10 th International Conference on Short and Medium Span Bridges Quebec City, Quebec, Canada, July 31 – August 3, 2018 EXPERIMENTAL STUDY ON REINFORCED CONCRETE BEAMS AFTER FIRE REPAIRED BY BOLTED SIDE-PLATING Li, Ling-zhi 1,2 , Bai, Yang 1 , Su, Lei 1 , Yu, Jiang-tao 1 , Lu, Zhoudao 1 1 College of Civil Engineering, Tongji University, 1239 Siping Road, Shanghai 200092, China 2 [email protected] Abstract: The structural performance of reinforced concrete (RC) beams degrades seriously after exposed to fire, thus the retrofitting techniques for fire-damaged RC beams are of great importance. The bolted-side plating (BSP) is an innovative technique where the steel plates are attached to the beams’ side faces using anchor bolts. It can enhance RC beams in both tensile and compressive reinforcement thus immune from reduction of ductility and the peeling failure on the plate-RC interface. Considering this background, the bending and shear tests of post-fire beams strengthened by BSP were conducted. The influence of the bolt spacing, the arrangement of steel-angle stiffeners, and the plate depth and thickness on the strength, stiffness and ductility was investigated. The results indicated that the bearing capacity and the stiffness of all the fire-damaged specimens were significantly improved by the BSP technique, but the variation of ductility was dependent on the arrangement of strengthening. The local buckling can be restrained effectively by adding stiffeners along the compressive edge. The digital image correlation method can be used to investigate the development of displacement and strain fields. 1 INTRODUCTION Reinforced concrete (RC) beams after fire might fail to achieve the prescribed performance due to the degradation of material properties caused by elevated temperature (El-Hawary et al. 1996; Kumar et al. 2003; Lee et al. 2008), thus the recovery and retrofitting of the fire-damaged RC beams is of great importance for the subsequent serviceability and safety of RC buildings. 360-1

The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

10th International Conference on Short and Medium Span Bridges

Quebec City, Quebec, Canada, July 31 – August 3, 2018

EXPERIMENTAL STUDY ON REINFORCED CONCRETE BEAMS AFTER FIRE REPAIRED BY BOLTED SIDE-PLATING

Li, Ling-zhi 1,2, Bai, Yang 1, Su, Lei 1, Yu, Jiang-tao 1, Lu, Zhoudao1

1 College of Civil Engineering, Tongji University, 1239 Siping Road, Shanghai 200092, China2 [email protected]

Abstract: The structural performance of reinforced concrete (RC) beams degrades seriously after exposed to fire, thus the retrofitting techniques for fire-damaged RC beams are of great importance. The bolted-side plating (BSP) is an innovative technique where the steel plates are attached to the beams’ side faces using anchor bolts. It can enhance RC beams in both tensile and compressive reinforcement thus immune from reduction of ductility and the peeling failure on the plate-RC interface. Considering this background, the bending and shear tests of post-fire beams strengthened by BSP were conducted. The influence of the bolt spacing, the arrangement of steel-angle stiffeners, and the plate depth and thickness on the strength, stiffness and ductility was investigated. The results indicated that the bearing capacity and the stiffness of all the fire-damaged specimens were significantly improved by the BSP technique, but the variation of ductility was dependent on the arrangement of strengthening. The local buckling can be restrained effectively by adding stiffeners along the compressive edge. The digital image correlation method can be used to investigate the development of displacement and strain fields.

1 INTRODUCTION

Reinforced concrete (RC) beams after fire might fail to achieve the prescribed performance due to the degradation of material properties caused by elevated temperature (El-Hawary

et al. 1996; Kumar et al. 2003; Lee et al. 2008), thus the recovery and retrofitting of the fire-damaged RC beams is of great importance for the subsequent serviceability and safety of

RC buildings.

