Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
HEATING AND COOLING
SIDE STREAM FILTRATION
www.V E XO i n t .co m
OSUPERIOR PROTECTION FOR HVAC SYSTEMS UP TO 95 C
Product of the Year
Commercial Building Services
WINNER
Product innovationof the year
The UK’S best sel l ing choice in its class
VEXO Proposal Doc Ver. 1.0 01/06/2020
Potential dangers hiding in closed system water.
Water is the main means of closed system
temperature distribution. It affects every single
piece of equipment and every single person in
the spaces that you manage. Wherever there is
closed loop system water four problems will
occur: scale formation, corrosion, fouling and
microbial growth.
The problem with dirty water
1. Scale formation
2. Corrosion
3. Microbial growth
4. Fouling & sludge
What dirty system water can do if left untreated.
Page 3
Why do you need superior filtration installed on your closed loop system?
At the heart of your facility
is a perfectly good heating
or cooling system.
This leads to
bad distribution,
breakdowns,
cold spots and
energy waste.
LIMESCALE
METALLIC SLUDGE
BACTERIALBIOFILM
You could be losing over 10% energy from dirty system water alone!
It loses its energy
and transfer capacity
to a fouled and dirty
circulatory system.
Erosion corrosion
Reduction in efficacy of inhibitor
Harbouring bacteria proliferation
Settlement of sediment
Non-repeatable commissioning readings
Delayed project handovers
Landlord losing tenants could lead to litigation
Efficiency losses
Lifecycle losses
Damage to reputation
YOUR INVESTMENT
PR
OG
RE
SS
IVE
LY L
ES
S R
OI
WHAT’S LEFT OF YOUR INVESTMENT
Page 2
How neglecting your hydronic thermal fluidcan affect your bottom line
Your investment reduces as dirty system water
slowly erodes your OPEX and reputation.
VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021
VEXO Proposal Doc Ver. 1.0 01/06/2020
Potential dangers hiding in closed system water.
Water is the main means of closed system
temperature distribution. It affects every single
piece of equipment and every single person in
the spaces that you manage. Wherever there is
closed loop system water four problems will
occur: scale formation, corrosion, fouling and
microbial growth.
The problem with dirty water
1. Scale formation
2. Corrosion
3. Microbial growth
4. Fouling & sludge
What dirty system water can do if left untreated.
Page 3
Why do you need superior filtration installed on your closed loop system?
At the heart of your facility
is a perfectly good heating
or cooling system.
This leads to
bad distribution,
breakdowns,
cold spots and
energy waste.
LIMESCALE
METALLIC SLUDGE
BACTERIALBIOFILM
You could be losing over 10% energy from dirty system water alone!
It loses its energy
and transfer capacity
to a fouled and dirty
circulatory system.
Erosion corrosion
Reduction in efficacy of inhibitor
Harbouring bacteria proliferation
Settlement of sediment
Non-repeatable commissioning readings
Delayed project handovers
Landlord losing tenants could lead to litigation
Efficiency losses
Lifecycle losses
Damage to reputation
YOUR INVESTMENT
PR
OG
RE
SS
IVE
LY L
ES
S R
OI
WHAT’S LEFT OF YOUR INVESTMENT
Page 2
How neglecting your hydronic thermal fluidcan affect your bottom line
Your investment reduces as dirty system water
slowly erodes your OPEX and reputation.
VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021
Page 4 Page 5
The VEXO X-POT is the UK leader in closed loop side stream filtration.
Higher System performance at a
smaller budget
Greater reliability with reduced
critical down time, increased heat
distribution, fewer call outs and
happier tenants.
Multi-Functional Design
Retro-fit all-in-one Solution
Particle sizelimitations
Only dosesadditives
Magnetite removal only
Improved system life cycle resulting
in CAPEX savings, reductions in
reactive maintenance and
operational cost savings.
Provides protection for new
systems and improved system
efficiency for aged systems;
resulting in less flushing, a
reduction in CO2 and a more
environmentally friendly facility.
MAGNETICFILTERS
DOSINGPOTS
DIRT & AIRSEPARATORS
Industry Leading Multi-Layered Filtration
The X-POT combines most current system filtration units into
one easy-install, easy-service, BSRIA acknowledged water
conditioning product.
THE ALL-IN-ONESOLUTION
VEXO X-POT
ALL IN ONE
.
Blocks due to magnetite sludge
CARTRIDGE & BAGFILTERS
What is the VEXO X-POT?
Absolutely. We have independently proven 3.5% energy saving after just 1 week, and an additional 5-10% savings with added X-PO10 Inhibitor!
Does the VEXO X-POT really work?
"The X-POT Side Stream
filtration system reduced
energy consumption by 3.5%
within the first 7 days of use"
Johnathan Cripps, MSc Dissertation: Low Energy Building Services Engineering (Effects of Corrosion on Heat Transfer Efficiency within a Heating System)
Loughborough University
"Results suggest gas bill
reductions of up to 10% are
possible whilst prolonging the
life cycle of existing heating
systems."
