This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
Notice
The 2012 edition of the Uniform Plumbing Code is developed through a consensus standards development processapproved by the American National Standards Institute. This process brings together volunteers representing variedviewpoints and interests to achieve consensus on plumbing issues. While the International Association of Plumbing andMechanical Officials (IAPMO) administers the process and establishes rules to promote fairness in the development ofconsensus, it does not independently test, evaluate, or verify the accuracy of any information or the soundness of anyjudgments contained in its codes and standards.
IAPMO disclaims liability for any personal injury, property, or other damages of any nature whatsoever, whetherspecial, indirect, consequential, or compensatory, directly or indirectly resulting from the publication, use of, or reliance onthis document. IAPMO also makes no guaranty or warranty as to the accuracy or completeness of any information publishedherein.
In issuing and making this document available, IAPMO is not undertaking to render professional or other services for oron behalf of any person or entity. Nor is IAPMO undertaking to perform any duty owed by any person or entity to someoneelse. Anyone using this document should rely on his or her own independent judgment or, as appropriate, seek the advice ofa competent professional in determining the exercise of reasonable care in any given circumstances.
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
2012 UNIFORM PLUMBINGCODE®
An American National StandardIAPMO/ANSI UPC 1-2012
®
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
Copyright © 2012by
International Association of Plumbing and Mechanical OfficialsAll Rights Reserved
No part of this work may be reproduced or recorded in any form or by any means,except as may be expressly permitted in writing by the publisher.
Twenty-Sixth Edition
First Printing, January 2012Second Printing, August 2012Third Printing, January 2013Fourth Printing, March 2013Fifth Printing, August 2013Sixth Printing, July 2014
Seventh Printing, January 2015Eighth Printing, July 2015
ISSN 0733-2335Published by the International Association of Plumbing and Mechanical Officials
4755 E. Philadelphia Street • Ontario, CA 91761-2816 – USAMain Phone: (909) 472-4100 • Main Fax: (909) 472-4150
REVISION MARKINGS
Solid vertical lines in the margins indicate a technical change from the requirements of the 2009 edition.Where a section, paragraph or table has been revised or relocated within the code, a solid vertical lineappears next to the section number and title.
An arrow in the margin indicates where an entire section, paragraph, or table has been deleted.
A reference in brackets [ ] following a section or paragraph indicates material that has been extracted fromanother document. This reprinted material is not the complete and official position of the source documenton the reference subject which is represented by the standard in its entirety. Text which has been extractedpursuant to IAPMO’s Extract Guidelines is denoted with the use of the source document in the margin. Thistext has not been fully processed by IAPMO in accordance with ANSI’s public announcement consensusrequirements for an American National Standard (ANS) nor approved by ANSI’s Board of StandardsReview, but will be fully processed in accordance with those requirements as part of the next revision cyclefor this document.
Information on referenced publications can be found in Chapter 14.
All pressures used in this code are gauge pressures unless otherwise indicated.
NFPANFPANFPANFPANFPANFPANFPANFPANFPANFPANFPANFPANFPANFPANFPA
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
2012 UPC Foreword
The advantages of a uniform plumbing code adopted by various local jurisdictions have long been recognized. Disorder inthe industry as a result of widely divergent plumbing practices and the use of many different, often conflicting, plumbingcodes by local jurisdictions influenced the Western Plumbing Officials Association (now the International Association ofPlumbing and Mechanical Officials [IAPMO]) to form a committee of plumbing inspectors, master and journeymanplumbers, and sanitary and mechanical engineers, assisted by public utility companies and the plumbing industry to create abasic plumbing document for general use. The product of this effort, the first edition of the Uniform Plumbing Code™(UPC™) was officially adopted by IAPMO in 1945. The widespread use of this code over the past five decades byjurisdictions throughout the United States and internationally is testament to its merit.
With the publication of the 2003 Edition of the Uniform Plumbing Code, another significant milestone was reached. For thefirst time in the history of the United States, a plumbing code was developed through a true consensus process. The 2012edition represents the most current approaches in the plumbing field and is the fourth edition developed under the ANSIconsensus process. Contributions to the content of the code were made by every segment of the built industry, includingsuch diverse interests as consumers, enforcing authorities, installers/maintainers, labor, manufacturers, research/standards/testinglaboratories, special experts, and users.
The UPC is designed to provide consumers with safe and sanitary plumbing systems while, at the same time, allowinglatitude for innovation and new technologies. The public at large is encouraged and invited to participate in IAPMO’s openconsensus code development process. This code is updated every three years. A code development timeline and otherrelevant information is available at IAPMO’s website at www.iapmo.org.
The Uniform Plumbing Code is dedicated to all those who, in working to achieve “the ultimate plumbing code,” haveunselfishly devoted their time, effort, and personal funds to create and maintain this, the finest plumbing code in existencetoday.
The 2012 Uniform Plumbing Code is supported by the American Society of Sanitary Engineering (ASSE), the MechanicalContractors Association of America (MCAA), the Plumbing-Heating-Cooling Contractors National Association (PHCC-NA), the United Association (UA), and the World Plumbing Council (WPC). The presence of these logos, while reflectingsupport, does not imply any ownership of the copyright to the UPC, which is held exclusively by IAPMO. Further, the logosof these associations indicates the support of IAPMO’s open, consensus process being used to develop IAPMO’s codes andstandards.
The addresses of the organizations are as follows:ASSE – 901 Canterbury Road, Suite A • Westlake, OH 44145-7201 • (440) 835-3040MCAA – 1385 Piccard Drive • Rockville, MD 20850 • (301) 869-5800PHCC-NA – PO Box 6808 • Falls Church, VA 22046 • (800) 533-7694UA – Three Park Place • Annapolis, MD 21401 • (410) 269-2000WPC – World Plumbing Council Secretariat
P.O. Box 810 • Lafayette, IN 47902, USA
v
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
vi
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
COMMITTEE ON UNIFORM PLUMBING CODEThese lists represent the membership at the time the Committee was balloted on the final text of this edition. Since that time, changes in the membership may have occurred.
Rand Ackroyd, Plumbing and Drainage Institute [M]Bob Adler, City of San Jose, California [E]Sarah Aguilar, Southland Industries [I/M]Julius Ballanco, American Society of Plumbing Engineers [SE]Denise Beach, NFPA [R/S/T]Sylvanus Bloice, Roots Plumbing Services [I/M]Jeremy Brown, NSF International [R/S/T]Dan Buuck, National Association of Home Builders [U]Paul Cabot, American Gas Association [U]Maggie Carroll, Underwriters Laboratories [R/S/T]Ian Chang, Intertek Testing Services [R/S/T]Richard Church, Plastic Pipe and Fittings Association [M]Rickey Fabra, Plumbers & Steamfitters [L]Pennie Feehan, Copper Development Association [M]
John Fischer, County of St. Louis [E]James Galvin, Plumbing Manufacturers International [M]Scott Hamilton, United Association [L]William LeVan, Cast Iron Soil Pipe Institute [M]David L. Mann, Plumbers & Steamfitters Local 342 [L]Thomas Pape, Alliance for Water Efficiency (AWE) [C]Arnold Rodio, Jr., Pace Setter Plumbing [I/M]Anthony Scarano, Plastics Piping Consultant [SE]Larry Soskin, Ace Duraflo [I/M]Jim Stack, Plumbing-Heating-Cooling Contractors National
Association [I/M]Amir Tabakh, City of Los Angeles - Department of Water and Power [E]April Trafton, Donald Dickerson Associates [SE]Steven Weinberger,MCAA [I/M]
AlternatesDJ Berger, Plumbers and Steamfitters [L]Lawrence Brown, National Association of Home Builders [U]Mark Casey, City of Los Angeles - Department of Building and Safety [E]Marty Cooper, City of Foster City, California [E]Michael Cudahy, Plastic Pipe and Fittings Association [M]James Dingman, Underwriters Laboratories [R/S/T]
Nasrin Kashefi, NSF International [R/S/T]Jim Kendzel, American Society of Plumbing Engineers [SE]Martin Salberg, United Association Local [L]James Pavesic, United Association [L]Arnold Rodio, Sr., Pace Setter Plumbing [I/M]James Walls, Cast Iron Soil Pipe Institute [M]
Dan Daniels, Ex-Officio, IAPMO [E] Matt Sigler, IAPMO Staff Liaison
Nonvoting
COMMITTEE MEMBERSHIP CLASSIFICATION ABBREVIATIONSThese classifications apply to Technical Committee members and represent their principal interest in the activity of a committee.
M Manufacturer: A representative of a maker or marketer of a product, assembly or system, or portion thereof, that is affected by the standard.U User: A representative of an entity that is subject to the provisions of the standard or that voluntarily uses the standard.I/M Installer/Maintainer: A representative of an entity that is in the business of installing or maintaining a product, assembly or system affected by the
standard.L Labor: A labor representative or employee concerned with safety in the workplace.R/S/T Research/Standards/Testing Laboratory: A representative of an independent research organization; an organization that develops codes, standards or
other similar documents; or an independent testing laboratory.E Enforcing Authority: A representative or an agency or an organization that promulgates and/or enforces standards.C Consumer: A person who is, or represents, the ultimate purchaser of a product, system, or service affected by the standard, but who is not included
in the User classification.SE Special Expert: A person not representing any of the previous classifications, but who has special expertise in the scope of the standard or portion
thereof.
IAPMO Standards Council
Tim Brink, Mechanical Contractors Association of Eastern PA [SE]Bob Courtnier, State of California [U]Rex Crawford, City of Lincoln [E]Ron George, Ron George Design & Consulting Services [SE]
Linden Raimer, Consultant [U]Phil Ribbs, PHR Consultants [SE]Kurt Steenhoek, Local Union 3 [L]Kevin Tindall, Tindall & Ranson Plumbing, Heating & A/C, Inc. [SE]
vii
Terry Swisher, ChairmanState of Oregon, [E]
Tim Collings, ChairmanSalt Lake City, Utah [E]
Gabriella M. Davis, SecretaryInternational Association of Plumbing and Mechanical Officials
Lynne Simnick, Recording SecretaryInternational Association of Plumbing and Mechanical Officials
Nonvoting
IAPMO Uniform Plumbing Code Technical Committee
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
FORM FOR PROPOSALS ON IAPMO UPC/UMC COMMITTEE DOCUMENTSNOTE: All Proposals MUST be received by 5:00 PM PST on January 3, 2013.
PLEASE USE SEPARATE FORM FOR EACH PROPOSALIAPMO’s green initiative is to lead the organization paper free by providing the Proposed Monographs, Annual Report onProposals and Comments in digital Adobe PDF http://www.iapmo.org/Pages/RequestFormforROPROC.aspx
Note printed copies of Report on Proposals and Report on Comments will not be available at the hearings. All requestedprinted copies will be mailed 30 days prior to the hearing date. Please submit by the following dates listed by the code belowon the request form.
Date Name Tel. No.
Company
Street Address City State Zip.
Please Indicate Organization Represented (if any)
1. IAPMO Document Title IAPMO No. & Year
Section/Paragraph
2. Proposal Recommends (check one): New Text Revised Text Deleted Text
3. Proposal (Include proposed new wording, or identification of wording to be deleted): [Note: Proposed textshould be in legislative format: i.e., use underscore to denote wording to be inserted (inserted wording) andstrike-through to denote wording to be deleted (deleted wording).] Please note if you are referencing a standardor other publication, please provide two copies.
4. Statement of Problem and Substantiation for Proposal: [Note: State the problem that will be resolved byyour recommendations: give the specific reason for your proposal including copies of tests, research papers,etc. If more then 200 words, it may be abstracted for publication.]
5. This Proposal is original material. [Note: Original material is considered to be the submitter’s own ideabased on or as a result of his/her own experience, thought or research and, to the best of his/her knowledge, isnot copied from another source.)
This Proposal is not original material; its source (if known) is as follows:
I hereby grant the IAPMO all and full rights in copyright, in this proposal, and I understand that I acquire no rights in any publicationof IAPMO in which this proposal in this or another similar or analogous form is used.
Signature (Required):
PLEASE USE SEPARATE FORM FOR EACH PROPOSAL • IAPMO FAX • (909) 472-4198 or (877) 852-6337Mail to: Code Development • IAPMO • 4755 E Philadelphia St • Ontario • CA • 91761-2816
Email to: [email protected]
For further information on the standards-making process, please contact theCodes and Standards Administration at 909-472-4110.
For technical assistance, please call IAPMO at 909-472-4111 or 909-230-5535.
FOR OFFICE USE ONLYLOG # :DATE REC’D:
viii
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
INSTRUCTIONS FOR SUBMITTING PROPOSALS– PLEASE READ CAREFULLY –
1. Type or print in BLACK ink.
2. Indicate the title of the document and the document year. Also, indicate the specific section orparagraph that the proposed amendment applies to.
3. Check the appropriate box to indicate whether this proposal recommends adding new text,revising existing text, or deleting text.
4. In the space identified as “Proposal,” indicate the exact wording you propose as new or revisedtext, or the text you propose be deleted.
5. In the space titled, “Statement of Problem and Substantiation for Proposal,” state the problemthat will be resolved by your recommendation and give the specific reason for your proposal.Include copies of test results, research papers, fire experience, or other materials thatsubstantiate your recommendation. (See note below, item (f).)
6. Check the appropriate box to indicate whether or not this proposal is original material, and if it isnot, indicate the source of the material.
