The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer Leif Nielsen DCSG Marketing

The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Embed Size (px)

Citation preview

Page 1: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

The Efficient DatacenterImproving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures

Nick Knupffer

Leif Nielsen

DCSG Marketing

Page 2: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Agenda

• Datacenters Today

• The High Ambient Temperature (HTA) Datacenter

• HTA Examples

• What Else Do You Need to Build a More Efficient Datacenter?

• Near-Future Technologies

• Summary

Page 3: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Today

– Datacenters are estimated to consume 1.5% of total world power and rising rapidly

– Equivalent to 50 power stations

– Generating 210 Million Metric tons of CO2

– Equivalent to 41 million cars

– Using ~300 Billion Litres of Water

– Equivalent to nearly 250,000 Olympic sized swimming pools

– Many datacenters still use CFC’s in their chillers

– $27 billion annual server energy cost

*See slide in backup for substantiation Photo: Samuel Mann

Page 4: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

2014

*See slide in backup for substantiation Photo: Samuel Mann

Page 5: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Why are datacenters cooled to 18-21°C?

• Because they always have been

• Non-homogeneous environment

• SLA’s and Warranties

• Legacy Systems Engineered to 21C

• Over-engineered hotspot avoidance

Photo: Drew Avery

Page 6: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif
Page 7: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

THE HIGH AMBIENT TEMPERATURE (HTA) DATACENTER

Page 8: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Definition of aHigh Ambient Temperature Datacenter

Noun~ Datacenter featuring a raised operating temperature designed to decrease cooling costs and increase power efficiency.

Page 9: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Power Usage Effectiveness (PUE)

PUE = Total Datacenter Power

Actual IT Power

Page 10: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

High Temperature Operation

50°C

Ultra High Temperature Datacenter

>40°C

Containers and modular design

35°C - 40°CHot/Cold aisle isolation, economizers

25–27°C to 30–35°C

Hot/Cold aisle isolation, economizers - retrofit

18–21°C to 25–27°C

Hot/Cold aisle airflow management

New / Modular Datacenters

Existing Datacenters

~2%

9%

12%

77%

New

*Intel Internal Estimate

Page 11: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Free Cooling

Page 12: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Leading adoption of datacenter efficiency standards

• Code of Conduct on Data Centres Energy Efficiency• Aligned with ASHRAE working towards DC operating at 40°C

by 2012

• 2011 Thermal Guidelines for Data Processing Environments

• Expanded the HTA recommended operating range

• Green Grid Metrics: Describing Datacenter Power Efficiency

• Aligned with ASHRAE

• Working towards enabling additional classes DC operating at 40°C by 2015

IDA (Singapore)CITR (China)

Page 13: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Industry Delivery to Usage Model RequirementsProof of Concept Solutions

Cloud On-Boarding:VM Interoperability

Data Center Efficiency:Carbon Footprint

Secure Cloud on-Boarding:Security Compliance

Unifed Fabric - Ethernet & FCoE: I/O Control

Trusted VM Deployment:Security Compliance

Cloud Interoperability:VM Interoperability

More at opendatacenteralliance.org See full reference architecture: http://www.intelcloudbuilders.com/docs/Intel%20Cloud%20Builders_Dell-JouleX_Sept2011.pdf

Page 14: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

The Effect of Increased PUE

PUE 3• Un-optimised datacenter

• Typical design used in emerging economies

PUE 1.25• Hot aisle containment

• Higher efficiency & reduced UPS

• Higher temperature operation

• Economizers instead of chillers

• Intel Node Manager

PUE 2• Retrofitted datacenter

• Hot and cold air aisle separation

• Blanking panels

IT Power

50%

UPS Power

9%

Cooling Power

40%

1%Lighting, Misc. Power

IT Power

81%

UPSPower

7%CoolingPower

10%

2%Lighting, Misc. Power

IT Power

33%

UPS Power

22%

Cooling Power

44%

1%Lighting, Misc. Power

*Intel Internal Data

Page 15: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Let’s Build a 15MW Datacenter

