Upload
buithuan
View
218
Download
4
Embed Size (px)
Citation preview
Vipac Reference: 30V-11-0424 -TRP- 264755-0 Date Vipac Engineers & Scientists Ltd Melbourne, Australia
Test Report
Aspirated Smoke Detectors (ASD) Performance and Reliability Testing in Dust Laden Environment
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing In Dust Laden Environment Page ii of 29
TABLE OF CONTENTS 1. INTRODUCTION 4 2. SCOPE 4 3. ASD units UNDER TEST 4 4. TEST SETUP 5
4.1 Laboratory .................................................................................................................................5 4.2 Dust Chamber ...........................................................................................................................5 4.3 Smoke Generation Box and Smoke Chamber..........................................................................6 4.4 Clean Air Sampling ...................................................................................................................7 4.5 ASD Units Setup .......................................................................................................................7 4.6 Test Instruments .......................................................................................................................8 4.7 Test Dust...................................................................................................................................8 4.8 Test Smoke...............................................................................................................................8
5. TEST PROCEDURE 9 5.1 Test Cycle .................................................................................................................................9 5.2 Sensitivity (Detection Performance)........................................................................................10 5.3 Pass/Fail Criteria.....................................................................................................................10
6. RESULTS 11 6.1 ASD Sensitivity (Detection Performance) ...............................................................................11 6.2 ASD Hardware Faults and Failures ........................................................................................12 6.2.1 Filter Faults .............................................................................................................................12 6.2.2 Critical Failures .......................................................................................................................12
7. CONCLUSIONS 14 APPENDIX A 15
DustTrack (Dust Chamber) Calibration Certificate............................................................................15 APPENDIX B 17
VelociCalc Plus Air Velocity Meter (TSI) Calibration.........................................................................17 APPENDIX C 22
ASHRAE 52/76 Calibration Certificate ..............................................................................................22 APPENDIX D 23
DustTrack Loading Analysis..............................................................................................................23 APPENDIX E 26
Sensitivity (Normalised) Calculation..................................................................................................26 APPENDIX F 27
Detailed Test Results – Individual ASD Units ...................................................................................27
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing In Dust Laden Environment Page iii of 29
TABLE OF FIGURES Figure 1: Test Setup – Schematic.......................................................................................................5
Figure 2: Dust Chamber ......................................................................................................................5
Figure 3: Smoke Generation Box and Smoke Chamber.....................................................................6
Figure 4: Clean Air Sampling Arrangement (HEPA filter) ...................................................................7
Figure 5: Test Cycle Steps..................................................................................................................9
Figure 6: ASD sensitivity (normalised) trend lines with critical fault and maintenance indicators ....11
Figure 7: SecuriRAS ASD 535-3 Filters (metallic mesh) ..................................................................12
Figure 8: Summary Graph Dust Loading 1 - 10 ................................................................................24
Figure 9: Summary Graph Dust Loading 11 - 13 ..............................................................................24
Figure 10: Summary Graph Dust Loading 14 - 15 ............................................................................25
LIST OF TABLES Table 1: ASD Units Under Test ...........................................................................................................4
Table 2: Dust Concentration (Dust Chamber / ASD Inlets).................................................................6
Table 3: ASD Particulate Filter Types .................................................................................................7
Table 4: ASD Baseline Flow-rates ......................................................................................................7
Table 5: ASD Configuration / Pipe Modelling Tools ............................................................................8
Table 6: Test Instruments....................................................................................................................8
Table 7: SecuriRAS ASD 535-3 Sensitivity Change with Filter Replacement ..................................12
Table 8: ASD Faults Timeline / Corrective Actions ...........................................................................13
Table 9: ASD Sensitivity Degradation ...............................................................................................14
Table 10: DustTrak Settings..............................................................................................................23
Table 11: Dust Loading Analysis.......................................................................................................23
Table 12: DustTrack Comparison Average Reading.........................................................................23
Table 13: Detailed Results: Smoke Tests / Normalised Sensitivity...................................................29
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 4 of 29
1. INTRODUCTION VIPAC Engineers & Scientists Ltd. was commissioned by Xtralis to carry out performance and reliability
testing on different models of Aspirated Smoke Detector (ASD) units in a dust-laden environment. Testing
was conducted at VIPAC laboratory in Port Melbourne, Australia, between the 7th and 22nd February
2012.
