18
HEATING AND COOLING SIDE STREAM FILTRATION www.VEXOint.com O SUPERIOR PROTECTION FOR HVAC SYSTEMS UP TO 95 C Product of the Year Commercial Building Services WINNER Product innovation of the year The UK’S best selling choice in its class

The UK’S best selling choice in its class

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

HEATING AND COOLING

SIDE STREAM FILTRATION

www.V E XO i n t .co m

OSUPERIOR PROTECTION FOR HVAC SYSTEMS UP TO 95 C

Product of the Year

Commercial Building Services

WINNER

Product innovationof the year

The UK’S best sel l ing choice in its class

VEXO Proposal Doc Ver. 1.0 01/06/2020

Potential dangers hiding in closed system water.

Water is the main means of closed system

temperature distribution. It affects every single

piece of equipment and every single person in

the spaces that you manage. Wherever there is

closed loop system water four problems will

occur: scale formation, corrosion, fouling and

microbial growth.

The problem with dirty water

1. Scale formation

2. Corrosion

3. Microbial growth

4. Fouling & sludge

What dirty system water can do if left untreated.

Page 3

Why do you need superior filtration installed on your closed loop system?

At the heart of your facility

is a perfectly good heating

or cooling system.

This leads to

bad distribution,

breakdowns,

cold spots and

energy waste.

LIMESCALE

METALLIC SLUDGE

BACTERIALBIOFILM

You could be losing over 10% energy from dirty system water alone!

It loses its energy

and transfer capacity

to a fouled and dirty

circulatory system.

Erosion corrosion

Reduction in efficacy of inhibitor

Harbouring bacteria proliferation

Settlement of sediment

Non-repeatable commissioning readings

Delayed project handovers

Landlord losing tenants could lead to litigation

Efficiency losses

Lifecycle losses

Damage to reputation

YOUR INVESTMENT

PR

OG

RE

SS

IVE

LY L

ES

S R

OI

WHAT’S LEFT OF YOUR INVESTMENT

Page 2

How neglecting your hydronic thermal fluidcan affect your bottom line

Your investment reduces as dirty system water

slowly erodes your OPEX and reputation.

VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021

VEXO Proposal Doc Ver. 1.0 01/06/2020

Potential dangers hiding in closed system water.

Water is the main means of closed system

temperature distribution. It affects every single

piece of equipment and every single person in

the spaces that you manage. Wherever there is

closed loop system water four problems will

occur: scale formation, corrosion, fouling and

microbial growth.

The problem with dirty water

1. Scale formation

2. Corrosion

3. Microbial growth

4. Fouling & sludge

What dirty system water can do if left untreated.

Page 3

Why do you need superior filtration installed on your closed loop system?

At the heart of your facility

is a perfectly good heating

or cooling system.

This leads to

bad distribution,

breakdowns,

cold spots and

energy waste.

LIMESCALE

METALLIC SLUDGE

BACTERIALBIOFILM

You could be losing over 10% energy from dirty system water alone!

It loses its energy

and transfer capacity

to a fouled and dirty

circulatory system.

Erosion corrosion

Reduction in efficacy of inhibitor

Harbouring bacteria proliferation

Settlement of sediment

Non-repeatable commissioning readings

Delayed project handovers

Landlord losing tenants could lead to litigation

Efficiency losses

Lifecycle losses

Damage to reputation

YOUR INVESTMENT

PR

OG

RE

SS

IVE

LY L

ES

S R

OI

WHAT’S LEFT OF YOUR INVESTMENT

Page 2

How neglecting your hydronic thermal fluidcan affect your bottom line

Your investment reduces as dirty system water

slowly erodes your OPEX and reputation.

VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021

Page 4 Page 5

The VEXO X-POT is the UK leader in closed loop side stream filtration.

Higher System performance at a

smaller budget

Greater reliability with reduced

critical down time, increased heat

distribution, fewer call outs and

happier tenants.

Multi-Functional Design

Retro-fit all-in-one Solution

Particle sizelimitations

Only dosesadditives

Magnetite removal only

Improved system life cycle resulting

in CAPEX savings, reductions in

reactive maintenance and

operational cost savings.

Provides protection for new

systems and improved system

efficiency for aged systems;

resulting in less flushing, a

reduction in CO2 and a more

environmentally friendly facility.

MAGNETICFILTERS

DOSINGPOTS

DIRT & AIRSEPARATORS

Industry Leading Multi-Layered Filtration

The X-POT combines most current system filtration units into

one easy-install, easy-service, BSRIA acknowledged water

conditioning product.

THE ALL-IN-ONESOLUTION

VEXO X-POT

ALL IN ONE

.

Blocks due to magnetite sludge

CARTRIDGE & BAGFILTERS

What is the VEXO X-POT?

Absolutely. We have independently proven 3.5% energy saving after just 1 week, and an additional 5-10% savings with added X-PO10 Inhibitor!

Does the VEXO X-POT really work?