$0

$50,000,000

$100,000,000

$150,000,000

$200,000,000

$250,000,000

PUE 3 PUE 2 at 27C PUE 1.25 at 35C

Cost of Construction

31%Saving

29%Saving

*Intel Internal Data

Page 16: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Option 1 – More Servers

0

5000

10000

15000

20000

25000

30000

35000

40000

45000

50000

PUE 3 PUE 2 at 27C PUE 1.25 at 35C

Number of Servers

*Intel Internal Data

Based on a 15 MW Datacenter

21,739

36,487

47,385

Page 17: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Option 2 – Have your Cake and Eat It

$-

$1,000,000.00

$2,000,000.00

$3,000,000.00

$4,000,000.00

$5,000,000.00

$6,000,000.00

$7,000,000.00

$8,000,000.00

PUE 3 PUE 2 at 27C PUE 1.25 at 35C

Annual Cooling Costs

56%Saving

85%Saving

*Intel Internal Data

22k Servers 32k Servers 34k Servers

Greater compute, at lower annual cooling costs

Page 18: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

HTA EXAMPLES

Page 19: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Facebook - Retooled

• Facebook retooled its Santa Clara datacenter to 81°F / 27°C

• Annual energy bill fell by $229,000

• $294,761 energy rebate earned

http://www.datacenterknowledge.com/archives/2010/10/14/facebook-saves-big-by-retooling-its-cooling/

Page 20: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Intel IT New Mexico Proof of Concept

• 900 production servers • 100% air exchange at up to 92°F/33°C

– No humidity control

– Minimal air filtration

• 67% estimated power savings

• Estimated annual savings of $2.87 million in a 10MW DC

http://www.datacenterknowledge.com/archives/2008/09/18/intel-servers-do-fine-withttp://www.intel.com/content/dam/doc/technology-brief/data-center-efficiency-xeon-reducing-data-center-cost-with-air-economizer-brief.pdfh-outside-air/

Page 21: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Yahoo Computing Coop

• Shape of Things to Come? – The data center operates with no

chillers, and will require water for only a handful of days each year

– Estimated PUE 1.08

– 100% natural air flow results in an average of less than 1 percent of the buildings' total energy consumption used for cooling.

http://pressroom.yahoo.net/pr/ycorp/508872.aspx

Page 22: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Further HTA Examples

• Google: Raise Your Data Center Temperature..80°F 2

• Sun – 4% savings in chiller energy costs for 1°C in upward change 2

• Microsoft saved 250K/yr energy costs by raising 2-4°c 2

1) http://www.datacenterknowledge.com/archives/2010/10/14/facebook-saves-big-by-retooling-its-cooling/2) http://www.datacenterknowledge.com/archives/2008/10/14/google-raise-your-data-center-temperature3) http://www.datacenterknowledge.com/archives/2010/04/26/yahoo-computing-coop-the-shape-of-things-to-come/

Page 23: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

WHAT ELSE DO YOU NEED TO BUILD A MORE EFFICIENT DATACENTER?

Choice of Intel products for high temperature operation Platform design guide to build HTA capable systems Data center prescriptive guide to achieve optimal set point

Page 24: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Grid

Distribution

Facility

Rack and Row Level Infrastructure

Server / Storage

Fans and CoolingMotherboard/VRs

PackageDie

Gates

Intel – Gate to GridAchieve efficiency by increasing users, compute and performance

32nm Silicon Technology

Package C1E/C6 Technology

ME-enabled BMC-less design VR12.1 Specs.