2. SCOPE The scope of the investigation was to compare the detection performance and reliability of ASD units
when exposed to (sampling) dust-laden air. The most common physical effects on any ASD unit from dust
sampling are:
• Contamination of optical components,
• Soiling of internal surfaces,
• Clogging of internal air filters and air paths,
• Abrasion/seizure of moving parts,
• Deterioration or failure of electrical components.
Sampling of dust is unavoidable in almost all environments and has the potential to compromise detection performance and reliability of an ASD unit resulting in increased demand for scheduled and unscheduled
maintenance including replacement of components or detector itself after critical failures. Specifically this
investigation measured, recorded and analysed:
• Reduction in sensitivity (detection performance),
• Smoke detection reliability (notification when sensitivity is compromised),
• Operational reliability (component failure),
• Fault reporting (notification of required service).
3. ASD UNITS UNDER TEST Table 1 lists the ASD models and manufacturers used for this investigation. All ASD units under test were
brand new.
No. Manufacturer Model Serial Number
1 Xtralis VLI-880 10811002
Smoke Detector: SecuriRAS ASD 535-3 5000623.0103.010409 Securiton: 022.235636
2 Securiton
Smoke Sensor: SSD 535-2 5000613.0103.080808 Securiton: 022.235679
3 System Sensor FAAST 8100 0026C800049F
Smoke Detector: TITANUS PRO SENS (TP-1-SL) 308698 4 Wagner
Detector Module: DM-TP-01-L 384109
Table 1: ASD Units Under Test
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 5 of 29
4. TEST SETUP The test setup comprised a Dust Chamber, Smoke Chamber, Smoke Generation Box and HEPA filtration arrangement as depicted in the schematic in Figure 1. All ASD units were connected to the Dust
Chamber, Smoke Chamber and HEPA filtration arrangement through individual pipe networks (21mm ID)
and valve arrangements to allow dust loading, smoke tests and clean air sampling independent of each
other.
Figure 1: Test Setup – Schematic
4.1 Laboratory • Ventilated space
• Temperature: 21-22˚C (70 – 72˚F)
• Humidity: 40-60%RH
4.2 Dust Chamber • Dust Chamber (Figure 2) internal volume: 0.216m3 (0.6 x 0.6 x 0.6)m [7.6ft3 (1.97x1.97x1.97)ft]
Figure 2: Dust Chamber
• ASD inlets were located in close proximity to each other and their exhausts were routed back to Dust Chamber for dust recirculation.
• Test dust: ASHRAE 52/76 standard test dust – see section 4.7 for details.
Dust Chamber
Smoke
Chamber
Smoke Reference Unit
ASD
Dust Reference unit
Valve
Clean Air
Smoke Gen. Box
Dust Chamber
ASD Inlet
TSI DustTrack Inlet
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 6 of 29
• Dust injection system: Dust placed in cylinder in center of Dust Chamber equipped with compressed air manifold and lid with holes for dust to escape through compressed air action.
Mixing fans provided for turbulent airflow conditions for homogeneous dust level.
• Dust Chamber internal pressure equalised to ambient using a separate inlet.
• Dust reference unit: TSI DustTrak (PM10) particulate measuring device. Sampling was arranged
in parallel to and in close proximity to ASD inlets.
• To verify that all ASD units were subjected to similar dust loading rates a comparison was made
between dust concentration levels inside the Dust Chamber and through each ASD inlet.
Simultaneous readings were taken with two TSI DustTrak instruments; one for Dust Chamber and the other for ASD inlets. Table 2 shows minimal difference (%) in dust concentration levels
between Dust Chamber and each ASD inlet indicating similar dust loading rates being applied
for all detectors under test. Dust readings shown represent instantaneous readings where
variations are expected inside the Dust Chamber.
