15
Cell Site No. 1CS4693 Cell Site Name: Prairie Creek Fixed Asset No. 10087694 Market: Wichita MSA/BTA Address: 1607 East Central, Andover, KS 67002 FIFTH AMENDMENT TO TOWER LEASE AGREEMENT THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT ("Fifth Amendment"), dated as of the latter of the signature dates below, is by and between the City of Andover, Kansas, a Municipal Corporation, having a mailing address of P.O. Box 295, 1609 E Central, Andover, Kansas 67002 (hereinafter referred to as ■'Landlord") and New Cingular Wireless PCS, LLC, a Delaware limited liability company, having a mailing address of 575 Morosgo Drive NE, Atlanta, OA 30324 (hereinafter referred to as "Tenant"). WHEREAS, Landlord and Tenant entered into a Tower Lease Agreement dated June 14, 2005, as amended by a First Amendment dated June 24, 2008, a Second Amendment dated April 24, 2012, a Third Amendment dated January 26, 2016 and a Fourth Amendment dated October 11, 2016 (collectively referred to as the "Agreement") whereby Landlord leased to Tenant certain Leased Property, therein described, that are a portion of the Tower Site and Tower located at 1607 East Central, Andover, KS 67002; and WHEREAS, Landlord and Tenant desire to amend the Agreement to allow Tenant to modify equipment on the Leased Property and to adjust the rent in conjunction with the modifications to the Agreement contained herein; and WHE^AS, Landlord and Tenant, in their mutual interest, wish to amend the Agreement as set forth below accordingly. NOW THEREFORE, in consideration of the foregoing and other good and valuable consideration, the receipt and sujficiency of which are hereby acknowledged. Landlord and Tenant agree as follows: 1. Rent. Article 2 of the Agreement is hereby amended such that the monthly rent shall be increased by Two Hundred Thirty-Seven Dollars and Fifty Cents ($237.50). Said additional rent shall commence upon issuance of NTP or June 12, 2018, whichever occurs first. 2. Equip] set m : foit ent. The parties acknowledge that Tenant may add additional equipment to the Leased Property as h in Exhibit 1 of this Fifth Amendment. l 3. Other Terms and Conditions Remain. In the event of any inconsistencies between the Agreement and this Fifth Amendment, the terms of this Fifth Amendment shall control. Except as expressly set forth in this Fifth Amendment, the Agreement otherwise is unmodified and remains in full force and effect. Each reference in the Agreement to itself shall be deemed also to refer to this Fifth Amendment. 4. Capitalized Terms. All capitalized terms used but not defined herein shall have the same meanings as defined in the Agreement. 20180412 Additional Equipment 2018

THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

Cell Site No. 1CS4693

Cell Site Name: Prairie Creek

Fixed Asset No. 10087694

Market: Wichita MSA/BTA

Address: 1607 East Central, Andover, KS 67002

FIFTH AMENDMENT TO TOWER LEASE AGREEMENT

THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT ("Fifth Amendment"), dated as of thelatter of the signature dates below, is by and between the City of Andover, Kansas, a Municipal Corporation,having a mailing address of P.O. Box 295, 1609 E Central, Andover, Kansas 67002 (hereinafter referred to as■'Landlord") and New Cingular Wireless PCS, LLC, a Delaware limited liability company, having a mailingaddress of 575 Morosgo Drive NE, Atlanta, OA 30324 (hereinafter referred to as "Tenant").

WHEREAS, Landlord and Tenant entered into a Tower Lease Agreement dated June 14, 2005, as amendedby a First Amendment dated June 24, 2008, a Second Amendment dated April 24, 2012, a Third Amendment datedJanuary 26, 2016 and a Fourth Amendment dated October 11, 2016 (collectively referred to as the "Agreement")whereby Landlord leased to Tenant certain Leased Property, therein described, that are a portion of the Tower Siteand Tower located at 1607 East Central, Andover, KS 67002; and

WHEREAS, Landlord and Tenant desire to amend the Agreement to allow Tenant to modify equipment onthe Leased Property and to adjust the rent in conjunction with the modifications to the Agreement contained herein;and

WHE^AS, Landlord and Tenant, in their mutual interest, wish to amend the Agreement as set forth belowaccordingly.

NOW THEREFORE, in consideration of the foregoing and other good and valuable consideration, thereceipt and sujficiency of which are hereby acknowledged. Landlord and Tenant agree as follows:

1. Rent. Article 2 of the Agreement is hereby amended such that the monthly rent shall be increased by TwoHundred Thirty-Seven Dollars and Fifty Cents ($237.50). Said additional rent shall commence uponissuance of NTP or June 12, 2018, whichever occurs first.

2. Equip]set

m: foit

ent. The parties acknowledge that Tenant may add additional equipment to the Leased Property ash in Exhibit 1 of this Fifth Amendment.l

3. Other Terms and Conditions Remain. In the event of any inconsistencies between the Agreement andthis Fifth Amendment, the terms of this Fifth Amendment shall control. Except as expressly set forth inthis Fifth Amendment, the Agreement otherwise is unmodified and remains in full force and effect. Eachreference in the Agreement to itself shall be deemed also to refer to this Fifth Amendment.

4. Capitalized Terms. All capitalized terms used but not defined herein shall have the same meanings asdefined in the Agreement.

20180412Additional Equipment

2018

Page 2: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

IN WITNESS WHEREOF, the parties have caused this Fifth Amendment to be effective as of the last datewritten below.

WITNESSES:

Print Name:

Print Name:

Print Name:

"LANDLORD"

City of Andover, Kansasa municipal corporation

By:Print Name:Its:

Date:

"TENANT"

New Cingular Wireless PCS, LLC,a Delaware limited liability companyBy: AT&T Mobility CorporationIts: Manager

Print Name:

By: .Print Name: MICHAEL BRIDWETT.Its: Area Mgr - Const & EngDate: f. | ̂

[ACKNOWLEDGMENTS APPEAR ON THE NEXT PAGE]

12.22.15

Additional Equipment Space Lease2015

Page 3: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

TENANT ACKNOWLEDGMENT

STATE OF

COUNTY OF St

J) ss:

J

acknowledged under oath that he is theManager of New Cingular Wireless PCS, LLC, the company named as Tenant in the attached instrument, and assuch was authorized to execute this instrument on behalf of the company.

A. CARSONNotary Public - Notary Seal

STATE OF MISSOURICommissioned for Saint Louis CountyMy Commission Expires: October 13,2019

Commission # 15698277

O-Notary Public:

jQ

My Commission Expires:

LANDLORD ACKNOWLEDGMENT

STATE OF KANSAS }) ss:

COUNTY OF BUTLER )

I CERTIFY that onrepresentative] personally came before me and acknowledged under oath that he or she:

_, 2018, [name of

(a) is the [title] of the City of Andover, the municipal corporation named in theattached instrument,

(b) was authorized to execute this instrument on behalf of the municipal corporation and(c) executed the instrument as the act of the municipal corporation.

Notary Public:My Commission Expires:

12.22.15

Additional Equipment Space Lease2015

Page 4: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

See attached construction drawings prepared by Black & Veatch and comprised of 11 pages.

Notes:

1. This

once

2. Anyby

3. Width

police4. The

illust^;

the

E

EXHIBIT 1

xhibit may be replaced by a land survey and/or construction drawings of the Leased Propertyit is received by Tenant.etback of the Leased Property from the Tower Site's boundaries shall be the distance requiredapplicable governmental authorities.of access road shall be the width required by the applicable governmental authorities, includingand fire departments.

type, number and mounting positions and locations of antennas and transmission lines areative only. Actual types, numbers and mounting positions may vary from what is shown above.

12.22.15

Additional Equipment Space Lease2015

Page 5: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

PRAIRIE CREEK

KS4693

10087694

LTE 50 FIRSTNET/BWE

190'-2"-MONOPOLESITE INFORMATION

CITY OF ANDOVtR. KS♦730 NORTH 2i7TH STREETWEST ANCMLE. KS 67001

9r 07" 05.10" W-97.11606

CONTACT INFORMATION

BLACK ft VEATCH CORPORATION6600 W, 115TH ST. SUITE 2292OVERLAND PARK. KS 66211

SITE LOCATION MAP

GENERAL NOTES

THE FACILITY IS UNMANNED AND NOT FOR HUMAN HABITATION. A TECHNICIAN WILL VISIT THE SITE AS REOUIRED FOR ROUTINE MAINTENANCE. WEPROJECT WILL NOT RESULT IN ANY SIGNIFICANT DISTURBANCE OR EFFECT ON DRAINAGE; NO SANITARY SEWER SERVICE, POTABLE WATER. OR TRASHDISPOSAL IS REOUIRED AND NO COMMERCIAL SIGNACE IS PROPOSED.

ENGINEERING

2012 INTERNATIONW. BUILDING CODE OR ADOPTED CODE2011 NATIONAL ELECTRIC CODE OR ADOPTED CODE

T1A/EIA-222-C OR ADOPTED CODE

DRAWING INDEX

SHEET NO: SHEET TITLE

11"x17" PLOT WILL BE HALF SCALE UNLESS OTHERWISE NOTED

CONTRACTOR SHAa VERIFY ALL PLANS ft EXISTING DIMENSIONS ft CONO<TtONS ONTHE JOB Sm ft SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING OF ANY DISCREPANCIES

BEFORE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR SAME

UTIUT1E8 PROTECTiON CENTER. INC.