Dr Rayner Mayer, Trials of VEXO X-PO10 InhibitorSciotech Projects
University of Reading
The results speak for themselves. With thousands of X-POT's installed across the world, all with 100% positive client feedback. Below are just a few of our recent examples.
VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021
Page 4 Page 5
The VEXO X-POT is the UK leader in closed loop side stream filtration.
Higher System performance at a
smaller budget
Greater reliability with reduced
critical down time, increased heat
distribution, fewer call outs and
happier tenants.
Multi-Functional Design
Retro-fit all-in-one Solution
Particle sizelimitations
Only dosesadditives
Magnetite removal only
Improved system life cycle resulting
in CAPEX savings, reductions in
reactive maintenance and
operational cost savings.
Provides protection for new
systems and improved system
efficiency for aged systems;
resulting in less flushing, a
reduction in CO2 and a more
environmentally friendly facility.
MAGNETICFILTERS
DOSINGPOTS
DIRT & AIRSEPARATORS
Industry Leading Multi-Layered Filtration
The X-POT combines most current system filtration units into
one easy-install, easy-service, BSRIA acknowledged water
conditioning product.
THE ALL-IN-ONESOLUTION
VEXO X-POT
ALL IN ONE
.
Blocks due to magnetite sludge
CARTRIDGE & BAGFILTERS
What is the VEXO X-POT?
Absolutely. We have independently proven 3.5% energy saving after just 1 week, and an additional 5-10% savings with added X-PO10 Inhibitor!
Does the VEXO X-POT really work?
"The X-POT Side Stream
filtration system reduced
energy consumption by 3.5%
within the first 7 days of use"
Johnathan Cripps, MSc Dissertation: Low Energy Building Services Engineering (Effects of Corrosion on Heat Transfer Efficiency within a Heating System)
Loughborough University
"Results suggest gas bill
reductions of up to 10% are
possible whilst prolonging the
life cycle of existing heating
systems."
Dr Rayner Mayer, Trials of VEXO X-PO10 InhibitorSciotech Projects
University of Reading
The results speak for themselves. With thousands of X-POT's installed across the world, all with 100% positive client feedback. Below are just a few of our recent examples.
VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021
Page 6
Side stream filtration for small tomedium commercial systems
Side stream filtration including
a magnetic filter, cartridge filter,
air and dirt separator and dosing
unit for small to medium
commercial systems.
Max working pressure: 4 Bar
Max system volume: 34,560 litres
Flow rate: Up to 24 l/m
Pipe connection: 1/2" BSP
Filtration rate: Down to 0.5 micron
Side View Front View Plan View
1 "/2
TUNDISH
1 "/2
AAV
NRV
DRAIN and/or clean RTN
DIR
TY
FL
OW
63
0 12,5
100
175 12
,59
5
156
220
90
75
107
DRAIN and/or clean RTN
1 "/2
DIR
TY
FL
OW
1 "/21 "/2
MAIN VENT
MAIN VENT
LEFT /RIGHT orBOTTOM
Conn.
DIRTYFLOW
285
225
190
190
135
TUNDISH
AAV
®
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
Page 7
Side stream filtration including
a magnetic filter, cartridge
filter, air and dirt separator
and dosing unit for medium
to large commercial systems.
Max working pressure: 7 Bar
Max system volume: 86,400 litres
Flow rate: Up to 60 l/m
Pipe connection: 1" BSP
Filtration rate: Down to 0.5 micron
TUNDISH
AAV
NRV
MAIN VENT
DIRTYFLOW
CLEANRETURN
DRAIN
LEFT HANDDIRTY FLOW
206
TUNDISH
AAV
MAIN VENT
NRV
DIRTYFLOW
CLEANRETURN
DRAIN
915
75
180
40
26
0
34
0
1 "/2
"1
"1
"1
"1460260
225
175
130
TUNDISH
AAVMAINVENT
DIRTYFLOW
PLUG
1 "/2 "1
Side View Front View Plan View
Side stream filtration for medium to large commercial systems
®
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021
Page 6
Side stream filtration for small tomedium commercial systems
Side stream filtration including
a magnetic filter, cartridge filter,
air and dirt separator and dosing
unit for small to medium
commercial systems.
Max working pressure: 4 Bar
Max system volume: 34,560 litres
Flow rate: Up to 24 l/m
Pipe connection: 1/2" BSP
Filtration rate: Down to 0.5 micron
Side View Front View Plan View
1 "/2
TUNDISH
1 "/2
AAV
NRV
DRAIN and/or clean RTN
DIR
TY
FL
OW
63
0 12,5
100
175 12
,59
5
156
220
90
75
107
DRAIN and/or clean RTN
1 "/2
DIR
TY
FL
OW
1 "/21 "/2
MAIN VENT
MAIN VENT
LEFT /RIGHT orBOTTOM
Conn.
