Upload
lamphuc
View
216
Download
2
Embed Size (px)
Citation preview
IN THIS SECTION
- Test & Balance
HA~RISAIRSYSTE1V1S, INC.
Heat;inB &...-Air Condit;ioninBInst;allat;ion &...-5ervice
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480
Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITES DATE:
PAGE:
2/22/2012
UNIT NO. MAU-1 MAU-2 FC-1
LOCATION ROOF ROOF POOL CEILING
MANUFACTURER ARES ARES JOHNSON CONTROLS
MODEL NO. SE2A BADE SE2A BADE NC090COOC6ATJ2A
SERIAL NO. A7751 A7752 N1H1273465
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTAL CFM 2520 2299 3340 3075 3000 2996
RETURN CFM - - - - 1470 1501
OUTSIDE CFM 2520 2299 3340 3075 1530 1495
EXT.STATIC PRESS .50"
TOT.STATIC PRESS. 040" AD" .90"
SUCTION PRESS. .15" .10" .80"
DISCHARGE PRESS. .25" .30" .10"
FAN SHEAVE AK144 1" AK144 1" AK56 1"
MOTOR SHEAVE 1VL30 5/8" 1VM40 5/8" 1VL40 7/8"
BELTS AX66 A68 A44
MOTOR MANUFCTR. BALDOR BALDOR MARATHON
SIZE 3/4 3/4 2.0
VOLTAGE 120 121 120 121 460 208,210,208
PHASE 1 1 1 1 3 3
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1786 1725 1781 1725 1580
AMPERAGE 10.2 9.2 10.2 9.5 6.8 3.3, 3.1, 3,0
RPM FAN 304 318 902
FILTER DROP/COIL 040"
COIL DROP
HTG DISCH. TEMP.
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480
Fax: (801) 282·3557
JOB NAME: SPRING HILL SUITES DATE:
PAGE:
2/22/2012
2
UNIT NO. EF-1 (2) EF-1 (04) EF-1 (06) EF-1 (08)
LOCATION ROOF ROOF ROOF ROOF
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. G-085-VG-4-X G-085-VG-4-X G-085-VG-4-X G-085-VG-4-X
SERIAL NO. 12534323-1108 12534314-1108 12534324-1108 12534321-1108
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTAL CFM 270 345 270 345 270 383 270 330
RETURN CFM 270 345 270 345 270 383 270 330
OUTSIDE CFM - - - - - - - -
EXT.STATIC PRESS - - - -
TOT.STATIC PRESS. - - - -
SUCTION PRESS. .28" .29" .25" .27"
DISCHARGE PRESS. - - - -
FAN SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR MANUFCTR. GREENHECK GREENHECK GREENHECK GREENHECK
SIZE 1/4 1/4 1/4 1/4
VOLTAGE 115 120 115 120 115 120 115 120
PHASE 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1708 1725 1728 1725 1714 1725 1719
AMPERAGE 3.9 .9 3.9 1.0 3.9 1.0 3.9 .9
RPM FAN 1708 1728 1714 1719
FILTER DROP/COIL
COIL DROP
SF
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480
Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITES DATE: 2/22/2012
PAGE: 3
UNIT NO. EF-1 (10) EF-1 (12) EF-1 (14) EF-2 (16)
LOCATION ROOF ROOF ROOF ROOF
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. G085-VG-4-X G085-VG-4-X G085-VG-4-X G085-VG-4-X
SERIAL NO. 12534320-1108 12534316-1108 12534309-11 08 12534319-1108
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTALCFM 270 346 270 297 270 340 360 448
RETURN CFM 270 346 270 297 270 340 360 448
OUTSIDE CFM - - - - - - - -
EXT.STATIC PRESS - - - -
TOT.STATIC PRESS. - - - -SUCTION PRESS. .26" .25" .21" .20"
DISCHARGE PRESS. - - - -
FAN SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR MANUFCTR. GREENHECK GREENHECK GREENHECK GREENHECK
SIZE 1/4 1/4 1/4 1/4
VOLTAGE 115 120 115 120 115 120 115 120
PHASE 1 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1728 1725 1728 1725 1701 1725 1691
AMPERAGE 3.9 1.0 3.9 1.0 3.9 .9 3.9 .9
RPM FAN 1728 1728 1701 1691
FILTER DROP/COIL
COIL DROP
---~-- ---
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480
Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITES DATE:
PAGE:
2/22/2012
4
UNIT NO. EF-2 (18) EF-2 (20) EF-2 (22) EF-2 (24)
LOCATION ROOF ROOF ROOF ROOF
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. G-095-VG-4-X G-095-VG-4-X G-095-VG-4-X G-095-VG-4-X
SERIAL NO. 12534338-11108 12534326-1108 12534328-1108 12534331-1108
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTALCFM 360 465 360 481 360 502 360 469
RETURN CFM 360 465 360 481 360 502 360 469
OUTSIDE CFM - - - - - - - .