^at&t

BLACK & VEATCH

6800 W. 115TH ST. SUITE 2292OVERLAND PARK, KS 6621 1

(913) 458-2000

PRAIRIE CREEK

KS4693

1607 EAST CENTRAL

ANDOVER, KS 67002

LTE 5C FIRSTNET/BWE

Page 6: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

-INSTMl (1) PHOPOSCD NOKM— '■) PROPOSED OCU

HICSSION UNIT INPROPOSED FIT RACK

vWWWWV

JL

EXISTING INSPECTIONWELL (TYP)

EXISTING COAXENTRY PORT (TYP)

ANTENNA (TYP)

^\\\\\\\\\\^ K\\\\\\\\\NSN

1. CONTRACTOR SHAU nELO VtWFY AU DIMENSIONS.

2. CONTRACTOR SHAU HELD VDflFY EXISTING HVACUNITS. IF LESS THAN 3 TON RATING. CONTRACTOR»HAa REMOVE EXISTING UNITS AND REPLACE WITM 3TON RATED UNITS, MATCHIIW EXISTINGMANUFACTURER.

3. PROPOSED LTE BBU TO BE INSTALLED ANDGROUNDED BY OTHERS, PER ATStT INSTALLATIONSTANBWaiS^

4. EXISTING RACK MOUNTED DCS SURGE SUPPRESSIONUNIT »4Aa BE UPGRADED WITH PROPOSED MODULESOR SWAPPED OUT FOR PROPOSED RACK MOUNTEDDC12 SURGE SUPPRESSION UNIT, WHEN REQUIREDFOR UPGRADE.

NOTES

(1) PROPOSED DOT2 SURGE SUPPRESSION UNIT(1) PROPOSED NOKIA BBU (BY OTHERS)(1) PROPOSED FIBER STORAGE BOX0) PROPOSED Fir RACK

GROUND SCOPE OF WORK

CABU ENTRY BOOT, PART#CX402-CB42D210 (ORENGINECR APPROVED EQUAL)

FINAL EQUIPMENT LAYOUT

at&t

BLACK &VEATCH

6800 W. 115TH ST, SUITE 2292OVERl^O PARK, KS 662T1

(913) 458-2000

12/24/17 ISSUEO FOR REVIEW

I A WOLATION OF LAW FDR ANT PERSON,

TO ALTER THB OOCUMCNT.

PRAIRIE CREEKK54693

1607 EAST CENTRALANDOVER, KS 67002

LTE 5C FIRSTNET/BWE

SHEET TTTLE

EQUIPMENT LAYOUT

SHEET NUMBER

C-1

Page 7: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

THIS DOCUMENT WAS PREPARED BASED DN THEINFORMATION PROVIDED TO BLACK * YEATCH. IFEXISTING CONDITIONS DO NOT REFUCT THOSEREPRESENTED. THESE CONSTRUCTION DRAWINGSARE NO LONGER VALID.

CL EU 17B'-0** AGL V

cabubTo" iwo«r2"^njaCONDUIT ALONG EXISTING AT*TCABU ROUTE. SEE NOTE #3

FINAL ELEVATION12" 8' 4' 0

(6) EXISTING ANTENNAS(B) EXISTING RRHs

(6) PROPOSED ANTENNAS(12) PROPOSED RRH»

PROPOSED 006 SURGE SUPPRESSION UNIT

PROPOSED nBER TRUNK

PROPOSED DC POWER TRUNKS

PROPOSED 2" FLEX CONDUIT

TOWER SCOPE OF WORK

THE EXISTING TOINER SHAU BE ANALYZED TO DETERMINE ITSSTRUCTURAL CAPACITY TO SUPPORT THE EXISTING AND PROPOSEDCABLES AND ANTENNAS. THESE DRAWINGS HAVE BEEN CREATED BASEDON THE AS^MPTION THAT THE TOWER HAS SUFFICIENT CAPACITY TOSUPPORT THE EXISTING AND PROPOSED LOADING CONTAINED WITHINTHESE DRAWINGS. NO WORK SHALL COMMENCE ON THIS TOWER UNTILA PASSING STRUCTURAL ANALY56 OR STRUCTURN. OPINION LETTER HASBEEN RECEIVED. APPROVED BY THE TOWER OWNER OR ATRT. ANDREVIEWED BY BLACK & VEATCH.

STRUCTURAL ANALYSIS NOTE

THE EXISTING ANTENNA MOUNTS ARE CURRENTLY BEING ANALYZEDBY BLACK ft VEATCH TO DETERMINE THOR STRUCTURAL CAPACITYTO SUPPORT THE PROPOSED NEW LOADING. THESE DRAWINGSHAVE BEEN CREATED BASED ON THE ASSUMPTION THAT THEANTENNA MOUNT ANALYSIS Wia SHOW THAT THE ANTENNAMOUNTS HAVE SUFFICIENT CAPACITY TO SUPPORT THE PROPOSEDNEW LOADING. INSTALUTION OF THE PROPOSED NEW LOADINGSHAa NOT COMMENCE UNTIL AN APPROVED ANTENNA MOUNTSANALYSIS HAS BEEN RECEIVED BY THE OWNER OR ATftT AND HASBEEN REVIEWED BY BLACK ft VEATCH.

MOUNT ANALYSIS NQTF

1. GROUND EQUIPMENT NOT SHOWN FOR CLARITY.

2. ANY ADDITIONAL EQUIPMENT NOTED ON THE STRUCTURAL ANALYSISSHOULD BE CONSIDERED AS RESERVED LOADING. WHICH COULD BEINSTALLED AT A FUTURE DATE.

OENERAL NOTES

at&t

BLACK & VEATCH

OVERI^I15TH ST, SUITE 2292,J0 PARK. KS 66211913) 458-2000

SSUEO FOR RCVICW

PRAIRIE CREEK

KS4693

1607 EAST CENTRAL

ANDOVER, KS 67002LTE 5C FIRSTNET/BWE

SHEET TITLE

ELEVATION

C-2

Page 8: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

mm.

IB

-•saiir'

.

AOMUftf

A,KATHREfN742266

UMTS 13KATHREIN

74226613

- -

A2* ANDREW

SBNHH-1D65CLTE 3C 13

OLHNTCL0S86S12-2

LTE 3C/BWE 13- -

ALCATEL-LUCENT825 RRH4x30-4ii

ALCATEL-LUCENTB66A-RRH4X45

AS« ANDREW

SBNHH-106565CLTE 'C/2C 13

QUINTEL0S86912-2

LTE 10/20/50 nWTNCr

13- -

AIRSOAIE DUAL RRH 4T4R812/14 320W AHLBA

ALCATEL-LUCENT8e6A-RRH4«45

A4- -

ASANDREW

SBNHH-1D65CLTE 4C/GSM 13

ANDREW

SBNHH-1D65CLTE 4C/GSM 13 2

ALCATEL-LUCENT

RRH4»25-WCS-4R -

B1KATHREIN

742266UMTS 133

KATHREIN

742266UMTS 133

- - -

82" ANDREW

SBNHH-1D65CLTE 3C 133

OUINTEL0886812-2

LTE SO/BWE 133- -

ALCATEL-LUCENT825 RRH4X30-4R

ALCATEL-LUCENTB88A-RRH4X49

83♦ POWERWAVE

P65-17-XLH-RRLTE 1C/2C 133

QUINTEL0886512-2

LTE 10/20/SO FIRimCT 133

- -

AIRSCAir DUAL RIM 4T4Rei2/14 320W AHLBA

ALCATEL-UICENT8e6A-RRH4)i4S

B4- - - - - - -

B5ANOWCW

SBNHH-1D65CLTE 4C/GSM 133

ANDREW

SBNHH-1D65CLTE 4C/CSM 133 2

ALCATEL-LUCENT

RRH4.25-WCS-4R -

C1 74226^ UMTS 253KATHREIN

742266UMTS 253 2

- - -

02• AIMORCW

SBNHH-1D6SCLTE 3C 253

OUINTEL0386512-2

LTE 30/BWE 253- -

ALCATEL-LUCENT825 RRH4X30-4R

ALCATEL-LUCENT866A-RRH4X45

03« ANDRCW

LTE 1C/2C 253QUINTEL

QS869t2-2LTE 10/20/50 FIRSTNn

253- -

AIRSOALE DUAL RRH 4T4R

812/14 320W AHLBAALCATEL-LUCENT86eA-RRH4K45

C4

C5ANDREW

SBNHH-1D65CLTE 4C/GSM 253

ANDREW

SBNHH-1D65CLTE 4C/GSM 253

ALCATEL-LUCENT

RRH4,25-WCS-4R

) PRIOR TO CONSTRUCTION.

antenna CQNFIQWRATION

EXISTING MONOPOIE

RRH (TYP)

EXISTING ANTENNA LAYOUT

1. SEE ANTENNA CONFIGURATION FOR MOOa NUMBERS AND AZIMUTHS.

CONSTRUCTION NOTES

""V (TYP Of 6)

MOUNT (TYP OF S)

ANTENNA MOUNT (TYP OF S)

PROPOSED ANTENNA LAYOUT NO SCALE Q

3t&t

BLA(XC&VEATCH

6800 W. 115TH ST, SUITE 2292OVERt^D PARK, KS 66211

(913) 458-2000

\Val\i BsutD row revip»

IT B A VKXAHON OF lAW FOR ANY PERSON,NLESS TFCY ARE ACTING UNDER THE OIRECTIONOF A LICENSED PROFESSOML ENGRCER,

TO ALTER THB OOCUMENT.

