THD AND EFFICIENCY STUDY FOR PV GRID-CONNECTED
LAFSAH BT MAT DAUD
A report submitted in partial fulfillment of the
requirements for the award of the degree of Bachelor of
Electrical Engineering (Power System)
Faculty of Electrical Engineering
Universiti Malaysia Pahang
JUNE 2012
v
ABSTRACT
Total harmonic distortion (THD) is a measurement of the harmonic distortion
and is defined as the ratio of the sum of the powers of all harmonic components to the
power of the fundamental frequency. In general, efficiency is a measurable concept,
quantitatively determined by the ratio of output to input. The project is all about the
experimental study on THD and efficiency for photovoltaic (PV) grid connected. A
scale-down less than 1kW system will be developed and established for the study. The
impact on THD and efficiency will be assessed to the real network environment by
connected three phase motor to Variable Frequency Drives (VFD’s) as the load. The
experimental will be done by using Power Quality Analyzer (PQA) software and the
comparison between before and after connected PV will be conducted. The results of the
THD and efficiency for PV grid connected system will be obtained and analyzed under
influence of load conditions.
vi
ABSTRAK
Jumlah herotan harmonik (THD) adalah ukuran herotan harmonik dan
ditakrifkan sebagai nisbah jumlah kuasa semua komponen harmonik kuasa frekuensi
asas. Secara amnya, kecekapan adalah satu konsep yang diukur, yang kuantitnya
ditentukan oleh nisbah output kepada input. Tujuan kertas ini adalah kajian eksperimen
THD dan kecekapan untuk grid photovoltaic (PV) yang berkaitan. Satu skala-turun
kurang daripada 1kW sistem akan dibangunkan dan ditubuhkan untuk kajian. Impak ke
atas THD dan kecekapan akan dinilai untuk persekitaran rangkaian sebenar oleh
penyambungan tiga fasa motor kepada Pemacu Frekuensi Variabel (VFD) sebagai
beban. Eksperimen adalah dengan menggunakan Kualiti Kuasa Analyzer (PQA) dan
perbandingan di antara sebelum dan selepas penyambungan PV akan dijalankan.
Keputusan THD dan kecekapan bagi sistem grid PV yang berkaitan akan diperolehi dan
dianalisis di bawah pengaruh keadaan beban.
vii
TABLE OF CONTENTS
CHAPTER CONTENTS
PAGE
DECLARATION ii
DEDICATION iii
ACKNOWLEDGEMENTS iv
ABSTRACT v
ABSTRAK vi
TABLE OF CONTENTS vii
LIST OF FIGURES xiii
LIST OF APPENDICES xvii
LIST OF ABBREVIATIONS
xviii
1 INTRODUCTION
1.1 Overview THD and Efficiency of
PV Grid Connected
1.2 Problem Statement
1.3 Project Background
1.4 Objective
1.5 Scope of Project
1.6 Report Outline
1
1
2
3
3
4
4
viii
2 LITERATURE REVIEW
2.1 Introduction
2.2 History of PV
2.3 Types of PV System
2.4 PV System Works
2.4.1 The Solar Cell
2.4.2 Types of PV Cell
2.4.3 Types of PV Panel
2.4.4 The PV System
2.4.5 On Grid System
2.4.6 Off Grid System
2.5 Introduction of Harmonics
2.6 Definition of THD
2.7 Definition of Efficiency in PV Grid-
Connected
2.8 Experimental evaluation that Related with
THD and efficiency in PV Grid- Connected
system
6
6
6
7
11
11
13
14
15
16
16
17
19
19
20
3 METHODOLOGY
3.1 Introduction
3.2 KEWPQAMASTERV203 Software
3.3 PQA Instrument
3.4 Flowchart of the study
3.5 Block Diagram
3.6 The function of each component in block
diagram
3.6.1 PV Array
3.6.2 MPPT
26
26
26
27
28
33
33
33
34
ix
3.6.3 DC-DC converter (Boost converter)
3.6.4 Capacitor
3.6.5 Common DC Link
3.6.6 Load
3.6.7 Inverter
3.6.8 Grid-Connected System
3.7 Flowchart of the Experimental Setup
3.8 Total Harmonic Distortion
3.9 Efficiency
3.9.1 Procedure to Get The Efficiency at
Load for PV Grid-Connected
System
3.9.2 Procedure to Get The Efficiency at
PV Inverter
34
35
35
35
36
36
36
42
44
44
48
4 RESULT AND DISCUSSION
4.1 Introduction
4.2 Result
4.3 Case 1: Total Harmonic Distortion (THD)
4.3.1 Comparison THD for
Frequency is 50 Hz with Speed
is 1500 rpm Before and After
Connected PV
4.3.1.1 THD at Grid
4.3.1.2 THD at Load
49
49
49
50
50
50
53
x
4.3.2 Comparison THD for
Frequency is 40 Hz with Speed
is 1200 rpm Before and After
Connected PV
4.3.2.1 THD at Grid
4.3.2.2 THD at Load
4.3.3 Comparison THD for
Frequency is 30 Hz with Speed
is 900 rpm Before and After
Connected PV
4.3.3.1 THD at Grid
4.3.3.2 THD at Load
4.3.4 Comparison result THD
for frequency is 50 Hz,
40 Hz and 30 Hz with speed
is 1500 rpm, 1200 rpm and
900 rpm before and after
connected PV.
