FAIRA TRANSPARENCY REPORT
4147 Longfellow Pl. NW, Bremerton, WA 98312
August 22, 2019
Thank you for your interest in this Faira Certified home.
We have coordinated the efforts of certified and licensed inspection and title professionals to createthe Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolioof information that is prepared on behalf of buyers in preparation for making an informed offer on theproperty.
Please note that not all sellers opt into the inspection portion of our reports.
You may view more detailed information for this home and can make an offer at
All of the information in the Faira Transparency Reports was gathered and compiled without any biasor influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s)ordered the same professionals to perform the evaluations on the same date. Nevertheless, Fairatakes no obligation of the reports being complete or accurate. The buyers are recommended toconduct their own due-diligence to their satisfaction.
Please contact us if you have any questions or would like more information.
We're happy you've chosen a Faira Certified home and look forward to the opportunity of working withyou!
The Faira Team
Inspection Report for Ms. Brenda FrancoProperty Address: 4147 Longfellow Pl NW, Bremerton, Washington 98312
NW WASHINGTON HOME INSPECTIONS LLC
Carl Liberman License #1758Bainbridge Island, Washington
Table of Contents
Cover Page.................................................................1
Table of Contents ........................................................2
Intro Page ...................................................................3
Significant Issues ........................................................5
Repair & Maintenance Summary ................................7
Future Improvements................................................11
1 Roof .......................................................................13
2 Attic ........................................................................16
3 Exterior...................................................................19
4 Wall Exteriors.........................................................28
5 Structure ................................................................33
6 Electrical ................................................................35
7 Garage...................................................................39
8 Interior....................................................................44
9 Plumbing ................................................................50
10 Heating.................................................................52
11 Bathrooms............................................................55
12 Kitchen and Built-in Appliances ...........................58
13 Laundry Room .....................................................61
Invoice.......................................................................63
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 2 of 63
Date: 8/21/2019 Time: 09:00 AM Report ID: 190821 AProperty:4147 Longfellow Pl NWBremerton Washington 98312
Customer:Ms. Brenda Franco
Real Estate Professional:
FAIRA.COM
Dear Ms. Franco,
Thank you for choosing NW WASHINGTON HOME INSPECTIONS LLC for your home inspection needs. I greatlyappreciate the importance of this inspection and have done my utmost to provide you with an organized,sufficiently-detailed, and easy-to-read report.
Three summary reports are provided at the beginning of the report highlighting the most significant findings. TheSignificant Issues Summary includes the most serious issues identified during the inspection. The Repair &Maintenance Summary includes the remainder of those potentially near-term actionable items for you to considerbased on the inspection. Future improvements are provided for your consideration.
The body of the report is organized by system: Roofing, Structure, Electrical, etc. I have included pictures whenpossible. Please review the entire report as there is additional information presented in the body of the report thatmay not be found in the summaries.
If you have any questions regarding your inspection, please feel free to contact me directly at 206.841.9532 or emailme at [email protected]. I look forward to providing future home inspection needs to you, yourfriends, and family.
Warm Regards,
Carl Liberman
Significant Issues ( ) = Items or discoveries indicate that these systems or components may cost significant moneyto correct now or in the near future, or items that require immediate attention to prevent additional damage or eliminatesafety hazards. Further investigation by a specialist and/or subsequent observation may be required.
Repair & Maintenance ( ) = Items or discoveries indicate that these systems or components do not function asintended and/or maintenance is required in the near term. Further investigation by a specialist and/or subsequentobservation may be required.
Future Improvements ( ) = Items or discoveries indicate that these systems or components should be considered forupgrade and/or modernization. Improved safety and/or energy efficiency may apply.
Standard Limitations: Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes ofthe need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance ornon-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability;The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence ofpests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Homeinspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system orcomponent; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspectoror other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does notrespond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debristhat obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardoussubstance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 3 of 63
effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limitedto failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information shouldhire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.
Standards of Practice:Washington State Standards of Practice forHome Inspectors & Inspections (WAC308-408C)
Type of building::Single Family (2-story)
Approximate Square Footage::2432
Approximate Year of OriginalConstruction::1983
Occupancy::Unoccupied, empty of furniture
Attending the Inspection::Owner
Weather during the Inspection::Light Rain, Cloudy
Significant precipitation in last 3 days::Yes
Temperature during inspection::Over 60 (F) = 15.5 (C)
Ground/Soil surface condition:Dry
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 4 of 63
Significant IssuesSignificant Issues = Items or discoveries indicate that these systems or components may cost significant money tocorrect now or in the near future, or items that require immediate attention to prevent additional damage or eliminatesafety hazards.
3. Exterior
3.6 Deck, Balcony, Bridge and Porch,(2) Decking on the front deck is in general poor condition with areas of rot throughout the decking. Some deckinghas been replaced.(5)
1. Significant rot to support posts and structural deck beams were found on the back deck structure (seephotos).
2. Deck posts are inadequately supported and secured at the foot. Concrete footers, if integrated into theslab, are not visible.
I would recommend further inspection and repairs by a licensed decking contractor.
