Upload
mark
View
230
Download
2
Embed Size (px)
DESCRIPTION
Termografía en cadenas
Citation preview
https://noppa.aalto.fi/noppa/kurssi/s-18.3150
LIQUID AND SOLID INSULATION
Lecture 4
S-18.3150 High Voltage Engineering
S-18.3146 Suurjännitetekniikka
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 2
Week Date Lecture Topic Exercises
38 15.9 1 General + Safety + High Voltage Lab Tour
39 22.9 2 Electrostatic Fields + FEM 1 + FEM tasks + Seminar Tasks
40 29.9 3 Gas Insulation
41 6.10 4 Liquid and Solid insulation 2
42 13.10 5 Transients 3
43 20.10 NO LECTURE Partial Discharge Lab
44 27.10 6 Overvoltages & Insulation Coordination 4
45 3.11 7 HV Testing & Measurements 5
46 10.11 8 Generation of High Voltages Seminar Presentations
47 17.11 Seminar Presentations (Seminars)
48 24.11 Excursion Surge Arrestor Lab
49 2.12 NO LECTURE
50 8.12 EXAM (13 – 16, S5)
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 4
• Protect solid insulation from discharge
• Extinguish arcing
• Efficiently remove heat (cooling)
PURPOSE
• Low viscosity (resistance of fluid - thickness) • Cooling properties
• Liquid fills all voids in solid insulation
• Viscosity must remain small at low temperatures (Finland) • Cannot become solid. Solidification temperature less than -40 °C)
• Chemically stable • Maintain insulating properties through long service life in varying conditions
REQUIREMENTS
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 5
REQUIREMENTS DEPEND ON APPLICATION:
Transformers • High withstand voltage – high dielectric strength of liquid
• Good heat transfer capability for cooling
• High resistivity, low loss factor, good PD tolerance
Cables and Bushings • Very good PD tolerance
• Very low viscosity (impregnation)
Switches • High flash temperature so that it can safely extinguish arc
MINERAL OIL
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 6
0 0
20
40
60
80
20 40 60
water content [µg/g]
80 100
Ub [kV]
(ii.) same oil
filtered twice
(i.) clean industrial
transformer oil
Most common liquid insulation
• Typical mineral oil is transformer oil
• Easy availability and economical
• Properties defined in IEC 60296
• Good dielectric properties for insulation and low viscosity for cooling
• Prone to oxidization and flammability (flash point over 130 °C)
• Moisture and impurities affect insulating properties
SYNTHETIC LIQUID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 7
CONTROLLED CHEMICAL STRUCTURE
DESIRED PROPERTIES MORE EXPENSIVE
Relative
Permittivity εr
[50 Hz, 25 °C]
Kinematic Viscosity
[mm2/s, 20 °C]
Solidification Point
[°C]
Flashpoint
[°C] Comments
Mineral Oil 2.2 16 -50 150-175
Mono/dibenzyl
toluene 2.7 6.5 -50 144
Very toxic for aquatic environment
Silicone Oil 2.9 50 -53 >335
Most environmentally friendly
Non-flammable
Poor heat transfer.