PRAIRIE CREEK

KS4693

1607 EAST CENTRAL

ANDOVER, KS 67002LTE 5C FIRSTNET/BWE

ANTENNA LAYOUT

AND SCHEDULE

SHEET NUMBER

C-3

Page 9: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

DIMENSIONS, WxOxH: (12 <7.2 (21.2^ 304x1S2x5Semm

IVEIGHT. W)TH0«;T MOONTINC KIT: (SS.O lbs.) 24.0 Itg

FieERGlASS. UV RESISTANT

24SaxW4x245nvn

(96%12*rt.6")

12 X 7/l« DM FEMALE7B01 FARLTf

OVERLAND PARK. KS 66204

BLACK &VEATCH

6600 W, 115TH ST, SUITE 2292OVERLAND PARK. KS 66211

(913) 458-2000

minnSiSSDUAL MOUNT ANTENNA BRACKET

15.4* (390mm)

9.5 (240mm)

26.8' (730mm)

WEX>NT (MTTHOUT MOUNT KIT) 101.4lbs (461(9)

OOOOJ

NO SCALE Q i!nnii3SKinffli

PRAIRIE CREEK

KS4693

1607 EAST CENTRAL

ANDOVER, KS 67002

LTE 5C FIRSTNET/BWE

SHEET TITLE

EQUIPMENT DETAILS

wmsmmmmm

Page 10: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

RAYCAP PC6-48-PP-18-9CDIMENSIONS. DxH; 260x798mm (10.24'xS1.41*)

NOMINAL OPERATING VOLTAGE:

NOMINAL DISCHARGE CURRENT;

MAXIMUM DISCHARGE CURRENT:

48 VDC

20 kA 8/20MS

60 kA 8/20MS

MAXIMUM CONTINUOUS OPERATING VOLTAGE: 75 VDC

VOLTAGE PROTECTION RATING: 400 V

WIND LOADING:

TOTAL WEKJHT: 26.2 lbs

PBPPggROE /^PPIWSaBffPIBIMIPNS

HOT UggP

HPT OSEP

NOT USED

NOT PSgp

NOT USgP

NOT USEP

NOT

NOT WSEP

at&t

BLACK &VEATCH

6800 W. 115TH ST, SUITE 2292OVERLAND PARK. KS 66211

(913) 458-2000

12/26/17 eSUEO FOR REVIEW

IT B A WCUTKM OF LAW FOR ANY ^UNLESS THEY ARE ACTOW UWOER THE DIRECTION

OF A UCENSCD PROFESSBNAL ENITO ALTER TMS DOCUMENT.

PRAIRIE CREEK

KS46931607 EAST CENTRAL

ANDOVER, KS 67002LTE 5C FIRSTNET/BWE

SHEET TITLE

EQUIPMENT DETAILS

SHEET NUMBER

C-5

Page 11: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

CABLE MARKING LOCATIONS TABLE

EACH CABLE SHAU BE COLOR COOEO WITH (1) SET OT V®WIOe BANDS NEAR THE TOP OF MAIN LINE AND WITH (1}

SET OF 3/4* WOE COLOR SANDS JUST PRIOR TO ENTERIN6THE SHELTER/OUTDOOR EQUIPMENT

®EACH CABLE SHALL BE COLOR CODED WITH (1} SET OF3/4' WIDE BANDS JUST WITHIN THE SHELTER NEAR THEHATCH PLATE fONLY INDOOR SITES)

©EACH CABLE SHALL BE COLOR COOED WITH (1) SET OF3/4* WIDE BANDS AT THE ENTRANCE OF THE EOUIPMENT

FIBER A DCPOWER JUMPER

CABLE (TYP)

1. COLORED TAPES MUST BE

3/4' WIDE A W RESISTANTVINYL ELECTRICAL COLORCODING TAPE AND SHOULD BEREADILY AVAILABLE TO THEELECTRICIAN OR COMTRACTOftON SITE.

2. ALL COLOR CODE TAPE SHALLBE 3U-3S AND SHALL BEINSTALLED USING A MINIMUMOF (3) THREE WRAPS OFTAPE AND SHALL BE NEATLYTRIMMED AND SMOOTHED OUTSO AS TO AVOID UNRAVELING.

3. ALL COLOR BANDS INSTALLED

AT THE TOP OF THE TOWER

SHALL BE A MINIMUM OF 3'WIDE, AND SHALL HAVE AMINIMUM OF r OF SPACEBETWEEN EACH COLOR.EXCEPT. AT RRH WKRELABELED END OF JUMPERSCONNECTS, COLOR BANDS

SHALL BE 3/4* WIDE WITH3/4" SPACE. AU COLORBANDS INSTALLED AT THEBASE OF THE TOWER SHAU

BE A MINIMUM OF 3/4' WIDE.AND SHAU HAVE A MINIMUMOF 3/4" OF SPACE BETWEENEACH COLOR.

4. ALL COLOR COOES SHALL BE

INSTALLED SO AS TO ALIGNNEATLY WITH ONE ANOTHERFROM SIDE-TO-SIDE.

5. IF EXISTING CABLES AT THESITE ALREADY HAVE A COLORCODING SCHEME AND THEYARE NOT INTENDED TO BEREUSED OR SHARED, THEEXISTING COLOR COOINGSCHEME SHAU REMAIN

UNTOUCHE).

6. FACTORY MADE JUMPERS SHALLBE INSTAUEO SO THE LABELS

ARE AT THE RADIO END ANDCOLOR CODE TAPE SHALL BEINSTALLED SUCH THAT IT DOCS

NOT COVER THE FACTORY

irgirgflrOTSg

asoMHz'n^/Rxz

1900 MHz TXl/RXl

8S0MHZTX2/RX2

1900MHITX1/RX1

1900 MHz TX2/RX2

>'< -1 r.t VPfflTM

btJiljaiiM

ZjqOMHzTXVRXl

lU)0MHz'n(4/RX4

»?riTffl^ff47j?>!fMw«TTffcTwl

P!

BEEHmniEBEClmlm2100 MHz TX2/RX2 WHfTE WHFTjE

2100MHz TX3/RX3 WHITE WHITE

Vil'. BH

OC POWER CABLE (TYP)

BLACK &VEATCH

6300 W. 115TH ST. SUITE 2292OVERUWO PARK. KS 66211

PRAIRIE CREEK

KS4693

1607 EAST CENTRAL

ANDOVER. KS 67002

LTE 50 FIRSTNET/BWE

CABLE COLOR CODING

Page 12: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

EXOTHERMIC CONNECTKm

MECHANICM. CONNECTION

"h»

LEGEND

. OWUNOINC 6 SHOWN OMGRAMMATICMXY ONLY. at&t

TTTT TTTT TTT>ii' i' i i> i' i' i' i'

1 '1 '1 '1 , , 'i '1 -1 °i , , 1 °i 'i '1SECTOR SECTOR • » SECTOf^

TOWER EXIT GROUND BAR

TOWER GROUND RING

©©

EXISTING SHELTER

#2_ AWG ^ CELL REFERENCE GROUND

i i

EXTERIOR GROUND RING

©

A-. L-i

2. CONIRACTOR SHAU CROUW Aa EQUIPMENT AS A COMPLETE SYSTEM. OROUNDMO SHAa BEIN COMPLMNCE WITH NEC SECTION 2S0 AND ATWT GROUNONC AND BONDING REQUIREMENTS(ATT-TP-7641B) AND MANUFACTURER'S SPEQFICAnONS.

3. ALL <»OUNO CONDUCTORS SHALL BE COPPER; NO ALUMINUM CONDUCTORS SHAa BE USED.

0 AND 1900 RRH'». TWO GROUNDS ARE REQUIRED (TOP AND

NOTES

©

©

©

©

EXTERIOR GROUND RING: |2 AWG SOUO COPPER, BURIED AT A DEPTH OF ATLEAST 30 INCHES BELOW GRADE. OR 6 INCHES BELOW THE FROST UNE ANDAPPROXIMATELY 24 INCHES FROM THE EXTERIOR WAa OR FOOTING.

(ATT-TP-76416 2.2.3.5/7.5.1)

TOWER GROUND RING: THE GROUND RING SYSTEM SHAa BE INSTALLED AROUND

AN ANTENNA TOWER'S LEGS, AND/OR GUY ANCHORS. WHERE SEPARATE SYSTEMSHAVE BEEN PROVIDED FOR THE TOWER AND THE BUILDING, AT LEAST TWO BONOSSHAa BE MADE KTWEEN THE TOWER RING GROUND SYSTEM AND THE BUILDINGRING GROUND SYSTEM USING MINIMUM §2 AYYC SOUD COPPER CONDUCTORS.(ATT-TP-7641B 7.5.1)

INTERIOR GROUND RING: §2 AWG STRANDED GREEN INSUUTED COPPERCONDUCTOR EXTENDED AROUND THE PERIMETER OF THE EQUIPMENT AREA ALLNON-TEaCOMMUNICATIONS RELATED METALLIC OBJECTS FOUND WITHW A SITESHAU BE GROUNDED TO THE INTERIOR GROUND RING WITH |6 AWG STRANDEDGREEN INSULATED CONDUCTOR. (ATT-TP-7e416 7.6.4)

BQNP TO INTERIOR GROUND RINC; |2 AWG SOUD TINNED COPPER WIRE PRIMARYBONOS SHAa BE PROVIDED AT LEAST AT FOUR POINTS ON THE INTERIORGROUND RING, LOCATED AT THE CORNERS OF THE BUILDING.