"The X-POT Side Stream

filtration system reduced

energy consumption by 3.5%

within the first 7 days of use"

Johnathan Cripps, MSc Dissertation: Low Energy Building Services Engineering (Effects of Corrosion on Heat Transfer Efficiency within a Heating System)

Loughborough University

"Results suggest gas bill

reductions of up to 10% are

possible whilst prolonging the

life cycle of existing heating

systems."

Dr Rayner Mayer, Trials of VEXO X-PO10 InhibitorSciotech Projects

University of Reading

The results speak for themselves. With thousands of X-POT's installed across the world, all with 100% positive client feedback. Below are just a few of our recent examples.

VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021

Page 4 Page 5

The VEXO X-POT is the UK leader in closed loop side stream filtration.

Higher System performance at a

smaller budget

Greater reliability with reduced

critical down time, increased heat

distribution, fewer call outs and

happier tenants.

Multi-Functional Design

Retro-fit all-in-one Solution

Particle sizelimitations

Only dosesadditives

Magnetite removal only

Improved system life cycle resulting

in CAPEX savings, reductions in

reactive maintenance and

operational cost savings.

Provides protection for new

systems and improved system

efficiency for aged systems;

resulting in less flushing, a

reduction in CO2 and a more

environmentally friendly facility.

MAGNETICFILTERS

DOSINGPOTS

DIRT & AIRSEPARATORS

Industry Leading Multi-Layered Filtration

The X-POT combines most current system filtration units into

one easy-install, easy-service, BSRIA acknowledged water

conditioning product.

THE ALL-IN-ONESOLUTION

VEXO X-POT

ALL IN ONE

.

Blocks due to magnetite sludge

CARTRIDGE & BAGFILTERS

What is the VEXO X-POT?

Absolutely. We have independently proven 3.5% energy saving after just 1 week, and an additional 5-10% savings with added X-PO10 Inhibitor!

Does the VEXO X-POT really work?

"The X-POT Side Stream

filtration system reduced

energy consumption by 3.5%

within the first 7 days of use"

Johnathan Cripps, MSc Dissertation: Low Energy Building Services Engineering (Effects of Corrosion on Heat Transfer Efficiency within a Heating System)

Loughborough University

"Results suggest gas bill

reductions of up to 10% are

possible whilst prolonging the

life cycle of existing heating

systems."

Dr Rayner Mayer, Trials of VEXO X-PO10 InhibitorSciotech Projects

University of Reading

The results speak for themselves. With thousands of X-POT's installed across the world, all with 100% positive client feedback. Below are just a few of our recent examples.

VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021

Page 6

Side stream filtration for small tomedium commercial systems

Side stream filtration including

a magnetic filter, cartridge filter,

air and dirt separator and dosing

unit for small to medium

commercial systems.

Max working pressure: 4 Bar

Max system volume: 34,560 litres

Flow rate: Up to 24 l/m

Pipe connection: 1/2" BSP

Filtration rate: Down to 0.5 micron

Side View Front View Plan View

1 "/2

TUNDISH

1 "/2

AAV

NRV

DRAIN and/or clean RTN

DIR

TY

FL

OW

63

0 12,5

100

175 12

,59

5

156

220

90

75

107

DRAIN and/or clean RTN

1 "/2

DIR

TY

FL

OW

1 "/21 "/2

MAIN VENT

MAIN VENT

LEFT /RIGHT orBOTTOM

Conn.

DIRTYFLOW

285

225

190

190

135

TUNDISH

AAV

®

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

Page 7

Side stream filtration including

a magnetic filter, cartridge

filter, air and dirt separator

and dosing unit for medium

to large commercial systems.

Max working pressure: 7 Bar

Max system volume: 86,400 litres

Flow rate: Up to 60 l/m

Pipe connection: 1" BSP

Filtration rate: Down to 0.5 micron

TUNDISH

AAV

NRV

MAIN VENT

DIRTYFLOW

CLEANRETURN

DRAIN

LEFT HANDDIRTY FLOW

206

TUNDISH

AAV

MAIN VENT

NRV

DIRTYFLOW

CLEANRETURN

DRAIN

915

75

180

40

26

0

34

0

1 "/2

"1

"1

"1

"1460260

225

175

130

TUNDISH

AAVMAINVENT

DIRTYFLOW

PLUG

1 "/2 "1

Side View Front View Plan View

Side stream filtration for medium to large commercial systems

®

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021

Page 6

Side stream filtration for small tomedium commercial systems

Side stream filtration including

a magnetic filter, cartridge filter,

air and dirt separator and dosing

unit for small to medium

commercial systems.

Max working pressure: 4 Bar

Max system volume: 34,560 litres

Flow rate: Up to 24 l/m

Pipe connection: 1/2" BSP

Filtration rate: Down to 0.5 micron

Side View Front View Plan View

1 "/2

TUNDISH

1 "/2

AAV

NRV

DRAIN and/or clean RTN

DIR

TY

FL

OW

63

0 12,5

100

175 12

,59

5

156

220

90

75

107

DRAIN and/or clean RTN

1 "/2

DIR

TY

FL

OW

1 "/21 "/2

MAIN VENT

MAIN VENT

LEFT /RIGHT orBOTTOM

Conn.