Poor discharge tolerance
(flammable gas by-products from arcing)
Ester 3.3 63 -50 310 Non-toxic,
Environmentally friendly
BREAKDOWN IN LIQUID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 8
Due to the density of the liquid, it is hard for electrons to achieve much energy between collisions
In relatively clean and homogenous liquids, the breakdown mechanism is similar to breakdown in gas
Electric field is applied to the charge carriers in the liquid (electrons already present
in the liquid and those released from the cathode through emission and electrochemical processes)
Electrons move in the opposite direction of the field
If the energy of the electrons is sufficient, dissociation of molecules by collisional ionization occurs (ionic compounds split into smaller particles – opposite of
recombination)
Microscopic gas bubbles form in liquid
Townsend avalanches and new free charges can form in the BUBBLES (smaller density)
BREAKDOWN IN LIQUID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 9
Mobility of electrons in the liquid is 105 times greater than positive ions
• electrons leave behind a concentration of positive ions
• these charge concentrations enhance electric field in certain regions and further advance ionization
Free charges created by ionization inside the bubble are displaced by the electric field • the bubble is stretched and grows in size
Eventually the bubble (or row of bubbles) will expand across the electrode gap
• an ionized channel is formed and advanced by streamer discharge
• the channel has lower density and smaller dielectric strength than the rest of the liquid
• continuous current flows through the channel
BREAKDOWN IN LIQUID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 10
• Impurity moves towards the area of highest electric field
• Impurity enhances the electric field and attracts other particles
• These particles bridge the electrodes leading to breakdown
Impurity.ɛr >
Liquid.ɛr
Fiber bridge
Bridging of impurities and bubble rows can be avoided by
•Inter-layering with solid insulation
•Displacing liquid (flowing)
Breakdown can also be caused by impurities
Moisture and foreign particles
BREAKDOWN IN LIQUID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 11
Dielectric strength of liquid is hard to determine:
• not constant
• once oxidation, electrochemical reactions, and impurities affect the liquid, its insulating properties are not the same
• dielectric strength of liquid measured in homogeneous gap even though most insulators are inhomogeneous
Temperature and pressure affect the liquid’s dielectric strength
• As temperature increases, viscosity decrease which increases the speed of electrons between collisions and increase the probability for breakdown
• As pressure increases, the formation of bubbles is more difficult which improves the dielectric strength of the liquid.
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 13
PURPOSE
• Mechanical support for conducting components
• Electrical insulation
REQUIREMENTS
• Mechanical strength
• Dielectric strength
• Heat tolerance
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 14
Insulation Breakdown
Field Strength [kV/mm]
Temperature Index TI
(20 000 h) [°C]
Comments
Organic
Paper (dry) 6 90 • easy to handle and machine
• typically good dielectric properties
• insulating properties change during service life
• temperatures above 100 °C deteriorate insulator
• typically porous – absorb liquids, impregnation
• transformers, cables, capacitors
Paper (oil impregnated) 40 – 75 105
Rubber 20 75
Wood (dry) 90
Wood (oil impregnated) 105
Press wood (dry) 6 90 – 120
Inorganic
Porcelain 30 1000 • withstand high temperatures
• excellent dielectric and mechanical properties
• poor machinability, cannot absorb liquids
• overhead lines, bushings, rotating machines
Glass 16 400 – 1000
Mica 80 500 – 700
Synthetic
Polymer
Polythene 20 105 • all industrially produced solid insulation
• excellent electric properties, easy to machine
• thermoplastic / thermoset plastic
• wide range of applications depending on manufacturing process - moisture sealing, tensile strength, flexibility
Polystyrene 100 80 – 90
Phenolic plastic (bakelite) 5 – 16 120 – 155
Epoxy plastic 20 – 40 105 – 155
Melamine 13 – 14 120
Organic
Non-organic
Synthetic Polymer
BREAKDOWN IN SOLID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 15
Mechanism of breakdown in solids remains unclear
F12 F21
When voltage stress is increased close to breakdown:
• Current through insulator increases exponentially (similar to gas)
• Assumed to be caused by increasing number of charge carriers in the insulation and electrode surfaces
In practice, other factors affect breakdown besides the increase of electrons:
• Pre-discharge current and dielectric losses causing heat
• Electrostatic forces at interfaces
• Electrochemical reactions
• Water trees, erosion
BREAKDOWN IN SOLID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 16
Breakdown is caused by energy provided by an electric field
Energy transfer can occur by:
Breakdown leads to thermal destruction
of insulator (melting, charring, vaporizing)
Permanent loss of insulating properties
(not self-restoring like gases)
In general:
Collision Ionization (electric breakdown) 1.
Thermal Losses (thermal breakdown) 2.
BREAKDOWN IN SOLID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 17
BREAKDOWN MECHANISMS IN SOLID INSULATION • Electrical Breakdown
• Intrinsic Breakdown
• Partial Discharge
• Electrical Treeing
• Electromechanical Breakdown
• Thermal Breakdown
• Electrolytic Breakdown
ELECTRICAL BREAKDOWN
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 18
Multi-stage phenomenon influenced by:
Discharge occurs when critical field strength is
exceeded locally
• assumed to begin at inhomogeneous region of the
insulation or electrode surface
Insulation is destroyed by different chemical
and physical processes
Conducting channel with numerous charge
carriers starts to progress
Complete breakdown occurs when the channel
has bridged the electrodes
• Different ionization mechanisms
• Space charges in discharge channel
• Heating of insulator material
• Molecular structure deformations
INTRINSIC (INTERNAL) BREAKDOWN
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 19
When an electric field is applied, the conduction electrons gain energy due to collisions between them and the energy is shared by all electrons.
