ISU-217:2004 część angielska 0 T T h h e e r r m m E E l l i i t t e e by termet INSTALLATION AND OPERATING INSTRUCTIONS FOR AUTOMATIC INSTANTANEOUS TYPE WATER HEATERS FOR USE WITH NATURAL AND LIQUEFIED PETROLEUM GAS Suitable for potable water heating and space heating Models: TE125PLP TE80PLP TE125PNG TE80PNG TE125XLP TE80XLP TE125XNG TE80XNG TE125HLP TE80HLP TE125HNG TE80HNG Exclusive U.S. Importer ELITE International Company, Inc. Los Angeles, California (866) Go-4elite (866) 464-3548 e-mail • [email protected] www.GO4ELITE.COM

ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

0

TThheerrmmEElliittee

by termet

INSTALLATION AND OPERATING INSTRUCTIONS FOR AUTOMATIC INSTANTANEOUS TYPE WATER HEATERS FOR

USE WITH NATURAL AND LIQUEFIED PETROLEUM GAS

Suitable for potable water heating and space heating

Models:

TE125PLP TE80PLP TE125PNG TE80PNG

TE125XLP TE80XLP TE125XNG TE80XNG

TE125HLP TE80HLP TE125HNG TE80HNG

Exclusive U.S. Importer ELITE International Company, Inc.

Los Angeles, California (866) Go-4elite (866) 464-3548 e-mail • [email protected]

www.GO4ELITE.COM

Page 2: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

1

Table Of Contents For your safety.. 1 Operation... 2 Preparing the appliance for operation. 2 Initial operation 2 Setting water temperature. 5 Setting water flow 5 Turning the heater off. 6 Installation.. 6 Locating the heater 6 Combustion air supply. 7 Exhaust venting.... 7 Gas supply piping. 10 Gas pressure regulator.. . 11 Water connections.. . 11 Pressure relief valve.. 12 Mounting the heater.. . 12 Exploded diagram 14-16 Parts list. 14-16 Schematic diagram.. 17-18 Performance chart 19-20 Other possible applications..21-24 Adapting the heater to different types of gas.. .. 25 Replacement of gas cones 28 Replacement of nozzles in the main burner 30 Replacement of nozzle in the ignition burner 31 Adjustment. 32 Protection equipment. 32 Maintenance 33 Venting system. 33 Heat exchanger 33 Burner. 33 Cleaning water filter. 33 Cleaning gas filter. 34 Check-up of protection equipment. 34 Diagnosis... 35 Diagnosis of ignition system.. 36 Troubleshooting.. 37 Specification 41

WARNING! If the information in this instruction manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. FOR YOUR SAFETY -Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance. • Do not touch any electrical switch,

do not use any phone in your building.

• Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions.

• If you cannot reach your gas supplier, call the fire department.

Installation and maintenance should be performed by a qualified installer, service agency or gas supplier.

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. Upon completion of the installation, these instructions should be given to the user of the appliance for future reference .

Page 3: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

2

OPERATION This instantaneous and continuous gas water heater efficiently supplies domestic or commercial hot water. It operates on the principle of heating water only on an on demand basis. Once a hot water faucet is opened, cold water flows through the coils of the heat exchanger. This same flow opens the gas valve, and the burner is ignited by the pilot flame, battery spark igniter or the hydro-generator, depending on the model selected. The coils and body of the heat exchanger absorb the heat generated by the main burner and transfer the heat to the water. When the hot water faucet is shut off, the gas valve automatically closes and the burner turns off. To turn on your water heater, simply open any hot water faucet. Each time you shut off your hot water faucet, you also shut off the water heater. PREPARING THE WATER HEATER FOR OPERATION For your safety, read the instructions thoroughly before operating. WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.

a) Models without a pilot light are equipped with an electronic ignition device, which automatically lights the burner. Do not try to light the burner on these models (having an X or H in their part number) by hand.

b) Before operating, check for any gas vapor accumulation in the areas around the heater. Pay special attention to areas near the floor as gas vapors are often heavier than air, and may accumulate near the floor.

c) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part that may have been damaged by being under water.

WARNING: IF YOU SMELL GAS:

• Do not turn on any electrical appliances or lights. • Do not touch any electrical switch, do not use any phone in your building. • Immediately call your gas supplier from a neighbors telephone. Follow the gas

suppliers instructions. • If you cannot reach your gas supplier, call the fire department.

INITIAL OPERATION Models: TE80X, TE80H, TE125X, TE125H 1. STOP! Do not operate this water heater without reading the safety information first. 2. If you do not have the TE80X or TE125X battery spark electronic models, proceed to point 3. The TE80X and TE125X (NG or LP) models are equipped with the D-Cell

Page 4: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

3

battery sparker. Before operating this unit, two D-Cell batteries are to be installed in the battery compartment.

To accomplish this, first remove the front shield by holding it with both hands at the bottom edges and pulling it gently toward you. When both prongs come out of the holes in the front shield, lift the shield about 4 inches until both screws come out of the heaters back shield. Take care when doing this so as not to damage the battery compartment. Now open the battery compartment by depressing the push-button as illustrated in Fig.1. Install two D-Cell batteries in the battery compartment, aligned as indicated. Close the lid of the battery compartment. Replacing the front shield can only be done when the temperature selection knob and gas control knob are removed.

Fig. 1 Opening the battery compartment 3. Open the natural gas line valve running to the heater. For liquid propane models, open the valve at the gas cylinder or tank. 4. Rotate the gas control knob from position 0 to one out of four gas flow positions

Fig. 2 Control panel *Only on heater TE80X and TE125X

Temperature selection knob Gas control knob

Battery indicator*

Note: If the battery status indicator is flashing, promptly replace old batteries. Take care to discard used batteries in an environmentally-acceptable manner.

Page 5: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

4

5. Set the desired water temperature and the water flow rate using the temperature selection knob.

6. After opening the hot water faucet you will hear an electronic clicking sound on models equipped with an electronic sparker (Models with an X or H in the part number.) Standing pilot light models are relatively quiet. Shortly the gas will light up on the ignition burner, and momentarily later on the main burner. The heater is now operating and supplying hot water.

If the ignition burner does not light the first time (the gas flow is automatically stopped after 50 seconds) turn off the how water facet and allow a few seconds for this to reset. Turn on the water faucet again and repeat the process allowing the ignition burner to light. Repeat, as many times as necessary, until the ignition burner lights and the then the main burner on the heater comes on. Be sure the gas line has been purged of air as describe on page 11 of these instructions

Opening the hot water faucet creates water flow which in turn automatically ignites the ignition burner which then ignites the gas for the main burner. Water flows through the heat exchanger and hot pipes and finally out of the faucet.

7. When closing the hot water faucet, the inflow of gas to both the ignition burner and the main burner is cut off, and the water heater will shut off. INITIAL OPERATION

Models: TE80P, TE125P

1. STOP! Do not operate this water heater without reading the safety information first. 2. Open the natural gas line valve running to the heater. For liquid propane models, open the valve at the gas cylinder or tank. 3. Turn the gas control knob left (about 20º), press home and turn left till you hear a click of piezoelectric lighter (i.e. about 75º from the previous position), with this, a spark appears which will light up the gas on the pilot burner. Hold the so pressed knob for about 10 seconds. In case of not lighting up the gas, repeat these steps. Fig. 3 Control panel

4. The ignition burner should remain lit up. By turning the gas control knob left, you rise the outlet water temperature 5. The heater is now ready to supply hot water. 6. Opening the hot water faucet creates water flow and ignition burner ignites the gas for the main burner. Water flows through the heat exchanger and hot pipes and finally out of the faucet. . When closing the hot water faucet, the inflow of gas to the main burner is cut off, and the water heater will shut off. The pilot burner still remains lit.

