00 2 30820 34600 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 1 18.00 2 30820 34602 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 2 18.00 2 30820 34604 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 3 18.00 0 # # # (70) BUS FAULT 30830 "KEARNEY" # 1 30830 30825 "1" 0 # LINE from KEARNEY 230.00 to MCMULLN1 230.00 1 30830 30835 "1" 0 # LINE from KEARNEY 230.00 to HERNDON 230.00 2 30830 34480 "2" 0 # TRAN from KEARNEY 230.00 to KEARNEY 70.00 0 # # # (71) BUS FAULT 30835 "HERNDON" 230 kV Bus Section 1 # 1 30835 30810 "1" 0 # LINE from HERNDON 230.00 to GREGG 230.00 1 30835 30830 "1" 0 # LINE from HERNDON 230.00 to KEARNEY 230.00 2 30835 30882 "1" 0 # TRAN from HERNDON 230.00 to HERNDN1M 115.00 0 # # # (72) BUS FAULT 30835 "HERNDON" 230 kV Bus Section 2 # 1 30835 30810 "2" 0 # LINE from HERNDON 230.00 to GREGG 230.00 1 30835 30840 "1" 0 # LINE from HERNDON 230.00 to FGRDN T1 230.00 2 30835 30883 "2" 0 # TRAN from HERNDON 230.00 to HERNDN2M 115.00 0 # # # (73) BUS FAULT 30841 "FIGRDN 1" # 1 30841 30840 "1" 0 # LINE from FIGRDN 1 230.00 to FGRDN T1 230.00 1 30841 30846 "1" 0 # LINE from FIGRDN 1 230.00 to FIGRDN 2 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 0 # # # (74) BUS FAULT 30846 "FIGRDN 2" # 1 30846 30841 "1" 0 # LINE from FIGRDN 2 230.00 to FIGRDN 1 230.00 1 30846 30845 "1" 0 # LINE from FIGRDN 2 230.00 to FGRDN T2 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 0 # # # (75) BUS FAULT 30850 "ASHLAN"

Page 101: To determine the system impacts caused by the Project

A-80 GWF Henrietta SISAppendix A

# 1 30850 30840 "1" 0 # LINE from ASHLAN 230.00 to FGRDN T1 230.00 1 30850 30845 "1" 0 # LINE from ASHLAN 230.00 to FGRDN T2 230.00 4 30850 0 "1 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==69.20(13.40) 4 30850 0 "2 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==64.54(12.84) 4 30850 0 "3 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==65.51(12.49) 0 # # # (76) BUS FAULT 30873 "HELM" # 1 30873 30790 "1" 0 # LINE from HELM 230.00 to PANOCHE 230.00 1 30873 30875 "1" 0 # LINE from HELM 230.00 to MC CALL 230.00 2 30873 34474 "1" 0 # TRAN from HELM 230.00 to HELM 70.00 0 # # # (77) BUS FAULT 30874 "P0615STN" # 1 30874 30875 "1" 0 # LINE from P0615STN 230.00 to MC CALL 230.00 1 30874 30875 "2" 0 # LINE from P0615STN 230.00 to MC CALL 230.00 2 30874 34685 "1" 0 # TRAN from P0615STN 230.00 to P0615CT1 16.50 2 30874 34686 "1" 0 # TRAN from P0615STN 230.00 to P0615CT2 16.50 2 30874 34687 "1" 0 # TRAN from P0615STN 230.00 to P0615STG 16.50 0 # # # (78) BUS FAULT 30875 "MC CALL" 230 kV Bus Section 1 # 1 30875 30870 "1" 0 # LINE from MC CALL 230.00 to PINE FLT 230.00 1 30875 30874 "1" 0 # LINE from MC CALL 230.00 to P0615STN 230.00 1 30875 30880 "1" 0 # LINE from MC CALL 230.00 to HENTAP2 230.00 2 30875 30877 "2" 0 # TRAN from MC CALL 230.00 to MCCALL2M 115.00 6 30875 0 "v" 0 # SVD from MC CALL 230.00 0 # # # (79) BUS FAULT 30875 "MC CALL" 230 kV Bus Section 2 # 1 30875 30873 "1" 0 # LINE from MC CALL 230.00 to HELM 230.00 1 30875 30860 "1" 0 # LINE from MC CALL 230.00 to BALCH3TP 230.00 1 30875 30874 "2" 0 # LINE from MC CALL 230.00 to P0615STN 230.00 2 30875 30876 "1" 0 # TRAN from MC CALL 230.00 to MCCALL1M 115.00 2 30875 30878 "3" 0 # TRAN from MC CALL 230.00 to MCCALL3M 115.00 0 # # # (80) BUS FAULT 30881 "HENRIETA" # 1 30881 30879 "1" 0 # LINE from HENRIETA 230.00 to HENTAP1 230.00 1 30881 30880 "1" 0 # LINE from HENRIETA 230.00 to HENTAP2 230.00 2 30881 34430 "3" 0 # TRAN from HENRIETA 230.00 to HENRETTA 115.00 2 30881 34540 "2" 0 # TRAN from HENRIETA 230.00 to HENRITTA 70.00 2 30881 34540 "4" 0 # TRAN from HENRIETA 230.00 to HENRITTA 70.00 0 # # # (81) BUS FAULT 30900 "GATES" 230 kV Bus Section 1D # 1 30900 30790 "1" 0 # LINE from GATES 230.00 to PANOCHE 230.00 1 30900 30905 "1" 0 # LINE from GATES 230.00 to TEMPLETN 230.00 2 30900 30901 "1" 0 # TRAN from GATES 230.00 to GATES 1M 230.00 6 30900 0 "v" 0 # SVD from GATES 230.00 0 # # # (82) BUS FAULT 30900 "GATES" 230 kV Bus Section 2D # 1 30900 30790 "2" 0 # LINE from GATES 230.00 to PANOCHE 230.00 1 30900 30915 "1" 0 # LINE from GATES 230.00 to MORROBAY 230.00

Page 102: To determine the system impacts caused by the Project

A-81 GWF Henrietta SISAppendix A

0 # # # (83) BUS FAULT 30900 "GATES" 230 kV Bus Section 1E # 1 30900 30879 "1" 0 # LINE from GATES 230.00 to HENTAP1 230.00 1 30900 30935 "1" 0 # LINE from GATES 230.00 to ARCO 230.00 0 # # # (84) BUS FAULT 30900 "GATES" 230 kV Bus Section 2E # 1 30900 30880 "1" 0 # LINE from GATES 230.00 to HENTAP2 230.00 1 30900 30970 "1" 0 # LINE from GATES 230.00 to MIDWAY 230.00 0 # # # (85) BUS FAULT 34356 "KERCKHF1" # 1 34356 34123 "2" 0 # LINE from KERCKHF1 115.00 to K1-JCT 115.00 1 34356 34358 "1" 0 # LINE from KERCKHF1 115.00 to KERCKHF2 115.00 2 34356 34344 "1" 0 # TRAN from KERCKHF1 115.00 to KERCKHOF 6.60 0 # # # (86) BUS FAULT 34358 "KERCKHF2" # 1 34358 34123 "2" 0 # LINE from KERCKHF2 115.00 to K1-JCT 115.00 1 34358 34356 "1" 0 # LINE from KERCKHF2 115.00 to KERCKHF1 115.00 1 34358 34360 "1" 0 # LINE from KERCKHF2 115.00 to WWARD JT 115.00 1 34358 34365 "1" 0 # LINE from KERCKHF2 115.00 to CLOVISJ2 115.00 2 34358 34308 "1" 0 # TRAN from KERCKHF2 115.00 to KERCKHOF 13.80 0 # # # (87) BUS FAULT 34361 "AIRWAYS" # 1 34361 34357 "1" 0 # LINE from AIRWAYS 115.00 to AIRWAYJ1 115.00 1 34361 34359 "1" 0 # LINE from AIRWAYS 115.00 to AIRWAYJ2 115.00 4 34361 0 "1 " 0 # LOAD-DROP AIRWAYS 115.00 LOAD==38.39(7.43) 4 34361 0 "2 " 0 # LOAD-DROP AIRWAYS 115.00 LOAD==12.60(2.56) 0 # # # (88) BUS FAULT 34362 "CLOVIS-1" # 1 34362 34363 "1" 0 # LINE from CLOVIS-1 115.00 to CLOVISJ1 115.00 1 34362 34364 "1" 0 # LINE from CLOVIS-1 115.00 to CLOVIS-2 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36) 4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 0 # # # (89) BUS FAULT 34364 "CLOVIS-2" # 1 34364 34362 "1" 0 # LINE from CLOVIS-2 115.00 to CLOVIS-1 115.00 1 34364 34365 "1" 0 # LINE from CLOVIS-2 115.00 to CLOVISJ2 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 0 # # # (90) BUS FAULT 34366 "SANGER" # 1 34366 34363 "1" 0 # LINE from SANGER 115.00 to CLOVISJ1 115.00 1 34366 34365 "1" 0 # LINE from SANGER 115.00 to CLOVISJ2 115.00 1 34366 34359 "1" 0 # LINE from SANGER 115.00 to AIRWAYJ2 115.00 1 34366 34368 "1" 0 # LINE from SANGER 115.00 to LASPALMS 115.00 1 34366 34370 "1" 0 # LINE from SANGER 115.00 to MC CALL 115.00 1 34366 34370 "2" 0 # LINE from SANGER 115.00 to MC CALL 115.00 1 34366 34370 "3" 0 # LINE from SANGER 115.00 to MC CALL 115.00

Page 103: To determine the system impacts caused by the Project

A-82 GWF Henrietta SISAppendix A

1 34366 34372 "1" 0 # LINE from SANGER 115.00 to MALAGA 115.00 1 34366 34389 "1" 0 # LINE from SANGER 115.00 to RAINBWTP 115.00 1 34366 34396 "1" 0 # LINE from SANGER 115.00 to PIEDRA 2 115.00 1 34366 34488 "1" 0 # LINE from SANGER 115.00 to SANGER 70.00 2 34366 34590 "1" 0 # TRAN from SANGER 115.00 to SANGR3T 115.00 4 34366 0 "1 " 0 # LOAD-DROP SANGER 115.00 LOAD==24.26(4.93) 0 # # # (91) BUS FAULT 34372 "MALAGA" # 1 34372 34366 "1" 0 # LINE from MALAGA 115.00 to SANGER 115.00 1 34372 34376 "1" 0 # LINE from MALAGA 115.00 to PPG 115.00 1 34372 34379 "1" 0 # LINE from MALAGA 115.00 to MALAGATP 115.00 1 34372 34381 "1" 0 # LINE from MALAGA 115.00 to KRCDP 115.00 4 34372 0 "1 " 0 # LOAD-DROP MALAGA 115.00 LOAD==25.25(5.12) 4 34372 0 "2 " 0 # LOAD-DROP MALAGA 115.00 LOAD==22.76(4.62) 4 34372 0 "3 " 0 # LOAD-DROP MALAGA 115.00 LOAD==23.13(4.69) 0 # # # (92) BUS FAULT 34378 "GATES" # 2 34378 30901 "1" 0 # TRAN from GATES 115.00 to GATES 1M 230.00 2 34378 34552 "2" 0 # TRAN from GATES 115.00 to GATES 70.00 4 34378 0 "3 " 0 # LOAD-DROP GATES 115.00 LOAD==19.45(3.95) 0 # # # (93) BUS FAULT 34380 "REEDLEY" # 1 34380 34384 "1" 0 # LINE from REEDLEY 115.00 to GERAWAN 115.00 1 34380 34394 "1" 0 # LINE from REEDLEY 115.00 to PIEDRA 1 115.00 2 34380 34492 "1" 0 # TRAN from REEDLEY 115.00 to REEDLEY 70.00 2 34380 34492 "2" 0 # TRAN from REEDLEY 115.00 to REEDLEY 70.00 4 34380 0 "3 " 0 # LOAD-DROP REEDLEY 115.00 LOAD==26.17(5.31) 0 # # # (94) BUS FAULT 34382 "WAHTOKE" # 1 34382 34370 "1" 0 # LINE from WAHTOKE 115.00 to MC CALL 115.00 1 34382 34384 "1" 0 # LINE from WAHTOKE 115.00 to GERAWAN 115.00 4 34382 0 "2 " 0 # LOAD-DROP WAHTOKE 115.00 LOAD==30.36(6.17) 4 34382 0 "3 " 0 # LOAD-DROP WAHTOKE 115.00 LOAD==20.84(4.24) 0 # # # (95) BUS FAULT 34400 "KNGSRVR1" # 1 34400 34394 "1" 0 # LINE from KNGSRVR1 115.00 to PIEDRA 1 115.00 2 34400 34616 "1" 0 # TRAN from KNGSRVR1 115.00 to KINGSRIV 13.80 0 # # # (96) BUS FAULT 34402 "CAL AVE" # 1 34402 34390 "1" 0 # LINE from CAL AVE 115.00 to DANISHCM 115.00 1 34402 34404 "1" 0 # LINE from CAL AVE 115.00 to WST FRSO 115.00 4 34402 0 "1 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==28.95(5.87) 4 34402 0 "2 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==31.26(6.35) 4 34402 0 "3 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==24.42(4.96) 0 # # # (97) BUS FAULT 34404 "WST FRSO" # 1 34404 34370 "1" 0 # LINE from WST FRSO 115.00 to MC CALL 115.00 1 34404 34402 "1" 0 # LINE from WST FRSO 115.00 to CAL AVE 115.00 4 34404 0 "1 " 0 # LOAD-DROP WST FRSO 115.00 LOAD==37.55(7.63)

Page 104: To determine the system impacts caused by the Project

A-83 GWF Henrietta SISAppendix A

4 34404 0 "2 " 0 # LOAD-DROP WST FRSO 115.00 LOAD==39.04(7.93) 0 # # # (98) BUS FAULT 34408 "BARTON" # 1 34408 34359 "1" 0 # LINE from BARTON 115.00 to AIRWAYJ2 115.00 1 34408 34412 "1" 0 # LINE from BARTON 115.00 to HERNDON 115.00 4 34408 0 "1 " 0 # LOAD-DROP BARTON 115.00 LOAD==43.27(8.79) 4 34408 0 "2 " 0 # LOAD-DROP BARTON 115.00 LOAD==37.15(7.54) 4 34408 0 "3 " 0 # LOAD-DROP BARTON 115.00 LOAD==26.96(5.47) 0 # # # (99) BUS FAULT 34410 "MANCHSTR" # 1 34410 34357 "1" 0 # LINE from MANCHSTR 115.00 to AIRWAYJ1 115.00 1 34410 34412 "1" 0 # LINE from MANCHSTR 115.00 to HERNDON 115.00 4 34410 0 "1 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==25.28(5.13) 4 34410 0 "2 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==25.47(5.18) 4 34410 0 "3 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==36.21(7.36) 0 # # # (100) BUS FAULT 34412 "HERNDON" 115 kV Bus Section 1 # 1 34412 34408 "1" 0 # LINE from HERNDON 115.00 to BARTON 115.00 1 34412 34409 "1" 0 # LINE from HERNDON 115.00 to PNDLJ2 115.00 2 34412 30882 "1" 0 # TRAN from HERNDON 115.00 to HERNDN1M 115.00 0 # # # (101) BUS FAULT 34412 "HERNDON" 115 kV Bus Section 2 # 1 34412 34410 "1" 0 # LINE from HERNDON 115.00 to MANCHSTR 115.00 1 34412 34411 "1" 0 # LINE from HERNDON 115.00 to PNDLJ1 115.00 1 34412 34422 "1" 0 # LINE from HERNDON 115.00 to CHLDHOSP 115.00 0 # # # (102) BUS FAULT 34413 "PNEDLE" # 1 34413 34409 "1" 0 # LINE from PNEDLE 115.00 to PNDLJ2 115.00 1 34413 34411 "1" 0 # LINE from PNEDLE 115.00 to PNDLJ1 115.00 4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25) 4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 0 # # # (103) BUS FAULT 34414 "WOODWARD" # 1 34414 34360 "1" 0 # LINE from WOODWARD 115.00 to WWARD JT 115.00 1 34414 34422 "1" 0 # LINE from WOODWARD 115.00 to CHLDHOSP 115.00 4 34414 0 "1 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==42.25(8.58) 4 34414 0 "2 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==52.69(10.70) 4 34414 0 "3 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==44.09(8.95) 0 # # # (104) BUS FAULT 34416 "BULLARD" # 1 34416 34409 "1" 0 # LINE from BULLARD 115.00 to PNDLJ2 115.00 1 34416 34411 "1" 0 # LINE from BULLARD 115.00 to PNDLJ1 115.00 4 34416 0 "1 " 0 # LOAD-DROP BULLARD 115.00 LOAD==44.87(9.11) 4 34416 0 "2 " 0 # LOAD-DROP BULLARD 115.00 LOAD==44.65(9.07) 4 34416 0 "3 " 0 # LOAD-DROP BULLARD 115.00 LOAD==42.52(8.63) 0 # # # (105) BUS FAULT 34418 "KINGSBRG" 115 kV Bus Section D

Page 105: To determine the system impacts caused by the Project

A-84 GWF Henrietta SISAppendix A

# 1 34418 34417 "1" 0 # LINE from KINGSBRG 115.00 to KINGS J2 115.00 1 34418 34428 "1" 0 # LINE from KINGSBRG 115.00 to CONTADNA 115.00 1 34418 34420 "2" 0 # LINE from KINGSBRG 115.00 to CORCORAN 115.00 4 34418 0 "1 " 0 # LOAD-DROP KINGSBRG 115.00 LOAD==39.24(7.96) 0 # # # (106) BUS FAULT 34418 "KINGSBRG" 115 kV Bus Section E # 1 34418 34420 "1" 0 # LINE from KINGSBRG 115.00 to CORCORAN 115.00 1 34418 34423 "1" 0 # LINE from KINGSBRG 115.00 to GAURD J1 115.00 2 34418 34576 "2" 0 # TRAN from KINGSBRG 115.00 to KNGLOBUS 70.00 4 34418 0 "3 " 0 # LOAD-DROP KINGSBRG 115.00 LOAD==24.32(4.94) 0 # # # (107) BUS FAULT 34420 "CORCORAN" # 1 34420 34391 "1" 0 # LINE from CORCORAN 115.00 to QUEBECTP 115.00 1 34420 34418 "1" 0 # LINE from CORCORAN 115.00 to KINGSBRG 115.00 1 34420 34418 "2" 0 # LINE from CORCORAN 115.00 to KINGSBRG 115.00 2 34420 34528 "2" 0 # TRAN from CORCORAN 115.00 to CORCORAN 70.00 4 34420 0 "3 " 0 # LOAD-DROP CORCORAN 115.00 LOAD==16.21(3.30) 4 34420 0 "4 " 0 # LOAD-DROP CORCORAN 115.00 LOAD==17.81(3.61) 0 # # # (108) BUS FAULT 34426 "ALPAUGH" # 1 34426 34391 "1" 0 # LINE from ALPAUGH 115.00 to QUEBECTP 115.00 1 34426 34700 "1" 0 # LINE from ALPAUGH 115.00 to SMYRNA 115.00 4 34426 0 "2 " 0 # LOAD-DROP ALPAUGH 115.00 LOAD==5.62(1.14) 0 # # # (109) BUS FAULT 34430 "HENRETTA" # 1 34430 34521 "1" 0 # LINE from HENRETTA 115.00 to LEPRNOFD 115.00 2 34430 30881 "3" 0 # TRAN from HENRETTA 115.00 to HENRIETA 230.00 0 # # # (110) BUS FAULT 34452 "WISHON" # 1 34452 34260 "1" 0 # LINE from WISHON 70.00 to SJNO2 70.00 1 34452 34491 "1" 0 # LINE from WISHON 70.00 to AUBRYTP 70.00 2 34452 34658 "1" 0 # TRAN from WISHON 70.00 to WISHON 2.30 0 # # # (111) BUS FAULT 34460 "GUERNSEY" # 1 34460 34462 "1" 0 # LINE from GUERNSEY 70.00 to GUR3TPT 70.00 1 34460 34528 "1" 0 # LINE from GUERNSEY 70.00 to CORCORAN 70.00 4 34460 0 "1 " 0 # LOAD-DROP GUERNSEY 70.00 LOAD==10.51(2.13) 0 # # # (112) BUS FAULT 34464 "COPPRMNE" # 1 34464 34454 "1" 0 # LINE from COPPRMNE 70.00 to RIVERROC 70.00 1 34464 34478 "1" 0 # LINE from COPPRMNE 70.00 to TVY VLLY 70.00 1 34464 34638 "1" 0 # LINE from COPPRMNE 70.00 to FRANTDM 70.00 1 34464 34491 "1" 0 # LINE from COPPRMNE 70.00 to AUBRYTP 70.00 4 34464 0 "1 " 0 # LOAD-DROP COPPRMNE 70.00 LOAD==22.96(4.67) 0 # # # (113) BUS FAULT 34466 "BIOLA"

Page 106: To determine the system impacts caused by the Project

A-85 GWF Henrietta SISAppendix A

# 1 34466 34264 "1" 0 # LINE from BIOLA 70.00 to EL PECO 70.00 1 34466 34482 "1" 0 # LINE from BIOLA 70.00 to OLDKERN 70.00 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 0 # # # (114) BUS FAULT 34472 "SAN JOQN" # 1 34472 34471 "1" 0 # LINE from SAN JOQN 70.00 to SNJQJCT 70.00 1 34472 34473 "1" 0 # LINE from SAN JOQN 70.00 to SNJQTP 70.00 4 34472 0 "1 " 0 # LOAD-DROP SAN JOQN 70.00 LOAD==6.44(1.31) 4 34472 0 "2 " 0 # LOAD-DROP SAN JOQN 70.00 LOAD==3.92(0.79) 0 # # # (115) BUS FAULT 34474 "HELM" # 1 34474 34471 "1" 0 # LINE from HELM 70.00 to SNJQJCT 70.00 1 34474 34473 "1" 0 # LINE from HELM 70.00 to SNJQTP 70.00 1 34474 34556 "1" 0 # LINE from HELM 70.00 to STRD JCT 70.00 1 34474 34564 "1" 0 # LINE from HELM 70.00 to STROUD 70.00 2 34474 30873 "1" 0 # TRAN from HELM 70.00 to HELM 230.00 0 # # # (116) BUS FAULT 34478 "TVY VLLY" # 1 34478 34464 "1" 0 # LINE from TVY VLLY 70.00 to COPPRMNE 70.00 1 34478 34492 "1" 0 # LINE from TVY VLLY 70.00 to REEDLEY 70.00 4 34478 0 "1 " 0 # LOAD-DROP TVY VLLY 70.00 LOAD==10.27(2.09) 0 # # # (117) BUS FAULT 34480 "KEARNEY" # 1 34480 34481 "1" 0 # LINE from KEARNEY 70.00 to FRWWTAP 70.00 1 34480 34482 "1" 0 # LINE from KEARNEY 70.00 to OLDKERN 70.00 1 34480 34512 "1" 0 # LINE from KEARNEY 70.00 to CARUTHRS 70.00 2 34480 30830 "2" 0 # TRAN from KEARNEY 70.00 to KEARNEY 230.00 0 # # # (118) BUS FAULT 34484 "KERMAN" # 1 34484 34475 "1" 0 # LINE from KERMAN 70.00 to AGRCJCT 70.00 1 34484 34481 "1" 0 # LINE from KERMAN 70.00 to FRWWTAP 70.00 4 34484 0 "1 " 0 # LOAD-DROP KERMAN 70.00 LOAD==19.44(3.95) 4 34484 0 "2 " 0 # LOAD-DROP KERMAN 70.00 LOAD==11.78(2.39) 0 # # # (119) BUS FAULT 34486 "CALIFRNV" # 1 34486 34488 "1" 0 # LINE from CALIFRNV 70.00 to SANGER 70.00 1 34486 34488 "2" 0 # LINE from CALIFRNV 70.00 to SANGER 70.00 0 # # # (120) BUS FAULT 34488 "SANGER" # 1 34488 34486 "1" 0 # LINE from SANGER 70.00 to CALIFRNV 70.00 1 34488 34486 "2" 0 # LINE from SANGER 70.00 to CALIFRNV 70.00 1 34488 34366 "1" 0 # LINE from SANGER 70.00 to SANGER 115.00 1 34488 34487 "1" 0 # LINE from SANGER 70.00 to SNGRJCT 70.00 2 34488 34590 "1" 0 # TRAN from SANGER 70.00 to SANGR3T 115.00 0 # # # (121) BUS FAULT 34492 "REEDLEY"

Page 107: To determine the system impacts caused by the Project

A-86 GWF Henrietta SISAppendix A

# 1 34492 34478 "1" 0 # LINE from REEDLEY 70.00 to TVY VLLY 70.00 1 34492 34490 "1" 0 # LINE from REEDLEY 70.00 to PARLIER 70.00 1 34492 34497 "1" 0 # LINE from REEDLEY 70.00 to DNUBAJCT 70.00 1 34492 34526 "1" 0 # LINE from REEDLEY 70.00 to ORSI JCT 70.00 2 34492 34380 "1" 0 # TRAN from REEDLEY 70.00 to REEDLEY 115.00 2 34492 34380 "2" 0 # TRAN from REEDLEY 70.00 to REEDLEY 115.00 4 34492 0 "1 " 0 # LOAD-DROP REEDLEY 70.00 LOAD==17.42(3.54) 0 # # # (122) BUS FAULT 34500 "DINUBA" # 1 34500 34496 "1" 0 # LINE from DINUBA 70.00 to STCRRL J 70.00 1 34500 34497 "1" 0 # LINE from DINUBA 70.00 to DNUBAJCT 70.00 4 34500 0 "1 " 0 # LOAD-DROP DINUBA 70.00 LOAD==19.23(3.91) 4 34500 0 "2 " 0 # LOAD-DROP DINUBA 70.00 LOAD==9.33(1.90) 0 # # # (123) BUS FAULT 34512 "CARUTHRS" # 1 34512 34480 "1" 0 # LINE from CARUTHRS 70.00 to KEARNEY 70.00 1 34512 34510 "1" 0 # LINE from CARUTHRS 70.00 to CMDN JCT 70.00 4 34512 0 "1 " 0 # LOAD-DROP CARUTHRS 70.00 LOAD==19.63(3.98) 0 # # # (124) BUS FAULT 34518 "LEMOORE" # 1 34518 34520 "1" 0 # LINE from LEMOORE 70.00 to LPRNO TP 70.00 1 34518 34522 "1" 0 # LINE from LEMOORE 70.00 to HNFRD SW 70.00 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) 0 # # # (125) BUS FAULT 34528 "CORCORAN" # 1 34528 34460 "1" 0 # LINE from CORCORAN 70.00 to GUERNSEY 70.00 1 34528 34530 "1" 0 # LINE from CORCORAN 70.00 to BSWLL TP 70.00 2 34528 34420 "2" 0 # TRAN from CORCORAN 70.00 to CORCORAN 115.00 0 # # # (126) BUS FAULT 34540 "HENRITTA" # 1 34540 34514 "1" 0 # LINE from HENRITTA 70.00 to MUSLSLGH 70.00 1 34540 34520 "1" 0 # LINE from HENRITTA 70.00 to LPRNO TP 70.00 1 34540 34537 "1" 0 # LINE from HENRITTA 70.00 to GWF_HENR 70.00 1 34540 34542 "1" 0 # LINE from HENRITTA 70.00 to JCBSCRNR 70.00 1 34540 34544 "1" 0 # LINE from HENRITTA 70.00 to TLRE LKE 70.00 2 34540 30881 "2" 0 # TRAN from HENRITTA 70.00 to HENRIETA 230.00 2 34540 30881 "4" 0 # TRAN from HENRITTA 70.00 to HENRIETA 230.00 4 34540 0 "1 " 0 # LOAD-DROP HENRITTA 70.00 LOAD==8.20(1.67) 0 # # # (127) BUS FAULT 34544 "TLRE LKE" # 1 34544 34540 "1" 0 # LINE from TLRE LKE 70.00 to HENRITTA 70.00 1 34544 34550 "1" 0 # LINE from TLRE LKE 70.00 to CHEVPLIN 70.00 1 34544 34580 "1" 0 # LINE from TLRE LKE 70.00 to BDGR HLL 70.00 4 34544 0 "1 " 0 # LOAD-DROP TLRE LKE 70.00 LOAD==6.79(1.38) 0 # # # (128) BUS FAULT 34552 "GATES" # 1 34552 34548 "1" 0 # LINE from GATES 70.00 to KETTLEMN 70.00

Page 108: To determine the system impacts caused by the Project

A-87 GWF Henrietta SISAppendix A

1 34552 34184 "1" 0 # LINE from GATES 70.00 to GATS2_TP 70.00 1 34552 34558 "1" 0 # LINE from GATES 70.00 to HURON 70.00 1 34552 34558 "2" 0 # LINE from GATES 70.00 to HURON 70.00 1 34552 34578 "1" 0 # LINE from GATES 70.00 to JACALITO 70.00 2 34552 34378 "2" 0 # TRAN from GATES 70.00 to GATES 115.00 0 # # # (129) BUS FAULT 34558 "HURON" # 1 34558 34552 "1" 0 # LINE from HURON 70.00 to GATES 70.00 1 34558 34552 "2" 0 # LINE from HURON 70.00 to GATES 70.00 1 34558 34560 "1" 0 # LINE from HURON 70.00 to CALFLAX 70.00 4 34558 34552 "1 " 1 # LOAD-TRANSFER HURON 70.00 TO GATES 70.00 LOAD==15.33(3.11) 0 # # # (130) BUS FAULT 34562 "SCHLNDLR" # 1 34562 34556 "1" 0 # LINE from SCHLNDLR 70.00 to STRD JCT 70.00 1 34562 34560 "1" 0 # LINE from SCHLNDLR 70.00 to CALFLAX 70.00 1 34562 34566 "1" 0 # LINE from SCHLNDLR 70.00 to PLSNTVLY 70.00 2 34562 34354 "1" 0 # TRAN from SCHLNDLR 70.00 to SCHINDLR 115.00 4 34562 0 "1 " 0 # LOAD-DROP SCHLNDLR 70.00 LOAD==9.59(1.95) 0 # # # (131) BUS FAULT 34564 "STROUD" # 1 34564 34556 "1" 0 # LINE from STROUD 70.00 to STRD JCT 70.00 1 34564 34474 "1" 0 # LINE from STROUD 70.00 to HELM 70.00 4 34564 0 "1 " 0 # LOAD-DROP STROUD 70.00 LOAD==13.09(2.66) 0 # # # (132) BUS FAULT 34570 "COLNGA 2" # 1 34570 34184 "1" 0 # LINE from COLNGA 2 70.00 to GATS2_TP 70.00 1 34570 34566 "1" 0 # LINE from COLNGA 2 70.00 to PLSNTVLY 70.00 1 34570 34572 "1" 0 # LINE from COLNGA 2 70.00 to TORNADO 70.00 2 34570 34652 "1" 0 # TRAN from COLNGA 2 70.00 to CHV.COAL 9.11 4 34570 0 "1 " 0 # LOAD-DROP COLNGA 2 70.00 LOAD==8.23(1.67) 0 # # # (133) BUS FAULT 34574 "COLNGA 1" # 1 34574 34572 "1" 0 # LINE from COLNGA 1 70.00 to TORNADO 70.00 1 34574 34578 "1" 0 # LINE from COLNGA 1 70.00 to JACALITO 70.00 1 34574 36354 "1" 0 # LINE from COLNGA 1 70.00 to SAN MIGL 70.00 4 34574 0 "1 " 0 # LOAD-DROP COLNGA 1 70.00 LOAD==9.34(1.90) 4 34574 0 "2 " 0 # LOAD-DROP COLNGA 1 70.00 LOAD==9.99(2.03) 0 # # # (134) BUS FAULT 34576 "KNGLOBUS" # 1 34576 34456 "1" 0 # LINE from KNGLOBUS 70.00 to HRDWK TP 70.00 1 34576 34508 "1" 0 # LINE from KNGLOBUS 70.00 to CAMDEN 70.00 2 34576 34418 "2" 0 # TRAN from KNGLOBUS 70.00 to KINGSBRG 115.00 0 # # -1 # EOF

Page 109: To determine the system impacts caused by the Project

A-88 GWF Henrietta SISAppendix A

Summer Off-Peak Category B Contingencies # Q272 2013 sumop category b contingency list # Yosemite and Fresno Divisions Zones 313 and 314 # # 2013 sumop category b contingency list # Yosemite Zone 313 # # # (1) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (2) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 0 # # # (3) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (4) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (5) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (6) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (7) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 0 # # # (8) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (9) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 110: To determine the system impacts caused by the Project

A-89 GWF Henrietta SISAppendix A

1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (10) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30793 "1 " 0 # line from PANOCHE 230.00 BRKR to (3) PANO_EC 230.00 2 30793 34326 "1 " 0 # TRAN from PANO_EC 230.00 (3) to (1) PANO_BS1 13.80 2 30793 34327 "1 " 0 # TRAN from PANO_EC 230.00 (3) to (1) PANO_BS2 13.80 4 34326 0 "ss" 0 # LOAD-DROP PANO_BS1 13.80 LOAD==4.50(2.49) 4 34327 0 "ss" 0 # LOAD-DROP PANO_BS2 13.80 LOAD==4.50(2.49) 3 34326 0 "1 " 0 # GEN-DROP PANO_BS1 13.80 GEN==102.50(20.25) 3 34326 0 "2 " 0 # GEN-DROP PANO_BS1 13.80 GEN==102.50(20.25) 3 34327 0 "3 " 0 # GEN-DROP PANO_BS2 13.80 GEN==102.50(20.25) 3 34327 0 "4 " 0 # GEN-DROP PANO_BS2 13.80 GEN==102.50(20.25) 0 # # # (11) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # sumop outage 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Kearney 230 kV line outage HTT/RAS 0 # # # (12) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 0 # # # (13) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (14) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (15) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) 0 # # # (16) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00

Page 111: To determine the system impacts caused by the Project

A-90 GWF Henrietta SISAppendix A

1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) 0 # # # (17) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30806 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR Q196 230.00 0 # # # (18) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30806 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR Q196 230.00 0 # # # (19) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line 0 # # # (20) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line 0 # # # (21) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34017 34010 "1 " 0 # line from CRWS LDG 60.00 (1) to (3) CRWS LDJ 60.00 1 34010 34006 "1 " 0 # line from CRWS LDJ 60.00 (3) to BRKR PATTERSN 60.00 1 34010 34012 "1 " 0 # line from CRWS LDJ 60.00 (3) to (2) GUSTN JT 60.00 1 34012 34014 "1 " 0 # line from GUSTN JT 60.00 (2) to BRKR NEWMAN 60.00 4 34017 0 "1 " 0 # LOAD-DROP CRWS LDG 60.00 LOAD==3.73(0.17) 1 34016 34017 "1 " 1 # Switches in Crows Landing SW 57 to transfer load 4 34017 0 "**" 1 # Restore Load at Crows Landing 0 # # # (22) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00 2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80

Page 112: To determine the system impacts caused by the Project

A-91 GWF Henrietta SISAppendix A

2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94) 4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11) 3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) 0 # # # (23) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 0 # # # (24) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34104 34108 "1 " 0 # line from ATWATER 115.00 BRKR to (3) CRESEY T 115.00 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (1) ATWATR J 115.00 1 34108 34114 "1 " 0 # line from CRESEY T 115.00 (3) to (3) JRWD GEN 115.00 1 34114 34124 "1 " 0 # line from JRWD GEN 115.00 (3) to (2) JR WOOD 115.00 2 34114 34332 "1 " 0 # TRAN from JRWD GEN 115.00 (3) to (1) JRWCOGEN 9.11 1 34124 34140 "1 " 0 # line from JR WOOD 115.00 (2) to (1) CRESSEY 115.00 4 34124 0 "1 " 0 # LOAD-DROP JR WOOD 115.00 LOAD==11.70(10.32) 4 34140 0 "1 " 0 # LOAD-DROP CRESSEY 115.00 LOAD==19.02(3.86) 3 34332 0 "1 " 0 # GEN-DROP JRWCOGEN 9.11 GEN==3.80(5.40) 0 # # # (25) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34105 34121 "1 " 0 # line from CERTANJ1 115.00 (2) to (3) SHARON T 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34121 34128 "1 " 0 # line from SHARON T 115.00 (3) to (3) OAKH_JCT 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34128 34123 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) K1-JCT 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) 0 # # # (26) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (3) ATWATR J 115.00 1 34110 34130 "1 " 0 # line from ATWATR J 115.00 (3) to (2) LIVNGSTN 115.00

Page 113: To determine the system impacts caused by the Project

A-92 GWF Henrietta SISAppendix A

1 34110 34144 "1 " 0 # line from ATWATR J 115.00 (3) to BRKR MERCED 115.00 1 34130 34132 "1 " 0 # line from LIVNGSTN 115.00 (2) to (1) GALLO 115.00 4 34130 0 "3 " 0 # LOAD-DROP LIVNGSTN 115.00 LOAD==24.58(5.00) 4 34132 0 "1 " 0 # LOAD-DROP GALLO 115.00 LOAD==4.30(3.68) 0 # # # (27) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34112 34116 "1 " 0 # line from EXCHEQUR 115.00 BRKR to BRKR LE GRAND 115.00 3 34306 0 "1 " 0 # Exchequer Unit will trip for this outage 4 34228 0 "**" 0 # Mariposa Loads will drop if bus is below 64 kV, this is anticipate 0 # # # (28) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34116 34134 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR WILSON A 115.00 0 # # # (29) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 0 # # # (30) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) 0 # # # (31) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 0 # # # (32) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34136 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR WILSON B 115.00 0 # # # (33) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34144 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR MERCED 115.00 0 # # # (34) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 114: To determine the system impacts caused by the Project

A-93 GWF Henrietta SISAppendix A

1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 0 # # # (35) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34136 34144 "2 " 0 # line from WILSON B 115.00 BRKR to BRKR MERCED 115.00 0 # # # (36) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34141 34148 "1 " 0 # line from PAN2_TAP 115.00 (2) to (2) CHENY 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80 1 34148 34149 "1 " 0 # line from CHENY 115.00 (2) to (3) CHENYT 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (37) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34150 34154 "1 " 0 # line from NEWHALL 115.00 (2) to BRKR DAIRYLND 115.00 1 34150 34178 "1 " 0 # line from NEWHALL 115.00 (2) to (3) MADERAPR 115.00 1 34178 34156 "1 " 0 # line from MADERAPR 115.00 (3) to BRKR MENDOTA 115.00 2 34178 34179 "1 " 0 # TRAN from MADERAPR 115.00 (3) to (1) MADERA_G 13.80 4 34150 0 "2 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==8.55(1.73) 4 34150 0 "3 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==10.62(2.16) 4 34179 0 "ss" 0 # LOAD-DROP MADERA_G 13.80 LOAD==3.60(0.85) 3 34179 0 "1 " 0 # GEN-DROP MADERA_G 13.80 GEN==28.60(6.34) 0 # # # (38) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34157 34156 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR MENDOTA 115.00 1 34157 34158 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR PANOCHE 115.00 3 34186 0 "1 " 0 # DG_PAN Unit trips for Panoche - Mendota 115 kV outage 0 # # # (39) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34158 34189 "1 " 0 # line from PANOCHE 115.00 BRKR to (3) STARWOOD 115.00 2 34189 34328 "1 " 0 # TRAN from STARWOOD 115.00 (3) to (1) STARGT1 13.80 2 34189 34329 "1 " 0 # TRAN from STARWOOD 115.00 (3) to (1) STARGT2 13.80 4 34328 0 "ss" 0 # LOAD-DROP STARGT1 13.80 LOAD==1.00(0.55) 4 34329 0 "ss" 0 # LOAD-DROP STARGT2 13.80 LOAD==1.00(0.55) 3 34328 0 "1 " 0 # GEN-DROP STARGT1 13.80 GEN==60.94(9.59) 3 34329 0 "2 " 0 # GEN-DROP STARGT2 13.80 GEN==60.94(9.59) 0 #

Page 115: To determine the system impacts caused by the Project

A-94 GWF Henrietta SISAppendix A

# # (40) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34158 34350 "1 " 0 # line from PANOCHE 115.00 BRKR to (2) KAMM 115.00 1 34350 34352 "1 " 0 # line from KAMM 115.00 (2) to (2) CANTUA 115.00 1 34352 34432 "1 " 0 # line from CANTUA 115.00 (2) to (2) WESTLNDS 115.00 1 34432 34354 "1 " 0 # line from WESTLNDS 115.00 (2) to BRKR SCHINDLR 115.00 4 34350 0 "1 " 0 # LOAD-DROP KAMM 115.00 LOAD==3.85(1.75) 4 34352 0 "1 " 0 # LOAD-DROP CANTUA 115.00 LOAD==16.79(3.41) 4 34432 0 "16" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==0.94(0.23) 4 34432 0 "18" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==1.21(0.32) 0 # # # (41) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34159 34158 "1 " 0 # line from PANOCHEJ 115.00 (3) to BRKR PANOCHE 115.00 1 34159 34160 "1 " 0 # line from PANOCHEJ 115.00 (3) to (2) HAMMONDS 115.00 1 34159 34180 "1 " 0 # line from PANOCHEJ 115.00 (3) to (3) OXFRDJCT 115.00 1 34160 34161 "1 " 0 # line from HAMMONDS 115.00 (2) to (3) DFSTP 115.00 1 34161 34162 "1 " 0 # line from DFSTP 115.00 (3) to BRKR ORO LOMA 115.00 1 34161 34164 "1 " 0 # line from DFSTP 115.00 (3) to (1) DFS 115.00 1 34180 34166 "1 " 0 # line from OXFRDJCT 115.00 (3) to (1) OXFORD 115.00 1 34180 34181 "1 " 0 # line from OXFRDJCT 115.00 (3) to (3) WSTLDJCT 115.00 1 34181 34182 "1 " 0 # line from WSTLDJCT 115.00 (3) to (1) WSTLD1RA 115.00 1 34181 34183 "1 " 0 # line from WSTLDJCT 115.00 (3) to (3) LUISJCT 115.00 1 34183 34163 "1 " 0 # line from LUISJCT 115.00 (3) to (1) LUIS_#3 115.00 1 34183 34165 "1 " 0 # line from LUISJCT 115.00 (3) to (1) LUIS_#5 115.00 4 34160 0 "1 " 0 # LOAD-DROP HAMMONDS 115.00 LOAD==10.00(2.03) 4 34164 0 "1 " 0 # LOAD-DROP DFS 115.00 LOAD==1.37(1.06) 4 34166 0 "1 " 0 # LOAD-DROP OXFORD 115.00 LOAD==3.87(1.76) 4 34182 0 "1 " 0 # LOAD-DROP WSTLD1RA 115.00 LOAD==2.98(0.71) 4 34163 0 "1 " 0 # LOAD-DROP LUIS_#3 115.00 LOAD==3.30(0.78) 4 34165 0 "1 " 0 # LOAD-DROP LUIS_#5 115.00 LOAD==3.40(0.81) 0 # # # (42) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34172 34170 "1 " 0 # line from WESTLAND 70.00 (2) to (1) WESIX 70.00 1 34172 34271 "1 " 0 # line from WESTLAND 70.00 (2) to (3) WSTLDJCT 70.00 1 34271 34269 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) BIOMSJCT 70.00 1 34271 34469 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) GFFNJCT 70.00 1 34269 34268 "1 " 0 # line from BIOMSJCT 70.00 (3) to BRKR MENDOTA 70.00 1 34269 34270 "1 " 0 # line from BIOMSJCT 70.00 (3) to (2) BIOMASS 70.00 2 34270 34334 "1 " 0 # TRAN from BIOMASS 70.00 (2) to (1) BIO PWR 9.11

Page 116: To determine the system impacts caused by the Project

A-95 GWF Henrietta SISAppendix A

1 34469 34470 "1 " 0 # line from GFFNJCT 70.00 (3) to (1) GIFFEN 70.00 1 34469 34471 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) SNJQJCT 70.00 1 34471 34472 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR SAN JOQN 70.00 1 34471 34474 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR HELM 70.00 4 34172 0 "1 " 0 # LOAD-DROP WESTLAND 70.00 LOAD==3.20(0.76) 4 34170 0 "1 " 0 # LOAD-DROP WESIX 70.00 LOAD==1.60(0.38) 4 34470 0 "1 " 0 # LOAD-DROP GIFFEN 70.00 LOAD==9.59(1.95) 3 34334 0 "1 " 0 # GEN-DROP BIO PWR 9.11 GEN==21.80(10.99) 1 34472 34473 "1 " 1 # Switches in San Joaquin CB22 to transfer load 4 34472 0 "**" 1 # Restore Load at San Joaquin 0 # # # (43) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34218 "1 " 0 # line from ORO LOMA 70.00 BRKR to (2) DOS PALS 70.00 1 34218 34216 "1 " 0 # line from DOS PALS 70.00 (2) to BRKR SNTA RTA 70.00 4 34218 0 "1 " 0 # LOAD-DROP DOS PALS 70.00 LOAD==10.29(2.09) 0 # # # (44) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00 1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93) 0 # # # (45) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34234 "1 " 0 # line from ORO LOMA 70.00 BRKR to (2) POSO J1 70.00 1 34234 34266 "1 " 0 # line from POSO J1 70.00 (2) to (2) FIREBAGH 70.00 1 34266 34267 "1 " 0 # line from FIREBAGH 70.00 (2) to (2) TOMATAK 70.00 1 34267 34268 "1 " 0 # line from TOMATAK 70.00 (2) to BRKR MENDOTA 70.00 4 34266 0 "1 " 0 # LOAD-DROP FIREBAGH 70.00 LOAD==11.13(2.26) 4 34267 0 "1 " 0 # LOAD-DROP TOMATAK 70.00 LOAD==6.40(4.97) 0 # # # (46) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34202 34203 "1 " 0 # line from MERCED 70.00 BRKR to (3) ELNIDOTP 70.00 1 34203 34205 "1 " 0 # line from ELNIDOTP 70.00 (3) to (2) ELNIDO 70.00 1 34203 34236 "1 " 0 # line from ELNIDOTP 70.00 (3) to (1) POSO J2 70.00

Page 117: To determine the system impacts caused by the Project

A-96 GWF Henrietta SISAppendix A

2 34205 34330 "1 " 0 # TRAN from ELNIDO 70.00 (2) to (1) ELNIDO 13.80 4 34330 0 "ss" 0 # LOAD-DROP ELNIDO 13.80 LOAD==2.00(1.11) 3 34330 0 "1 " 0 # GEN-DROP ELNIDO 13.80 GEN==12.50(5.69) 0 # # # (47) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34202 34230 "1 " 0 # line from MERCED 70.00 BRKR to BRKR MRCDFLLS 70.00 0 # # # (48) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34204 34212 "1 " 0 # line from LIVNGSTN 70.00 (1) to (3) LVNGSTNT 70.00 1 34212 34206 "1 " 0 # line from LVNGSTNT 70.00 (3) to BRKR CANAL 70.00 1 34212 34210 "1 " 0 # line from LVNGSTNT 70.00 (3) to (2) SNTA NLA 70.00 1 34210 34208 "1 " 0 # line from SNTA NLA 70.00 (2) to (2) CHEVPIPE 70.00 1 34208 34214 "1 " 0 # line from CHEVPIPE 70.00 (2) to BRKR LOS BANS 70.00 4 34204 0 "2 " 0 # LOAD-DROP LIVNGSTN 70.00 LOAD==5.51(1.12) 4 34210 0 "1 " 0 # LOAD-DROP SNTA NLA 70.00 LOAD==6.75(1.37) 4 34210 0 "2 " 0 # LOAD-DROP SNTA NLA 70.00 LOAD==9.50(1.93) 4 34208 0 "1 " 0 # LOAD-DROP CHEVPIPE 70.00 LOAD==0.63(0.42) 0 # # # (49) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34206 34216 "1 " 0 # line from CANAL 70.00 BRKR to BRKR SNTA RTA 70.00 0 # # # (50) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34214 34278 "1 " 0 # line from LOS BANS 70.00 BRKR to (2) PCHCO PP 70.00 1 34278 34280 "1 " 0 # line from PCHCO PP 70.00 (2) to (2) INTL TUR 70.00 2 34280 34342 "1 " 0 # TRAN from INTL TUR 70.00 (2) to (1) INT.TURB 9.11 4 34278 0 "1 " 0 # LOAD-DROP PCHCO PP 70.00 LOAD==18.00(4.10) 3 34342 0 "1 " 0 # GEN-DROP INT.TURB 9.11 GEN==1.10(0.00) 0 # # # (51) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34214 34282 "1 " 0 # line from LOS BANS 70.00 BRKR to (2) ONLL PMP 69.00 2 34282 34316 "1 " 0 # TRAN from ONLL PMP 69.00 (2) to (1) ONEILPMP 9.11 4 34282 0 "1 " 0 # LOAD-DROP ONLL PMP 69.00 LOAD==6.00(1.20) 3 34316 0 "1 " 0 # GEN-DROP ONEILPMP 9.11 GEN==0.50(0.00) 0 # # # (52) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34228 34232 "1 " 0 # line from MARIPOS2 70.00 (1) to BRKR EXCHEQUR 70.00 4 34228 0 "1 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.01(1.83) 4 34228 0 "2 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.37(1.90)

Page 118: To determine the system impacts caused by the Project

A-97 GWF Henrietta SISAppendix A

1 34228 34244 "1 " 1 # Switches in Mariposa SW 39 to transfer load 4 34228 0 "**" 1 # Restore Load at Mariposa 0 # # # (53) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34232 34242 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (2) BER VLLY 70.00 1 34242 34244 "1 " 0 # line from BER VLLY 70.00 (2) to (2) BRCEBG J 70.00 1 34244 34246 "1 " 0 # line from BRCEBG J 70.00 (2) to (3) SAXONCRK 70.00 1 34246 34248 "1 " 0 # line from SAXONCRK 70.00 (3) to (2) INDN FLT 70.00 2 34246 34346 "1 " 0 # TRAN from SAXONCRK 70.00 (3) to (1) SAXNCK L 4.16 1 34248 34250 "1 " 0 # line from INDN FLT 70.00 (2) to (1) YOSEMITE 70.00 4 34242 0 "1 " 0 # LOAD-DROP BER VLLY 70.00 LOAD==5.91(1.20) 4 34246 0 "1 " 0 # LOAD-DROP SAXONCRK 70.00 LOAD==0.03(0.02) 4 34248 0 "1 " 0 # LOAD-DROP INDN FLT 70.00 LOAD==2.02(0.41) 4 34250 0 "1 " 0 # LOAD-DROP YOSEMITE 70.00 LOAD==2.90(0.00) 0 # # # (54) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita 0 # # # (55) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34252 34256 "1 " 0 # line from MADERA 70.00 BRKR to BRKR BORDEN 70.00 0 # # # (56) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34252 34256 "2 " 0 # line from MADERA 70.00 BRKR to BRKR BORDEN 70.00 0 # # # (57) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34256 34240 "1 " 0 # line from BORDEN 70.00 BRKR to BRKR GLASS 70.00 0 # #

Page 119: To determine the system impacts caused by the Project

A-98 GWF Henrietta SISAppendix A

# (58) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34256 34262 "1 " 0 # line from BORDEN 70.00 BRKR to (2) CASSIDY 70.00 1 34262 34454 "1 " 0 # line from CASSIDY 70.00 (2) to (2) RIVERROC 70.00 1 34454 34464 "1 " 0 # line from RIVERROC 70.00 (2) to BRKR COPPRMNE 70.00 4 34262 0 "1 " 0 # LOAD-DROP CASSIDY 70.00 LOAD==14.31(2.90) 4 34454 0 "1 " 0 # LOAD-DROP RIVERROC 70.00 LOAD==2.01(1.83) 0 # # # (59) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34259 34261 "1 " 0 # line from NRTHFORK 70.00 (3) to (2) SJNO3 70.00 1 34259 34260 "1 " 0 # line from NRTHFORK 70.00 (3) to (3) SJNO2 70.00 2 34259 34340 "1 " 0 # TRAN from NRTHFORK 70.00 (3) to (1) N.FORK E 9.11 2 34261 34633 "1 " 0 # TRAN from SJNO3 70.00 (2) to (1) SJ3GEN 9.11 1 34260 34452 "1 " 0 # line from SJNO2 70.00 (3) to BRKR WISHON 70.00 2 34260 34631 "1 " 0 # TRAN from SJNO2 70.00 (3) to (1) SJ2GEN 9.11 4 34261 0 "2 " 0 # LOAD-DROP SJNO3 70.00 LOAD==6.95(1.41) 4 34260 0 "2 " 0 # LOAD-DROP SJNO2 70.00 LOAD==3.22(0.66) 4 34340 0 "1 " 0 # LOAD-DROP N.FORK E 9.11 LOAD==1.21(0.25) 3 34633 0 "1 " 0 # GEN-DROP SJ3GEN 9.11 GEN==1.00(0.00) 3 34631 0 "1 " 0 # GEN-DROP SJ2GEN 9.11 GEN==2.00(0.00) 0 # # # (60) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34321 34226 "1 " 0 # line from MCSWAINJ 70.00 (3) to (2) MC SWAIN 70.00 1 34321 34230 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR MRCDFLLS 70.00 1 34321 34232 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR EXCHEQUR 70.00 2 34226 34320 "1 " 0 # TRAN from MC SWAIN 70.00 (2) to (1) MCSWAIN 9.11 3 34320 0 "1 " 0 # GEN-DROP MCSWAIN 9.11 GEN==10.00(2.00) 0 # # # (61) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Melones - Wilson line 0 # # # (62) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (63) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30765 (30069) 30050 34302 : 2 30765 30050 "1 " 0 # TRAN from LOSBANOS 230.00 BRKR to (1) LOSBANOS 500.00 0

Page 120: To determine the system impacts caused by the Project

A-99 GWF Henrietta SISAppendix A

# # # (64) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30790 (30791) 34158 34310 : 2 30790 34158 "1 " 0 # TRAN from PANOCHE 230.00 BRKR to (1) PANOCHE 115.00 0 # # # (65) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 30790 34158 "2 " 0 # TRAN from PANOCHE 230.00 BRKR to BRKR PANOCHE 115.00 0 # # # (66) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 34112 (34176) 34232 34306 : 2 34112 34232 "1 " 0 # TRAN from EXCHEQUR 115.00 BRKR to (4) EXCHEQUR 70.00 1 34232 34228 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) MARIPOS2 70.00 1 34232 34242 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) BER VLLY 70.00 1 34232 34321 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) MCSWAINJ 70.00 4 34228 0 "1 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.01(1.83) 4 34228 0 "2 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.37(1.90) 1 34228 34244 "1 " 1 # Switches in Mariposa SW 39 to transfer load 4 34228 0 "**" 1 # Restore Load at Mariposa 0 # # # (67) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34134 30800 "1 " 0 # TRAN from WILSON A 115.00 BRKR to BRKR WILSON 230.00 0 # # # (68) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34136 30800 "2 " 0 # TRAN from WILSON B 115.00 BRKR to BRKR WILSON 230.00 0 # # # (69) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 34144 (34146) 34202 34312 : 2 34144 34202 "2 " 0 # TRAN from MERCED 115.00 BRKR to (1) MERCED 70.00 0 # # # (70) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34200 34162 "2 " 0 # TRAN from ORO LOMA 70.00 BRKR to (3) ORO LOMA 115.00 1 34162 34161 "1 " 0 # line from ORO LOMA 115.00 BRKR to (1) DFSTP 115.00 1 34162 34168 "1 " 0 # line from ORO LOMA 115.00 BRKR to (1) EL NIDO 115.00 0 # # # (71) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) #

Page 121: To determine the system impacts caused by the Project

A-100 GWF Henrietta SISAppendix A

2 34214 30765 "3 " 0 # TRAN from LOS BANS 70.00 BRKR to BRKR LOSBANOS 230.00 0 # # # (72) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34214 30765 "4 " 0 # TRAN from LOS BANS 70.00 BRKR to BRKR LOSBANOS 230.00 0 # # # (73) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34256 30805 "1 " 0 # TRAN from BORDEN 70.00 BRKR to BRKR BORDEN 230.00 0 # # # (74) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34256 30805 "2 " 0 # TRAN from BORDEN 70.00 BRKR to BRKR BORDEN 230.00 0 # # # (75) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34268 34156 "1 " 0 # TRAN from MENDOTA 70.00 BRKR to (3) MENDOTA 115.00 1 34156 34178 "1 " 0 # line from MENDOTA 115.00 BRKR to (1) MADERAPR 115.00 1 34156 34157 "1 " 0 # line from MENDOTA 115.00 BRKR to (1) PANOCHET 115.00 4 34156 0 "1 " 0 # LOAD-DROP MENDOTA 115.00 LOAD==24.55(4.99) 0 # # # (76) B1 GENERATOR OUTAGE # 3 34142 0 "1" 0 # WHD_PAN2 13.80 PGEN=49.00 QGEN=-22.43 0 # # # (77) B1 GENERATOR OUTAGE # 3 34179 0 "1" 0 # MADERA_G 13.80 PGEN=28.60 QGEN=3.67 0 # # # (78) B1 GENERATOR OUTAGE # 3 34186 0 "1" 0 # DG_PAN1 13.80 PGEN=49.00 QGEN=-17.22 0 # # # (79) B1 GENERATOR OUTAGE # 3 34301 0 "1" 0 # CHOWCOGN 13.80 PGEN=50.00 QGEN=0.72 0 # # # (80) B1 GENERATOR OUTAGE # 3 34305 0 "1" 0 # CHWCHLA2 13.80 PGEN=12.50 QGEN=7.35 0 # # # (81) B1 GENERATOR OUTAGE #

Page 122: To determine the system impacts caused by the Project

A-101 GWF Henrietta SISAppendix A

3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (82) B1 GENERATOR OUTAGE # 3 34316 0 "1" 0 # ONEILPMP 9.11 PGEN=0.52 QGEN=0.00 0 # # # (83) B1 GENERATOR OUTAGE # 3 34320 0 "1" 0 # MCSWAIN 9.11 PGEN=10.00 QGEN=0.00 0 # # # (84) B1 GENERATOR OUTAGE # 3 34322 0 "1" 0 # MERCEDFL 9.11 PGEN=3.50 QGEN=2.00 0 # # # (85) B1 GENERATOR OUTAGE # 3 34326 0 "1" 0 # PANO_BS1 13.80 PGEN=102.50 QGEN=25.42 0 # # # (86) B1 GENERATOR OUTAGE # 3 34326 0 "2" 0 # PANO_BS1 13.80 PGEN=102.50 QGEN=25.42 0 # # # (87) B1 GENERATOR OUTAGE # 3 34327 0 "3" 0 # PANO_BS2 13.80 PGEN=102.50 QGEN=25.42 0 # # # (88) B1 GENERATOR OUTAGE # 3 34327 0 "4" 0 # PANO_BS2 13.80 PGEN=102.50 QGEN=25.42 0 # # # (89) B1 GENERATOR OUTAGE # 3 34328 0 "1" 0 # STARGT1 13.80 PGEN=60.94 QGEN=13.94 0 # # # (90) B1 GENERATOR OUTAGE # 3 34329 0 "2" 0 # STARGT2 13.80 PGEN=60.94 QGEN=13.94 0 # # # (91) B1 GENERATOR OUTAGE # 3 34330 0 "1" 0 # ELNIDO 13.80 PGEN=12.50 QGEN=4.15 0 # # # (92) B1 GENERATOR OUTAGE # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=3.80 QGEN=5.40 0 # #

Page 123: To determine the system impacts caused by the Project

A-102 GWF Henrietta SISAppendix A

# (93) B1 GENERATOR OUTAGE # 3 34334 0 "1" 0 # BIO PWR 9.11 PGEN=21.80 QGEN=8.92 0 # # # (94) B1 GENERATOR OUTAGE # 3 34342 0 "1" 0 # INT.TURB 9.11 PGEN=1.10 QGEN=0.00 0 # # # (95) B1 GENERATOR OUTAGE # 3 34631 0 "1" 0 # SJ2GEN 9.11 PGEN=2.00 QGEN=0.00 0 # # # (96) B1 GENERATOR OUTAGE # 3 34633 0 "1" 0 # SJ3GEN 9.11 PGEN=1.00 QGEN=0.00 0 # # # (97) B1 GENERATOR OUTAGE # 3 34335 0 "1" 0 # Q196GT1 16.50 PGEN=192.50 QGEN=31.08 0 # # # (98) B1 GENERATOR OUTAGE # 3 34336 0 "2" 0 # Q196GT2 16.50 PGEN=192.50 QGEN=31.08 0 # # # (99) B1 GENERATOR OUTAGE # 3 34337 0 "3" 0 # Q196ST1 13.80 PGEN=68.50 QGEN=11.04 0 # # # (100) B1 GENERATOR OUTAGE # 3 34338 0 "4" 0 # Q196ST2 13.80 PGEN=68.50 QGEN=11.04 0 # # # (101) B CAPACITOR OUTAGE # 6 30765 0 "v" 0 # LOSBANOS 230.0 SVD 0 # # # (102) B CAPACITOR OUTAGE # 6 30796 0 "v" 0 # STOREY 1 230.0 SVD 0 # # # (103) B CAPACITOR OUTAGE # 6 34134 0 "v" 0 # WILSON A 115.0 SVD 0 # # # (104) B CAPACITOR OUTAGE # 6 34252 0 "v" 0 # MADERA 70.0 SVD 0

Page 124: To determine the system impacts caused by the Project

A-103 GWF Henrietta SISAppendix A

# # # (105) B CAPACITOR OUTAGE # 6 34302 0 "v" 0 # L.BANS T 13.8 SVD 0 # # # (106) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Chowchilla 115 kV Line and Exchequer 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00 2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80 2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94) 4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11) 3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (107) L-1/G-1 OVERLAPPING OUTAGE # Chowchilla - Kerckhoff #2 115 kV Line and Exchequer 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34105 34121 "1 " 0 # line from CERTANJ1 115.00 (2) to (3) SHARON T 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34121 34128 "1 " 0 # line from SHARON T 115.00 (3) to (3) OAKH_JCT 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34128 34123 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) K1-JCT 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (108) L-1/G-1 OVERLAPPING OUTAGE # Atwater - El Capitan 115 kV Line and Exchequer 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00

Page 125: To determine the system impacts caused by the Project

A-104 GWF Henrietta SISAppendix A

1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (109) L-1/G-1 OVERLAPPING OUTAGE # Atwater - Merced 115 kV Line and Exchequer 1 34104 34108 "1 " 0 # line from ATWATER 115.00 BRKR to (3) CRESEY T 115.00 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (1) ATWATR J 115.00 1 34108 34114 "1 " 0 # line from CRESEY T 115.00 (3) to (3) JRWD GEN 115.00 1 34114 34124 "1 " 0 # line from JRWD GEN 115.00 (3) to (2) JR WOOD 115.00 2 34114 34332 "1 " 0 # TRAN from JRWD GEN 115.00 (3) to (1) JRWCOGEN 9.11 1 34124 34140 "1 " 0 # line from JR WOOD 115.00 (2) to (1) CRESSEY 115.00 4 34124 0 "1 " 0 # LOAD-DROP JR WOOD 115.00 LOAD==11.70(10.32) 4 34140 0 "1 " 0 # LOAD-DROP CRESSEY 115.00 LOAD==19.02(3.86) 3 34332 0 "1 " 0 # GEN-DROP JRWCOGEN 9.11 GEN==3.80(5.40) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (110) L-1/G-1 OVERLAPPING OUTAGE # Cressy Tap 115 kV Line and Exchequer 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (3) ATWATR J 115.00 1 34110 34130 "1 " 0 # line from ATWATR J 115.00 (3) to (2) LIVNGSTN 115.00 1 34110 34144 "1 " 0 # line from ATWATR J 115.00 (3) to BRKR MERCED 115.00 1 34130 34132 "1 " 0 # line from LIVNGSTN 115.00 (2) to (1) GALLO 115.00 4 34130 0 "3 " 0 # LOAD-DROP LIVNGSTN 115.00 LOAD==24.58(5.00) 4 34132 0 "1 " 0 # LOAD-DROP GALLO 115.00 LOAD==4.30(3.68) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (111) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Dairyland 115 kV Line and Exchequer 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (112) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Oro Loma 115 kV Line and Exchequer 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # #

Page 126: To determine the system impacts caused by the Project

A-105 GWF Henrietta SISAppendix A

# (113) L-1/G-1 OVERLAPPING OUTAGE # El Capitan - Wilson 115 kV Line and Exchequer 1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (114) L-1/G-1 OVERLAPPING OUTAGE # Dairyland - Mendota 115 kV Line and Exchequer 1 34150 34154 "1 " 0 # line from NEWHALL 115.00 (2) to BRKR DAIRYLND 115.00 1 34150 34178 "1 " 0 # line from NEWHALL 115.00 (2) to (3) MADERAPR 115.00 1 34178 34156 "1 " 0 # line from MADERAPR 115.00 (3) to BRKR MENDOTA 115.00 2 34178 34179 "1 " 0 # TRAN from MADERAPR 115.00 (3) to (1) MADERA_G 13.80 4 34150 0 "2 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==8.55(1.73) 4 34150 0 "3 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==10.62(2.16) 4 34179 0 "ss" 0 # LOAD-DROP MADERA_G 13.80 LOAD==3.60(0.85) 3 34179 0 "1 " 0 # GEN-DROP MADERA_G 13.80 GEN==28.60(6.34) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (115) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Mendota 115 kV Line and Exchequer 1 34157 34156 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR MENDOTA 115.00 1 34157 34158 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR PANOCHE 115.00 3 34186 0 "1 " 0 # DG_PAN Unit trips for Panoche - Mendota 115 kV outage # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (116) L-1/G-1 OVERLAPPING OUTAGE # Glass - Biola - Madera 70 kV Line and Exchequer 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (117) L-1/G-1 OVERLAPPING OUTAGE # Merced Falls - Exchequer 70 kV Line and Exchequer 1 34321 34226 "1 " 0 # line from MCSWAINJ 70.00 (3) to (2) MC SWAIN 70.00

Page 127: To determine the system impacts caused by the Project

A-106 GWF Henrietta SISAppendix A

1 34321 34230 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR MRCDFLLS 70.00 1 34321 34232 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR EXCHEQUR 70.00 2 34226 34320 "1 " 0 # TRAN from MC SWAIN 70.00 (2) to (1) MCSWAIN 9.11 3 34320 0 "1 " 0 # GEN-DROP MCSWAIN 9.11 GEN==10.00(2.00) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (118) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Canal - Oro Loma 70 kV Line and Exchequer 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00 1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (119) L-1/G-1 OVERLAPPING OUTAGE # Atwater - El Capitan 115 kV Line and JR Wood Cogen 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=4.00 QGEN=5.40 0 # # # (120) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Atwater #2 115 kV Line and JR Wood Cogen 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=4.00 QGEN=5.40 0 # # # (121) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Chowchilla 115 kV Line and Kerckhoff 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00

Page 128: To determine the system impacts caused by the Project

A-107 GWF Henrietta SISAppendix A

2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80 2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94) 4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11) 3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (122) L-1/G-1 OVERLAPPING OUTAGE # Exchequer - Le Grand 115 kV Line and Kerckhoff 1 34112 34116 "1 " 0 # line from EXCHEQUR 115.00 BRKR to BRKR LE GRAND 115.00 3 34306 0 "1 " 0 # Exchequer Unit will trip for this outage 4 34228 0 "**" 0 # Mariposa Loads will drop if bus is below 64 kV, this is anticipate # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (123) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # Le Grand - Dairyland 115 kV Line and Kerckhoff 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (124) L-1/G-1 OVERLAPPING OUTAGE # Glass - Biola - Madera 70 kV Line and Kerckhoff 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (125) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Canal - Oro Loma 70 kV Line and Oneil Pump 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00

Page 129: To determine the system impacts caused by the Project

A-108 GWF Henrietta SISAppendix A

1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93) # 3 34316 0 "1" 0 # ONEILPMP 9.11 PGEN=0.52 QGEN=0.00 0 # # # (126) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Melones Unit 1 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (127) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Melones Unit 1 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (128) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Melones Unit 1 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (129) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Melones Unit 1 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (130) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Melones Unit 1 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (131) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Melones Unit 1 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00

Page 130: To determine the system impacts caused by the Project

A-109 GWF Henrietta SISAppendix A

0 # # # (132) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Helms Unit 1 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (133) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Helms Unit 1 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (134) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Helms Unit 1 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (135) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Helms Unit 1 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (136) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Helms Unit 1 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (137) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Helms Unit 1 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (138) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Helms Unit 1 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (139) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Helms Unit 1 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00

Page 131: To determine the system impacts caused by the Project

A-110 GWF Henrietta SISAppendix A

# 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (140) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Helms Unit 1 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (141) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Helms Unit 1 sumop outage 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Kearney 230 kV line outage HTT/RAS # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (142) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Helms Unit 1 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (143) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Helms Unit 1 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (144) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Helms Unit 1 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (145) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Helms Unit 1 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (146) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Helms Unit 1

Page 132: To determine the system impacts caused by the Project

A-111 GWF Henrietta SISAppendix A

1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (147) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Helms Unit 1 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (148) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Helms Unit 1 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (149) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Helms Unit 1 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (150) L-1/G-1 OVERLAPPING OUTAGE # Dos Amigos - Panoche 230 kV Line and Helms Unit 1 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (151) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Exchequer 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (152) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Exchequer 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (153) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Exchequer 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 #

Page 133: To determine the system impacts caused by the Project

A-112 GWF Henrietta SISAppendix A

3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (154) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Exchequer 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (155) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Exchequer 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (156) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Exchequer 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (157) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Exchequer 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (158) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Exchequer 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (159) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Exchequer 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (160) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Exchequer sumop outage 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Kearney 230 kV line outage HTT/RAS # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0

Page 134: To determine the system impacts caused by the Project

A-113 GWF Henrietta SISAppendix A

# # # (161) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Exchequer 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (162) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Exchequer 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (163) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Exchequer 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (164) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Exchequer 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (165) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Exchequer 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (166) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Exchequer 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (167) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Exchequer 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 #

Page 135: To determine the system impacts caused by the Project

A-114 GWF Henrietta SISAppendix A

# # (168) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Exchequer 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (169) L-1/G-1 OVERLAPPING OUTAGE # Dos Amigos - Panoche 230 kV Line and Exchequer 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (170) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Kerckhoff 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (171) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Kerckhoff 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (172) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Kerckhoff 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (173) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Kerckhoff 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (174) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Kerckhoff 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (175) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Kerckhoff 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 #

Page 136: To determine the system impacts caused by the Project

A-115 GWF Henrietta SISAppendix A

3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (176) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Kerckhoff 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (177) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Kerckhoff 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (178) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Kerckhoff 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (179) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Kerckhoff sumop outage 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Kearney 230 kV line outage HTT/RAS # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (180) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Kerckhoff 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (181) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Kerckhoff 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (182) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Kerckhoff 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0

Page 137: To determine the system impacts caused by the Project

A-116 GWF Henrietta SISAppendix A

# # # (183) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Kerckhoff 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (184) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Kerckhoff 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (185) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Kerckhoff 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (186) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Kerckhoff 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (187) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Kerckhoff 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (188) L-1/G-1 OVERLAPPING OUTAGE # Dos Amigos - Panoche 230 kV Line and Kerckhoff 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # 2013 sumop category b contingency list # Fresno Zone 314 # # # (189) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 138: To determine the system impacts caused by the Project

A-117 GWF Henrietta SISAppendix A

1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 0 # # # (190) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # sumop outage 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #1 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #1 line sumop 0 # # # (191) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # sumop outage 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #2 line sumop 0 # # # (192) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line 0 # # # (193) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line 0 # # # (194) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (195) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # sumop outage 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS 0 # #

Page 139: To determine the system impacts caused by the Project

A-118 GWF Henrietta SISAppendix A

# (196) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # sumop outage 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 3 34600 0 "**" 0 # Trip Helms 1 for Herndon - Kearney 230 kV line outage HTT/RAS 0 # # # (197) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 0 # # # (198) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) 0 # # # (199) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) 0 # # # (200) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30875 30874 "1 " 0 # line from MC CALL 230.00 BRKR to BRKR P0615STN 230.00 0 # # # (201) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30875 30874 "2 " 0 # line from MC CALL 230.00 BRKR to BRKR P0615STN 230.00 0 # # # (202) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 140: To determine the system impacts caused by the Project

A-119 GWF Henrietta SISAppendix A

1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 # # # (203) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 0 # # # (204) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 0 # # # (205) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 0 # # # (206) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 0 # # # (207) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 1 34123 34128 "1 " 0 # line from K1-JCT 115.00 (2) to (3) OAKH_JCT 115.00 1 34128 34121 "1 " 0 # line from OAKH_JCT 115.00 (3) to (3) SHARON T 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34121 34105 "1 " 0 # line from SHARON T 115.00 (3) to (2) CERTANJ1 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) 0 # # # (208) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 1 34149 34148 "1 " 0 # line from CHENYT 115.00 (3) to (2) CHENY 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00

Page 141: To determine the system impacts caused by the Project

A-120 GWF Henrietta SISAppendix A

1 34148 34141 "1 " 0 # line from CHENY 115.00 (2) to (2) PAN2_TAP 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (209) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00 2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) 0 # # # (210) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34356 34358 "1 " 0 # line from KERCKHF1 115.00 BRKR to BRKR KERCKHF2 115.00 0 # # # (211) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (212) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34358 34360 "1 " 0 # line from KERCKHF2 115.00 BRKR to (3) WWARD JT 115.00 1 34360 34414 "1 " 0 # line from WWARD JT 115.00 (3) to BRKR WOODWARD 115.00 1 34360 34363 "1 " 0 # line from WWARD JT 115.00 (3) to (3) CLOVISJ1 115.00 1 34363 34362 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR CLOVIS-1 115.00 1 34363 34366 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR SANGER 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36) 4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34362 0 "**" 1 # Restore Load at Clovis 1 0 # # # (213) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34359 34361 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR AIRWAYS 115.00 1 34359 34408 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR BARTON 115.00 1 34359 34366 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR SANGER 115.00 0

Page 142: To determine the system impacts caused by the Project

A-121 GWF Henrietta SISAppendix A

# # # (214) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34364 34365 "1 " 0 # line from CLOVIS-2 115.00 BRKR to (3) CLOVISJ2 115.00 1 34365 34358 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR KERCKHF2 115.00 1 34365 34366 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR SANGER 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34364 0 "**" 1 # Restore Load at Clovis 2 0 # # # (215) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (216) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "2 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (217) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "3 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (218) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34372 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MALAGA 115.00 0 # # # (219) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34389 "1 " 0 # line from SANGER 115.00 BRKR to (3) RAINBWTP 115.00 1 34389 34388 "1 " 0 # line from RAINBWTP 115.00 (3) to (1) RAINBW 115.00 1 34389 34394 "1 " 0 # line from RAINBWTP 115.00 (3) to (3) PIEDRA 1 115.00 1 34394 34380 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR REEDLEY 115.00 1 34394 34400 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR KNGSRVR1 115.00 4 34388 0 "1 " 0 # LOAD-DROP RAINBW 115.00 LOAD==16.20(3.29) 0 # # # (220) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34396 "1 " 0 # line from SANGER 115.00 BRKR to (2) PIEDRA 2 115.00 1 34396 34398 "1 " 0 # line from PIEDRA 2 115.00 (2) to (2) BALCH 115.00 2 34398 34624 "1 " 0 # TRAN from BALCH 115.00 (2) to (1) BALCH 1 13.20 4 34624 0 "1 " 0 # LOAD-DROP BALCH 1 13.20 LOAD==0.26(0.00) 3 34624 0 "1 " 0 # GEN-DROP BALCH 1 13.20 GEN==27.00(8.33)

Page 143: To determine the system impacts caused by the Project

A-122 GWF Henrietta SISAppendix A

0 # # # (221) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34369 34370 "1 " 0 # line from P0418 115.00 (5) to BRKR MC CALL 115.00 2 34369 34661 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT1 13.80 2 34369 34663 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT2 13.80 2 34369 34665 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT3 13.80 2 34369 34667 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT4 13.80 4 34661 0 "ss" 0 # LOAD-DROP P0418GT1 13.80 LOAD==3.00(1.66) 4 34663 0 "ss" 0 # LOAD-DROP P0418GT2 13.80 LOAD==3.00(1.66) 4 34665 0 "ss" 0 # LOAD-DROP P0418GT3 13.80 LOAD==3.00(1.66) 4 34667 0 "ss" 0 # LOAD-DROP P0418GT4 13.80 LOAD==3.00(1.66) 3 34661 0 "1 " 0 # GEN-DROP P0418GT1 13.80 GEN==78.80(13.93) 3 34663 0 "2 " 0 # GEN-DROP P0418GT2 13.80 GEN==78.80(13.93) 3 34665 0 "3 " 0 # GEN-DROP P0418GT3 13.80 GEN==78.80(13.93) 3 34667 0 "4 " 0 # GEN-DROP P0418GT4 13.80 GEN==78.80(13.93) 0 # # # (222) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 0 # # # (223) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34370 34385 "1 " 0 # line from MC CALL 115.00 BRKR to (3) KINGS J1 115.00 1 34385 34417 "1 " 0 # line from KINGS J1 115.00 (3) to (2) KINGS J2 115.00 1 34385 34425 "1 " 0 # line from KINGS J1 115.00 (3) to (3) KCOGNJCT 115.00 1 34417 34418 "1 " 0 # line from KINGS J2 115.00 (2) to BRKR KINGSBRG 115.00 1 34425 34387 "1 " 0 # line from KCOGNJCT 115.00 (3) to (1) SUNMAID 115.00 1 34425 34427 "1 " 0 # line from KCOGNJCT 115.00 (3) to (2) GRDNGLS2 115.00 1 34427 34386 "1 " 0 # line from GRDNGLS2 115.00 (2) to (2) KNGSCOGN 115.00 2 34386 34642 "1 " 0 # TRAN from KNGSCOGN 115.00 (2) to BRKR KINGSBUR 9.11 4 34387 0 "1 " 0 # LOAD-DROP SUNMAID 115.00 LOAD==3.40(3.28) 3 34642 0 "1 " 0 # GEN-DROP KINGSBUR 9.11 GEN==34.00(17.30) 0 # # # (224) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34402 34404 "1 " 0 # line from CAL AVE 115.00 BRKR to BRKR WST FRSO 115.00 0 # # # (225) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34376 "1 " 0 # line from MALAGA 115.00 BRKR to (1) PPG 115.00 4 34376 0 "1 " 0 # LOAD-DROP PPG 115.00 LOAD==6.25(3.87) 0 #

Page 144: To determine the system impacts caused by the Project

A-123 GWF Henrietta SISAppendix A

# # (226) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34379 "1 " 0 # line from MALAGA 115.00 BRKR to (3) MALAGATP 115.00 1 34379 34373 "1 " 0 # line from MALAGATP 115.00 (3) to (3) SCWAXJCT 115.00 1 34379 34375 "1 " 0 # line from MALAGATP 115.00 (3) to (3) ULTPWRJ 115.00 1 34373 34371 "1 " 0 # line from SCWAXJCT 115.00 (3) to (1) SCWAX 115.00 1 34373 34374 "1 " 0 # line from SCWAXJCT 115.00 (3) to (1) RANCHRS 115.00 1 34375 34377 "1 " 0 # line from ULTPWRJ 115.00 (3) to (2) AIRPROD 115.00 2 34375 34640 "1 " 0 # TRAN from ULTPWRJ 115.00 (3) to (1) ULTR.PWR 9.11 1 34377 34370 "1 " 0 # line from AIRPROD 115.00 (2) to BRKR MC CALL 115.00 4 34371 0 "1 " 0 # LOAD-DROP SCWAX 115.00 LOAD==2.70(1.53) 4 34374 0 "1 " 0 # LOAD-DROP RANCHRS 115.00 LOAD==9.16(1.86) 4 34377 0 "1 " 0 # LOAD-DROP AIRPROD 115.00 LOAD==5.10(2.02) 3 34640 0 "1 " 0 # GEN-DROP ULTR.PWR 9.11 GEN==14.50(13.00) 0 # # # (227) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34381 "1 " 0 # line from MALAGA 115.00 BRKR to (3) KRCDP 115.00 2 34381 34671 "1 " 0 # TRAN from KRCDP 115.00 (3) to (1) KRCDPCT1 13.80 2 34381 34672 "1 " 0 # TRAN from KRCDP 115.00 (3) to (1) KRCDPCT2 13.80 4 34671 0 "ss" 0 # LOAD-DROP KRCDPCT1 13.80 LOAD==1.05(0.65) 4 34672 0 "ss" 0 # LOAD-DROP KRCDPCT2 13.80 LOAD==1.05(0.65) 3 34671 0 "1 " 0 # GEN-DROP KRCDPCT1 13.80 GEN==50.00(7.14) 3 34672 0 "1 " 0 # GEN-DROP KRCDPCT2 13.80 GEN==50.00(7.14) 0 # # # (228) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34380 34384 "1 " 0 # line from REEDLEY 115.00 BRKR to (2) GERAWAN 115.00 1 34384 34382 "1 " 0 # line from GERAWAN 115.00 (2) to BRKR WAHTOKE 115.00 0 # # # (229) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34390 34370 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR MC CALL 115.00 1 34390 34402 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR CAL AVE 115.00 4 34390 0 "1 " 0 # LOAD-DROP DANISHCM 115.00 LOAD==4.10(3.51) 0 # # # (230) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34391 34392 "1 " 0 # line from QUEBECTP 115.00 (2) to (1) QUEBEC 115.00 1 34391 34426 "1 " 0 # line from QUEBECTP 115.00 (2) to BRKR ALPAUGH 115.00 4 34392 0 "1 " 0 # LOAD-DROP QUEBEC 115.00 LOAD==11.20(7.82) 0 # #

Page 145: To determine the system impacts caused by the Project

A-124 GWF Henrietta SISAppendix A

# (231) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (232) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (233) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34409 34413 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR PNEDLE 115.00 1 34409 34416 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR BULLARD 115.00 1 34409 34412 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR HERNDON 115.00 4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25) 4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 1 34411 34413 "1 " 1 # Switches in Pindale CB#12 to transfer load 4 34413 0 "**" 1 # Restore load at Pindale 0 # # # (234) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34410 34412 "1 " 0 # line from MANCHSTR 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (235) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34411 34416 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR BULLARD 115.00 1 34411 34412 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR HERNDON 115.00 0 # # # (236) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34412 34422 "1 " 0 # line from HERNDON 115.00 BRKR to (2) CHLDHOSP 115.00 1 34422 34414 "1 " 0 # line from CHLDHOSP 115.00 (2) to BRKR WOODWARD 115.00 4 34422 0 "1 " 0 # LOAD-DROP CHLDHOSP 115.00 LOAD==3.50(1.60) 0 # # # (237) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34420 "1 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (238) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34420 "2 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (239) B2 LINE OUTAGE (BREAKER-TO-BREAKER)

Page 146: To determine the system impacts caused by the Project

A-125 GWF Henrietta SISAppendix A

# 1 34418 34423 "1 " 0 # line from KINGSBRG 115.00 BRKR to (3) GAURD J1 115.00 1 34423 34370 "1 " 0 # line from GAURD J1 115.00 (3) to BRKR MC CALL 115.00 1 34423 34421 "1 " 0 # line from GAURD J1 115.00 (3) to (2) GAURD J2 115.00 1 34421 34424 "1 " 0 # line from GAURD J2 115.00 (2) to (1) GRDN GLS 115.00 4 34424 0 "1 " 0 # LOAD-DROP GRDN GLS 115.00 LOAD==3.50(1.15) 4 34418 0 "3 " 0 # Kingsburg Bank #3 will also be dropped on this outage 0 # # # (240) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34428 "1 " 0 # line from KINGSBRG 115.00 BRKR to (2) CONTADNA 115.00 1 34428 34429 "1 " 0 # line from CONTADNA 115.00 (2) to (4) GWF_HEP 115.00 1 34429 34521 "1 " 0 # line from GWF_HEP 115.00 (4) to (2) LEPRNOFD 115.00 2 34429 34431 "1 " 0 # TRAN from GWF_HEP 115.00 (4) to (1) GWF_HEP1 13.80 2 34429 34433 "1 " 0 # TRAN from GWF_HEP 115.00 (4) to (1) GWF_HEP2 13.80 1 34521 34430 "1 " 0 # line from LEPRNOFD 115.00 (2) to BRKR HENRETTA 115.00 4 34428 0 "1 " 0 # LOAD-DROP CONTADNA 115.00 LOAD==7.60(5.70) 4 34429 0 "ss" 0 # LOAD-DROP GWF_HEP 115.00 LOAD==3.00(0.68) 4 34521 0 "1 " 0 # LOAD-DROP LEPRNOFD 115.00 LOAD==6.65(4.30) 3 34431 0 "1 " 0 # GEN-DROP GWF_HEP1 13.80 GEN==50.00(21.27) 3 34433 0 "1 " 0 # GEN-DROP GWF_HEP2 13.80 GEN==50.00(21.27) 0 # # # (241) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34426 34700 "1 " 0 # line from ALPAUGH 115.00 BRKR to BRKR SMYRNA 115.00 0 # # # (242) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34452 34260 "1 " 0 # line from WISHON 70.00 BRKR to (3) SJNO2 70.00 1 34260 34259 "1 " 0 # line from SJNO2 70.00 (3) to (3) NRTHFORK 70.00 2 34260 34631 "1 " 0 # TRAN from SJNO2 70.00 (3) to (1) SJ2GEN 9.11 1 34259 34261 "1 " 0 # line from NRTHFORK 70.00 (3) to (2) SJNO3 70.00 2 34259 34340 "1 " 0 # TRAN from NRTHFORK 70.00 (3) to (1) N.FORK E 9.11 2 34261 34633 "1 " 0 # TRAN from SJNO3 70.00 (2) to (1) SJ3GEN 9.11 4 34260 0 "2 " 0 # LOAD-DROP SJNO2 70.00 LOAD==3.22(0.66) 4 34261 0 "2 " 0 # LOAD-DROP SJNO3 70.00 LOAD==6.95(1.41) 4 34340 0 "1 " 0 # LOAD-DROP N.FORK E 9.11 LOAD==1.21(0.25) 3 34631 0 "1 " 0 # GEN-DROP SJ2GEN 9.11 GEN==2.00(0.00) 3 34633 0 "1 " 0 # GEN-DROP SJ3GEN 9.11 GEN==1.00(0.00) 0 # # # (243) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34452 34491 "1 " 0 # line from WISHON 70.00 BRKR to (3) AUBRYTP 70.00

Page 147: To determine the system impacts caused by the Project

A-126 GWF Henrietta SISAppendix A

1 34491 34464 "1 " 0 # line from AUBRYTP 70.00 (3) to BRKR COPPRMNE 70.00 1 34491 34493 "1 " 0 # line from AUBRYTP 70.00 (3) to (1) AUBERRY 70.00 4 34493 0 "1 " 0 # LOAD-DROP AUBERRY 70.00 LOAD==6.07(1.23) 4 34493 0 "2 " 0 # LOAD-DROP AUBERRY 70.00 LOAD==7.15(1.45) 0 # # # (244) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34456 34458 "1 " 0 # line from HRDWK TP 70.00 (3) to (1) HARDWICK 70.00 1 34456 34522 "1 " 0 # line from HRDWK TP 70.00 (3) to (1) HNFRD SW 70.00 1 34456 34576 "1 " 0 # line from HRDWK TP 70.00 (3) to BRKR KNGLOBUS 70.00 4 34458 0 "1 " 0 # LOAD-DROP HARDWICK 70.00 LOAD==12.86(2.61) 0 # # # (245) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34460 34462 "1 " 0 # line from GUERNSEY 70.00 BRKR to (3) GUR3TPT 70.00 1 34462 34542 "1 " 0 # line from GUR3TPT 70.00 (3) to (2) JCBSCRNR 70.00 1 34462 34554 "1 " 0 # line from GUR3TPT 70.00 (3) to BRKR AMSTG SW 70.00 1 34542 34540 "1 " 0 # line from JCBSCRNR 70.00 (2) to BRKR HENRITTA 70.00 4 34460 0 "1 " 0 # LOAD-DROP GUERNSEY 70.00 LOAD==10.51(2.13) 4 34542 0 "1 " 0 # LOAD-DROP JCBSCRNR 70.00 LOAD==12.05(2.45) 4 34542 0 "2 " 0 # LOAD-DROP JCBSCRNR 70.00 LOAD==9.54(1.94) 0 # # # (246) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34464 34478 "1 " 0 # line from COPPRMNE 70.00 BRKR to BRKR TVY VLLY 70.00 0 # # # (247) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34464 34638 "1 " 0 # line from COPPRMNE 70.00 BRKR to (2) FRANTDM 70.00 2 34638 34636 "1 " 0 # TRAN from FRANTDM 70.00 (2) to (1) FRIANTDM 6.60 3 34636 0 "2 " 0 # GEN-DROP FRIANTDM 6.60 GEN==14.70(5.86) 3 34636 0 "3 " 0 # GEN-DROP FRIANTDM 6.60 GEN==7.80(3.11) 3 34636 0 "4 " 0 # GEN-DROP FRIANTDM 6.60 GEN==2.30(0.92) 0 # # # (248) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34466 34482 "1 " 0 # line from BIOLA 70.00 BRKR to BRKR OLDKERN 70.00 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 0 # # # (249) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34468 34482 "1 " 0 # line from BOWLES 70.00 (1) to BRKR OLDKERN 70.00 4 34468 0 "1 " 0 # LOAD-DROP BOWLES 70.00 LOAD==18.29(3.72) 0

Page 148: To determine the system impacts caused by the Project

A-127 GWF Henrietta SISAppendix A

# # # (250) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34469 34271 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) WSTLDJCT 70.00 1 34469 34470 "1 " 0 # line from GFFNJCT 70.00 (3) to (1) GIFFEN 70.00 1 34469 34471 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) SNJQJCT 70.00 1 34271 34172 "1 " 0 # line from WSTLDJCT 70.00 (3) to (2) WESTLAND 70.00 1 34271 34269 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) BIOMSJCT 70.00 1 34471 34472 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR SAN JOQN 70.00 1 34471 34474 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR HELM 70.00 1 34172 34170 "1 " 0 # line from WESTLAND 70.00 (2) to (1) WESIX 70.00 1 34269 34268 "1 " 0 # line from BIOMSJCT 70.00 (3) to BRKR MENDOTA 70.00 1 34269 34270 "1 " 0 # line from BIOMSJCT 70.00 (3) to (2) BIOMASS 70.00 2 34270 34334 "1 " 0 # TRAN from BIOMASS 70.00 (2) to (1) BIO PWR 9.11 4 34470 0 "1 " 0 # LOAD-DROP GIFFEN 70.00 LOAD==9.59(1.95) 4 34172 0 "1 " 0 # LOAD-DROP WESTLAND 70.00 LOAD==3.20(0.76) 4 34170 0 "1 " 0 # LOAD-DROP WESIX 70.00 LOAD==1.60(0.38) 3 34334 0 "1 " 0 # GEN-DROP BIO PWR 9.11 GEN==21.80(10.99) 1 34472 34473 "1 " 1 # Switches in San Joaquin CB22 to transfer load 4 34472 0 "**" 1 # Restore Load at San Joaquin 0 # # # (251) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34473 34472 "1 " 0 # line from SNJQTP 70.00 (2) to BRKR SAN JOQN 70.00 1 34473 34475 "1 " 0 # line from SNJQTP 70.00 (2) to (3) AGRCJCT 70.00 1 34475 34476 "1 " 0 # line from AGRCJCT 70.00 (3) to (2) AGRICO 70.00 1 34475 34484 "1 " 0 # line from AGRCJCT 70.00 (3) to BRKR KERMAN 70.00 2 34476 34608 "1 " 0 # TRAN from AGRICO 70.00 (2) to (1) AGRICO 13.80 4 34484 0 "1 " 0 # LOAD-DROP KERMAN 70.00 LOAD==19.44(3.95) 4 34484 0 "2 " 0 # LOAD-DROP KERMAN 70.00 LOAD==11.78(2.39) 3 34608 0 "2 " 0 # GEN-DROP AGRICO 13.80 GEN==7.00(1.08) 3 34608 0 "3 " 0 # GEN-DROP AGRICO 13.80 GEN==18.10(2.80) 3 34608 0 "4 " 0 # GEN-DROP AGRICO 13.80 GEN==26.00(4.02) 0 # # # (252) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34474 34556 "1 " 0 # line from HELM 70.00 BRKR to BRKR STRD JCT 70.00 0 # # # (253) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34478 34492 "1 " 0 # line from TVY VLLY 70.00 BRKR to BRKR REEDLEY 70.00 0 # # # (254) B2 LINE OUTAGE (BREAKER-TO-BREAKER)

Page 149: To determine the system impacts caused by the Project

A-128 GWF Henrietta SISAppendix A

# 1 34480 34481 "1 " 0 # line from KEARNEY 70.00 BRKR to (3) FRWWTAP 70.00 1 34481 34483 "1 " 0 # line from FRWWTAP 70.00 (3) to (3) FRESNOWW 70.00 1 34481 34483 "2 " 0 # line from FRWWTAP 70.00 (3) to (3) FRESNOWW 70.00 2 34483 34485 "1 " 0 # TRAN from FRESNOWW 70.00 (3) to (1) FRESNOWW 12.47 4 34485 0 "1 " 0 # LOAD-DROP FRESNOWW 12.47 LOAD==7.91(0.00) 3 34485 0 "1 " 0 # GEN-DROP FRESNOWW 12.47 GEN==9.00(0.00) 0 # # # (255) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34480 34482 "1 " 0 # line from KEARNEY 70.00 BRKR to (3) OLDKERN 70.00 1 34482 34466 "1 " 0 # line from OLDKERN 70.00 BRKR to BRKR BIOLA 70.00 1 34482 34468 "1 " 0 # line from OLDKERN 70.00 BRKR to (1) BOWLES 70.00 4 34482 0 "1 " 0 # LOAD-DROP OLDKERN 70.00 LOAD==18.75(3.81) 4 34482 0 "3 " 0 # LOAD-DROP OLDKERN 70.00 LOAD==7.57(1.54) 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 4 34468 0 "1 " 0 # LOAD-DROP BOWLES 70.00 LOAD==18.29(3.72) 0 # # # (256) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34480 34512 "1 " 0 # line from KEARNEY 70.00 BRKR to BRKR CARUTHRS 70.00 4 34512 0 "1 " 0 # LOAD-DROP CARUTHRS 70.00 LOAD==19.63(3.98) 0 # # # (257) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34487 34489 "1 " 0 # line from SNGRJCT 70.00 (3) to (2) SNGRCOGN 70.00 1 34487 34490 "1 " 0 # line from SNGRJCT 70.00 (3) to (2) PARLIER 70.00 1 34487 34488 "1 " 0 # line from SNGRJCT 70.00 (3) to BRKR SANGER 70.00 2 34489 34646 "1 " 0 # TRAN from SNGRCOGN 70.00 (2) to (1) SANGERCO 9.11 1 34490 34492 "1 " 0 # line from PARLIER 70.00 (2) to BRKR REEDLEY 70.00 4 34490 0 "1 " 0 # LOAD-DROP PARLIER 70.00 LOAD==20.24(4.11) 3 34646 0 "1 " 0 # GEN-DROP SANGERCO 9.11 GEN==37.50(1.40) 0 # # # (258) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34488 34366 "1 " 0 # line from SANGER 70.00 BRKR to BRKR SANGER 115.00 0 # # # (259) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34492 34497 "1 " 0 # line from REEDLEY 70.00 BRKR to (3) DNUBAJCT 70.00 1 34497 34499 "1 " 0 # line from DNUBAJCT 70.00 (3) to (2) DNUBAEGY 70.00 1 34497 34500 "1 " 0 # line from DNUBAJCT 70.00 (3) to BRKR DINUBA 70.00

Page 150: To determine the system impacts caused by the Project

A-129 GWF Henrietta SISAppendix A

2 34499 34648 "1 " 0 # TRAN from DNUBAEGY 70.00 (2) to (1) DINUBA E 13.80 4 34648 0 "ss" 0 # LOAD-DROP DINUBA E 13.80 LOAD==0.30(0.26) 3 34648 0 "1 " 0 # GEN-DROP DINUBA E 13.80 GEN==12.00(7.00) 0 # # # (260) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34492 34526 "1 " 0 # line from REEDLEY 70.00 BRKR to (3) ORSI JCT 70.00 1 34526 34495 "1 " 0 # line from ORSI JCT 70.00 (3) to (2) SANDCRK 70.00 1 34526 34502 "1 " 0 # line from ORSI JCT 70.00 (3) to BRKR OROSI 70.00 1 34495 34494 "1 " 0 # line from SANDCRK 70.00 (2) to (1) DUNLAP 70.00 4 34495 0 "1 " 0 # LOAD-DROP SANDCRK 70.00 LOAD==3.14(0.64) 4 34494 0 "1 " 0 # LOAD-DROP DUNLAP 70.00 LOAD==4.46(0.91) 0 # # # (261) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34496 34498 "1 " 0 # line from STCRRL J 70.00 (3) to (1) STONCRRL 70.00 1 34496 34500 "1 " 0 # line from STCRRL J 70.00 (3) to BRKR DINUBA 70.00 1 34496 34502 "1 " 0 # line from STCRRL J 70.00 (3) to (2) OROSI 70.00 1 34502 34526 "1 " 0 # line from OROSI 70.00 BRKR to (1) ORSI JCT 70.00 4 34498 0 "2 " 0 # LOAD-DROP STONCRRL 70.00 LOAD==3.37(0.68) 4 34498 0 "3 " 0 # LOAD-DROP STONCRRL 70.00 LOAD==2.68(0.54) 4 34502 0 "1 " 0 # LOAD-DROP OROSI 70.00 LOAD==8.38(1.70) 4 34502 0 "2 " 0 # LOAD-DROP OROSI 70.00 LOAD==7.43(1.51) 0 # # # (262) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34508 34510 "1 " 0 # line from CAMDEN 70.00 (2) to (1) CMDN JCT 70.00 1 34508 34576 "1 " 0 # line from CAMDEN 70.00 (2) to BRKR KNGLOBUS 70.00 4 34508 0 "1 " 0 # LOAD-DROP CAMDEN 70.00 LOAD==6.87(1.40) 4 34508 0 "2 " 0 # LOAD-DROP CAMDEN 70.00 LOAD==10.90(2.22) 0 # # # (263) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34514 34540 "1 " 0 # line from MUSLSLGH 70.00 (1) to BRKR HENRITTA 70.00 4 34514 0 "1 " 0 # LOAD-DROP MUSLSLGH 70.00 LOAD==22.00(13.60) 0 # # # (264) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83)

Page 151: To determine the system impacts caused by the Project

A-130 GWF Henrietta SISAppendix A

4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) 0 # # # (265) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34528 34530 "1 " 0 # line from CORCORAN 70.00 BRKR to (3) BSWLL TP 70.00 1 34530 34531 "1 " 0 # line from BSWLL TP 70.00 (3) to (2) JGBSWLL 70.00 1 34530 34538 "1 " 0 # line from BSWLL TP 70.00 (3) to (1) BOSWELL 70.00 1 34531 34536 "1 " 0 # line from JGBSWLL 70.00 (2) to (1) ANGIOLA 70.00 4 34538 0 "1 " 0 # LOAD-DROP BOSWELL 70.00 LOAD==2.37(1.53) 4 34536 0 "1 " 0 # LOAD-DROP ANGIOLA 70.00 LOAD==7.24(1.47) 0 # # # (266) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34532 34554 "1 " 0 # line from ARMSTRNG 70.00 (1) to (4) AMSTG SW 70.00 1 34554 34462 "1 " 0 # line from AMSTG SW 70.00 BRKR to (1) GUR3TPT 70.00 1 34554 34534 "1 " 0 # line from AMSTG SW 70.00 (4) to (1) RESERVE 70.00 2 34554 34650 "1 " 0 # TRAN from AMSTG SW 70.00 BRKR to (1) GWF-PWR. 13.80 4 34534 0 "1 " 0 # LOAD-DROP RESERVE 70.00 LOAD==2.03(0.41) 3 34650 0 "1 " 0 # GEN-DROP GWF-PWR. 13.80 GEN==23.00(12.00) 0 # # # (267) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34537 34540 "1 " 0 # line from GWF_HENR 70.00 (5) to BRKR HENRITTA 70.00 2 34537 34539 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) GWF_GT1 13.80 2 34537 34541 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) GWF_GT2 13.80 2 34537 34691 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) Q272_ST1 13.80 2 34537 34692 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) Q272SLST 13.80 4 34539 0 "ss" 0 # LOAD-DROP GWF_GT1 13.80 LOAD==1.10(0.25) 4 34541 0 "ss" 0 # LOAD-DROP GWF_GT2 13.80 LOAD==1.10(0.25) 4 34691 0 "ss" 0 # LOAD-DROP Q272_ST1 13.80 LOAD==2.00(1.11) 4 34692 0 "ss" 0 # LOAD-DROP Q272SLST 13.80 LOAD==14.00(7.75) 3 34539 0 "1 " 0 # GEN-DROP GWF_GT1 13.80 GEN==50.00(4.51) 3 34541 0 "1 " 0 # GEN-DROP GWF_GT2 13.80 GEN==50.00(4.51) 3 34691 0 "1 " 0 # GEN-DROP Q272_ST1 13.80 GEN==27.00(1.87) 3 34692 0 "1 " 0 # GEN-DROP Q272SLST 13.80 GEN==139.00(35.74) 0 # # # (268) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34544 34550 "1 " 0 # line from TLRE LKE 70.00 BRKR to (2) CHEVPLIN 70.00 1 34550 34546 "1 " 0 # line from CHEVPLIN 70.00 (2) to (2) AVENAL 70.00 1 34546 34548 "1 " 0 # line from AVENAL 70.00 (2) to BRKR KETTLEMN 70.00 4 34544 0 "1 " 0 # LOAD-DROP TLRE LKE 70.00 LOAD==6.79(1.38) 4 34550 0 "1 " 0 # LOAD-DROP CHEVPLIN 70.00 LOAD==1.01(0.73) 4 34546 0 "1 " 0 # LOAD-DROP AVENAL 70.00 LOAD==7.72(1.57) 0 #

Page 152: To determine the system impacts caused by the Project

A-131 GWF Henrietta SISAppendix A

# # (269) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34548 34552 "1 " 0 # line from KETTLEMN 70.00 (2) to BRKR GATES 70.00 1 34548 34546 "1 " 0 # line from KETTLEMN 70.00 BRKR to (1) AVENAL 70.00 4 34548 0 "1 " 0 # LOAD-DROP KETTLEMN 70.00 LOAD==6.32(1.29) 0 # # # (270) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34558 "1 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0 # # # (271) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34558 "2 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0 # # # (272) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.45(2.99) 0 # # # (273) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34556 34562 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR SCHLNDLR 70.00 0 # # # (274) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34556 34564 "1 " 0 # line from STRD JCT 70.00 (3) to BRKR STROUD 70.00 1 34556 34474 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR HELM 70.00 1 34556 34562 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR SCHLNDLR 70.00 4 34564 0 "1 " 0 # LOAD-DROP STROUD 70.00 LOAD==13.09(2.66) 0 # # # (275) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34558 34560 "1 " 0 # line from HURON 70.00 BRKR to (2) CALFLAX 70.00 1 34560 34562 "1 " 0 # line from CALFLAX 70.00 (2) to BRKR SCHLNDLR 70.00 4 34560 0 "1 " 0 # LOAD-DROP CALFLAX 70.00 LOAD==6.53(1.33) 1 34552 34558 "2 " 0 # Must include Gates - Huron in this outage 0 # # # (276) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34562 34566 "1 " 0 # line from SCHLNDLR 70.00 BRKR to (2) PLSNTVLY 70.00

Page 153: To determine the system impacts caused by the Project

A-132 GWF Henrietta SISAppendix A

1 34566 34570 "1 " 0 # line from PLSNTVLY 70.00 (2) to BRKR COLNGA 2 70.00 4 34566 0 "1 " 0 # LOAD-DROP PLSNTVLY 70.00 LOAD==10.00(2.51) 0 # # # (277) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34570 34572 "1 " 0 # line from COLNGA 2 70.00 BRKR to (3) TORNADO 70.00 1 34572 34574 "1 " 0 # line from TORNADO 70.00 (3) to BRKR COLNGA 1 70.00 2 34572 34654 "1 " 0 # TRAN from TORNADO 70.00 (3) to (1) COLNGAGN 9.11 4 34572 0 "1 " 0 # LOAD-DROP TORNADO 70.00 LOAD==1.74(1.44) 3 34654 0 "1 " 0 # GEN-DROP COLNGAGN 9.11 GEN==34.00(5.40) 2 34570 34652 "1 " 0 # Must include Colinga2 - Chv.coal in this outage - modeled on bus, 3 34652 0 "**" 0 # Drops units on Derrick Sub 4 34652 0 "**" 0 # Drops load at Derrick Sub 0 # # # (278) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 36354 34574 "1 " 0 # line from SAN MIGL 70.00 BRKR to BRKR COLNGA 1 70.00 0 # # # (279) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30835 (30882) 34412 34630 : 2 30835 34412 "1 " 0 # TRAN from HERNDON 230.00 BRKR to (1) HERNDON 115.00 0 # # # (280) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30835 (30883) 34412 34632 : 2 30835 34412 "2 " 0 # TRAN from HERNDON 230.00 BRKR to (1) HERNDON 115.00 0 # # # (281) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30876) 34370 34618 : 2 30875 34370 "1 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # # # (282) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30877) 34370 34620 : 2 30875 34370 "2 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # # # (283) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30878) 34370 34621 : 2 30875 34370 "3 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # #

Page 154: To determine the system impacts caused by the Project

A-133 GWF Henrietta SISAppendix A

# (284) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 30881 34430 "3 " 0 # TRAN from HENRIETA 230.00 BRKR to BRKR HENRETTA 115.00 0 # # # (285) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30900 (34607) 30055 34606 : 2 30900 30055 "11" 0 # TRAN from GATES 230.00 BRKR to (1) GATES 500.00 0 # # # (286) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 30900 30901 "1 " 0 # TRAN from GATES 230.00 BRKR to (3) GATES 1M 230.00 2 30901 34378 "1 " 0 # TRAN from GATES 1M 230.00 (3) to BRKR GATES 115.00 2 30901 34622 "1 " 0 # TRAN from GATES 1M 230.00 (3) to (1) GATES 1T 13.20 4 34378 0 "3 " 0 # Drop Gates Bank #3 0 # # # (287) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34356 34344 "1 " 0 # TRAN from KERCKHF1 115.00 BRKR to (1) KERCKHOF 6.60 4 34344 0 "4 " 0 # LOAD-DROP KERCKHOF 6.60 LOAD==3.24(0.66) 3 34344 0 "2 " 0 # GEN-DROP KERCKHOF 6.60 GEN==6.80(-4.00) 0 # # # (288) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34366 34590 "1 " 0 # TRAN from SANGER 115.00 BRKR to (2) SANGR3T 115.00 2 34590 34488 "1 " 0 # TRAN from SANGR3T 115.00 (2) to BRKR SANGER 70.00 4 34590 0 "3 " 0 # LOAD-DROP SANGR3T 115.00 LOAD==20.55(4.17) 0 # # # (289) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34418 34576 "2 " 0 # TRAN from KINGSBRG 115.00 BRKR to BRKR KNGLOBUS 70.00 0 # # # (290) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34474 30873 "1 " 0 # TRAN from HELM 70.00 BRKR to BRKR HELM 230.00 0 # # # (291) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34480 30830 "2 " 0 # TRAN from KEARNEY 70.00 BRKR to BRKR KEARNEY 230.00 0 # # # (292) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) #

Page 155: To determine the system impacts caused by the Project

A-134 GWF Henrietta SISAppendix A

2 34492 34380 "1 " 0 # TRAN from REEDLEY 70.00 BRKR to BRKR REEDLEY 115.00 0 # # # (293) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34492 34380 "2 " 0 # TRAN from REEDLEY 70.00 BRKR to BRKR REEDLEY 115.00 0 # # # (294) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34528 34420 "2 " 0 # TRAN from CORCORAN 70.00 BRKR to BRKR CORCORAN 115.00 1 34420 34391 "1 " 0 # Must include Corcoran - Quebec (Corcoran CB 142) in this outage 1 34420 34418 "2 " 0 # Must include Corcoran - Kingburg (Corcoran CB 162) in this outage 1 34528 34460 "1 " 0 # Must include Corcorna - Guernsey (Corcoran CB 42) in this outage 0 # # # (295) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34540 30881 "2 " 0 # TRAN from HENRITTA 70.00 BRKR to BRKR HENRIETA 230.00 0 # # # (296) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34540 30881 "4 " 0 # TRAN from HENRITTA 70.00 BRKR to BRKR HENRIETA 230.00 0 # # # (297) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34552 34378 "2 " 0 # TRAN from GATES 70.00 BRKR to BRKR GATES 115.00 0 # # # (298) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34562 34354 "1 " 0 # TRAN from SCHLNDLR 70.00 BRKR to (3) SCHINDLR 115.00 1 34354 34149 "1 " 0 # line from SCHINDLR 115.00 BRKR to (1) CHENYT 115.00 1 34354 34432 "1 " 0 # line from SCHINDLR 115.00 BRKR to (1) WESTLNDS 115.00 4 34354 0 "1 " 0 # LOAD-DROP SCHINDLR 115.00 LOAD==11.22(2.28) 0 # # # (299) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34652 34570 "1 " 0 # TRAN from CHV.COAL 9.11 (1) to BRKR COLNGA 2 70.00 4 34652 0 "S1" 0 # LOAD-DROP CHV.COAL 9.11 LOAD==5.12(2.48) 4 34652 0 "SG" 0 # LOAD-DROP CHV.COAL 9.11 LOAD==0.94(0.46) 3 34652 0 "1 " 0 # GEN-DROP CHV.COAL 9.11 GEN==2.50(8.30) 3 34652 0 "2 " 0 # GEN-DROP CHV.COAL 9.11 GEN==8.00(4.00) 0 # # # (300) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER)

Page 156: To determine the system impacts caused by the Project

A-135 GWF Henrietta SISAppendix A

# 2 34658 34452 "1 " 0 # TRAN from WISHON 2.30 (1) to BRKR WISHON 70.00 3 34658 0 "3 " 0 # GEN-DROP WISHON 2.30 GEN==4.50(1.00) 3 34658 0 "4 " 0 # GEN-DROP WISHON 2.30 GEN==4.50(1.00) 0 # # # (301) B1 GENERATOR OUTAGE # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (302) B1 GENERATOR OUTAGE # 3 34344 0 "2" 0 # KERCKHOF 6.60 PGEN=6.80 QGEN=-4.00 0 # # # (303) B1 GENERATOR OUTAGE # 3 34431 0 "1" 0 # GWF_HEP1 13.80 PGEN=50.00 QGEN=21.57 0 # # # (304) B1 GENERATOR OUTAGE # 3 34433 0 "1" 0 # GWF_HEP2 13.80 PGEN=50.00 QGEN=21.57 0 # # # (305) B1 GENERATOR OUTAGE # 3 34485 0 "1" 0 # FRESNOWW 12.47 PGEN=9.00 QGEN=0.00 0 # # # (306) B1 GENERATOR OUTAGE # 3 34539 0 "1" 0 # GWF_GT1 13.80 PGEN=50.00 QGEN=1.23 0 # # # (307) B1 GENERATOR OUTAGE # 3 34541 0 "1" 0 # GWF_GT2 13.80 PGEN=50.00 QGEN=1.23 0 # # # (308) B1 GENERATOR OUTAGE # 3 34553 0 "1" 0 # WHD_GAT2 13.80 PGEN=49.00 QGEN=-25.30 0 # # # (309) B1 GENERATOR OUTAGE # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (310) B1 GENERATOR OUTAGE # 3 34602 0 "1" 0 # HELMS 2 18.00 PGEN=404.00 QGEN=66.06 0 # # # (311) B1 GENERATOR OUTAGE #

Page 157: To determine the system impacts caused by the Project

A-136 GWF Henrietta SISAppendix A

3 34604 0 "1" 0 # HELMS 3 18.00 PGEN=404.00 QGEN=66.12 0 # # # (312) B1 GENERATOR OUTAGE # 3 34608 0 "2" 0 # AGRICO 13.80 PGEN=7.00 QGEN=1.64 0 # # # (313) B1 GENERATOR OUTAGE # 3 34608 0 "3" 0 # AGRICO 13.80 PGEN=18.10 QGEN=4.24 0 # # # (314) B1 GENERATOR OUTAGE # 3 34608 0 "4" 0 # AGRICO 13.80 PGEN=26.00 QGEN=6.09 0 # # # (315) B1 GENERATOR OUTAGE # 3 34610 0 "1" 0 # HAAS 13.80 PGEN=70.00 QGEN=18.75 0 # # # (316) B1 GENERATOR OUTAGE # 3 34610 0 "2" 0 # HAAS 13.80 PGEN=70.00 QGEN=18.75 0 # # # (317) B1 GENERATOR OUTAGE # 3 34612 0 "1" 0 # BLCH 2-2 13.80 PGEN=50.00 QGEN=9.61 0 # # # (318) B1 GENERATOR OUTAGE # 3 34614 0 "1" 0 # BLCH 2-3 13.80 PGEN=50.00 QGEN=13.00 0 # # # (319) B1 GENERATOR OUTAGE # 3 34616 0 "1" 0 # KINGSRIV 13.80 PGEN=47.00 QGEN=9.00 0 # # # (320) B1 GENERATOR OUTAGE # 3 34618 0 "1" 0 # MCCALL1T 13.20 PGEN=0.00 QGEN=36.40 0 # # # (321) B1 GENERATOR OUTAGE # 3 34621 0 "1" 0 # MCCALL3T 13.20 PGEN=0.00 QGEN=4.85 0 # # # (322) B1 GENERATOR OUTAGE # 3 34624 0 "1" 0 # BALCH 1 13.20 PGEN=27.00 QGEN=10.00 0 # #

Page 158: To determine the system impacts caused by the Project

A-137 GWF Henrietta SISAppendix A

# (323) B1 GENERATOR OUTAGE # 3 34630 0 "1" 0 # HERNDN1T 13.20 PGEN=0.00 QGEN=20.26 0 # # # (324) B1 GENERATOR OUTAGE # 3 34632 0 "1" 0 # HERNDN2T 13.20 PGEN=0.00 QGEN=32.58 0 # # # (325) B1 GENERATOR OUTAGE # 3 34636 0 "2" 0 # FRIANTDM 6.60 PGEN=14.70 QGEN=6.14 0 # # # (326) B1 GENERATOR OUTAGE # 3 34636 0 "3" 0 # FRIANTDM 6.60 PGEN=7.80 QGEN=3.26 0 # # # (327) B1 GENERATOR OUTAGE # 3 34636 0 "4" 0 # FRIANTDM 6.60 PGEN=2.30 QGEN=0.96 0 # # # (328) B1 GENERATOR OUTAGE # 3 34640 0 "1" 0 # ULTR.PWR 9.11 PGEN=14.50 QGEN=13.00 0 # # # (329) B1 GENERATOR OUTAGE # 3 34642 0 "1" 0 # KINGSBUR 9.11 PGEN=34.00 QGEN=17.30 0 # # # (330) B1 GENERATOR OUTAGE # 3 34646 0 "1" 0 # SANGERCO 9.11 PGEN=37.50 QGEN=4.31 0 # # # (331) B1 GENERATOR OUTAGE # 3 34648 0 "1" 0 # DINUBA E 13.80 PGEN=12.00 QGEN=7.00 0 # # # (332) B1 GENERATOR OUTAGE # 3 34650 0 "1" 0 # GWF-PWR. 13.80 PGEN=23.00 QGEN=12.00 0 # # # (333) B1 GENERATOR OUTAGE # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=2.50 QGEN=8.30 0 # # # (334) B1 GENERATOR OUTAGE # 3 34652 0 "2" 0 # CHV.COAL 9.11 PGEN=8.00 QGEN=4.00 0

Page 159: To determine the system impacts caused by the Project

A-138 GWF Henrietta SISAppendix A

# # # (335) B1 GENERATOR OUTAGE # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.00 QGEN=-3.48 0 # # # (336) B1 GENERATOR OUTAGE # 3 34658 0 "3" 0 # WISHON 2.30 PGEN=4.50 QGEN=1.00 0 # # # (337) B1 GENERATOR OUTAGE # 3 34658 0 "4" 0 # WISHON 2.30 PGEN=4.50 QGEN=1.00 0 # # # (338) B1 GENERATOR OUTAGE # 3 34671 0 "1" 0 # KRCDPCT1 13.80 PGEN=50.00 QGEN=10.75 0 # # # (339) B1 GENERATOR OUTAGE # 3 34672 0 "1" 0 # KRCDPCT2 13.80 PGEN=50.00 QGEN=10.75 0 # # # (340) B1 GENERATOR OUTAGE # 3 38720 0 "1" 0 # PINE FLT 13.80 PGEN=57.00 QGEN=23.30 0 # # # (341) B1 GENERATOR OUTAGE # 3 34661 0 "1" 0 # P0418GT1 13.80 PGEN=78.80 QGEN=13.93 0 # # # (342) B1 GENERATOR OUTAGE # 3 34663 0 "2" 0 # P0418GT2 13.80 PGEN=78.80 QGEN=13.93 0 # # # (343) B1 GENERATOR OUTAGE # 3 34665 0 "3" 0 # P0418GT3 13.80 PGEN=78.80 QGEN=13.93 0 # # # (344) B1 GENERATOR OUTAGE # 3 34667 0 "4" 0 # P0418GT4 13.80 PGEN=78.80 QGEN=13.93 0 # # # (345) B1 GENERATOR OUTAGE # 3 34685 0 "1" 0 # P0615CT1 16.50 PGEN=192.00 QGEN=35.45 0 # # # (346) B1 GENERATOR OUTAGE #

Page 160: To determine the system impacts caused by the Project

A-139 GWF Henrietta SISAppendix A

3 34686 0 "1" 0 # P0615CT2 16.50 PGEN=192.00 QGEN=35.45 0 # # # (347) B1 GENERATOR OUTAGE # 3 34687 0 "1" 0 # P0615STG 16.50 PGEN=193.00 QGEN=35.57 0 # # # (348) B1 GENERATOR OUTAGE # 3 34688 0 "1" 0 # Q254CTG1 18.00 PGEN=172.40 QGEN=41.25 0 # # # (349) B1 GENERATOR OUTAGE # 3 34689 0 "2" 0 # Q254CTG2 18.00 PGEN=172.40 QGEN=41.25 0 # # # (350) B1 GENERATOR OUTAGE # 3 34690 0 "3" 0 # Q254STG1 18.00 PGEN=290.80 QGEN=67.53 0 # # # (351) B1 GENERATOR OUTAGE # 3 34691 0 "1" 0 # Q272_ST1 13.80 PGEN=27.00 QGEN=1.87 0 # # # (352) B1 GENERATOR OUTAGE # 3 34692 0 "1" 0 # Q272SLST 13.80 PGEN=139.00 QGEN=35.74 0 # # # (353) L-1/G-1 OVERLAPPING OUTAGE # Smyrna - Semitropic - Midway 115 kV Line and Exchequer 1 34700 34708 "1 " 0 # line from SMYRNA 115.00 BRKR to (2) MCKIBBEN 115.00 1 34708 34742 "1 " 0 # line from MCKIBBEN 115.00 (2) to (2) SEMITRPJ 115.00 1 34742 34746 "1 " 0 # line from SEMITRPJ 115.00 (2) to (2) GANSO 115.00 1 34746 34774 "1 " 0 # line from GANSO 115.00 (2) to BRKR MIDWAY 115.00 4 34746 0 "1 " 0 # LOAD-DROP GANSO 115.00 LOAD==5.34(1.22) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=89.95 QGEN=18.49 0 # # # (354) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #2 70 kV Line and Chevron Coalinga Unit 1 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00 2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=17.00 QGEN=8.30 0 # #

Page 161: To determine the system impacts caused by the Project

A-140 GWF Henrietta SISAppendix A

# (355) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #1 70 kV Line and Chevron Coalinga Unit 1 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.03(2.5) 0 # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=17.00 QGEN=8.30 0 # # # (356) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #2 70 kV Line and Coalinga Cogen 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00 2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.22 QGEN=-13.50 0 # # # (357) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #1 70 kV Line and Coalinga Cogen 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.03(2.5) 0 # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.22 QGEN=-13.50 0 # # # (358) L-1/G-1 OVERLAPPING OUTAGE # Borden - Coppermine 70 kV Line and Friant PP Unit 2 1 34262 34454 "1 " 0 # line from CASSIDY 70.00 (2) to (2) RIVERROC 70.00 1 34262 34256 "1 " 0 # line from CASSIDY 70.00 (2) to BRKR BORDEN 70.00 1 34454 34464 "1 " 0 # line from RIVERROC 70.00 (2) to BRKR COPPRMNE 70.00 4 34262 0 "1 " 0 # LOAD-DROP CASSIDY 70.00 LOAD==14.31(2.90) 4 34454 0 "1 " 0 # LOAD-DROP RIVERROC 70.00 LOAD==2.01(1.83) # 3 34636 0 "2" 0 # FRIANTDM 6.60 PGEN=14.70 QGEN=6.14 0 # # # (359) L-1/G-1 OVERLAPPING OUTAGE # Henrietta - Lemoore 70 kV Line and GWF Hanford 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) # 3 34650 0 "1" 0 # GWF-PWR. 13.80 PGEN=23.00 QGEN=12.00 0 #

Page 162: To determine the system impacts caused by the Project

A-141 GWF Henrietta SISAppendix A

# # (360) L-1/G-1 OVERLAPPING OUTAGE # Henrietta - Lemoore 70 kV Line and GWF Henrietta Unit 1 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) # 3 34539 0 "1" 0 # GWF_GT1 13.80 PGEN=50.00 QGEN=1.23 0 # # # (361) L-1/G-1 OVERLAPPING OUTAGE # McCall - Wahtoke 115 kV Line and Sanger Cogen 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 # 3 34646 0 "1" 0 # SANGERCO 9.11 PGEN=37.50 QGEN=4.31 0 # # # (362) L-1/G-1 OVERLAPPING OUTAGE # McCall - Wahtoke 115 kV Line and Kings River Power House 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 # 3 34616 0 "1" 0 # KINGSRIV 13.80 PGEN=47.00 QGEN=9.00 0 # # # (363) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Exchequer 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (364) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Exchequer sumop outage 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #1 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #1 line sumop # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (365) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Exchequer sumop outage 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #2 line sumop # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (366) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Exchequer

Page 163: To determine the system impacts caused by the Project

A-142 GWF Henrietta SISAppendix A

1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (367) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Exchequer 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (368) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Exchequer 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (369) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Exchequer sumop outage 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (370) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Exchequer sumop outage 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 3 34600 0 "**" 0 # Trip Helms 1 for Herndon - Kearney 230 kV line outage HTT/RAS # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (371) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Exchequer 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00

Page 164: To determine the system impacts caused by the Project

A-143 GWF Henrietta SISAppendix A

1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (372) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Exchequer 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (373) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Exchequer 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (374) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Exchequer 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (375) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Exchequer 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (376) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Exchequer 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 #

Page 165: To determine the system impacts caused by the Project

A-144 GWF Henrietta SISAppendix A

3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (377) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Exchequer 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (378) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Exchequer 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (379) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Kerckhoff 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (380) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Kerckhoff sumop outage 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #1 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #1 line sumop # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (381) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Kerckhoff sumop outage 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #2 line sumop # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (382) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Kerckhoff 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (383) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Kerckhoff 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00

Page 166: To determine the system impacts caused by the Project

A-145 GWF Henrietta SISAppendix A

0 # # # (384) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Kerckhoff 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (385) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Kerckhoff sumop outage 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (386) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Kerckhoff sumop outage 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 3 34600 0 "**" 0 # Trip Helms 1 for Herndon - Kearney 230 kV line outage HTT/RAS # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (387) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Kerckhoff 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (388) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Kerckhoff 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00

Page 167: To determine the system impacts caused by the Project

A-146 GWF Henrietta SISAppendix A

2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (389) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Kerckhoff 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (390) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Kerckhoff 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (391) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Kerckhoff 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (392) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Kerckhoff 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (393) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Kerckhoff 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (394) L-1/G-1 OVERLAPPING OUTAGE

Page 168: To determine the system impacts caused by the Project

A-147 GWF Henrietta SISAppendix A

# Gates - Midway 230 kV Line and Kerckhoff 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (395) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Helms Unit 1 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (396) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Helms Unit 1 sumop outage 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #1 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #1 line sumop # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (397) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Helms Unit 1 sumop outage 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #2 line sumop # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (398) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Helms Unit 1 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (399) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Helms Unit 1 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (400) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Helms Unit 1 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line

Page 169: To determine the system impacts caused by the Project

A-148 GWF Henrietta SISAppendix A

1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (401) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Helms Unit 1 sumop outage 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (402) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Helms Unit 1 sumop outage 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 3 34600 0 "**" 0 # Trip Helms 1 for Herndon - Kearney 230 kV line outage HTT/RAS # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (403) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Helms Unit 1 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (404) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Helms Unit 1 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (405) L-1/G-1 OVERLAPPING OUTAGE

Page 170: To determine the system impacts caused by the Project

A-149 GWF Henrietta SISAppendix A

# Balch - McCall 230 kV Line and Helms Unit 1 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (406) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Helms Unit 1 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (407) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Helms Unit 1 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (408) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Helms Unit 1 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (409) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Helms Unit 1 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (410) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Helms Unit 1 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (411) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Melones Unit 1 sumop outage 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18)

Page 171: To determine the system impacts caused by the Project

A-150 GWF Henrietta SISAppendix A

3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Kearney 230 kV line outage HTT/RAS # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (412) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Melones Unit 1 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (413) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Melones Unit 1 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (414) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Melones Unit 1 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (415) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Melones Unit 1 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (416) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Melones Unit 1 sumop outage 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #1 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #1 line sumop # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (417) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Melones Unit 1 sumop outage 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #2 line sumop # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (418) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Melones Unit 1 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line

Page 172: To determine the system impacts caused by the Project

A-151 GWF Henrietta SISAppendix A

# 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (419) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Melones Unit 1 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (420) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Melones Unit 1 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (421) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Melones Unit 1 sumop outage 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (422) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Melones Unit 1 sumop outage 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 3 34600 0 "**" 0 # Trip Helms 1 for Herndon - Kearney 230 kV line outage HTT/RAS # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (423) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Melones Unit 1 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92)

Page 173: To determine the system impacts caused by the Project

A-152 GWF Henrietta SISAppendix A

1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (424) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Melones Unit 1 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (425) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Melones Unit 1 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (426) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Melones Unit 1 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (427) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Melones Unit 1 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (428) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Melones Unit 1 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 #

Page 174: To determine the system impacts caused by the Project

A-153 GWF Henrietta SISAppendix A

# # (429) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Melones Unit 1 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (430) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Melones Unit 1 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # -1 # EOF

Page 175: To determine the system impacts caused by the Project

A-154 GWF Henrietta SISAppendix A

Summer Off-Peak Category C Contingencies # Q272 2013 sumop category c contingency list (dctl and bus outages) # Yosemite and Fresno Divisions Zones 313 and 314 # # 2013 sumop category c contingency list # Yosemite Zone 313 # # # (1) C5 DCTL OUTAGE # Wilson - Atwater and El Capitan - Wilson 115 kV Lines 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 0 # # # (2) C5 DCTL OUTAGE # Wilson - Atwater and Atwater - El Capitan 115 kV Lines 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 0 # # # (3) C5 DCTL OUTAGE # Wilson - Merced #2 and Wilson - Oro Loma 115 kV Lines 1 34134 34144 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR MERCED 115.00 # 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) 0 # # # (4) C5 DCTL OUTAGE # Panoche - Schindler #1 and #2 115 kV Lines 1 34158 34350 "1 " 0 # line from PANOCHE 115.00 BRKR to (2) KAMM 115.00 1 34350 34352 "1 " 0 # line from KAMM 115.00 (2) to (2) CANTUA 115.00 1 34352 34432 "1 " 0 # line from CANTUA 115.00 (2) to (2) WESTLNDS 115.00 1 34432 34354 "1 " 0 # line from WESTLNDS 115.00 (2) to BRKR SCHINDLR 115.00 4 34350 0 "1 " 0 # LOAD-DROP KAMM 115.00 LOAD==3.85(1.75) 4 34352 0 "1 " 0 # LOAD-DROP CANTUA 115.00 LOAD==16.79(3.41) 4 34432 0 "16" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==0.94(0.23) 4 34432 0 "18" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==1.21(0.32) # 1 34141 34148 "1 " 0 # line from PAN2_TAP 115.00 (2) to (2) CHENY 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80

Page 176: To determine the system impacts caused by the Project

A-155 GWF Henrietta SISAppendix A

1 34148 34149 "1 " 0 # line from CHENY 115.00 (2) to (3) CHENYT 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (5) C5 DCTL OUTAGE # Gates - Panoche #1 and #2 230 kV Lines 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (6) C5 DCTL OUTAGE # Los Banos - Panoche #2 and Los Banos - Dos Amigos 230 kV Lines 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 0 # # # (7) C5 DCTL OUTAGE # Los Banos - Panoche #2 and Dos Amigos - Panoche 230 kV Lines 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (8) C5 DCTL OUTAGE # Los Banos - San Luis PGP #1 and #2 230 kV Lines 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (9) C5 DCTL OUTAGE # Bellota - Melones and Bellota - Warnerville 230 kV Lines 1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 30500 38208 "1 " 0 # line from BELLOTA 230.00 BRKR to (3) COTTLE B 230.00 1 38208 30515 "1 " 0 # line from COTTLE B 230.00 (3) to BRKR WARNERVL 230.00 4 38208 0 "2 " 0 # LOAD-DROP COTTLE B 230.00 LOAD==21.32(7.38) 0 # # # (10) C5 DCTL OUTAGE # Bellota - Melones and Warnerville - Wilson 230 kV Lines

Page 177: To determine the system impacts caused by the Project

A-156 GWF Henrietta SISAppendix A

1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (11) C5 DCTL OUTAGE # Bellota - Melones and Melones - Wilson 230 kV Lines 1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Melones - Wilson line 0 # # # (12) C5 DCTL OUTAGE # Melones - Wilson and Warnerville - Wilson 230 kV Lines 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Melones - Wilson line # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (13) C5 DCTL OUTAGE # Wilson - Borden #1 and #2 230 kV Lines 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) 0 # # # (14) C5 DCTL OUTAGE # Borden - Gregg #1 and #2 230 kV Lines 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line 0 # # # (15) C5 DCTL OUTAGE # Moss Landing - Panoche and Coburn - Panoche 230 kV Lines 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00

Page 178: To determine the system impacts caused by the Project

A-157 GWF Henrietta SISAppendix A

# 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (16) C5 DCTL OUTAGE # Panoche - Helm and Panoche - Kearney 230 kV Lines sumop outage 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Kearney 230 kV line outage HTT/RAS 0 # # # (17) BUS FAULT 30765 "LOSBANOS" Bus Section 1 # 1 30765 30670 "1" 0 # LINE from LOSBANOS 230.00 to WESTLEY 230.00 1 30765 30790 "2" 0 # LINE from LOSBANOS 230.00 to PANOCHE 230.00 1 30765 38625 "1" 0 # LINE from LOSBANOS 230.00 to SN LS PP 230.00 1 30765 38625 "2" 0 # LINE from LOSBANOS 230.00 to SN LS PP 230.00 2 30765 34214 "3" 0 # TRAN from LOSBANOS 230.00 to LOS BANS 70.00 6 30765 0 "v" 0 # drop Los Banos 230 kV shunt Caps 0 # # # (18) BUS FAULT 30765 "LOSBANOS" Bus Section 2 # 1 30765 30790 "1" 0 # LINE from LOSBANOS 230.00 to PANOCHE 230.00 1 30765 38615 "1" 0 # LINE from LOSBANOS 230.00 to DS AMIGO 230.00 2 30765 34214 "4" 0 # TRAN from LOSBANOS 230.00 to LOS BANS 70.00 0 # # # (19) BUS FAULT 30790 "PANOCHE" Bus Section 1 # 1 30790 30760 "1" 0 # LINE from PANOCHE 230.00 to COBURN 230.00 1 30790 30765 "1" 0 # LINE from PANOCHE 230.00 to LOSBANOS 230.00 1 30790 30765 "2" 0 # LINE from PANOCHE 230.00 to LOSBANOS 230.00 1 30790 30825 "1" 0 # LINE from PANOCHE 230.00 to MCMULLN1 230.00 1 30790 30900 "1" 0 # LINE from PANOCHE 230.00 to GATES 230.00 2 30790 30791 "1" 0 # TRAN from PANOCHE 230.00 to PNCHE 1M 230.00 0 # # # (20) BUS FAULT 30790 "PANOCHE" Bus Section 2 # 1 30790 30750 "1" 0 # LINE from PANOCHE 230.00 to MOSSLND2 230.00 1 30790 30793 "1" 0 # LINE from PANOCHE 230.00 to PANO_EC 230.00 1 30790 30873 "1" 0 # LINE from PANOCHE 230.00 to HELM 230.00 1 30790 30900 "2" 0 # LINE from PANOCHE 230.00 to GATES 230.00 1 30790 38615 "1" 0 # LINE from PANOCHE 230.00 to DS AMIGO 230.00 2 30790 34158 "2" 0 # TRAN from PANOCHE 230.00 to PANOCHE 115.00 0 # # # (21) BUS FAULT 34100 "CHWCHLLA" # 1 34100 34101 "1" 0 # LINE from CHWCHLLA 115.00 to CERTAN T 115.00 1 34100 34105 "1" 0 # LINE from CHWCHLLA 115.00 to CERTANJ1 115.00 4 34100 0 "1 " 0 # LOAD-DROP CHWCHLLA 115.00 LOAD==10.13(2.06) 4 34100 0 "2 " 0 # LOAD-DROP CHWCHLLA 115.00 LOAD==13.86(2.82) 0 #

Page 179: To determine the system impacts caused by the Project

A-158 GWF Henrietta SISAppendix A

# # (22) BUS FAULT 34104 "ATWATER" # 1 34104 34106 "1" 0 # LINE from ATWATER 115.00 to CASTLE 115.00 1 34104 34108 "1" 0 # LINE from ATWATER 115.00 to CRESEY T 115.00 1 34104 34134 "1" 0 # LINE from ATWATER 115.00 to WILSON A 115.00 4 34104 0 "1 " 0 # LOAD-DROP ATWATER 115.00 LOAD==32.40(6.57) 4 34104 0 "2 " 0 # LOAD-DROP ATWATER 115.00 LOAD==28.36(5.76) 0 # # # (23) BUS FAULT 34112 "EXCHEQUR" # 1 34112 34116 "1" 0 # LINE from EXCHEQUR 115.00 to LE GRAND 115.00 2 34112 34176 "1" 0 # TRAN from EXCHEQUR 115.00 to EXCHQRTP 115.00 0 # # # (24) BUS FAULT 34116 "LE GRAND" # 1 34116 34101 "1" 0 # LINE from LE GRAND 115.00 to CERTAN T 115.00 1 34116 34112 "1" 0 # LINE from LE GRAND 115.00 to EXCHEQUR 115.00 1 34116 34134 "1" 0 # LINE from LE GRAND 115.00 to WILSON A 115.00 1 34116 34154 "1" 0 # LINE from LE GRAND 115.00 to DAIRYLND 115.00 4 34116 0 "1 " 0 # LOAD-DROP LE GRAND 115.00 LOAD==13.41(2.72) 0 # # # (25) BUS FAULT 34134 "WILSON A" # 1 34134 34116 "1" 0 # LINE from WILSON A 115.00 to LE GRAND 115.00 1 34134 34104 "1" 0 # LINE from WILSON A 115.00 to ATWATER 115.00 1 34134 34136 "1" 0 # LINE from WILSON A 115.00 to WILSON B 115.00 1 34134 34144 "1" 0 # LINE from WILSON A 115.00 to MERCED 115.00 2 34134 30800 "1" 0 # TRAN from WILSON A 115.00 to WILSON 230.00 4 34134 0 "3 " 0 # LOAD-DROP WILSON A 115.00 LOAD==18.66(3.79) 6 34134 0 "v" 0 # drop Wilson A 115 kV shunt Caps 0 # # # (26) BUS FAULT 34136 "WILSON B" # 1 34136 34118 "1" 0 # LINE from WILSON B 115.00 to LE GRNDJ 115.00 1 34136 34134 "1" 0 # LINE from WILSON B 115.00 to WILSON A 115.00 1 34136 34138 "1" 0 # LINE from WILSON B 115.00 to EL CAPTN 115.00 1 34136 34144 "2" 0 # LINE from WILSON B 115.00 to MERCED 115.00 2 34136 30800 "2" 0 # TRAN from WILSON B 115.00 to WILSON 230.00 0 # # # (27) BUS FAULT 34138 "EL CAPTN" # 1 34138 34106 "1" 0 # LINE from EL CAPTN 115.00 to CASTLE 115.00 1 34138 34136 "1" 0 # LINE from EL CAPTN 115.00 to WILSON B 115.00 4 34138 0 "1 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==19.47(3.95) 4 34138 0 "2 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==25.91(5.26) 4 34138 0 "3 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==33.05(6.71) 0 # # # (28) BUS FAULT 34144 "MERCED" # 1 34144 34110 "1" 0 # LINE from MERCED 115.00 to ATWATR J 115.00 1 34144 34134 "1" 0 # LINE from MERCED 115.00 to WILSON A 115.00 1 34144 34136 "2" 0 # LINE from MERCED 115.00 to WILSON B 115.00 2 34144 34146 "2" 0 # TRAN from MERCED 115.00 to MERCED M 115.00 4 34144 0 "1 " 0 # LOAD-DROP MERCED 115.00 LOAD==37.10(7.53) 4 34144 0 "3 " 0 # LOAD-DROP MERCED 115.00 LOAD==19.45(3.95) 0 #

Page 180: To determine the system impacts caused by the Project

A-159 GWF Henrietta SISAppendix A

# # (29) BUS FAULT 34154 "DAIRYLND" # 1 34154 34116 "1" 0 # LINE from DAIRYLND 115.00 to LE GRAND 115.00 1 34154 34150 "1" 0 # LINE from DAIRYLND 115.00 to NEWHALL 115.00 4 34154 0 "1 " 0 # LOAD-DROP DAIRYLND 115.00 LOAD==25.82(5.24) 0 # # # (30) BUS FAULT 34158 "PANOCHE" Bus Section 1 # 1 34158 34149 "1" 0 # LINE from PANOCHE 115.00 to CHENYT 115.00 1 34158 34159 "1" 0 # LINE from PANOCHE 115.00 to PANOCHEJ 115.00 2 34158 30790 "2" 0 # TRAN from PANOCHE 115.00 to PANOCHE 230.00 2 34158 34186 "1" 0 # TRAN from PANOCHE 115.00 to DG_PAN1 13.80 0 # # # (31) BUS FAULT 34158 "PANOCHE" Bus Section 2 # 1 34158 34157 "1" 0 # LINE from PANOCHE 115.00 to PANOCHET 115.00 1 34158 34189 "1" 0 # LINE from PANOCHE 115.00 to STARWOOD 115.00 1 34158 34350 "1" 0 # LINE from PANOCHE 115.00 to KAMM 115.00 2 34158 30791 "1" 0 # TRAN from PANOCHE 115.00 to PNCHE 1M 230.00 0 # # # (32) BUS FAULT 34200 "ORO LOMA" # 1 34200 34218 "1" 0 # LINE from ORO LOMA 70.00 to DOS PALS 70.00 1 34200 34222 "1" 0 # LINE from ORO LOMA 70.00 to MRCYSPRS 70.00 1 34200 34234 "1" 0 # LINE from ORO LOMA 70.00 to POSO J1 70.00 2 34200 34162 "2" 0 # TRAN from ORO LOMA 70.00 to ORO LOMA 115.00 4 34200 0 "1 " 0 # LOAD-DROP ORO LOMA 70.00 LOAD==8.64(1.75) 0 # # # (33) BUS FAULT 34202 "MERCED" # 1 34202 34203 "1" 0 # LINE from MERCED 70.00 to ELNIDOTP 70.00 1 34202 34230 "1" 0 # LINE from MERCED 70.00 to MRCDFLLS 70.00 2 34202 34146 "2" 0 # TRAN from MERCED 70.00 to MERCED M 115.00 0 # # # (34) BUS FAULT 34206 "CANAL" # 1 34206 34212 "1" 0 # LINE from CANAL 70.00 to LVNGSTNT 70.00 1 34206 34216 "1" 0 # LINE from CANAL 70.00 to SNTA RTA 70.00 1 34206 34220 "1" 0 # LINE from CANAL 70.00 to ORTIGA 70.00 4 34206 0 "1 " 0 # LOAD-DROP CANAL 70.00 LOAD==30.56(6.21) 4 34206 0 "2 " 0 # LOAD-DROP CANAL 70.00 LOAD==31.27(6.35) 0 # # # (35) BUS FAULT 34214 "LOS BANS" # 1 34214 34208 "1" 0 # LINE from LOS BANS 70.00 to CHEVPIPE 70.00 1 34214 34272 "1" 0 # LINE from LOS BANS 70.00 to WRGHT PP 70.00 1 34214 34278 "1" 0 # LINE from LOS BANS 70.00 to PCHCO PP 70.00 1 34214 34282 "1" 0 # LINE from LOS BANS 70.00 to ONLL PMP 69.00 2 34214 30765 "3" 0 # TRAN from LOS BANS 70.00 to LOSBANOS 230.00 2 34214 30765 "4" 0 # TRAN from LOS BANS 70.00 to LOSBANOS 230.00 0 # # # (36) BUS FAULT 34216 "SNTA RTA" # 1 34216 34206 "1" 0 # LINE from SNTA RTA 70.00 to CANAL 70.00 1 34216 34218 "1" 0 # LINE from SNTA RTA 70.00 to DOS PALS 70.00

Page 181: To determine the system impacts caused by the Project

A-160 GWF Henrietta SISAppendix A

4 34216 0 "1 " 0 # LOAD-DROP SNTA RTA 70.00 LOAD==7.48(1.52) 0 # # # (37) BUS FAULT 34230 "MRCDFLLS" # 1 34230 34202 "1" 0 # LINE from MRCDFLLS 70.00 to MERCED 70.00 1 34230 34321 "1" 0 # LINE from MRCDFLLS 70.00 to MCSWAINJ 70.00 2 34230 34322 "1" 0 # TRAN from MRCDFLLS 70.00 to MERCEDFL 9.11 2 34230 34322 "2" 0 # TRAN from MRCDFLLS 70.00 to MERCEDFL 9.11 4 34230 0 "2 " 0 # LOAD-DROP MRCDFLLS 70.00 LOAD==8.94(1.82) 0 # # # (38) BUS FAULT 34238 "BONITA" # 1 34238 34236 "1" 0 # LINE from BONITA 70.00 to POSO J2 70.00 1 34238 34255 "1" 0 # LINE from BONITA 70.00 to TRIGO J 70.00 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 0 # # # (39) BUS FAULT 34240 "GLASS" # 1 34240 34237 "1" 0 # LINE from GLASS 70.00 to CANANDGA 70.00 1 34240 34256 "1" 0 # LINE from GLASS 70.00 to BORDEN 70.00 4 34240 0 "1 " 0 # LOAD-DROP GLASS 70.00 LOAD==9.05(4.89) 0 # # # (40) BUS FAULT 34252 "MADERA" # 1 34252 34254 "1" 0 # LINE from MADERA 70.00 to TRIGO 70.00 1 34252 34256 "1" 0 # LINE from MADERA 70.00 to BORDEN 70.00 1 34252 34256 "2" 0 # LINE from MADERA 70.00 to BORDEN 70.00 4 34252 0 "1 " 0 # LOAD-DROP MADERA 70.00 LOAD==17.99(3.65) 4 34252 0 "2 " 0 # LOAD-DROP MADERA 70.00 LOAD==23.16(4.71) 6 34252 0 "v" 0 # drop Madera 70 kV shunt Caps 0 # # # (41) BUS FAULT 34256 "BORDEN" # 1 34256 34252 "1" 0 # LINE from BORDEN 70.00 to MADERA 70.00 1 34256 34252 "2" 0 # LINE from BORDEN 70.00 to MADERA 70.00 1 34256 34240 "1" 0 # LINE from BORDEN 70.00 to GLASS 70.00 1 34256 34262 "1" 0 # LINE from BORDEN 70.00 to CASSIDY 70.00 2 34256 30805 "1" 0 # TRAN from BORDEN 70.00 to BORDEN 230.00 2 34256 30805 "2" 0 # TRAN from BORDEN 70.00 to BORDEN 230.00 0 # # # (42) BUS FAULT 34268 "MENDOTA" # 1 34268 34267 "1" 0 # LINE from MENDOTA 70.00 to TOMATAK 70.00 1 34268 34269 "1" 0 # LINE from MENDOTA 70.00 to BIOMSJCT 70.00 2 34268 34156 "1" 0 # TRAN from MENDOTA 70.00 to MENDOTA 115.00 0 # # # 2013 sumop category c contingency list # Fresno Zone 314 # # # (43) C5 DCTL OUTAGE # Gates - Schindler and Gates - Huron #1 70 kV Lines 1 34558 34560 "1 " 0 # line from HURON 70.00 BRKR to (2) CALFLAX 70.00 1 34560 34562 "1 " 0 # line from CALFLAX 70.00 (2) to BRKR SCHLNDLR 70.00

Page 182: To determine the system impacts caused by the Project

A-161 GWF Henrietta SISAppendix A

4 34560 0 "1 " 0 # LOAD-DROP CALFLAX 70.00 LOAD==6.53(1.33) 1 34552 34558 "2 " 0 # Must include Gates - Huron #2 in this outage # 1 34552 34558 "1 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0 # # # (44) C5 DCTL OUTAGE # Barton - Sanger and Manchester - Sanger 115 kV Lines 1 34359 34361 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR AIRWAYS 115.00 1 34359 34408 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR BARTON 115.00 1 34359 34366 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR SANGER 115.00 # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (45) C5 DCTL OUTAGE # Herndon - Barton and Herndon - Manchester 115 kV Lines 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 # 1 34410 34412 "1 " 0 # line from MANCHSTR 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (46) C5 DCTL OUTAGE # Herndon - Barton and Manchester - Sanger 115 kV Lines 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (47) C5 DCTL OUTAGE # Herndon - Bullard #1 and #2 115 kV Lines 1 34411 34416 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR BULLARD 115.00 1 34411 34412 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR HERNDON 115.00 # 1 34409 34413 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR PNEDLE 115.00 1 34409 34416 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR BULLARD 115.00 1 34409 34412 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR HERNDON 115.00 4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25)

Page 183: To determine the system impacts caused by the Project

A-162 GWF Henrietta SISAppendix A

4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 1 34411 34413 "1 " 1 # Switches in Pindale CB#12 to transfer load 4 34413 0 "**" 1 # Restore load at Pindale 0 # # # (48) C5 DCTL OUTAGE # Kerckhoff - Clovis - Sanger #1 and #2 115 kV Lines 1 34358 34360 "1 " 0 # line from KERCKHF2 115.00 BRKR to (3) WWARD JT 115.00 1 34360 34414 "1 " 0 # line from WWARD JT 115.00 (3) to BRKR WOODWARD 115.00 1 34360 34363 "1 " 0 # line from WWARD JT 115.00 (3) to (3) CLOVISJ1 115.00 1 34363 34362 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR CLOVIS-1 115.00 1 34363 34366 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR SANGER 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36) 4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34362 0 "**" 1 # Restore Load at Clovis 1 # 1 34364 34365 "1 " 0 # line from CLOVIS-2 115.00 BRKR to (3) CLOVISJ2 115.00 1 34365 34358 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR KERCKHF2 115.00 1 34365 34366 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR SANGER 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34364 0 "**" 1 # Restore Load at Clovis 2 0 # # # (49) C5 DCTL OUTAGE # Kingburg - Corcoran #1 and #2 115 kV Lines 1 34418 34420 "1 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 # 1 34418 34420 "2 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (50) C5 DCTL OUTAGE # Kings River - Sanger - Reedley and Balch - Sanger 115 kV Lines 1 34366 34389 "1 " 0 # line from SANGER 115.00 BRKR to (3) RAINBWTP 115.00 1 34389 34388 "1 " 0 # line from RAINBWTP 115.00 (3) to (1) RAINBW 115.00 1 34389 34394 "1 " 0 # line from RAINBWTP 115.00 (3) to (3) PIEDRA 1 115.00 1 34394 34380 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR REEDLEY 115.00 1 34394 34400 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR KNGSRVR1 115.00 4 34388 0 "1 " 0 # LOAD-DROP RAINBW 115.00 LOAD==16.20(3.29) # 1 34366 34396 "1 " 0 # line from SANGER 115.00 BRKR to (2) PIEDRA 2 115.00 1 34396 34398 "1 " 0 # line from PIEDRA 2 115.00 (2) to (2) BALCH 115.00 2 34398 34624 "1 " 0 # TRAN from BALCH 115.00 (2) to (1) BALCH 1 13.20 4 34624 0 "1 " 0 # LOAD-DROP BALCH 1 13.20 LOAD==0.26(0.00) 3 34624 0 "1 " 0 # GEN-DROP BALCH 1 13.20 GEN==27.00(8.33) 0 # #

Page 184: To determine the system impacts caused by the Project

A-163 GWF Henrietta SISAppendix A

# (51) C5 DCTL OUTAGE # McCall - Kingsburg #1 and #2 115 kV Lines 1 34370 34385 "1 " 0 # line from MC CALL 115.00 BRKR to (3) KINGS J1 115.00 1 34385 34417 "1 " 0 # line from KINGS J1 115.00 (3) to (2) KINGS J2 115.00 1 34385 34425 "1 " 0 # line from KINGS J1 115.00 (3) to (3) KCOGNJCT 115.00 1 34417 34418 "1 " 0 # line from KINGS J2 115.00 (2) to BRKR KINGSBRG 115.00 1 34425 34387 "1 " 0 # line from KCOGNJCT 115.00 (3) to (1) SUNMAID 115.00 1 34425 34427 "1 " 0 # line from KCOGNJCT 115.00 (3) to (2) GRDNGLS2 115.00 1 34427 34386 "1 " 0 # line from GRDNGLS2 115.00 (2) to (2) KNGSCOGN 115.00 2 34386 34642 "1 " 0 # TRAN from KNGSCOGN 115.00 (2) to BRKR KINGSBUR 9.11 4 34387 0 "1 " 0 # LOAD-DROP SUNMAID 115.00 LOAD==3.40(3.28) 3 34642 0 "1 " 0 # GEN-DROP KINGSBUR 9.11 GEN==34.00(17.30) # 1 34418 34423 "1 " 0 # line from KINGSBRG 115.00 BRKR to (3) GAURD J1 115.00 1 34423 34370 "1 " 0 # line from GAURD J1 115.00 (3) to BRKR MC CALL 115.00 1 34423 34421 "1 " 0 # line from GAURD J1 115.00 (3) to (2) GAURD J2 115.00 1 34421 34424 "1 " 0 # line from GAURD J2 115.00 (2) to (1) GRDN GLS 115.00 4 34424 0 "1 " 0 # LOAD-DROP GRDN GLS 115.00 LOAD==3.50(1.15) 4 34418 0 "3 " 0 # Kingsburg Bank #3 will also be dropped on this outage 0 # # # (52) C5 DCTL OUTAGE # McCall - Sanger #1 and #2 115 kV Lines 1 34366 34370 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 # 1 34366 34370 "2 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (53) C5 DCTL OUTAGE # McCall - West Fresno and California Ave. - West Fresno 115 kV Lines 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 # 1 34402 34404 "1 " 0 # line from CAL AVE 115.00 BRKR to BRKR WST FRSO 115.00 0 # # # (54) C5 DCTL OUTAGE # McCall - West Fresno and California Ave. - McCall 115 kV Lines 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 # 1 34390 34370 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR MC CALL 115.00 1 34390 34402 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR CAL AVE 115.00 4 34390 0 "1 " 0 # LOAD-DROP DANISHCM 115.00 LOAD==4.10(3.51) 0 # # # (55) C5 DCTL OUTAGE # Gates - Gregg and Gates - McCall 230 kV Lines sumop outage

Page 185: To determine the system impacts caused by the Project

A-164 GWF Henrietta SISAppendix A

1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS # 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 # # # (56) C5 DCTL OUTAGE # Panoche - Kearney and Gates - Gregg 230 kV Lines sumop outage 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Kearney 230 kV line outage HTT/RAS # 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS 0 # # # (57) C5 DCTL OUTAGE # Panoche - Kearney and Panoche - Helm 230 kV Lines sumop outage 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Q055BUS1 230 kV line outage HTT/RAS # 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 0 # # # (58) C5 DCTL OUTAGE # Panoche - Kearney and Helm - McCall 230 kV Lines sumop outage 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 3 34600 0 "**" 0 # Trip Helms 1 for Panoche - Kearney 230 kV line outage HTT/RAS # 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 0 #

Page 186: To determine the system impacts caused by the Project

A-165 GWF Henrietta SISAppendix A

# # (59) C5 DCTL OUTAGE # Helm - McCall and Gates - McCall 230 kV Lines 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 # # # (60) C5 DCTL OUTAGE # Helms - Gregg #1 and #2 230 kV Lines 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #1 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #1 line sumop # 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line sumop 3 34602 0 "**" 0 # Drop unit#2 with a loss Helm - Gregg #2 line sumop 0 # # # (61) C5 DCTL OUTAGE # Gregg - Herndon #1 and #2 230 kV Lines 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line 0 # # # (62) C5 DCTL OUTAGE # Herndon - Kearney and Herndon - Ashlan 230 kV Lines sumop outage 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 3 34600 0 "**" 0 # Trip Helms 1 for Herndon - Kearney 230 kV line outage HTT/RAS # 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 0 # # # (63) C5 DCTL OUTAGE # Herndon - Kearney and Gates - Gregg 230 kV Lines sumop outage 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 3 34600 0 "**" 0 # Trip Helms 1 for Herndon - Kearney 230 kV line outage HTT/RAS # 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00