Customized Fan Control

Intel On Demand Redundant Power TechnologyIntel Solid-State Drives

Intel® Intelligent Power Node Manager and Data Center Manager

Intel Open Energy Initiative

Optimized Thermal Solutions

Intel Smart Grid embedded TechnologyIn

tel X

eon

base

d Pl

atfo

rmD

atac

ente

rM

anag

erIn

tel L

abs

Inno

vatio

n

Page 25: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

2003 2005 2007 2009 201190 nm 65 nm 45 nm 32 nm 22 nm

STRAINED SILICON

HIGH-k METAL GATE

TRI-GATE

22nmA Revolutionary

Leap In Process Technology

37%Performance Gain at Low

Voltage*

>50%Active Power Reduction at

Constant Performance*

Process Technology Leadership

The Foundation For All Computing Source: Intel*Compared to Intel 32nm Technology

Invented SiGe

Strained Silicon

2nd Gen.SiGe

Strained Silicon

2nd Gen. Gate-Last

High-k Metal Gate

Invented Gate-Last

High-kMetal Gate

First to Implement Tri-Gate

Page 26: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Platform Innovation

Optimal Performance & Power Efficiency

• Up to 25% more performance/watt with Intel Xeon 5600 series based processors over prior generation processor1

Platform of Choice For High Ambient Operation• Broad offering – 130W, 95W, 80W , 60 W, 45W & 20W• Well defined, robust reliability verification• Processor and memory power/thermal management• Chipset, with Intel Node Manager for power capping• Explore SSD ‘s for higher temperature

Choice of Best In Class products for high temperature operation

Intel Node Manager

Intel Datacenter Manager

OpenIPMI

11 Source: Internal Intel estimates comparing OLTP Warehouse performance of Xeon® X7560 vs. Westmere-EX (top bin) systems with same memory capacity and system configurations. See Relative Top Bin Performance projections for more system configurations. Excludes possible additional system power savings with Westmere-EX due to power gating, LV DIMM support and standard or LV memory buffers (Millbrook2) usage. See Westmere-EX power management summary table for more details.

Page 27: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Intel Platform Guide

HTA

Board/Chassis• 2 U optimal • Spread core • Thermal features

enabled

Design• Cu Heatsink• Fan speed control

algorithm• Power

management features

Components• 80 – 95 W CPU’s • SSD• Memory -Larger

DIMM

• Platform Design Guide - Recommendations• Spread core layout - ~10%1 decrease in power

consumption • Processors with 80 – 95 W could provide

~10%1 in power reduction• Efficient Heat sink - Copper heatsink could

result in 7%1 lower system power

• Datacenter Optimization Guide• Predictive modeling to identify optimal set

point• Recommend - 30 – 35 C for existing

datacenters and > 35 C for modular/new datacenters

1

• Note - Intel Internal estimate, based on HTA optimized system using 60W Romley CPU vs 95W Romley CPU and assume 70% SpecPower workload and 24/7/365 ambient temperature in New Mexico

Page 28: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Example: Thermal Shadowing

• Thermal Shadowing is one example of how to optimize for HTA

• Cool air is heated up by passing fewer heat sources, reducing processor temperatures

• Using this and other techniques, such as copper heatsinks and the use of SSD’s; Intel-based HTA-optimized systems operating at 35C could save up to 10% power consumption*

CPU

CPU

CPUCPU

*Source: Intel Internal estimate, based on HTA optimized system using 60W Romley CPU vs 95W Romley CPU and assume 70% SpecPower workload and 24/7/365 ambient temperature in New Mexico DC

Page 29: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Intel Intelligent Power Node Manager and Data Center Manager

• Limit total RACK power draw• More productivity per rack

Limit aggregated ROWpower draw

• Report system level energy use• Limit individual SERVER power consumption

1

2

3

Aggregated, Policy-Based Power Management for the Data Center

Page 30: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Node Manager & Data Center Manager Results

Power and Thermal Monitoring

Increased Rack Density

Workload Power Optimization

Business Continuity

Replace IP power strips and serial concentrators, saving ~$400 per rack

Up to 40% more servers and performance per rack

Up to 30% power optimization without performance impact

Continued compute availability through power or thermal event

*Other brands and names may be claimed as the property of others.