Numerous strengthening techniques were proposed by researchers to retrofit RC beams (Triantafillou 1998; Li et al. 2013; Yang et al. 2018; Yu et al. 2018). Among which the bolted-

side plating (BSP), i.e. anchoring steel plates to the side faces of RC beams with anchor bolts (Li et al. 2017; Su et al. 2014), was an innovative method that can avoid the brittle

debonding and over-reinforced failure, if compared with the method of gluing carbon fiber reinforced polymers (CFRPs) to the tensile soffit (Deniaud et al. 2001; Park et al. 2003; Alam

et al. 2009; Zhu et al. 2017). It also has the advantages such as easy for construction and less space occupancy if compared to the conventional method of increasing cross-section

by newly cast concrete and cementitious composite (Wei et al. 2018; Yu et al. 2018a, 2018b).

Since the BSP technique has been accepted worldwide, studies on BSP beams have drawn comprehensive attention. Barnes et al. (2001) compared the retrofitting effect of two

methods of plate attachment, namely adhesive bonding and bolting. Oehlers, Ahmed, Nguyen and Smith (Ahmed et al. 2000; Nguyen et al. 2001; Oehlers et al. 1997a, 1997b; Smith

et al. 1999) conducted comprehensive experimental and theoretical studies to investigate the strengthening effect, partial-interaction and local buckling of BSP beams. Su, Zhu, Siu,

Lo and Li (Su et al. 2008, 2013; Zhu et al. 2010; Siu et al. 2011; Lo et al. 2014; Li et al. 2016) devoted themselves to optimizing the strengthening strategy of BSP beams, restraining

the local buckling of steel plates, and simplifying the design procedure. Kolsek et al. (2013) proposed a theoretical model to analyze the stress-strain state of linear-elastic BSP beams

cracked in flexure. Li, Jiang and Xu (Li et al. 2016; Jiang et al. 2017; Xu et al. 2017) conducted experimental and numerical studies on BSP beams and proposed a simplified design

method that can take the local buckling into account.

Although systematic researches on the BSP technique have been carried out, most of them were related to its implementation under room temperature, those focusing on fire-damage

360-1

Page 2: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

Anchor bolt

250

275

100

Steel plate 2600×100×4

250

75

300×7=2100Steel plate 2600×100×4

75

250

300

200

100×25=2500

300×7=2100

75

250

Steel plate 2600×100×4

250

300

300×7=2100

7575

250

200

Steel plate 2600×100×4

200

250

75

300×7=2100 250

75

300

Steel plate 2600×100×6

300×7=2100

200

75

250

300

75

250

P

T1

T2

150 1502600

900500900

350

L3L2 L1

P

P

T1

T2

150 1502600

900500900

350

L3L2 L1

P

2600

P P 350

(a) Reinforcement(b) FP40B03

(c) FP43B13 (d) FP43B33

(e) FP43B33A (f) FP63B33

RC beams have yet been sufficient. Therefore, this paper will report an experimental study, in which RC beams were exposed to fire and retrofitted with the BSP technique, and then

their flexural and shear performance was investigated.

2 EXPERIMENTAL PROGRAM

2.1 Specimen details

A total of eleven RC beams were fabricated as listed in Test set-up and instrumentation. The former six beams were used to investigate the flexural strengthening effect of the BSP

technique for fire-damaged RC beams as shown in Figure 1, the cross section is 200 mm × 350 mm, the stirrup is D10–100, the compressive and tensile reinforcements are 2D12 and

2D20, respectively. The latter six were employed to investigate the shear strengthening effect as shown in Figure 2, the cross section is 200 mm × 400 mm, the stirrup is D6–200, the

compressive and tensile reinforcements are 2D22 and 4D22, respectively.. All the RC beams was first exposed to fire, and then two of the fire-damaged RC beams, namely FCTRL

and SCTRL, remained unstrengthened. The rest were retrofitted with two steel plates anchored to their side faces, whose main control parameters were the plate depth, plate

thickness, bolt spacing and stiffeners at the compressive edge to limit buckling, and there strengthening details can be found in Figure 1 and Figure 2.

