1 greenTEG’s Thermal Insulation Measurement Devices 12 pages «take the guesswork out of thermal monitoring» Cases from the Middle East

Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

1

greenTEG’sThermal InsulationMeasurement Devices

12 pages

«take the guesswork out of thermal monitoring»

Cases from the Middle East

Page 2: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

2

Why bother about the U-Value?

The U-Value is a standardized measurement unit of building thermal insulation quality.

The lower the U-Value, the better the insulation.

U-Values are important building metrics in cold climates.

Even though U-Values are less commonly referred to in hot climates, they are nevertheless important.

Page 3: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

3

Why bother about the U-Value?

Cold Climates

Houses are heated.

If the bulding thermal insulation isnot good enough, heating energy is

lost to the environment.

More heating is necessary to keepthe indoor temperature constant.

Hot Climates

Houses are air-conditioned.

If the bulding thermal insulation isnot good enough, heat from theenvironment enters the building.

More air-conditioning is necessaryto keep the indoor temperature

constant.

Page 4: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

4

Examples for hot climates

Case study «Measurement of the heat storage capacity of building elements»

In hot climates, heat is stored in the building envelope and released to the interior of the building. Thisstudy shows how you can measure this heat and how you can find out if improving the buildingenvelope will save energy. Read more.

The study is conducted by Lemon Consult, an energy consultancy in Zurich, Switzerland.

Case study «Measurement of the U-Value in an Arabian Villa» &Case study «Energy Audit and Retrofitting in Yarmouk, Kuwait»

These case studies show how greenTEG’s U-Value KIT can be used to measure U-Values in hotclimates.

The studies are conducted by Smart Insulation Finishing Systems, a distributor of greenTEG in Dubai, United Arab Emirates.

Page 5: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Measurement of the U-Value

in an Arabian Villa5

Page 6: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Measurement of the U-Value in an Arabian Villa6

greenTEG’s

U value measurement kit

Temp.

U-Value

Page 7: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Measurement of the U-Value in an Arabian Villa

45 % reduction of energy losses with a 50 mm

SW Panel retrofit…

7

Current ConditionWith Smart Wall

Panel (50 mm)

With Smart Wall Panel

(100 mm)

U Value

W/m2.degC

Energy losses (Q/A)

kWh/m2/year

Total Energy Loss

through wall

kWh/year

Energy Saving

kWh/year

% 45 73

Cooling degree days for

UAE (CDD)7782

https://www.wunderground.com/history/airport/OMDB

Villa Wall area (m2) 470

*meaured using greenteg monitoring device which meausres U value in real-time using a method standardized in ISO

9869

39,501 63,641

Note

x

184.90 100.85 49.49

86,903 47,402 23,262

Arabian Ranches Villa Case Study

0.99* 0.54 0.265

Typical Masonry

wall

Retrofit with Smart

Wall Panel (50 mm)

Retrofit with EPS based

EIFS system (50 mm)

Retrofit with Rockwool

based EIFS system (50

mm)

U Value

W/m2.degC

Energy losses (Q/A)

kWh/m2/year

Energy Saving

%

Cooling degree days for

UAE (CDD)7782

Note

https://www.wunderground.com/history/airport/OMDB

0.64

119.53

87

Energy Savings when retrofitting a typical Masonry Wall (no insulation)

0.58

108.33

88x 90

5 0.48

933.84 89.65

Reduction of energy losses through

retrofitting recommended

Page 8: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Energy Audit and Retrofitting

in Yarmouk, Kuwait

Page 9: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Energy Audit and Retrofitting in Yarmouk, Kuwait

Typical U-Values New Regulation in Kuwait (2018)

Page 10: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Energy Audit and Retrofitting in Yarmouk, Kuwait

Page 11: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Energy Audit and Retrofitting in Yarmouk, Kuwait

Page 12: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Energy Audit and Retrofitting in Yarmouk, Kuwait

Energy audit

Detailed analysis of each wall

Recommendations for retrofitting

Page 13: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

Energy Audit and Retrofitting in Yarmouk, Kuwait

Before

After

Page 14: Thermal Insulation Measurement Devices...If the bulding thermal insulation is not good enough, heat from the environment enters the building. More air-conditioning is necessary to

14

Two systems to measure U-values

Energy Audit and Retrofittingin Yarmouk, Kuwait

gO Measurement System

• Wireless, Cloud based• Multiple parallel measurements possible

Measurement of the U-Valuein an Arabian Villa

U-Value Kit