4. Wall Exteriors
4.0 Door Exteriors(1)
1. The downstairs sliding door outer glass pane is broken and missing.2. The door-lock is missing.
4.2 Composite Siding(1) Hard-board siding is installed on the sides and back of the home. Hard-board siding produced prior to 1996 ofvarious manufacturers have seen problems with susceptibility to water absorption and subsequent related problemsand damage. Several class action lawsuits have been settled. Once damaged, replacement is generally the bestoption.
I did note damage to several areas of siding on all three of these exposures. Please see my further comments inthis section.
I would recommend further inspection, replacement and/or repairs by a licensed siding contractor.
6. Electrical
6.18 Carbon Monoxide DetectorsI did not locate any installed carbon monoxide detectors. Carbon monoxide alarms must be located outside of eachseparate sleeping area, in the immediate vicinity of the bedroom and on each level of the residence. Install inaccordance with manufactures recommend guidance or hire a licensed contractor for proper installation. ReferenceWAC 51-51-315: http://apps.leg.wa.gov/WAC/default.aspx?cite=51-51-0315
8. Interior
8.1 Walls
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 5 of 63
(1) I noted a deteriorating surface low on the exterior wall in the master bedroom closet. These areas tested for highmoisture content using my moisture meter. I would recommend further inspection by a qualified contractor.(4) I noted a deteriorating surface low on the exterior wall at the base of the stairs. This area tested for highmoisture content using my moisture meter. I would recommend further inspection by a qualified contractor.
8.2 CeilingsThe ceiling in the south downstairs bedroom has damage in several areas. I noted general unevenness, the ceilingcoating may be compromised. i would recommend further investigation by a qualified contractor.
Please note this section is not all-inclusive, please read the complete report.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 6 of 63
Repair & Maintenance SummaryRepair & Maintenance Issues = Items or discoveries indicate that these systems or components do not function asintended and/or maintenance is required in the near term. Further investigation by a specialist and/or subsequentobservation may be required.
1. Roof
1.3 Roof Drainage System(1) Several gutter seams are leaking. These conditions are conducive to wood destroying organisms.
(2) Gutters require cleaning and periodically thereafter.
2. Attic
2.3 Roof Structure VentilationI noted signs of bird nesting in the soffit vents.
2.4 Attic ElectricalElectrical junction boxes in the attic require cover-plates.
2.5 Attic Thermal EnvelopeDisplaced insulation in the attic requires redistribution in order to restore thermal performance.
2.6 Venting Systems (Kitchens, Baths and Laundry)I would recommend insulating bathroom ventilation ducting.
3. Exterior
3.1 DrivewayTree roots have uplifted an area of the driveway slab resulting in a potential trip hazard.
3.3 General GroundsSome areas of the front of the home (under the entry deck) may promotes surface drainage towards the foundation.A persistently wet foundation can cause a range of problems to include foundation damage, settlement, andmoisture related problems within the structure. A 6 inch drop in the first 10 feet of grade is recommended topromote natural drainage away from the foundation when possible. Please see my related comments in section8.1.
3.6 Deck, Balcony, Bridge and Porch,(3)
1. Deck railing repairs are incomplete on the front deck.2. Baluster spacing exceeds the maximum recommend spacing of 4 inches.3. A graspable handrail is recommended for the stairs.4. 4X4 bolted posts are recommended for railing support.
Please see http://www.awc.org/pdf/codes-standards/publications/dca/AWC-DCA62012-DeckGuide-1405.pdf forfurther guidelines. Additional local guidelines may apply.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 7 of 63
(4) This decking board on the front porch is not secured with fasteners.
3.7 Fences, Gates, and Boundary WallsPaint is failing on the north privacy fence.
4. Wall Exteriors
4.0 Door Exteriors(2) The front door jamb is damaged.
4.2 Composite Siding(2) South side wall damage noted to siding (see photos). Unusual dust or frass noted at the base of the wall. Theseconditions are conducive to wood destroying organisms.(3) Displaced siding noted under back deck.
(4) Siding and door damage at back door to deck.
(5) Siding missing/damaged north side.
6. Electrical
6.7 Service Panel Cabinet, Ampacity, and Cover1. The electrical panel cover is not fully installed due to interference with an interfering wall and missing cover
screws.2. Access to the panel is limited as the panel cover cannot be fully removed.
7. Garage
7.0 Vehicle DoorsThe left garage vehicle door failed to reverse when a reasonable amount of resistance was applied. I wouldrecommend service by a qualified garage door contractor.
7.1 Conventional DoorsThe door frame to the back garage door has is damaged.
7.3 Walls(1) The garage exterior walls are in need of paint/stain.
(2) This section of siding on the south garage wall requires repair/replacement.
7.6 Garage Electrical(1) Electrical outlets and junction boxes require cover-plates throughout the garage.
(2) This electrical splice should be housed within an electrical junction box.
7.9 Other(1) The entry breezeway on the north side of the garage has rot and water damage to trim and posts. Clearance tograde is inadequate. These conditions are further conducive to wood destroying organisms.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 8 of 63
8. Interior
8.1 Walls(2) Baseboard trim is not fully installed in the master bedroom.
(3) Staining on the walls of unknown origin was noted in the downstairs hot water-heater closet. Areas testeddemonstrated normal moisture levels using my moisture meter.
