t MEDIC Rack MountAssembly Instructions
Overview
Introduction This guide contains a description of the parts and tools required tosuccessfully assemble the FARADAY
TM t MEDIC rack mount (referred to as
tMEDIC in this document), as well as procedures on how to safely assemble,
mount, and ground the rack and cabinet.
In This
DocumentThis document contains the following topics:
Stage Description See Page
1. Gather the required tools and equipment 2
2. Open the box, inspect and account for all the parts 3
3. Assemble the rack 44. Determine a suitable installation location 6
5. Secure the rack to the installation location 7
6. Mount tMEDIC to the rack 8
7. Ground the tMEDIC and rack 10
994-0034-2.00-2 General, Full Release
© 2002, General Electric Canada, Inc. All rights reserved.
The contents of this manual are the property of General Electric Canada, Inc. No part of this work may be reproduced or transmitted
in any form or by any means, except as permitted in written license agreement with General Electric Canada, Inc. General Electric Canada,
Inc. has made every reasonable attempt to ensure the completeness and accuracy of this document. However, the information contained in this
manual is subject to change without notice, and does not represent a commitment on the part of General Electric Canada, Inc.
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 2/11
GE Energy Services
FARADAY tMEDIC Rack Mount
Assembly Instructions
994-0034 2.00 2 General
2 Full Release
Required Tools
Tools for the
JobBefore beginning the installation procedure, you require the following tools
and equipment.
Tools List Gather the following:
• Open-Ended Wrenches
• Adjustable Wrench
• Drill Motor
• Concrete Drill Bits
• A Heavy Lifting Device (for example, crane, forklift, pallet jack)
• Wire Cutters
• Wire Strippers
• Sledgehammer
• An assortment of ½ inch nuts and bolts
Suitable
Mounting
Location
The rack installation requires space on a mounting surface located near the
transformer (for example, on the transformer’s concrete pad, or on a concrete
pad poured specifically for the rack).
Build a New
PadPour a suitable concrete mounting pad if one does not already exist.
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 3/11
FARADAY tMEDIC Rack Mount
Assembly Instructions GE Energy Services
General 994-0034-2.00-2
Full Release 3
Parts List
Parts
DescriptionOpen the rack mount box and ensure it contains the following parts:
Part Name Description Quantity
Installation
Instructions
This document. 1
Rack Legs The rack’s vertical support structures. 2
Cross Beams Connect the rack legs and provide a mountingsurface for the tMEDIC.
2
(A) Connecting
Bolts
3/8 x 1-inch bolts (use with (A) locking nuts and
(A) flat washers) to secure cross beams to rack legs.
8
(A) Locking Nuts
Use with the (A) connecting bolts. 8
(A) Flat Washers Use with the (A) connecting bolts. 8
½ x 1-inch bolts (use with (B) flat washers and (B)
lock washers) to hang and secure tMEDIC to the
cross beams. Nuts are welded to the back of thecross beam.
4(B) Bolts
½ x 1-inch bolts (use with (B) flat washers and (B)
lock washers) to secure the cabinet to the concrete
pad.
6
(B) Flat Washers Use with the (B) bolts. 10
(B) Lock
Washers
Use with the (B) bolts. 10
Leveling Shims For leveling the rack assembly. 6
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 4/11
GE Energy Services
FARADAY tMEDIC Rack Mount
Assembly Instructions
994-0034 2.00 2 General
4 Full Release
Assembling the Rack
Rack Leg
OrientationYou can orient the rack legs to suit the available space at your location.
Example: The following top-view drawing illustrates the conventional rack
leg orientation with the legs pointing forward. You can reverse the position of one or both rack legs if it suits your installation.
Keep the Rack
SquareTo prevent the cabinet from twisting when mounting it to the rack, ensure the
rack legs are parallel to each other, and perpendicular to the mounting
surface. A square rack prevents tMEDIC from twisting when mounted.
Procedure The following procedure explains how to assemble the rack in a conventionalfashion (with the rack legs pointing forward):
Step Action
1 Move the box and tools near the area where you will install the rack.
2 Open the box and remove all the parts.
Continued on next page
Front of Rack
Rear of Rack
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 5/11
FARADAY tMEDIC Rack Mount
Assembly Instructions GE Energy Services
General 994-0034-2.00-2
Full Release 5
Assembling the Rack, Continued
Procedure (continued)
3 Attach the cross beams to the rack legs using the (A) 3/8 inch connecting bolts, (A) flat washers, and (A) locking nuts. Leave all bolts hand-tight.
4 Make sure the rack is level and square (for example, use a carpenter’s
square or measure from corner to corner), and tighten all the bolts.
5 Attach cabinet mounting (B) bolts (with washers and lock washers) to
the inner holes on the upper cross beam. These bolts are the cabinet
mounting points. Only install them hand-tight.
