Upload
others
View
8
Download
0
Embed Size (px)
Citation preview
FH BrundleUnit 6, Dorset RoadSaltley Business ParkSaltleyBirminghamB8 1BG
Client:
Lucideon UKWork Location:
This report supersedes the report issued on 27.04.16.
Project ManagerReviewer
TEST REPORT
Project Title:
Lucideon Reference:
Load Testing of FH Brundle Mezzirail System, which Comprises of Two Square Uprights and Two Cross-Rails, to BS EN 6180:2011
155217 (QT38377/1/SL)/Ref. 12/Supp1
1001
20 May, 2016
333597Purchase Order No.:
For the Attention of:
Author(s):
Mr Danny Hull
Mr Dave Boon
Report Date:
Consultancy TeamMr Dave BoonMr Dave Dix
Consultancy Team
Page 1 of 11 Pages
shall not be reproduced in part without the written approval of Lucideon Limited, nor used in any way as to lead to
Lucideon is the trading name of Lucideon Limited. Registered in England No. 1960455.
No responsibility is taken for the accuracy of the sampling unless this is done under our own supervision. This reportThis report is issued in accordance with the Conditions of Business of Lucideon Limited and relates only to the sample(s) tested.
misrepresentation of the results or their implications.
Test Report: 155217/Ref. 12/Supp1
Page 2 of 11 Pages
CONTENTS
Page 1 INTRODUCTION 3 2 SAMPLES RECEIVED 3 3 TEST METHOD 3 4 RESULTS 4 TABLES 5-8 PLATES 9 CHARTS 10-11 APPENDIX - Figures
Test Report: 155217/Ref. 12/Supp1
Page 3 of 11 Pages
1 INTRODUCTION Lucideon Limited were commissioned by the client, FH Brundle to carry out load testing in accordance with BS 6180:2011 Barriers in and about buildings, and EC1-1991-1-1:2002 UK National Annex to Eurocode 1 (BS EN991-1-3:2003+A1:2015): Actions on structures – Part 1-1: General actions - Densities, self-weight, imposed loads for buildings. This will allow their balustrade system to be classified for use in accordance with the Code of Practice included within the standard. The testing is also covered in BS 4592-0:2006+A1:2012: Flooring, stair treads, and handrails for industrial use-Part 0: Common design requirements and recommendations for installation. BS 4592-0:2006+A1:2012 has the same load requirements as BS 6180:2011. The system tested was referred to as Mezzirail consisting of Posts and Cross-Rail. The testing was carried out at the Lucideon Laboratories located in Queens Road, Stoke-on-Trent. This report summarises the test result obtained during the test and does not provide interpretation of those results.
2 SAMPLES RECEIVED 2 Square Posts nominally 50 mm x 50 mm, 1140 mm tall (including base thickness) and manufactured from galvanised steel. Two 3000 mm lengths of 33.7 mm diameter galvanised tube. 1 box of Fischer 040950 FBN II 12 X 105 Zinc Plated Fixings. The Mezzirail system is shown in the Figure in the Appendix.
3 TEST METHOD The 2 posts were bolted to a concrete substrate at 1200 mm centres and the cross-rails were fixed inside the holes in the square upright posts and securing with grub screws. One cross rail was located at the top, 1100 mm above the base and one at approximately mid-height. Plates 1 and 2 show the load arrangement of both 1200 mm and 1500 mm upright centre tests. A horizontal imposed line load was applied to the glass at a height of 1.1 m above the datum level of the floor and the deflection measured at the top central point of the panel 1.1 m above the datum level of the floor. The load was applied via a hydraulic ram and the deflection measured using a digital electronic displacement transducer (see Plate 1). A line load was applied to the Mezzirail with the uprights set at 1200 mm centres and a second line load was applied to the Mezzirail with the uprights set at 1500 mm centres. The Appendix shows three Figure showing dimensions and different angles of the system.
Test Report: 155217/Ref. 12/Supp1
Page 4 of 11 Pages
4 RESULTS
The tests were carried out in accordance with the guidance given in BS 6180 Barriers in and about buildings – Code of Practice. The standard states that the maximum allowable deflection for a free standing glass protective barrier panel is 25 mm. Table 2 of BS 6180 Barriers in and about buildings – Code of Practice categorises parapets, barriers and balustrades for areas of use depending on the loads they have achieved under testing. The load versus deflection curve for the Mezzirail system with the load applied as a line load across the top handrail with the uprights at 1200 mm and 1500 mm centres are shown in Chart 1 and 2 respectively. The loads achieved by the FH Brundle Mezzirail system under horizontal imposed line load to the maximum deflection of 25 mm are given in Table 1 (for 1200 mm and 1500 mm upright centres). All figures quoted in the Tables contain no safety factors and are direct loads as achieved by the system under test conditions. Tables 2 and 3 summarise the suitability of the tested systems in accordance with Table 2 of BS 6180:2011.