4.3.4.1 THD at grid
4.3.4.2 THD at PV
4.3.4.3 THD at load
4.4 Case 2: Efficiency
4.4.1 Comparison Efficiency for
Frequency is 50 Hz with Speed
is 1500 rpm Before and After
Connected PV
4.4.1.1 Efficiency at Load
57
57
60
64
64
67
71
71
74
77
80
81
81
xi
4.4.2 Comparison Efficiency for
Frequency is 40 Hz with Speed
is 1200 rpm Before and After
Connected PV
4.4.2.1 Efficiency at Load
4.4.3 Comparison Efficiency for
Frequency is 30 Hz with Speed
is 900 rpm Before and After
Connected PV
4.4.3.1 Efficiency at Load
4.4.4 Comparison Efficiency for
Frequency is 50 Hz, 40 Hz and
30Hz with Speed is 1500 rpm, 1400
rpm and 900 rpm Before and After
Connected PV.
4.4.5 Comparison of PV Inverter
Efficiency during No Load and
Fixed Load Conditions
85
85
89
89
93
95
5 CONCLUSION
5.1 Conclusion
98
6 RECOMMENDATION
6.1 Recommendation
99
REFERENCES
100
xii
APPENDICES
APPENDIX A Current Harmonics result
APPENDIX B Experimental Setup
APPENDIX C Datasheet for PV Array Module
APPENDIX D Datasheet for PV inverter
APPENDIX E Schematic Drawing for Three Phase Motor
APPENDIX F Schematic Drawing for DOL Motor Starter Box
xiii
LIST OF FIGURES
FIGURE NO. TITLE PAGE
2.1 Diagram of Grid-Connected photovoltaic system
8
2.2 Direct-coupled PV systems
9
2.3 Diagram of Stand-Alone PV system with battery storage powering DC and AC loads
10
2.4 Diagram of photovoltaic hybrid system
10
2.5 Major photovoltaic system components
11
2.6 Solar cell
12
2.7 Types of commercial solar cell available today
14
2.8 The PV panel
15
2.9 Grid connected PV system
16
2.10 Comparison of linear and non-linear VI characteristic
17
3.1 Instrument layout of PQA
27
3.2 Flowcharts for THD and efficiency study for PV Grid-Connected
32
3.3 Main components in PV grid connected system
33
xiv
3.4 Flowchart of experimental setup
41
3.5 Equivalent circuit during no load test
45
3.6 Equivalent circuits during Block Rotor Test
46
3.7 Emprical formulas
46
3.8 Formula and connection for Star and Delta
47
3.9 Equivalent circuit of induction Machine (from test) that recommended by IEEE
47
4.1 Comparison THDV at grid for frequency is 50 Hz with speed is 1500 rpm before and after connected PV
51
4.2 Comparison THDI at grid for frequency is 50 Hz with speed is 1500 rpm before and after connected PV.
53
4.3 Comparison result THDV at load for frequency is 50 Hz with speed is 1500 rpm before and after connected PV.
54
4.4 Comparison result THDI at load for frequency is 50 Hz with speed is 1500 rpm before and after connected PV
56
4.5 Comparison result THDV at grid for frequency is 40 Hz with speed is 1200 rpm before and after connected PV.
58
4.6 Comparison result THDI at grid for frequency is 40 Hz with speed is 1200 rpm before and after connected PV.
60
4.7 Comparison result THDV at load for frequency is 40 Hz with speed is 1200 rpm before and after connected PV.
61
4.8 Comparison result THDI at load for frequency is 40 Hz with speed is 1200 rpm before and after connected PV.
63
xv
4.9 Comparison result THDV at grid for frequency is 30 Hz with speed is 900 rpm before and after connected PV.
65
4.10 Comparison result THDI at grid for frequency is 30 Hz with speed is 900 rpm before and after connected PV.
67
4.11 Comparison result THDV at load for frequency is 30 Hz with speed is 900 rpm before and after connected PV.
68
4.12 Comparison result THDI at load for frequency is 30 Hz with speed is 900 rpm before and after connected PV.
70
4.13 Comparison result THDV at grid for frequency is 50 Hz, 40 Hz and 30 Hz with speed is 1500 rpm, 1200 rpm and 900 rpm before and after connected PV.