DIRTYFLOW
285
225
190
190
135
TUNDISH
AAV
®
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
Page 7
Side stream filtration including
a magnetic filter, cartridge
filter, air and dirt separator
and dosing unit for medium
to large commercial systems.
Max working pressure: 7 Bar
Max system volume: 86,400 litres
Flow rate: Up to 60 l/m
Pipe connection: 1" BSP
Filtration rate: Down to 0.5 micron
TUNDISH
AAV
NRV
MAIN VENT
DIRTYFLOW
CLEANRETURN
DRAIN
LEFT HANDDIRTY FLOW
206
TUNDISH
AAV
MAIN VENT
NRV
DIRTYFLOW
CLEANRETURN
DRAIN
915
75
180
40
26
0
34
0
1 "/2
"1
"1
"1
"1460260
225
175
130
TUNDISH
AAVMAINVENT
DIRTYFLOW
PLUG
1 "/2 "1
Side View Front View Plan View
Side stream filtration for medium to large commercial systems
®
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021
Page 8
Side stream filtration for large tovery large commercial systems
Side View Front ViewPlan View
AAV
MAIN VENT
1 "/2
TUNDISH
NRV
"1
DIRTYFLOW
1 "/2
146
0
870
135
135
206
TUNDISH
AAV"1
NRV1 "/2
PG
PG
DRAINCLEAN
RETURN
DIRTYFLOW
WALL BRACKET
430
900DIRTYFLOW
CL
EA
NR
ET
UR
N
MAINVENT
PG
43
03
00
490
195
DRAIN
2"
2"
2"
2"
Vexo X-Pot Brochure V2.0
1 "/2
2"
Max working pressure: 16Bar
Max system volume: 302,400 litres
Flow rate: Up to 210 l/m
2" BSPPipe connection:
Filtration rate: Down to 1 micron
Side stream filtration including a magnetic filter,
bag filter, air and dirt separator and dosing
unit for large to very large commercial systems.
Page 9
Made to order filtration for extreme high pressure or flow
Max working pressure: 30Bar
Max system volume: 302,400 litres
Flow rate: Up to 210 l/m
2" BSPPipe connection:
Filtration rate: Down to 1 micron
Side stream filtration including a magnetic filter,
bag filter, air and dirt separator and dosing unit
for extremely high pressure, high flow commercial systems.
Max working pressure: 10 or 30 Bar options
Max system volume: 2,592,000 litres
Up to 1800 l/mFlow rate:
6" PN 10 or 6" PN 30Pipe connection:
Filtration rate: Down to 1 micron.
Side stream filtration including a magnetic filter,
bag filter, air and dirt separator and dosing unit
for very large commercial systems.
HFHP
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021
Page 8
Side stream filtration for large tovery large commercial systems
Side View Front ViewPlan View
AAV
MAIN VENT
1 "/2
TUNDISH
NRV
"1
DIRTYFLOW
1 "/2
146
0
870
135
135
206
TUNDISH
AAV"1
NRV1 "/2
PG
PG
DRAINCLEAN
RETURN
DIRTYFLOW
WALL BRACKET
430
900DIRTYFLOW
CL
EA
NR
ET
UR
N
MAINVENT
PG
43
03
00
490
195
DRAIN
2"
2"
2"
2"
Vexo X-Pot Brochure V2.0
1 "/2
2"
Max working pressure: 16Bar
Max system volume: 302,400 litres
Flow rate: Up to 210 l/m
2" BSPPipe connection:
Filtration rate: Down to 1 micron
Side stream filtration including a magnetic filter,
bag filter, air and dirt separator and dosing
unit for large to very large commercial systems.
Page 9
Made to order filtration for extreme high pressure or flow
Max working pressure: 30Bar
Max system volume: 302,400 litres
Flow rate: Up to 210 l/m
2" BSPPipe connection:
Filtration rate: Down to 1 micron
Side stream filtration including a magnetic filter,
bag filter, air and dirt separator and dosing unit
for extremely high pressure, high flow commercial systems.
Max working pressure: 10 or 30 Bar options
Max system volume: 2,592,000 litres
Up to 1800 l/mFlow rate:
6" PN 10 or 6" PN 30Pipe connection:
Filtration rate: Down to 1 micron.
Side stream filtration including a magnetic filter,
bag filter, air and dirt separator and dosing unit
for very large commercial systems.
HFHP
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
*Extended to 8 years if used with VEXO Inhibitor
and supplied parts.
5 YEAR
VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021
Page 10 Page 11
Side stream filtration with integratedpump, alarm and BMS compatibility
Max working pressure: 10 Bar
Max system volume: 86,400 litres
Flow rate: 60L/min (1.0L/s)
1" BSPPipe connection:
Filtration rate: Down to 0.5 micron
VEXO™ X-POT XP+ Side Stream Filtration
& Dosing Unit with integrated pump and
BMS Compatibility for large to very large
commercial systems.
