NETA PowerTest 2018 Spotlight Presentation
By Bret Hammonds
As the electrical power industry has grown in its understanding of the potential benefits
associated with partial discharge testing, it has been recognized for its value as a
diagnostic tool. The identification of partial discharge has now become a significant
component of system reliability programs and the associated planning for critical
electrical systems.
During this 15-minute presentation we will discuss considerations and challenges relating
to partial discharge testing and its ability to impact electrical insulating systems and their
associated dielectric qualities.
• Insulation Resistance
• Power Factor (Various)
• Voltage Withstand (High Potential Testing)
• Tan Delta (Cables, Rotating Apparatus…)
• Partial Discharge
Online
Offline
Field Testing of Electrical Insulation
Insulation Resistance
• Spot Tests
• Dielectric Absorption Ratio
• Polarization Index
• Step Voltage
1 kV, 5 kV, 10 kV, 10 kV, 15 kV
Field Testing of Electrical Insulation
Voltage Withstand (High Potential Testing)
• AC Power System Frequency
• VLF (0.1 Hz)
• Sinewave
• Cosine Rectangular Waveform
Tan Delta (Cables, Rotating Apparatus…)
• TDM – A mean (or avg.) Tan ẟ at Power System Frequency
• TDTS – Time Stability of Tan ẟ Values (Std. Dev.)• Tip-Up – Voltage Dependency
Partial Discharge• Online
• Offline
• Introduction of Damped AC (DAC)
Field Testing of Electrical Insulation
Voltage Withstand – High Potential
HistoricalMuch of this type of testing was performed using DC
Problem: Potential for leaving space charges
Solution: Use AC
Field Testing of Electrical Insulation
Voltage Withstand – High Potential
Problem: Size and Weight of 60 Hz power supply didn’t make it practical for
field testing – Right back where we started.
Solution: Test at Lower Frequency 0.1 Hz. (VLF)
Power System
Frequency
Very Low
Frequency
60 Hz /100pF @ 16 KVV2 x 2πƒC = 9,650 VA
0.1 Hz / 100pF @ 16 KVV2 x 2πƒC = 16 VA
The required 60 Hz power supply would have to be
~ 600 Times
Larger than the required VLF power supply
100 pF is used for the
purposes of this example, but
will vary in relation to the
capacitance of the item being
tested.
Field Testing of Electrical Insulation
Voltage Withstand – High Potential
Problem: VLF Sinewave Doesn’t Precisely Correlate to Insulation
Breakdown Values Using 60 Hz. AC
Solution: Cosine Rectangular Waveform. The transition between positive
and negative more closely resembles that of a 60 Hz sinewave.
0.1 Hz SinewaveẟV/ẟt = Approx. 5 seconds.(1/2 Cycle at 0.1 Hz)
60 Hz SinewaveẟV/ẟt = Approx. 8 msec(1/2 cycle at 60 Hz)
0.1 Hz Cosine RectangularẟV/ẟt = Approx. 2 to 6 msec(per IEEE 400.2 30 to 250 Hz.)
Field Testing of Electrical Insulation
Diagnostic Tests
Life Cycle
I always knew that I would get
old…I just never knew how
long it would take to get there.
Field Testing of Electrical Insulation
Reliability
Diagnostic Tests
Tangent Delta – an measure of electrical losses that can be used in trending the current
condition of electrical insulation and the speed at which it may be deteriorating.
Problem: What works best for Withstand Testing may not be appropriate for Tan ẟTests
Solution: Must use Sinusoidal Waveform to look at quadrature components of current
Evaluation Criteria
• TDTS (Std. Dev.) – Time Stability of Tan Delta (at least 6 measurements at equivalent intervals)
• DTD (TipUp) - higher voltage dependency as service age increases.(0.5 Uo to 1.5 Uo)
• TDM – Mean value of Tangent Delta at Rated Voltage
While Tan ẟ testing might be very helpful in making judgements regarding the age and condition of insulation, it may not be helpful in localizing the source of identified problems unless combined with other technologies.
Field Testing of Electrical Insulation
Offline PD
Partial Discharge - An electric discharge which only partially bridges the insulation between conductors.
Notes: 1. Partial discharges occur when the local electric-field intensity exceeds the dielectric strength of the dielectric involved, resulting in local ionization and breakdown. (IEEE 100 Complete Dictionary)
Field Testing of Electrical Insulation
PDMWT
WithstandPD
PD
VLF Sinewave VLF Cosine Rectangular
WithstandTan ẟ
Damped AC (DAC)
Waveform Applications
0.1 Hz
30 – 250 Hz
Online PD
PD Sensor Technologies
Acoustic
• Airborne (~40 kHz)
• Contact (20 kHz – 300 kHz)
Electromagnetic
• TEV – Transient Earth Voltage (3 MHz –
100 MHz)
• UHF – Ultra High Frequency (300 MHz
– 1.5 GHz)
• High Frequency Current Sensor (500
kHz – 50 MHz)
Field Testing of Electrical Insulation
Online
Advantages Disadvantages
• Does not require interruption of power• Non-Invasive…Testing is performed with test
items in services• Less Time Consuming • Costs Less to perform
• Limited to identifying PD at rated voltages,which could already be a problem
• Unable to control supply voltage and are therefore unable to determine PDIV/PDEV
Offline
Advantages Disadvantages
• Predictive and helpful Current Status and Planning of Maint./Replacment
• Able to determine PDIV/PDEV
• Requires De-Energizing Items to be tested• More costly to perform - Requires Additional
test Equipment• More time consuming
Advantages & Disadvantages of
PD Testing Types
Combination of test methods already discussed:
Monitored Withstand – A test in which a voltage of a predetermined
magnitude is applied for a predetermined time. During the test other
properties of the test object are monitored and these are used together
with the withstand results to determine it’s condition. IEEE Std. 400.2-2013
• VLF Withstand
• Tan ẟ (TD) – (TD, DTD, TDST) – (Sinusoidal Waveform)
• Partial Discharge (PD)
Monitored Withstand Test – (MWT)
Equipment Rental Options
EA Technology
UltraTEV Plus+ Partial
Discharge Detector
Partial Discharge VLF Hipot Tan Delta
PMDT PDetector
Handheld Partial
Discharge Detector
Omicron OMS 605
Portable Partial
Discharge (PD)
Monitoring System
High Voltage VLF-
65E 65kV VLF Tester
HV Diagnostics
HVA34 34kV VLF /
DC High Voltage
Test Instrument
HV Diagnostics
TD90-MC 90kV
Portable Tan Delta
Measurement System
HV Diagnostics
TD30 30kV Tan
Delta Bridge
For more information on these products see our extensive catalog
at protecequip.com/products