EXT.STATIC PRESS - - - -
TOT.STATIC PRESS. - - - -
SUCTION PRESS. .25" .24" .21" .18"
DISCHARGE PRESS. - - - -
FAN SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR MANUFCTR. GREENHECK GREENHECK GREENHECK GREENHECK
SIZE 1/4 1/4 1/4 1/4
VOLTAGE 115 120 115 120 115 120 115 120
PHASE 1 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1723 1726 1721 1725 1718 1725 1717
AMPERAGE 3.9 1.5 3.9 1.4 3.9 1.6 3.9 1.4
RPM FAN 1723 1721 1718 1717
FILTER DROP
COIL DROP
AIR WASH
--------------------- ----------_ .._----
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11677 So. Lampton View Drive
So. Jordan, UT 84096Ph: (801) 282-3480
Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITES DATE: 2/22/2012
PAGE: 5
UNIT NO. EF-2 (26) EF-2 (28) EF-2 (80) EF-2 (32)
LOCATION ROOF ROOF ROOF ROOF
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. G-095-VG-4-X G-095-VG-4-X G-095-VG·4-X G-095-VG-4-X
SERIAL NO. 12534329-1108 12534342-1108 12534343-1108 12534336-1108
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTAL CFM 360 524 360 426 360 405 360 442
RETURN CFM 360 524 360 426 360 405 360 442
OUTSIDECFM - - - - - - - .
EXT.STATIC PRESS - - - -
TOT.STATIC PRESS. - - - -SUCTION PRESS. .16" .21" .20" .17"
DISCHARGE PRESS. - - - -
FAN SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR MANUFCTR. GREENHECK GREENHECK GREENHECK GREENHECK
SIZE 3/4 3/4 3/4 3/4
VOLTAGE 115 120 115 120 115 120 115 120
PHASE 1 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1715 1725 1722 1725 1708 1725 1694
AMPERAGE 3.9 1.3 3.9 1.4 3.9 1.5 3.9 1.5
RPM FAN 1715 1722 1708 1694
FILTER DROP
COIL DROP
AIR WASH
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480
Fax: (801) 282·3557
JOB NAME: SPRING HILL SUITES DATE:
PAGE:
2/22/2012
6
UNIT NO. EF-2 (35) EF-2 (33) EF-2 )31) EF-2 (29)
LOCATION ROOF ROOF ROOF ROOF
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. G-095-VG-4-X G-095-VG-4-X G-095-VG-4-X G-095-VG-4-X
SERIAL NO. 12534334-1108 12534339-1108 12534345-1108 12534341-1108
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTAL CFM 360 507 360 443 360 464 360 503
RETURN CFM 360 507 360 443 360 464 360 503
OUTSIDE CFM - - - - - - - -
EXT.STATIC PRESS - - - -
TOT.STATIC PRESS. - - - -SUCTION PRESS. .22" .21" .19" .20"
DISCHARGE PRESS. - - - -
FAN SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR MANUFCTR. GREENHECK GREENHECK GREENHECK GREENHECK
SIZE 1/4 1/4 1/4 1/4
VOLTAGE 115 120 115 120 11 5 120 115 120
PHASE 1 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1730 1725 1721 1725 1714 1725 1711
AMPERAGE 3.9 1.5 3.9 1.5 3.9 1.4 3.9 1.2
RPM FAN 1730 1721 1714 1711
FILTER DROP
COIL DROP
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480
Fax: (801) 282·3557
JOB NAME: SPRING HILL SUITES DATE:
PAGE:
2/22/2012
7
UNIT NO. EF-2 (27) EF-2 (25) EF-2 (23) EF-2 (21)
LOCATION ROOF ROOF ROOF ROOF
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. G-095-VG-4-X G-095-VG-4-X G-095-VG-4-X G-095-VG-4-X
SERIAL NO. 12534335-1108 12534333-1108 12534344-1108 12534330-1108
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTAL CFM 360 540 360 541 360 551 360 526
RETURN CFM 360 540 360 541 360 551 360 526
OUTSIDE CFM - - - - - - - -
EXT.STATIC PRESS - - . -
TOT.STATIC PRESS. - - - .
