APPENDIX B
NINE-BUS POWERSYSTEM CASE STUDY
TABLE B.1. Branch Data
From Bus To Bus R, pu X, pu B, pu Limit, MW
1 4 0 0.0576 0 2004 5 0.017 0.092 0.158 2005 6 0.039 0.17 0.358 1003 6 0 0.0586 0 2506 7 0.0119 0.1008 0.209 1007 8 0.0085 0.072 0.149 2008 2 0 0.0625 0 2008 9 0.032 0.161 0.306 2009 4 0.01 0.085 0.176 200
Power System Monitoring and Control, First Edition. Hassan Bevrani, Masayuki Watanabe,and Yasunori Mitani. 2014 John Wiley & Sons, Inc. Published 2014 by John Wiley & Sons, Inc.
254
TABLE B.4. Exciter Data
Low Pass Filter Regulator Exciter Output Limits
Generator Tr Ka Ta Ke Te Efmin Efmax
G1 20e�3 200 0.001 1 0 0 7G2 20e�3 200 0.001 1 0 0 12.3G3 20e�3 200 0.001 1 0 0 12.3
TABLE B.2. Generator Data
Generator G1 G2 G3
Nominal power (MVA) 128 247.5 192Type Hydro Steam SteamSpeed (rpm) 180 3600 3600VL–L (KV) 16.5 18.3 13.8Xd 0.146 0.8958 1.3125X0d 0.0608 0.1198 0.1813
X00d
0.205 0.155 0.22Xq 0.0969 0.8645 1.2578X0q
0.0969 0.1969 0.25
X00q
0.221 0.143 0.292
XL 0.0336 0.0521 0.0742T 0d 8.96 6 5.89
T 00d
0.02 0.02 0.02
T 0qo 0.00002 0.535 0.6
T 00q0 0.02 0.02 0.02
RS 2.8544e-3 2.8544e-3 2.8544e-3H (on 100MW) 23.64 3.01 6.4
Reactance values are in pu on 100MVA base, and all generators are equipped with a governor and PSS.
TABLE B.3. Load Data
Load Load A Load B Load C
Bus No. 9 5 7Active power (MW) 125 90 100Reactive power (MVAR) 50 30 35Number of blocks 6 4 5
APPENDIX B : N INE-BUS POWER SYSTEM CASE STUDY 255