8.3 LightingThis downstairs hall closet light requires installation, electrical wires are exposed.
8.4 DoorsThe glass on the master bedroom closet door is cracked.
8.6 StairsGraspable hand-rails are recommend for both flights of stairs.
9. Plumbing
9.4 Electric Water Heater(1)
1. Water heaters are required to be anchored or strapped to resist horizontal displacement due to earthquakemotion. Strappings shall be at points within the upper one-third and lower one-third of its verticaldimensions. At the lower point, a distance of not less than four (4) inches (102 mm) shall be maintainedfrom the controls to the strapping.
2. A surge tank is recommended.3. A plumbed drip pan is recommended.4. Copper flex-lines are recommended.
I would recommend repairs by a licensed plumbing contractor.
10. Heating
10.1 Heat PumpPosted service records do not indicate recent servicing of your furnace. The air filter is dirty. I would recommendservicing of your heating system by a licensed heating contractor and annually thereafter.
10.5 FireplaceThe living room fireplace was not operational when tested, the propane tank appears to be empty.
11. Bathrooms
11.10 BathtubThe master bathtub jets were not operational when tested.
11.11 ShowerA tile piece is missing at the master shower.
11.13 Sink
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 9 of 63
The upstairs bathroom sink is cracked.
12. Kitchen and Built-in Appliances
12.13 DishwasherThe dishwasher did not appear to have an anti-siphon device installed in the drain line. Anti-siphon devices areinstalled to prevent wastewater from the dishwasher from being siphoned back into the dishwasher andcontaminating its contents. I would recommend an anti-siphon device be installed by a qualified technician.
12.15 SinkThe garbage disposal is missing the flexible insert at the sink drain.
Please note this section is not all-inclusive, please read the complete report.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 10 of 63
Future Improvements
1. Roof
1.2 Roof FlashingNo drip edge flashing was installed at the time of the inspection. Lack of edge flashings may leave the edges of roofsheathing and underlayment exposed to the deteriorating effects of weather, with damage from moisture such asdelamination and decay possible. The International Residential Code (IRC) has required edge flashing since 2012.Most building authorities have adopted this code into there building standards.
1.5 Chimney at RoofI would recommend a rain-cap installed over this chimney.
1.6 Asphalt Composition ShingleI would recommend inquiring about a transferable warranty for this asphalt shingle replacement roof.
4. Wall Exteriors
4.1 Window ExteriorsWindow seals are noted to have failed in the living room back fixed windows (see photos). Generally, glassreplacement is necessary to restore visual clarity.
6. Electrical
6.17 Smoke Detectors1. Smoke detectors are recommended on each floor of the home, in each bedroom of the home, outside
common bedroom areas. Install in accordance with manufactures recommend guidance or hire a licensedcontractor for proper installation. Reference WAC 212-10-040: http://apps.leg.wa.gov/wac/default.aspx?cite=212-10-040
2. The National Fire Protection Association (NFPA) recommend replacement of smoke detectors greater than10 years old.
7. Garage
7.9 Other(2) Two foundation cracks on the west garage foundation wall were noted. I would recommend further assessmentby a structural engineer if conditions are noted to change.
9. Plumbing
9.4 Electric Water Heater(2) Please note, this water heater is approximately 13 years old and has reached the typical life-span of 12 - 18years. Consider a home warranty to mitigate repair/replacement costs. Budget for a replacement in the future.
12. Kitchen and Built-in Appliances
12.9 Kitchen Appliances
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 11 of 63
Consider purchasing a home warranty that covers your kitchen and other appliances to mitigate any near-termrepair or replacement costs.
13. Laundry Room
13.8 Dryer VentingI would recommend cleaning the dryer exhaust ducting.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 12 of 63
1. RoofThe roof inspection portion of the General Home Inspection will not be as comprehensive as an inspection performed by a qualified roofing contractor.Because of variations in installation requirements of the huge number of different roof-covering materials installed over the years, the General HomeInspection does not include confirmation of proper installation. Home Inspectors are trained to identify common deficiencies and to recognizeconditions that require evaluation by a specialist. Inspection of the roof typically includes visual evaluation of the roof structure, roof-coveringmaterials, flashing, and roof penetrations like chimneys, mounting hardware for roof-mounted equipment, attic ventilation devices, ducts forevaporative coolers, and combustion and plumbing vents. The roof inspection does not include leak-testing and will not certify or warranty the roofagainst future leakage. Other limitations may apply and will be included in the comments as necessary.
Styles & Materials
Method of inspection:Walked the roof
The roof style was:Gable
Primary roof-covering type:Architectural Fiberglass Asphalt Shingle
Drainage system description:Gutters and downspouts installed
Chimney flue material:Tile
Underlayment/Interlayment::Not Visible
Sky Light(s):Two
Items
1.0 Roof Structure ExteriorComments: Inspected
1.1 UnderlaymentComments: Not Inspected
1.2 Roof FlashingComments: Inspected
1.3 Roof Drainage SystemComments: Inspected
No drip edge flashing wasinstalled at the time of the inspection.Lack of edge flashings may leave theedges of roof sheathing andunderlayment exposed to thedeteriorating effects of weather, withdamage from moisture such asdelamination and decay possible. TheInternational Residential Code (IRC)has required edge flashing since2012. Most building authorities haveadopted this code into there buildingstandards.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 13 of 63
(1) Several gutter seams are leaking. These conditions are conducive to wood destroying organisms.