7. Sign the proposal.
If supplementary material (photographs, diagrams, reports, etc.) is included, you may be required tosubmit sufficient copies for all members and alternates of the technical committee. For publication inthe Report on Proposals, the technical committee is authorized to abstract the “Statement of Problemand Substantiation for Proposal” if it exceeds 200 words.
NOTE: The IAPMO Regulations Governing Committee Projects in Paragraph 4-3.3 state: Eachproposal shall be submitted to the council secretary and shall include: (a) identification of the submitterand his or her affiliation (i.e., technical committee, organization, company), where appropriate; (b)identification of the document, edition of the document, and paragraph of the document to which theproposal is directed; (c) the proposed text of the proposal, including the wording to be added, revised(and how revised), or deleted; (d) a statement of the problem and substantiation for proposal; (e) thesignature of the submitter; and (f) two copies of any document(s) (other than an IAPMO document)being proposed as a reference standard or publication (see 3-3.7).
ix
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
x
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
xiUNIFORM PLUMBING CODE
CHAPTER 1 ADMINISTRATION . . . . . . . . . . . . . .1101.0 General . . . . . . . . . . . . . . . . . . . . . . .1101.1 Title . . . . . . . . . . . . . . . . . . . . . . . . . .1101.2 Scope . . . . . . . . . . . . . . . . . . . . . . . .1101.3 Purpose . . . . . . . . . . . . . . . . . . . . . .1101.4 Conflicts Between Codes . . . . . . . . .1101.5 Plans Required . . . . . . . . . . . . . . . . .1101.6 Repairs and Alterations . . . . . . . . . .1101.7 Maintenance . . . . . . . . . . . . . . . . . . .1101.8 Existing Construction . . . . . . . . . . . .1101.9 Additions, Alterations, or
Repairs . . . . . . . . . . . . . . . . . . . . . . .1101.10 Appendices . . . . . . . . . . . . . . . . . . . .1101.11 Application to Existing
Plumbing System . . . . . . . . . . . . . . .1102.0 Organization and Enforcement . . . . .2102.1 Authority Having Jurisdiction . . . . . .2102.2 Duties and Powers of the
Authority Having Jurisdiction . . . . . .2102.3 Board of Appeals . . . . . . . . . . . . . . .3102.4 Violations . . . . . . . . . . . . . . . . . . . . .3102.5 Penalties . . . . . . . . . . . . . . . . . . . . . .3103.0 Permits and Inspections . . . . . . . . . .3103.1 Permits Required . . . . . . . . . . . . . . .3103.2 Application for Permit . . . . . . . . . . . .3103.3 Permit Issuance . . . . . . . . . . . . . . . .3103.4 Fees . . . . . . . . . . . . . . . . . . . . . . . . .4103.5 Inspections . . . . . . . . . . . . . . . . . . . .5103.6 Connection Approval . . . . . . . . . . . .6103.7 Unconstitutional . . . . . . . . . . . . . . . .6103.8 Validity . . . . . . . . . . . . . . . . . . . . . . .6Table 103.4 Plumbing Permit Fees . . . . . . . . . . .7
CHAPTER 2 DEFINITIONS . . . . . . . . . . . . . . . . . .9201.0 General . . . . . . . . . . . . . . . . . . . . . . .9201.1 Applicability . . . . . . . . . . . . . . . . . . . .9202.0 Definition of Terms . . . . . . . . . . . . . .9202.1 General . . . . . . . . . . . . . . . . . . . . . . .9
CHAPTER 3 GENERAL REGULATIONS . . . . . .19301.0 Materials – Standards and
Alternates . . . . . . . . . . . . . . . . . . . .19301.1 Minimum Standards . . . . . . . . . . . .19301.2 Alternate Materials and Methods
of Construction Equivalency . . . . . .19301.3 Flood Hazard Areas . . . . . . . . . . . .19
301.4 Alternative Engineered Design . . . .20302.0 Iron Pipe Size (IPS) Pipe . . . . . . . .20302.1 General . . . . . . . . . . . . . . . . . . . . . .20303.0 Disposal of Liquid Waste . . . . . . . .20303.1 General . . . . . . . . . . . . . . . . . . . . . .20304.0 Connections to Plumbing
System Required . . . . . . . . . . . . . .20304.1 General . . . . . . . . . . . . . . . . . . . . . .20305.0 Damage to Drainage System
or Public Sewer . . . . . . . . . . . . . . .20305.1 Unlawful Practices . . . . . . . . . . . . .20306.0 Industrial Wastes . . . . . . . . . . . . . .20306.1 Detrimental Wastes . . . . . . . . . . . .20306.2 Safe Discharge . . . . . . . . . . . . . . . .20307.0 Location . . . . . . . . . . . . . . . . . . . . .20307.1 System . . . . . . . . . . . . . . . . . . . . . .20307.2 Ownership . . . . . . . . . . . . . . . . . . .20308.0 Improper Location . . . . . . . . . . . . . .20308.1 General . . . . . . . . . . . . . . . . . . . . . .20309.0 Workmanship . . . . . . . . . . . . . . . . .21309.1 Engineering Practices . . . . . . . . . . .21309.2 Concealing Imperfections . . . . . . . .21309.3 Burred Ends . . . . . . . . . . . . . . . . . .21309.4 Installation Practices . . . . . . . . . . . .21310.0 Prohibited Fittings and
Practices . . . . . . . . . . . . . . . . . . . . .21310.1 Fittings . . . . . . . . . . . . . . . . . . . . . .21310.2 Drainage and Vent Piping . . . . . . . .21310.3 Waste Connection . . . . . . . . . . . . .21310.4 Use of Vent and Waste Pipes . . . . .21310.5 Obstruction of Flow . . . . . . . . . . . .21310.6 Dissimilar Metals . . . . . . . . . . . . . .21310.7 Direction of Flow . . . . . . . . . . . . . . .21310.8 Screwed Fittings . . . . . . . . . . . . . . .21311.0 Independent Systems . . . . . . . . . . .21311.1 General . . . . . . . . . . . . . . . . . . . . . .21312.0 Protection of Piping, Materials,
and Structures . . . . . . . . . . . . . . . .21312.1 General . . . . . . . . . . . . . . . . . . . . . .21312.2 Installation . . . . . . . . . . . . . . . . . . .21312.3 Building Sewer and Drainage
Piping . . . . . . . . . . . . . . . . . . . . . . .21312.4 Corrosion, Erosion, and
Mechanical Damage . . . . . . . . . . . .21312.5 Protectively Coated Pipe . . . . . . . .21
TABLE OF CONTENTS
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
312.6 Freezing Protection . . . . . . . . . . . .21312.7 Fire-Resistant Construction . . . . . .21312.8 Waterproofing of Openings . . . . . . .22312.9 Steel Nail Plates . . . . . . . . . . . . . . .22312.10 Sleeves . . . . . . . . . . . . . . . . . . . . . .22312.11 Structural Members . . . . . . . . . . . .22312.12 Rodentproofing . . . . . . . . . . . . . . . .22313.0 Hangers and Supports . . . . . . . . . .22313.1 Suspended Piping . . . . . . . . . . . . .22313.2 Piping Support . . . . . . . . . . . . . . . .22313.3 Underground Piping . . . . . . . . . . . .22313.4 Strength . . . . . . . . . . . . . . . . . . . . .22313.5 Piping, Fixtures, Appliances,
and Appurtenances . . . . . . . . . . . . .22313.6 Hanger Rod Sizes . . . . . . . . . . . . .22Table 313.6 Hanger Rod Sizes . . . . . . . . . . . . .22313.7 Gas Piping . . . . . . . . . . . . . . . . . . .22314.0 Trenching, Excavation, and
Backfill . . . . . . . . . . . . . . . . . . . . . .22314.1 Trenches . . . . . . . . . . . . . . . . . . . . .22314.2 Tunneling and Driving . . . . . . . . . . .22314.3 Open Trenches . . . . . . . . . . . . . . . .22314.4 Excavations . . . . . . . . . . . . . . . . . .22315.0 Joints and Connections . . . . . . . . .23315.1 Unions . . . . . . . . . . . . . . . . . . . . . .23315.2 Prohibited Joints and
Connections . . . . . . . . . . . . . . . . . .23316.0 Increasers and Reducers . . . . . . . .23316.1 General . . . . . . . . . . . . . . . . . . . . . .23317.0 Food-Handling Establishments . . . .23317.1 General . . . . . . . . . . . . . . . . . . . . . .23318.0 Test Gauges . . . . . . . . . . . . . . . . . .23318.1 General . . . . . . . . . . . . . . . . . . . . . .23318.2 Pressure Tests (10 psi or less) . . . .23318.3 Pressure Tests (greater than
10 psi to 100 psi) . . . . . . . . . . . . . .23318.4 Pressure Tests (exceeding
100 psi) . . . . . . . . . . . . . . . . . . . . . .23318.5 Pressure Range . . . . . . . . . . . . . . .23319.0 Medical Gas and Vacuum
Systems . . . . . . . . . . . . . . . . . . . . .23319.1 General . . . . . . . . . . . . . . . . . . . . . .23Table 313.1 Hangers and Supports . . . . . . . . . .24
CHAPTER 4 PLUMBING FIXTURESAND FIXTURE FITTINGS . . . . . . .25
401.0 Materials – GeneralRequirements . . . . . . . . . . . . . . . . .25
401.1 Quality of Fixtures . . . . . . . . . . . . .25
401.2 Lead . . . . . . . . . . . . . . . . . . . . . . . .25402.0 Installation . . . . . . . . . . . . . . . . . . .25402.1 Cleaning . . . . . . . . . . . . . . . . . . . . .25402.2 Joints . . . . . . . . . . . . . . . . . . . . . . .25402.3 Securing Fixtures . . . . . . . . . . . . . .25402.4 Wall-Hung Fixtures . . . . . . . . . . . . .25402.5 Setting . . . . . . . . . . . . . . . . . . . . . .25402.6 Flanged Fixture Connections . . . . .25402.7 Accessible Plumbing Facilities . . . .25402.8 Supply Fittings . . . . . . . . . . . . . . . .25402.9 Installation . . . . . . . . . . . . . . . . . . .26402.10 Design and Installation of
Plumbing Fixtures . . . . . . . . . . . . . .26402.11 Slip Joint Connections . . . . . . . . . .26402.12 Future Fixtures . . . . . . . . . . . . . . . .26403.0 Water-Conserving Fixtures
and Fittings . . . . . . . . . . . . . . . . . . .26403.1 Flush Volumes . . . . . . . . . . . . . . . .26403.2 Water Closets . . . . . . . . . . . . . . . . .26403.3 Urinals . . . . . . . . . . . . . . . . . . . . . .26403.4 Metered Faucets . . . . . . . . . . . . . . .26403.5 Pre-Rinse Spray Valve . . . . . . . . . .26404.0 Overflows . . . . . . . . . . . . . . . . . . . .26404.1 General . . . . . . . . . . . . . . . . . . . . . .26405.0 Strainers and Connections . . . . . . .26405.1 Strainers . . . . . . . . . . . . . . . . . . . . .26405.2 Continuous Wastes . . . . . . . . . . . . .26406.0 Prohibited Fixtures . . . . . . . . . . . . .26406.1 Prohibited Water Closets . . . . . . . .26406.2 Prohibited Urinals . . . . . . . . . . . . . .26406.3 Miscellaneous Fixtures . . . . . . . . . .26407.0 Special Fixtures and Specialties . .26407.1 Water and Waste Connections . . . .26407.2 Special Use Sinks . . . . . . . . . . . . .26407.3 Special Use Fixtures . . . . . . . . . . .27407.4 Zinc Alloy Components . . . . . . . . . .27408.0 Showers . . . . . . . . . . . . . . . . . . . . .27408.1 Application . . . . . . . . . . . . . . . . . . .27408.2 Water Consumption . . . . . . . . . . . .27408.3 Individual Shower and
Tub-Shower CombinationControl Valves . . . . . . . . . . . . . . . .27
408.4 Waste Outlet . . . . . . . . . . . . . . . . . .27408.5 Finished Curb or Threshold . . . . . .27408.6 Shower Compartments . . . . . . . . . .27408.7 Lining for Showers and
Receptors . . . . . . . . . . . . . . . . . . . .27408.8 Public Shower Floors . . . . . . . . . . .28408.9 Location of Valves and Heads . . . .28
xii UNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
408.10 Water Supply Riser . . . . . . . . . . . . .28409.0 Bathtubs and Whirlpool
Bathtubs . . . . . . . . . . . . . . . . . . . . .28409.1 Application . . . . . . . . . . . . . . . . . . .28409.2 Waste Outlet . . . . . . . . . . . . . . . . . .28409.3 Overflow . . . . . . . . . . . . . . . . . . . . .28409.4 Limitation of Hot Water in
Bathtubs and WhirlpoolBathtubs . . . . . . . . . . . . . . . . . . . . .28
409.5 Backflow Protection . . . . . . . . . . . .28409.6 Installation and Access . . . . . . . . . .28410.0 Bidets . . . . . . . . . . . . . . . . . . . . . . .29410.1 Application . . . . . . . . . . . . . . . . . . .29410.2 Backflow Protection . . . . . . . . . . . .29410.3 Limitation of Water