2.2 Test set-up and instrumentation

The RC beams were first exposed to fire in accordance with the international standard ISO834 temperature curve for 2 hours, and a constant load was imposed on the specimens to

simulate the service load, as shown in Figure 3. Thermocouples were installed in the beams to measure the temperature under fire.

For the flexural test, the clear span between the two roller supports was 2300 mm, and the shear span between the support and the nearest loading point was 900 mm, as illustrated

in Figure 1(a). While for the shear test, the clear span was 2400 mm, and the shear span was 495 mm, thus the shear span-to-depth ratio was 1.5, as illustrated in Figure 2(a). The

digital image correlation (DIC) method was employed to record the deformation development of both the RC beam and the steel plate. Two layers of white and black random paint

spots were sprayed onto the specimen surfaces, whose shapes before and after deformation were captured by digital single lens reflex cameras.

Table 1: Strengthening Parameters of specimens

Specimen Plate thickness (mm)

Plate depth (mm)

Rows of bolts

Upper bolt spacing (mm)

Lower bolt spacing (mm)

Steel angle (mm)

1 FCTRL — — –– — — —2 FP41B03 4 100 1 — 300 —3 FP43B13 4 300 2 100 300 —4 FP43B33 4 300 2 300 300 —5 FP43B33A 4 300 2 300 300 L63×40×56 FP63B33 6 300 2 300 300 —7 SCTRL –– –– –– –– –– ––8 SP42B22 4 200 2 200 200 ––9 SP42B11 4 200 3 100 100 ––

10 SP43B22 4 300 2 200 200 ––11 SP43B11 4 300 3 100 100 ––

360-2

Page 3: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

P

T1

T2

150 1502600

900500900

350

L3L2 L1

P

P

T1

T2

150 1502600

900500900

350

L3L2 L1

P

2600

P P

350

(a) Reinforcement(b) SP42B11

(e) SP43B11

  

   

(c) SP43B22 (d) SP42B22

4900

2600 2600Furnace

Reaction frame

Hydraulic jack

Specimen

1700

Figure 1: Details of specimens for flexural testing

Figure 2: Details of specimens for shear testing

Figure 3: General view of specimens under fire exposure

3 RESULT DISCUSSION

3.1 Thermal response

The temperature development of the RC beams under fire was shown in Figure 4(a), where d represents the distance of the thermocouple from the beam’s bottom surface. The

temperature of the furnace and the international standard ISO834 curve were also plotted for comparison. It is evident that the furnace temperature was slightly lower than the ISO834

curve, and the temperature of concrete surface was even lower. The temperature of concrete decreased with its embedment depth. In addition, the temperature of concrete inside the

beam maintained at 100 °C for about 50 min, due to the evaporation of moisture in concrete. It is also observed that the maximum temperature of inside concrete appeared 50

minutes after flameout, hence the fire failure might appear during the cooling phase after the flameout.

The development of the mid-span deflection of the RC beams was shown in Figure 4(b), and the variation of external load was plotted for comparison. It is shown that when the

external load was imposed on the RC beams, a deflection of about 4 mm occurred instantly. After the fire ignition, the beams’ deflection increased steadily with the temperature. When

the external load was unloaded at the flameout, the deflection decreased 4 mm instantly, which means the initial deflection caused by external load was recovered. Thereafter, the

deflection caused by fire was gradually recovered, and the residue deformation after 24 hours was estimated to be less than 5 mm, thus its influence on the subsequent strengthening

and loading test could be ignored.

360-3

Page 4: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

(a) Temperature–time curves of RC beams (b) Time‒deflection curves of RC beams

Figure 4: Development of temperature and deflection

3.2 Structural response of flexural test

3.2.1 Failure mode and flexural capacity

Figure 5 shows that the failure modes of all the specimens under flexural testing, which were similar and bending failure occurred. The first vertical flexural crack appeared in the mid-

span firstly, then new flexural cracks appeared one after another with the increase of load. When the load reached a certain value, no new vertical cracks appeared, but the cracks

gradually expanded and widened. Eventually, concrete in the compression zone of the mid-span crushed, and the compression rebars yielded. Then, the beams continued to be

loaded using displacement-controlled loading. When the load dropped to 0.85 Pu, the test was terminated. Due to the restriction of steel plates to concrete, the BSP beams showed

better deformability than the unstrengthened beam FCTRL during the test.