(2) Gutters require cleaning and periodically thereafter.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 14 of 63
1.4 Plumbing and Combustion VentsComments: Inspected
1.5 Chimney at RoofComments: Inspected
1.6 Asphalt Composition ShingleComments: Inspected
The roof of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.
I would recommend a rain-capinstalled over this chimney.
I would recommend inquiringabout a transferable warranty for thisasphalt shingle replacement roof.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 15 of 63
2. AtticInspection of the attic typically includes visual examination the following:roof structure (framing and sheathing); roof structure ventilation; thermalenvelope; electrical components (wiring, junction boxes, outlets, switches and lighting); plumbing components (supply and vent pipes, bathroom ventterminations) and HVAC components (drip pans, ducts, condensate and TPR discharge pipes).
Styles & Materials
Attic info:Scuttle hole
Attic inspected from:Inside the attic
Attic thermal insulation material:Blown-in Fiberglass
Approximate attic thermal insulationdepth:
R-19
Roof Structure Ventilation:Attic ventilation appeared sufficient
Roof structure ventilation device type:Continuous ridge ventSoffit vents
Roof Framing Type:Manufactured Roof Trusses
Roof Sheathing Material:Plywood
Items
2.0 Attic AccessComments: Inspected
2.1 Roof Framing (from attic)Comments: Inspected
2.2 Roof SheathingComments: Inspected
2.3 Roof Structure VentilationComments: Inspected
2.4 Attic ElectricalComments: Inspected
I noted signs of bird nesting in the soffit vents.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 16 of 63
2.5 Attic Thermal EnvelopeComments: Inspected
2.6 Venting Systems (Kitchens, Baths and Laundry)Comments: Inspected
Electrical junction boxes in the attic require cover-plates.
Displaced insulation in the atticrequires redistribution in order torestore thermal performance.
I would recommend insulatingbathroom ventilation ducting.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 17 of 63
2.7 Attic Rodent ActivityComments: Inspected
The attic of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 18 of 63
3. ExteriorInspection of the home exterior typically includes: exterior wall covering materials; exterior trim; window and door exteriors; adequate surfacedrainage; driveway and walkways; window wells; exterior electrical and plumbing components; and retaining wall conditions that may affect the homestructure. The potential for dangers/damage associated with trees- such as falling branches or root damage to foundations- varies with tree speciesand age, and requires an arborist evaluation.
The General Home Inspection does not include inspection of landscape irrigation systems, fencing or swimming pools/spas.
Styles & Materials
Driveway Material:Concrete
Walkway Materials:ConcreteWood
Appurtenance:Deck with stepsDeck
Downspout Discharge:Below Grade
Lot Description:Moderate Slope
Clearance to Grade:Standard
Items
3.0 Exterior ViewsComments: Inspected
3.1 DrivewayComments: Inspected
3.2 WalkwaysComments: Inspected
3.3 General GroundsComments: Inspected
Tree roots have uplifted an area of the driveway slab resulting in a potential trip hazard.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 19 of 63
3.4 Exterior TrimComments: Inspected
3.5 PorchComments: Inspected
3.6 Deck, Balcony, Bridge and Porch,Comments: Limitation
Some areas of the front of thehome (under the entry deck) maypromotes surface drainage towardsthe foundation. A persistently wetfoundation can cause a range ofproblems to include foundationdamage, settlement, and moisturerelated problems within the structure.A 6 inch drop in the first 10 feet ofgrade is recommended to promotenatural drainage away from thefoundation when possible. Pleasesee my related comments in section8.1.
(1) Please note, my inspection of thefront deck was limited as access to theunder-structure was restricted to myviews from the sides.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 20 of 63
(2) Decking on the front deck is in general poor condition with areas of rot throughout the decking. Somedecking has been replaced.
rot rot
rot rot
rot rot from underneath
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 21 of 63
rot from underneath
(3)1. Deck railing repairs are incomplete on the front deck.2. Baluster spacing exceeds the maximum recommend spacing of 4 inches.3. A graspable handrail is recommended for the stairs.4. 4X4 bolted posts are recommended for railing support.
Please see http://www.awc.org/pdf/codes-standards/publications/dca/AWC-DCA62012-DeckGuide-1405.pdffor further guidelines. Additional local guidelines may apply.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 22 of 63
(4) This decking board on thefront porch is not secured withfasteners.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 23 of 63
(5)1. Significant rot to support posts and structural deck beams were found on the back deck structure (see
photos).2. Deck posts are inadequately supported and secured at the foot. Concrete footers, if integrated into
the slab, are not visible.
I would recommend further inspection and repairs by a licensed decking contractor.
rot in post same post
improper deck post support.
Rot in deck post
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 24 of 63
rot in structural beam
same beam
same beam improper post support
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 25 of 63
3.7 Fences, Gates, and Boundary WallsComments: Inspected
3.8 Additional StructuresComments: Not Inspected
Paint is failing on the north privacy fence.
Outbuilding - not inspected.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 26 of 63
The exterior of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 27 of 63
4. Wall ExteriorsInspection of the home exterior typically includes: exterior wall covering materials; exterior trim; window and door exteriors; adequate surfacedrainage; driveway and walkways; window wells; exterior electrical and plumbing components; and retaining wall conditions that may affect the homestructure. The potential for dangers/damage associated with trees- such as falling branches or root damage to foundations- varies with tree speciesand age, and requires an arborist evaluation.