Warning: Do not hang tMEDIC yet.
Upper Cross Beam,
Inner Hole
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 6/11
GE Energy Services
FARADAY tMEDIC Rack Mount
Assembly Instructions
994-0034 2.00 2 General
6 Full Release
Finding a Suitable Installation Location
Introduction After the installers assemble the rack, the system engineer must locate a
suitable installation spot.
Guidelines Use the following guidelines to locate a suitable location to install the rack:
• Install the rack on a secure base (for example, a concrete pad)
• Keep in mind the eventual location of the sensors, and keep the length of wiring
conduit to a minimum
• Position the rack on the shady side of the transformer whenever possible
• Ensure there is a suitable location to install a grounding rod (there must be an
open piece of earth nearby into which you can drive a grounding rod)
• Do not block other equipment (for example, drain valves, fans, or other
transformer equipment)
•
Do not mount the rack in the exhaust path of a cooling fan or any other devicethat could adversely affect tMEDIC’s thermal characteristics
• Ensure there is enough clearance in front of the rack to mount tMEDIC so the
cabinet door can fully open.
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 7/11
FARADAY tMEDIC Rack Mount
Assembly Instructions GE Energy Services
General 994-0034-2.00-2
Full Release 7
Securing the Rack
Introduction The installers move the rack to the selected location near the transformer,
level it, and secure it to the concrete pad.
Procedure To secure the rack:
Step Action
1 Move the assembled rack to the concrete pad.
2 Prepare the concrete pad for rack installation. You may use either the
mounting holes in the rack legs as guides, or the measurements indicted
in the following “top view” diagram.
Note The following measurements are in inches, and the drawing is
not to scale.
3 Level the rack (use the supplied shims, stacked if necessary) so the rack
legs are parallel to each other and perpendicular to the mounting surface.
4 Secure the rack to the mounting surface. GE Energy Services
recommends using all mounting holes to secure the rack assembly.
0.675 dia.
40.74
Front of Rack
Rear of Rack
3.00
3.00
13.00
12.00
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 8/11
GE Energy Services
FARADAY tMEDIC Rack Mount
Assembly Instructions
994-0034 2.00 2 General
8 Full Release
Mounting tMEDIC
Caution tMEDIC is very heavy (300+ lbs/140+ kg). Lifting the cabinet into place on
the rack requires the use of a crane, forklift, pallet jack, or other heavy lifting
equipment.
Procedure To mount tMEDIC:
Step Action
1 Position the cabinet in front of the rack.
2 Secure lifting straps or cables through the four eyebolts on the top of
tMEDIC.
Warning: Do not lift the cabinet by the keyhole flange.
3 Use the appropriate device to lift the cabinet so the mounting bolts on
the upper cross beam are level with the keyhole on the cabinet’s
mounting flange.
4 Move the cabinet towards the rack until the mounting bolts protrude
through the keyholes.
5 Lower the cabinet until it hangs securely from the mounting bolts. Leave
the bolts snug, but not tight.
Warning: Keep the lifting device in place until the all the mounting bolts
are tightened.
Continued on next page
Keyhole Flange
Eyebolt
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 9/11
FARADAY tMEDIC Rack Mount
Assembly Instructions GE Energy Services
General 994-0034-2.00-2
Full Release 9
Mounting tMEDIC, Continued
Procedure (continued)
Step Action
6 Secure the cabinet’s lower flanges to the cross beam using the (B)
connecting bolts, lock washers, and flat washers. Leave the bolts snug,
but not tight.
7 Inspect the cabinet to ensure that:
• it is not twisted
• the front door is square to the cabinet
• the door opens easily.
If the front door does not open easily, add shims under the rack legs to
level the rack.
8 Tighten all the cabinet mounting bolts when you are certain the cabinet
is square on the rack.
Lower Flange
8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2
http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 10/11
GE Energy Services
FARADAY tMEDIC Rack Mount
Assembly Instructions
994-0034 2.00 2 General
10 Full Release
Grounding tMEDIC
Introduction Ensure the cabinet is properly grounded before starting any other installation
procedures. Grounding prevents nearby power sources such as transformers
and other electrical equipment from damaging the cabinet’s components.
Definition All components inside the cabinet ground to the copper rod on the back, left-hand side of the cabinet. The copper rod is wired to a stud that protrudes from
the side of tMEDIC.
Procedure To ground tMEDIC:
Step Action
1 Ground tMEDIC by connecting a wire from the grounding stud (located
on the lower left side of tMEDIC) to the main tank-grounding pad.
2 Refer to the Site Specific Manuals for grounding information.
Grounding Stud
Transformer
Grounding CableMain Tank
Grounding Pad