The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-generator System-2006

Embed Size (px)

Citation preview

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    1/9

    34 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS Vol.97(1) March 2006

    THE IMPACT OF CLOSED-LOOP POWER FLOW CONTROL

    STRATEGIES ON POWER SYSTEM STABILITY CHARACTERISTICS IN A

    SINGLE-GENERATOR SYSTEM

    A. Ally and B. S. Rigby

    School of Electrical, Electronic and Computer Engineering, University of KwaZulu-Natal, Durban 4041

    Abstract: This paper presents a theoretical study into the influence of closed-loop control of ac power flow on

    the small-signal and transient stability characteristics of a single-generator study system. Both the constant power

    and constant angle modes of power flow control are examined for a range of controller response times. The results

    indicate that the effect of a power flow controller on system stability is dependent on both the mode of the controller

    and its response time.

    Key words: Power Flow Control, Small-Signal Stability, Transient Stability, Thyristor Controlled Series Capacitor.

    1. INTRODUCTION

    The broad objective of Flexible AC Transmission Systems

    (FACTS) is to enhance the controllability and power transfer

    capability of interconnected ac power systems by means of

    power electronically controlled compensators [1]. Within

    this broad objective, FACTS devices can be used in a

    variety of ways to enhance the flexibility or controllability

    of power systems. One such application is the use of FACTS

    devices to provide direct control over the amount of power

    flowing in a particular transmission line, or group of lines,

    in an interconnected AC system [2,3]; this application has

    variously been described as power scheduling [2,4], power

    flow control [5,6], or closed-loop control of AC power flow

    [7]. Such closed-loop control of power flow in an AC systemcan provide a number of possible benefits: preventing

    unwanted loop flows in an interconnected system; allowing

    power to be directed along a contract path in a transmission

    system; preventing inadvertent overloading of lines already

    near their thermal limits [2,6].

    A FACTS devices capability to direct the flow of power

    rests on its ability to control dynamically one or more

    of the factors that influence power transfer in the line it

    compensates. Thus, closed-loop power flow control can

    be achieved using a thyristor controlled series capacitor

    (TCSC), a static synchronous series compensator (SSSC),

    or a unified power flow controller (UPFC), and a number

    of schemes employing these different devices have

    been proposed [3,4,5]. However, few researchers have

    considered the possible impact of closed-loop power flow

    control strategies on the stability characteristics of the rest

    of the power system, or the influence of the response time

    of these controllers on system stability, despite a range of

    powerflow controller designs and controller response times

    having been proposed in the literature.

    References [2] and [4] suggest that the response time

    of a closed-loop power flow controller should be on the

    order of 10 to 30 seconds, whereas references [3] and [5]

    report on controller designs with response times of tens

    of milliseconds. Reference [4] does consider the impact

    of FACTS device control on the stability characteristics of

    the power system as a whole, but in that study the FACTS

    device was equipped with both a power flow controller and

    a stabilising damping controller acting simultaneously:

    as such, it is not possible to draw conclusions from [4]

    on the impact of their power flow control strategies, or

    the response times of the power flow controller itself, in

    isolation from the other (supplementary) control functions

    of their FACTS device.

    This paper examines the impact of closed-loop power

    flow control on the small-signal and large-signal stabilitycharacteristics of an AC power system in isolation from

    any other supplementary controllers such as FACTS power

    oscillation damping controllers or power system stabilisers

    this is not to imply that such supplementary controls

    would not or should not be present in a power system,

    merely that the objective of the paper is to focus on, and

    isolate the influence of closed-loop power flow controllers

    on system stability. The paper considers a single generator

    infinite bus study system in order to allow the fundamental

    interactions to be examined readily, and considers a TCSC

    as the FACTS controllable compensator at the heart of the

    power flow controller. Furthermore, the paper considers

    power flow controller designs whose response times are

    on the order of several seconds as considered in [2, 4].