(ATT-TP-76416 7.5.2.2)

(amUND ROD; UL USTED COPPER CLAD STEEL MINIMUM 5/8' DIAMETER BYEIGHT FECT LONG. Aa GROUND RODS MAY K INSTALLED WITH INSPECTIONSLEEVES. 0WUND RODS SHAa BE DRIVEN TO THE DEPTH OF OWUND RINGCONDUCTOR. (ATT-TP-76416 1.4 / 2.2.3.10)

CEa REFERENCE GROUND BAR: POINT OF GROUND REFERENCE FOR Aa

COMMUNtCATIONS EQUIPMENT FRAMES. Aa BONDS ARE MADE WITH §2 AWGSTRANDED GREEN INSULATED COPPER CONDUCTORS. BONO TO GROUND RING

WITH (2) |2 SOLID TINNED COPPER CONDUCTORS. (ATT-TP-76416 7.6.7)

©

AND A CEa INFERENCE GROUND BAR ARE BOTH PRESENT, THE CR(» MUST BECONNECTED TO THE HATCH-PLATE AND TO THE INTERIOR GROUND RING USING

TYYO §2 AWG STRANDED GREEN INSULATED COPPER CONDUCTORS.

EXTERIOR CABLE ENTRY PORT GROUND BARS: LOCATED AT THE ENTRANCE TO

THE CEa SITE BUILDING. BOND TO GROUND RING WITH A #2 AWG SOUD TINNEDCOPPER CONDUCTORS WITH AN EXOTHERMIC VYELD AND INSPECTION SLEEVE.

(ATT-TP-76416 7.6.7.2)

©I

©I

©

©

©

©

THE BONDINC POINT FOR ItaCOM EQUIPMENT FRAMES SHALLK THE GROUND KJS THAT 6 NOT ISOUTEO FROM THE EQUIPMENTS METALFRAMEVYORK. BOND THE FRAME GROUND BUS TO THE 1" SECTION OF THE CEa

REFERENCE GROUW) BAR. (An-TP-76416 7.8)

INTEWOR UNIT BONOS: METAL FRAMES, CABINETS AND INDIVIDUAL METALLIC UNITS

LOCATED WITHIN THE AREA OF THE INTERIOR GROUND RING REQUIRE A #6 AWGSTRANDED GREEN INSUUTED COPPER BOND TO THE INTERIOR GROUND RING.(ATT-TP-76416 7.12.3.1)

FFNCF AND GATE GROUNDING: METAL FENCES WITHIN 7 FEET OF THE EXTERIOR

(^tOUND i«NG OR OBJECTS BONDED TO THE EXTERIOR GROUND RING SHAU K.BONDED TO THE OiOUNO RING WITH A #2 AWG SOUD TINNED COPPERCONDUCTOR AT AN INTERVAL NOT EXCEEDING 2S FEET. BONDS SHAa K MADEAT EACH GATE POST AND ACROSS GATE OPENINGS. (An-TP-764T6 7.12.2.2)

UNIT BONDS: METALLIC OBJECTS, EXTERNAL TO OR MOUNTED TO THEBUILDING, SHAa BE BONDED TO THE EXTERIOR GROUND RING.

(ATT-TP-7641$ 7.12.2)

ICF amocF SUPPORTS; EACH ICE BRIDGE LEG SHAa BE BONDED TO THE

GROUND IBNO WITH #2 AWG BARE TINNED COPPER CONDUCTOR. PROVIDEEXOTHERMIC WELDS AT BOTH THE ICE BRIDGE LEG AND BURIED GROUND RING.

(ATT-TP-76416 7.4.2.6)

DURING AU DC POWER STSTEM CHANCES INCLUOINC OC SYSTEM CHANGE OUTS,RECTinER REPLACEMENTS OR AODITIONS, BREAKER DISTRIBUTION CHANGES.BATTERY ADDITIONS. BATTERY REPLACEMENTS AND INSTALUTIONS OR CHANGES TODC CONVERTER SYSTEMS IT SHAa BE REQUIRED THAT SERVICES CONTRACTORSVERIFY Aa DC POWER SYSTEMS ARE EQUIPPED WITH A MASTER DC SYSTEMRETURN OTOUND CONDUCTOR FROM THE DC POWER SYSTEM COMMON RETURN

BUS DIRECTLY CONNECTED TO THE CEa SITE REFERENCE GROUND BAR (CRGB)PER TP76300 SECTION H 6 AND TP76416 RGURE 7-11 IgQUIREMENTS.

TQWER ANTENNA EQUIPMENT ORPUNPINQ QN^-MNE GROUNDING key notes

BLACK &VEATCH

6800 W. 11STH ST, SUITE 2292

12/28/17 Ba/CTFOPreWW

PRAIRIE CREEK

KS4693

1607 EAST CENTRAL

ANDGVER, KS 67002LTE 5C FIRSTNET/BWE

SHEET TITLE

GROUNDING ONE-LINE

ANTENNA EQUIPMENT

SHEET NUMBER

G-1

Page 13: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

EXOTHERMIC CONNECTION

MECHANICAL CONNECTION

CHEMICAL ELECTROLVnC GROUNDING SYSTEM

TEST CHEMICAL ELECTROLYTIC GROUNDING SYSTEM

EXOTHERMIC WITH INSPECTION SLEEVE

e

Ot

GROUNDING BAR

GROUND ROD

TEST GROUND ROD WITH INSPECTION SLEEVE

SINGLE POLE SWITCH

DUPLEX RECEPTACLE

DUPLEX GFCI RECEPTACLE

SMOKE DETECTION (DC)

EMERGENCY LIGHTING (DC)

SECURITY UGHT W/PHOTOCEa LTTHONIA AU<WLED-1-25A400/51K-SR4-120-PE-DDBTXD

CHAINUNK FENCE

WOOD/WROUGHT IRON FENCE

WAU STRUCTURE

LEASE AREA

PROPERTY UNE (PL)

SETBACKS

ICE BRIDGE

CABLE TRAY

WATER LINE

UNDERGROUND POWER

UNDERGROUND TELCO

OVERHEAD POWER

OVERHEAD TELCO

UNDERGROUND TELCO/POWER

ABOVE GROUND POWER

ABOVE GROUND TELCO

ABOVE GROUND TELCO/POWER

WORKPOINT

SECTION REFERENCE

DETAIL REFERENCE

ELEVATION MARKER

■IH

$(ft

a

- UCT/P —

> AGP -

- AGT/P AOT/P ACT/P AOT/P -

LEGEND

ANCHOR BOLT

ABOVE

ALTERNATING CURRENT

ADDITIONAL

ABOVE RNISHED FLOOR

ABOVE HNISHED GRADE

AMPEBACE INTEBWUPTIOM CAPACITY

POUND(S)UNEAR FEET

LONG TERM EVOLUTION

MASONRY

MB MACHINE BOLT

-4»KH MECHANICALALUMINUM

ALTERNATE

ANTENNA

APPROX

ARCH

ATS

AW6

BATT

aj)G

ARCHITECTURAL

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

BATTERY

BUILDING

BLOCK

BLOCKING

BEAM

BARE TINNED COPPER CONDUCTORBOTTOM OF FOOTING

CABINET

CANTILEVERED

CHARGING

CEIUNG

CLEAR

COLUMN

(N)NEC

N0.(#)

(P)P/C

COMM

CONC

CONSTR

CONCRETE

CONSTRUCTION

DOUBLE

DIRECT CURRENT

DEPARTMENT

DOUGLAS FIR

DIAMETER

MANUFACTURER

MASTER GROUND BAR

MINIMUM

MISCELLANEOUS

METAL

MANUAL TRANSFER SWITCH

MICROWAVE

NEW

NATIONAL ELECTRIC CODE

NUMBER

NOT TO SCALE

ON CENTER

OPENING

PROPOSED

PRECAST CONCRETE

PERSONAL COMMUNICATION SERVICES

PRIMARY CONTROL UNIT

PRIMARY RADIO CABINET

POLARIZtNG PRESERVING

POUNDS PER SQUARE FOOT

POUNDS PER SQUARE INCH

PRESSURE TREATED

POWER CABINET

QUANTITY

RADIUS

RECTIFIER

REFERENCE

DOWEL

EXISTING

EACH

EUCTRtCAL CONDUCTOR

ELEVATION

EUCTRICAL

ELECTRICAL METALLIC TUBINC

ENGINEER

EQUAL

EXPANSION

FABRICATION

FINISH FLOOR

FINISH GRADE

FACILITY INTERFACE FRAME

HNISKED)FLOOR

FOUNDATION

FACE OF CONCI«TE

FACE OF MASONRT

FACE OF STUD

FACE OF WAU

RNISH SUIVACE

FOOT

FOOTING

GAUGE

GENERATOR

GROUND FAULT CIRCUIT INTERRUPTER

OJJE LAMINATED BEAM

GALVANIZED

GLOBAL POSITIONING SYSTEM

GROUND

«U)8AL SYSTEM FOR MOSLE

HEADER

HANIXR

heataentilation/air conditioningHEKRTT

INTERIOR GROUND RING

INCH

INTERIOR

STRUCT

TEMP

REMOTE ELECTRIC TILT

RIGID METALLIC CONDUIT

REMOTE RADIO HEAD

REMOTE RADIO UNIT

RACEWAY

SCHEDULE

SHEET

SMART INTEGRATED DEVICE

SQUARE

STAINLESS STEa

STANDARD

STEEL

STRUCTURAL

TEMPORARY

THICKNESS

TOWER MOUNTED AMPUnER

TOE NAIL

TOP OF ANTENNA

TOP OF CURB

TOP OF FOUNDATION

TOP OF PLATE (PARAPET)TOP OF STEa

TOP OF WAa

TRANSIENT VOLTAGE SUPPRESSION SYSTEM

TYPICAL

UNDERGROUND

UNDERWRITERS LABORATORY

UNLESS NOTED OTHERWISE

UNIVERSAL MOBILE TELECOMMUNICATIONS

SYSTEM

UNINTERRUPTIBLE POWER SYSTEM

(X POWER PLANT)