ASD
Dust Concentration Dust Chamber (mg/m 3)
Dust Concentration ASD Inlet (mg/m 3)
% Difference
VLI-880 14.4 15.2 +5.55
SecuriRAS ASD 535-3 16.7 16.3 -2.39
FAAST 8100 20.5 20.2 -1.46
TITANUS PRO SENS 19.2 19.0 -1.04
Table 2: Dust Concentration (Dust Chamber / ASD Inl ets)
• Dust chamber designed and assembled by VIPAC.
4.3 Smoke Generation Box and Smoke Chamber • Internal volumes (Figure 3):
o Smoke Generation Box: 0.043m3 (0.35 x 0.35 x 0.35)m [1.52ft3 (1.15 x 1.15 x 1.15)ft]
o Smoke Chamber: 0.17m3 (0.85 x 0.5 x 0.4)m [6ft3 (2.78 x 1.64 x 1.31)ft]
Figure 3: Smoke Generation Box and Smoke Chamber
• Test smoke: smouldering cotton lamp wick (grey smoke) – see section 4.8 for details.
• Smoke generated in Smoke Generation Box and introduced to Smoke Chamber. ASD sampling
occurred from Smoke Chamber with inlets placed in close proximity.
• Smoke Chamber internal pressure equalised to ambient using separate inlets. Mixing fans ensured homogeneous smoke level.
Smoke Generation Box
Smoke Chamber
ASD Inlets
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 7 of 29
• Smoke reference unit: VESDA VLC-505. Sampling arranged in parallel to and in close proximity to ASD inlets. Reference unit provided ASDs’ Response Threshold Value (RTV) – see section
5.2 for RTV explanation.
• Smoke Generation Box and Smoke Chamber designed and assembled by Xtralis.
4.4 Clean Air Sampling All ASD units’ pipe network included a separate branch for clean air sampling through a HEPA filter
arrangement (Figure 4). This allowed ASDs to be purged with clean air to ascertain detector functionality
in clean air conditions and remove residual dust after each dust exposure prior to smoke tests.
Figure 4: Clean Air Sampling Arrangement (HEPA filt er)
4.5 ASD Units Setup • All ASD units were brand new, fitted with new internal particulate filters (where applicable) –
Table 3.
ASD Particulate Filter Type
VLI-880 HEPA / Foam filter
SecuriRAS ASD 535-3 Metallic mesh (60x40)mm with (1x1)mm openings
FAAST 8100 Particle separator / Foam filter
TITANUS PRO SENS No Filtration
Table 3: ASD Particulate Filter Types
• Baseline flow rate: 40L/min. Flow rate set by orifices on ASD inlets to Dust Chamber, Smoke Chamber and HEPA filter. Flow rates measured at each ASD exhaust with hot wire anemometer
(TSI VelociCalc Plus) for each sampling phase (Table 4).
ASD Aspirator Setting
Orifice Size (mm)
Flow rate (L/min)
VLI-880 4200rpm 7.5 43
SecuriRAS ASD 535-3 Level 5 7.0 43
FAAST 8100 Fixed 7.8 43
TITANUS PRO SENS 9V 9.0 41
Table 4: ASD Baseline Flow-rates
• Pipe networks designed short as possible to minimize transport times and dust deposition (loss)
within pipe.
HEPA filter
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 8 of 29
• Alarm delays: 0 sec.
• Alarms/Faults: latched.
• ASD RTV measured at 0.12%Obs/m (0.037%Obs/ft) alarm level.
• ASD units configured and flow rates validated with respective manufacturers’ software tools (Table 5).