Page 187: To determine the system impacts caused by the Project

A-166 GWF Henrietta SISAppendix A

1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS 0 # # # (64) C5 DCTL OUTAGE # Gates - Gregg and Gregg - Ashlan 230 kV Lines sumop outage 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 3 34600 0 "**" 0 # Trip Helms 1 for Gates - Gregg 230 kV line outage HTT/RAS # 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (65) C5 DCTL OUTAGE # Herndon - Ashlan and Gregg - Ashlan 230 kV Lines 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (66) C5 DCTL OUTAGE # Haas - McCall and Balch - McCall 230 kV Lines 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00

Page 188: To determine the system impacts caused by the Project

A-167 GWF Henrietta SISAppendix A

2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) 0 # # # (67) C5 DCTL OUTAGE # Morro Bay - Gates and Templeton - Gates 230 kV Lines 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 0 # # # (68) C5 DCTL OUTAGE # Gates - Midway and Gates - Arco 230 kV Lines 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 0 # # # (69) BUS FAULT 30820 "HELMS PP" # 1 30820 30810 "1" 0 # LINE from HELMS PP 230.00 to GREGG 230.00 1 30820 30810 "2" 0 # LINE from HELMS PP 230.00 to GREGG 230.00 2 30820 34600 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 1 18.00 2 30820 34602 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 2 18.00 2 30820 34604 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 3 18.00 0 # # # (70) BUS FAULT 30830 "KEARNEY" # 1 30830 30825 "1" 0 # LINE from KEARNEY 230.00 to MCMULLN1 230.00 1 30830 30835 "1" 0 # LINE from KEARNEY 230.00 to HERNDON 230.00 2 30830 34480 "2" 0 # TRAN from KEARNEY 230.00 to KEARNEY 70.00 0 # # # (71) BUS FAULT 30835 "HERNDON" 230 kV Bus Section 1 # 1 30835 30810 "1" 0 # LINE from HERNDON 230.00 to GREGG 230.00 1 30835 30830 "1" 0 # LINE from HERNDON 230.00 to KEARNEY 230.00 2 30835 30882 "1" 0 # TRAN from HERNDON 230.00 to HERNDN1M 115.00 0 # # # (72) BUS FAULT 30835 "HERNDON" 230 kV Bus Section 2 # 1 30835 30810 "2" 0 # LINE from HERNDON 230.00 to GREGG 230.00 1 30835 30840 "1" 0 # LINE from HERNDON 230.00 to FGRDN T1 230.00 2 30835 30883 "2" 0 # TRAN from HERNDON 230.00 to HERNDN2M 115.00

Page 189: To determine the system impacts caused by the Project

A-168 GWF Henrietta SISAppendix A

0 # # # (73) BUS FAULT 30841 "FIGRDN 1" # 1 30841 30840 "1" 0 # LINE from FIGRDN 1 230.00 to FGRDN T1 230.00 1 30841 30846 "1" 0 # LINE from FIGRDN 1 230.00 to FIGRDN 2 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 0 # # # (74) BUS FAULT 30846 "FIGRDN 2" # 1 30846 30841 "1" 0 # LINE from FIGRDN 2 230.00 to FIGRDN 1 230.00 1 30846 30845 "1" 0 # LINE from FIGRDN 2 230.00 to FGRDN T2 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 0 # # # (75) BUS FAULT 30850 "ASHLAN" # 1 30850 30840 "1" 0 # LINE from ASHLAN 230.00 to FGRDN T1 230.00 1 30850 30845 "1" 0 # LINE from ASHLAN 230.00 to FGRDN T2 230.00 4 30850 0 "1 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==69.20(13.40) 4 30850 0 "2 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==64.54(12.84) 4 30850 0 "3 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==65.51(12.49) 0 # # # (76) BUS FAULT 30873 "HELM" # 1 30873 30790 "1" 0 # LINE from HELM 230.00 to PANOCHE 230.00 1 30873 30875 "1" 0 # LINE from HELM 230.00 to MC CALL 230.00 2 30873 34474 "1" 0 # TRAN from HELM 230.00 to HELM 70.00 0 # # # (77) BUS FAULT 30874 "P0615STN" # 1 30874 30875 "1" 0 # LINE from P0615STN 230.00 to MC CALL 230.00 1 30874 30875 "2" 0 # LINE from P0615STN 230.00 to MC CALL 230.00 2 30874 34685 "1" 0 # TRAN from P0615STN 230.00 to P0615CT1 16.50 2 30874 34686 "1" 0 # TRAN from P0615STN 230.00 to P0615CT2 16.50 2 30874 34687 "1" 0 # TRAN from P0615STN 230.00 to P0615STG 16.50 0 # # # (78) BUS FAULT 30875 "MC CALL" 230 kV Bus Section 1 # 1 30875 30870 "1" 0 # LINE from MC CALL 230.00 to PINE FLT 230.00 1 30875 30874 "1" 0 # LINE from MC CALL 230.00 to P0615STN 230.00 1 30875 30880 "1" 0 # LINE from MC CALL 230.00 to HENTAP2 230.00 2 30875 30877 "2" 0 # TRAN from MC CALL 230.00 to MCCALL2M 115.00 6 30875 0 "v" 0 # SVD from MC CALL 230.00 0 # # # (79) BUS FAULT 30875 "MC CALL" 230 kV Bus Section 2 # 1 30875 30873 "1" 0 # LINE from MC CALL 230.00 to HELM 230.00 1 30875 30860 "1" 0 # LINE from MC CALL 230.00 to BALCH3TP 230.00 1 30875 30874 "2" 0 # LINE from MC CALL 230.00 to P0615STN 230.00 2 30875 30876 "1" 0 # TRAN from MC CALL 230.00 to MCCALL1M 115.00 2 30875 30878 "3" 0 # TRAN from MC CALL 230.00 to MCCALL3M 115.00 0 # # # (80) BUS FAULT 30881 "HENRIETA" #

Page 190: To determine the system impacts caused by the Project

A-169 GWF Henrietta SISAppendix A

1 30881 30879 "1" 0 # LINE from HENRIETA 230.00 to HENTAP1 230.00 1 30881 30880 "1" 0 # LINE from HENRIETA 230.00 to HENTAP2 230.00 2 30881 34430 "3" 0 # TRAN from HENRIETA 230.00 to HENRETTA 115.00 2 30881 34540 "2" 0 # TRAN from HENRIETA 230.00 to HENRITTA 70.00 2 30881 34540 "4" 0 # TRAN from HENRIETA 230.00 to HENRITTA 70.00 0 # # # (81) BUS FAULT 30900 "GATES" 230 kV Bus Section 1D # 1 30900 30790 "1" 0 # LINE from GATES 230.00 to PANOCHE 230.00 1 30900 30905 "1" 0 # LINE from GATES 230.00 to TEMPLETN 230.00 2 30900 30901 "1" 0 # TRAN from GATES 230.00 to GATES 1M 230.00 6 30900 0 "v" 0 # SVD from GATES 230.00 0 # # # (82) BUS FAULT 30900 "GATES" 230 kV Bus Section 2D # 1 30900 30790 "2" 0 # LINE from GATES 230.00 to PANOCHE 230.00 1 30900 30915 "1" 0 # LINE from GATES 230.00 to MORROBAY 230.00 0 # # # (83) BUS FAULT 30900 "GATES" 230 kV Bus Section 1E # 1 30900 30879 "1" 0 # LINE from GATES 230.00 to HENTAP1 230.00 1 30900 30935 "1" 0 # LINE from GATES 230.00 to ARCO 230.00 0 # # # (84) BUS FAULT 30900 "GATES" 230 kV Bus Section 2E # 1 30900 30880 "1" 0 # LINE from GATES 230.00 to HENTAP2 230.00 1 30900 30970 "1" 0 # LINE from GATES 230.00 to MIDWAY 230.00 0 # # # (85) BUS FAULT 34356 "KERCKHF1" # 1 34356 34123 "2" 0 # LINE from KERCKHF1 115.00 to K1-JCT 115.00 1 34356 34358 "1" 0 # LINE from KERCKHF1 115.00 to KERCKHF2 115.00 2 34356 34344 "1" 0 # TRAN from KERCKHF1 115.00 to KERCKHOF 6.60 0 # # # (86) BUS FAULT 34358 "KERCKHF2" # 1 34358 34123 "2" 0 # LINE from KERCKHF2 115.00 to K1-JCT 115.00 1 34358 34356 "1" 0 # LINE from KERCKHF2 115.00 to KERCKHF1 115.00 1 34358 34360 "1" 0 # LINE from KERCKHF2 115.00 to WWARD JT 115.00 1 34358 34365 "1" 0 # LINE from KERCKHF2 115.00 to CLOVISJ2 115.00 2 34358 34308 "1" 0 # TRAN from KERCKHF2 115.00 to KERCKHOF 13.80 0 # # # (87) BUS FAULT 34361 "AIRWAYS" # 1 34361 34357 "1" 0 # LINE from AIRWAYS 115.00 to AIRWAYJ1 115.00 1 34361 34359 "1" 0 # LINE from AIRWAYS 115.00 to AIRWAYJ2 115.00 4 34361 0 "1 " 0 # LOAD-DROP AIRWAYS 115.00 LOAD==38.39(7.43) 4 34361 0 "2 " 0 # LOAD-DROP AIRWAYS 115.00 LOAD==12.60(2.56) 0 # # # (88) BUS FAULT 34362 "CLOVIS-1" # 1 34362 34363 "1" 0 # LINE from CLOVIS-1 115.00 to CLOVISJ1 115.00 1 34362 34364 "1" 0 # LINE from CLOVIS-1 115.00 to CLOVIS-2 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36)

Page 191: To determine the system impacts caused by the Project

A-170 GWF Henrietta SISAppendix A

4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 0 # # # (89) BUS FAULT 34364 "CLOVIS-2" # 1 34364 34362 "1" 0 # LINE from CLOVIS-2 115.00 to CLOVIS-1 115.00 1 34364 34365 "1" 0 # LINE from CLOVIS-2 115.00 to CLOVISJ2 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 0 # # # (90) BUS FAULT 34366 "SANGER" # 1 34366 34363 "1" 0 # LINE from SANGER 115.00 to CLOVISJ1 115.00 1 34366 34365 "1" 0 # LINE from SANGER 115.00 to CLOVISJ2 115.00 1 34366 34359 "1" 0 # LINE from SANGER 115.00 to AIRWAYJ2 115.00 1 34366 34368 "1" 0 # LINE from SANGER 115.00 to LASPALMS 115.00 1 34366 34370 "1" 0 # LINE from SANGER 115.00 to MC CALL 115.00 1 34366 34370 "2" 0 # LINE from SANGER 115.00 to MC CALL 115.00 1 34366 34370 "3" 0 # LINE from SANGER 115.00 to MC CALL 115.00 1 34366 34372 "1" 0 # LINE from SANGER 115.00 to MALAGA 115.00 1 34366 34389 "1" 0 # LINE from SANGER 115.00 to RAINBWTP 115.00 1 34366 34396 "1" 0 # LINE from SANGER 115.00 to PIEDRA 2 115.00 1 34366 34488 "1" 0 # LINE from SANGER 115.00 to SANGER 70.00 2 34366 34590 "1" 0 # TRAN from SANGER 115.00 to SANGR3T 115.00 4 34366 0 "1 " 0 # LOAD-DROP SANGER 115.00 LOAD==24.26(4.93) 0 # # # (91) BUS FAULT 34372 "MALAGA" # 1 34372 34366 "1" 0 # LINE from MALAGA 115.00 to SANGER 115.00 1 34372 34376 "1" 0 # LINE from MALAGA 115.00 to PPG 115.00 1 34372 34379 "1" 0 # LINE from MALAGA 115.00 to MALAGATP 115.00 1 34372 34381 "1" 0 # LINE from MALAGA 115.00 to KRCDP 115.00 4 34372 0 "1 " 0 # LOAD-DROP MALAGA 115.00 LOAD==25.25(5.12) 4 34372 0 "2 " 0 # LOAD-DROP MALAGA 115.00 LOAD==22.76(4.62) 4 34372 0 "3 " 0 # LOAD-DROP MALAGA 115.00 LOAD==23.13(4.69) 0 # # # (92) BUS FAULT 34378 "GATES" # 2 34378 30901 "1" 0 # TRAN from GATES 115.00 to GATES 1M 230.00 2 34378 34552 "2" 0 # TRAN from GATES 115.00 to GATES 70.00 4 34378 0 "3 " 0 # LOAD-DROP GATES 115.00 LOAD==19.45(3.95) 0 # # # (93) BUS FAULT 34380 "REEDLEY" # 1 34380 34384 "1" 0 # LINE from REEDLEY 115.00 to GERAWAN 115.00 1 34380 34394 "1" 0 # LINE from REEDLEY 115.00 to PIEDRA 1 115.00 2 34380 34492 "1" 0 # TRAN from REEDLEY 115.00 to REEDLEY 70.00 2 34380 34492 "2" 0 # TRAN from REEDLEY 115.00 to REEDLEY 70.00 4 34380 0 "3 " 0 # LOAD-DROP REEDLEY 115.00 LOAD==26.17(5.31) 0 # # # (94) BUS FAULT 34382 "WAHTOKE" # 1 34382 34370 "1" 0 # LINE from WAHTOKE 115.00 to MC CALL 115.00 1 34382 34384 "1" 0 # LINE from WAHTOKE 115.00 to GERAWAN 115.00 4 34382 0 "2 " 0 # LOAD-DROP WAHTOKE 115.00 LOAD==30.36(6.17) 4 34382 0 "3 " 0 # LOAD-DROP WAHTOKE 115.00 LOAD==20.84(4.24) 0 # # # (95) BUS FAULT 34400 "KNGSRVR1"

Page 192: To determine the system impacts caused by the Project

A-171 GWF Henrietta SISAppendix A

# 1 34400 34394 "1" 0 # LINE from KNGSRVR1 115.00 to PIEDRA 1 115.00 2 34400 34616 "1" 0 # TRAN from KNGSRVR1 115.00 to KINGSRIV 13.80 0 # # # (96) BUS FAULT 34402 "CAL AVE" # 1 34402 34390 "1" 0 # LINE from CAL AVE 115.00 to DANISHCM 115.00 1 34402 34404 "1" 0 # LINE from CAL AVE 115.00 to WST FRSO 115.00 4 34402 0 "1 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==28.95(5.87) 4 34402 0 "2 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==31.26(6.35) 4 34402 0 "3 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==24.42(4.96) 0 # # # (97) BUS FAULT 34404 "WST FRSO" # 1 34404 34370 "1" 0 # LINE from WST FRSO 115.00 to MC CALL 115.00 1 34404 34402 "1" 0 # LINE from WST FRSO 115.00 to CAL AVE 115.00 4 34404 0 "1 " 0 # LOAD-DROP WST FRSO 115.00 LOAD==37.55(7.63) 4 34404 0 "2 " 0 # LOAD-DROP WST FRSO 115.00 LOAD==39.04(7.93) 0 # # # (98) BUS FAULT 34408 "BARTON" # 1 34408 34359 "1" 0 # LINE from BARTON 115.00 to AIRWAYJ2 115.00 1 34408 34412 "1" 0 # LINE from BARTON 115.00 to HERNDON 115.00 4 34408 0 "1 " 0 # LOAD-DROP BARTON 115.00 LOAD==43.27(8.79) 4 34408 0 "2 " 0 # LOAD-DROP BARTON 115.00 LOAD==37.15(7.54) 4 34408 0 "3 " 0 # LOAD-DROP BARTON 115.00 LOAD==26.96(5.47) 0 # # # (99) BUS FAULT 34410 "MANCHSTR" # 1 34410 34357 "1" 0 # LINE from MANCHSTR 115.00 to AIRWAYJ1 115.00 1 34410 34412 "1" 0 # LINE from MANCHSTR 115.00 to HERNDON 115.00 4 34410 0 "1 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==25.28(5.13) 4 34410 0 "2 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==25.47(5.18) 4 34410 0 "3 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==36.21(7.36) 0 # # # (100) BUS FAULT 34412 "HERNDON" 115 kV Bus Section 1 # 1 34412 34408 "1" 0 # LINE from HERNDON 115.00 to BARTON 115.00 1 34412 34409 "1" 0 # LINE from HERNDON 115.00 to PNDLJ2 115.00 2 34412 30882 "1" 0 # TRAN from HERNDON 115.00 to HERNDN1M 115.00 0 # # # (101) BUS FAULT 34412 "HERNDON" 115 kV Bus Section 2 # 1 34412 34410 "1" 0 # LINE from HERNDON 115.00 to MANCHSTR 115.00 1 34412 34411 "1" 0 # LINE from HERNDON 115.00 to PNDLJ1 115.00 1 34412 34422 "1" 0 # LINE from HERNDON 115.00 to CHLDHOSP 115.00 0 # # # (102) BUS FAULT 34413 "PNEDLE" # 1 34413 34409 "1" 0 # LINE from PNEDLE 115.00 to PNDLJ2 115.00 1 34413 34411 "1" 0 # LINE from PNEDLE 115.00 to PNDLJ1 115.00 4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25) 4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 0 # #

Page 193: To determine the system impacts caused by the Project

A-172 GWF Henrietta SISAppendix A

# (103) BUS FAULT 34414 "WOODWARD" # 1 34414 34360 "1" 0 # LINE from WOODWARD 115.00 to WWARD JT 115.00 1 34414 34422 "1" 0 # LINE from WOODWARD 115.00 to CHLDHOSP 115.00 4 34414 0 "1 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==42.25(8.58) 4 34414 0 "2 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==52.69(10.70) 4 34414 0 "3 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==44.09(8.95) 0 # # # (104) BUS FAULT 34416 "BULLARD" # 1 34416 34409 "1" 0 # LINE from BULLARD 115.00 to PNDLJ2 115.00 1 34416 34411 "1" 0 # LINE from BULLARD 115.00 to PNDLJ1 115.00 4 34416 0 "1 " 0 # LOAD-DROP BULLARD 115.00 LOAD==44.87(9.11) 4 34416 0 "2 " 0 # LOAD-DROP BULLARD 115.00 LOAD==44.65(9.07) 4 34416 0 "3 " 0 # LOAD-DROP BULLARD 115.00 LOAD==42.52(8.63) 0 # # # (105) BUS FAULT 34418 "KINGSBRG" 115 kV Bus Section D # 1 34418 34417 "1" 0 # LINE from KINGSBRG 115.00 to KINGS J2 115.00 1 34418 34428 "1" 0 # LINE from KINGSBRG 115.00 to CONTADNA 115.00 1 34418 34420 "2" 0 # LINE from KINGSBRG 115.00 to CORCORAN 115.00 4 34418 0 "1 " 0 # LOAD-DROP KINGSBRG 115.00 LOAD==39.24(7.96) 0 # # # (106) BUS FAULT 34418 "KINGSBRG" 115 kV Bus Section E # 1 34418 34420 "1" 0 # LINE from KINGSBRG 115.00 to CORCORAN 115.00 1 34418 34423 "1" 0 # LINE from KINGSBRG 115.00 to GAURD J1 115.00 2 34418 34576 "2" 0 # TRAN from KINGSBRG 115.00 to KNGLOBUS 70.00 4 34418 0 "3 " 0 # LOAD-DROP KINGSBRG 115.00 LOAD==24.32(4.94) 0 # # # (107) BUS FAULT 34420 "CORCORAN" # 1 34420 34391 "1" 0 # LINE from CORCORAN 115.00 to QUEBECTP 115.00 1 34420 34418 "1" 0 # LINE from CORCORAN 115.00 to KINGSBRG 115.00 1 34420 34418 "2" 0 # LINE from CORCORAN 115.00 to KINGSBRG 115.00 2 34420 34528 "2" 0 # TRAN from CORCORAN 115.00 to CORCORAN 70.00 4 34420 0 "3 " 0 # LOAD-DROP CORCORAN 115.00 LOAD==16.21(3.30) 4 34420 0 "4 " 0 # LOAD-DROP CORCORAN 115.00 LOAD==17.81(3.61) 0 # # # (108) BUS FAULT 34426 "ALPAUGH" # 1 34426 34391 "1" 0 # LINE from ALPAUGH 115.00 to QUEBECTP 115.00 1 34426 34700 "1" 0 # LINE from ALPAUGH 115.00 to SMYRNA 115.00 4 34426 0 "2 " 0 # LOAD-DROP ALPAUGH 115.00 LOAD==5.62(1.14) 0 # # # (109) BUS FAULT 34430 "HENRETTA" # 1 34430 34521 "1" 0 # LINE from HENRETTA 115.00 to LEPRNOFD 115.00 2 34430 30881 "3" 0 # TRAN from HENRETTA 115.00 to HENRIETA 230.00 0 # # # (110) BUS FAULT 34452 "WISHON" # 1 34452 34260 "1" 0 # LINE from WISHON 70.00 to SJNO2 70.00 1 34452 34491 "1" 0 # LINE from WISHON 70.00 to AUBRYTP 70.00 2 34452 34658 "1" 0 # TRAN from WISHON 70.00 to WISHON 2.30 0

Page 194: To determine the system impacts caused by the Project

A-173 GWF Henrietta SISAppendix A

# # # (111) BUS FAULT 34460 "GUERNSEY" # 1 34460 34462 "1" 0 # LINE from GUERNSEY 70.00 to GUR3TPT 70.00 1 34460 34528 "1" 0 # LINE from GUERNSEY 70.00 to CORCORAN 70.00 4 34460 0 "1 " 0 # LOAD-DROP GUERNSEY 70.00 LOAD==10.51(2.13) 0 # # # (112) BUS FAULT 34464 "COPPRMNE" # 1 34464 34454 "1" 0 # LINE from COPPRMNE 70.00 to RIVERROC 70.00 1 34464 34478 "1" 0 # LINE from COPPRMNE 70.00 to TVY VLLY 70.00 1 34464 34638 "1" 0 # LINE from COPPRMNE 70.00 to FRANTDM 70.00 1 34464 34491 "1" 0 # LINE from COPPRMNE 70.00 to AUBRYTP 70.00 4 34464 0 "1 " 0 # LOAD-DROP COPPRMNE 70.00 LOAD==22.96(4.67) 0 # # # (113) BUS FAULT 34466 "BIOLA" # 1 34466 34264 "1" 0 # LINE from BIOLA 70.00 to EL PECO 70.00 1 34466 34482 "1" 0 # LINE from BIOLA 70.00 to OLDKERN 70.00 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 0 # # # (114) BUS FAULT 34472 "SAN JOQN" # 1 34472 34471 "1" 0 # LINE from SAN JOQN 70.00 to SNJQJCT 70.00 1 34472 34473 "1" 0 # LINE from SAN JOQN 70.00 to SNJQTP 70.00 4 34472 0 "1 " 0 # LOAD-DROP SAN JOQN 70.00 LOAD==6.44(1.31) 4 34472 0 "2 " 0 # LOAD-DROP SAN JOQN 70.00 LOAD==3.92(0.79) 0 # # # (115) BUS FAULT 34474 "HELM" # 1 34474 34471 "1" 0 # LINE from HELM 70.00 to SNJQJCT 70.00 1 34474 34473 "1" 0 # LINE from HELM 70.00 to SNJQTP 70.00 1 34474 34556 "1" 0 # LINE from HELM 70.00 to STRD JCT 70.00 1 34474 34564 "1" 0 # LINE from HELM 70.00 to STROUD 70.00 2 34474 30873 "1" 0 # TRAN from HELM 70.00 to HELM 230.00 0 # # # (116) BUS FAULT 34478 "TVY VLLY" # 1 34478 34464 "1" 0 # LINE from TVY VLLY 70.00 to COPPRMNE 70.00 1 34478 34492 "1" 0 # LINE from TVY VLLY 70.00 to REEDLEY 70.00 4 34478 0 "1 " 0 # LOAD-DROP TVY VLLY 70.00 LOAD==10.27(2.09) 0 # # # (117) BUS FAULT 34480 "KEARNEY" # 1 34480 34481 "1" 0 # LINE from KEARNEY 70.00 to FRWWTAP 70.00 1 34480 34482 "1" 0 # LINE from KEARNEY 70.00 to OLDKERN 70.00 1 34480 34512 "1" 0 # LINE from KEARNEY 70.00 to CARUTHRS 70.00 2 34480 30830 "2" 0 # TRAN from KEARNEY 70.00 to KEARNEY 230.00 0 # # # (118) BUS FAULT 34484 "KERMAN" # 1 34484 34475 "1" 0 # LINE from KERMAN 70.00 to AGRCJCT 70.00 1 34484 34481 "1" 0 # LINE from KERMAN 70.00 to FRWWTAP 70.00 4 34484 0 "1 " 0 # LOAD-DROP KERMAN 70.00 LOAD==19.44(3.95) 4 34484 0 "2 " 0 # LOAD-DROP KERMAN 70.00 LOAD==11.78(2.39)

Page 195: To determine the system impacts caused by the Project

A-174 GWF Henrietta SISAppendix A

0 # # # (119) BUS FAULT 34486 "CALIFRNV" # 1 34486 34488 "1" 0 # LINE from CALIFRNV 70.00 to SANGER 70.00 1 34486 34488 "2" 0 # LINE from CALIFRNV 70.00 to SANGER 70.00 0 # # # (120) BUS FAULT 34488 "SANGER" # 1 34488 34486 "1" 0 # LINE from SANGER 70.00 to CALIFRNV 70.00 1 34488 34486 "2" 0 # LINE from SANGER 70.00 to CALIFRNV 70.00 1 34488 34366 "1" 0 # LINE from SANGER 70.00 to SANGER 115.00 1 34488 34487 "1" 0 # LINE from SANGER 70.00 to SNGRJCT 70.00 2 34488 34590 "1" 0 # TRAN from SANGER 70.00 to SANGR3T 115.00 0 # # # (121) BUS FAULT 34492 "REEDLEY" # 1 34492 34478 "1" 0 # LINE from REEDLEY 70.00 to TVY VLLY 70.00 1 34492 34490 "1" 0 # LINE from REEDLEY 70.00 to PARLIER 70.00 1 34492 34497 "1" 0 # LINE from REEDLEY 70.00 to DNUBAJCT 70.00 1 34492 34526 "1" 0 # LINE from REEDLEY 70.00 to ORSI JCT 70.00 2 34492 34380 "1" 0 # TRAN from REEDLEY 70.00 to REEDLEY 115.00 2 34492 34380 "2" 0 # TRAN from REEDLEY 70.00 to REEDLEY 115.00 4 34492 0 "1 " 0 # LOAD-DROP REEDLEY 70.00 LOAD==17.42(3.54) 0 # # # (122) BUS FAULT 34500 "DINUBA" # 1 34500 34496 "1" 0 # LINE from DINUBA 70.00 to STCRRL J 70.00 1 34500 34497 "1" 0 # LINE from DINUBA 70.00 to DNUBAJCT 70.00 4 34500 0 "1 " 0 # LOAD-DROP DINUBA 70.00 LOAD==19.23(3.91) 4 34500 0 "2 " 0 # LOAD-DROP DINUBA 70.00 LOAD==9.33(1.90) 0 # # # (123) BUS FAULT 34512 "CARUTHRS" # 1 34512 34480 "1" 0 # LINE from CARUTHRS 70.00 to KEARNEY 70.00 1 34512 34510 "1" 0 # LINE from CARUTHRS 70.00 to CMDN JCT 70.00 4 34512 0 "1 " 0 # LOAD-DROP CARUTHRS 70.00 LOAD==19.63(3.98) 0 # # # (124) BUS FAULT 34518 "LEMOORE" # 1 34518 34520 "1" 0 # LINE from LEMOORE 70.00 to LPRNO TP 70.00 1 34518 34522 "1" 0 # LINE from LEMOORE 70.00 to HNFRD SW 70.00 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) 0 # # # (125) BUS FAULT 34528 "CORCORAN" # 1 34528 34460 "1" 0 # LINE from CORCORAN 70.00 to GUERNSEY 70.00 1 34528 34530 "1" 0 # LINE from CORCORAN 70.00 to BSWLL TP 70.00 2 34528 34420 "2" 0 # TRAN from CORCORAN 70.00 to CORCORAN 115.00 0 # # # (126) BUS FAULT 34540 "HENRITTA" # 1 34540 34514 "1" 0 # LINE from HENRITTA 70.00 to MUSLSLGH 70.00 1 34540 34520 "1" 0 # LINE from HENRITTA 70.00 to LPRNO TP 70.00

Page 196: To determine the system impacts caused by the Project

A-175 GWF Henrietta SISAppendix A

1 34540 34537 "1" 0 # LINE from HENRITTA 70.00 to GWF_HENR 70.00 1 34540 34542 "1" 0 # LINE from HENRITTA 70.00 to JCBSCRNR 70.00 1 34540 34544 "1" 0 # LINE from HENRITTA 70.00 to TLRE LKE 70.00 2 34540 30881 "2" 0 # TRAN from HENRITTA 70.00 to HENRIETA 230.00 2 34540 30881 "4" 0 # TRAN from HENRITTA 70.00 to HENRIETA 230.00 4 34540 0 "1 " 0 # LOAD-DROP HENRITTA 70.00 LOAD==8.20(1.67) 0 # # # (127) BUS FAULT 34544 "TLRE LKE" # 1 34544 34540 "1" 0 # LINE from TLRE LKE 70.00 to HENRITTA 70.00 1 34544 34550 "1" 0 # LINE from TLRE LKE 70.00 to CHEVPLIN 70.00 1 34544 34580 "1" 0 # LINE from TLRE LKE 70.00 to BDGR HLL 70.00 4 34544 0 "1 " 0 # LOAD-DROP TLRE LKE 70.00 LOAD==6.79(1.38) 0 # # # (128) BUS FAULT 34552 "GATES" # 1 34552 34548 "1" 0 # LINE from GATES 70.00 to KETTLEMN 70.00 1 34552 34184 "1" 0 # LINE from GATES 70.00 to GATS2_TP 70.00 1 34552 34558 "1" 0 # LINE from GATES 70.00 to HURON 70.00 1 34552 34558 "2" 0 # LINE from GATES 70.00 to HURON 70.00 1 34552 34578 "1" 0 # LINE from GATES 70.00 to JACALITO 70.00 2 34552 34378 "2" 0 # TRAN from GATES 70.00 to GATES 115.00 0 # # # (129) BUS FAULT 34558 "HURON" # 1 34558 34552 "1" 0 # LINE from HURON 70.00 to GATES 70.00 1 34558 34552 "2" 0 # LINE from HURON 70.00 to GATES 70.00 1 34558 34560 "1" 0 # LINE from HURON 70.00 to CALFLAX 70.00 4 34558 34552 "1 " 1 # LOAD-TRANSFER HURON 70.00 TO GATES 70.00 LOAD==15.33(3.11) 0 # # # (130) BUS FAULT 34562 "SCHLNDLR" # 1 34562 34556 "1" 0 # LINE from SCHLNDLR 70.00 to STRD JCT 70.00 1 34562 34560 "1" 0 # LINE from SCHLNDLR 70.00 to CALFLAX 70.00 1 34562 34566 "1" 0 # LINE from SCHLNDLR 70.00 to PLSNTVLY 70.00 2 34562 34354 "1" 0 # TRAN from SCHLNDLR 70.00 to SCHINDLR 115.00 4 34562 0 "1 " 0 # LOAD-DROP SCHLNDLR 70.00 LOAD==9.59(1.95) 0 # # # (131) BUS FAULT 34564 "STROUD" # 1 34564 34556 "1" 0 # LINE from STROUD 70.00 to STRD JCT 70.00 1 34564 34474 "1" 0 # LINE from STROUD 70.00 to HELM 70.00 4 34564 0 "1 " 0 # LOAD-DROP STROUD 70.00 LOAD==13.09(2.66) 0 # # # (132) BUS FAULT 34570 "COLNGA 2" # 1 34570 34184 "1" 0 # LINE from COLNGA 2 70.00 to GATS2_TP 70.00 1 34570 34566 "1" 0 # LINE from COLNGA 2 70.00 to PLSNTVLY 70.00 1 34570 34572 "1" 0 # LINE from COLNGA 2 70.00 to TORNADO 70.00 2 34570 34652 "1" 0 # TRAN from COLNGA 2 70.00 to CHV.COAL 9.11 4 34570 0 "1 " 0 # LOAD-DROP COLNGA 2 70.00 LOAD==8.23(1.67) 0 # # # (133) BUS FAULT 34574 "COLNGA 1" # 1 34574 34572 "1" 0 # LINE from COLNGA 1 70.00 to TORNADO 70.00

Page 197: To determine the system impacts caused by the Project

A-176 GWF Henrietta SISAppendix A

1 34574 34578 "1" 0 # LINE from COLNGA 1 70.00 to JACALITO 70.00 1 34574 36354 "1" 0 # LINE from COLNGA 1 70.00 to SAN MIGL 70.00 4 34574 0 "1 " 0 # LOAD-DROP COLNGA 1 70.00 LOAD==9.34(1.90) 4 34574 0 "2 " 0 # LOAD-DROP COLNGA 1 70.00 LOAD==9.99(2.03) 0 # # # (134) BUS FAULT 34576 "KNGLOBUS" # 1 34576 34456 "1" 0 # LINE from KNGLOBUS 70.00 to HRDWK TP 70.00 1 34576 34508 "1" 0 # LINE from KNGLOBUS 70.00 to CAMDEN 70.00 2 34576 34418 "2" 0 # TRAN from KNGLOBUS 70.00 to KINGSBRG 115.00 0 # # -1 # EOF

Page 198: To determine the system impacts caused by the Project

A-177 GWF Henrietta SISAppendix A

Spring Peak Category B Contingencies # Q272 2013 sprpk category b contingency list # Yosemite and Fresno Divisions Zones 313 and 314 # # 2013 sprpk category b contingency list # Yosemite Zone 313 # # # (1) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (2) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 0 # # # (3) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (4) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (5) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (6) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (7) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 0 # # # (8) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (9) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 199: To determine the system impacts caused by the Project

A-178 GWF Henrietta SISAppendix A

1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (10) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30793 "1 " 0 # line from PANOCHE 230.00 BRKR to (3) PANO_EC 230.00 2 30793 34326 "1 " 0 # TRAN from PANO_EC 230.00 (3) to (1) PANO_BS1 13.80 2 30793 34327 "1 " 0 # TRAN from PANO_EC 230.00 (3) to (1) PANO_BS2 13.80 4 34326 0 "ss" 0 # LOAD-DROP PANO_BS1 13.80 LOAD==4.50(2.49) 4 34327 0 "ss" 0 # LOAD-DROP PANO_BS2 13.80 LOAD==4.50(2.49) 3 34326 0 "1 " 0 # GEN-DROP PANO_BS1 13.80 GEN==102.50(20.25) 3 34326 0 "2 " 0 # GEN-DROP PANO_BS1 13.80 GEN==102.50(20.25) 3 34327 0 "3 " 0 # GEN-DROP PANO_BS2 13.80 GEN==102.50(20.25) 3 34327 0 "4 " 0 # GEN-DROP PANO_BS2 13.80 GEN==102.50(20.25) 0 # # # (11) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 0 # # # (12) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 0 # # # (13) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (14) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (15) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) 0 # # # (16) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69)

Page 200: To determine the system impacts caused by the Project

A-179 GWF Henrietta SISAppendix A

0 # # # (17) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30806 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR Q196 230.00 0 # # # (18) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30806 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR Q196 230.00 0 # # # (19) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line 0 # # # (20) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line 0 # # # (21) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34017 34010 "1 " 0 # line from CRWS LDG 60.00 (1) to (3) CRWS LDJ 60.00 1 34010 34006 "1 " 0 # line from CRWS LDJ 60.00 (3) to BRKR PATTERSN 60.00 1 34010 34012 "1 " 0 # line from CRWS LDJ 60.00 (3) to (2) GUSTN JT 60.00 1 34012 34014 "1 " 0 # line from GUSTN JT 60.00 (2) to BRKR NEWMAN 60.00 4 34017 0 "1 " 0 # LOAD-DROP CRWS LDG 60.00 LOAD==3.73(0.17) 1 34016 34017 "1 " 1 # Switches in Crows Landing SW 57 to transfer load 4 34017 0 "**" 1 # Restore Load at Crows Landing 0 # # # (22) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00 2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80 2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94)

Page 201: To determine the system impacts caused by the Project

A-180 GWF Henrietta SISAppendix A

4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11) 3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) 0 # # # (23) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 0 # # # (24) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34104 34108 "1 " 0 # line from ATWATER 115.00 BRKR to (3) CRESEY T 115.00 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (1) ATWATR J 115.00 1 34108 34114 "1 " 0 # line from CRESEY T 115.00 (3) to (3) JRWD GEN 115.00 1 34114 34124 "1 " 0 # line from JRWD GEN 115.00 (3) to (2) JR WOOD 115.00 2 34114 34332 "1 " 0 # TRAN from JRWD GEN 115.00 (3) to (1) JRWCOGEN 9.11 1 34124 34140 "1 " 0 # line from JR WOOD 115.00 (2) to (1) CRESSEY 115.00 4 34124 0 "1 " 0 # LOAD-DROP JR WOOD 115.00 LOAD==11.70(10.32) 4 34140 0 "1 " 0 # LOAD-DROP CRESSEY 115.00 LOAD==19.02(3.86) 3 34332 0 "1 " 0 # GEN-DROP JRWCOGEN 9.11 GEN==3.80(5.40) 0 # # # (25) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34105 34121 "1 " 0 # line from CERTANJ1 115.00 (2) to (3) SHARON T 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34121 34128 "1 " 0 # line from SHARON T 115.00 (3) to (3) OAKH_JCT 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34128 34123 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) K1-JCT 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) 0 # # # (26) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (3) ATWATR J 115.00 1 34110 34130 "1 " 0 # line from ATWATR J 115.00 (3) to (2) LIVNGSTN 115.00 1 34110 34144 "1 " 0 # line from ATWATR J 115.00 (3) to BRKR MERCED 115.00

Page 202: To determine the system impacts caused by the Project

A-181 GWF Henrietta SISAppendix A

1 34130 34132 "1 " 0 # line from LIVNGSTN 115.00 (2) to (1) GALLO 115.00 4 34130 0 "3 " 0 # LOAD-DROP LIVNGSTN 115.00 LOAD==24.58(5.00) 4 34132 0 "1 " 0 # LOAD-DROP GALLO 115.00 LOAD==4.30(3.68) 0 # # # (27) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34112 34116 "1 " 0 # line from EXCHEQUR 115.00 BRKR to BRKR LE GRAND 115.00 3 34306 0 "1 " 0 # Exchequer Unit will trip for this outage 4 34228 0 "**" 0 # Mariposa Loads will drop if bus is below 64 kV, this is anticipate 0 # # # (28) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34116 34134 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR WILSON A 115.00 0 # # # (29) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 0 # # # (30) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) 0 # # # (31) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 0 # # # (32) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34136 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR WILSON B 115.00 0 # # # (33) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34134 34144 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR MERCED 115.00 0 # # # (34) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 0

Page 203: To determine the system impacts caused by the Project

A-182 GWF Henrietta SISAppendix A

# # # (35) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34136 34144 "2 " 0 # line from WILSON B 115.00 BRKR to BRKR MERCED 115.00 0 # # # (36) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34141 34148 "1 " 0 # line from PAN2_TAP 115.00 (2) to (2) CHENY 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80 1 34148 34149 "1 " 0 # line from CHENY 115.00 (2) to (3) CHENYT 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (37) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34150 34154 "1 " 0 # line from NEWHALL 115.00 (2) to BRKR DAIRYLND 115.00 1 34150 34178 "1 " 0 # line from NEWHALL 115.00 (2) to (3) MADERAPR 115.00 1 34178 34156 "1 " 0 # line from MADERAPR 115.00 (3) to BRKR MENDOTA 115.00 2 34178 34179 "1 " 0 # TRAN from MADERAPR 115.00 (3) to (1) MADERA_G 13.80 4 34150 0 "2 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==8.55(1.73) 4 34150 0 "3 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==10.62(2.16) 4 34179 0 "ss" 0 # LOAD-DROP MADERA_G 13.80 LOAD==3.60(0.85) 3 34179 0 "1 " 0 # GEN-DROP MADERA_G 13.80 GEN==28.60(6.34) 0 # # # (38) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34157 34156 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR MENDOTA 115.00 1 34157 34158 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR PANOCHE 115.00 3 34186 0 "1 " 0 # DG_PAN Unit trips for Panoche - Mendota 115 kV outage 0 # # # (39) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34158 34189 "1 " 0 # line from PANOCHE 115.00 BRKR to (3) STARWOOD 115.00 2 34189 34328 "1 " 0 # TRAN from STARWOOD 115.00 (3) to (1) STARGT1 13.80 2 34189 34329 "1 " 0 # TRAN from STARWOOD 115.00 (3) to (1) STARGT2 13.80 4 34328 0 "ss" 0 # LOAD-DROP STARGT1 13.80 LOAD==1.00(0.55) 4 34329 0 "ss" 0 # LOAD-DROP STARGT2 13.80 LOAD==1.00(0.55) 3 34328 0 "1 " 0 # GEN-DROP STARGT1 13.80 GEN==60.94(9.59) 3 34329 0 "2 " 0 # GEN-DROP STARGT2 13.80 GEN==60.94(9.59) 0 # # # (40) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 204: To determine the system impacts caused by the Project

A-183 GWF Henrietta SISAppendix A

1 34158 34350 "1 " 0 # line from PANOCHE 115.00 BRKR to (2) KAMM 115.00 1 34350 34352 "1 " 0 # line from KAMM 115.00 (2) to (2) CANTUA 115.00 1 34352 34432 "1 " 0 # line from CANTUA 115.00 (2) to (2) WESTLNDS 115.00 1 34432 34354 "1 " 0 # line from WESTLNDS 115.00 (2) to BRKR SCHINDLR 115.00 4 34350 0 "1 " 0 # LOAD-DROP KAMM 115.00 LOAD==3.85(1.75) 4 34352 0 "1 " 0 # LOAD-DROP CANTUA 115.00 LOAD==16.79(3.41) 4 34432 0 "16" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==0.94(0.23) 4 34432 0 "18" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==1.21(0.32) 0 # # # (41) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34159 34158 "1 " 0 # line from PANOCHEJ 115.00 (3) to BRKR PANOCHE 115.00 1 34159 34160 "1 " 0 # line from PANOCHEJ 115.00 (3) to (2) HAMMONDS 115.00 1 34159 34180 "1 " 0 # line from PANOCHEJ 115.00 (3) to (3) OXFRDJCT 115.00 1 34160 34161 "1 " 0 # line from HAMMONDS 115.00 (2) to (3) DFSTP 115.00 1 34161 34162 "1 " 0 # line from DFSTP 115.00 (3) to BRKR ORO LOMA 115.00 1 34161 34164 "1 " 0 # line from DFSTP 115.00 (3) to (1) DFS 115.00 1 34180 34166 "1 " 0 # line from OXFRDJCT 115.00 (3) to (1) OXFORD 115.00 1 34180 34181 "1 " 0 # line from OXFRDJCT 115.00 (3) to (3) WSTLDJCT 115.00 1 34181 34182 "1 " 0 # line from WSTLDJCT 115.00 (3) to (1) WSTLD1RA 115.00 1 34181 34183 "1 " 0 # line from WSTLDJCT 115.00 (3) to (3) LUISJCT 115.00 1 34183 34163 "1 " 0 # line from LUISJCT 115.00 (3) to (1) LUIS_#3 115.00 1 34183 34165 "1 " 0 # line from LUISJCT 115.00 (3) to (1) LUIS_#5 115.00 4 34160 0 "1 " 0 # LOAD-DROP HAMMONDS 115.00 LOAD==10.00(2.03) 4 34164 0 "1 " 0 # LOAD-DROP DFS 115.00 LOAD==1.37(1.06) 4 34166 0 "1 " 0 # LOAD-DROP OXFORD 115.00 LOAD==3.87(1.76) 4 34182 0 "1 " 0 # LOAD-DROP WSTLD1RA 115.00 LOAD==2.98(0.71) 4 34163 0 "1 " 0 # LOAD-DROP LUIS_#3 115.00 LOAD==3.30(0.78) 4 34165 0 "1 " 0 # LOAD-DROP LUIS_#5 115.00 LOAD==3.40(0.81) 0 # # # (42) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34172 34170 "1 " 0 # line from WESTLAND 70.00 (2) to (1) WESIX 70.00 1 34172 34271 "1 " 0 # line from WESTLAND 70.00 (2) to (3) WSTLDJCT 70.00 1 34271 34269 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) BIOMSJCT 70.00 1 34271 34469 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) GFFNJCT 70.00 1 34269 34268 "1 " 0 # line from BIOMSJCT 70.00 (3) to BRKR MENDOTA 70.00 1 34269 34270 "1 " 0 # line from BIOMSJCT 70.00 (3) to (2) BIOMASS 70.00 2 34270 34334 "1 " 0 # TRAN from BIOMASS 70.00 (2) to (1) BIO PWR 9.11 1 34469 34470 "1 " 0 # line from GFFNJCT 70.00 (3) to (1) GIFFEN 70.00 1 34469 34471 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) SNJQJCT 70.00

Page 205: To determine the system impacts caused by the Project

A-184 GWF Henrietta SISAppendix A

1 34471 34472 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR SAN JOQN 70.00 1 34471 34474 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR HELM 70.00 4 34172 0 "1 " 0 # LOAD-DROP WESTLAND 70.00 LOAD==3.20(0.76) 4 34170 0 "1 " 0 # LOAD-DROP WESIX 70.00 LOAD==1.60(0.38) 4 34470 0 "1 " 0 # LOAD-DROP GIFFEN 70.00 LOAD==9.59(1.95) 3 34334 0 "1 " 0 # GEN-DROP BIO PWR 9.11 GEN==21.80(10.99) 1 34472 34473 "1 " 1 # Switches in San Joaquin CB22 to transfer load 4 34472 0 "**" 1 # Restore Load at San Joaquin 0 # # # (43) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34218 "1 " 0 # line from ORO LOMA 70.00 BRKR to (2) DOS PALS 70.00 1 34218 34216 "1 " 0 # line from DOS PALS 70.00 (2) to BRKR SNTA RTA 70.00 4 34218 0 "1 " 0 # LOAD-DROP DOS PALS 70.00 LOAD==10.29(2.09) 0 # # # (44) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00 1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93) 0 # # # (45) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34200 34234 "1 " 0 # line from ORO LOMA 70.00 BRKR to (2) POSO J1 70.00 1 34234 34266 "1 " 0 # line from POSO J1 70.00 (2) to (2) FIREBAGH 70.00 1 34266 34267 "1 " 0 # line from FIREBAGH 70.00 (2) to (2) TOMATAK 70.00 1 34267 34268 "1 " 0 # line from TOMATAK 70.00 (2) to BRKR MENDOTA 70.00 4 34266 0 "1 " 0 # LOAD-DROP FIREBAGH 70.00 LOAD==11.13(2.26) 4 34267 0 "1 " 0 # LOAD-DROP TOMATAK 70.00 LOAD==6.40(4.97) 0 # # # (46) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34202 34203 "1 " 0 # line from MERCED 70.00 BRKR to (3) ELNIDOTP 70.00 1 34203 34205 "1 " 0 # line from ELNIDOTP 70.00 (3) to (2) ELNIDO 70.00 1 34203 34236 "1 " 0 # line from ELNIDOTP 70.00 (3) to (1) POSO J2 70.00 2 34205 34330 "1 " 0 # TRAN from ELNIDO 70.00 (2) to (1) ELNIDO 13.80 4 34330 0 "ss" 0 # LOAD-DROP ELNIDO 13.80 LOAD==2.00(1.11) 3 34330 0 "1 " 0 # GEN-DROP ELNIDO 13.80 GEN==12.50(5.69)

Page 206: To determine the system impacts caused by the Project

A-185 GWF Henrietta SISAppendix A

0 # # # (47) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34202 34230 "1 " 0 # line from MERCED 70.00 BRKR to BRKR MRCDFLLS 70.00 0 # # # (48) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34204 34212 "1 " 0 # line from LIVNGSTN 70.00 (1) to (3) LVNGSTNT 70.00 1 34212 34206 "1 " 0 # line from LVNGSTNT 70.00 (3) to BRKR CANAL 70.00 1 34212 34210 "1 " 0 # line from LVNGSTNT 70.00 (3) to (2) SNTA NLA 70.00 1 34210 34208 "1 " 0 # line from SNTA NLA 70.00 (2) to (2) CHEVPIPE 70.00 1 34208 34214 "1 " 0 # line from CHEVPIPE 70.00 (2) to BRKR LOS BANS 70.00 4 34204 0 "2 " 0 # LOAD-DROP LIVNGSTN 70.00 LOAD==5.51(1.12) 4 34210 0 "1 " 0 # LOAD-DROP SNTA NLA 70.00 LOAD==6.75(1.37) 4 34210 0 "2 " 0 # LOAD-DROP SNTA NLA 70.00 LOAD==9.50(1.93) 4 34208 0 "1 " 0 # LOAD-DROP CHEVPIPE 70.00 LOAD==0.63(0.42) 0 # # # (49) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34206 34216 "1 " 0 # line from CANAL 70.00 BRKR to BRKR SNTA RTA 70.00 0 # # # (50) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34214 34278 "1 " 0 # line from LOS BANS 70.00 BRKR to (2) PCHCO PP 70.00 1 34278 34280 "1 " 0 # line from PCHCO PP 70.00 (2) to (2) INTL TUR 70.00 2 34280 34342 "1 " 0 # TRAN from INTL TUR 70.00 (2) to (1) INT.TURB 9.11 4 34278 0 "1 " 0 # LOAD-DROP PCHCO PP 70.00 LOAD==18.00(4.10) 3 34342 0 "1 " 0 # GEN-DROP INT.TURB 9.11 GEN==1.10(0.00) 0 # # # (51) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34214 34282 "1 " 0 # line from LOS BANS 70.00 BRKR to (2) ONLL PMP 69.00 2 34282 34316 "1 " 0 # TRAN from ONLL PMP 69.00 (2) to (1) ONEILPMP 9.11 4 34282 0 "1 " 0 # LOAD-DROP ONLL PMP 69.00 LOAD==6.00(1.20) 3 34316 0 "1 " 0 # GEN-DROP ONEILPMP 9.11 GEN==0.50(0.00) 0 # # # (52) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34228 34232 "1 " 0 # line from MARIPOS2 70.00 (1) to BRKR EXCHEQUR 70.00 4 34228 0 "1 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.01(1.83) 4 34228 0 "2 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.37(1.90) 1 34228 34244 "1 " 1 # Switches in Mariposa SW 39 to transfer load 4 34228 0 "**" 1 # Restore Load at Mariposa 0 #

Page 207: To determine the system impacts caused by the Project

A-186 GWF Henrietta SISAppendix A

# # (53) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34232 34242 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (2) BER VLLY 70.00 1 34242 34244 "1 " 0 # line from BER VLLY 70.00 (2) to (2) BRCEBG J 70.00 1 34244 34246 "1 " 0 # line from BRCEBG J 70.00 (2) to (3) SAXONCRK 70.00 1 34246 34248 "1 " 0 # line from SAXONCRK 70.00 (3) to (2) INDN FLT 70.00 2 34246 34346 "1 " 0 # TRAN from SAXONCRK 70.00 (3) to (1) SAXNCK L 4.16 1 34248 34250 "1 " 0 # line from INDN FLT 70.00 (2) to (1) YOSEMITE 70.00 4 34242 0 "1 " 0 # LOAD-DROP BER VLLY 70.00 LOAD==5.91(1.20) 4 34246 0 "1 " 0 # LOAD-DROP SAXONCRK 70.00 LOAD==0.03(0.02) 4 34248 0 "1 " 0 # LOAD-DROP INDN FLT 70.00 LOAD==2.02(0.41) 4 34250 0 "1 " 0 # LOAD-DROP YOSEMITE 70.00 LOAD==2.90(0.00) 0 # # # (54) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita 0 # # # (55) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34252 34256 "1 " 0 # line from MADERA 70.00 BRKR to BRKR BORDEN 70.00 0 # # # (56) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34252 34256 "2 " 0 # line from MADERA 70.00 BRKR to BRKR BORDEN 70.00 0 # # # (57) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34256 34240 "1 " 0 # line from BORDEN 70.00 BRKR to BRKR GLASS 70.00 0 # # # (58) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34256 34262 "1 " 0 # line from BORDEN 70.00 BRKR to (2) CASSIDY 70.00

Page 208: To determine the system impacts caused by the Project

A-187 GWF Henrietta SISAppendix A

1 34262 34454 "1 " 0 # line from CASSIDY 70.00 (2) to (2) RIVERROC 70.00 1 34454 34464 "1 " 0 # line from RIVERROC 70.00 (2) to BRKR COPPRMNE 70.00 4 34262 0 "1 " 0 # LOAD-DROP CASSIDY 70.00 LOAD==14.31(2.90) 4 34454 0 "1 " 0 # LOAD-DROP RIVERROC 70.00 LOAD==2.01(1.83) 0 # # # (59) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34259 34261 "1 " 0 # line from NRTHFORK 70.00 (3) to (2) SJNO3 70.00 1 34259 34260 "1 " 0 # line from NRTHFORK 70.00 (3) to (3) SJNO2 70.00 2 34259 34340 "1 " 0 # TRAN from NRTHFORK 70.00 (3) to (1) N.FORK E 9.11 2 34261 34633 "1 " 0 # TRAN from SJNO3 70.00 (2) to (1) SJ3GEN 9.11 1 34260 34452 "1 " 0 # line from SJNO2 70.00 (3) to BRKR WISHON 70.00 2 34260 34631 "1 " 0 # TRAN from SJNO2 70.00 (3) to (1) SJ2GEN 9.11 4 34261 0 "2 " 0 # LOAD-DROP SJNO3 70.00 LOAD==6.95(1.41) 4 34260 0 "2 " 0 # LOAD-DROP SJNO2 70.00 LOAD==3.22(0.66) 4 34340 0 "1 " 0 # LOAD-DROP N.FORK E 9.11 LOAD==1.21(0.25) 3 34633 0 "1 " 0 # GEN-DROP SJ3GEN 9.11 GEN==1.00(0.00) 3 34631 0 "1 " 0 # GEN-DROP SJ2GEN 9.11 GEN==2.00(0.00) 0 # # # (60) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34321 34226 "1 " 0 # line from MCSWAINJ 70.00 (3) to (2) MC SWAIN 70.00 1 34321 34230 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR MRCDFLLS 70.00 1 34321 34232 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR EXCHEQUR 70.00 2 34226 34320 "1 " 0 # TRAN from MC SWAIN 70.00 (2) to (1) MCSWAIN 9.11 3 34320 0 "1 " 0 # GEN-DROP MCSWAIN 9.11 GEN==10.00(2.00) 0 # # # (61) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Melones - Wilson line 0 # # # (62) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (63) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30765 (30069) 30050 34302 : 2 30765 30050 "1 " 0 # TRAN from LOSBANOS 230.00 BRKR to (1) LOSBANOS 500.00 0 # # # (64) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) #

Page 209: To determine the system impacts caused by the Project

A-188 GWF Henrietta SISAppendix A

# **** 3-WINDING TRANSFORMER 30790 (30791) 34158 34310 : 2 30790 34158 "1 " 0 # TRAN from PANOCHE 230.00 BRKR to (1) PANOCHE 115.00 0 # # # (65) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 30790 34158 "2 " 0 # TRAN from PANOCHE 230.00 BRKR to BRKR PANOCHE 115.00 0 # # # (66) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 34112 (34176) 34232 34306 : 2 34112 34232 "1 " 0 # TRAN from EXCHEQUR 115.00 BRKR to (4) EXCHEQUR 70.00 1 34232 34228 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) MARIPOS2 70.00 1 34232 34242 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) BER VLLY 70.00 1 34232 34321 "1 " 0 # line from EXCHEQUR 70.00 BRKR to (1) MCSWAINJ 70.00 4 34228 0 "1 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.01(1.83) 4 34228 0 "2 " 0 # LOAD-DROP MARIPOS2 70.00 LOAD==9.37(1.90) 1 34228 34244 "1 " 1 # Switches in Mariposa SW 39 to transfer load 4 34228 0 "**" 1 # Restore Load at Mariposa 0 # # # (67) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34134 30800 "1 " 0 # TRAN from WILSON A 115.00 BRKR to BRKR WILSON 230.00 0 # # # (68) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34136 30800 "2 " 0 # TRAN from WILSON B 115.00 BRKR to BRKR WILSON 230.00 0 # # # (69) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 34144 (34146) 34202 34312 : 2 34144 34202 "2 " 0 # TRAN from MERCED 115.00 BRKR to (1) MERCED 70.00 0 # # # (70) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34200 34162 "2 " 0 # TRAN from ORO LOMA 70.00 BRKR to (3) ORO LOMA 115.00 1 34162 34161 "1 " 0 # line from ORO LOMA 115.00 BRKR to (1) DFSTP 115.00 1 34162 34168 "1 " 0 # line from ORO LOMA 115.00 BRKR to (1) EL NIDO 115.00 0 # # # (71) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34214 30765 "3 " 0 # TRAN from LOS BANS 70.00 BRKR to BRKR LOSBANOS 230.00 0 #

Page 210: To determine the system impacts caused by the Project

A-189 GWF Henrietta SISAppendix A

# # (72) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34214 30765 "4 " 0 # TRAN from LOS BANS 70.00 BRKR to BRKR LOSBANOS 230.00 0 # # # (73) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34256 30805 "1 " 0 # TRAN from BORDEN 70.00 BRKR to BRKR BORDEN 230.00 0 # # # (74) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34256 30805 "2 " 0 # TRAN from BORDEN 70.00 BRKR to BRKR BORDEN 230.00 0 # # # (75) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34268 34156 "1 " 0 # TRAN from MENDOTA 70.00 BRKR to (3) MENDOTA 115.00 1 34156 34178 "1 " 0 # line from MENDOTA 115.00 BRKR to (1) MADERAPR 115.00 1 34156 34157 "1 " 0 # line from MENDOTA 115.00 BRKR to (1) PANOCHET 115.00 4 34156 0 "1 " 0 # LOAD-DROP MENDOTA 115.00 LOAD==24.55(4.99) 0 # # # (76) B1 GENERATOR OUTAGE # 3 34142 0 "1" 0 # WHD_PAN2 13.80 PGEN=49.00 QGEN=-22.43 0 # # # (77) B1 GENERATOR OUTAGE # 3 34179 0 "1" 0 # MADERA_G 13.80 PGEN=28.60 QGEN=3.67 0 # # # (78) B1 GENERATOR OUTAGE # 3 34186 0 "1" 0 # DG_PAN1 13.80 PGEN=49.00 QGEN=-17.22 0 # # # (79) B1 GENERATOR OUTAGE # 3 34301 0 "1" 0 # CHOWCOGN 13.80 PGEN=50.00 QGEN=0.72 0 # # # (80) B1 GENERATOR OUTAGE # 3 34305 0 "1" 0 # CHWCHLA2 13.80 PGEN=12.50 QGEN=7.35 0 # # # (81) B1 GENERATOR OUTAGE # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # #

Page 211: To determine the system impacts caused by the Project

A-190 GWF Henrietta SISAppendix A

# (82) B1 GENERATOR OUTAGE # 3 34316 0 "1" 0 # ONEILPMP 9.11 PGEN=0.52 QGEN=0.00 0 # # # (83) B1 GENERATOR OUTAGE # 3 34320 0 "1" 0 # MCSWAIN 9.11 PGEN=10.00 QGEN=0.00 0 # # # (84) B1 GENERATOR OUTAGE # 3 34322 0 "1" 0 # MERCEDFL 9.11 PGEN=3.50 QGEN=2.00 0 # # # (85) B1 GENERATOR OUTAGE # 3 34326 0 "1" 0 # PANO_BS1 13.80 PGEN=102.50 QGEN=25.42 0 # # # (86) B1 GENERATOR OUTAGE # 3 34326 0 "2" 0 # PANO_BS1 13.80 PGEN=102.50 QGEN=25.42 0 # # # (87) B1 GENERATOR OUTAGE # 3 34327 0 "3" 0 # PANO_BS2 13.80 PGEN=102.50 QGEN=25.42 0 # # # (88) B1 GENERATOR OUTAGE # 3 34327 0 "4" 0 # PANO_BS2 13.80 PGEN=102.50 QGEN=25.42 0 # # # (89) B1 GENERATOR OUTAGE # 3 34328 0 "1" 0 # STARGT1 13.80 PGEN=60.94 QGEN=13.94 0 # # # (90) B1 GENERATOR OUTAGE # 3 34329 0 "2" 0 # STARGT2 13.80 PGEN=60.94 QGEN=13.94 0 # # # (91) B1 GENERATOR OUTAGE # 3 34330 0 "1" 0 # ELNIDO 13.80 PGEN=12.50 QGEN=4.15 0 # # # (92) B1 GENERATOR OUTAGE # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=3.80 QGEN=5.40 0 # # # (93) B1 GENERATOR OUTAGE # 3 34334 0 "1" 0 # BIO PWR 9.11 PGEN=21.80 QGEN=8.92 0

Page 212: To determine the system impacts caused by the Project

A-191 GWF Henrietta SISAppendix A

# # # (94) B1 GENERATOR OUTAGE # 3 34342 0 "1" 0 # INT.TURB 9.11 PGEN=1.10 QGEN=0.00 0 # # # (95) B1 GENERATOR OUTAGE # 3 34631 0 "1" 0 # SJ2GEN 9.11 PGEN=2.00 QGEN=0.00 0 # # # (96) B1 GENERATOR OUTAGE # 3 34633 0 "1" 0 # SJ3GEN 9.11 PGEN=1.00 QGEN=0.00 0 # # # (97) B1 GENERATOR OUTAGE # 3 34335 0 "1" 0 # Q196GT1 16.50 PGEN=192.50 QGEN=31.08 0 # # # (98) B1 GENERATOR OUTAGE # 3 34336 0 "2" 0 # Q196GT2 16.50 PGEN=192.50 QGEN=31.08 0 # # # (99) B1 GENERATOR OUTAGE # 3 34337 0 "3" 0 # Q196ST1 13.80 PGEN=68.50 QGEN=11.04 0 # # # (100) B1 GENERATOR OUTAGE # 3 34338 0 "4" 0 # Q196ST2 13.80 PGEN=68.50 QGEN=11.04 0 # # # (101) B CAPACITOR OUTAGE # 6 30765 0 "v" 0 # LOSBANOS 230.0 SVD 0 # # # (102) B CAPACITOR OUTAGE # 6 30796 0 "v" 0 # STOREY 1 230.0 SVD 0 # # # (103) B CAPACITOR OUTAGE # 6 34134 0 "v" 0 # WILSON A 115.0 SVD 0 # # # (104) B CAPACITOR OUTAGE # 6 34252 0 "v" 0 # MADERA 70.0 SVD 0 # # # (105) B CAPACITOR OUTAGE #

Page 213: To determine the system impacts caused by the Project

A-192 GWF Henrietta SISAppendix A

6 34302 0 "v" 0 # L.BANS T 13.8 SVD 0 # # # (106) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Chowchilla 115 kV Line and Exchequer 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00 2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80 2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94) 4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11) 3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (107) L-1/G-1 OVERLAPPING OUTAGE # Chowchilla - Kerckhoff #2 115 kV Line and Exchequer 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34105 34121 "1 " 0 # line from CERTANJ1 115.00 (2) to (3) SHARON T 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34121 34128 "1 " 0 # line from SHARON T 115.00 (3) to (3) OAKH_JCT 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34128 34123 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) K1-JCT 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (108) L-1/G-1 OVERLAPPING OUTAGE # Atwater - El Capitan 115 kV Line and Exchequer 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0

Page 214: To determine the system impacts caused by the Project

A-193 GWF Henrietta SISAppendix A

# # # (109) L-1/G-1 OVERLAPPING OUTAGE # Atwater - Merced 115 kV Line and Exchequer 1 34104 34108 "1 " 0 # line from ATWATER 115.00 BRKR to (3) CRESEY T 115.00 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (1) ATWATR J 115.00 1 34108 34114 "1 " 0 # line from CRESEY T 115.00 (3) to (3) JRWD GEN 115.00 1 34114 34124 "1 " 0 # line from JRWD GEN 115.00 (3) to (2) JR WOOD 115.00 2 34114 34332 "1 " 0 # TRAN from JRWD GEN 115.00 (3) to (1) JRWCOGEN 9.11 1 34124 34140 "1 " 0 # line from JR WOOD 115.00 (2) to (1) CRESSEY 115.00 4 34124 0 "1 " 0 # LOAD-DROP JR WOOD 115.00 LOAD==11.70(10.32) 4 34140 0 "1 " 0 # LOAD-DROP CRESSEY 115.00 LOAD==19.02(3.86) 3 34332 0 "1 " 0 # GEN-DROP JRWCOGEN 9.11 GEN==3.80(5.40) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (110) L-1/G-1 OVERLAPPING OUTAGE # Cressy Tap 115 kV Line and Exchequer 1 34108 34110 "1 " 0 # line from CRESEY T 115.00 BRKR to (3) ATWATR J 115.00 1 34110 34130 "1 " 0 # line from ATWATR J 115.00 (3) to (2) LIVNGSTN 115.00 1 34110 34144 "1 " 0 # line from ATWATR J 115.00 (3) to BRKR MERCED 115.00 1 34130 34132 "1 " 0 # line from LIVNGSTN 115.00 (2) to (1) GALLO 115.00 4 34130 0 "3 " 0 # LOAD-DROP LIVNGSTN 115.00 LOAD==24.58(5.00) 4 34132 0 "1 " 0 # LOAD-DROP GALLO 115.00 LOAD==4.30(3.68) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (111) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Dairyland 115 kV Line and Exchequer 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (112) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Oro Loma 115 kV Line and Exchequer 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (113) L-1/G-1 OVERLAPPING OUTAGE # El Capitan - Wilson 115 kV Line and Exchequer 1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 #

Page 215: To determine the system impacts caused by the Project

A-194 GWF Henrietta SISAppendix A

3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (114) L-1/G-1 OVERLAPPING OUTAGE # Dairyland - Mendota 115 kV Line and Exchequer 1 34150 34154 "1 " 0 # line from NEWHALL 115.00 (2) to BRKR DAIRYLND 115.00 1 34150 34178 "1 " 0 # line from NEWHALL 115.00 (2) to (3) MADERAPR 115.00 1 34178 34156 "1 " 0 # line from MADERAPR 115.00 (3) to BRKR MENDOTA 115.00 2 34178 34179 "1 " 0 # TRAN from MADERAPR 115.00 (3) to (1) MADERA_G 13.80 4 34150 0 "2 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==8.55(1.73) 4 34150 0 "3 " 0 # LOAD-DROP NEWHALL 115.00 LOAD==10.62(2.16) 4 34179 0 "ss" 0 # LOAD-DROP MADERA_G 13.80 LOAD==3.60(0.85) 3 34179 0 "1 " 0 # GEN-DROP MADERA_G 13.80 GEN==28.60(6.34) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (115) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Mendota 115 kV Line and Exchequer 1 34157 34156 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR MENDOTA 115.00 1 34157 34158 "1 " 0 # line from PANOCHET 115.00 (2) to BRKR PANOCHE 115.00 3 34186 0 "1 " 0 # DG_PAN Unit trips for Panoche - Mendota 115 kV outage # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (116) L-1/G-1 OVERLAPPING OUTAGE # Glass - Biola - Madera 70 kV Line and Exchequer 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (117) L-1/G-1 OVERLAPPING OUTAGE # Merced Falls - Exchequer 70 kV Line and Exchequer 1 34321 34226 "1 " 0 # line from MCSWAINJ 70.00 (3) to (2) MC SWAIN 70.00 1 34321 34230 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR MRCDFLLS 70.00 1 34321 34232 "1 " 0 # line from MCSWAINJ 70.00 (3) to BRKR EXCHEQUR 70.00 2 34226 34320 "1 " 0 # TRAN from MC SWAIN 70.00 (2) to (1) MCSWAIN 9.11

Page 216: To determine the system impacts caused by the Project

A-195 GWF Henrietta SISAppendix A

3 34320 0 "1 " 0 # GEN-DROP MCSWAIN 9.11 GEN==10.00(2.00) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (118) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Canal - Oro Loma 70 kV Line and Exchequer 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00 1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (119) L-1/G-1 OVERLAPPING OUTAGE # Atwater - El Capitan 115 kV Line and JR Wood Cogen 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=4.00 QGEN=5.40 0 # # # (120) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Atwater #2 115 kV Line and JR Wood Cogen 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 3 34332 0 "1" 0 # JRWCOGEN 9.11 PGEN=4.00 QGEN=5.40 0 # # # (121) L-1/G-1 OVERLAPPING OUTAGE # Le Grand - Chowchilla 115 kV Line and Kerckhoff 1 34100 34101 "1 " 0 # line from CHWCHLLA 115.00 BRKR to (3) CERTAN T 115.00 1 34101 34116 "1 " 0 # line from CERTAN T 115.00 (3) to BRKR LE GRAND 115.00 1 34101 34107 "1 " 0 # line from CERTAN T 115.00 (3) to (2) CERTANJ2 115.00 1 34107 34103 "1 " 0 # line from CERTANJ2 115.00 (2) to (3) CHWCGNJT 115.00 1 34103 34102 "1 " 0 # line from CHWCGNJT 115.00 (3) to (1) CERTTEED 115.00 1 34103 34109 "1 " 0 # line from CHWCGNJT 115.00 (3) to (3) CHWCGN 115.00 1 34109 34111 "1 " 0 # line from CHWCGN 115.00 (3) to (2) CHWCHLA2 115.00 2 34109 34301 "1 " 0 # TRAN from CHWCGN 115.00 (3) to (1) CHOWCOGN 13.80 2 34111 34305 "1 " 0 # TRAN from CHWCHLA2 115.00 (2) to (1) CHWCHLA2 13.80 4 34102 0 "1 " 0 # LOAD-DROP CERTTEED 115.00 LOAD==9.94(6.94) 4 34305 0 "ss" 0 # LOAD-DROP CHWCHLA2 13.80 LOAD==2.00(1.11)

Page 217: To determine the system impacts caused by the Project

A-196 GWF Henrietta SISAppendix A

3 34301 0 "1 " 0 # GEN-DROP CHOWCOGN 13.80 GEN==50.00(4.33) 3 34305 0 "1 " 0 # GEN-DROP CHWCHLA2 13.80 GEN==12.50(7.30) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (122) L-1/G-1 OVERLAPPING OUTAGE # Exchequer - Le Grand 115 kV Line and Kerckhoff 1 34112 34116 "1 " 0 # line from EXCHEQUR 115.00 BRKR to BRKR LE GRAND 115.00 3 34306 0 "1 " 0 # Exchequer Unit will trip for this outage 4 34228 0 "**" 0 # Mariposa Loads will drop if bus is below 64 kV, this is anticipate # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (123) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # Le Grand - Dairyland 115 kV Line and Kerckhoff 1 34116 34154 "1 " 0 # line from LE GRAND 115.00 BRKR to BRKR DAIRYLND 115.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (124) L-1/G-1 OVERLAPPING OUTAGE # Glass - Biola - Madera 70 kV Line and Kerckhoff 1 34237 34255 "1 " 0 # line from CANANDGA 70.00 (2) to (3) TRIGO J 70.00 1 34237 34240 "1 " 0 # line from CANANDGA 70.00 (2) to BRKR GLASS 70.00 1 34255 34238 "1 " 0 # line from TRIGO J 70.00 (3) to BRKR BONITA 70.00 1 34255 34254 "1 " 0 # line from TRIGO J 70.00 (3) to (3) TRIGO 70.00 1 34254 34252 "1 " 0 # line from TRIGO 70.00 (3) to BRKR MADERA 70.00 1 34254 34264 "1 " 0 # line from TRIGO 70.00 (3) to (1) EL PECO 70.00 4 34237 0 "1 " 0 # LOAD-DROP CANANDGA 70.00 LOAD==7.60(5.70) 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 4 34264 0 "1 " 0 # LOAD-DROP EL PECO 70.00 LOAD==9.86(2.01) 4 34264 0 "2 " 0 # LOAD-DROP EL PECO 70.00 LOAD==7.26(1.48) 1 34238 34236 "1 " 1 # Switches in Bonita SW23 to transfer load 4 34238 0 "1 " 1 # Restore Load at Bonita # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (125) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Canal - Oro Loma 70 kV Line and Oneil Pump 1 34200 34222 "1 " 0 # line from ORO LOMA 70.00 BRKR to (3) MRCYSPRS 70.00 1 34222 34220 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ORTIGA 70.00 1 34222 34224 "1 " 0 # line from MRCYSPRS 70.00 (3) to (2) ARBURUA 70.00 1 34220 34206 "1 " 0 # line from ORTIGA 70.00 (2) to BRKR CANAL 70.00 1 34224 34272 "1 " 0 # line from ARBURUA 70.00 (2) to (2) WRGHT PP 70.00 1 34272 34214 "1 " 0 # line from WRGHT PP 70.00 (2) to BRKR LOS BANS 70.00 4 34220 0 "1 " 0 # LOAD-DROP ORTIGA 70.00 LOAD==6.88(1.40) 4 34224 0 "1 " 0 # LOAD-DROP ARBURUA 70.00 LOAD==3.77(1.83) 4 34272 0 "1 " 0 # LOAD-DROP WRGHT PP 70.00 LOAD==9.50(1.93)

Page 218: To determine the system impacts caused by the Project

A-197 GWF Henrietta SISAppendix A

# 3 34316 0 "1" 0 # ONEILPMP 9.11 PGEN=0.52 QGEN=0.00 0 # # # (126) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Melones Unit 1 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (127) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Melones Unit 1 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (128) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Melones Unit 1 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (129) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Melones Unit 1 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (130) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Melones Unit 1 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (131) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Melones Unit 1 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (132) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Helms Unit 1 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00

Page 219: To determine the system impacts caused by the Project

A-198 GWF Henrietta SISAppendix A

# 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (133) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Helms Unit 1 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (134) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Helms Unit 1 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (135) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Helms Unit 1 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (136) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Helms Unit 1 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (137) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Helms Unit 1 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (138) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Helms Unit 1 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (139) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Helms Unit 1 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (140) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Helms Unit 1

Page 220: To determine the system impacts caused by the Project

A-199 GWF Henrietta SISAppendix A

1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (141) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Helms Unit 1 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (142) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Helms Unit 1 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (143) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Helms Unit 1 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (144) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Helms Unit 1 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (145) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Helms Unit 1 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (146) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Helms Unit 1 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # #

Page 221: To determine the system impacts caused by the Project

A-200 GWF Henrietta SISAppendix A

# (147) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Helms Unit 1 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (148) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Helms Unit 1 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (149) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Helms Unit 1 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (150) L-1/G-1 OVERLAPPING OUTAGE # Dos Amigos - Panoche 230 kV Line and Helms Unit 1 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (151) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Exchequer 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (152) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Exchequer 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (153) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Exchequer 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (154) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Exchequer 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77

Page 222: To determine the system impacts caused by the Project

A-201 GWF Henrietta SISAppendix A

0 # # # (155) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Exchequer 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (156) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Exchequer 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (157) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Exchequer 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (158) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Exchequer 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (159) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Exchequer 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (160) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Exchequer 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (161) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Exchequer 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (162) L-1/G-1 OVERLAPPING OUTAGE

Page 223: To determine the system impacts caused by the Project

A-202 GWF Henrietta SISAppendix A

# Gates - Panoche #1 230 kV Line and Exchequer 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (163) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Exchequer 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (164) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Exchequer 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (165) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Exchequer 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (166) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Exchequer 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (167) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Exchequer 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (168) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Exchequer 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (169) L-1/G-1 OVERLAPPING OUTAGE

Page 224: To determine the system impacts caused by the Project

A-203 GWF Henrietta SISAppendix A

# Dos Amigos - Panoche 230 kV Line and Exchequer 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (170) L-1/G-1 OVERLAPPING OUTAGE # Warnerville - Wilson 230 kV Line and Kerckhoff 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (171) L-1/G-1 OVERLAPPING OUTAGE # Westley - Los Banos 230 kV Line and Kerckhoff 1 30670 30765 "1 " 0 # line from WESTLEY 230.00 BRKR to BRKR LOSBANOS 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (172) L-1/G-1 OVERLAPPING OUTAGE # Moss Landing - Panoche 230 kV Line and Kerckhoff 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (173) L-1/G-1 OVERLAPPING OUTAGE # Coburn - Panoche 230 kV Line and Kerckhoff 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (174) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #1 230 kV Line and Kerckhoff 1 30765 30790 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (175) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Panoche #2 230 kV Line and Kerckhoff 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (176) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - Dos Amigos 230 kV Line and Kerckhoff 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 #

Page 225: To determine the system impacts caused by the Project

A-204 GWF Henrietta SISAppendix A

# # (177) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #1 230 kV Line and Kerckhoff 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (178) L-1/G-1 OVERLAPPING OUTAGE # Los Banos - San Luis PGP #2 230 kV Line and Kerckhoff 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (179) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Kerckhoff 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (180) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Kerckhoff 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (181) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Kerckhoff 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (182) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Kerckhoff 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (183) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #1 230 kV Line and Kerckhoff 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # #

Page 226: To determine the system impacts caused by the Project

A-205 GWF Henrietta SISAppendix A

# (184) L-1/G-1 OVERLAPPING OUTAGE # Wilson - Borden #2 230 kV Line and Kerckhoff 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (185) L-1/G-1 OVERLAPPING OUTAGE # Melones - Wilson 230 kV Line and Kerckhoff 1 37563 30800 "1 " 0 # line from MELONES 230.00 (2) to BRKR WILSON 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (186) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #1 230 kV Line and Kerckhoff 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (187) L-1/G-1 OVERLAPPING OUTAGE # Borden - Gregg #2 230 kV Line and Kerckhoff 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (188) L-1/G-1 OVERLAPPING OUTAGE # Dos Amigos - Panoche 230 kV Line and Kerckhoff 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # 2013 sprpk category b contingency list # Fresno Zone 314 # # # (189) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 0 # # # (190) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line 0 # # # (191) B2 LINE OUTAGE (BREAKER-TO-BREAKER) #

Page 227: To determine the system impacts caused by the Project

A-206 GWF Henrietta SISAppendix A

1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line 0 # # # (192) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line 0 # # # (193) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line 0 # # # (194) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (195) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 0 # # # (196) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 0 # # # (197) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 0

Page 228: To determine the system impacts caused by the Project

A-207 GWF Henrietta SISAppendix A

# # # (198) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) 0 # # # (199) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) 0 # # # (200) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30875 30874 "1 " 0 # line from MC CALL 230.00 BRKR to BRKR P0615STN 230.00 0 # # # (201) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30875 30874 "2 " 0 # line from MC CALL 230.00 BRKR to BRKR P0615STN 230.00 0 # # # (202) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 # # # (203) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 0 # # # (204) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 0 # #

Page 229: To determine the system impacts caused by the Project

A-208 GWF Henrietta SISAppendix A

# (205) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 0 # # # (206) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 0 # # # (207) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34123 34358 "2 " 0 # line from K1-JCT 115.00 (2) to BRKR KERCKHF2 115.00 1 34123 34128 "1 " 0 # line from K1-JCT 115.00 (2) to (3) OAKH_JCT 115.00 1 34128 34121 "1 " 0 # line from OAKH_JCT 115.00 (3) to (3) SHARON T 115.00 1 34128 34126 "1 " 0 # line from OAKH_JCT 115.00 (3) to (2) CORSGOLD 115.00 1 34121 34105 "1 " 0 # line from SHARON T 115.00 (3) to (2) CERTANJ1 115.00 1 34121 34120 "1 " 0 # line from SHARON T 115.00 (3) to (1) SHARON 115.00 1 34105 34100 "1 " 0 # line from CERTANJ1 115.00 (2) to BRKR CHWCHLLA 115.00 1 34126 34122 "1 " 0 # line from CORSGOLD 115.00 (2) to (1) OAKHURST 115.00 4 34126 0 "1 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==2.21(0.45) 4 34126 0 "2 " 0 # LOAD-DROP CORSGOLD 115.00 LOAD==26.19(5.32) 4 34120 0 "1 " 0 # LOAD-DROP SHARON 115.00 LOAD==7.10(4.96) 4 34122 0 "1 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==11.68(2.37) 4 34122 0 "2 " 0 # LOAD-DROP OAKHURST 115.00 LOAD==15.01(3.05) 0 # # # (208) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 1 34149 34148 "1 " 0 # line from CHENYT 115.00 (3) to (2) CHENY 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00 1 34148 34141 "1 " 0 # line from CHENY 115.00 (2) to (2) PAN2_TAP 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (209) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00 2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) 0 # # # (210) B2 LINE OUTAGE (BREAKER-TO-BREAKER)

Page 230: To determine the system impacts caused by the Project

A-209 GWF Henrietta SISAppendix A

# 1 34356 34358 "1 " 0 # line from KERCKHF1 115.00 BRKR to BRKR KERCKHF2 115.00 0 # # # (211) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (212) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34358 34360 "1 " 0 # line from KERCKHF2 115.00 BRKR to (3) WWARD JT 115.00 1 34360 34414 "1 " 0 # line from WWARD JT 115.00 (3) to BRKR WOODWARD 115.00 1 34360 34363 "1 " 0 # line from WWARD JT 115.00 (3) to (3) CLOVISJ1 115.00 1 34363 34362 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR CLOVIS-1 115.00 1 34363 34366 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR SANGER 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36) 4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34362 0 "**" 1 # Restore Load at Clovis 1 0 # # # (213) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34359 34361 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR AIRWAYS 115.00 1 34359 34408 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR BARTON 115.00 1 34359 34366 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR SANGER 115.00 0 # # # (214) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34364 34365 "1 " 0 # line from CLOVIS-2 115.00 BRKR to (3) CLOVISJ2 115.00 1 34365 34358 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR KERCKHF2 115.00 1 34365 34366 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR SANGER 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34364 0 "**" 1 # Restore Load at Clovis 2 0 # # # (215) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 #

Page 231: To determine the system impacts caused by the Project

A-210 GWF Henrietta SISAppendix A

# # (216) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "2 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (217) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34370 "3 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (218) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34372 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MALAGA 115.00 0 # # # (219) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34389 "1 " 0 # line from SANGER 115.00 BRKR to (3) RAINBWTP 115.00 1 34389 34388 "1 " 0 # line from RAINBWTP 115.00 (3) to (1) RAINBW 115.00 1 34389 34394 "1 " 0 # line from RAINBWTP 115.00 (3) to (3) PIEDRA 1 115.00 1 34394 34380 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR REEDLEY 115.00 1 34394 34400 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR KNGSRVR1 115.00 4 34388 0 "1 " 0 # LOAD-DROP RAINBW 115.00 LOAD==16.20(3.29) 0 # # # (220) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34366 34396 "1 " 0 # line from SANGER 115.00 BRKR to (2) PIEDRA 2 115.00 1 34396 34398 "1 " 0 # line from PIEDRA 2 115.00 (2) to (2) BALCH 115.00 2 34398 34624 "1 " 0 # TRAN from BALCH 115.00 (2) to (1) BALCH 1 13.20 4 34624 0 "1 " 0 # LOAD-DROP BALCH 1 13.20 LOAD==0.26(0.00) 3 34624 0 "1 " 0 # GEN-DROP BALCH 1 13.20 GEN==27.00(8.33) 0 # # # (221) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34369 34370 "1 " 0 # line from P0418 115.00 (5) to BRKR MC CALL 115.00 2 34369 34661 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT1 13.80 2 34369 34663 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT2 13.80 2 34369 34665 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT3 13.80 2 34369 34667 "1 " 0 # TRAN from P0418 115.00 (5) to (1) P0418GT4 13.80 4 34661 0 "ss" 0 # LOAD-DROP P0418GT1 13.80 LOAD==3.00(1.66) 4 34663 0 "ss" 0 # LOAD-DROP P0418GT2 13.80 LOAD==3.00(1.66) 4 34665 0 "ss" 0 # LOAD-DROP P0418GT3 13.80 LOAD==3.00(1.66) 4 34667 0 "ss" 0 # LOAD-DROP P0418GT4 13.80 LOAD==3.00(1.66) 3 34661 0 "1 " 0 # GEN-DROP P0418GT1 13.80 GEN==78.80(13.93) 3 34663 0 "2 " 0 # GEN-DROP P0418GT2 13.80 GEN==78.80(13.93) 3 34665 0 "3 " 0 # GEN-DROP P0418GT3 13.80 GEN==78.80(13.93)

Page 232: To determine the system impacts caused by the Project

A-211 GWF Henrietta SISAppendix A

3 34667 0 "4 " 0 # GEN-DROP P0418GT4 13.80 GEN==78.80(13.93) 0 # # # (222) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 0 # # # (223) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34370 34385 "1 " 0 # line from MC CALL 115.00 BRKR to (3) KINGS J1 115.00 1 34385 34417 "1 " 0 # line from KINGS J1 115.00 (3) to (2) KINGS J2 115.00 1 34385 34425 "1 " 0 # line from KINGS J1 115.00 (3) to (3) KCOGNJCT 115.00 1 34417 34418 "1 " 0 # line from KINGS J2 115.00 (2) to BRKR KINGSBRG 115.00 1 34425 34387 "1 " 0 # line from KCOGNJCT 115.00 (3) to (1) SUNMAID 115.00 1 34425 34427 "1 " 0 # line from KCOGNJCT 115.00 (3) to (2) GRDNGLS2 115.00 1 34427 34386 "1 " 0 # line from GRDNGLS2 115.00 (2) to (2) KNGSCOGN 115.00 2 34386 34642 "1 " 0 # TRAN from KNGSCOGN 115.00 (2) to BRKR KINGSBUR 9.11 4 34387 0 "1 " 0 # LOAD-DROP SUNMAID 115.00 LOAD==3.40(3.28) 3 34642 0 "1 " 0 # GEN-DROP KINGSBUR 9.11 GEN==34.00(17.30) 0 # # # (224) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34402 34404 "1 " 0 # line from CAL AVE 115.00 BRKR to BRKR WST FRSO 115.00 0 # # # (225) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34376 "1 " 0 # line from MALAGA 115.00 BRKR to (1) PPG 115.00 4 34376 0 "1 " 0 # LOAD-DROP PPG 115.00 LOAD==6.25(3.87) 0 # # # (226) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34379 "1 " 0 # line from MALAGA 115.00 BRKR to (3) MALAGATP 115.00 1 34379 34373 "1 " 0 # line from MALAGATP 115.00 (3) to (3) SCWAXJCT 115.00 1 34379 34375 "1 " 0 # line from MALAGATP 115.00 (3) to (3) ULTPWRJ 115.00 1 34373 34371 "1 " 0 # line from SCWAXJCT 115.00 (3) to (1) SCWAX 115.00 1 34373 34374 "1 " 0 # line from SCWAXJCT 115.00 (3) to (1) RANCHRS 115.00 1 34375 34377 "1 " 0 # line from ULTPWRJ 115.00 (3) to (2) AIRPROD 115.00 2 34375 34640 "1 " 0 # TRAN from ULTPWRJ 115.00 (3) to (1) ULTR.PWR 9.11 1 34377 34370 "1 " 0 # line from AIRPROD 115.00 (2) to BRKR MC CALL 115.00 4 34371 0 "1 " 0 # LOAD-DROP SCWAX 115.00 LOAD==2.70(1.53) 4 34374 0 "1 " 0 # LOAD-DROP RANCHRS 115.00 LOAD==9.16(1.86) 4 34377 0 "1 " 0 # LOAD-DROP AIRPROD 115.00 LOAD==5.10(2.02)

Page 233: To determine the system impacts caused by the Project

A-212 GWF Henrietta SISAppendix A

3 34640 0 "1 " 0 # GEN-DROP ULTR.PWR 9.11 GEN==14.50(13.00) 0 # # # (227) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34372 34381 "1 " 0 # line from MALAGA 115.00 BRKR to (3) KRCDP 115.00 2 34381 34671 "1 " 0 # TRAN from KRCDP 115.00 (3) to (1) KRCDPCT1 13.80 2 34381 34672 "1 " 0 # TRAN from KRCDP 115.00 (3) to (1) KRCDPCT2 13.80 4 34671 0 "ss" 0 # LOAD-DROP KRCDPCT1 13.80 LOAD==1.05(0.65) 4 34672 0 "ss" 0 # LOAD-DROP KRCDPCT2 13.80 LOAD==1.05(0.65) 3 34671 0 "1 " 0 # GEN-DROP KRCDPCT1 13.80 GEN==50.00(7.14) 3 34672 0 "1 " 0 # GEN-DROP KRCDPCT2 13.80 GEN==50.00(7.14) 0 # # # (228) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34380 34384 "1 " 0 # line from REEDLEY 115.00 BRKR to (2) GERAWAN 115.00 1 34384 34382 "1 " 0 # line from GERAWAN 115.00 (2) to BRKR WAHTOKE 115.00 0 # # # (229) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34390 34370 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR MC CALL 115.00 1 34390 34402 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR CAL AVE 115.00 4 34390 0 "1 " 0 # LOAD-DROP DANISHCM 115.00 LOAD==4.10(3.51) 0 # # # (230) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34391 34392 "1 " 0 # line from QUEBECTP 115.00 (2) to (1) QUEBEC 115.00 1 34391 34426 "1 " 0 # line from QUEBECTP 115.00 (2) to BRKR ALPAUGH 115.00 4 34392 0 "1 " 0 # LOAD-DROP QUEBEC 115.00 LOAD==11.20(7.82) 0 # # # (231) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (232) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (233) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34409 34413 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR PNEDLE 115.00 1 34409 34416 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR BULLARD 115.00 1 34409 34412 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR HERNDON 115.00

Page 234: To determine the system impacts caused by the Project

A-213 GWF Henrietta SISAppendix A

4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25) 4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 1 34411 34413 "1 " 1 # Switches in Pindale CB#12 to transfer load 4 34413 0 "**" 1 # Restore load at Pindale 0 # # # (234) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34410 34412 "1 " 0 # line from MANCHSTR 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (235) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34411 34416 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR BULLARD 115.00 1 34411 34412 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR HERNDON 115.00 0 # # # (236) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34412 34422 "1 " 0 # line from HERNDON 115.00 BRKR to (2) CHLDHOSP 115.00 1 34422 34414 "1 " 0 # line from CHLDHOSP 115.00 (2) to BRKR WOODWARD 115.00 4 34422 0 "1 " 0 # LOAD-DROP CHLDHOSP 115.00 LOAD==3.50(1.60) 0 # # # (237) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34420 "1 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (238) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34420 "2 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (239) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34423 "1 " 0 # line from KINGSBRG 115.00 BRKR to (3) GAURD J1 115.00 1 34423 34370 "1 " 0 # line from GAURD J1 115.00 (3) to BRKR MC CALL 115.00 1 34423 34421 "1 " 0 # line from GAURD J1 115.00 (3) to (2) GAURD J2 115.00 1 34421 34424 "1 " 0 # line from GAURD J2 115.00 (2) to (1) GRDN GLS 115.00 4 34424 0 "1 " 0 # LOAD-DROP GRDN GLS 115.00 LOAD==3.50(1.15) 4 34418 0 "3 " 0 # Kingsburg Bank #3 will also be dropped on this outage 0 # # # (240) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34418 34428 "1 " 0 # line from KINGSBRG 115.00 BRKR to (2) CONTADNA 115.00 1 34428 34429 "1 " 0 # line from CONTADNA 115.00 (2) to (4) GWF_HEP 115.00 1 34429 34521 "1 " 0 # line from GWF_HEP 115.00 (4) to (2) LEPRNOFD 115.00

Page 235: To determine the system impacts caused by the Project

A-214 GWF Henrietta SISAppendix A

2 34429 34431 "1 " 0 # TRAN from GWF_HEP 115.00 (4) to (1) GWF_HEP1 13.80 2 34429 34433 "1 " 0 # TRAN from GWF_HEP 115.00 (4) to (1) GWF_HEP2 13.80 1 34521 34430 "1 " 0 # line from LEPRNOFD 115.00 (2) to BRKR HENRETTA 115.00 4 34428 0 "1 " 0 # LOAD-DROP CONTADNA 115.00 LOAD==7.60(5.70) 4 34429 0 "ss" 0 # LOAD-DROP GWF_HEP 115.00 LOAD==3.00(0.68) 4 34521 0 "1 " 0 # LOAD-DROP LEPRNOFD 115.00 LOAD==6.65(4.30) 3 34431 0 "1 " 0 # GEN-DROP GWF_HEP1 13.80 GEN==50.00(21.27) 3 34433 0 "1 " 0 # GEN-DROP GWF_HEP2 13.80 GEN==50.00(21.27) 0 # # # (241) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34426 34700 "1 " 0 # line from ALPAUGH 115.00 BRKR to BRKR SMYRNA 115.00 0 # # # (242) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34452 34260 "1 " 0 # line from WISHON 70.00 BRKR to (3) SJNO2 70.00 1 34260 34259 "1 " 0 # line from SJNO2 70.00 (3) to (3) NRTHFORK 70.00 2 34260 34631 "1 " 0 # TRAN from SJNO2 70.00 (3) to (1) SJ2GEN 9.11 1 34259 34261 "1 " 0 # line from NRTHFORK 70.00 (3) to (2) SJNO3 70.00 2 34259 34340 "1 " 0 # TRAN from NRTHFORK 70.00 (3) to (1) N.FORK E 9.11 2 34261 34633 "1 " 0 # TRAN from SJNO3 70.00 (2) to (1) SJ3GEN 9.11 4 34260 0 "2 " 0 # LOAD-DROP SJNO2 70.00 LOAD==3.22(0.66) 4 34261 0 "2 " 0 # LOAD-DROP SJNO3 70.00 LOAD==6.95(1.41) 4 34340 0 "1 " 0 # LOAD-DROP N.FORK E 9.11 LOAD==1.21(0.25) 3 34631 0 "1 " 0 # GEN-DROP SJ2GEN 9.11 GEN==2.00(0.00) 3 34633 0 "1 " 0 # GEN-DROP SJ3GEN 9.11 GEN==1.00(0.00) 0 # # # (243) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34452 34491 "1 " 0 # line from WISHON 70.00 BRKR to (3) AUBRYTP 70.00 1 34491 34464 "1 " 0 # line from AUBRYTP 70.00 (3) to BRKR COPPRMNE 70.00 1 34491 34493 "1 " 0 # line from AUBRYTP 70.00 (3) to (1) AUBERRY 70.00 4 34493 0 "1 " 0 # LOAD-DROP AUBERRY 70.00 LOAD==6.07(1.23) 4 34493 0 "2 " 0 # LOAD-DROP AUBERRY 70.00 LOAD==7.15(1.45) 0 # # # (244) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # spring outage 1 34456 34458 "1 " 0 # line from HRDWK TP 70.00 (3) to (1) HARDWICK 70.00 1 34456 34522 "1 " 0 # line from HRDWK TP 70.00 (3) to (2) HNFRD SW 70.00 1 34456 34576 "1 " 0 # line from HRDWK TP 70.00 (3) to BRKR KNGLOBUS 70.00 1 34522 34518 "1 " 0 # line from HNFRD SW 70.00 (2) to BRKR LEMOORE 70.00 4 34458 0 "1 " 0 # LOAD-DROP HARDWICK 70.00 LOAD==12.86(2.61) 0 # #

Page 236: To determine the system impacts caused by the Project

A-215 GWF Henrietta SISAppendix A

# (245) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34460 34462 "1 " 0 # line from GUERNSEY 70.00 BRKR to (3) GUR3TPT 70.00 1 34462 34542 "1 " 0 # line from GUR3TPT 70.00 (3) to (2) JCBSCRNR 70.00 1 34462 34554 "1 " 0 # line from GUR3TPT 70.00 (3) to BRKR AMSTG SW 70.00 1 34542 34540 "1 " 0 # line from JCBSCRNR 70.00 (2) to BRKR HENRITTA 70.00 4 34460 0 "1 " 0 # LOAD-DROP GUERNSEY 70.00 LOAD==10.51(2.13) 4 34542 0 "1 " 0 # LOAD-DROP JCBSCRNR 70.00 LOAD==12.05(2.45) 4 34542 0 "2 " 0 # LOAD-DROP JCBSCRNR 70.00 LOAD==9.54(1.94) 0 # # # (246) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34464 34478 "1 " 0 # line from COPPRMNE 70.00 BRKR to BRKR TVY VLLY 70.00 0 # # # (247) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34464 34638 "1 " 0 # line from COPPRMNE 70.00 BRKR to (2) FRANTDM 70.00 2 34638 34636 "1 " 0 # TRAN from FRANTDM 70.00 (2) to (1) FRIANTDM 6.60 3 34636 0 "2 " 0 # GEN-DROP FRIANTDM 6.60 GEN==14.70(5.86) 3 34636 0 "3 " 0 # GEN-DROP FRIANTDM 6.60 GEN==7.80(3.11) 3 34636 0 "4 " 0 # GEN-DROP FRIANTDM 6.60 GEN==2.30(0.92) 0 # # # (248) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34466 34482 "1 " 0 # line from BIOLA 70.00 BRKR to BRKR OLDKERN 70.00 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 0 # # # (249) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34468 34482 "1 " 0 # line from BOWLES 70.00 (1) to BRKR OLDKERN 70.00 4 34468 0 "1 " 0 # LOAD-DROP BOWLES 70.00 LOAD==18.29(3.72) 0 # # # (250) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34469 34271 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) WSTLDJCT 70.00 1 34469 34470 "1 " 0 # line from GFFNJCT 70.00 (3) to (1) GIFFEN 70.00 1 34469 34471 "1 " 0 # line from GFFNJCT 70.00 (3) to (3) SNJQJCT 70.00 1 34271 34172 "1 " 0 # line from WSTLDJCT 70.00 (3) to (2) WESTLAND 70.00 1 34271 34269 "1 " 0 # line from WSTLDJCT 70.00 (3) to (3) BIOMSJCT 70.00 1 34471 34472 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR SAN JOQN 70.00 1 34471 34474 "1 " 0 # line from SNJQJCT 70.00 (3) to BRKR HELM 70.00 1 34172 34170 "1 " 0 # line from WESTLAND 70.00 (2) to (1) WESIX 70.00

Page 237: To determine the system impacts caused by the Project

A-216 GWF Henrietta SISAppendix A

1 34269 34268 "1 " 0 # line from BIOMSJCT 70.00 (3) to BRKR MENDOTA 70.00 1 34269 34270 "1 " 0 # line from BIOMSJCT 70.00 (3) to (2) BIOMASS 70.00 2 34270 34334 "1 " 0 # TRAN from BIOMASS 70.00 (2) to (1) BIO PWR 9.11 4 34470 0 "1 " 0 # LOAD-DROP GIFFEN 70.00 LOAD==9.59(1.95) 4 34172 0 "1 " 0 # LOAD-DROP WESTLAND 70.00 LOAD==3.20(0.76) 4 34170 0 "1 " 0 # LOAD-DROP WESIX 70.00 LOAD==1.60(0.38) 3 34334 0 "1 " 0 # GEN-DROP BIO PWR 9.11 GEN==21.80(10.99) 1 34472 34473 "1 " 1 # Switches in San Joaquin CB22 to transfer load 4 34472 0 "**" 1 # Restore Load at San Joaquin 0 # # # (251) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34473 34472 "1 " 0 # line from SNJQTP 70.00 (2) to BRKR SAN JOQN 70.00 1 34473 34475 "1 " 0 # line from SNJQTP 70.00 (2) to (3) AGRCJCT 70.00 1 34475 34476 "1 " 0 # line from AGRCJCT 70.00 (3) to (2) AGRICO 70.00 1 34475 34484 "1 " 0 # line from AGRCJCT 70.00 (3) to BRKR KERMAN 70.00 2 34476 34608 "1 " 0 # TRAN from AGRICO 70.00 (2) to (1) AGRICO 13.80 4 34484 0 "1 " 0 # LOAD-DROP KERMAN 70.00 LOAD==19.44(3.95) 4 34484 0 "2 " 0 # LOAD-DROP KERMAN 70.00 LOAD==11.78(2.39) 3 34608 0 "2 " 0 # GEN-DROP AGRICO 13.80 GEN==7.00(1.08) 3 34608 0 "3 " 0 # GEN-DROP AGRICO 13.80 GEN==18.10(2.80) 3 34608 0 "4 " 0 # GEN-DROP AGRICO 13.80 GEN==26.00(4.02) 0 # # # (252) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34474 34556 "1 " 0 # line from HELM 70.00 BRKR to BRKR STRD JCT 70.00 0 # # # (253) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34478 34492 "1 " 0 # line from TVY VLLY 70.00 BRKR to BRKR REEDLEY 70.00 0 # # # (254) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # spring outage 1 34480 34481 "1 " 0 # line from KEARNEY 70.00 BRKR to (4) FRWWTAP 70.00 1 34481 34483 "1 " 0 # line from FRWWTAP 70.00 (4) to (3) FRESNOWW 70.00 1 34481 34483 "2 " 0 # line from FRWWTAP 70.00 (4) to (3) FRESNOWW 70.00 1 34481 34484 "1 " 0 # line from FRWWTAP 70.00 (4) to BRKR KERMAN 70.00 2 34483 34485 "1 " 0 # TRAN from FRESNOWW 70.00 (3) to (1) FRESNOWW 12.47 4 34485 0 "1 " 0 # LOAD-DROP FRESNOWW 12.47 LOAD==7.91(0.00) 3 34485 0 "1 " 0 # GEN-DROP FRESNOWW 12.47 GEN==9.00(0.00) 0 # # # (255) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34480 34482 "1 " 0 # line from KEARNEY 70.00 BRKR to (3) OLDKERN 70.00

Page 238: To determine the system impacts caused by the Project

A-217 GWF Henrietta SISAppendix A

1 34482 34466 "1 " 0 # line from OLDKERN 70.00 BRKR to BRKR BIOLA 70.00 1 34482 34468 "1 " 0 # line from OLDKERN 70.00 BRKR to (1) BOWLES 70.00 4 34482 0 "1 " 0 # LOAD-DROP OLDKERN 70.00 LOAD==18.75(3.81) 4 34482 0 "3 " 0 # LOAD-DROP OLDKERN 70.00 LOAD==7.57(1.54) 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 4 34468 0 "1 " 0 # LOAD-DROP BOWLES 70.00 LOAD==18.29(3.72) 0 # # # (256) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34480 34512 "1 " 0 # line from KEARNEY 70.00 BRKR to BRKR CARUTHRS 70.00 4 34512 0 "1 " 0 # LOAD-DROP CARUTHRS 70.00 LOAD==19.63(3.98) 0 # # # (257) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34487 34489 "1 " 0 # line from SNGRJCT 70.00 (3) to (2) SNGRCOGN 70.00 1 34487 34490 "1 " 0 # line from SNGRJCT 70.00 (3) to (2) PARLIER 70.00 1 34487 34488 "1 " 0 # line from SNGRJCT 70.00 (3) to BRKR SANGER 70.00 2 34489 34646 "1 " 0 # TRAN from SNGRCOGN 70.00 (2) to (1) SANGERCO 9.11 1 34490 34492 "1 " 0 # line from PARLIER 70.00 (2) to BRKR REEDLEY 70.00 4 34490 0 "1 " 0 # LOAD-DROP PARLIER 70.00 LOAD==20.24(4.11) 3 34646 0 "1 " 0 # GEN-DROP SANGERCO 9.11 GEN==37.50(1.40) 0 # # # (258) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34488 34366 "1 " 0 # line from SANGER 70.00 BRKR to BRKR SANGER 115.00 0 # # # (259) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34492 34497 "1 " 0 # line from REEDLEY 70.00 BRKR to (3) DNUBAJCT 70.00 1 34497 34499 "1 " 0 # line from DNUBAJCT 70.00 (3) to (2) DNUBAEGY 70.00 1 34497 34500 "1 " 0 # line from DNUBAJCT 70.00 (3) to BRKR DINUBA 70.00 2 34499 34648 "1 " 0 # TRAN from DNUBAEGY 70.00 (2) to (1) DINUBA E 13.80 4 34648 0 "ss" 0 # LOAD-DROP DINUBA E 13.80 LOAD==0.30(0.26) 3 34648 0 "1 " 0 # GEN-DROP DINUBA E 13.80 GEN==12.00(7.00) 0 # # # (260) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34492 34526 "1 " 0 # line from REEDLEY 70.00 BRKR to (3) ORSI JCT 70.00 1 34526 34495 "1 " 0 # line from ORSI JCT 70.00 (3) to (2) SANDCRK 70.00 1 34526 34502 "1 " 0 # line from ORSI JCT 70.00 (3) to BRKR OROSI 70.00 1 34495 34494 "1 " 0 # line from SANDCRK 70.00 (2) to (1) DUNLAP 70.00 4 34495 0 "1 " 0 # LOAD-DROP SANDCRK 70.00 LOAD==3.14(0.64) 4 34494 0 "1 " 0 # LOAD-DROP DUNLAP 70.00 LOAD==4.46(0.91)

Page 239: To determine the system impacts caused by the Project

A-218 GWF Henrietta SISAppendix A

0 # # # (261) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34496 34498 "1 " 0 # line from STCRRL J 70.00 (3) to (1) STONCRRL 70.00 1 34496 34500 "1 " 0 # line from STCRRL J 70.00 (3) to BRKR DINUBA 70.00 1 34496 34502 "1 " 0 # line from STCRRL J 70.00 (3) to (2) OROSI 70.00 1 34502 34526 "1 " 0 # line from OROSI 70.00 BRKR to (1) ORSI JCT 70.00 4 34498 0 "2 " 0 # LOAD-DROP STONCRRL 70.00 LOAD==3.37(0.68) 4 34498 0 "3 " 0 # LOAD-DROP STONCRRL 70.00 LOAD==2.68(0.54) 4 34502 0 "1 " 0 # LOAD-DROP OROSI 70.00 LOAD==8.38(1.70) 4 34502 0 "2 " 0 # LOAD-DROP OROSI 70.00 LOAD==7.43(1.51) 0 # # # (262) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # spring outage 1 34508 34510 "1 " 0 # line from CAMDEN 70.00 (2) to (2) CMDN JCT 70.00 1 34508 34576 "1 " 0 # line from CAMDEN 70.00 (2) to BRKR KNGLOBUS 70.00 1 34510 34512 "1 " 0 # line from CMDN JCT 70.00 (2) to BRKR CARUTHRS 70.00 4 34508 0 "1 " 0 # LOAD-DROP CAMDEN 70.00 LOAD==6.87(1.40) 4 34508 0 "2 " 0 # LOAD-DROP CAMDEN 70.00 LOAD==10.90(2.22) 0 # # # (263) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34514 34540 "1 " 0 # line from MUSLSLGH 70.00 (1) to BRKR HENRITTA 70.00 4 34514 0 "1 " 0 # LOAD-DROP MUSLSLGH 70.00 LOAD==22.00(13.60) 0 # # # (264) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) 0 # # # (265) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34528 34530 "1 " 0 # line from CORCORAN 70.00 BRKR to (3) BSWLL TP 70.00 1 34530 34531 "1 " 0 # line from BSWLL TP 70.00 (3) to (2) JGBSWLL 70.00 1 34530 34538 "1 " 0 # line from BSWLL TP 70.00 (3) to (1) BOSWELL 70.00 1 34531 34536 "1 " 0 # line from JGBSWLL 70.00 (2) to (1) ANGIOLA 70.00 4 34538 0 "1 " 0 # LOAD-DROP BOSWELL 70.00 LOAD==2.37(1.53) 4 34536 0 "1 " 0 # LOAD-DROP ANGIOLA 70.00 LOAD==7.24(1.47) 0

Page 240: To determine the system impacts caused by the Project

A-219 GWF Henrietta SISAppendix A

# # # (266) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34532 34554 "1 " 0 # line from ARMSTRNG 70.00 (1) to (4) AMSTG SW 70.00 1 34554 34462 "1 " 0 # line from AMSTG SW 70.00 BRKR to (1) GUR3TPT 70.00 1 34554 34534 "1 " 0 # line from AMSTG SW 70.00 (4) to (1) RESERVE 70.00 2 34554 34650 "1 " 0 # TRAN from AMSTG SW 70.00 BRKR to (1) GWF-PWR. 13.80 4 34534 0 "1 " 0 # LOAD-DROP RESERVE 70.00 LOAD==2.03(0.41) 3 34650 0 "1 " 0 # GEN-DROP GWF-PWR. 13.80 GEN==23.00(12.00) 0 # # # (267) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34537 34540 "1 " 0 # line from GWF_HENR 70.00 (5) to BRKR HENRITTA 70.00 2 34537 34539 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) GWF_GT1 13.80 2 34537 34541 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) GWF_GT2 13.80 2 34537 34691 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) Q272_ST1 13.80 2 34537 34692 "1 " 0 # TRAN from GWF_HENR 70.00 (5) to (1) Q272SLST 13.80 4 34539 0 "ss" 0 # LOAD-DROP GWF_GT1 13.80 LOAD==1.10(0.25) 4 34541 0 "ss" 0 # LOAD-DROP GWF_GT2 13.80 LOAD==1.10(0.25) 4 34691 0 "ss" 0 # LOAD-DROP Q272_ST1 13.80 LOAD==2.00(1.11) 4 34692 0 "ss" 0 # LOAD-DROP Q272SLST 13.80 LOAD==14.00(7.75) 3 34539 0 "1 " 0 # GEN-DROP GWF_GT1 13.80 GEN==50.00(4.51) 3 34541 0 "1 " 0 # GEN-DROP GWF_GT2 13.80 GEN==50.00(4.51) 3 34691 0 "1 " 0 # GEN-DROP Q272_ST1 13.80 GEN==27.00(1.87) 3 34692 0 "1 " 0 # GEN-DROP Q272SLST 13.80 GEN==139.00(35.74) 0 # # # (268) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34544 34550 "1 " 0 # line from TLRE LKE 70.00 BRKR to (2) CHEVPLIN 70.00 1 34550 34546 "1 " 0 # line from CHEVPLIN 70.00 (2) to (2) AVENAL 70.00 1 34546 34548 "1 " 0 # line from AVENAL 70.00 (2) to BRKR KETTLEMN 70.00 4 34544 0 "1 " 0 # LOAD-DROP TLRE LKE 70.00 LOAD==6.79(1.38) 4 34550 0 "1 " 0 # LOAD-DROP CHEVPLIN 70.00 LOAD==1.01(0.73) 4 34546 0 "1 " 0 # LOAD-DROP AVENAL 70.00 LOAD==7.72(1.57) 0 # # # (269) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34548 34552 "1 " 0 # line from KETTLEMN 70.00 (2) to BRKR GATES 70.00 1 34548 34546 "1 " 0 # line from KETTLEMN 70.00 BRKR to (1) AVENAL 70.00 4 34548 0 "1 " 0 # LOAD-DROP KETTLEMN 70.00 LOAD==6.32(1.29) 0 # # # (270) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34558 "1 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0 #

Page 241: To determine the system impacts caused by the Project

A-220 GWF Henrietta SISAppendix A

# # (271) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34558 "2 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0 # # # (272) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.45(2.99) 0 # # # (273) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34556 34562 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR SCHLNDLR 70.00 0 # # # (274) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34556 34564 "1 " 0 # line from STRD JCT 70.00 (3) to BRKR STROUD 70.00 1 34556 34474 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR HELM 70.00 1 34556 34562 "1 " 0 # line from STRD JCT 70.00 BRKR to BRKR SCHLNDLR 70.00 4 34564 0 "1 " 0 # LOAD-DROP STROUD 70.00 LOAD==13.09(2.66) 0 # # # (275) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34558 34560 "1 " 0 # line from HURON 70.00 BRKR to (2) CALFLAX 70.00 1 34560 34562 "1 " 0 # line from CALFLAX 70.00 (2) to BRKR SCHLNDLR 70.00 4 34560 0 "1 " 0 # LOAD-DROP CALFLAX 70.00 LOAD==6.53(1.33) 1 34552 34558 "2 " 0 # Must include Gates - Huron in this outage 0 # # # (276) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34562 34566 "1 " 0 # line from SCHLNDLR 70.00 BRKR to (2) PLSNTVLY 70.00 1 34566 34570 "1 " 0 # line from PLSNTVLY 70.00 (2) to BRKR COLNGA 2 70.00 4 34566 0 "1 " 0 # LOAD-DROP PLSNTVLY 70.00 LOAD==10.00(2.51) 0 # # # (277) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 34570 34572 "1 " 0 # line from COLNGA 2 70.00 BRKR to (3) TORNADO 70.00 1 34572 34574 "1 " 0 # line from TORNADO 70.00 (3) to BRKR COLNGA 1 70.00 2 34572 34654 "1 " 0 # TRAN from TORNADO 70.00 (3) to (1) COLNGAGN 9.11 4 34572 0 "1 " 0 # LOAD-DROP TORNADO 70.00 LOAD==1.74(1.44) 3 34654 0 "1 " 0 # GEN-DROP COLNGAGN 9.11 GEN==34.00(5.40) 2 34570 34652 "1 " 0 # Must include Colinga2 - Chv.coal in this outage - modeled on bus,

Page 242: To determine the system impacts caused by the Project

A-221 GWF Henrietta SISAppendix A

3 34652 0 "**" 0 # Drops units on Derrick Sub 4 34652 0 "**" 0 # Drops load at Derrick Sub 0 # # # (278) B2 LINE OUTAGE (BREAKER-TO-BREAKER) # 1 36354 34574 "1 " 0 # line from SAN MIGL 70.00 BRKR to BRKR COLNGA 1 70.00 0 # # # (279) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30835 (30882) 34412 34630 : 2 30835 34412 "1 " 0 # TRAN from HERNDON 230.00 BRKR to (1) HERNDON 115.00 0 # # # (280) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30835 (30883) 34412 34632 : 2 30835 34412 "2 " 0 # TRAN from HERNDON 230.00 BRKR to (1) HERNDON 115.00 0 # # # (281) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30876) 34370 34618 : 2 30875 34370 "1 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # # # (282) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30877) 34370 34620 : 2 30875 34370 "2 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # # # (283) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30875 (30878) 34370 34621 : 2 30875 34370 "3 " 0 # TRAN from MC CALL 230.00 BRKR to (1) MC CALL 115.00 0 # # # (284) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 30881 34430 "3 " 0 # TRAN from HENRIETA 230.00 BRKR to BRKR HENRETTA 115.00 0 # # # (285) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # # **** 3-WINDING TRANSFORMER 30900 (34607) 30055 34606 : 2 30900 30055 "11" 0 # TRAN from GATES 230.00 BRKR to (1) GATES 500.00 0 # # # (286) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) #

Page 243: To determine the system impacts caused by the Project

A-222 GWF Henrietta SISAppendix A

2 30900 30901 "1 " 0 # TRAN from GATES 230.00 BRKR to (3) GATES 1M 230.00 2 30901 34378 "1 " 0 # TRAN from GATES 1M 230.00 (3) to BRKR GATES 115.00 2 30901 34622 "1 " 0 # TRAN from GATES 1M 230.00 (3) to (1) GATES 1T 13.20 4 34378 0 "3 " 0 # Drop Gates Bank #3 0 # # # (287) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34356 34344 "1 " 0 # TRAN from KERCKHF1 115.00 BRKR to (1) KERCKHOF 6.60 4 34344 0 "4 " 0 # LOAD-DROP KERCKHOF 6.60 LOAD==3.24(0.66) 3 34344 0 "2 " 0 # GEN-DROP KERCKHOF 6.60 GEN==6.80(-4.00) 0 # # # (288) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34366 34590 "1 " 0 # TRAN from SANGER 115.00 BRKR to (2) SANGR3T 115.00 2 34590 34488 "1 " 0 # TRAN from SANGR3T 115.00 (2) to BRKR SANGER 70.00 4 34590 0 "3 " 0 # LOAD-DROP SANGR3T 115.00 LOAD==20.55(4.17) 0 # # # (289) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34418 34576 "2 " 0 # TRAN from KINGSBRG 115.00 BRKR to BRKR KNGLOBUS 70.00 0 # # # (290) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34474 30873 "1 " 0 # TRAN from HELM 70.00 BRKR to BRKR HELM 230.00 0 # # # (291) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34480 30830 "2 " 0 # TRAN from KEARNEY 70.00 BRKR to BRKR KEARNEY 230.00 0 # # # (292) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34492 34380 "1 " 0 # TRAN from REEDLEY 70.00 BRKR to BRKR REEDLEY 115.00 0 # # # (293) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34492 34380 "2 " 0 # TRAN from REEDLEY 70.00 BRKR to BRKR REEDLEY 115.00 0 # # # (294) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34528 34420 "2 " 0 # TRAN from CORCORAN 70.00 BRKR to BRKR CORCORAN 115.00 1 34420 34391 "1 " 0 # Must include Corcoran - Quebec (Corcoran CB 142) in this outage

Page 244: To determine the system impacts caused by the Project

A-223 GWF Henrietta SISAppendix A

1 34420 34418 "2 " 0 # Must include Corcoran - Kingburg (Corcoran CB 162) in this outage 1 34528 34460 "1 " 0 # Must include Corcorna - Guernsey (Corcoran CB 42) in this outage 0 # # # (295) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34540 30881 "2 " 0 # TRAN from HENRITTA 70.00 BRKR to BRKR HENRIETA 230.00 0 # # # (296) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34540 30881 "4 " 0 # TRAN from HENRITTA 70.00 BRKR to BRKR HENRIETA 230.00 0 # # # (297) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34552 34378 "2 " 0 # TRAN from GATES 70.00 BRKR to BRKR GATES 115.00 0 # # # (298) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34562 34354 "1 " 0 # TRAN from SCHLNDLR 70.00 BRKR to (3) SCHINDLR 115.00 1 34354 34149 "1 " 0 # line from SCHINDLR 115.00 BRKR to (1) CHENYT 115.00 1 34354 34432 "1 " 0 # line from SCHINDLR 115.00 BRKR to (1) WESTLNDS 115.00 4 34354 0 "1 " 0 # LOAD-DROP SCHINDLR 115.00 LOAD==11.22(2.28) 0 # # # (299) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34652 34570 "1 " 0 # TRAN from CHV.COAL 9.11 (1) to BRKR COLNGA 2 70.00 4 34652 0 "S1" 0 # LOAD-DROP CHV.COAL 9.11 LOAD==5.12(2.48) 4 34652 0 "SG" 0 # LOAD-DROP CHV.COAL 9.11 LOAD==0.94(0.46) 3 34652 0 "1 " 0 # GEN-DROP CHV.COAL 9.11 GEN==2.50(8.30) 3 34652 0 "2 " 0 # GEN-DROP CHV.COAL 9.11 GEN==8.00(4.00) 0 # # # (300) B3 TRANSFORMER OUTAGE (BREAKER-TO-BREAKER) # 2 34658 34452 "1 " 0 # TRAN from WISHON 2.30 (1) to BRKR WISHON 70.00 3 34658 0 "3 " 0 # GEN-DROP WISHON 2.30 GEN==4.50(1.00) 3 34658 0 "4 " 0 # GEN-DROP WISHON 2.30 GEN==4.50(1.00) 0 # # # (301) B1 GENERATOR OUTAGE # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (302) B1 GENERATOR OUTAGE # 3 34344 0 "2" 0 # KERCKHOF 6.60 PGEN=6.80 QGEN=-4.00 0

Page 245: To determine the system impacts caused by the Project

A-224 GWF Henrietta SISAppendix A

# # # (303) B1 GENERATOR OUTAGE # 3 34431 0 "1" 0 # GWF_HEP1 13.80 PGEN=50.00 QGEN=21.57 0 # # # (304) B1 GENERATOR OUTAGE # 3 34433 0 "1" 0 # GWF_HEP2 13.80 PGEN=50.00 QGEN=21.57 0 # # # (305) B1 GENERATOR OUTAGE # 3 34485 0 "1" 0 # FRESNOWW 12.47 PGEN=9.00 QGEN=0.00 0 # # # (306) B1 GENERATOR OUTAGE # 3 34539 0 "1" 0 # GWF_GT1 13.80 PGEN=50.00 QGEN=1.23 0 # # # (307) B1 GENERATOR OUTAGE # 3 34541 0 "1" 0 # GWF_GT2 13.80 PGEN=50.00 QGEN=1.23 0 # # # (308) B1 GENERATOR OUTAGE # 3 34553 0 "1" 0 # WHD_GAT2 13.80 PGEN=49.00 QGEN=-25.30 0 # # # (309) B1 GENERATOR OUTAGE # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (310) B1 GENERATOR OUTAGE # 3 34602 0 "1" 0 # HELMS 2 18.00 PGEN=404.00 QGEN=66.06 0 # # # (311) B1 GENERATOR OUTAGE # 3 34604 0 "1" 0 # HELMS 3 18.00 PGEN=404.00 QGEN=66.12 0 # # # (312) B1 GENERATOR OUTAGE # 3 34608 0 "2" 0 # AGRICO 13.80 PGEN=7.00 QGEN=1.64 0 # # # (313) B1 GENERATOR OUTAGE # 3 34608 0 "3" 0 # AGRICO 13.80 PGEN=18.10 QGEN=4.24 0 # # # (314) B1 GENERATOR OUTAGE #

Page 246: To determine the system impacts caused by the Project

A-225 GWF Henrietta SISAppendix A

3 34608 0 "4" 0 # AGRICO 13.80 PGEN=26.00 QGEN=6.09 0 # # # (315) B1 GENERATOR OUTAGE # 3 34610 0 "1" 0 # HAAS 13.80 PGEN=70.00 QGEN=18.75 0 # # # (316) B1 GENERATOR OUTAGE # 3 34610 0 "2" 0 # HAAS 13.80 PGEN=70.00 QGEN=18.75 0 # # # (317) B1 GENERATOR OUTAGE # 3 34612 0 "1" 0 # BLCH 2-2 13.80 PGEN=50.00 QGEN=9.61 0 # # # (318) B1 GENERATOR OUTAGE # 3 34614 0 "1" 0 # BLCH 2-3 13.80 PGEN=50.00 QGEN=13.00 0 # # # (319) B1 GENERATOR OUTAGE # 3 34616 0 "1" 0 # KINGSRIV 13.80 PGEN=47.00 QGEN=9.00 0 # # # (320) B1 GENERATOR OUTAGE # 3 34618 0 "1" 0 # MCCALL1T 13.20 PGEN=0.00 QGEN=36.40 0 # # # (321) B1 GENERATOR OUTAGE # 3 34621 0 "1" 0 # MCCALL3T 13.20 PGEN=0.00 QGEN=4.85 0 # # # (322) B1 GENERATOR OUTAGE # 3 34624 0 "1" 0 # BALCH 1 13.20 PGEN=27.00 QGEN=10.00 0 # # # (323) B1 GENERATOR OUTAGE # 3 34630 0 "1" 0 # HERNDN1T 13.20 PGEN=0.00 QGEN=20.26 0 # # # (324) B1 GENERATOR OUTAGE # 3 34632 0 "1" 0 # HERNDN2T 13.20 PGEN=0.00 QGEN=32.58 0 # # # (325) B1 GENERATOR OUTAGE # 3 34636 0 "2" 0 # FRIANTDM 6.60 PGEN=14.70 QGEN=6.14 0 # #

Page 247: To determine the system impacts caused by the Project

A-226 GWF Henrietta SISAppendix A

# (326) B1 GENERATOR OUTAGE # 3 34636 0 "3" 0 # FRIANTDM 6.60 PGEN=7.80 QGEN=3.26 0 # # # (327) B1 GENERATOR OUTAGE # 3 34636 0 "4" 0 # FRIANTDM 6.60 PGEN=2.30 QGEN=0.96 0 # # # (328) B1 GENERATOR OUTAGE # 3 34640 0 "1" 0 # ULTR.PWR 9.11 PGEN=14.50 QGEN=13.00 0 # # # (329) B1 GENERATOR OUTAGE # 3 34642 0 "1" 0 # KINGSBUR 9.11 PGEN=34.00 QGEN=17.30 0 # # # (330) B1 GENERATOR OUTAGE # 3 34646 0 "1" 0 # SANGERCO 9.11 PGEN=37.50 QGEN=4.31 0 # # # (331) B1 GENERATOR OUTAGE # 3 34648 0 "1" 0 # DINUBA E 13.80 PGEN=12.00 QGEN=7.00 0 # # # (332) B1 GENERATOR OUTAGE # 3 34650 0 "1" 0 # GWF-PWR. 13.80 PGEN=23.00 QGEN=12.00 0 # # # (333) B1 GENERATOR OUTAGE # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=2.50 QGEN=8.30 0 # # # (334) B1 GENERATOR OUTAGE # 3 34652 0 "2" 0 # CHV.COAL 9.11 PGEN=8.00 QGEN=4.00 0 # # # (335) B1 GENERATOR OUTAGE # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.00 QGEN=-3.48 0 # # # (336) B1 GENERATOR OUTAGE # 3 34658 0 "3" 0 # WISHON 2.30 PGEN=4.50 QGEN=1.00 0 # # # (337) B1 GENERATOR OUTAGE # 3 34658 0 "4" 0 # WISHON 2.30 PGEN=4.50 QGEN=1.00 0

Page 248: To determine the system impacts caused by the Project

A-227 GWF Henrietta SISAppendix A

# # # (338) B1 GENERATOR OUTAGE # 3 34671 0 "1" 0 # KRCDPCT1 13.80 PGEN=50.00 QGEN=10.75 0 # # # (339) B1 GENERATOR OUTAGE # 3 34672 0 "1" 0 # KRCDPCT2 13.80 PGEN=50.00 QGEN=10.75 0 # # # (340) B1 GENERATOR OUTAGE # 3 38720 0 "1" 0 # PINE FLT 13.80 PGEN=57.00 QGEN=23.30 0 # # # (341) B1 GENERATOR OUTAGE # 3 34661 0 "1" 0 # P0418GT1 13.80 PGEN=78.80 QGEN=13.93 0 # # # (342) B1 GENERATOR OUTAGE # 3 34663 0 "2" 0 # P0418GT2 13.80 PGEN=78.80 QGEN=13.93 0 # # # (343) B1 GENERATOR OUTAGE # 3 34665 0 "3" 0 # P0418GT3 13.80 PGEN=78.80 QGEN=13.93 0 # # # (344) B1 GENERATOR OUTAGE # 3 34667 0 "4" 0 # P0418GT4 13.80 PGEN=78.80 QGEN=13.93 0 # # # (345) B1 GENERATOR OUTAGE # 3 34685 0 "1" 0 # P0615CT1 16.50 PGEN=192.00 QGEN=35.45 0 # # # (346) B1 GENERATOR OUTAGE # 3 34686 0 "1" 0 # P0615CT2 16.50 PGEN=192.00 QGEN=35.45 0 # # # (347) B1 GENERATOR OUTAGE # 3 34687 0 "1" 0 # P0615STG 16.50 PGEN=193.00 QGEN=35.57 0 # # # (348) B1 GENERATOR OUTAGE # 3 34688 0 "1" 0 # Q254CTG1 18.00 PGEN=172.40 QGEN=41.25 0 # # # (349) B1 GENERATOR OUTAGE #

Page 249: To determine the system impacts caused by the Project

A-228 GWF Henrietta SISAppendix A

3 34689 0 "2" 0 # Q254CTG2 18.00 PGEN=172.40 QGEN=41.25 0 # # # (350) B1 GENERATOR OUTAGE # 3 34690 0 "3" 0 # Q254STG1 18.00 PGEN=290.80 QGEN=67.53 0 # # # (351) B1 GENERATOR OUTAGE # 3 34691 0 "1" 0 # Q272_ST1 13.80 PGEN=27.00 QGEN=1.87 0 # # # (352) B1 GENERATOR OUTAGE # 3 34692 0 "1" 0 # Q272SLST 13.80 PGEN=139.00 QGEN=35.74 0 # # # (353) L-1/G-1 OVERLAPPING OUTAGE # Smyrna - Semitropic - Midway 115 kV Line and Exchequer 1 34700 34708 "1 " 0 # line from SMYRNA 115.00 BRKR to (2) MCKIBBEN 115.00 1 34708 34742 "1 " 0 # line from MCKIBBEN 115.00 (2) to (2) SEMITRPJ 115.00 1 34742 34746 "1 " 0 # line from SEMITRPJ 115.00 (2) to (2) GANSO 115.00 1 34746 34774 "1 " 0 # line from GANSO 115.00 (2) to BRKR MIDWAY 115.00 4 34746 0 "1 " 0 # LOAD-DROP GANSO 115.00 LOAD==5.34(1.22) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=89.95 QGEN=18.49 0 # # # (354) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #2 70 kV Line and Chevron Coalinga Unit 1 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00 2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=17.00 QGEN=8.30 0 # # # (355) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #1 70 kV Line and Chevron Coalinga Unit 1 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.03(2.5) 0 # 3 34652 0 "1" 0 # CHV.COAL 9.11 PGEN=17.00 QGEN=8.30 0 # # # (356) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #2 70 kV Line and Coalinga Cogen 1 34184 34570 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR COLNGA 2 70.00 1 34184 34552 "1 " 0 # line from GATS2_TP 70.00 (3) to BRKR GATES 70.00

Page 250: To determine the system impacts caused by the Project

A-229 GWF Henrietta SISAppendix A

2 34184 34553 "1 " 0 # TRAN from GATS2_TP 70.00 (3) to (1) WHD_GAT2 13.80 3 34553 0 "1 " 0 # GEN-DROP WHD_GAT2 13.80 GEN==49.00(-25.30) # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.22 QGEN=-13.50 0 # # # (357) L-1/G-1 OVERLAPPING OUTAGE # Gates - Coalinga #1 70 kV Line and Coalinga Cogen 1 34552 34578 "1 " 0 # line from GATES 70.00 BRKR to (2) JACALITO 70.00 1 34578 34574 "1 " 0 # line from JACALITO 70.00 (2) to BRKR COLNGA 1 70.00 4 34578 0 "1 " 0 # LOAD-DROP JACALITO 70.00 LOAD==4.03(2.5) 0 # 3 34654 0 "1" 0 # COLNGAGN 9.11 PGEN=34.22 QGEN=-13.50 0 # # # (358) L-1/G-1 OVERLAPPING OUTAGE # Borden - Coppermine 70 kV Line and Friant PP Unit 2 1 34262 34454 "1 " 0 # line from CASSIDY 70.00 (2) to (2) RIVERROC 70.00 1 34262 34256 "1 " 0 # line from CASSIDY 70.00 (2) to BRKR BORDEN 70.00 1 34454 34464 "1 " 0 # line from RIVERROC 70.00 (2) to BRKR COPPRMNE 70.00 4 34262 0 "1 " 0 # LOAD-DROP CASSIDY 70.00 LOAD==14.31(2.90) 4 34454 0 "1 " 0 # LOAD-DROP RIVERROC 70.00 LOAD==2.01(1.83) # 3 34636 0 "2" 0 # FRIANTDM 6.60 PGEN=14.70 QGEN=6.14 0 # # # (359) L-1/G-1 OVERLAPPING OUTAGE # Henrietta - Lemoore 70 kV Line and GWF Hanford 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) # 3 34650 0 "1" 0 # GWF-PWR. 13.80 PGEN=23.00 QGEN=12.00 0 # # # (360) L-1/G-1 OVERLAPPING OUTAGE # Henrietta - Lemoore 70 kV Line and GWF Henrietta Unit 1 1 34516 34520 "1 " 0 # line from LEPRINO 70.00 (1) to (4) LPRNO TP 70.00 1 34520 34518 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR LEMOORE 70.00 1 34520 34524 "1 " 0 # line from LPRNO TP 70.00 (4) to (1) CANDLEWK 70.00 1 34520 34540 "1 " 0 # line from LPRNO TP 70.00 (4) to BRKR HENRITTA 70.00 4 34516 0 "1 " 0 # LOAD-DROP LEPRINO 70.00 LOAD==16.10(9.12) 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) # 3 34539 0 "1" 0 # GWF_GT1 13.80 PGEN=50.00 QGEN=1.23 0 #

Page 251: To determine the system impacts caused by the Project

A-230 GWF Henrietta SISAppendix A

# # (361) L-1/G-1 OVERLAPPING OUTAGE # McCall - Wahtoke 115 kV Line and Sanger Cogen 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 # 3 34646 0 "1" 0 # SANGERCO 9.11 PGEN=37.50 QGEN=4.31 0 # # # (362) L-1/G-1 OVERLAPPING OUTAGE # McCall - Wahtoke 115 kV Line and Kings River Power House 1 34370 34382 "1 " 0 # line from MC CALL 115.00 BRKR to BRKR WAHTOKE 115.00 # 3 34616 0 "1" 0 # KINGSRIV 13.80 PGEN=47.00 QGEN=9.00 0 # # # (363) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Exchequer 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (364) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Exchequer 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (365) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Exchequer 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (366) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Exchequer 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (367) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Exchequer 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (368) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Exchequer

Page 252: To determine the system impacts caused by the Project

A-231 GWF Henrietta SISAppendix A

1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (369) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Exchequer 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (370) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Exchequer 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (371) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Exchequer 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (372) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Exchequer 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) #

Page 253: To determine the system impacts caused by the Project

A-232 GWF Henrietta SISAppendix A

3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (373) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Exchequer 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (374) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Exchequer 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (375) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Exchequer 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (376) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Exchequer 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (377) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Exchequer 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (378) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Exchequer 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34306 0 "1" 0 # EXCHQUER 13.80 PGEN=94.50 QGEN=8.77 0 # # # (379) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Kerckhoff

Page 254: To determine the system impacts caused by the Project

A-233 GWF Henrietta SISAppendix A

1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (380) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Kerckhoff 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (381) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Kerckhoff 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (382) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Kerckhoff 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (383) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Kerckhoff 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (384) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Kerckhoff 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (385) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Kerckhoff 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00

Page 255: To determine the system impacts caused by the Project

A-234 GWF Henrietta SISAppendix A

1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (386) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Kerckhoff 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (387) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Kerckhoff 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (388) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Kerckhoff 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (389) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Kerckhoff 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 #

Page 256: To determine the system impacts caused by the Project

A-235 GWF Henrietta SISAppendix A

# # (390) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Kerckhoff 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (391) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Kerckhoff 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (392) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Kerckhoff 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (393) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Kerckhoff 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (394) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Kerckhoff 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34308 0 "1" 0 # KERCKHOF 13.80 PGEN=129.00 QGEN=16.00 0 # # # (395) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Helms Unit 1 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (396) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Helms Unit 1 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (397) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Helms Unit 1

Page 257: To determine the system impacts caused by the Project

A-236 GWF Henrietta SISAppendix A

1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (398) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Helms Unit 1 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (399) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Helms Unit 1 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (400) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Helms Unit 1 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (401) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Helms Unit 1 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (402) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Helms Unit 1 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # #

Page 258: To determine the system impacts caused by the Project

A-237 GWF Henrietta SISAppendix A

# (403) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Helms Unit 1 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (404) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Helms Unit 1 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (405) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Helms Unit 1 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (406) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Helms Unit 1 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (407) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Helms Unit 1 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 #

Page 259: To determine the system impacts caused by the Project

A-238 GWF Henrietta SISAppendix A

# # (408) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Helms Unit 1 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (409) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Helms Unit 1 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (410) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Helms Unit 1 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 34600 0 "1" 0 # HELMS 1 18.00 PGEN=404.00 QGEN=66.02 0 # # # (411) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Kearney 230 kV Line and Melones Unit 1 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (412) L-1/G-1 OVERLAPPING OUTAGE # Panoche - Helm 230 kV Line and Melones Unit 1 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (413) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #1 230 kV Line and Melones Unit 1 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (414) L-1/G-1 OVERLAPPING OUTAGE # Gates - Panoche #2 230 kV Line and Melones Unit 1 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (415) L-1/G-1 OVERLAPPING OUTAGE # Helm - McCall 230 kV Line and Melones Unit 1

Page 260: To determine the system impacts caused by the Project

A-239 GWF Henrietta SISAppendix A

1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (416) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #1 230 kV Line and Melones Unit 1 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (417) L-1/G-1 OVERLAPPING OUTAGE # Helms - Gregg #2 230 kV Line and Melones Unit 1 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (418) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #1 230 kV Line and Melones Unit 1 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (419) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Herndon #2 230 kV Line and Melones Unit 1 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (420) L-1/G-1 OVERLAPPING OUTAGE # Gregg - Ashlan 230 kV Line and Melones Unit 1 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (421) L-1/G-1 OVERLAPPING OUTAGE # Gates - Gregg 230 kV Line and Melones Unit 1 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00

Page 261: To determine the system impacts caused by the Project

A-240 GWF Henrietta SISAppendix A

1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (422) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Kearney 230 kV Line and Melones Unit 1 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (423) L-1/G-1 OVERLAPPING OUTAGE # Herndon - Ashlan 230 kV Line and Melones Unit 1 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (424) L-1/G-1 OVERLAPPING OUTAGE # Haas - McCall 230 kV Line and Melones Unit 1 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (425) L-1/G-1 OVERLAPPING OUTAGE # Balch - McCall 230 kV Line and Melones Unit 1 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 #

Page 262: To determine the system impacts caused by the Project

A-241 GWF Henrietta SISAppendix A

# # (426) L-1/G-1 OVERLAPPING OUTAGE # Gates - McCall 230 kV Line and Melones Unit 1 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (427) L-1/G-1 OVERLAPPING OUTAGE # Templeton - Gates 230 kV Line and Melones Unit 1 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (428) L-1/G-1 OVERLAPPING OUTAGE # Morro Bay - Gates 230 kV Line and Melones Unit 1 1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (429) L-1/G-1 OVERLAPPING OUTAGE # Gates - Arco 230 kV Line and Melones Unit 1 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # # (430) L-1/G-1 OVERLAPPING OUTAGE # Gates - Midway 230 kV Line and Melones Unit 1 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 3 37561 0 "1" 0 # MELONE1 13.80 PGEN=119.00 QGEN=60.00 0 # # -1 # EOF

Page 263: To determine the system impacts caused by the Project

A-242 GWF Henrietta SISAppendix A

Spring Peak Category C Contingencies # Q272 2013 sprpk category c contingency list (dctl and bus outages) # Yosemite and Fresno Divisions Zones 313 and 314 # # 2013 sprpk category c contingency list # Yosemite Zone 313 # # # (1) C5 DCTL OUTAGE # Wilson - Atwater and El Capitan - Wilson 115 kV Lines 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 1 34136 34138 "1 " 0 # line from WILSON B 115.00 BRKR to BRKR EL CAPTN 115.00 0 # # # (2) C5 DCTL OUTAGE # Wilson - Atwater and Atwater - El Capitan 115 kV Lines 1 34134 34104 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR ATWATER 115.00 # 1 34104 34106 "1 " 0 # line from ATWATER 115.00 BRKR to (2) CASTLE 115.00 1 34106 34138 "1 " 0 # line from CASTLE 115.00 (2) to BRKR EL CAPTN 115.00 0 # # # (3) C5 DCTL OUTAGE # Wilson - Merced #2 and Wilson - Oro Loma 115 kV Lines 1 34134 34144 "1 " 0 # line from WILSON A 115.00 BRKR to BRKR MERCED 115.00 # 1 34118 34136 "1 " 0 # line from LE GRNDJ 115.00 (2) to BRKR WILSON B 115.00 1 34118 34168 "1 " 0 # line from LE GRNDJ 115.00 (2) to (2) EL NIDO 115.00 1 34168 34162 "1 " 0 # line from EL NIDO 115.00 (2) to BRKR ORO LOMA 115.00 4 34168 0 "1 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==12.49(2.54) 4 34168 0 "2 " 0 # LOAD-DROP EL NIDO 115.00 LOAD==15.00(3.05) 0 # # # (4) C5 DCTL OUTAGE # Panoche - Schindler #1 and #2 115 kV Lines 1 34158 34350 "1 " 0 # line from PANOCHE 115.00 BRKR to (2) KAMM 115.00 1 34350 34352 "1 " 0 # line from KAMM 115.00 (2) to (2) CANTUA 115.00 1 34352 34432 "1 " 0 # line from CANTUA 115.00 (2) to (2) WESTLNDS 115.00 1 34432 34354 "1 " 0 # line from WESTLNDS 115.00 (2) to BRKR SCHINDLR 115.00 4 34350 0 "1 " 0 # LOAD-DROP KAMM 115.00 LOAD==3.85(1.75) 4 34352 0 "1 " 0 # LOAD-DROP CANTUA 115.00 LOAD==16.79(3.41) 4 34432 0 "16" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==0.94(0.23) 4 34432 0 "18" 0 # LOAD-DROP WESTLNDS 115.00 LOAD==1.21(0.32) # 1 34141 34148 "1 " 0 # line from PAN2_TAP 115.00 (2) to (2) CHENY 115.00 2 34141 34142 "1 " 0 # TRAN from PAN2_TAP 115.00 (2) to (1) WHD_PAN2 13.80

Page 264: To determine the system impacts caused by the Project

A-243 GWF Henrietta SISAppendix A

1 34148 34149 "1 " 0 # line from CHENY 115.00 (2) to (3) CHENYT 115.00 1 34149 34158 "1 " 0 # line from CHENYT 115.00 (3) to BRKR PANOCHE 115.00 1 34149 34354 "1 " 0 # line from CHENYT 115.00 (3) to BRKR SCHINDLR 115.00 4 34148 0 "1 " 0 # LOAD-DROP CHENY 115.00 LOAD==13.12(2.66) 3 34142 0 "1 " 0 # GEN-DROP WHD_PAN2 13.80 GEN==49.00(4.03) 0 # # # (5) C5 DCTL OUTAGE # Gates - Panoche #1 and #2 230 kV Lines 1 30790 30900 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 # 1 30790 30900 "2 " 0 # line from PANOCHE 230.00 BRKR to BRKR GATES 230.00 0 # # # (6) C5 DCTL OUTAGE # Los Banos - Panoche #2 and Los Banos - Dos Amigos 230 kV Lines 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 1 30765 38615 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR DS AMIGO 230.00 0 # # # (7) C5 DCTL OUTAGE # Los Banos - Panoche #2 and Dos Amigos - Panoche 230 kV Lines 1 30765 30790 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR PANOCHE 230.00 # 1 38615 30790 "1 " 0 # line from DS AMIGO 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (8) C5 DCTL OUTAGE # Los Banos - San Luis PGP #1 and #2 230 kV Lines 1 30765 38625 "1 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 # 1 30765 38625 "2 " 0 # line from LOSBANOS 230.00 BRKR to BRKR SN LS PP 230.00 0 # # # (9) C5 DCTL OUTAGE # Bellota - Melones and Bellota - Warnerville 230 kV Lines 1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 30500 38208 "1 " 0 # line from BELLOTA 230.00 BRKR to (3) COTTLE B 230.00 1 38208 30515 "1 " 0 # line from COTTLE B 230.00 (3) to BRKR WARNERVL 230.00 4 38208 0 "2 " 0 # LOAD-DROP COTTLE B 230.00 LOAD==21.32(7.38) 0 # # # (10) C5 DCTL OUTAGE # Bellota - Melones and Warnerville - Wilson 230 kV Lines

Page 265: To determine the system impacts caused by the Project

A-244 GWF Henrietta SISAppendix A

1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (11) C5 DCTL OUTAGE # Bellota - Melones and Melones - Wilson 230 kV Lines 1 30500 38206 "1 " 0 # line from BELLOTA 230.00 BRKR to (2) COTTLE A 230.00 1 38206 37563 "1 " 0 # line from COTTLE A 230.00 (2) to BRKR MELONES 230.00 4 38206 0 "1 " 0 # LOAD-DROP COTTLE A 230.00 LOAD==19.23(0.00) 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Bellota - Melones line # 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Melones - Wilson line 0 # # # (12) C5 DCTL OUTAGE # Melones - Wilson and Warnerville - Wilson 230 kV Lines 1 37563 30800 "1 " 0 # line from MELONES 230.00 BRKR to BRKR WILSON 230.00 3 34604 0 "**" 0 # Drop Helms unit#3 with a loss Melones - Wilson line # 1 30515 30800 "1 " 0 # line from WARNERVL 230.00 BRKR to BRKR WILSON 230.00 0 # # # (13) C5 DCTL OUTAGE # Wilson - Borden #1 and #2 230 kV Lines 1 30795 30805 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR BORDEN 230.00 1 30795 30800 "1 " 0 # line from STOREY 2 230.00 (2) to BRKR WILSON 230.00 4 30795 0 "2 " 0 # LOAD-DROP STOREY 2 230.00 LOAD==33.89(6.88) # 1 30796 30800 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR WILSON 230.00 1 30796 30805 "1 " 0 # line from STOREY 1 230.00 (2) to BRKR BORDEN 230.00 4 30796 0 "1 " 0 # LOAD-DROP STOREY 1 230.00 LOAD==37.87(7.69) 0 # # # (14) C5 DCTL OUTAGE # Borden - Gregg #1 and #2 230 kV Lines 1 30805 30810 "1 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden line # 1 30805 30810 "2 " 0 # line from BORDEN 230.00 BRKR to BRKR GREGG 230.00 3 34604 0 "**" 0 # Drop unit#3 with loss of Gregg - Borden #2 line 0 # # # (15) C5 DCTL OUTAGE # Moss Landing - Panoche and Coburn - Panoche 230 kV Lines 1 30750 30790 "1 " 0 # line from MOSSLND2 230.00 BRKR to BRKR PANOCHE 230.00

Page 266: To determine the system impacts caused by the Project

A-245 GWF Henrietta SISAppendix A

# 1 30760 30790 "1 " 0 # line from COBURN 230.00 BRKR to BRKR PANOCHE 230.00 0 # # # (16) C5 DCTL OUTAGE # Panoche - Helm and Panoche - Kearney 230 kV Lines 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 # 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) 0 # # # (17) BUS FAULT 30765 "LOSBANOS" Bus Section 1 # 1 30765 30670 "1" 0 # LINE from LOSBANOS 230.00 to WESTLEY 230.00 1 30765 30790 "2" 0 # LINE from LOSBANOS 230.00 to PANOCHE 230.00 1 30765 38625 "1" 0 # LINE from LOSBANOS 230.00 to SN LS PP 230.00 1 30765 38625 "2" 0 # LINE from LOSBANOS 230.00 to SN LS PP 230.00 2 30765 34214 "3" 0 # TRAN from LOSBANOS 230.00 to LOS BANS 70.00 6 30765 0 "v" 0 # drop Los Banos 230 kV shunt Caps 0 # # # (18) BUS FAULT 30765 "LOSBANOS" Bus Section 2 # 1 30765 30790 "1" 0 # LINE from LOSBANOS 230.00 to PANOCHE 230.00 1 30765 38615 "1" 0 # LINE from LOSBANOS 230.00 to DS AMIGO 230.00 2 30765 34214 "4" 0 # TRAN from LOSBANOS 230.00 to LOS BANS 70.00 0 # # # (19) BUS FAULT 30790 "PANOCHE" Bus Section 1 # 1 30790 30760 "1" 0 # LINE from PANOCHE 230.00 to COBURN 230.00 1 30790 30765 "1" 0 # LINE from PANOCHE 230.00 to LOSBANOS 230.00 1 30790 30765 "2" 0 # LINE from PANOCHE 230.00 to LOSBANOS 230.00 1 30790 30825 "1" 0 # LINE from PANOCHE 230.00 to MCMULLN1 230.00 1 30790 30900 "1" 0 # LINE from PANOCHE 230.00 to GATES 230.00 2 30790 30791 "1" 0 # TRAN from PANOCHE 230.00 to PNCHE 1M 230.00 0 # # # (20) BUS FAULT 30790 "PANOCHE" Bus Section 2 # 1 30790 30750 "1" 0 # LINE from PANOCHE 230.00 to MOSSLND2 230.00 1 30790 30793 "1" 0 # LINE from PANOCHE 230.00 to PANO_EC 230.00 1 30790 30873 "1" 0 # LINE from PANOCHE 230.00 to HELM 230.00 1 30790 30900 "2" 0 # LINE from PANOCHE 230.00 to GATES 230.00 1 30790 38615 "1" 0 # LINE from PANOCHE 230.00 to DS AMIGO 230.00 2 30790 34158 "2" 0 # TRAN from PANOCHE 230.00 to PANOCHE 115.00 0 # # # (21) BUS FAULT 34100 "CHWCHLLA" # 1 34100 34101 "1" 0 # LINE from CHWCHLLA 115.00 to CERTAN T 115.00 1 34100 34105 "1" 0 # LINE from CHWCHLLA 115.00 to CERTANJ1 115.00 4 34100 0 "1 " 0 # LOAD-DROP CHWCHLLA 115.00 LOAD==10.13(2.06) 4 34100 0 "2 " 0 # LOAD-DROP CHWCHLLA 115.00 LOAD==13.86(2.82) 0 # # # (22) BUS FAULT 34104 "ATWATER"

Page 267: To determine the system impacts caused by the Project

A-246 GWF Henrietta SISAppendix A

# 1 34104 34106 "1" 0 # LINE from ATWATER 115.00 to CASTLE 115.00 1 34104 34108 "1" 0 # LINE from ATWATER 115.00 to CRESEY T 115.00 1 34104 34134 "1" 0 # LINE from ATWATER 115.00 to WILSON A 115.00 4 34104 0 "1 " 0 # LOAD-DROP ATWATER 115.00 LOAD==32.40(6.57) 4 34104 0 "2 " 0 # LOAD-DROP ATWATER 115.00 LOAD==28.36(5.76) 0 # # # (23) BUS FAULT 34112 "EXCHEQUR" # 1 34112 34116 "1" 0 # LINE from EXCHEQUR 115.00 to LE GRAND 115.00 2 34112 34176 "1" 0 # TRAN from EXCHEQUR 115.00 to EXCHQRTP 115.00 0 # # # (24) BUS FAULT 34116 "LE GRAND" # 1 34116 34101 "1" 0 # LINE from LE GRAND 115.00 to CERTAN T 115.00 1 34116 34112 "1" 0 # LINE from LE GRAND 115.00 to EXCHEQUR 115.00 1 34116 34134 "1" 0 # LINE from LE GRAND 115.00 to WILSON A 115.00 1 34116 34154 "1" 0 # LINE from LE GRAND 115.00 to DAIRYLND 115.00 4 34116 0 "1 " 0 # LOAD-DROP LE GRAND 115.00 LOAD==13.41(2.72) 0 # # # (25) BUS FAULT 34134 "WILSON A" # 1 34134 34116 "1" 0 # LINE from WILSON A 115.00 to LE GRAND 115.00 1 34134 34104 "1" 0 # LINE from WILSON A 115.00 to ATWATER 115.00 1 34134 34136 "1" 0 # LINE from WILSON A 115.00 to WILSON B 115.00 1 34134 34144 "1" 0 # LINE from WILSON A 115.00 to MERCED 115.00 2 34134 30800 "1" 0 # TRAN from WILSON A 115.00 to WILSON 230.00 4 34134 0 "3 " 0 # LOAD-DROP WILSON A 115.00 LOAD==18.66(3.79) 6 34134 0 "v" 0 # drop Wilson A 115 kV shunt Caps 0 # # # (26) BUS FAULT 34136 "WILSON B" # 1 34136 34118 "1" 0 # LINE from WILSON B 115.00 to LE GRNDJ 115.00 1 34136 34134 "1" 0 # LINE from WILSON B 115.00 to WILSON A 115.00 1 34136 34138 "1" 0 # LINE from WILSON B 115.00 to EL CAPTN 115.00 1 34136 34144 "2" 0 # LINE from WILSON B 115.00 to MERCED 115.00 2 34136 30800 "2" 0 # TRAN from WILSON B 115.00 to WILSON 230.00 0 # # # (27) BUS FAULT 34138 "EL CAPTN" # 1 34138 34106 "1" 0 # LINE from EL CAPTN 115.00 to CASTLE 115.00 1 34138 34136 "1" 0 # LINE from EL CAPTN 115.00 to WILSON B 115.00 4 34138 0 "1 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==19.47(3.95) 4 34138 0 "2 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==25.91(5.26) 4 34138 0 "3 " 0 # LOAD-DROP EL CAPTN 115.00 LOAD==33.05(6.71) 0 # # # (28) BUS FAULT 34144 "MERCED" # 1 34144 34110 "1" 0 # LINE from MERCED 115.00 to ATWATR J 115.00 1 34144 34134 "1" 0 # LINE from MERCED 115.00 to WILSON A 115.00 1 34144 34136 "2" 0 # LINE from MERCED 115.00 to WILSON B 115.00 2 34144 34146 "2" 0 # TRAN from MERCED 115.00 to MERCED M 115.00 4 34144 0 "1 " 0 # LOAD-DROP MERCED 115.00 LOAD==37.10(7.53) 4 34144 0 "3 " 0 # LOAD-DROP MERCED 115.00 LOAD==19.45(3.95) 0 # # # (29) BUS FAULT 34154 "DAIRYLND"

