Three-phase pollution test of diamond-shaped “suspension” insulator arrangement

for T-pylon tower

Page 2: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

2

Background and goal• The National Grid isplanning for the new 400kV overhead line with T-pylon towers

• Dielectric (lightning andswitching overvoltages)and ice performanceperformed by STRI

• Goal of this paper:verification of pollutionperformance

• Full-scale three-phasetest to be developed

Page 3: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

3

Challenges

• No IEC test for polymeric(composite) insulators

• No test for three-phasearrangement

• No IEC test for thesimulation of recovery ofhydrophobicity

Page 4: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

4

Methodology-1: principles of IEC 60507 (solid layer)

Page 5: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

5

Methodology-2: principles of CIGRE TB 555

Page 6: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

6

Methodology-3: full-scale three-phase tests from 3 single phase transformers

Page 7: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

7

High repeatability in pollution parameters

Page 8: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

8

High repeatability in leakage current parameters

Page 9: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

Practical summary

9

• Unique three phase full-scalepollution test for the complicatedgeometrical structure for 420 kVOHL equipped with compositeinsulators with hydrophobic surfacehas been successfully developed.

• Target pollution level withstood fortwo structures (no flashovers).

Page 10: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

Scientific summary

10

• The test is applicable for complicatedgeometrical structures.

• The test is repeatable.• Reported to CIGRE within workinggroup D1.44

• Verified at different configuration.

Page 11: Three-phase pollution test of diamond- shaped … 10.1 Igor_Gutman.pdfThree-phase pollution test of diamond-shaped “suspension” insulator arrangement for T-pylon tower 2 Background

Thank You!