SUCTION PRESS. .17" .20" .16" .18"
DISCHARGE PRESS. - - - -
FAN SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR MANUFCTR. GREENHECK GREENHECK GREENHECK GREENHECK
SIZE 1/4 1/4 1/4 1/4
VOLTAGE 115 120 115 120 115 120 115 120
PHASE 1 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1708 1725 1694 1725 1708 1725 1702
AMPERAGE 3.9 1.5 3.9 1.4 3.9 1.5 3.9 1.2
RPM FAN 1708 1694 1708 1702
FILTER DROP/COIL
COIL DROP
HTG DISCH. TEMP.
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480
Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITES DATE: 2/22/2012
PAGE: 8
UNIT NO. EF-2 (19) EF-1 (17) EF-1 (15) EF-4
LOCATION ROOF ROOF ROOF ROOF
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. G-095-VG-4-X G-095-VG-4-X G-095-VG-4-X S-CUBE-240-10-F
SERIAL NO. 12534325-1108 12534340-1108 12534337-1108 12514322-1107
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTALCFM 360 551 270 329 270 389 6270 4460
RETURN CFM 360 551 270 329 270 389 6270 4460
OUTSIDECFM - - - - - - - -
EXT.STATIC PRESS - - - -
TOT.STATIC PRESS. - - - -
SUCTION PRESS. .17" ,29: ,19" -
DISCHARGE PRESS. - - - -
FAN SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE 1" 2AK74DIRECT
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DRIVE 5/8" 2VP36
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE 2@ AP30
MOTOR MANUFCTR. GREENHECK GREENHECK GREENHECK WEG
SIZE 1/4 1/4 1/4 1
VOLTAGE 115 120 115 120 115 120 115 120
PHASE 1 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1730 1725 1706 1725 1704 1740
AMPERAGE 3.9 1.2 3.9 1.4 3.9 1.4 14.0
RPM FAN 1730 1706 1704
FILTER DROP/COIL
COIL DROP
SF
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480
Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITES DATE:
PAGE:
2/22/2012
9
UNIT NO. EF-3 EF-1 (11) EF-1 (09) EF- (07)
LOCATION ROOF ROOF ROOF ROOF
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. S-CUBE-200-7-F G-085-VG-4-X G-085-VG-4-X G-085-VG-4-X
SERIAL NO. 12514321-1107 12534312-1108 12534315-1108 12534313-1108
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTAL CFM 4435 4255 270 335 270 345 270 324
RETURN CFM 4435 4255 270 335 270 345 270 324
OUTSIDE CFM - - - - - - - -
EXT.STATIC PRESS - - - -
TOT.STATIC PRESS. - - - -
SUCTION PRESS. .19" .20" .16"
DISCHARGE PRESS. - - -
FAN SHEAVE 3/4" 2AK64 DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR SHEAVE 5/8" 2VP36 DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS 2@ AP26 DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR MANUFCTR. WEG GREENHECK GREENHECK GREENHECK
SIZE 3/4 1/4 1/4 1/4
VOLTAGE 115 120 115 120 115 120 115 120
PHASE 1 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1745 1725 1716 1725 1707 1725 1711
AMPERAGE 10.8 3.9 .9 3.9 .9 3.9 .9
RPM FAN 1716 1707 1711
FILTER DROP/COIL
COIL DROP
AIR MOVING EQUIPMENT TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480
Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITES DATE: 2/22/2012
PAGE: 10
UNIT NO. EF-1 (05) EF-1 (03) EF-1 (01) EF-6
LOCATION ROOF ROOF ROOF CEILING
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO. G-085-VG-4-X G-085-VG-4-X G-085-VG-4-X SQ-120-VG-5-X
SERIAL NO. 12534317-1108 12534318-1108 12534311-1108 12514098-1107
OPERATING CONDo SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL SPECIFIED ACTUAL
TOTAL CFM 270 335 270 308 270 335 1465 1406
RETURNCFM 270 335 270 308 270 335 1465 1406
OUTSIDE CFM - - - - - - - -
EXT.STATIC PRESS - - - -
TOT.STATIC PRESS. - - - .80"
SUCTION PRESS. .16" .22" .20" .30"
DISCHARGE PRESS. - - - .50"
FAN SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
MOTOR MANUFCTR. GREENHECK GREENHECK GREENHECK NIA
SIZE 1/4 1/4 1/4 NIA
VOLTAGE 115 121 115 121 115 121 115 121
PHASE 1 1 1 1 1 1 1 1
RATED ACTUAL RATED ACTUAL RATED ACTUAL RATED ACTUAL
RPM MOTOR 1725 1726 1725 1714 1725 1719 NIA 1733
AMPERAGE 3.9 1.0 3.9 .9 3.9 1.1 NIA 4.3
RPM FAN 1726 1714 1719 1733
FILTER DROP
COIL DROP
AIR WASH
DIFFUSER & GRILL TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITESDATE:PAGE:
2/22/201212
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-1
401 1 EG 6" 1.08 83 90 125 135 125 135
301 2 EG 6" 1.08 83 90 100 108 100 108
201 3 EG 6" 1.08 83 90 85 92 85 92
- - -
270 1.24 335 1.24 335
EF-1
402 1 EG 6" 1.08 83 90 115 124 115 124
302 2 EG 6" 1.08 83 90 100 108 100 108
202 3 EG 6" 1.08 83 90 105 113 105 113
- - -270 1.28 345 1.28 345
EF-1
403 1 EG 6" 1.08 83 90 90 97 90 97
303 2 EG 6" 1.08 83 90 95 103 95 103
203 3 EG 6" 1.08 83 90 100 108 100 108
-
270 1.14 308 1.14 308
EF-1
404 1 EG 6" 1.08 83 90 115 124 115 124
304 2 EG 6" 1.08 83 90 105 113 105 113
204 3 EG 6" 1.08 83 90 100 108 100 108
-270 1.28 345 1.28 345
EF-1
405 1 EG 6" 1.08 83 90 110 119 110 119
305 2 EG 6" 1.08 83 90 100 108 100 108
205 3 EG 6" 1.08 83 90 100 108 100 108
- - -
270 1.24 335 1.24 335
JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DATE:PAGE:
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480Fax: (801) 282-3557
212212012
13
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-1
406 1 EG 6" 1.08 83 90 130 140 130 140
306 2 EG 6" 1.08 83 90 110 119 110 119
206 3 EG 6" 1.08 83 90 115 124 115 124
- - -
270 1.42 383 1.42 383
EF-1
407 1 EG 6" 1.08 83 90 100 108 100 108
307 2 EG 6" 1.08 83 90 105 113 105 113
207 3 EG 6" 1.08 83 90 100 108 100 108
- - -270 1.20 324 1.20 324
EF-1
408 1 EG 6" 1.08 83 90 110 119 110 119
308 2 EG 6" 1.08 83 90 95 103 95 103
208 3 EG 6" 1.08 83 90 100 108 100 108
- . -
270 1.00 270 1.22 330
EF-l
409 1 EG 6" 1.08 83 90 105 113 105 113
309 2 EG 6" 1.08 83 90 110 119 110 119
209 3 EG 6" 1.08 83 90 105 113 105 113
- . -270 1.28 345 1.28 345
EF-1
410 1 EG 6" 1.08 83 90 110 119 110 119
310 2 EG 6" 1.08 83 90 100 108 100 108
210 3 EG 6" 1.08 83 90 110 119 110 119