DIRTYFLOW

285

225

190

190

135

TUNDISH

AAV

®

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

Page 7

Side stream filtration including

a magnetic filter, cartridge

filter, air and dirt separator

and dosing unit for medium

to large commercial systems.

Max working pressure: 7 Bar

Max system volume: 86,400 litres

Flow rate: Up to 60 l/m

Pipe connection: 1" BSP

Filtration rate: Down to 0.5 micron

TUNDISH

AAV

NRV

MAIN VENT

DIRTYFLOW

CLEANRETURN

DRAIN

LEFT HANDDIRTY FLOW

206

TUNDISH

AAV

MAIN VENT

NRV

DIRTYFLOW

CLEANRETURN

DRAIN

915

75

180

40

26

0

34

0

1 "/2

"1

"1

"1

"1460260

225

175

130

TUNDISH

AAVMAINVENT

DIRTYFLOW

PLUG

1 "/2 "1

Side View Front View Plan View

Side stream filtration for medium to large commercial systems

®

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021

Page 8

Side stream filtration for large tovery large commercial systems

Side View Front ViewPlan View

AAV

MAIN VENT

1 "/2

TUNDISH

NRV

"1

DIRTYFLOW

1 "/2

146

0

870

135

135

206

TUNDISH

AAV"1

NRV1 "/2

PG

PG

DRAINCLEAN

RETURN

DIRTYFLOW

WALL BRACKET

430

900DIRTYFLOW

CL

EA

NR

ET

UR

N

MAINVENT

PG

43

03

00

490

195

DRAIN

2"

2"

2"

2"

Vexo X-Pot Brochure V2.0

1 "/2

2"

Max working pressure: 16Bar

Max system volume: 302,400 litres

Flow rate: Up to 210 l/m

2" BSPPipe connection:

Filtration rate: Down to 1 micron

Side stream filtration including a magnetic filter,

bag filter, air and dirt separator and dosing

unit for large to very large commercial systems.

Page 9

Made to order filtration for extreme high pressure or flow

Max working pressure: 30Bar

Max system volume: 302,400 litres

Flow rate: Up to 210 l/m

2" BSPPipe connection:

Filtration rate: Down to 1 micron

Side stream filtration including a magnetic filter,

bag filter, air and dirt separator and dosing unit

for extremely high pressure, high flow commercial systems.

Max working pressure: 10 or 30 Bar options

Max system volume: 2,592,000 litres

Up to 1800 l/mFlow rate:

6" PN 10 or 6" PN 30Pipe connection:

Filtration rate: Down to 1 micron.

Side stream filtration including a magnetic filter,

bag filter, air and dirt separator and dosing unit

for very large commercial systems.

HFHP

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021

Page 8

Side stream filtration for large tovery large commercial systems

Side View Front ViewPlan View

AAV

MAIN VENT

1 "/2

TUNDISH

NRV

"1

DIRTYFLOW

1 "/2

146

0

870

135

135

206

TUNDISH

AAV"1

NRV1 "/2

PG

PG

DRAINCLEAN

RETURN

DIRTYFLOW

WALL BRACKET

430

900DIRTYFLOW

CL

EA

NR

ET

UR

N

MAINVENT

PG

43

03

00

490

195

DRAIN

2"

2"

2"

2"

Vexo X-Pot Brochure V2.0

1 "/2

2"

Max working pressure: 16Bar

Max system volume: 302,400 litres

Flow rate: Up to 210 l/m

2" BSPPipe connection:

Filtration rate: Down to 1 micron

Side stream filtration including a magnetic filter,

bag filter, air and dirt separator and dosing

unit for large to very large commercial systems.

Page 9

Made to order filtration for extreme high pressure or flow

Max working pressure: 30Bar

Max system volume: 302,400 litres

Flow rate: Up to 210 l/m

2" BSPPipe connection:

Filtration rate: Down to 1 micron

Side stream filtration including a magnetic filter,

bag filter, air and dirt separator and dosing unit

for extremely high pressure, high flow commercial systems.

Max working pressure: 10 or 30 Bar options

Max system volume: 2,592,000 litres

Up to 1800 l/mFlow rate:

6" PN 10 or 6" PN 30Pipe connection:

Filtration rate: Down to 1 micron.

Side stream filtration including a magnetic filter,

bag filter, air and dirt separator and dosing unit

for very large commercial systems.

HFHP

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

*Extended to 8 years if used with VEXO Inhibitor

and supplied parts.

5 YEAR

VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021

Page 10 Page 11

Side stream filtration with integratedpump, alarm and BMS compatibility

Max working pressure: 10 Bar

Max system volume: 86,400 litres

Flow rate: 60L/min (1.0L/s)

1" BSPPipe connection:

Filtration rate: Down to 0.5 micron

VEXO™ X-POT XP+ Side Stream Filtration

& Dosing Unit with integrated pump and

BMS Compatibility for large to very large

commercial systems.