Temperature in Bidets . . . . . . . . . .29411.0 Water Closets . . . . . . . . . . . . . . . . .29411.1 Water Closet Bowls . . . . . . . . . . . .29411.2 Water Closet Seats . . . . . . . . . . . . .29412.0 Urinals . . . . . . . . . . . . . . . . . . . . . .29412.1 General . . . . . . . . . . . . . . . . . . . . . .29413.0 Flushing Devices for Water
Closets and Urinals . . . . . . . . . . . .29413.1 Application . . . . . . . . . . . . . . . . . . .29413.2 Flushing Devices Required . . . . . .29413.3 Flushometer Valves . . . . . . . . . . . .29413.4 Water Supply for Flush Tanks . . . .29413.5 Overflows in Flush Tanks . . . . . . . .29414.0 Dishwashing Machines . . . . . . . . . .29414.1 Application . . . . . . . . . . . . . . . . . . .29414.2 Backflow Protection . . . . . . . . . . . .29414.3 Drainage Connection . . . . . . . . . . .29415.0 Drinking Fountains . . . . . . . . . . . . .29415.1 Application . . . . . . . . . . . . . . . . . . .29415.2 Where Required . . . . . . . . . . . . . . .29415.3 Drainage Connection . . . . . . . . . . .29415.4 Location . . . . . . . . . . . . . . . . . . . . .29416.0 Emergency Eyewash and
Shower Equipment . . . . . . . . . . . . .30416.1 Application . . . . . . . . . . . . . . . . . . .30416.2 Water Supply . . . . . . . . . . . . . . . . .30416.3 Installation . . . . . . . . . . . . . . . . . . .30416.4 Location . . . . . . . . . . . . . . . . . . . . .30416.5 Drain . . . . . . . . . . . . . . . . . . . . . . . .30417.0 Faucets and Fixture Fittings . . . . . .30417.1 Application . . . . . . . . . . . . . . . . . . .30417.2 Deck Mounted Bath/Shower
Valves . . . . . . . . . . . . . . . . . . . . . . .30417.3 Handheld Showers . . . . . . . . . . . . .30
417.4 Faucets and Fixture Fittingswith Hose Connected Outlets . . . . .30
417.5 Separate Controls for Hot andCold Water . . . . . . . . . . . . . . . . . . .30
418.0 Floor Drains . . . . . . . . . . . . . . . . . .30418.1 Application . . . . . . . . . . . . . . . . . . .30418.2 Strainer . . . . . . . . . . . . . . . . . . . . . .30418.3 Location of Floor Drains . . . . . . . . .30418.4 Food Storage Areas . . . . . . . . . . . .30418.5 Floor Slope . . . . . . . . . . . . . . . . . . .30419.0 Food Waste Disposal Units . . . . . .30419.1 Application . . . . . . . . . . . . . . . . . . .30419.2 Drainage Connection . . . . . . . . . . .30419.3 Water Supply . . . . . . . . . . . . . . . . .30420.0 Sinks . . . . . . . . . . . . . . . . . . . . . . . .30420.1 Application . . . . . . . . . . . . . . . . . . .30420.2 Water Consumption . . . . . . . . . . . .30420.3 Waste Outlet . . . . . . . . . . . . . . . . . .31421.0 Fixtures and Fixture Fittings
for Persons with Disabilities . . . . . .31421.1 General . . . . . . . . . . . . . . . . . . . . . .31421.2 Limitation of Hot Water
Temperature for PublicLavatories . . . . . . . . . . . . . . . . . . . .31
422.0 Minimum Number ofRequired Fixtures . . . . . . . . . . . . . .31
422.1 Fixture Count . . . . . . . . . . . . . . . . .31422.2 Separate Facilities . . . . . . . . . . . . .31422.3 Fixture Requirements for
Special Occupancies . . . . . . . . . . .31422.4 Toilet Facilities Serving
Employees and Customers . . . . . .31422.5 Toilet Facilities for Workers . . . . . .31Table 422.1 Minimum Plumbing Facilities . . . . .32
CHAPTER 5 WATER HEATERS . . . . . . . . . . . . .37501.0 General . . . . . . . . . . . . . . . . . . . . . .37501.1 Applicability . . . . . . . . . . . . . . . . . . .37Table 501.1 First Hour Rating . . . . . . . . . . . . . .37502.0 Permits . . . . . . . . . . . . . . . . . . . . . .37502.1 General . . . . . . . . . . . . . . . . . . . . . .37503.0 Inspection . . . . . . . . . . . . . . . . . . . .37503.1 Inspection of Chimneys or Vents . .37503.2 Final Water Heater Inspection . . . .37504.0 Water Heater Requirements . . . . . .37504.1 Location . . . . . . . . . . . . . . . . . . . . .37504.2 Vent . . . . . . . . . . . . . . . . . . . . . . . .37504.3 Clearance . . . . . . . . . . . . . . . . . . . .37504.4 Pressure-Limiting Devices . . . . . . .38
xiiiUNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
504.5 Temperature-Limiting Devices . . . .38504.6 Temperature, Pressure, and
Vacuum Relief Devices . . . . . . . . . .38505.0 Oil-Burning and Other Water
Heaters . . . . . . . . . . . . . . . . . . . . . .38505.1 Water Heaters . . . . . . . . . . . . . . . . .38505.2 Safety Devices . . . . . . . . . . . . . . . .38505.3 Oil-Fired Water Heaters . . . . . . . . .38505.4 Indirect-Fired Water Heaters . . . . .38506.0 Air for Combustion and
Ventilation . . . . . . . . . . . . . . . . . . . .38506.1 General . . . . . . . . . . . . . . . . . . . . . .38506.2 Indoor Combustion Air . . . . . . . . . .38506.3 Indoor Opening Size and
Location . . . . . . . . . . . . . . . . . . . . .39506.4 Outdoor Combustion Air . . . . . . . . .39506.5 Combination Indoor and
Outdoor Combustion Air . . . . . . . . .41506.6 Engineered Installations . . . . . . . . .41506.7 Mechanical Combustion Air
Supply . . . . . . . . . . . . . . . . . . . . . . .41506.8 Louvers, Grilles, and Screens . . . .41506.9 Combustion Air Ducts . . . . . . . . . . .41507.0 Other Water Heater Installation
Requirements . . . . . . . . . . . . . . . . .42507.1 Dielectric Insulator . . . . . . . . . . . . .42507.2 Seismic Provisions . . . . . . . . . . . . .42507.3 Ground Support . . . . . . . . . . . . . . .42507.4 Drainage Pan . . . . . . . . . . . . . . . . .42507.5 Relief Valve Discharge . . . . . . . . . .42507.6 Added or Converted Appliances . . .42507.7 Types of Gases . . . . . . . . . . . . . . .42507.8 Safety Shutoff Devices for
Unlisted LP-Gas ApplianceUsed Indoors . . . . . . . . . . . . . . . . .42
507.9 Use of Air or Oxygen UnderPressure . . . . . . . . . . . . . . . . . . . . .42
507.10 Protection of Gas Appliancesfrom Fumes or Gases otherthan Products of Combustion . . . . .42
507.11 Process Air . . . . . . . . . . . . . . . . . . .42507.12 Flammable Vapors . . . . . . . . . . . . .42507.13 Installation in Garages . . . . . . . . . .42507.14 Installation in Commercial
Garages . . . . . . . . . . . . . . . . . . . . .43507.15 Installation in Aircraft Hangars . . . .43507.16 Venting of Flue Gases . . . . . . . . . .43507.17 Extra Device or Attachment . . . . . .43507.18 Adequate Capacity of Piping . . . . .43507.19 Avoiding Strain on Gas Piping . . . .43
507.20 Gas Appliance PressureRegulators . . . . . . . . . . . . . . . . . . .43
507.21 Venting of Gas AppliancePressure Regulators . . . . . . . . . . . .43
507.22 Bleed Lines for Diaphragm-TypeValves . . . . . . . . . . . . . . . . . . . . . . .43
507.23 Combination of Appliances . . . . . . .44507.24 Installation Instructions . . . . . . . . . .44507.25 Protection of Outdoor
Appliances . . . . . . . . . . . . . . . . . . .44507.26 Accessibility for Service . . . . . . . . .44508.0 Appliances on Roofs . . . . . . . . . . .44508.1 General . . . . . . . . . . . . . . . . . . . . . .44508.2 Installation of Appliances on
Roofs . . . . . . . . . . . . . . . . . . . . . . .44508.3 Access to Equipment and
Appliances on Roofs . . . . . . . . . . .44508.4 Appliances in Attics and
Under-Floor Spaces . . . . . . . . . . . .44509.0 Venting of Appliances . . . . . . . . . . .45509.1 Minimum Safe Performance . . . . . .45509.2 Connection to Venting Systems . . .45509.3 Design and Construction . . . . . . . .45509.4 Type of Venting System to
be Used . . . . . . . . . . . . . . . . . . . . .46509.5 Masonry, Metal, and
Factory-Built Chimneys . . . . . . . . .46Table 509.4 Type of Venting System to
be Used . . . . . . . . . . . . . . . . . . . . .46509.6 Gas Vents . . . . . . . . . . . . . . . . . . . .48Table 509.6.2 Roof Pitch Height . . . . . . . . . . . . . .49509.7 Single-Wall Metal Pipe . . . . . . . . . .50Table 509.7.3 Clearance for Connectors . . . . . . .51509.8 Through-the-Wall Vent
Termination . . . . . . . . . . . . . . . . . . .52509.9 Condensation Drain . . . . . . . . . . . .53509.10 Vent Connectors for Category I
Appliances . . . . . . . . . . . . . . . . . . .53Table 509.7.3(1) Reduction of Clearances with
Specified Forms of Protection . . . .54Table 509.10.1 Minimum Thickness for
Galvanized Steel Vent Connectorsfor Low-Heat Appliances . . . . . . . .55
Table 509.10.1(1) Minimum Thickness for SteelVent Connectors for Medium-HeatAppliances and Commercial andIndustrial Incinerators . . . . . . . . . . .55
509.11 Draft Hoods and Draft Controls . . .57509.12 Manually Operated Dampers . . . . .57509.13 Automatically Operated
Vent Dampers . . . . . . . . . . . . . . . . .57509.14 Obstructions . . . . . . . . . . . . . . . . . .57
xiv UNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
510.0 Sizing of Category I VentingSystems . . . . . . . . . . . . . . . . . . . . .58
510.1 Installation . . . . . . . . . . . . . . . . . . .58510.2 Additional Requirements to
Multiple Appliance Vent Table 510.2(1)through Table 510.2(9) . . . . . . . . . .59
Table 510.2.1 Vent Connector MaximumLength . . . . . . . . . . . . . . . . . . . . . . .60
511.0 Direct-Vent Appliances . . . . . . . . . .62511.1 General . . . . . . . . . . . . . . . . . . . . . .62Table 510.1.2(1) Type B Double-Wall Gas Vent . . . .64Table 510.1.2(2) Type B Double-Wall Gas Vent . . . .67Table 510.1.2(3) Masonry Chimney . . . . . . . . . . . . . .69Table 510.1.2(4) Masonry Chimney . . . . . . . . . . . . . .71Table 510.1.2(5) Single-Wall Metal Pipe or
Type B Asbestos Cement Vent . . . .73Table 510.1.2(6) Exterior Masonry Chimney . . . . . . .74Table 510.2(1) Type B Double-Wall Vent . . . . . . .75Table 510.2(2) Type B Double-Wall Vent . . . . . . . .79Table 510.2(3) Masonry Chimney . . . . . . . . . . . . . .81Table 510.2(4) Masonry Chimney . . . . . . . . . . . . . .83Table 510.2(5) Single-Wall Metal Pipe or
Type B Asbestos Cement Vent . . . .85Table 510.2(6) Exterior Masonry Chimney . . . . . . .85Table 510.2(7) Exterior Masonry Chimney . . . . . . .86Table 510.2(8) Exterior Masonry Chimney . . . . . . .87Table 510.2(9) Exterior Masonry Chimney . . . . . . .88
CHAPTER 6 WATER SUPPLY ANDDISTRIBUTION . . . . . . . . . . . . . . .89
601.0 Hot and Cold Water Required . . . .89601.1 General . . . . . . . . . . . . . . . . . . . . . .89601.2 Identification of a Potable and
Nonpotable Water System . . . . . . .89Table 601.2.2 Minimum Length of Color
Field and Size of Letters . . . . . . . .89602.0 Unlawful Connections . . . . . . . . . . .89602.1 Prohibited Installation . . . . . . . . . . .89602.2 Cross-Contamination . . . . . . . . . . .90602.3 Backflow Prevention . . . . . . . . . . . .90602.4 Approval by Authority . . . . . . . . . . .90603.0 Cross-Connection Control . . . . . . .90603.1 General . . . . . . . . . . . . . . . . . . . . . .90603.2 Approval of Devices or
Assemblies . . . . . . . . . . . . . . . . . . .90603.3 Backflow Prevention Devices,
Assemblies, and Methods . . . . . . .90Table 603.2 Backflow Prevention Devices,
Assemblies, and Methods . . . . . . .91603.4 General Requirements . . . . . . . . . .92
Table 603.3.1 Minimum Air Gaps for WaterDistribution . . . . . . . . . . . . . . . . . . .93
603.5 Specific Requirements . . . . . . . . . .93604.0 Materials . . . . . . . . . . . . . . . . . . . . .96604.1 Pipe, Tube, and Fittings . . . . . . . . .96604.2 Copper Tube . . . . . . . . . . . . . . . . . .96604.3 Hard-Drawn Copper Tubing . . . . . .96604.4 Flexible Copper Connectors . . . . . .96604.5 Cast-Iron Fittings . . . . . . . . . . . . . .96604.6 Malleable Iron Fittings . . . . . . . . . .96604.7 Previously Used Piping and