    Two distinct strategies have been proposed for implementing

    closed-loop powerflow control. The first, constant power

    strategy [2,4] involves forcing the uncompensated line (or

    lines) in a transmission system to absorb any increase in

    the power dispatched, while the second, constant angle

    strategy [2,4] regulates the flow of power along a particular

    line in which the controllable series compensation is

    applied. This paper presents a theoretical analysis of both

    the constant power and constant angle control strategies

    Copyright (c) 2004 IEEE. This paper was first published in AFRICON 04,

    15-17 September 2004, Gabarone, Botswana

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    2/9

    Vol.97(1) March 2006 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS 35

    as well as the basic philosophy behind these two control

    strategies in an interconnected AC transmission system.

    The paper examines not only the impact of a power flow

    controllers response time on the small-signal and large-

    signal stability characteristics of a power system, but in

    addition examines whether the mode of power flow control

    (i.e. constant power vs. constant angle) itself has anyimpact on stability characteristics.

    Figure 1: Single-line diagram of the study system.

    2. DETAILS OF STUDY SYSTEM

    2.1 System Overview

    Fig.1 shows a diagram of the single-generator study-

    system considered in this paper. The system consists of

    a synchronous generator that is connected to an infinite

    busbar via a transformer and two parallel transmission

    lines. Transmission line L1 is compensated with a TCSC,

    while line L2 is uncompensated.

    The structure of the study system shown in Fig.1 is based on

    that which was used to study line power scheduling in [4].However in this paper the parameters of the study system

    are different from those in [4], and are based on those of

    the Machines Research Laboratory at the University of

    KwaZulu-Natal [9]. In addition, in this study the generator

    at the sending end of the transmission line is equipped

    with an automatic voltage regulator (AVR). The inclusion

    of the generators AVR is important when considering the

    stability characteristics of a study system, since an AVR is

    known to have a significant impact on both small-signal

    and transient stability characteristics [11]. A detailed

    simulation model of the study system shown in Fig.1 has

    been developed in the power system simulation package

    PSCAD [13]. The key elements of this study system model

    are discussed briefly below.

    The synchronous generator is represented using a detailed

    (7th-order) electro-mechanical model within PSCAD. The

    generator is connected to an infinite busbar via two parallel

    transmission circuits and a transformer. Each transmission line

    is represented using lumped impedances, while the generator

    step-up transformer is represented by its leakage reactance.

    2.2 TCSC Model

    Fig.2 shows a single-line diagram of a TCSC, which

    comprises a capacitor in parallel with a thyristor-controlled

    reactor (TCR). This device is inserted in series with the

    transmission line, much like a series compensating

    capacitor. The net compensating reactance -jXTCSCthat theTCSC provides to the system is the parallel combination of

    itsfixed capacitive reactance -jXCand the variable inductive

    reactance, jXTCR

    of its TCR, where the latters magnitude is

    a function of the thyristor delay angle . For the purpose of

    interfacing a TCSC to a high-level controller, the devices

    control input is not the thyristor delay angle but rather the

    TCSCs reactance order Xorder

    , where

    (1)

    Figure 2: Single-line diagram of the TCSC and its internal

    controls.

    The reactance order Xorder

    of a TCSC is thus a dimensionless

    ratio (gain) that defines the extent to which the devices

    net compensating reactance is increased over the value of

    its fixed internal capacitive reactance XC; for a practical

    TCSC, the value of Xorder

    can range between 1 and 4 [10].

    In the PSCAD model of the TCSC used in this study, a

    linearization function, in the form of a look-up table for

    Xorder

    to thyristor firing angle () mappings, is used to

    calculate the correct value of for the demanded Xorder

    value at the input to the TCSC [7].

    The PSCAD model of the TCSC used in this study

    represents the individual components of the device in all

    three phases, including its power electronic switches and

    their low-level firing controls. Although thefiring angleof

    a TCSCs thyristors is measured from the zero crossings of

    its capacitor voltage VC, in practice the synchronization of

    the thyristor firing controls is usually carried out indirectly

    by means of a phase locked loop (PLL) synchronized to

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    3/9

    36 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS Vol.97(1) March 2006

    the transmission line currents [12] in order to ensure stable

    operation of the TCSC. The PSCAD model of the TCSC

    used in this study includes a detailed representation of a

    phase locked loop which calculates the instantaneous

    angle of the TCSC voltages from the measured line

    currents; the model also represents the low-level controls

    used to generate thyristor firing signals in each phase bycomparing to . Finally, the PSCAD model includes a

    surge arrester connected across each phase of the TCSC as

    shown in Fig.2. Such surge arresters are always a feature

    of TCSC installations in the field [10,12]; it has been found

    necessary to include them in the TCSC model in transient

    stability studies to ensure satisfactory performance of

    the TCSCs capacitor voltages, and hence of its PLL-

    based firing controls, following short-circuit faults in the

    transmission line [14].