WIDE

WTTH

WOOD

WORK POINT

WEATHERPROOF

WEIGHT

ABBREVIATIONS

at&t

BLACK &VEATCH

6800 W. 115TH ST, SUITE 2292OVERl^D PARK, KS 66211

(913) 458-2000

PROJECT NO:

12/2B/t7 SSUCD FOR RtWtW

B A WOLAIION OF LAW FOR ANY PERSON.

PRAIRIE CREEKKS4693

1607 EAST CENTRALANDOVER. KS 67002

LTE 5C FIRSTNET/BWE

LEGEND &ABBREVIATIONS

SHEET NUMBER

GN-1

Page 14: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

GENERAL CONSTRUCTION NOTES

CfMFRAl COMSnturnOM

1. FOR THE PURPOSE OF CONSTRUCTION DRAVWNCS, THE FOaOWINC OEnNITIONS SHALL APPLY:(^NERAL CONTRAaOR - OVERLAND CONTRACTING INC: (B«V)CONTRACTOR: (CONSTRUCTION)OWNER - AT&T

2. Ag SITE WORK SHAU BE COMPLETED AS INDICATED ON THE DRAWINGS AND AT&T PROJECT SPECIFICATIONS.

31. CONTRACTOR SHALL LEAVE PREMISES IN A CLEAN CONDITION.

34. NO OUTOOOR STORAGE OR SOUD WASTE CONTAINERS ARE PROPOSED.

COAXIAL CABIE NOTES

63. TYPES AND SIZES OF THE ANTENNA CABLE ARE BASED ON ESTIMATED LENGTHS. PRIOR TO ORDERINGCABLE. CONTRACTOR SHAU VERIFY ACTUAL LENGTH BASED ON CONSTRUCTION LAYOUT AND NOTIFY THEPROJECT MANAGER IF ACTUAL LENGTHS EXCEED ESTIMATED LENGTHS.

64. CONTRACTOR STALL VERIFY THE DOWN-TILT OF EACH ANTENNA WITH A DIGITAL LEVEL

65. CONTRACTOR SHAa CONFIRM COAX COLOR COOING PRIOR TO CONSTRUCTION. REFER TO 'ANTENNA SYSTEM at&tGENERAL CONTRACTOR SHAa VISTT THE SITE AND SHAa FAMILIARIZE HIMSELF WITH Aa CONDITIONSAFTECTING THE PROPOSED WDRK AND SHAa MAKE PROMSONS. GENERAL CONTRACTOR SHAa BERESPONSIBLE FOR FAMOJARIZING HMSELF WITH Aa CONTRACT DOCUMENTS, HELD CONDITIONS. DIMENSIONS.AND CONnRMMC THAT THE WORK MAY BE ACCOMPUSHED AS SHOWN PRIOR TO PROCEEDING WITHCONSTRUCTION. ANY DISCREPANaES SHAa BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TOTHE COMMENCEMENT OF WORK.

Aa MATERIALS FURNISHED AND INSTALLED SHAa BE IN STRICT ACCORDANCE WITH Aa APPLICABLE COOES.REGULATIONS. AND ORDINANCES. GENERAL CONTRACTOR SHAa ISSUE Aa APPROPRIATE NOTICES ANDCOMPLY WITH Aa LAWS. ORDINANCES. RULES. REGUUT10NS. AND UWFUL ORDERS OF ANY PUOJCAUTHORITY REGARDING THE PERFORMANCE OF WORK.

PLANS ARE NOT TO BE SCALED. THESE PLANS ARE INTENDED TO BE A DIAGRAMMATIC OUTUNE ONLYUNLESS OTHERWISE NOTED. DIMENSIONS SHOWN ARE TO RNISH SURFACES UNLESS OTHERWISE NOTED.SPACING BETWEEN EQUIPMENT IS THE MINIMUM REQUIRED CLEARANCE. THEREFORE. IT IS CRITICAL TO HELDVERIFY DIMENSIONS. SHOULD THERE BE ANY QUESTIONS REGARDING THE CONTRACT DOOJMENTS. THECONTRACTOR SHAa BE RESPONSIBLE FOR OBTAINING A CLARIFICATION FROM THE ENQNEER PRIOR TOPROCEEDING WITH THE WORK. DETAILS ARE INTENDED TO SHOW DESIGN INTENT. MODIFICATTONS MAY BEREQUIRED TO SUIT JOB DIMENSIONS OR CONDITIONS AND SUCH MODIFICATIONS SHAa BE INCLUDED ASPART OF WORK AND PREPARED BY THE ENGINEER PRIOR TO PROCEEDING WTTH WORK.

V ACCORDANCE WITH MANUFACTURER'S

9. IF THE SPECIFIED EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THESE DRAWINGS. THE CONTRACTORSHALL PROPOSE AN ALTERNATIVE INSTALUTION SPACE FOR APPROVAL BY THE ENGINEER PRIOR TOPROCEEDING.

10. GENERAL CONTRACTOR SHAa BE RESPONSIBLE FOR THE SAFETY OF WORK AREA, ADJACENT AREAS ANDBUILDING OCCUPANTS THAT ARE LIKaY TO BE AFFECTED BY THE WORK UNDER THIS CONTRACT. WORKSHALL CONFORM TO Aa OSHA REQUIREMENTS AND THE LOCAL JURISDICTION.

11. GENERAL CONTRACTOR SHAa COORDINATE WORK AND SCHEDULE WORK ACTIVITIES WITH OTHER DISCIPUNES.

12. ERECTION SHAa BE DONE IN A WORKMANUKE MANNER BY COMPETENT EXPERIENCED WORKMAN INACCOROANCT; with APPUCABLE codes and the KST accepted practice. Aa MEMBERS SHAa BE LAIDPLUMB AND TRUE AS INDICATED ON THE DRAWINGS.

WORK PREVIOUSLY COMPLETED IS REPRESENTED BY LIGHT SHADED UNES AND NOTES. THE SCOPE OF WORKFOR THIS PROJECT IS REPRESENTED BY DARK SHAKD LINES AND NOTES. CONTRACTOR SHAa NOTIFY THEGENERAL CONTRACTOR OF ANY EXISTING CONDITIONS THAT DEVIATE FROM THE DRAWINGS PRIOR TOBEONNING CONSTRUCTION.

16. THE CONTRACTOR SHAa PROTECT EXISTING IMPROVEMENTS. PAVEMENTS. CURBS. LANDSCAPING ANDSTRUCTURES. ANY DAMAGED PART SHAa BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OFTHE OWFCR.

17. THE CONTRACTOR SHAa CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF CONSTRUCTION.

21. THE GENERAL CONTRACTOR SHAa PROVIDE PORTABLE FIRE EXTINGUISHERS WITH A RATING OF NOT LESSTHAN 2-A or 2-A:10-B:C AND SHAa BE WITHIN 25 FEET OF TRAVa DISTANCE TO Aa PORTIONS OFWHERE THE WORK IS BEING COMPLETED DURING CONSTRUCTION.

22. Aa EXISTING ACTIVE SEWER. WATER. OAS. ELECTRIC. AND OTHER UTILITIES SHAa BE PROTECTED AT AaTIMES. AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE WORK. SHAa BE RELOCATED ASDIRECTED BY THE ENONEER. EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR WHEN EXCAVATINGOR DRILUNC PIERS AROUND OR NEAR UTILITIES. CONTRACTOR SHAa PROVIDE SAFETY TRAINING FOR THEWORKING CREW. THIS SHAa INCLUDE BUT NOT BE UNITED TO A) FAa PROTECTION. B) CONFINED SPACE.C) ELECTRICAL SAFETY. AND 0) TRENCHING & EXCAVATION.

23. Aa EXITING INACTIVE SEWER. WATER. GAS. ELECTRIC. AND OTHER UTIUT1ES. WHICH INTERFERE WITH THEEXECUTION OF THE WORK. SHAa BE REMOVED. CAPPED. PLUGGED OR OTHERWISE DISCONNECTED AT POINTSWHICH Wia NOT INTERFERE WITH THE EXECUTION OF THE WORK. AS DII^CTED BY THE RESPONSiaXENGINEER. AND SUBJECT TO THE APPROIML OF THE OWNER AND/OR LOCAL UTILITIES.