Temperature selection knobGas control knob

Page 6: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

5

SETTING WATER TEMPERATURE AND WATER FLOW

ThermElite instantaneous gas water heaters are equipped with a highly-engineered combination gas and water valve which ensures proportional regulation enabling the water heater to produce a stable water temperature at the hot water faucet. This gas/water valve, controlled by the temperature control knob, regulates the amount of water flowing to the heater. If the temperature selection knob (Fig.2) is turned to its extreme right position, the water heater obtains the least flow of water, for example, 2.1 gallons per minute for the TE125 models. The highest temperature rise is obtained by setting the gas flow selector knob to its highest position while setting the temperature (water flow) knob to its lowest position. This restricts the flow of water in the heat exchanger for a longer period of time for additional heating. If the temperature selection knob (gas/water flow) is turned to the extreme left position, the Model 125 water heaters obtain their greatest flow of water, 4.2 gallons per minute with the least rise in temperature. Check the performance specifications for your specific water heater on the box or at the back of this manual.

Setting the temperature selection knob to the various incremental positions causes the temperature rise to change inversely proportionately to the amount of water flow. The flow rate, for example on the TE125 models, can be adjusted between 2.1 and 4.2 gallons with a temperature rise of between 45 and 90 degrees Fahrenheit. The temperature of water (in any set position of the temperature selection knob) can also be controlled by means of adjusting the gas control knob.

• We recommend setting the temperature selection knob between the low and high

positions and the gas control knob between position 3 and 4.

• If the gas control knob is set to the extreme left position and the temperature

selection knob is set to the extreme right, there is a risk of being scalded.

• Energy efficiency is the greatest at lower tolerable temperatures.

Page 7: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

6

TURNING THE WATER HEATER OFF

If the water heater will not be used for extended periods of time, it should be shut off and drained for safety reasons and to prevent possible damage.

To shut the water heater off, turn the gas control knob to the position 0 and close the natural gas valve on the gas supply line running to the water heater or the valve on the cylinder or tank if the water heater uses liquefied propane gas.

Drain the heater entirely if freezing temperatures are anticipated in the area where the heater is installed. To accomplish this, shut off the main valve controlling the inflow of cold water to the heater. Open the hot water faucets in the building to drain any standing water in the pipes. Finally, loosen the nut on the cold water supply line and capture any draining water in a pan or bucket, around 2-3 cups of water.

INSTALLATION

LOCATING THE TANKLESS WATER HEATER

Carefully select the location of your new water heater. As with all gas appliances, for your safety and for proper heater operation, you must ensure that there is an abundant supply of combustible air and the proper installation of the venting.

1. Place your heater as close to a vent or a chimney as possible and in a place not exposed to possible freezing conditions.

2. Keep the water heater area free and clear of combustible materials, gasoline and other flammable liquids and vapors. If installed in a garage, mount the water heater a minimum of 3-feet above the floor where automobile gasoline fumes might collect.

3. Do not install the water heater directly above a carpeted floor or above any material which could possibly burn.

4. This appliance should be located where accidental water leakage will not damage the flooring below.

5. The location where you install the heater must have adequate ventilation. Do not obstruct the flow of combustion and ventilation air to the appliance.

LEAVE ADEQUATE CLEARANCES FOR SERVICING AND PROPER OPERATION

This section is for the installer. The installer is responsible for the correct installation of your instantaneous gas water heater. FOR YOUR SAFETY: Only a certified and trained service technician or qualified plumber should service or install your product. If installed by the homeowner, a qualified plumber or certified technician should inspect the installation prior to operation. Please keep this instruction manual in a safe place for further reference.

The installation of this appliance must conform to local codes, or in the absence of local codes, the National Fuel Gas Code ANSI Z 223.I / NFPA 54

Page 8: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

7

COMBUSTION AIR SUPPLY Your tankless gas water heater must be installed in a location where the proper amount of combustible air will be available to it at all times. Observe the following guidelines concerning combustion air. If the water heater is located in a confined space, there must be permanent openings supplying air to the unit. If the openings will bring air directly from the outdoors, two openings are required, and they should be sized to give a minimum free area of one square inch for every 4,000 BTU/H of the maximum input rating of the unit. If the openings will bring air from an indoor area, they should be sized to give a minimum free area of one square inch for every 10,000 BTU/H of the maximum input rating of the unit. One of these openings should be within 12 of the ceiling, and the other should be within 12 of the floor. EXHAUST VENTING The heater should be installed as close as possible to a chimney or vent, and in a place not exposed to freezing, rain or other inclimate weather conditions.

VENT UNIT ACCORDING TO LOCAL CODES Models: TE125X, TE125H

Air grate

Gas reducer

max

12"

liquefied gas supplyOnly for

Air grate

Con

nect

ion

to g

as g

rid

Cut-off valvegas filter

with filterCut-off valve

supply lineCold water

Gas pressureregulator

(according to the arrowdirection on the body)

Pressure safety-valve

Plastic cap

Vent to outdoor terminal

min

7/16"8 9/16"

Domestic hotwater outlet 9 1/3"

3 2/5"

28 3/

8"~5

0"

min

8 1/

2"

25 1/

2"

Hood CollarExtention

Fig.4 Diagram of water and gas installation as well as exhaust venting.

Page 9: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

8

Model: TE125P

Air grate

Gas reducer

max

12"

liquefied gas supplyOnly for

Air grate

Con

nect

ion

to g

as g

rid

Cut-off valvegas filter

with filterCut-off valve

supply lineCold water

Pressure safety-valve

min

7/16"8 9/16"

Domestic hotwater outlet 9 1/3"

3 2/5"

28 3/

8 "~5

0"

min

8 1/

2"

25 1/

2"

Hood CollarExtention

Fig.5 Diagram of water and gas installation as well as exhaust venting.

Models: TE80X, TE80H

Air grate

min

Gas reducer

max

12"

liquefied gas supplyOnly for

Air grate

Con

nect

ion

to g

as g

rid

~50"

Cut-off valve

gas filter

min

8 1

/2"

with filterCut-off valve

7 7/8"

supply lineCold water

O5 3/16"

25 5

/8"

17 1

/4"

3"

Gas pressureregulator

(according to the arrowdirection on the body)

Pressure safety-valve

Plastic cap

Vent to outdoor terminal

7 1/4"

Fig.6 Diagram of water and gas installation as well as exhaust venting.

Page 10: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

9

Model: TE80P

Air grate

min

Gas reducer

max

12 "

liquefied gas supplyOnly for

Air grate

Con

nect

i on

to g

as g

rid

~50"

Cut-off valvegas filter

min

8 1

/2"

with filterCut-off valve

7 7/8"

supply lineCold water

O5 3/16"

25 5

/8"

17 1

/4"

3"

Pressure safety-valve

Vent to outdoor terminal

7 1/4"

Fig.7 Diagram of water and gas installation as well as exhaust venting.