Page 268: To determine the system impacts caused by the Project

A-247 GWF Henrietta SISAppendix A

# 1 34154 34116 "1" 0 # LINE from DAIRYLND 115.00 to LE GRAND 115.00 1 34154 34150 "1" 0 # LINE from DAIRYLND 115.00 to NEWHALL 115.00 4 34154 0 "1 " 0 # LOAD-DROP DAIRYLND 115.00 LOAD==25.82(5.24) 0 # # # (30) BUS FAULT 34158 "PANOCHE" Bus Section 1 # 1 34158 34149 "1" 0 # LINE from PANOCHE 115.00 to CHENYT 115.00 1 34158 34159 "1" 0 # LINE from PANOCHE 115.00 to PANOCHEJ 115.00 2 34158 30790 "2" 0 # TRAN from PANOCHE 115.00 to PANOCHE 230.00 2 34158 34186 "1" 0 # TRAN from PANOCHE 115.00 to DG_PAN1 13.80 0 # # # (31) BUS FAULT 34158 "PANOCHE" Bus Section 2 # 1 34158 34157 "1" 0 # LINE from PANOCHE 115.00 to PANOCHET 115.00 1 34158 34189 "1" 0 # LINE from PANOCHE 115.00 to STARWOOD 115.00 1 34158 34350 "1" 0 # LINE from PANOCHE 115.00 to KAMM 115.00 2 34158 30791 "1" 0 # TRAN from PANOCHE 115.00 to PNCHE 1M 230.00 0 # # # (32) BUS FAULT 34200 "ORO LOMA" # 1 34200 34218 "1" 0 # LINE from ORO LOMA 70.00 to DOS PALS 70.00 1 34200 34222 "1" 0 # LINE from ORO LOMA 70.00 to MRCYSPRS 70.00 1 34200 34234 "1" 0 # LINE from ORO LOMA 70.00 to POSO J1 70.00 2 34200 34162 "2" 0 # TRAN from ORO LOMA 70.00 to ORO LOMA 115.00 4 34200 0 "1 " 0 # LOAD-DROP ORO LOMA 70.00 LOAD==8.64(1.75) 0 # # # (33) BUS FAULT 34202 "MERCED" # 1 34202 34203 "1" 0 # LINE from MERCED 70.00 to ELNIDOTP 70.00 1 34202 34230 "1" 0 # LINE from MERCED 70.00 to MRCDFLLS 70.00 2 34202 34146 "2" 0 # TRAN from MERCED 70.00 to MERCED M 115.00 0 # # # (34) BUS FAULT 34206 "CANAL" # 1 34206 34212 "1" 0 # LINE from CANAL 70.00 to LVNGSTNT 70.00 1 34206 34216 "1" 0 # LINE from CANAL 70.00 to SNTA RTA 70.00 1 34206 34220 "1" 0 # LINE from CANAL 70.00 to ORTIGA 70.00 4 34206 0 "1 " 0 # LOAD-DROP CANAL 70.00 LOAD==30.56(6.21) 4 34206 0 "2 " 0 # LOAD-DROP CANAL 70.00 LOAD==31.27(6.35) 0 # # # (35) BUS FAULT 34214 "LOS BANS" # 1 34214 34208 "1" 0 # LINE from LOS BANS 70.00 to CHEVPIPE 70.00 1 34214 34272 "1" 0 # LINE from LOS BANS 70.00 to WRGHT PP 70.00 1 34214 34278 "1" 0 # LINE from LOS BANS 70.00 to PCHCO PP 70.00 1 34214 34282 "1" 0 # LINE from LOS BANS 70.00 to ONLL PMP 69.00 2 34214 30765 "3" 0 # TRAN from LOS BANS 70.00 to LOSBANOS 230.00 2 34214 30765 "4" 0 # TRAN from LOS BANS 70.00 to LOSBANOS 230.00 0 # # # (36) BUS FAULT 34216 "SNTA RTA" # 1 34216 34206 "1" 0 # LINE from SNTA RTA 70.00 to CANAL 70.00 1 34216 34218 "1" 0 # LINE from SNTA RTA 70.00 to DOS PALS 70.00 4 34216 0 "1 " 0 # LOAD-DROP SNTA RTA 70.00 LOAD==7.48(1.52) 0

Page 269: To determine the system impacts caused by the Project

A-248 GWF Henrietta SISAppendix A

# # # (37) BUS FAULT 34230 "MRCDFLLS" # 1 34230 34202 "1" 0 # LINE from MRCDFLLS 70.00 to MERCED 70.00 1 34230 34321 "1" 0 # LINE from MRCDFLLS 70.00 to MCSWAINJ 70.00 2 34230 34322 "1" 0 # TRAN from MRCDFLLS 70.00 to MERCEDFL 9.11 2 34230 34322 "2" 0 # TRAN from MRCDFLLS 70.00 to MERCEDFL 9.11 4 34230 0 "2 " 0 # LOAD-DROP MRCDFLLS 70.00 LOAD==8.94(1.82) 0 # # # (38) BUS FAULT 34238 "BONITA" # 1 34238 34236 "1" 0 # LINE from BONITA 70.00 to POSO J2 70.00 1 34238 34255 "1" 0 # LINE from BONITA 70.00 to TRIGO J 70.00 4 34238 0 "1 " 0 # LOAD-DROP BONITA 70.00 LOAD==14.37(2.92) 0 # # # (39) BUS FAULT 34240 "GLASS" # 1 34240 34237 "1" 0 # LINE from GLASS 70.00 to CANANDGA 70.00 1 34240 34256 "1" 0 # LINE from GLASS 70.00 to BORDEN 70.00 4 34240 0 "1 " 0 # LOAD-DROP GLASS 70.00 LOAD==9.05(4.89) 0 # # # (40) BUS FAULT 34252 "MADERA" # 1 34252 34254 "1" 0 # LINE from MADERA 70.00 to TRIGO 70.00 1 34252 34256 "1" 0 # LINE from MADERA 70.00 to BORDEN 70.00 1 34252 34256 "2" 0 # LINE from MADERA 70.00 to BORDEN 70.00 4 34252 0 "1 " 0 # LOAD-DROP MADERA 70.00 LOAD==17.99(3.65) 4 34252 0 "2 " 0 # LOAD-DROP MADERA 70.00 LOAD==23.16(4.71) 6 34252 0 "v" 0 # drop Madera 70 kV shunt Caps 0 # # # (41) BUS FAULT 34256 "BORDEN" # 1 34256 34252 "1" 0 # LINE from BORDEN 70.00 to MADERA 70.00 1 34256 34252 "2" 0 # LINE from BORDEN 70.00 to MADERA 70.00 1 34256 34240 "1" 0 # LINE from BORDEN 70.00 to GLASS 70.00 1 34256 34262 "1" 0 # LINE from BORDEN 70.00 to CASSIDY 70.00 2 34256 30805 "1" 0 # TRAN from BORDEN 70.00 to BORDEN 230.00 2 34256 30805 "2" 0 # TRAN from BORDEN 70.00 to BORDEN 230.00 0 # # # (42) BUS FAULT 34268 "MENDOTA" # 1 34268 34267 "1" 0 # LINE from MENDOTA 70.00 to TOMATAK 70.00 1 34268 34269 "1" 0 # LINE from MENDOTA 70.00 to BIOMSJCT 70.00 2 34268 34156 "1" 0 # TRAN from MENDOTA 70.00 to MENDOTA 115.00 0 # # # 2013 sprpk category c contingency list # Fresno Zone 314 # # # (43) C5 DCTL OUTAGE # Gates - Schindler and Gates - Huron #1 70 kV Lines 1 34558 34560 "1 " 0 # line from HURON 70.00 BRKR to (2) CALFLAX 70.00 1 34560 34562 "1 " 0 # line from CALFLAX 70.00 (2) to BRKR SCHLNDLR 70.00 4 34560 0 "1 " 0 # LOAD-DROP CALFLAX 70.00 LOAD==6.53(1.33) 1 34552 34558 "2 " 0 # Must include Gates - Huron #2 in this outage

Page 270: To determine the system impacts caused by the Project

A-249 GWF Henrietta SISAppendix A

# 1 34552 34558 "1 " 0 # line from GATES 70.00 BRKR to BRKR HURON 70.00 0 # # # (44) C5 DCTL OUTAGE # Barton - Sanger and Manchester - Sanger 115 kV Lines 1 34359 34361 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR AIRWAYS 115.00 1 34359 34408 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR BARTON 115.00 1 34359 34366 "1 " 0 # line from AIRWAYJ2 115.00 (3) to BRKR SANGER 115.00 # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (45) C5 DCTL OUTAGE # Herndon - Barton and Herndon - Manchester 115 kV Lines 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 # 1 34410 34412 "1 " 0 # line from MANCHSTR 115.00 BRKR to BRKR HERNDON 115.00 0 # # # (46) C5 DCTL OUTAGE # Herndon - Barton and Manchester - Sanger 115 kV Lines 1 34408 34412 "1 " 0 # line from BARTON 115.00 BRKR to BRKR HERNDON 115.00 # 1 34357 34361 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR AIRWAYS 115.00 1 34357 34368 "1 " 0 # line from AIRWAYJ1 115.00 (3) to (2) LASPALMS 115.00 1 34357 34410 "1 " 0 # line from AIRWAYJ1 115.00 (3) to BRKR MANCHSTR 115.00 1 34368 34366 "1 " 0 # line from LASPALMS 115.00 (2) to BRKR SANGER 115.00 4 34368 0 "1 " 0 # LOAD-DROP LASPALMS 115.00 LOAD==13.90(11.89) 0 # # # (47) C5 DCTL OUTAGE # Herndon - Bullard #1 and #2 115 kV Lines 1 34411 34416 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR BULLARD 115.00 1 34411 34412 "1 " 0 # line from PNDLJ1 115.00 (2) to BRKR HERNDON 115.00 # 1 34409 34413 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR PNEDLE 115.00 1 34409 34416 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR BULLARD 115.00 1 34409 34412 "1 " 0 # line from PNDLJ2 115.00 (3) to BRKR HERNDON 115.00 4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25) 4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 1 34411 34413 "1 " 1 # Switches in Pindale CB#12 to transfer load

Page 271: To determine the system impacts caused by the Project

A-250 GWF Henrietta SISAppendix A

4 34413 0 "**" 1 # Restore load at Pindale 0 # # # (48) C5 DCTL OUTAGE # Kerckhoff - Clovis - Sanger #1 and #2 115 kV Lines 1 34358 34360 "1 " 0 # line from KERCKHF2 115.00 BRKR to (3) WWARD JT 115.00 1 34360 34414 "1 " 0 # line from WWARD JT 115.00 (3) to BRKR WOODWARD 115.00 1 34360 34363 "1 " 0 # line from WWARD JT 115.00 (3) to (3) CLOVISJ1 115.00 1 34363 34362 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR CLOVIS-1 115.00 1 34363 34366 "1 " 0 # line from CLOVISJ1 115.00 (3) to BRKR SANGER 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36) 4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34362 0 "**" 1 # Restore Load at Clovis 1 # 1 34364 34365 "1 " 0 # line from CLOVIS-2 115.00 BRKR to (3) CLOVISJ2 115.00 1 34365 34358 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR KERCKHF2 115.00 1 34365 34366 "1 " 0 # line from CLOVISJ2 115.00 (3) to BRKR SANGER 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 1 34362 34364 "1 " 1 # Switches in Clovis SW 387 to transfer load 4 34364 0 "**" 1 # Restore Load at Clovis 2 0 # # # (49) C5 DCTL OUTAGE # Kingburg - Corcoran #1 and #2 115 kV Lines 1 34418 34420 "1 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 # 1 34418 34420 "2 " 0 # line from KINGSBRG 115.00 BRKR to BRKR CORCORAN 115.00 0 # # # (50) C5 DCTL OUTAGE # Kings River - Sanger - Reedley and Balch - Sanger 115 kV Lines 1 34366 34389 "1 " 0 # line from SANGER 115.00 BRKR to (3) RAINBWTP 115.00 1 34389 34388 "1 " 0 # line from RAINBWTP 115.00 (3) to (1) RAINBW 115.00 1 34389 34394 "1 " 0 # line from RAINBWTP 115.00 (3) to (3) PIEDRA 1 115.00 1 34394 34380 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR REEDLEY 115.00 1 34394 34400 "1 " 0 # line from PIEDRA 1 115.00 (3) to BRKR KNGSRVR1 115.00 4 34388 0 "1 " 0 # LOAD-DROP RAINBW 115.00 LOAD==16.20(3.29) # 1 34366 34396 "1 " 0 # line from SANGER 115.00 BRKR to (2) PIEDRA 2 115.00 1 34396 34398 "1 " 0 # line from PIEDRA 2 115.00 (2) to (2) BALCH 115.00 2 34398 34624 "1 " 0 # TRAN from BALCH 115.00 (2) to (1) BALCH 1 13.20 4 34624 0 "1 " 0 # LOAD-DROP BALCH 1 13.20 LOAD==0.26(0.00) 3 34624 0 "1 " 0 # GEN-DROP BALCH 1 13.20 GEN==27.00(8.33) 0 # # # (51) C5 DCTL OUTAGE # McCall - Kingsburg #1 and #2 115 kV Lines

Page 272: To determine the system impacts caused by the Project

A-251 GWF Henrietta SISAppendix A

1 34370 34385 "1 " 0 # line from MC CALL 115.00 BRKR to (3) KINGS J1 115.00 1 34385 34417 "1 " 0 # line from KINGS J1 115.00 (3) to (2) KINGS J2 115.00 1 34385 34425 "1 " 0 # line from KINGS J1 115.00 (3) to (3) KCOGNJCT 115.00 1 34417 34418 "1 " 0 # line from KINGS J2 115.00 (2) to BRKR KINGSBRG 115.00 1 34425 34387 "1 " 0 # line from KCOGNJCT 115.00 (3) to (1) SUNMAID 115.00 1 34425 34427 "1 " 0 # line from KCOGNJCT 115.00 (3) to (2) GRDNGLS2 115.00 1 34427 34386 "1 " 0 # line from GRDNGLS2 115.00 (2) to (2) KNGSCOGN 115.00 2 34386 34642 "1 " 0 # TRAN from KNGSCOGN 115.00 (2) to BRKR KINGSBUR 9.11 4 34387 0 "1 " 0 # LOAD-DROP SUNMAID 115.00 LOAD==3.40(3.28) 3 34642 0 "1 " 0 # GEN-DROP KINGSBUR 9.11 GEN==34.00(17.30) # 1 34418 34423 "1 " 0 # line from KINGSBRG 115.00 BRKR to (3) GAURD J1 115.00 1 34423 34370 "1 " 0 # line from GAURD J1 115.00 (3) to BRKR MC CALL 115.00 1 34423 34421 "1 " 0 # line from GAURD J1 115.00 (3) to (2) GAURD J2 115.00 1 34421 34424 "1 " 0 # line from GAURD J2 115.00 (2) to (1) GRDN GLS 115.00 4 34424 0 "1 " 0 # LOAD-DROP GRDN GLS 115.00 LOAD==3.50(1.15) 4 34418 0 "3 " 0 # Kingsburg Bank #3 will also be dropped on this outage 0 # # # (52) C5 DCTL OUTAGE # McCall - Sanger #1 and #2 115 kV Lines 1 34366 34370 "1 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 # 1 34366 34370 "2 " 0 # line from SANGER 115.00 BRKR to BRKR MC CALL 115.00 0 # # # (53) C5 DCTL OUTAGE # McCall - West Fresno and California Ave. - West Fresno 115 kV Lines 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 # 1 34402 34404 "1 " 0 # line from CAL AVE 115.00 BRKR to BRKR WST FRSO 115.00 0 # # # (54) C5 DCTL OUTAGE # McCall - West Fresno and California Ave. - McCall 115 kV Lines 1 34404 34370 "1 " 0 # line from WST FRSO 115.00 BRKR to BRKR MC CALL 115.00 # 1 34390 34370 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR MC CALL 115.00 1 34390 34402 "1 " 0 # line from DANISHCM 115.00 (2) to BRKR CAL AVE 115.00 4 34390 0 "1 " 0 # LOAD-DROP DANISHCM 115.00 LOAD==4.10(3.51) 0 # # # (55) C5 DCTL OUTAGE # Gates - Gregg and Gates - McCall 230 kV Lines 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00

Page 273: To determine the system impacts caused by the Project

A-252 GWF Henrietta SISAppendix A

1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) # 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 # # # (56) C5 DCTL OUTAGE # Panoche - Kearney and Gates - Gregg 230 kV Lines 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 0 # # # (57) C5 DCTL OUTAGE # Panoche - Kearney and Panoche - Helm 230 kV Lines 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 1 30790 30873 "1 " 0 # line from PANOCHE 230.00 BRKR to BRKR HELM 230.00 0 # # # (58) C5 DCTL OUTAGE # Panoche - Kearney and Helm - McCall 230 kV Lines 1 30790 30825 "1 " 0 # line from PANOCHE 230.00 BRKR to (2) MCMULLN1 230.00 1 30825 30830 "1 " 0 # line from MCMULLN1 230.00 (2) to BRKR KEARNEY 230.00 4 30825 0 "1 " 0 # LOAD-DROP MCMULLN1 230.00 LOAD==20.57(4.18) # 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 0 # # # (59) C5 DCTL OUTAGE # Helm - McCall and Gates - McCall 230 kV Lines 1 30873 30875 "1 " 0 # line from HELM 230.00 BRKR to BRKR MC CALL 230.00 # 1 30875 30880 "1 " 0 # line from MC CALL 230.00 BRKR to (2) HENTAP2 230.00 1 30880 30900 "1 " 0 # line from HENTAP2 230.00 (2) to BRKR GATES 230.00 0 #

Page 274: To determine the system impacts caused by the Project

A-253 GWF Henrietta SISAppendix A

# # (60) C5 DCTL OUTAGE # Helms - Gregg #1 and #2 230 kV Lines 1 30810 30820 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34600 0 "**" 0 # Drop unit#1 with a loss Helm - Gregg #1 line # 1 30810 30820 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HELMS PP 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Helm - Gregg #2 line 0 # # # (61) C5 DCTL OUTAGE # Gregg - Herndon #1 and #2 230 kV Lines 1 30810 30835 "1 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #1 line # 1 30810 30835 "2 " 0 # line from GREGG 230.00 BRKR to BRKR HERNDON 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Herndon #2 line 0 # # # (62) C5 DCTL OUTAGE # Herndon - Kearney and Herndon - Ashlan 230 kV Lines 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 0 # # # (63) C5 DCTL OUTAGE # Herndon - Kearney and Gates - Gregg 230 kV Lines 1 30830 30835 "1 " 0 # line from KEARNEY 230.00 BRKR to BRKR HERNDON 230.00 # 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) 0 # # # (64) C5 DCTL OUTAGE # Gates - Gregg and Gregg - Ashlan 230 kV Lines 1 30810 30879 "1 " 0 # line from GREGG 230.00 BRKR to (3) HENTAP1 230.00 1 30879 30881 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR HENRIETA 230.00 1 30879 30900 "1 " 0 # line from HENTAP1 230.00 (3) to BRKR GATES 230.00 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Henrietta Tap 1 line 1 30880 30881 "1 " 1 # Henrietta flip flop (Henrietta CB 222) #

Page 275: To determine the system impacts caused by the Project

A-254 GWF Henrietta SISAppendix A

1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (65) C5 DCTL OUTAGE # Herndon - Ashlan and Gregg - Ashlan 230 kV Lines 1 30835 30840 "1 " 0 # line from HERNDON 230.00 BRKR to (3) FGRDN T1 230.00 1 30840 30841 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR FIGRDN 1 230.00 1 30840 30850 "1 " 0 # line from FGRDN T1 230.00 (3) to BRKR ASHLAN 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30841 0 "**" 1 # Restore Load at Figarden 1 # 1 30810 30845 "1 " 0 # line from GREGG 230.00 BRKR to (3) FGRDN T2 230.00 1 30845 30846 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR FIGRDN 2 230.00 1 30845 30850 "1 " 0 # line from FGRDN T2 230.00 (3) to BRKR ASHLAN 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 3 34604 0 "**" 0 # Drop unit#3 with a loss Gregg - Figarden line 1 30841 30846 "1 " 1 # Switches in Figarden SW 286 to transfer load 4 30846 0 "**" 1 # Restore Load at Figarden 2 0 # # # (66) C5 DCTL OUTAGE # Haas - McCall and Balch - McCall 230 kV Lines 1 30855 30860 "1 " 0 # line from HAAS 230.00 (2) to (3) BALCH3TP 230.00 2 30855 34610 "1 " 0 # TRAN from HAAS 230.00 (2) to (1) HAAS 13.80 1 30860 30875 "1 " 0 # line from BALCH3TP 230.00 (3) to BRKR MC CALL 230.00 2 30860 34614 "1 " 0 # TRAN from BALCH3TP 230.00 (3) to (1) BLCH 2-3 13.80 3 34610 0 "1 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34610 0 "2 " 0 # GEN-DROP HAAS 13.80 GEN==70.00(10.21) 3 34614 0 "1 " 0 # GEN-DROP BLCH 2-3 13.80 GEN==50.00(7.64) # 1 30865 30870 "1 " 0 # line from BALCH 230.00 (2) to (3) PINE FLT 230.00 2 30865 34612 "1 " 0 # TRAN from BALCH 230.00 (2) to (1) BLCH 2-2 13.80 1 30870 30875 "1 " 0 # line from PINE FLT 230.00 (3) to BRKR MC CALL 230.00 2 30870 38720 "1 " 0 # TRAN from PINE FLT 230.00 (3) to (1) PINE FLT 13.80 3 34612 0 "1 " 0 # GEN-DROP BLCH 2-2 13.80 GEN==50.00(0.66) 3 38720 0 "1 " 0 # GEN-DROP PINE FLT 13.80 GEN==57.00(23.30) 0 # # # (67) C5 DCTL OUTAGE # Morro Bay - Gates and Templeton - Gates 230 kV Lines

Page 276: To determine the system impacts caused by the Project

A-255 GWF Henrietta SISAppendix A

1 30900 30915 "1 " 0 # line from GATES 230.00 BRKR to BRKR MORROBAY 230.00 # 1 30900 30905 "1 " 0 # line from GATES 230.00 BRKR to BRKR TEMPLETN 230.00 0 # # # (68) C5 DCTL OUTAGE # Gates - Midway and Gates - Arco 230 kV Lines 1 30900 30970 "1 " 0 # line from GATES 230.00 BRKR to BRKR MIDWAY 230.00 # 1 30900 30935 "1 " 0 # line from GATES 230.00 BRKR to BRKR ARCO 230.00 0 # # # (69) BUS FAULT 30820 "HELMS PP" # 1 30820 30810 "1" 0 # LINE from HELMS PP 230.00 to GREGG 230.00 1 30820 30810 "2" 0 # LINE from HELMS PP 230.00 to GREGG 230.00 2 30820 34600 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 1 18.00 2 30820 34602 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 2 18.00 2 30820 34604 "1" 0 # TRAN from HELMS PP 230.00 to HELMS 3 18.00 0 # # # (70) BUS FAULT 30830 "KEARNEY" # 1 30830 30825 "1" 0 # LINE from KEARNEY 230.00 to MCMULLN1 230.00 1 30830 30835 "1" 0 # LINE from KEARNEY 230.00 to HERNDON 230.00 2 30830 34480 "2" 0 # TRAN from KEARNEY 230.00 to KEARNEY 70.00 0 # # # (71) BUS FAULT 30835 "HERNDON" 230 kV Bus Section 1 # 1 30835 30810 "1" 0 # LINE from HERNDON 230.00 to GREGG 230.00 1 30835 30830 "1" 0 # LINE from HERNDON 230.00 to KEARNEY 230.00 2 30835 30882 "1" 0 # TRAN from HERNDON 230.00 to HERNDN1M 115.00 0 # # # (72) BUS FAULT 30835 "HERNDON" 230 kV Bus Section 2 # 1 30835 30810 "2" 0 # LINE from HERNDON 230.00 to GREGG 230.00 1 30835 30840 "1" 0 # LINE from HERNDON 230.00 to FGRDN T1 230.00 2 30835 30883 "2" 0 # TRAN from HERNDON 230.00 to HERNDN2M 115.00 0 # # # (73) BUS FAULT 30841 "FIGRDN 1" # 1 30841 30840 "1" 0 # LINE from FIGRDN 1 230.00 to FGRDN T1 230.00 1 30841 30846 "1" 0 # LINE from FIGRDN 1 230.00 to FIGRDN 2 230.00 4 30841 0 "1 " 0 # LOAD-DROP FIGRDN 1 230.00 LOAD==73.45(14.92) 0 # # # (74) BUS FAULT 30846 "FIGRDN 2" # 1 30846 30841 "1" 0 # LINE from FIGRDN 2 230.00 to FIGRDN 1 230.00 1 30846 30845 "1" 0 # LINE from FIGRDN 2 230.00 to FGRDN T2 230.00 4 30846 0 "1 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==52.57(10.67) 4 30846 0 "2 " 0 # LOAD-DROP FIGRDN 2 230.00 LOAD==36.77(7.47) 0 # # # (75) BUS FAULT 30850 "ASHLAN"

Page 277: To determine the system impacts caused by the Project

A-256 GWF Henrietta SISAppendix A

# 1 30850 30840 "1" 0 # LINE from ASHLAN 230.00 to FGRDN T1 230.00 1 30850 30845 "1" 0 # LINE from ASHLAN 230.00 to FGRDN T2 230.00 4 30850 0 "1 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==69.20(13.40) 4 30850 0 "2 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==64.54(12.84) 4 30850 0 "3 " 0 # LOAD-DROP ASHLAN 230.00 LOAD==65.51(12.49) 0 # # # (76) BUS FAULT 30873 "HELM" # 1 30873 30790 "1" 0 # LINE from HELM 230.00 to PANOCHE 230.00 1 30873 30875 "1" 0 # LINE from HELM 230.00 to MC CALL 230.00 2 30873 34474 "1" 0 # TRAN from HELM 230.00 to HELM 70.00 0 # # # (77) BUS FAULT 30874 "P0615STN" # 1 30874 30875 "1" 0 # LINE from P0615STN 230.00 to MC CALL 230.00 1 30874 30875 "2" 0 # LINE from P0615STN 230.00 to MC CALL 230.00 2 30874 34685 "1" 0 # TRAN from P0615STN 230.00 to P0615CT1 16.50 2 30874 34686 "1" 0 # TRAN from P0615STN 230.00 to P0615CT2 16.50 2 30874 34687 "1" 0 # TRAN from P0615STN 230.00 to P0615STG 16.50 0 # # # (78) BUS FAULT 30875 "MC CALL" 230 kV Bus Section 1 # 1 30875 30870 "1" 0 # LINE from MC CALL 230.00 to PINE FLT 230.00 1 30875 30874 "1" 0 # LINE from MC CALL 230.00 to P0615STN 230.00 1 30875 30880 "1" 0 # LINE from MC CALL 230.00 to HENTAP2 230.00 2 30875 30877 "2" 0 # TRAN from MC CALL 230.00 to MCCALL2M 115.00 6 30875 0 "v" 0 # SVD from MC CALL 230.00 0 # # # (79) BUS FAULT 30875 "MC CALL" 230 kV Bus Section 2 # 1 30875 30873 "1" 0 # LINE from MC CALL 230.00 to HELM 230.00 1 30875 30860 "1" 0 # LINE from MC CALL 230.00 to BALCH3TP 230.00 1 30875 30874 "2" 0 # LINE from MC CALL 230.00 to P0615STN 230.00 2 30875 30876 "1" 0 # TRAN from MC CALL 230.00 to MCCALL1M 115.00 2 30875 30878 "3" 0 # TRAN from MC CALL 230.00 to MCCALL3M 115.00 0 # # # (80) BUS FAULT 30881 "HENRIETA" # 1 30881 30879 "1" 0 # LINE from HENRIETA 230.00 to HENTAP1 230.00 1 30881 30880 "1" 0 # LINE from HENRIETA 230.00 to HENTAP2 230.00 2 30881 34430 "3" 0 # TRAN from HENRIETA 230.00 to HENRETTA 115.00 2 30881 34540 "2" 0 # TRAN from HENRIETA 230.00 to HENRITTA 70.00 2 30881 34540 "4" 0 # TRAN from HENRIETA 230.00 to HENRITTA 70.00 0 # # # (81) BUS FAULT 30900 "GATES" 230 kV Bus Section 1D # 1 30900 30790 "1" 0 # LINE from GATES 230.00 to PANOCHE 230.00 1 30900 30905 "1" 0 # LINE from GATES 230.00 to TEMPLETN 230.00 2 30900 30901 "1" 0 # TRAN from GATES 230.00 to GATES 1M 230.00 6 30900 0 "v" 0 # SVD from GATES 230.00 0 # # # (82) BUS FAULT 30900 "GATES" 230 kV Bus Section 2D # 1 30900 30790 "2" 0 # LINE from GATES 230.00 to PANOCHE 230.00 1 30900 30915 "1" 0 # LINE from GATES 230.00 to MORROBAY 230.00

Page 278: To determine the system impacts caused by the Project

A-257 GWF Henrietta SISAppendix A

0 # # # (83) BUS FAULT 30900 "GATES" 230 kV Bus Section 1E # 1 30900 30879 "1" 0 # LINE from GATES 230.00 to HENTAP1 230.00 1 30900 30935 "1" 0 # LINE from GATES 230.00 to ARCO 230.00 0 # # # (84) BUS FAULT 30900 "GATES" 230 kV Bus Section 2E # 1 30900 30880 "1" 0 # LINE from GATES 230.00 to HENTAP2 230.00 1 30900 30970 "1" 0 # LINE from GATES 230.00 to MIDWAY 230.00 0 # # # (85) BUS FAULT 34356 "KERCKHF1" # 1 34356 34123 "2" 0 # LINE from KERCKHF1 115.00 to K1-JCT 115.00 1 34356 34358 "1" 0 # LINE from KERCKHF1 115.00 to KERCKHF2 115.00 2 34356 34344 "1" 0 # TRAN from KERCKHF1 115.00 to KERCKHOF 6.60 0 # # # (86) BUS FAULT 34358 "KERCKHF2" # 1 34358 34123 "2" 0 # LINE from KERCKHF2 115.00 to K1-JCT 115.00 1 34358 34356 "1" 0 # LINE from KERCKHF2 115.00 to KERCKHF1 115.00 1 34358 34360 "1" 0 # LINE from KERCKHF2 115.00 to WWARD JT 115.00 1 34358 34365 "1" 0 # LINE from KERCKHF2 115.00 to CLOVISJ2 115.00 2 34358 34308 "1" 0 # TRAN from KERCKHF2 115.00 to KERCKHOF 13.80 0 # # # (87) BUS FAULT 34361 "AIRWAYS" # 1 34361 34357 "1" 0 # LINE from AIRWAYS 115.00 to AIRWAYJ1 115.00 1 34361 34359 "1" 0 # LINE from AIRWAYS 115.00 to AIRWAYJ2 115.00 4 34361 0 "1 " 0 # LOAD-DROP AIRWAYS 115.00 LOAD==38.39(7.43) 4 34361 0 "2 " 0 # LOAD-DROP AIRWAYS 115.00 LOAD==12.60(2.56) 0 # # # (88) BUS FAULT 34362 "CLOVIS-1" # 1 34362 34363 "1" 0 # LINE from CLOVIS-1 115.00 to CLOVISJ1 115.00 1 34362 34364 "1" 0 # LINE from CLOVIS-1 115.00 to CLOVIS-2 115.00 4 34362 0 "1 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==51.01(10.36) 4 34362 0 "2 " 0 # LOAD-DROP CLOVIS-1 115.00 LOAD==50.20(10.20) 0 # # # (89) BUS FAULT 34364 "CLOVIS-2" # 1 34364 34362 "1" 0 # LINE from CLOVIS-2 115.00 to CLOVIS-1 115.00 1 34364 34365 "1" 0 # LINE from CLOVIS-2 115.00 to CLOVISJ2 115.00 4 34364 0 "3 " 0 # LOAD-DROP CLOVIS-2 115.00 LOAD==44.76(9.09) 0 # # # (90) BUS FAULT 34366 "SANGER" # 1 34366 34363 "1" 0 # LINE from SANGER 115.00 to CLOVISJ1 115.00 1 34366 34365 "1" 0 # LINE from SANGER 115.00 to CLOVISJ2 115.00 1 34366 34359 "1" 0 # LINE from SANGER 115.00 to AIRWAYJ2 115.00 1 34366 34368 "1" 0 # LINE from SANGER 115.00 to LASPALMS 115.00 1 34366 34370 "1" 0 # LINE from SANGER 115.00 to MC CALL 115.00 1 34366 34370 "2" 0 # LINE from SANGER 115.00 to MC CALL 115.00 1 34366 34370 "3" 0 # LINE from SANGER 115.00 to MC CALL 115.00

Page 279: To determine the system impacts caused by the Project

A-258 GWF Henrietta SISAppendix A

1 34366 34372 "1" 0 # LINE from SANGER 115.00 to MALAGA 115.00 1 34366 34389 "1" 0 # LINE from SANGER 115.00 to RAINBWTP 115.00 1 34366 34396 "1" 0 # LINE from SANGER 115.00 to PIEDRA 2 115.00 1 34366 34488 "1" 0 # LINE from SANGER 115.00 to SANGER 70.00 2 34366 34590 "1" 0 # TRAN from SANGER 115.00 to SANGR3T 115.00 4 34366 0 "1 " 0 # LOAD-DROP SANGER 115.00 LOAD==24.26(4.93) 0 # # # (91) BUS FAULT 34372 "MALAGA" # 1 34372 34366 "1" 0 # LINE from MALAGA 115.00 to SANGER 115.00 1 34372 34376 "1" 0 # LINE from MALAGA 115.00 to PPG 115.00 1 34372 34379 "1" 0 # LINE from MALAGA 115.00 to MALAGATP 115.00 1 34372 34381 "1" 0 # LINE from MALAGA 115.00 to KRCDP 115.00 4 34372 0 "1 " 0 # LOAD-DROP MALAGA 115.00 LOAD==25.25(5.12) 4 34372 0 "2 " 0 # LOAD-DROP MALAGA 115.00 LOAD==22.76(4.62) 4 34372 0 "3 " 0 # LOAD-DROP MALAGA 115.00 LOAD==23.13(4.69) 0 # # # (92) BUS FAULT 34378 "GATES" # 2 34378 30901 "1" 0 # TRAN from GATES 115.00 to GATES 1M 230.00 2 34378 34552 "2" 0 # TRAN from GATES 115.00 to GATES 70.00 4 34378 0 "3 " 0 # LOAD-DROP GATES 115.00 LOAD==19.45(3.95) 0 # # # (93) BUS FAULT 34380 "REEDLEY" # 1 34380 34384 "1" 0 # LINE from REEDLEY 115.00 to GERAWAN 115.00 1 34380 34394 "1" 0 # LINE from REEDLEY 115.00 to PIEDRA 1 115.00 2 34380 34492 "1" 0 # TRAN from REEDLEY 115.00 to REEDLEY 70.00 2 34380 34492 "2" 0 # TRAN from REEDLEY 115.00 to REEDLEY 70.00 4 34380 0 "3 " 0 # LOAD-DROP REEDLEY 115.00 LOAD==26.17(5.31) 0 # # # (94) BUS FAULT 34382 "WAHTOKE" # 1 34382 34370 "1" 0 # LINE from WAHTOKE 115.00 to MC CALL 115.00 1 34382 34384 "1" 0 # LINE from WAHTOKE 115.00 to GERAWAN 115.00 4 34382 0 "2 " 0 # LOAD-DROP WAHTOKE 115.00 LOAD==30.36(6.17) 4 34382 0 "3 " 0 # LOAD-DROP WAHTOKE 115.00 LOAD==20.84(4.24) 0 # # # (95) BUS FAULT 34400 "KNGSRVR1" # 1 34400 34394 "1" 0 # LINE from KNGSRVR1 115.00 to PIEDRA 1 115.00 2 34400 34616 "1" 0 # TRAN from KNGSRVR1 115.00 to KINGSRIV 13.80 0 # # # (96) BUS FAULT 34402 "CAL AVE" # 1 34402 34390 "1" 0 # LINE from CAL AVE 115.00 to DANISHCM 115.00 1 34402 34404 "1" 0 # LINE from CAL AVE 115.00 to WST FRSO 115.00 4 34402 0 "1 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==28.95(5.87) 4 34402 0 "2 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==31.26(6.35) 4 34402 0 "3 " 0 # LOAD-DROP CAL AVE 115.00 LOAD==24.42(4.96) 0 # # # (97) BUS FAULT 34404 "WST FRSO" # 1 34404 34370 "1" 0 # LINE from WST FRSO 115.00 to MC CALL 115.00 1 34404 34402 "1" 0 # LINE from WST FRSO 115.00 to CAL AVE 115.00 4 34404 0 "1 " 0 # LOAD-DROP WST FRSO 115.00 LOAD==37.55(7.63)

Page 280: To determine the system impacts caused by the Project

A-259 GWF Henrietta SISAppendix A

4 34404 0 "2 " 0 # LOAD-DROP WST FRSO 115.00 LOAD==39.04(7.93) 0 # # # (98) BUS FAULT 34408 "BARTON" # 1 34408 34359 "1" 0 # LINE from BARTON 115.00 to AIRWAYJ2 115.00 1 34408 34412 "1" 0 # LINE from BARTON 115.00 to HERNDON 115.00 4 34408 0 "1 " 0 # LOAD-DROP BARTON 115.00 LOAD==43.27(8.79) 4 34408 0 "2 " 0 # LOAD-DROP BARTON 115.00 LOAD==37.15(7.54) 4 34408 0 "3 " 0 # LOAD-DROP BARTON 115.00 LOAD==26.96(5.47) 0 # # # (99) BUS FAULT 34410 "MANCHSTR" # 1 34410 34357 "1" 0 # LINE from MANCHSTR 115.00 to AIRWAYJ1 115.00 1 34410 34412 "1" 0 # LINE from MANCHSTR 115.00 to HERNDON 115.00 4 34410 0 "1 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==25.28(5.13) 4 34410 0 "2 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==25.47(5.18) 4 34410 0 "3 " 0 # LOAD-DROP MANCHSTR 115.00 LOAD==36.21(7.36) 0 # # # (100) BUS FAULT 34412 "HERNDON" 115 kV Bus Section 1 # 1 34412 34408 "1" 0 # LINE from HERNDON 115.00 to BARTON 115.00 1 34412 34409 "1" 0 # LINE from HERNDON 115.00 to PNDLJ2 115.00 2 34412 30882 "1" 0 # TRAN from HERNDON 115.00 to HERNDN1M 115.00 0 # # # (101) BUS FAULT 34412 "HERNDON" 115 kV Bus Section 2 # 1 34412 34410 "1" 0 # LINE from HERNDON 115.00 to MANCHSTR 115.00 1 34412 34411 "1" 0 # LINE from HERNDON 115.00 to PNDLJ1 115.00 1 34412 34422 "1" 0 # LINE from HERNDON 115.00 to CHLDHOSP 115.00 0 # # # (102) BUS FAULT 34413 "PNEDLE" # 1 34413 34409 "1" 0 # LINE from PNEDLE 115.00 to PNDLJ2 115.00 1 34413 34411 "1" 0 # LINE from PNEDLE 115.00 to PNDLJ1 115.00 4 34413 0 "2 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==30.74(6.25) 4 34413 0 "3 " 0 # LOAD-DROP PNEDLE 115.00 LOAD==40.42(8.20) 0 # # # (103) BUS FAULT 34414 "WOODWARD" # 1 34414 34360 "1" 0 # LINE from WOODWARD 115.00 to WWARD JT 115.00 1 34414 34422 "1" 0 # LINE from WOODWARD 115.00 to CHLDHOSP 115.00 4 34414 0 "1 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==42.25(8.58) 4 34414 0 "2 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==52.69(10.70) 4 34414 0 "3 " 0 # LOAD-DROP WOODWARD 115.00 LOAD==44.09(8.95) 0 # # # (104) BUS FAULT 34416 "BULLARD" # 1 34416 34409 "1" 0 # LINE from BULLARD 115.00 to PNDLJ2 115.00 1 34416 34411 "1" 0 # LINE from BULLARD 115.00 to PNDLJ1 115.00 4 34416 0 "1 " 0 # LOAD-DROP BULLARD 115.00 LOAD==44.87(9.11) 4 34416 0 "2 " 0 # LOAD-DROP BULLARD 115.00 LOAD==44.65(9.07) 4 34416 0 "3 " 0 # LOAD-DROP BULLARD 115.00 LOAD==42.52(8.63) 0 # # # (105) BUS FAULT 34418 "KINGSBRG" 115 kV Bus Section D

Page 281: To determine the system impacts caused by the Project

A-260 GWF Henrietta SISAppendix A

# 1 34418 34417 "1" 0 # LINE from KINGSBRG 115.00 to KINGS J2 115.00 1 34418 34428 "1" 0 # LINE from KINGSBRG 115.00 to CONTADNA 115.00 1 34418 34420 "2" 0 # LINE from KINGSBRG 115.00 to CORCORAN 115.00 4 34418 0 "1 " 0 # LOAD-DROP KINGSBRG 115.00 LOAD==39.24(7.96) 0 # # # (106) BUS FAULT 34418 "KINGSBRG" 115 kV Bus Section E # 1 34418 34420 "1" 0 # LINE from KINGSBRG 115.00 to CORCORAN 115.00 1 34418 34423 "1" 0 # LINE from KINGSBRG 115.00 to GAURD J1 115.00 2 34418 34576 "2" 0 # TRAN from KINGSBRG 115.00 to KNGLOBUS 70.00 4 34418 0 "3 " 0 # LOAD-DROP KINGSBRG 115.00 LOAD==24.32(4.94) 0 # # # (107) BUS FAULT 34420 "CORCORAN" # 1 34420 34391 "1" 0 # LINE from CORCORAN 115.00 to QUEBECTP 115.00 1 34420 34418 "1" 0 # LINE from CORCORAN 115.00 to KINGSBRG 115.00 1 34420 34418 "2" 0 # LINE from CORCORAN 115.00 to KINGSBRG 115.00 2 34420 34528 "2" 0 # TRAN from CORCORAN 115.00 to CORCORAN 70.00 4 34420 0 "3 " 0 # LOAD-DROP CORCORAN 115.00 LOAD==16.21(3.30) 4 34420 0 "4 " 0 # LOAD-DROP CORCORAN 115.00 LOAD==17.81(3.61) 0 # # # (108) BUS FAULT 34426 "ALPAUGH" # 1 34426 34391 "1" 0 # LINE from ALPAUGH 115.00 to QUEBECTP 115.00 1 34426 34700 "1" 0 # LINE from ALPAUGH 115.00 to SMYRNA 115.00 4 34426 0 "2 " 0 # LOAD-DROP ALPAUGH 115.00 LOAD==5.62(1.14) 0 # # # (109) BUS FAULT 34430 "HENRETTA" # 1 34430 34521 "1" 0 # LINE from HENRETTA 115.00 to LEPRNOFD 115.00 2 34430 30881 "3" 0 # TRAN from HENRETTA 115.00 to HENRIETA 230.00 0 # # # (110) BUS FAULT 34452 "WISHON" # 1 34452 34260 "1" 0 # LINE from WISHON 70.00 to SJNO2 70.00 1 34452 34491 "1" 0 # LINE from WISHON 70.00 to AUBRYTP 70.00 2 34452 34658 "1" 0 # TRAN from WISHON 70.00 to WISHON 2.30 0 # # # (111) BUS FAULT 34460 "GUERNSEY" # 1 34460 34462 "1" 0 # LINE from GUERNSEY 70.00 to GUR3TPT 70.00 1 34460 34528 "1" 0 # LINE from GUERNSEY 70.00 to CORCORAN 70.00 4 34460 0 "1 " 0 # LOAD-DROP GUERNSEY 70.00 LOAD==10.51(2.13) 0 # # # (112) BUS FAULT 34464 "COPPRMNE" # 1 34464 34454 "1" 0 # LINE from COPPRMNE 70.00 to RIVERROC 70.00 1 34464 34478 "1" 0 # LINE from COPPRMNE 70.00 to TVY VLLY 70.00 1 34464 34638 "1" 0 # LINE from COPPRMNE 70.00 to FRANTDM 70.00 1 34464 34491 "1" 0 # LINE from COPPRMNE 70.00 to AUBRYTP 70.00 4 34464 0 "1 " 0 # LOAD-DROP COPPRMNE 70.00 LOAD==22.96(4.67) 0 # # # (113) BUS FAULT 34466 "BIOLA"

Page 282: To determine the system impacts caused by the Project

A-261 GWF Henrietta SISAppendix A

# 1 34466 34264 "1" 0 # LINE from BIOLA 70.00 to EL PECO 70.00 1 34466 34482 "1" 0 # LINE from BIOLA 70.00 to OLDKERN 70.00 4 34466 0 "1 " 0 # LOAD-DROP BIOLA 70.00 LOAD==21.80(4.43) 0 # # # (114) BUS FAULT 34472 "SAN JOQN" # 1 34472 34471 "1" 0 # LINE from SAN JOQN 70.00 to SNJQJCT 70.00 1 34472 34473 "1" 0 # LINE from SAN JOQN 70.00 to SNJQTP 70.00 4 34472 0 "1 " 0 # LOAD-DROP SAN JOQN 70.00 LOAD==6.44(1.31) 4 34472 0 "2 " 0 # LOAD-DROP SAN JOQN 70.00 LOAD==3.92(0.79) 0 # # # (115) BUS FAULT 34474 "HELM" # 1 34474 34471 "1" 0 # LINE from HELM 70.00 to SNJQJCT 70.00 1 34474 34473 "1" 0 # LINE from HELM 70.00 to SNJQTP 70.00 1 34474 34556 "1" 0 # LINE from HELM 70.00 to STRD JCT 70.00 1 34474 34564 "1" 0 # LINE from HELM 70.00 to STROUD 70.00 2 34474 30873 "1" 0 # TRAN from HELM 70.00 to HELM 230.00 0 # # # (116) BUS FAULT 34478 "TVY VLLY" # 1 34478 34464 "1" 0 # LINE from TVY VLLY 70.00 to COPPRMNE 70.00 1 34478 34492 "1" 0 # LINE from TVY VLLY 70.00 to REEDLEY 70.00 4 34478 0 "1 " 0 # LOAD-DROP TVY VLLY 70.00 LOAD==10.27(2.09) 0 # # # (117) BUS FAULT 34480 "KEARNEY" # 1 34480 34481 "1" 0 # LINE from KEARNEY 70.00 to FRWWTAP 70.00 1 34480 34482 "1" 0 # LINE from KEARNEY 70.00 to OLDKERN 70.00 1 34480 34512 "1" 0 # LINE from KEARNEY 70.00 to CARUTHRS 70.00 2 34480 30830 "2" 0 # TRAN from KEARNEY 70.00 to KEARNEY 230.00 0 # # # (118) BUS FAULT 34484 "KERMAN" # 1 34484 34475 "1" 0 # LINE from KERMAN 70.00 to AGRCJCT 70.00 1 34484 34481 "1" 0 # LINE from KERMAN 70.00 to FRWWTAP 70.00 4 34484 0 "1 " 0 # LOAD-DROP KERMAN 70.00 LOAD==19.44(3.95) 4 34484 0 "2 " 0 # LOAD-DROP KERMAN 70.00 LOAD==11.78(2.39) 0 # # # (119) BUS FAULT 34486 "CALIFRNV" # 1 34486 34488 "1" 0 # LINE from CALIFRNV 70.00 to SANGER 70.00 1 34486 34488 "2" 0 # LINE from CALIFRNV 70.00 to SANGER 70.00 0 # # # (120) BUS FAULT 34488 "SANGER" # 1 34488 34486 "1" 0 # LINE from SANGER 70.00 to CALIFRNV 70.00 1 34488 34486 "2" 0 # LINE from SANGER 70.00 to CALIFRNV 70.00 1 34488 34366 "1" 0 # LINE from SANGER 70.00 to SANGER 115.00 1 34488 34487 "1" 0 # LINE from SANGER 70.00 to SNGRJCT 70.00 2 34488 34590 "1" 0 # TRAN from SANGER 70.00 to SANGR3T 115.00 0 # # # (121) BUS FAULT 34492 "REEDLEY"

Page 283: To determine the system impacts caused by the Project

A-262 GWF Henrietta SISAppendix A

# 1 34492 34478 "1" 0 # LINE from REEDLEY 70.00 to TVY VLLY 70.00 1 34492 34490 "1" 0 # LINE from REEDLEY 70.00 to PARLIER 70.00 1 34492 34497 "1" 0 # LINE from REEDLEY 70.00 to DNUBAJCT 70.00 1 34492 34526 "1" 0 # LINE from REEDLEY 70.00 to ORSI JCT 70.00 2 34492 34380 "1" 0 # TRAN from REEDLEY 70.00 to REEDLEY 115.00 2 34492 34380 "2" 0 # TRAN from REEDLEY 70.00 to REEDLEY 115.00 4 34492 0 "1 " 0 # LOAD-DROP REEDLEY 70.00 LOAD==17.42(3.54) 0 # # # (122) BUS FAULT 34500 "DINUBA" # 1 34500 34496 "1" 0 # LINE from DINUBA 70.00 to STCRRL J 70.00 1 34500 34497 "1" 0 # LINE from DINUBA 70.00 to DNUBAJCT 70.00 4 34500 0 "1 " 0 # LOAD-DROP DINUBA 70.00 LOAD==19.23(3.91) 4 34500 0 "2 " 0 # LOAD-DROP DINUBA 70.00 LOAD==9.33(1.90) 0 # # # (123) BUS FAULT 34512 "CARUTHRS" # 1 34512 34480 "1" 0 # LINE from CARUTHRS 70.00 to KEARNEY 70.00 1 34512 34510 "1" 0 # LINE from CARUTHRS 70.00 to CMDN JCT 70.00 4 34512 0 "1 " 0 # LOAD-DROP CARUTHRS 70.00 LOAD==19.63(3.98) 0 # # # (124) BUS FAULT 34518 "LEMOORE" # 1 34518 34520 "1" 0 # LINE from LEMOORE 70.00 to LPRNO TP 70.00 1 34518 34522 "1" 0 # LINE from LEMOORE 70.00 to HNFRD SW 70.00 4 34518 0 "1 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==18.86(3.83) 4 34518 0 "2 " 0 # LOAD-DROP LEMOORE 70.00 LOAD==32.81(6.66) 0 # # # (125) BUS FAULT 34528 "CORCORAN" # 1 34528 34460 "1" 0 # LINE from CORCORAN 70.00 to GUERNSEY 70.00 1 34528 34530 "1" 0 # LINE from CORCORAN 70.00 to BSWLL TP 70.00 2 34528 34420 "2" 0 # TRAN from CORCORAN 70.00 to CORCORAN 115.00 0 # # # (126) BUS FAULT 34540 "HENRITTA" # 1 34540 34514 "1" 0 # LINE from HENRITTA 70.00 to MUSLSLGH 70.00 1 34540 34520 "1" 0 # LINE from HENRITTA 70.00 to LPRNO TP 70.00 1 34540 34537 "1" 0 # LINE from HENRITTA 70.00 to GWF_HENR 70.00 1 34540 34542 "1" 0 # LINE from HENRITTA 70.00 to JCBSCRNR 70.00 1 34540 34544 "1" 0 # LINE from HENRITTA 70.00 to TLRE LKE 70.00 2 34540 30881 "2" 0 # TRAN from HENRITTA 70.00 to HENRIETA 230.00 2 34540 30881 "4" 0 # TRAN from HENRITTA 70.00 to HENRIETA 230.00 4 34540 0 "1 " 0 # LOAD-DROP HENRITTA 70.00 LOAD==8.20(1.67) 0 # # # (127) BUS FAULT 34544 "TLRE LKE" # 1 34544 34540 "1" 0 # LINE from TLRE LKE 70.00 to HENRITTA 70.00 1 34544 34550 "1" 0 # LINE from TLRE LKE 70.00 to CHEVPLIN 70.00 1 34544 34580 "1" 0 # LINE from TLRE LKE 70.00 to BDGR HLL 70.00 4 34544 0 "1 " 0 # LOAD-DROP TLRE LKE 70.00 LOAD==6.79(1.38) 0 # # # (128) BUS FAULT 34552 "GATES" # 1 34552 34548 "1" 0 # LINE from GATES 70.00 to KETTLEMN 70.00

Page 284: To determine the system impacts caused by the Project

A-263 GWF Henrietta SISAppendix A

1 34552 34184 "1" 0 # LINE from GATES 70.00 to GATS2_TP 70.00 1 34552 34558 "1" 0 # LINE from GATES 70.00 to HURON 70.00 1 34552 34558 "2" 0 # LINE from GATES 70.00 to HURON 70.00 1 34552 34578 "1" 0 # LINE from GATES 70.00 to JACALITO 70.00 2 34552 34378 "2" 0 # TRAN from GATES 70.00 to GATES 115.00 0 # # # (129) BUS FAULT 34558 "HURON" # 1 34558 34552 "1" 0 # LINE from HURON 70.00 to GATES 70.00 1 34558 34552 "2" 0 # LINE from HURON 70.00 to GATES 70.00 1 34558 34560 "1" 0 # LINE from HURON 70.00 to CALFLAX 70.00 4 34558 34552 "1 " 1 # LOAD-TRANSFER HURON 70.00 TO GATES 70.00 LOAD==15.33(3.11) 0 # # # (130) BUS FAULT 34562 "SCHLNDLR" # 1 34562 34556 "1" 0 # LINE from SCHLNDLR 70.00 to STRD JCT 70.00 1 34562 34560 "1" 0 # LINE from SCHLNDLR 70.00 to CALFLAX 70.00 1 34562 34566 "1" 0 # LINE from SCHLNDLR 70.00 to PLSNTVLY 70.00 2 34562 34354 "1" 0 # TRAN from SCHLNDLR 70.00 to SCHINDLR 115.00 4 34562 0 "1 " 0 # LOAD-DROP SCHLNDLR 70.00 LOAD==9.59(1.95) 0 # # # (131) BUS FAULT 34564 "STROUD" # 1 34564 34556 "1" 0 # LINE from STROUD 70.00 to STRD JCT 70.00 1 34564 34474 "1" 0 # LINE from STROUD 70.00 to HELM 70.00 4 34564 0 "1 " 0 # LOAD-DROP STROUD 70.00 LOAD==13.09(2.66) 0 # # # (132) BUS FAULT 34570 "COLNGA 2" # 1 34570 34184 "1" 0 # LINE from COLNGA 2 70.00 to GATS2_TP 70.00 1 34570 34566 "1" 0 # LINE from COLNGA 2 70.00 to PLSNTVLY 70.00 1 34570 34572 "1" 0 # LINE from COLNGA 2 70.00 to TORNADO 70.00 2 34570 34652 "1" 0 # TRAN from COLNGA 2 70.00 to CHV.COAL 9.11 4 34570 0 "1 " 0 # LOAD-DROP COLNGA 2 70.00 LOAD==8.23(1.67) 0 # # # (133) BUS FAULT 34574 "COLNGA 1" # 1 34574 34572 "1" 0 # LINE from COLNGA 1 70.00 to TORNADO 70.00 1 34574 34578 "1" 0 # LINE from COLNGA 1 70.00 to JACALITO 70.00 1 34574 36354 "1" 0 # LINE from COLNGA 1 70.00 to SAN MIGL 70.00 4 34574 0 "1 " 0 # LOAD-DROP COLNGA 1 70.00 LOAD==9.34(1.90) 4 34574 0 "2 " 0 # LOAD-DROP COLNGA 1 70.00 LOAD==9.99(2.03) 0 # # # (134) BUS FAULT 34576 "KNGLOBUS" # 1 34576 34456 "1" 0 # LINE from KNGLOBUS 70.00 to HRDWK TP 70.00 1 34576 34508 "1" 0 # LINE from KNGLOBUS 70.00 to CAMDEN 70.00 2 34576 34418 "2" 0 # TRAN from KNGLOBUS 70.00 to KINGSBRG 115.00 0 # # -1 # EOF

Page 285: To determine the system impacts caused by the Project

Appendix B Governor Power Flow Switching Sequences

Table of Content Category B Contingencies Gates - Los Banos #1 500-kV Single Line Outage .................................................................................... 1 Gates - Los Banos #3 500-kV Single Line Outage .................................................................................... 2 Gates - Midway 500-kV Single Line Outage............................................................................................ 3 Los Banos - Gates #1 500-kV Single Line Outage .................................................................................... 4 Los Banos - Gates #3 500-kV Single Line Outage .................................................................................... 5 Diablo - Midway 500-kV Single Line Outage .......................................................................................... 6 Tracy - Los Banos 500-kV Single Line Outage......................................................................................... 7 Tesla - Los Banos 500-kV Single Line Outage.......................................................................................... 8 Los Banos - Midway 500-kV Single Line Outage .................................................................................... 9 Moss Landing - Los Banos 500-kV Single Line Outage........................................................................ 10 Category C Contingencies Diablo - Midway #2 & #3 500-kV Double Line Outage ........................................................................ 11 Los Banos - Tesla & Los Banos – Tracy 500-kV Double Line Outage (North-to-South Flow) .............................................................................................................................. 12 Los Banos - Midway and Los Banos – Gates 500-kV Double Line Outage (North-to-South Flow) .............................................................................................................................. 13 Midway - Gates and Midway - Los Banos Double Line Outage (North-to-South Flow) .............................................................................................................................. 15 Los Banos - Tesla & Los Banos – Tracy 500-kV Double Line Outage (South-to-North Flow) .............................................................................................................................. 16 Los Banos - Midway and Los Banos – Gates 500-kV Double Line Outage (South-to-North Flow) .............................................................................................................................. 20 Midway - Gates and Midway - Los Banos Double Line Outage (South-to-North Flow) .............................................................................................................................. 24

Page 286: To determine the system impacts caused by the Project

B-1 GWF Henrietta SISAppendix B

Gates - Los Banos #1 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "GATES " 500. "LOSBANOS" 500. "1 " *

Page 287: To determine the system impacts caused by the Project

B-2 GWF Henrietta SISAppendix B

Gates - Los Banos #3 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "GATES " 500. "LOSBANOS" 500. "3 " *

Page 288: To determine the system impacts caused by the Project

B-3 GWF Henrietta SISAppendix B

Gates - Midway 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "GATES " 500. "MIDWAY " 500. "1 " *

Page 289: To determine the system impacts caused by the Project

B-4 GWF Henrietta SISAppendix B

Los Banos - Gates #1 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "LOSBANOS " 500. "GATES" 500. "1 " *

Page 290: To determine the system impacts caused by the Project

B-5 GWF Henrietta SISAppendix B

Los Banos - Gates #3 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "LOSBANOS " 500. "GATES" 500. "3 " *

Page 291: To determine the system impacts caused by the Project

B-6 GWF Henrietta SISAppendix B

Diablo - Midway 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "DIABLO " 500. "MIDWAY" 500. "2 " *

Page 292: To determine the system impacts caused by the Project

B-7 GWF Henrietta SISAppendix B

Tracy - Los Banos 500-kV Single Line Outage * * CC cards for post-transient only * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "TRACY " 500.0 "LOSBANOS" 500.0 "1 " * * THE 454 MVAr TABLE MT MSC TAKES MORE THAN ONE SECOND * TO INSERT AND IS NOT USUALLY MODELED FOR STABILITY * CC MSD 17.5 "TABLE MT" 500.0 "v " "C" 4.54 *

Page 293: To determine the system impacts caused by the Project

B-8 GWF Henrietta SISAppendix B

Tesla - Los Banos 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "TESLA " 500.0 "LOSBANOS" 500.0 "1 " * * THE 454 MVAr TABLE MT MSC TAKES MORE THAN ONE SECOND * TO INSERT AND IS NOT USUALLY MODELED FOR STABILITY * CC MSD 17.5 "TABLE MT" 500.0 "v " "C" 4.54 * *

Page 294: To determine the system impacts caused by the Project

B-9 GWF Henrietta SISAppendix B

Los Banos - Midway 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "LOSBANOS " 500. "MIDWAY" 500. "1 "

Page 295: To determine the system impacts caused by the Project

B-10 GWF Henrietta SISAppendix B

Moss Landing - Los Banos 500-kV Single Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "MOSSLAND" 500.0 "LOSBANOS" 500.0 "1 " *

Page 296: To determine the system impacts caused by the Project

B-11 GWF Henrietta SISAppendix B

Diablo - Midway #2 & #3 500-kV Double Line Outage * * CC cards for post-transient only * * Readjust Northwest SVC's CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * DL 4.0 "DIABLO " 500. "MIDWAY" 500. "2 " DL 4.0 "DIABLO " 500. "MIDWAY" 500. "3 " * * THE 454 MVAr TABLE MT MSC TAKES MORE THAN ONE SECOND * TO INSERT AND IS NOT USUALLY MODELED FOR STABILITY * CC MSD 90.0 "TABLE MT" 500.0 "v " "C" 4.54 CC MLS 90.0 "TABLE MT" 500.0 "TESLA " 500.0 "1 " 1 "f" D

Page 297: To determine the system impacts caused by the Project

B-12 GWF Henrietta SISAppendix B

Los Banos - Tesla & Los Banos – Tracy 500-kV Double Line Outage (North-to-South Flow) * * CC cards for post-transient only * * Readjust Northwest SVC's * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * * Trip Los Banos North lines * DL 4.0 "TESLA " 500. "LOSBANOS " 500. "1 " DL 4.0 "TRACY " 500. "LOSBANOS " 500. "1 " *

Page 298: To determine the system impacts caused by the Project

B-13 GWF Henrietta SISAppendix B

Los Banos - Midway and Los Banos – Gates 500-kV Double Line Outage (North-to-South Flow) * * Readjust Northwest SVC's * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * CC RG 0.0 "DALLES 3" 13.8 "1 " 180. -270. * * Fault bus at Los Banos FB 0.0 "LOSBANOS" 500. * * Clear fault at Los Banos CFB 4.0 "LOSBANOS " 500. * * Trip Los Banos South lines DL 4.0 "LOSBANOS " 500. "GATES " 500. "1 " DL 4.0 "LOSBANOS " 500. "MIDWAY" 500. "1 " * * Drop CDWR/Feather River Generation TG 13.0 "HYATT 1 " 12.5 "**" TG 13.0 "HYATT 2 " 12.5 "**" TG 13.0 "HYATT 3 " 12.5 "**" TG 13.0 "HYATT 4 " 12.5 "**" TG 13.0 "HYATT 5 " 12.5 "**" TG 13.0 "HYATT 6 " 12.5 "**" TG 13.0 "THERMLT1" 13.8 "**" TG 13.0 "THERMLT2" 13.8 "**" TG 13.0 "THERMLT3" 13.8 "**" TG 13.0 "THERMLT4" 13.8 "**" * * * Drop CDWR/Feather River Generation TG 15.0 "CRBOU2-3" 11.5 "**" * * Drop CDWR Pumps TG 15.0 "DELTA A " 13.2 "**" TG 15.0 "DELTA B " 13.2 "**" TG 15.0 "DELTA C " 13.2 "**" TG 15.0 "DELTA D " 13.2 "**" TG 15.0 "DELTA E " 13.2 "**" * TG 15.0 "WINDGAP1 " 13.2 "**" TG 15.0 "WINDGAP2 " 13.2 "**" TG 15.0 "WINDGAP3 " 13.2 "**" TG 15.0 "WINDGAP4 " 13.2 "**" * TG 15.0 "BUENAVS1 " 13.2 "**" TG 15.0 "BUENAVS2 " 13.2 "**" * TG 15.0 "WHLR RD1" 13.2 "**" TG 15.0 "WHLR RD2" 13.2 "**" * TG 18.0 "DOS AMG1" 13.2 "**" TG 18.0 "DOS AMG2" 13.2 "**" * TG 18.0 "PEARBMAP" 13.2 "**" TG 18.0 "PEARBMBP" 13.2 "**" * * INSERT 200 MVAr CAPACITORS AT OLINDA 500 kV * REMOVE 380 MVAr REACTORS AT OLINDA 500 kV * CC MSD 18.0 "OLINDA " 500.0 "v " "C" 2.00 CC MLS 17.5 "OLINDA " 500.0 "MAXWELL " 500.0 "1 " 1 "t" "D" CC MLS 17.5 "CAPTJACK" 500.0 "OLINDA " 500.0 "1 " 3 "f" "D" * Switch on Table Mountain Shunt cap * 2 x 217 caps (91 Mvar reactor modeled separately)

Page 299: To determine the system impacts caused by the Project

B-14 GWF Henrietta SISAppendix B

* CC MSD 90.0 "TABLE MT" 500.0 "v " "C" 4.54 CC MLS 90.0 "TABLE MT" 500.0 "TESLA " 500.0 "1 " 1 "f" D * * Bypass capacitors * FC 300. "OLINDA " 500. "MAXWELL " 500. "1 " 3 FC 300. "TABLE MT" 500. "TESLA " 500. "1 " 1 FC 300. "TABLE MT" 500. "VACA-DIX" 500. "1 " 1 FC 300. "TABLE MT" 500. "VACA-DIX" 500. "1 " 3 * * Drop PGE Generation TG 310. "BUTTVLLY" 13.8 "**" * * Edmonston & Pear Blossom CDWR pumps have a 5 minutes ramp down time, not modeled for transient * CC TG 9999.0 "EDMON1AP " 14.4 "**" CC TG 9999.0 "EDMON2AP " 14.4 "**" CC TG 9999.0 "EDMON3AP " 14.4 "**" CC TG 9999.0 "EDMON4AP " 14.4 "**" CC TG 9999.0 "EDMON5AP " 14.4 "**" CC TG 9999.0 "EDMON6AP " 14.4 "**" CC TG 9999.0 "EDMON7AP " 14.4 "**" CC TG 9999.0 "EDMON8AP " 14.4 "**" *

Page 300: To determine the system impacts caused by the Project

B-15 GWF Henrietta SISAppendix B

Midway - Gates and Midway - Los Banos Double Line Outage (North-to-South Flow) * * CC cards for post-transient only * * Readjust Northwest SVC's * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * CC RG 0.0 "DALLES 3" 13.8 "1 " 180. -270. * * Fault bus at Midway FB 0.0 "MIDWAY " 500. * * Clear fault at Midway CFB 4.0 "MIDWAY " 500. * * Trip Midway North lines DL 4.0 "MIDWAY " 500. "GATES " 500. "1 " DL 4.0 "MIDWAY " 500. "LOSBANOS" 500. "1 " * * Drop CDWR Pumps TG 15.0 "DELTA A " 13.2 "**" TG 15.0 "DELTA B " 13.2 "**" TG 15.0 "DELTA C " 13.2 "**" TG 15.0 "DELTA D " 13.2 "**" TG 15.0 "DELTA E " 13.2 "**" * TG 15.0 "WINDGAP1 " 13.2 "**" TG 15.0 "WINDGAP2 " 13.2 "**" TG 15.0 "WINDGAP3 " 13.2 "**" TG 15.0 "WINDGAP4 " 13.2 "**" * TG 15.0 "BUENAVS1 " 13.2 "**" TG 15.0 "BUENAVS2 " 13.2 "**" * TG 15.0 "WHLR RD1" 13.2 "**" TG 15.0 "WHLR RD2" 13.2 "**"

Page 301: To determine the system impacts caused by the Project

B-16 GWF Henrietta SISAppendix B

Los Banos - Tesla & Los Banos – Tracy 500-kV Double Line Outage (South-to-North Flow) * * CC cards for post-transient only * * Readjust Northwest SVC's * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * * FAULT ON LOS BANOS 500 KV BUS * FB 0.0 "LOSBANOS" 500.0 * * * CLEAR FAULT AND OPEN LINES - 4 CYCLES * CFB 4.0 "LOS BANOS" 500.0 DL 4.0 "TESLA" 500.0 "LOSBANOS" 500.0 "1 " DL 4.0 "TRACY" 500.0 "LOSBANOS" 500.0 "1 " * * * CDWR Pumps * TG 22.0 "DOS AMG1" 13.20 "1 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DOS AMG1" 13.20 "2 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DOS AMG1" 13.20 "3 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DELTA E " 13.20 "11" */gen drop is -1.00 MW 0.00 MVAr * Gen Group 1 * MBL 22.0 "SUNST " 230.00 "SG" "D" */ 11.79 MW 4.28 MVAr TG 22.0 "SUNSET G" 13.80 "1 " */gen drop is 75.00 MW 26.70 MVAr TG 22.0 "SUNSET G" 13.80 "2 " */gen drop is 75.00 MW 26.70 MVAr TG 22.0 "SUNSET G" 13.80 "3 " */gen drop is 75.00 MW 26.70 MVAr MBL 22.0 "DEXEL + " 13.80 "SG" "D" */ 0.32 MW 0.08 MVAr TG 22.0 "DEXEL + " 13.80 "1 " */gen drop is 28.60 MW 6.42 MVAr TG 22.0 "DOUBLE C" 13.80 "1 " */gen drop is 42.50 MW 5.96 MVAr MBL 22.0 "KERNFRNT" 9.11 "SG" "D" */ 0.70 MW 0.34 MVAr TG 22.0 "KERNFRNT" 9.11 "1 " */gen drop is 47.70 MW 16.00 MVAr TG 22.0 "HISIERRA" 13.80 "1 " */gen drop is 47.90 MW 6.87 MVAr TG 22.0 "BADGERCK" 13.80 "1 " */gen drop is 46.30 MW 6.59 MVAr TG 22.0 "TEXCO_NM" 9.11 "1 " */gen drop is 5.40 MW 5.50 MVAr TG 22.0 "TEXCO_NM" 9.11 "2 " */gen drop is 2.70 MW 5.00 MVAr MBL 22.0 "CHV-CYMR" 9.11 "SG" "D" */ 0.41 MW 0.10 MVAr TG 22.0 "CHV-CYMR" 9.11 "1 " */gen drop is 13.50 MW -1.24 MVAr TG 22.0 "MIDSUN +" 13.80 "1 " */gen drop is 24.50 MW 15.20 MVAr * Load Group 1 * MBL 22.0 "EL CRRTO" 115.00 "1 " "D" */ 20.73 MW 4.72 MVAr MBL 22.0 "EL CRRTO" 115.00 "2 " "D" */ 25.79 MW 5.88 MVAr MBL 22.0 "EL CRRTO" 115.00 "4 " "D" */ 45.19 MW 10.30 MVAr MBL 22.0 "CORDELIA" 115.00 "2 " "D" */ 15.10 MW 0.68 MVAr MBL 22.0 "VACAVLL2" 115.00 "2 " "D" */ 38.30 MW 1.71 MVAr MBL 22.0 "VACAVLL2" 115.00 "3 " "D" */ 37.61 MW 1.68 MVAr MBL 22.0 "HALE " 115.00 "1 " "D" */ 2.39 MW 1.42 MVAr MBL 22.0 "VACAVLL1" 115.00 "1 " "D" */ 26.13 MW 1.17 MVAr MBL 22.0 "JAMESON " 115.00 "1 " "D" */ 33.35 MW 1.49 MVAr MBL 22.0 "SCHMLBCH" 115.00 "1 " "D" */ 10.08 MW 6.77 MVAr MBL 22.0 "SUISUN " 115.00 "1 " "D" */ 25.41 MW 1.14 MVAr MBL 22.0 "SUISUN " 115.00 "2 " "D" */ 27.60 MW 1.23 MVAr MBL 22.0 "SUISUN " 115.00 "3 " "D" */ 22.48 MW 1.01 MVAr TG 22.0 "CTY FAIR" 9.11 "1 " */gen drop is 0.80 MW 0.07 MVAr TG 22.0 "CTY FAIR" 9.11 "2 " */gen drop is 1.50 MW 0.13 MVAr MBL 22.0 "FREMNT " 115.00 "1 " "D" */ 29.09 MW 6.63 MVAr MBL 22.0 "FREMNT " 115.00 "2 " "D" */ 17.77 MW 4.05 MVAr MBL 22.0 "FREMNT " 115.00 "3 " "D" */ 25.24 MW 5.75 MVAr MBL 22.0 "JARVIS " 115.00 "1 " "D" */ 16.23 MW 3.70 MVAr MBL 22.0 "JARVIS " 115.00 "2 " "D" */ 24.39 MW 5.56 MVAr MBL 22.0 "JARVIS " 115.00 "3 " "D" */ 31.32 MW 7.14 MVAr MBL 22.0 "JV BART " 115.00 "1 " "D" */ 7.10 MW 1.44 MVAr

Page 302: To determine the system impacts caused by the Project

B-17 GWF Henrietta SISAppendix B

MBL 22.0 "CRYOGEN " 115.00 "1 " "D" */ 0.17 MW 0.04 MVAr MBL 22.0 "WHISMAN " 115.00 "1 " "D" */ 19.38 MW 4.42 MVAr MBL 22.0 "WHISMAN " 115.00 "2 " "D" */ 20.85 MW 4.75 MVAr MBL 22.0 "WHISMAN " 115.00 "3 " "D" */ 17.65 MW 4.02 MVAr MBL 22.0 "MT VIEW " 115.00 "1 " "D" */ 26.30 MW 6.00 MVAr MBL 22.0 "MT VIEW " 115.00 "2 " "D" */ 27.95 MW 6.37 MVAr MBL 22.0 "MT VIEW " 115.00 "3 " "D" */ 25.27 MW 5.76 MVAr MBL 22.0 "STELLING" 115.00 "1 " "D" */ 26.98 MW 6.15 MVAr MBL 22.0 "STELLING" 115.00 "2 " "D" */ 27.53 MW 6.27 MVAr MBL 22.0 "STELLING" 115.00 "3 " "D" */ 28.16 MW 6.42 MVAr MBL 22.0 "WOLFE " 115.00 "1 " "D" */ 21.97 MW 5.01 MVAr MBL 22.0 "WOLFE " 115.00 "2 " "D" */ 27.70 MW 6.31 MVAr MBL 22.0 "WOLFE " 115.00 "3 " "D" */ 14.27 MW 3.25 MVAr MBL 22.0 "MOFT.FLD" 115.00 "1 " "D" */ 4.46 MW 1.12 MVAr MBL 22.0 "LOCKHD 1" 115.00 "1 " "D" */ 18.14 MW 15.03 MVAr MBL 22.0 "LAWRENCE" 115.00 "1 " "D" */ 43.73 MW 9.97 MVAr MBL 22.0 "LAWRENCE" 115.00 "2 " "D" */ 17.31 MW 3.94 MVAr MBL 22.0 "LAWRENCE" 115.00 "3 " "D" */ 30.52 MW 6.96 MVAr MBL 22.0 "PHILLIPS" 115.00 "1 " "D" */ 1.74 MW 0.00 MVAr MBL 22.0 "LOCKHD 2" 115.00 "1 " "D" */ 16.06 MW 12.46 MVAr MBL 22.0 "LOCKHD 2" 115.00 "2 " "D" */ 8.08 MW 1.84 MVAr MBL 22.0 "A.M.D " 115.00 "1 " "D" */ 7.85 MW 5.48 MVAr MBL 22.0 "BRITTN " 115.00 "1 " "D" */ 24.09 MW 5.49 MVAr MBL 22.0 "BRITTN " 115.00 "2 " "D" */ 41.32 MW 9.42 MVAr MBL 22.0 "BRITTN " 115.00 "3 " "D" */ 20.35 MW 4.64 MVAr MBL 22.0 "APP MAT " 115.00 "1 " "D" */ 12.24 MW 3.07 MVAr * Gen Group 2 * MBL 22.0 "ELKHIL1G" 18.00 "ss" "D" */ 6.70 MW 1.68 MVAr TG 22.0 "ELKHIL1G" 18.00 "1 " */gen drop is 185.00 MW 61.32 MVAr MBL 22.0 "ELKHIL2G" 18.00 "ss" "D" */ 6.70 MW 1.68 MVAr TG 22.0 "ELKHIL2G" 18.00 "1 " */gen drop is 185.00 MW 61.32 MVAr TG 22.0 "ELKHIL3G" 18.00 "1 " */gen drop is 225.50 MW 65.14 MVAr * Load Group 2 * MBL 22.0 "MARTIN C" 115.00 "4 " "D" */ 31.16 MW 1.97 MVAr MBL 22.0 "MARTIN C" 115.00 "1 " "D" */ 31.16 MW 1.97 MVAr MBL 22.0 "CLAYTN " 115.00 "1 " "D" */ 24.22 MW 5.52 MVAr MBL 22.0 "CLAYTN " 115.00 "2 " "D" */ 38.65 MW 8.81 MVAr MBL 22.0 "CLAYTN " 115.00 "3 " "D" */ 41.05 MW 9.36 MVAr MBL 22.0 "CLAYTN " 115.00 "5 " "D" */ 8.55 MW 1.95 MVAr MBL 22.0 "MEDW LNE" 115.00 "1 " "D" */ 35.45 MW 8.08 MVAr MBL 22.0 "MEDW LNE" 115.00 "2 " "D" */ 42.22 MW 9.62 MVAr MBL 22.0 "MEDW LNE" 115.00 "3 " "D" */ 39.54 MW 9.01 MVAr MBL 22.0 "EBMUDGRY" 115.00 "1 " "D" */ 5.64 MW 1.85 MVAr MBL 22.0 "LAKEWD-C" 115.00 "5 " "D" */ 17.55 MW 4.00 MVAr MBL 22.0 "LAKEWD-C" 115.00 "6 " "D" */ 39.82 MW 9.08 MVAr MBL 22.0 "LAKEWD-M" 115.00 "1 " "D" */ 34.30 MW 7.82 MVAr MBL 22.0 "LAKEWD-M" 115.00 "2 " "D" */ 23.18 MW 5.28 MVAr MBL 22.0 "LAKEWD-M" 115.00 "4 " "D" */ 43.34 MW 9.88 MVAr MBL 22.0 "LAKEWD-M" 115.00 "LW" "D" */ 5.66 MW 1.15 MVAr MBL 22.0 "DALY CTY" 115.00 "1 " "D" */ 32.76 MW 7.47 MVAr MBL 22.0 "DALY CTY" 115.00 "2 " "D" */ 19.77 MW 4.50 MVAr MBL 22.0 "SERRMNTE" 115.00 "1 " "D" */ 7.44 MW 1.69 MVAr * Gen Group 3 * TG 22.0 "LAPLM_G1" 21.00 "1 " */gen drop is 230.00 MW 101.64 MVAr TG 22.0 "LAPLM_G2" 21.00 "1 " */gen drop is 230.00 MW 101.64 MVAr * Load Group 3 * MBL 22.0 "ELDORAD " 115.00 "1 " "D" */ 9.95 MW 0.45 MVAr MBL 22.0 "APPLE HL" 115.00 "1 " "D" */ 15.59 MW 0.70 MVAr MBL 22.0 "APPLE HL" 115.00 "2 " "D" */ 9.85 MW 0.44 MVAr MBL 22.0 "PLCRVLB2" 115.00 "2 " "D" */ 9.60 MW 0.43 MVAr MBL 22.0 "PLCRVLB3" 115.00 "3 " "D" */ 27.61 MW 1.24 MVAr MBL 22.0 "DMND SPR" 115.00 "1 " "D" */ 10.49 MW 0.47 MVAr MBL 22.0 "DMND SPR" 115.00 "2 " "D" */ 29.87 MW 1.33 MVAr MBL 22.0 "SHPRING " 115.00 "1 " "D" */ 20.82 MW 0.93 MVAr MBL 22.0 "SHPRING " 115.00 "2 " "D" */ 22.87 MW 1.02 MVAr #MBL 22.0 "CPM " 115.00 "1 " "D" */ 0.00 MW 0.00 MVAr: Load Status Off MBL 22.0 "SPICAMIN" 115.00 "1 " "D" */ 4.19 MW 3.70 MVAr TG 22.0 "CHILIBAR" 4.16 "1 " */gen drop is 5.50 MW 4.00 MVAr MBL 22.0 "ELDRADO1" 21.60 "SG" "D" */ 0.04 MW 0.01 MVAr

Page 303: To determine the system impacts caused by the Project

B-18 GWF Henrietta SISAppendix B

TG 22.0 "ELDRADO1" 21.60 "1 " */gen drop is 10.00 MW -0.51 MVAr MBL 22.0 "ELDRADO2" 21.60 "SG" "D" */ 0.04 MW 0.01 MVAr TG 22.0 "ELDRADO2" 21.60 "1 " */gen drop is 10.00 MW -0.51 MVAr MBL 22.0 "CLRKSVLE" 115.00 "1 " "D" */ 47.44 MW 2.13 MVAr MBL 22.0 "CLRKSVLE" 115.00 "2 " "D" */ 50.42 MW 2.25 MVAr MBL 22.0 "CLRKSVLE" 115.00 "3 " "D" */ 48.18 MW 2.16 MVAr MBL 22.0 "BAY MDWS" 115.00 "1 " "D" */ 27.94 MW 6.37 MVAr MBL 22.0 "BAY MDWS" 115.00 "2 " "D" */ 22.32 MW 5.09 MVAr MBL 22.0 "BAY MDWS" 115.00 "3 " "D" */ 13.20 MW 3.01 MVAr MBL 22.0 "BAY MDWS" 115.00 "5 " "D" */ 12.14 MW 2.77 MVAr * Gen Group 4 * TG 22.0 "TEXSUN1G" 18.00 "1 " */gen drop is 169.00 MW 13.12 MVAr TG 22.0 "TEXSUN2G" 18.00 "1 " */gen drop is 169.00 MW 13.12 MVAr TG 22.0 "TEXSUNST" 18.00 "1 " */gen drop is 222.00 MW 60.83 MVAr * Load Group 4 * MBL 22.0 "GUALALA " 60.00 "1 " "D" */ 2.86 MW 0.58 MVAr MBL 22.0 "GUALALA " 60.00 "2 " "D" */ 1.39 MW 0.28 MVAr MBL 22.0 "ANNAPOLS" 60.00 "1 " "D" */ 0.24 MW 0.05 MVAr MBL 22.0 "FORT RSS" 60.00 "1 " "D" */ 0.81 MW 0.17 MVAr MBL 22.0 "SLMN CRK" 60.00 "1 " "D" */ 3.15 MW 0.64 MVAr MBL 22.0 "MONTE RO" 60.00 "1 " "D" */ 3.72 MW 0.76 MVAr MBL 22.0 "MONTE RO" 60.00 "2 " "D" */ 4.77 MW 0.97 MVAr MBL 22.0 "WOHLER " 60.00 "1 " "D" */ 4.54 MW 1.93 MVAr MBL 22.0 "MIRABEL " 60.00 "1 " "D" */ 9.76 MW 1.98 MVAr MBL 22.0 "MOLINO " 60.00 "1 " "D" */ 7.01 MW 1.42 MVAr MBL 22.0 "MOLINO " 60.00 "2 " "D" */ 18.02 MW 3.66 MVAr MBL 22.0 "LAGUNA " 60.00 "1 " "D" */ 5.94 MW 1.49 MVAr MBL 22.0 "COTATI " 60.00 "1 " "D" */ 6.58 MW 1.34 MVAr MBL 22.0 "COTATI " 60.00 "2 " "D" */ 6.00 MW 1.22 MVAr TG 22.0 "SONMA LF" 9.11 "1 " */gen drop is 4.00 MW 0.00 MVAr MBL 22.0 "HIGHWAY " 115.00 "1 " "D" */ 17.39 MW 3.53 MVAr MBL 22.0 "HIGHWAY " 115.00 "2 " "D" */ 21.35 MW 4.33 MVAr MBL 22.0 "LS GLLNS" 115.00 "1 " "D" */ 12.37 MW 2.51 MVAr MBL 22.0 "LS GLLNS" 115.00 "2 " "D" */ 8.35 MW 1.70 MVAr MBL 22.0 "LS GLLNS" 115.00 "3 " "D" */ 9.33 MW 1.89 MVAr MBL 22.0 "SAN RAFL" 115.00 "1 " "D" */ 22.68 MW 4.61 MVAr MBL 22.0 "SAN RAFL" 115.00 "2 " "D" */ 21.62 MW 4.39 MVAr MBL 22.0 "SAN RAFL" 115.00 "3 " "D" */ 15.02 MW 3.05 MVAr MBL 22.0 "MEYERS " 115.00 "1 " "D" */ 0.24 MW 0.05 MVAr MBL 22.0 "CARQUINZ" 115.00 "1 " "D" */ 11.14 MW 2.26 MVAr MBL 22.0 "CARQUINZ" 115.00 "2 " "D" */ 9.48 MW 1.92 MVAr MBL 22.0 "MRE IS-Q" 115.00 "1 " "D" */ 4.25 MW 0.86 MVAr * Gen Group 5 * TG 22.0 "LAPLM_G3" 21.00 "1 " */gen drop is 229.00 MW 101.52 MVAr TG 22.0 "LAPLM_G4" 21.00 "1 " */gen drop is 230.00 MW 101.64 MVAr * Load Group 5 * MBL 22.0 "STAGG " 60.00 "2 " "D" */ 18.49 MW 0.82 MVAr MBL 22.0 "STAGG " 60.00 "3 " "D" */ 18.49 MW 0.82 MVAr MBL 22.0 "CNTRY CB" 60.00 "1 " "D" */ 5.82 MW 0.26 MVAr MBL 22.0 "CNTRY CB" 60.00 "2 " "D" */ 9.54 MW 0.42 MVAr MBL 22.0 "CNTRY CB" 60.00 "3 " "D" */ 10.58 MW 0.48 MVAr MBL 22.0 "CNTRY CB" 60.00 "4 " "D" */ 16.21 MW 0.72 MVAr MBL 22.0 "UOP " 60.00 "1 " "D" */ 5.99 MW 4.18 MVAr MBL 22.0 "HAMMER " 60.00 "1 " "D" */ 18.60 MW 0.83 MVAr MBL 22.0 "HAMMER " 60.00 "2 " "D" */ 17.83 MW 0.80 MVAr MBL 22.0 "HAMMER " 60.00 "3 " "D" */ 19.45 MW 0.87 MVAr MBL 22.0 "METTLER " 60.00 "3 " "D" */ 8.13 MW 0.37 MVAr MBL 22.0 "TERMNOUS" 60.00 "1 " "D" */ 4.69 MW 0.21 MVAr MBL 22.0 "SEBASTIA" 60.00 "1 " "D" */ 2.82 MW 2.11 MVAr MBL 22.0 "NEW HOPE" 60.00 "1 " "D" */ 2.65 MW 0.12 MVAr MBL 22.0 "MSHR 60V" 60.00 "1 " "D" */ 19.65 MW 0.88 MVAr MBL 22.0 "MSHR 60V" 60.00 "2 " "D" */ 32.80 MW 1.47 MVAr MBL 22.0 "STAGG_5 " 21.00 "5 " "D" */ 58.29 MW 2.61 MVAr MBL 22.0 "STAGG_6 " 21.00 "6 " "D" */ 51.06 MW 2.28 MVAr MBL 22.0 "CMP EVRS" 115.00 "1 " "D" */ 19.11 MW 3.88 MVAr MBL 22.0 "CMP EVRS" 115.00 "2 " "D" */ 18.61 MW 3.78 MVAr MBL 22.0 "PAUL SWT" 115.00 "1 " "D" */ 26.41 MW 5.36 MVAr MBL 22.0 "PAUL SWT" 115.00 "2 " "D" */ 20.10 MW 4.08 MVAr MBL 22.0 "PAUL SWT" 115.00 "3 " "D" */ 27.66 MW 5.62 MVAr MBL 22.0 "ROB ROY " 115.00 "1 " "D" */ 11.56 MW 2.35 MVAr

Page 304: To determine the system impacts caused by the Project

B-19 GWF Henrietta SISAppendix B

TG 22.0 "PSWTSTCM" 8.00 "1 " */gen drop is 0.00 MW 41.03 MVAr MBL 22.0 "CSTRVLLE" 115.00 "1 " "D" */ 16.97 MW 3.45 MVAr MBL 22.0 "DEL MNTE" 115.00 "1 " "D" */ 15.17 MW 3.08 MVAr MBL 22.0 "DEL MNTE" 115.00 "2 " "D" */ 23.32 MW 4.74 MVAr MBL 22.0 "FORT ORD" 60.00 "1 " "D" */ 25.76 MW 5.23 MVAr MBL 22.0 "MANZANTA" 60.00 "1 " "D" */ 0.99 MW 0.20 MVAr MBL 22.0 "MONTEREY" 60.00 "1 " "D" */ 3.65 MW 0.74 MVAr MBL 22.0 "NVY SCHL" 60.00 "1 " "D" */ 2.13 MW 1.09 MVAr MBL 22.0 "VIEJO " 60.00 "1 " "D" */ 11.58 MW 2.35 MVAr MBL 22.0 "VIEJO " 60.00 "2 " "D" */ 13.74 MW 2.79 MVAr MBL 22.0 "HATTON " 60.00 "1 " "D" */ 10.06 MW 2.04 MVAr MBL 22.0 "NAVY LAB" 60.00 "1 " "D" */ 1.64 MW 0.70 MVAr MBL 22.0 "BORONDA " 60.00 "1 " "D" */ 7.01 MW 1.42 MVAr MBL 22.0 "RSVTN RD" 60.00 "1 " "D" */ 8.85 MW 1.80 MVAr MBL 22.0 "LAURELES" 60.00 "1 " "D" */ 4.94 MW 1.00 MVAr MBL 22.0 "OTTER " 60.00 "1 " "D" */ 2.90 MW 0.59 MVAr * MSD 180.0 "GATES" 230.0 "v " "D" MSD 180.0 "LOSBANOS" 230.0 "v " "D"

Page 305: To determine the system impacts caused by the Project

B-20 GWF Henrietta SISAppendix B

Los Banos - Midway and Los Banos – Gates 500-kV Double Line Outage (South-to-North Flow) * * CC cards for post-transient only * * Readjust Northwest SVC's * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * * * Fault at Los Banos 500 kV bus * FB 0.0 "LOSBANOS" 500.0 * * CLEAR FAULT AND OPEN LINES - 4 CYCLES * CFB 4.0 "LOSBANOS" 500.0 DL 4.0 "LOSBANOS" 500. "MIDWAY " 500. "1 " DL 4.0 "LOSBANOS" 500. "GATES " 500. "1 " * * * CDWR Pumps * TG 13.0 "SANLUIS1" 13.80 "1" */ TG 13.0 "SANLUIS1" 13.80 "2" */ TG 13.0 "SANLUIS2" 13.80 "1" */ TG 13.0 "SANLUIS2" 13.80 "2" */ TG 13.0 "SANLUIS3" 13.80 "1" */ TG 13.0 "SANLUIS3" 13.80 "2" */ TG 13.0 "SANLUIS4" 13.80 "1" */ TG 13.0 "SANLUIS4" 13.80 "2" */ * * REMOVE OLINDA and TRACY Capacitors * MSD 13.0 "OLINDA " 500.0 "v" "D" MSD 13.0 "TRACY " 500.0 "v" "D" * MLS 13.0 "OLINDA " 500.0 "MAXWELL " 500.0 "1 " 1 "f" "R" MLS 13.0 "CAPTJACK" 500.0 "OLINDA " 500.0 "1 " 3 "t" "R" MLS 13.0 "MAXWELL " 500.0 "TRACY " 500.0 "1 " 3 "t" "R" * TG 14.0 "HELMS 1 " 18.00 "1" */gen drop is -310.00 MW 65.88 MVAr TG 14.0 "HELMS 2 " 18.00 "1" */gen drop is -310.00 MW 155.01 MVAr TG 14.0 "HELMS 3 " 18.00 "1" */gen drop is 310.25 MW 83.10 MVAr: Units Are Off-Line * * CDWR Pumps * TG 22.0 "DOS AMG1" 13.20 "1 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DOS AMG1" 13.20 "2 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DOS AMG1" 13.20 "3 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DELTA E " 13.20 "11" */gen drop is -1.00 MW 0.00 MVAr * Gen Group 1 * MBL 22.0 "SUNST " 230.00 "SG" "D" */ 9.59 MW 3.48 MVAr TG 22.0 "SUNSET G" 13.80 "1 " */gen drop is 75.00 MW -20.00 MVAr TG 22.0 "SUNSET G" 13.80 "2 " */gen drop is 75.00 MW -20.00 MVAr TG 22.0 "SUNSET G" 13.80 "3 " */gen drop is 75.00 MW -20.00 MVAr MBL 22.0 "KERNFRNT" 9.11 "SG" "D" */ 0.57 MW 0.28 MVAr TG 22.0 "KERNFRNT" 9.11 "1 " */gen drop is 47.70 MW -12.00 MVAr TG 22.0 "DOUBLE C" 13.80 "1 " */gen drop is 42.50 MW 9.69 MVAr TG 22.0 "HISIERRA" 13.80 "1 " */gen drop is 47.90 MW 10.61 MVAr TG 22.0 "BADGERCK" 13.80 "1 " */gen drop is 46.30 MW 10.32 MVAr TG 22.0 "TEXCO_NM" 9.11 "1 " */gen drop is 5.40 MW -3.60 MVAr TG 22.0 "TEXCO_NM" 9.11 "2 " */gen drop is 2.70 MW -3.00 MVAr MBL 22.0 "CHV-CYMR" 9.11 "SG" "D" */ 0.33 MW 0.08 MVAr TG 22.0 "CHV-CYMR" 9.11 "1 " */gen drop is 13.50 MW -0.39 MVAr TG 22.0 "MIDSUN +" 13.80 "1 " */gen drop is 24.50 MW 15.20 MVAr MBL 22.0 "DEXEL + " 13.80 "SG" "D" */ 0.26 MW 0.06 MVAr

Page 306: To determine the system impacts caused by the Project

B-21 GWF Henrietta SISAppendix B

TG 22.0 "DEXEL + " 13.80 "1 " */gen drop is 28.60 MW 9.99 MVAr * Load Group 1 * MBL 22.0 "EL CRRTO" 115.00 "1 " "D" */ 13.64 MW 3.11 MVAr MBL 22.0 "EL CRRTO" 115.00 "2 " "D" */ 16.97 MW 3.87 MVAr MBL 22.0 "EL CRRTO" 115.00 "4 " "D" */ 29.73 MW 6.77 MVAr MBL 22.0 "WHISMAN " 115.00 "3 " "D" */ 9.00 MW 2.05 MVAr MBL 22.0 "WHISMAN " 115.00 "2 " "D" */ 10.63 MW 2.42 MVAr MBL 22.0 "WHISMAN " 115.00 "1 " "D" */ 9.88 MW 2.25 MVAr MBL 22.0 "MT VIEW " 115.00 "3 " "D" */ 12.88 MW 2.93 MVAr MBL 22.0 "MT VIEW " 115.00 "2 " "D" */ 14.25 MW 3.25 MVAr MBL 22.0 "MT VIEW " 115.00 "1 " "D" */ 13.40 MW 3.06 MVAr MBL 22.0 "HALE " 115.00 "1 " "D" */ 1.68 MW 1.00 MVAr MBL 22.0 "VACAVLL1" 115.00 "1 " "D" */ 10.33 MW 0.46 MVAr MBL 22.0 "JAMESON " 115.00 "1 " "D" */ 13.19 MW 0.59 MVAr MBL 22.0 "CORDELIA" 115.00 "2 " "D" */ 5.97 MW 0.27 MVAr MBL 22.0 "VACAVLL2" 115.00 "3 " "D" */ 14.87 MW 0.67 MVAr MBL 22.0 "VACAVLL2" 115.00 "2 " "D" */ 15.14 MW 0.68 MVAr MBL 22.0 "SCHMLBCH" 115.00 "1 " "D" */ 7.10 MW 4.77 MVAr MBL 22.0 "SUISUN " 115.00 "3 " "D" */ 8.89 MW 0.40 MVAr MBL 22.0 "SUISUN " 115.00 "2 " "D" */ 10.91 MW 0.49 MVAr MBL 22.0 "SUISUN " 115.00 "1 " "D" */ 10.04 MW 0.45 MVAr TG 22.0 "CTY FAIR" 9.11 "1 " */gen drop is 0.80 MW 0.10 MVAr TG 22.0 "CTY FAIR" 9.11 "2 " */gen drop is 1.50 MW 0.10 MVAr MBL 22.0 "WOLFSKIL" 13.80 "ss" "D" */ 1.30 MW 0.81 MVAr *TG 22.0 "WOLFSKIL" 13.80 "1 " */gen drop is 50.00 MW -6.30 MVAr: Unit Is Off-Line MBL 22.0 "FREMNT " 115.00 "3 " "D" */ 10.74 MW 2.45 MVAr MBL 22.0 "FREMNT " 115.00 "2 " "D" */ 7.56 MW 1.72 MVAr MBL 22.0 "FREMNT " 115.00 "1 " "D" */ 12.38 MW 2.82 MVAr MBL 22.0 "JARVIS " 115.00 "3 " "D" */ 13.33 MW 3.04 MVAr MBL 22.0 "JARVIS " 115.00 "2 " "D" */ 10.38 MW 2.36 MVAr MBL 22.0 "JARVIS " 115.00 "1 " "D" */ 6.91 MW 1.57 MVAr MBL 22.0 "JV BART " 115.00 "1 " "D" */ 5.11 MW 1.04 MVAr MBL 22.0 "CRYOGEN " 115.00 "1 " "D" */ 0.12 MW 0.03 MVAr MBL 22.0 "STELLING" 115.00 "3 " "D" */ 14.35 MW 3.27 MVAr MBL 22.0 "STELLING" 115.00 "2 " "D" */ 14.03 MW 3.20 MVAr MBL 22.0 "STELLING" 115.00 "1 " "D" */ 13.75 MW 3.13 MVAr MBL 22.0 "WOLFE " 115.00 "3 " "D" */ 7.27 MW 1.66 MVAr MBL 22.0 "WOLFE " 115.00 "2 " "D" */ 14.12 MW 3.22 MVAr MBL 22.0 "WOLFE " 115.00 "1 " "D" */ 11.20 MW 2.55 MVAr MBL 22.0 "MOFT.FLD" 115.00 "1 " "D" */ 3.48 MW 0.87 MVAr MBL 22.0 "LOCKHD 1" 115.00 "1 " "D" */ 14.14 MW 11.71 MVAr MBL 22.0 "LAWRENCE" 115.00 "3 " "D" */ 15.56 MW 3.55 MVAr MBL 22.0 "LAWRENCE" 115.00 "2 " "D" */ 8.82 MW 2.01 MVAr MBL 22.0 "LAWRENCE" 115.00 "1 " "D" */ 22.29 MW 5.08 MVAr MBL 22.0 "PHILLIPS" 115.00 "1 " "D" */ 1.36 MW 0.00 MVAr MBL 22.0 "LOCKHD 2" 115.00 "2 " "D" */ 6.18 MW 1.41 MVAr MBL 22.0 "LOCKHD 2" 115.00 "1 " "D" */ 12.51 MW 9.71 MVAr MBL 22.0 "A.M.D " 115.00 "1 " "D" */ 6.12 MW 4.27 MVAr MBL 22.0 "BRITTN " 115.00 "3 " "D" */ 10.37 MW 2.36 MVAr MBL 22.0 "BRITTN " 115.00 "2 " "D" */ 21.06 MW 4.80 MVAr MBL 22.0 "BRITTN " 115.00 "1 " "D" */ 12.28 MW 2.80 MVAr MBL 22.0 "APP MAT " 115.00 "1 " "D" */ 9.54 MW 2.39 MVAr * Gen Group 2 * MBL 22.0 "ELKHIL1G" 18.00 "ss" "D" */ 6.70 MW 1.68 MVAr TG 22.0 "ELKHIL1G" 18.00 "1 " */gen drop is 166.80 MW 59.64 MVAr MBL 22.0 "ELKHIL2G" 18.00 "ss" "D" */ 6.70 MW 1.68 MVAr TG 22.0 "ELKHIL2G" 18.00 "1 " */gen drop is 166.80 MW 59.64 MVAr TG 22.0 "ELKHIL3G" 18.00 "1 " */gen drop is 225.50 MW 65.23 MVAr * Load Group 2 * MBL 22.0 "MARTIN C" 115.00 "4 " "D" */ 17.44 MW 1.11 MVAr MBL 22.0 "MARTIN C" 115.00 "1 " "D" */ 17.44 MW 1.11 MVAr MBL 22.0 "CLAYTN " 115.00 "5 " "D" */ 3.27 MW 0.74 MVAr MBL 22.0 "CLAYTN " 115.00 "3 " "D" */ 15.68 MW 3.57 MVAr MBL 22.0 "CLAYTN " 115.00 "2 " "D" */ 14.76 MW 3.36 MVAr MBL 22.0 "CLAYTN " 115.00 "1 " "D" */ 9.25 MW 2.11 MVAr MBL 22.0 "MEDW LNE" 115.00 "3 " "D" */ 15.10 MW 3.44 MVAr MBL 22.0 "MEDW LNE" 115.00 "2 " "D" */ 16.12 MW 3.67 MVAr MBL 22.0 "MEDW LNE" 115.00 "1 " "D" */ 13.54 MW 3.08 MVAr MBL 22.0 "EBMUDGRY" 115.00 "1 " "D" */ 4.13 MW 1.36 MVAr

Page 307: To determine the system impacts caused by the Project

B-22 GWF Henrietta SISAppendix B

MBL 22.0 "LAKEWD-C" 115.00 "6 " "D" */ 15.21 MW 3.47 MVAr MBL 22.0 "LAKEWD-C" 115.00 "5 " "D" */ 6.70 MW 1.53 MVAr MBL 22.0 "LAKEWD-M" 115.00 "LW" "D" */ 4.15 MW 0.84 MVAr MBL 22.0 "LAKEWD-M" 115.00 "4 " "D" */ 16.55 MW 3.77 MVAr MBL 22.0 "LAKEWD-M" 115.00 "2 " "D" */ 8.85 MW 2.02 MVAr MBL 22.0 "LAKEWD-M" 115.00 "1 " "D" */ 13.10 MW 2.99 MVAr MBL 22.0 "DALY CTY" 115.00 "2 " "D" */ 11.94 MW 2.72 MVAr MBL 22.0 "DALY CTY" 115.00 "1 " "D" */ 19.78 MW 4.51 MVAr MBL 22.0 "SERRMNTE" 115.00 "1 " "D" */ 4.49 MW 1.02 MVAr * Gen Group 3 * TG 22.0 "LAPLM_G1" 21.00 "1 " */gen drop is 230.00 MW 101.84 MVAr TG 22.0 "LAPLM_G2" 21.00 "1 " */gen drop is 230.00 MW 101.84 MVAr * Load Group 3 * MBL 22.0 "ELDORAD " 115.00 "1 " "D" */ 3.29 MW 0.15 MVAr MBL 22.0 "APPLE HL" 115.00 "2 " "D" */ 3.26 MW 0.14 MVAr MBL 22.0 "APPLE HL" 115.00 "1 " "D" */ 5.15 MW 0.23 MVAr MBL 22.0 "PLCRVLB2" 115.00 "2 " "D" */ 3.17 MW 0.14 MVAr MBL 22.0 "PLCRVLB3" 115.00 "3 " "D" */ 9.12 MW 0.41 MVAr MBL 22.0 "DMND SPR" 115.00 "2 " "D" */ 9.87 MW 0.44 MVAr MBL 22.0 "DMND SPR" 115.00 "1 " "D" */ 3.47 MW 0.16 MVAr MBL 22.0 "SHPRING " 115.00 "2 " "D" */ 7.56 MW 0.34 MVAr MBL 22.0 "SHPRING " 115.00 "1 " "D" */ 6.88 MW 0.31 MVAr *MBL 22.0 "CPM " 115.00 "1 " "D" */ 0.00 MW 0.00 MVAr: Load Status Off MBL 22.0 "SPICAMIN" 115.00 "1 " "D" */ 2.87 MW 2.53 MVAr TG 22.0 "CHILIBAR" 4.16 "1 " */gen drop is 2.00 MW -2.00 MVAr MBL 22.0 "ELDRADO1" 21.60 "SG" "D" */ 0.03 MW 0.01 MVAr TG 22.0 "ELDRADO1" 21.60 "1 " */gen drop is 9.96 MW -3.30 MVAr MBL 22.0 "ELDRADO2" 21.60 "SG" "D" */ 0.03 MW 0.01 MVAr TG 22.0 "ELDRADO2" 21.60 "1 " */gen drop is 9.96 MW -3.30 MVAr MBL 22.0 "CLRKSVLE" 115.00 "3 " "D" */ 15.92 MW 0.71 MVAr MBL 22.0 "CLRKSVLE" 115.00 "2 " "D" */ 16.66 MW 0.75 MVAr MBL 22.0 "CLRKSVLE" 115.00 "1 " "D" */ 15.68 MW 0.70 MVAr MBL 22.0 "BAY MDWS" 115.00 "5 " "D" */ 7.33 MW 1.67 MVAr MBL 22.0 "BAY MDWS" 115.00 "3 " "D" */ 7.97 MW 1.82 MVAr MBL 22.0 "BAY MDWS" 115.00 "2 " "D" */ 13.47 MW 3.07 MVAr MBL 22.0 "BAY MDWS" 115.00 "1 " "D" */ 16.87 MW 3.85 MVAr * Gen Group 4 * TG 22.0 "TEXSUN2G" 18.00 "1 " */gen drop is 169.00 MW 13.22 MVAr TG 22.0 "TEXSUN1G" 18.00 "1 " */gen drop is 169.00 MW 13.22 MVAr TG 22.0 "TEXSUNST" 18.00 "1 " */gen drop is 222.00 MW 60.97 MVAr * Load Group 4 * MBL 22.0 "HIGHWAY " 115.00 "2 " "D" */ 11.09 MW 2.25 MVAr MBL 22.0 "HIGHWAY " 115.00 "1 " "D" */ 9.03 MW 1.84 MVAr MBL 22.0 "MEYERS " 115.00 "1 " "D" */ 0.18 MW 0.04 MVAr MBL 22.0 "CARQUINZ" 115.00 "2 " "D" */ 4.92 MW 1.00 MVAr MBL 22.0 "CARQUINZ" 115.00 "1 " "D" */ 5.78 MW 1.17 MVAr MBL 22.0 "MRE IS-Q" 115.00 "1 " "D" */ 4.25 MW 0.86 MVAr MBL 22.0 "GUALALA " 60.00 "2 " "D" */ 0.59 MW 0.12 MVAr MBL 22.0 "GUALALA " 60.00 "1 " "D" */ 1.21 MW 0.25 MVAr MBL 22.0 "ANNAPOLS" 60.00 "1 " "D" */ 0.10 MW 0.02 MVAr MBL 22.0 "FORT RSS" 60.00 "1 " "D" */ 0.34 MW 0.07 MVAr MBL 22.0 "SLMN CRK" 60.00 "1 " "D" */ 1.33 MW 0.27 MVAr MBL 22.0 "MONTE RO" 60.00 "2 " "D" */ 2.02 MW 0.41 MVAr MBL 22.0 "MONTE RO" 60.00 "1 " "D" */ 1.58 MW 0.32 MVAr MBL 22.0 "WOHLER " 60.00 "1 " "D" */ 3.21 MW 1.37 MVAr MBL 22.0 "MIRABEL " 60.00 "1 " "D" */ 4.13 MW 0.84 MVAr MBL 22.0 "MOLINO " 60.00 "2 " "D" */ 7.63 MW 1.55 MVAr MBL 22.0 "MOLINO " 60.00 "1 " "D" */ 2.97 MW 0.60 MVAr MBL 22.0 "LAGUNA " 60.00 "1 " "D" */ 4.20 MW 1.05 MVAr MBL 22.0 "COTATI " 60.00 "2 " "D" */ 2.54 MW 0.51 MVAr MBL 22.0 "COTATI " 60.00 "1 " "D" */ 2.79 MW 0.57 MVAr TG 22.0 "SONMA LF" 9.11 "1 " */gen drop is 4.00 MW 0.00 MVAr MBL 22.0 "LS GLLNS" 115.00 "3 " "D" */ 4.84 MW 0.98 MVAr MBL 22.0 "LS GLLNS" 115.00 "2 " "D" */ 4.33 MW 0.88 MVAr MBL 22.0 "LS GLLNS" 115.00 "1 " "D" */ 6.42 MW 1.30 MVAr MBL 22.0 "SAN RAFL" 115.00 "3 " "D" */ 7.80 MW 1.59 MVAr MBL 22.0 "SAN RAFL" 115.00 "2 " "D" */ 11.23 MW 2.28 MVAr MBL 22.0 "SAN RAFL" 115.00 "1 " "D" */ 11.78 MW 2.39 MVAr * Gen Group 5 *

Page 308: To determine the system impacts caused by the Project

B-23 GWF Henrietta SISAppendix B

TG 22.0 "LAPLM_G3" 21.00 "1 " */gen drop is 229.00 MW 101.72 MVAr TG 22.0 "LAPLM_G4" 21.00 "1 " */gen drop is 230.00 MW 101.84 MVAr * Load Group 5 * MBL 22.0 "NEW HOPE" 60.00 "1 " "D" */ 1.21 MW 0.05 MVAr MBL 22.0 "SEBASTIA" 60.00 "1 " "D" */ 2.12 MW 1.59 MVAr MBL 22.0 "STAGG " 60.00 "3 " "D" */ 8.43 MW 0.38 MVAr MBL 22.0 "STAGG " 60.00 "2 " "D" */ 8.43 MW 0.38 MVAr MBL 22.0 "CNTRY CB" 60.00 "4 " "D" */ 7.39 MW 0.33 MVAr MBL 22.0 "CNTRY CB" 60.00 "3 " "D" */ 4.82 MW 0.22 MVAr MBL 22.0 "CNTRY CB" 60.00 "2 " "D" */ 4.34 MW 0.19 MVAr MBL 22.0 "CNTRY CB" 60.00 "1 " "D" */ 2.65 MW 0.12 MVAr MBL 22.0 "UOP " 60.00 "1 " "D" */ 4.51 MW 3.15 MVAr MBL 22.0 "HAMMER " 60.00 "3 " "D" */ 8.86 MW 0.40 MVAr MBL 22.0 "HAMMER " 60.00 "2 " "D" */ 8.13 MW 0.36 MVAr MBL 22.0 "HAMMER " 60.00 "1 " "D" */ 8.47 MW 0.38 MVAr MBL 22.0 "METTLER " 60.00 "3 " "D" */ 3.70 MW 0.17 MVAr MBL 22.0 "TERMNOUS" 60.00 "1 " "D" */ 2.14 MW 0.10 MVAr MBL 22.0 "MSHR 60V" 60.00 "2 " "D" */ 14.95 MW 0.67 MVAr MBL 22.0 "MSHR 60V" 60.00 "1 " "D" */ 8.95 MW 0.40 MVAr MBL 22.0 "STAGG_5 " 21.00 "5 " "D" */ 26.56 MW 1.19 MVAr MBL 22.0 "STAGG_6 " 21.00 "6 " "D" */ 23.27 MW 1.04 MVAr MBL 22.0 "CMP EVRS" 115.00 "2 " "D" */ 11.31 MW 2.30 MVAr MBL 22.0 "CMP EVRS" 115.00 "1 " "D" */ 11.61 MW 2.36 MVAr MBL 22.0 "PAUL SWT" 115.00 "3 " "D" */ 16.81 MW 3.42 MVAr MBL 22.0 "PAUL SWT" 115.00 "2 " "D" */ 12.22 MW 2.48 MVAr MBL 22.0 "PAUL SWT" 115.00 "1 " "D" */ 16.05 MW 3.26 MVAr MBL 22.0 "ROB ROY " 115.00 "1 " "D" */ 7.02 MW 1.43 MVAr TG 22.0 "PSWTSTCM" 8.00 "1 " */gen drop is 0.00 MW -18.90 MVAr MBL 22.0 "CSTRVLLE" 115.00 "1 " "D" */ 10.31 MW 2.10 MVAr MBL 22.0 "DEL MNTE" 115.00 "2 " "D" */ 14.17 MW 2.88 MVAr MBL 22.0 "DEL MNTE" 115.00 "1 " "D" */ 9.22 MW 1.87 MVAr MBL 22.0 "FORT ORD" 60.00 "1 " "D" */ 15.66 MW 3.18 MVAr MBL 22.0 "MANZANTA" 60.00 "1 " "D" */ 0.60 MW 0.12 MVAr MBL 22.0 "MONTEREY" 60.00 "1 " "D" */ 2.22 MW 0.45 MVAr MBL 22.0 "NVY SCHL" 60.00 "1 " "D" */ 1.70 MW 0.87 MVAr MBL 22.0 "VIEJO " 60.00 "2 " "D" */ 8.35 MW 1.70 MVAr MBL 22.0 "VIEJO " 60.00 "1 " "D" */ 7.04 MW 1.43 MVAr MBL 22.0 "HATTON " 60.00 "1 " "D" */ 6.11 MW 1.24 MVAr MBL 22.0 "NAVY LAB" 60.00 "1 " "D" */ 1.30 MW 0.56 MVAr MBL 22.0 "BORONDA " 60.00 "1 " "D" */ 4.26 MW 0.86 MVAr MBL 22.0 "RSVTN RD" 60.00 "1 " "D" */ 5.38 MW 1.09 MVAr MBL 22.0 "LAURELES" 60.00 "1 " "D" */ 3.00 MW 0.61 MVAr MBL 22.0 "OTTER " 60.00 "1 " "D" */ 1.76 MW 0.36 MVAr * * REMOVE GARRISON REACTOR AND INSERT KINPORT CAP MBS 180.0 "KINPORT " 345. "1 " "R" MSD 180.0 "GARRISON" 500. "s " "D" * * MSD 180.0 "GATES" 230.0 "v " "D" MSD 180.0 "LOSBANOS" 230.0 "v " "D" *

Page 309: To determine the system impacts caused by the Project

B-24 GWF Henrietta SISAppendix B

Midway - Gates and Midway - Los Banos Double Line Outage (South-to-North Flow) * * CC cards for post-transient only * * Readjust Northwest SVC's * CC MSV 0.0 "KEEL-SVC" 19.60 "1 " 350. -300. CC MSV 0.0 "MV-SVC " 19.60 "1 " 350. -300. * * * Fault at Midway 500 kV bus * FB 0.0 "MIDWAY" 500.0 * * CLEAR FAULT AND OPEN LINES - 4 CYCLES * CFB 4.0 "MIDWAY" 500.0 DL 4.0 "GATES " 500. "MIDWAY" 500. "1 " DL 4.0 "LOSBANOS" 500. "MIDWAY" 500. "1 " * * * * CDWR Pumps * TG 22.0 "DOS AMG1" 13.20 "1 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DOS AMG1" 13.20 "2 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DOS AMG1" 13.20 "3 " */gen drop is -30.00 MW 0.00 MVAr TG 22.0 "DELTA E " 13.20 "11" */gen drop is -1.00 MW 0.00 MVAr * Helms Pumps * *TG 22.0 "HELMS 1 "18.00 "1 " */gen drop is -310.00 MW 120.00 MVAr: TG 22.0 "HELMS 2 " 18.00 "1 " */gen drop is -310.00 MW 120.00 MVAr TG 22.0 "HELMS 3 " 18.00 "1 " */gen drop is -310.00 MW 120.00 MVAr * Gen Group 1 * MBL 22.0 "SUNST " 230.00 "SG" "D" */ 9.59 MW 3.48 MVAr TG 22.0 "SUNSET G" 13.80 "1 " */gen drop is 75.00 MW -20.00 MVAr TG 22.0 "SUNSET G" 13.80 "2 " */gen drop is 75.00 MW -20.00 MVAr TG 22.0 "SUNSET G" 13.80 "3 " */gen drop is 75.00 MW -20.00 MVAr MBL 22.0 "KERNFRNT" 9.11 "SG" "D" */ 0.57 MW 0.28 MVAr TG 22.0 "KERNFRNT" 9.11 "1 " */gen drop is 47.70 MW -12.00 MVAr TG 22.0 "DOUBLE C" 13.80 "1 " */gen drop is 42.50 MW 9.69 MVAr TG 22.0 "HISIERRA" 13.80 "1 " */gen drop is 47.90 MW 10.61 MVAr TG 22.0 "BADGERCK" 13.80 "1 " */gen drop is 46.30 MW 10.32 MVAr TG 22.0 "TEXCO_NM" 9.11 "1 " */gen drop is 5.40 MW -3.60 MVAr TG 22.0 "TEXCO_NM" 9.11 "2 " */gen drop is 2.70 MW -3.00 MVAr MBL 22.0 "CHV-CYMR" 9.11 "SG" "D" */ 0.33 MW 0.08 MVAr TG 22.0 "CHV-CYMR" 9.11 "1 " */gen drop is 13.50 MW -0.39 MVAr TG 22.0 "MIDSUN +" 13.80 "1 " */gen drop is 24.50 MW 15.20 MVAr MBL 22.0 "DEXEL + " 13.80 "SG" "D" */ 0.26 MW 0.06 MVAr TG 22.0 "DEXEL + " 13.80 "1 " */gen drop is 28.60 MW 9.99 MVAr * Load Group 1 * MBL 22.0 "EL CRRTO" 115.00 "1 " "D" */ 13.64 MW 3.11 MVAr MBL 22.0 "EL CRRTO" 115.00 "2 " "D" */ 16.97 MW 3.87 MVAr MBL 22.0 "EL CRRTO" 115.00 "4 " "D" */ 29.73 MW 6.77 MVAr MBL 22.0 "WHISMAN " 115.00 "3 " "D" */ 9.00 MW 2.05 MVAr MBL 22.0 "WHISMAN " 115.00 "2 " "D" */ 10.63 MW 2.42 MVAr MBL 22.0 "WHISMAN " 115.00 "1 " "D" */ 9.88 MW 2.25 MVAr MBL 22.0 "MT VIEW " 115.00 "3 " "D" */ 12.88 MW 2.93 MVAr MBL 22.0 "MT VIEW " 115.00 "2 " "D" */ 14.25 MW 3.25 MVAr MBL 22.0 "MT VIEW " 115.00 "1 " "D" */ 13.40 MW 3.06 MVAr MBL 22.0 "HALE " 115.00 "1 " "D" */ 1.68 MW 1.00 MVAr MBL 22.0 "VACAVLL1" 115.00 "1 " "D" */ 10.33 MW 0.46 MVAr MBL 22.0 "JAMESON " 115.00 "1 " "D" */ 13.19 MW 0.59 MVAr MBL 22.0 "CORDELIA" 115.00 "2 " "D" */ 5.97 MW 0.27 MVAr MBL 22.0 "VACAVLL2" 115.00 "3 " "D" */ 14.87 MW 0.67 MVAr MBL 22.0 "VACAVLL2" 115.00 "2 " "D" */ 15.14 MW 0.68 MVAr MBL 22.0 "SCHMLBCH" 115.00 "1 " "D" */ 7.10 MW 4.77 MVAr MBL 22.0 "SUISUN " 115.00 "3 " "D" */ 8.89 MW 0.40 MVAr

Page 310: To determine the system impacts caused by the Project

B-25 GWF Henrietta SISAppendix B

MBL 22.0 "SUISUN " 115.00 "2 " "D" */ 10.91 MW 0.49 MVAr MBL 22.0 "SUISUN " 115.00 "1 " "D" */ 10.04 MW 0.45 MVAr TG 22.0 "CTY FAIR" 9.11 "1 " */gen drop is 0.80 MW 0.10 MVAr TG 22.0 "CTY FAIR" 9.11 "2 " */gen drop is 1.50 MW 0.10 MVAr MBL 22.0 "WOLFSKIL" 13.80 "ss" "D" */ 1.30 MW 0.81 MVAr MBL 22.0 "FREMNT " 115.00 "3 " "D" */ 10.74 MW 2.45 MVAr MBL 22.0 "FREMNT " 115.00 "2 " "D" */ 7.56 MW 1.72 MVAr MBL 22.0 "FREMNT " 115.00 "1 " "D" */ 12.38 MW 2.82 MVAr MBL 22.0 "JARVIS " 115.00 "3 " "D" */ 13.33 MW 3.04 MVAr MBL 22.0 "JARVIS " 115.00 "2 " "D" */ 10.38 MW 2.36 MVAr MBL 22.0 "JARVIS " 115.00 "1 " "D" */ 6.91 MW 1.57 MVAr MBL 22.0 "JV BART " 115.00 "1 " "D" */ 5.11 MW 1.04 MVAr MBL 22.0 "CRYOGEN " 115.00 "1 " "D" */ 0.12 MW 0.03 MVAr MBL 22.0 "STELLING" 115.00 "3 " "D" */ 14.35 MW 3.27 MVAr MBL 22.0 "STELLING" 115.00 "2 " "D" */ 14.03 MW 3.20 MVAr MBL 22.0 "STELLING" 115.00 "1 " "D" */ 13.75 MW 3.13 MVAr MBL 22.0 "WOLFE " 115.00 "3 " "D" */ 7.27 MW 1.66 MVAr MBL 22.0 "WOLFE " 115.00 "2 " "D" */ 14.12 MW 3.22 MVAr MBL 22.0 "WOLFE " 115.00 "1 " "D" */ 11.20 MW 2.55 MVAr MBL 22.0 "MOFT.FLD" 115.00 "1 " "D" */ 3.48 MW 0.87 MVAr MBL 22.0 "LOCKHD 1" 115.00 "1 " "D" */ 14.14 MW 11.71 MVAr MBL 22.0 "LAWRENCE" 115.00 "3 " "D" */ 15.56 MW 3.55 MVAr MBL 22.0 "LAWRENCE" 115.00 "2 " "D" */ 8.82 MW 2.01 MVAr MBL 22.0 "LAWRENCE" 115.00 "1 " "D" */ 22.29 MW 5.08 MVAr MBL 22.0 "PHILLIPS" 115.00 "1 " "D" */ 1.36 MW 0.00 MVAr MBL 22.0 "LOCKHD 2" 115.00 "2 " "D" */ 6.18 MW 1.41 MVAr MBL 22.0 "LOCKHD 2" 115.00 "1 " "D" */ 12.51 MW 9.71 MVAr MBL 22.0 "A.M.D " 115.00 "1 " "D" */ 6.12 MW 4.27 MVAr MBL 22.0 "BRITTN " 115.00 "3 " "D" */ 10.37 MW 2.36 MVAr MBL 22.0 "BRITTN " 115.00 "2 " "D" */ 21.06 MW 4.80 MVAr MBL 22.0 "BRITTN " 115.00 "1 " "D" */ 12.28 MW 2.80 MVAr MBL 22.0 "APP MAT " 115.00 "1 " "D" */ 9.54 MW 2.39 MVAr * Gen Group 2 * MBL 22.0 "ELKHIL1G" 18.00 "ss" "D" */ 6.70 MW 1.68 MVAr TG 22.0 "ELKHIL1G" 18.00 "1 " */gen drop is 166.80 MW 59.64 MVAr MBL 22.0 "ELKHIL2G" 18.00 "ss" "D" */ 6.70 MW 1.68 MVAr TG 22.0 "ELKHIL2G" 18.00 "1 " */gen drop is 166.80 MW 59.64 MVAr TG 22.0 "ELKHIL3G" 18.00 "1 " */gen drop is 225.50 MW 65.23 MVAr * Load Group 2 * MBL 22.0 "MARTIN C" 115.00 "4 " "D" */ 17.44 MW 1.11 MVAr MBL 22.0 "MARTIN C" 115.00 "1 " "D" */ 17.44 MW 1.11 MVAr MBL 22.0 "CLAYTN " 115.00 "5 " "D" */ 3.27 MW 0.74 MVAr MBL 22.0 "CLAYTN " 115.00 "3 " "D" */ 15.68 MW 3.57 MVAr MBL 22.0 "CLAYTN " 115.00 "2 " "D" */ 14.76 MW 3.36 MVAr MBL 22.0 "CLAYTN " 115.00 "1 " "D" */ 9.25 MW 2.11 MVAr MBL 22.0 "MEDW LNE" 115.00 "3 " "D" */ 15.10 MW 3.44 MVAr MBL 22.0 "MEDW LNE" 115.00 "2 " "D" */ 16.12 MW 3.67 MVAr MBL 22.0 "MEDW LNE" 115.00 "1 " "D" */ 13.54 MW 3.08 MVAr MBL 22.0 "EBMUDGRY" 115.00 "1 " "D" */ 4.13 MW 1.36 MVAr MBL 22.0 "LAKEWD-C" 115.00 "6 " "D" */ 15.21 MW 3.47 MVAr MBL 22.0 "LAKEWD-C" 115.00 "5 " "D" */ 6.70 MW 1.53 MVAr MBL 22.0 "LAKEWD-M" 115.00 "LW" "D" */ 4.15 MW 0.84 MVAr MBL 22.0 "LAKEWD-M" 115.00 "4 " "D" */ 16.55 MW 3.77 MVAr MBL 22.0 "LAKEWD-M" 115.00 "2 " "D" */ 8.85 MW 2.02 MVAr MBL 22.0 "LAKEWD-M" 115.00 "1 " "D" */ 13.10 MW 2.99 MVAr MBL 22.0 "DALY CTY" 115.00 "2 " "D" */ 11.94 MW 2.72 MVAr MBL 22.0 "DALY CTY" 115.00 "1 " "D" */ 19.78 MW 4.51 MVAr MBL 22.0 "SERRMNTE" 115.00 "1 " "D" */ 4.49 MW 1.02 MVAr * Gen Group 3 * TG 22.0 "LAPLM_G1" 21.00 "1 " */gen drop is 230.00 MW 101.84 MVAr TG 22.0 "LAPLM_G2" 21.00 "1 " */gen drop is 230.00 MW 101.84 MVAr * Load Group 3 * MBL 22.0 "ELDORAD " 115.00 "1 " "D" */ 3.29 MW 0.15 MVAr MBL 22.0 "APPLE HL" 115.00 "2 " "D" */ 3.26 MW 0.14 MVAr MBL 22.0 "APPLE HL" 115.00 "1 " "D" */ 5.15 MW 0.23 MVAr MBL 22.0 "PLCRVLB2" 115.00 "2 " "D" */ 3.17 MW 0.14 MVAr MBL 22.0 "PLCRVLB3" 115.00 "3 " "D" */ 9.12 MW 0.41 MVAr MBL 22.0 "DMND SPR" 115.00 "2 " "D" */ 9.87 MW 0.44 MVAr MBL 22.0 "DMND SPR" 115.00 "1 " "D" */ 3.47 MW 0.16 MVAr MBL 22.0 "SHPRING " 115.00 "2 " "D" */ 7.56 MW 0.34 MVAr

Page 311: To determine the system impacts caused by the Project

B-26 GWF Henrietta SISAppendix B

MBL 22.0 "SHPRING " 115.00 "1 " "D" */ 6.88 MW 0.31 MVAr MBL 22.0 "SPICAMIN" 115.00 "1 " "D" */ 2.87 MW 2.53 MVAr TG 22.0 "CHILIBAR" 4.16 "1 " */gen drop is 2.00 MW -2.00 MVAr MBL 22.0 "ELDRADO1" 21.60 "SG" "D" */ 0.03 MW 0.01 MVAr TG 22.0 "ELDRADO1" 21.60 "1 " */gen drop is 9.96 MW -3.30 MVAr MBL 22.0 "ELDRADO2" 21.60 "SG" "D" */ 0.03 MW 0.01 MVAr TG 22.0 "ELDRADO2" 21.60 "1 " */gen drop is 9.96 MW -3.30 MVAr MBL 22.0 "CLRKSVLE" 115.00 "3 " "D" */ 15.92 MW 0.71 MVAr MBL 22.0 "CLRKSVLE" 115.00 "2 " "D" */ 16.66 MW 0.75 MVAr MBL 22.0 "CLRKSVLE" 115.00 "1 " "D" */ 15.68 MW 0.70 MVAr MBL 22.0 "BAY MDWS" 115.00 "5 " "D" */ 7.33 MW 1.67 MVAr MBL 22.0 "BAY MDWS" 115.00 "3 " "D" */ 7.97 MW 1.82 MVAr MBL 22.0 "BAY MDWS" 115.00 "2 " "D" */ 13.47 MW 3.07 MVAr MBL 22.0 "BAY MDWS" 115.00 "1 " "D" */ 16.87 MW 3.85 MVAr * Gen Group 4 * TG 22.0 "TEXSUN2G" 18.00 "1 " */gen drop is 169.00 MW 13.22 MVAr TG 22.0 "TEXSUN1G" 18.00 "1 " */gen drop is 169.00 MW 13.22 MVAr TG 22.0 "TEXSUNST" 18.00 "1 " */gen drop is 222.00 MW 60.97 MVAr * Load Group 4 * MBL 22.0 "HIGHWAY " 115.00 "2 " "D" */ 11.09 MW 2.25 MVAr MBL 22.0 "HIGHWAY " 115.00 "1 " "D" */ 9.03 MW 1.84 MVAr MBL 22.0 "MEYERS " 115.00 "1 " "D" */ 0.18 MW 0.04 MVAr MBL 22.0 "CARQUINZ" 115.00 "2 " "D" */ 4.92 MW 1.00 MVAr MBL 22.0 "CARQUINZ" 115.00 "1 " "D" */ 5.78 MW 1.17 MVAr MBL 22.0 "MRE IS-Q" 115.00 "1 " "D" */ 4.25 MW 0.86 MVAr MBL 22.0 "GUALALA " 60.00 "2 " "D" */ 0.59 MW 0.12 MVAr MBL 22.0 "GUALALA " 60.00 "1 " "D" */ 1.21 MW 0.25 MVAr MBL 22.0 "ANNAPOLS" 60.00 "1 " "D" */ 0.10 MW 0.02 MVAr MBL 22.0 "FORT RSS" 60.00 "1 " "D" */ 0.34 MW 0.07 MVAr MBL 22.0 "SLMN CRK" 60.00 "1 " "D" */ 1.33 MW 0.27 MVAr MBL 22.0 "MONTE RO" 60.00 "2 " "D" */ 2.02 MW 0.41 MVAr MBL 22.0 "MONTE RO" 60.00 "1 " "D" */ 1.58 MW 0.32 MVAr MBL 22.0 "WOHLER " 60.00 "1 " "D" */ 3.21 MW 1.37 MVAr MBL 22.0 "MIRABEL " 60.00 "1 " "D" */ 4.13 MW 0.84 MVAr MBL 22.0 "MOLINO " 60.00 "2 " "D" */ 7.63 MW 1.55 MVAr MBL 22.0 "MOLINO " 60.00 "1 " "D" */ 2.97 MW 0.60 MVAr MBL 22.0 "LAGUNA " 60.00 "1 " "D" */ 4.20 MW 1.05 MVAr MBL 22.0 "COTATI " 60.00 "2 " "D" */ 2.54 MW 0.51 MVAr MBL 22.0 "COTATI " 60.00 "1 " "D" */ 2.79 MW 0.57 MVAr TG 22.0 "SONMA LF" 9.11 "1 " */gen drop is 4.00 MW 0.00 MVAr MBL 22.0 "LS GLLNS" 115.00 "3 " "D" */ 4.84 MW 0.98 MVAr MBL 22.0 "LS GLLNS" 115.00 "2 " "D" */ 4.33 MW 0.88 MVAr MBL 22.0 "LS GLLNS" 115.00 "1 " "D" */ 6.42 MW 1.30 MVAr MBL 22.0 "SAN RAFL" 115.00 "3 " "D" */ 7.80 MW 1.59 MVAr MBL 22.0 "SAN RAFL" 115.00 "2 " "D" */ 11.23 MW 2.28 MVAr MBL 22.0 "SAN RAFL" 115.00 "1 " "D" */ 11.78 MW 2.39 MVAr * Gen Group 5 * TG 22.0 "LAPLM_G3" 21.00 "1 " */gen drop is 229.00 MW 101.72 MVAr TG 22.0 "LAPLM_G4" 21.00 "1 " */gen drop is 230.00 MW 101.84 MVAr * Load Group 5 * MBL 22.0 "NEW HOPE" 60.00 "1 " "D" */ 1.21 MW 0.05 MVAr MBL 22.0 "SEBASTIA" 60.00 "1 " "D" */ 2.12 MW 1.59 MVAr MBL 22.0 "STAGG " 60.00 "3 " "D" */ 8.43 MW 0.38 MVAr MBL 22.0 "STAGG " 60.00 "2 " "D" */ 8.43 MW 0.38 MVAr MBL 22.0 "CNTRY CB" 60.00 "4 " "D" */ 7.39 MW 0.33 MVAr MBL 22.0 "CNTRY CB" 60.00 "3 " "D" */ 4.82 MW 0.22 MVAr MBL 22.0 "CNTRY CB" 60.00 "2 " "D" */ 4.34 MW 0.19 MVAr MBL 22.0 "CNTRY CB" 60.00 "1 " "D" */ 2.65 MW 0.12 MVAr MBL 22.0 "UOP " 60.00 "1 " "D" */ 4.51 MW 3.15 MVAr MBL 22.0 "HAMMER " 60.00 "3 " "D" */ 8.86 MW 0.40 MVAr MBL 22.0 "HAMMER " 60.00 "2 " "D" */ 8.13 MW 0.36 MVAr MBL 22.0 "HAMMER " 60.00 "1 " "D" */ 8.47 MW 0.38 MVAr MBL 22.0 "METTLER " 60.00 "3 " "D" */ 3.70 MW 0.17 MVAr MBL 22.0 "TERMNOUS" 60.00 "1 " "D" */ 2.14 MW 0.10 MVAr MBL 22.0 "MSHR 60V" 60.00 "2 " "D" */ 14.95 MW 0.67 MVAr MBL 22.0 "MSHR 60V" 60.00 "1 " "D" */ 8.95 MW 0.40 MVAr MBL 22.0 "STAGG_5 " 21.00 "5 " "D" */ 26.56 MW 1.19 MVAr MBL 22.0 "STAGG_6 " 21.00 "6 " "D" */ 23.27 MW 1.04 MVAr MBL 22.0 "CMP EVRS" 115.00 "2 " "D" */ 11.31 MW 2.30 MVAr MBL 22.0 "CMP EVRS" 115.00 "1 " "D" */ 11.61 MW 2.36 MVAr

Page 312: To determine the system impacts caused by the Project

B-27 GWF Henrietta SISAppendix B

MBL 22.0 "PAUL SWT" 115.00 "3 " "D" */ 16.81 MW 3.42 MVAr MBL 22.0 "PAUL SWT" 115.00 "2 " "D" */ 12.22 MW 2.48 MVAr MBL 22.0 "PAUL SWT" 115.00 "1 " "D" */ 16.05 MW 3.26 MVAr MBL 22.0 "ROB ROY " 115.00 "1 " "D" */ 7.02 MW 1.43 MVAr TG 22.0 "PSWTSTCM" 8.00 "1 " */gen drop is 0.00 MW -18.90 MVAr MBL 22.0 "CSTRVLLE" 115.00 "1 " "D" */ 10.31 MW 2.10 MVAr MBL 22.0 "DEL MNTE" 115.00 "2 " "D" */ 14.17 MW 2.88 MVAr MBL 22.0 "DEL MNTE" 115.00 "1 " "D" */ 9.22 MW 1.87 MVAr MBL 22.0 "FORT ORD" 60.00 "1 " "D" */ 15.66 MW 3.18 MVAr MBL 22.0 "MANZANTA" 60.00 "1 " "D" */ 0.60 MW 0.12 MVAr MBL 22.0 "MONTEREY" 60.00 "1 " "D" */ 2.22 MW 0.45 MVAr MBL 22.0 "NVY SCHL" 60.00 "1 " "D" */ 1.70 MW 0.87 MVAr MBL 22.0 "VIEJO " 60.00 "2 " "D" */ 8.35 MW 1.70 MVAr MBL 22.0 "VIEJO " 60.00 "1 " "D" */ 7.04 MW 1.43 MVAr MBL 22.0 "HATTON " 60.00 "1 " "D" */ 6.11 MW 1.24 MVAr MBL 22.0 "NAVY LAB" 60.00 "1 " "D" */ 1.30 MW 0.56 MVAr MBL 22.0 "BORONDA " 60.00 "1 " "D" */ 4.26 MW 0.86 MVAr MBL 22.0 "RSVTN RD" 60.00 "1 " "D" */ 5.38 MW 1.09 MVAr MBL 22.0 "LAURELES" 60.00 "1 " "D" */ 3.00 MW 0.61 MVAr MBL 22.0 "OTTER " 60.00 "1 " "D" */ 1.76 MW 0.36 MVAr * * MSD 180.0 "GATES" 230.0 "v " "D" MSD 180.0 "LOSBANOS" 230.0 "v " "D" * �

Page 313: To determine the system impacts caused by the Project

Appendix C Powerflow Results

Table of Content Table C-1: Category “A” Normal Overloads...................................................................... 1

2013 Summer Peak ......................................................................................................... 1 2013 Summer Off-Peak .................................................................................................. 1 2013 Spring Peak ............................................................................................................ 2

Table C-2: Category “B” Emergency Overloads................................................................ 3 2013 Summer Peak ......................................................................................................... 3 2013 Summer Off-Peak ................................................................................................ 45 2013 Spring Peak .......................................................................................................... 59

Table C-3: Category “C” Emergency Overloads.............................................................. 86 2013 Summer Peak ....................................................................................................... 86 2013 Summer Off-Peak .............................................................................................. 133 2013 Spring Peak ........................................................................................................ 148

Page 314: To determine the system impacts caused by the Project

C-1 GWF Henrietta SISAppendix C

Table C-1: Category “A” Normal Overloads #

Outage Description

Facility Rating Unit PU

Flow PU

Flow %

Change

2013 Summer Peak 1 BASE CASE WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 675.25 Amps 131.7 132.5 0.8 1 BASE CASE WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 675.25 Amps 145.4 146.2 0.8 1 BASE CASE TEMBLOR -BELRIDGE 115.00kV Ckt#1 Sec# 1 632.58 Amps 101.9 101.9 0.1 1 BASE CASE STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 675.25 Amps 111.8 112.4 0.5 1 BASE CASE STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 675.25 Amps 124.7 125.2 0.5 1 BASE CASE STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 743.02 Amps 119.7 120.2 0.6 1 BASE CASE Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 376.53 Amps 104.6 104.7 0.1 1 BASE CASE Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 825.86 Amps 128.8 128.9 0.1 1 BASE CASE Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 825.86 Amps 185.5 185.6 0.1 1 BASE CASE Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 825.86 Amps 183.9 184.0 0.1 1 BASE CASE PLACER -PLACER 115.00/ 60.00kV Bk#1 77 MVA 105.4 105.4 0.0 1 BASE CASE ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 243.31 Amps 105.5 104.8 -0.7 1 BASE CASE MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 825.11 Amps 107.9 107.7 -0.2 1 BASE CASE LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1484.04 Amps 110.8 111.1 0.3 1 BASE CASE LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 441.8 Amps 102.8 102.9 0.0 1 BASE CASE LAKE -LAKE 2 230.00/ 69.00kV Bk#1 160 MVA 101.1 101.1 0.0 1 BASE CASE E.NICOLS-E.NICOLS 115.00/ 60.00kV Bk#2 58.5 MVA 123.8 123.8 0.0 1 BASE CASE DELTA -CASCADE 115.00kV Ckt#1 Sec# 1 416.7 Amps 98.8 98.7 -0.1 1 BASE CASE COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 675.25 Amps 134.1 134.8 0.8 1 BASE CASE CHWCGNJT-CHWCGN 115.00kV Ckt#1 Sec# 1 296.21 Amps 101.6 101.6 0.0 1 BASE CASE CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 376.03 Amps 104.2 104.4 0.1 1 BASE CASE BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 675.25 Amps 146.1 146.7 0.6

1 BASE CASE BELLTA T-BLLTA 1M 13.80/ 230.00kV Bk#1 40 MVA 100.0 100.0 0.0

2013 Summer Off-Peak 1 BASE CASE WHEELBR -COTWDPGE 115.00kV Ckt#1 Sec# 1 441.8 Amps 100.9 100.9 0.0

Page 315: To determine the system impacts caused by the Project

C-2 GWF Henrietta SISAppendix C

# Outage

Description Facility Rating Unit

PU Flow

PU Flow

% Change

1 BASE CASE WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 675.25 Amps 108.5 109.2 0.7

1 BASE CASE SANGER -MC CALL 115.00kV Ckt#3 Sec# 1 823.35 Amps 108.7 108.7 0.0

1 BASE CASE LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1484.04 Amps 118.7 119.3 0.5

1 BASE CASE COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 675.25 Amps 103.2 103.9 0.7

2013 Spring Peak 1 BASE CASE WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 675.25 Amps 122.4 123.5 1.0

1 BASE CASE WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 675.25 Amps 121.9 122.7 0.8

1 BASE CASE STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 675.25 Amps 103.1 103.8 0.7

1 BASE CASE STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 675.25 Amps 113.2 113.9 0.7 1 BASE CASE STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 743.02 Amps 110.4 111.1 0.7 1 BASE CASE Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 825.86 Amps 101.4 101.6 0.1

1 BASE CASE Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 825.86 Amps 101.4 101.6 0.1 1 BASE CASE Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 825.86 Amps 101.4 101.6 0.1

1 BASE CASE Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 825.86 Amps 101.4 101.6 0.1

1 BASE CASE Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 825.86 Amps 101.4 101.6 0.1

1 BASE CASE COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 675.25 Amps 112.8 113.6 0.8

1 BASE CASE BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 675.25 Amps 132.8 133.6 0.8

1 BASE CASE BELLTA T-BLLTA 1M 13.80/ 230.00kV Bk#1 40 MVA 99.7 100.0 0.3

Page 316: To determine the system impacts caused by the Project

C-3 GWF Henrietta SISAppendix C

Table C-2: Category “B” Overloads

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change

2013 Summer Peak 131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 136.7 137.9 1.2

285 Open Xfmr GATES 230/GATES 500 #11 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 134.9 136.2 1.2 2 Open Line WESTLEY 230-LOSBANOS 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.3 131.5 1.2

185 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.6 126.4 0.8

166 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.4 125.5 1.1

196 Open Line KEARNEY 230-HERNDON 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.9 125.0 1.1 171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 129 MW Dropped : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.1 123.9 0.7

152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.3 123.4 1.0

422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.7 121.7 1.0

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.4 120.1 0.8

LB-Gts1

Los Banos - Gates #1 500-kV WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.9 119.6 0.7

Tsl-LB Tracy-Los Banos 500-kV WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.9 119.6 0.7 Tcy-LB Tracy-Los Banos 500-kV WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.3 118.0 0.7

189 Open Line HELM 230-MC CALL 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.0 117.7 0.7 291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.0 117.7 0.7 386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 129 MW Dropped : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.2 117.0 0.8

62 Open Line DS AMIGO 230-PANOCHE 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.2 116.8 0.7 12 Open Line PANOCHE 230-HELM 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.1 116.8 0.7

Page 317: To determine the system impacts caused by the Project

C-4 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.0 116.8 0.8

3 Open Line MOSSLND2 230-PANOCHE 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.8 116.7 0.9 370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.7 0.8

5 Open Line LOSBANOS 230-PANOCHE 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.6 0.7 255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line

OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 19 MW 3.8 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 7.7 MW 1.5 MVAR Drop : Drop Load at BIOLA 70 #1 : 22 MW 4.4 MVAR Dropped : Drop Load at BOWLES 70 #1 : 18.5 MW 3.7 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.8 116.6 0.8

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.6 116.3 0.7 202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

HENTAP2 230-GATES 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.1 0.6

26 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 24.9 MW 5 MVAR Dro : Drop Load at GALLO 115 #1 : 4.3 MW 3.6 MVAR Dropp :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.9 115.6 0.6

7 Open Line LOSBANOS 230-DS AMIGO 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.8 115.4 0.7 24 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY

T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 11.7 MW 10.3 MVAR D : Drop Load at CRESSEY 115 #1 : 19.3 MW 3.9 MVAR Dr : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.7 115.3 0.6

233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.6 115.2 0.6

Page 318: To determine the system impacts caused by the Project

C-5 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change25 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line

CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 7.1 MW 4.9 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.1 114.7 0.6

207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 26.5 MW 5.3 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.1 114.7 0.6

214 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Open Line CLOVISJ2 115-KERCKHF2 115 #1 : Open Line CLOVISJ2 115-SANGER 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.0 114.7 0.6

264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP 70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.6 MW 4.2 MVAR Drop : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.0 114.7 0.6

67 Open Xfmr WILSON A 115/WILSON 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.7 114.4 0.6 68 Open Xfmr WILSON B 115/WILSON 230 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.7 114.3 0.6

239 Open Line KINGSBRG 115-GAURD J1 115 #1 : Open Line GAURD J1 115-MC CALL 115 #1 : Open Line GAURD J1 115-GAURD J2 115 #1 : Open Line GAURD J2 115-GRDN GLS 115 #1 : Drop Load at GRDN GLS 115 #1 : 3.5 MW 1.1 MVAR Dr : Drop Load at KINGSBRG 115 #3 : 33 MW 6.6 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.6 114.3 0.6

58 Open Line BORDEN 70-CASSIDY 70 #1 : Open Line CASSIDY 70-RIVERROC 70 #1 : Open Line RIVERROC 70-COPPRMNE 70 #1 : Drop Load at CASSIDY 70 #1 : 14.5 MW 2.9 MVAR Dro : Drop

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.5 114.2 0.7

Page 319: To determine the system impacts caused by the Project

C-6 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeLoad at RIVERROC 70 #1 : 2 MW 1.8 MVAR Dropp :

280 Open Xfmr HERNDON 230/HERNDON 115 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.5 114.1 0.6 279 Open Xfmr HERNDON 230/HERNDON 115 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.5 114.1 0.7

54 Open Line CANANDGA 70-TRIGO J 70 #1 : Open Line CANANDGA 70-GLASS 70 #1 : Open Line TRIGO J 70-BONITA 70 #1 : Open Line TRIGO J 70-TRIGO 70 #1 : Open Line TRIGO 70-MADERA 70 #1 : Open Line TRIGO 70-EL PECO 70 #1 : Drop Load at CANANDGA 70 #1 : 7.6 MW 5.7 MVAR Dro : Drop Load at BONITA 70 #1 : 14.6 MW 2.9 MVAR Drop : Drop Load at EL PECO 70 #1 : 10 MW 2 MVAR Dropped : Drop Load at EL PECO 70 #2 : 7.3 MW 1.4 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.4 114.1 0.7

248 Open Line BIOLA 70-OLDKERN 70 #1 : Drop Load at BIOLA 70 #1 : 22 MW 4.4 MVAR Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.4 114.1 0.6

289 Open Xfmr KINGSBRG 115/KNGLOBUS 70 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.4 114.1 0.6 131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 148.6 149.1 0.5

285 Open Xfmr GATES 230/GATES 500 #11 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 140.1 140.8 0.6 185 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 129 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 136.5 137.3 0.8

166 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 136.0 136.4 0.3

196 Open Line KEARNEY 230-HERNDON 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.6 132.0 0.4 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.8 131.2 0.4

Tsl-LB Tracy-Los Banos 500-kV WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.6 130.4 0.7 11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.3 129.0 0.7

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.6 128.2 0.7

291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.3 127.9 0.6

Page 320: To determine the system impacts caused by the Project

C-7 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change3 Open Line MOSSLND2 230-PANOCHE 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.7 127.5 0.7

189 Open Line HELM 230-MC CALL 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.6 127.3 0.7 255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line

OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 19 MW 3.8 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 7.7 MW 1.5 MVAR Drop : Drop Load at BIOLA 70 #1 : 22 MW 4.4 MVAR Dropped : Drop Load at BOWLES 70 #1 : 18.5 MW 3.7 MVAR Drop :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.6 127.1 0.5

12 Open Line PANOCHE 230-HELM 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.1 126.8 0.7 415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 126.8 0.6

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.9 126.6 0.7

26 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 24.9 MW 5 MVAR Dro : Drop Load at GALLO 115 #1 : 4.3 MW 3.6 MVAR Dropp :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.9 126.5 0.7

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.8 126.5 0.8

62 Open Line DS AMIGO 230-PANOCHE 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.8 126.5 0.7 24 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY

T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 11.7 MW 10.3 MVAR D : Drop Load at CRESSEY 115 #1 : 19.3 MW 3.9 MVAR Dr : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.4 0.7

5 Open Line LOSBANOS 230-PANOCHE 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.4 0.7 6 Open Line LOSBANOS 230-PANOCHE 230 #2 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.5 126.2 0.7

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.2 0.5

233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.4 126.1 0.7

Page 321: To determine the system impacts caused by the Project

C-8 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangePNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

25 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 7.1 MW 4.9 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.2 125.9 0.7

207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 26.5 MW 5.3 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.2 125.9 0.7

264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP 70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.6 MW 4.2 MVAR Drop : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.1 125.8 0.7

358 Open Line CASSIDY 70-RIVERROC 70 #1 : Open Line CASSIDY 70-BORDEN 70 #1 : Open Line RIVERROC 70-COPPRMNE 70 #1 : Drop Load at CASSIDY 70 #1 : 14.5 MW 2.9 MVAR Dro : Drop Load at RIVERROC 70 #1 : 2 MW 1.8 MVAR Dropp : Drop Generator at FRIANTDM 6.6 #2: 14.7 MW Dropped :

TVY VLLY-REEDLEY 70.00kV Ckt#1 Sec# 1 297.75 Amps 128.3 128.2 -0.1

70 Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Open Line ORO LOMA 115-DFSTP 115 #1 : Open Line ORO LOMA 115-EL NIDO 115 #1 :

TOMATAK -MENDOTA 70.00kV Ckt#1 Sec# 1 395.9 Amps 104.7 105.1 0.3

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 119.9 119.7 -0.2

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 118.5 118.3 -0.2

Page 322: To determine the system impacts caused by the Project

C-9 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeKERCKHOF 13.8 #1: 129 MW Dropped :

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 118.1 117.9 -0.2

428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 118.0 117.8 -0.2

204 Open Line GATES 230-MORROBAY 230 #1 : TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 117.8 117.6 -0.2 204 Open Line GATES 230-MORROBAY 230 #1 : TEMBLOR -BELRIDGE 115.00kV Ckt#1 Sec# 1 743.02 Amps 100.4 100.4 0.0 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : TEMBLOR -BELRIDGE 115.00kV Ckt#1 Sec# 1 743.02 Amps 100.3 100.4 0.0

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

TEMBLOR -BELRIDGE 115.00kV Ckt#1 Sec# 1 743.02 Amps 100.3 100.3 0.0

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

TEMBLOR -BELRIDGE 115.00kV Ckt#1 Sec# 1 743.02 Amps 100.1 100.1 0.0

128 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 166.7 167.7 0.9

165 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 166.2 167.1 0.9

16 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 161.4 162.4 0.9

184 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 157.1 157.8 0.7

146 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.8 130.5 0.7

285 Open Xfmr GATES 230/GATES 500 #11 : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.1 109.9 0.8 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.6 0.6

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.5 109.1 0.5

196 Open Line KEARNEY 230-HERNDON 230 #1 : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 106.7 0.6 152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.4 106.0 0.7

Page 323: To determine the system impacts caused by the Project

C-10 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeEXCHQUER 13.8 #1: 94.5 MW Droppe :

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.4 104.9 0.5

160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.9 104.4 0.5

107 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 7.1 MW 4.9 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.5 0.5

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.6 103.2 0.7 386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 129 MW Dropped : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.5 103.1 0.6

415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.6 103.0 0.4

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.2 102.6 0.5

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.5 102.1 0.5

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.3 101.7 0.4

106 Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line CERTAN T 115-LE GRAND 115 #1 : Open Line CERTAN T 115-CERTANJ2 115 #1 : Open Line CERTANJ2 115-CHWCGNJT 115 #1 : Open Line CHWCGNJT 115-CERTTEED 115 #1 : Open Line CHWCGNJT 115-CHWCGN 115 #1 : Open Line CHWCGN 115-CHWCHLA2 115 #1 : Open Xfmr CHWCGN 115/CHOWCOGN 13.8 #1 : Open Xfmr CHWCHLA2 115/CHWCHLA2 13.8 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.0 101.4 0.5

Page 324: To determine the system impacts caused by the Project

C-11 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeDrop Load at CERTTEED 115 #1 : 9.9 MW 6.9 MVAR Dr :

28 Open Line LE GRAND 115-WILSON A 115 #1 : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.9 101.4 0.5 161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.8 101.3 0.5

116 Open Line CANANDGA 70-TRIGO J 70 #1 : Open Line CANANDGA 70-GLASS 70 #1 : Open Line TRIGO J 70-BONITA 70 #1 : Open Line TRIGO J 70-TRIGO 70 #1 : Open Line TRIGO 70-MADERA 70 #1 : Open Line TRIGO 70-EL PECO 70 #1 : Drop Load at CANANDGA 70 #1 : 7.6 MW 5.7 MVAR Dro : Drop Load at BONITA 70 #1 : 14.6 MW 2.9 MVAR Drop : Drop Load at EL PECO 70 #1 : 10 MW 2 MVAR Dropped : Drop Load at EL PECO 70 #2 : 7.3 MW 1.4 MVAR Drop :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.7 101.2 0.4

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.3 100.8 0.4

114 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 8.7 MW 1.7 MVAR Dro : Drop Load at NEWHALL 115 #3 : 10.8 MW 2.1 MVAR Dr : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at MADERA_G 13.8 #1 : 28.6 MW Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.2 100.6 0.4

169 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.9 100.3 0.5

374 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.9 100.3 0.4

155 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.8 100.2 0.5

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.8 100.2 0.5

Page 325: To determine the system impacts caused by the Project

C-12 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.6 100.2 0.6

156 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.6 100.1 0.5

115 Open Line PANOCHET 115-MENDOTA 115 #1 : Open Line PANOCHET 115-PANOCHE 115 #1 : Drop Generator at DG_PAN1 13.8 #1 : 49 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.6 100.1 0.4

128 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 177.9 178.9 0.9

165 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 177.3 178.2 0.9

16 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 172.5 173.5 0.9

184 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 168.2 168.9 0.7

146 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 140.7 141.4 0.7

285 Open Xfmr GATES 230/GATES 500 #11 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.2 120.9 0.8 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.1 120.7 0.6

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.6 120.1 0.5

196 Open Line KEARNEY 230-HERNDON 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.1 117.7 0.6 152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 117.1 0.7

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.5 116.0 0.6

Page 326: To determine the system impacts caused by the Project

C-13 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.9 115.5 0.5

107 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 7.1 MW 4.9 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.0 114.4 0.5

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.6 114.3 0.6 415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.7 114.1 0.4

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.5 114.0 0.5

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.2 113.6 0.5

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.5 113.1 0.5

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.3 112.8 0.4

106 Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line CERTAN T 115-LE GRAND 115 #1 : Open Line CERTAN T 115-CERTANJ2 115 #1 : Open Line CERTANJ2 115-CHWCGNJT 115 #1 : Open Line CHWCGNJT 115-CERTTEED 115 #1 : Open Line CHWCGNJT 115-CHWCGN 115 #1 : Open Line CHWCGN 115-CHWCHLA2 115 #1 : Open Xfmr CHWCGN 115/CHOWCOGN 13.8 #1 : Open Xfmr CHWCHLA2 115/CHWCHLA2 13.8 #1 : Drop Load at CERTTEED 115 #1 : 9.9 MW 6.9 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.9 112.4 0.5

28 Open Line LE GRAND 115-WILSON A 115 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.9 112.3 0.5 161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.8 112.3 0.5

Page 327: To determine the system impacts caused by the Project

C-14 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change116 Open Line CANANDGA 70-TRIGO J 70 #1 : Open Line

CANANDGA 70-GLASS 70 #1 : Open Line TRIGO J 70-BONITA 70 #1 : Open Line TRIGO J 70-TRIGO 70 #1 : Open Line TRIGO 70-MADERA 70 #1 : Open Line TRIGO 70-EL PECO 70 #1 : Drop Load at CANANDGA 70 #1 : 7.6 MW 5.7 MVAR Dro : Drop Load at BONITA 70 #1 : 14.6 MW 2.9 MVAR Drop : Drop Load at EL PECO 70 #1 : 10 MW 2 MVAR Dropped : Drop Load at EL PECO 70 #2 : 7.3 MW 1.4 MVAR Drop :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.7 112.2 0.4