Max working pressure: 16 Bar
Max system volume: 302,400 litres
60-210L/min (1.0-3.50L/s)Flow rate:
2" BSPPipe connection:
Filtration rate: Down to 1 micron.
VEXO™ X-POT6+ Side Stream Filtration
& Dosing Unit with integrated pump,
fault alarm and Enhanced BMS Compatibility
for medium to large commercial systems.
*Extended to 3 years if used with VEXO Inhibitor
and supplied parts.
2 YEAR
*Extended to 3 years if used with VEXO Inhibitor
and supplied parts.
2 YEAR
Indicative X-POT Side Stream Filtration Installations
TWIN PUMPX-POT
INSTALLATION
ZONE/MULTIPLEPUMP X-POT
INSTALLATIONSINGLE PUMP
X-POTINSTALLATION
The size of the connections to the X-POT is determined by the total system volume
being circulated through the X-POT in a 24 Hour
period.
10.083 - 0.4 I/s = / " Conn.230.4 - 0.6 l/s = / " Conn.4
0.6 - 1.0 l/s = 1" Conn.11.0 - 1.2 l/s = 1 / " Conn.411.2 - 2.1 l/s = 1 / " Conn.2
2.1 - 3.5 l/s = 2" Conn.
Working Pressure : 3BarSystem volume :
22,500Litres = 0.26 l/secChosen Vessel : X-POT Compact
Connection Size :1/2”
Working Pressure : 10BarSystem volume :
90,000Litres = 1.04 l/secChosen Vessel : X-POT XP
Connection Size : 1 1/4"
EXAMPLES
SYSTEM VOLUME
86,400sec l/sec
Which connectionsand X-POT?
Indicative system placement
PICV (Not supplied by VEXO)
Packaged Differential Pressure Monitor
1
2
PDMONITOR
CLEAN RETURN
PICV
1IV IV
STR
SYSTEMPUMP
DIRTYFLOW
SYSTEMFLOW
SYSTEMRETURN
PRESSUREINDEPENDENTCONTROLVALVE
HEATSOURCE
STR
X-POT
AAV
NRVIV
IV
IV
IV
IV
DRAIN2
Installationexample
The X-POT provides a number of installation
solutions. These examples are INDICATIVE
ONLY. If your system cannot accommodate
any of these scenarios due to complexity,
please contact the VEXO Technical Team:
+44 (0)1767 500 150 / [email protected]
THE X-POT SHOULD BE FITTED ON
THE SECONDARY
HEATING CIRCUIT TO
ENSURE BULK WATER SYSTEM
PROTECTION
24Hours
SystemVolume
ISOLATION VALVE
NON RETURN VALVE
STRAINER
AUTO AIR VENT
PRESSURE GAUGE
TEMPERATURE GAUGE
PRESSURE RELEASE VALVE
FLEX CONNECTION
PUMP
TM VEXO PD-MONITOR
PRESSURE INDEPENDENTCONTROL VALVE
COMMISSIONING VALVE
3 PORT VALVE
VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021
Page 10 Page 11
Side stream filtration with integratedpump, alarm and BMS compatibility
Max working pressure: 10 Bar
Max system volume: 86,400 litres
Flow rate: 60L/min (1.0L/s)
1" BSPPipe connection:
Filtration rate: Down to 0.5 micron
VEXO™ X-POT XP+ Side Stream Filtration
& Dosing Unit with integrated pump and
BMS Compatibility for large to very large
commercial systems.
Max working pressure: 16 Bar
Max system volume: 302,400 litres
60-210L/min (1.0-3.50L/s)Flow rate:
2" BSPPipe connection:
Filtration rate: Down to 1 micron.
VEXO™ X-POT6+ Side Stream Filtration
& Dosing Unit with integrated pump,
fault alarm and Enhanced BMS Compatibility
for medium to large commercial systems.
*Extended to 3 years if used with VEXO Inhibitor
and supplied parts.
2 YEAR
*Extended to 3 years if used with VEXO Inhibitor
and supplied parts.
2 YEAR
Indicative X-POT Side Stream Filtration Installations
TWIN PUMPX-POT
INSTALLATION
ZONE/MULTIPLEPUMP X-POT
INSTALLATIONSINGLE PUMP
X-POTINSTALLATION
The size of the connections to the X-POT is determined by the total system volume
being circulated through the X-POT in a 24 Hour
period.
10.083 - 0.4 I/s = / " Conn.230.4 - 0.6 l/s = / " Conn.4
0.6 - 1.0 l/s = 1" Conn.11.0 - 1.2 l/s = 1 / " Conn.411.2 - 2.1 l/s = 1 / " Conn.2
2.1 - 3.5 l/s = 2" Conn.
Working Pressure : 3BarSystem volume :
22,500Litres = 0.26 l/secChosen Vessel : X-POT Compact
Connection Size :1/2”
Working Pressure : 10BarSystem volume :
90,000Litres = 1.04 l/secChosen Vessel : X-POT XP
Connection Size : 1 1/4"
EXAMPLES
SYSTEM VOLUME
86,400sec l/sec
Which connectionsand X-POT?