- - -
270 1.28 346 1.28 346
JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DATE:PAGE:
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282·3557
2/22/201211
REQUIRED FLOW TEST RESULTS
ROOM NO OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
MUA-1
4TH CORR. 1 SWS 8" X 22" 1.10 764 840 260 286 570 627
3RD CaRR. 2 SWS 8" X 22" 1.10 764 840 1700 1870 930 1023
2ND CaRR. 3 SWS 8" X 22" 1.10 764 840 610 671 590 649
- -2520 1.12 2827 91 2299
MUA-2
4TH CaRR. 1 SWS 8" X 22" 1.10 759 835 1000 1100 720 792
3RD CaRR. 2 SWS 8" X 22" 110 759 835 920 1012 715 787
2ND CaRR. 3 SWS 8" X 22" 1.10 759 835 1120 1232 700 770
1ST CaRR. 4 SWS 8" X 22" 1.10 759 835 760 863 660 726
- - -
3340 1.25 4180 .92 3075
FC-1
111 1 LD-1 10" 1.08 306 330 405 437 340 367
111 2 LD-1 10" 1.08 306 330 455 491 305 329
111 3 LD-1 10" 1.08 306 330 440 475 330 356
111 4 LD-1 10" 1.08 306 330 300 324 330 356
111 5 LD-1 10" 1.08 306 330 320 346 320 346
111 6 LD-1 10" 1.08 306 330 455 491 330 356
111 7 LD-1 10" 108 306 330 460 497 320 346
HOT TUB 8 LD-1 10" 1.08 319 345 160 173 250 270
HOT TUB 9 LD-1 10" 1.08 319 345 320 346 250 270
- - -
3000 1.19 3580 1.00 2996
DATE:PAGE:JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
2/22/201214
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-1
411 1 EG 6" 1.08 83 90 100 108 100 108
311 2 EG 6" 1.08 83 90 100 108 100 108
211 3 EG 6" 1.08 83 90 110 119 110 119
- - -270 1.24 335 1.24 335
EF-1
412 1 EG 6" 1.08 83 90 100 108 100 108
312 2 EG 6" 1.08 83 90 90 97 90 97
212 3 EG 6" 1.08 83 90 85 92 85 92
- - -
270 1.10" 297 1.10" 297
EF-1
414 1 EG 6" 1.08 83 90 100 108 100 108
314 2 EG 6" 1.08 83 90 105 113 105 113
214 3 EG 6" 1.08 83 90 110 119 110 119
- - -270 1.26 340 1.26 340
EF-1
415 1 EG 6" 1.08 83 90 125 135 125 135
315 2 EG 6" 1.08 83 90 115 124 115 124
215 3 EG 6" 1.08 83 90 120 130 120 130
- - -
270 1.44 389 1.44 389
EF-1
416 1 EG 6" 1.08 83 90 95 103 95 103
316 2 EG 6" 1.08 83 90 110 119 110 119
216 3 EG 6" 1.08 83 90 105 113 105 113
116 4 EG 6" 1.08 83 90 105 113 105 113
- - -
360 1.24 448 1.24 448
JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DATE:
PAGE:
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480Fax: (801) 282·3557
212212012
15
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-2
417 1 EG 6" 1.08 83 90 115 124 115 124
317 2 EG 6" 1.08 83 90 100 108 100 108
217 3 EG 6" 1.08 83 90 90 97 90 97
- - -
360 1.22 329 1.22 329
EF-2
418 1 EG 6" 1.08 83 90 120 130 120 130
318 2 EG 6" 1.08 83 90 100 108 100 108
218 3 EG 6" 1.08 83 90 95 103 95 103
118 4 EG 6" 1.08 83 90 115 124 115 124
- - -
360 1.29 465 1.29 465
EF-2
419 1 EG 6" 1.08 83 90 140 151 140 151
319 2 EG 6" 1.08 83 90 120 130 120 130
219 3 EG 6" 1.08 83 90 115 124 115 124
119 4 EG 6" 1.08 83 90 135 146 135 146
- - -
360 1.53 551 1.53 551
EF-2
420 1 EG 6" 1.08 83 90 120 130 120 130