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.4 111.8 0.4

114 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 8.7 MW 1.7 MVAR Dro : Drop Load at NEWHALL 115 #3 : 10.8 MW 2.1 MVAR Dr : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at MADERA_G 13.8 #1 : 28.6 MW Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.2 111.6 0.4

169 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.9 111.3 0.5

374 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.9 111.3 0.4

155 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.8 111.2 0.5

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.8 111.2 0.4

153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.6 111.2 0.6

156 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.6 111.1 0.5

115 Open Line PANOCHET 115-MENDOTA 115 #1 : Open Line PANOCHET 115-PANOCHE 115 #1 : Drop Generator at DG_PAN1 13.8 #1 : 49 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.6 111.1 0.4

Page 328: To determine the system impacts caused by the Project

C-15 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change189 Open Line HELM 230-MC CALL 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.4 110.8 0.5 157 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.2 110.7 0.5

207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 26.5 MW 5.3 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.2 110.6 0.5

111 Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.0 110.4 0.4

429 Open Line GATES 230-ARCO 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.9 110.3 0.4

430 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.8 110.2 0.4

291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.7 110.1 0.4 112 Open Line LE GRNDJ 115-WILSON B 115 #1 : Open Line LE

GRNDJ 115-EL NIDO 115 #1 : Open Line EL NIDO 115-ORO LOMA 115 #1 : Drop Load at EL NIDO 115 #1 : 12.6 MW 2.5 MVAR Dr : Drop Load at EL NIDO 115 #2 : 15.2 MW 3 MVAR Drop : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.7 110.1 0.4

413 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.6 110.1 0.4

414 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.6 110.1 0.4

154 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.5 109.9 0.5

423 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.5 109.9 0.4

377 Open Line GATES 230-ARCO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.4 109.9 0.5

Page 329: To determine the system impacts caused by the Project

C-16 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change378 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.3 109.7 0.4

117 Open Line MCSWAINJ 70-MC SWAIN 70 #1 : Open Line MCSWAINJ 70-MRCDFLLS 70 #1 : Open Line MCSWAINJ 70-EXCHEQUR 70 #1 : Open Xfmr MC SWAIN 70/MCSWAIN 9.11 #1 : Drop Generator at MCSWAIN 9.11 #1 : 9 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.3 109.7 0.4

353 Open Line SMYRNA 115-MCKIBBEN 115 #1 : Open Line MCKIBBEN 115-SEMITRPJ 115 #1 : Open Line SEMITRPJ 115-GANSO 115 #1 : Open Line GANSO 115-MIDWAY 115 #1 : Drop Load at GANSO 115 #1 : 3.9 MW 0.7 MVAR Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.2 109.7 0.4

162 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.2 109.6 0.5

163 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.2 109.6 0.5

113 Open Line WILSON B 115-EL CAPTN 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.2 109.6 0.4

41 Open Line PANOCHEJ 115-PANOCHE 115 #1 : Open Line PANOCHEJ 115-HAMMONDS 115 #1 : Open Line PANOCHEJ 115-OXFRDJCT 115 #1 : Open Line HAMMONDS 115-DFSTP 115 #1 : Open Line DFSTP 115-ORO LOMA 115 #1 : Open Line DFSTP 115-DFS 115 #1 : Open Line OXFRDJCT 115-OXFORD 115 #1 : Open Line OXFRDJCT 115-WSTLDJCT 115 #1 : Open Line WSTLDJCT 115-WSTLD1RA 115 #1 : Open Line WSTLDJCT 115-LUISJCT 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.6 0.6

27 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Drop Generator at EXCHQUER 13.8 #1 : 94.5 MW Dropp : Drop Load at MARIPOS2 70 #**: 9.1 MW 1.8 MVAR Dro :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.1 109.5 0.4

81 Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.5 0.5 108 Open Line ATWATER 115-CASTLE 115 #1 : Open Line CASTLE

115-EL CAPTN 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.5 0.4

158 Open Line LOSBANOS 230-SN LS PP 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.5 0.4

159 Open Line LOSBANOS 230-SN LS PP 230 #2 : Drop Generator at STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.5 0.4

Page 330: To determine the system impacts caused by the Project

C-17 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeEXCHQUER 13.8 #1: 94.5 MW Droppe :

12 Open Line PANOCHE 230-HELM 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.5 0.5 371 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN

T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.4 0.4

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.9 109.4 0.6

118 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 7 MW 1.4 MVAR Dropped : Drop Load at ARBURUA 70 #1 : 3.8 MW 1.8 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 9.6 MW 1.9 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.9 109.4 0.4

255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 19 MW 3.8 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 7.7 MW 1.5 MVAR Drop : Drop Load at BIOLA 70 #1 : 22 MW 4.4 MVAR Dropped : Drop Load at BOWLES 70 #1 : 18.5 MW 3.7 MVAR Drop :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.9 109.4 0.5

427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.4 108.9 0.5

428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.2 108.7 0.5

70 Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Open Line ORO LOMA 115-DFSTP 115 #1 : Open Line ORO LOMA 115-EL NIDO 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.0 108.6 0.6

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.1 108.6 0.4

236 Open Line HERNDON 115-CHLDHOSP 115 #1 : Open Line CHLDHOSP 115-WOODWARD 115 #1 : Drop Load at CHLDHOSP STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.1 108.5 0.5

Page 331: To determine the system impacts caused by the Project

C-18 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change115 #1 : 3.5 MW 1.5 MVAR Dr :

62 Open Line DS AMIGO 230-PANOCHE 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.1 108.5 0.5 66 Open Xfmr EXCHEQUR 115/EXCHEQUR 70 #1 : Open Line

EXCHEQUR 70-MARIPOS2 70 #1 : Open Line EXCHEQUR 70-BER VLLY 70 #1 : Open Line EXCHEQUR 70-MCSWAINJ 70 #1 : Drop Load at MARIPOS2 70 #1 : 9.1 MW 1.8 MVAR Dro : Drop Load at MARIPOS2 70 #2 : 9.5 MW 1.9 MVAR Dro : Close Line MARIPOS2 70-BRCEBG J 70 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.0 108.5 0.5

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.0 108.4 0.4

5 Open Line LOSBANOS 230-PANOCHE 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.4 0.5 3 Open Line MOSSLND2 230-PANOCHE 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.4 0.6

233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.3 0.4

280 Open Xfmr HERNDON 230/HERNDON 115 #2 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.3 0.4 279 Open Xfmr HERNDON 230/HERNDON 115 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.3 0.4

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.3 0.5 109 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY

T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 11.7 MW 10.3 MVAR D : Drop Load at CRESSEY 115 #1 : 19.3 MW 3.9 MVAR Dr : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.2 0.4

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.2 0.4

110 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 24.9 MW 5 MVAR Dro : Drop Load at GALLO 115

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.7 108.1 0.4

Page 332: To determine the system impacts caused by the Project

C-19 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change#1 : 4.3 MW 3.6 MVAR Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

75 Open Xfmr MENDOTA 70/MENDOTA 115 #1 : Open Line MENDOTA 115-MADERAPR 115 #1 : Open Line MENDOTA 115-PANOCHET 115 #1 : Drop Load at MENDOTA 115 #1 : 24.9 MW 5 MVAR Drop :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 107.9 0.4

37 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 8.7 MW 1.7 MVAR Dro : Drop Load at NEWHALL 115 #3 : 10.8 MW 2.1 MVAR Dr : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at MADERA_G 13.8 #1 : 28.6 MW Dropp :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 107.9 0.4

264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP 70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.6 MW 4.2 MVAR Drop : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 107.9 0.4

7 Open Line LOSBANOS 230-DS AMIGO 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 107.8 0.5 214 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Open Line CLOVISJ2

115-KERCKHF2 115 #1 : Open Line CLOVISJ2 115-SANGER 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 107.8 0.4

58 Open Line BORDEN 70-CASSIDY 70 #1 : Open Line CASSIDY 70-RIVERROC 70 #1 : Open Line RIVERROC 70-COPPRMNE 70 #1 : Drop Load at CASSIDY 70 #1 : 14.5 MW 2.9 MVAR Dro : Drop Load at RIVERROC 70 #1 : 2 MW 1.8 MVAR Dropp :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.3 107.7 0.4

127 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 166.0 167.0 1.0

164 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 165.4 166.4 1.0

Page 333: To determine the system impacts caused by the Project

C-20 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change15 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2

230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 160.7 161.6 0.9

183 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 156.4 157.1 0.7

145 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 129.0 129.8 0.8

285 Open Xfmr GATES 230/GATES 500 #11 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 119.8 120.6 0.8 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 119.7 120.3 0.6

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 119.1 119.7 0.6

196 Open Line KEARNEY 230-HERNDON 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 116.4 117.1 0.7 152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 115.7 116.4 0.7

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 114.6 115.2 0.6

160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 114.0 114.6 0.6

107 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 7.1 MW 4.9 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 113.1 113.5 0.5

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 112.6 113.3 0.7 415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 112.7 113.1 0.5

Page 334: To determine the system impacts caused by the Project

C-21 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 129 MW Dropped : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 112.5 113.1 0.6

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 112.1 112.6 0.5

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 111.4 112.0 0.6

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 111.2 111.7 0.5

106 Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line CERTAN T 115-LE GRAND 115 #1 : Open Line CERTAN T 115-CERTANJ2 115 #1 : Open Line CERTANJ2 115-CHWCGNJT 115 #1 : Open Line CHWCGNJT 115-CERTTEED 115 #1 : Open Line CHWCGNJT 115-CHWCGN 115 #1 : Open Line CHWCGN 115-CHWCHLA2 115 #1 : Open Xfmr CHWCGN 115/CHOWCOGN 13.8 #1 : Open Xfmr CHWCHLA2 115/CHWCHLA2 13.8 #1 : Drop Load at CERTTEED 115 #1 : 9.9 MW 6.9 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.8 111.3 0.5

28 Open Line LE GRAND 115-WILSON A 115 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.7 111.2 0.5 161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.6 111.2 0.5

116 Open Line CANANDGA 70-TRIGO J 70 #1 : Open Line CANANDGA 70-GLASS 70 #1 : Open Line TRIGO J 70-BONITA 70 #1 : Open Line TRIGO J 70-TRIGO 70 #1 : Open Line TRIGO 70-MADERA 70 #1 : Open Line TRIGO 70-EL PECO 70 #1 : Drop Load at CANANDGA 70 #1 : 7.6 MW 5.7 MVAR Dro : Drop Load at BONITA 70 #1 : 14.6 MW 2.9 MVAR Drop : Drop Load at EL PECO 70 #1 : 10 MW 2 MVAR Dropped : Drop Load at EL PECO 70 #2 : 7.3 MW 1.4 MVAR Drop :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.6 111.1 0.5

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.2 110.6 0.5

114 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 8.7 MW 1.7 MVAR Dro : Drop Load at NEWHALL 115 #3 : 10.8 MW 2.1 MVAR Dr : Drop Load at

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.9 110.4 0.5

Page 335: To determine the system impacts caused by the Project

C-22 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeMADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at MADERA_G 13.8 #1 : 28.6 MW Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

169 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.6 110.1 0.5

374 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.6 110.1 0.5

155 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.5 110.0 0.5

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.5 110.0 0.5

153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.3 110.0 0.7

156 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.4 109.9 0.5

115 Open Line PANOCHET 115-MENDOTA 115 #1 : Open Line PANOCHET 115-PANOCHE 115 #1 : Drop Generator at DG_PAN1 13.8 #1 : 49 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.3 109.8 0.5

189 Open Line HELM 230-MC CALL 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.1 109.6 0.5 157 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.9 109.4 0.5

207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 26.5 MW 5.3 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.9 109.4 0.5

111 Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.7 109.1 0.5

Page 336: To determine the system impacts caused by the Project

C-23 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change429 Open Line GATES 230-ARCO 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.5 109.0 0.5

430 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.4 108.9 0.5

291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.4 108.8 0.5 112 Open Line LE GRNDJ 115-WILSON B 115 #1 : Open Line LE

GRNDJ 115-EL NIDO 115 #1 : Open Line EL NIDO 115-ORO LOMA 115 #1 : Drop Load at EL NIDO 115 #1 : 12.6 MW 2.5 MVAR Dr : Drop Load at EL NIDO 115 #2 : 15.2 MW 3 MVAR Drop : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.3 108.8 0.5

413 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.2 108.7 0.5

414 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.2 108.7 0.5

154 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.1 108.6 0.5

377 Open Line GATES 230-ARCO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.0 108.5 0.5

423 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.1 108.5 0.4

117 Open Line MCSWAINJ 70-MC SWAIN 70 #1 : Open Line MCSWAINJ 70-MRCDFLLS 70 #1 : Open Line MCSWAINJ 70-EXCHEQUR 70 #1 : Open Xfmr MC SWAIN 70/MCSWAIN 9.11 #1 : Drop Generator at MCSWAIN 9.11 #1 : 9 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.9 108.4 0.5

378 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.9 108.4 0.5

353 Open Line SMYRNA 115-MCKIBBEN 115 #1 : Open Line MCKIBBEN 115-SEMITRPJ 115 #1 : Open Line SEMITRPJ 115-GANSO 115 #1 : Open Line GANSO 115-MIDWAY 115 #1 : Drop Load at GANSO 115 #1 : 3.9 MW 0.7 MVAR Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.8 108.3 0.5

162 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.8 108.3 0.5

Page 337: To determine the system impacts caused by the Project

C-24 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeEXCHQUER 13.8 #1: 94.5 MW Droppe :

163 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.8 108.3 0.5

113 Open Line WILSON B 115-EL CAPTN 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.7 108.2 0.5

41 Open Line PANOCHEJ 115-PANOCHE 115 #1 : Open Line PANOCHEJ 115-HAMMONDS 115 #1 : Open Line PANOCHEJ 115-OXFRDJCT 115 #1 : Open Line HAMMONDS 115-DFSTP 115 #1 : Open Line DFSTP 115-ORO LOMA 115 #1 : Open Line DFSTP 115-DFS 115 #1 : Open Line OXFRDJCT 115-OXFORD 115 #1 : Open Line OXFRDJCT 115-WSTLDJCT 115 #1 : Open Line WSTLDJCT 115-WSTLD1RA 115 #1 : Open Line WSTLDJCT 115-LUISJCT 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.5 108.2 0.7

27 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Drop Generator at EXCHQUER 13.8 #1 : 94.5 MW Dropp : Drop Load at MARIPOS2 70 #**: 9.1 MW 1.8 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.6 108.1 0.5

158 Open Line LOSBANOS 230-SN LS PP 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.6 108.1 0.5

159 Open Line LOSBANOS 230-SN LS PP 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.6 108.1 0.5

81 Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.6 108.1 0.5 108 Open Line ATWATER 115-CASTLE 115 #1 : Open Line CASTLE

115-EL CAPTN 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.6 108.1 0.5

12 Open Line PANOCHE 230-HELM 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.6 108.1 0.5 371 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN

T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.6 108.1 0.5

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.4 108.0 0.6

Page 338: To determine the system impacts caused by the Project

C-25 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line

OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 19 MW 3.8 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 7.7 MW 1.5 MVAR Drop : Drop Load at BIOLA 70 #1 : 22 MW 4.4 MVAR Dropped : Drop Load at BOWLES 70 #1 : 18.5 MW 3.7 MVAR Drop :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.5 108.0 0.5

118 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 7 MW 1.4 MVAR Dropped : Drop Load at ARBURUA 70 #1 : 3.8 MW 1.8 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 9.6 MW 1.9 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.5 108.0 0.5

427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.9 107.4 0.5

428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.7 107.2 0.5

70 Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Open Line ORO LOMA 115-DFSTP 115 #1 : Open Line ORO LOMA 115-EL NIDO 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.5 107.1 0.7

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.6 107.1 0.5

236 Open Line HERNDON 115-CHLDHOSP 115 #1 : Open Line CHLDHOSP 115-WOODWARD 115 #1 : Drop Load at CHLDHOSP 115 #1 : 3.5 MW 1.5 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.6 107.1 0.5

62 Open Line DS AMIGO 230-PANOCHE 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.5 107.0 0.5 66 Open Xfmr EXCHEQUR 115/EXCHEQUR 70 #1 : Open Line

EXCHEQUR 70-MARIPOS2 70 #1 : Open Line EXCHEQUR 70-BER VLLY 70 #1 : Open Line EXCHEQUR 70-MCSWAINJ 70 #1 : Drop Load at MARIPOS2 70 #1 : 9.1 MW 1.8 MVAR Dro : Drop Load at MARIPOS2 70 #2 : 9.5 MW 1.9 MVAR Dro : Close Line MARIPOS2 70-BRCEBG J 70 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.5 107.0 0.5

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.4 106.9 0.5

5 Open Line LOSBANOS 230-PANOCHE 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.4 106.9 0.5

Page 339: To determine the system impacts caused by the Project

C-26 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change3 Open Line MOSSLND2 230-PANOCHE 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.2 106.9 0.7

233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.4 106.9 0.5

280 Open Xfmr HERNDON 230/HERNDON 115 #2 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.3 106.8 0.5 279 Open Xfmr HERNDON 230/HERNDON 115 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.3 106.8 0.5

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.3 106.8 0.5 109 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY

T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 11.7 MW 10.3 MVAR D : Drop Load at CRESSEY 115 #1 : 19.3 MW 3.9 MVAR Dr : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.3 106.8 0.5

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.2 106.7 0.5

110 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 24.9 MW 5 MVAR Dro : Drop Load at GALLO 115 #1 : 4.3 MW 3.6 MVAR Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.2 106.6 0.5

75 Open Xfmr MENDOTA 70/MENDOTA 115 #1 : Open Line MENDOTA 115-MADERAPR 115 #1 : Open Line MENDOTA 115-PANOCHET 115 #1 : Drop Load at MENDOTA 115 #1 : 24.9 MW 5 MVAR Drop :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.9 106.4 0.5

37 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 8.7 MW 1.7 MVAR Dro : Drop Load at NEWHALL 115 #3 : 10.8 MW 2.1 MVAR Dr : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at MADERA_G 13.8 #1 : 28.6 MW Dropp :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.9 106.3 0.5

Page 340: To determine the system impacts caused by the Project

C-27 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP

70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.6 MW 4.2 MVAR Drop : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.8 106.3 0.5

7 Open Line LOSBANOS 230-DS AMIGO 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.8 106.3 0.5 214 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Open Line CLOVISJ2

115-KERCKHF2 115 #1 : Open Line CLOVISJ2 115-SANGER 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.8 106.3 0.5

58 Open Line BORDEN 70-CASSIDY 70 #1 : Open Line CASSIDY 70-RIVERROC 70 #1 : Open Line RIVERROC 70-COPPRMNE 70 #1 : Drop Load at CASSIDY 70 #1 : 14.5 MW 2.9 MVAR Dro : Drop Load at RIVERROC 70 #1 : 2 MW 1.8 MVAR Dropp :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.7 106.2 0.5

38 Open Line PANOCHET 115-MENDOTA 115 #1 : Open Line PANOCHET 115-PANOCHE 115 #1 : Drop Generator at DG_PAN1 13.8 #1 : 49 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.7 106.1 0.5

127 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 190.2 191.3 1.0

164 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 189.6 190.6 1.1

15 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 184.5 185.6 1.0

183 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 180.0 180.7 0.7

285 Open Xfmr GATES 230/GATES 500 #11 : STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 140.7 141.6 0.9 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 140.6 141.2 0.7

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 140.0 140.7 0.6

152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 136.3 137.1 0.8

Page 341: To determine the system impacts caused by the Project

C-28 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeEXCHQUER 13.8 #1: 94.5 MW Droppe :

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 135.2 135.8 0.7

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 133.0 133.8 0.8 415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 133.1 133.6 0.5

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.5 132.0 0.5

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.4 130.9 0.5

429 Open Line GATES 230-ARCO 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.6 129.1 0.5

430 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.5 129.0 0.5

413 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.3 128.8 0.5

414 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.3 128.8 0.5

423 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.2 128.6 0.5

427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.9 127.4 0.6

428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

STOREY 1-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.6 127.2 0.6

361 Open Line MC CALL 115-WAHTOKE 115 #1 : Drop Generator at SANGERCO 9.11 #1: 37.5 MW Droppe :

SNGRJCT -SANGER 70.00kV Ckt#1 Sec# 1 395.9 Amps 104.2 104.2 0.0

361 Open Line MC CALL 115-WAHTOKE 115 #1 : Drop Generator at SANGERCO 9.11 #1: 37.5 MW Droppe :

REEDLEY -PIEDRA 1 115.00kV Ckt#1 Sec# 1 597.43 Amps 109.2 109.1 0.0

222 Open Line MC CALL 115-WAHTOKE 115 #1 : REEDLEY -PIEDRA 1 115.00kV Ckt#1 Sec# 1 597.43 Amps 102.4 102.4 0.0

Page 342: To determine the system impacts caused by the Project

C-29 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change362 Open Line MC CALL 115-WAHTOKE 115 #1 : Drop Generator at

KINGSRIV 13.8 #1: 47 MW Dropped : RAINBWTP-SANGER 115.00kV Ckt#1 Sec# 1 612.49 Amps 107.6 107.5 0.0

204 Open Line GATES 230-MORROBAY 230 #1 : Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 115.3 115.4 0.0 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 115.2 115.2 0.0

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 115.0 115.1 0.1

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 114.8 114.9 0.1

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.9 113.9 0.1

203 Open Line GATES 230-TEMPLETN 230 #1 : Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.6 113.7 0.0 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.5 113.6 0.1

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.4 113.4 0.1

391 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.2 113.2 0.1

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 112.2 112.3 0.1

285 Open Xfmr GATES 230/GATES 500 #11 : Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 111.1 111.5 0.4 204 Open Line GATES 230-MORROBAY 230 #1 : Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.3 101.2 -0.1 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.3 101.2 -0.1

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.2 101.1 0.0

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.1 101.0 0.0

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 100.7 100.6 -0.1

203 Open Line GATES 230-TEMPLETN 230 #1 : Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 100.2 100.2 0.0 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 100.2 100.2 0.0

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 100.1 100.1 0.0

Page 343: To determine the system impacts caused by the Project

C-30 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.9 130.0 0.1

391 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.7 129.8 0.1

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 128.9 128.9 0.1

285 Open Xfmr GATES 230/GATES 500 #11 : Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 128.1 128.5 0.4 1 Open Line WARNERVL 230-WILSON 230 #1 : Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 110.2 110.4 0.2

204 Open Line GATES 230-MORROBAY 230 #1 : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 182.9 182.9 0.0 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 182.7 182.8 0.0

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 182.6 182.6 0.0

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 182.4 182.4 0.0

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 181.4 181.5 0.0

203 Open Line GATES 230-TEMPLETN 230 #1 : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 178.7 178.8 0.1 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 178.6 178.7 0.0

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 178.5 178.5 0.1

391 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 178.3 178.3 0.0

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 177.3 177.4 0.0

285 Open Xfmr GATES 230/GATES 500 #11 : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 176.8 177.2 0.4 204 Open Line GATES 230-MORROBAY 230 #1 : Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.3 101.2 -0.1 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.3 101.2 -0.1

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.2 101.1 0.0

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.1 101.0 0.0

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 100.7 100.6 -0.1

Page 344: To determine the system impacts caused by the Project

C-31 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeHELMS 1 18 #1: 404 MW Dropped :

203 Open Line GATES 230-TEMPLETN 230 #1 : Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 100.2 100.2 0.0 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 100.2 100.2 0.0

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 100.1 100.1 0.0

204 Open Line GATES 230-MORROBAY 230 #1 : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 134.1 134.2 0.0 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 134.0 134.1 0.1

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 133.9 133.9 0.1

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 133.7 133.7 0.0

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 132.8 132.9 0.0

203 Open Line GATES 230-TEMPLETN 230 #1 : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 130.2 130.2 0.0 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 130.0 130.1 0.1

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.9 130.0 0.1

391 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.7 129.8 0.1

204 Open Line GATES 230-MORROBAY 230 #1 : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 181.4 181.5 0.0 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 181.3 181.4 0.0

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 181.2 181.2 0.0

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 180.9 181.0 0.1

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 180.0 180.1 0.0

203 Open Line GATES 230-TEMPLETN 230 #1 : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 177.3 177.4 0.1 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 177.2 177.3 0.1

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 177.1 177.1 0.1

Page 345: To determine the system impacts caused by the Project

C-32 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeEXCHQUER 13.8 #1: 94.5 MW Droppe :

391 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 176.8 176.9 0.0

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 175.9 176.0 0.0

285 Open Xfmr GATES 230/GATES 500 #11 : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 175.4 175.8 0.4 362 Open Line MC CALL 115-WAHTOKE 115 #1 : Drop Generator at

KINGSRIV 13.8 #1: 47 MW Dropped : PARLIER -SNGRJCT 70.00kV Ckt#1 Sec# 1 470.13 Amps 112.7 112.7 0.0

222 Open Line MC CALL 115-WAHTOKE 115 #1 : PARLIER -SNGRJCT 70.00kV Ckt#1 Sec# 1 470.13 Amps 101.8 101.8 0.0 285 Open Xfmr GATES 230/GATES 500 #11 : PANOCHE -DS AMIGO 230.00kV Ckt#1 Sec# 1 849.96 Amps 104.4 105.1 0.7 125 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line

MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 7 MW 1.4 MVAR Dropped : Drop Load at ARBURUA 70 #1 : 3.8 MW 1.8 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 9.6 MW 1.9 MVAR Dro : Drop Generator at ONEILPMP 9.11 #1: 0.5 MW Dropped :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 127.2 126.5 -0.8

44 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 7 MW 1.4 MVAR Dropped : Drop Load at ARBURUA 70 #1 : 3.8 MW 1.8 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 9.6 MW 1.9 MVAR Dro :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 127.1 126.4 -0.8

118 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 7 MW 1.4 MVAR Dropped : Drop Load at ARBURUA 70 #1 : 3.8 MW 1.8 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 9.6 MW 1.9 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 121.9 121.2 -0.8

285 Open Xfmr GATES 230/GATES 500 #11 : ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 100.9 101.3 0.3 1 Open Line WARNERVL 230-WILSON 230 #1 : ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 100.8 101.1 0.3

Page 346: To determine the system impacts caused by the Project

C-33 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change72 Open Xfmr LOS BANS 70/LOSBANOS 230 #4 : ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 100.9 100.4 -0.6 71 Open Xfmr LOS BANS 70/LOSBANOS 230 #3 : ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 100.4 99.8 -0.6

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 125.6 125.4 -0.2

391 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 124.1 123.9 -0.2

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 123.8 123.6 -0.2

427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 123.6 123.4 -0.2

203 Open Line GATES 230-TEMPLETN 230 #1 : MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 123.4 123.2 -0.2 1 Open Line WARNERVL 230-WILSON 230 #1 : MELONES -COTTLE A 230.00kV Ckt#1 Sec# 1 849.96 Amps 101.9 102.4 0.5

Tsl-LB Tracy-Los Banos 500-kV LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.9 110.3 0.4 1 Open Line WARNERVL 230-WILSON 230 #1 : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.8 107.4 0.5

Tcy-LB Tracy-Los Banos 500-kV LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 107.0 107.4 0.4 126 Open Line WARNERVL 230-WILSON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.4 107.0 0.5

Moss-LB

Moss Landing - Los Banos #1& #2 500-kV DLO LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.4 105.7 0.4

285 Open Xfmr GATES 230/GATES 500 #11 : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.8 105.4 0.6 151 Open Line WARNERVL 230-WILSON 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.7 105.2 0.6

170 Open Line WARNERVL 230-WILSON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 103.8 104.4 0.6

3 Open Line MOSSLND2 230-PANOCHE 230 #1 : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 100.9 101.5 0.6 128 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1

230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 100.9 101.4 0.5

16 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 100.8 101.4 0.5

15 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 99.9 100.4 0.6

Page 347: To determine the system impacts caused by the Project

C-34 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change127 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2

230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 99.9 100.4 0.5

165 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 99.5 100.1 0.5

153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 99.4 100.0 0.6

128 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 121.1 121.5 0.4

16 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 116.5 116.8 0.3

146 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 115.7 115.8 0.1

127 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 114.3 114.6 0.3

145 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 110.4 110.6 0.2

15 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 109.9 110.2 0.3

69 Open Xfmr MERCED 115/MERCED 70 #2 : LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 107.5 107.5 0.0 401 Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1

230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 104.1 104.4 0.3

133 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 103.6 103.7 0.1

184 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 100.9 101.0 0.1

Page 348: To determine the system impacts caused by the Project

C-35 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change7.7 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

47 Open Line MERCED 70-MRCDFLLS 70 #1 : LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 100.4 100.5 0.0 421 Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1

230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 99.9 100.1 0.3

12 Open Line PANOCHE 230-HELM 230 #1 : HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 107.4 107.8 0.4 412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 106.2 106.7 0.5

161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 105.1 105.5 0.4

48 Open Line LIVNGSTN 70-LVNGSTNT 70 #1 : Open Line LVNGSTNT 70-CANAL 70 #1 : Open Line LVNGSTNT 70-SNTA NLA 70 #1 : Open Line SNTA NLA 70-CHEVPIPE 70 #1 : Open Line CHEVPIPE 70-LOS BANS 70 #1 : Drop Load at LIVNGSTN 70 #2 : 5.6 MW 1.1 MVAR Dro : Drop Load at SNTA NLA 70 #1 : 6.8 MW 1.3 MVAR Dro : Drop Load at SNTA NLA 70 #2 : 9.6 MW 1.9 MVAR Dro : Drop Load at CHEVPIPE 70 #1 : 0.6 MW 0.4 MVAR Dro :

DOS PALS-ORO LOMA 70.00kV Ckt#1 Sec# 1 282.08 Amps 115.0 114.3 -0.6

131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 138.9 139.3 0.4

285 Open Xfmr GATES 230/GATES 500 #11 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.4 131.1 0.6 185 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 129 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.9 127.7 0.8

166 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.4 126.7 0.3

196 Open Line KEARNEY 230-HERNDON 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.0 122.3 0.4 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 121.1 121.5 0.5

Tsl-LB Tracy-Los Banos 500-kV COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.9 120.7 0.7 11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.6 119.3 0.7

Page 349: To determine the system impacts caused by the Project

C-36 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 119 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.8 118.5 0.7

291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.6 118.2 0.6 3 Open Line MOSSLND2 230-PANOCHE 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.0 117.8 0.7

189 Open Line HELM 230-MC CALL 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.0 117.6 0.7 255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line

OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 19 MW 3.8 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 7.7 MW 1.5 MVAR Drop : Drop Load at BIOLA 70 #1 : 22 MW 4.4 MVAR Dropped : Drop Load at BOWLES 70 #1 : 18.5 MW 3.7 MVAR Drop :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.9 117.5 0.5

12 Open Line PANOCHE 230-HELM 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 117.1 0.7 415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.5 117.1 0.5

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.2 116.9 0.7

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.1 116.9 0.8

26 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 24.9 MW 5 MVAR Dro : Drop Load at GALLO 115 #1 : 4.3 MW 3.6 MVAR Dropp :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.2 116.9 0.7

62 Open Line DS AMIGO 230-PANOCHE 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.1 116.8 0.7 24 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY

T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 11.7 MW 10.3 MVAR D : Drop Load at CRESSEY 115 #1 : 19.3 MW 3.9 MVAR Dr : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.1 116.7 0.7

5 Open Line LOSBANOS 230-PANOCHE 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.0 116.7 0.7 6 Open Line LOSBANOS 230-PANOCHE 230 #2 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.5 0.7

Page 350: To determine the system impacts caused by the Project

C-37 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.0 116.5 0.5

233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.8 116.4 0.7

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.7 116.4 0.7

25 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 7.1 MW 4.9 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.6 116.2 0.7

207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 26.5 MW 5.3 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.6 116.2 0.7

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 116.2 -0.2 264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP

70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.6 MW 4.2 MVAR Drop : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.1 0.7

7 Open Line LOSBANOS 230-DS AMIGO 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.1 0.7 214 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Open Line CLOVISJ2

115-KERCKHF2 115 #1 : Open Line CLOVISJ2 115-SANGER 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D : Close Line

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.1 0.7

Page 351: To determine the system impacts caused by the Project

C-38 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeCLOVIS-1 115-CLOVIS-2 115 #1 :

165 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

CERTAN T-LE GRAND 115.00kV Ckt#1 Sec# 1 396.61 Amps 109.3 109.8 0.5

164 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

CERTAN T-LE GRAND 115.00kV Ckt#1 Sec# 1 396.61 Amps 104.0 104.4 0.4

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

CERTAN T-LE GRAND 115.00kV Ckt#1 Sec# 1 396.61 Amps 101.0 101.4 0.4

204 Open Line GATES 230-MORROBAY 230 #1 : CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 114.9 114.9 0.0 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 114.7 114.8 0.1

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 114.6 114.7 0.1

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 114.4 114.4 0.1

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.4 113.5 0.1

203 Open Line GATES 230-TEMPLETN 230 #1 : CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.2 113.3 0.0 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 119 MW Dropped : CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.1 113.2 0.1

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.0 113.0 0.1

391 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 112.7 112.8 0.0

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 111.8 111.9 0.1

285 Open Xfmr GATES 230/GATES 500 #11 : CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 110.6 111.1 0.4 145 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2

230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Drop Generator at HELMS 1 18 #1: 404 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 150.6 151.4 0.8

196 Open Line KEARNEY 230-HERNDON 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 137.1 137.9 0.7

Page 352: To determine the system impacts caused by the Project

C-39 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 134.6 135.3 0.6

107 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 7.1 MW 4.9 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 133.6 134.1 0.5

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 133.0 133.6 0.7

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.6 133.1 0.5

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.8 132.5 0.6

106 Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line CERTAN T 115-LE GRAND 115 #1 : Open Line CERTAN T 115-CERTANJ2 115 #1 : Open Line CERTANJ2 115-CHWCGNJT 115 #1 : Open Line CHWCGNJT 115-CERTTEED 115 #1 : Open Line CHWCGNJT 115-CHWCGN 115 #1 : Open Line CHWCGN 115-CHWCHLA2 115 #1 : Open Xfmr CHWCGN 115/CHOWCOGN 13.8 #1 : Open Xfmr CHWCHLA2 115/CHWCHLA2 13.8 #1 : Drop Load at CERTTEED 115 #1 : 9.9 MW 6.9 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.2 131.7 0.5

28 Open Line LE GRAND 115-WILSON A 115 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.1 131.6 0.5 161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.0 131.5 0.5

116 Open Line CANANDGA 70-TRIGO J 70 #1 : Open Line CANANDGA 70-GLASS 70 #1 : Open Line TRIGO J 70-BONITA 70 #1 : Open Line TRIGO J 70-TRIGO 70 #1 : Open Line TRIGO 70-MADERA 70 #1 : Open Line TRIGO 70-EL PECO 70 #1 : Drop Load at CANANDGA 70 #1 : 7.6 MW 5.7 MVAR Dro : Drop Load at BONITA 70 #1 : 14.6 MW 2.9 MVAR Drop : Drop Load at EL

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.8 131.4 0.5

Page 353: To determine the system impacts caused by the Project

C-40 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangePECO 70 #1 : 10 MW 2 MVAR Dropped : Drop Load at EL PECO 70 #2 : 7.3 MW 1.4 MVAR Drop :

114 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 8.7 MW 1.7 MVAR Dro : Drop Load at NEWHALL 115 #3 : 10.8 MW 2.1 MVAR Dr : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at MADERA_G 13.8 #1 : 28.6 MW Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.2 130.7 0.5

169 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.9 130.4 0.5

374 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.9 130.4 0.5

155 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.7 130.3 0.5

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.8 130.3 0.5

153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.5 130.2 0.8

156 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.6 130.1 0.5

115 Open Line PANOCHET 115-MENDOTA 115 #1 : Open Line PANOCHET 115-PANOCHE 115 #1 : Drop Generator at DG_PAN1 13.8 #1 : 49 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.6 130.1 0.5

189 Open Line HELM 230-MC CALL 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.3 129.8 0.6 157 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.1 129.6 0.5

Page 354: To determine the system impacts caused by the Project

C-41 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-

OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 2.2 MW 0.4 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 26.5 MW 5.3 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.1 129.6 0.5

111 Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.8 129.4 0.5

112 Open Line LE GRNDJ 115-WILSON B 115 #1 : Open Line LE GRNDJ 115-EL NIDO 115 #1 : Open Line EL NIDO 115-ORO LOMA 115 #1 : Drop Load at EL NIDO 115 #1 : 12.6 MW 2.5 MVAR Dr : Drop Load at EL NIDO 115 #2 : 15.2 MW 3 MVAR Drop : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.5 129.0 0.5

291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.5 129.0 0.5 154 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.2 128.7 0.5

377 Open Line GATES 230-ARCO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.2 128.7 0.5

378 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.0 128.5 0.5

117 Open Line MCSWAINJ 70-MC SWAIN 70 #1 : Open Line MCSWAINJ 70-MRCDFLLS 70 #1 : Open Line MCSWAINJ 70-EXCHEQUR 70 #1 : Open Xfmr MC SWAIN 70/MCSWAIN 9.11 #1 : Drop Generator at MCSWAIN 9.11 #1 : 9 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.0 128.5 0.5

353 Open Line SMYRNA 115-MCKIBBEN 115 #1 : Open Line MCKIBBEN 115-SEMITRPJ 115 #1 : Open Line SEMITRPJ 115-GANSO 115 #1 : Open Line GANSO 115-MIDWAY 115 #1 : Drop Load at GANSO 115 #1 : 3.9 MW 0.7 MVAR Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.9 128.4 0.5

162 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.9 128.4 0.5

163 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.9 128.4 0.5

Page 355: To determine the system impacts caused by the Project

C-42 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change41 Open Line PANOCHEJ 115-PANOCHE 115 #1 : Open Line

PANOCHEJ 115-HAMMONDS 115 #1 : Open Line PANOCHEJ 115-OXFRDJCT 115 #1 : Open Line HAMMONDS 115-DFSTP 115 #1 : Open Line DFSTP 115-ORO LOMA 115 #1 : Open Line DFSTP 115-DFS 115 #1 : Open Line OXFRDJCT 115-OXFORD 115 #1 : Open Line OXFRDJCT 115-WSTLDJCT 115 #1 : Open Line WSTLDJCT 115-WSTLD1RA 115 #1 : Open Line WSTLDJCT 115-LUISJCT 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.6 128.3 0.7

113 Open Line WILSON B 115-EL CAPTN 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.8 128.3 0.5

27 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Drop Generator at EXCHQUER 13.8 #1 : 94.5 MW Dropp : Drop Load at MARIPOS2 70 #**: 9.1 MW 1.8 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.7 128.3 0.5

81 Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.7 128.2 0.5 108 Open Line ATWATER 115-CASTLE 115 #1 : Open Line CASTLE

115-EL CAPTN 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.7 128.2 0.5

158 Open Line LOSBANOS 230-SN LS PP 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.7 128.2 0.5

159 Open Line LOSBANOS 230-SN LS PP 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.7 128.2 0.5

12 Open Line PANOCHE 230-HELM 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.7 128.2 0.5 179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 129 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.6 128.2 0.7

371 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.7 128.2 0.5

Page 356: To determine the system impacts caused by the Project

C-43 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change118 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line

MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 7 MW 1.4 MVAR Dropped : Drop Load at ARBURUA 70 #1 : 3.8 MW 1.8 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 9.6 MW 1.9 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.6 128.1 0.5

255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 19 MW 3.8 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 7.7 MW 1.5 MVAR Drop : Drop Load at BIOLA 70 #1 : 22 MW 4.4 MVAR Dropped : Drop Load at BOWLES 70 #1 : 18.5 MW 3.7 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.5 128.1 0.5

70 Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Open Line ORO LOMA 115-DFSTP 115 #1 : Open Line ORO LOMA 115-EL NIDO 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.5 127.2 0.7

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.6 127.2 0.5

236 Open Line HERNDON 115-CHLDHOSP 115 #1 : Open Line CHLDHOSP 115-WOODWARD 115 #1 : Drop Load at CHLDHOSP 115 #1 : 3.5 MW 1.5 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.6 127.1 0.5

62 Open Line DS AMIGO 230-PANOCHE 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.6 127.1 0.5 66 Open Xfmr EXCHEQUR 115/EXCHEQUR 70 #1 : Open Line

EXCHEQUR 70-MARIPOS2 70 #1 : Open Line EXCHEQUR 70-BER VLLY 70 #1 : Open Line EXCHEQUR 70-MCSWAINJ 70 #1 : Drop Load at MARIPOS2 70 #1 : 9.1 MW 1.8 MVAR Dro : Drop Load at MARIPOS2 70 #2 : 9.5 MW 1.9 MVAR Dro : Close Line MARIPOS2 70-BRCEBG J 70 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.6 127.1 0.5

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.5 127.0 0.5

5 Open Line LOSBANOS 230-PANOCHE 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.4 127.0 0.5 3 Open Line MOSSLND2 230-PANOCHE 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 126.9 0.7

233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.4 126.9 0.5

Page 357: To determine the system impacts caused by the Project

C-44 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangePNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

280 Open Xfmr HERNDON 230/HERNDON 115 #2 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.4 126.9 0.5 279 Open Xfmr HERNDON 230/HERNDON 115 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.3 126.8 0.5 109 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY

T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 11.7 MW 10.3 MVAR D : Drop Load at CRESSEY 115 #1 : 19.3 MW 3.9 MVAR Dr : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.3 126.8 0.5

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.3 126.8 0.5 376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 94.5 MW Droppe : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 126.8 0.5

110 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 24.9 MW 5 MVAR Dro : Drop Load at GALLO 115 #1 : 4.3 MW 3.6 MVAR Dropp : Drop Generator at EXCHQUER 13.8 #1: 94.5 MW Droppe :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 126.7 0.5

75 Open Xfmr MENDOTA 70/MENDOTA 115 #1 : Open Line MENDOTA 115-MADERAPR 115 #1 : Open Line MENDOTA 115-PANOCHET 115 #1 : Drop Load at MENDOTA 115 #1 : 24.9 MW 5 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.9 126.4 0.5

37 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 8.7 MW 1.7 MVAR Dro : Drop Load at NEWHALL 115 #3 : 10.8 MW 2.1 MVAR Dr : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at MADERA_G 13.8 #1 : 28.6 MW Dropp :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.8 126.3 0.5

Page 358: To determine the system impacts caused by the Project

C-45 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP

70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.6 MW 4.2 MVAR Drop : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.8 126.3 0.5

7 Open Line LOSBANOS 230-DS AMIGO 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.8 126.3 0.5 214 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Open Line CLOVISJ2

115-KERCKHF2 115 #1 : Open Line CLOVISJ2 115-SANGER 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.3 0.5

58 Open Line BORDEN 70-CASSIDY 70 #1 : Open Line CASSIDY 70-RIVERROC 70 #1 : Open Line RIVERROC 70-COPPRMNE 70 #1 : Drop Load at CASSIDY 70 #1 : 14.5 MW 2.9 MVAR Dro : Drop Load at RIVERROC 70 #1 : 2 MW 1.8 MVAR Dropp :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.2 0.5

2013 Summer Off-Peak Tcy-LB Tracy-Los Banos 500-kV TESLA - LOSBANOS 500.0 Ckt #1 2963.89 Amps 100.6 101.0 0.4 LB-Mdwy

Los Banos - Midway 500-kV LOSBANOS - GATES 500.0 Ckt#1 2963.89 Amps 107.4 107.8 0.4

396 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.4 123.0 0.6

397 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.4 123.0 0.6

147 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.9 121.7 0.8

134 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.6 112.3 0.6

395 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.0 111.7 0.6

142 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.2 110.9 0.6

Tsl-LB Tracy-Los Banos 500-kV WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.1 110.8 0.7 133 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.1 110.7 0.6

Page 359: To determine the system impacts caused by the Project

C-46 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeHELMS 1 18 #1: -310 MW Dropped :

150 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.7 110.3 0.6

136 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.6 110.2 0.6

406 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.4 110.0 0.6

137 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.4 110.0 0.6

138 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.9 109.5 0.6

135 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.4 109.0 0.6

402 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.2 108.9 0.7

148 Open Line BORDEN 230-GREGG 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.5 0.6

149 Open Line BORDEN 230-GREGG 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.5 0.6

400 Open Line GREGG 230-FGRDN T2 230 #1 : Open Line FGRDN T2 230-FIGRDN 2 230 #1 : Open Line FGRDN T2 230-ASHLAN 230 #1 : Drop Load at FIGRDN 2 230 #1 : 24.1 MW 4.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.1 0.6

310 Drop Generator at HELMS 2 18 #1: -310 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.1 0.6 139 Open Line LOSBANOS 230-SN LS PP 230 #1 : Drop Generator at

HELMS 1 18 #1: -310 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.1 0.6

140 Open Line LOSBANOS 230-SN LS PP 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.1 0.6

309 Drop Generator at HELMS 1 18 #1: -310 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.1 0.6 398 Open Line GREGG 230-HERNDON 230 #1 : Drop Generator at

HELMS 1 18 #1: -310 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.1 0.6

399 Open Line GREGG 230-HERNDON 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.1 0.6

Page 360: To determine the system impacts caused by the Project

C-47 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change409 Open Line GATES 230-ARCO 230 #1 : Drop Generator at

HELMS 1 18 #1: -310 MW Dropped : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 108.0 0.6

403 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 33.6 MW 6.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 108.0 0.6

190 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 108.0 0.6

191 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 108.0 0.6

410 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.3 107.9 0.6

Tcy-LB Tracy-Los Banos 500-kV WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.0 107.7 0.7 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

HELMS 1 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.0 107.6 0.7

141 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.5 107.2 0.7

143 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.6 107.2 0.6

144 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.6 107.2 0.6

416 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.5 107.1 0.6

417 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.5 107.1 0.6

131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.2 107.0 0.8

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.3 106.9 0.6

Page 361: To determine the system impacts caused by the Project

C-48 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

HELMS 1 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.2 106.9 0.7

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 106.7 0.6

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.7 106.4 0.7

380 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.2 0.6

381 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.2 0.6

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.3 105.9 0.7

364 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.1 105.7 0.6

365 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.1 105.7 0.6

404 Open Line HAAS 230-BALCH3TP 230 #1 : Open Xfmr HAAS 230/HAAS 13.8 #1 : Open Line BALCH3TP 230-MC CALL 230 #1 : Open Xfmr BALCH3TP 230/BLCH 2-3 13.8 #1 : Drop Generator at HAAS 13.8 #1 : 60 MW Dropped : Drop Generator at HAAS 13.8 #2 : 0 MW Dropped : Drop Generator at BLCH 2-3 13.8 #1 : 39 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.8 105.4 0.6

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.5 105.2 0.7

Page 362: To determine the system impacts caused by the Project

C-49 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.0 104.7 0.7

285 Open Xfmr GATES 230/GATES 500 #11 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.7 104.5 0.8 LB-Gts1

Los Banos - Gates #1 500-kV WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.2 102.9 0.6

405 Open Line BALCH 230-PINE FLT 230 #1 : Open Xfmr BALCH 230/BLCH 2-2 13.8 #1 : Open Line PINE FLT 230-MC CALL 230 #1 : Open Xfmr PINE FLT 230/PINE FLT 13.8 #1 : Drop Generator at BLCH 2-2 13.8 #1 : 39 MW Dropped : Drop Generator at PINE FLT 13.8 #1 : 54 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.0 102.6 0.6

61 Open Line MELONES 230-WILSON 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.5 102.3 0.8 145 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2

230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 15 MW 3 MVAR Dropp : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.7 102.2 0.5

146 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 16.8 MW 3.4 MVAR D : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.8 100.4 0.5

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 111.4 111.1 -0.2

428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 111.3 111.1 -0.2

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 111.3 111.1 -0.2

204 Open Line GATES 230-MORROBAY 230 #1 : TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 111.1 110.9 -0.2 408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

HELMS 1 18 #1: -310 MW Dropped : TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 109.4 109.2 -0.2

213 Open Line AIRWAYJ2 115-AIRWAYS 115 #1 : Open Line AIRWAYJ2 115-BARTON 115 #1 : Open Line AIRWAYJ2 115-SANGER 115 #1 :

SANGER -LASPALMS 115.00kV Ckt#1 Sec# 1 1124.58 Amps 106.9 106.9 0.0

211 Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

SANGER -AIRWAYJ2 115.00kV Ckt#1 Sec# 1 1124.58 Amps 110.1 110.1 0.0

391 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 114.6 114.4 -0.2

Page 363: To determine the system impacts caused by the Project

C-50 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeKERCKHOF 13.8 #1: 44 MW Dropped :

427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 114.6 114.4 -0.2

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 114.5 114.3 -0.2

203 Open Line GATES 230-TEMPLETN 230 #1 : MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 114.4 114.2 -0.2 407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

HELMS 1 18 #1: -310 MW Dropped : MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 112.7 112.5 -0.2

215 Open Line SANGER 115-MC CALL 115 #1 : MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 120.0 120.0 0.0 216 Open Line SANGER 115-MC CALL 115 #2 : MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 120.0 120.0 0.0 379 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 44 MW Dropped : MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 112.4 112.5 0.1

415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 110.9 111.0 0.1

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 110.7 110.8 0.1

189 Open Line HELM 230-MC CALL 230 #1 : MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 110.1 110.2 0.1 180 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 44 MW Dropped : MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 106.9 107.0 0.1

362 Open Line MC CALL 115-WAHTOKE 115 #1 : Drop Generator at KINGSRIV 13.8 #1: 33 MW Dropped :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 106.3 106.3 0.0

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 105.3 105.3 0.1

226 Open Line MALAGA 115-MALAGATP 115 #1 : Open Line MALAGATP 115-SCWAXJCT 115 #1 : Open Line MALAGATP 115-ULTPWRJ 115 #1 : Open Line SCWAXJCT 115-SCWAX 115 #1 : Open Line SCWAXJCT 115-RANCHRS 115 #1 : Open Line ULTPWRJ 115-AIRPROD 115 #1 : Open Xfmr ULTPWRJ 115/ULTR.PWR 9.11 #1 : Open Line AIRPROD 115-MC CALL 115 #1 : Drop Load at SCWAX 115 #1 : 2 MW 1.1 MVAR Dropped : Drop Load at RANCHRS 115 #1 : 4.2 MW 0.8 MVAR Dro :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 105.3 105.3 0.0

161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 105.1 105.2 0.1

12 Open Line PANOCHE 230-HELM 230 #1 : MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 104.4 104.5 0.1 361 Open Line MC CALL 115-WAHTOKE 115 #1 : MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 103.4 103.4 0.0

Page 364: To determine the system impacts caused by the Project

C-51 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change395 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

HELMS 1 18 #1: -310 MW Dropped : MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 103.2 103.3 0.1

228 Open Line REEDLEY 115-GERAWAN 115 #1 : Open Line GERAWAN 115-WAHTOKE 115 #1 :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 100.1 100.1 0.0

406 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 101.2 101.6 0.4

Tsl-LB Tracy-Los Banos 500-kV LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 142.0 142.6 0.6 Tcy-LB Tracy-Los Banos 500-kV LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 137.1 137.8 0.6

132 Open Line WARNERVL 230-WILSON 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 116.6 117.2 0.6

Moss-LB

Moss Landing - Los Banos #1& #2 500-kV DLO LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 116.5 117.0 0.5

134 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 115.3 115.9 0.5

396 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 115.0 115.5 0.5

397 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 115.0 115.5 0.5

146 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 16.8 MW 3.4 MVAR D : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 111.8 112.3 0.5

145 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 15 MW 3 MVAR Dropp : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 111.2 111.7 0.5

147 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 110.8 111.3 0.5

135 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 110.6 111.1 0.5

141 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 110.1 110.6 0.5

Page 365: To determine the system impacts caused by the Project

C-52 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change401 Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1

230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 110.0 110.5 0.5

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 110.0 110.4 0.5

421 Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.7 110.2 0.5

285 Open Xfmr GATES 230/GATES 500 #11 : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.6 110.1 0.6 406 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

HENTAP2 230-GATES 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.6 110.0 0.5

160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.6 110.0 0.5

369 Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.4 109.9 0.5

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.4 109.9 0.5

398 Open Line GREGG 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

399 Open Line GREGG 230-HERNDON 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

190 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

Page 366: To determine the system impacts caused by the Project

C-53 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change191 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at

HELMS 2 18 #**: -310 MW Dropped : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

403 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 33.6 MW 6.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

139 Open Line LOSBANOS 230-SN LS PP 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

140 Open Line LOSBANOS 230-SN LS PP 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

309 Drop Generator at HELMS 1 18 #1: -310 MW Dropped : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5 310 Drop Generator at HELMS 2 18 #1: -310 MW Dropped : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5 400 Open Line GREGG 230-FGRDN T2 230 #1 : Open Line FGRDN T2

230-FIGRDN 2 230 #1 : Open Line FGRDN T2 230-ASHLAN 230 #1 : Drop Load at FIGRDN 2 230 #1 : 24.1 MW 4.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

409 Open Line GATES 230-ARCO 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.3 109.8 0.5

LB-Gts1

Los Banos - Gates #1 500-kV LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.2 109.7 0.5

410 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.2 109.7 0.5

148 Open Line BORDEN 230-GREGG 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.2 109.7 0.5

149 Open Line BORDEN 230-GREGG 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.2 109.7 0.5

385 Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.2 109.7 0.5

3 Open Line MOSSLND2 230-PANOCHE 230 #1 : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.1 109.6 0.5

Page 367: To determine the system impacts caused by the Project

C-54 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change416 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at

HELMS 2 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.0 109.5 0.5

417 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.0 109.5 0.5

402 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.0 109.5 0.5

1 Open Line WARNERVL 230-WILSON 230 #1 : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.8 109.4 0.6 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

HELMS 1 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.8 109.3 0.5

364 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.7 109.2 0.5

365 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.7 109.2 0.5

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.5 109.0 0.5

380 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.5 109.0 0.5

381 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.5 109.0 0.5

153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.4 108.9 0.5

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.5 108.9 0.5

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.4 108.9 0.5

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.3 108.7 0.5

Page 368: To determine the system impacts caused by the Project

C-55 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change172 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 44 MW Dropped : LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.2 108.7 0.5

126 Open Line WARNERVL 230-WILSON 230 #1 : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.1 108.7 0.6

151 Open Line WARNERVL 230-WILSON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 107.9 108.4 0.6

170 Open Line WARNERVL 230-WILSON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 107.7 108.3 0.6

404 Open Line HAAS 230-BALCH3TP 230 #1 : Open Xfmr HAAS 230/HAAS 13.8 #1 : Open Line BALCH3TP 230-MC CALL 230 #1 : Open Xfmr BALCH3TP 230/BLCH 2-3 13.8 #1 : Drop Generator at HAAS 13.8 #1 : 60 MW Dropped : Drop Generator at HAAS 13.8 #2 : 0 MW Dropped : Drop Generator at BLCH 2-3 13.8 #1 : 39 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 107.3 107.8 0.5

143 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.6 107.0 0.5

144 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.6 107.0 0.5

142 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.4 106.8 0.5

395 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.6 106.0 0.5

16 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 16.8 MW 3.4 MVAR D :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.4 105.9 0.5

138 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.4 105.9 0.5

128 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 16.8 MW 3.4 MVAR D : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.2 105.7 0.5

405 Open Line BALCH 230-PINE FLT 230 #1 : Open Xfmr BALCH 230/BLCH 2-2 13.8 #1 : Open Line PINE FLT 230-MC CALL 230 #1 : Open Xfmr PINE FLT 230/PINE FLT 13.8 #1 : Drop Generator at BLCH 2-2 13.8 #1 : 39 MW Dropped : Drop Generator at PINE FLT 13.8 #1 : 54 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.1 105.6 0.5

Page 369: To determine the system impacts caused by the Project

C-56 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change15 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2

230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 15 MW 3 MVAR Dropp :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.0 105.5 0.5

131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.0 105.5 0.5

165 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 16.8 MW 3.4 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.9 105.4 0.5

127 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 15 MW 3 MVAR Dropp : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.8 105.3 0.5

213 Open Line AIRWAYJ2 115-AIRWAYS 115 #1 : Open Line AIRWAYJ2 115-BARTON 115 #1 : Open Line AIRWAYJ2 115-SANGER 115 #1 :

LASPALMS-AIRWAYJ1 115.00kV Ckt#1 Sec# 1 1124.58 Amps 103.0 103.0 0.0

396 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.9 118.5 0.6

397 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.9 118.5 0.6

147 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.5 117.2 0.8

134 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.1 107.8 0.6

395 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.6 107.2 0.6

142 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.8 106.4 0.6

Tsl-LB Tracy-Los Banos 500-kV COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.3 0.7 133 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at

HELMS 1 18 #1: -310 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.2 0.6

150 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.2 105.8 0.6

136 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.1 105.7 0.6

Page 370: To determine the system impacts caused by the Project

C-57 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change406 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

HENTAP2 230-GATES 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.0 105.6 0.6

137 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.9 105.5 0.6

138 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.4 105.1 0.6

135 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.9 104.5 0.6

402 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.7 104.4 0.7

148 Open Line BORDEN 230-GREGG 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.4 104.0 0.6

149 Open Line BORDEN 230-GREGG 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.4 104.0 0.6

400 Open Line GREGG 230-FGRDN T2 230 #1 : Open Line FGRDN T2 230-FIGRDN 2 230 #1 : Open Line FGRDN T2 230-ASHLAN 230 #1 : Drop Load at FIGRDN 2 230 #1 : 24.1 MW 4.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6

309 Drop Generator at HELMS 1 18 #1: -310 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6 310 Drop Generator at HELMS 2 18 #1: -310 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6 139 Open Line LOSBANOS 230-SN LS PP 230 #1 : Drop Generator at

HELMS 1 18 #1: -310 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6

140 Open Line LOSBANOS 230-SN LS PP 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6

398 Open Line GREGG 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6

399 Open Line GREGG 230-HERNDON 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6

409 Open Line GATES 230-ARCO 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6

403 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 33.6 MW 6.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at HELMS 1

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.6 0.6

Page 371: To determine the system impacts caused by the Project

C-58 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change18 #1: -310 MW Dropped :

190 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.9 103.5 0.6

191 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.9 103.5 0.6

410 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.8 103.4 0.6

Tcy-LB Tracy-Los Banos 500-kV COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.5 103.2 0.7 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

HELMS 1 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.5 103.2 0.7

141 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.0 102.7 0.7

143 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.1 102.7 0.6

144 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.1 102.7 0.6

416 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.0 102.6 0.6

417 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.0 102.6 0.6

131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.7 102.5 0.8

407 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.8 102.4 0.6

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.7 102.4 0.7

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.6 102.2 0.6

Page 372: To determine the system impacts caused by the Project

C-59 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

HELMS 1 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.2 101.9 0.7

380 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.2 101.8 0.6

381 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.2 101.8 0.6

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at MELONE1 13.8 #1: 100 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.8 101.4 0.7

364 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.6 101.2 0.6

365 Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.6 101.2 0.6

404 Open Line HAAS 230-BALCH3TP 230 #1 : Open Xfmr HAAS 230/HAAS 13.8 #1 : Open Line BALCH3TP 230-MC CALL 230 #1 : Open Xfmr BALCH3TP 230/BLCH 2-3 13.8 #1 : Drop Generator at HAAS 13.8 #1 : 60 MW Dropped : Drop Generator at HAAS 13.8 #2 : 0 MW Dropped : Drop Generator at BLCH 2-3 13.8 #1 : 39 MW Dropped : Drop Generator at HELMS 1 18 #1: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.4 101.0 0.6

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at KERCKHOF 13.8 #1: 44 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.0 100.7 0.7

160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 38 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.5 100.2 0.7

2013 Spring Peak 285 Open Xfmr GATES 230/GATES 500 #11 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.7 129.8 1.1

Page 373: To determine the system impacts caused by the Project

C-60 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.9 125.0 1.1

196 Open Line KEARNEY 230-HERNDON 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.7 120.7 1.0 2 Open Line WESTLEY 230-LOSBANOS 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.7 120.5 0.9

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.8 1.0

422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.2 115.1 1.0

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.8 112.7 1.0

152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.9 112.7 0.9

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.5 112.4 0.8

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.0 112.0 1.0

166 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.4 111.5 1.1

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.4 111.4 1.0

185 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.1 111.2 1.1

189 Open Line HELM 230-MC CALL 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.6 110.5 0.9 202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

HENTAP2 230-GATES 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.6 110.5 0.9

12 Open Line PANOCHE 230-HELM 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.1 110.0 0.9 3 Open Line MOSSLND2 230-PANOCHE 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.8 109.7 0.9

160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.9 1.0

62 Open Line DS AMIGO 230-PANOCHE 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.7 0.9

Page 374: To determine the system impacts caused by the Project

C-61 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change5 Open Line LOSBANOS 230-PANOCHE 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.7 0.9 6 Open Line LOSBANOS 230-PANOCHE 230 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.4 0.9

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.2 108.2 1.0

7 Open Line LOSBANOS 230-DS AMIGO 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.0 107.9 0.9 255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line

OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 15.1 MW 3 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 6.1 MW 1.2 MVAR Drop : Drop Load at BIOLA 70 #1 : 17.5 MW 3.5 MVAR Dropp : Drop Load at BOWLES 70 #1 : 14.7 MW 2.9 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.8 107.7 0.9

30 Open Line LE GRNDJ 115-WILSON B 115 #1 : Open Line LE GRNDJ 115-EL NIDO 115 #1 : Open Line EL NIDO 115-ORO LOMA 115 #1 : Drop Load at EL NIDO 115 #1 : 10 MW 2 MVAR Droppe : Drop Load at EL NIDO 115 #2 : 12 MW 2.4 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.7 107.6 0.9

26 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 19.6 MW 3.9 MVAR D : Drop Load at GALLO 115 #1 : 4 MW 3.4 MVAR Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.5 107.4 0.9

24 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 10.9 MW 9.6 MVAR Dr : Drop Load at CRESSEY 115 #1 : 15.2 MW 3 MVAR Drop : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.4 107.3 0.9

29 Open Line LE GRAND 115-DAIRYLND 115 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 107.0 0.9 233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-

BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 107.0 0.9

67 Open Xfmr WILSON A 115/WILSON 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.9 106.8 0.9

Page 375: To determine the system impacts caused by the Project

C-62 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change68 Open Xfmr WILSON B 115/WILSON 230 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.9 106.8 0.9

214 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Open Line CLOVISJ2 115-KERCKHF2 115 #1 : Open Line CLOVISJ2 115-SANGER 115 #1 : Drop Load at CLOVIS-2 115 #3 : 36 MW 7.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.8 106.7 0.9

264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP 70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.2 MW 4 MVAR Droppe : Drop Load at LEMOORE 70 #1 : 15.2 MW 3 MVAR Dropp : Drop Load at LEMOORE 70 #2 : 26.4 MW 5.3 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.8 106.6 0.9

291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.5 106.4 0.9 4 Open Line COBURN 230-PANOCHE 230 #1 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.4 106.3 0.9

239 Open Line KINGSBRG 115-GAURD J1 115 #1 : Open Line GAURD J1 115-MC CALL 115 #1 : Open Line GAURD J1 115-GAURD J2 115 #1 : Open Line GAURD J2 115-GRDN GLS 115 #1 : Drop Load at GRDN GLS 115 #1 : 3.3 MW 1 MVAR Drop : Drop Load at KINGSBRG 115 #3 : 26.2 MW 5.3 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.4 106.3 0.9

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#3

75 MVA 102.1 102.3 0.2

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#3

75 MVA 99.9 100.1 0.2

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#2

75 MVA 102.1 102.3 0.2

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#2

75 MVA 99.9 100.1 0.2

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#1

150 MVA 102.0 102.3 0.2

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#1

150 MVA 99.8 100.1 0.2

131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.0 125.8 0.9

285 Open Xfmr GATES 230/GATES 500 #11 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 121.7 122.5 0.8 196 Open Line KEARNEY 230-HERNDON 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.1 114.8 0.7 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.7 113.4 0.7

Page 376: To determine the system impacts caused by the Project

C-63 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeMELONE1 13.8 #1: 166 MW Dropped :

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.6 112.4 0.7

166 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.1 111.9 0.9

185 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.7 111.5 0.9

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.2 111.0 0.7

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.6 109.3 0.7

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.6 0.7

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.6 108.3 0.7

3 Open Line MOSSLND2 230-PANOCHE 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.5 108.2 0.7 189 Open Line HELM 230-MC CALL 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.2 107.9 0.7

12 Open Line PANOCHE 230-HELM 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.9 107.6 0.7 2 Open Line WESTLEY 230-LOSBANOS 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.6 107.2 0.6

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.5 107.1 0.7

415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 106.8 0.7

160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 106.8 0.7

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.8 106.5 0.7

62 Open Line DS AMIGO 230-PANOCHE 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.8 106.5 0.7 5 Open Line LOSBANOS 230-PANOCHE 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.8 106.4 0.7

Page 377: To determine the system impacts caused by the Project

C-64 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line

OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 15.1 MW 3 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 6.1 MW 1.2 MVAR Drop : Drop Load at BIOLA 70 #1 : 17.5 MW 3.5 MVAR Dropp : Drop Load at BOWLES 70 #1 : 14.7 MW 2.9 MVAR Drop :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.7 106.4 0.7

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.3 0.7 30 Open Line LE GRNDJ 115-WILSON B 115 #1 : Open Line LE

GRNDJ 115-EL NIDO 115 #1 : Open Line EL NIDO 115-ORO LOMA 115 #1 : Drop Load at EL NIDO 115 #1 : 10 MW 2 MVAR Droppe : Drop Load at EL NIDO 115 #2 : 12 MW 2.4 MVAR Drop :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.5 106.2 0.7

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.4 106.2 0.7

26 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 19.6 MW 3.9 MVAR D : Drop Load at GALLO 115 #1 : 4 MW 3.4 MVAR Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.4 106.1 0.7

7 Open Line LOSBANOS 230-DS AMIGO 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.3 106.0 0.7 24 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY

T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 10.9 MW 9.6 MVAR Dr : Drop Load at CRESSEY 115 #1 : 15.2 MW 3 MVAR Drop : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.3 106.0 0.7

233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.1 105.8 0.7

29 Open Line LE GRAND 115-DAIRYLND 115 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.1 105.7 0.7

Page 378: To determine the system impacts caused by the Project

C-65 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change214 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Open Line CLOVISJ2

115-KERCKHF2 115 #1 : Open Line CLOVISJ2 115-SANGER 115 #1 : Drop Load at CLOVIS-2 115 #3 : 36 MW 7.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.0 105.7 0.7

67 Open Xfmr WILSON A 115/WILSON 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.0 105.6 0.7 264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP

70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.2 MW 4 MVAR Droppe : Drop Load at LEMOORE 70 #1 : 15.2 MW 3 MVAR Dropp : Drop Load at LEMOORE 70 #2 : 26.4 MW 5.3 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.0 105.6 0.7

68 Open Xfmr WILSON B 115/WILSON 230 #2 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.9 105.6 0.7 12 Open Line PANOCHE 230-HELM 230 #1 : STRD JCT-SCHLNDLR 70.00kV Ckt#1 Sec# 1 377.75 Amps 101.3 101.8 0.5

128 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 156.0 156.9 0.9

165 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 152.8 153.7 0.8

16 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 148.3 149.1 0.8

184 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 143.3 144.2 1.0

146 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.7 118.6 0.9

422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.3 107.0 0.7

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.5 105.2 0.7

285 Open Xfmr GATES 230/GATES 500 #11 : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.7 103.4 0.7 411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at MELONE1 13.8 #1: 166

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.5 103.2 0.7

Page 379: To determine the system impacts caused by the Project

C-66 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeMW Dropped :

196 Open Line KEARNEY 230-HERNDON 230 #1 : STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.2 102.8 0.6 160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.6 101.3 0.7

128 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 164.7 165.6 0.9

165 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 161.5 162.4 0.9

16 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 156.9 157.8 0.8

184 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 151.9 152.9 1.0

146 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 127.2 0.9

422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.1 115.7 0.7

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.2 113.8 0.7

285 Open Xfmr GATES 230/GATES 500 #11 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.3 112.1 0.7 411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.2 111.9 0.7

196 Open Line KEARNEY 230-HERNDON 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.8 111.5 0.7 160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.3 110.0 0.7

Page 380: To determine the system impacts caused by the Project

C-67 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.9 107.6 0.7

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.9 107.6 0.7

415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.8 106.4 0.6

152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.4 105.9 0.6

107 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 6.6 MW 4.6 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 1.8 MW 0.3 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.9 105.5 0.6

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.9 105.5 0.6

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.4 105.0 0.6

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.8 104.4 0.6

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.1 103.7 0.7

161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.8 103.4 0.6

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.7 103.2 0.5 374 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

HENTAP2 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.4 102.9 0.6

Page 381: To determine the system impacts caused by the Project

C-68 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change106 Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line

CERTAN T 115-LE GRAND 115 #1 : Open Line CERTAN T 115-CERTANJ2 115 #1 : Open Line CERTANJ2 115-CHWCGNJT 115 #1 : Open Line CHWCGNJT 115-CERTTEED 115 #1 : Open Line CHWCGNJT 115-CHWCGN 115 #1 : Open Line CHWCGN 115-CHWCHLA2 115 #1 : Open Xfmr CHWCGN 115/CHOWCOGN 13.8 #1 : Open Xfmr CHWCHLA2 115/CHWCHLA2 13.8 #1 : Drop Load at CERTTEED 115 #1 : 9.3 MW 6.4 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.9 102.5 0.6

429 Open Line GATES 230-ARCO 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.7 102.3 0.6

430 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.7 102.3 0.6

207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 1.8 MW 0.3 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 20.9 MW 4.2 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.3 101.9 0.6

413 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.3 101.9 0.6

414 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.3 101.9 0.6

116 Open Line CANANDGA 70-TRIGO J 70 #1 : Open Line CANANDGA 70-GLASS 70 #1 : Open Line TRIGO J 70-BONITA 70 #1 : Open Line TRIGO J 70-TRIGO 70 #1 : Open Line TRIGO 70-MADERA 70 #1 : Open Line TRIGO 70-EL PECO 70 #1 : Drop Load at CANANDGA 70 #1 : 7.1 MW 5.3 MVAR Dro : Drop Load at BONITA 70 #1 : 11.5 MW 2.3 MVAR Drop : Drop Load at EL PECO 70 #1 : 7.9 MW 1.6 MVAR Drop : Drop Load at EL PECO 70 #2 : 5.8 MW 1.1 MVAR Drop :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.3 101.8 0.6

423 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.2 101.7 0.6

Page 382: To determine the system impacts caused by the Project

C-69 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 90 MW Dropped : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.1 101.7 0.6

189 Open Line HELM 230-MC CALL 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.1 101.7 0.6 155 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 90 MW Dropped : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.8 101.4 0.6

169 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.8 101.4 0.6

156 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.6 101.2 0.6

115 Open Line PANOCHET 115-MENDOTA 115 #1 : Open Line PANOCHET 115-PANOCHE 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.5 101.1 0.6

427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.5 101.1 0.6

157 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.4 101.0 0.6

428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.3 100.9 0.6

12 Open Line PANOCHE 230-HELM 230 #1 : STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.1 100.7 0.6 114 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line

NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 6.8 MW 1.3 MVAR Dro : Drop Load at NEWHALL 115 #3 : 8.5 MW 1.7 MVAR Dro : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.9 100.5 0.6

154 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.7 100.3 0.6

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.7 100.3 0.6

377 Open Line GATES 230-ARCO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.7 100.3 0.6

378 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.6 100.2 0.6

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.5 100.1 0.5

Page 383: To determine the system impacts caused by the Project

C-70 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change127 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2

230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 155.5 156.4 0.9

164 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 152.2 153.1 0.9

15 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 147.6 148.6 0.9

183 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 142.7 143.7 0.9

145 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 117.1 118.1 0.9

422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 116.8 117.5 0.7

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 114.7 115.5 0.7

285 Open Xfmr GATES 230/GATES 500 #11 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 112.7 113.5 0.8 411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 112.6 113.3 0.7

196 Open Line KEARNEY 230-HERNDON 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 112.2 112.9 0.7 160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.5 111.2 0.7

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.9 108.6 0.7

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.9 108.6 0.7

415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.7 107.3 0.7

Page 384: To determine the system impacts caused by the Project

C-71 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 90 MW Dropped : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.2 106.8 0.6

107 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 6.6 MW 4.6 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 1.8 MW 0.3 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.8 106.4 0.7

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.6 106.3 0.7

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.1 105.8 0.6

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 104.5 105.1 0.7

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 103.7 104.4 0.7

161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 103.4 104.1 0.7

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 103.2 103.8 0.6 374 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

HENTAP2 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 102.9 103.6 0.6

106 Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line CERTAN T 115-LE GRAND 115 #1 : Open Line CERTAN T 115-CERTANJ2 115 #1 : Open Line CERTANJ2 115-CHWCGNJT 115 #1 : Open Line CHWCGNJT 115-CERTTEED 115 #1 : Open Line CHWCGNJT 115-CHWCGN 115 #1 : Open Line CHWCGN 115-CHWCHLA2 115 #1 : Open Xfmr CHWCGN 115/CHOWCOGN 13.8 #1 : Open Xfmr CHWCHLA2 115/CHWCHLA2 13.8 #1 : Drop Load at CERTTEED 115 #1 : 9.3 MW 6.4 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 102.4 103.1 0.7

429 Open Line GATES 230-ARCO 230 #1 : Drop Generator at STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 102.2 102.8 0.6

Page 385: To determine the system impacts caused by the Project

C-72 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeMELONE1 13.8 #1: 166 MW Dropped :

430 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 102.1 102.8 0.6

207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 1.8 MW 0.3 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 20.9 MW 4.2 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.8 102.4 0.7

116 Open Line CANANDGA 70-TRIGO J 70 #1 : Open Line CANANDGA 70-GLASS 70 #1 : Open Line TRIGO J 70-BONITA 70 #1 : Open Line TRIGO J 70-TRIGO 70 #1 : Open Line TRIGO 70-MADERA 70 #1 : Open Line TRIGO 70-EL PECO 70 #1 : Drop Load at CANANDGA 70 #1 : 7.1 MW 5.3 MVAR Dro : Drop Load at BONITA 70 #1 : 11.5 MW 2.3 MVAR Drop : Drop Load at EL PECO 70 #1 : 7.9 MW 1.6 MVAR Drop : Drop Load at EL PECO 70 #2 : 5.8 MW 1.1 MVAR Drop :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.7 102.4 0.6

413 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.7 102.4 0.6

414 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.7 102.4 0.6

153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.6 102.2 0.6

423 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.6 102.2 0.6

189 Open Line HELM 230-MC CALL 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.5 102.2 0.7 169 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 90 MW Dropped : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.2 101.8 0.6

155 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.2 101.8 0.6

156 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.0 101.7 0.6

Page 386: To determine the system impacts caused by the Project

C-73 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeEXCHQUER 13.8 #1: 90 MW Dropped :

427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.8 101.5 0.6

115 Open Line PANOCHET 115-MENDOTA 115 #1 : Open Line PANOCHET 115-PANOCHE 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.9 101.5 0.6

157 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.8 101.4 0.6

428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.7 101.3 0.6

12 Open Line PANOCHE 230-HELM 230 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.5 101.1 0.7 114 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line

NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 6.8 MW 1.3 MVAR Dro : Drop Load at NEWHALL 115 #3 : 8.5 MW 1.7 MVAR Dro : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.2 100.8 0.6

154 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.0 100.6 0.6

377 Open Line GATES 230-ARCO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.0 100.6 0.6

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.0 100.6 0.6

378 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.9 100.6 0.6

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.8 100.4 0.6

117 Open Line MCSWAINJ 70-MC SWAIN 70 #1 : Open Line MCSWAINJ 70-MRCDFLLS 70 #1 : Open Line MCSWAINJ 70-EXCHEQUR 70 #1 : Open Xfmr MC SWAIN 70/MCSWAIN 9.11 #1 : Drop Generator at MCSWAIN 9.11 #1 : 9 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.6 100.3 0.6

353 Open Line SMYRNA 115-MCKIBBEN 115 #1 : Open Line MCKIBBEN 115-SEMITRPJ 115 #1 : Open Line SEMITRPJ 115-GANSO 115 #1 : Open Line GANSO 115-MIDWAY 115 #1

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.6 100.2 0.6

Page 387: To determine the system impacts caused by the Project

C-74 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change: Drop Load at GANSO 115 #1 : 3 MW 0.6 MVAR Dropped : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

162 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.5 100.2 0.6

163 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.5 100.2 0.6

113 Open Line WILSON B 115-EL CAPTN 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.5 100.1 0.6

28 Open Line LE GRAND 115-WILSON A 115 #1 : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.4 100.1 0.6 158 Open Line LOSBANOS 230-SN LS PP 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 90 MW Dropped : STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.4 100.1 0.6

159 Open Line LOSBANOS 230-SN LS PP 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.4 100.1 0.6

285 Open Xfmr GATES 230/GATES 500 #11 : Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 106.6 106.9 0.4 204 Open Line GATES 230-MORROBAY 230 #1 : Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 103.5 103.6 0.1 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 103.3 103.4 0.1

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 103.3 103.3 0.1

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 103.0 103.1 0.1

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 102.2 102.3 0.1

203 Open Line GATES 230-TEMPLETN 230 #1 : Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 100.2 100.3 0.1 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 100.0 100.1 0.1

285 Open Xfmr GATES 230/GATES 500 #11 : Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 106.6 106.9 0.4 204 Open Line GATES 230-MORROBAY 230 #1 : Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.5 103.6 0.1 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.3 103.4 0.1

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.3 103.3 0.1

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.0 103.1 0.1

Page 388: To determine the system impacts caused by the Project

C-75 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

HELMS 1 18 #1: 400 MW Dropped : Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 102.2 102.3 0.1

203 Open Line GATES 230-TEMPLETN 230 #1 : Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.2 100.3 0.1 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.0 100.1 0.1

285 Open Xfmr GATES 230/GATES 500 #11 : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 106.6 106.9 0.4 204 Open Line GATES 230-MORROBAY 230 #1 : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.5 103.6 0.1 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.3 103.4 0.1

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.2 103.3 0.1

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.0 103.1 0.1

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 102.2 102.3 0.1

203 Open Line GATES 230-TEMPLETN 230 #1 : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.2 100.3 0.1 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.0 100.1 0.1

285 Open Xfmr GATES 230/GATES 500 #11 : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 106.6 106.9 0.4 204 Open Line GATES 230-MORROBAY 230 #1 : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.5 103.6 0.1 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.3 103.4 0.1

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.3 103.3 0.1

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.0 103.1 0.1

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 102.2 102.3 0.1

203 Open Line GATES 230-TEMPLETN 230 #1 : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.2 100.3 0.1 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.0 100.1 0.1

285 Open Xfmr GATES 230/GATES 500 #11 : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 106.6 106.9 0.4 204 Open Line GATES 230-MORROBAY 230 #1 : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.5 103.6 0.1 428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.3 103.4 0.1

Page 389: To determine the system impacts caused by the Project

C-76 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeMELONE1 13.8 #1: 166 MW Dropped :

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.2 103.3 0.1

392 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.0 103.1 0.1

408 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 102.2 102.3 0.1

203 Open Line GATES 230-TEMPLETN 230 #1 : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.2 100.3 0.1 427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.0 100.1 0.1

44 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 5.5 MW 1.1 MVAR Dropp : Drop Load at ARBURUA 70 #1 : 3.5 MW 1.7 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 7.6 MW 1.5 MVAR Dro :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 108.4 108.8 0.4

125 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 5.5 MW 1.1 MVAR Dropp : Drop Load at ARBURUA 70 #1 : 3.5 MW 1.7 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 7.6 MW 1.5 MVAR Dro : Drop Generator at ONEILPMP 9.11 #1: -6 MW Dropped :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 107.3 107.7 0.4

118 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 5.5 MW 1.1 MVAR Dropp : Drop Load at ARBURUA 70 #1 : 3.5 MW 1.7 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 7.6 MW 1.5 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 103.4 103.8 0.4

165 Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

OAKH_JCT-SHARON T 115.00kV Ckt#1 Sec# 1 396.61 Amps 104.9 105.4 0.5

Page 390: To determine the system impacts caused by the Project

C-77 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 90 MW Dropped : OAKH_JCT-SHARON T 115.00kV Ckt#1 Sec# 1 396.61 Amps 100.2 100.8 0.5

164 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

OAKH_JCT-SHARON T 115.00kV Ckt#1 Sec# 1 396.61 Amps 99.7 100.2 0.5

1 Open Line WARNERVL 230-WILSON 230 #1 : MELONES -COTTLE A 230.00kV Ckt#1 Sec# 1 849.96 Amps 102.6 103.2 0.5 202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

HENTAP2 230-GATES 230 #1 : MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 108.5 109.0 0.6

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 106.8 107.3 0.5

374 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 106.5 107.0 0.5

291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : KERMAN -AGRCJCT 70.00kV Ckt#1 Sec# 1 379.4 Amps 163.2 163.1 -0.1 291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : KEARNEY -FRWWTAP 70.00kV Ckt#1 Sec# 1 379.4 Amps 111.5 111.4 -0.1

12 Open Line PANOCHE 230-HELM 230 #1 : HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 122.2 122.7 0.5 412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 120.2 120.7 0.5

161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 120.0 120.6 0.5

180 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 112.4 112.9 0.5

142 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 106.0 106.5 0.5

291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : FRWWTAP -KERMAN 70.00kV Ckt#1 Sec# 1 379.4 Amps 107.9 107.8 -0.1 131 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.1 118.0 0.8

285 Open Xfmr GATES 230/GATES 500 #11 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.8 114.7 0.9 196 Open Line KEARNEY 230-HERNDON 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.3 107.1 0.7 422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.9 105.6 0.7

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.8 104.6 0.7

Page 391: To determine the system impacts caused by the Project

C-78 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change166 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at

EXCHQUER 13.8 #1: 90 MW Dropped : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.4 104.2 0.8

185 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.0 103.8 0.8

411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.4 103.2 0.7

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.8 101.5 0.7

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.1 100.9 0.7

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.8 100.5 0.7

3 Open Line MOSSLND2 230-PANOCHE 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.7 100.4 0.7 189 Open Line HELM 230-MC CALL 230 #1 : COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.5 100.2 0.7 291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : CAMDEN -KNGLOBUS 70.00kV Ckt#1 Sec# 1 398.37 Amps 100.7 101.0 0.3 127 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2

230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 176.2 177.2 0.9

164 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 172.8 173.8 1.0

15 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 167.9 168.9 1.0

183 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 162.7 163.7 1.0

145 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Drop Generator at HELMS 1 18 #1: 400 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 135.2 136.2 1.0

422 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 134.8 135.6 0.8

370 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.7 133.4 0.8

Page 392: To determine the system impacts caused by the Project

C-79 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change285 Open Xfmr GATES 230/GATES 500 #11 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.5 131.3 0.8 411 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.3 131.1 0.8

196 Open Line KEARNEY 230-HERNDON 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.9 130.7 0.8 160 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line

MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.2 128.9 0.8

386 Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.4 126.2 0.8

11 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.4 126.1 0.8

415 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.0 124.7 0.7

152 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.5 124.1 0.6

107 Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CERTANJ1 115-SHARON T 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line SHARON T 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line OAKH_JCT 115-K1-JCT 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Open Line K1-JCT 115-KERCKHF2 115 #2 : Drop Load at SHARON 115 #1 : 6.6 MW 4.6 MVAR Drop : Drop Load at CORSGOLD 115 #1 : 1.8 MW 0.3 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.1 123.8 0.7

412 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.8 123.6 0.7

426 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.3 123.0 0.7

363 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 121.7 122.4 0.7

179 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.9 121.7 0.8

Page 393: To determine the system impacts caused by the Project

C-80 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change230 #1 : 16.4 MW 3.3 MVAR D : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

161 Open Line PANOCHE 230-HELM 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.6 121.3 0.7

2 Open Line WESTLEY 230-LOSBANOS 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.3 121.0 0.6 374 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

HENTAP2 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.0 120.7 0.7

106 Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line CERTAN T 115-LE GRAND 115 #1 : Open Line CERTAN T 115-CERTANJ2 115 #1 : Open Line CERTANJ2 115-CHWCGNJT 115 #1 : Open Line CHWCGNJT 115-CERTTEED 115 #1 : Open Line CHWCGNJT 115-CHWCGN 115 #1 : Open Line CHWCGN 115-CHWCHLA2 115 #1 : Open Xfmr CHWCGN 115/CHOWCOGN 13.8 #1 : Open Xfmr CHWCHLA2 115/CHWCHLA2 13.8 #1 : Drop Load at CERTTEED 115 #1 : 9.3 MW 6.4 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.5 120.2 0.7

429 Open Line GATES 230-ARCO 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.2 119.8 0.7

430 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.1 119.8 0.7

207 Open Line K1-JCT 115-KERCKHF2 115 #2 : Open Line K1-JCT 115-OAKH_JCT 115 #1 : Open Line OAKH_JCT 115-SHARON T 115 #1 : Open Line OAKH_JCT 115-CORSGOLD 115 #1 : Open Line SHARON T 115-CERTANJ1 115 #1 : Open Line SHARON T 115-SHARON 115 #1 : Open Line CERTANJ1 115-CHWCHLLA 115 #1 : Open Line CORSGOLD 115-OAKHURST 115 #1 : Drop Load at CORSGOLD 115 #1 : 1.8 MW 0.3 MVAR Dr : Drop Load at CORSGOLD 115 #2 : 20.9 MW 4.2 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.8 119.5 0.7

116 Open Line CANANDGA 70-TRIGO J 70 #1 : Open Line CANANDGA 70-GLASS 70 #1 : Open Line TRIGO J 70-BONITA 70 #1 : Open Line TRIGO J 70-TRIGO 70 #1 : Open Line TRIGO 70-MADERA 70 #1 : Open Line TRIGO 70-EL PECO 70 #1 : Drop Load at CANANDGA 70 #1 : 7.1 MW 5.3 MVAR Dro : Drop Load at BONITA 70 #1 : 11.5 MW 2.3 MVAR Drop : Drop Load at EL PECO 70 #1 : 7.9 MW 1.6 MVAR Drop : Drop Load at EL PECO 70 #2 : 5.8 MW 1.1 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.7 119.4 0.7

Page 394: To determine the system impacts caused by the Project

C-81 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change413 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at

MELONE1 13.8 #1: 166 MW Dropped : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.7 119.3 0.7

414 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.7 119.3 0.7

153 Open Line MOSSLND2 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.6 119.3 0.7

189 Open Line HELM 230-MC CALL 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.5 119.2 0.7 423 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN

T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.5 119.2 0.7

169 Open Line DS AMIGO 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.2 118.9 0.7

155 Open Line LOSBANOS 230-PANOCHE 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.2 118.9 0.7

156 Open Line LOSBANOS 230-PANOCHE 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.0 118.7 0.7

115 Open Line PANOCHET 115-MENDOTA 115 #1 : Open Line PANOCHET 115-PANOCHE 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.8 118.4 0.7

157 Open Line LOSBANOS 230-DS AMIGO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.7 118.4 0.7

427 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.7 118.4 0.7

428 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.5 118.2 0.7

12 Open Line PANOCHE 230-HELM 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.4 118.1 0.7 114 Open Line NEWHALL 115-DAIRYLND 115 #1 : Open Line

NEWHALL 115-MADERAPR 115 #1 : Open Line MADERAPR 115-MENDOTA 115 #1 : Open Xfmr MADERAPR 115/MADERA_G 13.8 #1 : Drop Load at NEWHALL 115 #2 : 6.8 MW 1.3 MVAR Dro : Drop Load at NEWHALL 115 #3 : 8.5 MW 1.7 MVAR Dro : Drop Load at MADERA_G 13.8 #ss: 3.6 MW 0.8 MVAR D : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.1 117.8 0.7

154 Open Line COBURN 230-PANOCHE 230 #1 : Drop Generator at BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.9 117.6 0.7

Page 395: To determine the system impacts caused by the Project

C-82 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

ChangeEXCHQUER 13.8 #1: 90 MW Dropped :

202 Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.9 117.6 0.7

377 Open Line GATES 230-ARCO 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.9 117.6 0.7

378 Open Line GATES 230-MIDWAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.8 117.5 0.7

171 Open Line WESTLEY 230-LOSBANOS 230 #1 : Drop Generator at KERCKHOF 13.8 #1: 145 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.7 117.3 0.6

117 Open Line MCSWAINJ 70-MC SWAIN 70 #1 : Open Line MCSWAINJ 70-MRCDFLLS 70 #1 : Open Line MCSWAINJ 70-EXCHEQUR 70 #1 : Open Xfmr MC SWAIN 70/MCSWAIN 9.11 #1 : Drop Generator at MCSWAIN 9.11 #1 : 9 MW Dropped : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.5 117.2 0.7

353 Open Line SMYRNA 115-MCKIBBEN 115 #1 : Open Line MCKIBBEN 115-SEMITRPJ 115 #1 : Open Line SEMITRPJ 115-GANSO 115 #1 : Open Line GANSO 115-MIDWAY 115 #1 : Drop Load at GANSO 115 #1 : 3 MW 0.6 MVAR Dropped : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 117.1 0.7

162 Open Line PANOCHE 230-GATES 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 117.1 0.7

163 Open Line PANOCHE 230-GATES 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 117.1 0.7

28 Open Line LE GRAND 115-WILSON A 115 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 117.1 0.7 113 Open Line WILSON B 115-EL CAPTN 115 #1 : Drop Generator at

EXCHQUER 13.8 #1: 90 MW Dropped : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 117.0 0.7

81 Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 116.9 0.7 108 Open Line ATWATER 115-CASTLE 115 #1 : Open Line CASTLE

115-EL CAPTN 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 116.9 0.7

158 Open Line LOSBANOS 230-SN LS PP 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 116.9 0.7

159 Open Line LOSBANOS 230-SN LS PP 230 #2 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 116.9 0.7

Page 396: To determine the system impacts caused by the Project

C-83 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change371 Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN

T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 116.9 0.7

27 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Drop Generator at EXCHQUER 13.8 #1 : 90 MW Dropped : Drop Load at MARIPOS2 70 #**: 7.2 MW 1.4 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.2 116.9 0.7

118 Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line MRCYSPRS 70-ORTIGA 70 #1 : Open Line MRCYSPRS 70-ARBURUA 70 #1 : Open Line ORTIGA 70-CANAL 70 #1 : Open Line ARBURUA 70-WRGHT PP 70 #1 : Open Line WRGHT PP 70-LOS BANS 70 #1 : Drop Load at ORTIGA 70 #1 : 5.5 MW 1.1 MVAR Dropp : Drop Load at ARBURUA 70 #1 : 3.5 MW 1.7 MVAR Drop : Drop Load at WRGHT PP 70 #1 : 7.6 MW 1.5 MVAR Dro : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.1 116.7 0.7

111 Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.8 116.5 0.7

425 Open Line BALCH 230-PINE FLT 230 #1 : Open Xfmr BALCH 230/BLCH 2-2 13.8 #1 : Open Line PINE FLT 230-MC CALL 230 #1 : Open Xfmr PINE FLT 230/PINE FLT 13.8 #1 : Drop Generator at BLCH 2-2 13.8 #1 : 52 MW Dropped : Drop Generator at PINE FLT 13.8 #1 : 63 MW Dropped : Drop Generator at MELONE1 13.8 #1: 166 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.7 116.4 0.7

375 Open Line GATES 230-TEMPLETN 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.1 0.7

3 Open Line MOSSLND2 230-PANOCHE 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.1 0.7 112 Open Line LE GRNDJ 115-WILSON B 115 #1 : Open Line LE

GRNDJ 115-EL NIDO 115 #1 : Open Line EL NIDO 115-ORO LOMA 115 #1 : Drop Load at EL NIDO 115 #1 : 10 MW 2 MVAR Droppe : Drop Load at EL NIDO 115 #2 : 12 MW 2.4 MVAR Drop : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.3 116.0 0.7

376 Open Line GATES 230-MORROBAY 230 #1 : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.3 115.9 0.7

Page 397: To determine the system impacts caused by the Project

C-84 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change66 Open Xfmr EXCHEQUR 115/EXCHEQUR 70 #1 : Open Line

EXCHEQUR 70-MARIPOS2 70 #1 : Open Line EXCHEQUR 70-BER VLLY 70 #1 : Open Line EXCHEQUR 70-MCSWAINJ 70 #1 : Drop Load at MARIPOS2 70 #1 : 7.2 MW 1.4 MVAR Dro : Drop Load at MARIPOS2 70 #2 : 7.5 MW 1.5 MVAR Dro : Close Line MARIPOS2 70-BRCEBG J 70 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.3 115.9 0.7

41 Open Line PANOCHEJ 115-PANOCHE 115 #1 : Open Line PANOCHEJ 115-HAMMONDS 115 #1 : Open Line PANOCHEJ 115-OXFRDJCT 115 #1 : Open Line HAMMONDS 115-DFSTP 115 #1 : Open Line DFSTP 115-ORO LOMA 115 #1 : Open Line DFSTP 115-DFS 115 #1 : Open Line OXFRDJCT 115-OXFORD 115 #1 : Open Line OXFRDJCT 115-WSTLDJCT 115 #1 : Open Line WSTLDJCT 115-WSTLD1RA 115 #1 : Open Line WSTLDJCT 115-LUISJCT 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.2 115.9 0.7

109 Open Line ATWATER 115-CRESEY T 115 #1 : Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line CRESEY T 115-JRWD GEN 115 #1 : Open Line JRWD GEN 115-JR WOOD 115 #1 : Open Xfmr JRWD GEN 115/JRWCOGEN 9.11 #1 : Open Line JR WOOD 115-CRESSEY 115 #1 : Drop Load at JR WOOD 115 #1 : 10.9 MW 9.6 MVAR Dr : Drop Load at CRESSEY 115 #1 : 15.2 MW 3 MVAR Drop : Drop Generator at JRWCOGEN 9.11 #1 : 3.8 MW Droppe : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.1 115.8 0.7

255 Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line OLDKERN 70-BIOLA 70 #1 : Open Line OLDKERN 70-BOWLES 70 #1 : Drop Load at OLDKERN 70 #1 : 15.1 MW 3 MVAR Dropp : Drop Load at OLDKERN 70 #3 : 6.1 MW 1.2 MVAR Drop : Drop Load at BIOLA 70 #1 : 17.5 MW 3.5 MVAR Dropp : Drop Load at BOWLES 70 #1 : 14.7 MW 2.9 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.0 115.7 0.7

110 Open Line CRESEY T 115-ATWATR J 115 #1 : Open Line ATWATR J 115-LIVNGSTN 115 #1 : Open Line ATWATR J 115-MERCED 115 #1 : Open Line LIVNGSTN 115-GALLO 115 #1 : Drop Load at LIVNGSTN 115 #3 : 19.6 MW 3.9 MVAR D : Drop Load at GALLO 115 #1 : 4 MW 3.4 MVAR Dropped : Drop Generator at EXCHQUER 13.8 #1: 90 MW Dropped :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.0 115.7 0.7

5 Open Line LOSBANOS 230-PANOCHE 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.0 115.7 0.7 62 Open Line DS AMIGO 230-PANOCHE 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.0 115.7 0.7

Page 398: To determine the system impacts caused by the Project

C-85 GWF Henrietta SISAppendix C

# Outage Description Facility Rating Unit PU

Flow PU

Flow %

Change236 Open Line HERNDON 115-CHLDHOSP 115 #1 : Open Line

CHLDHOSP 115-WOODWARD 115 #1 : Drop Load at CHLDHOSP 115 #1 : 3.3 MW 1.4 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.9 115.6 0.7

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.8 115.5 0.7 291 Open Xfmr KEARNEY 70/KEARNEY 230 #2 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.8 115.4 0.7 279 Open Xfmr HERNDON 230/HERNDON 115 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.7 115.3 0.7 379 Open Line HELM 230-MC CALL 230 #1 : Drop Generator at

KERCKHOF 13.8 #1: 145 MW Dropped : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.6 115.3 0.7

233 Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.6 115.3 0.7

7 Open Line LOSBANOS 230-DS AMIGO 230 #1 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.5 115.2 0.7 280 Open Xfmr HERNDON 230/HERNDON 115 #2 : BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.5 115.2 0.7 264 Open Line LEPRINO 70-LPRNO TP 70 #1 : Open Line LPRNO TP

70-LEMOORE 70 #1 : Open Line LPRNO TP 70-CANDLEWK 70 #1 : Open Line LPRNO TP 70-HENRITTA 70 #1 : Drop Load at LEPRINO 70 #1 : 6.2 MW 4 MVAR Droppe : Drop Load at LEMOORE 70 #1 : 15.2 MW 3 MVAR Dropp : Drop Load at LEMOORE 70 #2 : 26.4 MW 5.3 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.2 114.9 0.7

Page 399: To determine the system impacts caused by the Project

C-86 GWF Henrietta SISAppendix C

Table C-3: Category “C” Emergency Overloads # Outage Description Facility Rating Units

PU Flow

PU Flow

% Change

2013 Summer Peak

61 Open Line GREGG 230-HERNDON 230 #1 : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line GREGG 230-HERNDON 230 #2 :

ASHLAN -FGRDN T2 230.00kV Ckt#1 Sec# 1 849.96 Amps 158.8 159.3 0.5

1 Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 :

ATWATR J-MERCED 115.00kV Ckt#1 Sec# 1 738 Amps 161.8 161.6 -0.3

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

BELRIDGE-MIDWAY 115.00kV Ckt#1 Sec# 1 743.02 Amps 127.6 127.6 -0.1

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 150.0 150.6 0.6

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 140.8 141.6 0.8

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 140.4 141.0 0.7

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 138.9 139.6 0.6

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 138.3 139.0 0.8

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 138.3 139.0 0.8

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 137.8 138.5 0.6

62 Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 137.2 137.9 0.7

Page 400: To determine the system impacts caused by the Project

C-87 GWF Henrietta SISAppendix C

Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 137.2 137.8 0.6

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 70 MW 13.5 MVAR Drop : Drop Load at ASHLAN 230 #2 : 65.3 MW 12.9 MVAR Dr : Drop Load at ASHLAN 230 #3 : 66.3 MW 12.6 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 135.7 136.5 0.8

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 134.5 135.2 0.8

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 134.2 135.0 0.8

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 133.7 134.5 0.8

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.1 131.6 0.5

104 Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 45.4 MW 9.2 MVAR Dr : Drop Load at

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.9 131.6 0.7

Page 401: To determine the system impacts caused by the Project

C-88 GWF Henrietta SISAppendix C

BULLARD 115 #2 : 45.2 MW 9.1 MVAR Dr : Drop Load at BULLARD 115 #3 : 43 MW 8.7 MVAR Drop :

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.9 130.4 0.5

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 42.7 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #2 : 53.3 MW 10.8 MVAR : Drop Load at WOODWARD 115 #3 : 44.6 MW 9 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.5 130.2 0.7

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 13.6 MW 2.7 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.3 129.9 0.5

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.3 129.8 0.6

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.2 129.8 0.6

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 4.1 MW 3.5 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.0 129.7 0.7

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.8 129.4 0.6

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.5 129.2 0.7

117

Open Line KEARNEY 70-FRWWTAP 70 #1 : Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.5 129.0 0.5

23 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Open Xfmr EXCHEQUR 115/EXCHQRTP 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.3 128.9 0.5

25 Open Line WILSON A 115-LE GRAND 115 #1 : Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON A 115-WILSON B 115 #1 : Open Line

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.0 128.8 0.8

Page 402: To determine the system impacts caused by the Project

C-89 GWF Henrietta SISAppendix C

WILSON A 115-MERCED 115 #1 : Open Xfmr WILSON A 115/WILSON 230 #1 : Drop Load at WILSON A 115 #3 : 18.9 MW 3.8 MVAR D :

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 43.8 MW 8.8 MVAR Dro : Drop Load at BARTON 115 #2 : 37.6 MW 7.6 MVAR Dro : Drop Load at BARTON 115 #3 : 27.3 MW 5.5 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.0 128.7 0.7

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.1 128.7 1.5

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.0 128.5 0.5

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.0 128.5 0.5

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 25.6 MW 5.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 25.8 MW 5.2 MVAR D : Drop Load at MANCHSTR 115 #3 : 36.6 MW 7.4 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.6 128.3 0.7

30

Open Line PANOCHE 115-CHENYT 115 #1 : Open Line PANOCHE 115-PANOCHEJ 115 #1 : Open Xfmr PANOCHE 115/PANOCHE 230 #2 : Open Xfmr PANOCHE 115/DG_PAN1 13.8 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.8 128.3 0.5

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 53.2 MW 10.7 MVAR :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.3 127.9 0.5

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.1 127.8 0.7

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.0 127.7 0.7

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 18.2 MW 3.7 MVAR Drop : Drop Load at MADERA 70 #2 : 23.4 MW 4.7 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.9 127.5 0.5

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.9 127.4 0.5

Page 403: To determine the system impacts caused by the Project

C-90 GWF Henrietta SISAppendix C

86

Open Line KERCKHF2 115-K1-JCT 115 #2 : Open Line KERCKHF2 115-KERCKHF1 115 #1 : Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line KERCKHF2 115-CLOVISJ2 115 #1 : Open Xfmr KERCKHF2 115/KERCKHOF 13.8 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.8 127.3 0.5

96

Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 29.3 MW 5.9 MVAR Dr : Drop Load at CAL AVE 115 #2 : 31.6 MW 6.4 MVAR Dr : Drop Load at CAL AVE 115 #3 : 24.7 MW 5 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.6 127.3 0.7

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.4 127.1 0.7

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 38 MW 7.7 MVAR Dro : Drop Load at WST FRSO 115 #2 : 39.5 MW 8 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.4 127.1 0.7

72 Open Line HERNDON 230-GREGG 230 #2 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Xfmr HERNDON 230/HERNDN2M 115 #2 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.5 127.0 0.5

100 Open Line HERNDON 115-BARTON 115 #1 : Open Line HERNDON 115-PNDLJ2 115 #1 : Open Xfmr HERNDON 115/HERNDN1M 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.4 127.0 0.5

87

Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 38.8 MW 7.5 MVAR Dr : Drop Load at AIRWAYS 115 #2 : 12.7 MW 2.5 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.3 126.8 0.5

45 Open Line BARTON 115-HERNDON 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 126.8 0.5

106

Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-GAURD J1 115 #1 : Open Xfmr KINGSBRG 115/KNGLOBUS 70 #2 : Drop Load at KINGSBRG 115 #3 : 33 MW 6.6 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.1 126.7 0.5

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.0 126.6 0.5

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.0 126.6 0.5

Page 404: To determine the system impacts caused by the Project

C-91 GWF Henrietta SISAppendix C

PANOCHE 230/PANOCHE 115 #2 :

121

Open Line REEDLEY 70-TVY VLLY 70 #1 : Open Line REEDLEY 70-PARLIER 70 #1 : Open Line REEDLEY 70-DNUBAJCT 70 #1 : Open Line REEDLEY 70-ORSI JCT 70 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #2 : Drop Load at REEDLEY 70 #1 : 17.6 MW 3.5 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.3 0.5

124 Open Line LEMOORE 70-LPRNO TP 70 #1 : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.2 0.5

100 Open Line HERNDON 115-BARTON 115 #1 : Open Line HERNDON 115-PNDLJ2 115 #1 : Open Xfmr HERNDON 115/HERNDN1M 115 #1 :

BULLARD -PNDLJ1 115.00kV Ckt#1 Sec# 1 743.02 Amps 148.4 148.4 -0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 176.7 176.7 -0.1

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 115.4 115.4 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 113.8 113.8 0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

CERTAN T-LE GRAND 115.00kV Ckt#1 Sec# 1 396.61 Amps 165.7 166.6 1.0

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

CERTAN T-LE GRAND 115.00kV Ckt#1 Sec# 1 396.61 Amps 119.4 119.4 0.0

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

CERTAN T-LE GRAND 115.00kV Ckt#1 Sec# 1 396.61 Amps 110.1 110.5 0.5

Page 405: To determine the system impacts caused by the Project

C-92 GWF Henrietta SISAppendix C

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

CHLDHOSP-HERNDON 115.00kV Ckt#1 Sec# 1 973.96 Amps 111.9 112.0 0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

CHWCHLLA-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 139.4 140.5 1.0

128

Open Line GATES 70-KETTLEMN 70 #1 : Open Line GATES 70-GATS2_TP 70 #1 : Open Line GATES 70-HURON 70 #1 : Open Line GATES 70-HURON 70 #2 : Open Line GATES 70-JACALITO 70 #1 : Open Xfmr GATES 70/GATES 115 #2 :

COLNGA 2-PLSNTVLY 70.00kV Ckt#1 Sec# 1 398.37 Amps 112.0 112.1 0.1

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

COPPRMNE-TVY VLLY 70.00kV Ckt#1 Sec# 1 297.75 Amps 105.9 105.6 -0.3

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 138.6 139.3 0.7 lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 133.7 134.5 0.8

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.2 124.6 0.4

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.3 123.9 0.6

71 Open Line HERNDON 230-GREGG 230 #1 : Open COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.0 123.7 0.7

Page 406: To determine the system impacts caused by the Project

C-93 GWF Henrietta SISAppendix C

Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.0 123.6 0.7

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 70 MW 13.5 MVAR Drop : Drop Load at ASHLAN 230 #2 : 65.3 MW 12.9 MVAR Dr : Drop Load at ASHLAN 230 #3 : 66.3 MW 12.6 MVAR Dr :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.2 123.6 0.4

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.2 123.6 0.4

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.2 123.6 0.4

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.9 123.3 0.5

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 121.8 122.6 0.8

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 121.6 122.3 0.7

27 Open Line EL CAPTN 115-CASTLE 115 #1 : Open COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.7 120.4 0.7

Page 407: To determine the system impacts caused by the Project

C-94 GWF Henrietta SISAppendix C

Line EL CAPTN 115-WILSON B 115 #1 : Drop Load at EL CAPTN 115 #1 : 19.7 MW 4 MVAR Dro : Drop Load at EL CAPTN 115 #2 : 26.2 MW 5.3 MVAR D : Drop Load at EL CAPTN 115 #3 : 33.5 MW 6.7 MVAR D :

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 45.4 MW 9.2 MVAR Dr : Drop Load at BULLARD 115 #2 : 45.2 MW 9.1 MVAR Dr : Drop Load at BULLARD 115 #3 : 43 MW 8.7 MVAR Drop :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.7 120.4 0.7

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 42.7 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #2 : 53.3 MW 10.8 MVAR : Drop Load at WOODWARD 115 #3 : 44.6 MW 9 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.4 120.1 0.7

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.1 119.8 0.7

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.2 119.8 0.6

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 4.1 MW 3.5 MVAR Dr :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.9 119.6 0.7

22

Open Line ATWATER 115-CASTLE 115 #1 : Open Line ATWATER 115-CRESEY T 115 #1 : Open Line ATWATER 115-WILSON A 115 #1 : Drop Load at ATWATER 115 #1 : 32.8 MW 6.6 MVAR Dr : Drop Load at ATWATER 115 #2 : 28.7 MW 5.8 MVAR Dr :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.5 119.1 0.7

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.4 119.1 0.7

Page 408: To determine the system impacts caused by the Project

C-95 GWF Henrietta SISAppendix C

2 115-CLOVISJ2 115 #1 :

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.3 119.0 0.7

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.2 118.9 0.7

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.2 118.9 0.7

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 43.8 MW 8.8 MVAR Dro : Drop Load at BARTON 115 #2 : 37.6 MW 7.6 MVAR Dro : Drop Load at BARTON 115 #3 : 27.3 MW 5.5 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.7 118.4 0.7

28

Open Line MERCED 115-ATWATR J 115 #1 : Open Line MERCED 115-WILSON A 115 #1 : Open Line MERCED 115-WILSON B 115 #2 : Open Xfmr MERCED 115/MERCED M 115 #2 : Drop Load at MERCED 115 #1 : 37.6 MW 7.6 MVAR Dro : Drop Load at MERCED 115 #3 : 19.7 MW 3.9 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.6 118.3 0.7

117

Open Line KEARNEY 70-FRWWTAP 70 #1 : OpenLine KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.6 118.2 0.6

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.3 118.0 0.7

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.3 118.0 0.7

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 25.6 MW 5.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 25.8 MW 5.2 MVAR D : Drop Load at MANCHSTR 115 #3 : 36.6 MW 7.4 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.2 117.9 0.7

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.2 117.8 0.6

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.0 117.7 0.7

Page 409: To determine the system impacts caused by the Project

C-96 GWF Henrietta SISAppendix C

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.1 117.5 1.3

96

Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 29.3 MW 5.9 MVAR Dr : Drop Load at CAL AVE 115 #2 : 31.6 MW 6.4 MVAR Dr : Drop Load at CAL AVE 115 #3 : 24.7 MW 5 MVAR Drop :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.6 117.3 0.7

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.5 117.2 0.7

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 53.2 MW 10.7 MVAR :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.6 117.1 0.5

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 117.0 0.7

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 38 MW 7.7 MVAR Dro : Drop Load at WST FRSO 115 #2 : 39.5 MW 8 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 117.0 0.7

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 18.2 MW 3.7 MVAR Drop : Drop Load at MADERA 70 #2 : 23.4 MW 4.7 MVAR Drop :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.1 116.7 0.7

32

Open Line ORO LOMA 70-DOS PALS 70 #1 : Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line ORO LOMA 70-POSO J1 70 #1 : Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Drop Load at ORO LOMA 70 #1 : 8.7 MW 1.7 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.7 0.8

87

Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 38.8 MW 7.5 MVAR Dr : Drop Load at AIRWAYS 115 #2 : 12.7 MW 2.5 MVAR Dr :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.6 0.7

106

Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-GAURD J1 115 #1 : Open Xfmr KINGSBRG 115/KNGLOBUS 70 #2 : Drop Load at KINGSBRG 115 #3 : 33 MW 6.6 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.0 116.6 0.5

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.6 0.7

121 Open Line REEDLEY 70-TVY VLLY 70 #1 : Open COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.4 0.5

Page 410: To determine the system impacts caused by the Project

C-97 GWF Henrietta SISAppendix C

Line REEDLEY 70-PARLIER 70 #1 : Open Line REEDLEY 70-DNUBAJCT 70 #1 : Open Line REEDLEY 70-ORSI JCT 70 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #2 : Drop Load at REEDLEY 70 #1 : 17.6 MW 3.5 MVAR Dro :

34

Open Line CANAL 70-LVNGSTNT 70 #1 : Open Line CANAL 70-SNTA RTA 70 #1 : Open Line CANAL 70-ORTIGA 70 #1 : Drop Load at CANAL 70 #1 : 30.9 MW 6.2 MVAR Dropp : Drop Load at CANAL 70 #2 : 31.7 MW 6.4 MVAR Dropp :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.5 116.1 0.7

49 Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-CORCORAN 115 #2 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.3 116.0 0.7

107

Open Line CORCORAN 115-KINGSBRG 115 #1 : Open Line CORCORAN 115-KINGSBRG 115 #2 : Open Xfmr CORCORAN 115/CORCORAN 70 #2 : Drop Load at CORCORAN 115 #3 : 16.4 MW 3.3 MVAR D : Drop Load at CORCORAN 115 #4 : 18 MW 3.6 MVAR Dro :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.3 116.0 0.7

11

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line MELONES 230-WILSON 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.2 116.0 0.8

1 Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 :

CRESEY T-ATWATR J 115.00kV Ckt#1 Sec# 1 512.08 Amps 199.0 198.7 -0.3

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

DFSTP -ORO LOMA 115.00kV Ckt#1 Sec# 1 607.47 Amps 114.6 114.9 0.4

23 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Open Xfmr EXCHEQUR 115/EXCHQRTP 115 #1 :

EXCHEQUR-MCSWAINJ 70.00kV Ckt#1 Sec# 1 280.43 Amps 109.2 109.2 -0.1

61 Open Line GREGG 230-HERNDON 230 #1 : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line GREGG 230-HERNDON 230 #2 :

FGRDN T2-GREGG 230.00kV Ckt#1 Sec# 1 849.96 Amps 174.5 175.0 0.5

13 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line

HAMMONDS-DFSTP 115.00kV Ckt#1 Sec# 1 607.47 Amps 115.7 116.0 0.4

Page 411: To determine the system impacts caused by the Project

C-98 GWF Henrietta SISAppendix C

STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

HAMMONDS-PANOCHEJ 115.00kV Ckt#1 Sec# 1 607.47 Amps 123.8 124.2 0.4

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

HELM -PANOCHE 230.00kV Ckt#1 Sec# 1 849.96 Amps 102.4 102.8 0.4

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 116.9 117.5 0.5

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 116.9 117.5 0.5

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 106.9 107.3 0.4

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

K1-JCT -OAKH_JCT 115.00kV Ckt#1 Sec# 1 743.02 Amps 114.8 115.3 0.5

Page 412: To determine the system impacts caused by the Project

C-99 GWF Henrietta SISAppendix C

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

KEARNEY -HERNDON 230.00kV Ckt#1 Sec# 1 974.97 Amps 114.7 115.5 0.7

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

KERCKHF2-K1-JCT 115.00kV Ckt#2 Sec# 1 743.02 Amps 114.8 115.3 0.5

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 207.1 208.0 0.9

14 Open Line BORDEN 230-GREGG 230 #1 : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line BORDEN 230-GREGG 230 #2 :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 122.4 122.9 0.5

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 114.4 114.4 0.0

37

Open Line MRCDFLLS 70-MERCED 70 #1 : Open Line MRCDFLLS 70-MCSWAINJ 70 #1 : Open Xfmr MRCDFLLS 70/MERCEDFL 9.11 #1 : Open Xfmr MRCDFLLS 70/MERCEDFL 9.11 #2 : Drop Load at MRCDFLLS 70 #2 : 9.1 MW 1.8 MVAR Dro :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 103.6 103.6 0.0

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 103.5 103.6 0.0

60

Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 1 18 #**: 404 MW Dropped : Open Line GREGG 230-HELMS PP 230 #2 : Drop Generator at HELMS 3 18 #**: 404 MW Dropped :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 103.0 103.1 0.1

Page 413: To determine the system impacts caused by the Project

C-100 GWF Henrietta SISAppendix C

69

Open Line HELMS PP 230-GREGG 230 #1 : Open Line HELMS PP 230-GREGG 230 #2 : Open Xfmr HELMS PP 230/HELMS 1 18 #1 : Open Xfmr HELMS PP 230/HELMS 2 18 #1 : Open Xfmr HELMS PP 230/HELMS 3 18 #1 :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 103.0 103.1 0.1

33 Open Line MERCED 70-ELNIDOTP 70 #1 : Open Line MERCED 70-MRCDFLLS 70 #1 : Open Xfmr MERCED 70/MERCED M 115 #2 :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 101.6 101.6 0.0

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 100.9 101.1 0.1

28

Open Line MERCED 115-ATWATR J 115 #1 : Open Line MERCED 115-WILSON A 115 #1 : Open Line MERCED 115-WILSON B 115 #2 : Open Xfmr MERCED 115/MERCED M 115 #2 : Drop Load at MERCED 115 #1 : 37.6 MW 7.6 MVAR Dro : Drop Load at MERCED 115 #3 : 19.7 MW 3.9 MVAR Dro :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 100.6 100.6 0.0

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 100.0 100.3 0.3

44

Open Line AIRWAYJ2 115-AIRWAYS 115 #1 : Open Line AIRWAYJ2 115-BARTON 115 #1 : Open Line AIRWAYJ2 115-SANGER 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 13.9 MW 11.8 MVAR :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 100.0 100.2 0.2

13.00

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

LE GRNDJ-WILSON B 115.00kV Ckt#1 Sec# 1 398.12 Amps 101.11 101.67 0.6

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 142.7 143.5 0.8 lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 122.8 123.0 0.2

13 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 112.9 113.5 0.6

Page 414: To determine the system impacts caused by the Project

C-101 GWF Henrietta SISAppendix C

STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

10

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line WARNERVL 230-WILSON 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.5 109.1 0.6

12 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line WARNERVL 230-WILSON 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.6 105.0 0.3

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 102.8 103.4 0.6

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 100.1 100.6 0.5

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 70 MW 13.5 MVAR Drop : Drop Load at ASHLAN 230 #2 : 65.3 MW 12.9 MVAR Dr : Drop Load at ASHLAN 230 #3 : 66.3 MW 12.6 MVAR Dr :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 99.9 100.5 0.5

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 4.1 MW 3.5 MVAR Dr :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 99.8 100.4 0.6

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 112.6 113.0 0.4

Page 415: To determine the system impacts caused by the Project

C-102 GWF Henrietta SISAppendix C

SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

79

Open Line MC CALL 230-HELM 230 #1 : Open Line MC CALL 230-BALCH3TP 230 #1 : Open Line MC CALL 230-Q128 230 #2 : Open Xfmr MC CALL 230/MCCALL1M 115 #1 : Open Xfmr MC CALL 230/MCCALL3M 115 #3 :

MC CALL -MCCALL2M 115.00/ 115.00kV Bk#2 465 MVA 104.8 104.7 -0.1

79

Open Line MC CALL 230-HELM 230 #1 : Open Line MC CALL 230-BALCH3TP 230 #1 : Open Line MC CALL 230-Q128 230 #2 : Open Xfmr MC CALL 230/MCCALL1M 115 #1 : Open Xfmr MC CALL 230/MCCALL3M 115 #3 :

MC CALL -MCCALL2M 230.00/ 115.00kV Bk#2 465 MVA 108.5 108.3 -0.1

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 13.6 MW 2.7 MVAR D :

MCSWAINJ-EXCHEQUR 70.00kV Ckt#1 Sec# 1 280.43 Amps 179.4 179.3 0.0

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 13.6 MW 2.7 MVAR D :

MCSWAINJ-MRCDFLLS 70.00kV Ckt#1 Sec# 1 379.4 Amps 152.3 152.2 0.0

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 13.6 MW 2.7 MVAR D :

MERCED -MERCED M 70.00/ 115.00kV Bk#2 60 MVA 113.3 113.3 0.0

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 13.6 MW 2.7 MVAR D :

MERCED -MERCED M 115.00/ 115.00kV Bk#2 60 MVA 123.1 123.1 0.0

1 Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 :

MERCED -WILSON A 115.00kV Ckt#1 Sec# 1 471.92 Amps 149.8 149.6 -0.2

26

Open Line WILSON B 115-LE GRNDJ 115 #1 : Open Line WILSON B 115-WILSON A 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 : Open Line WILSON B 115-MERCED 115 #2 : Open Xfmr WILSON B 115/WILSON 230 #2 :

MERCED -WILSON A 115.00kV Ckt#1 Sec# 1 471.92 Amps 123.7 123.7 0.0

Page 416: To determine the system impacts caused by the Project

C-103 GWF Henrietta SISAppendix C

1 Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 :

MERCED -WILSON B 115.00kV Ckt#2 Sec# 1 471.92 Amps 134.6 134.4 -0.2

25

Open Line WILSON A 115-LE GRAND 115 #1 : Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON A 115-WILSON B 115 #1 : Open Line WILSON A 115-MERCED 115 #1 : Open Xfmr WILSON A 115/WILSON 230 #1 : Drop Load at WILSON A 115 #3 : 18.9 MW 3.8 MVAR D :

MERCED -WILSON B 115.00kV Ckt#2 Sec# 1 471.92 Amps 101.2 101.2 0.0

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 121.8 121.5 -0.2

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 101.9 101.9 -0.1

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 13.6 MW 2.7 MVAR D :

MRCDFLLS-MERCED 70.00kV Ckt#1 Sec# 1 377.75 Amps 140.7 140.7 0.0

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

OAKH_JCT-SHARON T 115.00kV Ckt#1 Sec# 1 396.61 Amps 146.0 147.0 1.0

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 113.4 112.9 -0.6

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 107.3 106.9 -0.5

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 106.2 106.6 0.4

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 107.0 106.5 -0.5

10 Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 105.4 105.8 0.4

Page 417: To determine the system impacts caused by the Project

C-104 GWF Henrietta SISAppendix C

Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line WARNERVL 230-WILSON 230 #1 :

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 103.7 103.2 -0.5

12 Open Line MELONES 230-WILSON 230 #1 : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line WARNERVL 230-WILSON 230 #1 :

ORO LOMA-DOS PALS 70.00kV Ckt#1 Sec# 1 282.08 Amps 101.0 100.6 -0.4

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

ORO LOMA-EL NIDO 115.00kV Ckt#1 Sec# 1 512.08 Amps 103.0 103.4 0.4

42 Open Line MENDOTA 70-TOMATAK 70 #1 : Open Line MENDOTA 70-BIOMSJCT 70 #1 : Open Xfmr MENDOTA 70/MENDOTA 115 #1 :

ORO LOMA-ORO LOMA 115.00/ 70.00kV Bk#2 72 MVA 105.7 105.4 -0.4

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

ORO LOMA-ORO LOMA 115.00/ 70.00kV Bk#2 72 MVA 103.5 103.4 -0.2

10

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line WARNERVL 230-WILSON 230 #1 :

ORO LOMA-ORO LOMA 115.00/ 70.00kV Bk#2 72 MVA 102.3 102.8 0.5

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

PANOCHE -DS AMIGO 230.00kV Ckt#1 Sec# 1 849.96 Amps 123.5 124.1 0.6

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO PANOCHE -DS AMIGO 230.00kV Ckt#1 Sec# 1 849.96 Amps 101.2 101.8 0.7

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

PANOCHE -LOSBANOS 230.00kV Ckt#1 Sec# 1 974.97 Amps 107.6 108.7 1.1

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

PANOCHE -LOSBANOS 230.00kV Ckt#1 Sec# 1 974.97 Amps 99.3 100.4 1.1

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

PANOCHE -LOSBANOS 230.00kV Ckt#2 Sec# 1 849.96 Amps 108.2 109.4 1.3

Page 418: To determine the system impacts caused by the Project

C-105 GWF Henrietta SISAppendix C

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO PANOCHE -LOSBANOS 230.00kV Ckt#2 Sec# 1 849.96 Amps 99.7 100.4 0.7

93

Open Line REEDLEY 115-GERAWAN 115 #1 : Open Line REEDLEY 115-PIEDRA 1 115 #1 : Open Xfmr REEDLEY 115/REEDLEY 70 #1 : Open Xfmr REEDLEY 115/REEDLEY 70 #2 : Drop Load at REEDLEY 115 #3 : 26.5 MW 5.3 MVAR Dr :

PARLIER -SNGRJCT 70.00kV Ckt#1 Sec# 1 470.13 Amps 162.6 162.6 0.0

30

Open Line PANOCHE 115-CHENYT 115 #1 : Open Line PANOCHE 115-PANOCHEJ 115 #1 : Open Xfmr PANOCHE 115/PANOCHE 230 #2 : Open Xfmr PANOCHE 115/DG_PAN1 13.8 #1 :

POSO J1 -ORO LOMA 70.00kV Ckt#1 Sec# 1 282.08 Amps 100.1 99.9 -0.3

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

PSA RBLS-SAN MIGL 70.00kV Ckt#1 Sec# 1 346.41 Amps 154.2 154.0 -0.2

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 242.1 242.0 -0.1

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 181.9 182.0 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 178.2 178.2 0.0

Dblo-Mdwy_dlo

Diablo - Midway #2&#33q21 500-kV DLO Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 161.0 161.1 0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 158.9 159.1 0.2

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 158.0 158.2 0.2

68 Open Line GATES 230-MIDWAY 230 #1 : Open Line GATES 230-ARCO 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 157.4 157.6 0.1

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 157.4 157.5 0.1

5 Open Line PANOCHE 230-GATES 230 #1 : Open Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 157.4 157.5 0.1

Page 419: To determine the system impacts caused by the Project

C-106 GWF Henrietta SISAppendix C

Line PANOCHE 230-GATES 230 #2 :

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 145.9 146.0 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 192.3 192.3 -0.1

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 134.6 134.6 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 130.9 130.9 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q166 -Q239SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 133.9 133.8 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q166 -Q239SWST 230.00kV Ckt#2 Sec# 1 976.48 Amps 133.9 133.8 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 116.7 116.6 -0.1

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.5 101.5 0.0

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q194 -Q194SWST 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.0 100.9 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 243.6 243.6 -0.1

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 183.3 183.4 0.0

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 179.6 179.6 0.1

Dblo-Mdwy_dlo

Diablo - Midway #2&#33q21 500-kV DLO Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 162.4 162.5 0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 160.3 160.5 0.2

19 Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 159.4 159.6 0.2

Page 420: To determine the system impacts caused by the Project

C-107 GWF Henrietta SISAppendix C

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

68 Open Line GATES 230-MIDWAY 230 #1 : Open Line GATES 230-ARCO 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 158.8 158.9 0.1

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 158.8 158.9 0.1

5 Open Line PANOCHE 230-GATES 230 #1 : Open Line PANOCHE 230-GATES 230 #2 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 158.8 158.9 0.1

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 147.3 147.4 0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 112.1 112.3 0.2

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 111.3 111.5 0.2

68 Open Line GATES 230-MIDWAY 230 #1 : Open Line GATES 230-ARCO 230 #1 :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 110.8 110.9 0.1

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 110.7 110.9 0.1

5 Open Line PANOCHE 230-GATES 230 #1 : Open Line PANOCHE 230-GATES 230 #2 :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 110.7 110.8 0.1

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 110.5 110.6 0.1

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 110.4 110.5 0.1

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 110.2 110.3 0.1

Page 421: To determine the system impacts caused by the Project

C-108 GWF Henrietta SISAppendix C

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

Q194SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 110.2 110.3 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 116.7 116.6 -0.1

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.5 101.5 0.0

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q194SWST-Q194 230.00kV Ckt#1 Sec# 1 483.22 Amps 101.0 100.9 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 177.2 177.1 -0.1

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 115.8 115.9 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 114.2 114.3 0.1

93

Open Line REEDLEY 115-GERAWAN 115 #1 : Open Line REEDLEY 115-PIEDRA 1 115 #1 : Open Xfmr REEDLEY 115/REEDLEY 70 #1 : Open Xfmr REEDLEY 115/REEDLEY 70 #2 : Drop Load at REEDLEY 115 #3 : 26.5 MW 5.3 MVAR Dr :

REEDLEY -PARLIER 70.00kV Ckt#1 Sec# 1 395.9 Amps 145.6 145.5 -0.1

118 Open Line KERMAN 70-AGRCJCT 70 #1 : Drop Load at KERMAN 70 #1 : 19.7 MW 3.9 MVAR Drop : Drop Load at KERMAN 70 #2 : 11.9 MW 2.4 MVAR Drop :

SAN JOQN-SNJQJCT 70.00kV Ckt#1 Sec# 1 395.9 Amps 118.1 118.0 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

SAN MIGL-COLNGA 1 70.00kV Ckt#1 Sec# 1 346.41 Amps 136.0 135.8 -0.2

52 Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 :

SANGER -MC CALL 115.00kV Ckt#3 Sec# 1 973.96 Amps 123.8 123.7 -0.1

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

SANGER -MC CALL 115.00kV Ckt#3 Sec# 1 973.96 Amps 105.9 106.1 0.1

13 Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 34.3 MW 6.9 MVAR D : Open Line

SHARON T-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 139.7 140.7 1.0

Page 422: To determine the system impacts caused by the Project

C-109 GWF Henrietta SISAppendix C

STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 38.3 MW 7.7 MVAR D :

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

SN LS OB-Q238TAP 115.00kV Ckt#1 Sec# 1 436.78 Amps 124.0 124.0 0.0

93

Open Line REEDLEY 115-GERAWAN 115 #1 : Open Line REEDLEY 115-PIEDRA 1 115 #1 : Open Xfmr REEDLEY 115/REEDLEY 70 #1 : Open Xfmr REEDLEY 115/REEDLEY 70 #2 : Drop Load at REEDLEY 115 #3 : 26.5 MW 5.3 MVAR Dr :

SNGRJCT -SANGER 70.00kV Ckt#1 Sec# 1 395.9 Amps 109.4 109.4 0.0

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 128.4 129.0 0.5

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 119.8 120.5 0.7

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 119.4 120.0 0.6

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 118.1 118.7 0.6

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 117.4 118.2 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 117.4 118.2 0.7

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 117.1 117.7 0.6

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 116.5 117.1 0.6

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 116.4 117.0 0.5

Page 423: To determine the system impacts caused by the Project

C-110 GWF Henrietta SISAppendix C

HENTAP2 230-GATES 230 #1 :

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 70 MW 13.5 MVAR Drop : Drop Load at ASHLAN 230 #2 : 65.3 MW 12.9 MVAR Dr : Drop Load at ASHLAN 230 #3 : 66.3 MW 12.6 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 115.1 115.8 0.7

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 114.0 114.7 0.7

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 113.6 114.4 0.8

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 113.2 113.9 0.8

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 45.4 MW 9.2 MVAR Dr : Drop Load at BULLARD 115 #2 : 45.2 MW 9.1 MVAR Dr : Drop Load at BULLARD 115 #3 : 43 MW 8.7 MVAR Drop :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.6 111.3 0.7

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.8 111.2 0.4

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.6 110.1 0.5

Page 424: To determine the system impacts caused by the Project

C-111 GWF Henrietta SISAppendix C

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 42.7 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #2 : 53.3 MW 10.8 MVAR : Drop Load at WOODWARD 115 #3 : 44.6 MW 9 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.3 110.0 0.7

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 13.6 MW 2.7 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.1 109.6 0.5

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.0 109.6 0.5

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 109.0 109.5 0.5

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 4.1 MW 3.5 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.8 109.4 0.6

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.6 109.2 0.5

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.3 109.0 0.6

117

Open Line KEARNEY 70-FRWWTAP 70 #1 : Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.4 108.8 0.5

25

Open Line WILSON A 115-LE GRAND 115 #1 : Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON A 115-WILSON B 115 #1 : Open Line WILSON A 115-MERCED 115 #1 : Open Xfmr WILSON A 115/WILSON 230 #1 : Drop Load at WILSON A 115 #3 : 18.9 MW 3.8 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.0 108.7 0.7

23 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Open Xfmr EXCHEQUR 115/EXCHQRTP 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 108.2 108.7 0.5

98 Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.9 108.5 0.6

Page 425: To determine the system impacts caused by the Project

C-112 GWF Henrietta SISAppendix C

at BARTON 115 #1 : 43.8 MW 8.8 MVAR Dro : Drop Load at BARTON 115 #2 : 37.6 MW 7.6 MVAR Dro : Drop Load at BARTON 115 #3 : 27.3 MW 5.5 MVAR Dro :

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.1 108.5 1.4

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.9 108.4 0.5

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.9 108.4 0.5

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 25.6 MW 5.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 25.8 MW 5.2 MVAR D : Drop Load at MANCHSTR 115 #3 : 36.6 MW 7.4 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.6 108.2 0.6

30

Open Line PANOCHE 115-CHENYT 115 #1 : Open Line PANOCHE 115-PANOCHEJ 115 #1 : Open Xfmr PANOCHE 115/PANOCHE 230 #2 : Open Xfmr PANOCHE 115/DG_PAN1 13.8 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.7 108.2 0.5

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 53.2 MW 10.7 MVAR :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.3 107.8 0.5

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.1 107.7 0.7

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.0 107.6 0.6

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 18.2 MW 3.7 MVAR Drop : Drop Load at MADERA 70 #2 : 23.4 MW 4.7 MVAR Drop :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.9 107.4 0.5

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.8 107.3 0.5

96

Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 29.3 MW 5.9 MVAR Dr : Drop Load at CAL AVE 115 #2 : 31.6 MW 6.4 MVAR Dr : Drop Load at CAL AVE 115 #3 : 24.7 MW 5 MVAR Drop :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.6 107.3 0.7

Page 426: To determine the system impacts caused by the Project

C-113 GWF Henrietta SISAppendix C

86

Open Line KERCKHF2 115-K1-JCT 115 #2 : Open Line KERCKHF2 115-KERCKHF1 115 #1 : Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line KERCKHF2 115-CLOVISJ2 115 #1 : Open Xfmr KERCKHF2 115/KERCKHOF 13.8 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.7 107.2 0.5

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.4 107.0 0.6

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 38 MW 7.7 MVAR Dro : Drop Load at WST FRSO 115 #2 : 39.5 MW 8 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.4 107.0 0.6

72 Open Line HERNDON 230-GREGG 230 #2 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Xfmr HERNDON 230/HERNDN2M 115 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.4 106.9 0.5

100 Open Line HERNDON 115-BARTON 115 #1 : Open Line HERNDON 115-PNDLJ2 115 #1 : Open Xfmr HERNDON 115/HERNDN1M 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.4 106.9 0.5

87

Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 38.8 MW 7.5 MVAR Dr : Drop Load at AIRWAYS 115 #2 : 12.7 MW 2.5 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.3 106.8 0.5

45 Open Line BARTON 115-HERNDON 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.2 106.7 0.5

106

Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-GAURD J1 115 #1 : Open Xfmr KINGSBRG 115/KNGLOBUS 70 #2 : Drop Load at KINGSBRG 115 #3 : 33 MW 6.6 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.1 106.6 0.5

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.1 106.6 0.5

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 106.0 106.5 0.5

121

Open Line REEDLEY 70-TVY VLLY 70 #1 : Open Line REEDLEY 70-PARLIER 70 #1 : Open Line REEDLEY 70-DNUBAJCT 70 #1 : Open Line REEDLEY 70-ORSI JCT 70 #1 : Open Xfmr

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.8 106.3 0.5

Page 427: To determine the system impacts caused by the Project

C-114 GWF Henrietta SISAppendix C

REEDLEY 70/REEDLEY 115 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #2 : Drop Load at REEDLEY 70 #1 : 17.6 MW 3.5 MVAR Dro :

124 Open Line LEMOORE 70-LPRNO TP 70 #1 : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.7 106.2 0.5

49 Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-CORCORAN 115 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.6 106.1 0.5

107

Open Line CORCORAN 115-KINGSBRG 115 #1 : Open Line CORCORAN 115-KINGSBRG 115 #2 : Open Xfmr CORCORAN 115/CORCORAN 70 #2 : Drop Load at CORCORAN 115 #3 : 16.4 MW 3.3 MVAR D : Drop Load at CORCORAN 115 #4 : 18 MW 3.6 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 105.6 106.1 0.5

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.2 128.7 0.5

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.2 120.9 0.7

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.8 120.4 0.6

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.7 119.2 0.5

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.0 118.7 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.0 118.7 0.7

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.7 118.2 0.5

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.1 117.7 0.6

Page 428: To determine the system impacts caused by the Project

C-115 GWF Henrietta SISAppendix C

FIGRDN 1 230-FIGRDN 2 230 #1 :

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.1 117.6 0.5

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 70 MW 13.5 MVAR Drop : Drop Load at ASHLAN 230 #2 : 65.3 MW 12.9 MVAR Dr : Drop Load at ASHLAN 230 #3 : 66.3 MW 12.6 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.5 0.6

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.8 115.5 0.6

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.5 115.3 0.7

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.2 114.9 0.7

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.0 112.4 0.5

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 45.4 MW 9.2 MVAR Dr : Drop Load at BULLARD 115 #2 : 45.2 MW 9.1 MVAR Dr : Drop Load at BULLARD 115 #3 : 43 MW 8.7 MVAR Drop :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.8 112.4 0.6

Page 429: To determine the system impacts caused by the Project

C-116 GWF Henrietta SISAppendix C

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.9 111.4 0.5

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 42.7 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #2 : 53.3 MW 10.8 MVAR : Drop Load at WOODWARD 115 #3 : 44.6 MW 9 MVAR Dro :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.6 111.2 0.6

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 13.6 MW 2.7 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.4 110.9 0.4

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.4 110.8 0.5

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.3 110.8 0.5

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 4.1 MW 3.5 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.1 110.7 0.6

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.0 110.5 0.5

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.7 110.3 0.6

25

Open Line WILSON A 115-LE GRAND 115 #1 : Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON A 115-WILSON B 115 #1 : Open Line WILSON A 115-MERCED 115 #1 : Open Xfmr WILSON A 115/WILSON 230 #1 : Drop Load at WILSON A 115 #3 : 18.9 MW 3.8 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.5 110.2 0.6

117

Open Line KEARNEY 70-FRWWTAP 70 #1 : Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.7 110.1 0.4

23 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Open Xfmr EXCHEQUR 115/EXCHQRTP 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.6 110.0 0.4

Page 430: To determine the system impacts caused by the Project

C-117 GWF Henrietta SISAppendix C

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 43.8 MW 8.8 MVAR Dro : Drop Load at BARTON 115 #2 : 37.6 MW 7.6 MVAR Dro : Drop Load at BARTON 115 #3 : 27.3 MW 5.5 MVAR Dro :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.3 109.9 0.6

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.5 109.8 1.3

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.3 109.7 0.4

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.3 109.7 0.5

30

Open Line PANOCHE 115-CHENYT 115 #1 : Open Line PANOCHE 115-PANOCHEJ 115 #1 : Open Xfmr PANOCHE 115/PANOCHE 230 #2 : Open Xfmr PANOCHE 115/DG_PAN1 13.8 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.1 109.6 0.4

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 25.6 MW 5.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 25.8 MW 5.2 MVAR D : Drop Load at MANCHSTR 115 #3 : 36.6 MW 7.4 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.6 0.6

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 53.2 MW 10.7 MVAR :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.7 109.2 0.5

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.5 109.2 0.6

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.5 109.0 0.6

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 18.2 MW 3.7 MVAR Drop : Drop Load at MADERA 70 #2 : 23.4 MW 4.7 MVAR Drop :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.4 108.8 0.4

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.3 108.8 0.4

96 Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 29.3 MW 5.9 MVAR Dr : Drop

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.1 108.7 0.6

Page 431: To determine the system impacts caused by the Project

C-118 GWF Henrietta SISAppendix C

Load at CAL AVE 115 #2 : 31.6 MW 6.4 MVAR Dr : Drop Load at CAL AVE 115 #3 : 24.7 MW 5 MVAR Drop :

86

Open Line KERCKHF2 115-K1-JCT 115 #2 : Open Line KERCKHF2 115-KERCKHF1 115 #1 : Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line KERCKHF2 115-CLOVISJ2 115 #1 : Open Xfmr KERCKHF2 115/KERCKHOF 13.8 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.2 108.7 0.5

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.5 0.6

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 38 MW 7.7 MVAR Dro : Drop Load at WST FRSO 115 #2 : 39.5 MW 8 MVAR Dro :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.5 0.6

72 Open Line HERNDON 230-GREGG 230 #2 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Xfmr HERNDON 230/HERNDN2M 115 #2 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.0 108.4 0.4

100 Open Line HERNDON 115-BARTON 115 #1 : Open Line HERNDON 115-PNDLJ2 115 #1 : Open Xfmr HERNDON 115/HERNDN1M 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.4 0.5

87

Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 38.8 MW 7.5 MVAR Dr : Drop Load at AIRWAYS 115 #2 : 12.7 MW 2.5 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.2 0.4

45 Open Line BARTON 115-HERNDON 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.2 0.4

106

Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-GAURD J1 115 #1 : Open Xfmr KINGSBRG 115/KNGLOBUS 70 #2 : Drop Load at KINGSBRG 115 #3 : 33 MW 6.6 MVAR Dro :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.7 108.1 0.5

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.6 108.1 0.4

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.6 108.0 0.5

121 Open Line REEDLEY 70-TVY VLLY 70 #1 : Open STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.3 107.8 0.5

Page 432: To determine the system impacts caused by the Project

C-119 GWF Henrietta SISAppendix C

Line REEDLEY 70-PARLIER 70 #1 : Open Line REEDLEY 70-DNUBAJCT 70 #1 : Open Line REEDLEY 70-ORSI JCT 70 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #2 : Drop Load at REEDLEY 70 #1 : 17.6 MW 3.5 MVAR Dro :

124 Open Line LEMOORE 70-LPRNO TP 70 #1 : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.3 107.7 0.4

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.9 117.4 0.5

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.1 109.8 0.7

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.8 109.3 0.6

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.6 108.1 0.5

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.0 107.6 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.0 107.6 0.7

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.7 107.2 0.5

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 106.7 0.6

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 106.6 0.5

Page 433: To determine the system impacts caused by the Project

C-120 GWF Henrietta SISAppendix C

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 70 MW 13.5 MVAR Drop : Drop Load at ASHLAN 230 #2 : 65.3 MW 12.9 MVAR Dr : Drop Load at ASHLAN 230 #3 : 66.3 MW 12.6 MVAR Dr :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.9 105.5 0.6

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.8 104.5 0.6

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.5 104.2 0.7

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.1 103.8 0.7

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 45.4 MW 9.2 MVAR Dr : Drop Load at BULLARD 115 #2 : 45.2 MW 9.1 MVAR Dr : Drop Load at BULLARD 115 #3 : 43 MW 8.7 MVAR Drop :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.8 101.4 0.6

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.0 101.3 0.3

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.9 100.4 0.5

103 Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.6 100.2 0.6

Page 434: To determine the system impacts caused by the Project

C-121 GWF Henrietta SISAppendix C

Drop Load at WOODWARD 115 #1 : 42.7 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #2 : 53.3 MW 10.8 MVAR : Drop Load at WOODWARD 115 #3 : 44.6 MW 9 MVAR Dro :

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

TEMBLOR -BELRIDGE 115.00kV Ckt#1 Sec# 1 743.02 Amps 134.6 134.5 -0.1

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

TEMBLOR -BELRIDGE 115.00kV Ckt#1 Sec# 1 743.02 Amps 100.7 100.7 0.0

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 116.9 116.7 -0.2

30

Open Line PANOCHE 115-CHENYT 115 #1 : Open Line PANOCHE 115-PANOCHEJ 115 #1 : Open Xfmr PANOCHE 115/PANOCHE 230 #2 : Open Xfmr PANOCHE 115/DG_PAN1 13.8 #1 :

TOMATAK -MENDOTA 70.00kV Ckt#1 Sec# 1 395.9 Amps 106.6 106.2 -0.4

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

TVY VLLY-REEDLEY 70.00kV Ckt#1 Sec# 1 297.75 Amps 138.3 138.2 -0.1

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 148.5 149.2 0.7 lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 143.5 144.3 0.8

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 133.9 134.3 0.4

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 133.0 133.6 0.6

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.7 133.4 0.7

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.7 133.3 0.7

75 Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 70 MW 13.5 MVAR Drop : Drop Load

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.9 133.3 0.4

Page 435: To determine the system impacts caused by the Project

C-122 GWF Henrietta SISAppendix C

at ASHLAN 230 #2 : 65.3 MW 12.9 MVAR Dr : Drop Load at ASHLAN 230 #3 : 66.3 MW 12.6 MVAR Dr :

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.9 133.3 0.4

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.9 133.3 0.4

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.6 133.0 0.4

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.5 132.3 0.8

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 131.3 132.0 0.7

27

Open Line EL CAPTN 115-CASTLE 115 #1 : Open Line EL CAPTN 115-WILSON B 115 #1 : Drop Load at EL CAPTN 115 #1 : 19.7 MW 4 MVAR Dro : Drop Load at EL CAPTN 115 #2 : 26.2 MW 5.3 MVAR D : Drop Load at EL CAPTN 115 #3 : 33.5 MW 6.7 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.4 130.1 0.7

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 45.4 MW 9.2 MVAR Dr : Drop Load at BULLARD 115 #2 : 45.2 MW 9.1 MVAR Dr : Drop Load at

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.4 130.0 0.7

Page 436: To determine the system impacts caused by the Project

C-123 GWF Henrietta SISAppendix C

BULLARD 115 #3 : 43 MW 8.7 MVAR Drop :

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 42.7 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #2 : 53.3 MW 10.8 MVAR : Drop Load at WOODWARD 115 #3 : 44.6 MW 9 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.1 129.8 0.7

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.8 129.5 0.7

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.9 129.5 0.6

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 4.1 MW 3.5 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.6 129.3 0.7

22

Open Line ATWATER 115-CASTLE 115 #1 : Open Line ATWATER 115-CRESEY T 115 #1 : Open Line ATWATER 115-WILSON A 115 #1 : Drop Load at ATWATER 115 #1 : 32.8 MW 6.6 MVAR Dr : Drop Load at ATWATER 115 #2 : 28.7 MW 5.8 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.1 128.8 0.7

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.1 128.8 0.7

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.0 128.7 0.7

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.9 128.6 0.7

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.9 128.6 0.7

Page 437: To determine the system impacts caused by the Project

C-124 GWF Henrietta SISAppendix C

Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 43.8 MW 8.8 MVAR Dro : Drop Load at BARTON 115 #2 : 37.6 MW 7.6 MVAR Dro : Drop Load at BARTON 115 #3 : 27.3 MW 5.5 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.4 128.1 0.7

28

Open Line MERCED 115-ATWATR J 115 #1 : Open Line MERCED 115-WILSON A 115 #1 : Open Line MERCED 115-WILSON B 115 #2 : Open Xfmr MERCED 115/MERCED M 115 #2 : Drop Load at MERCED 115 #1 : 37.6 MW 7.6 MVAR Dro : Drop Load at MERCED 115 #3 : 19.7 MW 3.9 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.3 128.0 0.7

117

Open Line KEARNEY 70-FRWWTAP 70 #1 : Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.3 127.9 0.6

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.0 127.7 0.7

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.0 127.7 0.7

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 25.6 MW 5.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 25.8 MW 5.2 MVAR D : Drop Load at MANCHSTR 115 #3 : 36.6 MW 7.4 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.9 127.6 0.7

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.9 127.5 0.6

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.7 127.4 0.7

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.8 127.1 1.3

96

Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 29.3 MW 5.9 MVAR Dr : Drop Load at CAL AVE 115 #2 : 31.6 MW 6.4 MVAR Dr : Drop Load at CAL AVE 115 #3 : 24.7 MW 5 MVAR Drop :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 126.9 0.7

Page 438: To determine the system impacts caused by the Project

C-125 GWF Henrietta SISAppendix C

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 126.8 0.7

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 53.2 MW 10.7 MVAR :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.3 126.8 0.5

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.0 126.7 0.7

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 38 MW 7.7 MVAR Dro : Drop Load at WST FRSO 115 #2 : 39.5 MW 8 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.0 126.7 0.7

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 18.2 MW 3.7 MVAR Drop : Drop Load at MADERA 70 #2 : 23.4 MW 4.7 MVAR Drop :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.4 0.7

32

Open Line ORO LOMA 70-DOS PALS 70 #1 : Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line ORO LOMA 70-POSO J1 70 #1 : Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Drop Load at ORO LOMA 70 #1 : 8.7 MW 1.7 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.6 126.4 0.8

106

Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-GAURD J1 115 #1 : Open Xfmr KINGSBRG 115/KNGLOBUS 70 #2 : Drop Load at KINGSBRG 115 #3 : 33 MW 6.6 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.7 126.2 0.5

87

Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 38.8 MW 7.5 MVAR Dr : Drop Load at AIRWAYS 115 #2 : 12.7 MW 2.5 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.6 126.2 0.7

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.6 126.2 0.7

121

Open Line REEDLEY 70-TVY VLLY 70 #1 : Open Line REEDLEY 70-PARLIER 70 #1 : Open Line REEDLEY 70-DNUBAJCT 70 #1 : Open Line REEDLEY 70-ORSI JCT 70 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #2 : Drop Load at REEDLEY 70 #1 : 17.6 MW 3.5 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.6 126.1 0.5

34 Open Line CANAL 70-LVNGSTNT 70 #1 : Open Line CANAL 70-SNTA RTA 70 #1 : Open Line

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.1 125.8 0.7

Page 439: To determine the system impacts caused by the Project

C-126 GWF Henrietta SISAppendix C

CANAL 70-ORTIGA 70 #1 : Drop Load at CANAL 70 #1 : 30.9 MW 6.2 MVAR Dropp : Drop Load at CANAL 70 #2 : 31.7 MW 6.4 MVAR Dropp :

11

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line MELONES 230-WILSON 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.9 125.7 0.8

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 30.7 MW 1.3 MVAR D :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#1 150 MVA 130.9 131.4 0.5

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 30.7 MW 1.3 MVAR D :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#2 75 MVA 130.9 131.4 0.5

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 30.7 MW 1.3 MVAR D :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#3 75 MVA 130.9 131.4 0.5

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 148.9 149.6 0.8 lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 135.4 136.3 0.8

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 130.5 131.6 1.1

58 Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.9 129.0 1.1

Page 440: To determine the system impacts caused by the Project

C-127 GWF Henrietta SISAppendix C

Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 127.1 127.8 0.7

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.5 127.3 0.8

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 127.3 1.1

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 127.3 1.1

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 20.6 MW 4.1 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 126.2 127.3 1.1

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.8 126.6 0.8

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 70 MW 13.5 MVAR Drop : Drop Load at ASHLAN 230 #2 : 65.3 MW 12.9 MVAR Dr : Drop Load at ASHLAN 230 #3 : 66.3 MW 12.6 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.9 126.0 1.1

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.1 125.2 1.1

Page 441: To determine the system impacts caused by the Project

C-128 GWF Henrietta SISAppendix C

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.2 125.0 0.8

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.2 122.9 0.7

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.5 121.2 0.7

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.3 121.0 0.7

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 45.4 MW 9.2 MVAR Dr : Drop Load at BULLARD 115 #2 : 45.2 MW 9.1 MVAR Dr : Drop Load at BULLARD 115 #3 : 43 MW 8.7 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.0 120.9 0.9

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 42.7 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #2 : 53.3 MW 10.8 MVAR : Drop Load at WOODWARD 115 #3 : 44.6 MW 9 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.6 120.5 0.9

27

Open Line EL CAPTN 115-CASTLE 115 #1 : Open Line EL CAPTN 115-WILSON B 115 #1 : Drop Load at EL CAPTN 115 #1 : 19.7 MW 4 MVAR Dro : Drop Load at EL CAPTN 115 #2 : 26.2 MW 5.3 MVAR D : Drop Load at EL CAPTN 115 #3 : 33.5 MW 6.7 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.7 120.3 0.6

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.4 120.0 0.6

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 4.1 MW 3.5 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.8 119.7 0.9

Page 442: To determine the system impacts caused by the Project

C-129 GWF Henrietta SISAppendix C

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.3 119.2 0.9

22

Open Line ATWATER 115-CASTLE 115 #1 : Open Line ATWATER 115-CRESEY T 115 #1 : Open Line ATWATER 115-WILSON A 115 #1 : Drop Load at ATWATER 115 #1 : 32.8 MW 6.6 MVAR Dr : Drop Load at ATWATER 115 #2 : 28.7 MW 5.8 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.0 118.6 0.6

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.4 118.4 1.0

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 43.8 MW 8.8 MVAR Dro : Drop Load at BARTON 115 #2 : 37.6 MW 7.6 MVAR Dro : Drop Load at BARTON 115 #3 : 27.3 MW 5.5 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.1 118.0 0.9

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.1 117.8 0.7

28

Open Line MERCED 115-ATWATR J 115 #1 : Open Line MERCED 115-WILSON A 115 #1 : Open Line MERCED 115-WILSON B 115 #2 : Open Xfmr MERCED 115/MERCED M 115 #2 : Drop Load at MERCED 115 #1 : 37.6 MW 7.6 MVAR Dro : Drop Load at MERCED 115 #3 : 19.7 MW 3.9 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.1 117.8 0.6

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 74.3 MW 15 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.8 117.7 0.9

117

Open Line KEARNEY 70-FRWWTAP 70 #1 : Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.0 117.7 0.7

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 45.3 MW 9.1 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.5 117.4 0.9

99 Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 117.3 0.9

Page 443: To determine the system impacts caused by the Project

C-130 GWF Henrietta SISAppendix C

Drop Load at MANCHSTR 115 #1 : 25.6 MW 5.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 25.8 MW 5.2 MVAR D : Drop Load at MANCHSTR 115 #3 : 36.6 MW 7.4 MVAR D :

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 31.1 MW 6.3 MVAR Dro : Drop Load at PNEDLE 115 #3 : 40.9 MW 8.2 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.5 117.2 0.7

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.2 117.0 1.7

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.8 116.4 0.7

96

Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 29.3 MW 5.9 MVAR Dr : Drop Load at CAL AVE 115 #2 : 31.6 MW 6.4 MVAR Dr : Drop Load at CAL AVE 115 #3 : 24.7 MW 5 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.3 0.9

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 53.2 MW 10.7 MVAR :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.5 116.2 0.8

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.1 116.0 0.9

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 38 MW 7.7 MVAR Dro : Drop Load at WST FRSO 115 #2 : 39.5 MW 8 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.1 116.0 0.9

32

Open Line ORO LOMA 70-DOS PALS 70 #1 : Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line ORO LOMA 70-POSO J1 70 #1 : Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Drop Load at ORO LOMA 70 #1 : 8.7 MW 1.7 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.8 115.7 0.9

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 18.2 MW 3.7 MVAR Drop : Drop Load at MADERA 70 #2 : 23.4 MW 4.7 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.0 115.7 0.7

87

Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 38.8 MW 7.5 MVAR Dr : Drop Load at AIRWAYS 115 #2 : 12.7 MW 2.5 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.7 115.4 0.7

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.7 115.3 0.7

Page 444: To determine the system impacts caused by the Project

C-131 GWF Henrietta SISAppendix C

Load at CLOVIS-1 115 #1 : 51.6 MW 10.4 MVAR :

106

Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-GAURD J1 115 #1 : Open Xfmr KINGSBRG 115/KNGLOBUS 70 #2 : Drop Load at KINGSBRG 115 #3 : 33 MW 6.6 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.6 115.3 0.8

121

Open Line REEDLEY 70-TVY VLLY 70 #1 : Open Line REEDLEY 70-PARLIER 70 #1 : Open Line REEDLEY 70-DNUBAJCT 70 #1 : Open Line REEDLEY 70-ORSI JCT 70 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #2 : Drop Load at REEDLEY 70 #1 : 17.6 MW 3.5 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.4 115.1 0.8

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.9 114.6 0.6

49 Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-CORCORAN 115 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.9 114.6 0.7

107

Open Line CORCORAN 115-KINGSBRG 115 #1 : Open Line CORCORAN 115-KINGSBRG 115 #2 : Open Xfmr CORCORAN 115/CORCORAN 70 #2 : Drop Load at CORCORAN 115 #3 : 16.4 MW 3.3 MVAR D : Drop Load at CORCORAN 115 #4 : 18 MW 3.6 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.9 114.6 0.7

124 Open Line LEMOORE 70-LPRNO TP 70 #1 : Drop Load at LEMOORE 70 #1 : 19.1 MW 3.8 MVAR Dro : Drop Load at LEMOORE 70 #2 : 33.2 MW 6.7 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.8 114.5 0.7

