 t MEDIC Rack MountAssembly Instructions

Overview

Introduction This guide contains a description of the parts and tools required tosuccessfully assemble the FARADAY

TM t MEDIC rack mount (referred to as

tMEDIC in this document), as well as procedures on how to safely assemble,

mount, and ground the rack and cabinet.

In This

DocumentThis document contains the following topics:

Stage Description See Page

1. Gather the required tools and equipment 2

2. Open the box, inspect and account for all the parts 3

3. Assemble the rack 44. Determine a suitable installation location 6

5. Secure the rack to the installation location 7

6. Mount tMEDIC to the rack 8

7. Ground the tMEDIC and rack 10

994-0034-2.00-2  General,  Full Release 

© 2002, General Electric Canada, Inc. All rights reserved.

The contents of this manual are the property of General Electric Canada, Inc. No part of this work may be reproduced or transmitted

in any form or by any means, except as permitted in written license agreement with General Electric Canada, Inc. General Electric Canada,

 Inc. has made every reasonable attempt to ensure the completeness and accuracy of this document. However, the information contained in this

manual is subject to change without notice, and does not represent a commitment on the part of General Electric Canada, Inc.

Page 2: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 2/11

GE Energy Services

FARADAY tMEDIC Rack Mount

Assembly Instructions

994-0034 2.00 2 General

2 Full Release

Required Tools 

Tools for the

JobBefore beginning the installation procedure, you require the following tools

and equipment.

Tools List Gather the following:

• Open-Ended Wrenches

• Adjustable Wrench

• Drill Motor

• Concrete Drill Bits

• A Heavy Lifting Device (for example, crane, forklift, pallet jack)

• Wire Cutters

• Wire Strippers

• Sledgehammer

• An assortment of ½ inch nuts and bolts

Suitable

Mounting

Location

The rack installation requires space on a mounting surface located near the

transformer (for example, on the transformer’s concrete pad, or on a concrete

 pad poured specifically for the rack).

Build a New

PadPour a suitable concrete mounting pad if one does not already exist.

Page 3: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 3/11

FARADAY tMEDIC Rack Mount

Assembly Instructions GE Energy Services

General 994-0034-2.00-2

Full Release 3 

Parts List

Parts

DescriptionOpen the rack mount box and ensure it contains the following parts:

Part Name Description Quantity

Installation

Instructions

This document. 1

Rack Legs The rack’s vertical support structures. 2

Cross Beams Connect the rack legs and provide a mountingsurface for the tMEDIC.

2

(A) Connecting

Bolts

3/8 x 1-inch bolts (use with (A) locking nuts and

(A) flat washers) to secure cross beams to rack legs.

8

(A) Locking Nuts

Use with the (A) connecting bolts. 8

(A) Flat Washers Use with the (A) connecting bolts. 8

½ x 1-inch bolts (use with (B) flat washers and (B)

lock washers) to hang and secure tMEDIC to the

cross beams. Nuts are welded to the back of thecross beam.

4(B) Bolts

½ x 1-inch bolts (use with (B) flat washers and (B)

lock washers) to secure the cabinet to the concrete

 pad.

6

(B) Flat Washers Use with the (B) bolts. 10

(B) Lock

Washers

Use with the (B) bolts. 10

Leveling Shims For leveling the rack assembly. 6

Page 4: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 4/11

GE Energy Services

FARADAY tMEDIC Rack Mount

Assembly Instructions

994-0034 2.00 2 General

4 Full Release

Assembling the Rack

Rack Leg

OrientationYou can orient the rack legs to suit the available space at your location.

Example: The following top-view drawing illustrates the conventional rack

leg orientation with the legs pointing forward. You can reverse the position of one or both rack legs if it suits your installation.

Keep the Rack

SquareTo prevent the cabinet from twisting when mounting it to the rack, ensure the

rack legs are parallel to each other, and perpendicular to the mounting

surface. A square rack prevents tMEDIC from twisting when mounted.

Procedure The following procedure explains how to assemble the rack in a conventionalfashion (with the rack legs pointing forward):

Step Action

1 Move the box and tools near the area where you will install the rack.

2 Open the box and remove all the parts.

Continued on next page

Front of Rack

Rear of Rack 

Page 5: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 5/11

FARADAY tMEDIC Rack Mount

Assembly Instructions GE Energy Services

General 994-0034-2.00-2

Full Release 5 

Assembling the Rack, Continued

Procedure (continued)

3 Attach the cross beams to the rack legs using the (A) 3/8 inch connecting bolts, (A) flat washers, and (A) locking nuts. Leave all bolts hand-tight.

4 Make sure the rack is level and square (for example, use a carpenter’s

square or measure from corner to corner), and tighten all the bolts.

5 Attach cabinet mounting (B) bolts (with washers and lock washers) to

the inner holes on the upper cross beam. These bolts are the cabinet

mounting points. Only install them hand-tight.