Page 31: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Solution Choices For Directed Power Management

Growing Choices For Solutions Using Intel® Directed Power Management

DCM Enabled ConsolesNode Manager Servers

Data Center Solutions

PowerEdge C

*Other brands and names may be claimed as the property of others.

List represents OEMs, ODMs and ISVs that have supported Node Manager and/or Data Center Manager in Intel® Xeon® 5500, E5 and E7 generation servers and console products. Contact the OEM, ODM or ISV for up to date information on products that are supported.

Page 32: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

NEAR FUTURE TECHNOLOGIES

Page 33: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Power & Thermal Aware Scheduling (PTAS)

• Builds upon Intel Node Manager and Data Center Manager

• Lower operational costs ~20% 1

• Recovery up to 50% of unused cooling capacity1

• Reduce DC monitoring instrumentation costs

Integrate IT and Facilities Management

Maximize Operational Efficiency

1 Source: http://www.computerworld.com/s/article/9195918/Data_center_infrastructure_management_tools_eliminate_inefficiencies?source=rss_datacenter

Technology for the Automated Cloud

Page 34: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Intel® Battery Backup Solution

•Reduce UPS related capital expenditure costs ~ 5X1

•Recover UPS related power efficiency loss – ~30-40%2

•Easy deployment and time to market solution

•Integrate with Intel Node Manager to Increase battery life or reduce the size

Reduce Data Center Capital Costs

1Intel internal estimate2 APC whitepaper # 108

Page 35: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

What if -

The world used HTA for a 5°C Datacenter Rise?

Page 36: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

World HTA 5°C Datacenter Rise

• $2.16 Billion in immediate annual power savings

• 8% Decrease in WW datacenter power consumption

• 24.3 Billion KWh saved– More than month of total energy consumption by Spain,

South Africa, Australia or Taiwan

• Save ~49 Billion liters of water

• Equivalent to 1.7 Million metric tons of CO2

– Same as carbon sequestered by 43 Million tree seedlings grown for 10 years

*See slide in backup for substantiation

Page 37: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Call to Action

• Take advantage of the fine grained power control Intel’s Power Node Manger and Data Center Manager provide

• Kick the cooling habit– Save space and money by reducing or eliminating chiller

and UPS infrastructure

– Increase the compute capacity of your datacenter by adding more Intel Xeon-based servers

– Lower environmental impact

• Intel Xeon processors provide industry leading power and thermal efficiency

Page 38: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Further Reading

• Intel IT Datacenter Strategy http://www.intel.com/itcenter/tool/DCstrategy/index.htm

• Reducing Data Center Cost with an Air Economizer http://www.intel.com/content/www/us/en/data-center-efficiency/data-center-efficiency-xeon-reducing-data-center-cost-with-air-economizer-brief.html

• Intel IT Data Center Solutions: Strategies to Improve Efficiency http://www.intel.com/content/www/us/en/data-center-efficiency/intel-it-data-center-efficiency-strategies-to-improve-efficiency-paper.html

• IT@Intel: Data Center Solutions http://www.intel.com/content/www/us/en/it-management/intel-it/intel-it-data-center-solutions.html

• The Effect of Data Center Temperature on Energy Efficiency http://www.eco-info.org/IMG/pdf/Michael_K_Patterson_-_The_effect_of_Data_Center_Temperature_on_Energy_Efficiency.pdf

Page 39: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

BACKUP

Page 40: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Environmental Benefits Claims Details

• Today

– Datacenters consume 1.5% of total world power and rising rapidly

– Equivalent to 50 power stations

– Generating 210 Million Metric tons of CO2

– Equivalent to 41 million cars

– Using ~300 Billion Litres of Water

– Equivalent to nearly 250,000 Olympic sized swimming pools

– $27 billion annual server energy cost

• $2.16 Billion in immediate annual power savings

• 5C Worldwide Raise – What would it mean?