34

Open Line CANAL 70-LVNGSTNT 70 #1 : Open Line CANAL 70-SNTA RTA 70 #1 : Open Line CANAL 70-ORTIGA 70 #1 : Drop Load at CANAL 70 #1 : 30.9 MW 6.2 MVAR Dropp : Drop Load at CANAL 70 #2 : 31.7 MW 6.4 MVAR Dropp :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.7 114.4 0.6

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.6 114.3 0.7

94 Open Line WAHTOKE 115-MC CALL 115 #1 : Open Line WAHTOKE 115-GERAWAN 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.6 114.3 0.7

Page 445: To determine the system impacts caused by the Project

C-132 GWF Henrietta SISAppendix C

Drop Load at WAHTOKE 115 #2 : 30.7 MW 6.2 MVAR Dr : Drop Load at WAHTOKE 115 #3 : 21.1 MW 4.2 MVAR Dr :

45 Open Line BARTON 115-HERNDON 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.6 114.2 0.7

72 Open Line HERNDON 230-GREGG 230 #2 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Xfmr HERNDON 230/HERNDN2M 115 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.6 114.2 0.6

122

Open Line DINUBA 70-STCRRL J 70 #1 : Open Line DINUBA 70-DNUBAJCT 70 #1 : Drop Load at DINUBA 70 #1 : 19.4 MW 3.9 MVAR Drop : Drop Load at DINUBA 70 #2 : 9.4 MW 1.9 MVAR Dropp :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.5 114.1 0.7

113 Open Line BIOLA 70-OLDKERN 70 #1 : Drop Load at BIOLA 70 #1 : 22 MW 4.4 MVAR Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.4 114.1 0.6

134 Open Line KNGLOBUS 70-HRDWK TP 70 #1 : Open Line KNGLOBUS 70-CAMDEN 70 #1 : Open Xfmr KNGLOBUS 70/KINGSBRG 115 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.4 114.1 0.6

68 Open Line GATES 230-MIDWAY 230 #1 : Open Line GATES 230-ARCO 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.4 114.0 0.7

21

Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line CHWCHLLA 115-CERTANJ1 115 #1 : Drop Load at CHWCHLLA 115 #1 : 10.3 MW 2 MVAR Dro : Drop Load at CHWCHLLA 115 #2 : 14 MW 2.8 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.1 113.8 0.6

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

WOODWARD-CHLDHOSP 115.00kV Ckt#1 Sec# 1 973.96 Amps 109.8 109.9 0.1

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at

WRNRVLLE-STANDFRD 115.00kV Ckt#1 Sec# 1 938.82 Amps 105.5 105.9 0.4

Page 446: To determine the system impacts caused by the Project

C-133 GWF Henrietta SISAppendix C

COTTLE B 230 #2 : 30.7 MW 1.3 MVAR D :

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 26.7 MW 1.2 MVAR D : Drop Generator at HELMS 3 18 #**: 404 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 30.7 MW 1.3 MVAR D :

WRNRVLLE-STANDFRD 115.00kV Ckt#2 Sec# 1 938.82 Amps 105.5 105.9 0.4

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO LOSBANOS - DS AMIGO 230.0 Ckt#1 Sec# 1 849.96 Amps 101.0 101.7 0.7

2013 Summer Off-Peak

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

AIRWAYJ1-MANCHSTR 115.00kV Ckt#1 Sec# 1 1124.58 Amps 105.7 105.9 0.1

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

AIRWAYJ2-BARTON 115.00kV Ckt#1 Sec# 1 1124.58 Amps 119.0 119.1 0.1

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

AIRWAYJ2-BARTON 115.00kV Ckt#1 Sec# 1 1124.58 Amps 111.3 111.2 -0.1

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 11.6 MW 2.3 MVAR D : Drop Load at MANCHSTR 115 #2 : 11.7 MW 2.3 MVAR D : Drop Load at MANCHSTR 115 #3 : 16.6 MW 3.3 MVAR D :

AIRWAYJ2-BARTON 115.00kV Ckt#1 Sec# 1 1124.58 Amps 103.5 103.5 0.0

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 23.4 MW 4.7 MVAR D : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

AIRWAYJ2-BARTON 115.00kV Ckt#1 Sec# 1 1124.58 Amps 101.4 101.3 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 119.1 119.2 0.0

44 Open Line AIRWAYJ2 115-AIRWAYS 115 #1 : Open Line AIRWAYJ2 115-BARTON 115 #1 : Open Line AIRWAYJ2 115-SANGER 115 #1 : Open Line

CLOVISJ1-SANGER 115.00kV Ckt#1 Sec# 1 973.96 Amps 107.8 107.9 0.0

Page 447: To determine the system impacts caused by the Project

C-134 GWF Henrietta SISAppendix C

AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

44

Open Line AIRWAYJ2 115-AIRWAYS 115 #1 : Open Line AIRWAYJ2 115-BARTON 115 #1 : Open Line AIRWAYJ2 115-SANGER 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

CLOVISJ1-WWARD JT 115.00kV Ckt#1 Sec# 1 743.02 Amps 126.0 126.0 0.0

46

Open Line BARTON 115-HERNDON 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

CLOVISJ1-WWARD JT 115.00kV Ckt#1 Sec# 1 743.02 Amps 114.5 114.5 0.0

45 Open Line BARTON 115-HERNDON 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

CLOVISJ1-WWARD JT 115.00kV Ckt#1 Sec# 1 743.02 Amps 106.1 106.1 0.0

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

CLOVISJ1-WWARD JT 115.00kV Ckt#1 Sec# 1 743.02 Amps 100.0 100.1 0.2

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

COPPRMNE-RIVERROC 70.00kV Ckt#1 Sec# 1 437.14 Amps 100.7 100.7 0.0

lbs_dlo_5400, Los Banos - Gates & Los Banos - Midway 500-kV DLO w/ Path IRAS

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.5 120.2 0.7

60 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Open Line GREGG 230-HELMS PP 230 #2 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.9 118.5 0.6

Page 448: To determine the system impacts caused by the Project

C-135 GWF Henrietta SISAppendix C

69

Open Line HELMS PP 230-GREGG 230 #1 : Open Line HELMS PP 230-GREGG 230 #2 : Open Xfmr HELMS PP 230/HELMS 1 18 #1 : Open Xfmr HELMS PP 230/HELMS 2 18 #1 : Open Xfmr HELMS PP 230/HELMS 3 18 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.9 118.5 0.6

lbn_dlo_5400,

Los Banos - Tesla & Los Banos - Tracy 500-kV DLO w/ Path IRAS

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.0 114.8 0.8

14 Open Line BORDEN 230-GREGG 230 #1 : Open Line BORDEN 230-GREGG 230 #2 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.8 111.1 0.3

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line HELM 230-MC CALL 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.0 108.7 0.7

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.6 107.3 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line PANOCHE 230-HELM 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.6 107.3 0.7

62

Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 33.6 MW 6.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.7 104.4 0.7

11

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 12.7 MW 0.5 MVAR D : Open Line MELONES 230-WILSON 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.2 102.0 0.8

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line

GATES -PANOCHE 230.00kV Ckt#1 Sec# 1 849.96 Amps 103.6 104.2 0.6

Page 449: To determine the system impacts caused by the Project

C-136 GWF Henrietta SISAppendix C

PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

HELM -PANOCHE 230.00kV Ckt#1 Sec# 1 849.96 Amps 129.6 129.9 0.4

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

LASPALMS-AIRWAYJ1 115.00kV Ckt#1 Sec# 1 1124.58 Amps 115.6 115.8 0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 15 MW 3 MVAR Dropp : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 16.8 MW 3.4 MVAR D :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 121.7 122.5 0.8

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

LEPRNOFD-GWF_HEP 115.00kV Ckt#1 Sec# 1 743.02 Amps 100.6 99.6 -0.9

lbn_dlo_5400,

Los Banos - Tesla & Los Banos - Tracy 500-kV DLO w/ Path IRAS

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 179.0 179.9 0.9

10

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 12.7 MW 0.5 MVAR D : Open Line WARNERVL 230-WILSON 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 116.9 117.5 0.6

60 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Open

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 115.0 115.5 0.5

Page 450: To determine the system impacts caused by the Project

C-137 GWF Henrietta SISAppendix C

Line GREGG 230-HELMS PP 230 #2 :

69

Open Line HELMS PP 230-GREGG 230 #1 : Open Line HELMS PP 230-GREGG 230 #2 : Open Xfmr HELMS PP 230/HELMS 1 18 #1 : Open Xfmr HELMS PP 230/HELMS 2 18 #1 : Open Xfmr HELMS PP 230/HELMS 3 18 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 115.0 115.5 0.5

12 Open Line MELONES 230-WILSON 230 #1 : Open Line WARNERVL 230-WILSON 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 113.2 113.8 0.6

56

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 112.3 112.8 0.5

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 111.1 111.6 0.6

63

Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 111.0 111.5 0.5

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 15 MW 3 MVAR Dropp : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 16.8 MW 3.4 MVAR D :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 110.6 111.2 0.6

55

Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 110.1 110.6 0.5

64 Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 110.0 110.5 0.5

Page 451: To determine the system impacts caused by the Project

C-138 GWF Henrietta SISAppendix C

HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line GREGG 230-FGRDN T2 230 #1 : Open Line FGRDN T2 230-FIGRDN 2 230 #1 : Open Line FGRDN T2 230-ASHLAN 230 #1 : Drop Load at FIGRDN 2 230 #1 : 24.1 MW 4.8 MVAR D :

62

Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 33.6 MW 6.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 109.0 109.5 0.4

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 12.7 MW 0.5 MVAR D : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 14.6 MW 0.6 MVAR D :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 108.9 109.4 0.5

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.8 107.3 0.5

65

Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 33.6 MW 6.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Open Line GREGG 230-FGRDN T2 230 #1 : Open Line FGRDN T2 230-FIGRDN 2 230 #1 : Open Line FGRDN T2 230-ASHLAN 230 #1 : Drop Load at FIGRDN 2 230 #1 : 24.1 MW 4.8 MVAR D :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.4 106.9 0.5

Page 452: To determine the system impacts caused by the Project

C-139 GWF Henrietta SISAppendix C

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.4 106.8 0.4

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line PANOCHE 230-HELM 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.4 106.8 0.4

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 106.1 106.6 0.5

44

Open Line AIRWAYJ2 115-AIRWAYS 115 #1 : Open Line AIRWAYJ2 115-BARTON 115 #1 : Open Line AIRWAYJ2 115-SANGER 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.6 106.0 0.5

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 14.1 MW 2.8 MVAR Dro : Drop Load at PNEDLE 115 #3 : 18.5 MW 3.7 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.4 105.8 0.5

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 23.4 MW 4.7 MVAR D : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.3 105.8 0.5

75 Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.3 105.8 0.5

Page 453: To determine the system impacts caused by the Project

C-140 GWF Henrietta SISAppendix C

at ASHLAN 230 #1 : 31.7 MW 6.1 MVAR Dro : Drop Load at ASHLAN 230 #2 : 29.5 MW 5.8 MVAR Dro : Drop Load at ASHLAN 230 #3 : 30 MW 5.7 MVAR Dropp :

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 3.1 MW 2.6 MVAR Dr :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.2 105.7 0.5

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line HELM 230-MC CALL 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 105.3 105.7 0.4

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 19.3 MW 3.9 MVAR D : Drop Load at WOODWARD 115 #2 : 24.1 MW 4.8 MVAR D : Drop Load at WOODWARD 115 #3 : 20.2 MW 4 MVAR Dro :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.9 105.4 0.5

11

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 12.7 MW 0.5 MVAR D : Open Line MELONES 230-WILSON 230 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.9 105.4 0.5

46

Open Line BARTON 115-HERNDON 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.9 105.4 0.5

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 19.8 MW 4 MVAR Dropp : Drop Load at BARTON 115 #2 : 17 MW 3.4 MVAR Dropp : Drop Load at BARTON 115 #3 : 12.3 MW 2.5 MVAR Dro :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.9 105.4 0.5

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.9 105.3 0.4

104 Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 20.5 MW 4.1 MVAR Dr : Drop Load at

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.8 105.3 0.5

Page 454: To determine the system impacts caused by the Project

C-141 GWF Henrietta SISAppendix C

BULLARD 115 #2 : 20.4 MW 4.1 MVAR Dr : Drop Load at BULLARD 115 #3 : 19.5 MW 3.9 MVAR Dr :

35

Open Line LOS BANS 70-CHEVPIPE 70 #1 : Open Line LOS BANS 70-WRGHT PP 70 #1 : Open Line LOS BANS 70-PCHCO PP 70 #1 : Open Line LOS BANS 70-ONLL PMP 69 #1 : Open Xfmr LOS BANS 70/LOSBANOS 230 #3 : Open Xfmr LOS BANS 70/LOSBANOS 230 #4 :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.7 105.1 0.5

34

Open Line CANAL 70-LVNGSTNT 70 #1 : Open Line CANAL 70-SNTA RTA 70 #1 : Open Line CANAL 70-ORTIGA 70 #1 : Drop Load at CANAL 70 #1 : 13.5 MW 2.7 MVAR Dropp : Drop Load at CANAL 70 #2 : 13.8 MW 2.8 MVAR Dropp :

LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 104.6 105.1 0.5

52 Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 :

MALAGATP-ULTPWRJ 115.00kV Ckt#1 Sec# 1 743.02 Amps 101.9 101.9 0.0

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 147.0 147.4 0.4

55

Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 106.9 110.3 3.4

44

Open Line AIRWAYJ2 115-AIRWAYS 115 #1 : Open Line AIRWAYJ2 115-BARTON 115 #1 : Open Line AIRWAYJ2 115-SANGER 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 106.7 107.1 0.4

Page 455: To determine the system impacts caused by the Project

C-142 GWF Henrietta SISAppendix C

LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

lbs_dlo_5400, Los Banos - Gates & Los Banos - Midway 500-kV DLO w/ Path IRAS

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 104.9 105.4 0.5

46

Open Line BARTON 115-HERNDON 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 101.0 101.3 0.4

79

Open Line MC CALL 230-HELM 230 #1 : Open Line MC CALL 230-BALCH3TP 230 #1 : Open Line MC CALL 230-Q128 230 #2 : Open Xfmr MC CALL 230/MCCALL1M 115 #1 : Open Xfmr MC CALL 230/MCCALL3M 115 #3 :

MC CALL -MCCALL2M 230.00/ 115.00kV Bk#2 465 MVA 117.7 117.6 -0.1

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 110.1 110.2 0.1

55

Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 105.3 107.2 1.9

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line HELM 230-MC CALL 230 #1 :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 102.3 102.4 0.0

56

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 101.6 102.1 0.5

91 Open Line MALAGA 115-SANGER 115 #1 : Open Line MALAGA 115-PPG 115 #1 : Open Line

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 101.8 101.8 0.0

Page 456: To determine the system impacts caused by the Project

C-143 GWF Henrietta SISAppendix C

MALAGA 115-MALAGATP 115 #1 : Open Line MALAGA 115-KRCDP 115 #1 : Drop Load at MALAGA 115 #1 : 11.6 MW 2.3 MVAR Dro : Drop Load at MALAGA 115 #2 : 10.4 MW 2.1 MVAR Dro : Drop Load at MALAGA 115 #3 : 10.6 MW 2.1 MVAR Dro :

94

Open Line WAHTOKE 115-MC CALL 115 #1 : Open Line WAHTOKE 115-GERAWAN 115 #1 : Drop Load at WAHTOKE 115 #2 : 13.9 MW 2.8 MVAR Dr : Drop Load at WAHTOKE 115 #3 : 9.5 MW 1.9 MVAR Dro :

MC CALL -SANGER 115.00kV Ckt#3 Sec# 1 973.96 Amps 101.4 101.4 0.0

79

Open Line MC CALL 230-HELM 230 #1 : Open Line MC CALL 230-BALCH3TP 230 #1 : Open Line MC CALL 230-Q128 230 #2 : Open Xfmr MC CALL 230/MCCALL1M 115 #1 : Open Xfmr MC CALL 230/MCCALL3M 115 #3 :

MCCALL2M-MC CALL 115.00/ 115.00kV Bk#2 465 MVA 116.5 116.4 -0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

MORROBAY-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 111.8 111.5 -0.2

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

PANOCHE -DS AMIGO 230.00kV Ckt#1 Sec# 1 849.96 Amps 122.1 122.7 0.6

lbs_dlo_5400, Los Banos - Gates & Los Banos - Midway 500-kV DLO w/ Path IRAS

PANOCHE -DS AMIGO 230.00kV Ckt#1 Sec# 1 849.96 Amps 103.1 103.8 0.6

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

PANOCHE -LOSBANOS 230.00kV Ckt#1 Sec# 1 974.97 Amps 101.3 102.0 0.6

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

PANOCHE -LOSBANOS 230.00kV Ckt#2 Sec# 1 849.96 Amps 101.9 102.6 0.7

lbs_dlo_5400, Los Banos - Gates & Los Banos - Midway 500-kV DLO w/ Path IRAS

PANOCHE -LOSBANOS 230.00kV Ckt#2 Sec# 1 849.96 Amps 101.6 102.2 0.6

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

PSA RBLS-SAN MIGL 70.00kV Ckt#1 Sec# 1 346.41 Amps 145.6 145.5 -0.2

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

PSA RBLS-SAN MIGL 70.00kV Ckt#1 Sec# 1 346.41 Amps 101.8 101.8 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.4 129.4 0.0

Page 457: To determine the system impacts caused by the Project

C-144 GWF Henrietta SISAppendix C

Line GATES 230-TEMPLETN 230 #1 :

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.4 129.4 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.4 129.4 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 119.4 119.4 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q239SWST-MORROBAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.4 129.4 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q239SWST-MORROBAY 230.00kV Ckt#2 Sec# 1 976.48 Amps 129.4 129.4 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 129.4 129.4 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 129.4 129.4 0.0

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

REEDLEY -TVY VLLY 70.00kV Ckt#1 Sec# 1 297.75 Amps 140.2 140.2 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

SAN MIGL-COLNGA 1 70.00kV Ckt#1 Sec# 1 346.41 Amps 135.7 135.6 -0.2

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

SANGER -AIRWAYJ2 115.00kV Ckt#1 Sec# 1 1124.58 Amps 118.3 118.4 0.1

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 23.4 MW 4.7 MVAR D : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

SANGER -AIRWAYJ2 115.00kV Ckt#1 Sec# 1 1124.58 Amps 101.5 101.4 0.0

Page 458: To determine the system impacts caused by the Project

C-145 GWF Henrietta SISAppendix C

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

SANGER -LASPALMS 115.00kV Ckt#1 Sec# 1 1124.58 Amps 119.6 119.8 0.1

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 23.4 MW 4.7 MVAR D : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

SANGER -LASPALMS 115.00kV Ckt#1 Sec# 1 1124.58 Amps 102.7 102.7 0.0

52 Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 :

SANGER -MC CALL 115.00kV Ckt#3 Sec# 1 973.96 Amps 172.7 172.7 0.0

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

SANGER -MC CALL 115.00kV Ckt#3 Sec# 1 973.96 Amps 134.0 134.2 0.2

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

SANGER -MC CALL 115.00kV Ckt#3 Sec# 1 973.96 Amps 106.8 106.9 0.1

14 Open Line BORDEN 230-GREGG 230 #1 : Open Line BORDEN 230-GREGG 230 #2 :

SANGER -MC CALL 115.00kV Ckt#3 Sec# 1 973.96 Amps 101.1 101.0 -0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

SN LS OB-Q238TAP 115.00kV Ckt#1 Sec# 1 436.78 Amps 119.9 120.0 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

TEMBLOR -BELRIDGE 115.00kV Ckt#1 Sec# 1 743.02 Amps 103.6 103.6 0.0

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

TEMPLETN-GATES 230.00kV Ckt#1 Sec# 1 974.97 Amps 109.5 109.3 -0.2

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

TORNADO -COLNGA 2 70.00kV Ckt#1 Sec# 1 377.75 Amps 103.9 103.9 0.0

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line

TVY VLLY-COPPRMNE 70.00kV Ckt#1 Sec# 1 297.75 Amps 129.1 129.1 0.0

Page 459: To determine the system impacts caused by the Project

C-146 GWF Henrietta SISAppendix C

SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

lbs_dlo_5400, Los Banos - Gates & Los Banos - Midway 500-kV DLO w/ Path IRAS

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.0 124.7 0.7

60 Open Line GREGG 230-HELMS PP 230 #1 : Drop Generator at HELMS 2 18 #**: -310 MW Dropped : Open Line GREGG 230-HELMS PP 230 #2 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.4 123.0 0.6

69

Open Line HELMS PP 230-GREGG 230 #1 : Open Line HELMS PP 230-GREGG 230 #2 : Open Xfmr HELMS PP 230/HELMS 1 18 #1 : Open Xfmr HELMS PP 230/HELMS 2 18 #1 : Open Xfmr HELMS PP 230/HELMS 3 18 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.4 123.0 0.6

lbn_dlo_5400,

Los Banos - Tesla & Los Banos - Tracy 500-kV DLO w/ Path IRAS

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.5 119.3 0.8

14 Open Line BORDEN 230-GREGG 230 #1 : Open Line BORDEN 230-GREGG 230 #2 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.3 115.6 0.3

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line HELM 230-MC CALL 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.5 113.2 0.7

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.1 111.7 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 9.3 MW 1.8 MVAR Dr : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line PANOCHE 230-HELM 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.1 111.7 0.7

62

Open Line KEARNEY 230-HERNDON 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 33.6 MW 6.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.2 108.9 0.7

Page 460: To determine the system impacts caused by the Project

C-147 GWF Henrietta SISAppendix C

11

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 12.7 MW 0.5 MVAR D : Open Line MELONES 230-WILSON 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.7 106.4 0.8

55

Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Close Line HENTAP2 230-HENRIETA 230 #1 : Drop Generator at HELMS 1 18 #**: -310 MW Dropped : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.8 103.8 1.0

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.1 101.7 0.6

65

Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 33.6 MW 6.8 MVAR D : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 : Open Line GREGG 230-FGRDN T2 230 #1 : Open Line FGRDN T2 230-FIGRDN 2 230 #1 : Open Line FGRDN T2 230-ASHLAN 230 #1 : Drop Load at FIGRDN 2 230 #1 : 24.1 MW 4.8 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.5 100.1 0.6

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 12.7 MW 0.5 MVAR D : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 14.6 MW 0.6 MVAR D :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#1 150 MVA 102.3 102.9 0.6

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 12.7 MW 0.5 MVAR D : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 14.6 MW 0.6 MVAR D :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#2 75 MVA 102.3 102.9 0.6

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 12.7 MW 0.5 MVAR D : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#3 75 MVA 102.3 102.9 0.6

Page 461: To determine the system impacts caused by the Project

C-148 GWF Henrietta SISAppendix C

COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 14.6 MW 0.6 MVAR D :

lbs_dlo_5400, Los Banos - Gates & Los Banos - Midway 500-kV DLO w/ Path IRAS

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.8 103.5 0.7

44

Open Line AIRWAYJ2 115-AIRWAYS 115 #1 : Open Line AIRWAYJ2 115-BARTON 115 #1 : Open Line AIRWAYJ2 115-SANGER 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

WWARD JT-WOODWARD 115.00kV Ckt#1 Sec# 1 973.96 Amps 114.7 114.6 -0.1

46

Open Line BARTON 115-HERNDON 115 #1 : Open Line AIRWAYJ1 115-AIRWAYS 115 #1 : Open Line AIRWAYJ1 115-LASPALMS 115 #1 : Open Line AIRWAYJ1 115-MANCHSTR 115 #1 : Open Line LASPALMS 115-SANGER 115 #1 : Drop Load at LASPALMS 115 #1 : 10.5 MW 8.9 MVAR D :

WWARD JT-WOODWARD 115.00kV Ckt#1 Sec# 1 973.96 Amps 104.2 104.1 -0.1

lbs_dlo_5400, Los Banos - Gates & Los Banos - Midway 500-kV DLO w/ Path IRAS

LOSBANOS - DS AMIGO 230.0 Ckt#1 Sec# 1 849.96 Amps 102.9 103.7 0.8

2013 Spring Peak 1 Open Line WILSON A 115-ATWATER 115 #1 :

Open Line WILSON B 115-EL CAPTN 115 #1 : ATWATR J-MERCED 115.00kV Ckt#1 Sec# 1 738 Amps 119.5 119.5 0.1

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

BIOMSJCT-MENDOTA 70.00kV Ckt#1 Sec# 1 395.9 Amps 103.0 103.4 0.5

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

BIOMSJCT-MENDOTA 70.00kV Ckt#1 Sec# 1 395.9 Amps 103.0 103.4 0.5

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 135.5 136.3 0.8

16 Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 134.4 135.2 0.8

Page 462: To determine the system impacts caused by the Project

C-149 GWF Henrietta SISAppendix C

Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 134.4 135.2 0.8

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.9 133.7 0.8

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.3 133.1 0.9

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.9 130.7 0.8

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.5 130.3 0.8

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 129.2 129.9 0.8

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 128.2 128.9 0.7

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 124.4 125.9 1.6

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 55.7 MW 10.7 MVAR Dr : Drop Load at ASHLAN 230 #2 : 51.9 MW 10.3 MVAR Dr : Drop Load at ASHLAN 230 #3 : 52.7 MW 10 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.0 122.7 0.7

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 121.3 122.0 0.7

Page 463: To determine the system impacts caused by the Project

C-150 GWF Henrietta SISAppendix C

LOSBANOS 230/LOS BANS 70 #3 :

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.9 121.6 0.7

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.4 120.3 0.9

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.6 119.3 0.7

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.5 119.2 0.7

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 36.1 MW 7.3 MVAR Dr : Drop Load at BULLARD 115 #2 : 35.9 MW 7.2 MVAR Dr : Drop Load at BULLARD 115 #3 : 34.2 MW 6.9 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.2 118.9 0.7

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 118.1 118.7 0.6

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.9 118.5 0.6

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.5 118.1 0.6

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.4 118.1 0.7

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 34 MW 6.9 MVAR Dro : Drop Load at WOODWARD 115 #2 : 42.4 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #3 : 35.5 MW

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.2 117.9 0.7

Page 464: To determine the system impacts caused by the Project

C-151 GWF Henrietta SISAppendix C

7.2 MVAR D :

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 3.8 MW 3.2 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.8 117.4 0.7

23 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Open Xfmr EXCHEQUR 115/EXCHQRTP 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.6 117.3 0.7

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.5 117.2 0.7

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 117.1 0.7

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 117.0 0.7

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 116.9 0.7

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 34.8 MW 7 MVAR Dropp : Drop Load at BARTON 115 #2 : 29.9 MW 6 MVAR Dropp : Drop Load at BARTON 115 #3 : 21.7 MW 4.3 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.2 116.9 0.7

21

Open Line CHWCHLLA 115-CERTAN T 115 #1 : Open Line CHWCHLLA 115-CERTANJ1 115 #1 : Drop Load at CHWCHLLA 115 #1 : 8.1 MW 1.6 MVAR Dr : Drop Load at CHWCHLLA 115 #2 : 11.1 MW 2.2 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.0 116.7 0.7

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 20.3 MW 4.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 20.5 MW 4.1 MVAR D : Drop Load at MANCHSTR 115 #3 : 29.1 MW 5.9 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.9 116.6 0.7

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.8 116.5 0.7

117 Open Line KEARNEY 70-FRWWTAP 70 #1 : Open BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.7 116.4 0.7

Page 465: To determine the system impacts caused by the Project

C-152 GWF Henrietta SISAppendix C

Line KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

30

Open Line PANOCHE 115-CHENYT 115 #1 : Open Line PANOCHE 115-PANOCHEJ 115 #1 : Open Xfmr PANOCHE 115/PANOCHE 230 #2 : Open Xfmr PANOCHE 115/DG_PAN1 13.8 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.5 116.2 0.7

86

Open Line KERCKHF2 115-K1-JCT 115 #2 : Open Line KERCKHF2 115-KERCKHF1 115 #1 : Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line KERCKHF2 115-CLOVISJ2 115 #1 : Open Xfmr KERCKHF2 115/KERCKHOF 13.8 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.5 116.2 0.7

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 42.3 MW 8.5 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.0 0.7

45 Open Line BARTON 115-HERNDON 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.3 115.9 0.7

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 36 MW 7.3 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.2 115.9 0.7

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 14.4 MW 2.9 MVAR Drop : Drop Load at MADERA 70 #2 : 18.5 MW 3.7 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.0 115.7 0.7

100 Open Line HERNDON 115-BARTON 115 #1 : Open Line HERNDON 115-PNDLJ2 115 #1 : Open Xfmr HERNDON 115/HERNDN1M 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.0 115.6 0.7

96

Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 23.3 MW 4.7 MVAR Dr : Drop Load at CAL AVE 115 #2 : 25.1 MW 5.1 MVAR Dr : Drop Load at CAL AVE 115 #3 : 19.6 MW 3.9 MVAR Dr :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.9 115.6 0.7

91

Open Line MALAGA 115-SANGER 115 #1 : Open Line MALAGA 115-PPG 115 #1 : Open Line MALAGA 115-MALAGATP 115 #1 : Open Line MALAGA 115-KRCDP 115 #1 : Drop Load at MALAGA 115 #1 : 20.3 MW 4.1 MVAR Dro : Drop Load at MALAGA 115 #2 : 18.3 MW 3.7 MVAR Dro : Drop Load at MALAGA 115 #3 : 18.6 MW 3.7 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.8 115.5 0.7

Page 466: To determine the system impacts caused by the Project

C-153 GWF Henrietta SISAppendix C

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.7 115.4 0.7

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 30.2 MW 6.1 MVAR D : Drop Load at WST FRSO 115 #2 : 31.4 MW 6.3 MVAR D :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.7 115.4 0.7

72 Open Line HERNDON 230-GREGG 230 #2 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Xfmr HERNDON 230/HERNDN2M 115 #2 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.7 115.4 0.7

87

Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 30.9 MW 5.9 MVAR Dr : Drop Load at AIRWAYS 115 #2 : 10.1 MW 2 MVAR Drop :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.5 115.2 0.7

68 Open Line GATES 230-MIDWAY 230 #1 : Open Line GATES 230-ARCO 230 #1 :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.4 115.1 0.7

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro :

BORDEN -STOREY 1 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.3 115.0 0.7

100 Open Line HERNDON 115-BARTON 115 #1 : Open Line HERNDON 115-PNDLJ2 115 #1 : Open Xfmr HERNDON 115/HERNDN1M 115 #1 :

BULLARD -PNDLJ1 115.00kV Ckt#1 Sec# 1 743.02 Amps 114.7 114.7 0.0

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

CAMDEN -KNGLOBUS 70.00kV Ckt#1 Sec# 1 398.37 Amps 104.3 104.7 0.4

35

Open Line LOS BANS 70-CHEVPIPE 70 #1 : Open Line LOS BANS 70-WRGHT PP 70 #1 : Open Line LOS BANS 70-PCHCO PP 70 #1 : Open Line LOS BANS 70-ONLL PMP 69 #1 : Open Xfmr LOS BANS 70/LOSBANOS 230 #3 : Open Xfmr LOS BANS 70/LOSBANOS 230 #4 :

CANAL -SNTA RTA 70.00kV Ckt#1 Sec# 1 282.08 Amps 103.9 104.0 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

CARRIZO -TEMBLOR 115.00kV Ckt#1 Sec# 1 436.78 Amps 106.3 106.3 0.0

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

CERTAN T-CHWCHLLA 115.00kV Ckt#1 Sec# 1 512.08 Amps 102.7 103.3 0.7

13 Open Line STOREY 2 230-BORDEN 230 #1 : Open CERTAN T-LE GRAND 115.00kV Ckt#1 Sec# 1 396.61 Amps 134.9 135.8 0.9

Page 467: To determine the system impacts caused by the Project

C-154 GWF Henrietta SISAppendix C

Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

CERTAN T-LE GRAND 115.00kV Ckt#1 Sec# 1 396.61 Amps 101.5 101.6 0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

CHWCHLLA-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 151.3 152.2 0.9

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

CHWCHLLA-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 118.8 118.9 0.1

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

CHWCHLLA-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 118.8 118.9 0.1

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

CHWCHLLA-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 111.5 112.1 0.6

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.4 116.3 0.9

Page 468: To determine the system impacts caused by the Project

C-155 GWF Henrietta SISAppendix C

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.1 110.9 0.8

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.9 110.7 0.8

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.9 110.7 0.8

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.6 109.3 0.7

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.5 0.7

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.4 0.7

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.3 107.0 0.7

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.9 106.6 0.7

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.0 106.0 1.0

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.5 105.8 1.3

75 Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.3 103.9 0.7

Page 469: To determine the system impacts caused by the Project

C-156 GWF Henrietta SISAppendix C

at ASHLAN 230 #1 : 55.7 MW 10.7 MVAR Dr : Drop Load at ASHLAN 230 #2 : 51.9 MW 10.3 MVAR Dr : Drop Load at ASHLAN 230 #3 : 52.7 MW 10 MVAR Drop :

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.9 103.5 0.7

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.4 102.1 0.7

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.2 101.8 0.6

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.7 101.3 0.6

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.6 101.2 0.6

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 36.1 MW 7.3 MVAR Dr : Drop Load at BULLARD 115 #2 : 35.9 MW 7.2 MVAR Dr : Drop Load at BULLARD 115 #3 : 34.2 MW 6.9 MVAR Dr :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.5 101.2 0.7

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.3 101.0 0.7

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 34 MW 6.9 MVAR Dro : Drop Load at WOODWARD 115 #2 : 42.4 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #3 : 35.5 MW 7.2 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.3 101.0 0.7

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.3 100.9 0.7

Page 470: To determine the system impacts caused by the Project

C-157 GWF Henrietta SISAppendix C

27

Open Line EL CAPTN 115-CASTLE 115 #1 : Open Line EL CAPTN 115-WILSON B 115 #1 : Drop Load at EL CAPTN 115 #1 : 15.5 MW 3.1 MVAR D : Drop Load at EL CAPTN 115 #2 : 20.7 MW 4.1 MVAR D : Drop Load at EL CAPTN 115 #3 : 26.4 MW 5.3 MVAR D :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.2 100.9 0.7

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.1 100.7 0.7

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 3.8 MW 3.2 MVAR Dr :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.9 100.6 0.7

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.5 100.2 0.7

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

COTTLE B-BELLOTA 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.5 100.1 0.6

1 Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 :

CRESEY T-ATWATR J 115.00kV Ckt#1 Sec# 1 512.08 Amps 146.3 146.4 0.1

35

Open Line LOS BANS 70-CHEVPIPE 70 #1 : Open Line LOS BANS 70-WRGHT PP 70 #1 : Open Line LOS BANS 70-PCHCO PP 70 #1 : Open Line LOS BANS 70-ONLL PMP 69 #1 : Open Xfmr LOS BANS 70/LOSBANOS 230 #3 : Open Xfmr LOS BANS 70/LOSBANOS 230 #4 :

DOS PALS-ORO LOMA 70.00kV Ckt#1 Sec# 1 282.08 Amps 151.3 151.4 0.1

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 10.7 MW 2.1 MVAR D :

EXCHEQUR-MCSWAINJ 70.00kV Ckt#1 Sec# 1 280.43 Amps 183.2 183.2 0.0

61 Open Line GREGG 230-HERNDON 230 #1 : Drop FGRDN T1-ASHLAN 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.5 101.8 0.3

Page 471: To determine the system impacts caused by the Project

C-158 GWF Henrietta SISAppendix C

Generator at HELMS 3 18 #**: 400 MW Dropped : Open Line GREGG 230-HERNDON 230 #2 :

61 Open Line GREGG 230-HERNDON 230 #1 : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Open Line GREGG 230-HERNDON 230 #2 :

FGRDN T2-ASHLAN 230.00kV Ckt#1 Sec# 1 849.96 Amps 148.5 148.8 0.4

61 Open Line GREGG 230-HERNDON 230 #1 : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Open Line GREGG 230-HERNDON 230 #2 :

FGRDN T2-GREGG 230.00kV Ckt#1 Sec# 1 849.96 Amps 160.8 161.2 0.4

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

FRWWTAP -KERMAN 70.00kV Ckt#1 Sec# 1 379.4 Amps 106.9 106.8 -0.1

55

Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Close Line HENTAP2 230-HENRIETA 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

HELM -PANOCHE 230.00kV Ckt#1 Sec# 1 849.96 Amps 98.6 101.6 3.0

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 146.2 146.9 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 146.2 146.9 0.7

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

HELM -STRD JCT 70.00kV Ckt#1 Sec# 1 377.75 Amps 122.6 123.1 0.5

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

HERNDON -KEARNEY 230.00kV Ckt#1 Sec# 1 974.97 Amps 103.0 103.6 0.6

126

Open Line HENRITTA 70-MUSLSLGH 70 #1 : Open Line HENRITTA 70-LPRNO TP 70 #1 : Open Line HENRITTA 70-GWF_HENR 70 #1 : Open Line HENRITTA 70-JCBSCRNR 70 #1 : Open Xfmr

HNFRD SW-HRDWK TP 70.00kV Ckt#1 Sec# 1 379.4 Amps 140.5 140.5 0.0

Page 472: To determine the system impacts caused by the Project

C-159 GWF Henrietta SISAppendix C

HENRITTA 70/HENRIETA 230 #2 : Open Xfmr HENRITTA 70/HENRIETA 230 #4 : Drop Load at HENRITTA 70 #1 : 6.6 MW 1.3 MVAR Dro :

126

Open Line HENRITTA 70-MUSLSLGH 70 #1 : Open Line HENRITTA 70-LPRNO TP 70 #1 : Open Line HENRITTA 70-GWF_HENR 70 #1 : Open Line HENRITTA 70-JCBSCRNR 70 #1 : Open Xfmr HENRITTA 70/HENRIETA 230 #2 : Open Xfmr HENRITTA 70/HENRIETA 230 #4 : Drop Load at HENRITTA 70 #1 : 6.6 MW 1.3 MVAR Dro :

HRDWK TP-KNGLOBUS 70.00kV Ckt#1 Sec# 1 377.75 Amps 165.7 165.6 0.0

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

HRDWK TP-KNGLOBUS 70.00kV Ckt#1 Sec# 1 377.75 Amps 119.5 115.7 -3.8

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

K1-JCT -OAKH_JCT 115.00kV Ckt#1 Sec# 1 743.02 Amps 113.4 113.9 0.5

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

KEARNEY -FRWWTAP 70.00kV Ckt#1 Sec# 1 379.4 Amps 110.4 110.4 -0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

KEARNEY -HERNDON 230.00kV Ckt#1 Sec# 1 974.97 Amps 132.2 132.9 0.8

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

KEARNEY -MCMULLN1 230.00kV Ckt#1 Sec# 1 974.97 Amps 107.4 108.2 0.7

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at

KERCKHF2-K1-JCT 115.00kV Ckt#2 Sec# 1 743.02 Amps 113.4 113.9 0.5

Page 473: To determine the system impacts caused by the Project

C-160 GWF Henrietta SISAppendix C

STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

KERMAN -AGRCJCT 70.00kV Ckt#1 Sec# 1 379.4 Amps 161.9 161.8 -0.1

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

KINGS J2-KINGS J1 115.00kV Ckt#1 Sec# 1 599.98 Amps 104.6 103.8 -0.8

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

LE GRAND-WILSON A 115.00kV Ckt#1 Sec# 1 512.08 Amps 156.8 157.6 0.8

126

Open Line HENRITTA 70-MUSLSLGH 70 #1 : Open Line HENRITTA 70-LPRNO TP 70 #1 : Open Line HENRITTA 70-GWF_HENR 70 #1 : Open Line HENRITTA 70-JCBSCRNR 70 #1 : Open Xfmr HENRITTA 70/HENRIETA 230 #2 : Open Xfmr HENRITTA 70/HENRIETA 230 #4 : Drop Load at HENRITTA 70 #1 : 6.6 MW 1.3 MVAR Dro :

LEMOORE -HNFRD SW 70.00kV Ckt#1 Sec# 1 280.43 Amps 190.2 190.2 0.0

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

LEMOORE -HNFRD SW 70.00kV Ckt#1 Sec# 1 280.43 Amps 134.8 129.8 -5.0

80

Open Line HENRIETA 230-HENTAP1 230 #1 : Open Xfmr HENRIETA 230/HENRETTA 115 #3 : Open Xfmr HENRIETA 230/HENRITTA 70 #2 : Open Xfmr HENRIETA 230/HENRITTA 70 #4 :

LEMOORE -HNFRD SW 70.00kV Ckt#1 Sec# 1 280.43 Amps <98 121.1 >23.1

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

LEPRNOFD-GWF_HEP 115.00kV Ckt#1 Sec# 1 743.02 Amps 102.3 101.9 -0.4

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 99.6 100.8 1.2 lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO LOSBANOS-WESTLEY 230.00kV Ckt#1 Sec# 1 1699.92 Amps 100.0 100.7 0.7

55

Open Line GREGG 230-HENTAP1 230 #1 : Open Line HENTAP1 230-HENRIETA 230 #1 : Open Line HENTAP1 230-GATES 230 #1 : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Close Line HENTAP2 230-HENRIETA 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 112.3 115.6 3.3

Page 474: To determine the system impacts caused by the Project

C-161 GWF Henrietta SISAppendix C

GATES 230 #1 :

90

Open Line SANGER 115-CLOVISJ1 115 #1 : Open Line SANGER 115-CLOVISJ2 115 #1 : Open Line SANGER 115-AIRWAYJ2 115 #1 : Open Line SANGER 115-LASPALMS 115 #1 : Open Line SANGER 115-MC CALL 115 #1 : Open Line SANGER 115-MC CALL 115 #2 : Open Line SANGER 115-MC CALL 115 #3 : Open Line SANGER 115-MALAGA 115 #1 : Open Line SANGER 115-RAINBWTP 115 #1 : Open Line SANGER 115-PIEDRA 2 115 #1 :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 111.0 111.5 0.6

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 108.5 109.1 0.5

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

MC CALL -HELM 230.00kV Ckt#1 Sec# 1 849.96 Amps 102.6 103.2 0.6

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

MCMULLN1-PANOCHE 230.00kV Ckt#1 Sec# 1 974.97 Amps 103.2 103.9 0.7

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 10.7 MW 2.1 MVAR D :

MERCED -MERCED M 70.00/ 115.00kV Bk#2 60 MVA 117.7 117.7 0.0

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 10.7 MW 2.1 MVAR D :

MERCED -MERCED M 115.00/ 115.00kV Bk#2 60 MVA 129.2 129.1 0.0

1 Open Line WILSON A 115-ATWATER 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 :

MERCED -WILSON A 115.00kV Ckt#1 Sec# 1 471.92 Amps 109.2 109.3 0.0

24 Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 :

MRCDFLLS-MCSWAINJ 70.00kV Ckt#1 Sec# 1 379.4 Amps 154.9 154.9 0.0

Page 475: To determine the system impacts caused by the Project

C-162 GWF Henrietta SISAppendix C

Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 10.7 MW 2.1 MVAR D :

24

Open Line LE GRAND 115-CERTAN T 115 #1 : Open Line LE GRAND 115-EXCHEQUR 115 #1 : Open Line LE GRAND 115-WILSON A 115 #1 : Open Line LE GRAND 115-DAIRYLND 115 #1 : Drop Load at LE GRAND 115 #1 : 10.7 MW 2.1 MVAR D :

MRCDFLLS-MERCED 70.00kV Ckt#1 Sec# 1 377.75 Amps 146.5 146.5 0.0

35

Open Line LOS BANS 70-CHEVPIPE 70 #1 : Open Line LOS BANS 70-WRGHT PP 70 #1 : Open Line LOS BANS 70-PCHCO PP 70 #1 : Open Line LOS BANS 70-ONLL PMP 69 #1 : Open Xfmr LOS BANS 70/LOSBANOS 230 #3 : Open Xfmr LOS BANS 70/LOSBANOS 230 #4 :

MRCYSPRS-ORO LOMA 70.00kV Ckt#1 Sec# 1 511.37 Amps 114.1 114.2 0.1

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

OAKH_JCT-SHARON T 115.00kV Ckt#1 Sec# 1 396.61 Amps 157.8 158.7 0.9

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

OAKH_JCT-SHARON T 115.00kV Ckt#1 Sec# 1 396.61 Amps 125.7 125.7 0.0

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

OAKH_JCT-SHARON T 115.00kV Ckt#1 Sec# 1 396.61 Amps 117.9 118.5 0.6

35

Open Line LOS BANS 70-CHEVPIPE 70 #1 : Open Line LOS BANS 70-WRGHT PP 70 #1 : Open Line LOS BANS 70-PCHCO PP 70 #1 : Open Line LOS BANS 70-ONLL PMP 69 #1 : Open Xfmr LOS BANS 70/LOSBANOS 230 #3 : Open Xfmr LOS BANS 70/LOSBANOS 230 #4 :

ORO LOMA-ORO LOMA 115.00/ 70.00kV Bk#2 72 MVA 141.4 141.4 0.0

19 Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 :

PANOCHE -DS AMIGO 230.00kV Ckt#1 Sec# 1 849.96 Amps 113.1 113.7 0.6

Page 476: To determine the system impacts caused by the Project

C-163 GWF Henrietta SISAppendix C

Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

PANOCHE -LOSBANOS 230.00kV Ckt#1 Sec# 1 974.97 Amps 102.7 103.3 0.6

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

PANOCHE -LOSBANOS 230.00kV Ckt#2 Sec# 1 849.96 Amps 107.1 107.8 0.7

93

Open Line REEDLEY 115-GERAWAN 115 #1 : Open Line REEDLEY 115-PIEDRA 1 115 #1 : Open Xfmr REEDLEY 115/REEDLEY 70 #1 : Open Xfmr REEDLEY 115/REEDLEY 70 #2 : Drop Load at REEDLEY 115 #3 : 21.1 MW 4.2 MVAR Dr :

PARLIER -SNGRJCT 70.00kV Ckt#1 Sec# 1 470.13 Amps 113.5 113.5 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

PSA RBLS-SAN MIGL 70.00kV Ckt#1 Sec# 1 346.41 Amps 103.5 103.3 -0.2

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 140.2 140.3 0.0

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.8 103.9 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q166 -MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.4 100.6 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 140.2 140.3 0.0

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.8 103.9 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q166 -Q194SWST 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.4 100.6 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 140.2 140.3 0.0

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.8 103.9 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q194SWST-MIDWAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.4 100.6 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Q238TAP -CARRIZO 115.00kV Ckt#1 Sec# 1 436.78 Amps 106.6 106.7 0.0

Page 477: To determine the system impacts caused by the Project

C-164 GWF Henrietta SISAppendix C

Line GATES 230-TEMPLETN 230 #1 :

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q239SWST-MORROBAY 230.00kV Ckt#1 Sec# 1 976.48 Amps 106.6 106.6 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q239SWST-MORROBAY 230.00kV Ckt#2 Sec# 1 976.48 Amps 106.6 106.6 0.0

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 140.2 140.3 0.0

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 103.8 103.9 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q239SWST-Q166 230.00kV Ckt#1 Sec# 1 976.48 Amps 100.5 100.6 0.1

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 140.2 140.3 0.0

82 Open Line GATES 230-PANOCHE 230 #2 : Open Line GATES 230-MORROBAY 230 #1 :

Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 103.8 103.9 0.1

81 Open Line GATES 230-PANOCHE 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 : Open Xfmr GATES 230/GATES 1M 230 #1 :

Q239SWST-Q166 230.00kV Ckt#2 Sec# 1 976.48 Amps 100.5 100.6 0.1

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

SAN JOQN-SNJQJCT 70.00kV Ckt#1 Sec# 1 395.9 Amps 104.2 104.9 0.8

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

SANGER -MC CALL 115.00kV Ckt#3 Sec# 1 973.96 Amps 99.8 100.1 0.3

13

Open Line STOREY 2 230-BORDEN 230 #1 : Open Line STOREY 2 230-WILSON 230 #1 : Drop Load at STOREY 2 230 #2 : 27 MW 5.4 MVAR Dro : Open Line STOREY 1 230-WILSON 230 #1 : Open Line STOREY 1 230-BORDEN 230 #1 : Drop Load at STOREY 1 230 #1 : 30.2 MW 6.1 MVAR D :

SHARON T-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 151.5 152.4 0.9

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro : Close Line

SHARON T-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 119.0 119.1 0.1

Page 478: To determine the system impacts caused by the Project

C-165 GWF Henrietta SISAppendix C

CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

SHARON T-CERTANJ1 115.00kV Ckt#1 Sec# 1 396.61 Amps 111.7 112.4 0.6

67 Open Line GATES 230-MORROBAY 230 #1 : Open Line GATES 230-TEMPLETN 230 #1 :

SN LS OB-Q238TAP 115.00kV Ckt#1 Sec# 1 436.78 Amps 110.8 110.8 0.0

35

Open Line LOS BANS 70-CHEVPIPE 70 #1 : Open Line LOS BANS 70-WRGHT PP 70 #1 : Open Line LOS BANS 70-PCHCO PP 70 #1 : Open Line LOS BANS 70-ONLL PMP 69 #1 : Open Xfmr LOS BANS 70/LOSBANOS 230 #3 : Open Xfmr LOS BANS 70/LOSBANOS 230 #4 :

SNTA RTA-DOS PALS 70.00kV Ckt#1 Sec# 1 297.75 Amps 117.8 117.9 0.1

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 22.2 MW 0.9 MVAR D : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 25.5 MW 1.1 MVAR D :

STANDFRD-WRNRVLLE 115.00kV Ckt#1 Sec# 1 938.82 Amps 116.5 117.0 0.5

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 22.2 MW 0.9 MVAR D : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 25.5 MW 1.1 MVAR D :

STANDFRD-WRNRVLLE 115.00kV Ckt#2 Sec# 1 938.82 Amps 116.5 117.0 0.5

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 117.3 118.1 0.8

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 116.3 117.1 0.8

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 116.3 117.1 0.8

Page 479: To determine the system impacts caused by the Project

C-166 GWF Henrietta SISAppendix C

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 115.0 115.7 0.7

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 114.4 115.2 0.8

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 112.2 112.9 0.7

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 111.8 112.5 0.7

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 111.4 112.1 0.7

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 110.5 111.2 0.7

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 107.0 108.4 1.5

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 55.7 MW 10.7 MVAR Dr : Drop Load at ASHLAN 230 #2 : 51.9 MW 10.3 MVAR Dr : Drop Load at ASHLAN 230 #3 : 52.7 MW 10 MVAR Drop :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 104.8 105.4 0.6

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 104.2 104.8 0.6

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 103.8 104.5 0.6

Page 480: To determine the system impacts caused by the Project

C-167 GWF Henrietta SISAppendix C

HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 102.4 103.2 0.8

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.6 102.2 0.7

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.6 102.2 0.6

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 36.1 MW 7.3 MVAR Dr : Drop Load at BULLARD 115 #2 : 35.9 MW 7.2 MVAR Dr : Drop Load at BULLARD 115 #3 : 34.2 MW 6.9 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.2 101.9 0.6

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 101.1 101.7 0.6

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.9 101.5 0.6

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.6 101.2 0.6

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.4 101.1 0.6

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 34 MW 6.9 MVAR Dro : Drop Load at WOODWARD 115 #2 : 42.4 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #3 : 35.5 MW 7.2 MVAR D :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 100.3 100.9 0.6

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 3.8 MW 3.2 MVAR Dr :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.9 100.5 0.6

Page 481: To determine the system impacts caused by the Project

C-168 GWF Henrietta SISAppendix C

23 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Open Xfmr EXCHEQUR 115/EXCHQRTP 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.8 100.4 0.6

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.6 100.3 0.7

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.5 100.1 0.6

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.4 100.1 0.7

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.4 100.0 0.6

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 34.8 MW 7 MVAR Dropp : Drop Load at BARTON 115 #2 : 29.9 MW 6 MVAR Dropp : Drop Load at BARTON 115 #3 : 21.7 MW 4.3 MVAR Dro :

STOREY 1-WILSON 230.00kV Ckt#1 Sec# 1 850.96 Amps 99.4 100.0 0.6

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.5 116.3 0.7

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.6 115.3 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.6 115.3 0.7

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.4 114.0 0.7

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.9 113.6 0.7

62 Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.8 111.5 0.7

Page 482: To determine the system impacts caused by the Project

C-169 GWF Henrietta SISAppendix C

Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.4 111.1 0.7

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.2 110.8 0.6

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.3 110.0 0.6

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 107.4 1.3

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 55.7 MW 10.7 MVAR Dr : Drop Load at ASHLAN 230 #2 : 51.9 MW 10.3 MVAR Dr : Drop Load at ASHLAN 230 #3 : 52.7 MW 10 MVAR Drop :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.0 104.6 0.6

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.5 104.1 0.6

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 103.2 103.8 0.6

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.9 102.6 0.8 76 Open Line HELM 230-PANOCHE 230 #1 : Open STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.1 101.8 0.6

Page 483: To determine the system impacts caused by the Project

C-170 GWF Henrietta SISAppendix C

Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.1 101.7 0.6

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 36.1 MW 7.3 MVAR Dr : Drop Load at BULLARD 115 #2 : 35.9 MW 7.2 MVAR Dr : Drop Load at BULLARD 115 #3 : 34.2 MW 6.9 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.8 101.4 0.6

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.7 101.3 0.5

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.5 101.1 0.5

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.2 100.8 0.5

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.1 100.7 0.6

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 34 MW 6.9 MVAR Dro : Drop Load at WOODWARD 115 #2 : 42.4 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #3 : 35.5 MW 7.2 MVAR D :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.0 100.5 0.6

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 3.8 MW 3.2 MVAR Dr :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.6 100.2 0.6

23 Open Line EXCHEQUR 115-LE GRAND 115 #1 : Open Xfmr EXCHEQUR 115/EXCHQRTP 115 #1 :

STOREY 2-BORDEN 230.00kV Ckt#1 Sec# 1 793.23 Amps 99.5 100.0 0.6

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.8 107.6 0.7

Page 484: To determine the system impacts caused by the Project

C-171 GWF Henrietta SISAppendix C

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.9 106.6 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.9 106.6 0.7

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.7 105.4 0.7

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.2 104.9 0.7

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 102.2 102.8 0.6

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.8 102.5 0.7

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 101.5 102.1 0.6

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

STOREY 2-WILSON 230.00kV Ckt#1 Sec# 1 793.23 Amps 100.7 101.3 0.6

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

STRD JCT-SCHLNDLR 70.00kV Ckt#1 Sec# 1 377.75 Amps 125.2 126.0 0.7

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

STRD JCT-SCHLNDLR 70.00kV Ckt#1 Sec# 1 377.75 Amps 125.2 126.0 0.7

Page 485: To determine the system impacts caused by the Project

C-172 GWF Henrietta SISAppendix C

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

STRD JCT-SCHLNDLR 70.00kV Ckt#1 Sec# 1 377.75 Amps 101.3 101.8 0.5

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.3 124.2 0.9

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.9 118.7 0.8

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.7 118.5 0.8

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 117.7 118.5 0.8

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.3 117.1 0.7

71 Open Line HERNDON 230-GREGG 230 #1 : Open Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.6 116.3 0.7

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 115.6 116.2 0.7

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.1 114.8 0.7

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.7 114.4 0.7

Page 486: To determine the system impacts caused by the Project

C-173 GWF Henrietta SISAppendix C

Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.8 113.8 1.0

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.3 113.6 1.3

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 55.7 MW 10.7 MVAR Dr : Drop Load at ASHLAN 230 #2 : 51.9 MW 10.3 MVAR Dr : Drop Load at ASHLAN 230 #3 : 52.7 MW 10 MVAR Drop :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 111.0 111.7 0.7

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.6 111.3 0.7

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.2 109.9 0.7

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.9 109.5 0.6

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.5 109.1 0.6

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-DS AMIGO 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.4 109.0 0.6

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 36.1 MW 7.3 MVAR Dr : Drop Load at BULLARD 115 #2 : 35.9 MW 7.2 MVAR Dr : Drop Load at BULLARD 115 #3 : 34.2 MW 6.9 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.3 108.9 0.7

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.1 108.8 0.7

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 34 MW 6.9 MVAR Dro : Drop Load at WOODWARD 115 #2 : 42.4 MW 8.6

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.1 108.8 0.7

Page 487: To determine the system impacts caused by the Project

C-174 GWF Henrietta SISAppendix C

MVAR D : Drop Load at WOODWARD 115 #3 : 35.5 MW 7.2 MVAR D :

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.1 108.7 0.7

27

Open Line EL CAPTN 115-CASTLE 115 #1 : Open Line EL CAPTN 115-WILSON B 115 #1 : Drop Load at EL CAPTN 115 #1 : 15.5 MW 3.1 MVAR D : Drop Load at EL CAPTN 115 #2 : 20.7 MW 4.1 MVAR D : Drop Load at EL CAPTN 115 #3 : 26.4 MW 5.3 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.0 108.7 0.7

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.5 0.7

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 3.8 MW 3.2 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.7 108.4 0.7

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.3 108.0 0.7

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.3 107.9 0.6

22

Open Line ATWATER 115-CASTLE 115 #1 : Open Line ATWATER 115-CRESEY T 115 #1 : Open Line ATWATER 115-WILSON A 115 #1 : Drop Load at ATWATER 115 #1 : 25.9 MW 5.2 MVAR Dr : Drop Load at ATWATER 115 #2 : 22.6 MW 4.5 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.1 107.7 0.7

98 Open Line BARTON 115-AIRWAYJ2 115 #1 : Open WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.9 107.6 0.7

Page 488: To determine the system impacts caused by the Project

C-175 GWF Henrietta SISAppendix C

Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 34.8 MW 7 MVAR Dropp : Drop Load at BARTON 115 #2 : 29.9 MW 6 MVAR Dropp : Drop Load at BARTON 115 #3 : 21.7 MW 4.3 MVAR Dro :

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.5 107.2 0.7

28

Open Line MERCED 115-ATWATR J 115 #1 : Open Line MERCED 115-WILSON A 115 #1 : Open Line MERCED 115-WILSON B 115 #2 : Open Xfmr MERCED 115/MERCED M 115 #2 : Drop Load at MERCED 115 #1 : 29.6 MW 6 MVAR Dropp : Drop Load at MERCED 115 #3 : 15.5 MW 3.1 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.5 107.2 0.7

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 20.3 MW 4.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 20.5 MW 4.1 MVAR D : Drop Load at MANCHSTR 115 #3 : 29.1 MW 5.9 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.5 107.1 0.7

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 36 MW 7.3 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.4 107.1 0.7

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.2 106.9 0.7

117

Open Line KEARNEY 70-FRWWTAP 70 #1 : Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 106.7 0.7

96

Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 23.3 MW 4.7 MVAR Dr : Drop Load at CAL AVE 115 #2 : 25.1 MW 5.1 MVAR Dr : Drop Load at CAL AVE 115 #3 : 19.6 MW 3.9 MVAR Dr :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.8 106.5 0.7

26

Open Line WILSON B 115-LE GRNDJ 115 #1 : Open Line WILSON B 115-WILSON A 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 : Open Line WILSON B 115-MERCED 115 #2 : Open Xfmr WILSON B 115/WILSON 230 #2 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.7 106.4 0.7

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 42.3 MW 8.5 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.7 106.4 0.7

Page 489: To determine the system impacts caused by the Project

C-176 GWF Henrietta SISAppendix C

91

Open Line MALAGA 115-SANGER 115 #1 : Open Line MALAGA 115-PPG 115 #1 : Open Line MALAGA 115-MALAGATP 115 #1 : Open Line MALAGA 115-KRCDP 115 #1 : Drop Load at MALAGA 115 #1 : 20.3 MW 4.1 MVAR Dro : Drop Load at MALAGA 115 #2 : 18.3 MW 3.7 MVAR Dro : Drop Load at MALAGA 115 #3 : 18.6 MW 3.7 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.7 106.3 0.7

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.3 0.7

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 30.2 MW 6.1 MVAR D : Drop Load at WST FRSO 115 #2 : 31.4 MW 6.3 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.3 0.7

32

Open Line ORO LOMA 70-DOS PALS 70 #1 : Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line ORO LOMA 70-POSO J1 70 #1 : Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Drop Load at ORO LOMA 70 #1 : 6.9 MW 1.3 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.5 106.2 0.7

3

Open Line WILSON A 115-MERCED 115 #1 : Open Line LE GRNDJ 115-WILSON B 115 #1 : Open Line LE GRNDJ 115-EL NIDO 115 #1 : Open Line EL NIDO 115-ORO LOMA 115 #1 : Drop Load at EL NIDO 115 #1 : 10 MW 2 MVAR Droppe : Drop Load at EL NIDO 115 #2 : 12 MW 2.4 MVAR Drop :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.5 106.2 0.7

29 Open Line DAIRYLND 115-LE GRAND 115 #1 : Open Line DAIRYLND 115-NEWHALL 115 #1 : Drop Load at DAIRYLND 115 #1 : 20.6 MW 4.1 MVAR D :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.5 106.2 0.7

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 14.4 MW 2.9 MVAR Drop : Drop Load at MADERA 70 #2 : 18.5 MW 3.7 MVAR Drop :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.4 106.1 0.7

68 Open Line GATES 230-MIDWAY 230 #1 : Open Line GATES 230-ARCO 230 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.2 105.9 0.7

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.2 105.9 0.7

87 Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 30.9 MW 5.9 MVAR Dr : Drop Load

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.2 105.9 0.7

Page 490: To determine the system impacts caused by the Project

C-177 GWF Henrietta SISAppendix C

at AIRWAYS 115 #2 : 10.1 MW 2 MVAR Drop :

121

Open Line REEDLEY 70-TVY VLLY 70 #1 : Open Line REEDLEY 70-PARLIER 70 #1 : Open Line REEDLEY 70-DNUBAJCT 70 #1 : Open Line REEDLEY 70-ORSI JCT 70 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #2 : Drop Load at REEDLEY 70 #1 : 14 MW 2.8 MVAR Dropp :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.1 105.8 0.7

45 Open Line BARTON 115-HERNDON 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.0 105.7 0.7

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.0 105.6 0.7

34

Open Line CANAL 70-LVNGSTNT 70 #1 : Open Line CANAL 70-SNTA RTA 70 #1 : Open Line CANAL 70-ORTIGA 70 #1 : Drop Load at CANAL 70 #1 : 24.4 MW 4.9 MVAR Dropp : Drop Load at CANAL 70 #2 : 25 MW 5 MVAR Dropped :

WARNERVL-COTTLE B 230.00kV Ckt#1 Sec# 1 793.23 Amps 104.9 105.6 0.7

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 22.2 MW 0.9 MVAR D : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 25.5 MW 1.1 MVAR D :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#1 150 MVA 139.2 139.7 0.5

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#1 150 MVA 102.2 102.4 0.2

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 22.2 MW 0.9 MVAR D : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 25.5 MW 1.1 MVAR D :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#2 75 MVA 139.2 139.7 0.5

17 Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#2 75 MVA 102.2 102.4 0.2

Page 491: To determine the system impacts caused by the Project

C-178 GWF Henrietta SISAppendix C

Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

9

Open Line BELLOTA 230-COTTLE A 230 #1 : Open Line COTTLE A 230-MELONES 230 #1 : Drop Load at COTTLE A 230 #1 : 22.2 MW 0.9 MVAR D : Drop Generator at HELMS 3 18 #**: 400 MW Dropped : Open Line BELLOTA 230-COTTLE B 230 #1 : Open Line COTTLE B 230-WARNERVL 230 #1 : Drop Load at COTTLE B 230 #2 : 25.5 MW 1.1 MVAR D :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#3 75 MVA 139.2 139.7 0.5

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

WARNERVL-WRNRVLLE 230.00/ 115.00kV Bk#3 75 MVA 102.2 102.4 0.2

lbs-dlo-ns Los Banos - Gates & Los Banos - Midway 500-kV DLO WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 132.0 133.2 1.2

58

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line HELM 230-MC CALL 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.6 126.6 1.0

16

Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.3 126.3 1.0

57

Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line MCMULLN1 230-KEARNEY 230 #1 : Drop Load at MCMULLN1 230 #1 : 16.4 MW 3.3 MVAR D : Open Line PANOCHE 230-HELM 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 125.3 126.3 1.0

19

Open Line PANOCHE 230-COBURN 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #1 : Open Line PANOCHE 230-LOSBANOS 230 #2 : Open Line PANOCHE 230-MCMULLN1 230 #1 : Open Line PANOCHE 230-GATES 230 #1 : Open Xfmr PANOCHE 230/PNCHE 1M 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 123.1 124.1 0.9

59 Open Line HELM 230-MC CALL 230 #1 : Open Line MC CALL 230-HENTAP2 230 #1 : Open Line HENTAP2 230-GATES 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 122.9 123.8 1.0

71 Open Line HERNDON 230-GREGG 230 #1 : Open WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 121.9 122.9 1.0

Page 492: To determine the system impacts caused by the Project

C-179 GWF Henrietta SISAppendix C

Line HERNDON 230-KEARNEY 230 #1 : Open Xfmr HERNDON 230/HERNDN1M 115 #1 :

17

Open Line LOSBANOS 230-WESTLEY 230 #1 : Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line LOSBANOS 230-SN LS PP 230 #1 : Open Line LOSBANOS 230-SN LS PP 230 #2 : Open Xfmr LOSBANOS 230/LOS BANS 70 #3 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 120.6 121.4 0.9

62

Open Line KEARNEY 230-HERNDON 230 #1 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Line FGRDN T1 230-FIGRDN 1 230 #1 : Open Line FGRDN T1 230-ASHLAN 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR : Close Line FIGRDN 1 230-FIGRDN 2 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.7 120.7 1.0

70 Open Line KEARNEY 230-MCMULLN1 230 #1 : Open Line KEARNEY 230-HERNDON 230 #1 : Open Xfmr KEARNEY 230/KEARNEY 70 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 119.0 120.0 1.0

83 Open Line GATES 230-HENTAP1 230 #1 : Open Line GATES 230-ARCO 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 116.4 118.2 1.8

lbn-dlo-ns Los Banos - Tesla & Los Banos - Tracy 500-kV DLO WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.5 115.7 1.2

75

Open Line ASHLAN 230-FGRDN T1 230 #1 : Open Line ASHLAN 230-FGRDN T2 230 #1 : Drop Load at ASHLAN 230 #1 : 55.7 MW 10.7 MVAR Dr : Drop Load at ASHLAN 230 #2 : 51.9 MW 10.3 MVAR Dr : Drop Load at ASHLAN 230 #3 : 52.7 MW 10 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 114.3 115.2 0.9

47

Open Line PNDLJ1 115-BULLARD 115 #1 : Open Line PNDLJ1 115-HERNDON 115 #1 : Open Line PNDLJ2 115-PNEDLE 115 #1 : Open Line PNDLJ2 115-BULLARD 115 #1 : Open Line PNDLJ2 115-HERNDON 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro : Close Line PNDLJ1 115-PNEDLE 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.8 114.6 0.9

7 Open Line LOSBANOS 230-PANOCHE 230 #2 : Open Line DS AMIGO 230-PANOCHE 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 113.4 114.3 0.8

18 Open Line LOSBANOS 230-PANOCHE 230 #1 : Open Line LOSBANOS 230-DS AMIGO 230 #1 : Open Xfmr LOSBANOS 230/LOS BANS 70 #4 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.6 113.5 0.8

6 Open Line LOSBANOS 230-PANOCHE 230 #2 : WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 112.4 113.2 0.8

Page 493: To determine the system impacts caused by the Project

C-180 GWF Henrietta SISAppendix C

Open Line LOSBANOS 230-DS AMIGO 230 #1 :

15 Open Line MOSSLND2 230-PANOCHE 230 #1 : Open Line COBURN 230-PANOCHE 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.9 111.8 0.9

104

Open Line BULLARD 115-PNDLJ2 115 #1 : Open Line BULLARD 115-PNDLJ1 115 #1 : Drop Load at BULLARD 115 #1 : 36.1 MW 7.3 MVAR Dr : Drop Load at BULLARD 115 #2 : 35.9 MW 7.2 MVAR Dr : Drop Load at BULLARD 115 #3 : 34.2 MW 6.9 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.4 111.3 0.9

27

Open Line EL CAPTN 115-CASTLE 115 #1 : Open Line EL CAPTN 115-WILSON B 115 #1 : Drop Load at EL CAPTN 115 #1 : 15.5 MW 3.1 MVAR D : Drop Load at EL CAPTN 115 #2 : 20.7 MW 4.1 MVAR D : Drop Load at EL CAPTN 115 #3 : 26.4 MW 5.3 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.4 111.3 0.9

84 Open Line GATES 230-HENTAP2 230 #1 : Open Line GATES 230-MIDWAY 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.3 111.2 0.9

41

Open Line BORDEN 70-MADERA 70 #1 : Open Line BORDEN 70-MADERA 70 #2 : Open Line BORDEN 70-GLASS 70 #1 : Open Line BORDEN 70-CASSIDY 70 #1 : Open Xfmr BORDEN 70/BORDEN 230 #1 : Open Xfmr BORDEN 70/BORDEN 230 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.2 111.1 0.9

103

Open Line WOODWARD 115-WWARD JT 115 #1 : Open Line WOODWARD 115-CHLDHOSP 115 #1 : Drop Load at WOODWARD 115 #1 : 34 MW 6.9 MVAR Dro : Drop Load at WOODWARD 115 #2 : 42.4 MW 8.6 MVAR D : Drop Load at WOODWARD 115 #3 : 35.5 MW 7.2 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 110.2 111.1 0.9

48

Open Line KERCKHF2 115-WWARD JT 115 #1 : Open Line WWARD JT 115-WOODWARD 115 #1 : Open Line WWARD JT 115-CLOVISJ1 115 #1 : Open Line CLOVISJ1 115-CLOVIS-1 115 #1 : Open Line CLOVISJ1 115-SANGER 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro : Close Line CLOVIS-1 115-CLOVIS-2 115 #1 : Open Line CLOVIS-2 115-CLOVISJ2 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.8 110.7 0.9

76 Open Line HELM 230-PANOCHE 230 #1 : Open Line HELM 230-MC CALL 230 #1 : Open Xfmr HELM 230/HELM 70 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.7 110.6 0.9

Page 494: To determine the system impacts caused by the Project

C-181 GWF Henrietta SISAppendix C

54

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line DANISHCM 115-MC CALL 115 #1 : Open Line DANISHCM 115-CAL AVE 115 #1 : Drop Load at DANISHCM 115 #1 : 3.8 MW 3.2 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.5 110.4 0.9

22

Open Line ATWATER 115-CASTLE 115 #1 : Open Line ATWATER 115-CRESEY T 115 #1 : Open Line ATWATER 115-WILSON A 115 #1 : Drop Load at ATWATER 115 #1 : 25.9 MW 5.2 MVAR Dr : Drop Load at ATWATER 115 #2 : 22.6 MW 4.5 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 109.0 109.9 0.9

98

Open Line BARTON 115-AIRWAYJ2 115 #1 : Open Line BARTON 115-HERNDON 115 #1 : Drop Load at BARTON 115 #1 : 34.8 MW 7 MVAR Dropp : Drop Load at BARTON 115 #2 : 29.9 MW 6 MVAR Dropp : Drop Load at BARTON 115 #3 : 21.7 MW 4.3 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.5 109.3 0.9

28

Open Line MERCED 115-ATWATR J 115 #1 : Open Line MERCED 115-WILSON A 115 #1 : Open Line MERCED 115-WILSON B 115 #2 : Open Xfmr MERCED 115/MERCED M 115 #2 : Drop Load at MERCED 115 #1 : 29.6 MW 6 MVAR Dropp : Drop Load at MERCED 115 #3 : 15.5 MW 3.1 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.1 108.9 0.9

73 Open Line FIGRDN 1 230-FGRDN T1 230 #1 : Drop Load at FIGRDN 1 230 #1 : 59.1 MW 11.9 MVAR :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 108.0 108.8 0.9

99

Open Line MANCHSTR 115-AIRWAYJ1 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 : Drop Load at MANCHSTR 115 #1 : 20.3 MW 4.1 MVAR D : Drop Load at MANCHSTR 115 #2 : 20.5 MW 4.1 MVAR D : Drop Load at MANCHSTR 115 #3 : 29.1 MW 5.9 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.9 108.8 0.9

89 Open Line CLOVIS-2 115-CLOVISJ2 115 #1 : Drop Load at CLOVIS-2 115 #3 : 36 MW 7.3 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.8 108.7 0.9

102 Open Line PNEDLE 115-PNDLJ2 115 #1 : Drop Load at PNEDLE 115 #2 : 24.7 MW 5 MVAR Dropp : Drop Load at PNEDLE 115 #3 : 32.5 MW 6.5 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.6 108.4 0.9

117

Open Line KEARNEY 70-FRWWTAP 70 #1 : Open Line KEARNEY 70-OLDKERN 70 #1 : Open Line KEARNEY 70-CARUTHRS 70 #1 : Open Xfmr KEARNEY 70/KEARNEY 230 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.4 108.2 0.9

26 Open Line WILSON B 115-LE GRNDJ 115 #1 : Open Line WILSON B 115-WILSON A 115 #1 : Open Line WILSON B 115-EL CAPTN 115 #1 : Open Line

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 107.0 107.9 0.9

Page 495: To determine the system impacts caused by the Project

C-182 GWF Henrietta SISAppendix C

WILSON B 115-MERCED 115 #2 : Open Xfmr WILSON B 115/WILSON 230 #2 :

32

Open Line ORO LOMA 70-DOS PALS 70 #1 : Open Line ORO LOMA 70-MRCYSPRS 70 #1 : Open Line ORO LOMA 70-POSO J1 70 #1 : Open Xfmr ORO LOMA 70/ORO LOMA 115 #2 : Drop Load at ORO LOMA 70 #1 : 6.9 MW 1.3 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.9 107.8 0.9

96

Open Line CAL AVE 115-DANISHCM 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 : Drop Load at CAL AVE 115 #1 : 23.3 MW 4.7 MVAR Dr : Drop Load at CAL AVE 115 #2 : 25.1 MW 5.1 MVAR Dr : Drop Load at CAL AVE 115 #3 : 19.6 MW 3.9 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.9 107.8 0.9

74 Open Line FIGRDN 2 230-FGRDN T2 230 #1 : Drop Load at FIGRDN 2 230 #1 : 42.3 MW 8.5 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.9 107.7 0.9

20

Open Line PANOCHE 230-MOSSLND2 230 #1 : Open Line PANOCHE 230-PANO_EC 230 #1 : Open Line PANOCHE 230-HELM 230 #1 : Open Line PANOCHE 230-GATES 230 #2 : Open Line PANOCHE 230-DS AMIGO 230 #1 : Open Xfmr PANOCHE 230/PANOCHE 115 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.7 107.7 1.0

91

Open Line MALAGA 115-SANGER 115 #1 : Open Line MALAGA 115-PPG 115 #1 : Open Line MALAGA 115-MALAGATP 115 #1 : Open Line MALAGA 115-KRCDP 115 #1 : Drop Load at MALAGA 115 #1 : 20.3 MW 4.1 MVAR Dro : Drop Load at MALAGA 115 #2 : 18.3 MW 3.7 MVAR Dro : Drop Load at MALAGA 115 #3 : 18.6 MW 3.7 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.7 107.6 0.9

3

Open Line WILSON A 115-MERCED 115 #1 : Open Line LE GRNDJ 115-WILSON B 115 #1 : Open Line LE GRNDJ 115-EL NIDO 115 #1 : Open Line EL NIDO 115-ORO LOMA 115 #1 : Drop Load at EL NIDO 115 #1 : 10 MW 2 MVAR Droppe : Drop Load at EL NIDO 115 #2 : 12 MW 2.4 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.7 107.6 0.9

53 Open Line WST FRSO 115-MC CALL 115 #1 : Open Line CAL AVE 115-WST FRSO 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.7 107.5 0.9

97

Open Line WST FRSO 115-MC CALL 115 #1 : Open Line WST FRSO 115-CAL AVE 115 #1 : Drop Load at WST FRSO 115 #1 : 30.2 MW 6.1 MVAR D : Drop Load at WST FRSO 115 #2 : 31.4 MW 6.3 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.7 107.5 0.9

Page 496: To determine the system impacts caused by the Project

C-183 GWF Henrietta SISAppendix C

29 Open Line DAIRYLND 115-LE GRAND 115 #1 : Open Line DAIRYLND 115-NEWHALL 115 #1 : Drop Load at DAIRYLND 115 #1 : 20.6 MW 4.1 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.6 107.5 0.9

40

Open Line MADERA 70-TRIGO 70 #1 : Open Line MADERA 70-BORDEN 70 #1 : Open Line MADERA 70-BORDEN 70 #2 : Drop Load at MADERA 70 #1 : 14.4 MW 2.9 MVAR Drop : Drop Load at MADERA 70 #2 : 18.5 MW 3.7 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.4 107.3 0.9

87

Open Line AIRWAYS 115-AIRWAYJ1 115 #1 : Open Line AIRWAYS 115-AIRWAYJ2 115 #1 : Drop Load at AIRWAYS 115 #1 : 30.9 MW 5.9 MVAR Dr : Drop Load at AIRWAYS 115 #2 : 10.1 MW 2 MVAR Drop :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.2 107.1 0.9

88 Open Line CLOVIS-1 115-CLOVISJ1 115 #1 : Drop Load at CLOVIS-1 115 #1 : 41 MW 8.3 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.2 107.1 0.9

68 Open Line GATES 230-MIDWAY 230 #1 : Open Line GATES 230-ARCO 230 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.1 107.0 0.9

121

Open Line REEDLEY 70-TVY VLLY 70 #1 : Open Line REEDLEY 70-PARLIER 70 #1 : Open Line REEDLEY 70-DNUBAJCT 70 #1 : Open Line REEDLEY 70-ORSI JCT 70 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #1 : Open Xfmr REEDLEY 70/REEDLEY 115 #2 : Drop Load at REEDLEY 70 #1 : 14 MW 2.8 MVAR Dropp :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.0 106.8 0.9

45 Open Line BARTON 115-HERNDON 115 #1 : Open Line MANCHSTR 115-HERNDON 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 106.0 106.8 0.9

101 Open Line HERNDON 115-MANCHSTR 115 #1 : Open Line HERNDON 115-PNDLJ1 115 #1 : Open Line HERNDON 115-CHLDHOSP 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.9 106.8 0.9

107

Open Line CORCORAN 115-KINGSBRG 115 #1 : Open Line CORCORAN 115-KINGSBRG 115 #2 : Open Xfmr CORCORAN 115/CORCORAN 70 #2 : Drop Load at CORCORAN 115 #3 : 13 MW 2.6 MVAR Dro : Drop Load at CORCORAN 115 #4 : 14.3 MW 2.9 MVAR D :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.5 0.9

49 Open Line KINGSBRG 115-CORCORAN 115 #1 : Open Line KINGSBRG 115-CORCORAN 115 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.5 0.9

124

Open Line LEMOORE 70-LPRNO TP 70 #1 : Open Line LEMOORE 70-HNFRD SW 70 #1 : Drop Load at LEMOORE 70 #1 : 15.2 MW 3 MVAR Dropp : Drop Load at LEMOORE 70 #2 : 26.4 MW 5.3 MVAR Dro :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.6 106.5 0.9

Page 497: To determine the system impacts caused by the Project

C-184 GWF Henrietta SISAppendix C

34

Open Line CANAL 70-LVNGSTNT 70 #1 : Open Line CANAL 70-SNTA RTA 70 #1 : Open Line CANAL 70-ORTIGA 70 #1 : Drop Load at CANAL 70 #1 : 24.4 MW 4.9 MVAR Dropp : Drop Load at CANAL 70 #2 : 25 MW 5 MVAR Dropped :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.5 106.4 0.9

94

Open Line WAHTOKE 115-MC CALL 115 #1 : Open Line WAHTOKE 115-GERAWAN 115 #1 : Drop Load at WAHTOKE 115 #2 : 24.4 MW 4.9 MVAR Dr : Drop Load at WAHTOKE 115 #3 : 16.8 MW 3.4 MVAR Dr :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.5 106.3 0.9

100 Open Line HERNDON 115-BARTON 115 #1 : Open Line HERNDON 115-PNDLJ2 115 #1 : Open Xfmr HERNDON 115/HERNDN1M 115 #1 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.5 106.3 0.9

72 Open Line HERNDON 230-GREGG 230 #2 : Open Line HERNDON 230-FGRDN T1 230 #1 : Open Xfmr HERNDON 230/HERNDN2M 115 #2 :

WILSON -WARNERVL 230.00kV Ckt#1 Sec# 1 793.23 Amps 105.4 106.2 0.9

Page 498: To determine the system impacts caused by the Project

Appendix D Powerflow Plots of New and Significant Increased

Overloads

Page 499: To determine the system impacts caused by the Project

2013 Summer Peak Conditions

Plot # Descriptions Plot Area

Category A

Plot #1 2013 Summer Peak - Pre-Project : Normal Conditions (MW/MVAr) Henrietta 70-kV

Plot #2 2013 Summer Peak - Pre-Project : Normal Conditions (Amps/Pct) Henrietta 70-kV

Plot #3 2013 Summer Peak - Post-Project : Normal Conditions (MW/MVAr) Henrietta 70-kV

Plot #4 2013 Summer Peak - Post-Project : Normal Conditions (Amps/Pct) Henrietta 70-kV

New and Significant Increased Category B Overloads

Plot #5 2013 Summer Peak - Pre-Project : Gates-Gregg 230kV and Melones 1 (MW/MVAr) Greater Fresno 115-kV

Plot #6 2013 Summer Peak - Pre-Project : Gates-Gregg 230kV and Melones 1 (Amps/Pct) Greater Fresno 115-kV

Plot #7 2013 Summer Peak - Post-Project : Gates-Gregg 230kV and Melones 1 (MW/MVAr) Greater Fresno 115-kV

Plot #8 2013 Summer Peak - Post-Project : Gates-Gregg 230kV and Melones 1 (Amps/Pct) Greater Fresno 115-kV

Plot #9 2013 Summer Peak - Pre-Project : Wilson-Borden #2 230kV (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #10 2013 Summer Peak - Pre-Project : Wilson-Borden #2 230kV (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #11 2013 Summer Peak - Post-Project : Wilson-Borden #2 230kV (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #12 2013 Summer Peak - Post-Project : Wilson-Borden #2 230kV (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #13 2013 Summer Peak - Pre-Project : Dos Amigos-Panoche 230kV and Exchequer (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #14 2013 Summer Peak - Pre-Project : Dos Amigos-Panoche 230kV and Exchequer (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #15 2013 Summer Peak - Post-Project : Dos Amigos-Panoche 230kV and Exchequer (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #16 2013 Summer Peak - Post-Project : Dos Amigos-Panoche 230kV and Exchequer (Amps/Pct) Greater Fresno 500 & 230-kV

New and Significant Increased Category C Overloads

Plot #17 2013 Summer Peak - Pre-Project : Los Banos-Panoche #2 & Dos Amigos 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #18 2013 Summer Peak - Pre-Project : Los Banos-Panoche #2 & Dos Amigos 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #19 2013 Summer Peak - Post-Project : Los Banos-Panoche #2 & Dos Amigos 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #20 2013 Summer Peak - Post-Project : Los Banos-Panoche #2 & Dos Amigos 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #21 2013 Summer Peak - Pre-Project : Panoche-Los Banos #2 & Dos Amigos 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #22 2013 Summer Peak - Pre-Project : Panoche-Los Banos #2 & Dos Amigos 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #23 2013 Summer Peak - Post-Project : Panoche-Los Banos #2 & Dos Amigos 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #24 2013 Summer Peak - Post-Project : Panoche-Los Banos #2 & Dos Amigos 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #25 2013 Summer Peak - Pre-Project : Los Banos Bus Section 1 (MW/MVAr) Greater Fresno 115-kV

Plot #26 2013 Summer Peak - Pre-Project : Los Banos Bus Section 1 (Amps/Pct) Greater Fresno 115-kV

Plot #27 2013 Summer Peak - Post-Project : Los Banos Bus Section 1 (MW/MVAr) Greater Fresno 115-kV

Plot #28 2013 Summer Peak - Post-Project : Los Banos Bus Section 1 (Amps/Pct) Greater Fresno 115-kV

Plot #29 2013 Summer Peak - Pre-Project : Ashlan Bus (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #30 2013 Summer Peak - Pre-Project : Ashlan Bus (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #31 2013 Summer Peak - Post-Project : Ashlan Bus (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #32 2013 Summer Peak - Post-Project : Ashlan Bus (Amps/Pct) Greater Fresno 500 & 230-kV

Page 500: To determine the system impacts caused by the Project

Plot #33 2013 Summer Peak - Pre-Project : Gates 230kV Bus 1E (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #34 2013 Summer Peak - Pre-Project : Gates 230kV Bus 1E (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #35 2013 Summer Peak - Post-Project : Gates 230kV Bus 1E (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #36 2013 Summer Peak - Post-Project : Gates 230kV Bus 1E (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #37 2013 Summer Peak - Pre-Project : Los Banos South DLO (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #38 2013 Summer Peak - Pre-Project : Los Banos South DLO (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #39 2013 Summer Peak - Post-Project : Los Banos South DLO (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #40 2013 Summer Peak - Post-Project : Los Banos South DLO (Amps/Pct) Greater Fresno 500 & 230-kV

2013 Summer Off-Peak Conditions

Plot # Descriptions Plot Area

Category A

Plot #41 2013 Summer Off-Peak - Pre-Project : Normal Conditions (MW/MVAr) Henrietta 70-kV

Plot #42 2013 Summer Off-Peak - Pre-Project : Normal Conditions (Amps/Pct) Henrietta 70-kV

Plot #43 2013 Summer Off-Peak - Post-Project : Normal Conditions (MW/MVAr) Henrietta 70-kV

Plot #44 2013 Summer Off-Peak - Post-Project : Normal Conditions (Amps/Pct) Henrietta 70-kV

New and Significant Increased Category B Overloads

Plot #45 2013 Summer Off-Peak - Pre-Project : Wilson-Borden #2 230kV & Helms 1 (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #46 2013 Summer Off-Peak - Pre-Project : Wilson-Borden #2 230kV & Helms 1 (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #47 2013 Summer Off-Peak - Post-Project : Wilson-Borden #2 230kV & Helms 1 (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #48 2013 Summer Off-Peak - Post-Project : Wilson-Borden #2 230kV & Helms 1 (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #49 2013 Summer Off-Peak - Pre-Project : Panoche-Kearney 230kV & Kerckhoff (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #50 2013 Summer Off-Peak - Pre-Project : Panoche-Kearney 230kV & Kerckhoff (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #51 2013 Summer Off-Peak - Post-Project : Panoche-Kearney 230kV & Kerckhoff (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #52 2013 Summer Off-Peak - Post-Project : Panoche-Kearney 230kV & Kerckhoff (Amps/Pct) Greater Fresno 500 & 230-kV

New and Significant Increased Category C Overloads

Plot #53 2013 Summer Off-Peak - Pre-Project : Gates-Gregg & McCall 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #54 2013 Summer Off-Peak - Pre-Project : Gates-Gregg & McCall 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #55 2013 Summer Off-Peak - Post-Project : Gates-Gregg & McCall 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #56 2013 Summer Off-Peak - Post-Project : Gates-Gregg & McCall 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #57 2013 Summer Off-Peak - Pre-Project : Gates-Gregg & McCall 230kV Lines (MW/MVAr) Fresno South 115-kV

Plot #58 2013 Summer Off-Peak - Pre-Project : Gates-Gregg & McCall 230kV Lines (Amps/Pct) Fresno South 115-kV

Plot #59 2013 Summer Off-Peak - Post-Project : Gates-Gregg & McCall 230kV Lines (MW/MVAr) Fresno South 115-kV

Plot #60 2013 Summer Off-Peak - Post-Project : Gates-Gregg & McCall 230kV Lines (Amps/Pct) Fresno South 115-kV

Plot #61 2013 Summer Off-Peak - Pre-Project : Helm-McCall & Gates-McCall 230kV Lines (MW/MVAr) Greater Fresno 115-kV

Plot #62 2013 Summer Off-Peak - Pre-Project : Helm-McCall & Gates-McCall 230kV Lines (Amps/Pct) Greater Fresno 115-kV

Plot #63 2013 Summer Off-Peak - Post-Project : Helm-McCall & Gates-McCall 230kV Lines (MW/MVAr) Greater Fresno 115-kV

Plot #64 2013 Summer Off-Peak - Post-Project : Helm-McCall & Gates-McCall 230kV Lines (Amps/Pct) Greater Fresno 115-kV

Plot #65 2013 Summer Off-Peak - Pre-Project : Herndon-Ashlan & Gregg-Ashlan 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #66 2013 Summer Off-Peak - Pre-Project : Herndon-Ashlan & Gregg-Ashlan 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #67 2013 Summer Off-Peak - Post-Project : Herndon-Ashlan & Gregg-Ashlan 230kV Lines Greater Fresno 500 & 230-kV

Page 501: To determine the system impacts caused by the Project

(MW/MVAr)

Plot #68 2013 Summer Off-Peak - Post-Project : Herndon-Ashlan & Gregg-Ashlan 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

2013 Spring Peak Conditions

Plot # Descriptions Plot Area

Category A

Plot #69 2013 Spring Peak - Pre-Project : Normal Conditions (MW/MVAr) Henrietta 70-kV

Plot #70 2013 Spring Peak - Pre-Project : Normal Conditions (Amps/Pct) Henrietta 70-kV

Plot #71 2013 Spring Peak - Post-Project : Normal Conditions (MW/MVAr) Henrietta 70-kV

Plot #72 2013 Spring Peak - Post-Project : Normal Conditions (Amps/Pct) Henrietta 70-kV

New and Significant Increased Category B Overloads

Plot #73 2013 Spring Peak - Pre-Project : Wilson-Borden 230kV & Exchequer (MW/MVAr) Greater Fresno 115-kV

Plot #74 2013 Spring Peak - Pre-Project : Wilson-Borden 230kV & Exchequer (Amps/Pct) Greater Fresno 115-kV

Plot #75 2013 Spring Peak - Post-Project : Wilson-Borden 230kV & Exchequer (MW/MVAr) Greater Fresno 115-kV

Plot #76 2013 Spring Peak - Post-Project : Wilson-Borden 230kV & Exchequer (Amps/Pct) Greater Fresno 115-kV

Plot #77 2013 Spring Peak - Pre-Project : Gates-McCall 230kV (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #78 2013 Spring Peak - Pre-Project : Gates-McCall 230kV (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #79 2013 Spring Peak - Post-Project : Gates-McCall 230kV (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #80 2013 Spring Peak - Post-Project : Gates-McCall 230kV (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #81 2013 Spring Peak - Pre-Project : Gates-Templeton 230kV & Melones (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #82 2013 Spring Peak - Pre-Project : Gates-Templeton 230kV & Melones (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #83 2013 Spring Peak - Post-Project : Gates-Templeton 230kV & Melones (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #84 2013 Spring Peak - Post-Project : Gates-Templeton 230kV & Melones (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #85 2013 Spring Peak - Pre-Project : Coburn-Panoche 230 kV & Exchequer (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #86 2013 Spring Peak - Pre-Project : Coburn-Panoche 230 kV & Exchequer (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #87 2013 Spring Peak - Post-Project : Coburn-Panoche 230 kV & Exchequer (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #88 2013 Spring Peak - Post-Project : Coburn-Panoche 230 kV & Exchequer (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #89 2013 Spring Peak - Pre-Project : Dairyland-Mendota 115kV & Exchequer (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #90 2013 Spring Peak - Pre-Project : Dairyland-Mendota 115kV & Exchequer (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #91 2013 Spring Peak - Post-Project : Dairyland-Mendota 115kV & Exchequer (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #92 2013 Spring Peak - Post-Project : Dairyland-Mendota 115kV & Exchequer (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #93 2013 Spring Peak - Pre-Project : Westley-Los Banos 230kV & Kerckhoff (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #94 2013 Spring Peak - Pre-Project : Westley-Los Banos 230kV & Kerckhoff (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #95 2013 Spring Peak - Post-Project : Westley-Los Banos 230kV & Kerckhoff (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #96 2013 Spring Peak - Post-Project : Westley-Los Banos 230kV & Kerckhoff (Amps/Pct) Greater Fresno 500 & 230-kV

New and Significant Increased Category C Overloads

Plot #97 2013 Spring Peak - Pre-Project : McCall-West Fresno & Cal Ave.-McCall 115kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #98 2013 Spring Peak - Pre-Project : McCall-West Fresno & Cal Ave.-McCall 115kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #99 2013 Spring Peak - Post-Project : McCall-West Fresno & Cal Ave.-McCall 115kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #100 2013 Spring Peak - Post-Project : McCall-West Fresno & Cal Ave.-McCall 115kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Page 502: To determine the system impacts caused by the Project

Plot #101 2013 Spring Peak - Pre-Project : Gates-Gregg & Gates-McCall 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #102 2013 Spring Peak - Pre-Project : Gates-Gregg & Gates-McCall 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #103 2013 Spring Peak - Post-Project : Gates-Gregg & Gates-McCall 230kV Lines (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #104 2013 Spring Peak - Post-Project : Gates-Gregg & Gates-McCall 230kV Lines (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #105 2013 Spring Peak - Pre-Project : Helm-McCall & Gates-McCall 230kV Lines (MW/MVAr) Fresno South 115-kV

Plot #106 2013 Spring Peak - Pre-Project : Helm-McCall & Gates-McCall 230kV Lines (Amps/Pct) Fresno South 115-kV

Plot #107 2013 Spring Peak - Post-Project : Helm-McCall & Gates-McCall 230kV Lines (MW/MVAr) Fresno South 115-kV

Plot #108 2013 Spring Peak - Post-Project : Helm-McCall & Gates-McCall 230kV Lines (Amps/Pct) Fresno South 115-kV

Plot #109 2013 Spring Peak - Pre-Project : Henrietta 230kV Bus (MW/MVAr) Henrietta 70-kV

Plot #110 2013 Spring Peak - Pre-Project : Henrietta 230kV Bus (Amps/Pct) Henrietta 70-kV

Plot #111 2013 Spring Peak - Post-Project : Henrietta 230kV Bus (MW/MVAr) Henrietta 70-kV

Plot #112 2013 Spring Peak - Post-Project : Henrietta 230kV Bus (Amps/Pct) Henrietta 70-kV

Plot #113 2013 Spring Peak - Pre-Project : Gates 230kV Bus 1E (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #114 2013 Spring Peak - Pre-Project : Gates 230kV Bus 1E (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #115 2013 Spring Peak - Post-Project : Gates 230kV Bus 1E (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #116 2013 Spring Peak - Post-Project : Gates 230kV Bus 1E (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #117 2013 Spring Peak - Pre-Project : Woodward 115kV Bus (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #118 2013 Spring Peak - Pre-Project : Woodward 115kV Bus (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #119 2013 Spring Peak - Post-Project : Woodward 115kV Bus (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #120 2013 Spring Peak - Post-Project : Woodward 115kV Bus (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #121 2013 Spring Peak - Pre-Project : Los Banos North DLO (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #122 2013 Spring Peak - Pre-Project : Los Banos North DLO (Amps/Pct) Greater Fresno 500 & 230-kV

Plot #123 2013 Spring Peak - Post-Project : Los Banos North DLO (MW/MVAr) Greater Fresno 500 & 230-kV

Plot #124 2013 Spring Peak - Post-Project : Los Banos North DLO (Amps/Pct) Greater Fresno 500 & 230-kV

Page 503: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 1 - No Outage MW/MVAR

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:46 2008 2013sumpk_q272_pre.sav

HENRITTA74.20

LEMOORE71.57

MUSLSLGH73.93

CAMDEN68.58

KNGLOBUS

70.67

KINGSBRG118.4

HENRIETA228.5

34542JCBSCRNR

GUERNSEY75.11

34554

AMSTG SW

ARMSTRNG75.85

GWF-PWR.14.36RESERVE

75.83

34528

CORCORAN

34420

CORCORAN

HNFRD SW

69.90

HARDWICK

69.62

ANGIOLA

71.96

BOSWELL72.32

LEPRINO71.50

CANDLEWK71.62

CMDN JCT

BSWLL TP

JGBSWLL

72.30

GUR3TPT

GWF_HENR74.23

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

12.0

1

50

5

1

50

5

1 1

19.1

3.9

1

33.2

6.7

2

12.2

2.5

1

9.6

2.0

28.3

1.7

1

6.9

1.4

1

11.0

2.2

2

22.0 13.6

1

7.3

1.5

1

13.0 2.6

1

10.6 2.2

1

2.41.5

1

0.0

0.0

1

2.0 0.4

1

0.00.0

1

1

1

0

ss

1

0

ss ss

7

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

0.00.1

18.0 3.5

18.4 3.9

2.0

0.4

23.0

12.0

0.0

0.0

20.9

11.6

20.8

11.5

10.2

9.3

10.1 9.3

11.8 4.9

11.8

5.0

52.2

10.6

10.6

2.1

2.41.5

59.9

19.2

3.1

38.7

6.5

2.4

0.00.0

0.0

0.0

13.2

2.4

13.0 2.6

32.1

6.7

9.83.2

9.72.8

7.3

1.5

7.31.4

48.9

0.4

48.9

0.4

97.8

0.8

22.0

13.7

22.013.6

6.64.3

Page 504: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 2 - No Outage amps/rate

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:47 2008 2013sumpk_q272_pre.sav

HENRITTA74.20

LEMOORE71.57

MUSLSLGH73.93

CAMDEN68.58

KNGLOBUS

70.67

KINGSBRG118.4

HENRIETA228.5

34542JCBSCRNR

GUERNSEY75.11

34554

AMSTG SW

ARMSTRNG75.85

GWF-PWR.14.36RESERVE

75.83

34528

CORCORAN

34420

CORCORAN

HNFRD SW

69.90

HARDWICK

69.62

ANGIOLA

71.96

BOSWELL72.32

LEPRINO71.50

CANDLEWK71.62

CMDN JCT

BSWLL TP

JGBSWLL

72.30

GUR3TPT

GWF_HENR74.23

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

12.0

1

50

5

1

50

5

1 1

19.1

3.9

1

33.2

6.7

2

12.2

2.5

1

9.6

2.0

28.3

1.7

1

6.9

1.4

1

11.0

2.2

2

22.0 13.6

1

7.3

1.5

1

13.0 2.6

1

10.6 2.2

1

2.41.5

1

0.0

0.0

1

2.0 0.4

1

0.00.0

1

1

1

0

ss

1

0

ss ss

7

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

1.20.5

154.1 45.3

153.4 45.0

15.9

7.7

197.3

96.3

0.1

0.0

182.1

56.6

182.5

56.7

105.9

26.2

107.1 26.5

99.324.2

100.0

24.4

430.1

67.7

83.3

20.6

22.5 5.1

489.5

77.1

98.1

38.8

17.4

3.4

0.00.0

0.0

0.0

109.3

33.6

110.1 31.8

160.1

36.5

51.455.0

80.6

27.2

59.9

20.2

59.720.1

380.3

84.9

380.3

84.9

760.7

67.3

201.7 31.8

202.0 31.8

63.921.5

Page 505: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 3 - No Outage MW/MVAR

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:48 2008 2013sumpk_q272_pst_v2.sav

HENRITTA74.22

LEMOORE71.59

MUSLSLGH73.95

CAMDEN68.60

KNGLOBUS

70.69

KINGSBRG118.5

HENRIETA228.6

34542JCBSCRNR

GUERNSEY75.13

34554

AMSTG SW

ARMSTRNG75.88

GWF-PWR.14.36RESERVE

75.86

34528

CORCORAN

34420

CORCORAN

HNFRD SW

69.92

HARDWICK

69.64

ANGIOLA

71.98

BOSWELL72.34

LEPRINO71.52

CANDLEWK71.65

CMDN JCT

BSWLL TP

JGBSWLL

72.33

GUR3TPT

GWF_HENR74.26

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

12.0

1

50

4

1

50

4

1

27

2

1

19.1

3.9

1

33.2

6.7

2

12.2

2.5

1

9.6

2.0

28.3

1.7

1

6.9

1.4

1

11.0

2.2

2

22.0 13.6

1

7.3

1.5

1

13.0 2.6

1

10.6 2.2

1

2.41.5

1

0.0

0.0

1

2.0 0.4

1

0.00.0

1

1

1

0

ss

1

0

ss

2

1

ss

7

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

0.00.1

18.0 3.5

18.4 3.9

2.1

0.4

23.0

12.0

0.0

0.0

20.9

11.6

20.8

11.5

10.2

9.3

10.1 9.3

11.8 4.9

11.8

5.0

52.2

10.6

10.6

2.2

2.41.5

59.9

19.2

5.2

39.4

10.3

3.6

0.00.0

0.0

0.0

13.2

2.4

13.0 2.6

32.1

6.7

9.83.2

9.72.8

7.3

1.5

7.31.4

25.0

0.9

48.9

0.1

48.9

0.1

122.8

0.6

22.0

13.7

22.013.6

6.64.3

Page 506: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 4 - No Outage amps/rate

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:48 2008 2013sumpk_q272_pst_v2.sav

HENRITTA74.22

LEMOORE71.59

MUSLSLGH73.95

CAMDEN68.60

KNGLOBUS

70.69

KINGSBRG118.5

HENRIETA228.6

34542JCBSCRNR

GUERNSEY75.13

34554

AMSTG SW

ARMSTRNG75.88

GWF-PWR.14.36RESERVE

75.86

34528

CORCORAN

34420

CORCORAN

HNFRD SW

69.92

HARDWICK

69.64

ANGIOLA

71.98

BOSWELL72.34

LEPRINO71.52

CANDLEWK71.65

CMDN JCT

BSWLL TP

JGBSWLL

72.33

GUR3TPT

GWF_HENR74.26

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

12.0

1

50

4

1

50

4

1

27

2

1

19.1

3.9

1

33.2

6.7

2

12.2

2.5

1

9.6

2.0

28.3

1.7

1

6.9

1.4

1

11.0

2.2

2

22.0 13.6

1

7.3

1.5

1

13.0 2.6

1

10.6 2.2

1

2.41.5

1

0.0

0.0

1

2.0 0.4

1

0.00.0

1

1

1

0

ss

1

0

ss

2

1

ss

7

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

1.20.5

154.1 45.2

153.4 45.0

15.9

7.7

197.2

96.3

0.1

0.0

182.1

56.6

182.4

56.7

105.9

26.2

107.1 26.5

99.224.2

100.0

24.4

430.0

67.7

83.4

20.6

22.5 5.1

489.3

77.0

100.2

39.7

27.5

5.4

0.00.0

0.0

0.0

109.2

33.6

110.0 31.8

160.0

36.5

51.455.0

80.6

27.1

59.9

20.2

59.720.1

194.5

71.5

380.2

84.9

380.2

84.9

954.8

84.5

201.7 31.8

201.9 31.8

63.921.5

Page 507: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 5-Outage: Gates-Gregg 230kV and Melones 1 MW/MVAR

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:50 2008 2013sumpk_q272_pre.sav

HERNDON117.9

HERNDON231.8

BULLARD115.6

WOODWARD115.3

KERCKHF2116.8

SANGER118.4

MANCHSTR116.5

BARTON116.4

CHLDHOSP116.3

CLOVIS-1116.6

MC CALL120.4

MC CALL233.2

KERCKHF1116.7

KERCKHOF12.97

KERCKHOF6.638

CLOVIS-2116.4

SHARON115.6

CORSGOLD

113.7

OAKHURST

112.8

CHWCHLLA116.1

CERTTEED116.3

LE GRAND116.4

EXCHEQUR120.6

WILSON B117.2

WILSON226.8

DAIRYLND116.5

NEWHALL117.7

MADERAPR118.3

MENDOTA119.5

PANOCHE121.7

HAMMONDS120.2

EL CAPTN115.1

CASTLE114.8

ATWATER114.7

LIVNGSTN113.7

GALLO

113.6

WILSON A117.3

ORO LOMA117.3

EL NIDO116.4

MERCED

116.2

CANTUA120.4

WESTLNDS120.4

KAMM120.9

SCHINDLR120.5

PANOCHE232.7

EXCHEQUR

73.55

EXCHQUER13.80

CHENY121.9

SCHLNDLR72.87

AIRPROD119.4

MALAGA119.3

ULTR.PWR9.031

RANCHRS119.2

SCWAX119.2

PPG

119.3

WST FRSO114.3

DANISHCM114.4

CAL AVE114.1

OXFORD121.2

LUIS_#3121.1

LUIS_#5121.1

JR WOOD114.6

JRWD GEN114.6

CRESSEY114.2

MERCED

MENDOTA74.66

ORO LOMA71.47

PNEDLE115.8

WSTLD1RA121.2

DFS

118.4

PANOCHET

WHD_PAN214.42

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.8

CHOWCOGN

13.80

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.76

AIRWAYS116.7

LASPALMS116.9

P0418120.5

ATWATR JCRESEY T

MALAGATP

KRCDP119.4

KRCDPCT1

KRCDPCT214.49

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

30

1

0

20

1

0

48

1

129 16 1

9514 1

1

7 4

2 3

15

13

1

45 1

49 6 1

29 7 1

50

5

1

13

7

1

50 9 1

50 9 1

078

v

0

9

v

0

9

v

09

v

92

2

26 5

1

10 2

1

3 1

1

3 1

1

4 2

1

19

4

1

1210

1

33 7

1

29 6

2

12 2

1

15 3

2

20

1

27 5

2

4

4

1

38 8

1

26

5

1

26

5

2

37

7

3

52 10

1

44

9

1

38

8

2

27

6

3

45 9

1

45 9

2

43 9

3

3 2

1

43

9

1

53

11

2

45

9

3

7

5

1

10

7

1

10

2

1

14

3

2

14

3

1

20 4

1

26 5

2

33 7

3

13 3

1

15 3

2

17 3

1

4 2

1

38

8

1

39

8

2

9

2

1

3

2

1

26 5

1

23 5

2

23 5

3

6 4

1

5

2

1

29 6

1

4 4

1

13

3

1

11

1

41

ss

2 1

ss

39 8

1

13 3

2

14 12

1

25 5

1

31

1

51 10

2

45 9

3

11

ss

11

ss

19 4

3

31

6

2

41

8

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

44.327.0

96.8 4.7

41.6 0.7

21.6

21.3

55.4

4.2

107.4

15.4

92.026.2

4.3

3.4

51.610.5

136.5 25.9

115.1 65.9

115.4 52.5

207.3 94.7

201.2 73.0

190.5 47.3

3.4

25.5

96.019.5

3.5

4.6

69.6

23.1

41.7 9.9

48.4

8.9

4.3

3.4

92.424.2

91.6

21.1

12.2

5.4

8.68.2

27.2 8.6

43.3

2.3

63.2

6.4

38.4 2.2

11.2

6.8

7.3

5.8

58.5

16.7

18.7 0.2

3.5

4.7

56.6

12.2

27.2

5.3

7.1

5.0

21.1

18.2

3.1

23.1

9.7

3.2

20.4 8.1

136.5 25.9

53.3 6.4

47.9 3.9

6.23.9

21.315.1

39.022.5

17.2

2.3

47.2

3.3

29.2

8.5

12.2 5.0

26.3 9.1

124.5 27.7

15.214.7

44.2

8.9

92.818.1

114.7 24.3

72.0

14.6

91.913.7

41.7 4.5

46.0

7.3

90.2

1.6

35.5 0.4

32.6

3.5

2.9

3.9

11.9 3.0

69.1

16.3

104.8

8.6

118.4

12.0

93.7

4.2

92.5 1.4

27.7 1.9

27.7 5.8

9.9

6.9

50.2 2.6

21.3

18.4

129.0 0.1

86.4

2.3

86.4

2.3

50.2 2.6

60.3

4.4

49.1 1.2

44.9

4.0

94.514.2

10.5

5.0

10.5

5.0

50.0

0.4

145.0 6.0

94.226.5

91.3

18.8

13.9 3.4

13.9

3.0

71.9

14.4

71.714.0

303.2

11.7

49.0

3.5

48.8

3.1

68.4

14.8

49.0 3.5

4.87.8

25.0 4.6

31.0

14.031.0

14.0

19.3

3.6

69.6

23.9

48.1

29.8

47.9

29.0

78.123.7

76.0

17.9

129.4 11.0

37.0 4.1

91.5

17.1

147.2 5.2

14.5 6.0

130.2

8.2

14.5

12.4

70.1 1.9

69.6 0.3

9.3

1.9

2.7

1.5

12.0 3.462.4

16.3

50.4

13.0

50.413.0

97.8 7.3

49.0 3.8

49.0 3.8

1.9

17.7

0.7

3.6

97.0

35.0

94.741.6

29.214.1

Page 508: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 6-Outage: Gates-Gregg 230kV and Melones 1 amps/rate

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:52 2008 2013sumpk_q272_pre.sav

HERNDON117.9

HERNDON231.8

BULLARD115.6

WOODWARD115.3

KERCKHF2116.8

SANGER118.4

MANCHSTR116.5

BARTON116.4

CHLDHOSP116.3

CLOVIS-1116.6

MC CALL120.4

MC CALL233.2

KERCKHF1116.7

KERCKHOF12.97

KERCKHOF6.638

CLOVIS-2116.4

SHARON115.6

CORSGOLD

113.7

OAKHURST

112.8

CHWCHLLA116.1

CERTTEED116.3

LE GRAND116.4

EXCHEQUR120.6

WILSON B117.2

WILSON226.8

DAIRYLND116.5

NEWHALL117.7

MADERAPR118.3

MENDOTA119.5

PANOCHE121.7

HAMMONDS120.2

EL CAPTN115.1

CASTLE114.8

ATWATER114.7

LIVNGSTN113.7

GALLO

113.6

WILSON A117.3

ORO LOMA117.3

EL NIDO116.4

MERCED

116.2

CANTUA120.4

WESTLNDS120.4

KAMM120.9

SCHINDLR120.5

PANOCHE232.7

EXCHEQUR

73.55

EXCHQUER13.80

CHENY121.9

SCHLNDLR72.87

AIRPROD119.4

MALAGA119.3

ULTR.PWR9.031

RANCHRS119.2

SCWAX119.2

PPG

119.3

WST FRSO114.3

DANISHCM114.4

CAL AVE114.1

OXFORD121.2

LUIS_#3121.1

LUIS_#5121.1

JR WOOD114.6

JRWD GEN114.6

CRESSEY114.2

MERCED

MENDOTA74.66

ORO LOMA71.47

PNEDLE115.8

WSTLD1RA121.2

DFS

118.4

PANOCHET

WHD_PAN214.42

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.8

CHOWCOGN

13.80

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.76

AIRWAYS116.7

LASPALMS116.9

P0418120.5

ATWATR JCRESEY T

MALAGATP

KRCDP119.4

KRCDPCT1

KRCDPCT214.49

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

30

1

0

20

1

0

48

1

129 16 1

9514 1

1

7 4

2 3

15

13

1

45 1

49 6 1

29 7 1

50

5

1

13

7

1

50 9 1

50 9 1

078

v

0

9

v

0

9

v

09

v

92

2

26 5

1

10 2

1

3 1

1

3 1

1

4 2

1

19

4

1

1210

1

33 7

1

29 6

2

12 2

1

15 3

2

20

1

27 5

2

4

4

1

38 8

1

26

5

1

26

5

2

37

7

3

52 10

1

44

9

1

38

8

2

27

6

3

45 9

1

45 9

2

43 9

3

3 2

1

43

9

1

53

11

2

45

9

3

7

5

1

10

7

1

10

2

1

14

3

2

14

3

1

20 4

1

26 5

2

33 7

3

13 3

1

15 3

2

17 3

1

4 2

1

38

8

1

39

8

2

9

2

1

3

2

1

26 5

1

23 5

2

23 5

3

6 4

1

5

2

1

29 6

1

4 4

1

13

3

1

11

1

41

ss

2 1

ss

39 8

1

13 3

2

14 12

1

25 5

1

31

1

51 10

2

45 9

3

11

ss

11

ss

19 4

3

31

6

2

41

8

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

259.7 26.7

482.2 49.5

205.9 27.7

150.5

13.4

276.5

37.2

535.6

55.0

466.4 41.5

27.2

3.9

260.6 23.2

677.0 60.2

649.8 28.7

621.1 27.3

1092.7 49.3

1026.0 46.3

940.9 42.2

125.9

11.2

486.2 43.2

28.7

7.2

186.7 23.0

210.9 44.7

244.4

33.1

27.9

8.1

470.7 53.3

471.5

53.4

67.2

9.1

59.7 5.0

143.7 28.1

215.2

22.1

311.3

27.7

187.7 19.3

62.0

12.1

44.5

8.7

299.3

40.3

93.918.3

508.5

13.0

288.8

83.4

140.6

41.2

43.3

12.5

138.8

35.0

116.1

22.7

49.0

9.6

105.1 15.2

677.0 60.2

257.5 34.7

232.5 31.3

35.659.1

125.1 20.9

215.8 29.2

85.9

11.6

234.4

58.9

154.4

30.1

66.2 9.0

135.4 26.4

611.6 62.8

104.4 26.2

222.0

43.3

463.3 28.0

574.2 34.7

366.1

49.3

464.0 62.4

209.3 28.2

229.2

64.7

444.1

73.1

168.3 32.9

155.5

30.4

23.0

4.5

58.711.5

336.9

42.2

499.7

82.3

564.9

50.2

450.7

74.2

450.8 74.2

138.0 46.3

138.0 47.2

60.2

17.4

250.0 72.2

140.3

35.4

637.8 71.7

428.1

57.6

428.1

57.6

250.0 72.2

299.8

86.6

235.0 49.1

353.4

45.0

3998.0 95.6

57.4

92.9

57.4

11.2

247.1

89.3

707.5 62.9

469.1 41.7

470.9

41.9

72.2 9.7

71.7

9.7

369.7

32.9

369.9 32.9

1454.1

72.8

231.6

45.2

231.6

45.2

337.8

34.7

231.6 87.7

43.912.1

124.0 68.2

171.3

33.4

171.3

33.5

98.9

19.3

187.3 15.9

277.0

28.4

278.0

28.5

391.4 34.8

393.7

35.0

641.2 57.0

184.4 18.9

461.4

41.0

718.1 63.9

77.8 8.0

647.1

57.5

92.2

92.1

339.3 45.9

339.3 45.9

45.8

8.9

15.0

4.3

60.211.7312.0

42.0

252.1 33.9

252.1 33.9

474.9 56.0

237.4 70.1

237.4 70.1

44.2

4.8

9.0

2.5

511.4

99.9

509.3 99.5

161.5 40.7

Page 509: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 7-Outage: Gates-Gregg 230kV and Melones 1 MW/MVAR

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:54 2008 2013sumpk_q272_pst_v2.sav

HERNDON117.9

HERNDON231.9

BULLARD115.6

WOODWARD115.3

KERCKHF2116.8

SANGER118.5

MANCHSTR116.5

BARTON116.4

CHLDHOSP116.3

CLOVIS-1116.6

MC CALL120.4

MC CALL233.2

KERCKHF1116.8

KERCKHOF12.97

KERCKHOF6.639

CLOVIS-2116.4

SHARON115.6

CORSGOLD

113.8

OAKHURST

112.8

CHWCHLLA116.1

CERTTEED116.4

LE GRAND116.4

EXCHEQUR120.7

WILSON B117.3

WILSON226.9

DAIRYLND116.5

NEWHALL117.8

MADERAPR118.4

MENDOTA119.7

PANOCHE121.8

HAMMONDS120.3

EL CAPTN115.2

CASTLE114.8

ATWATER114.7

LIVNGSTN113.7

GALLO

113.6

WILSON A117.3

ORO LOMA117.5

EL NIDO116.5

MERCED

116.2

CANTUA120.5

WESTLNDS120.5

KAMM121.1

SCHINDLR120.6

PANOCHE233.1

EXCHEQUR

73.56

EXCHQUER13.80

CHENY122.0

SCHLNDLR72.93

AIRPROD119.4

MALAGA119.3

ULTR.PWR9.033

RANCHRS119.2

SCWAX119.3

PPG

119.3

WST FRSO114.3

DANISHCM114.5

CAL AVE114.1

OXFORD121.4

LUIS_#3121.3

LUIS_#5121.3

JR WOOD114.6

JRWD GEN114.6

CRESSEY114.3

MERCED

MENDOTA74.73

ORO LOMA71.68

PNEDLE115.8

WSTLD1RA121.4

DFS

118.6

PANOCHET

WHD_PAN214.42

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.9

CHOWCOGN

13.80

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.76

AIRWAYS116.7

LASPALMS116.9

P0418120.5

ATWATR JCRESEY T

MALAGATP

KRCDP119.4

KRCDPCT1

KRCDPCT214.49

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

30

1

0

20

1

0

48

1

129 16 1

9514 1

1

7 4

2 3

15

13

1

45 1

49 6 1

29 7 1

50

5

1

13

7

1

50 9 1

50 9 1

078

v

0

9

v

0

9

v

09

v

92

2

26 5

1

10 2

1

3 1

1

3 1

1

4 2

1

19

4

1

1210

1

33 7

1

29 6

2

12 2

1

15 3

2

20

1

27 5

2

4

4

1

38 8

1

26

5

1

26

5

2

37

7

3

52 10

1

44

9

1

38

8

2

27

6

3

45 9

1

45 9

2

43 9

3

3 2

1

43

9

1

53

11

2

45

9

3

7

5

1

10

7

1

10

2

1

14

3

2

14

3

1

20 4

1

26 5

2

33 7

3

13 3

1

15 3

2

17 3

1

4 2

1

38

8

1

39

8

2

9

2

1

3

2

1

26 5

1

23 5

2

23 5

3

6 4

1

5

2

1

29 6

1

4 4

1

13

3

1

11

1

41

ss

2 1

ss

39 8

1

13 3

2

14 12

1

25 5

1

31

1

51 10

2

45 9

3

11

ss

11

ss

19 4

3

31

6

2

41

8

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

43.827.1

97.4 4.6

41.6 0.7

22.6

21.4

56.0

4.0

107.9

15.3

92.326.1

4.0

3.3

51.610.5

137.2 25.9

114.0 66.3

114.3 52.8

207.9 95.0

201.7 73.1

191.0 47.6

4.3

25.8

96.019.5

3.5

4.6

69.4

22.8

41.7 9.9

48.4

8.9

4.3

3.4

92.424.2

91.6

21.1

12.2

5.4

8.68.2

27.2 8.6

43.4

2.6

63.2

6.7

38.4 2.7

11.0

7.0

7.1

6.0

58.5

16.7

18.7 0.2

3.5

4.7

56.6

12.2

27.2

5.3

7.1

5.0

21.4

18.4

2.8

23.3

9.9

3.4

20.7 8.4

137.2 25.9

53.6 6.5

48.2 4.0

6.33.9

20.715.2

38.422.6

17.2

2.0

47.1

3.4

29.2

8.5

12.2 5.0

26.3 9.0

124.8 27.7

15.414.1

44.4

8.2

92.818.1

114.7 24.3

72.0

14.6

91.913.7

41.7 4.5

45.9

6.1

90.3

2.1

35.5 0.4

32.7

4.4

2.7

4.0

12.0 3.1

69.0

16.9

104.9

8.1

118.5

11.5

93.8

3.7

92.6 0.9

27.7 1.8

27.7 5.8

10.0

6.9

50.2 2.7

21.6

18.6

129.0 0.1

86.8

2.4

86.8

2.4

50.2 2.7

60.3

4.3

49.1 1.3

44.9

4.0

94.514.1

10.5

5.0

10.5

5.0

50.0

0.5

145.9 5.9

94.226.5

91.3

18.8

13.9 3.4

13.9

3.0

71.9

14.4

71.714.0

303.2

11.4

49.0

2.7

48.8

2.3

68.2

15.4

49.0 2.7

4.67.8

25.0 4.4

31.0

14.031.0

14.0

19.3

3.6

69.3

23.7

47.5

29.9

47.4

29.1

78.123.7

76.0

17.9

130.3 11.2

37.1 4.1

92.4

17.4

148.1 5.2

14.5 6.0

131.2

8.4

14.5

12.4

70.4 1.7

69.9 0.1

9.3

1.9

2.7

1.5

12.0 3.462.7

16.3

50.8

13.0

50.713.0

97.8 7.2

49.0 3.7

49.0 3.7

2.1

20.6

0.7

4.6

97.3

35.1

95.041.7

29.514.2

Page 510: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 8-Outage: Gates-Gregg 230kV and Melones 1 amps/rate

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:56 2008 2013sumpk_q272_pst_v2.sav

HERNDON117.9

HERNDON231.9

BULLARD115.6

WOODWARD115.3

KERCKHF2116.8

SANGER118.5

MANCHSTR116.5

BARTON116.4

CHLDHOSP116.3

CLOVIS-1116.6

MC CALL120.4

MC CALL233.2

KERCKHF1116.8

KERCKHOF12.97

KERCKHOF6.639

CLOVIS-2116.4

SHARON115.6

CORSGOLD

113.8

OAKHURST

112.8

CHWCHLLA116.1

CERTTEED116.4

LE GRAND116.4

EXCHEQUR120.7

WILSON B117.3

WILSON226.9

DAIRYLND116.5

NEWHALL117.8

MADERAPR118.4

MENDOTA119.7

PANOCHE121.8

HAMMONDS120.3

EL CAPTN115.2

CASTLE114.8

ATWATER114.7

LIVNGSTN113.7

GALLO

113.6

WILSON A117.3

ORO LOMA117.5

EL NIDO116.5

MERCED

116.2

CANTUA120.5

WESTLNDS120.5

KAMM121.1

SCHINDLR120.6

PANOCHE233.1

EXCHEQUR

73.56

EXCHQUER13.80

CHENY122.0

SCHLNDLR72.93

AIRPROD119.4

MALAGA119.3

ULTR.PWR9.033

RANCHRS119.2

SCWAX119.3

PPG

119.3

WST FRSO114.3

DANISHCM114.5

CAL AVE114.1

OXFORD121.4

LUIS_#3121.3

LUIS_#5121.3

JR WOOD114.6

JRWD GEN114.6

CRESSEY114.3

MERCED

MENDOTA74.73

ORO LOMA71.68

PNEDLE115.8

WSTLD1RA121.4

DFS

118.6

PANOCHET

WHD_PAN214.42

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.9

CHOWCOGN

13.80

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.76

AIRWAYS116.7

LASPALMS116.9

P0418120.5

ATWATR JCRESEY T

MALAGATP

KRCDP119.4

KRCDPCT1

KRCDPCT214.49

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

30

1

0

20

1

0

48

1

129 16 1

9514 1

1

7 4

2 3

15

13

1

45 1

49 6 1

29 7 1

50

5

1

13

7

1

50 9 1

50 9 1

078

v

0

9

v

0

9

v

09

v

92

2

26 5

1

10 2

1

3 1

1

3 1

1

4 2

1

19

4

1

1210

1

33 7

1

29 6

2

12 2

1

15 3

2

20

1

27 5

2

4

4

1

38 8

1

26

5

1

26

5

2

37

7

3

52 10

1

44

9

1

38

8

2

27

6

3

45 9

1

45 9

2

43 9

3

3 2

1

43

9

1

53

11

2

45

9

3

7

5

1

10

7

1

10

2

1

14

3

2

14

3

1

20 4

1

26 5

2

33 7

3

13 3

1

15 3

2

17 3

1

4 2

1

38

8

1

39

8

2

9

2

1

3

2

1

26 5

1

23 5

2

23 5

3

6 4

1

5

2

1

29 6

1

4 4

1

13

3

1

11

1

41

ss

2 1

ss

39 8

1

13 3

2

14 12

1

25 5

1

31

1

51 10

2

45 9

3

11

ss

11

ss

19 4

3

31

6

2

41

8

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

257.7 26.5

484.8 49.8

205.8 27.7

154.2

13.7

279.1

37.6

538.1

55.3

467.7 41.6

25.8

3.7

260.6 23.2

680.3 60.5

645.7 28.5

616.4 27.1

1095.6 49.5

1028.6 46.4

943.5 42.3

128.1

11.4

486.1 43.2

28.7

7.2

185.8 22.9

210.8 44.7

244.3

33.1

27.9

8.1

470.5 53.3

471.3

53.3

67.2

9.1

59.7 5.0

143.6 28.0

215.2

22.1

311.3

27.7

187.9 19.3

61.7

12.1

44.5

8.7

299.2

40.3

93.918.3

508.4

13.0

288.8

83.4

140.5

41.2

43.3

12.5

140.4

35.4

116.8

22.8

49.9

9.7

106.9 15.5

680.3 60.5

259.0 34.9

234.0 31.5

35.659.1

123.2 20.5

213.5 28.9

85.8

11.5

234.3

58.9

154.3

30.1

66.2 9.0

135.3 26.4

612.6 62.9

103.0 25.9

221.9

43.3

463.2 28.0

574.1 34.7

366.0

49.3

463.9 62.4

209.3 28.2

227.5

64.3

443.8

73.1

168.1 32.8

156.5

30.6

23.1

4.5

59.511.6

336.5

42.2

499.3

82.2

564.4

50.2

450.5

74.2

450.5 74.2

138.0 46.3

138.0 47.2

60.2

17.4

249.9 72.1

142.0

35.8

637.7 71.7

429.6

57.8

429.6

57.8

249.9 72.1

299.7

86.5

234.8 49.1

353.5

45.0

3997.3 95.5

57.4

92.9

57.4

11.2

247.0

89.3

711.8 63.3

469.0 41.7

470.8

41.9

72.1 9.7

71.7

9.6

369.7

32.9

369.8 32.9

1453.8

72.8

231.2

45.1

231.2

45.1

337.4

34.6

231.2 87.6

43.812.1

123.7 68.0

171.2

33.4

171.3

33.4

98.9

19.3

186.4 15.9

274.9

28.2

276.0

28.3

391.3 34.8

393.6

35.0

645.6 57.4

184.6 19.0

465.6

41.4

722.4 64.2

77.5 8.0

651.6

57.9

92.2

92.1

340.7 46.1

340.7 46.1

45.8

8.9

15.0

4.3

60.211.7313.4

42.2

253.5 34.1

253.5 34.1

474.7 56.0

237.4 70.1

237.4 70.1

51.3

5.6

11.5

3.2

512.7

100.1

510.6 99.7

163.2 41.2

Page 511: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 9-Outage: Wilson-Borden #2 230kV MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:58 2008 2013sumpk_q272_pre.sav

MIDWAY523.9

24156VINCENT

MIDWAY227.3

30057DIABLO

528.61.057

GATES529.6

GATES228.7

MORROBAY233.7

TEMPLETN

ARCO226.0

LOSBANOS524.9

30045MOSSLAND

521.61.043

GREGG230.1

HELMS PP233.6

HENRIETA228.3

PANOCHE231.8

HELM231.7

MCMULLN1

HERNDON229.6

LOSBANOS

231.7

COBURN235.2

TESLA524.3

TRACY530.9

METCALF519.4

METCALF232.1

BALCH3TP237.4

PINE FLT236.2

GATES228.7

KEARNEY228.7

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.9

Q128233.7

Q239229.8

Q166229.6

Q194229.4

BORDEN229.4

STOREY 2232.2

STOREY 1227.8

WILSON222.7

WARNERVL228.3

DS AMIGO230.6

MELONES231.7

COTTLE A229.9

COTTLE B228.2

BELLOTA228.7

TESLA E231.1

SN LS PP

TESLA D232.8

TESLA C232.7

Q235SWST232.1

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.9

STANDFRD114.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.2

143.4

1213.0

61.6

1247.0

65.0

1539.0

57.1

315.4

120.7

316.0

3.1

737.4 67.1

733.4

115.9

356.9 26.3

341.4

71.2

468.2 59.1

298.9

68.8

14.0

5.214.1

17.8

74.5

14.2

75.0

7.0

983.9

110.3

976.8

34.3

476.4

221.9

472.8

161.6

137.5 39.8

392.4

5.2

392.4

5.2

32.7

87.0

254.8 18.4

250.7

41.2

236.4 29.0

50.230.3

49.7 9.3

697.4 6.2

695.0 45.2

877.2

570.0

826.9 1.3

594.5

48.1

594.5

48.1

486.9

36.2

485.3

100.5

1053.4

27.5

67.2

1.0

134.4 6.9

27.231.2

106.0 24.6

184.4 2.6

219.1 32.8

216.3 42.4

238.5 35.0

243.0 18.7

508.1

27.9

540.0

26.4

565.8

31.1

282.7

71.6

292.4 39.8

283.0

71.7

140.3 8.8

142.9

8.9

292.1 39.8

186.3 46.0

192.7 29.6

675.2

44.3

873.0

137.2

859.0

135.4

879.3

146.5

281.7 13.5281.7 13.5

581.9

143.9

605.3

37.8

216.7

18.0

216.7

18.0

425.2

11.2

587.2

144.8

185.4 26.2

94.811.4

94.0

18.5

94.0

18.5

94.811.4

245.5 0.1

80.8

25.3

79.1

25.6

581.0

27.2

539.1

18.3

282.1 84.1

103.3 62.0

219.8 1.8

318.7

49.2

189.0

17.3

680.3

37.3

742.2 98.0

962.2121.3

865.4166.4

145.3 71.8145.3 71.8

271.7 23.1

267.1 42.1

177.1

52.3

39.9

3.1

39.9

3.1

602.3 46.0

602.3 46.0

145.0 72.3145.0 72.3

793.0 63.0

1229.7 0.5

1249.7

82.9

587.9130.3

589.4

171.3

1554.0 42.8

402.2 34.3

402.2 34.7

402.2 34.7

596.2

7.8

133.0

9.1

132.6

9.9

93.8

18.9

125.1

44.8

123.2

42.3

125.1

44.8

123.2

42.3

790.1 77.1

86.910.743.4 5.343.4 5.3

86.0

17.9

86.0

17.9

350.1 44.8

44.3

27.8

44.416.5

44.3

27.8

44.416.5

529.6

144.3

527.8 57.3

249.0

1.4

247.8

7.7

Page 512: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 10-Outage: Wilson-Borden #2 230kV amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:22:59 2008 2013sumpk_q272_pre.sav

MIDWAY523.9

24156VINCENT

MIDWAY227.3

30057DIABLO

528.61.057

GATES529.6

GATES228.7

MORROBAY233.7

TEMPLETN

ARCO226.0

LOSBANOS524.9

30045MOSSLAND

521.61.043

GREGG230.1

HELMS PP233.6

HENRIETA228.3

PANOCHE231.8

HELM231.7

MCMULLN1

HERNDON229.6

LOSBANOS

231.7

COBURN235.2

TESLA524.3

TRACY530.9

METCALF519.4

METCALF232.1

BALCH3TP237.4

PINE FLT236.2

GATES228.7

KEARNEY228.7

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.9

Q128233.7

Q239229.8

Q166229.6

Q194229.4

BORDEN229.4

STOREY 2232.2

STOREY 1227.8

WILSON222.7

WARNERVL228.3

DS AMIGO230.6

MELONES231.7

COTTLE A229.9

COTTLE B228.2

BELLOTA228.7

TESLA E231.1

SN LS PP

TESLA D232.8

TESLA C232.7

Q235SWST232.1

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.9

STANDFRD114.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

869.8

29.3

1338.3

0.0

1375.9

0.0

1697.1

0.0

372.1

12.6

344.5

11.6

808.7 27.3

809.4

27.3

884.0 90.7

880.6

90.3

1165.8 68.0

774.3

79.4

38.0

4.058.0

6.2

193.8

20.6

190.2

20.2

1079.2

36.4

1075.0

36.3

579.1

19.5

549.5

18.5

356.5 36.6

984.7

50.4

984.7

50.4

102.2

9.2

636.4 65.3

633.1

64.9

593.4 69.8

146.0 17.2

124.0 14.6

767.0 25.9

771.0 26.0

1137.6

38.4

915.3 30.9

1496.7

66.1

1496.7

66.1

532.2

12.3

545.0

12.6

1148.7

75.2

168.6

8.9

333.0 34.2

104.7 10.7

269.3 30.4

456.6 51.5

552.2 65.0

549.1 64.6

600.7 70.7

603.4 71.0

565.6

35.0

600.9

39.8

629.8

50.5

725.4

41.6

731.3 42.0

726.1

41.7

348.4 40.9

351.3

41.3

730.6 41.9

475.5 55.9

485.7 57.1

744.2

25.1

973.8

78.8

958.3

77.5

982.3

79.5

696.8 37.5696.8 37.5

1522.5

155.9

1524.8

156.2

546.7

56.0

546.7

56.0

1069.5

109.5

1536.1

157.3

471.1 97.5

235.7 24.1

240.8

24.7

240.8

24.7

235.7 24.1

616.9 72.5

212.5

26.8

208.5

26.3

1463.7

184.5

1367.3

160.7

763.3 96.2

312.3 36.7

547.6 64.4

815.9

102.9

479.0

56.4

1697.8

99.9

824.3 66.7

1067.9 86.4

970.3 59.6

403.8 23.6403.8 23.6

679.2 79.9

676.9 79.6

462.3

54.4

99.8

10.2

99.8

10.2

656.9 58.0

656.9 58.0

401.9 23.4401.9 23.4

875.9 29.6

1354.1 49.6

1363.2

49.9

663.1 23.5

684.1

24.3

1690.6 39.3

997.6 89.7

997.7 89.7

997.8 89.7

1505.5

78.9

334.9

17.7

335.7

17.7

241.6

13.2

335.5

39.5

324.5

38.2

335.5

39.5

324.5

38.2

882.3 29.8

221.3 58.3110.7 58.3110.7 58.3

444.3

47.3

444.3

47.3

892.5112.5

131.3

7.0

117.9 6.3

131.3

7.0

117.9 6.3

603.7

20.4

577.4 19.5

626.1

64.2

626.0

64.2

Page 513: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 11-Outage: Wilson-Borden #2 230kV MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:01 2008 2013sumpk_q272_pst_v2.sav

MIDWAY523.8

24156VINCENT

MIDWAY227.3

30057DIABLO

528.51.057

GATES529.4

GATES228.6

MORROBAY233.7

TEMPLETN

ARCO225.9

LOSBANOS524.7

30045MOSSLAND

521.31.043

GREGG230.1

HELMS PP233.6

HENRIETA228.3

PANOCHE231.7

HELM231.6

MCMULLN1

HERNDON229.6

LOSBANOS

231.6

COBURN235.2

TESLA524.0

TRACY530.6

METCALF519.2

METCALF232.0

BALCH3TP237.4

PINE FLT236.2

GATES228.6

KEARNEY228.6

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.8

Q128233.7

Q239229.7

Q166229.6

Q194229.4

BORDEN229.4

STOREY 2232.2

STOREY 1227.7

WILSON222.5

WARNERVL228.2

DS AMIGO230.5

MELONES231.6

COTTLE A229.8

COTTLE B228.1

BELLOTA228.6

TESLA E231.0

SN LS PP

TESLA D232.7

TESLA C232.6

Q235SWST232.0

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.8

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.1

142.8

1212.1

62.5

1246.0

65.9

1537.8

58.2

314.4

118.1

315.1

0.6

737.4 65.7

733.4

114.5

356.3 26.4

340.9

70.7

467.7 59.2

298.3

68.3

15.0

5.515.1

18.1

75.6

13.9

76.1

6.8

991.9

108.7

984.8

34.1

481.9

220.0

478.1

160.4

139.3 40.0

393.6

5.2

393.6

5.2

31.8

87.2

256.3 18.0

252.2

41.3

237.9 28.7

50.930.4

50.4 9.5

701.7 6.2

699.3 44.2

881.3

568.9

831.2 0.7

594.5

47.8

594.5

47.8

490.8

35.2

489.2

100.6

1064.4

28.7

61.8

0.8

134.4 7.2

50.832.1

106.0 24.6

184.4 2.7

220.5 32.7

217.6 42.5

240.0 34.9

244.5 18.4

509.0

27.6

541.0

26.2

566.8

30.9

283.7

71.7

293.4 39.5

283.9

71.7

141.0 9.1

143.6

9.0

293.2 39.5

187.7 46.6

194.2 29.6

682.7

43.6

874.1

137.1

860.1

135.3

880.5

146.3

281.7 13.7281.7 13.7

582.4

144.1

605.8

38.0

217.2

18.0

217.2

18.0

425.8

11.2

587.7

145.0

185.4 26.5

95.311.5

94.6

18.6

94.6

18.6

95.311.5

245.5 0.2

82.3

25.5

80.6

25.8

584.0

28.5

542.1

19.3

284.2 84.5

104.2 62.1

220.7 2.1

320.3

49.6

189.8

17.9

683.7

37.4

743.0 97.7

968.1121.3

865.7166.2

146.6 71.9146.6 71.9

273.1 22.9

268.5 42.1

178.5

52.3

39.9

3.1

39.9

3.1

602.7 45.8

602.7 45.8

146.3 72.4146.3 72.4

791.7 62.5

1228.5 0.6

1248.4

82.7

583.5129.5

584.9

170.9

1552.7 42.8

402.2 34.6

402.2 35.0

402.2 34.9

596.2

9.0

133.1

9.3

132.6

10.1

111.9

20.0

126.8

44.8

124.9

42.6

126.8

44.8

124.9

42.6

788.8 76.6

87.110.843.5 5.443.5 5.4

86.2

18.0

86.2

18.0

351.6 45.1

43.5

27.8

43.516.6

43.5

27.8

43.516.6

535.9

143.7

534.0 57.8

250.9

1.0

249.7

7.5

Page 514: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 12-Outage: Wilson-Borden #2 230kV amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:03 2008 2013sumpk_q272_pst_v2.sav

MIDWAY523.8

24156VINCENT

MIDWAY227.3

30057DIABLO

528.51.057

GATES529.4

GATES228.6

MORROBAY233.7

TEMPLETN

ARCO225.9

LOSBANOS524.7

30045MOSSLAND

521.31.043

GREGG230.1

HELMS PP233.6

HENRIETA228.3

PANOCHE231.7

HELM231.6

MCMULLN1

HERNDON229.6

LOSBANOS

231.6

COBURN235.2

TESLA524.0

TRACY530.6

METCALF519.2

METCALF232.0

BALCH3TP237.4

PINE FLT236.2

GATES228.6

KEARNEY228.6

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.8

Q128233.7

Q239229.7

Q166229.6

Q194229.4

BORDEN229.4

STOREY 2232.2

STOREY 1227.7

WILSON222.5

WARNERVL228.2

DS AMIGO230.5

MELONES231.6

COTTLE A229.8

COTTLE B228.1

BELLOTA228.6

TESLA E231.0

SN LS PP

TESLA D232.7

TESLA C232.6

Q235SWST232.0

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.8

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

869.8

29.3

1337.7

0.0

1375.3

0.0

1696.2

0.0

370.2

12.5

343.6

11.6

808.7 27.3

809.5

27.3

882.5 90.5

879.2

90.2

1164.5 67.9

772.9

79.3

40.7

4.360.2

6.4

196.3

20.9

192.9

20.5

1088.1

36.7

1084.2

36.6

583.8

19.7

555.0

18.7

361.1 37.0

987.9

50.6

987.9

50.6

102.2

9.2

640.3 65.7

637.1

65.3

597.0 70.2

147.6 17.4

125.9 14.8

772.2 26.1

776.0 26.2

1141.4

38.5

920.5 31.1

1496.9

66.1

1496.9

66.1

536.6

12.4

549.5

12.7

1161.2

75.9

155.1

8.2

333.2 34.2

152.0 15.6

269.3 30.4

456.7 51.5

555.6 65.4

552.6 65.0

604.4 71.1

607.0 71.4

566.9

35.0

602.3

39.8

631.3

50.6

728.1

41.8

734.0 42.1

728.8

41.8

350.2 41.2

353.1

41.5

733.3 42.1

479.4 56.4

489.5 57.6

752.8

25.4

975.2

78.9

959.7

77.6

983.7

79.5

696.8 37.5696.8 37.5

1524.1

156.1

1526.4

156.3

548.1

56.1

548.1

56.1

1071.0

109.7

1537.7

157.5

471.3 97.5

237.1 24.3

242.2

24.8

242.2

24.8

237.1 24.3

617.0 72.5

216.3

27.3

212.3

26.8

1471.7

185.5

1375.3

161.6

769.3 97.0

314.7 37.0

550.1 64.7

820.3

103.4

481.5

56.7

1707.2

100.4

825.7 66.8

1075.0 87.0

971.2 59.6

407.0 23.7407.0 23.7

682.9 80.3

680.7 80.1

465.9

54.8

99.9

10.2

99.9

10.2

657.7 58.1

657.7 58.1

405.1 23.6405.1 23.6

875.0 29.5

1353.5 49.6

1362.5

49.9

658.5 23.4

679.5

24.1

1690.1 39.3

997.8 89.7

997.9 89.7

997.9 89.7

1506.0

78.9

335.2

17.7

336.0

17.7

287.2

15.6

339.7

40.0

328.8

38.7

339.7

40.0

328.8

38.7

881.3 29.7

222.0 58.5111.0 58.5111.0 58.5

445.6

47.5

445.6

47.5

896.9113.1

129.7

6.9

116.1 6.2

129.7

6.9

116.1 6.2

610.5

20.6

584.5 19.7

630.9

64.7

630.7

64.7

Page 515: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 13-Outage: Dos Amigos-Panoche 230kV and Exchequer MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:04 2008 2013sumpk_q272_pre.sav

MIDWAY524.0

24156VINCENT

MIDWAY227.3

30057DIABLO

528.61.057

GATES529.7

GATES228.8

MORROBAY233.7

TEMPLETN

ARCO226.1

LOSBANOS524.9

30045MOSSLAND

521.71.043

GREGG230.1

HELMS PP233.6

HENRIETA228.4

PANOCHE231.8

HELM231.9

MCMULLN1

HERNDON229.7

LOSBANOS

230.7

COBURN235.2

TESLA524.6

TRACY531.1

METCALF519.6

METCALF232.2

BALCH3TP237.4

PINE FLT236.2

GATES228.8

KEARNEY229.0

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.1

Q128233.7

Q239229.8

Q166229.7

Q194229.4

BORDEN229.2

STOREY 2228.1

STOREY 1228.3

WILSON224.2

WARNERVL228.4

DS AMIGO229.6

MELONES232.0

COTTLE A229.9

COTTLE B228.3

BELLOTA228.7

TESLA E231.3

SN LS PP

TESLA D233.0

TESLA C232.7

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.9

STANDFRD114.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.0

143.6

1211.9

61.5

1245.9

64.8

1537.7

56.8

313.0

121.5

313.7

3.8

737.8 67.5

733.8

116.4

357.9 26.1

342.4

72.0

469.0 58.9

299.8

69.6

12.4

4.612.5

17.3

72.9

14.8

73.4

7.5

975.2

107.6

968.3

30.1

472.0

220.3

468.4

159.4

67.123.6

334.0

7.6

334.0

7.6

124.2

111.4

305.9 8.8

300.0

46.6

284.4 22.3

53.430.2

52.8 9.6

665.4 2.0

663.2 46.1

850.3

572.0

807.9 3.3

594.5

47.9

594.5

47.9

482.6

35.1

481.0

102.3

1037.7

22.5

12.0

3.8

119.8 6.7

26.031.8

106.0 24.6

184.4 2.7

187.6 27.0

185.5 32.0

206.1 28.6

209.4 19.0

502.4

28.7

533.9

27.3

559.4

32.0

281.0

71.5

290.6 40.2

281.3

71.6

143.3 9.9

146.0

9.2

290.4 40.2

192.6 48.3

199.5 29.3

633.3

51.3

871.3

136.6

857.3

134.8

877.6

145.9

281.7 13.6281.7 13.6

581.2

143.5

604.5

37.6

215.9

18.0

215.9

18.0

424.4

11.3

586.5

144.4

185.4 25.9

93.911.3

93.2

18.5

93.2

18.5

93.911.3

245.5 0.1

168.9

20.7

165.5

21.8

348.7

17.9

409.0

0.2

368.9

2.2

313.1

4.6

325.5 72.1

120.8 57.5

236.8 0.2

342.9

49.6

205.3

20.4

607.2

57.5

736.6 97.0

931.3121.7

858.3165.2

135.5 70.4135.5 70.4

90.0

10.3

39.9

3.1

39.9

3.1

600.8 44.5

600.8 44.5

135.2 70.6135.2 70.6

793.7 65.1

1234.2 0.8

1254.2

83.4

608.9131.5

610.5

170.2

1558.6 41.2

402.2 34.4

402.2 34.8

402.2 34.8

596.2

6.1

118.8

10.9

118.4

12.5

37.9

10.5

101.8

42.0

100.5

36.0

101.8

42.0

100.5

36.0

790.8 79.2

95.610.347.8 5.247.8 5.2

94.6

19.2

94.6

19.2

374.3 44.7

56.4

25.0

56.514.0

56.4

25.0

56.514.0

494.8

149.3

493.3 57.2

176.6

0.8

176.0

2.4

Page 516: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 14-Outage: Dos Amigos-Panoche 230kV and Exchequer amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:05 2008 2013sumpk_q272_pre.sav

MIDWAY524.0

24156VINCENT

MIDWAY227.3

30057DIABLO

528.61.057

GATES529.7

GATES228.8

MORROBAY233.7

TEMPLETN

ARCO226.1

LOSBANOS524.9

30045MOSSLAND

521.71.043

GREGG230.1

HELMS PP233.6

HENRIETA228.4

PANOCHE231.8

HELM231.9

MCMULLN1

HERNDON229.7

LOSBANOS

230.7

COBURN235.2

TESLA524.6

TRACY531.1

METCALF519.6

METCALF232.2

BALCH3TP237.4

PINE FLT236.2

GATES228.8

KEARNEY229.0

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.1

Q128233.7

Q239229.8

Q166229.7

Q194229.4

BORDEN229.2

STOREY 2228.1

STOREY 1228.3

WILSON224.2

WARNERVL228.4

DS AMIGO229.6

MELONES232.0

COTTLE A229.9

COTTLE B228.3

BELLOTA228.7

TESLA E231.3

SN LS PP

TESLA D233.0

TESLA C232.7

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.9

STANDFRD114.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

869.5

29.3

1337.0

0.0

1374.6

0.0

1695.4

0.0

370.0

12.5

341.9

11.5

809.2 27.3

809.8

27.3

886.4 90.9

883.0

90.6

1167.6 68.1

776.8

79.7

33.7

3.654.5

5.8

190.0

20.2

186.2

19.8

1069.4

36.1

1065.6

36.0

573.9

19.4

544.2

18.4

177.2 18.2

838.3

42.9

838.3

42.9

183.5

16.6

762.3 78.2

759.8

77.9

710.5 83.6

152.7 17.9

131.8 15.5

731.9 24.7

735.7 24.8

1113.9

37.6

894.1 30.2

1496.7

66.1

1496.7

66.1

527.4

12.2

540.9

12.5

1131.3

74.0

31.6

1.7

297.1 30.5

103.7 10.6

269.3 30.4

456.6 51.5

471.7 55.5

468.9 55.2

517.9 60.9

520.6 61.2

559.1

34.6

594.0

39.3

622.6

49.9

721.2

41.4

727.1 41.7

721.9

41.4

356.0 41.8

359.1

42.2

726.4 41.7

492.0 57.9

502.1 59.1

698.9

23.6

971.7

78.6

956.2

77.3

980.2

79.3

696.8 37.5696.8 37.5

1520.3

155.7

1522.5

155.9

544.6

55.8

544.6

55.8

1067.3

109.3

1533.8

157.1

470.9 97.5

233.7 23.9

238.8

24.5

238.8

24.5

233.7 23.9

616.7 72.5

426.9

53.8

419.0

52.8

879.4

110.9

1030.2

129.9

933.0

109.6

792.3

99.9

858.6108.2

344.5 40.5

589.2 69.3

876.1

110.5

520.7

61.3

1526.0

89.8

817.6 66.2

1033.6 83.7

961.9 59.1

380.1 22.2380.1 22.2

227.8

26.8

100.2

10.3

100.2

10.3

654.9 57.9

654.9 57.9

378.1 22.1378.1 22.1

876.5 29.6

1358.2 49.8

1367.5

50.1

685.6 24.3

705.9

25.1

1694.8 39.4

997.7 89.7

997.8 89.7

997.8 89.7

1504.8

78.9

299.4

15.8

300.5

15.9

99.3

5.4

277.9

32.7

266.0

31.3

277.9

32.7

266.0

31.3

883.0 29.8

243.0 64.1121.5 64.1121.5 64.1

488.0

52.0

488.0

52.0

952.8120.1

154.7

8.2

144.9 7.7

154.7

8.2

144.9 7.7

568.5

19.2

539.8 18.2

443.9

45.5

443.9

45.5

Page 517: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 15-Outage: Dos Amigos-Panoche 230kV and Exchequer MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:07 2008 2013sumpk_q272_pst_v2.sav

MIDWAY524.2

24156VINCENT

MIDWAY227.4

30057DIABLO

528.71.057

GATES530.0

GATES228.9

MORROBAY233.8

TEMPLETN

ARCO226.2

LOSBANOS525.5

30045MOSSLAND

522.01.044

GREGG230.1

HELMS PP233.6

HENRIETA228.5

PANOCHE232.2

HELM232.2

MCMULLN1

HERNDON229.7

LOSBANOS

232.3

COBURN235.4

TESLA524.8

TRACY531.3

METCALF519.8

METCALF232.2

BALCH3TP237.5

PINE FLT236.3

GATES228.9

KEARNEY229.1

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY230.4

Q128233.7

Q239229.8

Q166229.7

Q194229.5

BORDEN229.3

STOREY 2228.2

STOREY 1228.3

WILSON224.2

WARNERVL228.4

DS AMIGO231.2

MELONES232.0

COTTLE A230.0

COTTLE B228.3

BELLOTA228.7

TESLA E231.3

SN LS PP

TESLA D233.0

TESLA C232.8

Q235SWST232.4

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254230.0

STANDFRD114.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.8

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

775.7

144.7

1210.6

60.4

1244.5

63.7

1536.1

55.4

311.6

125.8

312.3

8.0

738.3 69.8

734.3

118.7

357.4 25.6

341.9

72.1

468.6 58.3

299.4

69.7

13.4

4.713.4

17.3

73.9

14.8

74.4

7.6

983.6

113.9

976.6

37.4

477.6

225.9

473.9

165.8

69.025.7

335.1

6.8

335.1

6.8

126.7

78.0

309.0 18.3

303.0

57.0

286.8 31.3

54.029.6

53.4 9.0

669.2 7.1

667.1 50.9

855.1

574.8

811.9 0.5

594.6

48.2

594.6

48.2

486.9

38.0

485.2

99.1

1048.5

25.1

6.5

3.9

119.8 6.4

49.633.5

106.0 24.6

184.4 2.5

189.2 29.1

187.1 34.3

207.7 30.6

211.1 20.7

503.4

29.6

535.0

28.3

560.5

33.0

281.9

71.6

291.5 40.0

282.2

71.7

143.9 9.7

146.6

8.8

291.2 40.0

193.9 47.4

200.9 28.1

639.7

45.0

872.3

138.1

858.3

136.3

878.6

147.3

281.7 13.2281.7 13.2

581.6

144.0

604.9

37.4

216.3

17.9

216.3

17.9

424.9

11.2

586.9

144.9

185.4 25.7

94.411.3

93.7

18.5

93.7

18.5

94.411.3

245.5 0.0

170.5

21.2

167.1

22.3

350.2

18.1

410.7

0.4

370.6

2.3

314.5

4.7

327.6 72.1

121.8 57.5

237.8 0.4

345.0

50.0

206.2

20.9

614.8

34.9

737.3 96.9

937.4123.4

858.6165.1

137.1 69.5137.1 69.5

90.0

10.2

39.9

3.1

39.9

3.1

601.0 44.1

601.0 44.1

136.8 69.8136.8 69.8

792.9 65.4

1233.5 3.3

1253.6

86.2

604.9135.4

606.4

174.5

1558.6 38.0

402.2 34.2

402.2 34.6

402.2 34.6

596.2

4.4

118.8

10.7

118.4

12.2

55.9

12.5

103.7

44.1

102.4

38.4

103.7

44.1

102.4

38.4

790.0 79.7

95.510.547.8 5.247.8 5.2

94.5

19.3

94.5

19.3

376.5 45.0

54.8

23.5

54.912.5

54.8

23.5

54.912.5

500.1

144.3

498.5 52.6

178.5

2.6

177.9

4.3

Page 518: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 16-Outage: Dos Amigos-Panoche 230kV and Exchequer amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:08 2008 2013sumpk_q272_pst_v2.sav

MIDWAY524.2

24156VINCENT

MIDWAY227.4

30057DIABLO

528.71.057

GATES530.0

GATES228.9

MORROBAY233.8

TEMPLETN

ARCO226.2

LOSBANOS525.5

30045MOSSLAND

522.01.044

GREGG230.1

HELMS PP233.6

HENRIETA228.5

PANOCHE232.2

HELM232.2

MCMULLN1

HERNDON229.7

LOSBANOS

232.3

COBURN235.4

TESLA524.8

TRACY531.3

METCALF519.8

METCALF232.2

BALCH3TP237.5

PINE FLT236.3

GATES228.9

KEARNEY229.1

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY230.4

Q128233.7

Q239229.8

Q166229.7

Q194229.5

BORDEN229.3

STOREY 2228.2

STOREY 1228.3

WILSON224.2

WARNERVL228.4

DS AMIGO231.2

MELONES232.0

COTTLE A230.0

COTTLE B228.3

BELLOTA228.7

TESLA E231.3

SN LS PP

TESLA D233.0

TESLA C232.8

Q235SWST232.4

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254230.0

STANDFRD114.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.8

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

869.1

29.3

1334.9

0.0

1372.4

0.0

1692.8

0.0

370.1

12.5

340.3

11.5

809.7 27.3

810.2

27.3

885.0 90.8

881.5

90.4

1166.2 68.0

775.4

79.5

36.0

3.856.0

5.9

192.4

20.4

188.6

20.0

1078.6

36.4

1073.8

36.2

581.8

19.6

551.6

18.6

183.0 18.8

841.0

43.1

841.0

43.1

163.5

14.8

769.7 78.9

766.2

78.6

717.5 84.4

153.0 18.0

132.9 15.6

735.3 24.8

739.9 25.0

1119.6

37.8

898.0 30.3

1496.5

66.1

1496.5

66.1

532.0

12.3

544.1

12.6

1142.5

74.8

19.0

1.0

297.0 30.5

151.2 15.5

269.2 30.4

456.5 51.5

475.9 56.0

472.9 55.6

522.0 61.4

524.9 61.8

560.1

34.7

595.0

39.4

623.7

50.0

723.1

41.5

729.1 41.9

723.8

41.5

357.3 42.0

360.3

42.3

728.4 41.8

494.6 58.2

504.4 59.3

704.6

23.8

972.7

78.7

957.2

77.5

981.2

79.4

696.6 37.5696.6 37.5

1521.2

155.8

1523.4

156.0

545.7

55.9

545.7

55.9

1068.3

109.4

1534.7

157.2

470.8 97.4

234.8 24.0

239.8

24.6

239.8

24.6

234.8 24.0

616.7 72.5

431.0

54.3

423.0

53.3

883.0

111.3

1034.4

130.4

937.2

110.1

795.9

100.3

863.9108.9

346.8 40.8

591.7 69.6

881.5

111.1

523.2

61.6

1530.6

90.0

818.1 66.3

1040.2 84.3

961.9 59.1

382.5 22.3382.5 22.3

226.2

26.6

99.6

10.2

99.6

10.2

654.8 57.9

654.8 57.9

380.6 22.2380.6 22.2

875.3 29.5

1357.1 49.7

1367.0

50.1

681.9 24.2

702.9

25.0

1694.1 39.4

997.6 89.7

997.6 89.7

997.7 89.7

1504.1

78.8

299.2

15.8

300.3

15.9

144.6

7.9

284.3

33.4

271.9

32.0

284.3

33.4

271.9

32.0

881.9 29.8

242.9 64.1121.5 64.1121.5 64.1

487.7

52.0

487.7

52.0

958.2120.8

149.4

8.0

140.1 7.5

149.4

8.0

140.1 7.5

571.9

19.3

544.7 18.4

448.7

46.0

448.5

46.0

Page 519: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 17-Outage: Los Banos-Panoche #2 & Dos Amigos 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:10 2008 2013sumpk_q272_pre.sav