(a) FCTRL

(b) FP41B03

(c) FP43B13

(d) FP43B33

(e) FP43B33A

(f) FP63B33

Figure 5: Failure modes of specimens

It is shown from Table 2 that the specimens can be sorted in order of peak load (Pu) as following: FCTRL < FP41B03 < FP43B33 < FP63B33 < FP43B13 < FP43B33A. After

strengthened, the loading capacity of the fire-damaged beams was significantly improved. Compared with other strengthened beams, the peak load of FP41B03 was the minimum,

indicating that anchoring steel plates to the lower part of beam’s side faces will lead to over-reinforcement failure. Compared with FP43B33, the peak loads of FP63B33, FP43B13 and

FP43B33A were all much greater, which shows that the reinforcement effect of BSP beams could be improved by increasing the thickness of steel plates, the number of anchor bolts,

or adding angle stiffeners. Compared with FP43B13 and FP43B33A, the increase rate of FP63B33 is the lowest, which means increasing plate thickness without corresponding

increase in anchor bolts will lead to a reduction of cooperation degree between steel plate and concrete thus an unsatisfactory strengthening effect.

Table 2: Flexural capacity, stiffness and ductility of specimens

SpecimenFlexural capacity Stiffness Ductility

Pu (kN) Change (%) Ke (kN/mm) Change (%) Ut (kN.mm) Change (%)

360-4

Page 5: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

1 FCTRL 236.0 — 19.7 — 33797.0 —2 FP41B03 327.6 39 % 24.7 25 % 26422.4 −22 %3 FP43B13 422.2 79 % 31.0 57 % 66779.5   98 %4 FP43B33 384.4 63 % 29.3 49 % 32388.0   −4 %5 FP43B33A 431.3 83 % 32.7 66 % 51414.2   52 %6 FP63B33 418.6 77 % 35.5 80 % 31202.4   −8 %

Figure 6: Comparison of load–vertical displacement curves

The load-deflection curves in the mid-span of the beams are plotted in Figure 6, where the curves are generally divided into three phases: the straight ascending line, the ascending

curve, and the descending curve. That is, all the specimens experienced the initial elastic stage, the elasto-plastic stage after cracking and the post failure stage beyond the peak

load. The trend of the load-deflection curve was in accord with the characteristics of flexible failure.

3.2.2 Stiffness and ductility

It can be seen from Table 2 that the specimens can be sorted by the stiffness (Ke) as following: FCTRL < FP41B03 < FP43B33 <FP43B13 < FP43B33A < FP63B33. This indicates

that the stiffness of the fire-damaged beams can be effectively increased by the BSP technique and increasing the plate thickness resulted in a significant improvement, while

anchoring narrow steel plates in the tension zones only provides a negligible improvement.

It can also be seen from Table 2 that the specimens can be sorted by the ductility (Ut) as following: FP41B03 < FP63B33 ≈ FP43B33 ≈ FCTRL < FP43B33A < FP43B13. The ductility

of FP41B03 even decreased compared with FCTRL, which indicates that anchoring steel plates in the tension zones will lead to over-reinforcement shortcoming and the ductility will

decrease. Compared with FP43B33, the Ut of FP63B33 slightly decreased, while the Ut of FP43B33A and FP43B13 significantly increased. This shows that increasing plate thickness

cannot increase ductility unless more bolts are added concurrently, while adding steel-angle stiffeners can effectively increase the ductility. Compared with FP43B33A, the Ut of

FP43B13 is larger, which means adding more anchor bolts not only limits the buckling of steel plates but also increases the overall degree of cooperation between steel plates and

concrete.