Indicative system placement
PICV (Not supplied by VEXO)
Packaged Differential Pressure Monitor
1
2
PDMONITOR
CLEAN RETURN
PICV
1IV IV
STR
SYSTEMPUMP
DIRTYFLOW
SYSTEMFLOW
SYSTEMRETURN
PRESSUREINDEPENDENTCONTROLVALVE
HEATSOURCE
STR
X-POT
AAV
NRVIV
IV
IV
IV
IV
DRAIN2
Installationexample
The X-POT provides a number of installation
solutions. These examples are INDICATIVE
ONLY. If your system cannot accommodate
any of these scenarios due to complexity,
please contact the VEXO Technical Team:
+44 (0)1767 500 150 / [email protected]
THE X-POT SHOULD BE FITTED ON
THE SECONDARY
HEATING CIRCUIT TO
ENSURE BULK WATER SYSTEM
PROTECTION
24Hours
SystemVolume
ISOLATION VALVE
NON RETURN VALVE
STRAINER
AUTO AIR VENT
PRESSURE GAUGE
TEMPERATURE GAUGE
PRESSURE RELEASE VALVE
FLEX CONNECTION
PUMP
TM VEXO PD-MONITOR
PRESSURE INDEPENDENTCONTROL VALVE
COMMISSIONING VALVE
3 PORT VALVE
VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021
Page 12 Page 13
Upgrade your X-POT with a simple andadaptive monitor for system flow issues
Compatible with all hybrid applications.
DISPLAY
CONTROLLER
BEACONON/OFF
DISPLAY
CONTROLLER
BEACONON/OFF
DISPLAY
CONTROLLER
BEACONON/OFF
DISPLAY
CONTROLLER
BEACONON/OFF
DISPLAY
CONTROLLER
BEACONON/OFF
PD-MONITOR
PD-MONITOR PD-MONITOR
PD-MONITOR
PD-MONITOR
FILTRATIONPLANT
AIR HANDLING PLANT
HEAT EXCHANGER
SYSTEM PUMPS
PD-Monitor can be used for various hybrid applications
(i.e. plate heat exchangers, AHU coils and process equipment monitoring).
A packaged, wall mounted and factory tested
differential pressure monitoring unit
incorporating controller, two pressure
transducers, 240V ac mains cable and BMS
capability.
1 off Pre-Settable PICV
(X-POT Compact - DN20) (X-POT6 - DN32)
(X-POT XP LF - DN50) (X-POT XP HF - DN50 Flanged)
1 off Insulation Jacket
1 off Vexo PD-Monitor 0-30 Bar Modbus
1 YEAR
The X-POT Compliance Packs
The X-POT Compliance Pack completes your X-POT installation in accordance with Best Practise BSRIA BG29/50 Guidance.
The X-POT Compliance Pack features our pre-settable PICV for simple and
accurate commissioning, insulation jacket for our PICV to reduce thermal
loss and our PD-Monitor to accurately track your X-POT filter status, so
your system operates at its full potential.
BSRIA BG29/2020 recommends ‘5% of the circulating water should be diverted through the side stream filter' and 'Filters should be easily maintainable and fitted with a differential pressure indicator or BMS sensor'.
V-XCOMP(CP)PACK
X-POT Compact
DN20
V-XPOT6(CP)PACK
X-POT6
DN32
V-XPXP-LF(CP)PACK
X-POT XP LF
DN50
V-XPXP-LF(CP)PACK
X-POT XP HF
DN50 Flanged
X-POT COMPLIANCE PACK VARIATIONS & ORDER CODES
Each Compliance Pack contains:
Remote alarm for blocked X-POT filters
10 Bar & 30 Bar Max. working pressure options
Can be linked to BMS
Audible alarm and flashing beacon
Simple, adaptive monitor for system flow issues
VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021
Page 12 Page 13
Upgrade your X-POT with a simple andadaptive monitor for system flow issues
Compatible with all hybrid applications.
DISPLAY
CONTROLLER
BEACONON/OFF
DISPLAY
CONTROLLER
BEACONON/OFF
DISPLAY
CONTROLLER
BEACONON/OFF
DISPLAY
CONTROLLER
BEACONON/OFF
DISPLAY
CONTROLLER
BEACONON/OFF
PD-MONITOR
PD-MONITOR PD-MONITOR
PD-MONITOR
PD-MONITOR
FILTRATIONPLANT
AIR HANDLING PLANT
HEAT EXCHANGER
SYSTEM PUMPS
PD-Monitor can be used for various hybrid applications
(i.e. plate heat exchangers, AHU coils and process equipment monitoring).
A packaged, wall mounted and factory tested
differential pressure monitoring unit
incorporating controller, two pressure
transducers, 240V ac mains cable and BMS
capability.