Tubing . . . . . . . . . . . . . . . . . . . . . . .96604.8 Epoxy Coating . . . . . . . . . . . . . . . .96604.9 Plastic Materials . . . . . . . . . . . . . . .96604.10 Solder . . . . . . . . . . . . . . . . . . . . . . .96604.11 Lead Content . . . . . . . . . . . . . . . . .96604.12 Flexible Corrugated Connectors . . .96604.13 Water Heater Connectors . . . . . . . .96605.0 Joints and Connections . . . . . . . . .96605.1 Asbestos Cement Pipe and
Joints . . . . . . . . . . . . . . . . . . . . . . .96605.2 Brass Pipe and Joints . . . . . . . . . . .96Table 604.1 Materials for Building Supply
and Water Distribution Pipingand Fittings . . . . . . . . . . . . . . . . . . .97
605.3 Copper Pipe, Tubing, and Joints . .97605.4 CPVC Plastic Pipe and Joints . . . .98605.5 Ductile Iron Pipe and Joints . . . . . .99605.6 Galvanized Steel Pipe and
Joints . . . . . . . . . . . . . . . . . . . . . . .99605.7 PE Plastic Pipe/Tubing and
Joints . . . . . . . . . . . . . . . . . . . . . . .99605.8 PE-AL-PE Plastic Pipe/Tubing
and Joints . . . . . . . . . . . . . . . . . . . .99605.9 PE-RT . . . . . . . . . . . . . . . . . . . . . .100605.10 PEX Plastic Tubing and Joints . . .100605.11 PEX-AL-PEX Plastic Tubing
and Joints . . . . . . . . . . . . . . . . . . .100605.12 Polypropylene (PP) Piping
and Joints . . . . . . . . . . . . . . . . . . .100605.13 PVC Plastic Pipe and Joints . . . . .100605.14 Stainless Steel Pipe and Joints . .101605.15 Slip Joints . . . . . . . . . . . . . . . . . . .101605.16 Dielectric Unions . . . . . . . . . . . . . .101605.17 Joints Between Various
Materials . . . . . . . . . . . . . . . . . . . .101606.0 Valves . . . . . . . . . . . . . . . . . . . . . .101606.1 General . . . . . . . . . . . . . . . . . . . . .101606.2 Fullway Valve . . . . . . . . . . . . . . . .101606.3 Multidwelling Units . . . . . . . . . . . .101
xvUNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
606.4 Multiple Openings . . . . . . . . . . . . .101606.5 Control Valve . . . . . . . . . . . . . . . .101606.6 Accessible . . . . . . . . . . . . . . . . . .101606.7 Multiple Fixtures . . . . . . . . . . . . . .101607.0 Gravity Supply Tanks . . . . . . . . . .102607.1 General . . . . . . . . . . . . . . . . . . . . .102607.2 Potable Water Tanks . . . . . . . . . .102608.0 Water Pressure, Pressure
Regulators, Pressure ReliefValves, and Vacuum ReliefValves . . . . . . . . . . . . . . . . . . . . . .102
608.1 Inadequate Water Pressure . . . . .102608.2 Excessive Water Pressure . . . . . .102608.3 Expansion Tanks,
Combination Pressure, andTemperature Relief Valves . . . . . .102
608.4 Pressure Relief Valves . . . . . . . . .102608.5 Drains . . . . . . . . . . . . . . . . . . . . . .102608.6 Water-Heating Devices . . . . . . . . .102608.7 Vacuum Relief Valves . . . . . . . . . .102609.0 Installation, Testing, Unions,
and Location . . . . . . . . . . . . . . . . .102609.1 Installation . . . . . . . . . . . . . . . . . .102609.2 Trenches . . . . . . . . . . . . . . . . . . . .103609.3 Under Concrete Slab . . . . . . . . . .103609.4 Testing . . . . . . . . . . . . . . . . . . . . .103609.5 Unions . . . . . . . . . . . . . . . . . . . . .103609.6 Location . . . . . . . . . . . . . . . . . . . .103609.7 Abutting Lot . . . . . . . . . . . . . . . . .103609.8 Low-Pressure Cutoff Required
on Booster Pumps for WaterDistribution Systems . . . . . . . . . . .103
609.9 Disinfection of Potable WaterSystem . . . . . . . . . . . . . . . . . . . . .103
609.10 Water Hammer . . . . . . . . . . . . . . .104610.0 Size of Potable Water Piping . . . .104610.1 Size . . . . . . . . . . . . . . . . . . . . . . . .104610.2 Pressure Loss . . . . . . . . . . . . . . . .104610.3 Quantity of Water . . . . . . . . . . . . .104610.4 Parallel Distribution Systems . . . .104610.5 Sizing per Appendices
A and C . . . . . . . . . . . . . . . . . . . . .104610.6 Friction and Pressure Loss . . . . . .104610.7 Conditions for Using
Table 610.4 . . . . . . . . . . . . . . . . . .104610.8 Size of Meter and Building
Supply Pipe Using Table 610.4 . .104610.9 Size of Branches . . . . . . . . . . . . .104Table 610.3 Water Supply Fixture Units
(WSFU) and Minimum FixtureBranch Pipe Sizes . . . . . . . . . . . .105
Table 610.4 Fixture Unit Table forDetermining Water Pipe andMeter Sizes . . . . . . . . . . . . . . . . . .106
610.10 Sizing for Flushometer Valves . . .107Table 610.10 Flushometer Fixture Units
for Water Sizing UsingTable 610.3 . . . . . . . . . . . . . . . . . .107
610.11 Sizing Systems forFlushometer Tanks . . . . . . . . . . . .107
610.12 Sizing for Velocity . . . . . . . . . . . . .107610.13 Exceptions . . . . . . . . . . . . . . . . . .107611.0 Drinking Water Treatment
Units . . . . . . . . . . . . . . . . . . . . . . .108611.1 Application . . . . . . . . . . . . . . . . . .108611.2 Air Gap Discharge . . . . . . . . . . . .108611.3 Connection Tubing . . . . . . . . . . . .108611.4 Sizing of Residential Softeners . .108Table 611.4 Sizing of Residential Water
Softeners . . . . . . . . . . . . . . . . . . .108612.0 Residential Fire Sprinkler
Systems . . . . . . . . . . . . . . . . . . . .108612.1 General . . . . . . . . . . . . . . . . . . . . .108
CHAPTER 7 SANITARY DRAINAGE . . . . . . . .109Part I Drainage Systems . . . . . . . . . . .109701.0 Materials . . . . . . . . . . . . . . . . . . . .109701.1 Drainage Piping . . . . . . . . . . . . . .109701.2 Drainage Fittings . . . . . . . . . . . . .109701.3 Lead . . . . . . . . . . . . . . . . . . . . . . .109701.4 Caulking Ferrules . . . . . . . . . . . . .109701.5 Soldering Bushings . . . . . . . . . . . .109702.0 Fixture Unit Equivalents . . . . . . . .109702.1 Trap Size . . . . . . . . . . . . . . . . . . .109702.2 Intermittent Flow . . . . . . . . . . . . . .109702.3 Continuous Flow . . . . . . . . . . . . . .109Table 701.4 Caulking Ferrules . . . . . . . . . . . . .109Table 701.5 Soldering Bushings . . . . . . . . . . . .109Table 701.1 Materials for Drain, Waste,
Vent Pipe and Fittings . . . . . . . . . .110Table 702.1 Drainage Fixture Unit
Values (DFU) . . . . . . . . . . . . . . . . .111Table 702.2(a) Maximum Drainage Fixture
Units for a Trap and Trap Arm . . .112Table 702.2(b) Discharge Capacity in Gallons
Per Minute for IntermittentFlow Only . . . . . . . . . . . . . . . . . . .112
703.0 Size of Drainage Piping . . . . . . . .112703.1 Minimum Size . . . . . . . . . . . . . . . .112703.2 Maximum Number of Fixture
Units . . . . . . . . . . . . . . . . . . . . . . .112703.3 Sizing per Appendix C . . . . . . . . .112
xvi UNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
704.0 Fixture Connections (Drainage) . .112704.1 Inlet Fittings . . . . . . . . . . . . . . . . .112704.2 Single Vertical Drainage Pipe . . . .112704.3 Commercial Dishwashing
Machines and Sinks . . . . . . . . . . .112705.0 Joints and Connections . . . . . . . .112705.1 ABS and ABS Co-Extruded
Plastic Pipe and Joints . . . . . . . . .112705.2 Asbestos Cement Pipe and
Joints . . . . . . . . . . . . . . . . . . . . . . .112Table 703.2 Maximum Unit Loading and
Maximum Length of Drainageand Vent Piping . . . . . . . . . . . . . . .113
705.3 Brass Pipe and Joints . . . . . . . . . .113705.4 Cast-Iron Pipe and Joints . . . . . . .113705.5 Copper Pipe (DWV) and Joints . .114705.6 Galvanized Steel Pipe
and Joints . . . . . . . . . . . . . . . . . . .114705.7 PVC and PVC Co-Extruded
Plastic Pipe and JoiningMethods . . . . . . . . . . . . . . . . . . . .114
705.8 Stainless Steel Pipe and Joints . .114705.9 Vitrified Clay Pipe and Joints . . . .115705.10 Special Joints . . . . . . . . . . . . . . . .115705.11 Joints Between Various
Materials . . . . . . . . . . . . . . . . . . . .115706.0 Changes in Direction of
Drainage Flow . . . . . . . . . . . . . . . .115706.1 Approved Fittings . . . . . . . . . . . . .115706.2 Horizontal to Vertical . . . . . . . . . . .115706.3 Horizontal to Horizontal . . . . . . . .115706.4 Vertical to Horizontal . . . . . . . . . . .115707.0 Cleanouts . . . . . . . . . . . . . . . . . . .115707.1 Plug . . . . . . . . . . . . . . . . . . . . . . . .115Table 707.1 Cleanouts . . . . . . . . . . . . . . . . . . .116707.2 Approved . . . . . . . . . . . . . . . . . . . .116707.3 Gas and Watertight . . . . . . . . . . . .116707.4 Location . . . . . . . . . . . . . . . . . . . .116707.5 Cleaning . . . . . . . . . . . . . . . . . . . .116707.6 Extension . . . . . . . . . . . . . . . . . . .116707.7 Interceptor . . . . . . . . . . . . . . . . . . .116707.8 Access . . . . . . . . . . . . . . . . . . . . .116707.9 Clearance . . . . . . . . . . . . . . . . . . .116707.10 Fittings . . . . . . . . . . . . . . . . . . . . .116707.11 Pressure Drainage Systems . . . . .116707.12 Countersunk Cleanout Plugs . . . .116707.13 Hubless Blind Plugs . . . . . . . . . . .116707.14 Trap Arms . . . . . . . . . . . . . . . . . . .116708.0 Grade of Horizontal Drainage
Piping . . . . . . . . . . . . . . . . . . . . . .116
708.1 General . . . . . . . . . . . . . . . . . . . . .116709.0 Gravity Drainage Required . . . . . .116709.1 General . . . . . . . . . . . . . . . . . . . . .116710.0 Drainage of Fixtures Located
Below the Next UpstreamManhole or Below the MainSewer Level . . . . . . . . . . . . . . . . .116
710.1 Backflow Protection . . . . . . . . . . .116710.2 Sewage Discharge . . . . . . . . . . . .117710.3 Sewage Ejector and Pumps . . . . .117710.4 Discharge Line . . . . . . . . . . . . . . .117710.5 Size of Building Drains and
Sewers . . . . . . . . . . . . . . . . . . . . .117710.6 Backwater Valves . . . . . . . . . . . . .117710.7 Drainage and Venting Systems . .117710.8 Sump and Receiving Tank
Construction . . . . . . . . . . . . . . . . .117710.9 Alarm . . . . . . . . . . . . . . . . . . . . . . .117710.10 Sump and Receiving Tank
Covers and Vents . . . . . . . . . . . . .117710.11 Air Tanks . . . . . . . . . . . . . . . . . . . .117710.12 Grinder Pump Ejector . . . . . . . . . .118710.13 Macerating Toilet Systems . . . . . .118711.0 Suds Relief . . . . . . . . . . . . . . . . . .118711.1 General . . . . . . . . . . . . . . . . . . . . .118712.0 Testing . . . . . . . . . . . . . . . . . . . . . .118712.1 Media . . . . . . . . . . . . . . . . . . . . . .118712.2 Water Test . . . . . . . . . . . . . . . . . . .118712.3 Air Test . . . . . . . . . . . . . . . . . . . . .118Part II Building Sewers . . . . . . . . . . . . .118713.0 Sewer Required . . . . . . . . . . . . . .118713.1 Where Required . . . . . . . . . . . . . .118713.2 Private Sewage Disposal
System . . . . . . . . . . . . . . . . . . . . .118713.3 Public Sewer . . . . . . . . . . . . . . . . .118713.4 Public Sewer Availability . . . . . . . .118713.5 Permit . . . . . . . . . . . . . . . . . . . . . .118713.6 Lot . . . . . . . . . . . . . . . . . . . . . . . . .119713.7 Installation . . . . . . . . . . . . . . . . . . .119714.0 Damage to Public Sewer
or Private Sewage DisposalSystem . . . . . . . . . . . . . . . . . . . . .119
714.1 Unlawful Practices . . . . . . . . . . . .119714.2 Prohibited Water Discharge . . . . .119714.3 Prohibited Sewer Connection . . . .119714.4 Commercial Food Waste
Grinder . . . . . . . . . . . . . . . . . . . . .119714.5 Tanks . . . . . . . . . . . . . . . . . . . . . . .119715.0 Building Sewer Materials . . . . . . .119715.1 Materials . . . . . . . . . . . . . . . . . . . .119
xviiUNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