The General Home Inspection does not include inspection of landscape irrigation systems, fencing or swimming pools/spas.
Styles & Materials
Exterior wall-covering Material:Horizontal Lapped Wood SidingHardboard Lap Siding
Exterior Doors:Solid wood
Items
4.0 Door ExteriorsComments: Inspected
(1)1. The downstairs sliding door outer glass pane is broken and missing.2. The door-lock is missing.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 28 of 63
4.1 Window ExteriorsComments: Inspected
4.2 Composite SidingComments: Inspected
(2) The front door jamb isdamaged.
Window seals are noted to have failed in the living room back fixed windows (see photos). Generally,glass replacement is necessary to restore visual clarity.
(1) Hard-board siding is installed on the sides and back of the home. Hard-board siding produced prior to1996 of various manufacturers have seen problems with susceptibility to water absorption and subsequentrelated problems and damage. Several class action lawsuits have been settled. Once damaged, replacementis generally the best option.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 29 of 63
I did note damage to several areas of siding on all three of these exposures. Please see my further commentsin this section.
I would recommend further inspection, replacement and/or repairs by a licensed siding contractor.
(2) South side wall damage noted to siding (see photos). Unusual dust or frass noted at the base of thewall. These conditions are conducive to wood destroying organisms.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 30 of 63
(3) Displaced siding noted under back deck.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 31 of 63
The exterior of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.
(4) Siding and door damage at back door to deck.
(5) Siding missing/damaged north side.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 32 of 63
5. StructureThe General Home Inspection includes inspection of the home structural elements that were readily visible at the time of the inspection. This mayinclude the: foundation; walls; floor structure; and/or roof structure. Soils vary in their stability and ability to support the weight of a structure. Minorcracking is normal with some common foundation materials, is typically limited to the material surface, is not a structural concern, and may not becommented on. Cracking related to soil/foundation movement indicates the potential for present or future structural concerns and will be commentedon to the best of the inspector's ability.
Much of the home structure is hidden behind exterior and interior roof, floor, wall, and ceiling coverings, or is buried underground. Because theGeneral Home Inspection is limited to visual and non-invasive methods, this report may not identify all structural deficiencies. Identification of portionsof the wall structure not directly visible requires logical assumptions on the part of the Inspector that are based on the Inspectors past experience andknowledge of common building practices.
Upon observing indications that structural problems may exist that are not readily visible, or the evaluation of which lies beyond the Inspector'sexpertise, the inspector may recommend evaluation or testing by a specialist that may include invasive measures, which would require homeownerpermission.
Styles & Materials
Typical Ceiling Structure:Not visibleDrywall attached to roof trusses
Exterior Wall Structures:Wood Frame
Wall Insulation:Not Visible
Foundation Configuration:Finished basement
Foundation Method/Materials:Poured concrete foundation walls
% Foundation Not Visible:100%
Main Floor Structure:Not visible
Main Floor Structure- Perimeter Bearing:Not Visible
Main Floor Structure- IntermediateSupport:
Not visible
Floor System Insulation:Unknown
Items
5.0 Exterior Wall ConstructionComments: Limitation
5.1 Floor StructureComments: Limitation
5.2 Insulation Under Floor SystemComments: Not Inspected
5.3 FoundationComments: Limitation
5.4 OtherComments: Not Inspected
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 33 of 63
The structure of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.
This access area in the downstairseast room was not accessible forinspection.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 34 of 63
6. ElectricalOver the years, many different types and brands of electrical components have been installed in homes. Electrical components and standards havechanged and continue to change. Homes electrical systems are not required to be updated to meet newly enacted electrical codes or standards. Fulland accurate inspection of electrical systems requires contractor-level experience. For this reason, full inspection of home electrical systems liesbeyond the scope of the General Home Inspection.
The General Home Inspection is limited to identifying common electrical requirements and deficiencies. Conditions indicating the need for a morecomprehensive inspection will be referred to a qualified electrical contractor.Inspection of the home electrical system typically includes visualinspection of the following:service drop: conductors, weatherhead, and service mast; electric meter exterior; service panel and sub-panels; serviceand equipment grounding; system and component bonding; and visible branch wiring: receptacles (representative number), switches, lighting
Styles & Materials
Electrical Service Conductors:Underground serviceAluminum120/240 volt service
Service Panel Ampacity:200 amps
Service Panel Type:Load Center
Service Panel Manufacturer:General Electric
Service Disconnect Location:At Service Panel
Service Disconnect Type:Breaker
Service Grounding Electrode:Not Visible
Wiring Methods:Romex
Type of Branch Wiring:Solid CopperStranded Aluminum
Ground Fault Circuit Interruptor (GFCI)Protection:
Partial
Arc Fault Circuit Interruptor (AFCI)Protection:
NO
Items
6.0 General Electrical System DescriptionComments: Inspected
6.1 General Electrical System ConditionComments: Inspected
6.2 Service Drop, Drip Loop, Splice and AttachmentComments: Inspected
6.3 Electric MeterComments: Inspected
6.4 Service Entrance ConductorsComments: Inspected
6.5 Service Panel ManufacturerComments: Inspected
6.6 Service Panel Exposure RatingComments: Inspected
6.7 Service Panel Cabinet, Ampacity, and CoverComments: Limitation
1. The electrical panel cover is not fully installed due to interference with an interfering wall and missingcover screws.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 35 of 63
6.8 Service Panel WiringComments: Limitation
6.9 Overcurrent Protection DevicesComments: Limitation
2. Access to the panel is limited as the panel cover cannot be fully removed.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 36 of 63
6.10 Service Grounding Electrode System & Service BondComments: Limitation
6.11 Exterior Electrical ReceptaclesComments: Inspected
6.12 Conventional Electrical Receptacles (interior)Comments: Inspected
6.13 GFCI/AFCI Electrical ReceptaclesComments: Inspected
6.14 SwitchesComments: Inspected
6.15 LightingComments: Inspected
6.16 Visible Branch WiringComments: Inspected
6.17 Smoke DetectorsComments: Inspected
6.18 Carbon Monoxide DetectorsComments: Inspected
1. Smoke detectors arerecommended on each floorof the home, in eachbedroom of the home,outside common bedroomareas. Install in accordancewith manufacturesrecommend guidance or hirea licensed contractor forproper installation. ReferenceWAC 212-10-040:http://apps.leg.wa.gov/wac/default.aspx?cite=212-10-040
2. The National Fire ProtectionAssociation (NFPA)recommend replacement ofsmoke detectors greater than10 years old.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 37 of 63
6.19 DoorbellComments: Inspected
The electrical system of the home was inspected and reported on with the above information. Outlets were not removed and the inspection was onlyvisual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates tothe comments in this inspection report.