1 off Pre-Settable PICV
(X-POT Compact - DN20) (X-POT6 - DN32)
(X-POT XP LF - DN50) (X-POT XP HF - DN50 Flanged)
1 off Insulation Jacket
1 off Vexo PD-Monitor 0-30 Bar Modbus
1 YEAR
The X-POT Compliance Packs
The X-POT Compliance Pack completes your X-POT installation in accordance with Best Practise BSRIA BG29/50 Guidance.
The X-POT Compliance Pack features our pre-settable PICV for simple and
accurate commissioning, insulation jacket for our PICV to reduce thermal
loss and our PD-Monitor to accurately track your X-POT filter status, so
your system operates at its full potential.
BSRIA BG29/2020 recommends ‘5% of the circulating water should be diverted through the side stream filter' and 'Filters should be easily maintainable and fitted with a differential pressure indicator or BMS sensor'.
V-XCOMP(CP)PACK
X-POT Compact
DN20
V-XPOT6(CP)PACK
X-POT6
DN32
V-XPXP-LF(CP)PACK
X-POT XP LF
DN50
V-XPXP-LF(CP)PACK
X-POT XP HF
DN50 Flanged
X-POT COMPLIANCE PACK VARIATIONS & ORDER CODES
Each Compliance Pack contains:
Remote alarm for blocked X-POT filters
10 Bar & 30 Bar Max. working pressure options
Can be linked to BMS
Audible alarm and flashing beacon
Simple, adaptive monitor for system flow issues
VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021
Page 14
Our range of superior quality filters provides top class filtration, surpassing UK and USA Industry Standards.
X-POT fine filtration
800
700
600
500
400
300
200
100
0 10 6030 40 5020
Water Flow Rate (L/m)0.5µ Filter
Flow DP of X-POT Compact & X-POT6 Cartridge Filters including Magnet Grate
Pre
ssu
re D
rop
(m
bar)
X-POT Compact
5µ Filter
20µ Filter 50µ Filter
½" Conns 3/4" Conns 1" Conns
X-POT6
NOTE - Choice of X-POT is dependent upon system working pressure and system volume.Dirty filter state can be estimated by multiplying the clean filter state by a factor of 2.
800
700
600
500
400
300
200
100
0 20 12060 80 10040Water Flow Rate (L/m)
Flow DP of X-Pot XP Bag Filters including Magnet Grate
Pre
ssu
re D
rop
(m
bar)
1µ Filter 5µ Filter 25µ Filter 50 &100µ Filter
½" 3/4" 1" 11 /4"
NOTE - Choice of X-POT is dependent upon system working pressure and system volume.Dirty filter state can be estimated by multiplying the clean filter state by a factor of 2.
140 160 180 200 220
900
1000
1½" 2"
CONNECTION SIZES
Vexo's Industry leading Side Stream Filtration Range is fully compliant with BS EN ISO 9001:2015
BSRIA BG29/2020 Pre-commission 'Cleaning of Pipe Work Systems' recommends a 5 micron filtration rate. The X-POT utilizes industry leading 0.5 micron Cartridge Filters (10x Finer) and 1 micron Bag Filters (5x Finer), capturing more debris resulting in greater energy savings and prolonged life cycle realisation.
The water samples below were taken from a 2 year old LTHW Heating System. The system contained a dosing pot (closed off), D&A Separator and no trace of water treatment chemicals. The system contained corrosion debris. After installing an X-POT and X-PO10 inhibitor, the results speak for themselves. Simple and very effective!
Exis
tin
g d
irty
syst
em
wate
r
X-P
OT
filt
ere
d s
yst
em
wate
r
AF
TE
R
BE
FO
RE
MICRON
0.5
MICRON
Cartridge filters0.5, 5, 20 & 50
Bag filters1, 5, 25, 50 & 100
MICRON SIZES
1
Page 15
The X-POT and ancillary order codes
BAG FILTERS X-POT XP, X-POT XP+, X-POT HFHP
100µ V-XBFILTERS(5)100MIC 50µ V-XBFILTERS(5)50MIC 25µ V-XBFILTERS(5)25MIC
(Box of 5)
5µ V-X BFILTERS(5)5MIC1µ V-X BFILTERS(5)1MIC
REPLACEMENT FILTERS ORDER CODES
5µ VX-CFILTERS(20)5MIC
& X-POT6+ (Box of 20)
CARTRIDGE FILTERS
20µ VX-CFILTERS(20)20MIC50µ VX-CFILTERS(20)50MIC
0.5µ VX-CFILTERS(20)0.5MIC
X-POT COMPACT, X-POT6
5µ VX-CFILTERS(4)5MIC
CARTRIDGE FILTERS
0.5µ VX-CFILTERS(4)0.5MIC
& X-POT6+
20µ VX-CFILTERS(4)20MIC
(Box of 4)
X-POT COMPACT, X-POT6
50µ VX-CFILTERS(4)50MIC
X-POT ORDER CODES PD-MONITOR0-10Bar Unit0-30Bar Unit0-30 Bar plus Modbus VX-PDMONITOR 030MB
VX-PDMONITORVX-PDMONITOR 030
Order your X-POT, filter or PD-Monitor below by quoting the code (shown in green text) and quantity of units
MAIN UNITSX-POT CompactX-POT Compact Starter Pack
X-POT6X-POT 6 Starter Pack
X-POT XP X-POT XP Starter Pack
V-XPOTCOMPACT
V-X XP(Std)PACK
V-XCOMP(Std)PACK
V-XPOTXP
V-XPOTXPOT6V-XPOT6(Std)PACK
Essential for Installation (2 of 2 product)
All orders should includestarter pack for installation
(Box of 40) 100µ V-XBFILTERS(40)100MIC 50µ V-XBFILTERS(40)50MIC 25µ V-XBFILTERS(40)25MIC5µ V-X BFILTERS(40)5MIC1µ V-X BFILTERS(40)1MIC
®Remember to include your X-POTStarter Pack in your order
® ® ®
VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021
Page 14
Our range of superior quality filters provides top class filtration, surpassing UK and USA Industry Standards.