715.2 Joining Methods and Materials . . .119715.3 Existing Sewers . . . . . . . . . . . . . .119716.0 Markings . . . . . . . . . . . . . . . . . . . .119716.1 General . . . . . . . . . . . . . . . . . . . . .119717.0 Size of Building Sewers . . . . . . . .119717.1 General . . . . . . . . . . . . . . . . . . . . .119Table 717.1 Maximum/Minimum Fixture
Unit Loading on BuildingSewer Piping . . . . . . . . . . . . . . . . .119
718.0 Grade, Support, and Protectionof Building Sewers . . . . . . . . . . . .119
718.1 Slope . . . . . . . . . . . . . . . . . . . . . . .119718.2 Support . . . . . . . . . . . . . . . . . . . . .120718.3 Protection from Damage . . . . . . .120719.0 Cleanouts. . . . . . . . . . . . . . . . . . .120719.1 Locations . . . . . . . . . . . . . . . . . . .120719.2 No Additional Cleanouts . . . . . . . .120719.3 Building Sewer Cleanouts . . . . . .120719.4 Cleaning . . . . . . . . . . . . . . . . . . . .120719.5 Access . . . . . . . . . . . . . . . . . . . . .120719.6 Manholes . . . . . . . . . . . . . . . . . . .120720.0 Sewer and Water Pipes . . . . . . . .120720.1 General . . . . . . . . . . . . . . . . . . . . .120721.0 Location . . . . . . . . . . . . . . . . . . . .120721.1 Building Sewer . . . . . . . . . . . . . . .120721.2 Abutting Lot . . . . . . . . . . . . . . . . .120722.0 Abandoned Sewers and Sewage
Disposal Facilities . . . . . . . . . . . . .120722.1 Building (House) Sewer . . . . . . . .120Table 721.1 Minimum Horizontal Distance
Required from Building Sewer . . .121722.2 Cesspools, Septic Tanks, and
Seepage Pits . . . . . . . . . . . . . . . .121722.3 Filling . . . . . . . . . . . . . . . . . . . . . .121722.4 Ownership . . . . . . . . . . . . . . . . . .121722.5 Disposal Facilities . . . . . . . . . . . . .121723.0 Building Sewer Test . . . . . . . . . . .121723.1 General . . . . . . . . . . . . . . . . . . . . .121
CHAPTER 8 INDIRECT WASTES . . . . . . . . . .123801.0 Indirect Wastes . . . . . . . . . . . . . . .123801.1 Air Gap or Air Break Required . . .123801.2 Food and Beverage Handling
Establishments . . . . . . . . . . . . . . .123801.3 Bar and Fountain Sink Traps . . . .123801.4 Connections from Water
Distribution System . . . . . . . . . . . .123801.5 Sterilizers . . . . . . . . . . . . . . . . . . .123801.6 Drip or Drainage Outlets . . . . . . . .123
802.0 Approvals . . . . . . . . . . . . . . . . . . .123802.1 General . . . . . . . . . . . . . . . . . . . . .123803.0 Indirect Waste Piping . . . . . . . . . .123803.1 General . . . . . . . . . . . . . . . . . . . . .123804.0 Indirect Waste Receptors . . . . . . .124804.1 Standpipe Receptors . . . . . . . . . .124805.0 Pressure Drainage Connections .124805.1 General . . . . . . . . . . . . . . . . . . . . .124806.0 Sterile Equipment . . . . . . . . . . . . .124806.1 General . . . . . . . . . . . . . . . . . . . . .124807.0 Appliances . . . . . . . . . . . . . . . . . .124807.1 Non-Classed Apparatus . . . . . . . .124807.2 Condensate Waste . . . . . . . . . . . .124807.3 Undiluted Condensate Waste . . . .124807.4 Domestic Dishwashing
Machine . . . . . . . . . . . . . . . . . . . .124808.0 Cooling Water . . . . . . . . . . . . . . . .124808.1 General . . . . . . . . . . . . . . . . . . . . .124809.0 Drinking Fountains . . . . . . . . . . . .124809.1 General . . . . . . . . . . . . . . . . . . . . .124810.0 Steam and Hot Water Drainage
Condensers and Sumps . . . . . . . .124810.1 High Temperature Discharge . . . .124Table 810.1 Pipe Connections in Blowoff
Condensers and Sumps . . . . . . . .125810.2 Sumps, Condensers, and
Intercepting Tanks . . . . . . . . . . . .125810.3 Cleaning . . . . . . . . . . . . . . . . . . . .125810.4 Strainers . . . . . . . . . . . . . . . . . . . .125811.0 Chemical Wastes . . . . . . . . . . . . .125811.1 Pretreatment . . . . . . . . . . . . . . . . .125811.2 Waste and Vent Pipes . . . . . . . . .125811.3 Joining Materials . . . . . . . . . . . . . .125811.4 Access . . . . . . . . . . . . . . . . . . . . .125811.5 Permanent Record . . . . . . . . . . . .125811.6 Chemical Vent . . . . . . . . . . . . . . .125811.7 Discharge . . . . . . . . . . . . . . . . . . .125811.8 Diluted Chemicals . . . . . . . . . . . . .125812.0 Clear Water Wastes . . . . . . . . . . .125812.1 General . . . . . . . . . . . . . . . . . . . . .125813.0 Swimming Pools . . . . . . . . . . . . . .125813.1 General . . . . . . . . . . . . . . . . . . . . .125814.0 Condensate Wastes and Control .125814.1 Condensate Disposal . . . . . . . . . .125Table 814.1 Minimum Condensate
Pipe Size . . . . . . . . . . . . . . . . . . .126814.2 Size . . . . . . . . . . . . . . . . . . . . . . . .126814.3 Point of Discharge . . . . . . . . . . . .126
xviii UNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
CHAPTER 9 VENTS . . . . . . . . . . . . . . . . . . . . .127901.0 General . . . . . . . . . . . . . . . . . . . . .127901.1 Vents Required . . . . . . . . . . . . . . .127901.2 Trap Seal Protection . . . . . . . . . . .127902.0 Vents Not Required . . . . . . . . . . .127902.1 Interceptor . . . . . . . . . . . . . . . . . .127902.2 Bars, Soda Fountains, and
Counter . . . . . . . . . . . . . . . . . . . . .127903.0 Materials . . . . . . . . . . . . . . . . . . . .127903.1 Applicable Standards . . . . . . . . . .127903.2 Use of Copper Tubing . . . . . . . . .127903.3 Changes in Direction . . . . . . . . . .127904.0 Size of Vents . . . . . . . . . . . . . . . .127904.1 Size . . . . . . . . . . . . . . . . . . . . . . . .127904.2 Length . . . . . . . . . . . . . . . . . . . . . .127905.0 Vent Pipe Grades and
Connections . . . . . . . . . . . . . . . . .127905.1 Grade . . . . . . . . . . . . . . . . . . . . . .127905.2 Horizontal Drainage Pipe . . . . . . .128905.3 Vent Pipe Rise . . . . . . . . . . . . . . .128905.4 Roof Termination . . . . . . . . . . . . .128905.5 Location of Opening . . . . . . . . . . .128905.6 Common Vertical Pipe . . . . . . . . .128906.0 Vent Termination . . . . . . . . . . . . . .128906.1 Roof Termination . . . . . . . . . . . . .128906.2 Clearance . . . . . . . . . . . . . . . . . . .128906.3 Use of Roof . . . . . . . . . . . . . . . . .128906.4 Outdoor Installations . . . . . . . . . . .128906.5 Joints . . . . . . . . . . . . . . . . . . . . . .128906.6 Lead . . . . . . . . . . . . . . . . . . . . . . .128906.7 Frost or Snow Closure . . . . . . . . .128907.0 Vent Stacks and Relief Vents . . . .128907.1 Drainage Stack . . . . . . . . . . . . . . .128907.2 Yoke Vent . . . . . . . . . . . . . . . . . . .128908.0 Wet Venting . . . . . . . . . . . . . . . . .128908.1 Vertical Wet Venting . . . . . . . . . . .128908.2 Horizontal Wet Venting for
Bathroom Groups . . . . . . . . . . . . .129909.0 Special Venting for Island
Fixtures . . . . . . . . . . . . . . . . . . . . .129909.1 General . . . . . . . . . . . . . . . . . . . . .129910.0 Combination Waste and Vent
Systems . . . . . . . . . . . . . . . . . . . .129910.1 Where Permitted . . . . . . . . . . . . . .129910.2 Approval . . . . . . . . . . . . . . . . . . . .129910.3 Vents . . . . . . . . . . . . . . . . . . . . . . .129910.4 Size . . . . . . . . . . . . . . . . . . . . . . . .129910.5 Vertical Waste Pipe . . . . . . . . . . .129910.6 Cleanouts . . . . . . . . . . . . . . . . . . .129
910.7 Fixtures . . . . . . . . . . . . . . . . . . . . .129911.0 Engineered Vent System . . . . . . .130911.1 General . . . . . . . . . . . . . . . . . . . . .130911.2 Minimum Requirements . . . . . . . .130
CHAPTER 10 TRAPS ANDINTERCEPTORS . . . . . . . . . . . . .131
1001.0 Traps Required . . . . . . . . . . . . . . .1311001.1 Where Required . . . . . . . . . . . . . .1311002.0 Traps Protected by Vent Pipes . . .1311002.1 Vent Pipes . . . . . . . . . . . . . . . . . .1311002.2 Fixture Traps . . . . . . . . . . . . . . . . .131Table 1002.2 Horizontal Lengths of Trap
Arms . . . . . . . . . . . . . . . . . . . . . . .1311002.3 Change of Direction . . . . . . . . . . .1311002.4 Vent Pipe Opening . . . . . . . . . . . .1311003.0 Traps — Described . . . . . . . . . . . .1311003.1 General Requirements . . . . . . . . .1311003.2 Slip Joint Fittings . . . . . . . . . . . . .1311003.3 Size . . . . . . . . . . . . . . . . . . . . . . . .1321004.0 Traps . . . . . . . . . . . . . . . . . . . . . . .1321004.1 Prohibited . . . . . . . . . . . . . . . . . . .1321004.2 Movable Parts . . . . . . . . . . . . . . . .1321005.0 Trap Seals . . . . . . . . . . . . . . . . . .1321005.1 General . . . . . . . . . . . . . . . . . . . . .1321006.0 Floor Drain Traps . . . . . . . . . . . . .1321006.1 General . . . . . . . . . . . . . . . . . . . . .1321007.0 Trap Seal Protection . . . . . . . . . . .1321007.1 General . . . . . . . . . . . . . . . . . . . . .1321008.0 Building Traps . . . . . . . . . . . . . . . .1321008.1 General . . . . . . . . . . . . . . . . . . . . .1321009.0 Industrial Interceptors
(Clarifiers) and Separators . . . . . .1321009.1 Where Required . . . . . . . . . . . . . .1321009.2 Approval . . . . . . . . . . . . . . . . . . . .1321009.3 Design . . . . . . . . . . . . . . . . . . . . .1321009.4 Relief Vent . . . . . . . . . . . . . . . . . .1321009.5 Location . . . . . . . . . . . . . . . . . . . .1321009.6 Maintenance of Interceptors . . . . .1321009.7 Discharge . . . . . . . . . . . . . . . . . . .1321010.0 Slaughterhouses, Packing
Establishments, etc . . . . . . . . . . .1321010.1 General . . . . . . . . . . . . . . . . . . . . .1321011.0 Minimum Requirements for
Auto Wash Racks . . . . . . . . . . . . .1321011.1 General . . . . . . . . . . . . . . . . . . . . .1321012.0 Commercial and Industrial
Laundries . . . . . . . . . . . . . . . . . . .1331012.1 General . . . . . . . . . . . . . . . . . . . . .133
xixUNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
1013.0 Bottling Establishments . . . . . . . .1331013.1 General . . . . . . . . . . . . . . . . . . . . .1331014.0 Grease Interceptors . . . . . . . . . . .1331014.1 Where Required . . . . . . . . . . . . . .1331014.2 Hydromechanical Grease
Interceptors . . . . . . . . . . . . . . . . . .1331014.3 Gravity Grease Interceptors . . . . .133Table 1014.2.1 Hydromechanical Grease
Interceptor Sizing UsingGravity Flow Rates . . . . . . . . . . . .134
1015.0 FOG (Fats, Oils, and Greases)Disposal System . . . . . . . . . . . . . .134
1015.1 Purpose . . . . . . . . . . . . . . . . . . . .134Table 1014.3.6 Gravity Grease Interceptor
Sizing . . . . . . . . . . . . . . . . . . . . . .1351015.2 Scope . . . . . . . . . . . . . . . . . . . . . .1351015.3 Components, Materials, and
Equipment . . . . . . . . . . . . . . . . . .1351015.4 Sizing Application and
Installation . . . . . . . . . . . . . . . . . .1351015.5 Performance . . . . . . . . . . . . . . . . .1351016.0 Sand Interceptors . . . . . . . . . . . . .1351016.1 Discharge . . . . . . . . . . . . . . . . . . .1351016.2 Authority Having Jurisdiction . . . .1351016.3 Construction and Size . . . . . . . . .1351016.4 Separate Use . . . . . . . . . . . . . . . .1351017.0 Oil and Flammable Liquid
Interceptors . . . . . . . . . . . . . . . . . .1361017.1 Interceptors Required . . . . . . . . . .1361017.2 Design of Interceptors . . . . . . . . .136
CHAPTER 11 STORM DRAINAGE . . . . . . . . . .1371101.0 General . . . . . . . . . . . . . . . . . . . . .1371101.1 Where Required . . . . . . . . . . . . . .1371101.2 Storm Water Drainage to