MIDWAY523.6

24156VINCENT

MIDWAY227.1

30057DIABLO

528.41.057

GATES529.1

GATES228.4

MORROBAY233.7

TEMPLETN

ARCO225.8

LOSBANOS524.4

30045MOSSLAND

521.21.042

GREGG230.0

HELMS PP233.6

HENRIETA228.2

PANOCHE231.5

HELM231.8

MCMULLN1

HERNDON229.6

LOSBANOS

231.2

COBURN234.6

TESLA524.3

TRACY530.8

METCALF519.2

METCALF232.0

BALCH3TP237.4

PINE FLT236.2

GATES228.4

KEARNEY228.9

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.3

Q128233.6

Q239229.6

Q166229.5

Q194229.3

BORDEN229.2

STOREY 2228.1

STOREY 1228.3

WILSON224.1

WARNERVL227.9

DS AMIGO229.5

MELONES231.4

COTTLE A229.5

COTTLE B227.8

BELLOTA228.4

TESLA E231.2

SN LS PP

TESLA D232.9

TESLA C232.6

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.7

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.6

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.5

141.6

1213.1

63.8

1247.1

67.2

1539.1

59.9

317.9

114.3

318.6

3.0

736.6 63.5

732.6

112.1

353.8 26.6

338.6

68.9

464.7 59.3

296.2

66.6

19.7

6.619.8

19.1

80.3

12.7

80.8

6.0

1020.7

110.7

1013.2

41.2

498.4

220.5

494.5

163.2

60.820.9

329.4

8.2

329.4

8.2

192.9

93.4

387.9 10.1

378.4

78.0

66.930.2

66.111.7

660.8 3.1

658.7 47.6

858.4

572.5

826.0 4.8

594.5

47.6

594.5

47.6

505.1

35.5

503.3

97.7

1111.8

37.1

27.7

3.4

135.2 7.8

29.230.9

106.0 24.7

184.4 2.9

179.1 23.7

177.2 27.6

197.8 25.8

200.9 17.7

504.2

28.7

535.8

27.4

561.4

32.1

288.7

75.3

298.9 41.3

289.0

75.4

156.1 14.9

159.3

10.3

298.6 41.4

219.1 59.3

228.1 28.0

649.0

52.4

879.3

138.2

865.3

136.3

885.7

147.5

281.7 14.1281.7 14.1

584.7

145.2

608.3

38.7

219.8

18.0

219.8

18.0

428.3

11.0

590.0

146.1

185.4 27.3

97.911.9

97.1

18.6

97.1

18.6

97.911.9

245.5 0.3

165.7

20.6

162.4

21.6

345.8

18.1

405.6

0.5

365.5

2.6

310.2

4.9

364.1 68.0

136.7 55.6

252.2 2.1

366.0

53.9

219.9

27.0

578.4

50.5

740.1 95.0

953.9121.1

857.3162.7

137.5 69.4137.5 69.4

90.5 5.9

90.010.3

39.9

3.1

39.9

3.1

603.6 42.4

603.6 42.4

137.2 69.6137.2 69.6

781.3 68.0

1234.5 0.2

1254.6

82.2

597.7130.7

599.2

170.6

1559.1 42.1

402.2 34.7

402.2 35.1

402.2 35.0

596.2

11.7

133.9

9.8

133.4

10.6

56.7

10.8

71.6

38.6

70.929.3

71.6

38.6

70.9

29.3

778.5 83.5

102.4 11.151.2 5.551.2 5.5

101.2

21.4

101.2

21.4

397.6 48.4

60.0

21.7

60.110.9

60.0

21.7

60.110.9

508.1

150.8

506.5 60.9

170.2

0.9

169.6

0.4

Page 520: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 18-Outage: Los Banos-Panoche #2 & Dos Amigos 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:11 2008 2013sumpk_q272_pre.sav

MIDWAY523.6

24156VINCENT

MIDWAY227.1

30057DIABLO

528.41.057

GATES529.1

GATES228.4

MORROBAY233.7

TEMPLETN

ARCO225.8

LOSBANOS524.4

30045MOSSLAND

521.21.042

GREGG230.0

HELMS PP233.6

HENRIETA228.2

PANOCHE231.5

HELM231.8

MCMULLN1

HERNDON229.6

LOSBANOS

231.2

COBURN234.6

TESLA524.3

TRACY530.8

METCALF519.2

METCALF232.0

BALCH3TP237.4

PINE FLT236.2

GATES228.4

KEARNEY228.9

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.3

Q128233.6

Q239229.6

Q166229.5

Q194229.3

BORDEN229.2

STOREY 2228.1

STOREY 1228.3

WILSON224.1

WARNERVL227.9

DS AMIGO229.5

MELONES231.4

COTTLE A229.5

COTTLE B227.8

BELLOTA228.4

TESLA E231.2

SN LS PP

TESLA D232.9

TESLA C232.6

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.7

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.6

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

870.4

29.4

1339.5

0.0

1377.2

0.0

1698.4

0.0

372.6

12.6

347.7

11.7

807.8 27.3

808.8

27.3

876.5 89.9

873.4

89.6

1157.4 67.5

767.4

78.7

52.9

5.670.4

7.5

207.8

22.1

204.9

21.8

1120.3

37.8

1116.3

37.7

601.0

20.3

573.2

19.3

160.4 16.4

827.0

42.3

827.0

42.3

236.0

21.3

967.8 99.3

964.6

98.9

183.1 21.5

165.1 19.4

727.5 24.5

731.6 24.7

1122.3

37.9

915.0 30.9

1497.0

66.1

1497.0

66.1

552.5

12.8

564.4

13.0

1213.8

79.3

70.0

3.7

335.5 34.4

107.5 11.0

269.4 30.4

456.8 51.5

450.0 52.9

447.4 52.6

496.8 58.5

499.4 58.8

561.5

34.7

596.6

39.4

625.3

50.1

742.6

42.6

748.8 43.0

743.5

42.7

389.0 45.7

392.7

46.1

747.9 42.9

563.2 66.3

573.1 67.4

716.8

24.2

981.6

79.3

965.9

78.1

990.1

80.0

697.0 37.5697.0 37.5

1531.4

156.8

1533.6

157.1

554.8

56.8

554.8

56.8

1077.9

110.4

1544.9

158.2

471.8 97.6

243.6 24.9

248.6

25.5

248.6

25.5

243.6 24.9

617.2 72.5

419.0

52.8

411.2

51.8

872.3

110.0

1021.7

128.8

924.5

108.6

785.2

99.0

954.3120.3

380.1 44.7

629.0 74.0

937.6

118.2

560.0

65.9

1449.6

85.3

821.7 66.5

1058.8 85.7

960.9 59.0

383.5 22.4383.5 22.4

226.2 26.6

227.9 26.8

100.0

10.2

100.0

10.2

658.1 58.1

658.1 58.1

381.5 22.3381.5 22.3

863.6 29.1

1359.4 49.8

1368.5

50.1

673.7 23.9

694.3

24.7

1696.4 39.5

997.8 89.7

997.9 89.7

997.9 89.7

1507.3

79.0

337.5

17.8

338.4

17.9

145.9

7.9

205.6

24.2

191.4

22.5

205.6

24.2

191.4

22.5

870.6 29.4

260.8 68.6130.4 68.6130.4 68.6

523.6

55.8

523.6

55.8

1014.4 127.9

159.9

8.5

152.0 8.1

159.9

8.5

152.0 8.1

583.5

19.7

554.9 18.7

427.9

43.9

427.9

43.9

Page 521: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 19-Outage: Los Banos-Panoche #2 & Dos Amigos 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:13 2008 2013sumpk_q272_pst_v2.sav

MIDWAY523.8

24156VINCENT

MIDWAY227.2

30057DIABLO

528.51.057

GATES529.4

GATES228.5

MORROBAY233.7

TEMPLETN

ARCO225.8

LOSBANOS525.1

30045MOSSLAND

521.51.043

GREGG230.1

HELMS PP233.6

HENRIETA228.3

PANOCHE231.7

HELM232.0

MCMULLN1

HERNDON229.7

LOSBANOS

233.0

COBURN234.7

TESLA524.5

TRACY531.0

METCALF519.4

METCALF232.0

BALCH3TP237.4

PINE FLT236.2

GATES228.5

KEARNEY229.0

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.5

Q128233.7

Q239229.7

Q166229.5

Q194229.3

BORDEN229.2

STOREY 2228.1

STOREY 1228.3

WILSON224.1

WARNERVL228.0

DS AMIGO229.8

MELONES231.4

COTTLE A229.5

COTTLE B227.8

BELLOTA228.5

TESLA E231.3

SN LS PP

TESLA D233.0

TESLA C232.7

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.7

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.3

142.7

1211.8

62.6

1245.7

66.0

1537.4

58.3

316.6

118.8

317.2

1.4

737.1 65.9

733.1

114.6

353.2 26.2

338.1

68.9

464.2 58.9

295.7

66.7

20.7

6.820.8

19.2

81.3

12.7

81.9

6.0

1029.6

118.0

1021.9

49.6

504.2

226.9

500.1

170.5

62.522.4

330.5

7.7

330.5

7.7

196.7

56.2

392.2 22.0

382.5

91.5

67.629.8

66.711.3

664.5 8.8

662.4 53.0

863.2

575.9

830.0 1.9

594.5

47.8

594.5

47.8

509.6

38.9

507.8

94.0

1123.3

40.9

22.2

3.4

135.4 7.6

52.832.4

106.0 24.7

184.4 2.7

180.5 25.1

178.6 29.2

199.2 27.1

202.4 18.8

505.1

29.7

536.9

28.4

562.5

33.2

289.5

75.5

299.8 41.3

289.9

75.5

156.7 14.9

159.9

10.1

299.5 41.3

220.5 59.0

229.6 27.2

655.3

45.7

880.4

139.8

866.3

137.9

886.8

149.1

281.7 13.7281.7 13.7

585.2

145.7

608.8

38.5

220.3

17.9

220.3

17.9

428.8

11.0

590.5

146.6

185.4 27.1

98.411.8

97.6

18.5

97.6

18.5

98.411.8

245.5 0.3

167.3

21.0

164.0

22.0

347.3

18.3

407.4

0.7

367.3

2.7

311.7

5.0

366.3 68.1

137.7 55.6

253.2 2.3

368.2

54.3

220.9

27.6

586.2

25.5

740.8 94.8

960.0123.2

857.6162.4

139.1 68.3139.1 68.3

90.5 5.9

90.010.3

39.9

3.0

39.9

3.0

603.8 41.8

603.8 41.8

138.9 68.6138.9 68.6

780.5 68.7

1233.9 2.9

1254.0

85.2

593.6135.0

595.1

175.3

1559.2 38.7

402.2 34.5

402.2 34.9

402.2 34.9

596.2

10.3

134.0

9.6

133.6

10.3

74.8

12.7

73.2

40.0

72.530.8

73.2

40.0

72.5

30.8

777.7 84.3

102.3 11.351.1 5.751.1 5.7

101.1

21.6

101.1

21.6

399.7 48.8

58.3

19.9

58.4 8.9

58.3

19.9

58.4 8.9

513.3

145.5

511.6 55.9

171.9

0.3

171.4

1.7

Page 522: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 20-Outage: Los Banos-Panoche #2 & Dos Amigos 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:14 2008 2013sumpk_q272_pst_v2.sav

MIDWAY523.8

24156VINCENT

MIDWAY227.2

30057DIABLO

528.51.057

GATES529.4

GATES228.5

MORROBAY233.7

TEMPLETN

ARCO225.8

LOSBANOS525.1

30045MOSSLAND

521.51.043

GREGG230.1

HELMS PP233.6

HENRIETA228.3

PANOCHE231.7

HELM232.0

MCMULLN1

HERNDON229.7

LOSBANOS

233.0

COBURN234.7

TESLA524.5

TRACY531.0

METCALF519.4

METCALF232.0

BALCH3TP237.4

PINE FLT236.2

GATES228.5

KEARNEY229.0

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.5

Q128233.7

Q239229.7

Q166229.5

Q194229.3

BORDEN229.2

STOREY 2228.1

STOREY 1228.3

WILSON224.1

WARNERVL228.0

DS AMIGO229.8

MELONES231.4

COTTLE A229.5

COTTLE B227.8

BELLOTA228.5

TESLA E231.3

SN LS PP

TESLA D233.0

TESLA C232.7

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.7

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

870.0

29.4

1337.4

0.0

1375.0

0.0

1695.8

0.0

372.7

12.6

345.9

11.7

808.3 27.3

809.1

27.3

875.0 89.8

871.8

89.4

1155.9 67.4

766.0

78.6

55.4

5.972.4

7.7

210.3

22.3

207.4

22.0

1130.1

38.1

1124.9

38.0

609.4

20.6

581.0

19.6

165.5 17.0

829.5

42.5

829.5

42.5

224.9

20.4

978.7100.4

974.6

100.0

184.0 21.6

166.5 19.6

730.7 24.7

735.7 24.8

1128.1

38.1

918.9 31.0

1496.8

66.1

1496.8

66.1

557.3

12.9

567.8

13.1

1225.7

80.2

56.5

3.0

335.7 34.4

156.7 16.1

269.3 30.4

456.7 51.5

453.7 53.4

451.0 53.1

500.5 58.9

503.2 59.2

562.5

34.8

597.6

39.5

626.4

50.2

744.6

42.7

750.8 43.1

745.4

42.8

390.5 45.9

394.1

46.3

749.9 43.0

566.2 66.6

576.0 67.8

722.2

24.4

982.6

79.5

966.9

78.2

991.2

80.1

696.9 37.5696.9 37.5

1532.4

156.9

1534.6

157.2

555.9

56.9

555.9

56.9

1079.0

110.5

1545.9

158.3

471.7 97.6

244.8 25.1

249.8

25.6

249.8

25.6

244.8 25.1

617.2 72.5

423.2

53.4

415.3

52.4

876.0

110.4

1026.1

129.4

928.9

109.2

788.9

99.5

959.8121.0

382.6 45.0

631.6 74.3

943.1

118.9

562.5

66.2

1454.2

85.5

822.1 66.6

1065.4 86.3

960.8 59.0

385.7 22.5385.7 22.5

226.0 26.6

227.6 26.8

99.3

10.2

99.3

10.2

658.0 58.1

658.0 58.1

383.8 22.4383.8 22.4

862.5 29.1

1358.3 49.8

1368.0

50.1

670.2 23.8

691.5

24.6

1695.6 39.4

997.7 89.7

997.8 89.7

997.9 89.7

1506.7

79.0

337.7

17.8

338.5

17.9

191.8

10.4

210.7

24.8

196.2

23.1

210.7

24.8

196.2

23.1

869.6 29.3

260.6 68.6130.3 68.6130.3 68.6

523.4

55.8

523.4

55.8

1019.9 128.6

154.3

8.2

147.1 7.8

154.3

8.2

147.1 7.8

586.6

19.8

559.5 18.9

432.2

44.3

432.2

44.3

Page 523: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 21-Outage: Panoche-Los Banos #2 & Dos Amigos 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:16 2008 2013sumpk_q272_pre.sav

MIDWAY523.3

24156VINCENT

MIDWAY227.0

30057DIABLO

528.31.057

GATES528.7

GATES228.3

MORROBAY233.7

TEMPLETN

ARCO225.7

LOSBANOS524.0

30045MOSSLAND

520.91.042

GREGG230.0

HELMS PP233.5

HENRIETA228.1

PANOCHE231.5

HELM231.9

MCMULLN1

HERNDON229.6

LOSBANOS

230.7

COBURN234.5

TESLA524.0

TRACY530.6

METCALF519.0

METCALF231.9

BALCH3TP237.4

PINE FLT236.2

GATES228.3

KEARNEY228.9

30875MC CALL

233.11.014

MOSSLND2

MOSSLND1

WESTLEY230.1

Q128233.6

Q239229.6

Q166229.4

Q194229.2

BORDEN229.1

STOREY 2228.0

STOREY 1228.2

WILSON223.9

WARNERVL227.8

DS AMIGO229.5

MELONES231.2

COTTLE A229.3

COTTLE B227.6

BELLOTA228.3

TESLA E231.1

SN LS PP

TESLA D232.8

TESLA C232.6

Q235SWST232.1

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.6

STANDFRD114.0

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 94 1404 94 1

0.0135.6

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.8

140.3

1213.4

65.2

1247.4

68.7

1539.4

61.8

319.4

109.9

320.1

7.2

736.2 61.0

732.2

109.6

352.5 26.8

337.4

67.9

463.4 59.5

295.1

65.7

22.1

7.222.1

19.6

82.6

12.1

83.2

5.6

1035.0

108.2

1027.2

41.5

506.9

217.5

502.8

161.5

54.220.2

325.6

8.0

325.6

8.0

228.5

103.8

420.8 2.0

409.6

83.8

71.629.8

70.712.0

654.7 0.3

652.6 45.6

854.8

570.3

828.9 6.6

594.5

47.2

594.5

47.2

512.0

34.0

510.2

97.7

1135.0

39.8

29.7

3.4

138.7 8.4

29.930.4

106.0 24.7

184.4 2.9

173.1 23.0

171.4 26.1

192.3 25.0

195.3 17.8

503.4

28.2

535.0

26.8

560.5

31.4

290.8

76.4

301.2 41.7

291.2

76.5

160.4 16.5

163.8

10.3

300.8 41.8

228.3 62.6

238.0 26.7

648.8

55.9

881.9

138.1

867.8

136.2

888.3

147.4

281.7 14.2281.7 14.2

585.8

145.6

609.5

39.2

221.0

18.0

221.0

18.0

429.5

11.0

591.1

146.5

185.4 27.9

99.112.1

98.3

18.7

98.3

18.7

99.112.1

245.5 0.4

168.6

21.2

165.3

22.3

348.5

19.3

408.8

1.9

368.7

3.8

312.8

6.0

369.7 68.3

138.8 55.6

254.2 2.7

368.5

55.1

221.8

28.4

558.3

57.4

741.8 94.6

952.8119.4

859.3162.4

135.8 69.8135.8 69.8

90.0

10.3

39.9

3.1

39.9

3.1

605.6 42.4

605.6 42.4

135.6 70.1135.6 70.1

775.9 67.9

1234.6 0.8

1254.8

80.9

598.6128.3

600.1

168.1

1559.4 43.2

402.2 35.0

402.2 35.4

402.2 35.4

596.2

13.7

137.3

9.8

136.8

10.3

59.4

10.5

59.8

38.2

59.327.9

59.8

38.2

59.3

27.9

773.1 84.0

103.7 11.251.9 5.651.9 5.6

102.5

21.9

102.5

21.9

400.1 49.5

64.2

21.8

64.311.2

64.2

21.8

64.311.2

508.3

153.5

506.6 63.9

163.5

0.7

163.0

0.2

Page 524: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 22-Outage: Panoche-Los Banos #2 & Dos Amigos 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:17 2008 2013sumpk_q272_pre.sav

MIDWAY523.3

24156VINCENT

MIDWAY227.0

30057DIABLO

528.31.057

GATES528.7

GATES228.3

MORROBAY233.7

TEMPLETN

ARCO225.7

LOSBANOS524.0

30045MOSSLAND

520.91.042

GREGG230.0

HELMS PP233.5

HENRIETA228.1

PANOCHE231.5

HELM231.9

MCMULLN1

HERNDON229.6

LOSBANOS

230.7

COBURN234.5

TESLA524.0

TRACY530.6

METCALF519.0

METCALF231.9

BALCH3TP237.4

PINE FLT236.2

GATES228.3

KEARNEY228.9

30875MC CALL

233.11.014

MOSSLND2

MOSSLND1

WESTLEY230.1

Q128233.6

Q239229.6

Q166229.4

Q194229.2

BORDEN229.1

STOREY 2228.0

STOREY 1228.2

WILSON223.9

WARNERVL227.8

DS AMIGO229.5

MELONES231.2

COTTLE A229.3

COTTLE B227.6

BELLOTA228.3

TESLA E231.1

SN LS PP

TESLA D232.8

TESLA C232.6

Q235SWST232.1

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.6

STANDFRD114.0

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 94 1404 94 1

0.0135.6

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

870.8

29.4

1340.6

0.0

1378.3

0.0

1699.7

0.0

372.7

12.6

349.6

11.8

807.3 27.2

808.4

27.3

873.5 89.6

870.4

89.3

1154.3 67.3

764.5

78.4

59.0

6.375.6

8.0

213.6

22.7

210.9

22.4

1136.4

38.3

1132.8

38.2

608.5

20.5

581.9

19.6

144.3 14.8

817.6

41.9

817.6

41.9

276.5

25.0

1049.3 107.6

1046.4 107.3

193.4 22.7

176.5 20.7

721.4 24.3

725.1 24.5

1118.1

37.7

918.8 31.0

1497.3

66.1

1497.3

66.1

560.4

12.9

572.4

13.2

1240.1

81.0

75.1

4.0

344.1 35.3

108.0 11.1

269.4 30.4

456.8 51.6

434.8 51.2

432.3 50.9

482.9 56.8

485.6 57.1

560.9

34.7

595.9

39.4

624.6

50.0

748.6

43.0

754.9 43.3

749.6

43.0

400.4 47.1

404.2

47.5

754.0 43.3

587.6 69.1

597.3 70.3

717.5

24.2

984.8

79.6

969.1

78.3

993.4

80.3

697.1 37.5697.1 37.5

1535.0

157.2

1537.2

157.4

558.0

57.1

558.0

57.1

1081.3

110.7

1548.6

158.6

472.2 97.7

246.7 25.3

251.7

25.8

251.7

25.8

246.7 25.3

617.4 72.6

426.6

53.8

418.7

52.8

879.4

110.9

1030.0

129.9

932.9

109.6

792.3

99.9

969.5122.2

385.6 45.3

634.7 74.7

945.0

119.1

565.5

66.5

1404.7

82.6

823.8 66.6

1057.9 85.6

963.5 59.1

380.5 22.2380.5 22.2

227.9

26.8

100.3

10.3

100.3

10.3

660.6 58.3

660.6 58.3

378.5 22.1378.5 22.1

858.1 29.0

1360.2 49.8

1368.9

50.1

674.4 23.9

694.7

24.7

1697.5 39.5

998.0 89.7

998.1 89.7

998.1 89.7

1508.2

79.1

346.2

18.3

347.0

18.3

152.6

8.3

179.5

21.1

163.5

19.2

179.5

21.1

163.5

19.2

865.1 29.2

264.4 69.5132.2 69.6132.2 69.6

531.0

56.6

531.0

56.6

1021.8 128.8

170.1

9.1

162.6 8.7

170.1

9.1

162.6 8.7

585.0

19.7

555.6 18.7

411.1

42.2

411.1

42.2

Page 525: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 23-Outage: Panoche-Los Banos #2 & Dos Amigos 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:19 2008 2013sumpk_q272_pst_v2.sav

MIDWAY523.5

24156VINCENT

MIDWAY227.1

30057DIABLO

528.41.057

GATES529.1

GATES228.4

MORROBAY233.7

TEMPLETN

ARCO225.7

LOSBANOS524.6

30045MOSSLAND

521.21.042

GREGG230.0

HELMS PP233.5

HENRIETA228.2

PANOCHE231.8

HELM232.0

MCMULLN1

HERNDON229.6

LOSBANOS

232.4

COBURN234.6

TESLA524.3

TRACY530.8

METCALF519.1

METCALF231.9

BALCH3TP237.4

PINE FLT236.2

GATES228.4

KEARNEY228.9

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.4

Q128233.7

Q239229.6

Q166229.4

Q194229.2

BORDEN229.1

STOREY 2228.0

STOREY 1228.2

WILSON223.9

WARNERVL227.8

DS AMIGO231.3

MELONES231.2

COTTLE A229.3

COTTLE B227.6

BELLOTA228.3

TESLA E231.2

SN LS PP

TESLA D232.9

TESLA C232.6

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.7

STANDFRD114.0

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 94 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.5

141.5

1212.1

64.0

1246.1

67.5

1537.8

60.2

318.0

114.4

318.7

2.9

736.6 63.4

732.6

112.1

352.0 26.4

336.9

67.9

462.8 59.0

294.6

65.7

23.1

7.323.1

19.7

83.6

12.1

84.2

5.6

1043.8

115.5

1035.9

49.9

512.6

223.9

508.5

168.8

56.021.6

326.7

7.4

326.7

7.4

232.2

66.5

425.2 13.8

413.8

97.3

72.329.4

71.311.6

658.4 6.1

656.3 51.0

859.6

573.6

832.9 3.7

594.5

47.4

594.5

47.4

516.6

37.4

514.7

94.0

1146.4

43.7

24.3

3.3

138.8 8.1

53.531.9

106.0 24.7

184.4 2.8

174.6 24.4

172.8 27.7

193.8 26.3

196.7 18.9

504.4

29.2

536.0

27.9

561.6

32.6

291.6

76.6

302.1 41.7

292.0

76.7

161.1 16.4

164.5

10.2

301.7 41.7

229.7 62.3

239.5 25.9

655.1

49.1

883.0

139.7

868.8

137.8

889.4

149.0

281.7 13.9281.7 13.9

586.3

146.1

610.0

39.0

221.5

17.9

221.5

17.9

430.0

10.9

591.6

147.0

185.4 27.7

99.612.1

98.8

18.6

98.8

18.6

99.612.1

245.5 0.3

170.2

21.6

166.9

22.7

350.0

19.5

410.5

2.1

370.4

3.9

314.3

6.1

371.8 68.4

139.9 55.6

255.2 3.0

370.7

55.5

222.8

29.0

566.2

32.4

742.5 94.4

958.9121.4

859.6162.1

137.5 68.8137.5 68.8

90.0

10.2

39.9

3.1

39.9

3.1

605.8 41.8

605.8 41.8

137.2 69.0137.2 69.0

775.1 68.6

1234.1 1.8

1254.2

83.9

594.5132.7

596.0

172.9

1559.5 39.8

402.2 34.8

402.2 35.2

402.2 35.2

596.2

12.3

137.4

9.6

136.9

10.1

77.5

12.4

61.4

39.5

60.929.4

61.4

39.5

60.9

29.4

772.3 84.8

103.6 11.551.8 5.751.8 5.7

102.5

22.1

102.5

22.1

402.2 49.9

62.5

20.0

62.7 9.2

62.5

20.0

62.7 9.2

513.4

148.1

511.8 58.9

165.3

0.5

164.7

1.5

Page 526: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 24-Outage: Panoche-Los Banos #2 & Dos Amigos 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:20 2008 2013sumpk_q272_pst_v2.sav

MIDWAY523.5

24156VINCENT

MIDWAY227.1

30057DIABLO

528.41.057

GATES529.1

GATES228.4

MORROBAY233.7

TEMPLETN

ARCO225.7

LOSBANOS524.6

30045MOSSLAND

521.21.042

GREGG230.0

HELMS PP233.5

HENRIETA228.2

PANOCHE231.8

HELM232.0

MCMULLN1

HERNDON229.6

LOSBANOS

232.4

COBURN234.6

TESLA524.3

TRACY530.8

METCALF519.1

METCALF231.9

BALCH3TP237.4

PINE FLT236.2

GATES228.4

KEARNEY228.9

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.4

Q128233.7

Q239229.6

Q166229.4

Q194229.2

BORDEN229.1

STOREY 2228.0

STOREY 1228.2

WILSON223.9

WARNERVL227.8

DS AMIGO231.3

MELONES231.2

COTTLE A229.3

COTTLE B227.6

BELLOTA228.3

TESLA E231.2

SN LS PP

TESLA D232.9

TESLA C232.6

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.7

STANDFRD114.0

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 94 1404 93 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

870.4

29.4

1338.5

0.0

1376.1

0.0

1697.1

0.0

372.7

12.6

347.8

11.7

807.8 27.3

808.8

27.3

872.0 89.4

868.8

89.1

1152.8 67.2

763.0

78.3

61.5

6.577.8

8.3

216.0

23.0

213.4

22.7

1146.0

38.7

1141.3

38.5

616.9

20.8

589.6

19.9

149.4 15.3

820.2

42.0

820.2

42.0

265.8

24.0

1059.6 108.7

1056.0 108.3

194.3 22.8

177.9 20.9

724.5 24.4

729.2 24.6

1124.0

37.9

922.6 31.1

1497.1

66.1

1497.1

66.1

565.1

13.0

575.8

13.3

1251.9

81.8

61.5

3.2

344.3 35.3

157.7 16.2

269.4 30.4

456.7 51.5

438.6 51.6

435.9 51.3

486.7 57.3

489.4 57.6

561.8

34.7

596.9

39.5

625.6

50.1

750.6

43.1

756.9 43.4

751.5

43.1

401.9 47.2

405.6

47.7

756.0 43.4

590.6 69.5

600.2 70.6

722.9

24.4

985.8

79.7

970.1

78.4

994.4

80.4

696.9 37.5696.9 37.5

1536.0

157.3

1538.2

157.5

559.2

57.3

559.2

57.3

1082.4

110.9

1549.6

158.7

472.1 97.7

247.9 25.4

252.9

25.9

252.9

25.9

247.9 25.4

617.3 72.5

430.7

54.3

422.7

53.3

883.1

111.3

1034.4

130.4

937.2

110.1

795.9

100.3

974.9122.9

388.1 45.6

637.3 75.0

950.5

119.8

568.0

66.8

1408.8

82.9

824.2 66.7

1064.5 86.1

963.3 59.1

382.7 22.3382.7 22.3

226.1

26.6

99.5

10.2

99.5

10.2

660.5 58.3

660.5 58.3

380.8 22.2380.8 22.2

856.9 28.9

1359.0 49.8

1368.4

50.1

670.8 23.8

691.8

24.6

1696.7 39.5

997.9 89.7

998.0 89.7

998.0 89.7

1507.6

79.0

346.3

18.3

347.1

18.3

198.5

10.8

184.7

21.7

168.4

19.8

184.7

21.7

168.4

19.8

864.1 29.2

264.3 69.5132.2 69.5132.2 69.5

530.8

56.5

530.8

56.5

1027.3 129.5

164.5

8.8

157.7 8.4

164.5

8.8

157.7 8.4

588.1

19.8

560.3 18.9

415.5

42.6

415.5

42.6

Page 527: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 25-Outage: Los Banos Bus Section 1 MW/MVAR

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:22 2008 2013sumpk_q272_pre.sav

HERNDON117.2

HERNDON229.4

BULLARD114.8

WOODWARD114.8

KERCKHF2116.5

SANGER118.2

MANCHSTR116.0

BARTON116.3

CHLDHOSP115.7

CLOVIS-1116.3

MC CALL120.3

MC CALL233.1

KERCKHF1116.4

KERCKHOF12.93

KERCKHOF6.621

CLOVIS-2116.1

SHARON114.8

CORSGOLD

113.4

OAKHURST

112.4

CHWCHLLA115.3

CERTTEED115.6

LE GRAND115.3

EXCHEQUR120.1

WILSON B115.4

WILSON223.0

DAIRYLND115.6

NEWHALL117.1

MADERAPR117.7

MENDOTA119.0

PANOCHE121.2

HAMMONDS119.3

EL CAPTN113.3

CASTLE113.0

ATWATER112.9

LIVNGSTN111.9

GALLO

111.7

WILSON A115.5

ORO LOMA115.8

EL NIDO114.7

MERCED

114.4

CANTUA119.9

WESTLNDS119.9

KAMM120.4

SCHINDLR119.9

PANOCHE231.6

EXCHEQUR

73.25

EXCHQUER13.80

CHENY121.5

SCHLNDLR72.67

AIRPROD119.3

MALAGA119.2

ULTR.PWR9.024

RANCHRS119.1

SCWAX119.1

PPG

119.2

WST FRSO114.2

DANISHCM114.4

CAL AVE114.0

OXFORD120.6

LUIS_#3120.5

LUIS_#5120.5

JR WOOD112.7

JRWD GEN112.8

CRESSEY112.4

MERCED

MENDOTA74.28

ORO LOMA70.38

PNEDLE115.1

WSTLD1RA120.7

DFS

117.2

PANOCHET

WHD_PAN214.42

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.1

CHOWCOGN

13.80

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.68

AIRWAYS116.5

LASPALMS116.6

P0418120.4

ATWATR JCRESEY T

MALAGATP

KRCDP119.3

KRCDPCT1

KRCDPCT214.49

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

37

1

0

24

1

0

48

1

129 16 1

9518 1

1

7 4

2 3

15

13

1

45 1

49 9 1

29 9 1

50

8

1

13

7

1

50 9 1

50 9 1

075

v

0

9

v

0

9

v

09

v

92

2

26 5

1

10 2

1

3 1

1

3 1

1

4 2

1

19

4

1

1210

1

33 7

1

29 6

2

12 2

1

15 3

2

20

1

27 5

2

4

4

1

38 8

1

26

5

1

26

5

2

37

7

3

52 10

1

44

9

1

38

8

2

27

6

3

45 9

1

45 9

2

43 9

3

3 2

1

43

9

1

53

11

2

45

9

3

7

5

1

10

7

1

10

2

1

14

3

2

14

3

1

20 4

1

26 5

2

33 7

3

13 3

1

15 3

2

17 3

1

4 2

1

38

8

1

39

8

2

9

2

1

3

2

1

26 5

1

23 5

2

23 5

3

6 4

1

5

2

1

29 6

1

4 4

1

13

3

1

11

1

41

ss

2 1

ss

39 8

1

13 3

2

14 12

1

25 5

1

31

1

51 10

2

45 9

3

11

ss

11

ss

19 4

3

31

6

2

41

8

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

69.618.8

71.311.2

31.5 2.1

15.8

11.5

39.9

8.8

91.7

19.6

88.427.1

8.0

4.5

51.610.5

112.1 30.7

162.1 47.2

163.5 37.9

181.8 98.3

176.2 76.9

166.8 50.1

28.6

8.3

96.019.5

3.5

4.6

72.0

18.2

41.7 9.2

48.3

9.3

4.3

3.4

92.524.3

91.6

21.0

12.2

5.3

8.68.0

27.2 8.6

39.0

6.4

58.8

10.3

34.0 4.0

14.4

5.7

10.5

4.7

58.5

16.7

18.6 0.4

3.5

4.7

56.6

12.2

27.2

5.3

7.1

5.0

27.1

19.6

2.8

24.5

6.5

2.1

14.1 6.0

112.1 30.7

42.9 8.6

37.6 6.6

6.33.9

31.814.0

50.321.4

12.8

1.9

47.2

1.0

29.2

8.5

12.2 4.9

26.2 9.5

116.5 30.1

9.111.0

37.7

6.0

92.818.3

114.7 24.4

72.0

14.6

91.913.8

41.7 4.6

57.2

9.8

95.0

3.8

35.5 2.9

29.5

0.0

6.0

3.0

8.71.9

67.0

17.8

109.9

15.2

123.6

18.8

98.7

10.4

97.3 7.1

27.6 3.5

27.6 7.6

9.9

6.9

50.2 0.2

27.3

19.6

129.0 0.0

92.9

2.7

92.9

2.7

50.2 0.2

60.3

7.1

49.1 1.2

44.8

4.9

94.517.7

10.5

5.0

10.5

5.0

50.0

2.4

109.5 17.6

94.226.6

91.3

18.8

13.9 3.4

13.9

3.0

71.9

14.4

71.714.0

303.2

13.2

49.0

6.0

48.8

5.6

66.3

16.4

49.0 6.0

7.27.7

25.0 6.6

31.0

14.031.0

14.0

19.3

3.7

72.0

19.1

73.7

23.3

73.3

21.5

78.123.8

76.0

17.9

94.6 2.9

34.7 2.1

59.5

0.3

111.1 13.3

16.9 8.0

92.8

1.5

14.5

12.4

59.7 5.4

59.4 4.4

9.3

1.9

2.7

1.5

12.0 3.452.1

19.0

40.1

15.7

40.115.7

97.8 8.2

48.9 4.3

48.9 4.3

5.1

14.2

1.8

2.3

98.5

27.5

96.234.1

35.614.6

Page 528: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 26-Outage: Los Banos Bus Section 1 amps/rate

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:24 2008 2013sumpk_q272_pre.sav

HERNDON117.2

HERNDON229.4

BULLARD114.8

WOODWARD114.8

KERCKHF2116.5

SANGER118.2

MANCHSTR116.0

BARTON116.3

CHLDHOSP115.7

CLOVIS-1116.3

MC CALL120.3

MC CALL233.1

KERCKHF1116.4

KERCKHOF12.93

KERCKHOF6.621

CLOVIS-2116.1

SHARON114.8

CORSGOLD

113.4

OAKHURST

112.4

CHWCHLLA115.3

CERTTEED115.6

LE GRAND115.3

EXCHEQUR120.1

WILSON B115.4

WILSON223.0

DAIRYLND115.6

NEWHALL117.1

MADERAPR117.7

MENDOTA119.0

PANOCHE121.2

HAMMONDS119.3

EL CAPTN113.3

CASTLE113.0

ATWATER112.9

LIVNGSTN111.9

GALLO

111.7

WILSON A115.5

ORO LOMA115.8

EL NIDO114.7

MERCED

114.4

CANTUA119.9

WESTLNDS119.9

KAMM120.4

SCHINDLR119.9

PANOCHE231.6

EXCHEQUR

73.25

EXCHQUER13.80

CHENY121.5

SCHLNDLR72.67

AIRPROD119.3

MALAGA119.2

ULTR.PWR9.024

RANCHRS119.1

SCWAX119.1

PPG

119.2

WST FRSO114.2

DANISHCM114.4

CAL AVE114.0

OXFORD120.6

LUIS_#3120.5

LUIS_#5120.5

JR WOOD112.7

JRWD GEN112.8

CRESSEY112.4

MERCED

MENDOTA74.28

ORO LOMA70.38

PNEDLE115.1

WSTLD1RA120.7

DFS

117.2

PANOCHET

WHD_PAN214.42

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.1

CHOWCOGN

13.80

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.68

AIRWAYS116.5

LASPALMS116.6

P0418120.4

ATWATR JCRESEY T

MALAGATP

KRCDP119.3

KRCDPCT1

KRCDPCT214.49

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

37

1

0

24

1

0

48

1

129 16 1

9518 1

1

7 4

2 3

15

13

1

45 1

49 9 1

29 9 1

50

8

1

13

7

1

50 9 1

50 9 1

075

v

0

9

v

0

9

v

09

v

92

2

26 5

1

10 2

1

3 1

1

3 1

1

4 2

1

19

4

1

1210

1

33 7

1

29 6

2

12 2

1

15 3

2

20

1

27 5

2

4

4

1

38 8

1

26

5

1

26

5

2

37

7

3

52 10

1

44

9

1

38

8

2

27

6

3

45 9

1

45 9

2

43 9

3

3 2

1

43

9

1

53

11

2

45

9

3

7

5

1

10

7

1

10

2

1

14

3

2

14

3

1

20 4

1

26 5

2

33 7

3

13 3

1

15 3

2

17 3

1

4 2

1

38

8

1

39

8

2

9

2

1

3

2

1

26 5

1

23 5

2

23 5

3

6 4

1

5

2

1

29 6

1

4 4

1

13

3

1

11

1

41

ss

2 1

ss

39 8

1

13 3

2

14 12

1

25 5

1

31

1

51 10

2

45 9

3

11

ss

11

ss

19 4

3

31

6

2

41

8

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

362.6 37.2

359.6 36.9

156.4 21.0

97.1

8.6

203.8

27.4

464.1

47.7

451.3 40.1

45.5

6.5

261.2 23.2

567.3 50.4

832.1 36.6

826.9 36.2

991.6 44.7

922.4 41.6

835.6 37.5

146.9

13.1

487.3 43.3

28.8

7.3

192.3 23.3

213.6 45.3

248.4

33.7

28.4

8.2

478.2 54.1

479.0

54.2

68.2

9.2

60.2 5.0

146.0 28.5

197.4

20.3

294.1

26.1

167.8 17.2

73.7

14.4

55.1

10.8

304.2

40.9

95.218.6

509.9

13.0

289.8

83.7

141.0

41.3

43.6

12.6

167.5

42.2

123.6

24.1

32.9

6.4

73.610.6

567.3 50.4

209.8 28.2

184.6 24.8

35.659.2

166.8 27.8

262.1 35.5

65.0

8.7

236.2

59.3

156.9

30.6

67.2 9.1

136.2 26.6

577.4 59.3

71.417.9

190.4

37.2

466.2 28.1

577.8 34.9

368.4

49.6

467.0 62.8

210.7 28.4

289.5

80.7

473.7

78.0

169.5 33.1

140.3

27.4

31.9

6.2

42.7 8.3

330.5

41.4

529.9

87.2

595.6

53.0

480.4

79.1

480.7 79.1

140.6 46.4

140.6 47.8

60.6

17.5

251.4 72.6

168.9

42.6

639.4 71.7

461.4

62.1

461.4

62.1

251.4 72.6

303.2

87.5

236.1 49.1

355.3

45.1

4022.1 96.1

57.7

92.9

57.8

11.3

249.0

89.4

541.4 48.1

469.5 41.7

471.3

41.9

72.2 9.7

71.8

9.7

370.1

32.9

370.2 32.9

1455.5

72.8

233.5

45.6

233.5

45.6

331.6

34.0

233.5 88.1

51.214.1

126.8 69.3

174.1

34.0

174.1

34.0

100.6

19.6

192.8 16.1

380.7

39.1

381.2

39.1

391.8 34.8

394.1

35.0

468.3 41.6

172.3 17.7

296.1

26.3

546.1 48.6

92.4 9.5

460.8

41.0

92.3

92.1

290.6 39.3

290.8 39.4

45.8

8.9

15.0

4.3

60.211.8268.3

36.1

208.5 28.1

208.5 28.1

475.6 56.1

237.8 70.2

237.8 70.2

37.6

4.1

7.2

2.0

511.9

100.0

510.2 99.6

192.2 48.5

Page 529: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 27-Outage: Los Banos Bus Section 1 MW/MVAR

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:26 2008 2013sumpk_q272_pst_v2.sav

HERNDON117.2

HERNDON229.3

BULLARD114.8

WOODWARD114.8

KERCKHF2116.5

SANGER118.2

MANCHSTR116.0

BARTON116.3

CHLDHOSP115.7

CLOVIS-1116.3

MC CALL120.3

MC CALL233.1

KERCKHF1116.4

KERCKHOF12.93

KERCKHOF6.620

CLOVIS-2116.1

SHARON114.8

CORSGOLD

113.4

OAKHURST

112.4

CHWCHLLA115.2

CERTTEED115.5

LE GRAND115.3

EXCHEQUR120.1

WILSON B115.4

WILSON222.9

DAIRYLND115.6

NEWHALL117.1

MADERAPR117.7

MENDOTA118.9

PANOCHE121.1

HAMMONDS119.3

EL CAPTN113.3

CASTLE112.9

ATWATER112.8

LIVNGSTN111.8

GALLO

111.7

WILSON A115.4

ORO LOMA115.8

EL NIDO114.6

MERCED

114.3

CANTUA119.9

WESTLNDS119.9

KAMM120.4

SCHINDLR119.9

PANOCHE231.5

EXCHEQUR

73.24

EXCHQUER13.80

CHENY121.4

SCHLNDLR72.65

AIRPROD119.3

MALAGA119.2

ULTR.PWR9.023

RANCHRS119.1

SCWAX119.1

PPG

119.2

WST FRSO114.2

DANISHCM114.3

CAL AVE114.0

OXFORD120.6

LUIS_#3120.5

LUIS_#5120.5

JR WOOD112.7

JRWD GEN112.7

CRESSEY112.3

MERCED

MENDOTA74.26

ORO LOMA70.35

PNEDLE115.1

WSTLD1RA120.6

DFS

117.1

PANOCHET

WHD_PAN214.42

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.1

CHOWCOGN

13.80

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.67

AIRWAYS116.5

LASPALMS116.6

P0418120.4

ATWATR JCRESEY T

MALAGATP

KRCDP119.3

KRCDPCT1

KRCDPCT214.49

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

37

1

0

24

1

0

48

1

129 16 1

9518 1

1

7 4

2 3

15

13

1

45 1

49 9 1

29 9 1

50

8

1

13

7

1

50 9 1

50 9 1

075

v

0

9

v

0

9

v

09

v

92

2

26 5

1

10 2

1

3 1

1

3 1

1

4 2

1

19

4

1

1210

1

33 7

1

29 6

2

12 2

1

15 3

2

20

1

27 5

2

4

4

1

38 8

1

26

5

1

26

5

2

37

7

3

52 10

1

44

9

1

38

8

2

27

6

3

45 9

1

45 9

2

43 9

3

3 2

1

43

9

1

53

11

2

45

9

3

7

5

1

10

7

1

10

2

1

14

3

2

14

3

1

20 4

1

26 5

2

33 7

3

13 3

1

15 3

2

17 3

1

4 2

1

38

8

1

39

8

2

9

2

1

3

2

1

26 5

1

23 5

2

23 5

3

6 4

1

5

2

1

29 6

1

4 4

1

13

3

1

11

1

41

ss

2 1

ss

39 8

1

13 3

2

14 12

1

25 5

1

31

1

51 10

2

45 9

3

11

ss

11

ss

19 4

3

31

6

2

41

8

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

69.718.7

71.211.2

31.3 2.1

15.9

11.5

40.0

8.8

91.8

19.6

88.527.1

7.9

4.5

51.610.5

112.1 30.7

162.3 47.1

163.6 37.8

181.4 98.3

175.7 77.0

166.4 50.0

28.7

8.3

96.019.5

3.5

4.6

71.9

18.1

41.7 9.2

48.3

9.3

4.3

3.4

92.524.3

91.6

21.0

12.2

5.3

8.68.0

27.2 8.6

39.0

6.4

58.7

10.4

34.0 4.0

14.3

5.7

10.4

4.8

58.5

16.7

18.6 0.4

3.5

4.7

56.6

12.2

27.2

5.3

7.1

5.0

27.4

19.7

3.1

24.6

6.6

2.1

14.2 6.1

112.1 30.7

42.9 8.6

37.6 6.5

6.33.9

31.214.0

49.621.4

12.8

1.9

47.1

0.9

29.2

8.5

12.2 4.9

26.2 9.5

116.5 30.1

9.111.0

37.7

6.0

92.818.3

114.7 24.4

72.0

14.6

91.913.8

41.7 4.6

57.4

9.9

95.1

3.9

35.5 3.1

29.6

0.1

5.9

3.0

8.81.9

67.0

17.8

110.0

15.3

123.7

18.9

98.9

10.5

97.5 7.2

27.7 3.5

27.7 7.6

9.9

6.9

50.2 0.3

27.6

19.7

129.0 0.0

93.2

2.8

93.2

2.8

50.2 0.3

60.3

7.2

49.1 1.3

44.8

4.9

94.517.8

10.5

5.0

10.5

5.0

50.0

2.5

109.4 17.7

94.226.6

91.3

18.8

13.9 3.4

13.9

3.0

71.9

14.4

71.714.0

303.2

13.3

49.0

6.2

48.8

5.8

66.3

16.4

49.0 6.2

7.27.7

25.0 6.7

31.0

14.031.0

14.0

19.3

3.7

71.9

19.1

73.8

23.3

73.4

21.4

78.123.8

76.0

17.9

94.5 3.0

34.7 2.1

59.4

0.3

111.0 13.3

16.9 8.0

92.7

1.6

14.5

12.4

59.7 5.5

59.4 4.5

9.3

1.9

2.7

1.5

12.0 3.452.1

18.9

40.1

15.7

40.115.7

97.8 8.3

48.9 4.3

48.9 4.3

5.1

13.8

1.8

2.1

98.7

27.3

96.434.0

35.814.6

Page 530: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 28-Outage: Los Banos Bus Section 1 amps/rate

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:28 2008 2013sumpk_q272_pst_v2.sav

HERNDON117.2

HERNDON229.3

BULLARD114.8

WOODWARD114.8

KERCKHF2116.5

SANGER118.2

MANCHSTR116.0

BARTON116.3

CHLDHOSP115.7

CLOVIS-1116.3

MC CALL120.3

MC CALL233.1

KERCKHF1116.4

KERCKHOF12.93

KERCKHOF6.620

CLOVIS-2116.1

SHARON114.8

CORSGOLD

113.4

OAKHURST

112.4

CHWCHLLA115.2

CERTTEED115.5

LE GRAND115.3

EXCHEQUR120.1

WILSON B115.4

WILSON222.9

DAIRYLND115.6

NEWHALL117.1

MADERAPR117.7

MENDOTA118.9

PANOCHE121.1

HAMMONDS119.3

EL CAPTN113.3

CASTLE112.9

ATWATER112.8

LIVNGSTN111.8

GALLO

111.7

WILSON A115.4

ORO LOMA115.8

EL NIDO114.6

MERCED

114.3

CANTUA119.9

WESTLNDS119.9

KAMM120.4

SCHINDLR119.9

PANOCHE231.5

EXCHEQUR

73.24

EXCHQUER13.80

CHENY121.4

SCHLNDLR72.65

AIRPROD119.3

MALAGA119.2

ULTR.PWR9.023

RANCHRS119.1

SCWAX119.1

PPG

119.2

WST FRSO114.2

DANISHCM114.3

CAL AVE114.0

OXFORD120.6

LUIS_#3120.5

LUIS_#5120.5

JR WOOD112.7

JRWD GEN112.7

CRESSEY112.3

MERCED

MENDOTA74.26

ORO LOMA70.35

PNEDLE115.1

WSTLD1RA120.6

DFS

117.1

PANOCHET

WHD_PAN214.42

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.1

CHOWCOGN

13.80

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.67

AIRWAYS116.5

LASPALMS116.6

P0418120.4

ATWATR JCRESEY T

MALAGATP

KRCDP119.3

KRCDPCT1

KRCDPCT214.49

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

37

1

0

24

1

0

48

1

129 16 1

9518 1

1

7 4

2 3

15

13

1

45 1

49 9 1

29 9 1

50

8

1

13

7

1

50 9 1

50 9 1

075

v

0

9

v

0

9

v

09

v

92

2

26 5

1

10 2

1

3 1

1

3 1

1

4 2

1

19

4

1

1210

1

33 7

1

29 6

2

12 2

1

15 3

2

20

1

27 5

2

4

4

1

38 8

1

26

5

1

26

5

2

37

7

3

52 10

1

44

9

1

38

8

2

27

6

3

45 9

1

45 9

2

43 9

3

3 2

1

43

9

1

53

11

2

45

9

3

7

5

1

10

7

1

10

2

1

14

3

2

14

3

1

20 4

1

26 5

2

33 7

3

13 3

1

15 3

2

17 3

1

4 2

1

38

8

1

39

8

2

9

2

1

3

2

1

26 5

1

23 5

2

23 5

3

6 4

1

5

2

1

29 6

1

4 4

1

13

3

1

11

1

41

ss

2 1

ss

39 8

1

13 3

2

14 12

1

25 5

1

31

1

51 10

2

45 9

3

11

ss

11

ss

19 4

3

31

6

2

41

8

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

363.1 37.3

359.2 36.9

155.5 20.9

97.2

8.6

204.1

27.5

464.5

47.7

451.9 40.2

45.0

6.4

261.3 23.2

567.4 50.5

832.6 36.6

827.6 36.2

989.8 44.6

920.6 41.5

833.7 37.4

147.1

13.1

487.3 43.3

28.8

7.3

192.0 23.3

213.7 45.3

248.5

33.7

28.4

8.2

478.4 54.1

479.2

54.2

68.2

9.2

60.3 5.0

146.1 28.5

197.5

20.3

294.2

26.2

167.8 17.2

73.3

14.3

54.8

10.7

304.4

41.0

95.318.6

509.9

13.0

289.8

83.7

141.1

41.3

43.6

12.6

169.0

42.6

124.2

24.3

33.4

6.5

74.510.7

567.4 50.5

209.9 28.2

184.7 24.9

35.659.2

164.0 27.3

259.1 35.1

65.0

8.7

236.2

59.3

157.0

30.7

67.2 9.1

136.3 26.6

577.5 59.3

71.417.9

190.5

37.2

466.3 28.1

577.9 34.9

368.5

49.6

467.0 62.9

210.7 28.4

290.3

80.9

474.6

78.1

169.6 33.1

140.7

27.5

31.6

6.2

43.2 8.4

330.5

41.4

530.8

87.4

596.5

53.0

481.2

79.2

481.5 79.3

140.8 46.5

140.8 47.8

60.6

17.5

251.4 72.6

170.3

42.9

639.5 71.7

462.9

62.3

462.9

62.3

251.4 72.6

303.3

87.6

236.1 49.1

355.5

45.1

4023.0 96.2

57.7

92.9

57.8

11.3

249.0

89.4

541.2 48.1

469.5 41.8

471.4

41.9

72.2 9.7

71.8

9.7

370.1

32.9

370.2 32.9

1455.6

72.9

233.7

45.6

233.7

45.6

331.6

34.0

233.7 88.1

51.314.1

126.9 69.4

174.2

34.0

174.2

34.0

100.6

19.6

192.6 16.1

381.2

39.1

381.8

39.2

391.8 34.8

394.1

35.0

467.9 41.6

172.3 17.7

295.8

26.3

545.9 48.5

92.5 9.5

460.5

41.0

92.3

92.1

290.7 39.3

290.9 39.4

45.8

8.9

15.0

4.3

60.211.8268.3

36.1

208.6 28.1

208.6 28.1

475.7 56.1

237.8 70.2

237.8 70.2

36.6

4.0

7.0

1.9

513.0

100.2

511.4 99.9

193.7 48.8

Page 531: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 29-Outage: Ashlan Bus MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:29 2008 2013sumpk_q272_pre.sav

MIDWAY523.8

24156VINCENT

MIDWAY227.2

30057DIABLO

528.51.057

GATES529.3

GATES228.5

MORROBAY233.7

TEMPLETN

ARCO225.9

LOSBANOS524.6

30045MOSSLAND

521.21.042

GREGG229.8

HELMS PP233.4

HENRIETA228.1

PANOCHE231.7

HELM231.6

MCMULLN1

HERNDON229.4

LOSBANOS

231.5

COBURN235.1

TESLA523.9

TRACY530.5

METCALF519.0

METCALF231.9

BALCH3TP237.4

PINE FLT236.2

GATES228.5

KEARNEY228.5

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.7

Q128233.7

Q239229.7

Q166229.6

Q194229.4

BORDEN228.9

STOREY 2227.7

STOREY 1227.8

WILSON223.3

WARNERVL227.1

DS AMIGO230.5

MELONES230.7

COTTLE A228.9

COTTLE B227.0

BELLOTA228.0

TESLA E230.9

SN LS PP

TESLA D232.6

TESLA C232.6

Q235SWST232.0

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.8

STANDFRD113.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 95 1404 95 1404 95 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.4

142.5

1213.5

62.6

1247.5

66.0

1539.6

58.4

316.6

117.3

317.2

0.2

737.0 65.2

733.0

114.0

356.2 26.6

340.8

70.5

467.5 59.3

298.3

68.1

15.2

5.615.2

18.2

75.7

13.8

76.2

6.7

990.5

108.1

983.4

33.3

480.2

219.3

476.5

159.6

136.3 40.5

349.2

6.4

349.2

6.4

16.9

87.7

258.3 17.6

254.1

41.5

239.7 28.5

52.830.3

52.3 9.7

707.2 7.1

704.7 44.2

900.9

571.4

837.4 0.4

594.5

45.7

594.5

45.7

490.1

34.9

488.4

100.9

1064.8

29.2

68.4

2.4

138.1 7.2

28.230.5

106.0 24.7

184.4 2.8

220.7 32.6

217.8 42.4

238.5 34.7

243.0 18.4

513.5

27.3

545.7

25.8

571.8

30.5

285.9

72.5

295.8 39.6

286.1

72.6

142.8 9.7

145.4

9.0

295.5 39.6

191.5 47.9

198.2 29.4

686.7

42.8

874.3

136.9

860.3

135.1

880.6

146.2

281.7 13.9281.7 13.9

582.5

144.1

605.9

38.1

217.3

18.0

217.3

18.0

425.9

11.2

587.8

145.0

185.4 26.6

95.411.5

94.7

18.6

94.7

18.6

95.411.5

245.5 0.2

186.3

21.9

182.7

23.1

363.6

22.1

426.7

5.0

386.4

5.9

327.9

8.1

377.2 66.7

143.4 55.6

258.6 4.2

379.3

60.7

226.0

31.5

680.0

37.8

735.7 97.2

1001.8 122.8

844.4165.8

153.3 71.0153.3 71.0

275.0 22.6

270.3 42.2

180.3

52.4

39.9

3.1

39.9

3.1

594.7 45.1

594.7 45.1

153.0 71.7153.0 71.7

799.7 62.9

1231.7 1.1

1251.7

81.2

569.9130.9

571.3

173.6

1554.7 44.6

402.2 36.1

402.2 36.5

402.2 36.4

596.2

9.6

136.8

8.8

136.3

9.4

96.0

19.9

121.1

44.5

119.4

41.3

121.1

44.5

119.4

41.3

796.8 76.0

101.8 7.550.9 3.850.9 3.8

100.7

17.7

100.7

17.7

410.9 54.9

35.6

28.8

35.617.3

35.6

28.8

35.617.3

537.5

144.0

535.7 58.4

247.9

2.2

246.7

8.5

Page 532: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 30-Outage: Ashlan Bus amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:31 2008 2013sumpk_q272_pre.sav

MIDWAY523.8

24156VINCENT

MIDWAY227.2

30057DIABLO

528.51.057

GATES529.3

GATES228.5

MORROBAY233.7

TEMPLETN

ARCO225.9

LOSBANOS524.6

30045MOSSLAND

521.21.042

GREGG229.8

HELMS PP233.4

HENRIETA228.1

PANOCHE231.7

HELM231.6

MCMULLN1

HERNDON229.4

LOSBANOS

231.5

COBURN235.1

TESLA523.9

TRACY530.5

METCALF519.0

METCALF231.9

BALCH3TP237.4

PINE FLT236.2

GATES228.5

KEARNEY228.5

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.7

Q128233.7

Q239229.7

Q166229.6

Q194229.4

BORDEN228.9

STOREY 2227.7

STOREY 1227.8

WILSON223.3

WARNERVL227.1

DS AMIGO230.5

MELONES230.7

COTTLE A228.9

COTTLE B227.0

BELLOTA228.0

TESLA E230.9

SN LS PP

TESLA D232.6

TESLA C232.6

Q235SWST232.0

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.8

STANDFRD113.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 95 1404 95 1404 95 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

870.1

29.4

1339.4

0.0

1377.1

0.0

1698.4

0.0

372.1

12.6

346.0

11.7

808.2 27.3

809.1

27.3

882.5 90.5

879.2

90.2

1164.2 67.9

773.0

79.3

41.1

4.460.6

6.4

196.6

20.9

193.2

20.5

1086.7

36.7

1082.9

36.5

581.9

19.6

553.0

18.7

354.4 36.4

877.6

44.9

877.6

44.9

98.3

8.9

645.3 66.2

642.0

65.9

601.7 70.8

151.7 17.8

130.5 15.3

778.3 26.3

782.2 26.4

1161.0

39.2

927.7 31.3

1498.3

66.2

1498.3

66.2

535.9

12.4

548.9

12.7

1161.8

76.0

172.0

9.1

342.5 35.1

105.2 10.8

269.4 30.4

456.7 51.5

556.0 65.4

552.9 65.1

600.8 70.7

603.4 71.0

572.0

35.3

607.7

40.2

637.0

51.0

734.1

42.1

740.0 42.5

734.8

42.2

354.9 41.7

357.9

42.1

739.3 42.4

489.4 57.6

499.5 58.8

757.2

25.5

975.5

78.9

959.9

77.6

984.0

79.6

696.9 37.5696.9 37.5

1524.5

156.1

1526.8

156.4

548.5

56.2

548.5

56.2

1071.4

109.7

1538.1

157.5

471.4 97.5

237.4 24.3

242.5

24.8

242.5

24.8

237.4 24.3

617.0 72.5

471.4

59.4

462.6

58.3

919.0

115.9

1076.5

135.7

979.4

115.1

831.7

104.8

990.3124.8

397.7 46.7

647.3 76.2

977.0

123.2

577.8

68.0

1698.3

99.9

817.8 66.1

1112.3 90.0

948.3 58.2

421.1 24.6421.1 24.6

687.6 80.9

685.5 80.6

470.5

55.4

99.9

10.2

99.9

10.2

649.1 57.3

649.1 57.3

419.3 24.5419.3 24.5

884.0 29.8

1357.4 49.7

1366.2

50.0

644.4 22.9

666.2

23.7

1692.6 39.4

998.6 89.7

998.7 89.7

998.8 89.7

1506.3

79.0

344.3

18.2

345.1

18.2

247.7

13.5

326.0

38.4

314.8

37.0

326.0

38.4

314.8

37.0

890.3 30.0

259.6 68.1129.8 68.1129.8 68.1

521.5

55.5

521.5

55.5

1053.9 132.9

115.0

6.1

98.7 5.3

115.0

6.1

98.7 5.3

612.4

20.7

586.4 19.8

624.0

64.0

623.8

64.0

Page 533: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 31-Outage: Ashlan Bus MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:33 2008 2013sumpk_q272_pst_v2.sav

MIDWAY523.6

24156VINCENT

MIDWAY227.2

30057DIABLO

528.41.057

GATES529.2

GATES228.5

MORROBAY233.7

TEMPLETN

ARCO225.8

LOSBANOS524.3

30045MOSSLAND

520.91.042

GREGG229.8

HELMS PP233.4

HENRIETA228.2

PANOCHE231.6

HELM231.5

MCMULLN1

HERNDON229.3

LOSBANOS

231.4

COBURN235.0

TESLA523.6

TRACY530.2

METCALF518.8

METCALF231.8

BALCH3TP237.4

PINE FLT236.2

GATES228.5

KEARNEY228.4

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.6

Q128233.6

Q239229.7

Q166229.5

Q194229.3

BORDEN228.8

STOREY 2227.7

STOREY 1227.8

WILSON223.3

WARNERVL227.3

DS AMIGO230.3

MELONES230.7

COTTLE A228.8

COTTLE B227.2

BELLOTA228.0

TESLA E230.8

SN LS PP

TESLA D232.5

TESLA C232.5

Q235SWST231.9

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.7

STANDFRD113.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 95 1404 95 1404 95 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

776.3

141.9

1212.3

63.5

1246.3

66.9

1538.1

59.5

315.2

114.8

315.9

2.6

737.1 63.9

733.1

112.7

355.7 26.7

340.3

70.0

467.0 59.5

297.8

67.7

16.1

5.816.2

18.4

76.7

13.5

77.2

6.5

998.5

106.4

991.2

33.2

485.7

217.5

482.0

158.4

137.7 40.5

350.0

6.5

350.0

6.5

16.2

87.7

259.7 17.3

255.4

41.5

241.0 28.2

53.530.4

52.9 9.8

711.5 7.1

709.1 43.3

905.3

570.5

841.7 0.3

594.5

45.6

594.5

45.6

494.0

33.9

492.3

101.1

1075.2

30.2

62.5

2.1

138.0 7.5

51.831.4

106.0 24.7

184.4 2.8

221.9 32.5

219.0 42.4

239.8 34.6

244.4 18.1

514.4

27.1

546.7

25.6

572.8

30.3

286.8

72.5

296.8 39.3

287.1

72.6

143.4 9.9

146.1

9.1

296.5 39.3

192.8 48.5

199.7 29.3

694.1

41.9

875.3

136.8

861.3

135.0

881.7

146.1

281.7 14.0281.7 14.0

583.0

144.2

606.4

38.3

217.8

18.0

217.8

18.0

426.4

11.1

588.2

145.1

185.4 26.8

95.911.6

95.2

18.6

95.2

18.6

95.911.6

245.5 0.2

188.5

21.7

184.8

22.9

365.6

22.0

429.0

4.9

388.8

5.6

329.8

8.0

380.3 69.1

144.6 55.5

259.7 4.3

381.6

57.5

227.0

32.0

683.3

38.2

736.7 96.7

1007.7 123.0

845.2165.1

154.7 71.0154.7 71.0

276.3 22.3

271.6 42.2

181.6

52.4

39.9

3.1

39.9

3.1

595.3 44.8

595.3 44.8

154.4 71.7154.4 71.7

798.5 62.5

1230.7 0.9

1250.7

81.1

565.7130.5

567.1

173.6

1554.1 44.2

402.2 36.1

402.2 36.5

402.2 36.5

596.2

10.6

136.6

9.1

136.2

9.6

113.7

20.8

122.9

44.5

121.1

41.7

122.9

44.5

121.1

41.7

795.6 75.6

102.1 11.651.1 5.851.1 5.8

101.0

21.9

101.0

21.9

413.2 51.7

34.8

28.7

34.817.2

34.8

28.7

34.817.2

543.7

143.4

541.8 58.9

249.3

1.8

248.1

8.2

Page 534: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 32-Outage: Ashlan Bus amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:34 2008 2013sumpk_q272_pst_v2.sav

MIDWAY523.6

24156VINCENT

MIDWAY227.2

30057DIABLO

528.41.057

GATES529.2

GATES228.5

MORROBAY233.7

TEMPLETN

ARCO225.8

LOSBANOS524.3

30045MOSSLAND

520.91.042

GREGG229.8

HELMS PP233.4

HENRIETA228.2

PANOCHE231.6

HELM231.5

MCMULLN1

HERNDON229.3

LOSBANOS

231.4

COBURN235.0

TESLA523.6

TRACY530.2

METCALF518.8

METCALF231.8

BALCH3TP237.4

PINE FLT236.2

GATES228.5

KEARNEY228.4

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.6

Q128233.6

Q239229.7

Q166229.5

Q194229.3

BORDEN228.8

STOREY 2227.7

STOREY 1227.8

WILSON223.3

WARNERVL227.3

DS AMIGO230.3

MELONES230.7

COTTLE A228.8

COTTLE B227.2

BELLOTA228.0

TESLA E230.8

SN LS PP

TESLA D232.5

TESLA C232.5

Q235SWST231.9

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.7

STANDFRD113.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 95 1404 95 1404 95 1

0.0135.7

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

870.1

29.4

1338.5

0.0

1376.1

0.0

1697.1

0.0

369.9

12.5

344.7

11.6

808.3 27.3

809.3

27.3

881.1 90.4

877.9

90.0

1163.0 67.8

771.6

79.1

43.6

4.662.7

6.7

198.9

21.1

195.7

20.8

1095.5

37.0

1092.1

36.8

586.8

19.8

558.7

18.8

357.8 36.7

879.6

45.0

879.6

45.0

98.2

8.9

648.9 66.6

645.7

66.2

605.0 71.2

153.3 18.0

132.2 15.5

783.5 26.4

787.3 26.6

1165.1

39.3

932.8 31.5

1498.3

66.2

1498.3

66.2

540.3

12.5

553.4

12.8

1173.6

76.7

157.2

8.3

342.3 35.1

153.3 15.7

269.4 30.4

456.7 51.5

559.1 65.8

556.1 65.4

604.1 71.1

606.7 71.4

573.3

35.4

609.1

40.2

638.4

51.1

736.7

42.3

742.6 42.6

737.4

42.3

356.6 41.9

359.6

42.3

741.9 42.6

493.0 58.0

503.1 59.2

765.7

25.8

976.8

79.0

961.2

77.7

985.3

79.7

697.0 37.5697.0 37.5

1526.0

156.3

1528.2

156.5

549.8

56.3

549.8

56.3

1072.7

109.9

1539.6

157.7

471.5 97.6

238.7 24.4

243.8

25.0

243.8

25.0

238.7 24.4

617.1 72.5

476.8

60.1

468.0

59.0

924.1

116.5

1082.5

136.5

985.3

115.8

836.7

105.5

999.3126.0

400.3 47.0

650.1 76.5

980.6

123.6

580.6

68.3

1707.6

100.5

819.3 66.2

1119.4 90.5

949.6 58.2

424.4 24.8424.4 24.8

691.1 81.3

689.0 81.1

473.8

55.7

100.0

10.2

100.0

10.2

650.0 57.3

650.0 57.3

422.6 24.7422.6 24.7

883.1 29.8

1357.0 49.7

1365.8

50.0

640.2 22.7

662.0

23.5

1692.9 39.4

998.7 89.7

998.8 89.7

998.8 89.7

1506.8

79.0

344.1

18.2

344.9

18.2

292.0

15.9

330.3

38.9

319.3

37.6

330.3

38.9

319.3

37.6

889.4 30.0

261.1 68.5130.5 68.5130.5 68.5

524.2

55.8

524.2

55.8

1057.5 133.3

113.3

6.0

96.9 5.2

113.3

6.0

96.9 5.2

619.1

20.9

593.4 20.0

627.5

64.4

627.4

64.4

Page 535: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 33-Outage: Gates 230kV Bus 1E MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:36 2008 2013sumpk_q272_pre.sav

MIDWAY524.0

24156VINCENT

MIDWAY227.3

30057DIABLO

528.71.057

GATES529.9

GATES229.1

MORROBAY233.8

TEMPLETN

ARCO221.7

LOSBANOS525.0

30045MOSSLAND

521.71.043

GREGG230.0

HELMS PP233.6

HENRIETA227.7

PANOCHE231.7

HELM231.7

MCMULLN1

HERNDON229.6

LOSBANOS

230.7

COBURN235.3

TESLA524.5

TRACY531.1

METCALF519.6

METCALF232.1

BALCH3TP237.4

PINE FLT236.3

GATES229.1

KEARNEY228.8

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.9

Q128233.7

Q239229.8

Q166229.6

Q194229.4

BORDEN229.3

STOREY 2228.2

STOREY 1228.4

WILSON224.6

WARNERVL228.3

DS AMIGO230.0

MELONES231.9

COTTLE A229.7

COTTLE B228.1

BELLOTA228.6

TESLA E231.1

SN LS PP

TESLA D232.9

TESLA C232.7

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254230.2

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.8

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

778.6

144.1

1211.2

61.3

1245.2

64.7

1536.8

56.6

343.8

124.4

344.6

7.7

732.4 70.0

728.5

117.5

356.5 24.6

341.1

72.4

467.7 57.4

298.5

70.0

61.0

22.260.5

31.9

948.7

105.4

942.2

23.6

443.6

220.6

440.4

156.2

101.7 30.8

355.4

6.3

355.4

6.3

25.7

114.7

246.8 10.6

242.9

31.3

229.3 21.5

47.930.5

47.4 9.2

681.1 4.4

678.9 46.1

869.4

573.0

810.4 1.2

594.5

47.7

594.5

47.7

469.5

34.6

468.0

105.0

1034.4

14.8

16.4

12.4

128.4 5.0

16.525.5

106.0 24.6

184.4 2.5

211.4 30.6

208.7 39.0

228.6 32.5

232.7 18.4

506.4

28.5

538.2

27.1

563.9

31.9

279.7

70.4

289.2 39.5

280.0

70.5

138.1 8.3

140.6

8.9

288.9 39.5

181.7 44.7

187.8 30.2

642.6

47.3

849.0

137.3

835.4

135.5

855.1

146.4

281.7 13.3281.7 13.3

582.4

143.9

605.7

38.1

217.2

18.3

217.2

18.3

425.7

11.5

587.6

144.8

185.4 26.2

95.211.8

94.5

18.8

94.5

18.8

95.211.8

245.5 0.1

161.2

17.8

158.0

18.8

341.5

15.1

400.5

2.9

360.5

0.5

305.9

2.2

349.2 67.1

131.2 55.4

246.9 0.3

360.4

51.0

214.9

23.5

655.7

55.9

731.2 97.9

953.5123.3

846.5166.3

143.2 70.7143.2 70.7

264.5 15.5

260.3 33.0

170.3

43.3

39.9

3.1

39.9

3.1

593.6 45.3

593.6 45.3

142.9 71.1142.9 71.1

804.1 64.1

1233.5 0.4

1253.6

83.1

596.7132.3

598.3

172.3

1557.1 42.1

402.2 34.6

402.2 35.0

402.2 35.0

596.2

1.3

127.2

8.1

126.8

9.2

121.5

41.4

119.7

38.1

121.5

41.4

119.7

38.1

801.1 76.9

98.110.349.1 5.149.1 5.1

97.1

19.6

97.1

19.6

391.9 45.7

42.9

28.1

43.016.9

42.9

28.1

43.016.9

501.2

146.7

499.6 55.4

212.0

1.4

211.2

5.2

Page 536: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 34-Outage: Gates 230kV Bus 1E amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:37 2008 2013sumpk_q272_pre.sav

MIDWAY524.0

24156VINCENT

MIDWAY227.3

30057DIABLO

528.71.057

GATES529.9

GATES229.1

MORROBAY233.8

TEMPLETN

ARCO221.7

LOSBANOS525.0

30045MOSSLAND

521.71.043

GREGG230.0

HELMS PP233.6

HENRIETA227.7

PANOCHE231.7

HELM231.7

MCMULLN1

HERNDON229.6

LOSBANOS

230.7

COBURN235.3

TESLA524.5

TRACY531.1

METCALF519.6

METCALF232.1

BALCH3TP237.4

PINE FLT236.3

GATES229.1

KEARNEY228.8

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY229.9

Q128233.7

Q239229.8

Q166229.6

Q194229.4

BORDEN229.3

STOREY 2228.2

STOREY 1228.4

WILSON224.6

WARNERVL228.3

DS AMIGO230.0

MELONES231.9

COTTLE A229.7

COTTLE B228.1

BELLOTA228.6

TESLA E231.1

SN LS PP

TESLA D232.9

TESLA C232.7

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254230.2

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.8

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

872.4

29.4

1336.2

0.0

1373.7

0.0

1694.3

0.0

402.8

13.6

375.5

12.7

803.5 27.1

803.9

27.1

882.4 90.5

878.8

90.1

1163.6 67.9

772.7

79.3

164.8

17.5178.0

18.9

1040.0

35.1

1036.4

35.0

545.8

18.4

513.8

17.3

264.7 27.1

892.0

45.7

892.0

45.7

129.3

11.7

615.5 63.1

613.1

62.9

573.9 67.5

141.4 16.6

118.5 13.9

749.0 25.3

752.9 25.4

1132.0

38.2

896.7 30.3

1496.9

66.1

1496.9

66.1

512.9

11.8

527.4

12.2

1127.0

73.8

51.7

2.7

318.0 32.6

77.1 7.9

269.2 30.4

456.6 51.5

532.0 62.6

529.1 62.3

575.1 67.7

577.7 68.0

563.5

34.9

598.7

39.6

627.6

50.3

717.4

41.2

723.2 41.5

718.0

41.2

342.8 40.3

345.7

40.6

722.6 41.5

463.6 54.6

474.0 55.8

708.5

23.9

947.5

76.7

932.4

75.4

955.8

77.3

696.7 37.5696.7 37.5

1523.8

156.1

1526.0

156.3

548.0

56.1

548.0

56.1

1070.7

109.7

1537.3

157.4

471.1 97.5

236.9 24.3

242.1

24.8

242.1

24.8

236.9 24.3

616.8 72.5

406.9

51.3

399.4

50.4

860.8

108.5

1008.5

127.1

911.1

107.1

773.9

97.6

914.1115.2

366.1 43.0

614.8 72.3

921.0

116.1

546.0

64.2

1647.1

96.9

812.0 65.8

1058.2 85.7

949.6 58.3

397.7 23.2397.7 23.2

660.3 77.7

658.6 77.5

441.0

51.9

100.3

10.3

100.3

10.3

647.2 57.2

647.2 57.2

395.8 23.1395.8 23.1

887.9 30.0

1357.8 49.7

1366.9

50.1

672.8 23.9

693.7

24.6

1693.4 39.4

997.8 89.7

997.9 89.7

997.9 89.7

1502.8

78.8

319.6

16.9

320.3

16.9

323.4

38.0

313.0

36.8

323.4

38.0

313.0

36.8

894.2 30.2

249.5 65.8124.8 65.8124.8 65.8

501.1

53.4

501.1

53.4

997.8125.8

128.8

6.9

114.9 6.1

128.8

6.9

114.9 6.1

574.2

19.4

546.4 18.4

533.1

54.7

533.0

54.7

Page 537: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 35-Outage: Gates 230kV Bus 1E MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:39 2008 2013sumpk_q272_pst_v2.sav

MIDWAY524.3

24156VINCENT

MIDWAY227.4

30057DIABLO

528.81.058

GATES530.3

GATES229.2

MORROBAY233.8

TEMPLETN

ARCO221.8

LOSBANOS525.6

30045MOSSLAND

522.01.044

GREGG230.0

HELMS PP233.6

HENRIETA227.8

PANOCHE232.1

HELM232.0

MCMULLN1

HERNDON229.6

LOSBANOS

232.1

COBURN235.5

TESLA524.6

TRACY531.2

METCALF519.7

METCALF232.2

BALCH3TP237.5

PINE FLT236.3

GATES229.2

KEARNEY228.9

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY230.1

Q128233.8

Q239229.8

Q166229.7

Q194229.4

BORDEN229.2

STOREY 2228.2

STOREY 1228.4

WILSON224.4

WARNERVL228.2

DS AMIGO231.0

MELONES231.7

COTTLE A229.7

COTTLE B228.0

BELLOTA228.5

TESLA E231.2

SN LS PP

TESLA D232.9

TESLA C232.7

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254230.3

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.8

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

778.4

145.2

1209.8

60.2

1243.7

63.5

1535.1

55.1

342.1

128.9

342.9

12.1

732.9 72.4

729.0

119.9

356.3 24.0

340.9

72.8

467.5 56.8

298.3

70.4

61.0

22.260.5

32.0

953.5

110.8

946.9

29.4

447.0

225.8

443.7

161.8

108.6 34.8

360.6

4.8

360.6

4.8

25.2

84.7

249.8 18.6

245.9

40.0

231.8 29.0

48.729.7

48.2 8.4

683.7 9.3

681.4 50.7

873.8

575.6

813.7 1.6

594.5

47.6

594.5

47.6

472.0

37.1

470.4

102.4

1039.3

16.0

36.0

14.1

132.8 4.5

36.126.5

106.0 24.5

184.4 2.3

215.1 33.5

212.4 42.4

232.6 35.3

236.8 20.4

507.2

29.4

539.1

28.0

564.8

32.8

280.6

70.5

290.1 39.3

280.8

70.5

138.9 7.9

141.4

8.5

289.8 39.3

183.5 43.7

189.6 28.7

647.2

41.1

849.3

138.6

835.7

136.7

855.4

147.7

281.7 12.9281.7 12.9

582.5

144.2

605.9

37.8

217.3

18.2

217.3

18.2

425.8

11.5

587.8

145.1

185.4 25.9

95.411.7

94.7

18.8

94.7

18.8

95.411.7

245.5 0.1

165.7

18.4

162.4

19.5

345.5

15.9

405.2

2.0

365.1

0.1

309.9

2.8

354.3 67.4

133.5 55.4

249.1 1.0

364.3

52.1

217.0

24.9

663.0

34.9

731.4 98.0

959.2124.9

845.9166.5

144.8 69.9144.8 69.9

266.9 23.2

262.6 41.1

172.6

51.3

39.9

3.1

39.9

3.1

593.3 45.1

593.3 45.1

144.5 70.4144.5 70.4

803.5 64.2

1233.0 2.8

1253.1

85.7

593.0136.1

594.5

176.5

1557.2 39.1

402.2 34.7

402.2 35.1

402.2 35.0

596.2

0.8

131.5

7.0

131.1

7.9

120.9

43.4

119.1

40.1

120.9

43.4

119.1

40.1

800.6 77.1

98.510.649.3 5.349.3 5.3

97.5

20.0

97.5

20.0

395.9 46.7

41.0

27.1

41.115.7

41.0

27.1

41.115.7

504.9

141.7

503.3 50.5

219.2

3.8

218.2

8.0

Page 538: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 36-Outage: Gates 230kV Bus 1E amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:40 2008 2013sumpk_q272_pst_v2.sav

MIDWAY524.3

24156VINCENT

MIDWAY227.4

30057DIABLO

528.81.058

GATES530.3

GATES229.2

MORROBAY233.8

TEMPLETN

ARCO221.8

LOSBANOS525.6

30045MOSSLAND

522.01.044

GREGG230.0

HELMS PP233.6

HENRIETA227.8

PANOCHE232.1

HELM232.0

MCMULLN1

HERNDON229.6

LOSBANOS

232.1

COBURN235.5

TESLA524.6

TRACY531.2

METCALF519.7

METCALF232.2

BALCH3TP237.5

PINE FLT236.3

GATES229.2

KEARNEY228.9

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY230.1

Q128233.8

Q239229.8

Q166229.7

Q194229.4

BORDEN229.2

STOREY 2228.2

STOREY 1228.4

WILSON224.4

WARNERVL228.2

DS AMIGO231.0

MELONES231.7

COTTLE A229.7

COTTLE B228.0

BELLOTA228.5

TESLA E231.2

SN LS PP

TESLA D232.9

TESLA C232.7

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254230.3

STANDFRD114.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404 93 1404 93 1404 93 1

0.0135.8

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

872.0

29.4

1333.9

0.0

1371.4

0.0

1691.5

0.0

402.6

13.6

373.6

12.6

804.1 27.1

804.4

27.1

881.8 90.4

878.2

90.1

1162.8 67.8

772.2

79.2

164.8

17.5178.0

18.9

1045.1

35.3

1040.6

35.1

551.5

18.6

518.8

17.5

283.6 29.1

905.1

46.3

905.1

46.3

97.1

8.8

623.0 63.9

619.7

63.6

580.9 68.4

141.8 16.7

120.0 14.1

751.1 25.3

755.8 25.5

1137.1

38.4

899.9 30.4

1496.9

66.1

1496.9

66.1

515.4

11.9

528.8

12.2

1131.7

74.1

97.0

5.1

328.8 33.7

113.6 11.7

269.1 30.4

456.4 51.5

541.7 63.7

538.5 63.4

585.4 68.9

588.2 69.2

564.4

34.9

599.6

39.7

628.5

50.4

719.3

41.3

725.1 41.6

720.0

41.3

344.6 40.5

347.3

40.8

724.5 41.6

467.1 55.0

477.0 56.1

712.3

24.0

947.6

76.7

932.5

75.5

955.9

77.4

696.4 37.5696.4 37.5

1523.9

156.1

1526.1

156.3

548.3

56.1

548.3

56.1

1070.9

109.7

1537.4

157.4

470.9 97.5

237.3 24.3

242.4

24.8

242.4

24.8

237.3 24.3

616.7 72.5

418.3

52.7

410.6

51.8

871.1

109.8

1020.5

128.7

923.2

108.5

784.1

98.9

927.6116.9

371.8 43.7

620.6 73.0

931.8

117.5

551.8

64.9

1651.6

97.2

812.0 65.8

1064.4 86.2

948.7 58.3

400.2 23.3400.2 23.3

666.4 78.4

664.1 78.1

449.9

52.9

99.7

10.2

99.7

10.2

646.7 57.2

646.7 57.2

398.3 23.2398.3 23.2

887.0 29.9

1356.8 49.7

1366.6

50.1

669.6 23.8

691.1

24.5

1692.8 39.4

997.8 89.7

997.9 89.7

997.9 89.7

1502.0

78.7

330.1

17.4

330.7

17.5

323.5

38.1

312.6

36.8

323.5

38.1

312.6

36.8

893.4 30.1

250.7 66.1125.4 66.1125.4 66.1

503.5

53.6

503.5

53.6

1008.5 127.1

123.4

6.6

109.5 5.8

123.4

6.6

109.5 5.8

576.0

19.4

549.7 18.5

551.1

56.5

550.9

56.5

Page 539: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 37-Outage: Los Banos South DLO

Los Banos - Gates, Los Banos - Midway Double Line Out

MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:42 2008 post-2013sumpk_q272_pre_lbs-dlo-ns.sav

MIDWAY519.0

24156VINCENT

MIDWAY226.4

30057DIABLO

525.01.050

GATES515.4

GATES225.3

MORROBAY232.8

TEMPLETN

ARCO223.8

LOSBANOS505.5

30045MOSSLAND

508.11.016

GREGG227.4

HELMS PP232.4

HENRIETA225.6

PANOCHE225.4

HELM227.1

MCMULLN1

HERNDON227.0

LOSBANOS

221.7

COBURN229.6

TESLA510.3

TRACY516.5

METCALF507.3

METCALF227.4

BALCH3TP236.5

PINE FLT234.8

GATES225.3

KEARNEY225.5

30875MC CALL

231.61.007

MOSSLND2

MOSSLND1

WESTLEY223.5

Q128232.2

Q239229.8

Q166229.7

Q194229.5

BORDEN226.4

STOREY 2224.8

STOREY 1224.9

WILSON218.3

WARNERVL222.8

DS AMIGO222.1

MELONES225.3

COTTLE A224.0

COTTLE B222.7

BELLOTA223.9

TESLA E225.4

SN LS PP

TESLA D227.1

TESLA C228.1

Q235SWST226.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254227.4

STANDFRD111.6

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404108 1404108 1404108 1

0.0133.8

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

705.5

115.9

1037.0

143.2

1065.8

148.2

1312.8

153.8

531.0

122.5

528.9

224.6

879.9 61.9

874.0

33.4

397.9 48.0

378.3

81.4

510.8 81.9

335.0

77.4

66.5

1.166.0

10.9

5.5

19.1

5.5

9.5

110.2 13.9

339.1

11.3

339.1

11.3

200.2

123.7

354.7 17.4

346.3

42.1

330.9 0.0

94.033.9

92.322.5

717.1 81.5

714.4 56.4

943.5

487.1

910.4 29.1

594.3

29.2

594.3

29.2

2013.5

309.0

1983.0

260.5

610.6

117.8

101.0

22.8

24.223.6

8.112.4

105.7 26.7

184.2 8.2

261.9 14.6

257.8 32.3

276.5 18.3

282.7 7.7

497.6

2.3

528.7

0.7

554.1

2.7

309.5

77.3

321.8 34.6

310.0

77.5

180.9 29.8

185.4

14.6

321.3 34.6

269.1 95.2

283.7 30.2

817.3

108.1

848.7

86.5

835.1

85.5

855.1

95.1

281.3 25.9281.3 25.9

545.2

119.3

565.6

38.2

177.2

18.7

177.2

18.7

385.9

12.1

550.4

120.1

185.0 25.8

54.8 8.1

54.5

19.0

54.5

19.0

54.8 8.1

245.5 0.1

220.5

23.6

216.2

25.1

396.2

42.5

465.5

28.9

424.8

26.7

360.2

26.6

441.2 68.6

169.8 52.2

283.2 10.7

419.2

64.1

249.0

49.2

796.5

91.5

668.1 70.9

928.1 59.8

755.4135.1

160.7 80.6160.7 80.6

335.7 1.0

328.4 36.3

328.4

36.3

39.7

3.5

39.7

3.5

539.7 28.9

539.7 28.9

160.3 81.9160.3 81.9

676.2 19.4

1136.6 36.3

1154.7

22.4

139.5 67.1

139.6

136.4

1377.1 47.1

402.1 48.4

402.1 48.8

402.2 48.8

596.1

60.7

24.1

35.0

24.0

38.9

94.0

19.1

313.1

29.3

302.0

80.1

313.1

29.3

302.0

80.1

674.0 42.5

111.2 11.455.6 5.755.6 5.7

109.8

24.4

109.8

24.4

451.0 57.0

1.5

38.5

1.427.4

1.5

38.5

1.427.4

648.8

194.7

645.9142.5

220.8

18.5

219.9

13.9

Page 540: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project Case

PATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FY

Plot 38-Outage: Los Banos South DLO

Los Banos - Gates, Los Banos - Midway Double Line Out

amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:42 2008 post-2013sumpk_q272_pre_lbs-dlo-ns.sav

MIDWAY519.0

24156VINCENT

MIDWAY226.4

30057DIABLO

525.01.050

GATES515.4

GATES225.3

MORROBAY232.8

TEMPLETN

ARCO223.8

LOSBANOS505.5

30045MOSSLAND

508.11.016

GREGG227.4

HELMS PP232.4

HENRIETA225.6

PANOCHE225.4

HELM227.1

MCMULLN1

HERNDON227.0

LOSBANOS

221.7

COBURN229.6

TESLA510.3

TRACY516.5

METCALF507.3

METCALF227.4

BALCH3TP236.5

PINE FLT234.8

GATES225.3

KEARNEY225.5

30875MC CALL

231.61.007

MOSSLND2

MOSSLND1

WESTLEY223.5

Q128232.2

Q239229.8

Q166229.7

Q194229.5

BORDEN226.4

STOREY 2224.8

STOREY 1224.9

WILSON218.3

WARNERVL222.8

DS AMIGO222.1

MELONES225.3

COTTLE A224.0

COTTLE B222.7

BELLOTA223.9

TESLA E225.4

SN LS PP

TESLA D227.1

TESLA C228.1

Q235SWST226.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254227.4

STANDFRD111.6

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404108 1404108 1404108 1

0.0133.8

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

795.3

26.8

1164.5

0.0

1197.0

0.0

1470.4

0.0

606.2

20.5

643.7

21.7

969.9 32.7

979.7

33.1

993.7101.9

991.5

101.7

1282.7 74.8

881.1

90.4

169.6

18.0172.5

18.3

51.3

5.4

28.1

3.0

284.4 29.2

861.2

44.1

861.2

44.1

268.7

23.4

909.4 93.3

908.5

93.2

847.3 99.7

256.0 30.1

238.9 28.1

824.2 27.8

814.3 27.5

1186.8

40.0

1035.0 34.9

1510.6

66.7

1510.6

66.7

2281.9

52.7

2284.2

52.7

696.6

44.4

262.9

13.9

84.2 8.6

37.9 3.9

271.9 30.7

459.6 51.9

667.0 78.5

665.4 78.3

704.6 82.9

705.1 83.0

566.3

34.2

601.6

38.9

630.7

49.4

809.9

46.5

815.8 46.8

811.1

46.6

462.2 54.3

467.7

55.0

814.6 46.8

719.6 84.7

730.7 86.0

941.6

31.8

949.0

76.0

933.8

74.8

957.1

76.7

702.3 37.8702.3 37.8

1423.2

145.8

1425.0

145.9

447.9

45.9

447.9

45.9

970.6

99.4

1436.7

147.1

469.9 97.3

137.3 14.1

145.1

14.9

145.1

14.9

137.3 14.1

616.8 72.5

563.0

71.0

552.5

69.7

1016.3

128.1

1189.5

150.0

1092.6

128.4

927.4

116.9

1180.9

148.9

469.7 55.2

726.3 85.5

1099.5

138.6

654.6

77.0

2088.1

122.8

760.1 59.9

1052.2 82.9

868.1 51.9

459.5 26.8459.5 26.8

859.8101.2

858.8101.0

858.8

101.0

103.9

10.6

103.9

10.6

604.1 51.9

604.1 51.9

457.6 26.7457.6 26.7

765.3 25.8

1286.5 47.1

1304.9

47.8

175.1 6.2

223.0

7.9

1540.1 35.8

1006.3 90.0

1006.4 90.0

1006.5 90.0

1535.3

80.5

108.0

5.7

117.2

6.2

245.9

13.4

805.7

94.8

800.1

94.1

805.7

94.8

800.1

94.1

768.6 25.9

289.7 74.5144.9 74.5144.9 74.5

581.8

62.0

581.8

62.0

1177.9 148.5

99.4

5.3

70.2 3.7

99.4

5.3

70.2 3.7

773.6

26.1

739.2 24.9

563.6

57.8

564.2

57.9

Page 541: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 39-Outage: Los Banos South DLO

Los Banos - Gates, Los Banos - Midway Double Line Out

MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:43 2008 post-2013sumpk_q272_pst_v2_lbs-dlo-ns.sav

MIDWAY519.0

24156VINCENT

MIDWAY226.4

30057DIABLO

525.11.050

GATES515.5

GATES225.4

MORROBAY232.8

TEMPLETN

ARCO223.9

LOSBANOS506.2

30045MOSSLAND

508.41.017

GREGG227.5

HELMS PP232.4

HENRIETA225.8

PANOCHE225.8

HELM227.3

MCMULLN1

HERNDON227.1

LOSBANOS

223.1

COBURN229.8

TESLA510.5

TRACY516.8

METCALF507.5

METCALF227.5

BALCH3TP236.6

PINE FLT234.8

GATES225.4

KEARNEY225.6

30875MC CALL

231.61.007

MOSSLND2

MOSSLND1

WESTLEY223.8

Q128232.3

Q239229.8

Q166229.7

Q194229.5

BORDEN226.4

STOREY 2224.8

STOREY 1224.9

WILSON218.3

WARNERVL222.9

DS AMIGO223.2

MELONES225.3

COTTLE A224.0

COTTLE B222.7

BELLOTA224.0

TESLA E225.5

SN LS PP

TESLA D227.2

TESLA C228.2

Q235SWST226.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254227.4

STANDFRD111.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404108 1404108 1404108 1

0.0133.9

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

705.1

116.1

1035.9

142.9

1064.7

148.0

1311.5

153.4

535.4

120.3

533.3

222.2

880.8 61.2

874.9

34.3

397.6 47.6

378.1

81.6

510.6 81.4

334.8

77.6

65.9

0.965.4

10.8

5.0

19.3

4.9

9.7

112.4 16.3

340.4

10.4

340.4

10.4

200.9

96.4

358.1 9.7

349.6

50.6

333.7 7.3

94.733.3

93.021.9

720.2 76.3

717.6 51.3

948.3

490.4

914.0 26.4

594.4

29.5

594.4

29.5

2026.2

306.5

1995.3

271.1

618.1

118.6

107.1

23.1

23.623.5

31.612.7

105.7 26.7

184.2 8.0

264.1 17.0

259.9 35.0

278.7 20.6

284.9 6.0

498.5

3.2

529.7

0.3

555.2

3.7

310.4

77.5

322.6 34.4

310.8

77.6

181.6 29.4

186.1

14.1

322.1 34.5

270.6 94.4

285.3 28.8

822.8

101.6

849.3

86.8

835.7

85.8

855.7

95.4

281.3 25.5281.3 25.5

545.4

119.4

565.8

38.2

177.4

18.8

177.4

18.8

386.1

12.1

550.7

120.2

185.0 25.7

55.0 8.2

54.7

19.1

54.7

19.1

55.0 8.2

245.5 0.1

222.3

24.2

217.9

25.6

397.8

42.8

467.4

29.2

426.7

26.9

361.7

26.8

443.5 68.9

170.8 52.1

284.2 11.0

421.4

64.2

250.0

49.9

804.5

73.2

668.7 70.8

934.1 61.7

755.5134.8

162.4 79.7162.4 79.7

338.6 8.4

331.2 44.2

331.2

44.2

39.7

3.5

39.7

3.5

539.8 28.4

539.8 28.4

162.0 81.0162.0 81.0

675.6 19.9

1136.7 39.0

1154.8

19.6

135.4 71.3

135.6

140.6

1377.7 44.0

402.1 48.1

402.1 48.6

402.2 48.6

596.1

59.3

23.5

34.9

23.5

38.8

76.7

18.9

316.6

31.4

305.2

83.6

316.6

31.4

305.2

83.6

673.4 43.1

111.1 12.155.6 6.155.6 6.1

109.7

25.1

109.7

25.1

453.2 57.1

3.2

36.9

3.225.8

3.2

36.9

3.225.8

653.3

189.6

650.3137.8

223.2

16.6

222.2

11.8

Page 542: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project Case

PATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FY

Plot 40-Outage: Los Banos South DLO

Los Banos - Gates, Los Banos - Midway Double Line Out

amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:44 2008 post-2013sumpk_q272_pst_v2_lbs-dlo-ns.sav

MIDWAY519.0

24156VINCENT

MIDWAY226.4

30057DIABLO

525.11.050

GATES515.5

GATES225.4

MORROBAY232.8

TEMPLETN

ARCO223.9

LOSBANOS506.2

30045MOSSLAND

508.41.017

GREGG227.5

HELMS PP232.4

HENRIETA225.8

PANOCHE225.8

HELM227.3

MCMULLN1

HERNDON227.1

LOSBANOS

223.1

COBURN229.8

TESLA510.5

TRACY516.8

METCALF507.5

METCALF227.5

BALCH3TP236.6

PINE FLT234.8

GATES225.4

KEARNEY225.6

30875MC CALL

231.61.007

MOSSLND2

MOSSLND1

WESTLEY223.8

Q128232.3

Q239229.8

Q166229.7

Q194229.5

BORDEN226.4

STOREY 2224.8

STOREY 1224.9

WILSON218.3

WARNERVL222.9

DS AMIGO223.2

MELONES225.3

COTTLE A224.0

COTTLE B222.7

BELLOTA224.0

TESLA E225.5

SN LS PP

TESLA D227.2

TESLA C228.2

Q235SWST226.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254227.4

STANDFRD111.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

404108 1404108 1404108 1

0.0133.9

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

794.8

26.8

1163.2

0.0

1195.6

0.0

1468.7

0.0

610.3

20.6

647.0

21.8

970.7 32.8

980.5

33.1

992.9101.8

990.7

101.6

1281.9 74.8

880.2

90.3

168.1

17.9171.0

18.2

51.4

5.5

27.8

3.0

290.4 29.8

864.3

44.3

864.3

44.3

254.2

22.2

915.7 93.9

914.2

93.8

853.3100.4

256.6 30.2

240.0 28.2

826.1 27.9

816.9 27.6

1192.7

40.2

1038.4 35.0

1510.4

66.7

1510.4

66.7

2295.0

53.0

2296.7

53.0

704.8

44.9

278.2

14.7

83.0 8.5

87.0 8.9

271.8 30.7

459.4 51.8

672.1 79.1

670.3 78.9

709.8 83.5

710.4 83.6

567.1

34.3

602.5

38.9

631.6

49.5

811.7

46.6

817.7 46.9

813.0

46.7

463.5 54.5

468.9

55.1

816.4 46.9

722.2 85.0

733.2 86.3

945.6

31.9

949.5

76.1

934.4

74.9

957.7

76.7

702.1 37.8702.1 37.8

1423.7

145.8

1425.5

146.0

448.5

45.9

448.5

45.9

971.1

99.5

1437.2

147.2

469.9 97.2

137.8 14.1

145.6

14.9

145.6

14.9

137.8 14.1

616.8 72.5

567.5

71.5

556.9

70.2

1020.3

128.6

1194.1

150.5

1097.3

129.0

931.4

117.4

1186.8

149.6

472.3 55.5

728.9 85.8

1104.9

139.3

657.1

77.3

2090.8

123.0

760.4 59.9

1058.6 83.4

867.8 51.9

462.0 26.9462.0 26.9

865.8101.9

864.4101.7

864.4

101.7

103.2

10.6

103.2

10.6

603.9 51.9

603.9 51.9

460.1 26.8460.1 26.8

764.3 25.8

1286.1 47.1

1305.2

47.8

173.1 6.1

223.1

7.9

1539.8 35.8

1006.1 90.0

1006.3 90.0

1006.3 90.0

1534.3

80.4

106.9

5.6

116.2

6.1

202.5

11.0

815.0

95.9

809.1

95.2

815.0

95.9

809.1

95.2

767.6 25.9

289.6 74.5144.8 74.5144.8 74.5

581.7

62.0

581.7

62.0

1183.4 149.2

95.5

5.1

66.4 3.5

95.5

5.1

66.4 3.5

775.8

26.2

742.6 25.1

569.0

58.4

569.5

58.4

Page 543: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 41 - No Outage MW/MVAR

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:45 2008 2013sumop_q272_pre.sav

HENRITTA73.86

LEMOORE72.58

MUSLSLGH73.66

CAMDEN69.96

KNGLOBUS

70.84

KINGSBRG118.5

HENRIETA227.6

34542JCBSCRNR

GUERNSEY73.20

34554

AMSTG SW

ARMSTRNG73.37

GWF-PWR.13.87RESERVE

73.36

34528

CORCORAN

34420

CORCORAN

HNFRD SW

70.53

HARDWICK

70.39

ANGIOLA

73.57

BOSWELL73.72

LEPRINO72.52

CANDLEWK72.61

CMDN JCT

BSWLL TP

JGBSWLL

73.72

GUR3TPT

GWF_HENR73.89

GWF_GT114.01

GWF_GT214.01

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

8.0

1

50

4

1

50

4

1 1

8.6

1.8

1

15.0

3.0

2

5.5

1.1

1

4.4

0.9

23.8

0.8

1

3.1

0.6

1

5.0

1.0

2

16.6 10.3

1

3.3

0.7

1

5.91.2

1

4.8 1.0

1

1.81.2

1

0.0

0.0

1

0.9 0.2

1

0.00.0

1

1

1

0

ss

1

0

ss ss

5

3

1

1.044 1.000

1.017

1.000

1.0001.0001.000

0.00.1

8.11.5

8.21.2

0.9

0.2

23.0

8.0

0.0

0.0

22.1

8.2

21.9

8.3

17.1

9.3

16.9 9.5

7.011.5

6.9

11.4

23.7

4.8

4.81.0

1.81.2

28.9

8.8

16.6

39.6

33.6

4.8

0.00.0

0.0

0.0

5.9

0.7

5.91.2

14.7

2.1

5.11.8

5.11.5

3.3

0.7

3.30.5

48.9

0.1

48.9

0.1

97.8

0.2

16.6

10.3

16.610.3

5.03.2

Page 544: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 42 - No Outage amps/rate

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:45 2008 2013sumop_q272_pre.sav

HENRITTA73.86

LEMOORE72.58

MUSLSLGH73.66

CAMDEN69.96

KNGLOBUS

70.84

KINGSBRG118.5

HENRIETA227.6

34542JCBSCRNR

GUERNSEY73.20

34554

AMSTG SW

ARMSTRNG73.37

GWF-PWR.13.87RESERVE

73.36

34528

CORCORAN

34420

CORCORAN

HNFRD SW

70.53

HARDWICK

70.39

ANGIOLA

73.57

BOSWELL73.72

LEPRINO72.52

CANDLEWK72.61

CMDN JCT

BSWLL TP

JGBSWLL

73.72

GUR3TPT

GWF_HENR73.89

GWF_GT114.01

GWF_GT214.01

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

8.0

1

50

4

1

50

4

1 1

8.6

1.8

1

15.0

3.0

2

5.5

1.1

1

4.4

0.9

23.8

0.8

1

3.1

0.6

1

5.0

1.0

2

16.6 10.3

1

3.3

0.7

1

5.91.2

1

4.8 1.0

1

1.81.2

1

0.0

0.0

1

0.9 0.2

1

0.00.0

1

1

1

0

ss

1

0

ss ss

5

3

1

1.044 1.000

1.017

1.000

1.0001.0001.000

1.20.5

68.320.0

67.719.9

7.4

3.6

191.6

90.5

0.1

0.0

185.2

57.6

184.9

57.5

153.6

38.0

152.8 37.8

106.0 25.9

104.3

25.4

192.0

30.2

38.7

9.6

16.6 3.8

236.1

37.2

109.0

43.0

86.1

17.0

0.00.0

0.0

0.0

48.6

15.0

49.314.2

72.5

16.5

26.829.1

41.7

14.0

26.5

8.9

26.3 8.9

382.1

84.9

382.1

84.9

764.1

67.6

152.6 24.0

152.8 24.1

47.516.0

Page 545: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 43 - No Outage MW/MVAR

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:47 2008 2013sumop_q272_pst.sav

HENRITTA73.88

LEMOORE72.60

MUSLSLGH73.68

CAMDEN69.96

KNGLOBUS

70.84

KINGSBRG118.5

HENRIETA227.6

34542JCBSCRNR

GUERNSEY73.22

34554

AMSTG SW

ARMSTRNG73.39

GWF-PWR.13.87RESERVE

73.38

34528

CORCORAN

34420

CORCORAN

HNFRD SW

70.52

HARDWICK

70.39

ANGIOLA

73.57

BOSWELL73.72

LEPRINO72.54

CANDLEWK72.63

CMDN JCT

BSWLL TP

JGBSWLL

73.72

GUR3TPT

GWF_HENR73.92

GWF_GT114.01

GWF_GT214.01

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

8.0

1

50

4

1

50

4

1

27

4

1

8.6

1.8

1

15.0

3.0

2

5.5

1.1

1

4.4

0.9

23.8

0.8

1

3.1

0.6

1

5.0

1.0

2

16.6 10.3

1

3.3

0.7

1

5.91.2

1

4.8 1.0

1

1.81.2

1

0.0

0.0

1

0.9 0.2

1

0.00.0

1

1

1

0

ss

1

0

ss

2

1

ss

5

3

1

1.044 1.000

1.017

1.000

1.0001.0001.000

0.00.1

8.11.5

8.21.2

0.9

0.2

23.0

8.0

0.0

0.0

22.1

8.2

21.9

8.3

17.1

9.3

16.9 9.5

7.011.5

6.9

11.4

23.6

4.8

4.81.0

1.81.2

28.9

8.8

24.9

40.0

50.3

5.5

0.00.0

0.0

0.0

5.9

0.7

5.91.2

14.7

2.1

5.11.8

5.11.5

3.3

0.7

3.30.5

25.0

1.0

48.9

0.2

48.9

0.2

122.8

0.6

16.6

10.3

16.610.3

5.03.2

Page 546: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 44 - No Outage amps/rate

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:47 2008 2013sumop_q272_pst.sav

HENRITTA73.88

LEMOORE72.60

MUSLSLGH73.68

CAMDEN69.96

KNGLOBUS

70.84

KINGSBRG118.5

HENRIETA227.6

34542JCBSCRNR

GUERNSEY73.22

34554

AMSTG SW

ARMSTRNG73.39

GWF-PWR.13.87RESERVE

73.38

34528

CORCORAN

34420

CORCORAN

HNFRD SW

70.52

HARDWICK

70.39

ANGIOLA

73.57

BOSWELL73.72

LEPRINO72.54

CANDLEWK72.63

CMDN JCT

BSWLL TP

JGBSWLL

73.72

GUR3TPT

GWF_HENR73.92

GWF_GT114.01

GWF_GT214.01

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

8.0

1

50

4

1

50

4

1

27

4

1

8.6

1.8

1

15.0

3.0

2

5.5

1.1

1

4.4

0.9

23.8

0.8

1

3.1

0.6

1

5.0

1.0

2

16.6 10.3

1

3.3

0.7

1

5.91.2

1

4.8 1.0

1

1.81.2

1

0.0

0.0

1

0.9 0.2

1

0.00.0

1

1

1

0

ss

1

0

ss

2

1

ss

5

3

1

1.044 1.000

1.017

1.000

1.0001.0001.000

1.20.5

68.320.0

67.719.9

7.4

3.6

191.6

90.5

0.1

0.0

185.1

57.5

184.9

57.5

153.6

38.0

152.7 37.8

106.0 25.9

104.3

25.4

191.9

30.2

38.7

9.6

16.6 3.8

236.0

37.2

119.4

47.1

128.4

25.3

0.00.0

0.0

0.0

48.6

15.0

49.314.2

72.5

16.5

26.829.1

41.7

14.0

26.5

8.9

26.3 8.9

195.4

71.5

381.9

84.9

381.9

84.9

959.1

84.9

152.5 24.0

152.7 24.1

47.516.0

Page 547: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 45-Outage: Wilson-Borden #2 230kV & Helms 1 MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:49 2008 2013sumop_q272_pre.sav

MIDWAY525.5

24156VINCENT

MIDWAY228.1

30057DIABLO

524.61.049

GATES521.4

GATES227.8

MORROBAY232.9

TEMPLETN

ARCO226.6

LOSBANOS511.9

30045MOSSLAND

514.61.029

GREGG231.1

HELMS PP232.9

HENRIETA227.9

PANOCHE229.9

HELM227.9

MCMULLN1

HERNDON231.0

LOSBANOS

229.6

COBURN228.5

TESLA525.0

TRACY529.9

METCALF518.1

METCALF231.4

BALCH3TP229.5

PINE FLT229.7

GATES227.8

KEARNEY230.5

30875MC CALL

229.50.998

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128230.4

Q239230.0

Q166228.8

Q194230.0

BORDEN231.2

STOREY 2230.7

STOREY 1225.4

WILSON230.4

WARNERVL232.6

DS AMIGO228.6

MELONES231.2

COTTLE A232.9

COTTLE B232.7

BELLOTA234.1

TESLA E230.9

SN LS PP

TESLA D232.3

TESLA C232.8

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.2

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310111 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

646.7

176.5

81.7

211.5

83.6

214.7

102.6

195.9

1191.1

88.6

1182.0

137.3

998.6 10.1

991.1

124.8

323.0 20.2

310.2

56.5

383.8 32.5

285.4

53.9

42.6

3.042.4

8.8

4.4

16.0

4.4

6.1

1993.5

44.7

1963.7

142.9

1696.7

40.9

1656.6

252.5

5.011.3

14.3

17.2

14.3

17.2

33.8

21.2

257.5 15.8

253.3

40.1

239.1 26.7

58.213.0

57.6 6.4

1007.9 66.7

1002.8 99.6

433.1

485.5

1060.0 125.0

156.4

39.7

156.4

39.7

980.3

63.5

973.3

65.1

800.8

95.7

182.9

51.4

119.3 8.0

107.0 34.3

198.5 31.7

96.011.9

257.1 59.1

253.0 76.6

296.0 52.5

303.2 20.3

192.2

18.6

204.2

18.2

213.9

19.9

225.6

67.8

230.2 52.1

224.0

69.2

175.5 39.5

179.8

25.8

231.9 50.5

231.9 61.3

242.1 22.5

1889.9

84.2

623.9

102.6

613.9

101.8

627.6

116.2

281.7 40.8281.7 40.8

227.5

31.2

230.9

13.3

230.9

13.3

230.9

13.3

230.9

13.3

227.5

31.2

235.3 9.7

231.0

12.8

231.0

12.8

235.3 9.7

116.8

13.5

114.8

12.3

291.2

17.7

275.3

24.6

191.7 49.1

75.322.2

174.1 41.7

298.3

62.7

158.5

47.5

750.4

86.6

125.3104.8

443.8 89.7

49.8106.5

132.5 0.4132.5 0.4

274.3 20.7

269.7 40.6

179.7

51.1

39.9

3.2

39.9

3.2

53.615.2

53.615.2

132.3 0.6132.3 0.6

443.2166.0

854.6271.6

844.8

203.1

1270.7 155.4

1264.3

229.5

1103.8 233.6

0.20.8

311.2 74.1

0.20.7

596.2

21.9

118.2

4.1

117.9

2.6

79.0

11.6

213.5

43.6

208.3

60.2

213.5

43.6

208.3

60.2

444.3212.3

61.721.430.910.730.910.7

61.3

24.8

61.3

24.8

313.5 59.7

192.4

46.5

191.3 46.4

192.4

46.5

191.3 46.4

1662.1

158.1

1644.2

452.4

50.2

5.8

50.1 8.6

Page 548: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 46-Outage: Wilson-Borden #2 230kV & Helms 1 amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:51 2008 2013sumop_q272_pre.sav

MIDWAY525.5

24156VINCENT

MIDWAY228.1

30057DIABLO

524.61.049

GATES521.4

GATES227.8

MORROBAY232.9

TEMPLETN

ARCO226.6

LOSBANOS511.9

30045MOSSLAND

514.61.029

GREGG231.1

HELMS PP232.9

HENRIETA227.9

PANOCHE229.9

HELM227.9

MCMULLN1

HERNDON231.0

LOSBANOS

229.6

COBURN228.5

TESLA525.0

TRACY529.9

METCALF518.1

METCALF231.4

BALCH3TP229.5

PINE FLT229.7

GATES227.8

KEARNEY230.5

30875MC CALL

229.50.998

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128230.4

Q239230.0

Q166228.8

Q194230.0

BORDEN231.2

STOREY 2230.7

STOREY 1225.4

WILSON230.4

WARNERVL232.6

DS AMIGO228.6

MELONES231.2

COTTLE A232.9

COTTLE B232.7

BELLOTA234.1

TESLA E230.9

SN LS PP

TESLA D232.3

TESLA C232.8

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.2

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310111 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

736.5

24.8

249.1

0.0

253.1

0.0

243.0

0.0

1312.2

44.3

1317.5

44.5

1098.9 37.1

1106.0

37.3

802.2 82.3

799.3

82.0

954.8 55.7

736.2

75.5

108.1

11.5110.3

11.7

42.2

4.5

19.0

2.0

2207.7

74.5

2220.6

74.9

1864.6

62.9

1890.0

63.8

31.0 3.2

55.9

2.9

55.9

2.9

45.0

4.0

647.9 66.5

644.9

66.1

604.1 71.1

149.6 17.6

146.3 17.2

1139.2 38.4

1130.6 38.1

708.8

23.9

1197.5 40.4

403.2

17.8

403.2

17.8

1087.6

25.1

1100.2

25.4

892.9

57.5

474.8

25.0

300.7 30.8

284.7 29.2

505.7 57.1

243.4 27.5

668.4 78.6

663.8 78.1

761.4 89.6

764.2 89.9

215.2

13.3

228.5

15.1

239.4

19.1

587.8

33.7

591.9 34.0

584.9

33.6

450.8 53.0

459.0

53.9

594.6 34.1

601.6 70.8

610.6 71.8

2133.6

72.0

694.6

56.4

683.7

55.5

701.2

56.9

713.1 38.4713.1 38.4

581.0

59.5

583.5

59.8

583.5

59.8

583.5

59.8

583.5

59.8

581.1

59.5

583.8 59.8

583.6

59.8

583.6

59.8

583.8 59.8

293.8

37.0

288.4

36.4

728.7

91.9

691.7

87.2

496.0 62.5

196.8 23.1

447.2 52.6

756.5

95.4

408.2

48.0

1899.6

111.7

179.6 14.6

497.9 40.4

129.3 7.9

328.8 19.2328.8 19.2

690.8 81.3

688.8 81.0

471.7

55.5

100.8

10.3

100.8

10.3

60.8 5.4

60.8 5.4

328.8 19.2328.8 19.2

520.5 17.6

986.1 36.1

946.2

34.7

1407.8 50.0

1394.9

49.5

1229.3 28.6

2.00.2

793.1 71.1

1.90.2

1512.2

79.3

299.1

15.8

298.8

15.8

202.4

11.0

552.4

65.0

544.6

64.1

552.4

65.0

544.6

64.1

548.7 18.5

162.2 43.681.143.681.143.6

324.4

34.6

324.4

34.6

792.0 99.8

495.6

26.4

488.5 26.0

495.6

26.4

488.5 26.0

1883.1

63.5

1858.0

62.7

126.2

12.9

127.3

13.1

Page 549: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 47-Outage: Wilson-Borden #2 230kV & Helms 1 MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:53 2008 2013sumop_q272_pst.sav

MIDWAY525.4

24156VINCENT

MIDWAY228.1

30057DIABLO

524.61.049

GATES521.2

GATES227.7

MORROBAY232.9

TEMPLETN

ARCO226.6

LOSBANOS511.6

30045MOSSLAND

514.41.029

GREGG231.0

HELMS PP232.9

HENRIETA227.9

PANOCHE229.8

HELM227.8

MCMULLN1

HERNDON231.0

LOSBANOS

229.5

COBURN228.4

TESLA524.8

TRACY529.7

METCALF517.9

METCALF231.4

BALCH3TP229.5

PINE FLT229.6

GATES227.7

KEARNEY230.5

30875MC CALL

229.50.998

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128230.4

Q239230.0

Q166228.8

Q194230.0

BORDEN231.1

STOREY 2230.7

STOREY 1225.4

WILSON230.3

WARNERVL232.6

DS AMIGO228.5

MELONES231.1

COTTLE A232.8

COTTLE B232.6

BELLOTA234.1

TESLA E230.9

SN LS PP

TESLA D232.2

TESLA C232.7

Q235SWST232.4

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.2

STANDFRD117.6

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310112 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

646.8

175.8

82.2

212.2

84.1

215.5

103.1

197.0

1190.0

91.2

1180.8

139.9

998.3 11.5

990.8

123.4

322.3 20.3

309.6

56.0

383.2 32.6

284.8

53.4

41.4

2.841.3

9.0

3.3

15.6

3.3

5.8

2000.0

46.9

1970.0

143.3

1700.5

43.5

1660.2

251.9

3.111.3

15.5

17.1

15.5

17.1

32.6

21.2

259.0 15.5

254.7

40.2

240.4 26.5

58.813.1

58.2 6.2

1011.4 67.3

1006.3 101.3

436.9

483.8

1063.6 125.8

156.4

39.8

156.4

39.8

983.5

64.8

976.4

64.9

811.9

95.2

188.2

52.4

119.4 7.7

130.6 35.2

198.5 31.6

96.011.8

258.4 59.0

254.3 76.8

297.3 52.4

304.6 19.8

193.1

18.0

205.2

17.6

214.9

19.2

226.5

68.2

231.0 52.3

224.8

69.6

176.1 39.8

180.5

25.8

232.7 50.6

233.2 62.0

243.5 22.4

1895.7

83.9

625.2

102.1

615.2

101.4

628.9

115.7

281.7 40.9281.7 40.9

228.0

31.4

231.4

13.3

231.4

13.3

231.4

13.3

231.5

13.3

228.0

31.4

235.9 9.9

231.5

12.8

231.5

12.8

235.9 9.9

115.4

13.3

113.4

12.1

294.1

17.3

278.1

24.4

193.8 49.5

76.222.5

175.0 41.6

299.9

63.1

159.4

47.7

753.4

87.1

126.1104.4

449.7 88.8

50.0106.0

133.7 0.1133.7 0.1

275.7 20.4

271.0 40.7

181.0

51.1

39.9

3.2

39.9

3.2

54.015.4

54.015.4

133.5 0.3133.5 0.3

443.9165.7

854.7272.5

844.9

204.2

1273.8 157.2

1267.4

232.3

1104.0 234.7

0.20.8

311.2 74.4

0.20.7

596.2

22.9

118.3

3.9

118.0

2.4

60.8

10.9

215.1

43.5

209.9

60.5

215.1

43.5

209.9

60.5

445.0211.9

62.021.531.010.731.010.7

61.5

24.8

61.5

24.8

315.0 60.1

193.2

46.7

192.0 46.7

193.2

46.7

192.0 46.7

1667.0

157.9

1648.9

455.1

52.1

5.8

52.0 8.6

Page 550: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 48-Outage: Wilson-Borden #2 230kV & Helms 1 amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:54 2008 2013sumop_q272_pst.sav

MIDWAY525.4

24156VINCENT

MIDWAY228.1

30057DIABLO

524.61.049

GATES521.2

GATES227.7

MORROBAY232.9

TEMPLETN

ARCO226.6

LOSBANOS511.6

30045MOSSLAND

514.41.029

GREGG231.0

HELMS PP232.9

HENRIETA227.9

PANOCHE229.8

HELM227.8

MCMULLN1

HERNDON231.0

LOSBANOS

229.5

COBURN228.4

TESLA524.8

TRACY529.7

METCALF517.9

METCALF231.4

BALCH3TP229.5

PINE FLT229.6

GATES227.7

KEARNEY230.5

30875MC CALL

229.50.998

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128230.4

Q239230.0

Q166228.8

Q194230.0

BORDEN231.1

STOREY 2230.7

STOREY 1225.4

WILSON230.3

WARNERVL232.6

DS AMIGO228.5

MELONES231.1

COTTLE A232.8

COTTLE B232.6

BELLOTA234.1

TESLA E230.9

SN LS PP

TESLA D232.2

TESLA C232.7

Q235SWST232.4

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.2

STANDFRD117.6

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310112 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

736.6

24.9

250.1

0.0

254.2

0.0

244.3

0.0

1311.5

44.3

1317.1

44.4

1098.8 37.1

1105.9

37.3

800.7 82.1

797.7

81.8

953.4 55.6

734.7

75.4

105.2

11.2107.6

11.4

40.7

4.3

16.8

1.8

2215.9

74.8

2228.9

75.2

1869.3

63.1

1894.9

63.9

29.4 3.0

57.6

2.9

57.6

2.9

43.8

3.9

651.7 66.8

648.7

66.5

607.6 71.5

151.4 17.8

147.9 17.4

1143.9 38.6

1135.2 38.3

710.5

24.0

1202.2 40.6

403.4

17.8

403.4

17.8

1091.6

25.2

1104.3

25.5

905.4

58.3

488.2

25.7

301.0 30.9

342.7 35.2

505.7 57.1

243.4 27.5

671.7 79.0

667.2 78.5

765.0 90.0

767.8 90.3

216.2

13.3

229.6

15.1

240.6

19.2

590.1

33.9

594.3 34.1

587.3

33.7

452.6 53.2

460.8

54.2

597.0 34.3

605.4 71.2

614.3 72.3

2141.3

72.2

696.1

56.5

685.1

55.6

702.7

57.0

713.2 38.4713.2 38.4

582.6

59.7

585.0

59.9

585.1

59.9

585.1

59.9

585.1

59.9

582.6

59.7

585.3 59.9

585.1

59.9

585.1

59.9

585.3 59.9

290.3

36.6

284.9

35.9

735.8

92.8

698.8

88.1

501.4 63.2

199.3 23.4

449.4 52.9

760.5

95.9

410.4

48.3

1908.1

112.3

180.1 14.6

504.2 40.8

128.9 7.9

331.9 19.4331.9 19.4

694.5 81.7

692.5 81.5

475.3

55.9

100.8

10.3

100.8

10.3

61.2 5.4

61.2 5.4

331.9 19.4331.9 19.4

521.2 17.6

986.9 36.2

946.8

34.7

1411.9 50.1

1398.9

49.7

1230.1 28.6

2.00.2

793.4 71.1

1.90.2

1512.7

79.3

299.5

15.8

299.2

15.8

156.6

8.5

556.5

65.5

548.7

64.6

556.5

65.5

548.7

64.6

549.4 18.5

162.8 43.781.443.781.443.7

325.7

34.7

325.7

34.7

796.0100.4

497.6

26.5

490.5 26.1

497.6

26.5

490.5 26.1

1889.5

63.8

1864.3

62.9

130.9

13.4

132.0

13.5

Page 551: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 49-Outage: Panoche-Kearney 230kV & Kerckhoff MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:56 2008 2013sumop_q272_pre.sav

MIDWAY526.0

24156VINCENT

MIDWAY228.3

30057DIABLO

524.91.050

GATES522.2

GATES228.0

MORROBAY232.9

TEMPLETN

ARCO226.8

LOSBANOS512.8

30045MOSSLAND

515.31.031

GREGG231.2

HELMS PP233.0

HENRIETA227.8

PANOCHE230.2

HELM228.2

MCMULLN1

HERNDON231.2

LOSBANOS

230.0

COBURN228.7

TESLA525.5

TRACY530.4

METCALF518.6

METCALF231.6

BALCH3TP229.4

PINE FLT229.6

GATES228.0

KEARNEY230.7

30875MC CALL

229.40.997

MOSSLND2

MOSSLND1

WESTLEY230.9

Q128230.3

Q239230.0

Q166229.0

Q194230.0

BORDEN231.5

STOREY 2231.4

STOREY 1231.6

WILSON231.2

WARNERVL232.8

DS AMIGO228.9

MELONES231.2

COTTLE A232.9

COTTLE B232.8

BELLOTA234.1

TESLA E231.1

SN LS PP

TESLA D232.4

TESLA C232.9

Q235SWST232.7

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.4

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310109 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

646.2

179.0

80.4

208.5

82.3

211.7

101.0

192.0

1195.0

79.5

1185.8

128.3

999.5 5.0

992.0

129.9

325.5 19.9

312.6

58.3

386.2 32.1

287.8

55.6

47.1

3.746.8

7.8

8.8

17.1

8.8

7.2

1967.6

37.0

1938.6

140.3

1681.5

31.9

1642.2

253.5

1.4

26.1

1.4

26.1

35.5

20.9

251.4 17.2

247.4

39.8

233.3 27.8

55.812.9

55.3 6.9

995.8 64.1

990.8 93.2

424.0

491.2

1047.0 122.1

156.4

38.9

156.4

38.9

967.7

59.1

960.9

66.1

757.4

97.7

230.4

65.7

99.1 9.1

103.7 33.5

198.5 31.0

96.011.4

234.1 56.3

230.7 69.6

270.4 49.0

276.4 23.7

190.0

20.5

201.9

20.3

211.5

22.0

222.9

66.5

227.2 51.6

221.3

67.9

173.3 38.6

177.5

25.8

229.0 49.9

227.3 59.1

237.1 22.8

1867.4

84.4

619.0

103.8

609.1

103.0

622.6

117.4

281.7 41.7281.7 41.7

225.3

30.7

228.7

13.4

228.7

13.4

228.7

13.4

228.7

13.4

225.4

30.7

233.0 8.9

228.8

12.9

228.8

12.9

233.0 8.9

79.7

3.6

78.2

4.2

168.8

18.3

197.7

39.8

180.6

24.9

153.5

21.8

216.4 43.6

85.319.2

183.9 41.7

313.7

62.3

168.0

49.7

735.9

84.4

119.3107.1

430.6 93.2

41.3109.8

129.7 1.7129.7 1.7

268.5 21.8

264.0 40.6

174.0

51.0

39.9

3.2

39.9

3.2

49.313.8

49.313.8

129.5 2.0129.5 2.0

437.4166.0

853.4268.2

843.6

198.8

1262.7 148.8

1256.5

220.5

1103.1 229.5

0.20.8

311.2 72.5

0.20.7

596.2

18.4

98.4

2.6

98.1

0.2

131.6

11.6

206.7

43.6

201.9

58.3

206.7

43.6

201.9

58.3

438.5212.8

66.121.433.010.733.010.7

65.6

25.3

65.6

25.3

328.9 59.1

192.0

45.9

190.8 45.7

192.0

45.9

190.8 45.7

1643.1

158.4

1625.6

441.2

45.8

7.7

45.810.5

Page 552: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 50-Outage: Panoche-Kearney 230kV & Kerckhoff amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:58 2008 2013sumop_q272_pre.sav

MIDWAY526.0

24156VINCENT

MIDWAY228.3

30057DIABLO

524.91.050

GATES522.2

GATES228.0

MORROBAY232.9

TEMPLETN

ARCO226.8

LOSBANOS512.8

30045MOSSLAND

515.31.031

GREGG231.2

HELMS PP233.0

HENRIETA227.8

PANOCHE230.2

HELM228.2

MCMULLN1

HERNDON231.2

LOSBANOS

230.0

COBURN228.7

TESLA525.5

TRACY530.4

METCALF518.6

METCALF231.6

BALCH3TP229.4

PINE FLT229.6

GATES228.0

KEARNEY230.7

30875MC CALL

229.40.997

MOSSLND2

MOSSLND1

WESTLEY230.9

Q128230.3

Q239230.0

Q166229.0

Q194230.0

BORDEN231.5

STOREY 2231.4

STOREY 1231.6

WILSON231.2

WARNERVL232.8

DS AMIGO228.9

MELONES231.2

COTTLE A232.9

COTTLE B232.8

BELLOTA234.1

TESLA E231.1

SN LS PP

TESLA D232.4

TESLA C232.9

Q235SWST232.7

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.4

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310109 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

736.0

24.8

245.3

0.0

249.3

0.0

238.2

0.0

1314.5

44.4

1318.7

44.5

1099.4 37.1

1106.2

37.3

808.3 82.9

805.2

82.6

960.5 56.0

742.2

76.1

119.4

12.7120.8

12.8

48.9

5.2

28.8

3.1

2175.8

73.4

2188.1

73.8

1845.9

62.3

1870.6

63.1

65.3

3.3

65.3

3.3

46.4

4.1

632.1 64.8

628.9

64.5

589.4 69.3

143.6 16.9

140.5 16.5

1123.3 37.9

1115.0 37.6

706.2

23.8

1181.1 39.9

402.4

17.8

402.4

17.8

1071.9

24.7

1084.3

25.0

844.4

54.5

598.1

31.5

250.4 25.7

276.3 28.3

505.7 57.1

243.4 27.5

609.0 71.7

604.4 71.1

695.1 81.8

698.2 82.1

212.7

13.1

225.9

14.9

236.7

18.9

579.8

33.3

583.9 33.5

576.9

33.1

444.5 52.2

452.8

53.2

586.7 33.7

588.6 69.2

597.5 70.3

2104.4

71.0

688.9

55.9

678.0

55.1

695.4

56.5

713.8 38.4713.8 38.4

575.1

58.9

577.6

59.2

577.6

59.2

577.6

59.2

577.6

59.2

575.2

58.9

577.9 59.2

577.6

59.2

577.6

59.2

577.9 59.2

199.1

25.1

195.4

24.6

423.4

53.4

503.0

63.4

454.3

53.4

386.8

48.8

551.1 69.5

218.3 25.7

470.8 55.4

793.2

100.0

432.0

50.8

1859.5

109.4

176.2 14.3

484.0 39.3

128.9 7.9

321.6 18.8321.6 18.8

675.7 79.5

673.6 79.2

457.2

53.8

100.6

10.3

100.6

10.3

55.7 4.9

55.7 4.9

321.7 18.8321.7 18.8

514.0 17.3

982.7 36.0

943.3

34.6

1396.8 49.6

1384.3

49.2

1226.3 28.5

2.00.2

791.7 71.0

1.90.2

1510.4

79.2

248.6

13.1

248.4

13.1

334.6

18.2

535.0

62.9

527.0

62.0

535.0

62.9

527.0

62.0

542.6 18.3

172.2 46.386.146.386.146.3

344.6

36.7

344.6

36.7

828.7104.5

493.5

26.3

486.5 25.9

493.5

26.3

486.5 25.9

1858.3

62.7

1833.3

61.9

116.1

11.9

117.6

12.1

Page 553: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 51-Outage: Panoche-Kearney 230kV & Kerckhoff MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:23:59 2008 2013sumop_q272_pst.sav

MIDWAY525.9

24156VINCENT

MIDWAY228.3

30057DIABLO

524.81.050

GATES522.0

GATES227.9

MORROBAY232.9

TEMPLETN

ARCO226.8

LOSBANOS512.6

30045MOSSLAND

515.11.030

GREGG231.2

HELMS PP233.0

HENRIETA227.8

PANOCHE230.1

HELM228.2

MCMULLN1

HERNDON231.2

LOSBANOS

229.9

COBURN228.7

TESLA525.4

TRACY530.3

METCALF518.4

METCALF231.6

BALCH3TP229.4

PINE FLT229.6

GATES227.9

KEARNEY230.7

30875MC CALL

229.40.997

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128230.3

Q239230.0

Q166228.9

Q194230.0

BORDEN231.5

STOREY 2231.3

STOREY 1231.6

WILSON231.2

WARNERVL232.7

DS AMIGO228.8

MELONES231.2

COTTLE A232.8

COTTLE B232.7

BELLOTA234.1

TESLA E231.0

SN LS PP

TESLA D232.4

TESLA C232.9

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.3

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310110 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

646.4

178.3

80.8

209.3

82.7

212.5

101.5

193.1

1193.9

81.9

1184.8

130.7

999.2 6.4

991.8

128.5

324.9 20.0

312.0

57.8

385.6 32.2

287.2

55.2

45.9

3.645.7

8.1

7.7

16.8

7.7

6.9

1974.1

39.2

1944.9

140.8

1685.3

34.3

1645.8

253.0

1.8

25.9

1.8

25.9

34.6

20.9

252.6 17.0

248.5

39.9

234.5 27.6

56.413.0

55.8 6.7

999.3 64.7

994.3 94.9

427.9

489.7

1050.6 122.8

156.4

39.0

156.4

39.0

970.9

60.3

964.0

65.9

768.4

97.3

235.4

66.8

99.3 8.8

127.3 34.5

198.5 30.9

96.011.4

235.6 56.2

232.2 69.8

272.0 48.9

278.1 23.2

190.9

20.0

202.9

19.7

212.5

21.4

223.7

66.9

228.1 51.7

222.0

68.3

173.9 38.9

178.1

25.8

229.8 50.1

228.5 59.7

238.4 22.8

1873.1

84.2

620.2

103.5

610.3

102.7

623.9

117.0

281.7 41.8281.7 41.8

225.9

30.9

229.2

13.4

229.2

13.4

229.2

13.4

229.3

13.4

225.9

30.9

233.6 9.1

229.3

12.9

229.3

12.9

233.6 9.1

77.5

3.9

76.0

4.4

170.8

18.2

200.1

39.7

182.9

24.9

155.5

21.7

219.2 43.9

86.519.5

185.1 41.6

315.7

62.7

169.1

49.9

738.6

84.9

120.1106.7

436.8 92.3

41.4109.4

130.9 1.4130.9 1.4

269.7 21.6

265.1 40.6

175.1

51.0

39.9

3.2

39.9

3.2

49.614.0

49.614.0

130.7 1.7130.7 1.7

437.9165.7

853.3269.1

843.6

199.9

1265.7 150.6

1259.4

223.2

1103.0 230.7

0.20.8

311.2 72.7

0.20.7

596.2

19.3

98.5

2.4

98.3

0.0

113.1

11.2

208.6

43.5

203.6

58.6

208.6

43.5

203.6

58.6

438.9212.5

66.421.433.210.733.210.7

65.9

25.3

65.9

25.3

330.9 59.5

192.7

46.0

191.6 45.9

192.7

46.0

191.6 45.9

1647.8

158.2

1630.1

443.9

45.8

7.7

45.810.5

Page 554: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 52-Outage: Panoche-Kearney 230kV & Kerckhoff amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:01 2008 2013sumop_q272_pst.sav

MIDWAY525.9

24156VINCENT

MIDWAY228.3

30057DIABLO

524.81.050

GATES522.0

GATES227.9

MORROBAY232.9

TEMPLETN

ARCO226.8

LOSBANOS512.6

30045MOSSLAND

515.11.030

GREGG231.2

HELMS PP233.0

HENRIETA227.8

PANOCHE230.1

HELM228.2

MCMULLN1

HERNDON231.2

LOSBANOS

229.9

COBURN228.7

TESLA525.4

TRACY530.3

METCALF518.4

METCALF231.6

BALCH3TP229.4

PINE FLT229.6

GATES227.9

KEARNEY230.7

30875MC CALL

229.40.997

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128230.3

Q239230.0

Q166228.9

Q194230.0

BORDEN231.5

STOREY 2231.3

STOREY 1231.6

WILSON231.2

WARNERVL232.7

DS AMIGO228.8

MELONES231.2

COTTLE A232.8

COTTLE B232.7

BELLOTA234.1

TESLA E231.0

SN LS PP

TESLA D232.4

TESLA C232.9

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.3

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310110 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

736.1

24.8

246.3

0.0

250.3

0.0

239.5

0.0

1313.8

44.3

1318.4

44.5

1099.3 37.1

1106.1

37.3

806.7 82.7

803.7

82.4

959.1 55.9

740.6

76.0

116.5

12.4118.1

12.6

47.0

5.0

26.2

2.8

2183.9

73.7

2196.4

74.1

1850.6

62.4

1875.5

63.3

64.9

3.3

64.9

3.3

45.5

4.0

635.4 65.2

632.2

64.8

592.4 69.7

145.2 17.1

142.0 16.7

1127.9 38.1

1119.6 37.8

708.0

23.9

1185.6 40.0

402.5

17.8

402.5

17.8

1075.9

24.8

1088.4

25.1

856.7

55.2

611.0

32.2

250.8 25.7

334.3 34.3

505.7 57.1

243.4 27.5

612.9 72.1

608.3 71.6

699.3 82.3

702.3 82.6

213.8

13.2

227.1

15.0

237.9

19.0

582.1

33.4

586.2 33.7

579.2

33.2

446.1 52.4

454.4

53.4

588.9 33.8

591.9 69.6

600.8 70.7

2111.9

71.3

690.3

56.0

679.5

55.2

696.9

56.6

713.8 38.4713.8 38.4

576.6

59.1

579.1

59.3

579.1

59.3

579.1

59.3

579.1

59.3

576.7

59.1

579.4 59.3

579.1

59.3

579.1

59.3

579.4 59.3

193.7

24.4

190.1

24.0

428.3

54.0

508.7

64.1

460.1

54.1

391.8

49.4

558.4 70.4

221.5 26.0

473.8 55.7

798.5

100.7

434.9

51.2

1867.3

109.8

176.6 14.3

490.6 39.8

128.5 7.9

324.8 18.9324.8 18.9

678.8 79.9

676.7 79.6

460.2

54.1

100.6

10.3

100.6

10.3

56.1 5.0

56.1 5.0

324.9 18.9324.9 18.9

514.5 17.4

983.2 36.0

943.7

34.6

1400.7 49.7

1388.2

49.3

1226.9 28.5

2.00.2

791.9 71.0

1.90.2

1510.9

79.2

249.1

13.2

248.9

13.2

288.0

15.7

539.6

63.5

531.7

62.6

539.6

63.5

531.7

62.6

543.1 18.3

173.1 46.586.646.586.646.5

346.5

36.9

346.5

36.9

834.0105.1

495.6

26.4

488.6 26.0

495.6

26.4

488.6 26.0

1864.5

62.9

1839.4

62.1

116.1

11.9

117.6

12.1

Page 555: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 53-Outage: Gates-Gregg & McCall 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:03 2008 2013sumop_q272_pre.sav

MIDWAY525.7

24156VINCENT

MIDWAY228.2

30057DIABLO

524.71.049

GATES521.7

GATES227.7

MORROBAY232.9

TEMPLETN

ARCO226.6

LOSBANOS512.3

30045MOSSLAND

514.91.030

GREGG231.3

HELMS PP233.1

HENRIETA223.9

PANOCHE229.7

HELM226.8

MCMULLN1

HERNDON231.3

LOSBANOS

229.7

COBURN228.5

TESLA525.3

TRACY530.1

METCALF518.3

METCALF231.5

BALCH3TP229.0

PINE FLT229.1

GATES227.7

KEARNEY230.7

30875MC CALL

228.60.994

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128229.6

Q239230.0

Q166228.9

Q194230.0

BORDEN231.6

STOREY 2231.5

STOREY 1231.7

WILSON231.3

WARNERVL232.8

DS AMIGO228.6

MELONES231.2

COTTLE A232.9

COTTLE B232.8

BELLOTA234.1

TESLA E231.0

SN LS PP

TESLA D232.3

TESLA C232.8

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.1

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310109 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

646.5

177.4

81.1

210.4

83.0

213.6

101.9

194.5

1193.2

86.3

1184.0

135.0

999.0 8.6

991.5

126.4

324.3 20.9

311.5

56.7

385.0 33.2

286.7

54.1

45.1

2.744.9

8.9

6.9

15.8

6.9

5.9

1978.6

39.4

1949.3

142.6

1688.1

36.3

1648.5

252.7

79.921.5

94.8

54.9

94.8

54.9

37.4

19.0

252.1 18.2

248.0

41.1

233.9 28.8

56.213.7

55.6 6.0

1000.9 66.1

995.8 96.9

427.2

488.2

1051.4 124.2

156.4

38.6

156.4

38.6

973.1

60.5

966.2

65.0

776.2

91.4

0.00.0

198.5 27.2

96.0 8.7

305.8 72.9

299.9101.2

349.1 68.7

359.3 19.3

190.8

19.5

202.8

19.2

212.4

20.8

223.6

67.1

228.0 51.9

222.0

68.5

173.7 39.2

177.9

26.2

229.7 50.3

227.8 60.9

237.7 24.0

1875.7

85.8

621.2

103.1

611.3

102.4

624.9

116.7

281.7 47.4281.7 47.4

226.4

31.0

229.8

13.4

229.8

13.4

229.8

13.4

229.8

13.4

226.4

31.0

234.1 9.3

229.9

12.9

229.9

12.9

234.1 9.3

96.5

0.5

94.7

0.3

155.7

17.1

182.4

38.1

165.2

22.9

140.5

20.3

207.9 43.5

81.819.0

180.5 41.5

308.4

61.3

164.7

48.7

739.4

87.2

121.5105.9

435.3 91.2

44.3108.2

130.6 1.0130.6 1.0

269.0 22.8

264.5 41.8

174.5

52.2

39.9

3.2

39.9

3.2

51.014.5

51.014.5

130.4 1.3130.4 1.3

439.0165.9

853.7269.8

843.9

200.8

1265.3 152.1

1259.1

224.7

1103.3 231.5

0.20.8

311.2 71.8

0.20.7

596.2

23.6

211.4

42.9

206.3

58.9

211.4

42.9

206.3

58.9

440.1212.5

64.621.132.310.632.310.6

64.1

24.8

64.1

24.8

323.6 58.2

191.8

46.3

190.6 46.1

191.8

46.3

190.6 46.1

1650.1

159.5

1632.4

446.9

24.2

19.8

24.322.9

Page 556: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 54-Outage: Gates-Gregg & McCall 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:05 2008 2013sumop_q272_pre.sav

MIDWAY525.7

24156VINCENT

MIDWAY228.2

30057DIABLO

524.71.049

GATES521.7

GATES227.7

MORROBAY232.9

TEMPLETN

ARCO226.6

LOSBANOS512.3

30045MOSSLAND

514.91.030

GREGG231.3

HELMS PP233.1

HENRIETA223.9

PANOCHE229.7

HELM226.8

MCMULLN1

HERNDON231.3

LOSBANOS

229.7

COBURN228.5

TESLA525.3

TRACY530.1

METCALF518.3

METCALF231.5

BALCH3TP229.0

PINE FLT229.1

GATES227.7

KEARNEY230.7

30875MC CALL

228.60.994

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128229.6

Q239230.0

Q166228.9

Q194230.0

BORDEN231.6

STOREY 2231.5

STOREY 1231.7

WILSON231.3

WARNERVL232.8

DS AMIGO228.6

MELONES231.2

COTTLE A232.9

COTTLE B232.8

BELLOTA234.1

TESLA E231.0

SN LS PP

TESLA D232.3

TESLA C232.8

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.1

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310109 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

736.2

24.8

247.7

0.0

251.7

0.0

241.2

0.0

1313.8

44.3

1318.8

44.5

1099.2 37.1

1106.2

37.3

805.7 82.6

802.8

82.3

958.0 55.9

739.8

75.9

114.4

12.2116.7

12.4

43.9

4.7

23.1

2.4

2190.2

73.9

2202.7

74.3

1854.4

62.6

1879.5

63.4

208.0 21.3

273.4

14.0

273.4

14.0

47.3

4.2

635.2 65.2

631.9

64.8

592.3 69.7

145.3 17.1

141.3 16.6

1130.4 38.1

1121.9 37.9

706.4

23.8

1187.2 40.1

402.1

17.8

402.1

17.8

1079.0

24.9

1091.4

25.2

864.9

55.7

0.00.0

506.0 57.1

243.5 27.5

800.4 94.2

795.5 93.6

905.7106.6

908.5106.9

213.7

13.2

226.9

15.0

237.7

19.0

582.2

33.4

586.3 33.7

579.3

33.3

445.9 52.4

454.3

53.4

589.0 33.8

591.3 69.6

600.5 70.7

2116.0

71.4

691.6

56.1

680.7

55.2

698.1

56.7

718.1 38.7718.1 38.7

578.1

59.2

580.6

59.5

580.6

59.5

580.6

59.5

580.6

59.5

578.2

59.2

580.9 59.5

580.7

59.5

580.7

59.5

580.9 59.5

240.9

30.4

236.5

29.8

390.6

49.2

464.4

58.6

415.6

48.8

354.0

44.6

530.3 66.9

209.7 24.6

462.4 54.4

779.6

98.3

423.5

49.8

1871.7

110.1

177.2 14.4

488.9 39.6

128.5 7.9

323.9 18.9323.9 18.9

678.6 79.8

676.4 79.6

460.1

54.1

100.7

10.3

100.7

10.3

57.7 5.1

57.7 5.1

324.0 18.9324.0 18.9

515.9 17.4

984.1 36.0

944.4

34.6

1400.8 49.7

1388.2

49.3

1227.7 28.6

2.00.2

791.1 71.0

1.90.2

1513.0

79.3

547.1

64.4

539.3

63.4

547.1

64.4

539.3

63.4

544.4 18.4

168.5 45.384.345.384.345.3

337.3

35.9

337.3

35.9

815.2102.8

493.6

26.3

486.5 25.9

493.6

26.3

486.5 25.9

1868.2

63.0

1843.1

62.2

78.2

8.0

83.5 8.6

Page 557: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 55-Outage: Gates-Gregg & McCall 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:06 2008 2013sumop_q272_pst.sav

MIDWAY525.6

24156VINCENT

MIDWAY228.2

30057DIABLO

524.71.049

GATES521.5

GATES227.6

MORROBAY232.9

TEMPLETN

ARCO226.5

LOSBANOS512.1

30045MOSSLAND

514.71.029

GREGG231.2

HELMS PP233.0

HENRIETA223.9

PANOCHE229.6

HELM226.5

MCMULLN1

HERNDON231.2

LOSBANOS

229.5

COBURN228.4

TESLA525.1

TRACY530.0

METCALF518.2

METCALF231.5

BALCH3TP228.9

PINE FLT229.0

GATES227.6

KEARNEY230.6

30875MC CALL

228.50.993

MOSSLND2

MOSSLND1

WESTLEY230.7

Q128229.5

Q239230.0

Q166228.8

Q194230.0

BORDEN231.5

STOREY 2231.3

STOREY 1231.6

WILSON231.1

WARNERVL232.7

DS AMIGO228.4

MELONES231.2

COTTLE A232.8

COTTLE B232.7

BELLOTA234.1

TESLA E230.9

SN LS PP

TESLA D232.3

TESLA C232.8

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.1

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310110 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

646.6

176.9

81.4

210.9

83.2

214.2

102.1

195.2

1192.7

88.0

1183.5

136.6

998.8 9.5

991.4

125.4

324.1 21.1

311.3

56.4

384.7 33.4

286.5

53.8

44.8

2.644.5

9.1

6.6

15.6

6.5

5.7

1980.6

40.9

1951.3

142.1

1689.3

38.0

1649.6

251.8

76.421.2

97.5

56.5

97.5

56.5

33.4

17.6

254.4 18.2

250.2

41.8

236.0 28.8

57.113.9

56.5 5.6

1002.6 66.3

997.5 97.7

430.1

487.0

1054.1 124.7

156.4

39.2

156.4

39.2

974.0

61.3

967.2

65.2

779.8

91.0

0.00.0

198.5 26.3

96.0 8.1

315.4 75.2

309.0105.8

359.7 71.4

370.5 18.2

191.5

19.0

203.5

18.7

213.2

20.4

224.4

67.5

228.8 52.1

222.7

68.9

174.5 39.7

178.8

26.3

230.5 50.5

229.6 62.0

239.7 24.1

1879.1

85.5

621.6

102.9

611.7

102.1

625.3

116.4

281.7 48.6281.7 48.6

226.6

31.1

230.0

13.4

230.0

13.3

230.0

13.3

230.0

13.3

226.6

31.1

234.3 9.4

230.1

12.8

230.1

12.8

234.3 9.4

93.8

0.6

92.1

1.3

158.4

17.1

185.5

38.2

168.4

23.0

143.1

20.4

212.1 44.3

83.619.7

182.3 41.5

311.3

62.2

166.4

49.1

742.2

88.0

121.7105.8

440.1 90.5

43.7108.1

131.6 0.7131.6 0.7

271.2 22.8

266.6 42.3

176.6

52.7

39.9

3.2

39.9

3.2

50.814.5

50.814.5

131.4 1.0131.4 1.0

439.5165.7

853.7270.5

843.9

201.7

1267.8 153.4

1261.5

226.8

1103.4 232.3

0.20.8

311.2 73.0

0.20.7

596.2

24.5

209.3

42.2

204.3

57.6

209.3

42.2

204.3

57.6

440.6212.3

65.221.232.610.632.610.6

64.7

25.0

64.7

25.0

326.5 59.0

192.8

46.6

191.6 46.5

192.8

46.6

191.6 46.5

1652.9

159.2

1635.1

448.4

20.7

19.2

20.822.3

Page 558: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 56-Outage: Gates-Gregg & McCall 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:08 2008 2013sumop_q272_pst.sav

MIDWAY525.6

24156VINCENT

MIDWAY228.2

30057DIABLO

524.71.049

GATES521.5

GATES227.6

MORROBAY232.9

TEMPLETN

ARCO226.5

LOSBANOS512.1

30045MOSSLAND

514.71.029

GREGG231.2

HELMS PP233.0

HENRIETA223.9

PANOCHE229.6

HELM226.5

MCMULLN1

HERNDON231.2

LOSBANOS

229.5

COBURN228.4

TESLA525.1

TRACY530.0

METCALF518.2

METCALF231.5

BALCH3TP228.9

PINE FLT229.0

GATES227.6

KEARNEY230.6

30875MC CALL

228.50.993

MOSSLND2

MOSSLND1

WESTLEY230.7

Q128229.5

Q239230.0

Q166228.8

Q194230.0

BORDEN231.5

STOREY 2231.3

STOREY 1231.6

WILSON231.1

WARNERVL232.7

DS AMIGO228.4

MELONES231.2

COTTLE A232.8

COTTLE B232.7

BELLOTA234.1

TESLA E230.9

SN LS PP

TESLA D232.3

TESLA C232.8

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.1

STANDFRD117.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

1310110 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

736.3

24.8

248.3

0.0

252.4

0.0

242.0

0.0

1313.7

44.3

1318.9

44.5

1099.2 37.1

1106.2

37.3

805.3 82.6

802.4

82.3

957.4 55.8

739.4

75.8

113.5

12.1115.8

12.3

43.1

4.6

22.0

2.3

2193.0

74.0

2205.6

74.4

1856.0

62.6

1881.2

63.5

199.3 20.4

281.3

14.4

281.3

14.4

42.6

3.8

641.3 65.8

638.0

65.4

598.0 70.4

147.7 17.4

143.6 16.9

1132.8 38.2

1124.2 37.9

707.8

23.9

1190.5 40.2

402.7

17.8

402.7

17.8

1080.4

24.9

1092.8

25.2

869.1

56.0

0.00.0

506.1 57.1

243.6 27.5

826.4 97.2

821.4 96.6

934.6110.0

937.5110.3

214.4

13.2

227.7

15.0

238.6

19.1

584.4

33.5

588.6 33.8

581.5

33.4

448.4 52.7

456.8

53.7

591.3 33.9

596.5 70.2

605.7 71.3

2120.7

71.6

692.1

56.2

681.2

55.3

698.7

56.7

719.1 38.7719.1 38.7

578.7

59.3

581.2

59.5

581.2

59.5

581.2

59.5

581.2

59.5

578.8

59.3

581.5 59.6

581.3

59.5

581.3

59.5

581.5 59.6

234.2

29.5

229.9

29.0

397.4

50.1

472.4

59.6

423.7

49.8

360.9

45.5

541.4 68.3

214.6 25.2

466.8 54.9

787.4

99.3

427.9

50.3

1879.9

110.6

177.3 14.4

494.0 40.0

128.2 7.9

326.6 19.1326.6 19.1

684.5 80.5

682.3 80.3

465.8

54.8

100.8

10.3

100.8

10.3

57.5 5.1

57.5 5.1

326.7 19.1326.7 19.1

516.4 17.4

984.6 36.1

944.8

34.6

1404.0 49.9

1391.3

49.4

1228.2 28.6

2.00.2

792.1 71.0

1.90.2

1513.5

79.3

541.6

63.7

533.8

62.8

541.6

63.7

533.8

62.8

544.9 18.4

170.1 45.785.145.785.145.7

340.4

36.3

340.4

36.3

823.0103.8

496.3

26.4

489.2 26.1

496.3

26.4

489.2 26.1

1872.0

63.2

1846.8

62.3

70.6

7.2

76.2 7.8

Page 559: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 57-Outage: Gates-Gregg & McCall 230kV Lines MW/MVAR

Rating = 2

fres_so_115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:10 2008 2013sumop_q272_pre.sav

