Test on Transformer

Embed Size (px)

Citation preview

  • 7/30/2019 Test on Transformer

    1/13

    Test on transformerTesting of Transformers The structure of the circuit

    equivalent of a practical transformer is developed earlier.

    The performance parameters of interest can be obtained by

    solving that circuit for any load conditions. The equivalent

    circuit parameters are available to the designer of the

    transformers from the various expressions that he uses for

    designing the transformers. But for a user these are notavailable most of the times. Also when a transformer is

    rewound with different primary and secondary windings the

    equivalent circuit also changes. In order to get the

    equivalent circuit parameters test methods are heavily

    depended upon. From the analysis of the equivalent circuit

    one can determine the electrical parameters. But if thetemperature rise of the transformer is required, then test

    method is the most dependable one.

    There are several tests that can be done on the

    transformer :-

    1.Winding resistance test2. Polarity Test

    3 .Open Circuit Test

    4 .Short Circuit Test

    5. Dvdf Test

    6. Hv Test

    7. T.T.R Test

  • 7/30/2019 Test on Transformer

    2/13

    1. Winding resistance test:-

    Winding resistance measurements in transformers are

    of fundamental importance for the following purposes:- Calculations of the I2R component of conductor

    losses.- Calculation of winding temperature at the end of a

    temperature test cycle.- As a base for assessing possible damage in the field.

    Transformers are subject to vibration. Problems orfaults occur due to poor design, assembly, handing,poor environments, overloading or poor maintenance.Measuring the resistance of the windings assures that

    the connections are correct and the resistance

    measurements indicates that there are no severemismatches or opens. Many transformers have tapsbuilt into them. These taps allow ratio to be increased

    or decreased by fractions of a percent. Any of theratio changes involve a mechanical movement of a

    contact from one position to another. These tapchanges will also be checked during a winding

    resistance test.Regardless of the configuration either wye or delta,

    the measurements are made phase to phase andcomparisons are made to determine if the readings

    are comparable. If all readings are within one percentof each other, then they are acceptable. Keep in mindthat the purpose of the test is to check for gross

    differences between the windings and for opens in theconnections. The tests are not made to duplicate the

  • 7/30/2019 Test on Transformer

    3/13

    readings of the manufactured device which was testedin the factory under controlled conditions and perhapsat other temperatures

    2. Polarity Test:-

    transformer polarity test are used two know about the

    poalrity of a transformers .for these purpose to

    transformer are used and his low voltage winding and

    high voltage winding are coonected in parallel to each

    other the secondary windings of a transformer which

    has commonly high voltage winding fuse are

    connected to his secondary side of a transformer a manpoint to be noted here that a wire used for fuse are so

    small rating similarly when the polarity of

    autotransformer same no current will be flow as a

    reason the dont blow. otherwise when the polarity are

    different the current will be flow and fuse will be blow

    out

  • 7/30/2019 Test on Transformer

    4/13

    3. Open Circuit Test

    Method :-

    The secondary of the transformer is left open-circuited. A

    wattmeter is connected to the primary. An ammeter is

    connected in series with the primary winding. A voltmeter

    is optional since the applied voltage is same as the

    voltmeter reading. Rated voltage is applied at primary.

    If the applied voltage is normal voltage then normal fluxwill be set up. As the Iron loss is a function of applied

    voltage, normal iron loss will occur. Hence the iron loss is

    maximum at rated voltage. This maximum iron loss is

    measured using the wattmeter. Since the impedance of the

    series winding of the transformer is very small compared to

    that of the excitation branch, all of the input voltage isdropped across the excitation branch. Thus the wattmeter

    measures only the iron loss. It should be noted that the iron

    losses consist of the hysteresis loss and the eddy current

    loss. This test only measures the combined loss. Although

    the hysteresis loss is less than the eddy current loss, it is not

    negligible. The two losses can be separated by driving the

    transformer from a variable frequency source since thehysteresis loss varies linearly with supply frequency and the

    eddy current loss varies with the square.