CONTRACTOR SHAa MINIMIZE DISTURBANCE TO THE EXISTING SITE DURING CONSTRUCTION. EROSIONCONTROL MEASURES. IF REQUIRED DURING CONSTRUCTION. SHAa BE IN CONFORMANCE WITH THE FEDERALAND LOCAL JURISDICTION FOR EROSION AND FOMENT CONTROL

27. THE SUBGRAOE SHAa BE BROUGHT TO A SMOOTH UNIFORM GRADE AND COMPACTED TO 95 PERCENTSTANDARD PROCTOR DENSITY UNDER PAVEMENT AND STRUCTURES AND 60 PERCENT STANDARD PROCTORDENSITY IN OPEN SPACE. Aa TRENCHES IN PUBLJC RIGHT OF WAY SHAa BE BACKRLLED WITH aOWABLEFia OR OTHER MATERIAL PRC-APPROVED BY THE LOCAL JURISDICTION.

29. Aa BROCHURES. OPERATING AND MAINTENANCE MANUALS. CATALOGS. SHOP DRAWINGS. AND OTHERDOCUMENTS SHAa BE TURNED OVER TO THE GENERAL CONTRACTOR AT COMPLETION OF CONSTRUCTION ANDPRIOR TO PAYMENT.

r BETWEEN THE CONSTRUCTION SPEOFICATION AND THE DRAWINGS. THE DRAWINGS SHAa GOVERN.

36. CONTRACTORS SHAa BE RESPONSIBLE FOR OBTAINING Aa PERMITS AND INSPECTIONS ISQUIISD FORCONSTRUCTION. IF CONTRACTOR CANNOT OBTAIN A PERMIT. THEY MUST NOTIFY THE GENERAL CONTRACTORIMMEDIATELY.

37. CONTRACTOR SHAa REMOVE Aa TRASH AND DEBRIS FROM THE SITE ON A DAILY BASIS.

OROEMNG MATERIAL OR PROCEEDING WITH CONSTRUCTION.

40. Aa COAXIAL CABLE INSTALUT10NS TO FOaOW MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.

ANTENNA MOUNTIWO

49. JUMPERS FROM THE TMA'S MUST TERMINATE TO OPPOSITE POLARIZATIONS IN EACH SECTOR.

51.

52. ANTENNAS SHAa HAVE A 2'-0' MIN. CENTER TO CENTER HORIZONTAL SEPARATION.

TORQUE REQUIREMENTS

53. Aa RF CONNECTIONS »1Aa BE TIGHTENED BY A TORQUE WRENCH.

54. Aa RF CONNECTIONS. GROUNDING HARDWARE AND ANTENNA HARDWARE SHAa HAVE A TORQUE MARKINSTALLED IN A CONTINUOUS STRAIGHT UNE FROM BOTH SIDES OF THE CONNECTION.

A. RF CONNECTION BOTH SIDES OF THE CONNECTOR.

B. GROUNDING AND ANTENNA HARDWARE ON THE NUT SIDE STARTING FROM THE THREADS TO THE SOUDSURFACE. EXAMPU OF SOUD SURFACE: GROUND BAR. ANTENNA BRACKET METAL

55. Aa BM ANTENNA HARDWARE SHAa K TIOOENED TO 9 LB-FT (12 NM).

56. Aa I2M ANTENNA HAROWARE SHAa K TIGHTENED TO 43 LB-FT (58 NM).

56. Aa DIN TYPE CONNECTIONS SHAa BE TIGHTENED TO 18-22 LB-FT (24.4 - 29.8 NM).

59. Aa N TYPE CONNECTIONS SHAa BE TIGHTENED TO 15-20 LB-W (1.7 - 2.3 NM).

nam * power cable mpuntino

60. THE RBER OPTIC TRUNK CABLES SHAa K INSTALLED INTO CONDUITS, CHANNa CABLE TRAYS. DR CABLETRAY. WHEN INSTALLING FIKR DPTIC TRUNK CABLES INTO A CABLE TRAY SYSTEM. TFCY SHAa BEINSTALLED INTO AN INTER OUCT AND A PARTITION BARRIER SHAa BE INSTALLED BETWEEN THE 600 VOLTCABLES AND THE INTER DUCT IN ORDER TO SEGREGATE CABU TYPES. OPTIC FIBER TRUNK CABLES SHAaHAVE APPROVED CABLE RESTRAINTS EVERY (60) SIXTY FEET AND SECURaY FASTENED TO THE CABLE TRAYSYSTEM. NFPA 70 (NEC) ARTICLE 770 RULES SHAa APPLY.

61. THE TYPE TC-ER CABLES SHAa K INSTALLED INTO CONDUITS. CHANNa CABLE TRAYS. OR CARE TRAYAND SHAa BE SECURED AT INTERVALS NOT EXCEEDING (6) SIX FEET. AN EXCEPTION; WHERE TYPE TC-ERCABLES ARE NOT SUBJECT TO PHYSICAL DAMAGE. CAaES SHAa BE PERMITTED TO MAKE A TRANSITIONBETWEEN CONDUITS. CHANNEL CABLE TRAYS, OR CABLE TRAY WHICH ARE SERVING UTILIZATION EQUIPMENTOR DEVICES. A DISTANT (6) SIX FEET SHAa NOT BE EXCEEDED WITHOUT CONTINUOUS SUPPORTING.NFPA 70 (NEC) ARTICLES 336 AND 392 RULES SHAa APPLY.

GENERAL CABU: AND EQUIPMEMT NOTTS

73. Aa OUTDOOR RF CONNECTORS/CONNECTIONS SHAa BE WEATHERPROOFED. EXCEPT THE RET CONNECTORS.USING BUTYL TAPE AFTER INSTALUTION AND FINAL CONNECTIONS ARE MADE. BUTYL TAPE SHAa HAVE AMINIMUM OF ONE-HALF TAPE WIDTH OVERLAP ON EACH TURN AND EACH UYER SHAa BE WRAPPEDTHREE TIMES. WEATHERPROOFING SHAa BE SMOOTH WITHOUT KJCKUNG. BUTYL aEEDINO IS NOTALLOWED.

74. IF REQUIRED TO PAINT ANTENNAS AND/OR COAX:A. TEMPERATURE SHAa BE ABOVE 50 F.

B. PAINT COLOR MUST BE APPROVED BY BUILDING OWNER/LANDLORD.C. FOR REGUUTEO TOWERS. FAIL*D. DO NOT PAINT OVER COLOR C

75. Aa CABLES SHAa BE GROUNDED WITH COAXIAL CABLE GROUND KITS. FOaOW THEMANUFACTURER'S RECOMMENDATIONS.

A. GROUNDING AT THE ANTENNA LEVa

B. GRDUNDING AT MID LEVEL. TOWERS WHICH ARE OVER 200'-0'. ADDITIONAL CABLE GROUNDINGREQUIRED.

C. WTOUNDING AT BASE OF TOWER PRIOR TO TURNING HORIZONTALD. GROUNDING OUTSIDE THE EQUIPMENT SHELTER AT ENTRY PORT.E. GROUNDING INSIDE THE EQUIPtCNT SHaTER AT THE ENTRY PORT.

76. Aa PROPOSED GROUND BAR DOWNLEADS ARE TO BE TERMINATED TO THE EXISTING ADJACENT GROUNDBAR DOWNLEADS A MINIMUM DISTANCE OF 4'-0' BELOW GROUND BAR. TERMINATIONS MAY BE EXOTHERMICOR COMPRESSION.

L l2'-0* T-BOOM SECTOR ANTENNA MOUNT. IF

https://blaekandveateh.8har«polnLeom/t«ama/ESSAM«com/ProJeet«/PubllcNet»erli9/ATT/ArrTurf/- . . . p*|/shoredX200oeument8/Forn»«/Allll«fTw.o#px

BLACK &VEATCH

6800 W. 115TH ST, SUITE 2292OVERUND PARK. KS 66211

(913) 458-2000

12/2B/17 ssueo FOB WVIEW

IT 6 A MOLATKM OF lAW FOR ANY PERSON.

PRAIRIE CREEK

KS4693

1607 EAST CENTRAL

ANDOVER, KS 67002LTE 5C FIRSTNET/BWE

GENERAL CONSTRUCTION

NOTES

SHEET NUMBER

GN-2

Page 15: THIS fwm AMENDMENT TO TOWER LEASE AGREEMENT (Fifth

GENERAL ELECTRICAL NOTES

PART 1 - grNFRftl

1.1 GENERAL CONOmONS

A. CONTRACTOR SHAU INSPECT THE EXISTING SITE CONDITIONS PRIOR TO SUBMimNG BID. ANYQUESTIONS ARISING DURING THE BID PERIOD IN REGARDS TO THE CONTRACTORS FUNCTIONS, THESCOPE OF WORK. OR ANY OTHER ISSUE RELATED TO THIS PROJECT SHAU BE KWUGHT UP DURINGTHE BID PEfWOD WITH THE PROJECT MANA<»< FW CLAWFICATION. NOT AFTER THE CONTRACT HAS

1.2 LAWS, REGULATIONS, ORDINANCES, STATUTES AND COOES.

A Aa WORK SHAU BE INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONALELECTRICAL CODE, AND AU APPLICABLE LOCAL LAWS, REGUUTTONS. ORDINANCES, STATUTES ANDCODES. CONDUIT BENDS SHAU BE THE RADIUS BEND FOR THE TRADE SIZE OF CONDUIT INCOMPLIANCE WITH THE LATEST EDITIONS OF NEC.