HOOD COLLAR EXTENTION The 4 Hood Collar Extension (packed inside the carton) must be installed at the very top of the heater before any other venting is attached. Install this extension by fitting it to the venting collar. WARNING: Should overheating occur or the gas supply fails to shut off, turn off the manual gas control valve to the appliance. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

Page 11: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

10

5'm

in3'm

in

2'm

in

Recommended vent installation

GAS SUPPLY PIPING

Before connecting the gas supply, check the rating plate on the side of the front cover to be sure that the heater is designed for the same gas to which it will be connected. You cannot connect a water heater that has been plumbed for natural gas (NG) to a liquefied propane (LP) gas source or vise versa. Fuel conversion kits are available but, by law, may only be installed by a licensed, certified plumber.

In the United States: The installation must conform with local codes or in the absence of local codes, to the National Fuel Gas Code ANSI Z223.1/NFPA54. It is recommended that the gas connection to the heater be copper or steel gas supply piping.

Always purge the gas line of any debris before connecting it to the water heater. Bleed Gas Line– Before starting the heater, the first time, be sure to bleed the Gas Line as it enters the heater (see figures 11, 12 & 13 at Part number 15). Do this by loosening the gas line where it is attached to the heater (at the end of the gas flex connection if a flex is used to connect the gas line). Let a small amount of gas escape ( when you first smell the gas coming out of the loosened gas line) to bleed the line and then securely reattach the nut on the line to prevent any gas leakage WARNING: The tankless gas water heater must be isolated from the gas supply piping system by closing the manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or more than 0.5 psi. The appliance must be isolated from the gas piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi (3.5 kpa). When your connections are made, check for gas leaks at all joints. Apply some soapy water to all gas fittings and gas valves. Soap bubbles are a sign of a leak. Never test for gas leaks using a match or flame. GAS PRESSURE REGULATOR

Always install an in-line manual shut-off valve on the gas supply line in case of anemergency, or if service or maintenance is necessary. A gas fuel filter should be installed between the manual shut-off valve and the heater to secure long and reliable operation of the gas water heater and the burner. The gas fuel filter is not provided with the water heater.

Page 12: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

11

GAS PRESSURE REGULATOR NOTE: The tankless water heaters TE125X, TE125H, TE80X and TE80H are supplied with a gas pressure regulator that must be installed on the heater before attaching the gas supply line. (See Fig.8) Failure to install the gas regulator as illustrated will violate the CSA certification of the unit. The regulator supplied with the heater is pre-set to the correct pressure for the gas shown on the rating plate to the correct pressure. The pressure regulator provided with the heater is adjusted to deliver the proper gas (LP or NG) pressure (as indicated on the rating plate).

Fig.8 Gas Pressure Regulator

Note: An embossed arrow on the rear of the Gas Pressure Regulator indicates the flow direction of the fuel. Always install the regulator with the arrow pointing in the direction of the heater inlet. WATER CONNECTIONS Install a manual in-line water control valve on the inlet water line. Although water piping throughout your structure may be other than copper, we recommend that copper piping be used for at least three feet before and after the water heater. Be sure to use a dielectric union to prevent electrolysis. If the water heater is installed in a closed water system, means should be provided to control thermal expansion such the installation of a water expansion tank. Contact the water supplier, a certified plumber or the local plumbing inspector on how to handle this situation.

Be sure to remove the plastic pipe stops (used for shipping purposes only) at the water connections before connecting the water pipes to the heater. Connect the cold water pipe to the right water-in connection, as you face the heater. Connect the hot water pipe to the left water-out connection, as you face the heater.

NOTE: Models TE80P and TE125P are supplied with a gas pressure regulator that is built in the gas/water unit.

Page 13: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

12

PRESSURE RELIEF VALVE

Caution:

When operating the relief valve make sure that the water heater is not operating and the burner is not lit. Stay as far away from the valve as possible in order to reduce the possibility of being burned from the release of steam or hot water from the release valve. There is no necessity to operate the valve unless the system is be purges or the heater is being removed for replacement or repair.

WARNING:

If a relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. Do not plug the relief valve.

MOUNTING THE TANKLESS WATER HEATER ON THE WALL

ThermElite tankless hot water heaters are designed and certified for wall mounting with no special wall preparation requirements. Select the location for the heater as desired, following all applicable local codes. Adhere to all indoor clearances that apply to the installation. Do not install this appliance on a carpeted wall or above any floor covering which is combustible, such as carpeting or area rugs. The water heater must be securely attached to a load-bearing wall. Secure the two hooks provided with the heater to a wall surface. Hollow wall anchors may be used but it is recommended to use wooden cross pieces secured to the wall studs. Position the cross pieces at the top and bottom of the water heater. This will keep the water heater level while giving a more secure fastening. Place the heater on hooks. See Fig.9 for required mounting clearances to combustible and non-combustible walls. WARNING:

If a water heater is installed in a closed water supply system, such as one having a backflow preventor in the cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or local plumbing inspector on how to control this situation.

NOTE: An approved pressure relief valve must be installed in conjunction with this unit. The pressure relief valve must be installed on the hot water line out ofthe unit with no check valves or control valves between the water heater and thepressure relief valve. Do not plug the pressure relief valve. The pressure relief valve should be manually actuated once a year to check for proper operation.

Page 14: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

13

18 1/8"

4" 4"

28 3 /

8"

21"

9 1/3"

FRONT CLEARANCE 12” BOTTOM CLEARANCE 8” FROM FLOOR Fig 9. Required mounting clearances to combustible and non-combustible walls

for models TE125X, TE125H, TE125P

4" 12"

4"

25 5

/8"

14 1/6" 7 1/4"

Fig 10. Required mounting clearances to combustible and non-combustible walls

for models TE80X, TE80H, TE80P

Note: The design of the cabinet and the rear shield are designed in a manner toensure that the heater is the proper distance from the wall. No special preparation of the wall is required. DO NOT install the water heater on a carpeted or paneled wall. Sheet rock or dry wall is acceptable.

Page 15: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

14

EXPLODED DIAGRAMS

16

292726

15

28

1

3

2 B

17

923

8

2419

14

20

22

13

12

6

11

18

5

7

A

19

Larg

e bl

ack

conn

ectio

n

Pink

Gra

y

30

WhiteWhite

Gre

en

B

Bla

ck

Ora

nge

White

A

Red

Black

25

Smal

l bla

ck c

onne

ctio

n

32

33

Fig.11 Parts and subassemblies of TE125X, TE80X - and wiring diagram

1 .Front cover subassembly 2. Draft hood 3. Angle bar 5. Back cover subassembly Left and right screen 6. Heat exchanger 7. Main burner 8. Ignition burner subassembly 9. Gas water unit 11. Gas pressure regulator 12. Connector pipe 13. Connecting pipe subassembly 14. Inlet pipe subassembly 15. Outlet pipe subassembly 16.Gas pipe subassembly 17. Ignition pipe subassembly 18. Pipe subassembly

19. Gasket 20. Gasket 22. Gasket 23. Gasket 24. Sealing ring 25 .Spark generator 26. Gas control knob 27. Temperature selection knob 28. Battery compartment 29. Tray 30. Low battery indicator light 32. Adapter ¾ - ½ 33. Cut-off valve with filter

Page 16: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

15

16

292726

15

1

3

17

923

8

2419

14

20

22

13

12

7

Larg

e bl

ack

conn

ectio

n

Red

Gre

en

B

Bla

ck

Ora

nge

White

A

Red

Black

25

Smal

l bla

ck c

onne

ctio

n

Bro

wn

Whi

te

10

21

19

A

6B2

32

11 33

5

18

Fig.12 Parts and subassemblies of TE125H, TE80H and wiring diagram

1. Front cover subassembly 2. Draft hood 3. Angle bar

5. Back cover subassembly 6. Heat exchanger 7. Main burner

8. Ignition burner subassembly 9. Gas water unit 10. Hydro-generator

11. Gas pressure regulator 12. Connector pipe 13. Connecting pipe subassembly 14. Inlet pipe subassembly 15. Outlet pipe subassembly 16. Gas pipe subassembly