ASD Configuration Pipe Modelling
VLI-880 VSC 3.04.03 (S/W) ASPIRE2 2.04
SecuriRAS ASD 535-3 ASD Config 01.01.00 (S/W) ASD Pipeflow 2.0.4.3
FAAST 8100 PipeIQ 1.2.0 (S/W) PipeIQ 1.2.0
TITANUS PRO SENS (detector module)
Switch settings (DIP) –
Installation Instruction Manual Not Available
Table 5: ASD Configuration / Pipe Modelling Tools
4.6 Test Instruments Test instruments for the investigation are outlined in Table 6.
Instrument Measurand Model Serial No. Calibration
DustTrack Dust Chamber dust concentration
8250 85201887 APPENDIX A
DustTrack ASD Inlet dust concentration 8250 23390
Calibrated against Dust Chamber DustTrack (APPENDIX D)
VelociCalc Plus Pipe airflow
8386A-M-GB 02080484 APPENDIX B
VESDA Smoke concentration VLC-505 8417637 Factory calibrated
Table 6: Test Instruments
4.7 Test Dust • ASHRAE 52/76 test dust referenced in ANSI/ASHRAE Standard 52.2-2007 “Method of Testing
General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size” – see
APPENDIX C for calibration certificate. This type of dust was chosen as it is used for the
loading of ventilation filters to simulate accumulation of particulate over service life and is representative of common dust types present in commercial and industrial environments.
• Dust concentration per loading: 10-40mg/m3.
4.8 Test Smoke • The test smoke was smouldering cotton lamp wick (grey smoke) referenced in UL268 Standard
“Smoke Detectors for Fire Alarm Systems” (2009), Section 30 – Sensitivity Test.
• The smouldering of the cotton lamp wick occurred inside the Smoke Generation Box and smoke was gradually introduced to the Smoke Chamber.
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 9 of 29
5. TEST PROCEDURE
5.1 Test Cycle A total of 14 test cycles were conducted. Each test cycle comprised dust loading of detectors, measurement of detectors sensitivity, functional checks and service/corrective actions (where required)
according to the sequence in Figure 5.
Figure 5: Test Cycle Steps
Note: An additional test cycle (#15) was conducted for the SecuriRAS ASD 535-3 unit to ascertain
sensitivity improvement with internal filter replacement.
Dust loading parameters are included in APPENDIX D.
Throughout all steps a log was maintained of ASD faults / failures and corrective actions. A replacement dust track was utilised for the
Maintenance schedule:
• At the end of each test cycle maintenance was performed on the DustTrack instrument (filter replaced, capillary cleaned, flow check, zero check).
• At end of each test cycle the Dust Chamber was cleaned and ASD pipe work purged with compressed air to clean orifices and remove dust deposits.
• Smoke reference unit (VESDA VLC-505) internal filter replaced at the end of test cycles 3, 7, 11.
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 10 of 29
5.2 Sensitivity (Detection Performance) The impact of dust sampling on detectors sensitivity (detection performance) was determined by
measuring each ASD unit Response Threshold Value (RTV) after each dust loading. The RTV is the
amount of smoke concentration the ASD is subjected to in order to generate an alarm signal according to EN54 Standard “Fire Detection and Fire Alarm Systems – Part 20: Aspirating Smoke Detectors. A change
in RTV therefore will entail a change in detector sensitivity. For example when the sensitivity of the ASD
deteriorates its RTV will increase i.e. greater amount of smoke concentration will be required for the ASD
to generate an alarm signal.
The initial baseline ASD sensitivity was determined (ASD out of box) and subsequent measurements
after each dust load were normalised against this baseline to ascertain impact on detectors’ sensitivity
(see APPENDIX E for calculation method).
For the RTV measurements, the ASD units were subjected to a slowly increasing smoke concentration at
a rate that allowed an alarm to be issued between 2 to 10 min from start of test. The ASDs’ RTV was
provided by the reference smoke detector (VESDA VLC-505) that was only operational during the smoke
tests.
5.3 Pass/Fail Criteria The following conditions constituted a failure:
• 50% reduction in ASD sensitivity. For a 50% reduction in sensitivity the ASD requires double the
amount of smoke concentration to issue an alarm signal.
• ASD hardware faults and failures (non-field maintainable items).
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 11 of 29
6. RESULTS 6.1 ASD Sensitivity (Detection Performance) Figure 6 depicts the trend lines of sensitivity (normalised) reduction for each ASD unit throughout the dust loading cycles along with the chronology of critical fault and maintenance indicators. Table 8 lists the
details of the fults and maintenance indicators and detailed normalised sensitivity results are included in
APPENDIX F.