X-POT fine filtration
800
700
600
500
400
300
200
100
0 10 6030 40 5020
Water Flow Rate (L/m)0.5µ Filter
Flow DP of X-POT Compact & X-POT6 Cartridge Filters including Magnet Grate
Pre
ssu
re D
rop
(m
bar)
X-POT Compact
5µ Filter
20µ Filter 50µ Filter
½" Conns 3/4" Conns 1" Conns
X-POT6
NOTE - Choice of X-POT is dependent upon system working pressure and system volume.Dirty filter state can be estimated by multiplying the clean filter state by a factor of 2.
800
700
600
500
400
300
200
100
0 20 12060 80 10040Water Flow Rate (L/m)
Flow DP of X-Pot XP Bag Filters including Magnet Grate
Pre
ssu
re D
rop
(m
bar)
1µ Filter 5µ Filter 25µ Filter 50 &100µ Filter
½" 3/4" 1" 11 /4"
NOTE - Choice of X-POT is dependent upon system working pressure and system volume.Dirty filter state can be estimated by multiplying the clean filter state by a factor of 2.
140 160 180 200 220
900
1000
1½" 2"
CONNECTION SIZES
Vexo's Industry leading Side Stream Filtration Range is fully compliant with BS EN ISO 9001:2015
BSRIA BG29/2020 Pre-commission 'Cleaning of Pipe Work Systems' recommends a 5 micron filtration rate. The X-POT utilizes industry leading 0.5 micron Cartridge Filters (10x Finer) and 1 micron Bag Filters (5x Finer), capturing more debris resulting in greater energy savings and prolonged life cycle realisation.
The water samples below were taken from a 2 year old LTHW Heating System. The system contained a dosing pot (closed off), D&A Separator and no trace of water treatment chemicals. The system contained corrosion debris. After installing an X-POT and X-PO10 inhibitor, the results speak for themselves. Simple and very effective!
Exis
tin
g d
irty
syst
em
wate
r
X-P
OT
filt
ere
d s
yst
em
wate
r
AF
TE
R
BE
FO
RE
MICRON
0.5
MICRON
Cartridge filters0.5, 5, 20 & 50
Bag filters1, 5, 25, 50 & 100
MICRON SIZES
1
Page 15
The X-POT and ancillary order codes
50µ V-XBFILTERS(5)50MIC25µ V-XBFILTERS(5)25MIC5µ 1µ
V-X BFILTERS(5)5MIC V-X BFILTERS(5)1MIC
REPLACEMENT FILTERS ORDER CODES
CARTRIDGE FILTERSX-POT COMPACT, X-POT6& X-POT6+(Box of 20)50µ VX-CFILTERS(20)50MIC 20µ VX-CFILTERS(20)20MIC 5µ VX-CFILTERS(20)5MIC 0.5µ VX-CFILTERS(20)0.5MIC
CARTRIDGE FILTERS
& X-POT6+
20µ VXXPCARTRIDGE20 5µ VXXPCARTRIDGE50.5µ VX-CFILTERS(4)0.5MIC
(Box of 4)
X-POT COMPACT, X-POT6
50µ VXXPCARTRIDGE50
X-POT ORDER CODESPD-MONITOR0-10Bar Unit0-30Bar Unit0-30 Bar plus Modbus
VXXPPDMVX-PDMONITOR 030 VX-PDMONITOR 030MB
Order your X-POT, filter or PD-Monitor below by quoting the Stourflex code (shown in green text) and quantity of units. VEXO order codes show in red.(Contact details on back cover)
MAIN UNITSX-POT CompactX-POT Compact Starter Pack
X-POT6X-POT 6 Starter Pack
X-POT XP X-POT XP Starter Pack VXXPSTARTERPACKXP
VXXPSTARTERPACKC
VXXPXP
VXXP6VXXPSTARTERPACK6
Essential for Installation (2 of 2 product)
All orders should include starter pack for installation
BAG FILTERS X-POT XP, X-POT XP+, X-POT HFHP(Box of 5) (Box of 40) 100µ V-XBFILTERS(5)100MIC 100µ VXBFILTERS(40)100MIC
50µ V-XBFILTERS(40)50MIC 25µ V-XBFILTERS(40)25MIC 5µ V-X BFILTERS(40)5MIC 1µ V-X BFILTERS(40)1MIC
®Remember to include your X-POTStarter Pack in your order
® ® ®
VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021
VXXPC
Page 16
Here are some of the recent messages we received from our clients in various project fields.