320 2 EG 6" 1.08 83 90 110 119 110 119
220 3 EG 6" 1.08 83 90 100 108 100 108
120 4 EG 6" 1.08 83 90 115 124 115 124
- - -360 1.34 481 1.34 481
DIFFUSER & GRILL TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITESDATE:PAGE:
2/22/201216
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-2
421 1 EG 6" 1.08 83 90 130 140 130 140
321 2 EG 6" 1.08 83 90 120 132 120 132
221 3 EG 6" 1.08 83 90 115 124 115 124
121 4 EG 6" 1.08 83 90 120 130 120 130
- - -
360 1.46 526 1.46 526
EF-2
422 1 EG 6" 1.08 83 90 125 135 125 135
322 2 EG 6" 1.08 83 90 110 119 110 119
222 3 EG 6" 1.08 83 90 115 124 115 124
122 4 EG 6" 1.08 83 90 115 124 115 124
- - -
360 1.39 502 1.39 502
EF-2
423 1 EG 6" 1.08 83 90 150 162 150 162
323 2 EG 6" 1.08 83 90 130 140 130 140
223 3 EG 6" 1.08 83 90 110 119 110 119
123 4 EG 6" 1.08 83 90 120 130 120 130
- - -
360 1.53 551 1.53 551
EF-2
424 1 EG 6" 1.08 83 90 115 124 115 124
324 2 EG 6" 1.08 83 90 105 113 105 113
224 3 EG 6" 1.08 83 90 105 113 105 113
124 4 EG 6" 1.08 83 90 110 119 110 119
- - -
360 1.30 469 1.30 469
JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DATE:
PAGE:
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480Fax: (801) 282·3557
212212012
17
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-2
425 1 EG 6" 1.08 83 90 145 157 145 157
325 2 EG 6" 1.08 83 90 135 146 135 146
225 3 EG 6" 1.08 83 90 100 108 100 108
125 4 EG 6" 1.08 83 90 120 130 120 130
- - -
360 1.50 541 1.50 541
EF-2
426 1 EG 6" 1.08 83 90 135 146 135 146
326 2 EG 6" 1.08 83 90 135 146 135 146
226 3 EG 6" 1.08 83 90 110 119 110 119
126 4 EG 6" 1.08 83 90 105 113 105 113
- - -
360 1.46 524 1.46 524
EF-2
427 1 EG 6" 1.08 83 90 155 167 155 167
327 2 EG 6" 1.08 83 90 140 151 140 151
227 3 EG 6" 1.08 83 90 95 103 95 103
127 4 EG 6" 1.08 83 90 110 119 110 119
- - -360 1.50 540 1.50 540
EF-2
428 1 EG 6" 1.08 83 90 110 119 110 119
328 2 EG 6" 1.08 83 90 105 113 105 113
228 3 EG 6" 1.08 83 90 90 97 90 97
128 4 EG 6" 1.08 83 90 90 97 90 97
- - -
360 1.18 426 1.18 426
JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DATE:PAGE:
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
2/22/201220
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-2
435 1 EG 6" 108 83 90 135 146 135 146
335 2 EG 6" 1.08 83 90 125 135 125 135
235 3 EG 6" 1.08 83 90 105 113 105 113
135 4 EG 6" 1.08 83 90 105 113 105 113
-
360 1.41 507 1.41 507
EF-2
436 1 EG 6" 1.08 83 90 130 140 130 140
336 2 EG 6" 1.08 83 90 125 135 125 135
236 3 EG 6" 108 83 90 100 108 100 108
- -
360 1.42 383 1.42 383
EF-3
113 1 EG 4.5' x 2' 1.34 3310 4435 3175 4255 3175 4255
- -
4435 .96 4255 .96 4255
EF-4
213 1 EG 34" x 16" 1.18 1771 2090 605 714 NOT OPERATING
313 2 EG 34" x 16" 1.18 1771 2090 1080 1274
413 3 EG 34" x 16" 1.18 1771 2090 2095 2472
-6270 .71 4460
EF-6
111 1 EG-2 18"x18" 1.09 670 730 620 676 620 676
111 2 EG-2 18" x 18" 1.09 674 735 670 730 670 730