0
20
40
60
80
100
120
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
ASD Sensitivity -Normalised (%)
Dust Loading Cycle
VLI - 880 SecuriRAS ASD535-3 FAAST 8100 TITANUS PRO SENS
TITANUS PRO SENS Hardware M odule Failure - M odule not replaced
FAAST 8100 Filter Fault - Filter replaced
FAAST 8100 Aspirator Fault - Aspirator replaced
Figure 6: ASD sensitivity (normalised) trend lines with critical fault and maintenance indicators
The following are noted:
• All ASD units except the Xtralis VLI-800 recorded a 50% reduction in sensitivity. The Xtralis VLI-880 sensitivity for the same loading characteristics was reduced by approximately 10%.
• The TITANUS PRO SENSE issued a detector module failure during the first dust loading cycle.
• The FAAST 8100 unit issued multiple filter and aspirator faults.
• No notification was issued by the SecuriRAS ASD 535-3 unit for a 50% reduction in sensitivity.
50% drop in sensitivity
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 12 of 29
6.2 ASD Hardware Faults and Failures
6.2.1 Filter Faults
Where detectors exhibited field rectifiable faults, most commonly Filter Faults, the recommended field
maintenance was carried out as per the manufacturer’s instruction.
FAAST 8100:
From Figure 6 the FAAST 8100 unit issued four Filter Faults – fault conditions were not cleared with
detector RESET. As per manufacturer’s “Installation and Maintenance Instructions” document #I56-3630-
000 (2010), this fault indicates the device filter is clogged and requires replacement. This is a field
replacement items and in each fault condition the filter cartridge was replaced with new as per prescribed maintenance. This action did not restore the detector sensitivity.
SecuriRAS ASD 535-3:
Though the SecuriRAS ASD 535-3 has no filter status reporting function, the detector filters (metallic mesh before and after smoke sensor) were replaced with new to ascertain improvement in sensitivity.
The detector was subject to an additional dust loading cycle (#15) and its sensitivity was ascertained both
with the “loaded” and new filters (Figure 7). Replacement with new filters did not improve the detector
sensitivity as seen from Table 7.
Loaded Filter – before smoke sensor
Loaded Filter – after smoke sensor
New Filter
Figure 7: SecuriRAS ASD 535-3 Filters (metallic mes h)
Dust Loading 15 Normalised Sensitivity (%)
Loaded Filters 50
New Filters 51
Table 7: SecuriRAS ASD 535-3 Sensitivity Change wit h Filter Replacement
6.2.2 Critical Failures
From Figure 6 two ASD units (TITANUS PRO SENS, FAAST 8100) exhibited critical failures that would
require the unit to be replaced or returned for service.
1. TITANUS PRO SENS: Unit suffered “Detector Module Hardware Defect” during the first
loading cycle – fault condition was not cleared with detector RESET. According to the manufacturer’s
technical manual “Air Sampling Smoke Detection System TITANUS PROSENS” doc #69-30-0226
(2009), the detector module requires immediate replacement. This is a field serviceable item. Since only one detector module was available, testing continued for 4 dust loading cycles (unit was able to
detect smoke) despite manufacturer’s recommendation to have the detector module replaced.
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 13 of 29
2. FAAST 8100: Unit suffered frequent “Aspirator Faults”. The aspirator ceased operation a
total of 4 times in the course of testing which rendered it incapable of detecting smoke – all fault conditions were not cleared with detector RESET. According to the manufacturer’s “Installation and
Maintenance Instructions” doc #I56-3630-000 (2010), this fault indicates the fan has stopped working
and requires immediate attention. While this is not a field maintenance item for the purpose of this
investigation the faulty aspirators were replaced with new. In practice, however, each failure would
have necessitated the unit be replaced or returned for service.
ASD Fault Type Timeline Comments Corrective Actions
TITANUS PRO SENS
Detector Module Defect
2hr into dust loading #1 Detector module fault LED permanently lit
Field maintenance item Module not replaced. Fault condition maintained for remainder of test cycles
Prior to dust loading #3
Prior to dust loading #5
2hr into dust loading #11 Filter Fault
End dust loading #13
Filter fault LED permanently lit
Field maintenance item For every fault condition new filter inserted.