Max working pressure: 16 Bar

Max system volume: 302,400 litres

60-210L/min (1.0-3.50L/s)Flow rate:

2" BSPPipe connection:

Filtration rate: Down to 1 micron.

VEXO™ X-POT6+ Side Stream Filtration

& Dosing Unit with integrated pump,

fault alarm and Enhanced BMS Compatibility

for medium to large commercial systems.

*Extended to 3 years if used with VEXO Inhibitor

and supplied parts.

2 YEAR

*Extended to 3 years if used with VEXO Inhibitor

and supplied parts.

2 YEAR

Indicative X-POT Side Stream Filtration Installations

TWIN PUMPX-POT

INSTALLATION

ZONE/MULTIPLEPUMP X-POT

INSTALLATIONSINGLE PUMP

X-POTINSTALLATION

The size of the connections to the X-POT is determined by the total system volume

being circulated through the X-POT in a 24 Hour

period.

10.083 - 0.4 I/s = / " Conn.230.4 - 0.6 l/s = / " Conn.4

0.6 - 1.0 l/s = 1" Conn.11.0 - 1.2 l/s = 1 / " Conn.411.2 - 2.1 l/s = 1 / " Conn.2

2.1 - 3.5 l/s = 2" Conn.

Working Pressure : 3BarSystem volume :

22,500Litres = 0.26 l/secChosen Vessel : X-POT Compact

Connection Size :1/2”

Working Pressure : 10BarSystem volume :

90,000Litres = 1.04 l/secChosen Vessel : X-POT XP

Connection Size : 1 1/4"

EXAMPLES

SYSTEM VOLUME

86,400sec l/sec

Which connectionsand X-POT?

Indicative system placement

PICV (Not supplied by VEXO)

Packaged Differential Pressure Monitor

1

2

PDMONITOR

CLEAN RETURN

PICV

1IV IV

STR

SYSTEMPUMP

DIRTYFLOW

SYSTEMFLOW

SYSTEMRETURN

PRESSUREINDEPENDENTCONTROLVALVE

HEATSOURCE

STR

X-POT

AAV

NRVIV

IV

IV

IV

IV

DRAIN2

Installationexample

The X-POT provides a number of installation

solutions. These examples are INDICATIVE

ONLY. If your system cannot accommodate

any of these scenarios due to complexity,

please contact the VEXO Technical Team:

+44 (0)1767 500 150 / [email protected]

THE X-POT SHOULD BE FITTED ON

THE SECONDARY

HEATING CIRCUIT TO

ENSURE BULK WATER SYSTEM

PROTECTION

24Hours

SystemVolume

ISOLATION VALVE

NON RETURN VALVE

STRAINER

AUTO AIR VENT

PRESSURE GAUGE

TEMPERATURE GAUGE

PRESSURE RELEASE VALVE

FLEX CONNECTION

PUMP

TM VEXO PD-MONITOR

PRESSURE INDEPENDENTCONTROL VALVE

COMMISSIONING VALVE

3 PORT VALVE

VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021

Page 10 Page 11

Side stream filtration with integratedpump, alarm and BMS compatibility

Max working pressure: 10 Bar

Max system volume: 86,400 litres

Flow rate: 60L/min (1.0L/s)

1" BSPPipe connection:

Filtration rate: Down to 0.5 micron

VEXO™ X-POT XP+ Side Stream Filtration

& Dosing Unit with integrated pump and

BMS Compatibility for large to very large

commercial systems.

Max working pressure: 16 Bar

Max system volume: 302,400 litres

60-210L/min (1.0-3.50L/s)Flow rate:

2" BSPPipe connection:

Filtration rate: Down to 1 micron.

VEXO™ X-POT6+ Side Stream Filtration

& Dosing Unit with integrated pump,

fault alarm and Enhanced BMS Compatibility

for medium to large commercial systems.

*Extended to 3 years if used with VEXO Inhibitor

and supplied parts.

2 YEAR

*Extended to 3 years if used with VEXO Inhibitor

and supplied parts.

2 YEAR

Indicative X-POT Side Stream Filtration Installations

TWIN PUMPX-POT

INSTALLATION

ZONE/MULTIPLEPUMP X-POT

INSTALLATIONSINGLE PUMP

X-POTINSTALLATION

The size of the connections to the X-POT is determined by the total system volume

being circulated through the X-POT in a 24 Hour

period.

10.083 - 0.4 I/s = / " Conn.230.4 - 0.6 l/s = / " Conn.4

0.6 - 1.0 l/s = 1" Conn.11.0 - 1.2 l/s = 1 / " Conn.411.2 - 2.1 l/s = 1 / " Conn.2

2.1 - 3.5 l/s = 2" Conn.

Working Pressure : 3BarSystem volume :

22,500Litres = 0.26 l/secChosen Vessel : X-POT Compact

Connection Size :1/2”

Working Pressure : 10BarSystem volume :

90,000Litres = 1.04 l/secChosen Vessel : X-POT XP

Connection Size : 1 1/4"

EXAMPLES

SYSTEM VOLUME

86,400sec l/sec

Which connectionsand X-POT?