    This PSCAD simulation model of the single generator

    study system, together with the detailed TCSC model, was

    used to investigate the performance of a closed-loop powerflow controller implemented in transmission line L1. The

    theory of power flow control is discussed in the following

    section.

    3. POWER FLOW CONTROL THEORY

    In Fig.1, the approximate expression for the active power

    transfer in line L1 is given by

    (2)

    where |V2| and |V

    3| are the magnitudes of the voltages at

    buses 2 and 3 of the system and 23

    is the transmission

    angle between these bus voltages.

    Equation 2 highlights the principle by which series

    compensation can be used to manipulate the net impedance

    of a particular transmission line and hence influence its

    power transfer. When the TCSCs reactance is increased for

    a given transmission angle 23

    , the net reactance XLX

    TCSC

    of the compensated line is reduced, thereby increasing the

    active power transfer. Hence, the magnitude of the active

    power transfer in the compensated line can be increased

    for a given transmission angle by increasing the amount

    of TCSC compensation. Alternatively an increase in theamount of TCSC compensation can be used to reduce

    the transmission angle required for a given active power

    transfer in the compensated line.

    These two observations underlie two distinct strategies

    that have been proposed for closed-loop control of line

    power flow [2]: the constant power strategy which

    keeps the power flow in the compensated line constant,

    and the constant angle strategy which ensures that the

    compensated line transfers any increase in dispatched

    power. Each of these strategies is now discussed in more

    detail.

    3.1 Constant Power Strategy

    Consider the system shown in Fig.1 initially operating at

    steady state, and then subjected to an increase in the output

    power of the generator. This increase in the generator

    output power (Pt) causes the common transmission angle

    23

    across both lines L1 and L2 to increase, and hence the

    active power transfer across both lines initially increases.

    However in the constant power strategy the TCSC is to be

    used to keep the power flow in line L1 constant at some

    desired set point value. The relationship in (2) shows that

    to achieve this, the TCSCs capacitive reactance has to be

    altered to counter any change in angle across line L1. In

    other words, when the generator output power is increased,

    the TCSCs reactance is then decreased accordingly so

    that the power transfer in line L1 remains unchanged fromthe desired set point value. Consequently, in this mode

    of control, all the increase in dispatched power from the

    generator is then forced to flow through line L2.

    3.2 Constant Angle Strategy

    Consider once again, the situation when the generator

    output power Ptin the system of Fig.1 is increased, but now

    the TCSC is to be used to maintain a constant transmission

    angle23

    across both lines. From (2) in order for additional

    power to be transmitted, either the capacitive reactance of

    the TCSC has to be increased or the transmission angle 23

    has to be increased. In this scenario, where the angle acrosslines L1 and L2 is to be kept constant, when the generator

    output power increases the TCSCs capacitive reactance

    has to be increased accordingly. Increasing the TCSCs

    reactance in this manner results in the compensated line

    L1 transferring all the additional power dispatched. This

    ensures that the angle across line L1 and L2 is kept constant

    and that the power transfer in the uncompensated line L2

    remains unchanged.

    3.3 Structure of the Power Flow Controller

    A feedback control system has been developed in order

    to implement TCSC-based, closed-loop control of

    transmission line power flow in the study system of Fig.1; the structure of this control system has been devised in

    such a way that the powerflow controller can be operated in

    either the constant power mode or the constant angle mode

    simply by setting a toggle switch in the PSCAD simulation

    model. Figs. 3 and 4 show the structure of this feedback

    control system as it appears for each of the two settings

    of the toggle switch. Note that the initial setting for the

    powerflow controller is always constant power mode: that

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    4/9

    Vol.97(1) March 2006 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS 37

    is, the power flow controller starts, by default, in constant

    power mode, and can be switched into constant angle mode

    thereafter if desired.

