Upload
others
View
17
Download
2
Embed Size (px)
Citation preview
Thermocouple Fail-Overfrom drift or burn-out
Honeywell UDC ¼ DIN ControllersHoneywell HC-900 Process Automation Controller
1
Thermocouple Fail-over
Situation• Fail-Over strategy
• Primary Control thermocouple burns out• Secondary control thermocouple is mounted nearby, but a
control setup is needed to switch over to the secondary thermocouple when the primary thermocouple fails
• Drift• The higher the working temperature, the more the
chemical degradation of the thermocouple hot junction which creates thermocouple drift.
• Thermocouple failure will include T/C drift detection, even though the thermocouple has not yet broken open.
2
UDC ¼ DIN controller: Thermocouple Fail-over
What’s needed• UDC ¼ DIN PID temperature controller
• two low level, thermocouple inputs, or temperature transmitter for 2nd input• 2nd input on UDC 3200 or UDC 3500 is thermocouple input• UDC 2500 would need a temperature transmitter for its 2nd input,
a high level input• digital input option• alarm relay output
• 2 control thermocouples mounted close to one another• Primary thermocouple for control• Secondary thermocouple for backup
• Configuration to get the controller to ‘fail-over’ to secondary thermocouple when • primary T/C drifts to the condition detected as thermocouple FAIL, or• primary T/C breaks open and upscale burnout is invoked
3
UDC ¼ DIN controller: Thermocouple Fail-over
Approach• An alarm is generated when either
• Thermocouple Health monitoring detects an immanent thermocouple failure (TC FAIL)
• Thermocouple burns out• temperature (PV) > X°F
• (2400° is upscale burn-out value for Type K)• The alarm relay output is wired into a digital input• When the digital input is activated by the alarm relay contact,
it changes the PID’s analog input• from PV 1, the primary thermocouple on Input #1• to PV 2, the secondary thermocouple on Input #2
4
UDC 3500 Thermocouple Fail-over
1st Thermocouple on Input #1
2nd Thermocouple on Input #2
Dual input: 2 thermocouples, one on input #1, the 2nd on Input #2
The drawings look identical. They’re not, the terminal numbers differ. Be sure to get the correct T/C on the correct set of terminals
The cold junction compensator is an external device, highlighted in red (on the right) that needs to be connected,
5
UDC 3500 Thermocouple fail-over Alarm #1 configured to alarm on Thermocouple FAIL or PV > 2400°F (TC burn-out)
Alarm #1 is relay #5 (Table 2-6), for current output.
Alarm 1 NC contacts (relay #5) wire to Digital Input #1:
17 to 2316 to 19 6
UDC 3200 Thermocouple Fail-over
1st Thermocouple on Input #1
2nd Thermocouple on Input #2
Dual input: 2 thermocouples, one on input #1, the 2nd on Input #2
The drawings look identical. They’re not, the terminal numbers differ. Be sure to get the correct T/C on the correct set of terminals
The cold junction compensation is internal on a UDC 3200
7
UDC 3500 Thermocouple fail-over Alarm Configuration
TC FAIL
PVTC IN 1 High Value *
HIGH
0.1
NoLATCH
- -- -- -
- -
DISABLE DISABLE ENABLE
* example: Type K IN 1 high value is 2400°F
8
UDC 3200 Thermocouple fail-over Alarm #1 configured to alarm on Thermocouple FAIL or PV > 2400°F (TC burn-out)
Alarm #1 is output #4 (Table 2-6), for a current output model.
9
UDC 3200 Thermocouple fail-over Alarm #1 NC contact is wired to Digital Input 1
Digital Input #1 is configured for PV2; meaning, change to PV2 (back-up thermocouple on Input #2, when the DI is active [closed switch on the input])
Alarm 1 NC contacts (relay #5) wire to Digital Input #1:
8 to 117 to 10
10
UDC 3200 Thermocouple fail-over Alarm Configuration
TC FAIL
HIGH
PVTC IN 1 High Value *
0.1NoLATCHDISABLEDISABLE
- -- -- -
- -
* example: Type K IN 1 high value is 2400°F11
HC-900 Process Automation Controller: Thermocouple fail-over Function block configuration for dual thermocouple inputs, output of
analog switch block determined by state of thermocouple Failure alarm