NOTE: The results given in this report apply only to the samples that have been tested. END OF REPORT
Test Report: 155217/Ref. 12/Supp1
Page 5 of 11 Pages
Table 1 - Summary of Performance of FH Brundle Mezzirail System with Load Applied to Top Rail at 1200 mm and 1500 mm Post Centres
Detail Imposed Line Load at 25 mm Deflection
(kN/m)
Expected Working Line
Load for System (kN/m)
Deflection at Working Line Load for System (mm)
Achieved Classification
(kN/m)
Mezzirail System comprising of 2 uprights and 2 cross-rails (uprights’ set at 1200 mm centres)
1.78 1.50 18.53 1.50
Mezzirail System comprising of 2 uprights and 2 cross-rails (uprights’ set at 1500 mm centres)
1.07 0.74 16.13 0.74
Table 2 - Summary of Suitability of FH Brundle Mezzirail System with Load Applied to Top Rail, at 1200 mm Post Centres
Type of Occupancy for Part of
the Building
Examples of Specific Use
Horizontal Uniformly
Distributed Line Load
(kN/m)
Mezzirail System
Domestic and residential activities
(i) all areas within or serving exclusively one single family dwelling including stairs, landings, etc. but excluding external balconies and edges of roofs
0.36
(ii) other residential, i.e. houses of multiple occupancy and balconies, including Juliette balconies and edges of roofs in single family dwellings
0.74
Offices and work areas not included elsewhere, including storage areas
(iii) light access stairs and gangways not more than 600 mm wide
0.36
(iv) light pedestrian traffic routes in industrial and storage buildings except designated escape routes
0.36
(v) areas not susceptible to overcrowding in office and institutional buildings, also industrial and storage buildings except as given above
0.74
Areas where people might congregate
(vi) areas having fixed seating within 530 mm of the barrier, balustrade or parapet
1.50
Areas with tables or fixed seating
(vii) restaurants and bars 1.50
Test Report: 155217/Ref. 12/Supp1
Page 6 of 11 Pages
Table 2 (Continued)
Note A - See requirements of the appropriate certifying authority. Note B – See Appendix A of BS 6180:2011.
Type of Occupancy for
Part of the Building
Examples of Specific Use
Horizontal Uniformly
Distributed Line Load
(kN/m)
Mezzirail System
Areas without obstacles for moving people and not susceptible to overcrowding
(viii) stairs, landings corridors ramps 0.74
(ix) external balconies including Juliette balconies and edges of roofs; footways and pavements within building cartilage adjacent to basement/sunken areas
0.74
Areas susceptible to overcrowding
(x) footways or pavements less than 3 m wide adjacent to sunken areas
1.50
(xi) theatres, cinemas, discotheques, bars, auditoria, shopping malls, assembly areas, studios; footways or pavements greater than 3 m wide adjacent to sunken areas
3.00 x
(xii) grandstands and stadia (Note A) -
Retail areas (xiii) all retail areas including public areas of banks/building societies or betting shops
1.50
Vehicular
(xiv) pedestrian areas in car parks, including stairs, landings, ramps, edges of internal floors, footways, edges of roofs
(Note B)
(xv) horizontal loads imposed by vehicles (Note B) -
Test Report: 155217/Ref. 12/Supp1
Page 7 of 11 Pages
Table 3 - Summary of Suitability of FH Brundle Mezzirail System with Load Applied to Top Rail, at 1500 mm Post Centres
Type of Occupancy for Part of
the Building
Examples of Specific Use
Horizontal Uniformly
Distributed Line Load
(kN/m)
Mezzirail System
Domestic and residential activities
(i) all areas within or serving exclusively one single family dwelling including stairs, landings, etc. but excluding external balconies and edges of roofs
0.36
(ii) other residential, i.e. houses of multiple occupancy and balconies, including Juliette balconies and edges of roofs in single family dwellings
0.74
Offices and work areas not included elsewhere, including storage areas
(iii) light access stairs and gangways not more than 600 mm wide
0.36
(iv) light pedestrian traffic routes in industrial and storage buildings except designated escape routes
0.36
(v) areas not susceptible to overcrowding in office and institutional buildings, also industrial and storage buildings except as given above
0.74
Areas where people might congregate
(vi) areas having fixed seating within 530 mm of the barrier, balustrade or parapet
1.50 x
Areas with tables or fixed seating
(vii) restaurants and bars 1.50 x
Test Report: 155217/Ref. 12/Supp1
Page 8 of 11 Pages
Table 3 (Continued)
Note A - See requirements of the appropriate certifying authority. Note B – See Appendix A of BS 6180:2011.