3.3 Structural response of shear test

3.3.1 Failure mode and shear capacity

The failure modes of the specimens for shear test are shown in Figure 7. For the unstrengthened specimen SCTRL, the flexural cracks occurred first at the mid span of the beam,

then the first diagonal crack occurred, and after that more diagonal cracks appeared and the failure of the beam was triggered by the formation of a main diagonal crack as shown in

Figure 7(a). Thus, the beam SCTRL reached its shear capacity.

(a) SCTRL(d) SP43B22

360-5

Page 6: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

(b) SP42B22

(c) SP42B11

(e) SP43B11

Figure 7: Failure modes of specimens

The shear capacities of all the specimens are listed in The shear capacities of all the specimens are listed in The shear capacities of all the specimens are listed in Table 3. After being

strengthened, the occurrence of cracks in SP42B22 and SP42B11 was delayed and the shear capacity was significantly increased. This is because with the development of diagonal

cracks and mid-span displacement, the bolted steel plates will work together with the original fire-damaged RC beam gradually to resist external load. The main diagonal crack in

SP42B11 was obvious, the steel plates deformed and contributed to the resistant capacity significantly. However, because the bolt spacing was too large in SP42B22, the end

anchorage of the bolted steel plates was weak, the failure was induced by the crush of the concrete near the left support, thus the strengthening effect was not desirable.. After being

strengthened, the occurrence of cracks in SP42B22 and SP42B11 was delayed and the shear capacity was significantly increased. This is because with the development of diagonal

cracks and mid-span displacement, the bolted steel plates will work together with the original fire-damaged RC beam gradually to resist external load. The main diagonal crack in

SP42B11 was obvious, the steel plates deformed and contributed to the resistant capacity significantly. However, because the bolt spacing was too large in SP42B22, the end

anchorage of the bolted steel plates was weak, the failure was induced by the crush of the concrete near the left support, thus the strengthening effect was not desirable.. After being

strengthened, the occurrence of cracks in SP42B22 and SP42B11 was delayed and the shear capacity was significantly increased. This is because with the development of diagonal

cracks and mid-span displacement, the bolted steel plates will work together with the original fire-damaged RC beam gradually to resist external load. The main diagonal crack in

SP42B11 was obvious, the steel plates deformed and contributed to the resistant capacity significantly. However, because the bolt spacing was too large in SP42B22, the end

anchorage of the bolted steel plates was weak, the failure was induced by the crush of the concrete near the left support, thus the strengthening effect was not desirable.

For the depth of the bolted steel plates was 300 mm in specimens SP43B22 and SP43B11, the side faces of the RC beams were covered thus the occurrence of the flexural and

shear cracking was not observed. The shear capacity of SP43B22 was only slightly greater than that of SP42B22, and even much less than SP42B11, which was caused by the poor

end anchorage of the bolted steel plates due to the large bolt spacing (i.e. 200  mm). On the other hand, the enhancement of SP43B11 was significant due to the great plate depth and

the small bolt spacing. The failure modes of specimens SP43B22 and SP43B11 were illustrated in Figure 7(d) & (e).

Table 3: Shear capacity, stiffness and ductility of specimens

Specimen Shear capacity Stiffness DuctilityPu (kN) Change (%) Ke (kN/mm) Change (%) Ut (kN.mm) Change (%)

1 SCTRL 580 -- 79.4 -- 2580 --2 SP42B22 800 38% 90.2 14% 5812 125%3 SP42B11 930 60% 88.6 12% 18927 634%4 SP43B22 840 45% 82.1 3% 15359 495%5 SP43B11 1030 78% 113.5 43% 20458 693%

3.3.2 Stiffness and ductility

The load‒deflection curves of all the specimens are shown in Figure 8 and the parameters Ke and Ut were compared in The shear capacities of all the specimens are listed in The

shear capacities of all the specimens are listed in Table 3. After being strengthened, the occurrence of cracks in SP42B22 and SP42B11 was delayed and the shear capacity was

significantly increased. This is because with the development of diagonal cracks and mid-span displacement, the bolted steel plates will work together with the original fire-damaged

RC beam gradually to resist external load. The main diagonal crack in SP42B11 was obvious, the steel plates deformed and contributed to the resistant capacity significantly.