Indicative system placement

PICV (Not supplied by VEXO)

Packaged Differential Pressure Monitor

1

2

PDMONITOR

CLEAN RETURN

PICV

1IV IV

STR

SYSTEMPUMP

DIRTYFLOW

SYSTEMFLOW

SYSTEMRETURN

PRESSUREINDEPENDENTCONTROLVALVE

HEATSOURCE

STR

X-POT

AAV

NRVIV

IV

IV

IV

IV

DRAIN2

Installationexample

The X-POT provides a number of installation

solutions. These examples are INDICATIVE

ONLY. If your system cannot accommodate

any of these scenarios due to complexity,

please contact the VEXO Technical Team:

+44 (0)1767 500 150 / [email protected]

THE X-POT SHOULD BE FITTED ON

THE SECONDARY

HEATING CIRCUIT TO

ENSURE BULK WATER SYSTEM

PROTECTION

24Hours

SystemVolume

ISOLATION VALVE

NON RETURN VALVE

STRAINER

AUTO AIR VENT

PRESSURE GAUGE

TEMPERATURE GAUGE

PRESSURE RELEASE VALVE

FLEX CONNECTION

PUMP

TM VEXO PD-MONITOR

PRESSURE INDEPENDENTCONTROL VALVE

COMMISSIONING VALVE

3 PORT VALVE

VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021

Page 12 Page 13

Upgrade your X-POT with a simple andadaptive monitor for system flow issues

Compatible with all hybrid applications.

DISPLAY

CONTROLLER

BEACONON/OFF

DISPLAY

CONTROLLER

BEACONON/OFF

DISPLAY

CONTROLLER

BEACONON/OFF

DISPLAY

CONTROLLER

BEACONON/OFF

DISPLAY

CONTROLLER

BEACONON/OFF

PD-MONITOR

PD-MONITOR PD-MONITOR

PD-MONITOR

PD-MONITOR

FILTRATIONPLANT

AIR HANDLING PLANT

HEAT EXCHANGER

SYSTEM PUMPS

PD-Monitor can be used for various hybrid applications

(i.e. plate heat exchangers, AHU coils and process equipment monitoring).

A packaged, wall mounted and factory tested

differential pressure monitoring unit

incorporating controller, two pressure

transducers, 240V ac mains cable and BMS

capability.

1 off Pre-Settable PICV

(X-POT Compact - DN20) (X-POT6 - DN32)

(X-POT XP LF - DN50) (X-POT XP HF - DN50 Flanged)

1 off Insulation Jacket

1 off Vexo PD-Monitor 0-30 Bar Modbus

1 YEAR

The X-POT Compliance Packs

The X-POT Compliance Pack completes your X-POT installation in accordance with Best Practise BSRIA BG29/50 Guidance.

The X-POT Compliance Pack features our pre-settable PICV for simple and

accurate commissioning, insulation jacket for our PICV to reduce thermal

loss and our PD-Monitor to accurately track your X-POT filter status, so

your system operates at its full potential.

BSRIA BG29/2020 recommends ‘5% of the circulating water should be diverted through the side stream filter' and 'Filters should be easily maintainable and fitted with a differential pressure indicator or BMS sensor'.

V-XCOMP(CP)PACK

X-POT Compact

DN20

V-XPOT6(CP)PACK

X-POT6

DN32

V-XPXP-LF(CP)PACK

X-POT XP LF

DN50

V-XPXP-LF(CP)PACK

X-POT XP HF

DN50 Flanged

X-POT COMPLIANCE PACK VARIATIONS & ORDER CODES

Each Compliance Pack contains:

Remote alarm for blocked X-POT filters

10 Bar & 30 Bar Max. working pressure options

Can be linked to BMS

Audible alarm and flashing beacon

Simple, adaptive monitor for system flow issues

VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021

Page 12 Page 13

Upgrade your X-POT with a simple andadaptive monitor for system flow issues

Compatible with all hybrid applications.

DISPLAY

CONTROLLER

BEACONON/OFF

DISPLAY

CONTROLLER

BEACONON/OFF

DISPLAY

CONTROLLER

BEACONON/OFF

DISPLAY

CONTROLLER

BEACONON/OFF

DISPLAY

CONTROLLER

BEACONON/OFF

PD-MONITOR

PD-MONITOR PD-MONITOR

PD-MONITOR

PD-MONITOR

FILTRATIONPLANT

AIR HANDLING PLANT

HEAT EXCHANGER

SYSTEM PUMPS

PD-Monitor can be used for various hybrid applications

(i.e. plate heat exchangers, AHU coils and process equipment monitoring).

A packaged, wall mounted and factory tested

differential pressure monitoring unit

incorporating controller, two pressure

transducers, 240V ac mains cable and BMS

capability.