Type of Occupancy for
Part of the Building
Examples of Specific Use
Horizontal Uniformly
Distributed Line Load
(kN/m)
Mezzirail System
Areas without obstacles for moving people and not susceptible to overcrowding
(viii) stairs, landings corridors ramps 0.74
(ix) external balconies including Juliette balconies and edges of roofs; footways and pavements within building cartilage adjacent to basement/sunken areas
0.74
Areas susceptible to overcrowding
(x) footways or pavements less than 3 m wide adjacent to sunken areas
1.50 x
(xi) theatres, cinemas, discotheques, bars, auditoria, shopping malls, assembly areas, studios; footways or pavements greater than 3 m wide adjacent to sunken areas
3.00 x
(xii) grandstands and stadia (Note A) -
Retail areas (xiii) all retail areas including public areas of banks/building societies or betting shops
1.50 x
Vehicular
(xiv) pedestrian areas in car parks, including stairs, landings, ramps, edges of internal floors, footways, edges of roofs
(Note B)
(xv) horizontal loads imposed by vehicles (Note B) -
Test Report: 155217/Ref. 12/Supp1
Page 9 of 11 Pages
Plate 1 - Test Arrangement when Uprights Set at 1200 mm Centres
Plate 2 - Test Arrangement when Uprights Set at 1500 mm Centres
1000
1500
2000
2500
Load
(N)
Chart 1 - Load v Deflection for FH Brundle Mezzirail System, Line Load Applied 1100 mm fromBase of Concrete onto Handrail with Post at 1200 mm Centres Test Report: 155217/Ref. 12/Supp1
0
500
0 5 10 15 20 25 30 35 40 45Deflection (mm)
Test 1Key
Page 10 of 11 Pages
600
800
1000
1200
1400
1600
Load
(N)
Chart 2 - Load v Deflection for FH Brundle Mezzirail System, Line Load Applied 1100 mm fromBase of Concrete onto Handrail with Post at 1500 mm Centres Test Report: 155217/Ref. 12/Supp1
0
200
400
0 5 10 15 20 25 30 35 40Deflection (mm)
Test 1Key
Page 11 of 11 Pages
DIMENSION (A)
113
0
110
4.20
Concrete Base
Fixings Needed
33.7 BZP
30413373
25SPi
Test: Dimension (A) BS Standard Parts Needed Fixed Into Loading Hole Size Fixings Needed Notes
Test 12: Mezzirail System
1200mm 1500mm
BS6180:2011 and EC1-1991-1-1:2002
2 x 25SPI 2 X 30413373 - BZP 33.7 -2.0mm Tube.
Concrete 1.5kn 13mm 507563 - FBN 11 12 X 105 - 316 Trying to achieve 1.5kn at 1200mm & 1500mm fixed
post centres
A0197-010-12
Technical Drawing - Drawing Not To Be Supplied To Customer
04/07/2016GC
A3
SHEET 1 OF 1SCALE:1:10
DWG NO:
DO NOT SCALE DRAWING
NA
DATENAME
FINISH:
REV. BY
DRAWNWEIGHT:
NOTES:
REVISION
DESCRIPTION:
NAMATERIAL:PART NO: NA
NA
GRIT SIZE:
FH BRUNDLETel: 01282 834545
Email: [email protected] Web: www.fhbrundle.co.uk
UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN MILLIMETERS
Test 12
NA
APPENDIX - Figures
Front Cover 155217 Ref 12 Supp1.pdf155217 Ref 12 Supp2- FH Brundle155217 Ref 12 Supp1 - Chart 1 & 2155217 Ref 12 - Chart 1.pdf155217 Ref 12 - Chart 2
Appendix Figure 1-3 - 155217 Ref 12 Supp1Appendix Figure 1 155217 Ref 12.pdfSheet1Drawing View1Drawing View2
Appendix Figure 2 155217 Ref 121.pdf2.1
Appendix Figure 3 155217 Ref 12