However, because the bolt spacing was too large in SP42B22, the end anchorage of the bolted steel plates was weak, the failure was induced by the crush of the concrete near the

left support, thus the strengthening effect was not desirable.. After being strengthened, the occurrence of cracks in SP42B22 and SP42B11 was delayed and the shear capacity was

significantly increased. This is because with the development of diagonal cracks and mid-span displacement, the bolted steel plates will work together with the original fire-damaged

RC beam gradually to resist external load. The main diagonal crack in SP42B11 was obvious, the steel plates deformed and contributed to the resistant capacity significantly.

However, because the bolt spacing was too large in SP42B22, the end anchorage of the bolted steel plates was weak, the failure was induced by the crush of the concrete near the

left support, thus the strengthening effect was not desirable.. It can be found that the ascending branch of the load‒deflection curve of SCTRL were substantially straight, which

indicated a shear failure occurred for SCTRL.

360-6

Page 7: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

Figure 8: Comparison of load-vertical displacement curves

Figure 9: Load–displacement curves based on two measurement methods

After being strengthened, the stiffness and ductility were enhanced. Due to the poor end anchorage of the bolted steel plates in SP42B22, there was no evident post-peak descending

branch and the enhancement was the least among all the BSP specimens. On the other hand, SP42B11 presented improved shear performance thanks to its halved bolt space.

Although the plate depth was much greater in SP43B22, the strengthening effect was only slightly greater than SP42B22 and even not so significant compared to SP42B11. This is

because the large bolt spacing could not guarantee a satisfactory collaboration between the steel plates and the RC beam. When both greater plate depth and less bolt spacing were

employed, the stiffness and ductility of SP43B11 was greater than those of the others.

3.4 Analysis of BSP beams’ behavior based on DIC

The digital image correlation (DIC) was a non-contact optical technique for measuring strain and displacement. In order to verify its accuracy, the data obtained from DIC analysis was

compared with the data measured by LDTs, as shown in Figure 9. It can be seen that the load-displacement curves obtained from the DIC analysis was very close to the curves

measured by LDTs.

As shown in Figure 10 – Figure 11, the fields of both the horizontal and vertical displacements present are symmetrically distributed. For the BSP beams for flexural test, the local

buckling area of the bolted steel plates can be visually identified in the vertical displacement field. It is seen from Figure 12 – Figure 13 that the fields of principal strains are also

symmetrically distributed. It is evident from Figure 12 that the local buckling of steel plates appeared first at the loading points rather than the mid-span, which indicates that the plate

buckling was a result of not only bending but also shearing. There was obvious stress concentrated zones on specimen surface, and the main crack path agreed with strain

concentration zones.

(a) Horizontal displacement field (P = Pu) (b) Vertical displacement field (P = Pu)

Figure 10: Displacement fields of FP43B33 derived for the DIC technique

(a) Horizontal displacement field (P = Pu) (b) Vertical displacement field (P = Pu)

Figure 11: Displacement fields of SP42B22 derived for the DIC technique

360-7

Page 8: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

(a) P = 0.75 Pu (b) P = Pu

Figure 12: Principal tensile-strain fields of FP43B33 derived for the DIC technique

(a) Principal strain field (e1) (b) Principal strain field (e2)

Figure 13: Principal strain fields of SP42B22 derived for the DIC technique

4 CONCLUSIONS

The flexural and shear behaviors of several fire damaged RC beams strengthened with the BSP technique was investigated and the following conclusions can be summarized:

(1) Obvious temperature gradient was observed in the RC beams under fire, delay of peak temperature was also found after flameout due to the poor heat conductivity of concrete.

The post-fire residual deformation was negligible for the subsequent strengthening and loading tests.

(2) After being retrofitted using the BSP technique, both the flexural and shear capacity, the stiffness and the ductility of the fire-damaged RC beams were recovered, and the

occurrence of the concrete cracks was delayed slightly.

(3) The enhancement increases as the increase of the plate depth and the decrease of the bolt spacing.