I did not locate any installedcarbon monoxide detectors. Carbonmonoxide alarms must be locatedoutside of each separate sleepingarea, in the immediate vicinity of thebedroom and on each level of theresidence. Install in accordance withmanufactures recommend guidance orhire a licensed contractor for properinstallation. Reference WAC51-51-315: http://apps.leg.wa.gov/WAC/default.aspx?cite=51-51-0315
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 38 of 63
7. GarageInspection of the garage typically includes examination of the following:general structure; floor, wall and ceiling surfaces; operation of all accessibleconventional doors and door hardware; vehicle door condition and operation proper electrical condition including Ground Fault Circuit Interrupter(GFCI) protection; interior and exterior lighting; stairs and stairways proper firewall separation from living space; and proper floor drainage
Styles & Materials
Garage Vehicle Door Type:Double
Number of Vehicle Doors:2
Number of Automatic Openers:1
Vehicle Door Automatic Reverse:Failure to reverse
Auto-opener Manufacturer:LIFT-MASTER
Items
7.0 Vehicle DoorsComments: Inspected
7.1 Conventional DoorsComments: Inspected
The left garage vehicle door failed to reverse when a reasonable amount of resistance was applied. Iwould recommend service by a qualified garage door contractor.
The door frame to the back garage door has is damaged.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 39 of 63
7.2 FloorsComments: Inspected
7.3 WallsComments: Inspected
7.4 CeilingComments: Inspected
7.5 Stairs/Steps to Living SpaceComments: Inspected
7.6 Garage ElectricalComments: Inspected
(1) The garage exterior walls are in need of paint/stain.
(2) This section of siding on thesouth garage wall requires repair/replacement.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 40 of 63
7.7 AtticComments: Inspected
7.8 RoofComments: Inspected
7.9 OtherComments: Inspected
(1) Electrical outlets and junction boxes require cover-plates throughout the garage.
(2) This electrical splice shouldbe housed within an electrical junctionbox.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 41 of 63
(1) The entry breezeway on the north side of the garage has rot and water damage to trim and posts.Clearance to grade is inadequate. These conditions are further conducive to wood destroying organisms.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 42 of 63
7.10 Roof DrainageComments: Inspected
The structure of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.
(2) Two foundation cracks on the west garage foundation wall were noted. I would recommend furtherassessment by a structural engineer if conditions are noted to change.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 43 of 63
8. InteriorInspection of the home interior does not include testing for mold, radon, asbestos, lead paint, or other environmental hazards unless specificallyrequested as an ancillary inspection. Inspection of the home interior typically includes: interior wall, floor and ceiling coverings and surfaces; doorsand windows: condition, hardware, and operation; interior trim: baseboard, casing, molding, etc.; permanently-installed furniture, countertops,shelving, and cabinets; and ceiling and whole-house fans.
Styles & Materials
Walls and Ceilings:Drywall
Floor Covering Materials:CarpetModern Hardwood Flooring
Interior Doors:Wood Hollow Core
Window Material:Aluminum
Window Glazing:Double-pane
Window Operation:Sliding
Smoke/CO Detectors:Additional smoke detectors
recommendedAdditional carbon monoxide detector(s)
required
Items
8.0 FloorsComments: Inspected
8.1 WallsComments: Inspected
(1) I noted a deteriorating surface low on the exterior wall in the master bedroom closet. These areastested for high moisture content using my moisture meter. I would recommend further inspection by a qualifiedcontractor.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 44 of 63
(2) Baseboard trim is not fullyinstalled in the master bedroom.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 45 of 63
8.2 CeilingsComments: Inspected
(3) Staining on the walls of unknown origin was noted in the downstairs hot water-heater closet. Areastested demonstrated normal moisture levels using my moisture meter.