Sanitary Sewer Prohibited . . . . . .1371101.3 Material Uses . . . . . . . . . . . . . . . .1371101.4 Expansion Joints Required . . . . . .1371101.5 Subsoil Drains . . . . . . . . . . . . . . .1371101.6 Building Subdrains . . . . . . . . . . . .1371101.7 Areaway Drains . . . . . . . . . . . . . .1371101.8 Window Areaway Drains . . . . . . .1381101.9 Filling Stations and Motor
Vehicle WashingEstablishments . . . . . . . . . . . . . . .138
1101.10 Paved Areas . . . . . . . . . . . . . . . . .1381101.11 Roof Drainage . . . . . . . . . . . . . . .1381101.12 Cleanouts . . . . . . . . . . . . . . . . . . .1381101.13 Rainwater Sumps . . . . . . . . . . . . .1381102.0 Materials . . . . . . . . . . . . . . . . . . . .138
1102.1 Conductors . . . . . . . . . . . . . . . . . .1381102.2 Leaders . . . . . . . . . . . . . . . . . . . . .1381102.3 Underground Building Storm
Drains . . . . . . . . . . . . . . . . . . . . . .1391102.4 Building Storm Sewers . . . . . . . . .1391102.5 Subsoil Drains . . . . . . . . . . . . . . .139Table 1102.5 Materials for Subsoil Drain
Pipe and Fittings . . . . . . . . . . . . . .1391103.0 Traps on Storm Drains and
Leaders . . . . . . . . . . . . . . . . . . . . .1391103.1 Where Required . . . . . . . . . . . . . .1391103.2 Where Not Required . . . . . . . . . . .1391103.3 Trap Size . . . . . . . . . . . . . . . . . . .1391103.4 Method of Installation of
Combined Sewer . . . . . . . . . . . . .1391104.0 Leaders, Conductors, and
Connections . . . . . . . . . . . . . . . . .1391104.1 Improper Use . . . . . . . . . . . . . . . .1391104.2 Protection of Leaders . . . . . . . . . .1391104.3 Combining Storm with
Sanitary Drainage . . . . . . . . . . . . .1391105.0 Roof Drains . . . . . . . . . . . . . . . . . .1391105.1 Materials . . . . . . . . . . . . . . . . . . . .1391105.2 Dome or Strainer for
General Use . . . . . . . . . . . . . . . . .1391105.3 Strainers for Flat Decks . . . . . . . .1391105.4 Roof Drain Flashings . . . . . . . . . .1391106.0 Size of Leaders, Conductors,
and Storm Drains . . . . . . . . . . . . .1391106.1 Vertical Conductors
and Leaders . . . . . . . . . . . . . . . . .1391106.2 Size of Horizontal Storm
Drains and Sewers . . . . . . . . . . . .1391106.3 Size of Roof Gutters . . . . . . . . . . .1391106.4 Side Walls Draining onto
a Roof . . . . . . . . . . . . . . . . . . . . . .1401107.0 Values for Continuous Flow . . . . .1401107.1 General . . . . . . . . . . . . . . . . . . . . .1401108.0 Controlled-Flow Roof Drainage . . .1401108.1 Application . . . . . . . . . . . . . . . . . .140Table 1108.1(2) Controlled-Flow Maximum
Roof Water Depth . . . . . . . . . . . . .1401108.2 Setback Roofs . . . . . . . . . . . . . . .140Table 1108.1(8) Distance of Scupper Bottoms
Above Roof . . . . . . . . . . . . . . . . . .1411109.0 Testing . . . . . . . . . . . . . . . . . . . . .1411109.1 Testing Required . . . . . . . . . . . . . .1411109.2 Methods of Testing Storm
Drainage Systems . . . . . . . . . . . .141Table 1101.7 Sizing of Horizontal
Rainwater Piping . . . . . . . . . . . . .142
xx UNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
Table 1101.11 Sizing Roof Drains, Leaders,and Vertical Rainwater Piping . . .143
Table 1106.3 Size of Gutters . . . . . . . . . . . . . . .144
CHAPTER 12 FUEL GAS PIPING . . . . . . . . . . .1451201.0 Scope of Gas Piping . . . . . . . . . . .1451201.1 Coverage of Piping System . . . . .1451201.2 Piping System Requirements . . . .1451201.3 Application . . . . . . . . . . . . . . . . . .1451202.0 General . . . . . . . . . . . . . . . . . . . . .1451202.1 Installation . . . . . . . . . . . . . . . . . .1451203.0 Inspection . . . . . . . . . . . . . . . . . . .1451203.1 Inspection Notification . . . . . . . . .1451203.2 Excavation . . . . . . . . . . . . . . . . . .1451203.3 Type of Inspections . . . . . . . . . . .1451203.4 Inspection Waived . . . . . . . . . . . .1451204.0 Certificate of Inspection . . . . . . . .1461204.1 Issuance . . . . . . . . . . . . . . . . . . . .1461204.2 Gas Supplier . . . . . . . . . . . . . . . . .1461204.3 Unlawful . . . . . . . . . . . . . . . . . . . .1461205.0 Authority to Render Gas
Service . . . . . . . . . . . . . . . . . . . . .1461205.1 Authorized Personnel . . . . . . . . . .1461205.2 Outlets . . . . . . . . . . . . . . . . . . . . .1461206.0 Authority to Disconnect . . . . . . . .1461206.1 Disconnection . . . . . . . . . . . . . . . .1461206.2 Notice . . . . . . . . . . . . . . . . . . . . . .1461206.3 Capped Outlets . . . . . . . . . . . . . . .1461207.0 Temporary Use of Gas . . . . . . . . .1461207.1 General . . . . . . . . . . . . . . . . . . . . .1461208.0 Gas Piping System Design,
Materials, and Components . . . . .1461208.1 Installation of Piping System . . . .1461208.2 Provision for Location of
Point of Delivery . . . . . . . . . . . . . .1461208.3 Interconnections Between
Gas Piping Systems . . . . . . . . . . .1461208.4 Sizing of Gas Piping Systems . . .1461208.5 Acceptable Piping Materials
and Joining Methods . . . . . . . . . .147Table 1208.4.1 Approximate Gas Input for
Typical Appliances . . . . . . . . . . . .147Table 1208.5.7.2 Specifications for Threading
Metallic Pipe . . . . . . . . . . . . . . . . .1481208.6 Gas Meters . . . . . . . . . . . . . . . . . .1501208.7 Gas Pressure Regulators . . . . . . .1501208.8 Backpressure Protection . . . . . . .1511208.9 Low-Pressure Protection . . . . . . .1511208.10 Shutoff Valves . . . . . . . . . . . . . . . .151
1208.11 Expansion and Flexibility . . . . . . .1511209.0 Excess Flow Valve . . . . . . . . . . . .1511209.1 General . . . . . . . . . . . . . . . . . . . . .1511210.0 Gas Piping Installation . . . . . . . . .1511210.1 Piping Underground . . . . . . . . . . .1511210.2 Installation of Piping . . . . . . . . . . .152Table 1210.2.4.1 Support of Piping . . . . . . . . . . . . .1531210.3 Concealed Piping in Buildings . . .1531210.4 Piping in Vertical Chases . . . . . . .1531210.5 Maximum Design Operating
Pressure . . . . . . . . . . . . . . . . . . . .1541210.6 Appliance Overpressure
Protection . . . . . . . . . . . . . . . . . . .1541210.7 Gas Pipe Turns . . . . . . . . . . . . . . .1541210.8 Drips and Sediment Traps . . . . . .1541210.9 Outlets . . . . . . . . . . . . . . . . . . . . .1551210.10 Branch Pipe Connection . . . . . . . .1551210.11 Manual Gas Shutoff Valves . . . . .1551210.12 Prohibited Devices . . . . . . . . . . . .1551210.13 Systems Containing Gas-Air
Mixtures Outside theFlammable Range . . . . . . . . . . . .155
1210.14 Systems Containing FlammableGas-Air Mixtures . . . . . . . . . . . . . .155
1210.15 Electrical Bonding andGrounding . . . . . . . . . . . . . . . . . . .155
1210.16 Electrical Circuits . . . . . . . . . . . . .1561210.17 Electrical Connections . . . . . . . . .1561211.0 Appliance Connections to
Building Piping . . . . . . . . . . . . . . .1561211.1 Connecting Gas Appliances . . . . .1561211.2 Suspended Low-Intensity
Infrared Tube Heaters . . . . . . . . .1561211.3 Use of Nonmetallic Gas Hose
Connectors . . . . . . . . . . . . . . . . . .1561211.4 Connection of Portable
and Mobile IndustrialGas Appliances . . . . . . . . . . . . . . .156
1211.5 Appliance Shutoff Valvesand Connections . . . . . . . . . . . . . .157
1211.6 Quick-Disconnect Devices . . . . . .1571211.7 Gas Convenience Outlets . . . . . .1571211.8 Sediment Trap . . . . . . . . . . . . . . .1571211.9 Installation of Piping . . . . . . . . . . .1571212.0 Liquefied Petroleum Gas
Facilities and Piping . . . . . . . . . . .1571212.1 General . . . . . . . . . . . . . . . . . . . . .1571213.0 Pressure Testing and Inspection .1571213.1 Piping Installations . . . . . . . . . . . .1571213.2 Test Preparation . . . . . . . . . . . . . .158
xxiUNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
1213.3 Test Pressure . . . . . . . . . . . . . . . .1581213.4 Detection of Leaks and Defects . .1581213.5 Piping Systems Leak Test . . . . . .1581213.6 Purging Requirements . . . . . . . . .158Table 1213.6.1 Size and Length of Piping . . . . . .1591214.0 Interconnections Between
Gas Piping Systems . . . . . . . . . . .1601214.1 Interconnections Supplying
Separate Users . . . . . . . . . . . . . . .1601214.2 Interconnections for Standby
Fuels . . . . . . . . . . . . . . . . . . . . . . .1601215.0 Required Gas Supply . . . . . . . . . .1601215.1 General . . . . . . . . . . . . . . . . . . . . .1601215.2 Volume . . . . . . . . . . . . . . . . . . . . .1601215.3 Gas Appliances . . . . . . . . . . . . . . .1601215.4 Size of Piping Outlets . . . . . . . . . .1601216.0 Required Gas Piping Size . . . . . .1601216.1 Pipe Sizing Methods . . . . . . . . . . .1601216.2 Tables for Sizing Gas Piping
Systems . . . . . . . . . . . . . . . . . . . .1601216.3 Sizing Equations . . . . . . . . . . . . . .160Table 1216.3 Cr and Y for Natural Gas and
Undiluted Propane at StandardConditions . . . . . . . . . . . . . . . . . . .161
1216.4 Sizing of Piping Sections . . . . . . .1611216.5 Engineering Methods . . . . . . . . . .1611216.6 Variable Gas Pressure . . . . . . . . .161Table 1216.2(1) Schedule 40 Metallic Pipe . . . . . .163Table 1216.2(2) Schedule 40 Metallic Pipe . . . . . .164Table 1216.2(3) Schedule 40 Metallic Pipe . . . . . .165Table 1216.2(4) Schedule 40 Metallic Pipe . . . . . .166Table 1216.2(5) Schedule 40 Metallic Pipe . . . . . .167Table 1216.2(6) Schedule 40 Metallic Pipe . . . . . .168Table 1216.2(7) Semi-Rigid Copper Tubing . . . . . .169Table 1216.2(8) Semi-Rigid Copper Tubing . . . . . .170Table 1216.2(9) Semi-Rigid Copper Tubing . . . . . .171Table 1216.2(10) Semi-Rigid Copper Tubing . . . . . .172Table 1216.2(11) Semi-Rigid Copper Tubing . . . . . .173Table 1216.2(12) Semi-Rigid Copper Tubing . . . . . .174Table 1216.2(13) Semi-Rigid Copper Tubing . . . . . .175Table 1216.2(14) Corrugated Stainless Steel
Tubing (CSST) . . . . . . . . . . . . . . .176Table 1216.2(15) Corrugated Stainless Steel
Tubing (CSST) . . . . . . . . . . . . . . .177Table 1216.2(16) Corrugated Stainless Steel
Tubing (CSST) . . . . . . . . . . . . . . .178Table 1216.2(17) Corrugated Stainless Steel
Tubing (CSST) . . . . . . . . . . . . . . .179Table 1216.2(18) Corrugated Stainless Steel
Tubing (CSST) . . . . . . . . . . . . . . .180
Table 1216.2(19) Polyethylene Plastic Pipe . . . . . . .181Table 1216.2(20) Polyethylene Plastic Pipe . . . . . . .182Table 1216.2(21) Polyethylene Plastic Pipe . . . . . . .183Table 1216.2(22) Polyethylene Plastic Tubing . . . . .184Table 1216.2(23) Polyethylene Plastic Tubing . . . . .184Table 1216.2(24) Schedule 40 Metallic Pipe . . . . . .185Table 1216.2(25) Schedule 40 Metallic Pipe . . . . . .186Table 1216.2(26) Schedule 40 Metallic Pipe . . . . . .187Table 1216.2(27) Schedule 40 Metallic Pipe . . . . . .188Table 1216.2(28) Semi-Rigid Copper Tubing . . . . . .189Table 1216.2(29) Semi-Rigid Copper Tubing . . . . . .190Table 1216.2(30) Semi-Rigid Copper Tubing . . . . . .191Table 1216.2(31) Corrugated Stainless Steel
Tubing (CSST) . . . . . . . . . . . . . . .192Table 1216.2(32) Corrugated Stainless Steel
Tubing (CSST) . . . . . . . . . . . . . . .193Table 1216.2(33) Corrugated Stainless Steel
Tubing (CSST) . . . . . . . . . . . . . . .194Table 1216.2(34) Polyethylene Plastic Pipe . . . . . . .195Table 1216.2(35) Polyethylene Plastic Pipe . . . . . . .196Table 1216.2(36) Polyethylene Plastic Tubing . . . . .197
CHAPTER 13 HEALTH CARE FACILITIESAND MEDICAL GAS ANDVACUUM SYSTEMS . . . . . . . . . .199
Part I Special Requirements forHealth Care Facilities . . . . . . . . .199