72
4.14 Comparison result THDI at grid for frequency is 50 Hz, 40 Hz and 30 Hz with speed is 1500 rpm, 1200 rpm and 900 rpm before and after connected PV.
74
4.15 Comparison result THDV at PV for frequency is 50 Hz, 40Hz and 30 Hz with speed is 1500 rpm, 1200 rpm and 900 rpm after connected PV.
75
4.16 Comparison result THDI at PV for frequency is 50 Hz, 40Hz and 30 Hz with speed is 1500 rpm, 1200 rpm and 900 rpm after connected PV.
76
4.17 Comparison result THDV at load for frequency is 50 Hz, 40 Hz and 30 Hz with speed is 1500 rpm, 1200 rpm and 900 rpm before and after connected PV.
78
4.18 Comparison result THDI at load for frequency is 50 Hz, 40 Hz and 30 Hz with speed is 1500 rpm, 1200 rpm and 900 rpm before and after connected PV.
80
xvi
4.19 Comparison result efficiency versus time at load for frequency is 50 Hz with speed is 1500 rpm before and after connected PV.
81
4.20 Comparison THDV versus efficiency at load for frequency is 50 Hz with speed is 1500 rpm before and after connected PV.
83
4.21 Comparison THDI versus efficiency at load for frequency is 50 Hz with speed is 1500 rpm before and after connected PV.
85
4.22 Comparison result efficiency versus time at load for frequency is 40 Hz with speed is 1200 rpm before and after connected PV.
86
4.23 Comparison THDV versus efficiency at load for frequency is 40 Hz with speed is 1200 rpm before and after connected PV.
87
4.24 Comparison THDI versus efficiency at load for frequency is 40 Hz with speed is 1200 rpm before and after connected PV.
89
4.25 Comparison result efficiency versus time at load for frequency is 30 Hz with speed is 900 rpm before and after connected PV.
90
4.26 Comparison result THDV versus efficiency at load for frequency is 30 Hz with speed is 900 rpm before and after connected PV.
91
4.27 Comparison result THDI versus efficiency at load for frequency is 30 Hz with speed is 900 rpm before and after connected PV.
93
4.28 Comparison result efficiency versus time at load for frequency is 50 Hz, 40 Hz and 30 Hz with speed is 1500 rpm, 1200 rpm and 900 rpm before and after connected PV.
95
4.29 Comparison result efficiency of PV inverter during no load and fixed load conditions.
97
xvii
LIST OF APPENDICES
APPENDIX TITLE
PAGE
A Current Harmonics result
104
B Experimental Setup
108
C Datasheet for PV Array Module
111
D Datasheet for PV inverter
114
E Schematic Drawing for Three Phase Motor
116
F Schematic Drawing for DOL Motor Starter Box
117
xviii
LIST OF ABBREVIATIONS
PV - Photovoltaic
DC - Direct Current
AC - Alternating Current
THD - Total Harmonic Distortion
THDI - Total Harmonic Distortion Current
THDV - Total Harmonic Distortion Voltage
PCU - Power Conditioning Unit
MPPT - Maximum Power Point Tracker
ARC - Anti-Reflective Coating
PE - Power Electronic
PWM - Pulse Width Modulation
PCC - Point Common Coupling
VFDs - Variable Frequency Drives
PQA - Power Quality Analyzer
CHAPTER 1
INTRODUCTION 1.1 Overview THD and Efficiency of PV Grid-Connected
Today, the use of Grid-Connected Photovoltaic (PV) systems has been grown to
be popular in many parts of the world. More numbers of Grid-Connected PV generators
connected to a distribution network through PV inverters can afford to cause harmonic
problems. In general, a harmonic problem can be defined as a particular disturbance,
which is created by the presence of non-linear components in the electrical system that
determines a permanent modification of the voltage and current sinusoidal wave shapes
in terms of sinusoidal components at a frequency different from the fundamental. In a
grid interconnected photovoltaic power system, the Direct Current (DC) output power of
the photovoltaic array should be converted into the Alternating Current (AC) power of
the utility power system.