(4) I noted a deteriorating surface low on the exterior wall at the base of the stairs. This area tested forhigh moisture content using my moisture meter. I would recommend further inspection by a qualifiedcontractor.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 46 of 63
8.3 LightingComments: Inspected
The ceiling in the south downstairs bedroom has damage in several areas. I noted general unevenness,the ceiling coating may be compromised. i would recommend further investigation by a qualified contractor.
wave in the ceiling
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 47 of 63
8.4 DoorsComments: Inspected
8.5 Windows and SkylightsComments: Inspected
8.6 StairsComments: Inspected
This downstairs hall closet lightrequires installation, electrical wiresare exposed.
The glass on the masterbedroom closet door is cracked.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 48 of 63
8.7 Bathroom and Laundry VentilationComments: Inspected
The interior of the home was inspected and reported on with the above information. The inspection did not involve moving furniture and inspectingbehind furniture, area rugs or areas obstructed from view. Any repair items mentioned in this report should be considered before purchase. It isrecommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Graspable hand-rails are recommend for both flights of stairs.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 49 of 63
9. PlumbingInspection of the plumbing system typically includes (limited) operation and visual inspection of: water supply source (identification as public orprivate); sewage disposal system (identification as public or private); water supply/distribution pipes; drain, waste and vent (DWV) system; waterheater (type, condition and operation); gas system; and sump pump (confirmation of installation/operation).
Styles & Materials
Water Supply Source:Unknown
Main Water Supply Pipe:Not Visible
Main Water Supply Location:Not Located
Water Distribution Pipes:1/2-inch and 3/4-inch copperCross-linked Polyethylene (PEX)
Distribution Pipe Bonding:Not Visible
Sewage System Type:Unknown
Drain Waste and Vent Pipe Materials:Acrylonitrile butadiene styrene (ABS)Not Visible
Water Heater Manufacturer:------------------------
Date of Manufacture:2006
Water Heater Fuel Type:Electric
Water Heater Type:Tank (conventional)
Water Heater Tank Capacity:50 gallons
Water Heater Location:Basement
Washer Drain Size:2" Diameter
Gas Pipe Material:Not Visible
Type of Gas:Propane
Items
9.0 Exterior PlumbingComments: Inspected
9.1 Source of WaterComments: Not Inspected
9.2 Water Supply and DistributionComments: Limitation
9.3 Sewage and DWV SystemsComments: Limitation
9.4 Electric Water HeaterComments: Inspected
Generally not visible.
Generally not visible.
(1)1. Water heaters are required to be anchored or strapped to resist horizontal displacement due to
earthquake motion. Strappings shall be at points within the upper one-third and lower one-third of itsvertical dimensions. At the lower point, a distance of not less than four (4) inches (102 mm) shall bemaintained from the controls to the strapping.
2. A surge tank is recommended.3. A plumbed drip pan is recommended.4. Copper flex-lines are recommended.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 50 of 63
The plumbing in the home was inspected and reported on with the above information. Washing machine drain line for example cannot be checked forleaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed andbarely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waitingfor closing) rust or deposits within the pipes can further clog the piping system. Any repair items mentioned in this report should be considered beforepurchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.
The plumbing in the home was inspected and reported on with the above information. Washing machine drain line for example cannot be checked forleaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed andbarely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waitingfor closing) rust or deposits within the pipes can further clog the piping system. Any repair items mentioned in this report should be considered beforepurchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.
I would recommend repairs by a licensed plumbing contractor.
(2) Please note, this water heateris approximately 13 years old and hasreached the typical life-span of 12 - 18years. Consider a home warranty tomitigate repair/replacement costs.Budget for a replacement in the future.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 51 of 63
10. HeatingHeating system inspection will not be as comprehensive as that performed by a qualified heating, ventilating, and air-conditioning (HVAC) systemcontractor. For example: identification of cracked heat exchangers requires a contractor evaluation. Report comments are limited to identification ofcommon requirements and deficiencies. Observed indications that further evaluation is needed will result in referral to a qualified HVAC contractor.The general home inspection does not include any type of heating system warranty or guaranty. Inspection of heating systems is limited to basicevaluation based on visual examination and operation using normal controls. Report comments are limited to identification of common requirementsand deficiencies. Observed indications that further evaluation is needed will be referred to a qualified heating, ventilating, and air-conditioning (HVAC)contractor. Inspection of heating systems typically includes (limited) operation and visual inspection of: the heating appliance (confirmation ofadequate response to the call for heat); proper heating appliance location; proper or adequate heating system configuration; exterior cabinetcondition; fuel supply configuration and condition; combustion exhaust venting; heat distribution components; proper condensation discharge; andtemperature/pressure relief valve and discharge pipe (presence, condition, and configuration).