100% Positive client feedback
– Maine General Hospital, USA
“Various costly MRI
failures, and warranty
voids caused by blocked
plate heat exchanger
cleared up immediately
upon installing an X-POT”
“Since adding X-P010 to our central heating
system, the conversion efficiency from gas to heat
output has increased from 83 to 90% and our 50
year old radiators no longer need bleeding. In
addition the life of our aluminium heat exchanger
has increased from 2 years to more than 8 years
because corrosion has been effectively stopped.”
–Dr Rayner Mayer, Reading University
“A number of X-POT units are currently in operation in sites in London. Further
projects where we will be looking to specify the VEXO equipment in a 42 storey
hotel and private residences development. Our team would have no hesitation in
recommending the VEXO X-POT range and have since advised our colleagues in
our sister teams of the benefits that VEXO equipment have to offer in what has
historically been a difficult and un-engineered aspect of hydraulic design in
building services systems.”
– Ashley Nicholson Associate Director, WSP Consulting engineers
“There was a constant stream of
complaints from residents about heating
issues. The X-POT has been life
changing. We have been able to get the
best value in terms of temperatures and
efficiency.”
– Christopher Collins, Abbeyfield Care Home
“Due to the multiple benefits
within one unit, Bmech have now
made it compulsory to install an
X-POT to all future commercial
boiler installs and replacements.”
– Bmech Energy Efficient Engineering
Page 17
With the correct additives, X-POTs provide full, non-flush cleansing for old systems
only MAXIMISE
YOUR
X-POT
Energy Savings Trustand NSF endorsements
for X-PO10
8 YEAR
3 Years extra warrantyon your X-POT
No need to flush your system
to get rid of sludge
0.36%v/v
Additives that go further by treating more waterat lower concentrations
Low hazard,environmentally friendly formula
Gentle cleaningof old systemcomponents
All you need for easy
treatmentand testing
Use 3 months in advance of strip-out to clean an old system
and protect new componentsagainst legacy sludge
with
VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021
Page 16
Here are some of the recent messages we received from our clients in various project fields.
100% Positive client feedback
– Maine General Hospital, USA
“Various costly MRI
failures, and warranty
voids caused by blocked
plate heat exchanger
cleared up immediately
upon installing an X-POT”
“Since adding X-P010 to our central heating
system, the conversion efficiency from gas to heat
output has increased from 83 to 90% and our 50
year old radiators no longer need bleeding. In
addition the life of our aluminium heat exchanger
has increased from 2 years to more than 8 years
because corrosion has been effectively stopped.”
–Dr Rayner Mayer, Reading University
“A number of X-POT units are currently in operation in sites in London. Further
projects where we will be looking to specify the VEXO equipment in a 42 storey
hotel and private residences development. Our team would have no hesitation in
recommending the VEXO X-POT range and have since advised our colleagues in
our sister teams of the benefits that VEXO equipment have to offer in what has
historically been a difficult and un-engineered aspect of hydraulic design in
building services systems.”
– Ashley Nicholson Associate Director, WSP Consulting engineers
“There was a constant stream of
complaints from residents about heating
issues. The X-POT has been life
changing. We have been able to get the
best value in terms of temperatures and
efficiency.”
– Christopher Collins, Abbeyfield Care Home
“Due to the multiple benefits
within one unit, Bmech have now
made it compulsory to install an
X-POT to all future commercial
boiler installs and replacements.”
– Bmech Energy Efficient Engineering
Page 17
With the correct additives, X-POTs provide full, non-flush cleansing for old systems
only MAXIMISE
YOUR
X-POT
Energy Savings Trustand NSF endorsements
for X-PO10
8 YEAR
3 Years extra warrantyon your X-POT
No need to flush your system
to get rid of sludge
0.36%v/v
Additives that go further by treating more waterat lower concentrations
Low hazard,environmentally friendly formula
Gentle cleaningof old systemcomponents
All you need for easy
treatmentand testing
Use 3 months in advance of strip-out to clean an old system
and protect new componentsagainst legacy sludge
with
VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021
www.VEXOint.comHead Office: 6 The Granary Building, Millow Hall Farm, Millow, Biggleswade, Bedfordshire SG18 8RH.
Tel: 01767 500 150
The UK’s No. 1 brand for closed loop water treatment and conditioning
X-POT and X-PO are registered trade marks of VEXO International (UK) Ltd.
Available from your local STOURFLEX branch