Warning: Do not hang tMEDIC yet. 

Upper Cross Beam,

Inner Hole

Page 6: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 6/11

GE Energy Services

FARADAY tMEDIC Rack Mount

Assembly Instructions

994-0034 2.00 2 General

6 Full Release

Finding a Suitable Installation Location

Introduction After the installers assemble the rack, the system engineer must locate a

suitable installation spot.

Guidelines Use the following guidelines to locate a suitable location to install the rack:

• Install the rack on a secure base (for example, a concrete pad)

• Keep in mind the eventual location of the sensors, and keep the length of wiring

conduit to a minimum

• Position the rack on the shady side of the transformer whenever possible

• Ensure there is a suitable location to install a grounding rod (there must be an

open piece of earth nearby into which you can drive a grounding rod)

• Do not block other equipment (for example, drain valves, fans, or other

transformer equipment)

Do not mount the rack in the exhaust path of a cooling fan or any other devicethat could adversely affect tMEDIC’s thermal characteristics

• Ensure there is enough clearance in front of the rack to mount tMEDIC so the

cabinet door can fully open.

Page 7: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 7/11

FARADAY tMEDIC Rack Mount

Assembly Instructions GE Energy Services

General 994-0034-2.00-2

Full Release 7  

Securing the Rack

Introduction The installers move the rack to the selected location near the transformer,

level it, and secure it to the concrete pad.

Procedure To secure the rack:

Step Action

1 Move the assembled rack to the concrete pad.

2 Prepare the concrete pad for rack installation. You may use either the

mounting holes in the rack legs as guides, or the measurements indicted

in the following “top view” diagram.

Note The following measurements are in inches, and the drawing is

not to scale.

3 Level the rack (use the supplied shims, stacked if necessary) so the rack

legs are parallel to each other and perpendicular to the mounting surface.

4 Secure the rack to the mounting surface. GE Energy Services

recommends using all mounting holes to secure the rack assembly.

0.675 dia.

40.74

Front of Rack

Rear of Rack

3.00

3.00

13.00

12.00

Page 8: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 8/11

GE Energy Services

FARADAY tMEDIC Rack Mount

Assembly Instructions

994-0034 2.00 2 General

8 Full Release

Mounting tMEDIC

Caution tMEDIC is very heavy (300+ lbs/140+ kg). Lifting the cabinet into place on

the rack requires the use of a crane, forklift, pallet jack, or other heavy lifting

equipment.

Procedure To mount tMEDIC:

Step Action

1 Position the cabinet in front of the rack.

2 Secure lifting straps or cables through the four eyebolts on the top of

tMEDIC.

Warning: Do not lift the cabinet by the keyhole flange.

3 Use the appropriate device to lift the cabinet so the mounting bolts on

the upper cross beam are level with the keyhole on the cabinet’s

mounting flange.

4 Move the cabinet towards the rack until the mounting bolts protrude

through the keyholes.

5 Lower the cabinet until it hangs securely from the mounting bolts. Leave

the bolts snug, but not tight.

Warning: Keep the lifting device in place until the all the mounting bolts

are tightened.

Continued on next page

Keyhole Flange

Eyebolt

Page 9: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 9/11

FARADAY tMEDIC Rack Mount

Assembly Instructions GE Energy Services

General 994-0034-2.00-2

Full Release 9 

Mounting tMEDIC, Continued

Procedure (continued)

Step Action

6 Secure the cabinet’s lower flanges to the cross beam using the (B)

connecting bolts, lock washers, and flat washers. Leave the bolts snug,

 but not tight.

7 Inspect the cabinet to ensure that:

• it is not twisted

• the front door is square to the cabinet

• the door opens easily.

If the front door does not open easily, add shims under the rack legs to

level the rack.

8 Tighten all the cabinet mounting bolts when you are certain the cabinet

is square on the rack.

Lower Flange

Page 10: TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

8/10/2019 TMEDIC Rack Mount Assy Inst Ver 2.00 Rev 2

http://slidepdf.com/reader/full/tmedic-rack-mount-assy-inst-ver-200-rev-2 10/11

GE Energy Services

FARADAY tMEDIC Rack Mount

Assembly Instructions

994-0034 2.00 2 General

10 Full Release

Grounding tMEDIC

Introduction Ensure the cabinet is properly grounded before starting any other installation

 procedures. Grounding prevents nearby power sources such as transformers

and other electrical equipment from damaging the cabinet’s components.

Definition All components inside the cabinet ground to the copper rod on the back, left-hand side of the cabinet. The copper rod is wired to a stud that protrudes from

the side of tMEDIC.

Procedure To ground tMEDIC:

Step Action

1 Ground tMEDIC by connecting a wire from the grounding stud (located

on the lower left side of tMEDIC) to the main tank-grounding pad.

2 Refer to the Site Specific Manuals for grounding information.

Grounding Stud

Transformer 

Grounding CableMain Tank

Grounding Pad