• For a stable condition, this energy must be somehow dissipated.
• The field raises the energy of the electrons more rapidly than they can transfer it to the lattice.
• Electron temperature increases and conduction continues to increase to a complete breakdown.
The energy gained by electrons from the electric field exceeds the amount of energy that electrons can transfer, resulting in the collapse of the entire molecular lattice
Intrinsic strength is a property of the MATERIAL and TEMPERATURE only
In pure homogeneous dielectric materials the conduction and valence bands are separated by a large energy gap and at room temperature the electrons cannot acquire sufficient thermal energy to make transitions from valence to conduction band.
metal semiconductor insulator
conduction band
valence band
Fermi level
elec
tro
n e
ner
gy
band gap
PARTIAL DISCHARGE BREAKDOWN
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 20
Insulators usually have voids or gas bubbles
If the void has lower permittivity than its
surrounding material, voltage
stress is higher inside the void
Once the void’s withstand strength is
exceeded, partial discharge begins
Positive ions and electrons released by the discharge collide with the
void wall causing slow erosion
(discharge by-products can also
cause chemical erosion)
Irregularities in the void
wall enhance the electric field locally
As further discharges
concentrate on this area, the erosion
path is advanced
ELECTRICAL TREEING
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 21
If stress is continuous, eventually discharges will advance through a solid insulator in a branching erosion path (electric tree) along which a complete breakdown can occur Treeing commences at impurities on the electrode or in the insulation (pre-breakdown phenomenon)
Water treeing – moisture advances in insulator under the influence of the electric field
E.g. Chemical degradation of polymeric insulation such as XLPE or EPR that only occurs in the presence of water and electrical stress (initiates from inhomogenities within the insulation or at insulation/screen interface)
Electrical treeing Vented water treeing Bow tie water treeing
ELECTROMECHANICAL BREAKDOWN
The pressure forces the
insulator to compress
Electrode distance
decreases causing the
electric field to further increase
pressure
Localized heating and softening of the insulator
leads to mechanical
collapse
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 23
Mechanical force between charges at electrodes causes pressure (force of attraction between surface charges)
2
2
1Ep
(not very common for typical insulators)
ELECTROMECHANICAL BREAKDOWN
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 24
Mechanical collapse when electrostatic compressive forces exceed mechanical compressive strength:
Stress (E = U/d0) required for collapse (d < 0.6d0)
21
0
6.0
r
YE
21
0
0
0
2
2
0
2 ln2
ln2
1
2
1
d
dYdU
d
dY
d
UEp
r
r
Y = Young’s modulus of elasticity d0 = original distance d = compressed distance
PET (polyethylene terephthalate, thermoplastic polymer resin) ɛr = 3, Y = 3.1 x 109 Pa E = 6480 kV/mm!
BaTiO3 (barium titanate, dielectric ceramic used in capacitors) ɛr = 18500, Y = 167.4.1 x 109 Pa E = 607 kV/mm!
THERMAL BREAKDOWN
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 25
An electric field causes the insulator to experience heat produced by conductivity and dielectric losses
• as temperature of the insulator increases conductivity increases more heating
• the dissipation factor tan δ increases with temperature more dielectric losses
Field strength E1: insulator temperature
stabilizes at t1
no thermal breakdown
1. Field strength E2:
temperature increases to t2
unstable
(small temporary fluctuation can lead to
thermal breakdown)
2. Stabilization point
unreachable
thermal breakdown
Heat produced at E3 always exceeds cooling
3.