(4) Local buckling occurred in the bolted steel plates under a combination of bending and shear stress in the later stage of testing, which was restrained effectively by adding

stiffeners or using more anchor bolts.

(5) The DIC technique could be employed to record the development of displacement and strain fields, thus analyze the failure mode of BSP beams reliably.

Acknowledgements

The research described here received financial support from the National Natural Science Foundation of China (Project No. 51778496 and No. 51778497).

ReferencesAhmed, M. Oehlers, D.J. and Bradford, M.A. 2000. Retrofitting Reinforced Concrete Beams by Bolting

Steel Plates to Their Sides-Part 1: Behaviour and Experiments. Struct. Eng. Mech. 10(3): 211-226.Alam, M.A. and Jumaat, M.Z. 2009. Eliminating Premature End Peeling of Flexurally Strengthened

Reinforced Concrete Beams. Journal of Applied Sciences, 9(6): 1106-1113.Barnes, R.A. Baglin, P.S. Mays, G.C. and Subedi, N.K. 2001. External Steel Plate Systems for the Shear

Strengthening of Reinforced Concrete Beams. Eng. Struct. 23(9): 1162-1176.Deniaud, C. and Cheng, J.J.R. 2001. Shear Behavior of Reinforced Concrete T-Beams with Externally

Bonded Fiber-Reinforced Polymer Sheets. ACI Struct. J. 98: 386-394.El-Hawary, M.M. Ragab, A.M. El-Azim, A.A. and Elibiari, S. 1996. Effect of Fire on Flexural Behaviour of

RC Beams. Constr. Build. Mater. 10(2): 147-150.Jiang, C.J. Lu, Z.D. and Li, L.Z. 2017. Shear Performance of Fire-Damaged Reinforced Concrete Beams

Repaired by a Bolted Side-Plating Technique. J. Struct. Eng. 143(5): 04017007.Kolsek, J. Hozjan, T. Saje, M. and Planinc, I. 2013. Analytical Solution of Linear Elastic Beams Cracked in

Flexure and Strengthened with Side Plates. J. Compos. Mater. 47(22): 2847-2864.Kumar, A. and Kumar, V. 2003. Behaviour of RCC Beams after Exposure to Elevated Temperatures.

Journal of the Institution of Engineers. India. Civil Engineering Division, 84(11): 165-170.Lee, J. Xi, Y. and Willam, K. 2008. Properties of Concrete After High-Temperature Heating and Cooling.

ACI Mater. J. 105(4): 334-341.

360-8

Page 9: The buildingSMART Canada BIM Strategy · Web viewThe former six beams were used to investigate the flexural strengthening effect of the BSP technique for fire-damaged RC beams as

Li, L.Z. Cai, Z.W. Lu, Z.D. Zhang, X.L. and Wang, L. 2017. Shear Performance of Bolted Side-Plated Reinforced Concrete Beams. Eng. Struct. 144(8): 73-87.

Li, L.Z. Jiang, C.J. Jia, L.J. and Lu, Z.D. 2016. Local Buckling of Bolted Steel Plates with Different Stiffener Configuration. Eng. Struct. 119(7): 186-197.

Li, L.Z. Jiang, C.J. Su, R.K.L. and Lo, S.H. 2016. Design of Bolted Side-Plated Reinforced-Concrete Beams with Partial Interaction. P. I. Civil Eng.-Str. B. 169(2): 81-95.

Li, L.Z. Lo, S.H. and Su, R.K.L. 2013. Experimental Study of Moderately Reinforced Concrete Beams Strengthened with Bolted-Side Steel Plates. Adv. Struct. Eng. 16(3): 499-516.

Lo, S.H. Li, L.Z. and Su, R.K.L. 2014. Optimization of Partial Interaction in Bolted Side-Plated Reinforced Concrete Beams. Comput. Struct. 131(7): 70-80.

Nguyen, N.T. Oehlers, D.J. and Bradford, M.A. 2001. an Analytical Model for Reinforced Concrete Beams with Bolted Side Plates Accounting for Longitudinal and Transverse Partial Interaction. Int. J. Solids Struct. 38(38-39): 6985-6996.