    Note also that in both power flow control modes, the

    innermost part of the controller is the same in each case.

    Specifically, in both Fig. 3 (constant power mode) and Fig.4 (constant angle mode) a feedback loop compares a signal

    PL1

    *, representing the commandedvalue of power transfer

    in line L1, to the actual (measured) value of power transfer

    in line L1 (PL1

    ) in order to generate an error signal PL1

    ;

    this error signal PL1

    is used to drive a proportional-integral

    (PI) controller which adjusts the Xorder

    value of the TCSC

    around some set-point value Xorder 0

    in order to force PL1

    to

    follow the commanded value PL1

    *.

    Figure 3: Block diagram showing the structure of the

    powerflow controller as it appears in the constant power

    mode of control.

    Figure 4: Block diagram showing the structure of the power

    flow controller as it appears in the constant angle mode ofcontrol.

    The difference between the two mode settings of the power

    flow controller lies in how this commanded value of PL1

    *at

    the input to the feedback loop is created in each case: the

    actual value of PL1

    *is obtained by adding the output of the

    Mode Select switch to the value of a user-settable input

    PL1 set

    which represents the set-point value for the power

    transfer in line L1.

    Thus, in Fig. 3, when the Mode Select switch is set to

    position A, the output of this Mode Select switch is zero

    and the commanded value of power transfer in line L1

    is then simply the set-point value PL1 set; in this case thefeedback loop will then maintain the power transfer P

    L1in

    line L1 at whatever value is chosen by the user at the input

    PL1 set

    , that is the controller will operate in constant power

    mode.

    Once the power flow controller has reached steady state in

    constant power mode it can then, if desired, be switched

    into constant angle mode by activating the toggle switch in

    Fig. 4. When the toggle switch is activated in this way, itperforms two functions: firstly, it changes the Mode Selectswitch to position B; secondly, it activates a sample andhold circuit which takes a measurement of the active poweroutput P

    tat the generator terminals and saves its value at

    the onset of constant angle control to a storage variable Pt 0

    .

    Fig. 4 shows that a signal

    Pt= Pt

    Pt 0is then created whichrepresents the change in power dispatch from the generatorsince the time at which constant angle control commenced;in constant angle mode, (Mode Select switch in positionB) this signal P

    tis then added to the set-point value P

    L1 set

    to form the new commanded value PL1

    *of power transferin line L1 applied at the input to the feedback loop. In thisway, if and when the power flow controller is switched toconstant angle mode, the commanded input to the powerflow controller becomes P

    L1

    *= PL1 set

    + Pt, such that line

    L1 is forced to transfer its initial power, plus any changeingenerator dispatch.

    4. SMALL SIGNAL BEHAVIOUR

    4.1 Verification of control modes

    This section examines the impact of the two closed-looppowerflow control strategies on the small-signal dynamiccharacteristics of the study system in Fig.1. However, priorto considering this issue, the basic characteristics of thetwo modes of power flow control are verified by means ofthree simulation studies.

    To test the performance of each control strategy, in eachcase the simulation study was started from the same steadystate condition in which the generators active power outputP

    t= 0.769 p.u., and with this active power being initially

    transferred by the two lines L1 and L2 as follows: PL1

    =

    0.462 p.u. and PL2= 0.307 p.u.

    Figure 5: Response of the study system with no power

    flow control.

    Subsequently, the mechanical input power to the generatorwas increased by P

    m= 0.04 p.u. such that the total active

    power Pt dispatched was increased to 0.809 p.u. The

    response of the system to this small increase in generatordispatch was then studied for the system without the power

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    5/9

    38 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS Vol.97(1) March 2006

    flow control activated (i.e. with the TCSCs Xorder

    held

    constant) as well as with the power flow control activated

    in each of the two control modes.