If heat is being produced in the insulator faster than it is removed by cooling thermal breakdown
t 1
t 2
specimen temperature
3 ( E 3 )
1 ( E 1 )
2 ( E 2 )
ELECTROLYTIC BREAKDOWN
Electrolyte
Any substance containing free
ions that behave as an electrically
conductive medium
Ions transport conducting
material from the electrodes
into the interior of the dielectric
Ions (oxygen, chlorine) present in the insulator migrate to the
electrodes causing a chemical reaction
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 26
Insulators with moisture and impurities
are prone to electrolytic breakdown
Highly dependant on
local environmental
conditions
Gradual build up (years)
resulting in sudden
breakdown
BREAKDOWN IN SOLID INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 27
10 2
10 3
10 4
10 5
10 6
10 6 10 3 10 0 10 - 3 10 - 6 10 - 9 10 9 t
[s]
[V/m
m]
b E
Water Treeing
Thermal Breakdown
Partial Discharge
Electrical Treeing
Electrical Breakdown
Electromechanical Breakdown
Breakdown strength and
discharge processes are
highly dependent
on stress duration
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 29
Above certain temperature hard plastic becomes soft and its mechanical and dielectric properties degrade
As temperature decreases plastic becomes brittle and its impact strength weakens
• Voltage withstand strength • Surface distance • Dirt accumulation prevention • Self-cleaning (aerodynamic shape) • Water sealing • Mechanical strength – arcing, erosion, UV radiation, thermal reaction
All outdoor insulators need to consider:
Insulators are needed to support live (voltage) components so that their distance to grounded parts and other devices is maintained.
All organic insulators are influenced by temperature and stress duration
170 146
OVERHEAD LINE COMPONENTS
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 32
Pin Insulator (porcelain)
Disk Insulator, Cap and Pin Insulator (glass or porcelain)
Line Post Insulator (porcelain)
Long-Rod Insulator
Composite Insulator
Cast Plastic
Insulators
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 33
• Typically porcelain
Weaker mechanical and electrical strength compared to toughened glass.
Different constituents in porcelain have different thermal expansion at varying temperatures
• No shattering and easier to manufacture large insulators
CERAMIC INSULATORS
• Toughened glass Improved mechanical strength
Smaller size
• Microscopic fractures on glass surface during manufacturing Shattering caused by mechanical impact or erosion (surface impurities)
GLASS INSULATORS
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 34
Δce
x
l
U 0
• Capacitance chain with highly non-linear voltage distribution
• Each individual unit has:
self capacitance Δcs
capacitance to ground Δce
capacitance to conductor Δcv
xcxl
Cc i
ii
x
c
x
lCc s
ss
i = e (earth) or v (voltage conductor)
l = length of insulator string
Δx = insulator unit length
Insulator String
Δce
Δce
Δce
Δcs
Δcs
Δcs
Δcs
Δcs
Δcv
Δcv
Δcv
Δcv
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 35
Voltage distribution depends on capacitance ratio Cv/Ce
Cv/Ce < 1 voltage stress concentrates on conductor side
Cv/Ce = 1 voltage distribution is symmetrically
Cv/Ce > 1 voltage stress concentrates on tower beam side
Beam (GND)
Conductor
10 20 n
5 15
0.5
1.0
0
N = 7 N = 15 N = 22
10 20 n
5 15
0.5
1.0
0
U [p.u.]
N = 7 N = 15, 20
N = number of units
n = unit number
Cv/Ce ≈ 0 Cv/Ce =1.3
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 36
Emax = 4.6
kV/mm
Emax = 3.75
kV/mm
Emax = 4.5
kV/mm
U
GND
GND
GND
U
U
COMPOSITE INSULATORS
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 39
Protect core from moisture/chemicals/UV radiation/surface discharge
• PD can release hydrogen which forms acid when combined with moisture leading to fracture
+ mechanical strength + light weight + elastic (hard to vandalize) – cost – uncertain long term stability
• Used in overhead lines as insulator strings, phase separators and external insulation for surge arresters, bushings, transformers
Manufactured from at least two different insulating materials
CABLE INSULATION
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 40
AC: plastic – PVC, PE, XLPE (PEX)
DC: HVDC transmission (> 150 kV) with oil-paper insulation
plastic – polarization state does not change fast enough when polarity is changed or voltage transients are applied to the cable
critical field strength is exceeded – breakdown.