End of dust loading #3
1.5hr into dust loading #7
2hr into dust loading #11
FAAST 8100
Aspirator Fault
End dust loading #13
Aspirator fault LED permanently lit. Aspirator ceased operation
Non field maintenance item For every fault condition faulty aspirator replaced.
Table 8: ASD Faults Timeline / Corrective Actions
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 14 of 29
7. CONCLUSIONS Performance and reliability testing was conducted on four ASD units operating in a dust-laden
environment.
For the purpose of this investigation all ASD units were installed and configured identically (flow rate,
alarm threshold, alarm delay) and subject to identical dust loading conditions.
The findings and observations from this investigation are summarised below:
ASD Sensitivity (Detection Performance) Degradation:
Over the duration of testing significant trends were observed in ASDs’ sensitivity. Notably:
• All ASD units except the Xtralis VLI-880 experienced sensitivity degradation of more than 50%
(Table 9).
• The Xtralis VLI-880 sensitivity for the same loading characteristics was reduced by less than 10%.
• No notification was issued by the SecuriRAS ASD 535-3 unit for a 50% reduction in sensitivity.
ASD Time to 50% sensitivity drop
Sensitivity drop at end of 14 th dust cycle
VLI-880 Did not fail 10%
SecuriRAS ASD 535-3 14 cycles 50%
FAAST 8100 10 cycles 55%
TITANUS PRO SENS 4 cycles 55%*
Table 9: ASD Sensitivity Degradation
* TITANUS PRO SENS data presented for only 4 dust cycles since the detector sensitivity by that stage had reduced by more than 50%.
ASD Maintenance:
• The FAAST 8100 unit issued four filter maintenance notifications. When prescribed manufacturer’s maintenance was performed the sensitivity of the unit was not restored.
• Though the SecuriRAS ASD 535-3 unit had no filter status reporting function, replacing the heavily soiled “loaded” filters with new showed no improvement of detector sensitivity.
ASD Critical Failures: Two ASD units exhibited critical failures requiring repair:
• TITANUS PRO SENS – One “Detector Module” failure notification was issued during the first dust
loading cycle. This is a field maintenance item.
• FAAST 8100 – Four “Aspirator Fault” failures occurred. The first fault occurred after the second dust
loading cycle. This is not a field maintenance item and requires the unit to be replaced or returned to
the manufacturer for service.
A critical attribute of fire detection systems is that the system performance be maintained within
acceptable and expected bounds over the operational life of the product. While no specific comment is
made on the design of any particular ASD product tested, the results presented can be considered
significant and should be taken into consideration when selecting an ASD product for deployment in harsh (dust-laden) environments if reliable detector operation is to be maintained.
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 15 of 29
APPENDIX A DustTrack (Dust Chamber) Calibration Certificate
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 16 of 29
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 17 of 29
APPENDIX B VelociCalc Plus Air Velocity Meter (TSI) Calibration
Methodology The VelociCalc Plus air velocity hot anemometer meter was calibrated in-series with the Laminar Flow
Element (below schematic).
Instruments • Laminar Flow Meter: FC0318 DP Transmitter + Flow Element (Furness Controls Ltd). UKAS
Accredited Calibration Laboratory No.0580, Calibration Certificate No. 06632.