- -
1465 .96 1406 96 1406
DIFFUSER & GRILL TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITESDATE:PAGE:
2/22/201218
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-2
429 1 EG 6" 1.08 83 90 135 146 135 146
329 2 EG 6" 1.08 83 90 120 130 120 130
229 3 EG 6" 1.08 83 90 95 103 95 103
129 4 EG 6" 1.08 83 90 115 124 115 124
- - -
360 1.40 503 1.40 503
EF-2
430 1 EG 6" 1.08 83 90 100 108 100 108
330 2 EG 6" 1.08 83 90 115 124 115 124
230 3 EG 6" 1.08 83 90 60 65 60 65
130 4 EG 6" 1.08 83 90 100 108 100 108
- - -
360 1.13 405 1.13 405
EF-2
431 1 EG 6" 1.08 83 90 125 135 125 135
331 2 EG 6" 1.08 83 90 120 130 120 130
231 3 EG 6" 1.08 83 90 80 86 80 86
131 4 EG 6" 1.08 83 90 105 113 105 113
- - -
360 1.29 464 1.29 464
EF-2
432 1 EG 6" 1.08 83 90 110 119 110 119
332 2 EG 6" 1.08 83 90 105 113 105 113
232 3 EG 6" 1.08 83 90 65 70 65 70
132 4 EG 6" 1.08 83 90 130 140 130 140
- - -
360 1.23 442 1.23 442
JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DATE:
PAGE:
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
2/22/2012
19
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-2
433 1 EG 6" 1.08 83 90 125 135 125 135
333 2 EG 6" 1.08 83 90 110 119 110 119
233 3 EG 6" 1.08 83 90 80 86 80 86
133 4 EG 6" 1.08 83 90 95 103 95 103
- - -
360 1.23 443 1.23 443
EF-2
434 1 EG 6" 1.08 83 90 150 162 150 162
334 2 EG 6" 1.08 83 90 135 146 135 146
234 3 EG 6" 1.08 83 90 115 124 115 124
134 4 EG 6" 1.08 83 90 110 119 110 119
- - -
360 1.53 551 1.53 551
EF-2
435 1 EG 6" 1.08 83 90 135 146 135 146
335 2 EG 6" 1.08 83 90 125 135 125 135
235 3 EG 6" 1.08 83 90 105 113 105 113
135 4 EG 6" 1.08 83 90 105 113 1105 113
- - -360 1.41 507 1.41 507
EF-2
436 1 EG 6" 1.08 83 90 130 140 130 140
336 2 EG 6" 1.08 83 90 125 135 125 135
236 3 EG 6" 1.08 83 90 100 108 100 108
- - -
360 1.42 383 1.42 383
DIFFUSER & GRILL TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
JOB NAME: SPRING HILL SUITESDATE:PAGE:
2/22/201221
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-7
109B 1 EG-1 10" x4" 1.08 69 75 50 54 65 71
109B 2 EG-1 10" x 4" 1.08 69 75 45 48 65 71
109B 3 EG-1 10" x 4" 1.08 69 75 175 189 75 81
109B 4 EG-1 10" x 4" 1.08 88 95 45 48 80 86
109A 5 EG-1 10" x 4" 1.08 88 95 150 162 100 108
109A 6 EG-1 10" x 4" 1.08 69 75 45 49 60 65
109A 7 EG-1 10" x 4" 1.08 69 75 115 124 80 86
- - -
565 1.19 674 1.01 568
EF-8
110 1 EG-1 10" 1.08 310 335 90 97 315 340
- -
335 .29 97 1.01 340
EF-10
213B 1 EG 6" 1.08 83 90 105 113 105 113
-
90 1.26 113 1.26 113
EF-10
2000 1 EG 6" 1.08 83 90 110 119 110 119
- - -
90 1.32 119 1.32 119
EF-10
313B 1 EG 6" 1.08 83 90 95 103 95 103
- - -
90 1.04 103 1.04 103
EF-10
413B 1 EG 6" 1.08 83 90 100 108 100 108
- - -
90 1.20 108 1.20 108
JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DATE:
PAGE:
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
2/22/2012
22