17. Ignition pipe subassembly 18. Pipe subassembly 19. Gasket 20. Gasket 21. Gasket 22. Gasket 23. Gasket 24. Sealing ring 25. Spark generator 26. Gas control knob 27. Temperature selection knob 29. Tray 32. Adapter ¾ - ½ 33. Cut-off valve with filter

Page 17: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

16

16

2927

15

1

3

2419

14

20

2212

B

A 31

269

1713

8

B26

7

A

19

32

33

18

5

Fig. 13 Parts and subassemblies of TE125P, TE80P and wiring diagram

1. Front cover subassembly 2. Draft hood 3. Angle bar 5. Back cover subassembly 6. Heat exchanger 7. Main burner 8. Ignition burner subassembly 9. Gas- water unit with gas pressure regulator 12. Connector pipe 13. Connecting pipe subassembly 14. Inlet pipe subassembly 15. Outlet pipe subassembly 16. Gas pipe subassembly 17. Ignition pipe subassembly 18. Pipe subassembly 19. Gasket

20. Gasket 22. Gasket 24. Sealing ring 26. Gas control knob 27. Temperature selection knob 29. Tray 31. Thermocouple subassembly 32. Adapter ¾ - ½ 33. Cut-off valve with filter

Page 18: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

17

HV S

INPUT:DC1.5VOUTPUT:MIN12kV

123456789

1011

4

1

3.5

3.4

10

2.1

12

3.8

3.13.3

2.2

11

6 7

2

3.2

3.7

3.5.23.5.1

13

14

3

+

-

HV S

INPUT:DC1.5VOUTPUT:MIN12kV

123456789

1011

4

1

3.5

3.4

10

12

3.8

3.13.3

connector pipe tomeasure gas pressurein the main burrner

11

6

2

3.2

3.7

3.5.23.5.1

3

gas

water

2.12.2

connector pipe tomeasure gas pressurein the main burrner

gas

water

Fig. 14 Schematic diagram of heater TE125X,TE80X, TE125H and TE80H

1.Main burner subassembly 2 Ignition burner subassembly 2.1.Ignition electrode 2.2. Supervision electrode 3. Gas-water unit 3.1. Gas control knob 3.2. Temperature selection knob 3.3Gas filter 3.4. Inlet water filter 3.5. Pressure differential valve 3.5.1. Coil I of pressure differential valve 3.5.2. Coil II of pressure differential valve 3.7 Adjusting screw of micro-switch 3.8 Adjusting screw of small water discharge

4.Heat exchanger 6.Spark generator 7. Battery compartment 10. Temperature limiter/protection against outflow of flue gas to the room 11. Temperature limiter/protection against overheating of heat exchanger 12. Gas pressure regulator (only on heaters using Natural Gas 13. Battery indicator 14. Hydro-generator

TE125X TE80X

TE125H TE80H

Page 19: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

18

Fig.15 Schematic diagram of the heater TE125P and TE80P

1.Main burner assembly 2. Ignition burner assembly 2.1. Ignition electrode 2.2. ignition burner nozzle 2.3. Thermocouple 3. Gas-water unit 3.1. Gas control knob and piezo-igniter 3.2. Temperature selection knob 3.3. Gas filter 3.4. Inlet water pipe 3.5. Electromagnetic valve 3.6. Gas pressure stabilizer 3.7 Piezo- igniter 3.8. Gas filter of ignition burner

3.9. Gas adjusting screw of ignition burner 4. Heat exchanger 6.1. Temperature limiter as the protection against outflow of flue gas to the room 6.2. Temperature limiter as the protection against overheating of heat exchanger

33.4

3.5

2.31

2.1

2.2

gas pressure in the main burnerconnector pipe to measure

3.1

connector pipe to measuregas pressure in the installation

3.3

3.83.9

6

3.2

3.7

3.6

2

4 6.2

6.1TE125P TE80P

Page 20: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

19

PERFORMANCE CHART FOR MODELS TE125X, TE125H & TE125P

Fig.16

Page 21: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

20

PERFORMANCE CHART FOR MODELS TE80X, TE80H & TE80P

Fig.17

OTHER POSSIBLE APPLICATIONS ThermElite instantaneous tankless gas water heaters can be installed in a variety of plumbing applications Many such applications offer economical, energy-saving solutions for providing reliable hot potable water as well as radiant space heating. The versatility of tankless gas water heaters extends to plumbing multiple units in parallel for greater desired capacity. Several diagrams are illustrated on the following pages for possible applications other than that of just supplying hot water.

Page 22: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

21

Design 1. One TE125 with storage and optional recirculating water system

Models: TE125X, TE125H or TE 125P Applications: Intermittent high flow requirements for large residences, motels, laundromats, carwashes, commercial dishwashers, etc.

S

Primary Pump

Cut-off valve with filter

Pressure Relief Velve*

Boiler Drain

Cut-off valve

ColdWater In

CheckValve

Optional DHWCirculating return

pump

Hot WaterOut

Cut-off valve

Dip Tube

Aquastat

Storage Tank

* Pipe PRV to appropriate discharge

NOTES 1. Typical applications call for the TE125P, TE125X or TE125H. The TE80 SpaceMan models can

be substituted if lower production capacity is acceptable.

2. Maximum operating temperature -185°F

3. For each water heater installed in the system at a 90°F temperature rise, the recovery rate is as follows TE125 -127 GPH TE80 - 88 GPH

4. This particular schematic employs an electric storage tank water heater. The supply water for the tankless water heater loop is drawn by tapping the lower heating element. 5. If the circulation flow to tankless water heater is restricted, it may be necessary to adjust the temperature control knob to prevent overheating

Page 23: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

22

Design 2. Two ThermElite tankless water heaters with expandable storage

Models: TE125 / TE80 Applications: For increased water flow at temperatures up to 150°F Restaurants, dairy food processors, etc.

S

Storage Tank

* Pipe PRV to appropriate discharge

Aquastat

Dip Tube

Primary Pump

Cut-off valve with filter

Pressure Relief Velve*

Boiler Drain

Cut-off valve

ColdWater In

Hot WaterOut

NOTES 1. May be used with any model TE125 or TE80 ThermElite tankless hot water heater.

2. Maximum operating temperature -185°F

3. For each ThermElite unit in the system at a 90°F temperature rise, the recovery rate is as follows:

TE125 -127 GPH TE80 - 88 GPH

4. This schematic employs an electric storage tank water heater. The supply water for the TE loop is drawn by tapping the lower heating element.

5. If circulation flow to the TE heater is restricted, it may be necessary to adjust the temperature control

knob to prevent overheating.

Page 24: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

23

Design 3. Open loop combination potable water and space heating system* To be used with a tank, check local codes. May not be permitted in

some jurisdictions. Models: TE125 / TE80 Applications: High recovery, domestic hot water and radiant space Heating for residential and small commercial installations.