1301.0 Application . . . . . . . . . . . . . . . . . .1991301.1 Where Required . . . . . . . . . . . . . .1991301.2 Health Care Facilities . . . . . . . . . .1991301.3 Breathing Air Replenishment
(BAR) System . . . . . . . . . . . . . . . .1991302.0 Medical Gas and Vacuum
Piping Systems – InstallationRequirements . . . . . . . . . . . . . . . .199
1302.1 General . . . . . . . . . . . . . . . . . . . . .1991302.2 Manufacturer’s Instructions . . . . .1991302.3 Installation . . . . . . . . . . . . . . . . . .1991302.4 Brazing . . . . . . . . . . . . . . . . . . . . .1991302.5 Documentation . . . . . . . . . . . . . . .1991303.0 Protrusions from Walls . . . . . . . . .1991303.1 Drinking Fountain Control
Valves . . . . . . . . . . . . . . . . . . . . . .1991303.2 Exposed Piping . . . . . . . . . . . . . . .1991304.0 Psychiatric Patient Rooms . . . . . .1991304.1 General . . . . . . . . . . . . . . . . . . . . .1991305.0 Locations for Ice Storage . . . . . . .1991305.1 General . . . . . . . . . . . . . . . . . . . . .1991306.0 Sterilizers . . . . . . . . . . . . . . . . . . .1991306.1 General . . . . . . . . . . . . . . . . . . . . .199
xxii UNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
1306.2 Indirect Waste Connections . . . . .1991307.0 Vapor Vents and Stacks for
Sterilizers . . . . . . . . . . . . . . . . . . .1991307.1 General . . . . . . . . . . . . . . . . . . . . .1991308.0 Aspirators . . . . . . . . . . . . . . . . . . .2001308.1 General . . . . . . . . . . . . . . . . . . . . .200Part II Medical Gas and Vacuum
Systems . . . . . . . . . . . . . . . . . . . .2001309.0 Application . . . . . . . . . . . . . . . . . .2001309.1 General . . . . . . . . . . . . . . . . . . . . .2001309.2 Purpose . . . . . . . . . . . . . . . . . . . .2001309.3 Terms . . . . . . . . . . . . . . . . . . . . . .2001309.4 Portable Compressed Gas
Systems . . . . . . . . . . . . . . . . . . . .2001309.5 Where Not Applicable . . . . . . . . . .2001309.6 Requirements . . . . . . . . . . . . . . . .2001309.7 Existing Systems . . . . . . . . . . . . .2001310.0 General Requirements . . . . . . . . .2001310.1 Oxygen Compatibility . . . . . . . . . .2001310.2 Certification . . . . . . . . . . . . . . . . . .2001310.3 Documentation . . . . . . . . . . . . . . .2001310.4 Supply Source . . . . . . . . . . . . . . .2011310.5 Health Care Organization
Personnel . . . . . . . . . . . . . . . . . . .2011310.6 Brazing Procedures . . . . . . . . . . .2011311.0 Plan Review . . . . . . . . . . . . . . . . .2011311.1 Plans and Specifications . . . . . . .2011311.2 Requirements . . . . . . . . . . . . . . . .2011311.3 Extent of Work . . . . . . . . . . . . . . .2011311.4 Record . . . . . . . . . . . . . . . . . . . . .2011312.0 System Performance . . . . . . . . . .2011312.1 Required Operating Pressures . . .2011312.2 Minimum Flow Rates . . . . . . . . . .2011312.3 Minimum Station Outlets/Inlets . . .201Table 1312.1 Standard Designation Colors
and Operating Pressures forGas and Vacuum Systems . . . . . .202
Table 1312.2 Minimum Flow Rates . . . . . . . . . .2021313.0 Required Pipe Sizing . . . . . . . . . .2021313.1 Maximum Demand . . . . . . . . . . . .2021313.2 Sizing Procedures . . . . . . . . . . . .202Table 1312.3 Minimum Outlets/Inlets per
Station . . . . . . . . . . . . . . . . . . . . .2031313.3 Engineering Methods . . . . . . . . . .2031314.0 Workmanship . . . . . . . . . . . . . . . .2031314.1 Accepted Engineering
Practices . . . . . . . . . . . . . . . . . . . .2031314.2 Imperfections . . . . . . . . . . . . . . . .2031314.3 Burred Ends . . . . . . . . . . . . . . . . .203
1315.0 Materials . . . . . . . . . . . . . . . . . . . .2031315.1 General . . . . . . . . . . . . . . . . . . . . .2031315.2 Cleaning . . . . . . . . . . . . . . . . . . . .2031315.3 Delivery . . . . . . . . . . . . . . . . . . . . .203Table 1313.1 System Sizing – Flow
Requirements for StationInlet/Outlet . . . . . . . . . . . . . . . . . .204
Table 1313.2 Size of Gas/Vacuum Piping . . . . .2041315.4 Tubes . . . . . . . . . . . . . . . . . . . . . .2041315.5 Changes in Direction . . . . . . . . . .2051315.6 Special Fittings . . . . . . . . . . . . . . .2051315.7 Prohibited Joints . . . . . . . . . . . . . .2051315.8 Shutoff Valves . . . . . . . . . . . . . . . .2051315.9 Soldered Joints . . . . . . . . . . . . . . .2051316.0 Cleaning for Medical Gas
Piping Systems . . . . . . . . . . . . . . .2051316.1 Cleaning . . . . . . . . . . . . . . . . . . . .2051316.2 Contaminated Materials . . . . . . . .2051317.0 Installation of Piping . . . . . . . . . . .2051317.1 Pipe Protection . . . . . . . . . . . . . . .2051317.2 Location . . . . . . . . . . . . . . . . . . . .2061317.3 Frost Protection . . . . . . . . . . . . . .2061317.4 Underground Piping . . . . . . . . . . .2061317.5 Connectors . . . . . . . . . . . . . . . . . .2061317.6 Positive-Pressure Medical
Gas Piping DistributionSystems . . . . . . . . . . . . . . . . . . . .206
1317.7 Support . . . . . . . . . . . . . . . . . . . . .2061317.8 Seismic Provisions . . . . . . . . . . . .2061317.9 Testing . . . . . . . . . . . . . . . . . . . . .2061317.10 Labeled . . . . . . . . . . . . . . . . . . . . .2061318.0 Joints . . . . . . . . . . . . . . . . . . . . . .2071318.1 General . . . . . . . . . . . . . . . . . . . . .2071318.2 Brazed Joints . . . . . . . . . . . . . . . .2071318.3 Tube Ends . . . . . . . . . . . . . . . . . .2071318.4 Cleaning Procedures . . . . . . . . . .207Table 1317.7 Maximum Pipe Support
Spacing . . . . . . . . . . . . . . . . . . . . .2071318.5 Flux . . . . . . . . . . . . . . . . . . . . . . . .2081318.6 Heat and Brazing . . . . . . . . . . . . .2081318.7 Purge Gas . . . . . . . . . . . . . . . . . .2081318.8 Prohibited Joints . . . . . . . . . . . . . .2081319.0 Valves – Requirements,
Locations, and Labeling . . . . . . . .2091319.1 General Requirements . . . . . . . . .2091319.2 In-Line Shutoff Valves . . . . . . . . . .2091319.3 Future Piping . . . . . . . . . . . . . . . .2091319.4 Source Valves . . . . . . . . . . . . . . . .2091319.5 Main Valves . . . . . . . . . . . . . . . . .209
xxiiiUNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
1319.6 Riser Valves . . . . . . . . . . . . . . . . .2091319.7 Zone Valves . . . . . . . . . . . . . . . . .2101319.8 Service Valves . . . . . . . . . . . . . . .2101320.0 Pressure-Regulating Equipment . .2101320.1 Where Required . . . . . . . . . . . . . .2101320.2 Pressure-Relief Valves . . . . . . . . .2101320.3 Pressure Gauges . . . . . . . . . . . . .2101321.0 Station Outlets/Inlets . . . . . . . . . .2101321.1 General . . . . . . . . . . . . . . . . . . . . .2101321.2 Post Installation . . . . . . . . . . . . . .2101322.0 Labeling and Identification . . . . . .2101322.1 General . . . . . . . . . . . . . . . . . . . . .2101322.2 Pipe Labeling . . . . . . . . . . . . . . . .2101322.3 Shutoff Valve Identification . . . . . .2111322.4 Station Outlet/Inlet
Identification . . . . . . . . . . . . . . . . .2111322.5 Shutoff Valve Labeling . . . . . . . . .2111323.0 Alarms . . . . . . . . . . . . . . . . . . . . . .2111323.1 General . . . . . . . . . . . . . . . . . . . . .2111323.2 Components . . . . . . . . . . . . . . . . .2111324.0 Medical Air System . . . . . . . . . . . .2111324.1 General . . . . . . . . . . . . . . . . . . . . .2111324.2 Medical Air Compressors . . . . . . .2111324.3 Air Source . . . . . . . . . . . . . . . . . . .2121324.4 Air Intakes . . . . . . . . . . . . . . . . . . .2121324.5 Drains . . . . . . . . . . . . . . . . . . . . . .2121324.6 Medical Air Receivers . . . . . . . . . .2121324.7 Requirements for Medical Air
Receivers . . . . . . . . . . . . . . . . . . .2121325.0 Medical Vacuum Pump System . .2121325.1 General . . . . . . . . . . . . . . . . . . . . .2121325.2 Medical-Surgical Vacuum
Sources . . . . . . . . . . . . . . . . . . . .2121325.3 Exhausts . . . . . . . . . . . . . . . . . . . .2131325.4 Receivers . . . . . . . . . . . . . . . . . . .2131325.5 Piping . . . . . . . . . . . . . . . . . . . . . .2131325.6 Drains . . . . . . . . . . . . . . . . . . . . . .2131326.0 Testing and Inspection . . . . . . . . .2131326.1 Where Required . . . . . . . . . . . . . .2131326.2 Systems . . . . . . . . . . . . . . . . . . . .2141326.3 Advance Notice . . . . . . . . . . . . . .2141326.4 Responsibility . . . . . . . . . . . . . . . .2141326.5 Testing . . . . . . . . . . . . . . . . . . . . .2141326.6 Retesting . . . . . . . . . . . . . . . . . . .2141326.7 Initial Pressure Test – Piped
Gas Systems . . . . . . . . . . . . . . . .2141326.8 Cross-Connection Test – Piped
Gas Systems . . . . . . . . . . . . . . . .214
1326.9 Standing Pressure Test – PipedGas Systems . . . . . . . . . . . . . . . .214
1326.10 Initial Pressure Test – PipedVacuum Systems . . . . . . . . . . . . .215
1326.11 Standing Pressure Test – PipedVacuum Systems . . . . . . . . . . . . .215
1326.12 Corrections . . . . . . . . . . . . . . . . . .2151326.13 Approval . . . . . . . . . . . . . . . . . . . .2151326.14 Covering or Use . . . . . . . . . . . . . .2151326.15 Uncovering . . . . . . . . . . . . . . . . . .2151327.0 System Certification . . . . . . . . . . .2151327.1 Certification . . . . . . . . . . . . . . . . . .2151327.2 Certification Tests . . . . . . . . . . . . .2151327.3 Reports . . . . . . . . . . . . . . . . . . . . .2161327.4 Report Items . . . . . . . . . . . . . . . . .216
CHAPTER 14 REFERENCEDSTANDARDS . . . . . . . . . . . . . . . .217
1401.0 General . . . . . . . . . . . . . . . . . . . . .2171401.1 Standards . . . . . . . . . . . . . . . . . . .217Table 1401.1 Referenced Standards . . . . . . . . .217
CHAPTER 15 FIRESTOP PROTECTION . . . . . .2411501.0 General . . . . . . . . . . . . . . . . . . . . .2411501.1 Applicability . . . . . . . . . . . . . . . . . .2411502.0 Plans and Specifications . . . . . . .2411502.1 Penetrations . . . . . . . . . . . . . . . . .2411503.0 Installation . . . . . . . . . . . . . . . . . .2411503.1 Materials . . . . . . . . . . . . . . . . . . . .2411504.0 Combustible Piping
Installations . . . . . . . . . . . . . . . . . .2411504.1 General Requirements . . . . . . . . .2411504.2 Fire-Resistance Rating . . . . . . . . .2411504.3 Firestop Systems . . . . . . . . . . . . .2411504.4 Connections . . . . . . . . . . . . . . . . .2411504.5 Insulation and Coverings . . . . . . .2411504.6 Sleeves . . . . . . . . . . . . . . . . . . . . .2411505.0 Noncombustible Piping
Installations . . . . . . . . . . . . . . . . . .2411505.1 General Requirements . . . . . . . . .2411505.2 Fire-Resistance Rating . . . . . . . . .2411505.3 Firestop Systems . . . . . . . . . . . . .2411505.4 Connections . . . . . . . . . . . . . . . . .2421505.5 Unshielded Couplings . . . . . . . . . .2421505.6 Sleeves . . . . . . . . . . . . . . . . . . . . .2421505.7 Insulation and Coverings . . . . . . .2421506.0 Required Inspection . . . . . . . . . . .2421506.1 General . . . . . . . . . . . . . . . . . . . . .2421506.2 Examination . . . . . . . . . . . . . . . . .242
xxiv UNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
1506.3 Penetrations . . . . . . . . . . . . . . . . .2421506.4 Field Installations . . . . . . . . . . . . .242
CHAPTER 16 ALTERNATE WATERSOURCES FORNONPOTABLEAPPLICATIONS . . . . . . . . . . . . . .243
1601.0 General . . . . . . . . . . . . . . . . . . . . .2431601.1 Applicability . . . . . . . . . . . . . . . . . .2431601.2 System Design . . . . . . . . . . . . . . .2431601.3 Permit . . . . . . . . . . . . . . . . . . . . . .2431601.4 Component Identification . . . . . . .2431601.5 Maintenance and Inspection . . . .2431601.6 Operation and Maintenance