MC CALL119.1

KINGSBRG118.0

KNGSCOGN

118.4

KINGSBUR8.988

34427GRDNGLS2

118.4

GRDN GLS118.5

CONTADNA116.9

HENRETTA113.9

CORCORAN116.7

CORCORAN73.53

QUEBEC112.4

ALPAUGH112.8

SMYRNA

113.6

HENRIETA223.9

MC CALL228.6

HENRITTA73.06

KNGLOBUS70.51

SUNMAID

SANGER117.8

WAHTOKE118.4

GERAWAN118.4

REEDLEY

118.0

RAINBW117.8

KNGSRVR1119.2

BALCH118.6

KINGSRIV13.66

BALCH 1

13.07

REEDLEY72.38

SANGER72.56

RAINBWTPPIEDRA 2

QUEBECTP34429

GWF_HEP 116.91.016

GWF_HEP113.66

GWF_HEP213.66

LEPRNOFD115.0

GAURD J2

KINGS J1

KCOGNJCT

GAURD J1

P0418119.2

P0418GT114.01

P0418GT214.01

P0418GT314.01

P0418GT414.01

to Air Products

to West Fresno

to McKibben

to 230 kV system

to Clovis #1 and #2to Malaga

to Las Palmas

to Barton

to Danish Cream

Fresno Southern 115-kV

0

18

1

1

33.0

0.4

1

24.0

4.1

1

50

16

1

50

16

1

0

12

1

79 22 1

79 22 2

79 22 3

79 22 4

5.7

4.3

1

2.60.9

1

8.45.9

1

2.7

0.6

1

7.4

1.5

3

8.2

1.7

4

2.6

2.5

1

13.9

2.8

2

7.4

1.5

1

15

3

1

15

3

3

12

7

1

31

2

92

3

3 2

ss

3 2

ss

3 2

ss

3 2

ss

11 2

4

14 3

5

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.0001.017

1.000

1.044

1.000

1.000 1.000

1.000

1.000

1.000

1.000

1.000

126.7

34.6

128.8 20.8

10.3

0.6

10.2

2.4

10.6

0.6

10.5

2.5

11.0 5.4

11.1

2.9

13.8 2.5

178.9 20.4

178.1

6.7

178.9 20.4

178.1

6.7

211.4 5.6

209.0

10.4

171.9 22.7

158.5 13.0

167.3 45.0

5.1

1.8

94.8 2.4

0.00.0

90.1 0.0

89.5 2.8

66.1 7.6

33.0

2.7

23.8

5.5

20.8

7.8

137.3

0.2

91.5

3.2

58.4

9.0

24.1

5.4

23.8

5.5

7.4

1.5

32.7 2.3

33.0 2.7

1.0

3.4

24.1

5.4

24.1 5.6

31.7 4.5

66.1 7.6

65.7

8.3

14.7

2.1

8.55.7

8.5

5.7

134.6 16.5

134.7 15.7

37.839.2

38.038.6

50.1

31.8

50.331.1

50.428.8

16.733.7

33.7

4.9

0.00.0

0.0

0.0

0.00.0

2.62.4

28.723.9

26.9

22.831.5

23.2

31.5

23.2

29.5

20.6

29.6

20.7

2.60.8

2.60.9

29.520.6

2.6

2.5

50.0

12.1

50.0

12.1

42.5 9.0

209.4

6.8

210.9

18.6

35.5 8.2

2.9

19.0

8.0

24.1

1.4

21.6

303.2 32.6

75.8 8.2

75.8 8.2

75.8 8.2

75.8 8.2

Page 560: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 58-Outage: Gates-Gregg & McCall 230kV Lines amps/rate

Rating = 2

fres_so_115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:12 2008 2013sumop_q272_pre.sav

MC CALL119.1

KINGSBRG118.0

KNGSCOGN

118.4

KINGSBUR8.988

34427GRDNGLS2

118.4

GRDN GLS118.5

CONTADNA116.9

HENRETTA113.9

CORCORAN116.7

CORCORAN73.53

QUEBEC112.4

ALPAUGH112.8

SMYRNA

113.6

HENRIETA223.9

MC CALL228.6

HENRITTA73.06

KNGLOBUS70.51

SUNMAID

SANGER117.8

WAHTOKE118.4

GERAWAN118.4

REEDLEY

118.0

RAINBW117.8

KNGSRVR1119.2

BALCH118.6

KINGSRIV13.66

BALCH 1

13.07

REEDLEY72.38

SANGER72.56

RAINBWTPPIEDRA 2

QUEBECTP34429

GWF_HEP 116.91.016

GWF_HEP113.66

GWF_HEP213.66

LEPRNOFD115.0

GAURD J2

KINGS J1

KCOGNJCT

GAURD J1

P0418119.2

P0418GT114.01

P0418GT214.01

P0418GT314.01

P0418GT414.01

to Air Products

to West Fresno

to McKibben

to 230 kV system

to Clovis #1 and #2to Malaga

to Las Palmas

to Barton

to Danish Cream

Fresno Southern 115-kV

0

18

1

1

33.0

0.4

1

24.0

4.1

1

50

16

1

50

16

1

0

12

1

79 22 1

79 22 2

79 22 3

79 22 4

5.7

4.3

1

2.60.9

1

8.45.9

1

2.7

0.6

1

7.4

1.5

3

8.2

1.7

4

2.6

2.5

1

13.9

2.8

2

7.4

1.5

1

15

3

1

15

3

3

12

7

1

31

2

92

3

3 2

ss

3 2

ss

3 2

ss

3 2

ss

11 2

4

14 3

5

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.0001.017

1.000

1.044

1.000

1.000 1.000

1.000

1.000

1.000

1.000

1.000

643.1

66.4

644.6 66.5

50.5

12.6

51.9

13.0

51.9

13.0

53.4

13.4

62.9 7.9

58.2

7.3

71.1 8.9

873.0 77.6

873.3

77.7

873.0 77.6

873.3

77.7

1025.3 105.3

1025.2

105.3

840.6 37.5

771.2 34.2

840.1 37.5

27.0

24.3

459.5 61.8

0.00.0

436.6 44.8

436.6 44.8

324.2 57.8

160.4

67.6

118.9

74.0

108.7

16.8

672.5

69.1

448.7

39.9

289.6

39.2

120.8

19.7

118.9

23.2

37.1

7.2

159.9 26.1

160.4 26.2

17.4

2.9

120.8

19.7

121.2 19.8

156.3 25.5

324.2 57.8

324.0

57.8

72.8

15.0

52.215.1

52.2

6.5

669.6 68.8

669.7 68.8

268.9 36.2

272.0 36.6

297.9

40.1

299.6 40.3

149.6 34.5

96.935.1

87.8

15.5

0.10.0

0.0

0.0

0.10.0

17.1 3.3

181.2 24.5

170.9

28.5190.3

25.8

191.7

25.9

175.7

23.8

176.7

23.9

13.4 3.9

13.5 3.9

175.7 29.3

17.4

3.4

253.9

48.2

253.9

48.2

210.5 18.7

1026.7

91.3

1037.4

92.3

176.5 15.7

94.3

39.1

124.4

50.8

172.0

46.0

1477.6 74.0

369.4 76.2

369.4 76.2

369.4 76.2

369.4 76.2

Page 561: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 59-Outage: Gates-Gregg & McCall 230kV Lines MW/MVAR

Rating = 2

fres_so_115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:13 2008 2013sumop_q272_pst.sav

MC CALL119.0

KINGSBRG117.7

KNGSCOGN

118.2

KINGSBUR8.975

34427GRDNGLS2

118.2

GRDN GLS118.3

CONTADNA116.6

HENRETTA113.9

CORCORAN116.5

CORCORAN73.39

QUEBEC112.4

ALPAUGH112.8

SMYRNA

113.6

HENRIETA223.9

MC CALL228.5

HENRITTA73.14

KNGLOBUS70.38

SUNMAID

SANGER117.7

WAHTOKE118.3

GERAWAN118.3

REEDLEY

117.9

RAINBW117.7

KNGSRVR1119.1

BALCH118.5

KINGSRIV13.66

BALCH 1

13.07

REEDLEY72.32

SANGER72.48

RAINBWTPPIEDRA 2

QUEBECTP34429

GWF_HEP 116.61.014

GWF_HEP113.66

GWF_HEP213.66

LEPRNOFD114.8

GAURD J2

KINGS J1

KCOGNJCT

GAURD J1

P0418119.0

P0418GT114.01

P0418GT214.01

P0418GT314.01

P0418GT414.01

to Air Products

to West Fresno

to McKibben

to 230 kV system

to Clovis #1 and #2to Malaga

to Las Palmas

to Barton

to Danish Cream

Fresno Southern 115-kV

0

21

1

1

33.0

0.1

1

24.0

3.9

1

50

18

1

50

18

1

0

13

1

79 22 1

79 22 2

79 22 3

79 22 4

5.7

4.3

1

2.60.9

1

8.45.9

1

2.7

0.6

1

7.4

1.5

3

8.2

1.7

4

2.6

2.5

1

13.9

2.8

2

7.4

1.5

1

15

3

1

15

3

3

12

7

1

31

2

92

3

3 2

ss

3 2

ss

3 2

ss

3 2

ss

11 2

4

14 3

5

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.0001.017

1.000

1.044

1.000

1.000 1.000

1.000

1.000

1.000

1.000

1.000

150.3

41.6

153.3 21.5

10.3

0.6

10.2

2.4

10.6

0.6

10.5

2.5

11.0 5.4

11.1

2.9

13.8 2.5

181.9 20.7

181.1

6.6

181.9 20.7

181.1

6.6

215.0 5.7

212.5

10.9

168.0 26.8

154.9 13.9

163.5 47.0

5.1

1.8

96.1 2.4

0.00.0

91.2 0.2

90.6 3.2

67.2 8.0

33.0

2.4

23.8

5.2

21.1

7.9

139.6

0.4

92.9

2.9

59.7

9.2

24.5

5.3

23.8

5.2

7.4

1.5

32.7 2.0

33.0 2.4

0.6

3.6

24.5

5.3

24.5 5.5

32.1 4.4

67.1 8.0

66.8

8.7

14.7

2.1

8.55.7

8.5

5.7

159.0 17.2

159.2 16.0

62.342.3

62.740.4

74.8

33.5

75.231.6

75.327.4

24.933.2

50.4

5.8

0.00.0

0.0

0.0

0.00.0

2.62.4

40.828.1

38.1

26.843.6

27.1

43.8

26.8

40.8

24.2

40.9

24.1

2.60.8

2.60.9

40.824.2

2.6

2.5

50.0

13.5

50.0

13.5

42.5 9.0

213.2

6.8

214.7

18.9

35.5 8.2

2.8

19.0

7.9

24.0

1.5

21.5

303.2 34.4

75.8 8.6

75.8 8.6

75.8 8.6

75.8 8.6

Page 562: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 60-Outage: Gates-Gregg & McCall 230kV Lines amps/rate

Rating = 2

fres_so_115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:15 2008 2013sumop_q272_pst.sav

MC CALL119.0

KINGSBRG117.7

KNGSCOGN

118.2

KINGSBUR8.975

34427GRDNGLS2

118.2

GRDN GLS118.3

CONTADNA116.6

HENRETTA113.9

CORCORAN116.5

CORCORAN73.39

QUEBEC112.4

ALPAUGH112.8

SMYRNA

113.6

HENRIETA223.9

MC CALL228.5

HENRITTA73.14

KNGLOBUS70.38

SUNMAID

SANGER117.7

WAHTOKE118.3

GERAWAN118.3

REEDLEY

117.9

RAINBW117.7

KNGSRVR1119.1

BALCH118.5

KINGSRIV13.66

BALCH 1

13.07

REEDLEY72.32

SANGER72.48

RAINBWTPPIEDRA 2

QUEBECTP34429

GWF_HEP 116.61.014

GWF_HEP113.66

GWF_HEP213.66

LEPRNOFD114.8

GAURD J2

KINGS J1

KCOGNJCT

GAURD J1

P0418119.0

P0418GT114.01

P0418GT214.01

P0418GT314.01

P0418GT414.01

to Air Products

to West Fresno

to McKibben

to 230 kV system

to Clovis #1 and #2to Malaga

to Las Palmas

to Barton

to Danish Cream

Fresno Southern 115-kV

0

21

1

1

33.0

0.1

1

24.0

3.9

1

50

18

1

50

18

1

0

13

1

79 22 1

79 22 2

79 22 3

79 22 4

5.7

4.3

1

2.60.9

1

8.45.9

1

2.7

0.6

1

7.4

1.5

3

8.2

1.7

4

2.6

2.5

1

13.9

2.8

2

7.4

1.5

1

15

3

1

15

3

3

12

7

1

31

2

92

3

3 2

ss

3 2

ss

3 2

ss

3 2

ss

11 2

4

14 3

5

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.0001.017

1.000

1.044

1.000

1.000 1.000

1.000

1.000

1.000

1.000

1.000

764.9

78.9

766.3 79.1

50.6

12.7

52.0

13.0

52.0

13.0

53.5

13.4

62.9 7.9

58.2

7.3

71.2 8.9

888.7 79.0

888.9

79.0

888.7 79.0

888.9

79.0

1043.7 107.2

1043.6

107.2

825.8 36.8

754.9 33.5

825.6 36.8

27.0

24.3

466.5 62.8

0.00.0

442.4 45.4

442.3 45.4

330.0 58.8

160.4

67.5

118.7

73.8

110.1

17.0

684.9

70.3

455.9

40.5

296.4

40.1

122.8

20.1

118.7

23.2

37.1

7.2

159.9 26.1

160.4 26.2

17.6

2.9

122.8

20.1

123.1 20.1

158.3 25.9

330.0 58.8

329.8

58.8

72.9

15.0

52.215.1

52.2

6.5

791.9 81.3

791.9 81.3

372.6 50.1

375.0 50.5

412.3

55.5

413.5 55.7

206.6 47.7

107.0 38.8

130.9

23.1

0.10.0

0.0

0.0

0.10.0

17.1 3.3

240.7 32.6

226.0

37.7250.6

33.9

251.8

34.1

232.0

31.4

233.0

31.5

13.5 3.9

13.5 3.9

232.0 38.7

17.4

3.4

256.1

48.5

256.1

48.5

210.7 18.7

1046.3

93.0

1057.3

94.0

176.7 15.7

94.2

39.1

124.1

50.6

171.7

45.9

1479.9 74.1

370.0 76.3

370.0 76.3

370.0 76.3

370.0 76.3

Page 563: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 61-Outage: Helm-McCall & Gates-McCall 230kV Lines MW/MVAR

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:17 2008 2013sumop_q272_pre.sav

HERNDON115.4

HERNDON229.4

BULLARD114.6

WOODWARD114.1

KERCKHF2116.4

SANGER116.6

MANCHSTR114.9

BARTON113.4

CHLDHOSP114.5

CLOVIS-1115.6

MC CALL118.4

MC CALL227.2

KERCKHF1116.3

KERCKHOF13.01

KERCKHOF6.592

CLOVIS-2116.1

SHARON115.6

CORSGOLD

114.8

OAKHURST

114.4

CHWCHLLA116.3

CERTTEED116.2

LE GRAND117.7

EXCHEQUR118.4

WILSON B120.0

WILSON230.5

DAIRYLND118.1

NEWHALL119.1

MADERAPR119.4

MENDOTA120.0

PANOCHE121.4

HAMMONDS120.8

EL CAPTN119.0

CASTLE118.7

ATWATER118.7

LIVNGSTN118.2

GALLO

118.1

WILSON A120.0

ORO LOMA119.6

EL NIDO119.5

MERCED

119.5

CANTUA121.1

WESTLNDS121.1

KAMM121.2

SCHINDLR121.2

PANOCHE231.5

EXCHEQUR

72.23

EXCHQUER13.25

CHENY121.4

SCHLNDLR73.48

AIRPROD117.2

MALAGA117.0

ULTR.PWR8.868

RANCHRS117.0

SCWAX117.0

PPG

117.0

WST FRSO115.8

DANISHCM115.8

CAL AVE115.7

OXFORD121.2

LUIS_#3121.1

LUIS_#5121.2

JR WOOD118.5

JRWD GEN118.6

CRESSEY118.4

MERCED

MENDOTA74.67

ORO LOMA73.20

PNEDLE114.6

WSTLD1RA121.2

DFS

120.1

PANOCHET

WHD_PAN214.21

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.4

CHOWCOGN

13.67

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.71

AIRWAYS114.5

LASPALMS114.8

P0418118.5

ATWATR JCRESEY T

MALAGATP

KRCDP117.0

KRCDPCT1

KRCDPCT214.02

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

3

1

0

40

1

0

30

1

44 16 1

38 6 1

0 2

1

0 2

2

0 2

3

15

13

1

44 1

1

29 3 1

1

13

7

1

1

1

081

v

0

9

v

0

9

v

09

v

41

2

11 2

1

41

1

3 1

1

2 1

1

3 1

1

8 2

1

98

1

14 3

1

13 3

2

51

1

71

2

10

1

12 2

2

3

3

1

16 3

1

12

2

1

12

2

2

17

3

3

23 5

1

20

4

1

17

3

2

12

3

3

21 4

1

20 4

2

19 4

3

3 1

1

19

4

1

24

5

2

20

4

3

5

4

1

7

5

1

4

1

1

6

1

2

6

1

1

92

1

11 2

2

15 3

3

61

1

71

2

8 2

1

3 1

1

17

3

1

18

4

2

4

1

1

2

1

1

12 2

1

10 2

2

11 2

3

5 3

1

4

2

1

13 3

1

3 3

1

6

1

1

11

1

41

ss

2 1

ss

18 3

1

61

2

10 9

1

11 2

1

21

1

23 5

2

20 4

3

11

ss

11

ss

82

3

14

3

2

19

4

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

96.527.6

161.7 4.6

16.017.3

212.7

23.9

145.8

22.5

171.4

10.5

111.2 1.7

66.5

15.0

23.4 4.7

224.4 9.0

190.4135.4

195.9 58.1

295.6 24.7

288.1 40.5

273.0 4.4

175.7

94.5

43.5 8.8

1.5

6.5

11.6

5.4

15.3 5.9

23.2

5.7

3.2

2.5

40.511.6

40.3

11.6

5.6

5.1

4.49.9

13.412.5

22.0

5.7

30.5

6.6

5.65.5

0.3

3.2

3.2

2.8

25.8

9.3

9.02.4

1.5

6.6

24.5

4.0

11.8

1.8

5.3

3.7

57.3

40.5

46.7

42.7

10.9

2.1

23.6 6.0

224.4 9.0

115.7 0.4

110.5 7.6

4.72.9

55.6 7.0

59.9 6.9

10.5

4.3

21.8

5.9

14.1

4.7

5.64.5

23.4 1.4

107.4 1.0

7.57.1

19.9

7.2

41.8 4.1

51.6 6.6

32.6

6.6

41.6 3.9

18.8 0.4

33.5

2.1

53.4

5.0

5.81.1

0.1

2.5

5.9

1.5

12.5 2.0

25.2

16.2

59.9

2.1

70.1

0.6

55.2

3.5

54.7 4.0

19.9 1.0

19.9 0.9

7.5

5.2

3.00.1

58.0

39.3

44.013.9

92.9

25.5

92.9

25.5

3.00.1

10.5

5.1

22.2 7.2

15.6

0.8

38.0 5.8

10.5

5.0

10.5

5.0

0.0

0.0

271.2 18.5

42.5 9.1

41.9

8.7

6.82.0

6.8

1.6

31.9

5.8

31.9 5.9

303.2

42.9

0.0

0.0

0.0

0.0

25.0

16.7

0.00.0

8.510.2

25.0 1.1

17.2

9.017.2

9.1

8.41.3

11.5

6.1

92.9

34.6

93.5

31.2

35.5 8.3

35.0

8.5

254.3 47.1

25.512.9

223.8

76.3

268.7 1.3

2.28.4

261.9

22.5

14.5

12.4

79.2 8.5

78.610.8

4.2

0.9

2.0

1.2

6.21.9124.9

4.5

118.6 2.4

118.6 2.3

2.11.2

1.10.7

1.10.7

18.2

3.9

6.6

1.2

74.9

47.2

73.251.5

67.629.2

Page 564: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 62-Outage: Helm-McCall & Gates-McCall 230kV Lines amps/rate

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:18 2008 2013sumop_q272_pre.sav

HERNDON115.4

HERNDON229.4

BULLARD114.6

WOODWARD114.1

KERCKHF2116.4

SANGER116.6

MANCHSTR114.9

BARTON113.4

CHLDHOSP114.5

CLOVIS-1115.6

MC CALL118.4

MC CALL227.2

KERCKHF1116.3

KERCKHOF13.01

KERCKHOF6.592

CLOVIS-2116.1

SHARON115.6

CORSGOLD

114.8

OAKHURST

114.4

CHWCHLLA116.3

CERTTEED116.2

LE GRAND117.7

EXCHEQUR118.4

WILSON B120.0

WILSON230.5

DAIRYLND118.1

NEWHALL119.1

MADERAPR119.4

MENDOTA120.0

PANOCHE121.4

HAMMONDS120.8

EL CAPTN119.0

CASTLE118.7

ATWATER118.7

LIVNGSTN118.2

GALLO

118.1

WILSON A120.0

ORO LOMA119.6

EL NIDO119.5

MERCED

119.5

CANTUA121.1

WESTLNDS121.1

KAMM121.2

SCHINDLR121.2

PANOCHE231.5

EXCHEQUR

72.23

EXCHQUER13.25

CHENY121.4

SCHLNDLR73.48

AIRPROD117.2

MALAGA117.0

ULTR.PWR8.868

RANCHRS117.0

SCWAX117.0

PPG

117.0

WST FRSO115.8

DANISHCM115.8

CAL AVE115.7

OXFORD121.2

LUIS_#3121.1

LUIS_#5121.2

JR WOOD118.5

JRWD GEN118.6

CRESSEY118.4

MERCED

MENDOTA74.67

ORO LOMA73.20

PNEDLE114.6

WSTLD1RA121.2

DFS

120.1

PANOCHET

WHD_PAN214.21

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.4

CHOWCOGN

13.67

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.71

AIRWAYS114.5

LASPALMS114.8

P0418118.5

ATWATR JCRESEY T

MALAGATP

KRCDP117.0

KRCDPCT1

KRCDPCT214.02

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

3

1

0

40

1

0

30

1

44 16 1

38 6 1

0 2

1

0 2

2

0 2

3

15

13

1

44 1

1

29 3 1

1

13

7

1

1

1

081

v

0

9

v

0

9

v

09

v

41

2

11 2

1

41

1

3 1

1

2 1

1

3 1

1

8 2

1

98

1

14 3

1

13 3

2

51

1

71

2

10

1

12 2

2

3

3

1

16 3

1

12

2

1

12

2

2

17

3

3

23 5

1

20

4

1

17

3

2

12

3

3

21 4

1

20 4

2

19 4

3

3 1

1

19

4

1

24

5

2

20

4

3

5

4

1

7

5

1

4

1

1

6

1

2

6

1

1

92

1

11 2

2

15 3

3

61

1

71

2

8 2

1

3 1

1

17

3

1

18

4

2

4

1

1

2

1

1

12 2

1

10 2

2

11 2

3

5 3

1

4

2

1

13 3

1

3 3

1

6

1

1

11

1

41

ss

2 1

ss

18 3

1

61

2

10 9

1

11 2

1

21

1

23 5

2

20 4

3

11

ss

11

ss

82

3

14

3

2

19

4

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

507.9 52.1

813.9 83.6

116.9 15.7

1089.8

96.9

742.4

99.9

857.1

88.0

550.7 49.0

338.3

48.1

119.0 10.6

1111.5 98.8

1168.4 50.6

1021.8 44.1

1446.1 64.2

1418.5 63.0

1331.5 58.7

998.1

88.8

220.6 19.6

33.3

8.4

32.1

4.0

78.916.7

115.6

15.7

19.8

5.7

202.5 22.9

203.5

23.0

36.7

5.0

52.6 4.4

89.317.4

110.9

11.4

151.5

13.5

38.0 3.9

15.3

3.0

20.3

4.0

131.9

17.8

45.4 8.9

590.1

15.0

124.2

35.9

60.3

17.7

32.4

9.4

348.5

87.9

314.1

61.3

52.9

10.3

116.0 16.9

1111.5 98.8

564.3 75.9

545.7 73.4

27.445.5

273.4 45.6

294.0 39.8

55.7

7.5

110.8

27.8

72.6

14.2

35.0 4.7

116.2 22.7

523.9 53.8

49.812.5

102.2

20.0

210.1 12.7

260.4 15.7

167.4

22.5

210.5 28.3

95.012.8

162.1

46.6

259.0

42.6

28.2 5.5

12.0

2.3

28.9

5.6

60.511.8

142.3

17.8

285.1

46.9

333.3

29.6

264.1

43.5

263.9 43.4

96.233.2

96.233.2

45.2

13.0

15.0 4.3

349.8

88.2

229.0 25.6

477.9

64.3

477.9

64.3

15.1 4.3

57.9

16.7

114.1 23.4

124.8

15.6

1674.9 38.4

57.6

92.9

57.6

11.3

0.0

0.0

1345.3 119.6

211.8 18.8

213.4

19.0

35.5 4.8

35.0

4.7

161.8

14.4

161.9 14.4

1492.0

74.7

0.0

0.0

0.1

0.0

144.7

14.9

0.00.0

64.117.8

121.0 67.1

94.6

18.594.6

18.5

41.5

8.1

32.6

2.8

496.1

50.9

496.7

51.0

177.6 15.8

179.6

16.0

1300.5 115.6

144.4 14.8

1188.3

105.7

1330.1 118.3

43.6 4.5

1338.1

119.0

93.9

92.0

393.0 53.2

392.7 53.1

21.1

4.1

11.5

3.3

32.2 6.3616.2

82.9

585.2 78.8

585.2 78.8

12.0 1.4

6.11.8

6.11.8

46.5

5.0

16.7

4.7

434.0

84.8

430.8 84.1

367.7 92.7

Page 565: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 63-Outage: Helm-McCall & Gates-McCall 230kV Lines MW/MVAR

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:20 2008 2013sumop_q272_pst.sav

HERNDON115.4

HERNDON229.3

BULLARD114.6

WOODWARD114.1

KERCKHF2116.3

SANGER116.6

MANCHSTR114.8

BARTON113.4

CHLDHOSP114.5

CLOVIS-1115.5

MC CALL118.4

MC CALL227.2

KERCKHF1116.3

KERCKHOF13.01

KERCKHOF6.592

CLOVIS-2116.1

SHARON115.5

CORSGOLD

114.8

OAKHURST

114.4

CHWCHLLA116.2

CERTTEED116.2

LE GRAND117.7

EXCHEQUR118.4

WILSON B119.9

WILSON230.4

DAIRYLND118.1

NEWHALL119.1

MADERAPR119.4

MENDOTA120.0

PANOCHE121.4

HAMMONDS120.8

EL CAPTN119.0

CASTLE118.7

ATWATER118.6

LIVNGSTN118.2

GALLO

118.1

WILSON A120.0

ORO LOMA119.6

EL NIDO119.5

MERCED

119.5

CANTUA121.0

WESTLNDS121.1

KAMM121.2

SCHINDLR121.2

PANOCHE231.4

EXCHEQUR

72.22

EXCHQUER13.25

CHENY121.3

SCHLNDLR73.46

AIRPROD117.2

MALAGA117.0

ULTR.PWR8.867

RANCHRS117.0

SCWAX117.0

PPG

117.0

WST FRSO115.8

DANISHCM115.8

CAL AVE115.7

OXFORD121.2

LUIS_#3121.1

LUIS_#5121.1

JR WOOD118.5

JRWD GEN118.5

CRESSEY118.4

MERCED

MENDOTA74.65

ORO LOMA73.18

PNEDLE114.6

WSTLD1RA121.2

DFS

120.0

PANOCHET

WHD_PAN214.20

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.4

CHOWCOGN

13.67

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.71

AIRWAYS114.5

LASPALMS114.8

P0418118.5

ATWATR JCRESEY T

MALAGATP

KRCDP117.0

KRCDPCT1

KRCDPCT214.02

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

3

1

0

40

1

0

30

1

44 16 1

38 6 1

0 2

1

0 2

2

0 2

3

15

13

1

43 1

1

29 4 1

1

13

7

1

1

1

081

v

0

9

v

0

9

v

09

v

41

2

11 2

1

41

1

3 1

1

2 1

1

3 1

1

8 2

1

98

1

14 3

1

13 3

2

51

1

71

2

10

1

12 2

2

3

3

1

16 3

1

12

2

1

12

2

2

17

3

3

23 5

1

20

4

1

17

3

2

12

3

3

21 4

1

20 4

2

19 4

3

3 1

1

19

4

1

24

5

2

20

4

3

5

4

1

7

5

1

4

1

1

6

1

2

6

1

1

92

1

11 2

2

15 3

3

61

1

71

2

8 2

1

3 1

1

17

3

1

18

4

2

4

1

1

2

1

1

12 2

1

10 2

2

11 2

3

5 3

1

4

2

1

13 3

1

3 3

1

6

1

1

11

1

41

ss

2 1

ss

18 3

1

61

2

10 9

1

11 2

1

21

1

23 5

2

20 4

3

11

ss

11

ss

82

3

14

3

2

19

4

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

96.627.6

161.7 4.5

15.817.4

213.0

23.8

146.0

22.5

171.7

10.5

111.5 1.7

66.7

15.0

23.4 4.7

224.6 9.1

190.6135.4

196.1 58.2

295.6 24.9

288.1 40.6

273.0 4.5

175.9

94.6

43.5 8.8

1.5

6.5

11.6

5.4

15.3 5.9

23.2

5.7

3.2

2.5

40.511.6

40.3

11.6

5.6

5.1

4.49.9

13.412.5

21.8

5.8

30.4

6.7

5.45.5

0.4

3.2

3.3

2.8

25.8

9.3

9.02.4

1.5

6.5

24.5

4.0

11.8

1.8

5.3

3.7

57.6

40.6

47.0

42.8

11.0

2.1

23.8 6.1

224.6 9.1

115.8 0.3

110.6 7.6

4.72.9

55.1 6.9

59.3 6.8

10.3

4.4

21.8

5.8

14.1

4.7

5.64.5

23.4 1.4

107.5 0.9

7.37.1

19.8

7.1

41.8 4.1

51.6 6.6

32.6

6.6

41.6 3.9

18.8 0.4

33.7

2.1

53.5

5.0

5.81.1

0.2

2.5

6.0

1.6

12.6 2.0

25.0

16.2

59.9

2.0

70.1

0.5

55.2

3.4

54.8 3.9

19.9 1.0

19.9 0.9

7.5

5.2

3.00.1

58.4

39.4

44.013.9

93.3

25.5

93.3

25.5

3.00.1

10.5

5.1

22.2 7.1

15.6

0.8

38.0 5.7

10.5

5.0

10.5

5.0

0.0

0.0

271.4 18.5

42.5 9.1

41.9

8.7

6.82.0

6.8

1.6

31.9

5.8

31.9 5.9

303.2

43.0

0.0

0.0

0.0

0.0

24.9

16.7

0.00.0

8.610.2

25.0 1.1

17.2

9.017.2

9.1

8.41.3

11.5

6.1

93.0

34.6

93.6

31.2

35.5 8.3

35.0

8.5

254.6 47.1

25.613.0

224.0

76.3

269.0 1.2

2.28.4

262.1

22.4

14.5

12.4

79.3 8.4

78.710.8

4.2

0.9

2.0

1.2

6.21.9125.1

4.5

118.8 2.4

118.7 2.3

2.11.2

1.00.7

1.00.7

18.4

3.7

6.7

1.3

75.0

47.2

73.451.6

68.029.3

Page 566: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 64-Outage: Helm-McCall & Gates-McCall 230kV Lines amps/rate

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:22 2008 2013sumop_q272_pst.sav

HERNDON115.4

HERNDON229.3

BULLARD114.6

WOODWARD114.1

KERCKHF2116.3

SANGER116.6

MANCHSTR114.8

BARTON113.4

CHLDHOSP114.5

CLOVIS-1115.5

MC CALL118.4

MC CALL227.2

KERCKHF1116.3

KERCKHOF13.01

KERCKHOF6.592

CLOVIS-2116.1

SHARON115.5

CORSGOLD

114.8

OAKHURST

114.4

CHWCHLLA116.2

CERTTEED116.2

LE GRAND117.7

EXCHEQUR118.4

WILSON B119.9

WILSON230.4

DAIRYLND118.1

NEWHALL119.1

MADERAPR119.4

MENDOTA120.0

PANOCHE121.4

HAMMONDS120.8

EL CAPTN119.0

CASTLE118.7

ATWATER118.6

LIVNGSTN118.2

GALLO

118.1

WILSON A120.0

ORO LOMA119.6

EL NIDO119.5

MERCED

119.5

CANTUA121.0

WESTLNDS121.1

KAMM121.2

SCHINDLR121.2

PANOCHE231.4

EXCHEQUR

72.22

EXCHQUER13.25

CHENY121.3

SCHLNDLR73.46

AIRPROD117.2

MALAGA117.0

ULTR.PWR8.867

RANCHRS117.0

SCWAX117.0

PPG

117.0

WST FRSO115.8

DANISHCM115.8

CAL AVE115.7

OXFORD121.2

LUIS_#3121.1

LUIS_#5121.1

JR WOOD118.5

JRWD GEN118.5

CRESSEY118.4

MERCED

MENDOTA74.65

ORO LOMA73.18

PNEDLE114.6

WSTLD1RA121.2

DFS

120.0

PANOCHET

WHD_PAN214.20

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.80

CHWCGNJT

CERTANJ2

CHWCGN

116.4

CHOWCOGN

13.67

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.71

AIRWAYS114.5

LASPALMS114.8

P0418118.5

ATWATR JCRESEY T

MALAGATP

KRCDP117.0

KRCDPCT1

KRCDPCT214.02

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

3

1

0

40

1

0

30

1

44 16 1

38 6 1

0 2

1

0 2

2

0 2

3

15

13

1

43 1

1

29 4 1

1

13

7

1

1

1

081

v

0

9

v

0

9

v

09

v

41

2

11 2

1

41

1

3 1

1

2 1

1

3 1

1

8 2

1

98

1

14 3

1

13 3

2

51

1

71

2

10

1

12 2

2

3

3

1

16 3

1

12

2

1

12

2

2

17

3

3

23 5

1

20

4

1

17

3

2

12

3

3

21 4

1

20 4

2

19 4

3

3 1

1

19

4

1

24

5

2

20

4

3

5

4

1

7

5

1

4

1

1

6

1

2

6

1

1

92

1

11 2

2

15 3

3

61

1

71

2

8 2

1

3 1

1

17

3

1

18

4

2

4

1

1

2

1

1

12 2

1

10 2

2

11 2

3

5 3

1

4

2

1

13 3

1

3 3

1

6

1

1

11

1

41

ss

2 1

ss

18 3

1

61

2

10 9

1

11 2

1

21

1

23 5

2

20 4

3

11

ss

11

ss

82

3

14

3

2

19

4

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.043

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000 1.000

508.3 52.2

814.4 83.6

116.5 15.7

1091.1

97.0

743.7

100.1

858.4

88.1

551.8 49.1

339.4

48.3

119.1 10.6

1112.9 99.0

1169.7 50.6

1023.4 44.1

1446.3 64.2

1418.6 63.0

1331.5 58.7

999.4

88.9

220.6 19.6

32.9

8.3

32.1

4.0

78.916.7

115.6

15.7

19.8

5.7

202.6 22.9

203.5

23.0

36.7

5.0

52.7 4.4

89.317.4

110.3

11.3

150.8

13.4

37.4 3.8

15.5

3.0

20.6

4.0

131.9

17.8

45.4 8.9

584.4

14.8

124.2

35.9

60.3

17.7

32.4

9.4

350.3

88.3

315.9

61.7

53.3

10.4

116.9 17.0

1112.9 99.0

564.9 76.0

546.3 73.5

27.345.3

270.8 45.1

291.2 39.4

55.1

7.4

110.7

27.8

72.6

14.2

35.0 4.7

116.2 22.7

524.4 53.8

49.112.3

101.4

19.8

210.1 12.7

260.5 15.7

167.4

22.5

210.5 28.3

95.012.8

163.1

46.9

259.3

42.7

28.2 5.5

12.1

2.4

29.3

5.7

60.911.9

141.8

17.8

285.3

47.0

333.6

29.7

264.3

43.5

264.1 43.5

96.233.2

96.233.2

45.2

13.0

15.1 4.3

351.7

88.7

229.0 25.6

479.9

64.6

479.9

64.6

15.1 4.3

57.9

16.7

113.9 23.4

124.8

15.6

1674.3 38.4

57.6

92.9

57.7

11.3

0.0

0.0

1346.7 119.8

211.8 18.8

213.4

19.0

35.6 4.8

35.0

4.7

161.8

14.4

161.9 14.4

1492.1

74.7

0.0

0.0

0.1

0.0

144.2

14.8

0.00.0

64.217.8

121.0 67.1

94.6

18.594.7

18.5

41.5

8.1

32.6

2.8

496.5

51.0

497.1

51.0

177.6 15.8

179.6

16.0

1301.8 115.8

144.5 14.8

1189.7

105.8

1331.5 118.4

43.7 4.5

1339.5

119.1

93.9

92.0

393.7 53.3

393.3 53.2

21.1

4.1

11.5

3.3

32.2 6.3616.8

83.0

585.9 78.9

585.9 78.9

12.0 1.4

6.11.8

6.11.8

46.9

5.1

16.9

4.7

434.8

84.9

431.6 84.3

369.6 93.2

Page 567: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 65-Herndon-Ashlan & Gregg-Ashlan 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:23 2008 2013sumop_q272_pre.sav

MIDWAY526.4

24156VINCENT

MIDWAY228.4

30057DIABLO

525.11.050

GATES522.8

GATES228.1

MORROBAY233.0

TEMPLETN

ARCO226.9

LOSBANOS513.8

30045MOSSLAND

516.11.032

GREGG229.7

HELMS PP232.7

HENRIETA227.4

PANOCHE230.4

HELM228.4

MCMULLN1

HERNDON229.8

LOSBANOS

230.5

COBURN229.1

TESLA526.3

TRACY531.2

METCALF519.3

METCALF231.9

BALCH3TP229.4

PINE FLT229.6

GATES228.1

KEARNEY229.5

30875MC CALL

229.40.998

MOSSLND2

MOSSLND1

WESTLEY231.3

Q128230.3

Q239230.0

Q166229.1

Q194230.0

BORDEN230.3

STOREY 2230.3

STOREY 1230.6

WILSON230.9

WARNERVL232.9

DS AMIGO229.4

MELONES231.3

COTTLE A233.0

COTTLE B232.9

BELLOTA234.3

TESLA E231.4

SN LS PP

TESLA D232.7

TESLA C233.1

Q235SWST233.0

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.4

STANDFRD117.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

310113 1310114 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

645.8

181.2

78.9

205.9

80.7

209.0

99.3

188.5

1198.6

71.7

1189.4

120.5

1000.4 0.6

992.9

134.4

327.3 19.9

314.3

59.3

388.0 32.2

289.4

56.6

50.4

3.950.2

7.4

12.2

17.6

12.1

7.7

1948.7

27.3

1920.4

142.4

1670.8

22.2

1632.1

257.3

76.6 9.1

87.8

43.0

87.8

43.0

56.8

23.6

237.7 19.6

234.1

38.5

220.5 29.4

50.312.8

49.9 7.8

982.8 63.2

977.9 88.4

404.0

497.7

1028.9 119.8

313.8

55.5

313.8

55.5

958.6

53.9

952.0

65.0

725.1

95.1

252.3

63.7

95.2 9.3

104.2 31.2

198.5 31.1

96.011.5

236.5 58.2

233.0 71.9

272.5 50.8

278.6 24.9

185.4

22.8

197.1

22.7

206.4

24.5

217.9

64.3

221.9 50.6

216.2

65.6

168.2 36.6

172.1

25.8

223.7 49.0

216.5 54.4

225.3 23.7

1842.3

87.3

615.3

105.3

605.5

104.5

618.9

118.9

281.7 41.6281.7 41.6

223.8

30.5

227.0

13.5

227.1

13.5

227.1

13.5

227.1

13.5

223.8

30.5

231.3 8.2

227.1

13.1

227.1

13.1

231.3 8.2

100.8

19.1

98.8

19.6

150.2

23.2

175.7

45.0

158.6

29.9

134.9

26.3

193.8 46.5

75.720.1

174.5 42.2

297.8

61.5

158.9

48.1

717.3

82.1

117.3108.3

398.8 96.9

43.9111.0

122.7 3.1122.7 3.1

255.5 23.6

251.4 39.8

161.4

50.2

39.9

3.1

39.9

3.1

49.613.5

49.613.5

122.6 3.6122.6 3.6

434.0166.8

853.1264.3

843.4

194.1

1246.3 141.2

1240.3

208.4

1102.5 225.0

311.2 76.0

311.2 76.5

0.20.7

596.2

16.9

94.5

2.4

94.3

0.2

154.1

3.9

214.7

45.2

209.4

62.0

214.7

45.2

209.4

62.0

435.0214.1

63.021.631.510.831.510.8

62.5

25.1

62.5

25.1

313.0 58.5

186.1

44.7

185.0 43.8

186.1

44.7

185.0 43.8

1622.7

160.6

1605.7

431.5

21.0

7.0

21.010.1

Page 568: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Pre-Project Case

PATH15= 5001 MW(S-N) PATH26= 253 MW(N-S) PDCI=-1846 MW(N-S) COI=-3647 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Pre-Project FY

Plot 66-Herndon-Ashlan & Gregg-Ashlan 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:25 2008 2013sumop_q272_pre.sav

MIDWAY526.4

24156VINCENT

MIDWAY228.4

30057DIABLO

525.11.050

GATES522.8

GATES228.1

MORROBAY233.0

TEMPLETN

ARCO226.9

LOSBANOS513.8

30045MOSSLAND

516.11.032

GREGG229.7

HELMS PP232.7

HENRIETA227.4

PANOCHE230.4

HELM228.4

MCMULLN1

HERNDON229.8

LOSBANOS

230.5

COBURN229.1

TESLA526.3

TRACY531.2

METCALF519.3

METCALF231.9

BALCH3TP229.4

PINE FLT229.6

GATES228.1

KEARNEY229.5

30875MC CALL

229.40.998

MOSSLND2

MOSSLND1

WESTLEY231.3

Q128230.3

Q239230.0

Q166229.1

Q194230.0

BORDEN230.3

STOREY 2230.3

STOREY 1230.6

WILSON230.9

WARNERVL232.9

DS AMIGO229.4

MELONES231.3

COTTLE A233.0

COTTLE B232.9

BELLOTA234.3

TESLA E231.4

SN LS PP

TESLA D232.7

TESLA C233.1

Q235SWST233.0

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.4

STANDFRD117.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

310113 1310114 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

735.6

24.8

241.8

0.0

245.7

0.0

233.6

0.0

1316.8

44.4

1320.1

44.5

1099.9 37.1

1106.4

37.3

812.7 83.4

809.5

83.0

965.0 56.3

746.4

76.6

127.9

13.6129.0

13.7

54.4

5.8

36.4

3.9

2152.1

72.6

2163.7

73.0

1832.5

61.8

1856.5

62.6

193.3 19.8

245.7

12.6

245.7

12.6

69.1

6.1

597.6 61.3

594.2

60.9

557.3 65.6

130.0 15.3

127.2 14.9

1106.6 37.3

1098.5 37.1

696.7

23.5

1158.7 39.1

800.8

35.4

800.8

35.4

1060.3

24.5

1072.2

24.7

807.6

52.2

653.9

34.5

240.6 24.7

276.1 28.3

505.7 57.1

243.4 27.5

615.7 72.4

610.9 71.9

700.7 82.4

703.9 82.8

207.7

12.8

220.6

14.6

231.1

18.5

565.7

32.5

569.7 32.7

562.7

32.3

430.4 50.6

438.6

51.5

572.5 32.9

558.7 65.7

567.6 66.8

2072.3

69.9

684.6

55.6

673.8

54.8

691.1

56.2

713.6 38.4713.6 38.4

570.7

58.4

573.2

58.7

573.2

58.7

573.2

58.7

573.2

58.7

570.7

58.5

573.6 58.7

573.2

58.7

573.2

58.7

573.6 58.7

257.9

32.5

253.1

31.9

380.9

48.0

454.6

57.3

404.1

47.5

344.6

43.4

498.2 62.8

195.8 23.0

448.2 52.7

753.7

95.0

409.1

48.1

1808.2

106.4

175.2 14.2

450.2 36.6

130.9 8.1

304.1 17.7304.1 17.7

642.8 75.6

640.5 75.4

425.3

50.0

100.3

10.3

100.3

10.3

55.8 4.9

55.8 4.9

304.2 17.7304.2 17.7

510.0 17.2

979.7 35.9

941.1

34.5

1376.0 48.9

1364.1

48.4

1223.0 28.4

794.9 71.2

795.2 71.2

1.90.2

1509.7

79.1

238.7

12.6

238.6

12.6

390.2

21.2

555.3

65.3

547.2

64.4

555.3

65.3

547.2

64.4

539.0 18.2

165.0 44.482.544.482.544.4

330.2

35.2

330.2

35.2

789.2 99.5

477.9

25.4

470.9 25.1

477.9

25.4

470.9 25.1

1832.2

61.8

1807.1

61.0

55.7

5.7

58.7 6.0

Page 569: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 67-Herndon-Ashlan & Gregg-Ashlan 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:26 2008 2013sumop_q272_pst.sav

MIDWAY526.3

24156VINCENT

MIDWAY228.4

30057DIABLO

525.01.050

GATES522.6

GATES228.0

MORROBAY233.0

TEMPLETN

ARCO226.9

LOSBANOS513.6

30045MOSSLAND

515.91.032

GREGG229.7

HELMS PP232.7

HENRIETA227.5

PANOCHE230.4

HELM228.3

MCMULLN1

HERNDON229.7

LOSBANOS

230.4

COBURN229.0

TESLA526.1

TRACY531.0

METCALF519.1

METCALF231.8

BALCH3TP229.4

PINE FLT229.6

GATES228.0

KEARNEY229.5

30875MC CALL

229.40.998

MOSSLND2

MOSSLND1

WESTLEY231.2

Q128230.3

Q239230.0

Q166229.1

Q194230.0

BORDEN230.3

STOREY 2230.3

STOREY 1230.5

WILSON230.9

WARNERVL232.9

DS AMIGO229.3

MELONES231.2

COTTLE A233.0

COTTLE B232.9

BELLOTA234.3

TESLA E231.3

SN LS PP

TESLA D232.7

TESLA C233.1

Q235SWST232.9

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.4

STANDFRD117.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

310114 1310114 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

645.9

180.6

79.3

206.6

81.2

209.7

99.8

189.5

1197.4

73.9

1188.3

122.8

1000.1 1.8

992.6

133.1

326.7 20.0

313.7

58.9

387.4 32.2

288.8

56.2

49.3

3.849.0

7.6

11.1

17.3

11.0

7.5

1955.1

29.4

1926.6

142.8

1674.5

24.6

1635.6

256.8

75.0 9.2

86.9

42.8

86.9

42.8

55.6

23.6

239.1 19.3

235.5

38.6

221.8 29.2

50.912.8

50.5 7.6

986.3 63.7

981.4 90.0

407.8

496.1

1032.4 120.5

313.8

55.7

313.8

55.7

961.7

55.1

955.1

64.9

736.0

94.8

257.8

65.0

95.2 9.1

127.8 32.0

198.5 31.1

96.011.4

237.7 58.1

234.2 72.0

273.8 50.7

280.0 24.5

186.3

22.2

198.0

22.2

207.4

23.9

218.7

64.6

222.8 50.8

217.0

66.0

168.8 36.9

172.8

25.8

224.5 49.2

217.8 55.0

226.7 23.7

1848.0

87.0

616.5

105.0

606.7

104.2

620.1

118.6

281.7 41.7281.7 41.7

224.3

30.6

227.6

13.5

227.6

13.5

227.6

13.5

227.6

13.5

224.3

30.6

231.9 8.4

227.7

13.0

227.7

13.0

231.9 8.4

99.0

19.4

97.0

19.8

151.9

23.1

177.7

45.0

160.6

29.9

136.6

26.3

196.3 46.8

76.820.4

175.6 42.2

299.6

61.8

159.9

48.3

720.2

82.6

118.0107.9

404.6 95.9

44.1110.5

124.0 2.8124.0 2.8

256.8 23.4

252.7 39.9

162.7

50.2

39.9

3.2

39.9

3.2

49.913.7

49.913.7

123.8 3.3123.8 3.3

434.6166.5

853.3265.1

843.6

195.2

1249.5 142.9

1243.4

211.0

1102.7 226.0

311.2 76.2

311.2 76.7

0.20.7

596.2

17.7

94.5

2.2

94.3

0.4

136.1

3.6

216.3

45.0

210.9

62.3

216.3

45.0

210.9

62.3

435.7213.7

63.321.631.710.831.710.8

62.8

25.1

62.8

25.1

314.8 58.9

186.9

44.9

185.8 44.0

186.9

44.9

185.8 44.0

1627.4

160.4

1610.3

434.1

19.4

7.0

19.410.1

Page 570: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Summer Off Peak Post-Project Case

PATH15= 4999 MW(S-N) PATH26= 254 MW(N-S) PDCI=-1846 MW(N-S) COI=-3646 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Off Peak Post-Project FY

Plot 68-Herndon-Ashlan & Gregg-Ashlan 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:28 2008 2013sumop_q272_pst.sav

MIDWAY526.3

24156VINCENT

MIDWAY228.4

30057DIABLO

525.01.050

GATES522.6

GATES228.0

MORROBAY233.0

TEMPLETN

ARCO226.9

LOSBANOS513.6

30045MOSSLAND

515.91.032

GREGG229.7

HELMS PP232.7

HENRIETA227.5

PANOCHE230.4

HELM228.3

MCMULLN1

HERNDON229.7

LOSBANOS

230.4

COBURN229.0

TESLA526.1

TRACY531.0

METCALF519.1

METCALF231.8

BALCH3TP229.4

PINE FLT229.6

GATES228.0

KEARNEY229.5

30875MC CALL

229.40.998

MOSSLND2

MOSSLND1

WESTLEY231.2

Q128230.3

Q239230.0

Q166229.1

Q194230.0

BORDEN230.3

STOREY 2230.3

STOREY 1230.5

WILSON230.9

WARNERVL232.9

DS AMIGO229.3

MELONES231.2

COTTLE A233.0

COTTLE B232.9

BELLOTA234.3

TESLA E231.3

SN LS PP

TESLA D232.7

TESLA C233.1

Q235SWST232.9

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254229.4

STANDFRD117.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

310114 1310114 1

1

0.00.0

v

1.000

1.000

1.0001.0001.000

1.000 1.0001.000

1.000

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.044

1.044

1.044

735.7

24.8

242.8

0.0

246.7

0.0

234.9

0.0

1316.0

44.4

1319.6

44.5

1099.7 37.1

1106.3

37.3

811.1 83.2

808.0

82.9

963.5 56.2

744.9

76.4

125.0

13.3126.3

13.4

52.3

5.6

33.7

3.6

2160.0

72.9

2171.8

73.3

1837.0

62.0

1861.2

62.8

189.4 19.4

243.5

12.5

243.5

12.5

67.9

6.0

601.2 61.7

597.8

61.3

560.7 66.0

131.7 15.5

128.7 15.1

1111.0 37.5

1102.9 37.2

698.2

23.6

1163.2 39.2

801.0

35.4

801.0

35.4

1064.1

24.6

1076.1

24.8

819.7

52.9

668.1

35.2

240.7 24.7

334.4 34.3

505.7 57.1

243.4 27.5

618.8 72.8

614.1 72.3

704.0 82.8

707.2 83.2

208.7

12.9

221.6

14.7

232.2

18.6

568.0

32.6

572.0 32.8

565.0

32.4

432.1 50.8

440.4

51.7

574.8 33.0

562.2 66.2

571.2 67.2

2079.7

70.2

686.0

55.7

675.2

54.9

692.6

56.3

713.7 38.4713.7 38.4

572.2

58.6

574.6

58.9

574.7

58.9

574.7

58.9

574.7

58.9

572.2

58.6

575.0 58.9

574.7

58.9

574.7

58.9

575.0 58.9

253.6

32.0

248.9

31.4

385.1

48.5

459.5

57.9

409.0

48.1

348.8

44.0

504.6 63.6

198.7 23.3

450.8 53.0

758.5

95.6

411.7

48.4

1816.3

106.9

175.5 14.3

456.3 37.1

130.5 8.0

307.2 17.9307.2 17.9

646.2 76.0

644.0 75.8

428.6

50.4

100.4

10.3

100.4

10.3

56.2 5.0

56.2 5.0

307.3 17.9307.3 17.9

510.7 17.2

980.5 35.9

941.7

34.5

1380.1 49.0

1368.0

48.6

1223.8 28.5

795.1 71.2

795.4 71.2

1.90.2

1510.1

79.2

238.8

12.6

238.7

12.6

344.7

18.8

559.3

65.8

551.2

64.9

559.3

65.8

551.2

64.9

539.7 18.2

165.8 44.682.944.682.944.6

331.8

35.3

331.8

35.3

793.9100.1

480.0

25.6

473.0 25.2

480.0

25.6

473.0 25.2

1838.3

62.0

1813.2

61.2

51.9

5.3

55.1 5.7

Page 571: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 69 - No Outage MW/MVAR

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:29 2008 2013sprpk_q272_pre.sav

HENRITTA74.38

LEMOORE71.72

MUSLSLGH74.13

CAMDEN71.17

KNGLOBUS

71.83

KINGSBRG119.6

HENRIETA230.4

34542JCBSCRNR

GUERNSEY74.04

34554

AMSTG SW

ARMSTRNG74.43

GWF-PWR.14.08RESERVE

74.42

34528

CORCORAN

34420

CORCORAN

HNFRD SW

71.72

HARDWICK

71.24

ANGIOLA

73.29

BOSWELL73.57

LEPRINO71.66

CANDLEWK71.78

CMDN JCT

BSWLL TP

JGBSWLL

73.56

GUR3TPT

GWF_HENR74.40

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

0.2

1

49

3

1

49

3

1 1

15.2

3.1

1

26.4

5.4

2

9.7

2.0

1

7.7

1.6

26.6

1.3

1

5.5

1.1

1

8.8

1.8

2

20.5 12.7

1

5.8

1.2

1

10.3 2.1

1

8.5 1.7

1

2.21.4

1

0.0

0.0

1

1.6 0.3

1

0.00.0

1

1

1

0

ss

1

0

ss ss

6

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

4.99.1

19.2 6.2

19.7 5.7

1.6

0.3

23.0

0.2

0.0

0.0

21.4

0.5

21.2

0.6

12.8

2.3

12.7 2.2

4.7

5.8

4.7

5.6

30.0

17.6

8.51.7

2.21.4

36.7

23.4

7.3

45.0

14.7

13.9

0.00.0

11.8

9.1

22.6

6.6

10.3 2.1

42.9

11.5

8.12.7

8.12.4

5.8

1.2

5.81.1

47.9

1.3

47.9

1.3

95.8

2.6

20.5

12.7

20.512.7

6.24.0

4.9

9.0

11.6 9.1

11.8 9.1

Page 572: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 70 - No Outage amps/rate

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:29 2008 2013sprpk_q272_pre.sav

HENRITTA74.38

LEMOORE71.72

MUSLSLGH74.13

CAMDEN71.17

KNGLOBUS

71.83

KINGSBRG119.6

HENRIETA230.4

34542JCBSCRNR

GUERNSEY74.04

34554

AMSTG SW

ARMSTRNG74.43

GWF-PWR.14.08RESERVE

74.42

34528

CORCORAN

34420

CORCORAN

HNFRD SW

71.72

HARDWICK

71.24

ANGIOLA

73.29

BOSWELL73.57

LEPRINO71.66

CANDLEWK71.78

CMDN JCT

BSWLL TP

JGBSWLL

73.56

GUR3TPT

GWF_HENR74.40

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

0.2

1

49

3

1

49

3

1 1

15.2

3.1

1

26.4

5.4

2

9.7

2.0

1

7.7

1.6

26.6

1.3

1

5.5

1.1

1

8.8

1.8

2

20.5 12.7

1

5.8

1.2

1

10.3 2.1

1

8.5 1.7

1

2.21.4

1

0.0

0.0

1

1.6 0.3

1

0.00.0

1

1

1

0

ss

1

0

ss ss

6

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

83.732.7

163.8 48.1

164.8 48.4

12.9

6.2

178.3

85.5

0.1

0.0

165.7

51.5

165.7

51.5

101.4

25.1

101.1 25.0

58.114.2

56.6

13.8

279.8

44.1

67.2

16.6

20.6 4.7

337.8

53.2

114.3

45.6

50.6

10.1

0.00.0

119.6

37.2

189.1

58.2

85.624.7

214.5

49.4

42.045.7

65.7

22.1

46.8

15.8

46.615.7

371.8

83.2

371.8

83.2

743.6

65.8

187.6 29.5

187.8 29.6

59.520.0

82.6

32.3

118.4 47.9

119.6 48.4

Page 573: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 71 - No Outage MW/MVAR

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:30 2008 2013sprpk_q272_pst_v2.sav

HENRITTA74.37

LEMOORE71.75

MUSLSLGH74.12

CAMDEN71.15

KNGLOBUS

71.81

KINGSBRG119.6

HENRIETA230.4

34542JCBSCRNR

GUERNSEY74.04

34554

AMSTG SW

ARMSTRNG74.43

GWF-PWR.14.08RESERVE

74.42

34528

CORCORAN

34420

CORCORAN

HNFRD SW

71.71

HARDWICK

71.23

ANGIOLA

73.28

BOSWELL73.56

LEPRINO71.69

CANDLEWK71.81

CMDN JCT

BSWLL TP

JGBSWLL

73.55

GUR3TPT

GWF_HENR74.39

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

0.1

1

49

3

1

49

3

1

27

1

1

15.2

3.1

1

26.4

5.4

2

9.7

2.0

1

7.7

1.6

26.6

1.3

1

5.5

1.1

1

8.8

1.8

2

20.5 12.7

1

5.8

1.2

1

10.3 2.1

1

8.5 1.7

1

2.21.4

1

0.0

0.0

1

1.6 0.3

1

0.00.0

1

1

1

0

ss

1

0

ss

2

1

ss

6

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

5.19.2

19.4 6.3

19.9 5.8

1.6

0.3

23.0

0.1

0.0

0.0

21.4

0.4

21.2

0.5

12.8

2.2

12.7 2.2

4.7

5.7

4.7

5.5

31.6

16.6

8.51.7

2.21.4

38.4

22.6

15.0

45.5

30.3

14.9

0.00.0

10.1

8.2

20.8

5.9

10.3 2.1

41.3

11.0

8.12.7

8.12.4

5.8

1.2

5.81.1

25.0

1.6

47.9

1.2

47.9

1.2

120.8

4.1

20.5

12.7

20.512.7

6.24.0

5.1

9.1

9.9

8.2

10.1 8.2

Page 574: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 72 - No Outage amps/rate

Rating = 1

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:31 2008 2013sprpk_q272_pst_v2.sav

HENRITTA74.37

LEMOORE71.75

MUSLSLGH74.12

CAMDEN71.15

KNGLOBUS

71.81

KINGSBRG119.6

HENRIETA230.4

34542JCBSCRNR

GUERNSEY74.04

34554

AMSTG SW

ARMSTRNG74.43

GWF-PWR.14.08RESERVE

74.42

34528

CORCORAN

34420

CORCORAN

HNFRD SW

71.71

HARDWICK

71.23

ANGIOLA

73.28

BOSWELL73.56

LEPRINO71.69

CANDLEWK71.81

CMDN JCT

BSWLL TP

JGBSWLL

73.55

GUR3TPT

GWF_HENR74.39

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

0.1

1

49

3

1

49

3

1

27

1

1

15.2

3.1

1

26.4

5.4

2

9.7

2.0

1

7.7

1.6

26.6

1.3

1

5.5

1.1

1

8.8

1.8

2

20.5 12.7

1

5.8

1.2

1

10.3 2.1

1

8.5 1.7

1

2.21.4

1

0.0

0.0

1

1.6 0.3

1

0.00.0

1

1

1

0

ss

1

0

ss

2

1

ss

6

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

85.333.4

165.6 48.6

166.6 48.9

12.9

6.2

178.3

85.5

0.1

0.0

165.7

51.5

165.7

51.5

101.3

25.1

101.0 25.0

57.714.1

56.2

13.7

287.7

45.3

67.2

16.6

20.6 4.7

345.6

54.4

120.1

47.9

84.5

16.9

0.00.0

104.8

32.6

174.0

53.5

85.624.7

206.6

47.5

42.045.7

65.7

22.1

46.8

15.8

46.615.7

194.4

71.6

371.8

83.2

371.8

83.2

938.0

83.0

187.6 29.5

187.8 29.6

59.420.0

84.2

32.9

103.5 41.8

104.8 42.3

Page 575: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 73- Wilson-Borden 230kV & Exchequer MW/MVAR

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:32 2008 2013sprpk_q272_pre.sav

HERNDON117.8

HERNDON230.9

BULLARD116.1

WOODWARD116.1

KERCKHF2117.5

SANGER118.7

MANCHSTR117.0

BARTON117.4

CHLDHOSP116.7

CLOVIS-1117.3

MC CALL120.7

MC CALL233.4

KERCKHF1117.5

KERCKHOF13.59

KERCKHOF6.681

CLOVIS-2117.1

SHARON112.9

CORSGOLD

114.6

OAKHURST

113.8

CHWCHLLA113.1

CERTTEED113.0

LE GRAND114.1

EXCHEQUR112.5

WILSON B116.3

WILSON223.5

DAIRYLND114.5

NEWHALL115.8

MADERAPR116.3

MENDOTA118.6

PANOCHE121.2

HAMMONDS120.1

EL CAPTN114.7

CASTLE114.4

ATWATER114.3

LIVNGSTN113.5

GALLO

113.3

WILSON A116.3

ORO LOMA117.9

EL NIDO116.2

MERCED

115.4

CANTUA119.9

WESTLNDS119.8

KAMM120.4

SCHINDLR119.7

PANOCHE234.1

EXCHEQUR

68.71

EXCHQUER12.68

CHENY121.0

SCHLNDLR72.33

AIRPROD119.2

MALAGA119.0

ULTR.PWR9.010

RANCHRS118.9

SCWAX118.9

PPG

118.9

WST FRSO116.0

DANISHCM116.1

CAL AVE115.8

OXFORD120.8

LUIS_#3120.7

LUIS_#5120.7

JR WOOD114.2

JRWD GEN114.2

CRESSEY113.9

MERCED

MENDOTA73.98

ORO LOMA72.39

PNEDLE116.3

WSTLD1RA120.8

DFS

118.7

PANOCHET

WHD_PAN214.16

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.35

CHWCGNJT

CERTANJ2

CHWCGN

113.2

CHOWCOGN

13.29

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.36

AIRWAYS117.4

LASPALMS117.5

P0418120.7

ATWATR JCRESEY T

MALAGATP

KRCDP118.9

KRCDPCT1

KRCDPCT214.26

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

5

1

0

19

1

0

40

1

145 16 1

1

1

6 4

2 3

15

13

1

45 1

1

1

1

13

7

1

1

1

076

v

0

9

v

0

9

v

09

v

71

2

21 4

1

82

1

3 1

1

3 1

1

4 2

1

15

3

1

1110

1

26 5

1

23 5

2

92

1

12 2

2

20

1

21 4

2

4

3

1

30 6

1

20

4

1

20

4

2

29

6

3

41 8

1

35

7

1

30

6

2

22

4

3

36 7

1

36 7

2

34 7

3

3 1

1

34

7

1

42

9

2

35

7

3

7

5

1

9

6

1

8

2

1

11

2

2

11

2

1

16 3

1

21 4

2

26 5

3

10 2

1

12 2

2

14 3

1

4 2

1

30

6

1

31

6

2

7

1

1

3

1

1

20 4

1

18 4

2

19 4

3

6 4

1

5

2

1

23 5

1

4 3

1

10

2

1

11

1

41

ss

2 1

ss

31 6

1

10 2

2

13 11

1

20 4

1

31

1

40 8

2

36 7

3

11

ss

11

ss

15 3

3

25

5

2

33

7

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.013 1.000

75.6 9.8

36.312.8

16.3 3.3

42.1

3.6

20.1

8.7

61.1

16.6

68.119.8

8.5

3.4

41.0 8.3

75.732.2

166.9 46.0

168.4 2.7

121.5 84.0

117.4 68.1

111.1 44.9

49.1

4.5

76.415.5

3.6

4.5

96.8

5.6

40.6 6.7

36.4

6.4

4.0

3.2

74.218.6

73.7

16.8

11.1

4.5

9.97.0

22.3 7.0

23.0

9.0

38.4

11.5

42.112.4

12.0

6.6

8.4

5.8

47.6

12.8

12.5 0.2

3.6

4.5

44.5

8.9

21.4

3.9

6.6

4.6

65.4

30.3

46.3

34.2

5.2

3.8

13.2 9.3

75.732.2

65.513.8

60.310.7

5.83.6

32.5 5.4

50.9 9.6

2.4

5.7

14.6

0.6

23.6

7.2

11.1 4.1

26.8 0.9

80.428.1

1.70.2

20.5

2.2

73.712.4

91.017.1

57.2

11.6

73.110.0

33.1 2.6

44.9

1.5

65.4

0.7

10.5 2.1

13.5

5.9

3.1

4.0

7.23.6

59.5

26.7

76.2

6.3

88.9

8.9

67.8

3.6

67.1 2.4

5.22.7

5.22.9

9.3

6.5

1.21.3

66.3

28.9

145.0 2.3

123.6

7.6

123.6

7.6

1.21.3

10.5

5.0

14.4 1.1

14.4

0.7

0.00.0

10.5

4.9

10.5

4.9

0.0

0.0

60.220.6

74.619.2

72.9

15.0

11.3 2.9

11.3

2.5

56.9

11.1

56.810.9

303.2

7.3

0.0

0.0

0.0

0.0

58.9

25.6

0.00.0

3.39.0

3.60.9

26.1

12.426.1

12.4

15.2

2.8

96.4

6.1

79.4

14.6

79.1

12.5

62.017.3

60.7

14.4

46.9 8.9

25.4 0.6

21.4

10.0

60.313.8

15.6 8.6

44.3

4.8

14.5

12.4

0.33.7

0.34.4

7.4

1.5

2.5

1.4

9.92.974.8

23.1

64.9

20.2

64.820.2

2.11.2

1.10.7

1.10.7

39.4

8.0

14.9

19.0

23.5

32.8

23.132.9

77.816.5

Page 576: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 74- Wilson-Borden 230kV & Exchequer amps/rate

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:34 2008 2013sprpk_q272_pre.sav

HERNDON117.8

HERNDON230.9

BULLARD116.1

WOODWARD116.1

KERCKHF2117.5

SANGER118.7

MANCHSTR117.0

BARTON117.4

CHLDHOSP116.7

CLOVIS-1117.3

MC CALL120.7

MC CALL233.4

KERCKHF1117.5

KERCKHOF13.59

KERCKHOF6.681

CLOVIS-2117.1

SHARON112.9

CORSGOLD

114.6

OAKHURST

113.8

CHWCHLLA113.1

CERTTEED113.0

LE GRAND114.1

EXCHEQUR112.5

WILSON B116.3

WILSON223.5

DAIRYLND114.5

NEWHALL115.8

MADERAPR116.3

MENDOTA118.6

PANOCHE121.2

HAMMONDS120.1

EL CAPTN114.7

CASTLE114.4

ATWATER114.3

LIVNGSTN113.5

GALLO

113.3

WILSON A116.3

ORO LOMA117.9

EL NIDO116.2

MERCED

115.4

CANTUA119.9

WESTLNDS119.8

KAMM120.4

SCHINDLR119.7

PANOCHE234.1

EXCHEQUR

68.71

EXCHQUER12.68

CHENY121.0

SCHLNDLR72.33

AIRPROD119.2

MALAGA119.0

ULTR.PWR9.010

RANCHRS118.9

SCWAX118.9

PPG

118.9

WST FRSO116.0

DANISHCM116.1

CAL AVE115.8

OXFORD120.8

LUIS_#3120.7

LUIS_#5120.7

JR WOOD114.2

JRWD GEN114.2

CRESSEY113.9

MERCED

MENDOTA73.98

ORO LOMA72.39

PNEDLE116.3

WSTLD1RA120.8

DFS

118.7

PANOCHET

WHD_PAN214.16

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.35

CHWCGNJT

CERTANJ2

CHWCGN

113.2

CHOWCOGN

13.29

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.36

AIRWAYS117.4

LASPALMS117.5

P0418120.7

ATWATR JCRESEY T

MALAGATP

KRCDP118.9

KRCDPCT1

KRCDPCT214.26

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

5

1

0

19

1

0

40

1

145 16 1

1

1

6 4

2 3

15

13

1

45 1

1

1

1

13

7

1

1

1

076

v

0

9

v

0

9

v

09

v

71

2

21 4

1

82

1

3 1

1

3 1

1

4 2

1

15

3

1

1110

1

26 5

1

23 5

2

92

1

12 2

2

20

1

21 4

2

4

3

1

30 6

1

20

4

1

20

4

2

29

6

3

41 8

1

35

7

1

30

6

2

22

4

3

36 7

1

36 7

2

34 7

3

3 1

1

34

7

1

42

9

2

35

7

3

7

5

1

9

6

1

8

2

1

11

2

2

11

2

1

16 3

1

21 4

2

26 5

3

10 2

1

12 2

2

14 3

1

4 2

1

30

6

1

31

6

2

7

1

1

3

1

1

20 4

1

18 4

2

19 4

3

6 4

1

5

2

1

23 5

1

4 3

1

10

2

1

11

1

41

ss

2 1

ss

31 6

1

10 2

2

13 11

1

20 4

1

31

1

40 8

2

36 7

3

11

ss

11

ss

15 3

3

25

5

2

33

7

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.013 1.000

379.1 38.9

189.9 19.5

81.611.0

207.8

18.5

107.8

14.5

311.2

32.0

344.8 30.7

45.0

6.4

206.1 18.3

400.0 35.6

848.4 37.5

825.2 36.3

706.2 32.0

648.9 29.4

573.1 25.8

241.3

21.5

384.2 34.2

28.2

7.1

250.3 30.4

204.0 43.2

185.0

25.1

26.0

7.5

379.8 43.0

380.6

43.1

60.6

8.2

61.1 5.1

118.3 23.1

124.6

12.8

199.9

17.8

218.0 22.4

65.2

12.7

48.7

9.5

244.8

32.9

63.012.3

499.7

12.8

225.5

65.1

109.6

32.1

41.3

11.9

368.3

92.9

293.9

57.4

30.9

6.0

77.811.2

400.0 35.6

320.2 43.1

296.7 39.9

33.255.1

157.4 26.2

247.8 33.5

31.3

4.2

74.1

18.6

125.7

24.5

59.6 8.1

130.4 25.5

407.3 41.8

8.52.1

100.8

19.7

366.0 22.1

453.8 27.4

290.0

39.0

366.7 49.4

165.2 22.2

220.1

62.4

320.1

52.7

50.9 9.9

70.4

13.8

24.0

4.7

38.8 7.6

310.8

38.9

364.9

60.1

425.9

37.9

326.3

53.7

326.4 53.7

29.3 9.7

29.3 9.9

57.8

16.7

9.02.6

369.2

93.1

712.6 80.6

609.3

82.0

609.3

82.0

9.02.6

59.3

17.1

74.314.5

120.8

14.4

0.00.0

59.1

92.7

59.1

11.5

0.0

0.0

309.2 27.5

368.7 32.8

370.5

32.9

58.0 7.8

57.6

7.7

288.2

25.6

288.3 25.6

1450.1

72.6

0.0

0.0

0.1

0.0

312.6

32.1

0.00.0

46.512.7

18.4 9.9

146.2

28.5

146.2

28.6

78.1

15.3

249.5 20.9

395.7

40.6

396.0

40.7

308.0 27.4

310.2

27.6

234.4 20.8

125.0 12.8

116.4

10.4

300.6 26.7

87.5 9.0

218.9

19.5

92.4

92.1

18.2 2.5

21.4 2.9

36.5

7.1

14.1

4.1

50.0 9.8379.3

51.1

329.6 44.4

329.6 44.4

11.8 1.4

6.01.8

6.01.8

99.1

10.9

59.4

16.7

204.2

39.9

199.7 39.0

395.4 99.7

Page 577: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 75- Wilson-Borden 230kV & Exchequer MW/MVAR

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:36 2008 2013sprpk_q272_pst_v2.sav

HERNDON117.8

HERNDON230.9

BULLARD116.1

WOODWARD116.1

KERCKHF2117.5

SANGER118.7

MANCHSTR116.9

BARTON117.4

CHLDHOSP116.7

CLOVIS-1117.3

MC CALL120.7

MC CALL233.4

KERCKHF1117.4

KERCKHOF13.59

KERCKHOF6.680

CLOVIS-2117.1

SHARON112.8

CORSGOLD

114.6

OAKHURST

113.8

CHWCHLLA113.0

CERTTEED112.9

LE GRAND114.0

EXCHEQUR112.5

WILSON B116.3

WILSON223.4

DAIRYLND114.5

NEWHALL115.8

MADERAPR116.3

MENDOTA118.5

PANOCHE121.1

HAMMONDS120.0

EL CAPTN114.6

CASTLE114.3

ATWATER114.2

LIVNGSTN113.4

GALLO

113.2

WILSON A116.3

ORO LOMA117.9

EL NIDO116.2

MERCED

115.3

CANTUA119.8

WESTLNDS119.8

KAMM120.4

SCHINDLR119.7

PANOCHE234.1

EXCHEQUR

68.67

EXCHQUER12.68

CHENY121.0

SCHLNDLR72.31

AIRPROD119.2

MALAGA118.9

ULTR.PWR9.009

RANCHRS118.9

SCWAX118.9

PPG

118.9

WST FRSO116.0

DANISHCM116.1

CAL AVE115.8

OXFORD120.7

LUIS_#3120.6

LUIS_#5120.7

JR WOOD114.1

JRWD GEN114.1

CRESSEY113.8

MERCED

MENDOTA73.96

ORO LOMA72.36

PNEDLE116.3

WSTLD1RA120.8

DFS

118.7

PANOCHET

WHD_PAN214.16

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.34

CHWCGNJT

CERTANJ2

CHWCGN

113.1

CHOWCOGN

13.29

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.36

AIRWAYS117.4

LASPALMS117.5

P0418120.7

ATWATR JCRESEY T

MALAGATP

KRCDP118.9

KRCDPCT1

KRCDPCT214.25

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

5

1

0

19

1

0

40

1

145 16 1

1

1

6 4

2 3

15

13

1

45 1

1

1

1

13

7

1

1

1

076

v

0

9

v

0

9

v

09

v

71

2

21 4

1

82

1

3 1

1

3 1

1

4 2

1

15

3

1

1110

1

26 5

1

23 5

2

92

1

12 2

2

20

1

21 4

2

4

3

1

30 6

1

20

4

1

20

4

2

29

6

3

41 8

1

35

7

1

30

6

2

22

4

3

36 7

1

36 7

2

34 7

3

3 1

1

34

7

1

42

9

2

35

7

3

7

5

1

9

6

1

8

2

1

11

2

2

11

2

1

16 3

1

21 4

2

26 5

3

10 2

1

12 2

2

14 3

1

4 2

1

30

6

1

31

6

2

7

1

1

3

1

1

20 4

1

18 4

2

19 4

3

6 4

1

5

2

1

23 5

1

4 3

1

10

2

1

11

1

41

ss

2 1

ss

31 6

1

10 2

2

13 11

1

20 4

1

31

1

40 8

2

36 7

3

11

ss

11

ss

15 3

3

25

5

2

33

7

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.013 1.000

75.7 9.8

36.212.8

16.0 3.3

42.1

3.5

20.2

8.7

61.3

16.6

68.319.8

8.3

3.5

41.0 8.3

75.832.2

167.0 45.9

168.5 2.7

120.7 84.2

116.6 68.1

110.4 44.9

49.0

4.5

76.415.5

3.6

4.5

96.6

5.6

40.6 6.7

36.4

6.5

4.0

3.2

74.218.6

73.7

16.8

11.1

4.5

9.97.0

22.3 7.0

23.0

9.1

38.4

11.6

42.112.5

11.9

6.6

8.2

5.8

47.6

12.8

12.5 0.2

3.6

4.5

44.5

8.9

21.4

3.9

6.6

4.6

65.8

30.4

46.7

34.3

5.3

3.8

13.4 9.4

75.832.2

65.513.8

60.310.7

5.83.6

31.2 5.6

49.6 9.8

2.4

5.8

14.7

0.6

23.6

7.2

11.1 4.1

26.8 0.9

80.428.1

1.70.3

20.5

2.3

73.712.4

91.017.1

57.2

11.6

73.110.0

33.1 2.6

45.1

1.6

65.5

0.7

10.5 2.1

13.4

5.9

2.9

4.0

7.33.7

59.5

26.8

76.4

6.3

89.1

8.9

67.9

3.6

67.3 2.5

5.22.7

5.22.9

9.3

6.5

1.21.3

66.6

29.0

145.0 2.3

124.0

7.6

124.0

7.6

1.21.3

10.5

5.0

14.5 1.1

14.4

0.7

0.00.0

10.5

4.9

10.5

4.9

0.0

0.0

60.220.6

74.619.2

72.9

15.0

11.3 2.9

11.3

2.5

56.9

11.1

56.810.9

303.2

7.5

0.0

0.0

0.0

0.0

58.9

25.6

0.00.0

3.38.9

3.60.9

26.1

12.426.1

12.4

15.2

2.8

96.2

6.1

79.5

14.6

79.2

12.5

62.017.3

60.7

14.4

46.9 8.9

25.4 0.6

21.4

10.0

60.313.8

15.6 8.6

44.3

4.8

14.5

12.4

0.33.7

0.34.4

7.4

1.5

2.5

1.4

9.92.974.8

23.1

64.9

20.2

64.920.2

2.11.2

1.10.7

1.10.7

39.3

7.8

14.9

18.9

23.8

32.9

23.433.0

78.216.4

Page 578: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 76- Wilson-Borden 230kV & Exchequer amps/rate

Rating = 2

gfres115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:38 2008 2013sprpk_q272_pst_v2.sav

HERNDON117.8

HERNDON230.9

BULLARD116.1

WOODWARD116.1

KERCKHF2117.5

SANGER118.7

MANCHSTR116.9

BARTON117.4

CHLDHOSP116.7

CLOVIS-1117.3

MC CALL120.7

MC CALL233.4

KERCKHF1117.4

KERCKHOF13.59

KERCKHOF6.680

CLOVIS-2117.1

SHARON112.8

CORSGOLD

114.6

OAKHURST

113.8

CHWCHLLA113.0

CERTTEED112.9

LE GRAND114.0

EXCHEQUR112.5

WILSON B116.3

WILSON223.4

DAIRYLND114.5

NEWHALL115.8

MADERAPR116.3

MENDOTA118.5

PANOCHE121.1

HAMMONDS120.0

EL CAPTN114.6

CASTLE114.3

ATWATER114.2

LIVNGSTN113.4

GALLO

113.2

WILSON A116.3

ORO LOMA117.9

EL NIDO116.2

MERCED

115.3

CANTUA119.8

WESTLNDS119.8

KAMM120.4

SCHINDLR119.7

PANOCHE234.1

EXCHEQUR

68.67

EXCHQUER12.68

CHENY121.0

SCHLNDLR72.31

AIRPROD119.2

MALAGA118.9

ULTR.PWR9.009

RANCHRS118.9

SCWAX118.9

PPG

118.9

WST FRSO116.0

DANISHCM116.1

CAL AVE115.8

OXFORD120.7

LUIS_#3120.6

LUIS_#5120.7

JR WOOD114.1

JRWD GEN114.1

CRESSEY113.8

MERCED

MENDOTA73.96

ORO LOMA72.36

PNEDLE116.3

WSTLD1RA120.8

DFS

118.7

PANOCHET

WHD_PAN214.16

PANOCHEJ

OXFRDJCTWSTLDJCTLUISJCT

MADERA_G13.34

CHWCGNJT

CERTANJ2

CHWCGN

113.1

CHOWCOGN

13.29

CERTAN T

CERTANJ1

SHARON T

OAKH_JCT

K1-JCT

WWARD JT

CHWCHLA2

CHWCHLA213.36

AIRWAYS117.4

LASPALMS117.5

P0418120.7

ATWATR JCRESEY T

MALAGATP

KRCDP118.9

KRCDPCT1

KRCDPCT214.25

to KingsburgGreater Fresno 115 kV system

to Piedra Jct

to Wahtoke

0

5

1

0

19

1

0

40

1

145 16 1

1

1

6 4

2 3

15

13

1

45 1

1

1

1

13

7

1

1

1

076

v

0

9

v

0

9

v

09

v

71

2

21 4

1

82

1

3 1

1

3 1

1

4 2

1

15

3

1

1110

1

26 5

1

23 5

2

92

1

12 2

2

20

1

21 4

2

4

3

1

30 6

1

20

4

1

20

4

2

29

6

3

41 8

1

35

7

1

30

6

2

22

4

3

36 7

1

36 7

2

34 7

3

3 1

1

34

7

1

42

9

2

35

7

3

7

5

1

9

6

1

8

2

1

11

2

2

11

2

1

16 3

1

21 4

2

26 5

3

10 2

1

12 2

2

14 3

1

4 2

1

30

6

1

31

6

2

7

1

1

3

1

1

20 4

1

18 4

2

19 4

3

6 4

1

5

2

1

23 5

1

4 3

1

10

2

1

11

1

41

ss

2 1

ss

31 6

1

10 2

2

13 11

1

20 4

1

31

1

40 8

2

36 7

3

11

ss

11

ss

15 3

3

25

5

2

33

7

3

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

1.013 1.000

379.7 39.0

189.5 19.5

80.510.8

207.8

18.5

108.5

14.6

312.0

32.0

345.7 30.7

44.2

6.3

206.1 18.3

400.5 35.6

848.6 37.5

825.6 36.3

703.9 31.9

645.9 29.2

569.9 25.6

241.3

21.5

384.2 34.2

28.2

7.1

250.0 30.4

204.1 43.3

185.2

25.1

26.0

7.5

380.1 43.0

380.8

43.1

60.6

8.2

61.1 5.1

118.3 23.1

124.8

12.8

200.1

17.8

218.2 22.4

64.8

12.6

48.3

9.4

244.9

33.0

63.112.3

499.8

12.8

225.6

65.1

109.7

32.1

41.3

11.9

370.3

93.4

295.9

57.8

31.4

6.1

78.911.4

400.5 35.6

320.4 43.1

296.9 40.0

33.355.2

151.6 25.3

241.7 32.7

31.8

4.3

74.2

18.6

125.7

24.6

59.7 8.1

130.4 25.5

407.5 41.8

8.42.1

101.0

19.7

366.1 22.1

453.8 27.4

290.0

39.0

366.7 49.4

165.3 22.2

220.9

62.6

321.1

52.9

51.010.0

69.9

13.7

23.7

4.6

39.3 7.7

311.0

39.0

365.9

60.2

426.9

38.0

327.3

53.9

327.4 53.9

29.4 9.8

29.4 9.9

57.9

16.7

9.02.6

371.3

93.6

712.7 80.6

611.5

82.3

611.5

82.3

9.02.6

59.4

17.1

74.414.5

121.0

14.4

0.00.0

59.1

92.7

59.2

11.6

0.0

0.0

309.3 27.5

368.7 32.8

370.5

32.9

58.0 7.8

57.6

7.7

288.3

25.6

288.4 25.6

1450.3

72.6

0.0

0.0

0.1

0.0

312.7

32.1

0.00.0

46.412.7

18.4 9.9

146.3

28.6

146.3

28.6

78.2

15.3

249.2 20.9

396.2

40.7

396.5

40.7

308.1 27.4

310.3

27.6

234.5 20.9

125.0 12.8

116.5

10.4

300.7 26.7

87.5 9.0

219.0

19.5

92.4

92.1

18.2 2.5

21.4 2.9

36.5

7.1

14.0

4.1

50.0 9.8379.5

51.1

329.8 44.4

329.8 44.4

11.8 1.4

6.01.8

6.01.8

98.9

10.8

59.2

16.7

205.5

40.1

200.9 39.2

397.4100.2

Page 579: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 77- Gates-McCall 230kV MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:39 2008 2013sprpk_q272_pre.sav

MIDWAY532.9

24156VINCENT

MIDWAY229.7

30057DIABLO

534.31.069

GATES539.8

GATES231.8

MORROBAY234.5

TEMPLETN

ARCO228.9

LOSBANOS536.8

30045MOSSLAND

531.61.063

GREGG231.4

HELMS PP234.2

HENRIETA230.0

PANOCHE234.0

HELM231.4

MCMULLN1

HERNDON231.0

LOSBANOS

237.5

COBURN235.7

TESLA535.6

TRACY541.9

METCALF534.2

METCALF234.8

BALCH3TP234.3

PINE FLT234.5

GATES231.8

KEARNEY229.9

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128233.7

Q239228.3

Q166228.3

Q194228.3

BORDEN230.6

STOREY 2229.7

STOREY 1229.9

WILSON225.7

WARNERVL224.5

DS AMIGO235.6

MELONES233.1

COTTLE A230.6

COTTLE B224.8

BELLOTA229.1

TESLA E231.6

SN LS PP

TESLA D233.0

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.2

STANDFRD107.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 85 1400 85 1

0.0135.7

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

410.8

122.1

874.7

67.3

899.3

69.5

1111.5

46.7

404.2

155.1

405.2

36.3

324.5139.2

323.7

108.6

259.1 1.0

251.1

41.0

364.1 28.6

211.9

41.9

40.0

6.540.2

18.6

92.9

12.7

93.7

6.7

620.2

145.8

617.5

14.5

215.4

255.0

214.1

167.7

203.0 63.3

320.2

9.4

320.2

9.4

64.8

77.7

242.2 48.0

238.5

67.4

223.5 56.0

67.525.4

66.7 6.2

712.2 33.9

709.9 76.6

871.6

561.3

585.8114.7

588.9

55.1

588.9

55.1

308.8

62.2

308.1

106.2

1010.5

63.1

166.4

9.3

104.9 56.5

113.9 1.2

177.1 20.7

319.6 71.9

313.4101.4

361.3 71.2

371.8 20.5

550.6

38.2

584.7

44.1

613.3

42.5

190.1

58.9

192.6 51.5

188.3

59.7

156.2 13.0

159.4

8.6

194.5 50.4

221.9 50.9

230.8 20.0

299.9

46.0

627.7

176.6

617.6

174.1

631.6

184.5

281.7 13.7281.7 13.7

320.6

74.3

327.5

27.7

327.5

27.7

327.5

27.7

327.5

27.6

320.6

74.3

0.00.0

208.6 23.1

205.2

8.2

205.2

8.2

208.6 23.1

245.0 68.8

116.1

23.5

113.7

24.1

315.5

14.5

370.4

3.4

338.7

2.4

287.4

4.2

339.3 19.5

96.454.5

260.2 3.9

291.1

101.6

232.0

23.3

556.3

51.1

628.1 52.4

948.8 93.2

679.0105.8

128.6 57.6128.6 57.6

244.8 54.6

241.1 68.7

189.1

71.9

22.5

1.4

22.5

1.4

489.8 5.3

489.8 5.3

128.4 57.5128.4 57.5

1170.3 14.4

1387.5 130.2

1412.4

178.9

872.3254.8

875.4

257.3

1659.1 140.4

398.2 27.6

398.2 28.0

398.2 27.9

596.3

43.2

267.0

79.8

52.2

30.7

51.919.2

52.2

30.7

51.9

19.2

1164.4 51.1

130.9 32.165.416.165.416.1

128.8

13.0

128.8

13.0

317.2 97.7

79.2

16.5

79.4 6.3

79.2

16.5

79.4 6.3

192.4

141.7

192.1 13.6

289.6

0.6

288.0

8.8

Page 580: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 78- Gates-McCall 230kV amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:41 2008 2013sprpk_q272_pre.sav

MIDWAY532.9

24156VINCENT

MIDWAY229.7

30057DIABLO

534.31.069

GATES539.8

GATES231.8

MORROBAY234.5

TEMPLETN

ARCO228.9

LOSBANOS536.8

30045MOSSLAND

531.61.063

GREGG231.4

HELMS PP234.2

HENRIETA230.0

PANOCHE234.0

HELM231.4

MCMULLN1

HERNDON231.0

LOSBANOS

237.5

COBURN235.7

TESLA535.6

TRACY541.9

METCALF534.2

METCALF234.8

BALCH3TP234.3

PINE FLT234.5

GATES231.8

KEARNEY229.9

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128233.7

Q239228.3

Q166228.3

Q194228.3

BORDEN230.6

STOREY 2229.7

STOREY 1229.9

WILSON225.7

WARNERVL224.5

DS AMIGO235.6

MELONES233.1

COTTLE A230.6

COTTLE B224.8

BELLOTA229.1

TESLA E231.6

SN LS PP

TESLA D233.0

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.2

STANDFRD107.2

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 85 1400 85 1

0.0135.7

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

464.3

15.7

950.4

0.0

977.1

0.0

1205.1

0.0

469.0

15.8

435.1

14.7

381.5 12.9

365.2

12.3

638.1 65.5

633.8

65.0

899.5 52.5

538.1

55.2

101.8

10.8111.7

11.9

236.5

25.1

233.9

24.8

681.4

23.0

664.4

22.4

361.5

12.2

292.5

9.9

524.7 53.8

799.4

40.9

799.4

40.9

108.8

10.1

609.3 62.5

602.6

61.8

568.4 66.9

177.9 20.9

164.1 19.3

766.9 25.9

775.4 26.2

1104.5

37.3

648.2 21.9

1475.7

65.2

1475.7

65.2

336.9

7.8

350.5

8.1

1082.9

72.2

415.8

21.9

299.0 30.7

281.9 31.8

441.6 49.8

817.4 96.2

812.6 95.6

918.9108.1

921.8108.5

596.5

37.9

633.8

43.1

664.4

54.8

489.4

28.1

493.5 28.3

485.8

27.9

387.8 45.6

391.0

45.9

497.0 28.5

563.5 66.3

571.6 67.3

326.4

11.0

706.4

58.1

695.1

57.2

712.9

58.6

696.8 37.5696.8 37.5

827.1

84.7

831.1

85.1

831.1

85.1

831.1

85.1

831.1

85.1

827.2

84.7

0.00.0

516.7 52.9

519.2

53.2

519.2

53.2

516.7 52.9

643.6 75.6

295.6

37.3

290.1

36.6

790.6

99.7

927.1

116.9

850.8

100.0

722.4

91.1

869.3109.6

283.4 33.3

644.5 75.8

791.8

99.8

587.6

69.1

1358.2

79.9

679.4 56.2

1027.7 85.0

740.8 46.5

350.4 20.4350.4 20.4

618.9 72.8

614.3 72.3

495.7

58.3

54.7

5.6

54.7

5.6

521.8 47.1

521.8 47.1

348.6 20.3348.6 20.3

1261.7 42.6

1502.3 55.0

1533.3

56.2

979.6 34.8

1003.8

35.6

1773.9 41.3

983.9 88.7

984.0 88.7

984.0 88.7

1489.2

78.1

694.2

37.8

150.9

17.8

136.4

16.1

150.9

17.8

136.4

16.1

1259.7 42.5

346.5 89.8173.3 89.9173.3 89.9

697.6

74.3

697.6

74.3

853.5107.6

202.3

10.8

198.1 10.5

202.3

10.8

198.1 10.5

257.0

8.7

205.2 6.9

723.8

74.2

723.7

74.2

Page 581: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 79- Gates-McCall 230kV MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:42 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.9

24156VINCENT

MIDWAY229.7

30057DIABLO

534.31.069

GATES539.7

GATES231.7

MORROBAY234.4

TEMPLETN

ARCO228.8

LOSBANOS536.6

30045MOSSLAND

531.51.063

GREGG231.3

HELMS PP234.2

HENRIETA230.0

PANOCHE233.9

HELM231.3

MCMULLN1

HERNDON231.0

LOSBANOS

237.4

COBURN235.6

TESLA535.5

TRACY541.9

METCALF534.1

METCALF234.7

BALCH3TP234.3

PINE FLT234.5

GATES231.7

KEARNEY229.8

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128233.7

Q239228.3

Q166228.3

Q194228.2

BORDEN230.6

STOREY 2229.6

STOREY 1229.8

WILSON225.6

WARNERVL224.5

DS AMIGO235.5

MELONES233.0

COTTLE A230.5

COTTLE B224.7

BELLOTA229.1

TESLA E231.6

SN LS PP

TESLA D233.0

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.1

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 85 1400 85 1400 85 1

0.0135.7

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

410.5

121.9

872.2

67.8

896.6

70.0

1108.3

47.3

400.8

153.6

401.8

34.7

325.0138.5

324.3

107.9

258.6 0.8

250.6

40.6

363.7 28.7

211.4

41.5

40.8

6.941.0

18.9

93.8

12.4

94.5

6.5

629.9

145.8

627.1

15.5

222.7

254.5

221.4

167.7

204.6 63.6

320.9

9.5

320.9

9.5

65.7

78.4

243.8 47.9

240.1

67.7

225.0 56.0

68.225.4

67.4 6.4

717.3 34.1

714.9 75.8

876.1

561.3

590.9115.2

588.9

54.8

588.9

54.8

313.5

62.0

312.9

105.9

1021.0

65.1

161.2

9.4

127.3 57.5

113.9 1.3

177.1 20.7

321.3 71.9

315.1101.8

363.1 71.3

373.7 19.9

551.5

38.2

585.8

44.0

614.4

42.4

191.1

59.2

193.6 51.6

189.3

60.0

156.9 13.3

160.1

8.7

195.5 50.6

223.3 51.6

232.4 20.0

309.3

47.0

628.7

176.6

618.6

174.1

632.6

184.5

281.7 13.8281.7 13.8

321.0

74.5

327.9

27.7

327.9

27.7

327.9

27.7

327.9

27.7

321.0

74.5

0.00.0

209.0 23.2

205.6

8.2

205.6

8.2

209.0 23.2

245.0 68.8

118.0

23.7

115.6

24.3

317.2

15.0

372.4

2.9

340.8

2.9

289.1

4.6

341.9 19.7

97.654.6

261.3 3.5

293.0

102.2

233.1

24.1

560.1

50.3

628.9 52.6

955.2 93.5

679.1106.1

130.0 57.7130.0 57.7

246.4 54.6

242.6 69.0

190.6

72.2

22.5

1.4

22.5

1.4

490.1 5.0

490.1 5.0

129.7 57.6129.7 57.6

1168.4 13.6

1385.1 128.5

1410.0

177.9

866.3253.0

869.4

256.5

1656.2 138.2

398.2 27.8

398.2 28.1

398.2 28.1

596.3

42.2

284.1

81.9

53.9

30.8

53.619.4

53.9

30.8

53.6

19.4

1162.4 49.9

131.2 32.165.616.065.616.0

129.1

12.9

129.1

12.9

319.2 98.2

78.2

16.9

78.4 6.7

78.2

16.9

78.4 6.7

200.3

142.8

200.1 15.2

291.3

1.0

289.7

8.6

Page 582: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 80- Gates-McCall 230kV amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:44 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.9

24156VINCENT

MIDWAY229.7

30057DIABLO

534.31.069

GATES539.7

GATES231.7

MORROBAY234.4

TEMPLETN

ARCO228.8

LOSBANOS536.6

30045MOSSLAND

531.51.063

GREGG231.3

HELMS PP234.2

HENRIETA230.0

PANOCHE233.9

HELM231.3

MCMULLN1

HERNDON231.0

LOSBANOS

237.4

COBURN235.6

TESLA535.5

TRACY541.9

METCALF534.1

METCALF234.7

BALCH3TP234.3

PINE FLT234.5

GATES231.7

KEARNEY229.8

30875MC CALL

233.21.014

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128233.7

Q239228.3

Q166228.3

Q194228.2

BORDEN230.6

STOREY 2229.6

STOREY 1229.8

WILSON225.6

WARNERVL224.5

DS AMIGO235.5

MELONES233.0

COTTLE A230.5

COTTLE B224.7

BELLOTA229.1

TESLA E231.6

SN LS PP

TESLA D233.0

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.1

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 85 1400 85 1400 85 1

0.0135.7

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

464.0

15.7

947.8

0.0

974.4

0.0

1201.8

0.0

465.0

15.7

431.4

14.6

381.8 12.9

365.6

12.3

636.9 65.3

632.6

64.9

898.3 52.4

536.9

55.1

104.1

11.1114.0

12.1

238.7

25.4

236.1

25.1

691.6

23.3

674.9

22.8

366.4

12.4

298.8

10.1

528.9 54.2

801.2

41.0

801.2

41.0

110.0

10.2

613.3 62.9

606.6

62.2

572.2 67.3

179.7 21.1

166.0 19.5

772.6 26.1

781.0 26.4

1108.6

37.4

653.9 22.1

1475.8

65.2

1475.8

65.2

341.9

7.9

355.3

8.2

1094.4

73.0

402.9

21.2

350.6 36.0

281.9 31.8

441.6 49.8

821.9 96.7

817.2 96.1

923.6108.7

926.5109.0

597.6

38.0

635.0

43.2

665.7

54.9

492.1

28.2

496.2 28.5

488.4

28.0

389.6 45.8

392.8

46.2

499.7 28.7

567.5 66.8

575.5 67.7

336.6

11.4

707.5

58.2

696.2

57.3

713.9

58.7

696.9 37.5696.9 37.5

828.4

84.8

832.3

85.2

832.4

85.2

832.4

85.2

832.4

85.2

828.4

84.8

0.00.0

517.9 53.0

520.4

53.3

520.4

53.3

517.9 53.0

643.7 75.6

300.4

37.9

294.9

37.2

795.2

100.2

932.5

117.6

856.2

100.6

727.0

91.7

876.3110.5

286.2 33.6

647.5 76.2

797.2

100.5

590.6

69.5

1367.7

80.5

680.4 56.2

1034.8 85.5

741.1 46.5

353.5 20.6353.5 20.6

622.7 73.3

618.1 72.7

499.5

58.8

54.7

5.6

54.7

5.6

522.2 47.1

522.2 47.1

351.8 20.5351.8 20.5

1259.8 42.5

1499.7 54.9

1530.6

56.1

973.0 34.6

997.2

35.4

1770.7 41.2

984.0 88.7

984.1 88.7

984.1 88.7

1489.4

78.1

736.6

40.1

154.8

18.2

140.6

16.5

154.8

18.2

140.6

16.5

1257.7 42.4

347.3 90.0173.7 90.0173.7 90.0

699.2

74.5

699.2

74.5

858.9108.3

200.2

10.7

195.7 10.4

200.2

10.7

195.7 10.4

264.7

8.9

213.8 7.2

728.1

74.7

728.0

74.7

Page 583: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 81- Gates-Templeton 230kV & Melones MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:45 2008 2013sprpk_q272_pre.sav

MIDWAY532.5

24156VINCENT

MIDWAY229.2

30057DIABLO

534.11.068

GATES539.7

GATES231.9

MORROBAY233.8

TEMPLETN

ARCO228.8

LOSBANOS536.8

30045MOSSLAND

531.91.064

GREGG231.4

HELMS PP234.2

HENRIETA230.4

PANOCHE234.7

HELM232.8

MCMULLN1

HERNDON231.1

LOSBANOS

238.0

COBURN236.2

TESLA535.8

TRACY542.1

METCALF534.5

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES231.9

KEARNEY230.2

30875MC CALL

233.61.016

MOSSLND2

MOSSLND1

WESTLEY231.0

Q128234.0

Q239226.3

Q166226.3

Q194226.3

BORDEN230.6

STOREY 2229.5

STOREY 1229.7

WILSON224.8

WARNERVL224.5

DS AMIGO236.3

MELONES226.7

COTTLE A227.9

COTTLE B224.8

BELLOTA228.8

TESLA E231.7

SN LS PP

TESLA D233.1

TESLA C232.7

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.3

STANDFRD107.3

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

406.1

119.0

876.2

69.5

900.7

71.7

1113.2

49.6

354.2

173.6

355.1

53.2

334.0139.7

333.2

110.2

342.4 8.2

328.3

78.6

163.7 27.7

31.5

2.231.6

14.7

84.4

16.6

85.0

9.9

638.8

151.0

635.9

21.7

245.9

264.0

244.4

179.2

174.4 57.9

336.3

3.5

336.3

3.5

18.6

63.5

224.3 46.8

221.1

61.7

206.8 54.2

60.624.4

59.9 4.1

716.2 30.0

713.8 72.2

851.9

558.2

578.6115.5

588.9

55.5

588.9

55.5

318.0

64.3

317.3

103.2

978.6

51.9

126.0

10.2

203.1 9.1

74.751.4

113.9 0.8

177.1 22.0

237.3 56.8

233.9 69.5

269.8 52.1

275.6 28.5

546.4

38.9

580.3

44.7

608.6

43.2

186.0

56.9

188.2 50.4

184.1

57.6

149.7 9.7

152.6

7.4

190.1 49.3

208.6 43.2

216.4 18.9

303.0

48.3

659.4

190.1

648.8

187.3

663.5

198.4

281.7 10.8281.7 10.8

371.5

104.1

381.0

35.8

381.0

35.8

381.0

35.8

381.0

35.8

371.5

104.1

0.00.0

264.3 33.7

258.8

1.4

258.8

1.4

264.3 33.7

244.9 70.2

119.9

29.5

117.5

30.0

317.6

20.9

372.9

4.1

341.3

9.8

289.4

10.5

301.5 27.8

148.1 30.6

144.6 32.7

274.4

95.9

120.5

33.2

548.5

57.9

638.8 53.3

911.4 90.9

707.3107.9

121.4 58.0121.4 58.0

228.0 52.7

224.8 63.9

172.8

67.1

22.5

1.4

22.5

1.4

500.7 4.7

500.7 4.7

121.2 57.8121.2 57.8

1164.1 17.8

1384.2 129.8

1409.1

179.8

887.5252.9

890.8

253.2

1656.4 141.3

398.2 27.2

398.2 27.6

398.2 27.6

596.3

45.5

200.2

19.8

199.2

23.3

198.3

61.6

75.8

37.8

75.128.2

75.8

37.8

75.1

28.2

1158.2 53.2

121.2 30.560.615.260.615.2

119.4

14.2

119.4

14.2

300.5 92.4

87.9

13.9

88.1 4.2

87.9

13.9

88.1 4.2

197.1

142.9

196.8 15.0

262.2

5.2

260.9

12.3

Page 584: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 82- Gates-Templeton 230kV & Melones amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:47 2008 2013sprpk_q272_pre.sav

MIDWAY532.5

24156VINCENT

MIDWAY229.2

30057DIABLO

534.11.068

GATES539.7

GATES231.9

MORROBAY233.8

TEMPLETN

ARCO228.8

LOSBANOS536.8

30045MOSSLAND

531.91.064

GREGG231.4

HELMS PP234.2

HENRIETA230.4

PANOCHE234.7

HELM232.8

MCMULLN1

HERNDON231.1

LOSBANOS

238.0

COBURN236.2

TESLA535.8

TRACY542.1

METCALF534.5

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES231.9

KEARNEY230.2

30875MC CALL

233.61.016

MOSSLND2

MOSSLND1

WESTLEY231.0

Q128234.0

Q239226.3

Q166226.3

Q194226.3

BORDEN230.6

STOREY 2229.5

STOREY 1229.7

WILSON224.8

WARNERVL224.5

DS AMIGO236.3

MELONES226.7

COTTLE A227.9

COTTLE B224.8

BELLOTA228.8

TESLA E231.7

SN LS PP

TESLA D233.1

TESLA C232.7

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.3

STANDFRD107.3

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

458.8

15.5

952.9

0.0

979.6

0.0

1208.1

0.0

427.6

14.4

384.1

13.0

391.3 13.2

375.4

12.7

845.9 86.8

840.4

86.2

410.1 23.9

79.6

8.588.0

9.3

217.0

23.0

213.0

22.6

702.2

23.7

684.3

23.1

391.2

13.2

325.9

11.0

452.1 46.4

838.8

43.0

838.8

43.0

71.2

6.6

563.6 57.8

556.9

57.1

526.0 61.9

160.7 18.9

146.9 17.3

770.9 26.0

778.7 26.3

1084.7

36.6

640.4 21.6

1475.4

65.2

1475.4

65.2

347.1

8.0

358.8

8.3

1048.4

69.9

315.4

16.6

502.6 51.5

227.2 23.3

281.4 31.8

441.2 49.8

605.0 71.2

600.3 70.6

681.3 80.2

684.8 80.6

591.6

37.6

628.6

42.8

659.0

54.4

477.9

27.4

481.9 27.7

474.1

27.2

370.8 43.6

373.4

43.9

485.5 27.9

526.8 62.0

534.3 62.9

329.9

11.1

744.0

61.2

732.1

60.2

750.8

61.7

695.5 37.5695.5 37.5

971.6

99.5

976.3

100.0

976.3

100.0

976.3

100.0

976.3

100.0

971.7

99.5

0.00.0

658.0 67.4

660.2

67.6

660.2

67.6

658.0 67.4

650.0 76.4

308.1

38.8

302.4

38.1

796.8

100.5

933.8

117.7

858.1

100.8

728.4

91.8

777.7 98.0

388.5 45.7

377.6 44.4

746.7

94.1

315.5

37.1

1338.0

78.7

690.8 57.1

987.0 81.6

771.0 48.4

334.4 19.5334.4 19.5

575.6 67.7

570.9 67.2

452.9

53.3

54.6

5.6

54.6

5.6

533.3 48.1

533.3 48.1

332.6 19.4332.6 19.4

1254.5 42.3

1498.2 54.9

1529.4

56.0

994.5 35.3

1018.0

36.2

1770.6 41.2

983.8 88.7

983.8 88.7

983.9 88.7

1488.7

78.0

500.4

26.4

499.1

26.4

517.0

28.1

210.7

24.8

197.3

23.2

210.7

24.8

197.3

23.2

1252.3 42.3

321.3 83.3160.7 83.3160.7 83.3

647.0

68.9

647.0

68.9

808.3101.9

222.4

11.8

219.3 11.7

222.4

11.8

219.3 11.7

261.8

8.8

210.2 7.1

655.2

67.2

654.9

67.2

Page 585: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 83- Gates-Templeton 230kV & Melones MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:49 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.5

24156VINCENT

MIDWAY229.2

30057DIABLO

534.11.068

GATES539.6

GATES231.9

MORROBAY233.8

TEMPLETN

ARCO228.8

LOSBANOS536.7

30045MOSSLAND

531.81.064

GREGG231.4

HELMS PP234.2

HENRIETA230.4

PANOCHE234.6

HELM232.8

MCMULLN1

HERNDON231.0

LOSBANOS

237.9

COBURN236.2

TESLA535.7

TRACY542.0

METCALF534.4

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES231.9

KEARNEY230.2

30875MC CALL

233.61.015

MOSSLND2

MOSSLND1

WESTLEY231.0

Q128234.0

Q239226.3

Q166226.3

Q194226.2

BORDEN230.5

STOREY 2229.5

STOREY 1229.6

WILSON224.7

WARNERVL224.4

DS AMIGO236.2

MELONES226.6

COTTLE A227.8

COTTLE B224.7

BELLOTA228.7

TESLA E231.7

SN LS PP

TESLA D233.1

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.2

STANDFRD107.3

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

405.8

118.8

873.6

70.0

898.1

72.2

1110.0

50.2

351.0

172.1

351.8

51.6

334.6139.0

333.7

109.6

341.7 8.3

327.6

78.1

163.7 27.7

32.4

2.532.5

14.9

85.3

16.3

85.9

9.6

648.5

151.0

645.5

22.7

253.2

263.5

251.7

179.2

176.0 58.2

337.0

3.5

337.0

3.5

19.5

64.1

225.9 46.8

222.7

62.0

208.3 54.2

61.324.5

60.7 4.3

721.3 30.1

718.9 71.4

856.3

558.1

583.8116.0

588.9

55.3

588.9

55.3

322.8

64.1

322.1

102.8

989.4

53.9

120.8

10.1

203.5 8.8

97.052.8

113.9 0.6

177.1 22.0

239.0 56.8

235.6 69.8

271.5 52.2

277.4 28.2

547.4

38.8

581.4

44.7

609.7

43.1

187.0

57.2

189.2 50.5

185.1

58.0

150.4 9.9

153.3

7.5

191.2 49.5

210.0 43.9

217.9 19.0

312.4

49.3

660.3

190.1

649.7

187.3

664.4

198.4

281.7 11.0281.7 11.0

371.8

104.3

381.3

35.8

381.3

35.8

381.3

35.8

381.3

35.8

371.8

104.3

0.00.0

264.7 33.8

259.1

1.4

259.1

1.4

264.7 33.8

244.9 70.2

121.8

29.7

119.3

30.2

319.3

21.3

375.0

4.6

343.3

10.2

291.1

10.9

304.1 28.1

149.3 30.7

145.7 33.1

276.3

96.6

121.6

33.8

552.3

57.2

639.6 53.4

917.9 91.2

707.5108.1

122.8 58.1122.8 58.1

229.5 52.7

226.2 64.1

174.2

67.4

22.5

1.4

22.5

1.4

501.0 4.4

501.0 4.4

122.5 57.9122.5 57.9

1162.1 16.9

1381.9 128.1

1406.6

178.9

881.5251.1

884.8

252.5

1653.5 139.1

398.2 27.4

398.2 27.8

398.2 27.8

596.3

44.4

200.5

19.6

199.5

23.2

215.3

63.5

77.5

37.9

76.828.6

77.5

37.9

76.8

28.6

1156.2 52.0

121.5 30.460.715.260.715.2

119.7

14.1

119.7

14.1

302.4 93.0

86.9

14.3

87.1 4.6

86.9

14.3

87.1 4.6

205.1

144.0

204.8 16.7

263.8

4.9

262.5

12.2

Page 586: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 84- Gates-Templeton 230kV & Melones amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:50 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.5

24156VINCENT

MIDWAY229.2

30057DIABLO

534.11.068

GATES539.6

GATES231.9

MORROBAY233.8

TEMPLETN

ARCO228.8

LOSBANOS536.7

30045MOSSLAND

531.81.064

GREGG231.4

HELMS PP234.2

HENRIETA230.4

PANOCHE234.6

HELM232.8

MCMULLN1

HERNDON231.0

LOSBANOS

237.9

COBURN236.2

TESLA535.7

TRACY542.0

METCALF534.4

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES231.9

KEARNEY230.2

30875MC CALL

233.61.015

MOSSLND2

MOSSLND1

WESTLEY231.0

Q128234.0

Q239226.3

Q166226.3

Q194226.2

BORDEN230.5

STOREY 2229.5

STOREY 1229.6

WILSON224.7

WARNERVL224.4

DS AMIGO236.2

MELONES226.6

COTTLE A227.8

COTTLE B224.7

BELLOTA228.7

TESLA E231.7

SN LS PP

TESLA D233.1

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.2

STANDFRD107.3

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

458.5

15.5

950.3

0.0

977.0

0.0

1204.8

0.0

423.8

14.3

380.5

12.8

391.6 13.2

375.8

12.7

844.2 86.6

838.7

86.0

410.1 23.9

81.9

8.790.4

9.6

219.1

23.3

215.3

22.9

712.5

24.0

694.8

23.4

396.3

13.4

332.3

11.2

456.2 46.8

840.8

43.1

840.8

43.1

72.1

6.7

567.7 58.2

560.9

57.5

529.7 62.3

162.5 19.1

148.7 17.5

776.6 26.2

784.2 26.5

1088.8

36.7

646.1 21.8

1475.6

65.2

1475.6

65.2

352.1

8.1

363.7

8.4

1060.2

70.7

302.3

15.9

503.5 51.6

276.7 28.4

281.5 31.8

441.2 49.8

609.2 71.7

604.6 71.1

685.7 80.7

689.1 81.1

592.8

37.7

629.9

42.9

660.3

54.5

480.6

27.6

484.5 27.8

476.8

27.4

372.6 43.8

375.3

44.1

488.1 28.0

530.7 62.4

538.3 63.3

340.2

11.5

745.0

61.2

733.1

60.3

751.8

61.8

695.6 37.5695.6 37.5

972.6

99.6

977.2

100.1

977.2

100.1

977.2

100.1

977.2

100.1

972.6

99.6

0.00.0

658.9 67.5

661.1

67.7

661.1

67.7

658.9 67.5

650.1 76.4

312.9

39.4

307.1

38.7

801.4

101.0

939.1

118.4

863.5

101.5

733.0

92.4

784.7 98.9

391.6 46.0

380.6 44.8

752.1

94.8

318.5

37.5

1347.4

79.3

691.7 57.2

994.1 82.2

771.3 48.4

337.6 19.7337.6 19.7

579.5 68.2

574.8 67.6

456.6

53.7

54.6

5.6

54.6

5.6

533.6 48.1

533.6 48.1

335.7 19.6335.7 19.6

1252.5 42.3

1495.6 54.8

1526.6

55.9

987.8 35.1

1011.4

35.9

1767.5 41.1

983.9 88.7

983.9 88.7

984.0 88.7

1488.9

78.0

501.3

26.5

500.1

26.4

558.8

30.4

214.9

25.3

201.6

23.7

214.9

25.3

201.6

23.7

1250.3 42.2

322.1 83.5161.1 83.5161.1 83.5

648.6

69.1

648.6

69.1

813.7102.6

220.2

11.7

216.9 11.6

220.2

11.7

216.9 11.6

269.5

9.1

218.8 7.4

659.3

67.6

659.1

67.6

Page 587: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 85- Coburn-Panoche 230 kV & Exchequer MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:52 2008 2013sprpk_q272_pre.sav

MIDWAY532.9

24156VINCENT

MIDWAY229.7

30057DIABLO

534.31.069

GATES539.8

GATES231.9

MORROBAY234.5

TEMPLETN

ARCO228.9

LOSBANOS536.9

30045MOSSLAND

532.01.064

GREGG231.7

HELMS PP234.3

HENRIETA230.4

PANOCHE234.3

HELM232.7

MCMULLN1

HERNDON231.3

LOSBANOS

237.7

COBURN236.7

TESLA535.8

TRACY542.1

METCALF534.5

METCALF235.0

BALCH3TP234.5

PINE FLT234.7

GATES231.9

KEARNEY230.3

30875MC CALL

233.61.015

MOSSLND2

MOSSLND1

WESTLEY231.0

Q128234.0

Q239228.2

Q166228.2

Q194228.2

BORDEN230.9

STOREY 2229.9

STOREY 1230.1

WILSON226.0

WARNERVL225.1

DS AMIGO235.9

MELONES233.7

COTTLE A231.1

COTTLE B225.4

BELLOTA229.4

TESLA E231.8

SN LS PP

TESLA D233.1

TESLA C232.6

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.2

STANDFRD107.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 83 1400 83 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

411.1

121.9

875.5

67.4

900.0

69.5

1112.5

46.9

407.8

155.5

408.8

36.8

323.8139.3

323.1

108.7

256.3 1.7

248.4

40.4

361.9 27.8

209.1

41.3

44.9

7.245.1

19.0

97.9

12.3

98.7

6.8

650.9

149.1

647.9

20.9

232.8

257.9

231.5

171.8

173.9 54.6

338.9

5.9

338.9

5.9

42.8

70.7

234.9 47.7

231.4

65.2

216.7 55.5

740.4 31.0

737.9 69.3

869.9

559.8

571.8114.7

588.9

57.0

588.9

57.0

323.9

63.1

323.2

103.8

1060.6

66.7

124.3

8.9

199.9 9.1

73.651.4

113.9 0.6

177.1 21.9

234.8 54.2

231.5 66.5

268.8 50.3

274.5 27.0

551.4

39.6

585.7

45.5

614.3

44.0

179.6

54.3

181.8 49.0

178.1

55.0

91.6 7.1

92.7

4.2

183.4 48.1

222.7 51.2

231.7 20.0

306.5

47.6

633.0

177.9

622.8

175.3

636.9

185.9

281.7 11.0281.7 11.0

322.7

75.3

329.7

27.8

329.7

27.8

329.7

27.8

329.7

27.8

322.7

75.3

0.00.0

210.9 23.6

207.4

8.1

207.4

8.1

210.9 23.6

245.0 68.8

118.1

25.0

115.6

25.6

315.8

14.4

370.8

3.6

339.1

2.3

287.7

4.1

303.1 22.0

80.855.2

244.9 5.8

267.3

96.3

217.5

16.5

553.6

53.5

630.8 51.9

933.5 92.9

687.8104.7

125.8 57.5125.8 57.5

238.0 54.0

234.4 66.9

182.4

70.1

22.5

1.4

22.5

1.4

493.6 5.7

493.6 5.7

125.6 57.4125.6 57.4

1187.1 17.3

1387.5 130.9

1412.4

179.9

880.3255.4

883.6

256.7

1658.9 141.6

398.2 26.2

398.2 26.5

398.2 26.5

596.3

44.8

197.0

19.0

196.0

22.3

195.6

59.6

77.9

35.7

77.226.4

77.9

35.7

77.2

26.4

1181.0 56.9

125.5 32.362.816.262.816.2

123.7

14.8

123.7

14.8

293.4 92.8

83.2

15.1

83.4 5.2

83.2

15.1

83.4 5.2

198.4

143.0

198.1 15.2

262.1

2.2

260.8

9.4

Page 588: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 86- Coburn-Panoche 230 kV & Exchequer amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:53 2008 2013sprpk_q272_pre.sav

MIDWAY532.9

24156VINCENT

MIDWAY229.7

30057DIABLO

534.31.069

GATES539.8

GATES231.9

MORROBAY234.5

TEMPLETN

ARCO228.9

LOSBANOS536.9

30045MOSSLAND

532.01.064

GREGG231.7

HELMS PP234.3

HENRIETA230.4

PANOCHE234.3

HELM232.7

MCMULLN1

HERNDON231.3

LOSBANOS

237.7

COBURN236.7

TESLA535.8

TRACY542.1

METCALF534.5

METCALF235.0

BALCH3TP234.5

PINE FLT234.7

GATES231.9

KEARNEY230.3

30875MC CALL

233.61.015

MOSSLND2

MOSSLND1

WESTLEY231.0

Q128234.0

Q239228.2

Q166228.2

Q194228.2

BORDEN230.9

STOREY 2229.9

STOREY 1230.1

WILSON226.0

WARNERVL225.1

DS AMIGO235.9

MELONES233.7

COTTLE A231.1

COTTLE B225.4

BELLOTA229.4

TESLA E231.8

SN LS PP

TESLA D233.1

TESLA C232.6

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.2

STANDFRD107.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 83 1400 83 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

464.6

15.7

951.2

0.0

978.0

0.0

1206.2

0.0

472.8

16.0

439.0

14.8

380.9 12.9

364.5

12.3

631.1 64.7

626.7

64.3

893.6 52.1

530.7

54.4

114.3

12.1123.5

13.1

248.8

26.4

246.3

26.2

714.2

24.1

697.1

23.5

376.4

12.7

310.0

10.5

449.0 46.1

844.9

43.3

844.9

43.3

88.9

8.2

590.6 60.6

583.9

59.9

551.1 64.8

796.9 26.9

804.3 27.1

1101.7

37.2

633.0 21.4

1474.5

65.1

1474.5

65.1

352.9

8.1

365.1

8.4

1136.5

75.8

310.5

16.4

494.6 50.7

225.0 23.1

281.5 31.8

441.2 49.8

597.8 70.3

593.3 69.8

678.6 79.8

681.9 80.2

597.1

38.0

634.5

43.2

665.2

54.9

461.0

26.5

465.6 26.7

457.9

26.3

227.0 26.7

226.2

26.6

468.5 26.9

564.9 66.5

573.0 67.4

333.6

11.3

712.3

58.6

700.9

57.7

718.8

59.1

695.6 37.5695.6 37.5

833.0

85.3

837.0

85.7

837.0

85.7

837.0

85.7

837.0

85.7

833.1

85.3

0.00.0

522.5 53.5

525.0

53.8

525.0

53.8

522.5 53.5

643.8 75.7

300.8

37.9

295.2

37.2

790.6

99.7

927.2

116.9

851.0

100.0

722.5

91.1

776.4 97.9

250.0 29.4

605.1 71.2

728.0

91.8

548.9

64.6

1350.7

79.5

682.1 56.4

1010.9 83.6

749.7 47.0

343.8 20.1343.8 20.1

601.2 70.7

596.5 70.2

478.3

56.3

54.7

5.6

54.7

5.6

525.7 47.4

525.7 47.4

342.0 19.9342.0 19.9

1279.4 43.2

1501.8 55.0

1533.0

56.2

987.8 35.1

1011.7

35.9

1773.2 41.2

983.2 88.7

983.3 88.7

983.3 88.7

1488.9

78.0

492.4

26.0

491.2

26.0

509.2

27.7

213.5

25.1

201.0

23.6

213.5

25.1

201.0

23.6

1277.1 43.1

332.5 86.4166.3 86.4166.3 86.4

669.5

71.3

669.5

71.3

789.3 99.5

211.3

11.3

207.6 11.1

211.3

11.3

207.6 11.1

263.0

8.9

211.6 7.1

654.3

67.1

654.2

67.1

Page 589: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 87- Coburn-Panoche 230 kV & Exchequer MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:55 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.9

24156VINCENT

MIDWAY229.6

30057DIABLO

534.31.069

GATES539.7

GATES231.8

MORROBAY234.5

TEMPLETN

ARCO228.9

LOSBANOS536.7

30045MOSSLAND

531.81.064

GREGG231.6

HELMS PP234.3

HENRIETA230.4

PANOCHE234.3

HELM232.6

MCMULLN1

HERNDON231.2

LOSBANOS

237.7

COBURN236.7

TESLA535.7

TRACY542.0

METCALF534.4

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES231.8

KEARNEY230.3

30875MC CALL

233.51.015

MOSSLND2

MOSSLND1

WESTLEY230.9

Q128234.0

Q239228.2

Q166228.2

Q194228.2

BORDEN230.8

STOREY 2229.9

STOREY 1230.0

WILSON225.9

WARNERVL225.0

DS AMIGO235.9

MELONES233.6

COTTLE A231.0

COTTLE B225.3

BELLOTA229.4

TESLA E231.7

SN LS PP

TESLA D233.1

TESLA C232.6

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.2

STANDFRD107.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 83 1400 83 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

410.9

121.7

872.9

67.9

897.4

70.1

1109.2

47.4

404.4

154.0

405.5

35.2

324.4138.6

323.6

108.0

255.7 1.5

247.9

40.0

361.4 27.9

208.6

40.9

45.8

7.646.0

19.3

98.8

12.0

99.6

6.5

660.7

149.1

657.6

22.0

240.2

257.4

238.8

171.8

175.4 54.9

339.6

5.9

339.6

5.9

43.8

71.4

236.6 47.7

233.1

65.6

218.3 55.5

745.8 31.1

743.2 68.4

874.4

559.8

576.8115.2

588.9

56.7

588.9

56.7

328.7

62.9

328.0

103.5

1071.3

68.8

119.0

8.7

200.3 8.8

95.952.7

113.9 0.5

177.1 21.9

236.4 54.2

233.0 66.8

270.4 50.3

276.2 26.6

552.4

39.6

586.7

45.5

615.4

44.0

180.5

54.6

182.8 49.1

179.0

55.3

91.6 7.1

92.7

4.1

184.3 48.2

224.3 52.0

233.4 20.1

316.0

48.7

633.9

177.9

623.8

175.3

637.9

185.9

281.7 11.2281.7 11.2

323.1

75.5

330.2

27.8

330.2

27.8

330.2

27.8

330.2

27.8

323.2

75.5

0.00.0

211.4 23.7

207.9

8.1

207.9

8.1

211.4 23.7

245.0 68.9

120.0

25.1

117.5

25.7

317.6

14.9

372.9

3.0

341.2

2.7

289.5

4.5

305.7 22.3

82.055.4

246.0 5.5

269.3

96.9

218.6

17.2

557.5

52.7

631.6 52.1

939.9 93.2

687.9104.9

127.1 57.7127.1 57.7

239.6 54.0

236.0 67.2

184.0

70.4

22.5

1.4

22.5

1.4

493.9 5.5

493.9 5.5

126.9 57.6126.9 57.6

1185.3 16.5

1385.1 129.2

1410.0

178.9

874.3253.6

877.5

255.9

1656.0 139.4

398.2 26.3

398.2 26.7

398.2 26.7

596.3

43.7

197.4

18.9

196.4

22.2

212.6

61.5

79.6

35.9

78.826.7

79.6

35.9

78.8

26.7

1179.2 55.8

125.8 32.362.916.162.916.1

123.9

14.7

123.9

14.7

295.3 93.4

82.2

15.5

82.4 5.6

82.2

15.5

82.4 5.6

206.4

144.2

206.2 16.9

263.7

1.9

262.3

9.2

Page 590: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 88- Coburn-Panoche 230 kV & Exchequer amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:56 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.9

24156VINCENT

MIDWAY229.6

30057DIABLO

534.31.069

GATES539.7

GATES231.8

MORROBAY234.5

TEMPLETN

ARCO228.9

LOSBANOS536.7

30045MOSSLAND

531.81.064

GREGG231.6

HELMS PP234.3

HENRIETA230.4

PANOCHE234.3

HELM232.6

MCMULLN1

HERNDON231.2

LOSBANOS

237.7

COBURN236.7

TESLA535.7

TRACY542.0

METCALF534.4

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES231.8

KEARNEY230.3

30875MC CALL

233.51.015

MOSSLND2

MOSSLND1

WESTLEY230.9

Q128234.0

Q239228.2

Q166228.2

Q194228.2

BORDEN230.8

STOREY 2229.9

STOREY 1230.0

WILSON225.9

WARNERVL225.0

DS AMIGO235.9

MELONES233.6

COTTLE A231.0

COTTLE B225.3

BELLOTA229.4

TESLA E231.7

SN LS PP

TESLA D233.1

TESLA C232.6

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.2

STANDFRD107.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 83 1400 83 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

464.3

15.7

948.7

0.0

975.3

0.0

1202.9

0.0

468.9

15.8

435.4

14.7

381.2 12.9

365.0

12.3

629.8 64.6

625.4

64.2

892.5 52.1

529.4

54.3

116.7

12.4125.9

13.4

251.0

26.7

248.6

26.4

724.5

24.4

707.8

23.9

381.5

12.9

316.5

10.7

453.0 46.5

846.7

43.4

846.7

43.4

90.1

8.3

594.9 61.0

588.1

60.3

555.0 65.3

802.9 27.1

810.2 27.3

1105.9

37.3

638.6 21.5

1474.6

65.1

1474.6

65.1

358.0

8.3

370.0

8.5

1148.4

76.6

297.5

15.7

495.6 50.8

274.3 28.1

281.5 31.8

441.3 49.8

601.9 70.8

597.4 70.3

682.7 80.3

686.1 80.7

598.3

38.1

635.8

43.3

666.5

55.0

463.4

26.6

468.0 26.9

460.3

26.4

227.0 26.7

226.2

26.6

470.9 27.0

569.2 67.0

577.3 67.9

343.9

11.6

713.4

58.7

702.0

57.7

719.9

59.2

695.7 37.5695.7 37.5

834.3

85.4

838.2

85.8

838.3

85.8

838.3

85.8

838.3

85.9

834.3

85.4

0.00.0

523.7 53.6

526.2

53.9

526.2

53.9

523.7 53.6

643.9 75.7

305.6

38.5

299.9

37.8

795.2

100.3

932.6

117.6

856.4

100.6

727.1

91.7

783.5 98.8

252.8 29.7

608.2 71.6

733.4

92.5

551.8

64.9

1360.4

80.0

683.0 56.5

1017.9 84.2

749.9 47.0

347.0 20.2347.0 20.2

605.2 71.2

600.6 70.7

482.2

56.7

54.7

5.6

54.7

5.6

526.0 47.4

526.0 47.4

345.2 20.1345.2 20.1

1277.6 43.1

1499.2 54.9

1530.3

56.1

981.1 34.8

1005.1

35.7

1770.1 41.2

983.3 88.7

983.4 88.7

983.4 88.7

1489.1

78.1

493.4

26.1

492.2

26.0

551.1

30.0

217.4

25.6

205.1

24.1

217.4

25.6

205.1

24.1

1275.4 43.0

333.3 86.6166.7 86.6166.7 86.6

671.1

71.5

671.1

71.5

794.7100.2

209.0

11.1

205.2 10.9

209.0

11.1

205.2 10.9

270.9

9.1

220.3 7.4

658.3

67.5

658.2

67.5

Page 591: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 89- Dairyland-Mendota 115kV & Exchequer MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:58 2008 2013sprpk_q272_pre.sav

MIDWAY533.1

24156VINCENT

MIDWAY229.7

30057DIABLO

534.41.069

GATES540.0

GATES232.0

MORROBAY234.5

TEMPLETN

ARCO229.0

LOSBANOS537.1

30045MOSSLAND

532.01.064

GREGG231.6

HELMS PP234.3

HENRIETA230.5

PANOCHE234.9

HELM233.0

MCMULLN1

HERNDON231.2

LOSBANOS

238.1

COBURN236.2

TESLA535.8

TRACY542.2

METCALF534.5

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES232.0

KEARNEY230.4

30875MC CALL

233.61.016

MOSSLND2

MOSSLND1

WESTLEY231.1

Q128234.0

Q239228.3

Q166228.3

Q194228.3

BORDEN230.8

STOREY 2229.8

STOREY 1230.0

WILSON225.6

WARNERVL225.0

DS AMIGO236.3

MELONES233.6

COTTLE A231.1

COTTLE B225.3

BELLOTA229.4

TESLA E231.8

SN LS PP

TESLA D233.1

TESLA C232.7

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.4

STANDFRD107.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 83 1400 83 1

0.0136.2

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

411.0

122.4

875.3

66.7

899.9

68.8

1112.3

45.9

407.2

158.5

408.2

39.7

324.0140.6

323.3

109.9

256.9 2.1

249.0

41.1

362.4 27.3

209.7

42.0

44.0

6.644.2

18.5

96.9

13.0

97.7

7.3

644.8

149.4

641.9

20.4

229.3

259.0

227.9

172.8

174.9 57.9

339.6

4.7

339.6

4.7

32.9

64.8

230.0 46.2

226.6

62.3

212.2 53.8

63.024.1

62.3 4.0

719.0 33.2

716.6 75.0

865.9

561.6

584.1114.0

588.9

56.8

588.9

56.8

320.9

63.4

320.2

104.0

1050.7

63.1

122.0

9.6

197.7 9.7

73.051.9

113.9 0.9

177.1 22.1

237.3 57.0

233.9 69.7

269.5 53.1

275.2 29.6

549.7

38.2

583.8

44.0

612.3

42.4

188.1

57.5

190.5 50.5

186.3

58.2

152.0 10.3

155.0

7.3

192.4 49.5

213.5 44.4

221.6 18.0

305.8

45.7

631.9

178.2

621.7

175.6

635.9

186.2

281.7 10.7281.7 10.7

322.2

75.0

329.2

27.8

329.2

27.8

329.2

27.8

329.2

27.8

322.2

75.0

0.00.0

210.3 23.4

206.9

8.1

206.9

8.1

210.3 23.4

245.0 68.8

118.6

26.8

116.1

27.3

316.3

16.5

371.4

1.1

339.7

4.7

288.2

6.1

297.6 24.7

78.456.1

242.6 5.1

263.6

96.7

215.2

16.5

550.8

57.4

633.3 52.1

936.9 93.9

690.7104.8

125.7 57.2125.7 57.2

233.4 52.4

230.0 64.3

178.0

67.5

22.5

1.4

22.5

1.4

495.2 5.8

495.2 5.8

125.5 57.0125.5 57.0

1169.2 15.7

1386.4 131.1

1411.3

180.6

877.0256.3

880.2

258.1

1658.3 142.0

398.2 26.3

398.2 26.7

398.2 26.6

596.3

47.2

194.9

19.1

193.9

22.2

192.7

60.4

82.2

38.9

81.430.1

82.2

38.9

81.4

30.1

1163.3 52.0

124.8 31.962.416.062.416.0

122.9

14.7

122.9

14.7

289.6 93.3

84.4

14.2

84.6 4.3

84.4

14.2

84.6 4.3

198.2

141.4

197.9 13.5

262.6

5.2

261.3

12.4

Page 592: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 90- Dairyland-Mendota 115kV & Exchequer amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:24:59 2008 2013sprpk_q272_pre.sav

MIDWAY533.1

24156VINCENT

MIDWAY229.7

30057DIABLO

534.41.069

GATES540.0

GATES232.0

MORROBAY234.5

TEMPLETN

ARCO229.0

LOSBANOS537.1

30045MOSSLAND

532.01.064

GREGG231.6

HELMS PP234.3

HENRIETA230.5

PANOCHE234.9

HELM233.0

MCMULLN1

HERNDON231.2

LOSBANOS

238.1

COBURN236.2

TESLA535.8

TRACY542.2

METCALF534.5

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES232.0

KEARNEY230.4

30875MC CALL

233.61.016

MOSSLND2

MOSSLND1

WESTLEY231.1

Q128234.0

Q239228.3

Q166228.3

Q194228.3

BORDEN230.8

STOREY 2229.8

STOREY 1230.0

WILSON225.6

WARNERVL225.0

DS AMIGO236.3

MELONES233.6

COTTLE A231.1

COTTLE B225.3

BELLOTA229.4

TESLA E231.8

SN LS PP

TESLA D233.1

TESLA C232.7

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.4

STANDFRD107.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 83 1400 83 1

0.0136.2

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

464.5

15.7

950.8

0.0

977.5

0.0

1205.7

0.0

473.2

16.0

438.5

14.8

381.6 12.9

365.0

12.3

632.6 64.9

628.0

64.4

894.8 52.2

532.2

54.6

111.7

11.9120.8

12.8

246.5

26.2

243.9

25.9

707.6

23.9

690.3

23.3

374.7

12.6

307.4

10.4

453.0 46.5

846.5

43.3

846.5

43.3

78.2

7.2

576.6 59.1

570.0

58.5

538.1 63.3

165.9 19.5

152.7 17.9

773.7 26.1

781.9 26.4

1099.0

37.1

645.9 21.8

1474.6

65.1

1474.6

65.1

349.7

8.1

362.0

8.4

1125.4

75.1

304.9

16.1

489.2 50.2

224.4 23.0

281.4 31.8

441.2 49.8

604.7 71.1

600.0 70.6

680.6 80.1

684.1 80.5

595.2

37.9

632.4

43.1

663.0

54.7

483.5

27.8

487.3 28.0

479.7

27.5

376.6 44.3

379.3

44.6

490.9 28.2

539.2 63.4

546.7 64.3

332.3

11.2

711.1

58.5

699.7

57.6

717.6

59.1

695.5 37.5695.5 37.5

831.5

85.2

835.5

85.6

835.5

85.6

835.5

85.6

835.5

85.6

831.5

85.2

0.00.0

521.1 53.4

523.5

53.6

523.5

53.6

521.1 53.4

643.6 75.6

303.0

38.2

297.4

37.5

792.2

99.9

928.9

117.1

852.8

100.2

724.0

91.3

764.1 96.3

246.8 29.0

599.6 70.5

719.5

90.7

543.3

63.9

1343.1

79.0

684.6 56.6

1014.5 83.9

752.7 47.2

343.1 20.0343.1 20.0

588.0 69.2

583.4 68.6

465.1

54.7

54.6

5.6

54.6

5.6

527.3 47.6

527.3 47.6

341.3 19.9341.3 19.9

1259.8 42.5

1500.4 55.0

1531.8

56.1

984.4 35.0

1008.6

35.8

1772.3 41.2

983.3 88.7

983.3 88.7

983.4 88.7

1488.4

78.0

486.9

25.7

485.8

25.7

502.6

27.4

226.4

26.6

213.3

25.1

226.4

26.6

213.3

25.1

1257.7 42.4

330.4 85.9165.2 85.9165.2 85.9

665.3

70.9

665.3

70.9

780.6 98.4

213.8

11.4

210.5 11.2

213.8

11.4

210.5 11.2

261.7

8.8

211.2 7.1

655.8

67.3

655.6

67.2

Page 593: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 91- Dairyland-Mendota 115kV & Exchequer MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:01 2008 2013sprpk_q272_pst_v2.sav

MIDWAY533.0

24156VINCENT

MIDWAY229.7

30057DIABLO

534.41.069

GATES539.9

GATES232.0

MORROBAY234.5

TEMPLETN

ARCO229.0

LOSBANOS537.0

30045MOSSLAND

531.91.064

GREGG231.6

HELMS PP234.3

HENRIETA230.5

PANOCHE234.8

HELM232.9

MCMULLN1

HERNDON231.2

LOSBANOS

238.0

COBURN236.2

TESLA535.8

TRACY542.1

METCALF534.4

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES232.0

KEARNEY230.3

30875MC CALL

233.61.016

MOSSLND2

MOSSLND1

WESTLEY231.1

Q128234.0

Q239228.3

Q166228.3

Q194228.2

BORDEN230.8

STOREY 2229.8

STOREY 1229.9

WILSON225.5

WARNERVL225.0

DS AMIGO236.3

MELONES233.5

COTTLE A231.0

COTTLE B225.2

BELLOTA229.4

TESLA E231.8

SN LS PP

TESLA D233.1

TESLA C232.7

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.3

STANDFRD107.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 83 1400 83 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

410.8

122.2

872.8

67.2

897.3

69.3

1109.1

46.5

403.8

157.0

404.8

38.1

324.6139.9

323.8

109.3

256.4 2.0

248.5

40.7

361.9 27.4

209.2

41.6

44.8

7.045.1

18.8

97.8

12.6

98.6

7.0

654.5

149.4

651.5

21.5

236.6

258.6

235.2

172.8

176.5 58.2

340.3

4.7

340.3

4.7

33.8

65.4

231.6 46.1

228.2

62.6

213.6 53.8

63.824.1

63.1 4.2

724.1 33.3

721.7 74.2

870.4

561.6

589.3114.5

588.9

56.6

588.9

56.6

325.7

63.2

325.0

103.7

1061.3

65.1

116.7

9.5

198.1 9.5

95.353.3

113.9 0.8

177.1 22.0

239.0 57.0

235.5 70.1

271.1 53.2

277.0 29.3

550.7

38.1

584.9

44.0

613.4

42.4

189.1

57.8

191.5 50.7

187.3

58.6

152.7 10.6

155.7

7.4

193.4 49.6

214.9 45.1

223.2 18.0

315.2

46.7

632.9

178.2

622.7

175.6

636.8

186.2

281.7 10.8281.7 10.8

322.6

75.2

329.6

27.8

329.6

27.8

329.6

27.8

329.7

27.8

322.7

75.2

0.00.0

210.8 23.6

207.3

8.1

207.3

8.1

210.8 23.6

245.0 68.8

120.5

26.9

118.0

27.5

318.0

16.9

373.4

0.6

341.7

5.1

289.9

6.5

300.1 25.1

79.656.3

243.7 4.8

265.5

97.3

216.3

17.2

554.6

56.7

634.1 52.2

943.3 94.2

690.9105.0

127.0 57.3127.0 57.3

234.9 52.4

231.5 64.6

179.5

67.8

22.5

1.4

22.5

1.4

495.5 5.6

495.5 5.6

126.8 57.2126.8 57.2

1167.2 14.8

1384.1 129.4

1408.9

179.6

871.0254.5

874.2

257.3

1655.4 139.8

398.2 26.5

398.2 26.9

398.2 26.8

596.3

46.2

195.3

19.0

194.3

22.1

209.7

62.3

84.0

39.0

83.130.4

84.0

39.0

83.1

30.4

1161.3 50.8

125.0 31.962.515.962.515.9

123.2

14.5

123.2

14.5

291.5 93.9

83.4

14.6

83.6 4.6

83.4

14.6

83.6 4.6

206.2

142.5

205.9 15.1

264.3

4.9

262.9

12.2

Page 594: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 92- Dairyland-Mendota 115kV & Exchequer amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:02 2008 2013sprpk_q272_pst_v2.sav

MIDWAY533.0

24156VINCENT

MIDWAY229.7

30057DIABLO

534.41.069

GATES539.9

GATES232.0

MORROBAY234.5

TEMPLETN

ARCO229.0

LOSBANOS537.0

30045MOSSLAND

531.91.064

GREGG231.6

HELMS PP234.3

HENRIETA230.5

PANOCHE234.8

HELM232.9

MCMULLN1

HERNDON231.2

LOSBANOS

238.0

COBURN236.2

TESLA535.8

TRACY542.1

METCALF534.4

METCALF234.9

BALCH3TP234.5

PINE FLT234.7

GATES232.0

KEARNEY230.3

30875MC CALL

233.61.016

MOSSLND2

MOSSLND1

WESTLEY231.1

Q128234.0

Q239228.3

Q166228.3

Q194228.2

BORDEN230.8

STOREY 2229.8

STOREY 1229.9

WILSON225.5

WARNERVL225.0

DS AMIGO236.3

MELONES233.5

COTTLE A231.0

COTTLE B225.2

BELLOTA229.4

TESLA E231.8

SN LS PP

TESLA D233.1

TESLA C232.7

Q235SWST232.6

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.3

STANDFRD107.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 83 1400 83 1

0.0136.1

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

464.2

15.7

948.2

0.0

974.8

0.0

1202.4

0.0

469.3

15.8

434.8

14.7

381.9 12.9

365.5

12.3

631.3 64.8

626.8

64.3

893.7 52.1

530.9

54.5

114.0

12.1123.1

13.1

248.7

26.4

246.1

26.1

717.9

24.2

700.9

23.6

379.7

12.8

313.8

10.6

457.1 46.9

848.4

43.4

848.4

43.4

79.2

7.3

580.6 59.6

574.0

58.9

541.8 63.7

167.6 19.7

154.5 18.2

779.4 26.3

787.5 26.6

1103.1

37.2

651.6 22.0

1474.8

65.1

1474.8

65.1

354.8

8.2

366.8

8.5

1137.0

75.8

291.9

15.4

490.1 50.3

273.6 28.1

281.4 31.8

441.2 49.8

609.0 71.6

604.3 71.1

684.9 80.6

688.4 81.0

596.3

37.9

633.6

43.1

664.3

54.8

486.1

27.9

490.0 28.1

482.3

27.7

378.4 44.5

381.1

44.8

493.6 28.3

543.1 63.9

550.6 64.8

342.6

11.6

712.2

58.6

700.8

57.7

718.7

59.1

695.5 37.5695.5 37.5

832.7

85.3

836.7

85.7

836.7

85.7

836.7

85.7

836.8

85.7

832.8

85.3

0.00.0

522.3 53.5

524.7

53.7

524.7

53.7

522.3 53.5

643.7 75.6

307.7

38.8

302.0

38.1

796.7

100.4

934.2

117.8

858.1

100.8

728.6

91.8

771.1 97.2

249.5 29.3

602.6 70.9

724.8

91.4

546.2

64.3

1352.4

79.6

685.6 56.7

1021.5 84.5

753.0 47.2

346.3 20.2346.3 20.2

591.8 69.6

587.2 69.1

468.8

55.2

54.6

5.6

54.6

5.6

527.7 47.6

527.7 47.6

344.5 20.1344.5 20.1

1257.8 42.4

1497.9 54.9

1529.0

56.0

977.8 34.7

1002.0

35.6

1769.1 41.1

983.4 88.7

983.4 88.7

983.5 88.7

1488.6

78.0

487.9

25.8

486.7

25.7

544.4

29.6

230.5

27.1

217.6

25.6

230.5

27.1

217.6

25.6

1255.8 42.4

331.2 86.0165.6 86.0165.6 86.0

666.8

71.0

666.8

71.0

786.0 99.1

211.6

11.3

208.1 11.1

211.6

11.3

208.1 11.1

269.5

9.1

219.8 7.4

660.0

67.7

659.8

67.7

Page 595: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 93- Westley-Los Banos 230kV & Kerckhoff MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:04 2008 2013sprpk_q272_pre.sav

MIDWAY532.3

24156VINCENT

MIDWAY229.5

30057DIABLO

533.81.068

GATES538.8

GATES231.7

MORROBAY234.4

TEMPLETN

ARCO228.7

LOSBANOS535.2

30045MOSSLAND

529.91.060

GREGG231.5

HELMS PP234.3

HENRIETA230.3

PANOCHE234.5

HELM233.0

MCMULLN1

HERNDON231.1

LOSBANOS

236.7

COBURN235.4

TESLA533.7

TRACY539.8

METCALF532.5

METCALF234.1

BALCH3TP234.4

PINE FLT234.6

GATES231.7

KEARNEY230.3

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY228.5

Q128233.8

Q239228.1

Q166228.1

Q194228.0

BORDEN230.7

STOREY 2229.7

STOREY 1229.9

WILSON225.6

WARNERVL223.9

DS AMIGO235.5

MELONES232.9

COTTLE A230.3

COTTLE B224.2

BELLOTA228.7

TESLA E230.8

SN LS PP

TESLA D232.1

TESLA C232.0

Q235SWST231.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.1

STANDFRD106.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

411.6

119.8

877.6

70.8

902.2

73.1

1115.0

51.4

411.3

143.3

412.4

25.0

322.8133.8

322.1

103.0

255.5 1.3

247.7

39.7

360.9 28.1

208.5

40.6

46.4

7.446.6

19.0

99.4

12.1

100.2

6.7

656.4

132.4

653.4

5.5

235.4

243.0

234.1

156.8

143.4 48.1

345.3

7.1

345.3

7.1

386.0

83.4

162.5 36.5

160.8

38.8

149.8 41.9

76.723.1

75.7 5.3

789.4 39.9

786.5 68.4

837.9

537.4

663.2114.9

588.9

55.8

588.9

55.8

326.2

54.8

325.5

110.9

1073.0

59.2

112.3

8.9

182.9 9.6

67.349.7

113.9 0.3

177.1 21.3

200.8 49.4

198.4 56.5

233.7 44.9

238.1 29.6

552.6

39.2

586.9

45.1

615.5

43.5

202.5

61.8

205.6 51.7

200.8

62.6

164.8 14.4

168.3

7.2

207.4 50.6

240.1 54.0

250.6 14.2

465.6

40.1

634.6

173.9

624.4

171.4

638.6

181.9

281.7 12.4281.7 12.4

323.4

75.2

330.4

27.4

330.5

27.4

330.5

27.4

330.5

27.4

323.4

75.2

0.00.0

211.7 24.3

208.2

8.5

208.2

8.5

211.7 24.3

245.0 68.9

117.5

24.8

115.1

25.4

315.0

15.6

369.8

2.0

338.1

3.8

286.8

5.4

345.4 13.8

93.553.7

257.3 5.2

268.2

102.6

229.3

21.3

711.5 59.0

941.7 82.6

795.1115.0

84.265.184.265.1

170.3 40.4

168.5 43.3

116.5

46.5

22.5

1.4

22.5

1.4

579.3 7.6

579.3 7.6

84.064.484.064.4

1099.1 20.5

1380.2 119.0

1405.0

167.5

869.1233.3

872.2

236.5

1653.4 128.1

398.2 27.0

398.2 27.4

398.2 27.4

596.3

42.3

180.5

15.9

179.6

17.9

177.7

54.9

53.4

34.8

53.123.4

53.4

34.8

53.1

23.4

1093.8 45.8

145.3 36.472.618.272.618.2

142.7

12.5

142.7

12.5

294.2 99.1

215.5

12.8

216.9 15.6

215.5

12.8

216.9 15.6

343.9

134.6

343.1 18.6

229.2

5.1

228.2

9.8

Page 596: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 94- Westley-Los Banos 230kV & Kerckhoff amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:06 2008 2013sprpk_q272_pre.sav

MIDWAY532.3

24156VINCENT

MIDWAY229.5

30057DIABLO

533.81.068

GATES538.8

GATES231.7

MORROBAY234.4

TEMPLETN

ARCO228.7

LOSBANOS535.2

30045MOSSLAND

529.91.060

GREGG231.5

HELMS PP234.3

HENRIETA230.3

PANOCHE234.5

HELM233.0

MCMULLN1

HERNDON231.1

LOSBANOS

236.7

COBURN235.4

TESLA533.7

TRACY539.8

METCALF532.5

METCALF234.1

BALCH3TP234.4

PINE FLT234.6

GATES231.7

KEARNEY230.3

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY228.5

Q128233.8

Q239228.1

Q166228.1

Q194228.0

BORDEN230.7

STOREY 2229.7

STOREY 1229.9

WILSON225.6

WARNERVL223.9

DS AMIGO235.5

MELONES232.9

COTTLE A230.3

COTTLE B224.2

BELLOTA228.7

TESLA E230.8

SN LS PP

TESLA D232.1

TESLA C232.0

Q235SWST231.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.1

STANDFRD106.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

465.0

15.7

955.0

0.0

981.8

0.0

1210.7

0.0

472.4

15.9

442.7

14.9

377.9 12.8

362.3

12.2

629.4 64.6

625.1

64.1

891.6 52.0

529.2

54.3

118.1

12.6127.1

13.5

252.7

26.8

250.2

26.6

717.5

24.2

704.8

23.8

367.0

12.4

303.9

10.3

372.5 38.2

861.5

44.1

861.5

44.1

426.0

39.3

410.0 42.1

403.5

41.4

382.9 45.1

197.2 23.2

186.1 21.9

852.7 28.8

860.1 29.0

1064.7

35.9

733.3 24.7

1475.2

65.2

1475.2

65.2

354.4

8.2

371.0

8.6

1151.4

76.6

281.0

14.8

453.0 46.5

209.7 21.5

281.7 31.8

441.4 49.8

512.4 60.3

507.7 59.7

589.8 69.4

593.5 69.8

600.6

38.1

638.2

43.3

669.1

55.0

522.3

30.0

526.2 30.2

518.7

29.8

410.3 48.2

413.3

48.6

529.6 30.4

610.8 71.9

618.0 72.7

504.1

17.0

713.7

58.6

702.3

57.7

720.2

59.2

696.2 37.5696.2 37.5

835.4

85.6

839.3

86.0

839.4

86.0

839.4

86.0

839.4

86.0

835.5

85.6

0.00.0

524.7 53.7

527.3

54.0

527.3

54.0

524.7 53.7

644.2 75.7

299.5

37.8

294.0

37.1

789.1

99.5

925.3

116.7

849.1

99.8

720.9

90.9

884.4111.5

276.0 32.4

638.1 75.1

739.5

93.2

581.3

68.4

772.4 63.6

1022.6 84.2

869.1 54.3

265.9 15.5265.9 15.5

430.8 50.7

426.3 50.2

307.4

36.2

54.9

5.6

54.9

5.6

619.7 55.7

619.7 55.7

263.3 15.4263.3 15.4

1189.2 40.1

1498.7 54.9

1527.5

56.0

973.5 34.6

995.8

35.4

1773.7 41.2

983.7 88.7

983.7 88.7

983.8 88.7

1489.4

78.1

450.9

23.8

449.8

23.8

463.4

25.2

158.9

18.7

142.8

16.8

158.9

18.7

142.8

16.8

1187.0 40.0

386.2 99.8193.1 99.8193.1 99.8

777.4

82.8

777.4

82.8

800.6100.9

545.3

29.0

543.3 28.9

545.3

29.0

543.3 28.9

398.4

13.4

367.5 12.4

572.7

58.7

572.5

58.7

Page 597: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 95- Westley-Los Banos 230kV & Kerckhoff MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:08 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.2

24156VINCENT

MIDWAY229.4

30057DIABLO

533.81.068

GATES538.7

GATES231.7

MORROBAY234.4

TEMPLETN

ARCO228.7

LOSBANOS535.0

30045MOSSLAND

529.81.060

GREGG231.5

HELMS PP234.2

HENRIETA230.3

PANOCHE234.4

HELM232.9

MCMULLN1

HERNDON231.0

LOSBANOS

236.6

COBURN235.3

TESLA533.5

TRACY539.7

METCALF532.3

METCALF234.0

BALCH3TP234.4

PINE FLT234.6

GATES231.7

KEARNEY230.3

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY228.5

Q128233.8

Q239228.0

Q166228.0

Q194228.0

BORDEN230.7

STOREY 2229.7

STOREY 1229.9

WILSON225.5

WARNERVL223.8

DS AMIGO235.4

MELONES232.8

COTTLE A230.2

COTTLE B224.1

BELLOTA228.7

TESLA E230.7

SN LS PP

TESLA D232.1

TESLA C232.0

Q235SWST231.4

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.1

STANDFRD106.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

411.8

119.4

878.0

71.3

902.7

73.6

1115.5

52.1

412.4

141.4

413.5

23.2

322.6133.0

321.8

102.1

254.9 1.1

247.1

39.2

360.3 28.3

207.9

40.2

47.5

7.747.8

19.3

100.5

11.8

101.4

6.5

663.0

132.0

659.9

6.0

239.1

242.2

237.7

156.2

144.9 48.3

346.0

7.1

346.0

7.1

389.3

84.2

163.6 36.3

161.9

38.9

150.9 41.8

77.423.1

76.4 5.5

793.3 39.9

790.4 67.6

841.8

536.9

667.3115.1

588.9

55.5

588.9

55.5

329.5

54.4

328.8

110.8

1084.3

61.1

107.3

8.7

183.4 9.3

89.651.0

113.9 0.4

177.1 21.2

202.3 49.4

199.8 56.7

235.2 45.0

239.6 29.3

553.5

39.3

587.8

45.2

616.5

43.6

203.4

62.1

206.5 51.8

201.7

62.9

165.5 14.7

169.1

7.3

208.4 50.7

241.5 54.8

252.2 14.1

472.7

40.5

635.8

173.8

625.6

171.3

639.8

181.7

281.7 12.6281.7 12.6

323.9

75.4

331.0

27.4

331.0

27.4

331.0

27.4

331.0

27.4

324.0

75.4

0.00.0

212.3 24.5

208.7

8.6

208.7

8.6

212.3 24.5

245.0 69.0

119.3

24.9

116.9

25.5

316.6

16.1

371.7

1.5

340.1

4.3

288.5

5.8

347.8 14.0

94.653.8

258.4 4.9

269.8

103.2

230.3

21.9

712.7 58.8

947.9 82.3

795.8114.7

85.265.285.265.2

171.3 40.3

169.5 43.3

117.5

46.5

22.5

1.4

22.5

1.4

580.1 7.5

580.1 7.5

85.164.585.164.5

1097.9 20.1

1379.8 118.5

1404.6

166.9

865.5232.5

868.6

236.2

1652.9 127.4

398.2 27.2

398.2 27.6

398.2 27.6

596.3

41.1

181.0

15.8

180.2

17.8

194.9

56.7

54.7

34.9

54.323.7

54.7

34.9

54.3

23.7

1092.6 45.4

145.6 36.372.818.272.818.2

143.1

12.3

143.1

12.3

295.8 99.6

215.4

12.8

216.8 15.6

215.4

12.8

216.8 15.6

349.8

135.1

349.0 19.7

230.7

4.8

229.7

9.6

Page 598: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 96- Westley-Los Banos 230kV & Kerckhoff amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:09 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.2