o Flow Element Serial Number: 1007175
o Transmitter Serial Number: 1007173
• VelociCalc Plus Air Velocity Meter (TSI): Model: 8386A-M-GB, Serial Number: 02080484
Test Ambient Conditions
• Ambient Temperature: 20°C (68°F)
• Relative Humidity: 40-60%RH
Laminar Flow Element
VelociCalc Plus
Air Flow
0.3m 0.3m 0.3m
FAN
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 18 of 29
Comparison Results
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 19 of 29
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 20 of 29
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 21 of 29
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 22 of 29
APPENDIX C ASHRAE 52/76 Calibration Certificate
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 23 of 29
APPENDIX D DustTrack Loading Analysis
Data logging Interval
Averaging time for data points
Data points per Loading (3.5 hrs)
1 minute 10 seconds 210
Table 10: DustTrak Settings
Dust Loading Cycle
Min (mg/m 3)
Mean (mg/m 3)
Max (mg/m 3)
SDEV (σ)
1 0.123 18.951 27.517 3.757
2 7.529 18.516 29.022 2.947
3 0.028 15.923 22.467 2.646
4 6.054 16.589 24.172 2.637
5 2.047 16.084 22.675 2.737
6 10.308 15.206 23.014 2.644
7 3.787 15.446 29.873 3.579
8 6.074 16.031 25.495 2.574
9 3.441 16.031 23.368 2.817
10 6.006 14.788 23.974 3.048
11 12.66 19.882 27.855 3.119
12 0.303 20.296 20.296 6.879
13 8.854 23.658 30.967 3.301
14 14.199 35.684 94.167 8.858
15 7.164 33.291 62.737 7.569
Table 11: Dust Loading Analysis
DustTrack 85201887 Average concentration
(mg/m 3)
DustTrack 23390 Average concentration
(mg/m 3)
22.84 22.79
Table 12: DustTrack Comparison Average Reading
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 24 of 29
Dusttrak Loading cycles 1 - 10
0
5
10
15
20
25
30
35
40
45
50
0 50 100 150 200 250
Data Points
Con
cent
ratio
n m
g/m
3
Loading 1 Loading 2 Loading 3 Loading 4 Loading 5 Loading 6 loading 7 Loading 8 Loading 9 Loading 10
Mean - 16.313
Figure 8: Summary Graph Dust Loading 1 - 10
Figure 9: Summary Graph Dust Loading 11 - 13
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 25 of 29
Dust trak loading cycles 14-15
0
10
20
30
40
50
60
70
80
90
100
0 50 100 150 200 250
Data Points
conc
entr
atio
n m
g/m
3
Loading 14 Loading 15
Mean - 34.470
Figure 10: Summary Graph Dust Loading 14 - 15
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 26 of 29
APPENDIX E Sensitivity (Normalised) Calculation
The normalized sensitivity after each dust loading was calculated as follows:
RTVN: Normalised sensitivity
RTV0: Baseline. Average of two RTV measurements (%Obs/m) taken for ASD out of box
RTVn: Average of two RTV measurements (%Obs/m) following dust loading
Example:
• RTVN = 100 � Baseline (ASD out of box)
• RTVN = 67 � 33% reduction in sensitivity � ASD requires x1.5 the amount of smoke concentration compared to baseline for alarm condition
• RTVN = 50 � 50% reduction in sensitivity � ASD requires x2 the amount of smoke concentration compared to baseline for alarm condition
1000 ×=
n
NRTV
RTVRTV
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 27 of 29
APPENDIX F Detailed Test Results – Individual ASD Units