    Since the secondary of the transformer is open, the

    primary draws only no load current which will have

    some copper loss. This no load current is very small

    and because the copper loss in the primary is

  • 7/30/2019 Test on Transformer

    5/13

    proportional to the square of this current, it is

    negligible. There is no copper loss in the secondary

    because there is no secondary current.

    Current, voltage and power are measured at the

    primary winding to ascertain the admittance and powe

    factor angle.

    Another method of determining the series impedance

    of a real transformer is the short circuit test.

    Calculation:-

    The current is very small.

    If is the wattmeter reading then,

    The above equation can be rewritten as,

    http://en.wikipedia.org/wiki/File:Open_circuit_test.png
  • 7/30/2019 Test on Transformer

    6/13

    Thus,

    Impedance:-

    By using the above equations, and can be

    calculated as,

    Thus,

    or

    Admittance:-

    The admittance is the inverse of impedance. Therefore,

    The conductance can be calculated as,

  • 7/30/2019 Test on Transformer

    7/13

    Hence the suspectance,

    or

    Here,

    is the wattmeter reading

    is the applied rated voltage

    is the no load current

    is the magnetizing component of no load current

    is the core loss component of no load current

    is the exciting impedance

    is the exciting admittance

    4.Short Circuit Test:-

  • 7/30/2019 Test on Transformer

    8/13

    The test is conducted on the high voltage (HV) side of

    the transformer where the low voltage (LV) side or thesecondary is short circuited. The supply voltage

    required to circulate rated current through the

    transformer is usually very small and is of the order of

    a few percent of the nominal voltage and this voltage

    is applied across primary. The core losses are very

    small because applied voltage is only a few percentage

    of the nominal voltage and hence can be neglected.Thus the wattmeter reading measures only the full load

    copper loss.

    Procedure:-

    http://en.wikipedia.org/wiki/File:Short_Circuit_test.jpg
  • 7/30/2019 Test on Transformer

    9/13

    For carrying short circuit test on power transformer:-

    1. Isolate the power transformer from service.

    2. Remove HV/LV jumps and disconnect neutralfrom earth/ground.

    3. Short LV phases and connect these short circuited

    terminals to neutral

    4. Energise HV side by LV supply.

    5. Measure current in neutral, LV line voltages, HV

    voltage and HV line currents

    Calculations:-

    is the Full load copper loss

    is the applied voltage

    is the rated current

    is the resistance as viewed from the primary

    is the total impedance as viewed from the primaryis the reactance as viewed from the primary

  • 7/30/2019 Test on Transformer

    10/13

    Analysis:-

    If neutral current is near to zero transformer windings

    are operational.

    If neutral current is higher or equal to line current

    between LV phase one of the winding is open.

    5. Dvdf Test:-

  • 7/30/2019 Test on Transformer

    11/13

    The DVDF (double voltage double frequency) test is

    an overvoltage withstand test. It is performed byapplying a higher than nominal voltage (2 times) to the

    transformer for a relatively short period of time

    (usually 1 minute). Since a prolonged (significant)

    overvoltage will cause the transformer to overexcite,

    the volts per hertz are kept constant by applying a

    higher than nominal frequency (2 times in this case).

  • 7/30/2019 Test on Transformer

    12/13

    6. Hv Test:-

    Seperate source voltage withstand test (High Voltagetests on HV & LV). This test checks the insulation

    property between Primary to earth, Secondary to earth

    and between Primary & Secondary.

    HV high voltage test:-LV winding connected together

    and earthed. HV winding connected together and given28 KV ( for 11KV transformer) for 1 minute.

    LV high Voltage test :- HV winding connected

    together and earthed. LV winding connected together

    and given 3 KV for 1 minute.

    Equipment used:-High Voltage tester ( 100 KV &3KV).

  • 7/30/2019 Test on Transformer

    13/13