24156VINCENT

MIDWAY229.4

30057DIABLO

533.81.068

GATES538.7

GATES231.7

MORROBAY234.4

TEMPLETN

ARCO228.7

LOSBANOS535.0

30045MOSSLAND

529.81.060

GREGG231.5

HELMS PP234.2

HENRIETA230.3

PANOCHE234.4

HELM232.9

MCMULLN1

HERNDON231.0

LOSBANOS

236.6

COBURN235.3

TESLA533.5

TRACY539.7

METCALF532.3

METCALF234.0

BALCH3TP234.4

PINE FLT234.6

GATES231.7

KEARNEY230.3

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY228.5

Q128233.8

Q239228.0

Q166228.0

Q194228.0

BORDEN230.7

STOREY 2229.7

STOREY 1229.9

WILSON225.5

WARNERVL223.8

DS AMIGO235.4

MELONES232.8

COTTLE A230.2

COTTLE B224.1

BELLOTA228.7

TESLA E230.7

SN LS PP

TESLA D232.1

TESLA C232.0

Q235SWST231.4

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.1

STANDFRD106.4

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

465.1

15.7

955.7

0.0

982.5

0.0

1211.5

0.0

473.0

16.0

443.9

15.0

377.4 12.7

361.8

12.2

627.8 64.4

623.6

64.0

890.2 51.9

527.7

54.1

121.1

12.9130.1

13.8

255.4

27.1

253.1

26.9

724.5

24.4

712.1

24.0

369.2

12.5

307.0

10.4

376.2 38.6

863.3

44.2

863.3

44.2

429.8

39.6

412.8 42.3

406.3

41.7

385.5 45.4

199.0 23.4

187.9 22.1

857.1 28.9

864.5 29.2

1068.1

36.0

737.9 24.9

1475.4

65.2

1475.4

65.2

357.9

8.3

374.4

8.6

1163.9

77.5

268.5

14.2

454.4 46.6

258.5 26.5

281.7 31.8

441.4 49.8

516.1 60.7

511.5 60.2

593.6 69.8

597.2 70.3

601.8

38.1

639.4

43.4

670.3

55.1

524.7

30.1

528.6 30.3

521.1

29.9

412.1 48.4

415.2

48.8

531.9 30.5

614.8 72.3

621.9 73.2

511.9

17.3

715.1

58.7

703.7

57.8

721.6

59.3

696.3 37.5696.3 37.5

837.0

85.7

840.9

86.1

841.0

86.1

841.0

86.1

841.0

86.1

837.1

85.7

0.00.0

526.3 53.9

528.8

54.2

528.8

54.2

526.3 53.9

644.4 75.7

304.1

38.3

298.4

37.6

793.5

100.0

930.4

117.3

854.2

100.4

725.3

91.4

891.2112.4

278.6 32.7

640.9 75.4

744.2

93.8

584.1

68.7

773.8 63.7

1029.5 84.8

870.0 54.4

268.1 15.6268.1 15.6

433.5 51.0

429.0 50.5

309.9

36.5

54.9

5.6

54.9

5.6

620.6 55.7

620.6 55.7

265.5 15.5265.5 15.5

1188.2 40.1

1498.5 54.9

1527.3

55.9

969.7 34.4

992.0

35.2

1773.5 41.2

983.8 88.7

983.8 88.7

983.9 88.7

1489.6

78.1

452.3

23.9

451.3

23.8

506.0

27.5

161.7

19.0

145.8

17.2

161.7

19.0

145.8

17.2

1186.0 40.0

387.2100.1193.6100.1193.6100.1

779.5

83.0

779.5

83.0

805.3101.5

545.2

29.0

543.2 28.9

545.2

29.0

543.2 28.9

404.6

13.7

374.0 12.6

576.5

59.1

576.3

59.1

Page 599: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 97- McCall-West Fresno & Cal Ave.-McCall 115kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:11 2008 2013sprpk_q272_pre.sav

MIDWAY532.4

24156VINCENT

MIDWAY229.5

30057DIABLO

534.01.068

GATES539.0

GATES231.5

MORROBAY234.4

TEMPLETN

ARCO228.6

LOSBANOS536.0

30045MOSSLAND

530.91.062

GREGG231.6

HELMS PP234.3

HENRIETA230.1

PANOCHE234.1

HELM232.3

MCMULLN1

HERNDON231.2

LOSBANOS

237.3

COBURN235.6

TESLA534.9

TRACY541.3

METCALF533.5

METCALF234.5

BALCH3TP234.7

PINE FLT234.9

GATES231.5

KEARNEY230.1

30875MC CALL

233.91.017

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128234.3

Q239228.0

Q166228.0

Q194228.0

BORDEN230.8

STOREY 2229.8

STOREY 1230.0

WILSON225.8

WARNERVL224.5

DS AMIGO235.5

MELONES233.1

COTTLE A230.5

COTTLE B224.8

BELLOTA229.0

TESLA E231.4

SN LS PP

TESLA D232.8

TESLA C232.4

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.0

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 84 1400 84 1

0.0136.6

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

411.7

120.3

877.1

70.0

901.7

72.3

1114.4

50.4

412.2

145.2

413.3

26.9

322.7135.0

322.0

104.1

253.4 0.5

245.7

38.0

359.0 28.8

206.5

39.0

49.7

9.150.0

20.5

102.7

10.5

103.6

5.4

679.8

146.4

676.6

21.8

249.2

253.0

247.8

168.0

196.7 60.6

332.0

6.1

332.0

6.1

53.7

72.5

243.3 46.0

239.5

65.6

224.5 54.3

68.824.8

68.0 5.9

740.7 33.8

738.2 71.4

897.0

558.8

609.4115.3

588.9

56.3

588.9

56.3

338.1

61.1

337.3

103.7

1109.2

76.5

141.3

7.8

241.3 3.0

88.851.7

113.9 2.5

177.2 23.3

276.2 59.0

271.7 78.8

311.9 55.9

319.6 21.2

556.5

38.9

591.0

44.7

619.9

43.1

194.2

59.7

196.8 51.4

192.4

60.5

157.4 12.9

160.7

8.1

198.7 50.3

224.5 50.8

233.7 18.6

344.8

48.0

638.3

176.7

628.1

174.2

642.3

184.7

281.7 8.2281.7 8.2

325.1

76.3

332.2

27.8

332.2

27.8

332.2

27.8

332.3

27.8

325.1

76.3

0.00.0

213.5 24.5

209.9

8.2

209.9

8.2

213.5 24.5

245.0 69.0

116.6

24.9

114.2

25.4

315.3

14.8

370.2

3.1

338.5

2.8

287.2

4.5

339.3 18.2

96.554.0

260.3 4.4

291.7

100.7

232.1

22.8

570.3

51.4

635.7 51.0

985.7 92.9

684.9103.7

135.6 58.1135.6 58.1

245.9 52.8

242.2 67.0

190.2

70.2

22.5

1.4

22.5

1.4

494.4 5.8

494.4 5.8

135.3 58.2135.3 58.2

1165.6 13.7

1384.9 127.7

1409.8

176.2

850.6251.3

853.6

257.0

1656.3 137.1

398.2 26.6

398.2 27.0

398.2 27.0

596.3

38.3

237.1

23.2

235.7

30.0

227.1

64.4

81.5

37.0

80.728.1

81.5

37.0

80.7

28.1

1159.6 50.0

130.6 32.465.316.265.316.2

128.5

13.4

128.5

13.4

317.8 96.8

76.7

16.6

76.9 6.4

76.7

16.6

76.9 6.4

229.9

144.4

229.5 18.9

284.8

0.2

283.3

8.9

Page 600: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 98- McCall-West Fresno & Cal Ave.-McCall 115kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:13 2008 2013sprpk_q272_pre.sav

MIDWAY532.4

24156VINCENT

MIDWAY229.5

30057DIABLO

534.01.068

GATES539.0

GATES231.5

MORROBAY234.4

TEMPLETN

ARCO228.6

LOSBANOS536.0

30045MOSSLAND

530.91.062

GREGG231.6

HELMS PP234.3

HENRIETA230.1

PANOCHE234.1

HELM232.3

MCMULLN1

HERNDON231.2

LOSBANOS

237.3

COBURN235.6

TESLA534.9

TRACY541.3

METCALF533.5

METCALF234.5

BALCH3TP234.7

PINE FLT234.9

GATES231.5

KEARNEY230.1

30875MC CALL

233.91.017

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128234.3

Q239228.0

Q166228.0

Q194228.0

BORDEN230.8

STOREY 2229.8

STOREY 1230.0

WILSON225.8

WARNERVL224.5

DS AMIGO235.5

MELONES233.1

COTTLE A230.5

COTTLE B224.8

BELLOTA229.0

TESLA E231.4

SN LS PP

TESLA D232.8

TESLA C232.4

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.0

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 83 1400 84 1400 84 1

0.0136.6

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

465.1

15.7

954.1

0.0

980.9

0.0

1209.6

0.0

473.9

16.0

443.6

15.0

378.2 12.8

362.4

12.2

624.3 64.0

620.2

63.6

887.2 51.8

524.2

53.8

127.1

13.5136.5

14.5

260.8

27.7

258.8

27.5

744.8

25.1

729.2

24.6

385.1

13.0

322.4

10.9

507.6 52.1

827.9

42.4

827.9

42.4

97.1

9.0

610.7 62.6

604.2

62.0

569.7 67.0

180.5 21.2

167.2 19.7

798.7 26.9

806.5 27.2

1127.2

38.0

674.5 22.8

1474.9

65.1

1474.9

65.1

368.0

8.5

380.2

8.8

1190.8

79.3

352.9

18.6

595.5 61.1

257.9 26.4

281.1 31.7

440.9 49.8

702.1 82.6

697.7 82.1

787.7 92.7

790.6 93.0

603.7

38.3

641.4

43.6

672.4

55.4

500.1

28.7

504.1 28.9

496.4

28.5

391.1 46.0

394.2

46.3

507.5 29.1

570.4 67.1

578.2 68.0

375.0

12.7

718.2

59.0

706.8

58.1

724.8

59.6

694.4 37.4694.4 37.4

840.1

86.0

844.1

86.4

844.1

86.5

844.1

86.5

844.2

86.5

840.2

86.0

0.00.0

529.4 54.2

531.9

54.5

531.9

54.5

529.4 54.2

644.5 75.7

297.2

37.5

291.7

36.8

789.7

99.6

926.0

116.7

849.8

99.9

721.5

91.0

868.6109.5

282.8 33.2

644.7 75.9

792.6

99.9

587.9

69.2

1393.2

82.0

688.3 56.8

1068.6 88.2

747.7 46.8

367.1 21.4367.1 21.4

620.4 73.0

615.9 72.5

496.9

58.5

54.8

5.6

54.8

5.6

527.3 47.5

527.3 47.5

365.4 21.3365.4 21.3

1258.1 42.5

1501.1 55.0

1531.7

56.1

957.3 34.0

981.9

34.9

1772.6 41.2

983.5 88.7

983.5 88.7

983.6 88.7

1490.3

78.1

593.8

31.4

592.5

31.3

588.8

32.0

223.2

26.3

210.7

24.8

223.2

26.3

210.7

24.8

1256.1 42.4

346.0 89.7173.0 89.7173.0 89.7

696.6

74.2

696.6

74.2

854.3107.7

196.6

10.5

192.1 10.2

196.6

10.5

192.1 10.2

292.4

9.9

245.6 8.3

711.3

73.0

711.1

72.9

Page 601: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 99- McCall-West Fresno & Cal Ave.-McCall 115kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:14 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.3

24156VINCENT

MIDWAY229.4

30057DIABLO

533.91.068

GATES538.9

GATES231.4

MORROBAY234.4

TEMPLETN

ARCO228.5

LOSBANOS535.8

30045MOSSLAND

530.81.062

GREGG231.5

HELMS PP234.3

HENRIETA230.1

PANOCHE234.0

HELM232.2

MCMULLN1

HERNDON231.1

LOSBANOS

237.2

COBURN235.5

TESLA534.8

TRACY541.2

METCALF533.4

METCALF234.5

BALCH3TP234.7

PINE FLT234.9

GATES231.4

KEARNEY230.0

30875MC CALL

233.91.017

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128234.3

Q239228.0

Q166228.0

Q194227.9

BORDEN230.7

STOREY 2229.8

STOREY 1229.9

WILSON225.7

WARNERVL224.4

DS AMIGO235.4

MELONES233.0

COTTLE A230.5

COTTLE B224.7

BELLOTA229.0

TESLA E231.4

SN LS PP

TESLA D232.7

TESLA C232.4

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254231.9

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0136.5

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

411.4

120.1

874.6

70.6

899.1

72.8

1111.2

51.0

408.9

143.6

409.9

25.2

323.3134.2

322.5

103.4

252.9 0.4

245.2

37.6

358.5 29.0

206.0

38.6

50.6

9.550.9

20.8

103.6

10.2

104.5

5.2

689.5

146.3

686.1

22.8

256.5

252.4

255.0

167.9

198.3 60.8

332.7

6.2

332.7

6.2

54.5

73.1

244.9 45.9

241.1

65.9

226.0 54.2

69.524.9

68.7 6.1

745.8 34.0

743.2 70.6

901.4

558.7

614.5115.8

588.9

56.1

588.9

56.1

342.9

60.8

342.1

103.4

1119.8

78.5

136.1

7.7

241.6 2.8

111.1 52.8

113.9 2.4

177.2 23.2

277.9 59.1

273.3 79.2

313.6 56.0

321.4 20.8

557.4

38.8

592.1

44.7

621.0

43.1

195.1

60.0

197.8 51.5

193.3

60.8

158.1 13.2

161.4

8.2

199.7 50.5

225.9 51.5

235.2 18.6

354.1

49.0

639.3

176.7

629.0

174.1

643.3

184.7

281.7 8.3281.7 8.3

325.5

76.5

332.7

27.8

332.7

27.8

332.7

27.8

332.7

27.8

325.6

76.5

0.00.0

214.0 24.6

210.4

8.2

210.4

8.2

214.0 24.6

245.0 69.0

118.5

25.0

116.1

25.6

317.1

15.2

372.2

2.6

340.6

3.2

288.9

4.9

341.8 18.5

97.754.1

261.4 4.1

293.6

101.4

233.2

23.6

574.0

50.7

636.5 51.2

992.1 93.2

685.1104.0

136.9 58.2136.9 58.2

247.4 52.7

243.6 67.2

191.6

70.5

22.5

1.4

22.5

1.4

494.7 5.6

494.7 5.6

136.6 58.4136.6 58.4

1163.6 12.9

1382.5 125.9

1407.3

175.2

844.6249.4

847.6

256.1

1653.4 134.9

398.2 26.8

398.2 27.2

398.2 27.2

596.3

37.2

237.5

23.0

236.0

29.9

244.1

66.3

83.2

37.1

82.428.4

83.2

37.1

82.4

28.4

1157.7 48.8

130.9 32.365.416.265.416.2

128.8

13.2

128.8

13.2

319.7 97.4

75.8

17.0

75.9 6.8

75.8

17.0

75.9 6.8

237.8

145.4

237.5 20.5

286.4

0.5

284.9

8.6

Page 602: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 100- McCall-West Fresno & Cal Ave.-McCall 115kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:16 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.3

24156VINCENT

MIDWAY229.4

30057DIABLO

533.91.068

GATES538.9

GATES231.4

MORROBAY234.4

TEMPLETN

ARCO228.5

LOSBANOS535.8

30045MOSSLAND

530.81.062

GREGG231.5

HELMS PP234.3

HENRIETA230.1

PANOCHE234.0

HELM232.2

MCMULLN1

HERNDON231.1

LOSBANOS

237.2

COBURN235.5

TESLA534.8

TRACY541.2

METCALF533.4

METCALF234.5

BALCH3TP234.7

PINE FLT234.9

GATES231.4

KEARNEY230.0

30875MC CALL

233.91.017

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128234.3

Q239228.0

Q166228.0

Q194227.9

BORDEN230.7

STOREY 2229.8

STOREY 1229.9

WILSON225.7

WARNERVL224.4

DS AMIGO235.4

MELONES233.0

COTTLE A230.5

COTTLE B224.7

BELLOTA229.0

TESLA E231.4

SN LS PP

TESLA D232.7

TESLA C232.4

Q235SWST232.2

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254231.9

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 84 1400 84 1400 84 1

0.0136.5

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

464.8

15.7

951.6

0.0

978.3

0.0

1206.4

0.0

470.0

15.9

440.0

14.8

378.5 12.8

362.8

12.2

623.0 63.9

619.0

63.5

886.1 51.7

522.9

53.6

129.4

13.7138.8

14.8

263.0

27.9

261.1

27.7

755.1

25.5

739.7

25.0

390.3

13.2

329.0

11.1

511.7 52.5

829.9

42.5

829.9

42.5

98.3

9.1

614.7 63.0

608.3

62.4

573.5 67.5

182.3 21.4

169.1 19.9

804.4 27.1

812.1 27.4

1131.3

38.2

680.2 22.9

1475.1

65.2

1475.1

65.2

373.0

8.6

385.0

8.9

1202.5

80.1

339.8

17.9

596.4 61.2

308.8 31.7

281.1 31.7

441.0 49.8

706.3 83.1

701.9 82.6

792.0 93.2

794.9 93.5

604.9

38.4

642.7

43.7

673.8

55.5

502.7

28.9

506.7 29.1

499.1

28.6

393.0 46.2

396.1

46.5

510.2 29.3

574.3 67.6

582.1 68.5

385.2

13.0

719.3

59.1

707.8

58.2

725.9

59.7

694.5 37.4694.5 37.4

841.4

86.2

845.4

86.6

845.4

86.6

845.4

86.6

845.4

86.6

841.5

86.2

0.00.0

530.6 54.3

533.1

54.6

533.1

54.6

530.6 54.3

644.6 75.7

302.0

38.1

296.4

37.4

794.2

100.1

931.4

117.4

855.2

100.5

726.1

91.5

875.6110.4

285.6 33.6

647.8 76.2

798.0

100.6

590.9

69.5

1402.6

82.5

689.3 56.9

1075.6 88.8

748.0 46.8

370.3 21.6370.3 21.6

624.2 73.4

619.7 72.9

500.7

58.9

54.8

5.6

54.8

5.6

527.7 47.5

527.7 47.5

368.6 21.5368.6 21.5

1256.2 42.4

1498.6 54.9

1528.9

56.0

950.7 33.8

975.3

34.6

1769.5 41.2

983.6 88.7

983.6 88.7

983.7 88.7

1490.5

78.1

594.8

31.4

593.5

31.4

630.9

34.3

227.3

26.7

215.0

25.3

227.3

26.7

215.0

25.3

1254.2 42.3

346.7 89.9173.4 89.9173.4 89.9

698.1

74.4

698.1

74.4

859.7108.4

194.5

10.4

189.8 10.1

194.5

10.4

189.8 10.1

300.4

10.1

254.2 8.6

715.4

73.4

715.3

73.4

Page 603: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 101- Gates-Gregg & Gates-McCall 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:18 2008 2013sprpk_q272_pre.sav

MIDWAY534.5

24156VINCENT

MIDWAY230.3

30057DIABLO

535.41.071

GATES542.2

GATES233.5

MORROBAY234.8

TEMPLETN

ARCO230.2

LOSBANOS539.3

30045MOSSLAND

534.01.068

GREGG233.3

HELMS PP235.3

HENRIETA225.2

PANOCHE235.3

HELM232.0

MCMULLN1

HERNDON233.0

LOSBANOS

238.9

COBURN236.8

TESLA537.6

TRACY543.9

METCALF536.4

METCALF235.7

BALCH3TP234.3

PINE FLT234.5

GATES233.5

KEARNEY231.8

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY231.9

Q128233.7

Q239229.0

Q166229.0

Q194229.0

BORDEN232.5

STOREY 2231.7

STOREY 1231.8

WILSON228.1

WARNERVL226.2

DS AMIGO237.1

MELONES235.1

COTTLE A232.1

COTTLE B226.4

BELLOTA230.0

TESLA E232.5

SN LS PP

TESLA D233.8

TESLA C233.2

Q235SWST233.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254233.4

STANDFRD107.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 71 1400 71 1

1

0.0135.8

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

409.0

127.1

869.7

59.0

894.2

60.9

1105.6

35.5

389.8

189.0

390.9

69.0

328.1153.3

327.3

123.3

269.1 6.2

260.5

50.6

373.4 23.7

221.1

51.3

24.1

1.524.1

11.4

76.9

20.1

77.4

12.7

521.7

145.5

519.8

3.6

159.7

265.5

158.7

175.3

156.3 46.6

251.9

28.3

251.9

28.3

44.2

69.6

221.5 49.5

218.4

63.6

204.1 56.6

58.024.3

57.4 3.4

658.8 34.3

656.8 86.6

808.5

569.0

530.6112.3

394.4

21.0

394.4

21.0

260.3

64.3

259.8

110.3

845.6

17.5

0.00.0

113.9 0.9

177.1 20.9

326.8 81.0

320.3112.2

373.6 80.9

384.8 25.8

536.6

37.3

570.0

43.0

597.8

41.5

178.2

55.4

180.1 50.5

176.4

56.1

147.3 9.1

150.1

7.7

182.0 49.5

203.7 41.3

211.1 19.5

207.5

38.8

609.8

179.1

600.0

176.5

613.6

186.9

281.7 13.3281.7 13.3

312.5

70.8

319.0

27.4

319.0

27.4

319.0

27.4

319.0

27.4

312.5

70.8

0.00.0

199.8 20.5

196.7

8.1

196.7

8.1

199.8 20.5

245.0 68.3

74.4

36.2

72.7

36.2

279.1

9.8

327.3

8.5

296.0

0.4

251.2

0.9

292.9 11.7

75.851.8

240.1 10.8

259.1

89.5

213.0

9.6

515.6

60.1

617.3 54.5

852.2 97.0

679.8107.0

109.6 55.4109.6 55.4

225.2 55.2

222.0 65.8

170.0

69.0

22.5

1.3

22.5

1.3

486.1 5.5

486.1 5.5

109.4 54.9109.4 54.9

1181.0 18.9

1392.1 138.1

1417.1

188.4

926.4267.4

930.0

261.7

1664.6 150.9

398.2 15.1

398.2 15.4

0.20.7

596.3

71.5

30.5

24.8

30.411.8

30.5

24.8

30.4

11.8

1175.0 56.1

124.9 33.362.516.662.516.6

123.0

16.1

123.0

16.1

285.1 86.2

91.3

12.2

91.6 2.6

91.3

12.2

91.6 2.6

116.2

133.7

116.1 1.1

229.5

6.9

228.6

2.3

Page 604: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 102- Gates-Gregg & Gates-McCall 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:19 2008 2013sprpk_q272_pre.sav

MIDWAY534.5

24156VINCENT

MIDWAY230.3

30057DIABLO

535.41.071

GATES542.2

GATES233.5

MORROBAY234.8

TEMPLETN

ARCO230.2

LOSBANOS539.3

30045MOSSLAND

534.01.068

GREGG233.3

HELMS PP235.3

HENRIETA225.2

PANOCHE235.3

HELM232.0

MCMULLN1

HERNDON233.0

LOSBANOS

238.9

COBURN236.8

TESLA537.6

TRACY543.9

METCALF536.4

METCALF235.7

BALCH3TP234.3

PINE FLT234.5

GATES233.5

KEARNEY231.8

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY231.9

Q128233.7

Q239229.0

Q166229.0

Q194229.0

BORDEN232.5

STOREY 2231.7

STOREY 1231.8

WILSON228.1

WARNERVL226.2

DS AMIGO237.1

MELONES235.1

COTTLE A232.1

COTTLE B226.4

BELLOTA230.0

TESLA E232.5

SN LS PP

TESLA D233.8

TESLA C233.2

Q235SWST233.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254233.4

STANDFRD107.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 71 1400 71 1

1

0.0135.8

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

462.6

15.6

941.5

0.0

968.0

0.0

1194.8

0.0

467.9

15.8

422.6

14.3

390.5 13.2

372.4

12.6

661.9 67.9

656.3

67.3

920.1 53.7

561.3

57.6

60.4

6.467.0

7.1

199.2

21.2

193.9

20.6

576.7

19.5

556.5

18.8

334.7

11.3

253.2

8.5

400.1 41.0

627.3

32.1

627.3

32.1

88.2

8.2

556.8 57.1

549.7

56.4

519.7 61.1

154.4 18.1

140.3 16.5

706.2 23.8

716.3 24.2

1049.5

35.4

586.4 19.8

977.5

43.2

977.5

43.2

285.5

6.6

302.2

7.0

900.5

60.3

0.00.0

281.8 31.8

441.5 49.8

837.8 98.6

832.7 98.0

951.4111.9

954.7112.3

578.9

37.0

615.2

42.0

644.9

53.4

457.2

26.2

461.3 26.5

453.3

26.0

363.8 42.8

366.4

43.1

465.0 26.7

512.6 60.3

520.1 61.2

226.0

7.6

686.4

56.6

675.5

55.7

692.7

57.2

696.6 37.5696.6 37.5

803.2

82.3

807.1

82.7

807.1

82.7

807.1

82.7

807.2

82.7

803.2

82.3

0.00.0

493.8 50.6

496.1

50.8

496.1

50.8

493.8 50.6

641.3 75.4

204.7

25.8

200.9

25.3

693.5

87.4

813.2

102.5

737.1

86.6

626.0

78.9

742.0 93.5

232.4 27.3

590.3 69.5

699.0

88.1

535.1

63.0

1254.4

73.8

665.4 55.2

921.0 76.4

739.0 46.5

304.2 17.7304.2 17.7

568.9 66.9

563.9 66.4

446.9

52.6

54.4

5.6

54.4

5.6

516.0 46.7

516.0 46.7

302.3 17.6302.3 17.6

1268.4 42.8

1502.3 55.0

1535.1

56.2

1035.4 36.8

1059.1

37.6

1774.2 41.3

977.9 88.6

978.0 88.6

1.90.2

1485.1

77.8

97.2

11.4

79.9 9.4

97.2

11.4

79.9

9.4

1266.0 42.7

329.9 86.2165.0 86.2165.0 86.2

664.4

70.8

664.4

70.8

760.3 95.8

229.4

12.2

227.0 12.1

229.4

12.2

227.0 12.1

189.6

6.4

123.2 4.2

569.1

58.4

569.3

58.4

Page 605: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 103- Gates-Gregg & Gates-McCall 230kV Lines MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:21 2008 2013sprpk_q272_pre.sav

MIDWAY534.5

24156VINCENT

MIDWAY230.3

30057DIABLO

535.41.071

GATES542.2

GATES233.5

MORROBAY234.8

TEMPLETN

ARCO230.2

LOSBANOS539.3

30045MOSSLAND

534.01.068

GREGG233.3

HELMS PP235.3

HENRIETA225.2

PANOCHE235.3

HELM232.0

MCMULLN1

HERNDON233.0

LOSBANOS

238.9

COBURN236.8

TESLA537.6

TRACY543.9

METCALF536.4

METCALF235.7

BALCH3TP234.3

PINE FLT234.5

GATES233.5

KEARNEY231.8

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY231.9

Q128233.7

Q239229.0

Q166229.0

Q194229.0

BORDEN232.5

STOREY 2231.7

STOREY 1231.8

WILSON228.1

WARNERVL226.2

DS AMIGO237.1

MELONES235.1

COTTLE A232.1

COTTLE B226.4

BELLOTA230.0

TESLA E232.5

SN LS PP

TESLA D233.8

TESLA C233.2

Q235SWST233.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254233.4

STANDFRD107.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 71 1400 71 1

1

0.0135.8

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

409.0

127.1

869.7

59.0

894.2

60.9

1105.6

35.5

389.8

189.0

390.9

69.0

328.1153.3

327.3

123.3

269.1 6.2

260.5

50.6

373.4 23.7

221.1

51.3

24.1

1.524.1

11.4

76.9

20.1

77.4

12.7

521.7

145.5

519.8

3.6

159.7

265.5

158.7

175.3

156.3 46.6

251.9

28.3

251.9

28.3

44.2

69.6

221.5 49.5

218.4

63.6

204.1 56.6

58.024.3

57.4 3.4

658.8 34.3

656.8 86.6

808.5

569.0

530.6112.3

394.4

21.0

394.4

21.0

260.3

64.3

259.8

110.3

845.6

17.5

0.00.0

113.9 0.9

177.1 20.9

326.8 81.0

320.3112.2

373.6 80.9

384.8 25.8

536.6

37.3

570.0

43.0

597.8

41.5

178.2

55.4

180.1 50.5

176.4

56.1

147.3 9.1

150.1

7.7

182.0 49.5

203.7 41.3

211.1 19.5

207.5

38.8

609.8

179.1

600.0

176.5

613.6

186.9

281.7 13.3281.7 13.3

312.5

70.8

319.0

27.4

319.0

27.4

319.0

27.4

319.0

27.4

312.5

70.8

0.00.0

199.8 20.5

196.7

8.1

196.7

8.1

199.8 20.5

245.0 68.3

74.4

36.2

72.7

36.2

279.1

9.8

327.3

8.5

296.0

0.4

251.2

0.9

292.9 11.7

75.851.8

240.1 10.8

259.1

89.5

213.0

9.6

515.6

60.1

617.3 54.5

852.2 97.0

679.8107.0

109.6 55.4109.6 55.4

225.2 55.2

222.0 65.8

170.0

69.0

22.5

1.3

22.5

1.3

486.1 5.5

486.1 5.5

109.4 54.9109.4 54.9

1181.0 18.9

1392.1 138.1

1417.1

188.4

926.4267.4

930.0

261.7

1664.6 150.9

398.2 15.1

398.2 15.4

0.20.7

596.3

71.5

30.5

24.8

30.411.8

30.5

24.8

30.4

11.8

1175.0 56.1

124.9 33.362.516.662.516.6

123.0

16.1

123.0

16.1

285.1 86.2

91.3

12.2

91.6 2.6

91.3

12.2

91.6 2.6

116.2

133.7

116.1 1.1

229.5

6.9

228.6

2.3

Page 606: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 104- Gates-Gregg & Gates-McCall 230kV Lines amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:22 2008 2013sprpk_q272_pst_v2.sav

MIDWAY534.5

24156VINCENT

MIDWAY230.3

30057DIABLO

535.41.071

GATES542.1

GATES233.4

MORROBAY234.8

TEMPLETN

ARCO230.2

LOSBANOS539.2

30045MOSSLAND

533.91.068

GREGG233.2

HELMS PP235.2

HENRIETA225.6

PANOCHE235.2

HELM231.7

MCMULLN1

HERNDON232.8

LOSBANOS

238.8

COBURN236.7

TESLA537.6

TRACY543.8

METCALF536.3

METCALF235.7

BALCH3TP234.3

PINE FLT234.5

GATES233.4

KEARNEY231.6

30875MC CALL

233.11.014

MOSSLND2

MOSSLND1

WESTLEY231.8

Q128233.6

Q239229.0

Q166229.0

Q194229.0

BORDEN232.3

STOREY 2231.5

STOREY 1231.7

WILSON227.9

WARNERVL226.1

DS AMIGO236.9

MELONES234.9

COTTLE A232.0

COTTLE B226.3

BELLOTA230.0

TESLA E232.5

SN LS PP

TESLA D233.8

TESLA C233.1

Q235SWST233.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254233.4

STANDFRD107.8

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 72 1400 72 1

1

0.0135.6

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

462.3

15.6

939.0

0.0

965.4

0.0

1191.5

0.0

464.0

15.7

418.7

14.1

390.9 13.2

372.9

12.6

661.7 67.9

656.0

67.3

919.8 53.6

561.1

57.6

60.8

6.567.6

7.2

199.6

21.2

194.3

20.6

581.9

19.6

562.1

19.0

336.7

11.4

256.2

8.6

410.3 42.1

620.9

31.8

620.9

31.8

92.1

8.6

563.3 57.8

556.2

57.0

525.7 61.9

156.9 18.4

142.8 16.8

709.8 23.9

719.8 24.3

1052.7

35.5

591.0 19.9

977.9

43.2

977.9

43.2

288.0

6.6

304.7

7.0

904.3

60.6

0.00.0

282.0 31.8

441.6 49.8

863.2101.6

858.0100.9

979.0115.2

982.2115.6

579.8

37.0

616.1

42.1

645.9

53.5

459.8

26.4

463.8 26.6

455.9

26.2

366.3 43.0

369.0

43.4

467.5 26.8

517.9 60.9

525.6 61.8

233.5

7.9

686.7

56.7

675.7

55.8

693.0

57.2

697.0 37.5697.0 37.5

803.5

82.3

807.5

82.7

807.5

82.7

807.5

82.7

807.5

82.7

803.6

82.3

0.00.0

494.1 50.6

496.5

50.8

496.5

50.8

494.1 50.6

641.3 75.4

211.0

26.6

207.1

26.1

701.1

88.4

822.0

103.6

746.0

87.7

633.5

79.9

753.7 95.0

237.1 27.9

595.3 70.0

707.6

89.2

539.9

63.5

1263.6

74.3

665.7 55.2

926.8 76.9

738.4 46.5

307.0 17.9307.0 17.9

575.0 67.7

570.1 67.1

453.0

53.3

54.4

5.6

54.4

5.6

515.8 46.7

515.8 46.7

305.0 17.8305.0 17.8

1266.6 42.7

1500.0 54.9

1532.6

56.1

1029.6 36.6

1053.3

37.4

1771.3 41.2

978.3 88.6

978.3 88.6

1.90.2

1485.2

77.9

92.3

10.9

75.0 8.8

92.3

10.9

75.0

8.8

1264.3 42.7

331.4 86.5165.7 86.5165.7 86.5

667.3

71.1

667.3

71.1

769.0 96.9

226.8

12.1

224.1 11.9

226.8

12.1

224.1 11.9

194.5

6.6

129.4 4.4

576.9

59.2

577.0

59.2

Page 607: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 105- Helm-McCall & Gates-McCall 230kV Lines MW/MVAR

Rating = 2

fres_so_115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:24 2008 2013sprpk_q272_pre.sav

MC CALL120.1

KINGSBRG118.5

KNGSCOGN

119.6

KINGSBUR9.292

34427GRDNGLS2

119.6

GRDN GLS119.2

CONTADNA117.0

HENRETTA113.9

CORCORAN116.3

CORCORAN73.12

QUEBEC112.4

ALPAUGH113.0

SMYRNA

114.1

HENRIETA228.5

MC CALL231.9

HENRITTA73.74

KNGLOBUS71.57

SUNMAID

SANGER117.9

WAHTOKE118.2

GERAWAN118.1

REEDLEY

117.2

RAINBW117.7

KNGSRVR1119.6

BALCH120.4

KINGSRIV13.80

BALCH 1

13.46

REEDLEY71.50

SANGER72.40

RAINBWTPPIEDRA 2

QUEBECTP34429

GWF_HEP 117.01.017

GWF_HEP113.66

GWF_HEP213.66

LEPRNOFD114.8

GAURD J2

KINGS J1

KCOGNJCT

GAURD J1

P0418120.1

P0418GT114.01

P0418GT214.01

P0418GT314.01

P0418GT414.01

to Air Products

to West Fresno

to McKibben

to 230 kV system

to Clovis #1 and #2to Malaga

to Las Palmas

to Barton

to Danish Cream

Fresno Southern 115-kV

0

48

1

34.015.5

1

48.0

4.0

1

27.5

2.8

1

50

16

1

50

16

1

0

7

1

79 18 1

79 18 2

79 18 3

79 18 4

7.1

5.3

1

3.31.1

1

10.4 7.3

1

4.0

0.8

1

13.0

2.7

3

14.3

2.9

4

3.2

3.1

1

24.4

5.0

2

13.0

2.6

1

27

5

1

26

5

3

15

9

1

51

2

17 3

3

3 2

ss

3 2

ss

3 2

ss

3 2

ss

19 4

4

24 5

5

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.0001.017

1.000

1.044

1.000

1.000 1.000

1.000

1.000

1.000

1.000

1.000

64.0

6.7

63.5 4.6

17.7

2.5

17.5

4.1

18.2

2.6

18.0

4.2

15.0 7.2

15.1

4.8

19.1 4.7

167.8 37.8

167.1

25.6

167.8 37.8

167.1

25.6

200.2 27.1

198.0

12.8

294.6 75.1

271.7 30.9

286.9 57.2

8.1

2.7

105.4 9.9

34.013.4

113.0 21.0

112.1 15.9

70.9 7.5

48.0

0.7

27.3

1.1

26.2

1.7

127.4

14.1

96.4

18.1

38.6

3.8

14.7

8.3

27.3

1.1

13.0

2.6

47.3 1.3

48.0 0.7

19.4

6.0

14.7

8.3

14.7 8.6

27.9 6.4

70.9 7.5

70.5

6.6

94.1

25.5

10.5 7.1

10.5

7.1

56.4 0.7

56.4 0.8

152.3 22.0

150.7 11.4

135.7

2.9

134.7 3.3

134.3 14.7

16.244.8

32.7

14.8

34.0

13.4

34.0

13.4

34.013.4

30.810.3

122.9 3.5

99.6

2.4118.8

1.1

118.0

4.5

129.6

4.8

128.8

1.5

3.31.0

3.31.1

129.6 4.8

3.2

3.0

49.5

11.7

49.5

11.7

74.719.3

184.6

4.5

184.3

0.5

62.117.4

2.1

12.4

2.3

26.7

14.3

22.6

303.2 17.3

75.8 4.3

75.8 4.3

75.8 4.3

75.8 4.3

Page 608: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 106- Helm-McCall & Gates-McCall 230kV Lines amps/rate

Rating = 2

fres_so_115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:25 2008 2013sprpk_q272_pre.sav

MC CALL120.1

KINGSBRG118.5

KNGSCOGN

119.6

KINGSBUR9.292

34427GRDNGLS2

119.6

GRDN GLS119.2

CONTADNA117.0

HENRETTA113.9

CORCORAN116.3

CORCORAN73.12

QUEBEC112.4

ALPAUGH113.0

SMYRNA

114.1

HENRIETA228.5

MC CALL231.9

HENRITTA73.74

KNGLOBUS71.57

SUNMAID

SANGER117.9

WAHTOKE118.2

GERAWAN118.1

REEDLEY

117.2

RAINBW117.7

KNGSRVR1119.6

BALCH120.4

KINGSRIV13.80

BALCH 1

13.46

REEDLEY71.50

SANGER72.40

RAINBWTPPIEDRA 2

QUEBECTP34429

GWF_HEP 117.01.017

GWF_HEP113.66

GWF_HEP213.66

LEPRNOFD114.8

GAURD J2

KINGS J1

KCOGNJCT

GAURD J1

P0418120.1

P0418GT114.01

P0418GT214.01

P0418GT314.01

P0418GT414.01

to Air Products

to West Fresno

to McKibben

to 230 kV system

to Clovis #1 and #2to Malaga

to Las Palmas

to Barton

to Danish Cream

Fresno Southern 115-kV

0

48

1

34.015.5

1

48.0

4.0

1

27.5

2.8

1

50

16

1

50

16

1

0

7

1

79 18 1

79 18 2

79 18 3

79 18 4

7.1

5.3

1

3.31.1

1

10.4 7.3

1

4.0

0.8

1

13.0

2.7

3

14.3

2.9

4

3.2

3.1

1

24.4

5.0

2

13.0

2.6

1

27

5

1

26

5

3

15

9

1

51

2

17 3

3

3 2

ss

3 2

ss

3 2

ss

3 2

ss

19 4

4

24 5

5

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.0001.017

1.000

1.044

1.000

1.000 1.000

1.000

1.000

1.000

1.000

1.000

313.5

32.4

314.1 32.4

87.2

21.9

89.1

22.3

89.8

22.5

91.7

23.0

85.010.7

80.1

10.0

99.112.4

827.0 73.5

827.7

73.6

827.0 73.5

827.7

73.6

971.3 99.7

971.7

99.8

1462.0 65.8

1314.8 58.8

1406.7 63.3

42.4

38.1

508.9 68.5

176.3 81.2

552.5 56.7

553.3 56.8

348.5 62.1

231.7

98.0

130.8

82.7

129.3

19.9

627.7

64.4

480.3

42.7

190.2

25.7

82.7

13.5

130.8

25.6

65.2

12.7

231.6 37.8

231.7 37.8

99.9

16.7

82.7

13.5

83.513.6

140.0 22.9

348.5 62.1

348.7

62.2

475.1

98.5

64.718.7

64.7

8.1

278.4 28.6

278.4 28.6

759.5102.2

760.0102.3

682.5

91.9

682.5 91.9

341.3 80.4

120.5 44.6

90.6

16.3

176.4

34.4

176.3

34.4

176.4 50.9

157.0 30.7

591.2 80.0

478.9

79.8575.4

77.9

575.4

77.9

627.5

84.9

627.6

84.9

16.5 4.8

16.6 4.8

627.5104.6

21.3

4.2

250.9

47.6

250.9

47.6

370.8 33.0

904.3

80.4

902.3

80.2

309.8 27.6

61.4

25.5

131.0

53.5

213.4

56.9

1459.6 73.1

364.9 75.9

364.9 75.9

364.9 75.9

364.9 75.9

Page 609: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 107- Helm-McCall & Gates-McCall 230kV Lines MW/MVAR

Rating = 2

fres_so_115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:27 2008 2013sprpk_q272_pst_v2.sav

MC CALL120.1

KINGSBRG118.5

KNGSCOGN

119.6

KINGSBUR9.292

34427GRDNGLS2

119.6

GRDN GLS119.2

CONTADNA117.0

HENRETTA114.0

CORCORAN116.3

CORCORAN73.12

QUEBEC112.4

ALPAUGH113.0

SMYRNA

114.1

HENRIETA228.5

MC CALL231.8

HENRITTA73.78

KNGLOBUS71.57

SUNMAID

SANGER117.9

WAHTOKE118.1

GERAWAN118.1

REEDLEY

117.2

RAINBW117.7

KNGSRVR1119.6

BALCH120.4

KINGSRIV13.80

BALCH 1

13.46

REEDLEY71.50

SANGER72.39

RAINBWTPPIEDRA 2

QUEBECTP34429

GWF_HEP 117.01.017

GWF_HEP113.66

GWF_HEP213.66

LEPRNOFD114.8

GAURD J2

KINGS J1

KCOGNJCT

GAURD J1

P0418120.1

P0418GT114.01

P0418GT214.01

P0418GT314.01

P0418GT414.01

to Air Products

to West Fresno

to McKibben

to 230 kV system

to Clovis #1 and #2to Malaga

to Las Palmas

to Barton

to Danish Cream

Fresno Southern 115-kV

0

48

1

34.015.5

1

48.0

4.0

1

27.5

2.8

1

50

16

1

50

16

1

0

7

1

79 18 1

79 18 2

79 18 3

79 18 4

7.1

5.3

1

3.31.1

1

10.4 7.3

1

4.0

0.8

1

13.0

2.7

3

14.3

2.9

4

3.2

3.1

1

24.4

5.0

2

13.0

2.6

1

27

5

1

26

5

3

15

9

1

51

2

17 3

3

3 2

ss

3 2

ss

3 2

ss

3 2

ss

19 4

4

24 5

5

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.0001.017

1.000

1.044

1.000

1.000 1.000

1.000

1.000

1.000

1.000

1.000

63.4

6.7

62.9 4.7

17.7

2.5

17.5

4.1

18.2

2.6

18.0

4.2

15.0 7.2

15.1

4.8

19.1 4.7

168.3 37.9

167.6

25.7

168.3 37.9

167.6

25.7

200.8 27.2

198.6

12.8

294.6 75.1

271.7 31.0

286.9 57.3

8.1

2.7

105.6 10.0

34.013.4

113.2 21.0

112.3 15.9

71.1 7.5

48.0

0.7

27.3

1.2

26.2

1.7

127.8

14.2

96.7

18.2

38.9

3.8

14.8

8.3

27.3

1.2

13.0

2.6

47.3 1.3

48.0 0.7

19.3

6.0

14.8

8.3

14.8 8.6

28.0 6.4

71.1 7.5

70.7

6.6

92.7

25.4

10.5 7.1

10.5

7.1

55.8 0.7

55.8 0.7

151.7 21.9

150.1 11.4

135.1

2.9

134.1 3.3

133.7 14.5

23.944.9

48.5

15.0

34.0

13.4

34.0

13.4

34.013.4

30.810.3

121.8 3.4

98.6

2.5117.8

1.1

117.0

4.4

128.6

4.8

127.8

1.6

3.31.0

3.31.1

128.6 4.8

3.2

3.1

49.5

11.7

49.5

11.7

74.719.3

185.2

4.6

184.8

0.5

62.117.4

2.2

12.4

2.3

26.6

14.3

22.6

303.2 17.4

75.8 4.4

75.8 4.4

75.8 4.4

75.8 4.4

Page 610: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 108- Helm-McCall & Gates-McCall 230kV Lines amps/rate

Rating = 2

fres_so_115.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:28 2008 2013sprpk_q272_pst_v2.sav

MC CALL120.1

KINGSBRG118.5

KNGSCOGN

119.6

KINGSBUR9.292

34427GRDNGLS2

119.6

GRDN GLS119.2

CONTADNA117.0

HENRETTA114.0

CORCORAN116.3

CORCORAN73.12

QUEBEC112.4

ALPAUGH113.0

SMYRNA

114.1

HENRIETA228.5

MC CALL231.8

HENRITTA73.78

KNGLOBUS71.57

SUNMAID

SANGER117.9

WAHTOKE118.1

GERAWAN118.1

REEDLEY

117.2

RAINBW117.7

KNGSRVR1119.6

BALCH120.4

KINGSRIV13.80

BALCH 1

13.46

REEDLEY71.50

SANGER72.39

RAINBWTPPIEDRA 2

QUEBECTP34429

GWF_HEP 117.01.017

GWF_HEP113.66

GWF_HEP213.66

LEPRNOFD114.8

GAURD J2

KINGS J1

KCOGNJCT

GAURD J1

P0418120.1

P0418GT114.01

P0418GT214.01

P0418GT314.01

P0418GT414.01

to Air Products

to West Fresno

to McKibben

to 230 kV system

to Clovis #1 and #2to Malaga

to Las Palmas

to Barton

to Danish Cream

Fresno Southern 115-kV

0

48

1

34.015.5

1

48.0

4.0

1

27.5

2.8

1

50

16

1

50

16

1

0

7

1

79 18 1

79 18 2

79 18 3

79 18 4

7.1

5.3

1

3.31.1

1

10.4 7.3

1

4.0

0.8

1

13.0

2.7

3

14.3

2.9

4

3.2

3.1

1

24.4

5.0

2

13.0

2.6

1

27

5

1

26

5

3

15

9

1

51

2

17 3

3

3 2

ss

3 2

ss

3 2

ss

3 2

ss

19 4

4

24 5

5

1.000

1.000

1.000

1.000

1.000

1.0001.000

1.0001.017

1.000

1.044

1.000

1.000 1.000

1.000

1.000

1.000

1.000

1.000

310.6

32.1

311.2 32.1

87.2

21.9

89.1

22.3

89.8

22.5

91.7

23.0

85.110.7

80.1

10.0

99.112.4

829.6 73.8

830.3

73.8

829.6 73.8

830.3

73.8

974.4100.0

974.8

100.1

1462.2 65.8

1314.9 58.8

1406.9 63.3

42.4

38.1

510.0 68.6

176.3 81.2

553.5 56.8

554.2 56.9

349.5 62.3

231.7

98.0

130.9

82.7

129.5

19.9

630.0

64.7

482.0

42.9

191.3

25.9

83.0

13.5

130.9

25.6

65.2

12.7

231.6 37.8

231.7 37.8

99.5

16.7

83.0

13.5

83.713.7

140.3 22.9

349.4 62.3

349.6

62.3

468.3

97.1

64.718.7

64.7

8.1

275.4 28.3

275.4 28.3

756.5101.8

757.0101.9

679.5

91.5

679.5 91.4

339.8 80.0

128.6 47.6

128.1

23.1

176.3

34.4

176.3

34.4

176.3 50.9

157.0 30.7

586.0 79.3

474.1

79.0570.3

77.2

570.2

77.2

622.8

84.3

622.8

84.3

16.6 4.8

16.6 4.8

622.8103.8

21.3

4.2

250.8

47.6

250.8

47.6

370.9 33.0

907.2

80.7

905.3

80.5

309.9 27.6

61.5

25.5

130.9

53.5

213.4

56.9

1459.7 73.1

364.9 75.9

364.9 75.9

364.9 75.9

364.9 75.9

Page 611: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 109- Henrietta 230kV Bus MW/MVAR

Rating = 2

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:29 2008 2013sprpk_q272_pre.sav

HENRITTA73.05

LEMOORE71.19

MUSLSLGH72.79

CAMDEN70.95

KNGLOBUS

71.50

KINGSBRG119.6

HENRIETA234.6

34542JCBSCRNR

GUERNSEY73.78

34554

AMSTG SW

ARMSTRNG74.39

GWF-PWR.14.08RESERVE

74.38

34528

CORCORAN

34420

CORCORAN

HNFRD SW

70.82

HARDWICK

70.64

ANGIOLA

73.30

BOSWELL73.57

LEPRINO71.10

CANDLEWK71.22

CMDN JCT

BSWLL TP

JGBSWLL

73.57

GUR3TPT

GWF_HENR73.16

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

7.0

1

49

16

1

49

16

1 1

15.2

3.1

1

26.4

5.4

2

9.7

2.0

1

7.7

1.6

26.6

1.3

1

5.5

1.1

1

8.8

1.8

2

20.5 12.7

1

5.8

1.2

1

10.3 2.1

1

8.5 1.7

1

2.21.4

1

0.0

0.0

1

1.6 0.3

1

0.00.0

1

1

1

0

ss

1

0

ss ss

6

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

9.412.4

23.7 9.5

24.5 8.5

1.6

0.3

23.0

7.0

0.0

0.0

21.4

6.7

21.2

6.6

12.8

4.9

12.7 4.9

4.7

1.4

4.7

1.6

56.6

0.9

8.41.7

2.21.4

63.9

9.6

0.00.0

14.8

7.7

4.2

9.8

10.3 2.1

20.9

1.4

8.12.7

8.12.4

5.8

1.2

5.81.1

47.9

11.3

47.9

11.3

95.8

22.5

20.5

12.7

20.512.7

6.24.0

9.3

12.5

15.1 7.6

14.8 7.7

Page 612: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 110- Henrietta 230kV Bus amps/rate

Rating = 2

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:31 2008 2013sprpk_q272_pre.sav

HENRITTA73.05

LEMOORE71.19

MUSLSLGH72.79

CAMDEN70.95

KNGLOBUS

71.50

KINGSBRG119.6

HENRIETA234.6

34542JCBSCRNR

GUERNSEY73.78

34554

AMSTG SW

ARMSTRNG74.39

GWF-PWR.14.08RESERVE

74.38

34528

CORCORAN

34420

CORCORAN

HNFRD SW

70.82

HARDWICK

70.64

ANGIOLA

73.30

BOSWELL73.57

LEPRINO71.10

CANDLEWK71.22

CMDN JCT

BSWLL TP

JGBSWLL

73.57

GUR3TPT

GWF_HENR73.16

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

7.0

1

49

16

1

49

16

1 1

15.2

3.1

1

26.4

5.4

2

9.7

2.0

1

7.7

1.6

26.6

1.3

1

5.5

1.1

1

8.8

1.8

2

20.5 12.7

1

5.8

1.2

1

10.3 2.1

1

8.5 1.7

1

2.21.4

1

0.0

0.0

1

1.6 0.3

1

0.00.0

1

1

1

0

ss

1

0

ss ss

6

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

127.0 42.8

207.9 52.2

209.2 52.5

12.9

5.6

186.5

89.3

0.1

0.0

173.7

45.8

173.9

45.8

107.0

22.8

107.6 22.9

38.6 8.2

39.2

8.3

459.3

61.9

67.4

14.3

20.6 4.0

510.9

68.8

0.00.0

135.9

35.8

85.8

22.7

86.321.8

101.0

21.1

42.038.1

65.7

19.0

46.8

13.5

46.613.4

388.3

85.4

388.3

85.4

776.6

68.7

191.0 25.7

191.2 25.8

59.917.3

126.0

42.4

136.8 48.8

135.9 48.5

Page 613: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 111- Henrietta 230kV Bus MW/MVAR

Rating = 2

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:32 2008 2013sprpk_q272_pst_v2.sav

HENRITTA73.32

LEMOORE71.50

MUSLSLGH73.07

CAMDEN70.60

KNGLOBUS

71.05

KINGSBRG119.3

HENRIETA234.6

34542JCBSCRNR

GUERNSEY73.83

34554

AMSTG SW

ARMSTRNG74.40

GWF-PWR.14.08RESERVE

74.39

34528

CORCORAN

34420

CORCORAN

HNFRD SW

70.27

HARDWICK

70.05

ANGIOLA

73.12

BOSWELL73.40

LEPRINO71.41

CANDLEWK71.53

CMDN JCT

BSWLL TP

JGBSWLL

73.39

GUR3TPT

GWF_HENR73.43

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

5.6

1

49

13

1

49

13

1

27

6

1

15.2

3.1

1

26.4

5.4

2

9.7

2.0

1

7.7

1.6

26.6

1.3

1

5.5

1.1

1

8.8

1.8

2

20.5 12.7

1

5.8

1.2

1

10.3 2.1

1

8.5 1.7

1

2.21.4

1

0.0

0.0

1

1.6 0.3

1

0.00.0

1

1

1

0

ss

1

0

ss

2

1

ss

6

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

10.814.0

25.111.1

26.0 9.9

1.6

0.3

23.0

5.5

0.0

0.0

21.4

5.2

21.2

5.1

12.8

3.4

12.7 3.5

4.7

0.1

4.7

0.2

80.7

7.0

8.41.7

2.21.4

88.9

6.1

0.00.0

37.3

17.5

25.2

22.6

10.3 2.1

1.3

12.8

8.12.7

8.12.4

5.8

1.2

5.81.1

25.0

3.7

47.9

8.6

47.9

8.6

120.8

20.8

20.5

12.7

20.512.7

6.24.0

10.6

14.1

39.115.5

37.317.5

Page 614: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 112- Henrietta 230kV Bus amps/rate

Rating = 2

hen_70.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:33 2008 2013sprpk_q272_pst_v2.sav

HENRITTA73.32

LEMOORE71.50

MUSLSLGH73.07

CAMDEN70.60

KNGLOBUS

71.05

KINGSBRG119.3

HENRIETA234.6

34542JCBSCRNR

GUERNSEY73.83

34554

AMSTG SW

ARMSTRNG74.40

GWF-PWR.14.08RESERVE

74.39

34528

CORCORAN

34420

CORCORAN

HNFRD SW

70.27

HARDWICK

70.05

ANGIOLA

73.12

BOSWELL73.40

LEPRINO71.41

CANDLEWK71.53

CMDN JCT

BSWLL TP

JGBSWLL

73.39

GUR3TPT

GWF_HENR73.43

GWF_GT114.08

GWF_GT214.08

Q272_ST113.94

Henrietta 70 kV system

Project Q272

to Caruthers

23.0

5.6

1

49

13

1

49

13

1

27

6

1

15.2

3.1

1

26.4

5.4

2

9.7

2.0

1

7.7

1.6

26.6

1.3

1

5.5

1.1

1

8.8

1.8

2

20.5 12.7

1

5.8

1.2

1

10.3 2.1

1

8.5 1.7

1

2.21.4

1

0.0

0.0

1

1.6 0.3

1

0.00.0

1

1

1

0

ss

1

0

ss

2

1

ss

6

4

1

1.044 1.000

1.017

1.000

1.0001.0001.000

144.7 48.7

224.3 56.3

225.7 56.7

12.9

5.6

183.5

87.9

0.1

0.0

170.7

45.0

170.8

45.0

103.5

22.0

103.9 22.1

36.9 7.8

36.9

7.8

653.7

88.1

67.4

14.3

20.7 4.0

701.9

94.6

0.00.0

338.7

89.3

275.0

72.8

87.022.0

62.1

13.0

42.138.1

65.9

19.0

46.9

13.5

46.713.5

198.7

72.2

382.6

84.5

382.6

84.5

963.7

85.3

190.3 25.6

190.5 25.7

59.717.2

143.7

48.4

339.5121.1

338.7120.8

Page 615: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 113- Gates 230kV Bus 1E MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:35 2008 2013sprpk_q272_pre.sav

MIDWAY533.1

24156VINCENT

MIDWAY229.7

30057DIABLO

534.41.069

GATES540.2

GATES232.5

MORROBAY234.6

TEMPLETN

ARCO224.8

LOSBANOS537.0

30045MOSSLAND

531.81.064

GREGG230.9

HELMS PP234.0

HENRIETA228.4

PANOCHE234.2

HELM232.2

MCMULLN1

HERNDON230.5

LOSBANOS

237.6

COBURN235.8

TESLA535.7

TRACY542.0

METCALF534.3

METCALF234.8

BALCH3TP234.4

PINE FLT234.6

GATES232.5

KEARNEY229.3

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY230.9

Q128233.8

Q239228.2

Q166228.2

Q194228.2

BORDEN230.2

STOREY 2229.1

STOREY 1229.3

WILSON224.9

WARNERVL224.0

DS AMIGO235.8

MELONES232.4

COTTLE A230.1

COTTLE B224.3

BELLOTA228.9

TESLA E231.6

SN LS PP

TESLA D233.0

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.7

STANDFRD107.0

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 87 1400 87 1400 87 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

414.6

122.4

873.8

66.8

898.3

68.9

1110.4

46.0

447.3

159.8

448.6

42.6

316.8142.3

316.1

110.9

254.7 4.2

246.9

42.0

359.8 25.3

207.7

43.1

53.1

18.752.7

29.5

614.9

142.7

612.3

10.7

195.4

255.8

194.2

167.5

238.5 79.1

388.8

1.8

388.8

1.8

71.5

78.0

243.2 47.1

239.4

66.7

224.4 55.3

67.925.0

67.1 5.8

707.2 35.1

704.9 78.7

870.2

562.8

582.4113.5

588.8

51.8

588.8

51.8

306.1

60.8

305.4

108.1

1053.5

50.0

20.6

13.9

254.9 10.6

20.727.0

113.9 0.3

177.1 21.3

271.5 61.7

267.1 80.7

303.9 58.2

311.2 25.5

550.2

38.0

584.4

43.8

612.9

42.2

189.9

58.7

192.4 51.4

188.1

59.5

156.5 12.9

159.7

8.4

194.2 50.3

222.7 50.4

231.7 19.3

291.4

43.5

603.1

177.7

593.4

175.1

606.8

185.5

281.7 12.4281.7 12.4

324.3

75.7

331.4

27.7

331.4

27.7

331.4

27.7

331.4

27.7

324.4

75.7

0.00.0

212.6 24.2

209.1

8.2

209.1

8.2

212.6 24.2

245.0 68.8

139.7

21.8

137.0

22.6

334.9

17.7

393.3

0.1

361.5

4.7

306.6

6.5

358.9 22.0

105.0 55.4

268.4 1.0

303.8

106.7

239.8

29.2

553.6

52.9

624.8 53.3

947.9 93.9

673.1107.5

128.6 57.1128.6 57.1

245.8 53.8

242.0 68.0

190.0

71.3

22.5

1.4

22.5

1.4

487.1 4.8

487.1 4.8

128.3 57.1128.3 57.1

1172.7 15.0

1388.3 130.8

1413.3

179.4

873.6256.1

876.8

258.4

1659.9 141.0

398.2 29.9

398.2 30.3

398.2 30.3

596.3

54.6

250.3

34.8

248.6

42.9

57.7

28.3

57.317.0

57.7

28.3

57.3

17.0

1166.7 52.0

133.8 31.366.915.766.915.7

131.7

11.3

131.7

11.3

329.9102.5

78.0

16.7

78.2 6.5

78.0

16.7

78.2 6.5

184.8

139.6

184.6 11.0

334.7

1.3

332.5

15.1

Page 616: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 114- Gates 230kV Bus 1E amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:36 2008 2013sprpk_q272_pre.sav

MIDWAY533.1

24156VINCENT

MIDWAY229.7

30057DIABLO

534.41.069

GATES540.2

GATES232.5

MORROBAY234.6

TEMPLETN

ARCO224.8

LOSBANOS537.0

30045MOSSLAND

531.81.064

GREGG230.9

HELMS PP234.0

HENRIETA228.4

PANOCHE234.2

HELM232.2

MCMULLN1

HERNDON230.5

LOSBANOS

237.6

COBURN235.8

TESLA535.7

TRACY542.0

METCALF534.3

METCALF234.8

BALCH3TP234.4

PINE FLT234.6

GATES232.5

KEARNEY229.3

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY230.9

Q128233.8

Q239228.2

Q166228.2

Q194228.2

BORDEN230.2

STOREY 2229.1

STOREY 1229.3

WILSON224.9

WARNERVL224.0

DS AMIGO235.8

MELONES232.4

COTTLE A230.1

COTTLE B224.3

BELLOTA228.9

TESLA E231.6

SN LS PP

TESLA D233.0

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.7

STANDFRD107.0

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 87 1400 87 1400 87 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

468.2

15.8

949.2

0.0

975.8

0.0

1203.7

0.0

514.4

17.4

481.6

16.2

375.2 12.7

358.0

12.1

626.9 64.3

622.0

63.8

887.9 51.8

526.7

54.0

141.5

15.0155.1

16.5

674.7

22.8

658.3

22.2

348.6

11.8

275.7

9.3

619.3 63.5

972.0

49.8

972.0

49.8

113.7

10.5

610.6 62.6

604.0

62.0

569.7 67.0

178.3 21.0

164.8 19.4

761.2 25.7

770.0 26.0

1103.9

37.2

644.2 21.7

1477.7

65.3

1477.7

65.3

333.5

7.7

348.3

8.0

1127.2

75.2

62.1

3.3

631.1 64.7

85.9 8.8

281.7 31.8

441.4 49.8

692.3 81.4

687.6 80.9

769.3 90.5

772.5 90.9

596.0

37.9

633.2

43.1

663.9

54.8

488.7

28.1

492.8 28.3

485.0

27.8

388.5 45.7

391.6

46.0

496.3 28.5

565.1 66.5

573.0 67.4

316.7

10.7

681.0

56.0

670.1

55.1

687.3

56.6

696.2 37.5696.2 37.5

837.2

85.7

841.2

86.2

841.2

86.2

841.2

86.2

841.3

86.2

837.3

85.8

0.00.0

526.8 53.9

529.3

54.2

529.3

54.2

526.8 53.9

643.7 75.6

353.6

44.6

347.0

43.7

841.2

106.1

986.6

124.4

910.3

107.0

772.8

97.4

923.2116.4

304.8 35.8

666.8 78.5

828.8

104.5

609.4

71.7

1351.3

79.5

675.9 55.9

1026.7 84.9

734.7 46.1

349.7 20.4349.7 20.4

620.2 73.0

615.6 72.4

497.0

58.5

54.7

5.6

54.7

5.6

518.9 46.8

518.9 46.8

348.0 20.3348.0 20.3

1264.0 42.6

1503.0 55.1

1534.1

56.2

981.2 34.8

1005.5

35.7

1774.4 41.3

985.2 88.7

985.3 88.7

985.3 88.8

1487.1

78.0

628.3

33.2

626.6

33.1

159.5

18.8

147.2

17.3

159.5

18.8

147.2

17.3

1261.9 42.6

354.2 91.6177.1 91.6177.1 91.6

713.1

76.0

713.1

76.0

890.5112.3

199.4

10.6

195.0 10.4

199.4

10.6

195.0 10.4

249.0

8.4

197.0 6.6

838.3

86.0

838.1

86.0

Page 617: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 115- Gates 230kV Bus 1E MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:38 2008 2013sprpk_q272_pst_v2.sav

MIDWAY533.0

24156VINCENT

MIDWAY229.6

30057DIABLO

534.41.069

GATES540.1

GATES232.4

MORROBAY234.5

TEMPLETN

ARCO224.8

LOSBANOS536.9

30045MOSSLAND

531.71.063

GREGG230.8

HELMS PP234.0

HENRIETA228.5

PANOCHE234.1

HELM232.1

MCMULLN1

HERNDON230.4

LOSBANOS

237.5

COBURN235.7

TESLA535.6

TRACY542.0

METCALF534.2

METCALF234.8

BALCH3TP234.4

PINE FLT234.6

GATES232.4

KEARNEY229.2

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128233.8

Q239228.2

Q166228.2

Q194228.2

BORDEN230.0

STOREY 2229.0

STOREY 1229.1

WILSON224.6

WARNERVL223.8

DS AMIGO235.6

MELONES232.2

COTTLE A229.9

COTTLE B224.1

BELLOTA228.8

TESLA E231.6

SN LS PP

TESLA D233.0

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.6

STANDFRD106.9

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 88 1400 88 1400 88 1

0.0135.8

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

414.3

122.3

871.1

67.3

895.5

69.4

1106.9

46.5

443.4

158.3

444.7

41.0

317.5141.6

316.7

110.3

254.4 4.0

246.7

41.7

359.6 25.5

207.5

42.7

53.1

18.752.7

29.4

621.4

142.4

618.7

11.1

200.9

255.1

199.7

167.1

244.2 81.2

393.1

1.7

393.1

1.7

74.3

79.4

245.3 47.2

241.5

67.3

226.4 55.4

68.825.1

68.0 6.2

711.1 35.3

708.7 78.2

874.3

562.8

586.8114.0

588.8

51.1

588.8

51.1

309.3

60.5

308.6

108.0

1058.7

51.7

38.2

15.2

259.6 10.2

38.327.6

113.9 0.5

177.1 21.2

275.3 62.1

270.7 81.9

307.7 58.7

315.2 24.9

551.1

38.0

585.3

43.8

613.9

42.2

190.9

59.1

193.4 51.5

189.1

59.9

157.4 13.3

160.6

8.6

195.2 50.5

224.4 51.5

233.6 19.4

299.0

44.4

603.4

177.5

593.7

175.0

607.1

185.3

281.7 12.7281.7 12.7

324.5

75.8

331.6

27.7

331.6

27.7

331.6

27.7

331.6

27.7

324.6

75.8

0.00.0

212.9 24.2

209.3

8.2

209.3

8.2

212.9 24.2

245.0 68.9

144.2

21.9

141.3

22.7

338.9

18.7

398.0

1.2

366.2

5.6

310.6

7.4

364.1 22.6

107.3 55.7

270.6 0.2

307.3

108.1

241.9

30.8

557.1

51.9

625.1 53.5

954.0 94.2

672.4108.0

129.9 57.2129.9 57.2

247.8 53.9

244.0 68.5

192.0

71.8

22.5

1.4

22.5

1.4

487.0 4.5

487.0 4.5

129.6 57.2129.6 57.2

1171.0 14.2

1386.2 129.2

1411.1

178.4

868.1254.3

871.3

257.5

1657.2 138.9

398.2 30.5

398.2 30.9

398.2 30.9

596.3

53.5

254.7

35.7

253.0

44.4

56.9

27.8

56.516.5

56.9

27.8

56.5

16.5

1165.1 51.0

134.5 31.267.215.667.215.6

132.3

11.0

132.3

11.0

333.5103.8

76.8

17.2

77.0 7.0

76.8

17.2

77.0 7.0

191.2

140.5

191.0 12.3

341.1

0.6

338.9

15.1

Page 618: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 116- Gates 230kV Bus 1E amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:39 2008 2013sprpk_q272_pst_v2.sav

MIDWAY533.0

24156VINCENT

MIDWAY229.6

30057DIABLO

534.41.069

GATES540.1

GATES232.4

MORROBAY234.5

TEMPLETN

ARCO224.8

LOSBANOS536.9

30045MOSSLAND

531.71.063

GREGG230.8

HELMS PP234.0

HENRIETA228.5

PANOCHE234.1

HELM232.1

MCMULLN1

HERNDON230.4

LOSBANOS

237.5

COBURN235.7

TESLA535.6

TRACY542.0

METCALF534.2

METCALF234.8

BALCH3TP234.4

PINE FLT234.6

GATES232.4

KEARNEY229.2

30875MC CALL

233.31.014

MOSSLND2

MOSSLND1

WESTLEY230.8

Q128233.8

Q239228.2

Q166228.2

Q194228.2

BORDEN230.0

STOREY 2229.0

STOREY 1229.1

WILSON224.6

WARNERVL223.8

DS AMIGO235.6

MELONES232.2

COTTLE A229.9

COTTLE B224.1

BELLOTA228.8

TESLA E231.6

SN LS PP

TESLA D233.0

TESLA C232.6

Q235SWST232.5

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.6

STANDFRD106.9

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 88 1400 88 1400 88 1

0.0135.8

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

467.9

15.8

946.3

0.0

972.9

0.0

1200.0

0.0

510.0

17.2

477.4

16.1

375.6 12.7

358.5

12.1

626.3 64.2

621.5

63.8

887.4 51.8

526.2

54.0

141.5

15.0155.1

16.5

681.5

23.0

665.4

22.5

351.7

11.9

280.0

9.4

634.7 65.1

983.1

50.3

983.1

50.3

116.9

10.8

616.1 63.2

609.6

62.5

574.8 67.6

180.6 21.2

167.1 19.6

765.6 25.8

774.3 26.1

1107.6

37.4

649.1 21.9

1478.2

65.3

1478.2

65.3

336.9

7.8

351.6

8.1

1133.0

75.6

102.7

5.4

642.7 65.9

119.4 12.2

281.7 31.8

441.4 49.8

702.1 82.6

697.5 82.1

779.2 91.7

782.4 92.1

597.0

38.0

634.4

43.2

665.0

54.8

491.3

28.2

495.4 28.4

487.7

28.0

390.8 45.9

394.0

46.3

498.9 28.6

570.0 67.1

578.0 68.0

325.0

11.0

681.3

56.1

670.4

55.2

687.6

56.6

696.4 37.5696.4 37.5

837.9

85.8

841.8

86.2

841.9

86.2

841.9

86.2

841.9

86.2

837.9

85.8

0.00.0

527.4 54.0

529.8

54.3

529.8

54.3

527.4 54.0

643.8 75.7

364.8

46.0

358.0

45.1

851.8

107.4

998.9

125.9

922.7

108.4

783.3

98.8

937.5118.2

310.6 36.5

672.9 79.2

839.2

105.8

615.4

72.4

1360.3

80.0

676.3 55.9

1033.3 85.4

734.1 46.0

352.8 20.6352.8 20.6

625.4 73.6

620.9 73.1

502.1

59.1

54.7

5.6

54.7

5.6

518.8 46.8

518.8 46.8

351.1 20.5351.1 20.5

1262.4 42.6

1500.8 55.0

1531.7

56.1

975.1 34.6

999.4

35.5

1771.6 41.2

985.5 88.8

985.6 88.8

985.6 88.8

1487.3

78.0

639.9

33.8

638.2

33.7

157.4

18.5

145.2

17.1

157.4

18.5

145.2

17.1

1260.3 42.5

356.1 92.0178.1 92.0178.1 92.0

716.8

76.4

716.8

76.4

901.0113.6

196.9

10.5

192.2 10.2

196.9

10.5

192.2 10.2

255.2

8.6

203.9 6.9

854.7

87.7

854.5

87.7

Page 619: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 117- Woodward 115kV Bus MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:41 2008 2013sprpk_q272_pre.sav

MIDWAY532.5

24156VINCENT

MIDWAY229.5

30057DIABLO

534.01.068

GATES539.2

GATES231.6

MORROBAY234.4

TEMPLETN

ARCO228.7

LOSBANOS536.2

30045MOSSLAND

531.11.062

GREGG231.9

HELMS PP234.4

HENRIETA230.2

PANOCHE234.2

HELM232.4

MCMULLN1

HERNDON231.5

LOSBANOS

237.4

COBURN235.7

TESLA535.0

TRACY541.4

METCALF533.6

METCALF234.6

BALCH3TP234.6

PINE FLT234.8

GATES231.6

KEARNEY230.4

30875MC CALL

233.71.016

MOSSLND2

MOSSLND1

WESTLEY230.7

Q128234.1

Q239228.1

Q166228.1

Q194228.0

BORDEN231.1

STOREY 2230.1

STOREY 1230.3

WILSON226.0

WARNERVL224.6

DS AMIGO235.7

MELONES233.2

COTTLE A230.6

COTTLE B224.8

BELLOTA229.1

TESLA E231.4

SN LS PP

TESLA D232.8

TESLA C232.5

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.0

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 82 1400 82 1400 82 1

0.0136.3

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

411.6

120.7

876.7

69.4

901.3

71.6

1113.9

49.6

411.2

147.8

412.3

29.4

323.0136.0

322.2

105.2

254.1 0.9

246.4

38.7

359.7 28.5

207.1

39.7

48.6

8.648.9

20.1

101.6

11.0

102.5

5.8

673.0

146.6

669.8

21.1

245.3

253.9

243.9

168.6

202.7 61.3

325.0

0.5

325.0

0.5

51.5

71.1

241.0 46.0

237.3

64.9

222.4 54.1

67.924.7

67.1 5.6

737.2 34.0

734.7 72.2

893.3

559.6

605.4114.9

588.9

58.8

588.9

58.8

334.7

61.4

334.0

103.9

1097.8

73.3

150.6

6.7

223.0 5.9

80.851.1

113.9 1.3

177.2 22.4

259.8 57.6

255.8 74.3

292.9 54.0

299.8 24.5

555.7

38.7

590.2

44.6

619.0

43.0

193.3

59.3

195.9 51.2

191.5

60.1

156.6 12.5

159.8

8.0

197.7 50.2

222.8 49.7

231.9 18.5

337.9

47.3

637.1

177.0

626.8

174.4

641.1

185.0

281.7 10.0281.7 10.0

324.5

76.0

331.6

27.8

331.6

27.8

331.6

27.8

331.6

27.8

324.6

76.0

0.00.0

212.9 24.3

209.3

8.2

209.3

8.2

212.9 24.3

245.0 69.0

119.2

28.1

116.7

28.6

316.9

15.5

372.1

2.3

340.4

3.6

288.8

5.2

341.7 17.1

97.553.7

261.2 4.7

293.1

100.6

233.0

22.9

566.3

52.6

634.4 51.2

980.2 93.2

683.6104.0

134.4 57.8134.4 57.8

243.8 52.6

240.1 66.4

188.1

69.7

22.5

1.4

22.5

1.4

493.7 5.9

493.7 5.9

134.2 57.9134.2 57.9

1167.1 14.0

1385.4 128.4

1410.4

176.9

854.0252.4

857.1

257.6

1656.9 138.0

398.2 24.9

398.2 25.2

398.2 25.2

596.3

40.2

219.5

21.4

218.2

26.6

228.2

64.3

80.9

37.2

80.128.2

80.9

37.2

80.1

28.2

1161.1 50.5

131.0 32.465.516.265.516.2

129.0

13.3

129.0

13.3

319.3 96.7

77.4

16.2

77.5 6.0

77.4

16.2

77.5 6.0

224.1

143.6

223.8 17.7

294.1

1.4

292.4

8.4

Page 620: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 118- Woodward 115kV Bus amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:42 2008 2013sprpk_q272_pre.sav

MIDWAY532.5

24156VINCENT

MIDWAY229.5

30057DIABLO

534.01.068

GATES539.2

GATES231.6

MORROBAY234.4

TEMPLETN

ARCO228.7

LOSBANOS536.2

30045MOSSLAND

531.11.062

GREGG231.9

HELMS PP234.4

HENRIETA230.2

PANOCHE234.2

HELM232.4

MCMULLN1

HERNDON231.5

LOSBANOS

237.4

COBURN235.7

TESLA535.0

TRACY541.4

METCALF533.6

METCALF234.6

BALCH3TP234.6

PINE FLT234.8

GATES231.6

KEARNEY230.4

30875MC CALL

233.71.016

MOSSLND2

MOSSLND1

WESTLEY230.7

Q128234.1

Q239228.1

Q166228.1

Q194228.0

BORDEN231.1

STOREY 2230.1

STOREY 1230.3

WILSON226.0

WARNERVL224.6

DS AMIGO235.7

MELONES233.2

COTTLE A230.6

COTTLE B224.8

BELLOTA229.1

TESLA E231.4

SN LS PP

TESLA D232.8

TESLA C232.5

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.0

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 82 1400 82 1400 82 1

0.0136.3

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

465.0

15.7

953.4

0.0

980.2

0.0

1208.8

0.0

473.7

16.0

442.5

14.9

378.9 12.8

362.9

12.2

625.9 64.2

621.7

63.8

888.7 51.8

525.8

53.9

124.1

13.2133.4

14.2

258.0

27.4

255.9

27.2

737.4

24.9

721.6

24.3

382.8

12.9

319.3

10.8

522.1 53.6

809.0

41.4

809.0

41.4

94.6

8.7

604.8 62.0

598.3

61.4

564.2 66.4

178.2 20.9

165.0 19.4

794.7 26.8

802.5 27.1

1124.0

37.9

669.9 22.6

1473.4

65.1

1473.4

65.1

364.4

8.4

376.7

8.7

1178.0

78.5

375.3

19.8

551.1 56.5

239.8 24.6

281.3 31.7

441.1 49.8

661.0 77.8

656.5 77.2

739.9 87.0

743.0 87.4

602.6

38.3

640.3

43.5

671.3

55.3

497.6

28.6

501.6 28.8

493.9

28.4

388.9 45.7

391.9

46.1

505.1 29.0

565.6 66.5

573.3 67.5

367.4

12.4

716.8

58.9

705.4

58.0

723.4

59.5

695.2 37.4695.2 37.4

838.4

85.9

842.4

86.3

842.4

86.3

842.4

86.3

842.5

86.3

838.5

85.9

0.00.0

527.7 54.0

530.2

54.3

530.2

54.3

527.7 54.0

644.3 75.7

304.8

38.4

299.1

37.7

792.8

99.9

929.7

117.2

853.6

100.3

724.7

91.4

874.1110.2

284.4 33.4

647.0 76.1

795.8

100.3

590.2

69.4

1383.0

81.4

686.8 56.7

1062.4 87.8

746.2 46.8

364.1 21.2364.1 21.2

614.8 72.3

610.3 71.8

491.4

57.8

54.7

5.6

54.7

5.6

526.4 47.4

526.4 47.4

362.4 21.1362.4 21.1

1259.4 42.5

1501.4 55.0

1532.1

56.1

961.0 34.1

985.5

35.0

1772.9 41.2

982.5 88.7

982.6 88.7

982.6 88.7

1489.8

78.1

549.2

29.0

548.0

28.9

590.9

32.2

221.9

26.1

209.3

24.6

221.9

26.1

209.3

24.6

1257.4 42.4

347.1 90.0173.6 90.0173.6 90.0

698.8

74.4

698.8

74.4

857.5108.1

197.8

10.5

193.5 10.3

197.8

10.5

193.5 10.3

286.6

9.7

239.3 8.1

733.3

75.2

733.2

75.2

Page 621: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 119- Woodward 115kV Bus MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:44 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.5

24156VINCENT

MIDWAY229.5

30057DIABLO

534.01.068

GATES539.1

GATES231.5

MORROBAY234.4

TEMPLETN

ARCO228.6

LOSBANOS536.0

30045MOSSLAND

530.91.062

GREGG231.9

HELMS PP234.4

HENRIETA230.2

PANOCHE234.1

HELM232.4

MCMULLN1

HERNDON231.5

LOSBANOS

237.3

COBURN235.6

TESLA535.0

TRACY541.4

METCALF533.5

METCALF234.5

BALCH3TP234.6

PINE FLT234.8

GATES231.5

KEARNEY230.3

30875MC CALL

233.71.016

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128234.1

Q239228.0

Q166228.0

Q194228.0

BORDEN231.0

STOREY 2230.0

STOREY 1230.2

WILSON225.9

WARNERVL224.5

DS AMIGO235.6

MELONES233.1

COTTLE A230.5

COTTLE B224.8

BELLOTA229.0

TESLA E231.4

SN LS PP

TESLA D232.8

TESLA C232.4

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.0

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 82 1400 82 1400 82 1

0.0136.3

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

411.3

120.5

874.2

69.9

898.7

72.2

1110.7

50.2

407.9

146.2

408.9

27.7

323.5135.3

322.8

104.5

253.6 0.7

245.9

38.3

359.2 28.6

206.6

39.3

49.4

8.949.7

20.4

102.5

10.7

103.4

5.6

682.7

146.5

679.4

22.2

252.6

253.3

251.1

168.6

204.3 61.6

325.7

0.5

325.7

0.5

52.4

71.8

242.6 45.9

238.9

65.3

223.9 54.1

68.724.7

67.9 5.7

742.3 34.1

739.8 71.4

897.7

559.5

610.5115.4

588.9

58.5

588.9

58.5

339.5

61.1

338.7

103.6

1108.3

75.4

145.3

6.6

223.4 5.7

103.1 52.3

113.9 1.2

177.2 22.4

261.5 57.6

257.4 74.6

294.6 54.1

301.5 24.1

556.7

38.7

591.2

44.6

620.1

43.0

194.3

59.7

196.9 51.4

192.5

60.4

157.3 12.8

160.5

8.0

198.8 50.3

224.2 50.5

233.4 18.5

347.2

48.3

638.0

176.9

627.8

174.4

642.0

184.9

281.7 10.1281.7 10.1

325.0

76.2

332.1

27.8

332.1

27.8

332.1

27.8

332.1

27.8

325.0

76.2

0.00.0

213.3 24.4

209.8

8.2

209.8

8.2

213.3 24.4

245.0 69.0

121.1

28.2

118.6

28.7

318.7

16.0

374.1

1.7

342.5

4.1

290.5

5.6

344.3 17.4

98.753.7

262.4 4.3

295.0

101.3

234.1

23.6

570.0

51.8

635.2 51.3

986.5 93.6

683.8104.2

135.8 57.9135.8 57.9

245.3 52.6

241.5 66.7

189.5

69.9

22.5

1.4

22.5

1.4

494.0 5.6

494.0 5.6

135.5 58.1135.5 58.1

1165.1 13.2

1383.1 126.6

1407.9

175.9

848.1250.5

851.1

256.7

1654.0 135.8

398.2 25.1

398.2 25.4

398.2 25.4

596.3

39.2

219.8

21.2

218.5

26.4

245.1

66.3

82.6

37.3

81.828.5

82.6

37.3

81.8

28.5

1159.2 49.3

131.3 32.465.716.265.716.2

129.3

13.1

129.3

13.1

321.1 97.3

76.4

16.6

76.6 6.4

76.4

16.6

76.6 6.4

232.0

144.7

231.7 19.3

295.7

1.8

294.1

8.2

Page 622: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 120- Woodward 115kV Bus amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:46 2008 2013sprpk_q272_pst_v2.sav

MIDWAY532.5

24156VINCENT

MIDWAY229.5

30057DIABLO

534.01.068

GATES539.1

GATES231.5

MORROBAY234.4

TEMPLETN

ARCO228.6

LOSBANOS536.0

30045MOSSLAND

530.91.062

GREGG231.9

HELMS PP234.4

HENRIETA230.2

PANOCHE234.1

HELM232.4

MCMULLN1

HERNDON231.5

LOSBANOS

237.3

COBURN235.6

TESLA535.0

TRACY541.4

METCALF533.5

METCALF234.5

BALCH3TP234.6

PINE FLT234.8

GATES231.5

KEARNEY230.3

30875MC CALL

233.71.016

MOSSLND2

MOSSLND1

WESTLEY230.6

Q128234.1

Q239228.0

Q166228.0

Q194228.0

BORDEN231.0

STOREY 2230.0

STOREY 1230.2

WILSON225.9

WARNERVL224.5

DS AMIGO235.6

MELONES233.1

COTTLE A230.5

COTTLE B224.8

BELLOTA229.0

TESLA E231.4

SN LS PP

TESLA D232.8

TESLA C232.4

Q235SWST232.3

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254232.0

STANDFRD107.1

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 82 1400 82 1400 82 1

0.0136.3

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

464.7

15.7

950.9

0.0

977.6

0.0

1205.6

0.0

469.8

15.9

438.9

14.8

379.1 12.8

363.3

12.3

624.6 64.1

620.5

63.6

887.6 51.8

524.5

53.8

126.4

13.4135.7

14.4

260.2

27.6

258.1

27.4

747.7

25.2

732.1

24.7

387.9

13.1

325.8

11.0

526.2 54.0

811.0

41.5

811.0

41.5

95.7

8.8

608.8 62.4

602.3

61.8

568.0 66.8

180.0 21.1

166.8 19.6

800.4 27.0

808.1 27.3

1128.1

38.1

675.5 22.8

1473.6

65.1

1473.6

65.1

369.4

8.5

381.5

8.8

1189.6

79.2

362.2

19.1

552.0 56.6

290.0 29.7

281.3 31.8

441.2 49.8

665.2 78.3

660.7 77.7

744.2 87.6

747.3 87.9

603.8

38.4

641.6

43.6

672.6

55.4

500.2

28.7

504.2 28.9

496.6

28.5

390.7 45.9

393.8

46.3

507.7 29.1

569.5 67.0

577.3 67.9

377.6

12.7

717.9

59.0

706.4

58.1

724.5

59.6

695.2 37.4695.2 37.4

839.7

86.0

843.7

86.4

843.7

86.4

843.7

86.4

843.7

86.4

839.8

86.0

0.00.0

528.9 54.2

531.4

54.4

531.4

54.4

528.9 54.2

644.4 75.7

309.6

39.0

303.8

38.3

797.4

100.5

935.0

117.9

858.9

100.9

729.3

91.9

881.1111.1

287.2 33.8

650.0 76.5

801.2

101.0

593.1

69.8

1392.4

81.9

687.8 56.8

1069.5 88.3

746.5 46.8

367.3 21.4367.3 21.4

618.6 72.8

614.1 72.3

495.1

58.3

54.8

5.6

54.8

5.6

526.8 47.5

526.8 47.5

365.6 21.3365.6 21.3

1257.5 42.4

1498.9 54.9

1529.3

56.0

954.3 33.9

978.9

34.8

1769.8 41.2

982.6 88.7

982.7 88.7

982.7 88.7

1490.1

78.1

550.1

29.1

548.9

29.0

633.1

34.5

226.0

26.6

213.5

25.1

226.0

26.6

213.5

25.1

1255.5 42.4

347.8 90.2173.9 90.2173.9 90.2

700.3

74.6

700.3

74.6

862.9108.8

195.7

10.4

191.2 10.2

195.7

10.4

191.2 10.2

294.5

9.9

247.9 8.4

737.5

75.6

737.4

75.6

Page 623: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 121-Outage: Los Banos North DLO

Tesla - Los Banos and Tracy - Los Banos Double Line Out

MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:47 2008 post-2013sprpk_q272_pre_lbn-dlo-ns.sav

MIDWAY530.9

24156VINCENT

MIDWAY229.1

30057DIABLO

532.81.066

GATES536.5

GATES231.3

MORROBAY234.3

TEMPLETN

ARCO228.4

LOSBANOS530.7

30045MOSSLAND

526.31.053

GREGG231.3

HELMS PP234.2

HENRIETA230.0

PANOCHE233.5

HELM232.1

MCMULLN1

HERNDON231.0

LOSBANOS

235.9

COBURN234.7

TESLA532.1

TRACY538.4

METCALF529.8

METCALF232.9

BALCH3TP234.4

PINE FLT234.6

GATES231.3

KEARNEY229.9

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY229.2

Q128233.9

Q239227.9

Q166227.9

Q194227.8

BORDEN230.5

STOREY 2229.5

STOREY 1229.7

WILSON225.1

WARNERVL223.8

DS AMIGO234.5

MELONES232.2

COTTLE A229.8

COTTLE B224.1

BELLOTA228.4

TESLA E230.3

SN LS PP

TESLA D231.7

TESLA C231.5

Q235SWST231.1

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254231.8

STANDFRD106.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 85 1400 85 1400 85 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

413.1

116.0

887.0

85.2

911.8

88.0

1126.1

70.5

421.7

105.2

422.8

11.9

319.8119.7

319.1

88.4

258.4 0.6

250.4

39.3

364.1 30.0

211.0

40.1

41.1

6.441.3

18.3

94.0

12.5

94.8

6.7

605.0

78.0

602.4

52.0

201.2

193.8

200.3

104.6

179.8 53.8

337.6

6.2

337.6

6.2

96.0

43.7

233.0 39.1

229.6

56.1

215.3 47.4

72.323.6

71.4 5.3

1005.8 40.0

1001.0 21.0

778.3

576.1

831.5136.2

589.0

54.9

589.0

54.9

299.7

29.1

299.1

136.4

1008.4

30.6

114.0

7.7

192.6 6.8

72.148.3

113.9 0.2

177.2 21.4

245.3 52.5

241.7 66.6

278.2 48.9

284.4 23.2

552.8

37.6

587.1

43.4

615.8

41.7

218.3

65.5

222.2 51.6

216.5

66.4

160.7 12.2

164.1

6.0

224.0 50.4

231.3 50.4

241.1 14.4

628.7

163.2

618.6

160.9

632.7

171.0

281.8 12.2281.8 12.2

320.8

73.2

327.8

26.3

327.8

26.3

327.8

26.3

327.8

26.3

320.8

73.2

0.00.0

208.9 24.8

205.5

9.7

205.5

9.7

208.9 24.8

245.0 69.1

124.8

26.0

122.3

26.6

322.1

18.1

378.2

0.7

346.5

6.1

293.9

7.5

353.7 17.8

103.9 53.6

267.4 3.3

306.5

102.9

238.9

26.7

689.9

49.3

596.1 42.9

919.4 75.7

633.0 95.7

130.5 61.3130.5 61.3

236.6 45.8

233.2 58.4

181.2

61.7

22.5

1.4

22.5

1.4

452.6 10.8

452.6 10.8

130.3 61.3130.3 61.3

931.1 2.5

1402.7 126.4

1428.5

165.0

902.6237.7

906.0

234.4

1683.4 141.2

398.3 27.8

398.3 28.1

398.3 28.1

596.3

35.1

189.9

15.2

189.0

18.0

184.1

53.1

100.1

36.8

98.930.0

100.1

36.8

98.9

30.0

927.3 2.5

130.1 32.965.016.465.016.4

128.0

13.8

128.0

13.8

332.6 98.6

42.9

23.9

43.012.7

42.9

23.9

43.012.7

267.7

0.7

266.3

7.0

Page 624: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Pre-Project Case

PATH15= 966 MW(S-N) PATH26= 2889 MW(N-S) PDCI= 3092 MW(N-S) COI= 4501 MW(N-S)

Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Spring Peak Pre-Project FY

Plot 122-Outage: Los Banos North DLO

Tesla - Los Banos and Tracy - Los Banos Double Line Out

amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:47 2008 post-2013sprpk_q272_pre_lbn-dlo-ns.sav

MIDWAY530.9

24156VINCENT

MIDWAY229.1

30057DIABLO

532.81.066

GATES536.5

GATES231.3

MORROBAY234.3

TEMPLETN

ARCO228.4

LOSBANOS530.7

30045MOSSLAND

526.31.053

GREGG231.3

HELMS PP234.2

HENRIETA230.0

PANOCHE233.5

HELM232.1

MCMULLN1

HERNDON231.0

LOSBANOS

235.9

COBURN234.7

TESLA532.1

TRACY538.4

METCALF529.8

METCALF232.9

BALCH3TP234.4

PINE FLT234.6

GATES231.3

KEARNEY229.9

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY229.2

Q128233.9

Q239227.9

Q166227.9

Q194227.8

BORDEN230.5

STOREY 2229.5

STOREY 1229.7

WILSON225.1

WARNERVL223.8

DS AMIGO234.5

MELONES232.2

COTTLE A229.8

COTTLE B224.1

BELLOTA228.4

TESLA E230.3

SN LS PP

TESLA D231.7

TESLA C231.5

Q235SWST231.1

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254231.8

STANDFRD106.7

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 85 1400 85 1400 85 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

466.7

15.7

969.0

0.0

996.1

0.0

1227.0

0.0

472.6

15.9

455.1

15.4

370.0 12.5

356.3

12.0

636.6 65.3

632.6

64.9

900.3 52.5

536.2

55.0

104.7

11.1114.1

12.1

239.7

25.5

237.1

25.2

656.4

22.1

657.8

22.2

303.8

10.2

245.8

8.3

464.0 47.6

842.6

43.1

842.6

43.1

114.7

10.5

584.1 59.9

578.4

59.3

544.9 64.1

188.0 22.1

176.2 20.7

1095.1 36.9

1098.4 37.1

1038.3

35.0

924.3 31.2

1476.3

65.2

1476.3

65.2

324.0

7.5

357.6

8.3

1085.6

72.0

285.1

15.0

476.7 48.9

218.0 22.4

281.7 31.8

441.5 49.8

624.1 73.4

619.8 72.9

702.7 82.7

705.7 83.0

603.7

38.1

641.5

43.3

672.5

55.0

564.9

32.4

568.5 32.6

561.4

32.2

401.3 47.2

403.9

47.5

571.9 32.8

590.1 69.4

597.2 70.3

706.4

57.9

695.1

57.0

712.8

58.4

696.3 37.5696.3 37.5

829.2

84.9

833.0

85.3

833.1

85.3

833.1

85.3

833.1

85.3

829.2

84.9

0.00.0

518.3 53.1

521.0

53.4

521.0

53.4

518.3 53.1

644.9 75.8

318.2

40.1

312.3

39.4

807.9

101.9

947.2

119.4

871.2

102.4

739.6

93.2

908.3114.5

299.7 35.2

664.8 78.2

832.9

105.0

607.6

71.5

1692.4

99.6

648.4 53.3

1000.8 82.2

694.5 43.3

360.6 21.0360.6 21.0

595.8 70.1

591.8 69.6

471.1

55.4

55.1

5.6

55.1

5.6

485.4 43.5

485.4 43.5

358.8 20.9358.8 20.9

1010.2 34.1

1528.1 56.0

1556.9

57.0

1012.7 36.0

1034.3

36.7

1811.4 42.1

984.3 88.7

984.4 88.7

984.4 88.7

1491.0

78.2

474.9

25.1

473.9

25.0

478.3

26.0

266.1

31.3

255.5

30.1

266.1

31.3

255.5

30.1

1010.4 34.1

346.0 89.4173.0 89.4173.0 89.4

696.8

74.2

696.8

74.2

895.0112.8

123.8

6.6

112.1 6.0

123.8

6.6

112.1 6.0

669.2

68.6

669.1

68.6

Page 625: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 123-Outage: Los Banos North DLO

Tesla - Los Banos and Tracy - Los Banos Double Line Out

MW/MVAR

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:49 2008 post-2013sprpk_q272_pst_v2_lbn-dlo-ns.sav

MIDWAY530.8

24156VINCENT

MIDWAY229.1

30057DIABLO

532.81.066

GATES536.4

GATES231.2

MORROBAY234.3

TEMPLETN

ARCO228.3

LOSBANOS530.5

30045MOSSLAND

526.01.052

GREGG231.3

HELMS PP234.2

HENRIETA230.0

PANOCHE233.4

HELM232.0

MCMULLN1

HERNDON230.9

LOSBANOS

235.8

COBURN234.6

TESLA532.0

TRACY538.4

METCALF529.6

METCALF232.8

BALCH3TP234.4

PINE FLT234.6

GATES231.2

KEARNEY229.8

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY229.1

Q128233.8

Q239227.8

Q166227.8

Q194227.8

BORDEN230.5

STOREY 2229.4

STOREY 1229.6

WILSON225.0

WARNERVL223.7

DS AMIGO234.4

MELONES232.1

COTTLE A229.7

COTTLE B224.0

BELLOTA228.3

TESLA E230.3

SN LS PP

TESLA D231.7

TESLA C231.5

Q235SWST231.1

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254231.8

STANDFRD106.6

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 85 1400 85 1400 85 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

412.9

115.7

884.9

85.9

909.6

88.7

1123.4

71.3

418.8

103.1

419.9

14.2

320.3118.7

319.5

87.4

257.9 0.8

249.9

38.9

363.7 30.2

210.6

39.7

41.8

6.742.0

18.5

94.7

12.2

95.5

6.4

613.1

76.7

610.4

52.3

207.3

192.3

206.4

103.4

181.2 53.9

338.1

6.2

338.1

6.2

99.6

44.2

234.6 38.9

231.2

56.3

216.8 47.3

73.323.6

72.4 5.5

1020.2 41.4

1015.3 18.8

778.6

576.8

844.5137.4

589.0

54.5

589.0

54.5

303.6

28.3

303.0

136.6

1017.1

31.7

108.1

7.6

192.5 6.6

94.349.5

113.9 0.3

177.2 21.3

247.0 52.4

243.4 66.8

279.9 48.9

286.2 22.7

553.8

37.4

588.2

43.2

616.9

41.5

220.2

66.2

224.2 51.8

218.4

67.1

161.6 12.6

165.0

6.0

226.0 50.6

233.2 51.3

243.2 14.3

629.5

162.9

619.4

160.6

633.6

170.7

281.8 12.4281.8 12.4

321.2

73.4

328.1

26.3

328.1

26.3

328.1

26.3

328.2

26.2

321.2

73.4

0.00.0

209.3 25.0

205.9

9.7

205.9

9.7

209.3 25.0

245.0 69.1

127.3

26.2

124.7

26.9

324.4

18.8

380.9

1.5

349.2

6.8

296.2

8.1

357.3 18.0

105.5 53.6

269.0 2.8

309.2

103.7

240.4

27.7

698.1

48.7

595.8 43.2

924.7 76.0

631.5 96.2

131.9 61.4131.9 61.4

238.2 45.6

234.6 58.5

182.6

61.8

22.5

1.4

22.5

1.4

451.5 10.4

451.5 10.4

131.6 61.5131.6 61.5

921.4 4.9

1401.0 125.1

1426.8

164.2

897.8236.3

901.2

233.8

1681.6 139.6

398.3 28.0

398.3 28.4

398.4 28.4

596.3

34.0

189.9

15.0

189.0

17.7

200.3

54.7

102.4

36.8

101.2

30.3

102.4

36.8

101.2

30.3

917.6 6.2

130.4 32.865.216.465.216.4

128.3

13.6

128.3

13.6

335.4 99.4

40.7

24.8

40.813.5

40.7

24.8

40.813.5

269.1

1.0

267.7

6.7

Page 626: To determine the system impacts caused by the Project

PG&E 2007 CASE SERIES: 2013 Spring Peak Post-Project Case

PATH15= 958 MW(S-N) PATH26= 2895 MW(N-S) PDCI= 3091 MW(N-S) COI= 4507 MW(N-S)

Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Spring Peak Post-Project FY

Plot 124-Outage: Los Banos North DLO

Tesla - Los Banos and Tracy - Los Banos Double Line Out

amps/rate

Rating = 2

gfres2.drw

General Electric International, Inc. PSLF Program Wed Oct 01 08:25:49 2008 post-2013sprpk_q272_pst_v2_lbn-dlo-ns.sav

MIDWAY530.8

24156VINCENT

MIDWAY229.1

30057DIABLO

532.81.066

GATES536.4

GATES231.2

MORROBAY234.3

TEMPLETN

ARCO228.3

LOSBANOS530.5

30045MOSSLAND

526.01.052

GREGG231.3

HELMS PP234.2

HENRIETA230.0

PANOCHE233.4

HELM232.0

MCMULLN1

HERNDON230.9

LOSBANOS

235.8

COBURN234.6

TESLA532.0

TRACY538.4

METCALF529.6

METCALF232.8

BALCH3TP234.4

PINE FLT234.6

GATES231.2

KEARNEY229.8

30875MC CALL

233.41.015

MOSSLND2

MOSSLND1

WESTLEY229.1

Q128233.8

Q239227.8

Q166227.8

Q194227.8

BORDEN230.5

STOREY 2229.4

STOREY 1229.6

WILSON225.0

WARNERVL223.7

DS AMIGO234.4

MELONES232.1

COTTLE A229.7

COTTLE B224.0

BELLOTA228.3

TESLA E230.3

SN LS PP

TESLA D231.7

TESLA C231.5

Q235SWST231.1

37585TRCY PMP

Q235230.0

HELMS 1

HELMS 2

HELMS 3

Q254231.8

STANDFRD106.6

HUNTWSTP

To Table Mt.

To Vaca-Dixon

To OIinda

Greater Fresno500-kV & 230-kV System

400 85 1400 85 1400 85 1

0.0135.9

v

1.000

1.000

0.9750.9750.975

1.000 1.0001.000

0.975

0.975

0.975

1.025

1.025

1.000

1.0001.000

1.044

1.044

1.044

466.4

15.7

967.0

0.0

994.1

0.0

1224.4

0.0

469.1

15.8

452.3

15.3

370.1 12.5

356.6

12.0

635.5 65.2

631.6

64.8

899.4 52.5

535.1

54.9

106.6

11.3116.1

12.3

241.5

25.7

239.0

25.4

665.0

22.4

666.8

22.5

307.5

10.4

251.2

8.5

467.6 48.0

843.9

43.2

843.9

43.2

118.6

10.8

588.2 60.3

582.5

59.7

548.7 64.6

190.4 22.4

178.6 21.0

1111.2 37.5

1114.4 37.6

1039.1

35.1

939.1 31.7

1476.5

65.2

1476.5

65.2

328.2

7.6

361.7

8.3

1095.3

72.6

270.4

14.3

476.6 48.9

267.4 27.4

281.7 31.8

441.5 49.8

628.4 73.9

624.2 73.4

707.2 83.2

710.2 83.6

605.0

38.1

642.9

43.4

674.0

55.1

570.1

32.7

573.8 32.9

566.6

32.5

403.8 47.5

406.4

47.8

577.1 33.1

595.4 70.1

602.5 70.9

707.3

58.0

696.0

57.0

713.7

58.5

696.4 37.5696.4 37.5

830.3

85.0

834.1

85.4

834.1

85.4

834.1

85.4

834.2

85.4

830.3

85.0

0.00.0

519.4 53.2

522.1

53.5

522.1

53.5

519.4 53.2

645.0 75.8

324.5

40.9

318.5

40.1

813.9

102.6

954.2

120.3

878.3

103.2

745.6

94.0

917.9115.7

303.7 35.7

669.1 78.7

840.7

106.0

611.8

72.0

1713.4

100.8

648.2 53.2

1006.7 82.7

693.1 43.2

363.9 21.2363.9 21.2

599.7 70.6

595.7 70.1

474.9

55.9

55.1

5.6

55.1

5.6

484.3 43.4

484.3 43.4

362.1 21.1362.1 21.1

999.8 33.7

1526.3 55.9

1554.9

57.0

1007.4 35.8

1029.0

36.5

1809.5 42.1

984.5 88.7

984.5 88.7

984.6 88.7

1491.3

78.2

474.8

25.1

473.9

25.0

518.5

28.2

271.7

32.0

261.2

30.7

271.7

32.0

261.2

30.7

1000.3 33.8

347.0 89.6173.5 89.6173.5 89.6

698.6

74.4

698.6

74.4

902.8113.8

120.0

6.4

107.4 5.7

120.0

6.4

107.4 5.7

672.8

69.0

672.7

69.0

Page 627: To determine the system impacts caused by the Project

Appendix E Transient Stability Plots

Page 628: To determine the system impacts caused by the Project

Full load rejection (127 MW) of Project and GWF Henrietta

Page 629: To determine the system impacts caused by the Project

Project Relative Rotor Angle

-180.00

-90.00

0.00

90.00

180.00

-180.0Q272_ST1 ang34691 Q272_ST1 13.8 1 1 180.0-180.0GWF_GT1 ang34539 GWF_GT1 13.8 1 1 180.0-180.0GWF_GT2 ang34541 GWF_GT2 13.8 3 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

Project Terminal Voltage

0.70

0.85

1.00

1.15

1.30

0.7 Q272_ST1 vt34691 Q272_ST1 13.8 1 1 1.30.7 GWF_GT1 vt34539 GWF_GT1 13.8 2 1 1.30.7 GWF_GT2 vt34541 GWF_GT2 13.8 3 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Project Rotor Speed

0.99

1.00

1.00

1.00

1.01

0.99 Q272_ST1 spd34691 Q272_ST1 13.8 1 1 1.010.99 GWF_GT1 spd34539 GWF_GT1 13.8 2 1 1.010.99 GWF_GT2 spd34541 GWF_GT2 13.8 3 1 1.01

Time( sec )0.0 20.05.0 10.0 15.0

Project Generation

0.00

25.00

50.00

75.00

100.00

0.0 Q272_ST1 pg34691 Q272_ST1 13.8 1 1 100.00.0 GWF_GT1 pg34539 GWF_GT1 13.8 2 1 100.00.0 GWF_GT2 pg34541 GWF_GT2 13.8 3 1 100.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYProject Q272 and GWF Henrietta Full Load Rejection

.

Wed Oct 08 10:32:11 2008

Page 1

2013sumpk_q272_pst_tr_Q272_Reject.chf

Page 630: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 1

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34540 HENRITTA 70.0 * 1 1.30.7 70 vbul34544 TLRE LKE 70.0 * 1 1.30.7 70 vbul34542 JCBSCRNR 70.0 * 1 1.30.7 70 vbul34518 LEMOORE 70.0 * 1 1.30.7 70 vbul34516 LEPRINO 70.0 * 1 1.30.7 70 vbul34532 ARMSTRNG 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 2

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34460 GUERNSEY 70.0 * 1 1.30.7 70 vbul34534 RESERVE 70.0 * 1 1.30.7 70 vbul34514 MUSLSLGH 70.0 * 1 1.30.7 70 vbul34458 HARDWICK 70.0 * 1 1.30.7 70 vbus34576 KNGLOBUS 70.0 * 1 1.30.7 70 vbul34512 CARUTHRS 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYProject Q272 and GWF Henrietta Full Load Rejection

.

Wed Oct 08 10:32:11 2008

Page 2

2013sumpk_q272_pst_tr_Q272_Reject.chf

Page 631: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 3

0.70

0.85

1.00

1.15

1.30

0.7 230 vbus30881 HENRIETA 230.0 * 1 1.30.7 230 vbus30900 GATES 230.0 * 1 1.30.7 230 vbus30810 GREGG 230.0 * 1 1.30.7 230 vbus30875 MC CALL 230.0 * 1 1.30.7 230 vbus30790 PANOCHE 230.0 * 1 1.30.7 230 vbus30935 ARCO 230.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 4

0.70

0.85

1.00

1.15

1.30

0.7 115 vbus34430 HENRETTA 115.0 * 1 1.30.7 115 vbul34521 LEPRNOFD 115.0 * 1 1.30.7 115 vbul34429 GWF_HEP 115.0 * 1 1.30.7 115 vbul34428 CONTADNA 115.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYProject Q272 and GWF Henrietta Full Load Rejection

.

Wed Oct 08 10:32:11 2008

Page 3

2013sumpk_q272_pst_tr_Q272_Reject.chf

Page 632: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 1

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34540 HENRITTA 70.0 * 1 61.059.0 70 fbul34544 TLRE LKE 70.0 * 1 61.059.0 70 fbul34542 JCBSCRNR 70.0 * 1 61.059.0 70 fbul34518 LEMOORE 70.0 * 1 61.059.0 70 fbul34516 LEPRINO 70.0 * 1 61.059.0 70 fbul34532 ARMSTRNG 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 2

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34460 GUERNSEY 70.0 * 1 61.059.0 70 fbul34534 RESERVE 70.0 * 1 61.059.0 70 fbul34514 MUSLSLGH 70.0 * 1 61.059.0 70 fbul34458 HARDWICK 70.0 * 1 61.059.0 70 fbus34576 KNGLOBUS 70.0 * 1 61.059.0 70 fbul34512 CARUTHRS 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYProject Q272 and GWF Henrietta Full Load Rejection

.

Wed Oct 08 10:32:11 2008

Page 4

2013sumpk_q272_pst_tr_Q272_Reject.chf

Page 633: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 3

59.00

59.50

60.00

60.50

61.00

59.0 230 fbus30881 HENRIETA 230.0 * 1 61.059.0 230 fbus30900 GATES 230.0 * 1 61.059.0 230 fbus30810 GREGG 230.0 * 1 61.059.0 230 fbus30875 MC CALL 230.0 * 1 61.059.0 230 fbus30790 PANOCHE 230.0 * 1 61.059.0 230 fbus30935 ARCO 230.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 4

59.00

59.50

60.00

60.50

61.00

59.0 115 fbus34430 HENRETTA 115.0 1 1 61.059.0 115 fbul34521 LEPRNOFD 115.0 1 1 61.059.0 115 fbul34429 GWF_HEP 115.0 1 1 61.059.0 115 fbul34428 CONTADNA 115.0 1 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYProject Q272 and GWF Henrietta Full Load Rejection

.

Wed Oct 08 10:32:11 2008

Page 5

2013sumpk_q272_pst_tr_Q272_Reject.chf

Page 634: To determine the system impacts caused by the Project

Generator Angles of Local Units

-180.00

-90.00

0.00

90.00

180.00

-180.0 #1 ang 34600 HELMS 1 18.0 * 1 180.0-180.0 GWF-PWR ang34650 GWF-PWR. 13.8 * 1 180.0-180.0 1 ang 34431 GWF_HEP1 13.8 * 1 180.0-180.0 2 ang 34433 GWF_HEP2 13.8 * 1 180.0-180.0 GT1 ang 34661 P0418GT1 13.8 * 1 180.0-180.0 Cogen ang34642 KINGSBUR 9.1 * 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYProject Q272 and GWF Henrietta Full Load Rejection

.

Wed Oct 08 10:32:11 2008

Page 6

2013sumpk_q272_pst_tr_Q272_Reject.chf

Page 635: To determine the system impacts caused by the Project

Three-phase close-in fault on the Henrietta-Guernsey 70-kV line at the Henrietta 70-kV bus with normal clearing time followed by the loss of the Henrietta-Guernsey 70-

kV line.

Page 636: To determine the system impacts caused by the Project

Project Relative Rotor Angle

-180.00

-90.00

0.00

90.00

180.00

-180.0Q272_ST1 ang34691 Q272_ST1 13.8 1 1 180.0-180.0GWF_GT1 ang34539 GWF_GT1 13.8 1 1 180.0-180.0GWF_GT2 ang34541 GWF_GT2 13.8 3 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

Project Terminal Voltage

0.70

0.85

1.00

1.15

1.30

0.7 Q272_ST1 vt34691 Q272_ST1 13.8 1 1 1.30.7 GWF_GT1 vt34539 GWF_GT1 13.8 2 1 1.30.7 GWF_GT2 vt34541 GWF_GT2 13.8 3 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Project Rotor Speed

0.99

1.00

1.00

1.00

1.01

0.99 Q272_ST1 spd34691 Q272_ST1 13.8 1 1 1.010.99 GWF_GT1 spd34539 GWF_GT1 13.8 2 1 1.010.99 GWF_GT2 spd34541 GWF_GT2 13.8 3 1 1.01

Time( sec )0.0 20.05.0 10.0 15.0

Project Generation

0.00

25.00

50.00

75.00

100.00

0.0 Q272_ST1 pg34691 Q272_ST1 13.8 1 1 100.00.0 GWF_GT1 pg34539 GWF_GT1 13.8 2 1 100.00.0 GWF_GT2 pg34541 GWF_GT2 13.8 3 1 100.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Guernsey 70-kV Single Line Out

.

Wed Oct 08 09:50:42 2008

Page 1

2013sumpk_q272_pst_tr_hen-guernsey.chf

Page 637: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 1

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34540 HENRITTA 70.0 * 1 1.30.7 70 vbul34544 TLRE LKE 70.0 * 1 1.30.7 70 vbul34542 JCBSCRNR 70.0 * 1 1.30.7 70 vbul34518 LEMOORE 70.0 * 1 1.30.7 70 vbul34516 LEPRINO 70.0 * 1 1.30.7 70 vbul34532 ARMSTRNG 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 2

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34460 GUERNSEY 70.0 * 1 1.30.7 70 vbul34534 RESERVE 70.0 * 1 1.30.7 70 vbul34514 MUSLSLGH 70.0 * 1 1.30.7 70 vbul34458 HARDWICK 70.0 * 1 1.30.7 70 vbus34576 KNGLOBUS 70.0 * 1 1.30.7 70 vbul34512 CARUTHRS 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Guernsey 70-kV Single Line Out

.

Wed Oct 08 09:50:42 2008

Page 2

2013sumpk_q272_pst_tr_hen-guernsey.chf

Page 638: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 3

0.70

0.85

1.00

1.15

1.30

0.7 230 vbus30881 HENRIETA 230.0 * 1 1.30.7 230 vbus30900 GATES 230.0 * 1 1.30.7 230 vbus30810 GREGG 230.0 * 1 1.30.7 230 vbus30875 MC CALL 230.0 * 1 1.30.7 230 vbus30790 PANOCHE 230.0 * 1 1.30.7 230 vbus30935 ARCO 230.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 4

0.70

0.85

1.00

1.15

1.30

0.7 115 vbus34430 HENRETTA 115.0 * 1 1.30.7 115 vbul34521 LEPRNOFD 115.0 * 1 1.30.7 115 vbul34429 GWF_HEP 115.0 * 1 1.30.7 115 vbul34428 CONTADNA 115.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Guernsey 70-kV Single Line Out

.

Wed Oct 08 09:50:42 2008

Page 3

2013sumpk_q272_pst_tr_hen-guernsey.chf

Page 639: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 1

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34540 HENRITTA 70.0 * 1 61.059.0 70 fbul34544 TLRE LKE 70.0 * 1 61.059.0 70 fbul34542 JCBSCRNR 70.0 * 1 61.059.0 70 fbul34518 LEMOORE 70.0 * 1 61.059.0 70 fbul34516 LEPRINO 70.0 * 1 61.059.0 70 fbul34532 ARMSTRNG 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 2

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34460 GUERNSEY 70.0 * 1 61.059.0 70 fbul34534 RESERVE 70.0 * 1 61.059.0 70 fbul34514 MUSLSLGH 70.0 * 1 61.059.0 70 fbul34458 HARDWICK 70.0 * 1 61.059.0 70 fbus34576 KNGLOBUS 70.0 * 1 61.059.0 70 fbul34512 CARUTHRS 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Guernsey 70-kV Single Line Out

.

Wed Oct 08 09:50:42 2008

Page 4

2013sumpk_q272_pst_tr_hen-guernsey.chf

Page 640: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 3

59.00

59.50

60.00

60.50

61.00

59.0 230 fbus30881 HENRIETA 230.0 * 1 61.059.0 230 fbus30900 GATES 230.0 * 1 61.059.0 230 fbus30810 GREGG 230.0 * 1 61.059.0 230 fbus30875 MC CALL 230.0 * 1 61.059.0 230 fbus30790 PANOCHE 230.0 * 1 61.059.0 230 fbus30935 ARCO 230.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 4

59.00

59.50

60.00

60.50

61.00

59.0 115 fbus34430 HENRETTA 115.0 1 1 61.059.0 115 fbul34521 LEPRNOFD 115.0 1 1 61.059.0 115 fbul34429 GWF_HEP 115.0 1 1 61.059.0 115 fbul34428 CONTADNA 115.0 1 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Guernsey 70-kV Single Line Out

.

Wed Oct 08 09:50:42 2008

Page 5

2013sumpk_q272_pst_tr_hen-guernsey.chf

Page 641: To determine the system impacts caused by the Project

Generator Angles of Local Units

-180.00

-90.00

0.00

90.00

180.00

-180.0 #1 ang 34600 HELMS 1 18.0 * 1 180.0-180.0 GWF-PWR ang34650 GWF-PWR. 13.8 * 1 180.0-180.0 1 ang 34431 GWF_HEP1 13.8 * 1 180.0-180.0 2 ang 34433 GWF_HEP2 13.8 * 1 180.0-180.0 GT1 ang 34661 P0418GT1 13.8 * 1 180.0-180.0 Cogen ang34642 KINGSBUR 9.1 * 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Guernsey 70-kV Single Line Out

.

Wed Oct 08 09:50:42 2008

Page 6

2013sumpk_q272_pst_tr_hen-guernsey.chf

Page 642: To determine the system impacts caused by the Project

Three-phase close-in fault on the Henrietta-Lemoore NAS 70-kV line at the Henrietta 70-kV bus with normal clearing time followed by the loss of the Henrietta-Lemoore

NAS 70-kV line.

Page 643: To determine the system impacts caused by the Project

Project Relative Rotor Angle

-180.00

-90.00

0.00

90.00

180.00

-180.0Q272_ST1 ang34691 Q272_ST1 13.8 1 1 180.0-180.0GWF_GT1 ang34539 GWF_GT1 13.8 1 1 180.0-180.0GWF_GT2 ang34541 GWF_GT2 13.8 3 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

Project Terminal Voltage

0.70

0.85

1.00

1.15

1.30

0.7 Q272_ST1 vt34691 Q272_ST1 13.8 1 1 1.30.7 GWF_GT1 vt34539 GWF_GT1 13.8 2 1 1.30.7 GWF_GT2 vt34541 GWF_GT2 13.8 3 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Project Rotor Speed

0.99

1.00

1.00

1.00

1.01

0.99 Q272_ST1 spd34691 Q272_ST1 13.8 1 1 1.010.99 GWF_GT1 spd34539 GWF_GT1 13.8 2 1 1.010.99 GWF_GT2 spd34541 GWF_GT2 13.8 3 1 1.01

Time( sec )0.0 20.05.0 10.0 15.0

Project Generation

0.00

25.00

50.00

75.00

100.00

0.0 Q272_ST1 pg34691 Q272_ST1 13.8 1 1 100.00.0 GWF_GT1 pg34539 GWF_GT1 13.8 2 1 100.00.0 GWF_GT2 pg34541 GWF_GT2 13.8 3 1 100.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore NAS 70-kV Single Line Out

.

Wed Oct 08 09:58:39 2008

Page 1

2013sumpk_q272_pst_tr_hen-LemNAS.chf

Page 644: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 1

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34540 HENRITTA 70.0 * 1 1.30.7 70 vbul34544 TLRE LKE 70.0 * 1 1.30.7 70 vbul34542 JCBSCRNR 70.0 * 1 1.30.7 70 vbul34518 LEMOORE 70.0 * 1 1.30.7 70 vbul34516 LEPRINO 70.0 * 1 1.30.7 70 vbul34532 ARMSTRNG 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 2

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34460 GUERNSEY 70.0 * 1 1.30.7 70 vbul34534 RESERVE 70.0 * 1 1.30.7 70 vbul34514 MUSLSLGH 70.0 * 1 1.30.7 70 vbul34458 HARDWICK 70.0 * 1 1.30.7 70 vbus34576 KNGLOBUS 70.0 * 1 1.30.7 70 vbul34512 CARUTHRS 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore NAS 70-kV Single Line Out

.

Wed Oct 08 09:58:39 2008

Page 2

2013sumpk_q272_pst_tr_hen-LemNAS.chf

Page 645: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 3

0.70

0.85

1.00

1.15

1.30

0.7 230 vbus30881 HENRIETA 230.0 * 1 1.30.7 230 vbus30900 GATES 230.0 * 1 1.30.7 230 vbus30810 GREGG 230.0 * 1 1.30.7 230 vbus30875 MC CALL 230.0 * 1 1.30.7 230 vbus30790 PANOCHE 230.0 * 1 1.30.7 230 vbus30935 ARCO 230.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 4

0.70

0.85

1.00

1.15

1.30

0.7 115 vbus34430 HENRETTA 115.0 * 1 1.30.7 115 vbul34521 LEPRNOFD 115.0 * 1 1.30.7 115 vbul34429 GWF_HEP 115.0 * 1 1.30.7 115 vbul34428 CONTADNA 115.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore NAS 70-kV Single Line Out

.

Wed Oct 08 09:58:39 2008

Page 3

2013sumpk_q272_pst_tr_hen-LemNAS.chf

Page 646: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 1

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34540 HENRITTA 70.0 * 1 61.059.0 70 fbul34544 TLRE LKE 70.0 * 1 61.059.0 70 fbul34542 JCBSCRNR 70.0 * 1 61.059.0 70 fbul34518 LEMOORE 70.0 * 1 61.059.0 70 fbul34516 LEPRINO 70.0 * 1 61.059.0 70 fbul34532 ARMSTRNG 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 2

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34460 GUERNSEY 70.0 * 1 61.059.0 70 fbul34534 RESERVE 70.0 * 1 61.059.0 70 fbul34514 MUSLSLGH 70.0 * 1 61.059.0 70 fbul34458 HARDWICK 70.0 * 1 61.059.0 70 fbus34576 KNGLOBUS 70.0 * 1 61.059.0 70 fbul34512 CARUTHRS 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore NAS 70-kV Single Line Out

.

Wed Oct 08 09:58:39 2008

Page 4

2013sumpk_q272_pst_tr_hen-LemNAS.chf

Page 647: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 3

59.00

59.50

60.00

60.50

61.00

59.0 230 fbus30881 HENRIETA 230.0 * 1 61.059.0 230 fbus30900 GATES 230.0 * 1 61.059.0 230 fbus30810 GREGG 230.0 * 1 61.059.0 230 fbus30875 MC CALL 230.0 * 1 61.059.0 230 fbus30790 PANOCHE 230.0 * 1 61.059.0 230 fbus30935 ARCO 230.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 4

59.00

59.50

60.00

60.50

61.00

59.0 115 fbus34430 HENRETTA 115.0 1 1 61.059.0 115 fbul34521 LEPRNOFD 115.0 1 1 61.059.0 115 fbul34429 GWF_HEP 115.0 1 1 61.059.0 115 fbul34428 CONTADNA 115.0 1 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore NAS 70-kV Single Line Out

.

Wed Oct 08 09:58:39 2008

Page 5

2013sumpk_q272_pst_tr_hen-LemNAS.chf

Page 648: To determine the system impacts caused by the Project

Generator Angles of Local Units

-180.00

-90.00

0.00

90.00

180.00

-180.0 #1 ang 34600 HELMS 1 18.0 * 1 180.0-180.0 GWF-PWR ang34650 GWF-PWR. 13.8 * 1 180.0-180.0 1 ang 34431 GWF_HEP1 13.8 * 1 180.0-180.0 2 ang 34433 GWF_HEP2 13.8 * 1 180.0-180.0 GT1 ang 34661 P0418GT1 13.8 * 1 180.0-180.0 Cogen ang34642 KINGSBUR 9.1 * 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore NAS 70-kV Single Line Out

.

Wed Oct 08 09:58:39 2008

Page 6

2013sumpk_q272_pst_tr_hen-LemNAS.chf

Page 649: To determine the system impacts caused by the Project

Three-phase close-in fault on the Henrietta-Lemoore 70-kV line at the Henrietta 70-kV bus with normal clearing time followed by the loss of the Henrietta-Lemoore 70-

kV line.

Page 650: To determine the system impacts caused by the Project

Project Relative Rotor Angle

-180.00

-90.00

0.00

90.00

180.00

-180.0Q272_ST1 ang34691 Q272_ST1 13.8 1 1 180.0-180.0GWF_GT1 ang34539 GWF_GT1 13.8 1 1 180.0-180.0GWF_GT2 ang34541 GWF_GT2 13.8 3 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

Project Terminal Voltage

0.70

0.85

1.00

1.15

1.30

0.7 Q272_ST1 vt34691 Q272_ST1 13.8 1 1 1.30.7 GWF_GT1 vt34539 GWF_GT1 13.8 2 1 1.30.7 GWF_GT2 vt34541 GWF_GT2 13.8 3 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Project Rotor Speed

0.99

1.00

1.00

1.00

1.01

0.99 Q272_ST1 spd34691 Q272_ST1 13.8 1 1 1.010.99 GWF_GT1 spd34539 GWF_GT1 13.8 2 1 1.010.99 GWF_GT2 spd34541 GWF_GT2 13.8 3 1 1.01

Time( sec )0.0 20.05.0 10.0 15.0

Project Generation

0.00

25.00

50.00

75.00

100.00

0.0 Q272_ST1 pg34691 Q272_ST1 13.8 1 1 100.00.0 GWF_GT1 pg34539 GWF_GT1 13.8 2 1 100.00.0 GWF_GT2 pg34541 GWF_GT2 13.8 3 1 100.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore 70-kV Single Line Out

.

Wed Oct 08 10:06:44 2008

Page 1

2013sumpk_q272_pst_tr_hen-lemoore.chf

Page 651: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 1

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34540 HENRITTA 70.0 * 1 1.30.7 70 vbul34544 TLRE LKE 70.0 * 1 1.30.7 70 vbul34542 JCBSCRNR 70.0 * 1 1.30.7 70 vbul34518 LEMOORE 70.0 * 1 1.30.7 70 vbul34516 LEPRINO 70.0 * 1 1.30.7 70 vbul34532 ARMSTRNG 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 2

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34460 GUERNSEY 70.0 * 1 1.30.7 70 vbul34534 RESERVE 70.0 * 1 1.30.7 70 vbul34514 MUSLSLGH 70.0 * 1 1.30.7 70 vbul34458 HARDWICK 70.0 * 1 1.30.7 70 vbus34576 KNGLOBUS 70.0 * 1 1.30.7 70 vbul34512 CARUTHRS 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore 70-kV Single Line Out

.

Wed Oct 08 10:06:44 2008

Page 2

2013sumpk_q272_pst_tr_hen-lemoore.chf

Page 652: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 3

0.70

0.85

1.00

1.15

1.30

0.7 230 vbus30881 HENRIETA 230.0 * 1 1.30.7 230 vbus30900 GATES 230.0 * 1 1.30.7 230 vbus30810 GREGG 230.0 * 1 1.30.7 230 vbus30875 MC CALL 230.0 * 1 1.30.7 230 vbus30790 PANOCHE 230.0 * 1 1.30.7 230 vbus30935 ARCO 230.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 4

0.70

0.85

1.00

1.15

1.30

0.7 115 vbus34430 HENRETTA 115.0 * 1 1.30.7 115 vbul34521 LEPRNOFD 115.0 * 1 1.30.7 115 vbul34429 GWF_HEP 115.0 * 1 1.30.7 115 vbul34428 CONTADNA 115.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore 70-kV Single Line Out

.

Wed Oct 08 10:06:44 2008

Page 3

2013sumpk_q272_pst_tr_hen-lemoore.chf

Page 653: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 1

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34540 HENRITTA 70.0 * 1 61.059.0 70 fbul34544 TLRE LKE 70.0 * 1 61.059.0 70 fbul34542 JCBSCRNR 70.0 * 1 61.059.0 70 fbul34518 LEMOORE 70.0 * 1 61.059.0 70 fbul34516 LEPRINO 70.0 * 1 61.059.0 70 fbul34532 ARMSTRNG 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 2

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34460 GUERNSEY 70.0 * 1 61.059.0 70 fbul34534 RESERVE 70.0 * 1 61.059.0 70 fbul34514 MUSLSLGH 70.0 * 1 61.059.0 70 fbul34458 HARDWICK 70.0 * 1 61.059.0 70 fbus34576 KNGLOBUS 70.0 * 1 61.059.0 70 fbul34512 CARUTHRS 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore 70-kV Single Line Out

.

Wed Oct 08 10:06:44 2008

Page 4

2013sumpk_q272_pst_tr_hen-lemoore.chf

Page 654: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 3

59.00

59.50

60.00

60.50

61.00

59.0 230 fbus30881 HENRIETA 230.0 * 1 61.059.0 230 fbus30900 GATES 230.0 * 1 61.059.0 230 fbus30810 GREGG 230.0 * 1 61.059.0 230 fbus30875 MC CALL 230.0 * 1 61.059.0 230 fbus30790 PANOCHE 230.0 * 1 61.059.0 230 fbus30935 ARCO 230.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 4

59.00

59.50

60.00

60.50

61.00

59.0 115 fbus34430 HENRETTA 115.0 1 1 61.059.0 115 fbul34521 LEPRNOFD 115.0 1 1 61.059.0 115 fbul34429 GWF_HEP 115.0 1 1 61.059.0 115 fbul34428 CONTADNA 115.0 1 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore 70-kV Single Line Out

.

Wed Oct 08 10:06:44 2008

Page 5

2013sumpk_q272_pst_tr_hen-lemoore.chf

Page 655: To determine the system impacts caused by the Project

Generator Angles of Local Units

-180.00

-90.00

0.00

90.00

180.00

-180.0 #1 ang 34600 HELMS 1 18.0 * 1 180.0-180.0 GWF-PWR ang34650 GWF-PWR. 13.8 * 1 180.0-180.0 1 ang 34431 GWF_HEP1 13.8 * 1 180.0-180.0 2 ang 34433 GWF_HEP2 13.8 * 1 180.0-180.0 GT1 ang 34661 P0418GT1 13.8 * 1 180.0-180.0 Cogen ang34642 KINGSBUR 9.1 * 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta-Lemoore 70-kV Single Line Out

.

Wed Oct 08 10:06:44 2008

Page 6

2013sumpk_q272_pst_tr_hen-lemoore.chf

Page 656: To determine the system impacts caused by the Project

Three-phase close-in fault on the Henrietta 230/70-kV Transformer #2 at the Henrietta 70-kV bus with normal clearing time followed by the loss of the Henrietta 230/70-kV

Transformer #2.

Page 657: To determine the system impacts caused by the Project

Project Relative Rotor Angle

-180.00

-90.00

0.00

90.00

180.00

-180.0Q272_ST1 ang34691 Q272_ST1 13.8 1 1 180.0-180.0GWF_GT1 ang34539 GWF_GT1 13.8 1 1 180.0-180.0GWF_GT2 ang34541 GWF_GT2 13.8 3 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

Project Terminal Voltage

0.70

0.85

1.00

1.15

1.30

0.7 Q272_ST1 vt34691 Q272_ST1 13.8 1 1 1.30.7 GWF_GT1 vt34539 GWF_GT1 13.8 2 1 1.30.7 GWF_GT2 vt34541 GWF_GT2 13.8 3 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Project Rotor Speed

0.99

1.00

1.00

1.00

1.01

0.99 Q272_ST1 spd34691 Q272_ST1 13.8 1 1 1.010.99 GWF_GT1 spd34539 GWF_GT1 13.8 2 1 1.010.99 GWF_GT2 spd34541 GWF_GT2 13.8 3 1 1.01

Time( sec )0.0 20.05.0 10.0 15.0

Project Generation

0.00

25.00

50.00

75.00

100.00

0.0 Q272_ST1 pg34691 Q272_ST1 13.8 1 1 100.00.0 GWF_GT1 pg34539 GWF_GT1 13.8 2 1 100.00.0 GWF_GT2 pg34541 GWF_GT2 13.8 3 1 100.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#2

.

Wed Oct 08 10:24:17 2008

Page 1

2013sumpk_q272_pst_tr_HenBk#2.chf

Page 658: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 1

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34540 HENRITTA 70.0 * 1 1.30.7 70 vbul34544 TLRE LKE 70.0 * 1 1.30.7 70 vbul34542 JCBSCRNR 70.0 * 1 1.30.7 70 vbul34518 LEMOORE 70.0 * 1 1.30.7 70 vbul34516 LEPRINO 70.0 * 1 1.30.7 70 vbul34532 ARMSTRNG 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 2

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34460 GUERNSEY 70.0 * 1 1.30.7 70 vbul34534 RESERVE 70.0 * 1 1.30.7 70 vbul34514 MUSLSLGH 70.0 * 1 1.30.7 70 vbul34458 HARDWICK 70.0 * 1 1.30.7 70 vbus34576 KNGLOBUS 70.0 * 1 1.30.7 70 vbul34512 CARUTHRS 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#2

.

Wed Oct 08 10:24:17 2008

Page 2

2013sumpk_q272_pst_tr_HenBk#2.chf

Page 659: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 3

0.70

0.85

1.00

1.15

1.30

0.7 230 vbus30881 HENRIETA 230.0 * 1 1.30.7 230 vbus30900 GATES 230.0 * 1 1.30.7 230 vbus30810 GREGG 230.0 * 1 1.30.7 230 vbus30875 MC CALL 230.0 * 1 1.30.7 230 vbus30790 PANOCHE 230.0 * 1 1.30.7 230 vbus30935 ARCO 230.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 4

0.70

0.85

1.00

1.15

1.30

0.7 115 vbus34430 HENRETTA 115.0 * 1 1.30.7 115 vbul34521 LEPRNOFD 115.0 * 1 1.30.7 115 vbul34429 GWF_HEP 115.0 * 1 1.30.7 115 vbul34428 CONTADNA 115.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#2

.

Wed Oct 08 10:24:17 2008

Page 3

2013sumpk_q272_pst_tr_HenBk#2.chf

Page 660: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 1

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34540 HENRITTA 70.0 * 1 61.059.0 70 fbul34544 TLRE LKE 70.0 * 1 61.059.0 70 fbul34542 JCBSCRNR 70.0 * 1 61.059.0 70 fbul34518 LEMOORE 70.0 * 1 61.059.0 70 fbul34516 LEPRINO 70.0 * 1 61.059.0 70 fbul34532 ARMSTRNG 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 2

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34460 GUERNSEY 70.0 * 1 61.059.0 70 fbul34534 RESERVE 70.0 * 1 61.059.0 70 fbul34514 MUSLSLGH 70.0 * 1 61.059.0 70 fbul34458 HARDWICK 70.0 * 1 61.059.0 70 fbus34576 KNGLOBUS 70.0 * 1 61.059.0 70 fbul34512 CARUTHRS 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#2

.

Wed Oct 08 10:24:17 2008

Page 4

2013sumpk_q272_pst_tr_HenBk#2.chf

Page 661: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 3

59.00

59.50

60.00

60.50

61.00

59.0 230 fbus30881 HENRIETA 230.0 * 1 61.059.0 230 fbus30900 GATES 230.0 * 1 61.059.0 230 fbus30810 GREGG 230.0 * 1 61.059.0 230 fbus30875 MC CALL 230.0 * 1 61.059.0 230 fbus30790 PANOCHE 230.0 * 1 61.059.0 230 fbus30935 ARCO 230.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 4

59.00

59.50

60.00

60.50

61.00

59.0 115 fbus34430 HENRETTA 115.0 1 1 61.059.0 115 fbul34521 LEPRNOFD 115.0 1 1 61.059.0 115 fbul34429 GWF_HEP 115.0 1 1 61.059.0 115 fbul34428 CONTADNA 115.0 1 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#2

.

Wed Oct 08 10:24:18 2008

Page 5

2013sumpk_q272_pst_tr_HenBk#2.chf

Page 662: To determine the system impacts caused by the Project

Generator Angles of Local Units

-180.00

-90.00

0.00

90.00

180.00

-180.0 #1 ang 34600 HELMS 1 18.0 * 1 180.0-180.0 GWF-PWR ang34650 GWF-PWR. 13.8 * 1 180.0-180.0 1 ang 34431 GWF_HEP1 13.8 * 1 180.0-180.0 2 ang 34433 GWF_HEP2 13.8 * 1 180.0-180.0 GT1 ang 34661 P0418GT1 13.8 * 1 180.0-180.0 Cogen ang34642 KINGSBUR 9.1 * 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#2

.

Wed Oct 08 10:24:18 2008

Page 6

2013sumpk_q272_pst_tr_HenBk#2.chf

Page 663: To determine the system impacts caused by the Project

Three-phase close-in fault on the Henrietta 230/70-kV Transformer #4 at the Henrietta 70-kV bus with normal clearing time followed by the loss of the Henrietta 230/70-kV

Transformer #4.

Page 664: To determine the system impacts caused by the Project

Project Relative Rotor Angle

-180.00

-90.00

0.00

90.00

180.00

-180.0Q272_ST1 ang34691 Q272_ST1 13.8 1 1 180.0-180.0GWF_GT1 ang34539 GWF_GT1 13.8 1 1 180.0-180.0GWF_GT2 ang34541 GWF_GT2 13.8 3 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

Project Terminal Voltage

0.70

0.85

1.00

1.15

1.30

0.7 Q272_ST1 vt34691 Q272_ST1 13.8 1 1 1.30.7 GWF_GT1 vt34539 GWF_GT1 13.8 2 1 1.30.7 GWF_GT2 vt34541 GWF_GT2 13.8 3 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Project Rotor Speed

0.99

1.00

1.00

1.00

1.01

0.99 Q272_ST1 spd34691 Q272_ST1 13.8 1 1 1.010.99 GWF_GT1 spd34539 GWF_GT1 13.8 2 1 1.010.99 GWF_GT2 spd34541 GWF_GT2 13.8 3 1 1.01

Time( sec )0.0 20.05.0 10.0 15.0

Project Generation

0.00

25.00

50.00

75.00

100.00

0.0 Q272_ST1 pg34691 Q272_ST1 13.8 1 1 100.00.0 GWF_GT1 pg34539 GWF_GT1 13.8 2 1 100.00.0 GWF_GT2 pg34541 GWF_GT2 13.8 3 1 100.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#4

.

Wed Oct 08 10:15:29 2008

Page 1

2013sumpk_q272_pst_tr_HenBk#4.chf

Page 665: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 1

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34540 HENRITTA 70.0 * 1 1.30.7 70 vbul34544 TLRE LKE 70.0 * 1 1.30.7 70 vbul34542 JCBSCRNR 70.0 * 1 1.30.7 70 vbul34518 LEMOORE 70.0 * 1 1.30.7 70 vbul34516 LEPRINO 70.0 * 1 1.30.7 70 vbul34532 ARMSTRNG 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 2

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34460 GUERNSEY 70.0 * 1 1.30.7 70 vbul34534 RESERVE 70.0 * 1 1.30.7 70 vbul34514 MUSLSLGH 70.0 * 1 1.30.7 70 vbul34458 HARDWICK 70.0 * 1 1.30.7 70 vbus34576 KNGLOBUS 70.0 * 1 1.30.7 70 vbul34512 CARUTHRS 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#4

.

Wed Oct 08 10:15:29 2008

Page 2

2013sumpk_q272_pst_tr_HenBk#4.chf

Page 666: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 3

0.70

0.85

1.00

1.15

1.30

0.7 230 vbus30881 HENRIETA 230.0 * 1 1.30.7 230 vbus30900 GATES 230.0 * 1 1.30.7 230 vbus30810 GREGG 230.0 * 1 1.30.7 230 vbus30875 MC CALL 230.0 * 1 1.30.7 230 vbus30790 PANOCHE 230.0 * 1 1.30.7 230 vbus30935 ARCO 230.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 4

0.70

0.85

1.00

1.15

1.30

0.7 115 vbus34430 HENRETTA 115.0 * 1 1.30.7 115 vbul34521 LEPRNOFD 115.0 * 1 1.30.7 115 vbul34429 GWF_HEP 115.0 * 1 1.30.7 115 vbul34428 CONTADNA 115.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#4

.

Wed Oct 08 10:15:29 2008

Page 3

2013sumpk_q272_pst_tr_HenBk#4.chf

Page 667: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 1

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34540 HENRITTA 70.0 * 1 61.059.0 70 fbul34544 TLRE LKE 70.0 * 1 61.059.0 70 fbul34542 JCBSCRNR 70.0 * 1 61.059.0 70 fbul34518 LEMOORE 70.0 * 1 61.059.0 70 fbul34516 LEPRINO 70.0 * 1 61.059.0 70 fbul34532 ARMSTRNG 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 2

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34460 GUERNSEY 70.0 * 1 61.059.0 70 fbul34534 RESERVE 70.0 * 1 61.059.0 70 fbul34514 MUSLSLGH 70.0 * 1 61.059.0 70 fbul34458 HARDWICK 70.0 * 1 61.059.0 70 fbus34576 KNGLOBUS 70.0 * 1 61.059.0 70 fbul34512 CARUTHRS 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#4

.

Wed Oct 08 10:15:30 2008

Page 4

2013sumpk_q272_pst_tr_HenBk#4.chf

Page 668: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 3

59.00

59.50

60.00

60.50

61.00

59.0 230 fbus30881 HENRIETA 230.0 * 1 61.059.0 230 fbus30900 GATES 230.0 * 1 61.059.0 230 fbus30810 GREGG 230.0 * 1 61.059.0 230 fbus30875 MC CALL 230.0 * 1 61.059.0 230 fbus30790 PANOCHE 230.0 * 1 61.059.0 230 fbus30935 ARCO 230.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 4

59.00

59.50

60.00

60.50

61.00

59.0 115 fbus34430 HENRETTA 115.0 1 1 61.059.0 115 fbul34521 LEPRNOFD 115.0 1 1 61.059.0 115 fbul34429 GWF_HEP 115.0 1 1 61.059.0 115 fbul34428 CONTADNA 115.0 1 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#4

.

Wed Oct 08 10:15:30 2008

Page 5

2013sumpk_q272_pst_tr_HenBk#4.chf

Page 669: To determine the system impacts caused by the Project

Generator Angles of Local Units

-180.00

-90.00

0.00

90.00

180.00

-180.0 #1 ang 34600 HELMS 1 18.0 * 1 180.0-180.0 GWF-PWR ang34650 GWF-PWR. 13.8 * 1 180.0-180.0 1 ang 34431 GWF_HEP1 13.8 * 1 180.0-180.0 2 ang 34433 GWF_HEP2 13.8 * 1 180.0-180.0 GT1 ang 34661 P0418GT1 13.8 * 1 180.0-180.0 Cogen ang34642 KINGSBUR 9.1 * 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Post-Project CasePATH15= 1955 MW(S-N) PATH26= 4001 MW(N-S) PDCI= 2500 MW(N-S) COI= 4795 MW(N-S)Q272 150 MW at GWF Henrietta 70 kV IFS - 2013 Summer Peak Post-Project FYHenrietta 230/70-kV Bk#4

.

Wed Oct 08 10:15:30 2008

Page 6

2013sumpk_q272_pst_tr_HenBk#4.chf

Page 670: To determine the system impacts caused by the Project

Three-phase fault on the Gates-Gregg and Gates-McCall 230-kV lines at the Henrietta 230-kV bus with normal clearing time followed by the loss of the Gates-Gregg and

Gates-McCall 230-kV lines.

Page 671: To determine the system impacts caused by the Project

Project Relative Rotor Angle

-180.00

-90.00

0.00

90.00

180.00

-180.0Q272_ST1 ang34691 0.0 1 180.0-180.0GWF_GT1 ang34539 GWF_GT1 13.8 1 1 180.0-180.0GWF_GT2 ang34541 GWF_GT2 13.8 3 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

Project Terminal Voltage

0.70

0.85

1.00

1.15

1.30

0.7 Q272_ST1 vt34691 0.0 1 1.30.7 GWF_GT1 vt34539 GWF_GT1 13.8 2 1 1.30.7 GWF_GT2 vt34541 GWF_GT2 13.8 3 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Project Rotor Speed

0.99

1.00

1.00

1.00

1.01

0.99 Q272_ST1 spd34691 0.0 1 1.010.99 GWF_GT1 spd34539 GWF_GT1 13.8 2 1 1.010.99 GWF_GT2 spd34541 GWF_GT2 13.8 3 1 1.01

Time( sec )0.0 20.05.0 10.0 15.0

Project Generation

0.00

25.00

50.00

75.00

100.00

0.0 Q272_ST1 pg34691 0.0 1 100.00.0 GWF_GT1 pg34539 GWF_GT1 13.8 2 1 100.00.0 GWF_GT2 pg34541 GWF_GT2 13.8 3 1 100.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project CasePATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FYHenrietta 230-kV Bus Outage

.

Fri Oct 03 14:35:58 2008

Page 1

2013sumpk_q272_pre_tr_gts-gregg_mccall.chf

Page 672: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 1

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34540 HENRITTA 70.0 * 1 1.30.7 70 vbul34544 TLRE LKE 70.0 * 1 1.30.7 70 vbul34542 JCBSCRNR 70.0 * 1 1.30.7 70 vbul34518 LEMOORE 70.0 * 1 1.30.7 70 vbul34516 LEPRINO 70.0 * 1 1.30.7 70 vbul34532 ARMSTRNG 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 2

0.70

0.85

1.00

1.15

1.30

0.7 70 vbul34460 GUERNSEY 70.0 * 1 1.30.7 70 vbul34534 RESERVE 70.0 * 1 1.30.7 70 vbul34514 MUSLSLGH 70.0 * 1 1.30.7 70 vbul34458 HARDWICK 70.0 * 1 1.30.7 70 vbus34576 KNGLOBUS 70.0 * 1 1.30.7 70 vbul34512 CARUTHRS 70.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project CasePATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FYHenrietta 230-kV Bus Outage

.

Fri Oct 03 14:35:58 2008

Page 2

2013sumpk_q272_pre_tr_gts-gregg_mccall.chf

Page 673: To determine the system impacts caused by the Project

Bus Voltage Magnitude Group 3

0.70

0.85

1.00

1.15

1.30

0.7 230 vbus30881 HENRIETA 230.0 * 1 1.30.7 230 vbus30900 GATES 230.0 * 1 1.30.7 230 vbus30810 GREGG 230.0 * 1 1.30.7 230 vbus30875 MC CALL 230.0 * 1 1.30.7 230 vbus30790 PANOCHE 230.0 * 1 1.30.7 230 vbus30935 ARCO 230.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

Bus Voltage Magnitude Group 4

0.70

0.85

1.00

1.15

1.30

0.7 115 vbus34430 HENRETTA 115.0 * 1 1.30.7 115 vbul34521 LEPRNOFD 115.0 * 1 1.30.7 115 vbul34429 GWF_HEP 115.0 * 1 1.30.7 115 vbul34428 CONTADNA 115.0 * 1 1.3

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project CasePATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FYHenrietta 230-kV Bus Outage

.

Fri Oct 03 14:35:58 2008

Page 3

2013sumpk_q272_pre_tr_gts-gregg_mccall.chf

Page 674: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 1

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34540 HENRITTA 70.0 * 1 61.059.0 70 fbul34544 TLRE LKE 70.0 * 1 61.059.0 70 fbul34542 JCBSCRNR 70.0 * 1 61.059.0 70 fbul34518 LEMOORE 70.0 * 1 61.059.0 70 fbul34516 LEPRINO 70.0 * 1 61.059.0 70 fbul34532 ARMSTRNG 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 2

59.00

59.50

60.00

60.50

61.00

59.0 70 fbul34460 GUERNSEY 70.0 * 1 61.059.0 70 fbul34534 RESERVE 70.0 * 1 61.059.0 70 fbul34514 MUSLSLGH 70.0 * 1 61.059.0 70 fbul34458 HARDWICK 70.0 * 1 61.059.0 70 fbus34576 KNGLOBUS 70.0 * 1 61.059.0 70 fbul34512 CARUTHRS 70.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project CasePATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FYHenrietta 230-kV Bus Outage

.

Fri Oct 03 14:35:58 2008

Page 4

2013sumpk_q272_pre_tr_gts-gregg_mccall.chf

Page 675: To determine the system impacts caused by the Project

Bus Frequency Magnitude Group 3

59.00

59.50

60.00

60.50

61.00

59.0 230 fbus30881 HENRIETA 230.0 * 1 61.059.0 230 fbus30900 GATES 230.0 * 1 61.059.0 230 fbus30810 GREGG 230.0 * 1 61.059.0 230 fbus30875 MC CALL 230.0 * 1 61.059.0 230 fbus30790 PANOCHE 230.0 * 1 61.059.0 230 fbus30935 ARCO 230.0 * 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

Bus Frequency Magnitude Group 4

59.00

59.50

60.00

60.50

61.00

59.0 115 fbus34430 HENRETTA 115.0 1 1 61.059.0 115 fbul34521 LEPRNOFD 115.0 1 1 61.059.0 115 fbul34429 GWF_HEP 115.0 1 1 61.059.0 115 fbul34428 CONTADNA 115.0 1 1 61.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project CasePATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FYHenrietta 230-kV Bus Outage

.

Fri Oct 03 14:35:58 2008

Page 5

2013sumpk_q272_pre_tr_gts-gregg_mccall.chf

Page 676: To determine the system impacts caused by the Project

Generator Angles of Local Units

-180.00

-90.00

0.00

90.00

180.00

-180.0 #1 ang 34600 HELMS 1 18.0 * 1 180.0-180.0 GWF-PWR ang34650 GWF-PWR. 13.8 * 1 180.0-180.0 1 ang 34431 GWF_HEP1 13.8 * 1 180.0-180.0 2 ang 34433 GWF_HEP2 13.8 * 1 180.0-180.0 GT1 ang 34661 P0418GT1 13.8 * 1 180.0-180.0 Cogen ang34642 KINGSBUR 9.1 * 1 180.0

Time( sec )0.0 20.05.0 10.0 15.0

PG&E 2007 CASE SERIES: 2013 San Joaquin Valley Summer Peak Pre-Project CasePATH15= 1964 MW(S-N) PATH26= 3996 MW(N-S) PDCI= 2500 MW(N-S) COI= 4790 MW(N-S)Q272 150 MW GWF Henrietta 70 kV IFS - 2013 Summer Peak Pre-Project FYHenrietta 230-kV Bus Outage

.

Fri Oct 03 14:35:58 2008

Page 6

2013sumpk_q272_pre_tr_gts-gregg_mccall.chf

Page 677: To determine the system impacts caused by the Project

Appendix F Governor Machine Dynamic Data

Table of Content Machine Data for ST Unit........................................................................................................................... 1 Excitation Data for ST Unit: ....................................................................................................................... 2 Governor Data for ST Unit ......................................................................................................................... 3 PSS Data for ST Unit.................................................................................................................................... 5

Page 678: To determine the system impacts caused by the Project

F-1 GWF Henrietta SISAppendix F

Machine Data for ST Unit: Model: genrou

MVA S Base 31.93 Tpdo D-axis transient rotor time constant 7 Tppdo D-axis sub-transient rotor time constant 0.03 Tpqo Q-axis transient rotor time constant 0.75 Tppqo Q-axis sub-transient rotor time constant 0.05 H Inertia constant, sec 3 D Damping factor, pu 0 Ld D-axis synchronous reactance 2.1 Lq Q-axis synchronous reactance 2 Lpd D-axis transient reactance 0.2 Lpq Q-axis transient reactance 0.5 Lppd D-axis transient reactance 0.18 Ll Stator leakage reactance, pu 0.15 S1 Saturation factor at 1 pu flux 0.05 S12 Saturation factor at 1.2 pu flux 0.3 Ra Stator resistance, pu 0 Rcomp Compounding resistance for voltage control, pu 0 Xcomp Compounding reactance for voltage control, pu 0

Page 679: To determine the system impacts caused by the Project

F-2 GWF Henrietta SISAppendix F

Excitation Data for ST Unit: Model: exac1

Tr Filter time constant, sec. 0 Tb Time constant, sec. 1 Tc Time constant, sec. 1 Ka Voltage regulator gain 200 Ta Time constant, sec. 0.1

Vamax Maximum control element output, p.u. 7.5 Vamin Minimum control element output, p.u. -7.5

Te Exciter time constant, sec. 1 Kf Rate feedback gain, p.u. 0.03 Tf Rate feedback time constant, sec 1 Kc Rectifier regulation factor, p.u. 0.5 Kd Exciter internal reactance, p.u. 0.3 Ke Exciter field resistance constant, p.u. 1 E1 Field voltage value, 1 3

S(E1) Saturation factor at E1 0.03 E2 Field voltage value, 2 4

S(E2) Saturation factor at E2 0.1 Vrmax Voltage regulator maximum output,

p.u. 7.5

Vrmin Voltage regulator minimum output, p.u.

-7.5

Page 680: To determine the system impacts caused by the Project

F-3 GWF Henrietta SISAppendix F

Governor Data for ST Unit: Model: ggov1

r Permanent droop, p.u. 0.04 rselect Feedback signal for droop 1 Tpelec Electrical power transducer time constant,

sec. 1.0

maxerr Maximum value for speed error signal 0.05 minerr Minimum value for speed error signal -0.05 Kpgov Governor proportional gain 10.0 Kigov Governor integral gain 2.0 Kdgov Governor derivative gain 0.0 Tdgov Governor derivative controller time

constant 1.0

vmax Maximum valve position limit 1.0 vmin Minimum valve position limit 0.15 Tact Actuator time constant 0.5

Kturb Turbine gain 1.5 wfnl No load fuel flow, p.u 0.2 Tb Turbine lag time constant 0.5

Page 681: To determine the system impacts caused by the Project

F-4 GWF Henrietta SISAppendix F

Tc Turbine lead time constant 0.0 Flag Switch for fuel source characteristic 1.0 Teng Transport lag time constant for diesel

engine 0.0

Tfload Load Limiter time constant 3.0 Kpload Load limiter proportional gain for PI

controller 2.0

Kiload Load limiter integral gain for PI controller 0.67 Ldref Load limiter reference value p.u. 1.0 Dm Speed sensitivity coefficient, p.u. 0.0

ropen Maximum valve opening rate, p.u./sec. .10 rclose Minimum valve closing rate, p.u./sec. -0.1 Kimw Power controller (reset) gain 0.002

Pmwset Power controller setpoint, MW 80.0 aset Acceleration limiter setpoint, p.u./sec. 0.01 Ka Acceleration limiter Gain 10.0 Ta Acceleration limiter time constant, sec. 0.1 db Speed governor dead band 0.0 Tsa Temperature detection lead time constant,

sec. 4.0

Tsb Temperature detection lag time constant, sec.

5.0

rup Maximum rate of load limit increase 99.0 rdown Maximum rate of load limit decrease -99.0

Page 682: To determine the system impacts caused by the Project

F-5 GWF Henrietta SISAppendix F

PSS Data for ST Unit: Model: pss2a

J1 Input signal #1 code 1K1 Input signal #1 remote bus number 0J2 Input signal #2 code 3K2 Input signal #2 remote bus number 0

Tw1 First washout on signal #1, sec. 2Tw2 Second washout on signal #1, sec. 2Tw3 First washout on signal #2, sec. 2Tw4 Second washout on signal #2, sec. 0T6 Time constant on signal #1, sec. 0T7 Time constant on signal #2, sec. 2Ks2 Gain on signal #2 0.2Ks3 Gain on signal #2 1Ks4 Gain on signal #2 1T8 Lead of ramp tracking filter 0.5T9 Lag of ramp tracking filter 0.1n Order of ramp tracking filter 1m Order of ramp tracking filter 5

Ks1 Stabilizer gain 10T1 Lead/lag time constant, sec. 0.25T2 Lead/lag time constant, sec. 0.04T3 Lead/lag time constant, sec. 0.20T4 Lead/lag time constant, sec. 0.03

Vstmax Stabilizer output max limit, p.u. 0.1Vstmin Stabilizer output min limit, p.u. -0.1