Under this condition, an inverter to convert DC power into AC power is required.
A line commutated inverter uses a switching device like a commutating thyristor that
can control the timing of turn ON but cannot control the timing of turn OFF by itself.
Turn OFF should be performed by reducing circuit current to zero with the assist
2
of supplemental circuit or a source. On the other hand, a self-commutated inverter is
characterized in that it uses a switching device that can freely control the ON-state and
the OFF-state, such as an IGBT or a MOSFET. A self-commutated inverter can freely
control the voltage and the current waveform at the AC side, adjust the power factor, and
suppress the harmonic current, and is highly resistant to utility system disturbance.The
sum voltage harmonic distortion of the utility grid has been established to influence the
harmonic currents of an inverter [1].
The number of PV Grid-Connected system that connected to the utility grid has
no result to the inverter’s harmonic currents but it is not the case for load power factor.
The ordinary installation pattern of a PV Grid-Connected system consists of a PV array
and a grid connected inverter. While the inverter injects power produced from the PV
array into the utility grid, there are roughly always some types of loads receiving power
from the grid at the same moment. It is usual to ask whether the grid condition and the
local loads have influence, if any on the inverter output in addition to the irradiation
which directly affects the dc output power of the PV array. In this study, the issues of
local loads by taking into consideration the load condition at PCC on the harmonic
currents of a grid-connected inverter must be analyzed. An experimentalbefore and after
connected PV platform is prepared to measure the Total Harmonic Distortion (THD) and
efficiency values on both DC and AC sides.
1.2 Problem Statement
This study has been proposed because of the rapid growth of PV Grid-Connected
installation and it is important to explore its effects on THD and efficiency.The total
voltage harmonic distortion of the utility grid has been recognized as main factors that
can affect the harmonic currents of an inverter. At the same time, the harmonics is
majority occurs under influence of load conditions.
3
1.3 Project Background
The term “harmonics” was originated in the field of acoustics, where it was
related to the vibration of a string or an air column at a frequency that is multiple of the
base frequency [2]. A harmonic component in an AC power system is defined as a
sinusoidal component of a periodic waveform that has a frequency equal to an integer
multiple of the fundamental frequency of the system [2]. Harmonics in the voltage or
current waveform can then be conceived as completely sinusoidal components of
frequencies multiple of the fundamental frequency [2]. PV systems use inverters to get
linked to distribution networks that utilize alternative voltage. On the other hand,
harmonic currents generated by PV systems may downgrade the quality of the electrical
network and change performance of other electrical equipment. In this study, the THD
and efficiency of PV Grid-Connected system hasbeenanalyzed under influence of load
conditions by varied the frequency.
1.4 Objective The objectives for this project are stated below:
i. To measure the value of THD and efficiency at PV Grid-Connected.
ii. To obtain and analyzed THD and efficiency under influence of load
conditions by varied the frequency.
iii. To compare the experimental of THD and efficiency before and after
connected PV.
4
1.5 Scope of Project
Data has been collected at FKEE laboratory by using Power Quality Analyzer
(PQA). The harmonic and efficiency data that already get will be transferred to the
computer by using KEWPQAMASTERV203 software. The PV Grid-Connected system
configuration has been setup at FKEE laboratory. The setup consist PV array, DC to AC
inverter, load and grid system.
1.6 Report Outline
Chapter 1 discuss about the introduction, project background, objective and
scope project. Otherwise this chapter discusses more about the application and the goal
of THD and efficiency analysis.
Chapter 2 discusses more about the literature review. Besides that the history of
PV, PV system works, types of PV, introduction of harmonics, definition of THD,
definition of efficiency in PV Grid-Connected and experimental evaluation that related
with THD in PV Grid-Connected system also discuss in this chapter.
Chapter 3 focused on methodologies for determine the harmonic and efficiency
data. In addition, the flowchart about main procedure PSM 1 and PSM 2 will be
discussing more details in this chapter. MATLAB software, Power Quality Analyzer
(PQA), block diagram, PV Grid-Connected design using MATLAB, experimental setup
of PV Grid-Connected, THD and efficiency formula is also discussed with details in this
chapter.
Chapter 4 exposed about the result that displayed and analyzed. This data will
be discussing further to get the THD and efficiency study for PV Grid-Connected. The
5
THD and efficiency will be discussed and analyzed at the grid, PV and motor (load) by
varied the frequency and speed by using the Variable Frequency Drives (VFD’s).