S

CheckValve

ColdWater In

Pressure Relief Velve*

Boiler Drain

Cut-off valve

Primary Pump

Cut-off valve with filter

Hot WaterOut

Dip Tube

Aquastat

Storage Tank

* Pipe PRV to appropriate discharge

Expansion Tank

Secondary Pump

Room Thermostat

NOTES 1. May be used with any model TE125 or TE80 ThermElite tankless hot water heater.

2. Maximum operating temperature -185°F

3. Maximum heating capacity: 40°F rise 20°F rise TE125 80,000 BTU/hr 40,000 BTU/hr TE80 80,000 BTU/hr 40,000 BTU/hr

4. The system diagram shown includes an electric storage tank and recirculating pumps. The supply water for the TE loop is drawn by tapping the lower heating element.

5. If circulation flow to the TE heater is restricted, it may be necessary to adjust the temperature

slide control to prevent overheating CAUTION: Components connected to the water heater for the space heating application shall be suitable for use with potable water

Page 25: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

24

Design 4. ThermElite tankless gas water heater recirculating to a tank for closed-loop hydronic space heating systems

Models: TE125 / TE80 Applications: Residential, small commercial

ColdWater In

Cut-off valve with filter

Primary Pump

Pressure Relief Velve*

Boiler DrainCut-off valve

Expansion Tank

CheckValve

Room Thermostat

Secondary Pump

Dip Tube

Aquastat

Storage Tank

Air Separater

Pressure Reducing Valve

* Pipe PRV to appropriate discharge NOTES 1. May be used with any model TE125 or TE80 ThermElite tankless hot water heater.

2. Maximum operating temperature -185°F

3. Maximum heating capacity: 40°F rise 20°F rise TE125 80,000 BTU/hr 40,000 BTU/hr TE80 80,000 BTU/hr 40,000 BTU/hr

4. The system diagram shown includes an electric storage tank and recirculating pumps. The supply water for the TE loop is drawn by tapping the lower heating element.

5. If circulation flow to the TE heater is restricted, it may be necessary to adjust the temperature slide

control to prevent overheating WARNING: Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used for space heating

Page 26: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

25

ADAPTING THE WATER HEATER TO DIFFERENT GAS TYPES (CONVERSION KIT INSTRUCTIONS) A qualified service agency is any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for the connection, utilization, repair or servicing of gas utilization equipment or accessories; who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction. IN CANADA THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN-B149.1, NATURAL GAS AND PROPANE INSTALLATION CODE. The heater delivered by the manufacturer is designed for the gas shown on the rating plate (Natural Gas or Propane). Check the rating plate on the side of the front cover to be sure that the heater is designed for the specific gas to which it will be connected. If gas conversion is required, determine to what type of gas the heater must be converted. Turn off the gas supply before converting the appliance and leak test the converted water heater prior to placing it into operation. To leak test all joints and replaced parts apply some soapy water to the replaced joints and parts. Look for soap bubbles which are a sign of a leak. Never test for gas leaks using a match or flame. A standard gas detector can also be used to test for leaks instead of using soapy water. The manifold pressure after the conversion shall be as outlined in the gas pressure table in the installation instructions. Instructions on how to measure and adjust the manifold pressure can be found in the Making Adjustments Section of the installation instructions manual. Please follow the minimum and maximum inlet gas pressure as outlined in the gas pressure table in the installation instructions. To check the inlet pressure the qualified service agency doing the conversion shall check the inlet gas pressure in the inlet gas line after it exits the gas pressure regulator just before it enters the heater. The qualified service agency shall use whatever gas pressure measuring instrument they commonly use to test gas pressure.

WARNING: This conversion kit shall be installed by a qualified service agency in accordance with the manufacturers instructions and all applicable codes and requirements of the authority having jurisdiction. The information in these instructions must be followed to minimize the risk of fire or explosion or to prevent property damage, personal injury or death. The qualified service agencyis responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturers instructions supplied with the kit.

Page 27: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

26

After converting the water heater, please verify the input rate. The required input rate for the Natural gas Model is 115,000 BTU/H and for the propane model is 100,000 BTU/H. The burner flame size and shape can be seen in the instructions manual in the schematic diagrams. The pilot flame is automatically adjusted when the ignition burner nozzle is replaced by following the instructions under REPLACEMENT OF THE NOZZLE IN THE IGNITION BURNER found on page 30 of these instructions. The input rate is based on sea level operation (i.e., up to 2,000 ft elevation). For the USA, for operation at elevations above 2,000 ft, the input rating shall be reduced at the rate of 4% for each 1,000 feet above sea level. The models TE125X, TE125H are not approved for high altitude in Canada. Make sure that the following checklist of parts from the conversion kit has been installed. 1. Gas cone replacement part (1 piece) was changed and installed. 2. Gas cone seat part (1 piece) was changed and installed. 3. Main burner nozzles (18 pieces for TE125X and TE125H models or 12 pieces for TE80X and TE80H) was changed and installed.

4. Ignition burner nozzle (1 piece) was changed and installed. Check that the ignition system of the heater is working normally by following the steps outlined in this instruction manual under the INITIAL OPERATION section found on pages 2 through 5 of these instructions. The gas conversion process for models TE125X, TE125H, TE80X and TE80H consists of the following steps:

1. Replacement of gas cones and gas cone seats in gas/water unit (beneath the temperature control valve - see table below.)

2. Replacement of the gas pressure regulator. 3. Replacement of nozzles in the main burner. 4. Replacement of a nozzle in the ignition burner. 5. Testing for leaks. 6. Adjustments. 7. Recording the conversion in the Warranty Book.

Page 28: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

27

The gas conversion for models TE125P and TE80P consists of following steps:

1. Replacement of gas cone and gas cone seat in gas-water unit (see table below), 2. Replacement of nozzles in the main burner, 3. Replacement of a nozzle in the ignition burner 4. Leak tests 5. Adjustment 6. Record in a Warranty Book