1 off Pre-Settable PICV

(X-POT Compact - DN20) (X-POT6 - DN32)

(X-POT XP LF - DN50) (X-POT XP HF - DN50 Flanged)

1 off Insulation Jacket

1 off Vexo PD-Monitor 0-30 Bar Modbus

1 YEAR

The X-POT Compliance Packs

The X-POT Compliance Pack completes your X-POT installation in accordance with Best Practise BSRIA BG29/50 Guidance.

The X-POT Compliance Pack features our pre-settable PICV for simple and

accurate commissioning, insulation jacket for our PICV to reduce thermal

loss and our PD-Monitor to accurately track your X-POT filter status, so

your system operates at its full potential.

BSRIA BG29/2020 recommends ‘5% of the circulating water should be diverted through the side stream filter' and 'Filters should be easily maintainable and fitted with a differential pressure indicator or BMS sensor'.

V-XCOMP(CP)PACK

X-POT Compact

DN20

V-XPOT6(CP)PACK

X-POT6

DN32

V-XPXP-LF(CP)PACK

X-POT XP LF

DN50

V-XPXP-LF(CP)PACK

X-POT XP HF

DN50 Flanged

X-POT COMPLIANCE PACK VARIATIONS & ORDER CODES

Each Compliance Pack contains:

Remote alarm for blocked X-POT filters

10 Bar & 30 Bar Max. working pressure options

Can be linked to BMS

Audible alarm and flashing beacon

Simple, adaptive monitor for system flow issues

VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021

Page 14

Our range of superior quality filters provides top class filtration, surpassing UK and USA Industry Standards.

X-POT fine filtration

800

700

600

500

400

300

200

100

0 10 6030 40 5020

Water Flow Rate (L/m)0.5µ Filter

Flow DP of X-POT Compact & X-POT6 Cartridge Filters including Magnet Grate

Pre

ssu

re D

rop

(m

bar)

X-POT Compact

5µ Filter

20µ Filter 50µ Filter

½" Conns 3/4" Conns 1" Conns

X-POT6

NOTE - Choice of X-POT is dependent upon system working pressure and system volume.Dirty filter state can be estimated by multiplying the clean filter state by a factor of 2.

800

700

600

500

400

300

200

100

0 20 12060 80 10040Water Flow Rate (L/m)

Flow DP of X-Pot XP Bag Filters including Magnet Grate

Pre

ssu

re D

rop

(m

bar)

1µ Filter 5µ Filter 25µ Filter 50 &100µ Filter

½" 3/4" 1" 11 /4"

NOTE - Choice of X-POT is dependent upon system working pressure and system volume.Dirty filter state can be estimated by multiplying the clean filter state by a factor of 2.

140 160 180 200 220

900

1000

1½" 2"

CONNECTION SIZES

Vexo's Industry leading Side Stream Filtration Range is fully compliant with BS EN ISO 9001:2015

BSRIA BG29/2020 Pre-commission 'Cleaning of Pipe Work Systems' recommends a 5 micron filtration rate. The X-POT utilizes industry leading 0.5 micron Cartridge Filters (10x Finer) and 1 micron Bag Filters (5x Finer), capturing more debris resulting in greater energy savings and prolonged life cycle realisation.

The water samples below were taken from a 2 year old LTHW Heating System. The system contained a dosing pot (closed off), D&A Separator and no trace of water treatment chemicals. The system contained corrosion debris. After installing an X-POT and X-PO10 inhibitor, the results speak for themselves. Simple and very effective!

Exis

tin

g d

irty

syst

em

wate

r

X-P

OT

filt

ere

d s

yst

em

wate

r

AF

TE

R

BE

FO

RE

MICRON

0.5

MICRON

Cartridge filters0.5, 5, 20 & 50

Bag filters1, 5, 25, 50 & 100

MICRON SIZES

1

Page 15

The X-POT and ancillary order codes

BAG FILTERS X-POT XP, X-POT XP+, X-POT HFHP

100µ V-XBFILTERS(5)100MIC 50µ V-XBFILTERS(5)50MIC 25µ V-XBFILTERS(5)25MIC

(Box of 5)

5µ V-X BFILTERS(5)5MIC1µ V-X BFILTERS(5)1MIC

REPLACEMENT FILTERS ORDER CODES

5µ VX-CFILTERS(20)5MIC

& X-POT6+ (Box of 20)

CARTRIDGE FILTERS

20µ VX-CFILTERS(20)20MIC50µ VX-CFILTERS(20)50MIC

0.5µ VX-CFILTERS(20)0.5MIC

X-POT COMPACT, X-POT6

5µ VX-CFILTERS(4)5MIC

CARTRIDGE FILTERS

0.5µ VX-CFILTERS(4)0.5MIC

& X-POT6+

20µ VX-CFILTERS(4)20MIC

(Box of 4)

X-POT COMPACT, X-POT6

50µ VX-CFILTERS(4)50MIC

X-POT ORDER CODES PD-MONITOR0-10Bar Unit0-30Bar Unit0-30 Bar plus Modbus VX-PDMONITOR 030MB