1.3 REFERENCES

A THE PUBLICATIONS LISTED BELOW ARE PART OF THIS SPECIFICATION. EACH PUBUCATION SHALL BETHE LATEST REVISION AND ADDENDUM IN EFFECT ON THE DATE. THIS SPECIFICATION IS ISSUED FORCONSTRUCTION UNLESS OTHERWISE NOTED. EXCEPT AS MODinED BY THE REQUIREMENT SPECIFIEDHEREIN OR THE DETAILS OF THE DRAWINGS, WORK INCLUDED IN THIS SPECIFICATION SHALL CONFORMTO THE APPLICABLE PROVISION OF THESE PUBLICATIONS.

1. ANSI/IEEE (AMERICAN NATIONAL STANDARDS INSTITUTE)2. ASTM (AMERICAN SOCIETY FOR TESTING AND MATERIALS)3. ICE (INSULATED CABLE ENGINEERS ASSOCtATKIN)4. NEMA (NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION)5. NFPA (NATIONAL FIRE PROTECTION ASSOCIATION)6. OSHA (OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION)7. UL (UNOERW " 'a. ATftT GROUN

1.4 SCOPE OF WORK

A. WORK UNDER THIS SECTION SHAU CONSIST OF FURNISHING ALL LAK>R, MATERIAL, AND ASSOCIATEDSERVICES REQUIRED TO COMPLETE REQUIRED CONSTRUCTION AND BE OPERATIONAL.

A RNAL INSPECTION AND

E. THE CONTRACTOR SHAU PREPARE A COMPLETE SCT OF AS-BUILT DRAWINGS, DOCUMENT AU WIRINGEQUIPMENT CONDITIONS, AND CHANGES WHILE COMPLETING THIS CONTRACT. THE AS-WJILT DRAWINGSSHAU BE SUBMITTED AT COMPLETION OF THE PROJECT.

PfflT 2 - PRODUCTS

2.1 GENERAL

A Aa MATERIALS AND EQUIPMENT SHAU K UL LISTED, NEW, AND FKt FROM DEFECTS.

D. Aa OVERCURRENT DEVICES SHAa HAVE AN INTERRUPTING CURRENT RATING THAT SHAa BE GREATERTHAN THE SHORT CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED, 10.000 AlC MINIMUM. VEWFYAVAILABLE SHORT CIRCUIT CUMTENT DOES NOT EXCEED THE RATING OF ELECTRICAL EQUIPMENT INACCORDANCE WITH ARTICa 110.24 NEC OR THE MOST CURRENT ADOPTED CODE PER THEGOVERNING JURI»)ICTION.

2.2 MATERIALS AND EQUIPMENT

A. CONDUIT

1. RIGID IENDS AND THREADS A

2. LIQUIOTIGHT FLEXIBLE METAL CONDUIT SHAa BE UL LISTED.

3. CONDUIT CLAMPS. STRAPS AND SUPPORTS SHAa BE STEa OR MAaEAfflE IRON. Aa FITTINGSSHAa BE COMPRESSION AND CONCRETE TIGHT TYPE. GROUNDING BUSHINGS WITH INSULATEDTHROATS SHALL BE INSTALLED ON Aa CONDUIT TERMINATIONS.

CONDUCTORS AND CABLE

1. AC CONDUCTORS SHAa BE FLAME-RETAROANT, MOISTURE AND HEAT RESISTANT THERMOPLASTIC,SINGLE CONDUCTOR, COPPER, TYPE THHN/THWN-2, 600 VOLT, SIZE AS INDICATED, #12 AWGSHAa BE THE MINIMUM SIZE CONDUCTOR USED.

2. 110 AWG AND SMALLER CONDUCTOR SHAa BE SOUO OR STRANDED AND #6 AWG AND LARGERCONDUCTORS SHAa BE STRANDED.

4. STRAIN-REUEF SUPPORTS GRIPS SHAa BE HUBBEa KELLEMS OR APPROVED EQUAL CABLESSHAa BE SUPPORTED IN ACCORDANCE WITH THE NEC AND CABa MANUFACTURER'SRECOMMENDATIONS.

5. Aa CONDUCTORS SHAa BE TAGGED AT BOTH ENDS OF THE CONDUCTOR. AT Aa PUa BOXES,J-BOXES, EQUIPMENT AND CABINETS AND SHAa BE IDENTIFIED WITH APPROVED PLASTIC TAGS(ACTION CRAFT, BRADY, OR APPROVED EQUAL).

C. DISCONNECT SWITCHES

1. DISaMNECT SWITCHES SHAa BE HEAVY DUTY, DEAO-FRONT, QUICK-MAKE, QUtCK-BREAiCEXTEMMay OPERABa, HANOa LOCKABa AND INTERLOCK WITH COVER IN aOSED POSITON,RATING AS INDICATED, UL LABELED FURNISHED IN NEMA 3R ENCLOSURE, SQUARE-0 ORENGINEERED APPROVE EQUAL

D. CHEMICAL EaCTROLYTC GROUNDING SYSTEM;

1. mSTAa CHEMICAL GROUNDING AS REQUIRED. THE SYSTEM SHAa BE EaCTROLYTIC MAINTENANCE

FREE EaCTROOE CONSISTING OF RODS WITH A MINIMUM #2 AWG CU EXOTHERMAaY WELDEDPIGTAIL PROTECTIVE BOXES. AND BACKRa MATERIAL MANUFACTURER SHAa BE LYNCOa XITCROUNDINC ROD TYPES K2-(*)^ OR K2L-(*)CS (•) LENGTH AS REQUIRED.

2. GROUND ACCESS BOX SHAa BE A POLYPLASTTC BOX FOR NON-TRAFFIC APPLICATIONS, INCLUDING BOLT DOWNFLUSH COVER WITH 'WTEATHER* HOLES, XIT MODEL tXB-22. Aa DISCONNECT SWITCHES AND CONTROLLINGDEVICES SHAa BE PROVIDED WITH ENGRAVED LAMICOID NAMEPLATES INDICATING EQUIPMENT CONTROLLED, BRANCHCIRCUrrS id numbering, and the EaCTRICAL POWER SOURCE.

3. BACKFia MATERIAL SHAa BE LYNCONITE AND LYNCOa GROUNDING GRAVEL

E. SYSTEM GROUNDING:

3. CONNECTCmS SHAa BE HIGH-CONDUCTIVITY, HEAVY DUTY, LISTED AND LABELED AS GROUNDING CONNECTORS FOR

5. OROUNO ROOS SHAa BE ERICO #615800, COPPER-CLAD STEEL WITH HWH-STRENGTH STEa CORE ANOELECTROLYTIC-GRADE COPPER OUTER SHEATH, MOLTEN WELDED TO CORE, S/B'iclO'-O'. Aa GROUNDING ROOSSHAa BE »«TALLED WITH INSPECTION SLOm.

e. INSTAa AN EOUtPMENT CROUNDINC CONDUCTOR IN Aa CONDUITS IN COMPUANCE WITH THE ATftT SPECIFICATTONSAND NEC. THE EQUIPMENT (XTOUNDING CONDUCTORS SHAa BE BONDED AT Aa JUNCTION BOXES, PUaBOXES,DISCONNECT SWITCHES, STARTERS, AND EQUIPMENT CABINETS.

F. OTHER MATERIALS:

2. PROVIDE PUa BOXES ANO JUNCTION BOXES WHERE SHOWN OR REQUIRED BY NEC.

C. PANELS AND LOAD CENTERS;

I. Aa PANa DIRECTORIES SHAa BE TYPEWRITTEN.

PART 3 - PgCUTIQM

3.1 GENERAL:

3.2 LABOR AND WORKMANSHIP:

3.3 COORDINATION:

3.4 INSTALLATION:

A. CONDUIT:

. PROVIDE RIGID PVC SCHEDUa 80 CONDUITS FOR Aa RISERS, RMC OTHERWISE NOTED. EMT MAY BE INSTALLEDFOR EXTERIOR CONDUITS WHEIK NOT SUBJECT TO PHYSCAL DAMAGE.

. INSTAa SCH. 40 PVC CONDUIT WITH A MINIMUM COVER OF 24* UNKR ROADWAYS, PARKING LOTS, STREETS, ANDALLEYS. CONDUIT SHAa HAVE A MINIMUM COVER OF IB' IN Aa OTHER NON-TRAFFIC APPUCATIONS (REFER TO2008 NEC, TABa 300.5).

. USE GALVANIZED FLEXIBa STEa CONDUIT WHERE DIRECT CONNECTION TO EQUIPMENT WITH MOVEMENT, VBRATION,OR FOR EASE OF MAINTENANCE. USE LIQUID TIGHT, FLEXIBLE METAL CONDUIT FOR OUTDOOR APPUCATIONS.INSTAa GALVANIZED FLEXIBa STEa CONDUIT AT Aa POINTS OF CONNECTION TO EQUIPMENT MOUNTED ONSUPPORT TO ALLOW FOR EXPANSION AND CONTRACTION.