Models: TE80X, TE80H, TE125X, TE125H

Part Drawing number

Number of pieces per unit

Remarks Image

Gas cone I

TE125 NG TE 125 LP TE80 NG TE80 LP

053.03.00.01 054.03.00.01 383.03.00.01 384.03.00.01

1

1 1 1

Inner diameter

Ø 8,30 Ø 6,59 Ø 8,43 Ø 6,75

Gas cone II

TE125 NG TE125 LP TE80 NG TE80 LP

053.03.00.03 054.03.00.03 383.03.00.03 384.03.00.03

1 1 1 1

Inner diameter

Ø 8,49 Ø 6,72 Ø 8,50 Ø 6,80

Gas cone seat

TE125 NG TE125 LP TE80 NG TE80 LP

053.03.00.02 054.03.00.02 372.03.00.02 383.03.00.02

1 1 1 1

Inner diameter

Ø 9 Ø 7 Ø 9 Ø 7

Main burner nozzle

TE125 NG TE125 LP TE80 NG TE80 LP

053.01.00.01 374.01.00.01 373.01.00.01 374.01.00.01

18 18 12 12

Designation

126 72

126 72

Ignition burner

nozzle

TE125 NG TE125 LP TE80 NG TE80 LP

383.12.00.01 384.12.00.01 383.12.00.01 384.12.00.01

1 1 1 1

Designation

13 74 13 74

Page 29: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

28

Models: TE125P, TE80P

Part Drawing number Number of pieces per

unit Remarks Image

Gas cone

TE125P NG TE125P LP TE80P NG TE80P LP

053.03.00.01 054.03.00.01 373.03.00.01 374.03.00.01

1 1 1 1

Inner diameter

Ø 8,30 Ø 6,59 Ø 6,35 Ø4,60

Gas cone seat

TE125P NG TE125P LP TE80P NG TE80P LP

053.03.00.02 054.03.00.02 373.03.00.02 374.03.00.02

1 1 1 1

Inner diameter

Ø 9 Ø 7 Ø 9 Ø 7

Main burner nozzle

TE125P NG TE125P LP TE80P NG TE80P LP

053.01.00.01 054.01.00.01 373.01.00.01 374.01.00.01

18 18 12 12

Designation

126 72

126 72

Ignition burner nozzle

TE125P NG TE125P LP TE80P NG TE80P LP

372.02.01.01 374.02.01.01 372.02.01.01 374.02.01.01

1 1 1 1

Designation

blue brown blue

brown

REPLACEMENT OF GAS CONES AND GAS CONE SEATS IN THE GAS/WATER UNIT BENEATH THE TEMPERATURE CONTROL KNOB Models: TE125X,TE125H, TE80X, TE80H Beneath the cover of the gas/water unit is the valve being operated by means of the gas control knob. This valve contains the gas cone II and gas cone seat. To convert the gas/water unit to a different type of gas, follow the steps below:

• Remove the cover by undoing the two screws. • Remove the gas cone; use pliers if necessary. • Remove the gas cone seat, also by pliers if necessary. • Insert the new gas cone in the same direction as the one removed. • Insert the new gas cone seat paying special attention not to damage the sealing

ring. • Re-install the cover. Make sure that the cover is properly set so that the lever

faces toward the micro switch. (Check orientation before removing the cover.)

Page 30: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

29

Gas cone II Gas cone seat

Fig.18 Gas cone II and gas cone seat

In the gas outflow orifice in the gas/water unit (see Fig.19), there is a valve controlled by the water flow which contains gas cone 1, the gas cone seat and a clamp. To convert the gas/water unit to a different type of gas, follow the steps below:

• Remove the ignition burner and main burner along with the connector pipe (item 12 in Fig.11)

• Remove the gas cone using pliers if necessary. • Remove the clamp by means of a screwdriver. • Remove the gas cone seat using pliers if necessary. • Insert the new gas cone in the same direction as the one removed. • Insert the new gas cone seat paying special attention not to damage the sealing

ring. • Secure the gas cone seat with a clamp, paying special attention to properly place

it in a slot.

Gas cone seat clamp Gas cone I

Fig.19 Gas/Water unit

REPLACEMENT OF GAS CONE AND GAS CONE SEAT IN THE GAS-WATER UNIT Models: TE125P, TE80P

In the gas outflow orifice in the gas-water unit, there is a valve controlled by the water flow, which consists of gas cone 1, gas cone seat and a clamp. To convert the gas-water unit to different type of gas follow the steps below:

• Remove the ignition burner and main burner along with connector pipe • Remove gas cone by means of pliers, • Remove the gas cone seat by means of pliers, • Place a new gas cone, • Place a new gas cone seat, paying special attention not to damage the sealing

ring,

Page 31: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

30

• Secure the gas cone seat with a clamp, paying special attention to properly place it in a slot.

Fig.20 Gas water unit

REPLACEMENT OF NOZZLES IN THE MAIN BURNER (All models)

• Undo the mixers subassemblies (left and right) from the burner body (8 bolts), • Remove the old nozzles and screw in the new nozzles (screw the nozzles in

tightly, paying special attention not to damage the threads), • Reconnect the burner to the heater using 8 bolts.

Fig.21 Main burner

Gas cone Gas cone seat

Clamp

Mixers subassemblies

screws

nozzle

Connector pipe to measure gas pressure in the burner

Burner body

Page 32: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

31

REPLACEMENT OF THE NOZZLE IN THE IGNITION BURNER (Models: TE125X, TE125H, TE80X, TE80H)

• Disconnect the pipe from the igniter leading to the ignition burner. • Remove the nozzle from the seat and insert a new one. • Reconnect the pipe to the igniter.

Ignition burner Nozzle

Fig.22 Igniter nozzle REPLACEMENT OF A NOZZLE IN THE IGNITION BURNER (Models: TE125P,TE80P)

• Undo the screw fixing the cover, • Remove the nozzle from the seat and place a new one, • Re-install the ignition burner into the heater.

Fig.23 Ignition burner

cover nozzle Screw

Ignition electrode

Page 33: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

32

MAKING ADJUSTMENTS

Start up the water heater so that the gas on the burner is lit. Set the gas control knob to the maximum position (extreme left.) Connect the manometer to the connector located on the burner body. Set the gas pressure in the burner and in the gas pressure regulator according to the following table. An adjustment screw is visible after unscrewing the aluminum plug in the body of the gas pressure regulator.

Gas Pressure Table

Gas type

Kinetic gas pressure in the installation

Nominal pressure w.c. (inches)

Manifold Pressure w.c. (inches)

Gas consumption1)

(gal/min) Models TE125P, TE125X, TE125H

Natural gas 7 3.4 15,8 Liquid Propane 11 10 4,9

Models: TE80P, TE80X, TE80H Natural gas 7 3.7 10,8

Liquid Propane 11 10 3.2

The Maximum Gas Inlet Pressure (10.5 for Natural Gas, and 13.5 for Propane) must not be exceeded.

1) Gas consumption refers to the listed gases in normal conditions (590 F, atmospheric pressure 14.7 psi) rated at 80% of the water heaters efficiency

Fig. 24 Measurement point

PROTECTION SYSTEMS

• ThermElite tankless gas water heaters feature a protection system preventing an outflow of dangerous flue gas to the room. The system consists of a built-in temperature limiter (item 10, see Fig.14) which shuts off the main valve in the gas/water unit and cuts off the fuel gas inflow to the burner when the chimney draft is smaller than 0.01 W.C. (water column) or there is a back pressure in the chimney. If there is an emergency shutdown of the water heater, you should close any open hot water faucets. After 10 minutes, when the temperature limiter

Page 34: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

33

is cooled down (time depends on the room temperature) the gas water heater will automatically restart and hot water will flow to the faucets. If the emergency shut-down process continues, check the chimney draft. Do not make any modifications to the protection system. Eliminating or modifying the protection system or damaging it may result in a dangerous or even life-threatening outflow of flue gas to the room.

• The Anti-fuel flow protection device is based on an ionization flame control and

eliminates gas inflow to the burner when there is no flame on the burner.

• The guard against overheating of the heat exchanger, consists of temperature limiter (item11, see Fig.14) which shuts off the gas inflow to the main burner and the ignition burner when water temperature in the heat exchanger exceeds the pre-set factory setting of 200° F.

ROUTINE PREVENTATIVE MAINTENANCE The unit should be checked once a year or as often as necessary by a certified and trained technician or licensed plumber. If repairs or service is required, such repairs should likewise be done by a trained technician or knowledgeable plumber. The following systems and parts should be checked at least once a year:

• Venting system - should be checked annually. Clean and repair as needed. • Heat exchanger - in very hard water areas, periodic de-scaling may be

necessary to ensure longer life and higher heat transfer efficiency. To de-scale, remove the heat exchanger from the heater and flush the heating coils with a de-scaling solution or acetic acid (concentration 10-20%). Let the de-scaling product work for 10-15 minutes (if using acetic acid let sit for 3 hours.)

Fig.25 Copper heat exchanger

• Burner – clean the cover plates on the burner segments with a soft brush (not a wire brush.) Pay special attention to check that the cover plates and burner segments have not been damaged.