Manual . . . . . . . . . . . . . . . . . . . . .2431601.7 Minimum Water Quality
Requirements . . . . . . . . . . . . . . . .243Table 1601.5 Minimum Alternate Water
Source Testing, Inspection,and Maintenance Frequency . . . .244
1601.8 Material Compatibility . . . . . . . . . .2441601.9 System Controls . . . . . . . . . . . . . .2441602.0 Gray Water Systems . . . . . . . . . .2441602.1 General . . . . . . . . . . . . . . . . . . . . .2441602.2 System Requirements . . . . . . . . .2441602.3 Connections to Potable and
Reclaimed (Recycled) WaterSystems . . . . . . . . . . . . . . . . . . . .245
1602.4 Location . . . . . . . . . . . . . . . . . . . .245Table 1602.4 Location of Gray Water System . .2451602.5 Plot Plan Submission . . . . . . . . . .2451602.6 Prohibited Location . . . . . . . . . . . .2451602.7 Drawings and Specifications . . . .2451602.8 Procedure for Estimating
Gray Water Discharge . . . . . . . . .2461602.9 Gray Water System
Components . . . . . . . . . . . . . . . . .2461602.10 Subsurface Irrigation
System Zones . . . . . . . . . . . . . . . .247Table 1602.10 Design of Six Typical Soils . . . . . .2471602.11 Subsurface and Subsoil
Irrigation Field, and MulchBasin Design and Construction . .247
Table 1602.11 Subsurface Irrigation DesignCriteria for Six Typical Soils . . . . .247
Table 1602.11.3 Subsoil Irrigation FieldConstruction . . . . . . . . . . . . . . . . .248
1602.12 Gray Water System Color and MarkingInformation . . . . . . . . . . . . . . . . . .248
1602.13 Other Collection andDistribution Systems . . . . . . . . . . .248
1602.14 Testing . . . . . . . . . . . . . . . . . . . . .2491602.15 Maintenance . . . . . . . . . . . . . . . . .2491603.0 Reclaimed (Recycled) Water
Systems . . . . . . . . . . . . . . . . . . . .2491603.1 General . . . . . . . . . . . . . . . . . . . . .2491603.2 Permit . . . . . . . . . . . . . . . . . . . . . .2491603.3 System Changes . . . . . . . . . . . . .2491603.4 Connections to Potable or
Reclaimed (Recycled)Water Systems . . . . . . . . . . . . . . .249
1603.5 Initial Cross-Connection Test . . . .2491603.6 Reclaimed (Recycled) Water
System Materials . . . . . . . . . . . . .2491603.7 Reclaimed (Recycled) Water
System Color and MarkingInformation . . . . . . . . . . . . . . . . . .249
1603.8 Valves . . . . . . . . . . . . . . . . . . . . . .2491603.9 Installation . . . . . . . . . . . . . . . . . .2491603.10 Signs . . . . . . . . . . . . . . . . . . . . . . .2501603.11 Inspection and Testing . . . . . . . . .2501603.12 Sizing . . . . . . . . . . . . . . . . . . . . . .2511604.0 On-Site Treated Nonpotable
Water Systems . . . . . . . . . . . . . . .2511604.1 General . . . . . . . . . . . . . . . . . . . . .2511604.2 Plumbing Plan Submission . . . . . .2511604.3 System Changes . . . . . . . . . . . . .2511604.4 Connections to Potable or
Reclaimed (Recycled) WaterSystems . . . . . . . . . . . . . . . . . . . .251
1604.5 Initial Cross-Connection Test . . . .2511604.6 On-Site Treated Nonpotable
Water System Materials . . . . . . . .2511604.7 On-Site Treated Nonpotable
Water Devices and Systems . . . .2511604.8 On-Site Treated Nonpotable
Water System Color andMarking Information . . . . . . . . . . .251
1604.9 Valves . . . . . . . . . . . . . . . . . . . . . .2511604.10 Design and Installation . . . . . . . . .2511604.11 Signs . . . . . . . . . . . . . . . . . . . . . . .2521604.12 Inspection and Testing . . . . . . . . .2521604.13 Sizing . . . . . . . . . . . . . . . . . . . . . .253
CHAPTER 17 NONPOTABLE RAINWATERCATCHMENT SYSTEMS . . . . . . .255
1701.0 General . . . . . . . . . . . . . . . . . . . . .2551701.1 Applicability . . . . . . . . . . . . . . . . . .2551702.0 Nonpotable Rainwater
Catchment Systems . . . . . . . . . . .2551702.1 General . . . . . . . . . . . . . . . . . . . . .255
xxvUNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
1702.2 Plumbing Plan Submission . . . . . .2551702.3 System Changes . . . . . . . . . . . . .2551702.4 Connections to Potable or
Reclaimed (Recycled)Water Systems . . . . . . . . . . . . . . .255
1702.5 Initial Cross-Connection Test . . . .2551702.6 Sizing . . . . . . . . . . . . . . . . . . . . . .2551702.7 Rainwater Catchment System
Materials . . . . . . . . . . . . . . . . . . . .2551702.8 Rainwater Catchment System
Color and MarkingInformation . . . . . . . . . . . . . . . . . .255
1702.9 Design and Installation . . . . . . . . .2551702.10 Signs . . . . . . . . . . . . . . . . . . . . . . .2571702.11 Inspection and Testing . . . . . . . . .257
APPENDICES TABLE OF CONTENTS . . . . . . . .259Appendix A Recommended Rules for
Sizing the Water SupplySystem . . . . . . . . . . . . . . . . . . . . .261
Appendix B Explanatory Notes onCombination Waste and VentSystems . . . . . . . . . . . . . . . . . . . .271
Appendix C Alternate Plumbing Systems . . . .273Appendix D Sizing Storm Water Drainage
Systems . . . . . . . . . . . . . . . . . . . .281Appendix E Manufactured/Mobile Home
Parks and RecreationalVehicle Parks . . . . . . . . . . . . . . . .289
Appendix F Firefighter Breathing AirReplenishment Systems . . . . . . . .301
Appendix G Sizing of Venting SystemsServing Appliances Equippedwith Draft Hoods, Category IAppliances, and AppliancesListed for Use with Type BVents . . . . . . . . . . . . . . . . . . . . . . .305
Appendix H Private Sewage DisposalSystems . . . . . . . . . . . . . . . . . . . .315
Appendix I Installation Standards . . . . . . . . . .325Appendix J Combination of Indoor and
Outdoor Combustion andVentilation Opening Design . . . . .431
Appendix K Potable Rainwater CatchmentSystems . . . . . . . . . . . . . . . . . . . .433
Appendix L Sustainable Practices . . . . . . . . . .437
USEFUL TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . .451
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . .459
xxvi UNIFORM PLUMBING CODE
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.
101.0 General.101.1 Title. This document shall be known as the “UniformPlumbing Code,’’ may be cited as such, and will be referredto herein as “this code.’’101.2 Scope. The provisions of this code shall apply to theerection, installation, alteration, repair, relocation, replace-ment, addition to, use, or maintenance of plumbing systemswithin this jurisdiction.101.3 Purpose. This code is an ordinance providing mini-mum requirements and standards for the protection of thepublic health, safety, and welfare.101.4 Conflicts Between Codes. Where the require-ments within the jurisdiction of this plumbing code conflictwith the requirements of the mechanical code, this code shallprevail. In instances where the code, applicable standards, orthe manufacturer’s installation instructions conflict, the morestringent provisions shall prevail. Where there is a conflictbetween a general requirement and a specific requirement,the specific requirement shall prevail.101.5 Plans Required. The Authority Having Jurisdictionshall be permitted to require the submission of plans, speci-fications, drawings, and such other information in accordancewith the Authority Having Jurisdiction, prior to the com-mencement of, and at a time during the progress of, work reg-ulated by this code.
The issuance of a permit upon plans and specificationsshall not prevent the Authority Having Jurisdiction fromthereafter requiring the correction of errors in said plans andspecifications or from preventing construction operationsbeing carried on thereunder where in violation of this code orof other pertinent ordinance or from revoking a certificate ofapproval where issued in error.101.6 Repairs and Alterations. In existing buildings orpremises in which plumbing installations are to be altered,repaired, or renovated, deviations from the provisions of thiscode are permitted, provided such deviations are found to benecessary and are first approved by the Authority HavingJurisdiction.
101.6.1 Building Sewers and Drains. Existingbuilding sewers and building drains shall be permitted tobe used in connection with new buildings or new plumb-ing and drainage work where they are found on exami-nation and test to be in accordance with the requirementsgoverning new work, and the proper Authority HavingJurisdiction shall notify the owner to make changes nec-essary to be in accordance with this code. No building, orpart thereof, shall be erected or placed over a part of adrainage system that is constructed of materials otherthan those approved elsewhere in this code for use underor within a building.
101.6.2 Openings. Openings into a drainage or ventsystem, excepting those openings to which plumbing fix-tures are properly connected or which constitute vent ter-minals, shall be permanently plugged or capped in anapproved manner, using the appropriate materials inaccordance with this code.
101.7 Maintenance. The plumbing and drainage system ofa premises under the Authority Having Jurisdiction shall bemaintained in a sanitary and safe operating condition by theowner or the owner’s agent.101.8 Existing Construction. No provision of this codeshall be deemed to require a change in a portion of a plumb-ing or drainage system or other work regulated by this codein or on an existing building or lot where such work wasinstalled and is maintained in accordance with law in effectprior to the effective date of this code, except where suchplumbing or drainage system or other work regulated by thiscode is determined by the Authority Having Jurisdiction tobe in fact dangerous, unsafe, insanitary, or a nuisance and amenace to life, health, or property.101.9 Additions, Alterations, or Repairs. Additions,alterations, repairs, and replacement of plumbing systemsshall comply with the provisions for new systems except asotherwise provided in Section 101.11.101.10 Appendices. The provisions in the appendices areintended to supplement the requirements of this code andshall not be considered part of this code unless formallyadopted as such.101.11 Application to Existing Plumbing System.Additions, alterations, or repairs shall be permitted to be madeto a plumbing system without requiring the existing plumb-ing system to be in accordance with the requirements of thiscode, provided the addition, alteration, or repair is in accor-dance with that required for a new plumbing system. Addi-tions, alterations, or repairs shall not cause an existing systemto become unsafe, insanitary, or overloaded.
101.11.1 Health and Safety. Where compliance withthe provisions of this code fail to eliminate or alleviate anuisance, or other dangerous or insanitary condition thatinvolves health or safety hazards, the owner or theowner’s agent shall install such additional plumbing anddrainage facilities or shall make such repairs or alter-ations as ordered by the Authority Having Jurisdiction.101.11.2 Existing Installation. Plumbing systemslawfully in existence at the time of the adoption of thiscode shall be permitted to have their use, maintenance, orrepair continued where the use, maintenance, or repair isin accordance with the original design and location andno hazard to life, health, or property has been created bysuch plumbing system.
12012 UNIFORM PLUMBING CODE
CHAPTER 1ADMINISTRATION
This is a preview of "IAPMO/ANSI UPC-2012". Click here to purchase the full version from the ANSI store.