Styles & Materials
Heating System Type:Heat Pump Forced Air (also provides cool
air)Radiant Flooring Heat
Energy Source:Electric
Number of Heat Systems (excludingwood):
Two
Heating/Cooling Ducts:Insulated
Air Filter:Disposable
Air Filter Location:Behind removable panel at furnace
Heating System Brand:Lennox
Types of FIreplaces:Vented gas logsInsert
Operational Fireplaces:Two
Items
10.0 Presence of installed heat source in each roomComments: Inspected
10.1 Heat PumpComments: Inspected
Posted service records do not indicate recent servicing of your furnace. The air filter is dirty. I wouldrecommend servicing of your heating system by a licensed heating contractor and annually thereafter.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 52 of 63
10.2 Heaters, ElectricComments: Inspected
10.3 Fuel, Piping and SupportComments: Not Inspected
10.4 ThermostatComments: Inspected
10.5 FireplaceComments: Inspected
The propane tank appears to be empty.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 53 of 63
The heating system of this home was inspected and reported on with the above information. The inspection is not meant to be technically exhaustive.The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensedheat contractor would discover. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualifiedcontractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
The living room fireplace was notoperational when tested, the propanetank appears to be empty.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 54 of 63
11. BathroomsInspection of the bathrooms typically includes the following:walls, floors and ceiling; sink (basin, faucet, overflow); cabinets (exteriors, doors, drawers,undersink); toilet/bidet tub and shower (valves, showerhead, walls, enclosure); electrical (outlets, lighting); and room ventilation
Styles & Materials
Exhaust Fans:Fan with light
Items
11.0 FloorsComments: Inspected
11.1 WallsComments: Inspected
11.2 CeilingsComments: Inspected
11.3 DoorsComments: Inspected
11.4 WindowsComments: Inspected
11.5 Electrical Receptacles and SwitchesComments: Inspected
11.6 LightingComments: Inspected
11.7 VentilationComments: Inspected
11.8 CabinetsComments: Inspected
11.9 ToiletComments: Inspected
11.10 BathtubComments: Inspected
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 55 of 63
11.11 ShowerComments: Inspected
11.12 MirrorsComments: Inspected
11.13 SinkComments: Inspected
The master bathtub jets were not operational when tested.
A tile piece is missing at themaster shower.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 56 of 63
The bathrooms of the home was inspected and reported on with the above information. Any repair items mentioned in this report should beconsidered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to thecomments in this inspection report.
The upstairs bathroom sink iscracked.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 57 of 63
12. Kitchen and Built-in AppliancesInspection of kitchens typically includes (limited) operation and visual inspection of the following: wall, ceiling and floor; windows, skylights and doors;range/cooktop (basic functions, anti-tip); range hood (fan, lights, type); dishwasher; Cabinetry exterior and interior; door and drawer; Sink basincondition; supply valves; adequate trap configuration; functional water flow and drainage; disposal; Electrical switch operation; and outlet placement,grounding, and GFCI protection. Note: Appliances are operated at the discretion of the Inspector.
Styles & Materials
Cabinets:Solid Wood
Countertop Material:Granite
Range:Electric
Range/Oven Brand:LG
Range Hood:Vents to exteriorLights operableFan Operable
Range Hood Brand:Faber
Dishwasher:Present, Inspected
Dishwasher brand:Kitchen Aid
Dishwasher Anti-siphon method:No anti-siphon installed
Garbage Disposal brand:InSinkErator
Built-in Oven Brand:Whirlpool
Refrigerator:Inspected
Refridgerator Brand:Maytag
Items
12.0 FloorsComments: Inspected
12.1 WallsComments: Inspected
12.2 CeilingsComments: Inspected
12.3 DoorsComments: Inspected
12.4 WindowsComments: Inspected
12.5 Interior TrimComments: Inspected
12.6 Receptacles and SwitchesComments: Inspected
12.7 LightingComments: Inspected
12.8 CabinetsComments: Inspected
12.9 Kitchen AppliancesComments: Inspected
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 58 of 63
12.10 RangeComments: Inspected
12.11 Range HoodComments: Inspected
12.12 Garbage DisposalComments: Inspected
12.13 DishwasherComments: Inspected
12.14 CounterComments: Inspected
12.15 SinkComments: Inspected
Consider purchasing a homewarranty that covers your kitchen andother appliances to mitigate any near-term repair or replacement costs.
The dishwasher did not appear tohave an anti-siphon device installed inthe drain line. Anti-siphon devices areinstalled to prevent wastewater fromthe dishwasher from being siphonedback into the dishwasher andcontaminating its contents. I wouldrecommend an anti-siphon device beinstalled by a qualified technician.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 59 of 63
The Kitchen and built-in appliances of the home were inspected and reported on with the above information. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates tothe comments in this inspection report.
The garbage disposal is missingthe flexible insert at the sink drain.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 60 of 63
13. Laundry RoomIn addition to those items typically inspected as part of the interior, inspection of the laundry room includes examination of the following:dryerconnections and venting; room ventilation; and provision of proper clothes washer waste pipe.
Styles & Materials
Dryer Power:Electric
Dryer Vent:Smooth-bore metal
Dryer 240-volt electrical receptacle:Installed
Items
13.0 FloorsComments: Inspected
13.1 WallsComments: Inspected
13.2 CeilingsComments: Inspected
13.3 DoorsComments: Inspected
13.4 WindowsComments: Inspected
13.5 Receptacles, Switches, ConnectionsComments: Inspected
13.6 LightingComments: Inspected
13.7 CabinetsComments: Inspected
13.8 Dryer VentingComments: Inspected
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 61 of 63
13.9 Washer/DryerComments: Not Inspected
The laundry room of the home was inspected and reported on with the above information. Any repair items mentioned in this report should beconsidered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to thecomments in this inspection report.
I would recommend cleaning thedryer exhaust ducting.
NW WASHINGTON HOME INSPECTIONS LLC Franco
4147 Longfellow Pl NW Page 62 of 63