• Periodic cleaning of the water filter: Should be done if the water flow rate is

noticeably reduced at the faucets or debris is commonly found in water supply.

- Turn off the cold water and gas supply lines to the heater.

WARNING: Turn off any electrical power supply, the manual gas control valve and the manual water control valve before servicing.

Page 35: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

34

- Remove the inlet filter screen at the water inlet with your fingers. - Rinse the water filter screen with running water. - Re-insert the water filter screen.

Fig. 26 Periodic cleaning of the gas filter in the gas/water unit

If the gas flow rate on the main burner is noticeably reduced and the burner does not light up, the gas filter should be cleaned.

- Turn off the cold water and gas supply lines to the heater. - Check and clean the gas filter on the gas supply pipe before the heater. - If there is no gas filter on the gas supply pipe leading to the heater, the inner gas

filter in the gas/water unit may have become plugged. Remove the gas/water unit, remove the inner gas filter and clean it , then re-install the gas/water unit to the heater (see Fig. 26)

• Check-up of protection equipment

- Check-up of protection system against the outflow of flue gas to the room

The temperature limiter (item 10, see Fig.14) is a protection device against outflow of flue gas to room. The temperature limiter is preset for 185±5.4º F To check the correctness of the setting of the temperature limiter: - Insert a thermometer in an empty metal container and fill it with water. - Remove the temperature limiter from its holder by undoing the screws and

place it in the container, immersing only the metal cap. - Heat the water up to 176º F at which point the temperature limiter should

cease to operate. - Continue to heat the water up to 190.4ºF. At this temperature the

temperature limiter should operate.

The properly-operating temperature limiter should disconnect the contacts within the temperature range of 179.6 ºF 190.4º F.

Check-up of protection system against overheating of the heat exchanger

The temperature limiter (item 11, see Fig.14) is also the protection device against exceeding the upper limiting temperature of water in the heater, is pre-

gas filter

Page 36: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

35

set for 185±5.4 º F. To ensure that it is operating properly, follow the steps in the section above. A properly-operating temperature limiter should disconnect the contacts within temperature range of 179.6 º F 190.4º F.

A periodic (at least yearly) visual check of the pilot and burner flames should be made and compared with the pictures on pages 17 & 18 of these instructions. A periodic visual check should be made (at least yearly) of the area around to heater to make sure it is free from combustible material, gasoline and other flammable vapors and liquids. Be sure that there is nothing obstructing the flow of combustion and ventilation air. GENERAL REPAIR/SERVICE DIAGNOSIS During production and assembly, all ThermElite tankless gas water heaters undergo numerous quality assurance tests. However, occasionally during such testing some disturbances may occur. To make it easier to define an eventual malfunction in the heaters operation and to shorten the repair time, helpful information has been listed in the table below. Before starting any repairs, please do the following:

• Check the rating plate on the side of the front cover to ensure that the fuel supply (NG or LP) matches the model heater (P=Propane, N=Natural Gas.)

• Check that the inlet gas pressure meets at least the required minimum. • Check that the sub-atmospheric pressure in the chimney is between 0.01 0.06

inches water column. • Check for weak batteries on the battery status indicator (on heater TE125X.)

Page 37: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

36

Diagnosis of ignition system Once a hot water faucet is opened, water flowing through the heater should ignite the burner as a result of the following process:

- Joining of contacts in the micro switch. - Sparking between the ignition electrode and the spring located on the ignition

burner pipe. - Electrical current to coil #1 opens valve #1 in the pressure differential valve. - Gas lights-up on the ignition burner an ionization current is being sensed by the

monitoring electrode. - Electrical current to coil #2 causes valve #2 in the pressure differential valve to

shut off. - Opening of the main gas valve as a result of a pressure differential above and

beneath the membrane located in the pressure differential valve. - Ignition of the main burner assembly.

Check-up of the ignition system If the ignition system does not operate properly, it should be checked according to the steps below.

1. Check that there are no loose or broken electrical connections. 2. Using a voltmeter, connect to the negative (-) end located: - in heaters TE80X and TE125X - the spring in the battery compartment. - in heater TE80H and TE125H hydro-generator conductor in white - insulation. 3. Connect the voltmeter to the positive end (+) end located: - in heater TE 80X and TE125X the sheet in the battery compartment. - In heater TE80H and TE125H hydro-generator conductor in red - insulation. 4. Measure the voltage - in heater TE80X and TE125X the battery voltage is 1.5 VDC. - in heater TE80H and TE125H hydro-generator voltage at a resistance of - 10Ω and water flow of 0.79 gal/min is 1.3 1.6 VDC. 5. Measure the voltage of the ignition system. The system works properly within the

range of 0.9 1.5V. 6. Check the voltage at the temperature limiter device which protects against the

outflow of flue gas to the room (voltage like on a battery). 7. Check the voltage at the temperature limiter device which protects against the

heat exchanger overheating by cutting-off fuel to the main burner (voltage like on the battery).

8. Check the voltage on the spark generator clamp (voltage like on the battery) 9. Join the micro-switch contacts. Joining the contacts should cause sparking

between the ignition electrode and a spring on the ignition burner pipe 10. Check the voltage on the clamps of coil #1 (the system operates properly at a

voltage of 0.9 1.5 V).

Page 38: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

37

11. After the ionization current is being sensed by the monitoring electrode (after the flame is lit up), check the voltage on the clamps of coil #2 (the system operates properly at voltage of 0.9 1.5 V).

TROUBLESHOOTING

Models: TE125X, TE125H, TE80X, TE80H Problem Reasons What to do 1 2 3 4

• Disconnected electrode conductor

• Improve connection

• Damaged electrode • Check - replace • Damaged spark generator • Check - replace • Run-down battery or damaged

hydro-generator • Check -replace

• Badly adjusted micro-switch • Adjust the micro-switch by screwing down the bolt placed on the micro-switch lever. Make sure that after adjustment there is no sparking when there is no water flow..

• Plugged water filter.(limited water flow)

• Remove impurity, clean, replace

1.

Lack of spark (lack of ignition during water consumption)

• Damaged elements in gas-water unit

⇒ Damaged water membrane ⇒ Damaged control mechanism of

gas valve head

• Replace gas-water unit or damaged elements

• Lack of gas supply (damaged electrode)

• Open the manual gas control valve before the heater

• Air in the gas line • Bleed the air out • Damaged ignition burner • Replace

2. Ignition burner does not light up from the spark

• Run-down battery or damaged hydro-generator

• Replace

• Disconnected conductor of supervision electrode

• Improve connection

• Damaged supervision electrode • Check -replace • Damaged spark generator • Check -replace

3.

Ignition burner lights up, main burner does not light up • Damaged pressure differential

valve • Check -replace

4. Attempted ignition without water flow

• Badly adjusted micro-switch • Adjust the micro-switch by unscrewing the bolt on the micro-switch lever. Make sure that after the adjustment there is no effect of ignition delay while starting the heater.

Page 39: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

38

• Small flame on the burner • Check gas pressure in the installation• Check the setting of gas flow

stabilizer • Impure burner • Remove impurity from cover plates

and nozzles of the burner • Impure ribs in heat exchanger • Remove impurities from the ribs

• De-scale • Improper gas content • Check if the main burner, ignition

burner and gas/water unit are designed for gas being used.

• Excessive discharge of water • Check small water flow- if the flow is greater than 1,5 gal/min , it must be adjusted by a small water discharge screw.