    Fig. 5 shows the simulated response of the study system

    to the increase in generator dispatch without power flow

    control; the variables shown are the active power transfersin each line as well as the TCSCs X

    ordervalue. The result

    in Fig.5 confirms that, without the power flow controller

    activated, the additional power dispatched by the generator

    is shared between both of the two parallel transmission

    lines, with line L1 transferring a larger proportion of the

    additional power: line L1 transfers a larger share of the

    dispatched power since it is electrically shorter than line

    L2 as a result of the (in this case) fixed value of TCSC

    compensation. In this scenario (fixed TCSC compensation)

    any increase in generator dispatch results in both

    transmission lines transferring a portion of the increased

    power, and no form of power flow control along a contract

    path can be instituted.

    Fig. 6 now considers the study system with the power

    flow controller active and set to the constant power mode.

    The results show that, following the increase in generator

    dispatch, initially the power transfer in both lines L1 and L2

    increases, which then results in the power flow controller

    reducing the degree of capacitive compensation provided

    by the TCSC. By reducing the capacitive reactance of the

    TCSC, the power transfer in line L1 decreases accordingly

    and returns to its nominal operating point of 0.462 p.u. All

    of the additional power dispatched by the generator is thus

    forced to flow through line L2, where the power transfer is

    increased to 0.347 p.u. This response thus satisfies the basic

    philosophy of the constant power strategy discussed inSection 3, and confirms that the constant power controller

    is correctly implemented in the PSCAD model of the study

    system in Fig.1.

    Figure 6: Response of the study system with the power

    flow controller in constant power mode.

    Fig.7 shows the behaviour of the study system following

    the increase in generator dispatch with the power flow

    controller now set to operate in constant angle mode.

    According to [2,4] the constant angle strategy should

    ensure that the compensated line transfers all the additional

    output power of the generator. Fig.7 shows that initially,

    following the increase in generator dispatch, the active

    power transferred by both lines increases; however, the

    power flow controller responds by increasing the degree

    of capacitive compensation provided by the TCSC such

    that the power transfer in line L2 returns to its nominal

    operating point of 0.307 p.u and all the additional dispatch

    is transferred by line L1 (PL1

    increases to 0.502 p.u). Fig.7

    thus confirms that the constant angle controller is correctly

    implemented in the PSCAD model of the study system in

    Fig.1.

    4.2 Influence of power flow control on small-signal

    characteristics of the study system.

    Section 4.1 has confirmed the correct operation of the power

    flow controller in the constant power and constant angle

    modes. This section now examines the impact that each

    of these power flow control modes has on the small-signal

    stability characteristics of the study system when the power

    flow controller is designed to respond at different rates.

    Previous work [7] has described a technique for designing

    the dynamic response characteristics of the closed-loop

    powerflow controller. In this section, the design method of

    [7] has been used to arrive at three different settling times

    for the power flow controller implemented on the study

    system of Fig.1. The settling times considered are, tS= 5s;

    tS

    = 10s and tS

    = 25s. For each of these settling times, and

    for both modes of power flow control, the response of the

    study system was examined for a small step increase in the

    mechanical input power to the generator.

    Fig.8 compares the small-signal response of the study

    system to an increase in generator dispatch for the three

    different settling time designs of the controller in constant

    power mode. In considering the responses in Fig. 8, there

    are two aspects to the behaviour of the system that are

    Figure 7: Response of the study system with the power flow

    controller in constant angle mode.

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    6/9

    Vol.97(1) March 2006 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS 39

    affected by the design of the power flow controller. Firstly,

    the rate at which the power transfer in each line is returned

    to the correct post-disturbance steady state value is

    different in each case, which is the expected (and intended)

    consequence of adjusting the controller design. However

    the results show that the damping of the generators

    electromechanical oscillations is also affected by the powerflow controllers response time: close inspection of Fig. 8

    shows that the rate of decay of the oscillatory components

    of the line powers PL1

    and PL2

    becomes greater as the

    settling time of the power flow controller is made shorter.