VX-PDMONITORVX-PDMONITOR 030

Order your X-POT, filter or PD-Monitor below by quoting the code (shown in green text) and quantity of units

MAIN UNITSX-POT CompactX-POT Compact Starter Pack

X-POT6X-POT 6 Starter Pack

X-POT XP X-POT XP Starter Pack

V-XPOTCOMPACT

V-X XP(Std)PACK

V-XCOMP(Std)PACK

V-XPOTXP

V-XPOTXPOT6V-XPOT6(Std)PACK

Essential for Installation (2 of 2 product)

All orders should includestarter pack for installation

(Box of 40) 100µ V-XBFILTERS(40)100MIC 50µ V-XBFILTERS(40)50MIC 25µ V-XBFILTERS(40)25MIC5µ V-X BFILTERS(40)5MIC1µ V-X BFILTERS(40)1MIC

®Remember to include your X-POTStarter Pack in your order

® ® ®

VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021

Page 14

Our range of superior quality filters provides top class filtration, surpassing UK and USA Industry Standards.

X-POT fine filtration

800

700

600

500

400

300

200

100

0 10 6030 40 5020

Water Flow Rate (L/m)0.5µ Filter

Flow DP of X-POT Compact & X-POT6 Cartridge Filters including Magnet Grate

Pre

ssu

re D

rop

(m

bar)

X-POT Compact

5µ Filter

20µ Filter 50µ Filter

½" Conns 3/4" Conns 1" Conns

X-POT6

NOTE - Choice of X-POT is dependent upon system working pressure and system volume.Dirty filter state can be estimated by multiplying the clean filter state by a factor of 2.

800

700

600

500

400

300

200

100

0 20 12060 80 10040Water Flow Rate (L/m)

Flow DP of X-Pot XP Bag Filters including Magnet Grate

Pre

ssu

re D

rop

(m

bar)

1µ Filter 5µ Filter 25µ Filter 50 &100µ Filter

½" 3/4" 1" 11 /4"

NOTE - Choice of X-POT is dependent upon system working pressure and system volume.Dirty filter state can be estimated by multiplying the clean filter state by a factor of 2.

140 160 180 200 220

900

1000

1½" 2"

CONNECTION SIZES

Vexo's Industry leading Side Stream Filtration Range is fully compliant with BS EN ISO 9001:2015

BSRIA BG29/2020 Pre-commission 'Cleaning of Pipe Work Systems' recommends a 5 micron filtration rate. The X-POT utilizes industry leading 0.5 micron Cartridge Filters (10x Finer) and 1 micron Bag Filters (5x Finer), capturing more debris resulting in greater energy savings and prolonged life cycle realisation.

The water samples below were taken from a 2 year old LTHW Heating System. The system contained a dosing pot (closed off), D&A Separator and no trace of water treatment chemicals. The system contained corrosion debris. After installing an X-POT and X-PO10 inhibitor, the results speak for themselves. Simple and very effective!

Exis

tin

g d

irty

syst

em

wate

r

X-P

OT

filt

ere

d s

yst

em

wate

r

AF

TE

R

BE

FO

RE

MICRON

0.5

MICRON

Cartridge filters0.5, 5, 20 & 50

Bag filters1, 5, 25, 50 & 100

MICRON SIZES

1

Page 15

The X-POT and ancillary order codes

50µ V-XBFILTERS(5)50MIC25µ V-XBFILTERS(5)25MIC5µ 1µ

V-X BFILTERS(5)5MIC V-X BFILTERS(5)1MIC

REPLACEMENT FILTERS ORDER CODES

CARTRIDGE FILTERSX-POT COMPACT, X-POT6& X-POT6+(Box of 20)50µ VX-CFILTERS(20)50MIC 20µ VX-CFILTERS(20)20MIC 5µ VX-CFILTERS(20)5MIC 0.5µ VX-CFILTERS(20)0.5MIC

CARTRIDGE FILTERS

& X-POT6+

20µ VXXPCARTRIDGE20 5µ VXXPCARTRIDGE50.5µ VX-CFILTERS(4)0.5MIC

(Box of 4)

X-POT COMPACT, X-POT6

50µ VXXPCARTRIDGE50

X-POT ORDER CODESPD-MONITOR0-10Bar Unit0-30Bar Unit0-30 Bar plus Modbus

VXXPPDMVX-PDMONITOR 030 VX-PDMONITOR 030MB

Order your X-POT, filter or PD-Monitor below by quoting the Stourflex code (shown in green text) and quantity of units. VEXO order codes show in red.(Contact details on back cover)

MAIN UNITSX-POT CompactX-POT Compact Starter Pack

X-POT6X-POT 6 Starter Pack

X-POT XP X-POT XP Starter Pack VXXPSTARTERPACKXP

VXXPSTARTERPACKC

VXXPXP

VXXP6VXXPSTARTERPACK6

Essential for Installation (2 of 2 product)

All orders should include starter pack for installation

BAG FILTERS X-POT XP, X-POT XP+, X-POT HFHP(Box of 5) (Box of 40) 100µ V-XBFILTERS(5)100MIC 100µ VXBFILTERS(40)100MIC

50µ V-XBFILTERS(40)50MIC 25µ V-XBFILTERS(40)25MIC 5µ V-X BFILTERS(40)5MIC 1µ V-X BFILTERS(40)1MIC

®Remember to include your X-POTStarter Pack in your order

® ® ®

VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021

VXXPC

Page 16

Here are some of the recent messages we received from our clients in various project fields.