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-12
115A 1 EG 6" 1.08 83 90 100 108 100 108
- - -90 1.2 108 1.2 108
EF-12
136B 1 EG 6" 1.08 46 50 45 49 45 49
- - -50 .98 49 .98 49
EF-12
200B 1 EG 6" 1.08 46 50 80 86 80 86
- - -50 1.72 86 1.72 86
EF-12
237A 1 EG 6" 1.08 46 50 90 97 90 97
- - -
50 1.94 97 1.94 97
EF-12
300B 1 EG 6" 1.08 46 50 105 113 105 113
- - -
50 2.26 113 2.26 113
EF-12
337 1 EG 6" 1.08 46 50 95 103 95 103
- - -
50 2.06 103 2.06 103
EF-12
400B 1 EG 6" 1.08 46 50 95 103 95 103
- - -
50 2.06 103 2.06 103
JOB NAME SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DATE:PAGE'
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282·3480Fax: (801) 282·3557
2/22/2012
23
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
EF-12
437A 1 EG 6" 1.08 47 50 100 108 100 108
· ·
50 2.16 108 2.16 108
EF-13
117 1 EG 6" 108 185 200 60 65 190 205
· -200 .33 65 1.03 205
EF-13
111C 1 EG 6" 1.08 185 200 195 211 195 211
· · ·
200 1.06 211 1.06 211
AH-1
107 1 LD 24" X 24" 1.09 523 565 470 512 470 512
· · ·
565 .91 512 .91 512
AH-2
107 1 LD 24" X 24" 109 523 565 460 501 460 501
·
565 .89 501 89 501
AH-3
107 1 LD 24" X 24" 1.09 523 565 450 491 450 491
- ·
565 .87 491 .87 491
AH-4
107 1 LD 24" X 24" 1.09 523 565 455 496 455 496
· · ·
565 .88 496 .88 496
DATE:PAGE:JOB NAME: SPRING HILL SUITES
DIFFUSER & GRILL TEST SHEET
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
21221201224
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
AH-5
103 1 LD 24" x 24" 1.09 583 635 450 491 450 491
- - -
635 .77. 491 .77 491
AH-6
1 LD 24" x 24" 1.08 417 450 350 378 350 378
- - -
450 .84 378 .84 378
AH-9
101B 1 LD 24" x 24" 1.09 583 635 550 600 550 600
- - -635 .94 600 .94 600
AH-10
101A 1 LD 24" x 24" 1.09 583 635 590 643 590 643
- - -
635 1.01 643 1.01 643
AH-11
106 1 LD 24" x 24" 1.08 417 450 520 562 520 562
- - -450 1.25 562 1.25 562
AH-12
101A 1 LD 24" x 24" 1.09 583 635 540 589 540 589
- - -635 .93 . 589 .93 589
AH-13
1018 1 LD 24" x 24" 1.09 583 635 560 610 560 610
- - -
635 .96 610 .96 610
AH-14
110 1 LD 24" x 24" 1.09 583 635 590 643 590 643
- - -
635 1.01 643 1.01 643
--------------------------------- -
DIFFUSER & GRILL TEST SHEET
JOB NAME: SPRING HILL SUITES
DATE:
PAGE:
DIAMOND TEST AND BALANCE11577 So. Lampton View Drive
So. Jordan, UT 84095Ph: (801) 282-3480Fax: (801) 282-3557
2/22/201225
REQUIRED FLOW TEST RESULTS
ROOM NO. OUTLET NO. CODE SIZE CORRECTION FPM CFM FPM CFM FINAL FINAL
FACTOR VEL VEL FPM CFM
AH-16
106A 1 LD 24" X 24" 1.08 417 450 460 497 460 497
- - -
450 1.10 497 1.10 497
AH-17
115 1 LD 24" X 24" 1.08 417 450 460 497 460 497
- - -
450 1.10 497 1.10 497
AH-18
113 1 LD 24" X 24" 1.08 417 450 510 551 510 551
- - -
450 1.22 551 1.22 551
AH-19
105 1 LD 24" X 24" 1.08 417 450 460 497 460 497
- - -450 1.10 497 1.10 497
AH-20
117 1 LD 24" X 24" 1.09 583 635 480 523 480 523
- - .
635 .82 523 .82 523