    The electromechanical swing mode of the generator in

    this system has a frequency of approximately 1 Hz. As

    such, one would expect that the power flow controller

    would be more likely to influence the characteristics of

    this electromechanical swing mode (via the associated

    oscillations in the line power transfers) as the response

    of the controller is made faster. Conversely, one would

    expect the power flow controller to have less influence

    on the characteristics of the systems electromechanical

    oscillations when its response time is designed to be

    significantly longer than the period of these oscillations.

    However, the results in Fig. 8 show not only that the

    power flow controller has a greater influence on the

    electromechanical oscillations of the study system as its

    response time is made shorter, but in addition that this

    influence is to increasethe damping of these oscillations,

    at least in constant power mode.

    Fig.9 once again compares the response of the system to

    an increase in dispatch at the three different settling times

    of the power flow controller, but with the controller now

    operating in constant angle mode. As in the case of constantpower mode, the design of the controllers settling time

    influences not only the rate at which the power transfers in

    each line are returned to their correct steady state values,

    but also the damping of the post-disturbance oscillatory

    components present in these power transfers as a result of

    the generators electromechanical swings.

    Figure 9: Small-signal response for different powerflow controller

    settling times: constant angle mode.

    Close inspection of Fig. 9 shows that in constant angle

    mode, the influence of the power flow controller is to

    decrease the damping of the systems electromechanical

    oscillations: the results show that as the settling time of

    the power flow controller is made shorter, the systems

    electromechanical oscillations take progressively longer to

    die out following the disturbance.

    The results of the small-signal investigations in this section

    have thus shown that in both modes of operation, the

    closed-loop power flow controller has a more pronounced

    influence on the damping of the systems electromechanical

    oscillations as its response time is made shorter. However

    the natureof this influence of the power flow controller

    is dependent on its mode of operation: in constant power

    mode the influence is beneficial, adding to the inherent

    damping of the system; in constant angle mode the influence

    is detrimental, acting to diminish the systems inherent

    damping. The reasons for the opposite influences on system

    damping in the two power flow control modes requiresfurther investigation, but the conclusion is clear: operation

    in constant angle mode is detrimental to the inherent

    damping of the system, particularly at short settling times

    of the power flow controller; as a result, careful design of a

    constant-angle controller would be required, in conjunction

    with any other damping controllers present in the system,

    prior to practical implementation of such a scheme.

    5. LARGE SIGNAL BEHAVIOUR

    The previous section has considered the impact of power

    flow controller design, and controller mode, on the small

    signal characteristics of the study system. This sectionnow examines the impact of closed-loop power flow

    control on the behaviour of the study system under the

    transient conditions that typically follow a large system

    disturbance.

    Once again the characteristics of the study system in Fig.1

    are investigated, firstly with the power flow controller

    disabled, and thereafter for each of the two modes of power

    flow control, in this case for a single value of settling time

    tS= 5s. The study system in Fig.1 was started from a steady

    state condition at which the generators total active power

    output is 0.733 p.u. A three-phase short-circuit fault was

    then applied in the uncompensated line L2 and removedafter 700ms, with the fault located 33% of the way along

    the line from bus 2. The fault duration of 700 ms chosen

    for this study is relatively long: although faults of this

    duration can occur in practice, they are relatively rare.

    However, this severe disturbance to the study system has

    been chosen in order to be able to demonstrate more clearly

    the influence of the different power flow controller modes

    under transient conditions.

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    7/9

    40 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS Vol.97(1) March 2006

    Fig. 10 shows the simulated response of the study system

    following the three-phase short-circuit fault with no power

    flow control. The variables shown are the generators

    transmission angle relative to the infinite bus, its rotor

    speed deviation, as well as the value of Xorder

    at the input to

    the TCSC. When such a fault occurs, the electrical output

    power of the generator is reduced (since the fault is applied

    midway along the line, there is still some power transfer

    on the unfaulted line) while the mechanical input power

    remains constant. As a result of the imbalance between the

    mechanical input power and electrical output power of the

    generator, the generator rotor starts to accelerate and its

    transmission angle increases. When the fault is removed

    the electrical output power increases abruptly, such that

    the electrical output power of the generator then exceeds

    the mechanical input power, hence causing the generator

    to decelerate and, in this case, return to synchronism. Notealso, that with no power flow control implemented, the

    amount of compensation provided by the TCSC remains

    constant both during the fault, and in the post-fault transient

    period.