VLI - 880 FAAST 8100 SecuriRAS
ASD535 TITANIUS PRO
SENS
Baseline (ASD out of box)
Smoke Test 1 (%/m) 0.211 0.460 0.318 0.297
Smoke Test 2 (%/m) 0.195 0.490 0.332 0.280
Average RTV 0 (%/m) 0.203 0.475 0.325 0.289
RTVN (%) 100 100 100 100
Dust Loading 1
Smoke Test 1 (%/m) 0.249 0.560 0.366 0.366
Smoke Test 2 (%/m) 0.170 0.556 0.388 0.417
Average RTV 1 (%/m) 0.210 0.558 0.377 0.392
RTVN (%) 97 85 86 74
Dust Loading 2
Smoke Test 1 (%/m) 0.213 0.671 0.37 0.448
Smoke Test 2 (%/m) 0.210 0.666 0.392 0.494
Average RTV 2 (%/m) 0.212 0.669 0.381 0.471
RTVN (%) 96 71 85 61
Dust Loading 3
Smoke Test 1 (%/m) 0.187 0.648 0.386 0.520
Smoke Test 2 (%/m) 0.195 0.702 0.424 0.484
Average RTV 3 (%/m) 0.191 0.680 0.405 0.502
RTVN (%) 106 70 80 57
Dust Loading 4
Smoke Test 1 (%/m) 0.199 0.722 0.471 0.595
Smoke Test 2 (%/m) 0.227 0.603 0.468 0.663
Average RTV 4 (%/m) 0.213 0.663 0.470 0.629
RTVN (%) 95 72 69 46
Dust Loading 5
Smoke Test 1 (%/m) 0.197 0.631 0.450 NT*
Smoke Test 2 (%/m) 0.189 0.722 0.458 NT
Average RTV 5 (%/m) 0.193 0.677 0.454
RTVN (%) 105 70 72
Dust Loading 6
Smoke Test 1 (%/m) 0.249 0.814 0.470 NT
Smoke Test 2 (%/m) 0.190 0.716 0.476 NT
Average RTV 6 (%/m) 0.220 0.765 0.473
RTVN (%) 92 62 69
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 28 of 29
VLI - 880 FAAST 8100 SecuriRAS
ASD535 TITANIUS PRO
SENS
Dust Loading 7
Smoke Test 1 (%/m) 0.198 0.738 0.510 NT
Smoke Test 2 (%/m) 0.245 0.852 0.503 NT
Average RTV 7 (%/m) 0.222 0.795 0.507
RTVN (%) 92 60 64
Dust Loading 8
Smoke Test 1 (%/m) 0.248 1.008 0.514 NT
Smoke Test 2 (%/m) 0.231 0.817 0.513 NT
Average RTV 8 (%/m) 0.240 0.913 0.514
RTVN (%) 85 52 63
Dust Loading 9
Smoke Test 1 (%/m) 0.219 0.765 0.608 NT
Smoke Test 2 (%/m) 0.208 0.830 0.575 NT
Average RTV 9 (%/m) 0.214 0.798 0.592
RTVN (%) 95 60 55
Dust Loading 10
Smoke Test 1 (%/m) 0.199 1.015 0.508 NT
Smoke Test 2 (%/m) 0.262 0.965 0.498 NT
Average RTV 10 (%/m) 0.231 0.990 0.503
RTVN (%) 88 48 65
Dust Loading 11
Smoke Test 1 (%/m) 0.257 1.008 0.549 NT
Smoke Test 2 (%/m) 0.263 0.982 0.605 NT
Average RTV 11 (%/m) 0.260 0.995 0.577
RTVN (%) 78 48 56
Dust Loading 12
Smoke Test 1 (%/m) 0.213 0.838 0.593 NT
Smoke Test 2 (%/m) 0.229 0.907 0.59 NT
Average RTV 12 (%/m) 0.221 0.873 0.592
RTVN (%) 92 54 55
Dust Loading 13
Smoke Test 1 (%/m) 0.219 0.999 0.606 NT
Smoke Test 2 (%/m) 0.214 1.000 0.590 NT
Average RTV 13 (%/m) 0.217 1.000 0.598
RTVN (%) 94 48 54
Dust Loading 14
Smoke Test 1 (%/m) 0.200 1.090 0.678 NT
Smoke Test 2 (%/m) 0.212 1.024 0.642 NT
Average RTV 14 (%/m) 0.206 1.057 0.660
RTVN (%) 99 45 49
Vipac Reference: 30V-11-0424-TRP- 264755-0
ASD – Performance and Reliability Testing in Dust Laden Environment Page 29 of 29
VLI - 880 FAAST 8100 SecuriRAS
ASD535 TITANIUS PRO
SENS
Dust Loading 15 – Loaded Filters
Smoke Test 1 (%/m) NT NT 0.651 NT
Smoke Test 2 (%/m) NT NT 0.650 NT
Average RTV 15 (%/m) 0.651
RTVN (%) 50
Dust Loading 15 – New Filters
Smoke Test 1 (%/m) NT NT 0.625 NT
Smoke Test 2 (%/m) NT NT 0.650 NT
Average RTV 15 (%/m) 0.638
RTVN (%) 51
NT: Not Tested
Table 13: Detailed Results: Smoke Tests / Normalise d Sensitivity