5. Heater does not heat water sufficiently

• Damaged elements of gas- water unit

• Replace gas/water unit or damaged elements

• Badly adjusted gas flow stabilizer

• Adjust the gas flow stabilizer according to section AJUSTMENT in this instruction manual

• Improper gas content • Check if main burner, ignition burner and gas water unit are adapted to gas that is being used

• Small discharge of water • Check small water flow if the flow is smaller than 1,5 gal/min must be adjusted with small water discharge screw

6. Heater overheats water

• Mechanical damage of mechanism controlling gas valve head

• Replace gas/water unit or damaged elements

7. The heater does not shut off after closing the faucet

• Mechanical damage of elements in gas-water unit

• Replace gas/water unit or damaged elements

• Small flame of ignition burner • Damaged pressure differential

valve

• Plugged nozzle of ignition burner- clean or replace

8. Explosive ignition of main burner • Plugged gas flow to the ignition

burner in gas-water unit • Replace gas/water unit or pressure

differential valve • Damaged sealing ring at the

inlet of gas water unit • Replace the sealing ring with the

new one

• Damaged gasket at the outlet of gas-water unit or at the inlet of main burner

• Replace the gasket with the new one9. There are leaks in gas circuit in the heater

• Mechanically damaged gas-water unit

• Replace gas/water unit or damaged elements

Page 40: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

39

• Damaged gasket at the inlet of gas-water unit

• Replace the gasket

• Damaged gasket at the outlet of gas water unit

• Replace the gasket with the new one

• One of gaskets damaged at heat exchanger connections

• Replace the gasket with the new one10.

There are leaks in water system of the heater

• Mechanically damaged gas water unit

• Replace gas water unit or damaged elements

• Protection device was activated ⇒ Protection against outflow of

flue gas to the room

• Check temperature limiter if

damaged, replace.

• Check the correctness of sub-atmospheric pressure in the chimney

⇒ Protection against exceeding the upper limiting temperature of water

• Check the temperature limiter- if damaged, replace

11.

The heater shuts off during operation during water consumption

• Improper chimney draft • Check the chimney ducts • Yellow flame • Impure burner (improper

burning)

• Check the type of gas • Clean the burner 12

The ribs of heat exchanger get dirty in a short period of time

• Too much gas consumption • Check -adjust

TE125P, TE80P Problem Reason What to do 1 2 3 4

1. Heater does not start up

• ignition burner does not heat the end of the thermocouple sufficiently

• increase the flame of ignition burner by means of adjustment screw

• the nozzle of ignition burner is plugged-clean or replace

• clean the end of thermocouple • lack of current transition between

the contacts of thermocouple conductor subassembly and a temperature limiter

• clean the connection slide-sleeve • check the clamp of the sleeve on the

slide • check if there is the current transition on

the temperature limiter (if there is no transition, change the temperature limiter)

• improperly fixed thermocouple conductor subassembly end to the gas-water unit (lack of contact between end and electromagnet)

• tighten up the end • clean gently the tin part of the end

• defective thermocouple conductor subassembly

• replace the thermocouple conductor subassembly

• defective electromagnet in gas-water unit

• check the protection system by means of a model electromagnet

• if the test of protection system with a

Page 41: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

40

model electromagnet is positive, replace the gas-water unit with the new one

• plugged water filter • remove the impurity • damaged elements in gas-water

unit ⇒ damaged water membrane ⇒ damaged control mechanism of gas

valve head ⇒ plugged gas flow to the ignition

burner

• replace the gas-water unit with the new one

2. Heater does not heat the water sufficiently

• small flame on the burner • check the gas pressure in the installation• check the setting of gas pressure

regulator • impure burner • remove the impurity from the cover

plates and nozzles of the burner • impure ribs in the heat exchanger • remove the impurities from the ribs

• descale • improper gas content • check if main burner, ignition burner

and gas-water unit are designed for gas being used

• excessive discharge of water • check small water flow if the flow is greater than 1,5 gal/min , it must be adjusted by a small water discharge screw

• damaged elements of gas-water unit

• replace the gas-water unit with the new one

3. Heater overheats the water

• badly set gas pressure regulator • readjust the gas pressure regulator to the local conditions

• improper gas content • check if the main burner, ignition burner and gas-water unit are adapted to the gasbeing used

• small discharge of water • check small water flow if the flow is smaller than 1,5 gal/min , it must be adjusted by a small water discharge screw

• mechanical damage of mechanism controlling gas valve head

• replace the gas-water unit with the new one

4. The heater does not shut off after closing the water flow

• mechanical damage of elements in gas-water unit

• replace the gas-water unit

5. Explosive ignition of main burner

• small flame on ignition burner • increase the flame on the ignition burner by means of a adjusting screw.

• Plugged nozzle of ignition burner clean or replace

• Plugged inflow of gas to the ignition burner in the gas-water unit

• Replace gas-water unit with the new one

6. There are leaks in the gas circuit in the heater

• Damaged sealing ring at the inlet of gas-water unit

• Replace the sealing ring with the new one

Page 42: ThermElite - Healthy Home MallISU-217:2004 część angielska 4 5. Set the desired water temperature and the water flow rate using the temperature selection knob. 6. After …

ISU-217:2004 część angielska

41

• Damaged gasket at the outlet of gas-water unit or at the inlet of main burner

• Replace the gasket with the new one

• Mechanically damaged gas-water unit

• Replace the gas-water unit with the new one

There are leaks in water system of the heater

• Damaged gasket at the inlet of gas-water unit

• Replace the gasket

• Damaged gasket at the outlet of gas-water unit

• Replace the gasket

• One of gaskets is damaged at the connections of heat exchanger

• Replace the gasket with the new one

7.

• Mechanically damaged gas-water unit

• Replace the gas-water unit with the new one

WARNING: A water heater that will be used to supply potable water shall not be connected to any heating system or component(s) previously used with a non-potable water heating system. When the system requires water for space heating at temperatures higher than required for other uses, a means such as a mixing valve shall be installed to temper the water for those uses in order to reduce scald hazard potential. MANUFACTURER Termet S.A.

Ul.Walbrzyska 33 58-160 Swiebodzice, Poland

www.termet.com.pl

Gas water heater- SPECIFICATION

Parameter Unit TE125X TE125H TE125PInput rating BTU/HR 28 000 - 117 000 Efficiency % 82 (INPUT)

Working pressure Psi 4.4 -150 Hot water output (∆ t = 90 °F)

gal/min 0,9 ÷ 2,1

Hot water output (∆ t = 45° F)

gal/min 1,8 ÷ 4,2

Max. temperature of outlet water

° F 185

Vent terminal inch 5 Overall dimensions inch 28-3/8 x 18-1/8 x 9-31/3 Weight lbs 40 36 Gas connection Water connection (both ½ adaptable)

Inch Inch

¾ ¾

Gas water heater- SPECIFICATION

Parameter Unit TE80X TE80H TE80P Input rating BTU/HR 21 000 - 80 000 Efficiency % 82 (INPUT)

Working pressure Psi 4.4 - 150 Hot water output (∆ t = 90 °F)

gal/min 0,73 ÷ 1,5

Hot water output (∆ t = 45° F)

gal/min 1,5 ÷ 2,9

Max. temperature of outlet water

° F 185

Vent terminal inch 5 Overall dimensions inch 25-5/8 x 14-1/8 x 7-1/4 Weight lbs 24 20 Gas connection Water connection (both ½ adaptable)

Inch Inch

¾ ¾