    Figure 10: Response of study system to the 3-phase short-circuit

    fault: no power flow control.

    Fig. 11 now shows the response of the study system with the

    powerflow controller active in the constant power mode.

    As before, when the fault is applied, the total output power

    of the generator decreases causing the generator rotor to

    accelerate. However, in this case, with the power flow

    controller activated, the controller responds to the transient

    swings in the power transferred by the lines by varying

    the amount of compensation provided by the TCSC. In

    particular, Fig. 11 shows that the response of the controllerin constant power mode is initially to increasethe TCSCs

    Xorder

    value in an effort to return the power transfer in the

    compensated line L1 to its nominal operating point when

    the fault appears. However once the fault is removed,

    the electrical output power of the generator increases,

    which results in the compensated lines power transfer

    temporarily exceeding its nominal operating point value.

    The power flow controller then decreases the TCSCs Xorder

    accordingly in order to return the power in the compensated

    line to its pre-disturbance operating point value.

    Fig. 12 now shows the response of the study system with

    the power flow controller in constant angle mode. Theresults show that in this mode of operation, the power flow

    controller responds to the short circuit fault by initially

    sharply decreasingthe compensation in line L1.

    Recall that in constant angle mode the controller is designed

    to respond to a reduction in generator dispatch by reducing

    the degree of compensation of line L1 in order to maintain a

    Figure 8: Small-signal response for different powerflow controller

    settling times: constant power mode.

    Figure 11: Response of the study system to the 3-phase short-

    circuit fault: constant power mode.

    Figure 12: Response of the study system to the 3-phase short-

    circuit fault: constant angle mode.

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    8/9

    Vol.97(1) March 2006 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS 41

    constant angle across both lines. In this case, the reduction

    in generator output power is a transient one caused by a

    short-circuit fault, rather than as a result of a permanent

    change in system operating point, but the constant angle

    control nevertheless responds to the transient swings in the

    generator and transmission line power transfers.

    Comparison of Figs. 11 and 12 thus shows that the power

    flow controller initially responds in the opposite manner

    to the same short-circuit fault in its two different modes of

    operation: in constant power mode the controller initially

    responds by reducing the net impedance of the compensated

    line, with the effect being that the total power transfer out

    of the generator during the fault is increased by the action

    of the controller; in constant angle mode, the controller

    initially responds by increasing the net impedance of the

    compensated line, with the effect being that the total power

    transfer out of the generator during the fault is reduced by

    the action of the controller.

    It is well known that the transient (first-swing) stability

    of a generator is enhanced by any action that results in

    improved transfer of active power out of the generator

    during, and immediately after a fault condition [11]. The

    results in Figs. 11 and 12 therefore suggest that the mode

    of the power flow controller will have an effect on the

    first swing characteristics of the generator in response to a

    short-circuit fault. Fig. 13 therefore compares the response

    of the generators transmission angle and speed deviation

    to the short-circuit fault for the cases where the power flow

    control is inactive; active in constant power mode; active

    in constant angle mode (i.e. the results of Figs. 10, 11 and

    12 are now plotted on the same axes).

    Figure 13: Comparison of responses to the short-circuit fault:

    constant power; constant angle; no control.

    The results in Fig. 13 confirm that the powerflow controller,

    and its mode of operation, both influence the first swing

    characteristics of the generator: the amplitude of the first

    swing of the generator angle is slightly smaller in constant

    power mode than for the case when there is no power flow

    control; by contrast, the amplitude of the first swing of

    the generator angle is noticeably larger when the power

    flow controller is in constant angle mode. The post-fault

    behaviour of the generators speed deviations in Fig.13

    also provide further confirmation of the findings in Section4 of the paper the small-signal damping is significantly

    improved by the power flow controller in constant power

    mode whereas the damping is clearly reduced by the

    controller in constant angle mode.