– 8% Decrease in WW datacenter power consumption

– 24.3 Billion KWh saved

– More than month of total energy consumption by Spain, South Africa, Australia or Taiwan.

– Equivalent to 1.7 Million metric tons of CO2

– Same as carbon sequestered by 43 Million tree seedlings grown for 10 years

•Total World Power Generation: –http://www.iea.org/stats/electricitydata.asp?COUNTRY_CODE=29 20,260,838,000,000 kWh Total World Electricity Generation /1.5= 303,912,570,000 kWh is total power used by Datacenters

– CO2 Calculator http://www.epa.gov/cleanenergy/energy-resources/calculator.html

– 1.5% of World Power – Koomey 2011 http://www.analyticspress.com/datacenters.html•Water:

–http://www.hp.com/hpinfo/newsroom/press_kits/2011/HPFortCollins/Water_Efficiency_Paper.pdf–1KWh of DC uses ~2L of water = 303,912,570,000 x 2 = 607,825,140,000 L of water used by WW DC’s. –1 Olympic Swimming pool uses 2,5M Litres.

•$27 billion annual server energy cost (IDC 2009)•Data will grow 44 times to 35ZB between 2009 – 2020…IDC 2011•X2 Claim

–Assumption based on linear extrapolation of data in EPA Report to Congress on Server and Data Center Energy Efficiency; August 2, 2007–Total power consumed by datacenters could be ..2-3% of all electricity generated by 2014–Source: Extrapolation of EPA Report to Congress on Server and Data Center Energy Efficiency; August 2, 2007 http://www.energystar.gov/ia/partners/prod_development/downloads/EPA_Datacenter_Report_Congress_Final1.pdf–2011 - ~110 B Kwh/year= 1% decrease = 1.1 Bkwh/hr

•5C Worldwide Raise–http://www.iea.org/stats/electricitydata.asp?COUNTRY_CODE=29 20,260,838,000,000 kWh Total World Electricity Generation in 2008 /1.5= 303,912,570,000 kWh is total power used by Datacenters

–1.5% of World Power – Koomey 2011 http://www.analyticspress.com/datacenters.html–20% decrease in cooling energy costs. (4% savings for 1 0c increase in temp) -

http://www.datacenterknowledge.com/archives/2008/10/14/google-raise-your-data-center-temperature/

– Carbon Calculator: http://www.epa.gov/cleanenergy/energy-resources/calculator.html#results

– Electricity Generation by country from CIA World Factbookhttp://en.wikipedia.org/wiki/List_of_countries_by_electricity_production

– Water: http://www.hp.com/hpinfo/newsroom/press_kits/2011/HPFortCollins/Water_Efficiency_Paper.pdf 1KWh of DC uses ~2L of water

Page 41: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

Node Manager Claims Back Up

Extreme Efficiency: Power Management•Rack density statement based on Baidu proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-4212.•Power Optimization claims based on BMW proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-4040

Increasing Rack Density Proof Points•Baidu statement based on proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-4212.•Oracle statement based on proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-3977

Increasing Rack Density Proof Points•Baidu statement based on proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-4212.•BMW statement based on proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-4040•Oracle statement based on proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-3977•Intel IT and FSI results based on Intel internal testing of Intel Xeon Processor 5500 series whiteboxes in an NDA environment.

Increasing Rack Density Model Baidu Proof PointBaidu statement based on proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-4212.

Power Optimization Model Oracle Proof PointOracle statement based on proof of concept results documented in Intel legally approved whitepaper posted at http://communities.intel.com/docs/DOC-3977

Page 42: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif
Page 43: The Efficient Datacenter - Insyde Software · The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient Temperatures Nick Knupffer. Leif

AUTOMATEDIT can focus more on innovation

and less on management

FEDERATEDShare data securely across public and private clouds

CLIENT AWAREOptimizing services based on device

capability

Intel’s Cloud2015 Vision