Chapter 5 is about the conclusions for this study that have been elaborate
details.
Chapter 6 is about the recommendation for this study that have been elaborate
details.
CHAPTER 2
LITERATURE REVIEW 2.1 Introduction This chapter present about the literature review. Besides that the history of PV,
PV system works, types of PV system, introduction of harmonics, definition of THD,
definition of efficiency in PV Grid-Connected and experimental evaluation that related
with THD in PV Grid-Connected system also discuss in this chapter.
2.2 History of PV
In the late 1950s the first conventional photovoltaic cells were created, and
during the 1960s were mainly used to supply electrical power for earth-orbiting satellites
[3]. In the 1970s, improvements in industrialized, performance and excellence of PV
modules helped to decrease costs and opened up a number of opportunities for powering
7
distant terrestrial applications, including battery charging for navigational aids, signals,
telecommunications equipment and other critical, low power needs [3]. Photovoltaic
became a popular power source for consumer electronic devices, including calculators,
watches, radios, lanterns and other small battery charging applications in the 1980s.
Subsequent the energy crises of the 1970s, significant efforts also began to build
up PV power systems for residential and commercial uses both for stand-alone, remote
power as well as for utility-connected applications. Throughout the similar period,
international applications for PV systems to power rural health clinics, refrigeration,
water pumping, telecommunications, and off-grid households increased dramatically,
and remain a major portion of the present world market for PV products [3]. Nowadays,
the industry’s manufacture of PV modules is growing at approximately 25 percent
annually, and major programs in the U.S, Japan and Europe are rapidly accelerating the
accomplishment of PV systems on buildings and interconnection to utility networks [3].
2.3 Types of PV System
Photovoltaic power systems are normally classified according to their useful and
operational requirements, component configurations, and how the equipment is
connected to other power sources and electrical loads [3]. Two principles for
classifications are grid-connected or utility-interactive systems and stand-alone systems.
Photovoltaic systems can be designed to give DC and/or AC power service, can function
interconnected with or independent of the utility grid, and can be connected with other
energy sources and energy storage systems [3].
The first one type is Grid-Connected (Utility-Interactive) PV Systems. Grid-
Connected or Utility-Interactive PV systems are designed to function in parallel with
and interconnected with the electric utility grid [3]. The main component in grid-
connected PV systems is the inverter, or power conditioning unit (PCU) [3]. The PCU
converts the DC power produced by the PV array into AC power
voltage and power quality requirements of the utility grid, and automatically stops
supplying power to the grid when the utility grid is not energized
Figure 2.1 illustrates that
load demand, this allows the AC power produced by the PV system to either supply on
site electrical loads, or to back feed the grid. At
when the electrical loads are
necessary by the loads is received from t
required in all Grid-
carry on to operate and feed back onto the utility grid when the grid is
service or repair [3].
Figure 2.1
Since there is no electrical energy storage (batteries) in direct
the load only operates during sunlight hours, making these designs suitable for common
applications such as ventilation fans, water pumps, and small circulation pumps for so
converts the DC power produced by the PV array into AC power
voltage and power quality requirements of the utility grid, and automatically stops
supplying power to the grid when the utility grid is not energized [3]
illustrates that when the PV system output is greater than the on
his allows the AC power produced by the PV system to either supply on
site electrical loads, or to back feed the grid. At nighttime and throughout
when the electrical loads are larger than the PV system output, the
by the loads is received from the electric utility This safety
-Connected PV systems, and ensures that the PV system will not
to operate and feed back onto the utility grid when the grid is
Figure 2.1 Diagram of Grid-Connected Photovoltaic system [3]
Since there is no electrical energy storage (batteries) in direct
the load only operates during sunlight hours, making these designs suitable for common
applications such as ventilation fans, water pumps, and small circulation pumps for so
8
converts the DC power produced by the PV array into AC power dependable with the
voltage and power quality requirements of the utility grid, and automatically stops
[3].
hen the PV system output is greater than the on-site
his allows the AC power produced by the PV system to either supply on-
throughout other periods
than the PV system output, the equilibrium of power
he electric utility This safety characteristic is
onnected PV systems, and ensures that the PV system will not
to operate and feed back onto the utility grid when the grid is downward for
hotovoltaic system [3]
Since there is no electrical energy storage (batteries) in direct-coupled systems,
the load only operates during sunlight hours, making these designs suitable for common
applications such as ventilation fans, water pumps, and small circulation pumps for solar