    6. CONCLUSION

    This paper has considered the application of a thyristor

    controlled series capacitor for closed-loop control of

    power flow in both constant power and constant angle

    modes of operation. The results indicate that the power

    flow controllers operation has an important influence on

    both the small-signal and transient stability characteristicsof a power system. In particular it has been shown that

    the constant angle mode of operation can be detrimental

    to system damping and first swing stability, particularly

    for a relatively fast-responding power flow controller. By

    contrast, the constant power mode of operation has been

    shown to have a beneficial impact on both system damping

    and first-swing stability under the conditions studied.

    7. REFERENCES

    [1] Adapa R, Baker MH, Habashi K: Proposed Terms

    and Definitions for Flexible AC Transmission System

    (FACTS), IEEE Transactions on Power Delivery,

    Vol.12, No.4, 1997.

    [2] Larsen EV, Bowler CEJ, Damsky B, Nilsson S: Benefits

    of Thyristor Controlled Series Compensation, CIGRE

    Paper 14/37/38-04, Paris, 1992.

    [3] Gyugyi L, Rietman TR, Edris A, The Unified

    Power Flow Controller: A New Approach to Power

    Transmission Control IEEE Transactions on Power

    Delivery, Vol. 10, No.2, April 1995.

    [4] Martins N, Paserba JJ, Pinto JCP: Using a TCSC

    for Line Power Scheduling and System OscillationDamping Small Signal and Transient Stability

    Studies, Proceedings IEEE PES Winter Meeting,

    Singapore, January 2000.

    [5] Mihalic R, Papic I, Power Flow Control Using Static

    Synchronous Series Compensator, Proceedings UPEC

    97, pp. 174-177.

  • 7/25/2019 The Impact of Closed-loop Power Flow Control Strategies on Power System Stability Characteristics in a Single-ge

    9/9

    42 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS Vol.97(1) March 2006

    [6] Noroozian M, Andersson G, Power Flow Control

    By Use Of Controllable Series Components, IEEE

    Transactions on Power Delivery, Vol. 8, No.3, July

    1993, pp. 1420-1429.

    [7] Rigby BS: An AC Transmission Line Power Flow

    Controller Using a Thyristor Controlled SeriesCapacitor, Proceedings IEEE Africon 2002, George,

    South Africa, October 2002, pp.773-778.

    [8] Ally A, Rigby BS, The Application of a Thyristor

    Controlled Series Capacitor for Closed-Loop Control

    of Transmission Line Power Flow, Proceedings

    SAUPEC 04, Stellenbosch, South Africa, Jan 2004.

    [9] Limebeer DJN, Harley RG, Schuck SM,

    Subsynchronous Resonance of the Koeberg turbo-

    generators and of a laboratory micro-alternator

    system, Transactions of the SAIEE, Vol. 70, Part 11,

    Nov. 1979, pp. 278-297.

    [10] Hingorani NG, Gyugyi L, Understanding FACTS:

    Concepts and Technology of Flexible AC Transmission

    System, IEEE Press, Piscataway New Jersey, 1999,

    ISBN 0-7803-3455-8.

    [11] Kundur P, Power System Stability and Control,

    McGraw Hill Inc, New York, 1994.

    [12] Song YH, Johns AT, Flexible AC Transmission

    Systems, IEEE Power & Energy Series 30, ISBN 085

    2 9677 13.

    [13] Manitoba HVDC Research Centre Inc: Introduction

    to PSCAD/EMTDC Version 3.0.

    [14] Carpanen RP, Rigby BS: Transient Stability

    Enhancement Using a Thyristor Controlled Series

    Capacitor, Proceedings IEEE Africon 2004,

    Gaborone, Botswana, September 2004.

    8. APPENDIX

    Line Parameters (L1& L

    2): R

    L= 0.033 pu X

    L= 0.75 pu

    TCSC Parameters: XC= 0.124 pu XL = 0.025 puTransformer Parameters: X = 0.13 pu

    Synchronous Generator Parameters documented in reference [9]

    Per Unit System: Vbase

    = 220 Vrms (l-l) Pbase

    =3KVA

    Zbase

    = 16.13 Ohm Ibase

    =7.87Arms