. A RUN OF CONDUIT KTWEEN BOXES OR EQUIPMENT SHAa NOT CONTAIN MORE THAN THE EOmVALENT OF THREEQUARTER-BENDS. CONDUIT BEND SHAa BE MADE WITH THE UL USTED KNDER OR FACTORY 90 DEGREE ELBOWSMAY BE USED.

A CONDUIT CUTTING TOOL AND REAMED TO PROVIDE A

7. PROVIDE INSULATED GROUNDING BUSHING FOR Aa CONDUITS.

B. CONTRACTOR IS RESPONSIBa FOR PROTECTING Aa CONDUITS DURING CONSTRUCTION. TEMPORARY OPENINGS INTHE CONDUIT SYSTEM SHAa BE PLUGGED OR CAPPED TO PREVENT ENTRANCE OF MOISTURE OR FOREIGN MATTER.CONTRACTOR SHAa REPLACE ANY CONDUITS CONTAININC FOREIGN MATERIALS THAT CANNOT BE REMOVED.

10. INSTAa PUa STRINGS IN Aa CLEAN EMPTY CONDUITS. IDENTIFY Pua STRINGS AT EACH END.

11. INSTAa 2* HIGHLY VISIBa ANO DETECTABa TAPE 12* ABOVE Aa UNDERGROUND CONDUITS AND CONDUCTORS.

N SUCH A MANNER AS TO ENSURE AGAINST COaECTION OF TRAPPED

13. PROVIDE CORE DRILUNG AS NECESSARY FOR PENETRATIONS TO AaOW FOR RACEWAYS AND CABLES TO BE ROUTED

CONDUCTORS AND CABa

1. Aa POWER WIRING SHAa BE COLOR CODED AS FOaOWS:

PHASE BPHASE CNEUTRALGROUNDING

208/240/120^^ STSTtJUS

BLUEWHITEGREEN

CABLES SHAa BE NEATLY TRAINED, WHHOUT INTERLAONC, AND BE OF SUFFICIENT aNGTH IN AaBOXES Sc EQUIPMENT TO PERMIT MAKING A NEAT ARRANGEMENT. CASaS SHAa BE SECURED IN AMANNER TO AVOID TENSION ON CONDUCTORS OR TERMINALS. CONDUCTORS SHAa BE PROTECTEDFROM MECHANICAL INJURY AND MOISTURE. SHARP BENDS OVER CONDUIT BUSHINGS IS PROHIBITED.DAMAGED CABLES SHAa BE REMOVED AND REPLACED AT THE CONTRACTOR'S EXPENSE.

1. Aa METALLIC PARTS OF EaCTRICAL EQUIPMENT WHICH DO NOT CARRY CURRENT SHAa BEGROUNDED IN ACCORDANCE WITH THE REQUIREMENTS OF THE BUILDING MANUFACTURER, ATftTGROUNDING AND BONDING STANDARDS TP-76416, ND-00135. AND THE NATIONAL EaCTTUCALCODE.

2. PROVIDE EaCTRICAL GROUNDING AND BONDING SYSTEM INDICATED WIIH ASSEMBLY OF MATERIALS,INaUDING GROUNDING ELECTRODES, BONDING JUMPERS AND ADDHIONAL ACCESSORIES ASREQUIRED FOR A COMPLETE INSTALLATION.

3. Aa GROUNDING CONDUCTORS SHAa PROVIDE A STRAIGHT DOWNWARD PATH TO GROUND WITHGRADUAL BEND AS REQUIRED. GROUNDING CONDUCTORS SHAa NOT BE LOOPED OR SHARPLYBENT. ROUTE GROUNDING CONNECTIONS AND CONDUCTORS TO GROUND IN THE SHORTEST ANOSTRAKMTCST PATHS POSSIBa TO MINIMIZE TRANSIENT VOLTAGE RISES.

GROUNDING C _ -ROUTE TWO CROUNOiwIcbNOUCTOre THE ROOFTOP," TOWEIS^ AND WATER TT^RS'GROUNDRING, TO THE EXISTING GROUNDING SYSTEM, THE GROUNDING CONDUCTORS SHAa NOT BESMALLER THAN 2/0 AWG COPPER. ROOFTOP GROUND RING SHAa BE BONDED TO THE EXISTINGGROUNDING SYSTtM, THE BUILDING STEEL COLUMNS, LIGHTNING PROTECTION SYSTEM, AND BUILDINGMAIN WATER LINE (FERROUS OR NONFERROUS METAL PIPING ONLY). Sa STANDARD 6.3.2.2.

. TIGHTEN GROUNDING AND BONDING CONNECTORS, INCLUDING SCREWS AND BOLTS, IN ACCORDANCEWITH MANUFACTURER'S PUBLIS1CD TORQUE TIGHTENING VALUES FDR CONNECTORS AND BOLTS.WHERE MANUFACTURER'S TORQUING REQUIREMENTS ARE NOT AVAILABa, TIGHTEN CONNECTIONS TOCOMPLY WITH TIGHTENING TORQUE VALUES SPECIHED IN UL TO ENSURE PERMANENT ANOEFFECTIVE GROUNDING.

. CONTRACTOR SHAa VERIFY THE LOCATIONS OF GROUNDING TIE-IN-POINTS TO THE EXISTINGGROUNDING SYSTEM. Aa UNDERGROUND GROUNDING CONNECTIONS SHAa BE MADE BY THEEXOTHERMIC WELD PROCESS AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'SINSTRUCTIONS.

. Aa GROUNDING CONNECTIONS SHAa BE INSPECTED FOR TIGHTNESS. EXOTHERMIC WELDEDCONNECTIONS SHAa BE APPROVED BY THE INSPECTOR HAVNG JURISDICTION BEFORE BEINGPERMANENTLY CONCEAaO.

. APPLY CORROSION-RESISTANCE RNISH TO HELD CONNECTIONS AND PLACES WHERE FACTORYAPPLIED PROTECTIVE COATINGS HAVE BEEN DESTROYED. USE KOPR-SHIELD ANTI-OXIDATIONCOMPOUND ON Aa COMPRESSION CROUNDINC CONNECTIONS.

11. DIRECT BURIED GROUNDING CONDUCTORS SHAa BE INSTALLED AT A NOMINAL DEPTH OF 36*MINIMUM BELOW GRADE, OR 6* BELOW THE FROST LINE. USING THE GREATER OF THE TWODISTANCES.

13. THE INSTALLATION OF CHEMICAL EaCTROLYTIC GROUNDING SYSTEM IN STTHCT ACCORDANCE WITHMANUFACTURER'S INSTRUCTIONS. REMOVE SEALING TAPE FROM LEACHING AND BREATHER HOLES.INSTAa PROTECTIVE BOX FLUSH WITH GRADE.

15. IF COAX ON THE ICT BRIDGE IS MOIS THAN 6 R. FROM THE «K)UND BAR AT THE BASE OF THETOWER, A SECOND GROUND BAR Wia BE NEEDED AT THE END OF THE ICE BRIDGE, TO GROUNDTHE COAX CABa GROUNDING KITS AND IN-UNE ARRESTORS.

16. CONTRACTOR SHAa REPAIR, AND/OR REPLACE, EXISTING GROUNDING SYSTEM COMPONENTS. \.wrffnra.iwn ^rvu.u r^tr-nin, nnv/wn nc.rwM., tAWiifW vnwni/i,

DAMAGED DURING CONSTRUCTION AT THE CONTRACTORS EXPENSE.

3.5 ACCEPTANCE TESTING

B. WHEN MATERIAL AND/OR WORKMANSHIP IS FOUND NOT TO COMPLY WITH THE SPECIFIEDREQUIREMENTS, THE NON-COMPLYING ITEMS SHALL BE REMOVED FROM THE PROJECT SITE ANDREPLACED WITH ITEMS COMPLYING WITH THE SPECinED REQUIREMENTS PROMPTLY AFTER RECEIPT OFNOTICE FOR NON-COMPLIANCE.

C. TEST PROCEDURES

1. Aa FEEDERS SHAa HAVE INaiLATION TESTED AFTER INSTALLATION, BEFORE CONNECTION TODEVICES. THE CONDUCTORS SHAa TEST FREE FROM SHORT CIRCUITS ANO GROUNDS. TESTINGSHAa BE FOR ONE MINUTE USING 1000V DC. PROVIDE WRTTTEN DOCUMENTATION FOR Aa TESTRESULTS.

PERFORM GROUNDING TEST TO MEASURE GROUNDING RESISTANCE OF GROUNDING SYSTEM USING

THE lEK STANDAW) 3-POINT *FAa-OF-POTEMTIAL* METHOD. PROVIDE PLOTTED TEST VALUES ANDLOCATION SKETCH. NOTIFY THE ENGINEER IMMEDIATaY IF MEASURED VALUE IS OVER 5 OHMS.

3tSt

BLACK &VEATCH

6800 W. II5TH ST, SUITE 2292OVERLAND PARK, KS 66211

(913) 458-2000

u/a/17 ssutD FOR mvaw

OF A UCEN5ED PROFESSKMN. eNGMEOI,TO ALTER THS DOCUMENT.

PRAIRIE CREEK

KS4693

1607 EAST CENTRAL

ANDOVER, KS 67002LTE 5C FIRSTNET/BWE

SHEET TTTU

GENERAL

ELECTRICAL NOTES

SHEET NUMBER

GN-3