Oehlers, D.J. Nguyen, N.T. Ahmed, M. and Bradford, M.A. 1997a. Transverse and Longitudinal Partial Interaction in Composite Bolted Side-Plated Reinforced-Concrete Beams. Struct. Eng. Mech. 5(5): 553-563.

Oehlers, D.J. Nguyen, N.T. Ahmed, M. and Bradford, M.A. 1997b. Transverse and Longitudinal Partial Interaction in Composite Bolted Side-Plated Reinforced-Concrete Beams. Struct. Eng. Mech. 5(5): 553-563.

Park, D.G. Cho, J.Y. and Oh, B.H. 2003. Failure Behavior and Separation Criterion for Strengthened Concrete Members with Steel Plates. J. Struct. Eng. 129(9): 1191-1198.

Siu, W.H. and Su, R.K.L. 2011. Analysis of Side-Plated Reinforced Concrete Beams with Partial Interaction. Comput. Concrete, 8(1): 71-96.

Smith, S.T. and Bradford, M.A. 1999. Local Buckling of Side-Plated Reinforced-Concrete Beams. I: Theoretical Study. J. Struct. Eng. 125(6): 622-634.

Su, R.K.L. Li, L.Z. and Lo, S.H. 2013. Shear Transfer in Bolted Side-Plated Reinforced Concrete Beam. Eng. Struct. 56(11): 1372-1383.

Su, R.K.L. Li, L.Z. and Lo, S.H. 2014. Longitudinal Partial Interaction in Bolted Side-Plated Reinforced Concrete Beams. Adv. Struct. Eng. 17(7): 921-936.

Su, R.K.L. and Cheng, B. 2008. the Effect of Coarse Aggregate Size On the Stress-Strain Curves of Concrete Under Uniaxial Compression. Transactions-Hong Kong Institution of Engineers, 15:6.

Triantafillou, T.C. 1998. Shear Strengthening of Reinforced Concrete Beams Using Epoxy-Bonded FRP Composites. ACI Struct. J. 95(2): 107-115.

Wei, L. Wang, Y. Yu, J. Xiao, J. and Xu, S. 2018. Feasibility Study of Strain Hardening Magnesium Oxychloride Cement-Based Composites. Constr. Build. Mater. 165: 750-760.

Xu, X.L. Lu, Z.D. Li, L.Z. and Jiang, C.J. 2017. Numerical Study On the Local Buckling Behaviour of Bolted Steel Plates in Steel Jacketing. Adv. Mater. Sci. Eng. 2017: 1352084.

Yang, X. Gao, W.Y. Dai, J.G. Lu, Z.D. and Yu, K.Q. 2018. Flexural Strengthening of RC Beams with CFRP Grid-Reinforced ECC Matrix. Compos. Struct. 189: 9-26.

Yu, J.T. Liu, K.K. Li, L.Z. Wang, Y.C. Yu, K.Q. and Xu, Q.F. 2018. A Simplified Method to Predict the Fire Resistance of RC Beams Strengthened with Near-Surface Mounted CFRP. Compos. Struct. 193(6): 1-7.

Yu, K.Q. Li, L.Z. Yu, J.T. Wanga, Y.C. Ye, J.H. and Xu, Q.F. 2018. Direct Tensile Properties of Engineered Cementitious Composites: a Review. Constr. Build. Mater. 165: 346-362.

Yu, K.Q. Yu, J.T. Dai, J.G. Lu, Z.D. and Shah, S.P. 2018. Development of Ultra-High Performance Engineered Cementitious Composites Using Polyethylene (PE) Fibers. Constr. Build. Mater. 158: 217-227.

Zhu, J. Wei, L. Moahmoud, H. Redaelli, E. Xing, F. and Bertolini, L. 2017. Investigation On CFRP As Dual-Functional Material in Chloride-Contaminated Solutions. Constr. Build. Mater. 151: 127-137.

360-9