100% Positive client feedback

– Maine General Hospital, USA

“Various costly MRI

failures, and warranty

voids caused by blocked

plate heat exchanger

cleared up immediately

upon installing an X-POT”

“Since adding X-P010 to our central heating

system, the conversion efficiency from gas to heat

output has increased from 83 to 90% and our 50

year old radiators no longer need bleeding. In

addition the life of our aluminium heat exchanger

has increased from 2 years to more than 8 years

because corrosion has been effectively stopped.”

–Dr Rayner Mayer, Reading University

“A number of X-POT units are currently in operation in sites in London. Further

projects where we will be looking to specify the VEXO equipment in a 42 storey

hotel and private residences development. Our team would have no hesitation in

recommending the VEXO X-POT range and have since advised our colleagues in

our sister teams of the benefits that VEXO equipment have to offer in what has

historically been a difficult and un-engineered aspect of hydraulic design in

building services systems.”

– Ashley Nicholson Associate Director, WSP Consulting engineers

“There was a constant stream of

complaints from residents about heating

issues. The X-POT has been life

changing. We have been able to get the

best value in terms of temperatures and

efficiency.”

– Christopher Collins, Abbeyfield Care Home

“Due to the multiple benefits

within one unit, Bmech have now

made it compulsory to install an

X-POT to all future commercial

boiler installs and replacements.”

– Bmech Energy Efficient Engineering

Page 17

With the correct additives, X-POTs provide full, non-flush cleansing for old systems

only MAXIMISE

YOUR

X-POT

Energy Savings Trustand NSF endorsements

for X-PO10

8 YEAR

3 Years extra warrantyon your X-POT

No need to flush your system

to get rid of sludge

0.36%v/v

Additives that go further by treating more waterat lower concentrations

Low hazard,environmentally friendly formula

Gentle cleaningof old systemcomponents

All you need for easy

treatmentand testing

Use 3 months in advance of strip-out to clean an old system

and protect new componentsagainst legacy sludge

with

VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021

Page 16

Here are some of the recent messages we received from our clients in various project fields.

100% Positive client feedback

– Maine General Hospital, USA

“Various costly MRI

failures, and warranty

voids caused by blocked

plate heat exchanger

cleared up immediately

upon installing an X-POT”

“Since adding X-P010 to our central heating

system, the conversion efficiency from gas to heat

output has increased from 83 to 90% and our 50

year old radiators no longer need bleeding. In

addition the life of our aluminium heat exchanger

has increased from 2 years to more than 8 years

because corrosion has been effectively stopped.”

–Dr Rayner Mayer, Reading University

“A number of X-POT units are currently in operation in sites in London. Further

projects where we will be looking to specify the VEXO equipment in a 42 storey

hotel and private residences development. Our team would have no hesitation in

recommending the VEXO X-POT range and have since advised our colleagues in

our sister teams of the benefits that VEXO equipment have to offer in what has

historically been a difficult and un-engineered aspect of hydraulic design in

building services systems.”

– Ashley Nicholson Associate Director, WSP Consulting engineers

“There was a constant stream of

complaints from residents about heating

issues. The X-POT has been life

changing. We have been able to get the

best value in terms of temperatures and

efficiency.”

– Christopher Collins, Abbeyfield Care Home

“Due to the multiple benefits

within one unit, Bmech have now

made it compulsory to install an

X-POT to all future commercial

boiler installs and replacements.”

– Bmech Energy Efficient Engineering

Page 17

With the correct additives, X-POTs provide full, non-flush cleansing for old systems

only MAXIMISE

YOUR

X-POT

Energy Savings Trustand NSF endorsements

for X-PO10

8 YEAR

3 Years extra warrantyon your X-POT

No need to flush your system

to get rid of sludge

0.36%v/v

Additives that go further by treating more waterat lower concentrations

Low hazard,environmentally friendly formula

Gentle cleaningof old systemcomponents

All you need for easy

treatmentand testing

Use 3 months in advance of strip-out to clean an old system

and protect new componentsagainst legacy sludge

with

VEXO X-POT (Std) Ver. 1 Rev 3 16/06/2021VEXO X-POT (Std) Ver. 1 Rev 3 11/06/2021

www.VEXOint.comHead Office: 6 The Granary Building, Millow Hall Farm, Millow, Biggleswade, Bedfordshire SG18 8RH.

Tel: 01767 500 150

The UK’s No. 1 brand for closed loop water treatment and conditioning

X-POT and X-PO are registered trade marks of VEXO International (UK) Ltd.

Available from your local STOURFLEX branch