Cable
Cable Termination
Cable Joint
PAPER INSULATION (IN CABLES)
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 41
10 – 50 mm wide paper tape wrapped around the conductor with small gaps left between adjacent tapes
• next layer is positioned to avoid continuous radial layering
• the positioning of the tape is called registration and describes how much the layers are on top of each other
50% registration 75% registration
Inhomogeneous construction:
paper enables formation of thin, high dielectric strength oil sheet layers and prevents impurities from traveling between layers
defines mechanical properties – cannot bend cable so that the layers connect
CABLE DESIGN
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 42
1. stranded conductor
2. conductor screen
3. insulation
4. insulation screen
5. metallic screen
6. bedding
7. metallic sheath
8. seperation sheath
9. armouring
10. outer sheath
• Water blocking powder can be used between the strands to prevent water migration.
CONDUCTOR STRANDS
• Standard in most cables.
BASIC LAYERS (2 – 4)
• Vary depending on cable type and intended application • E.g. submarine, underground, etc.
ADDITIONAL LAYERS (5 – 10)
• Serves multiple purposes • E.g. protection against short circuit currents, external
fields, mechanical stress, and moisture.
GROUNDED COMPONENTS (5, 7, 9)
• Used for cushioning and water blocking.
BEDDING (6)
• Can be implemented to separate different metallic layers.
SEPARATION SHEATH (8)
• Serves as external protection.
THE OUTER SHEATH (10)
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 43
Screens help to maintain the cylindrical symmetry of the field
Small cavities and impurities are unavoidable in the cable
Screens (semiconducting layers) are placed between the conductor and insulation layer and also between the insulation layer and the sheath.
1. conductor/insulation – conductor screen (conductor cover) 2. insulation/sheath – insulation screen (corona shield)
2.
1.
eriste
ru
rs
s
x
r
x
r
Et
a
b
Er
johdin
CABLE JOINTS
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 44
CONICAL CONSTRUCTION
Should be logarithmic but straight conical is satisfactory
• Some cables have pre-molded joints – insulation does not need to be altered
• No voids or impurities
insulation
r outer
r inner
a
a
D s
D x
D r
x
r
E t
E r
conductor
insulation
ground
conductor
CABLE TERMINATIONS
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 46
Local concentration of electric field occurs where a conducting electrode continues and the grounded electrode terminates
aim is to maintain a small and constant field
the stress cone has a conducting layer on its surface or in its interior
grading is done by adding a stress cone on top of the cable insulation
Grading of the electric field is necessary (FI: kentänohjaus)
a.) no grading b.) geometric grading c.) refractive grading
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 47
Conductive surface of stress cone displayed as darker bold line.
The design is inserted through a hollow core (porcelain) insulator in this figure.
d .) stress cone placed directly on conductor
e.) stress cone placed on top of cable insulation
stress cone (solid
insulation)
gas/liquid insulation
solid insulation
(mechanical)
E E
• Coat electrode edges with appropriately shaped insulation having different permittivity than the surrounding insulation.
• A high permittivity insulating cylinder can be fastened over the section of the cable that has been stripped of insulation. Capacitance grows between the edge of the metal sheath
and the bare section of insulation.
Forces the field in the surrounding air to be distributed fairly uniformly along the surface of the insulation.
Permittivity-based grading (refractive stress control, ɛ control, or resistive and capacitive grading)
100%
75%
50%
25%
0%
without grading
100% 75%
50%
25%
0%
capacitive grading
Folio sheets
inserted into
insulation
BUSHING (FEED-THROUGH INSULATOR)
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 49
A live conductor is fed through a grounded enclosure
To avoid electric field concentration:
• Electrodes and insulation shape is considered
• Grading ring can be applied (kentänohjausrengas)
• Capacitive grading – field electrodes added
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 54
Voltage level
Insulator string length
Number of insulator
units
110 kV ~ 1 m 6-8
220 kV ~ 2 m 10-12
400 kV ~ 4 m 18-21
(in Finland, approx. 1 m/100 kV)
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 55
110/20 kV Substation (Espoo)
110 kV switching yard and line terminals - Main transformer (1-3 units),
busbar, circuit breakers, disconnectors, current transformers, surge arresters
20 kV panels and line terminals - Busbar, circuit breakers, disconnectors, current
transformers
Control and monitoring equipment - Measurement, protection, data transfer, local
automation, remote application, interlocking devices, backup electrical system, storage batteries
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 56
110/20 kV Substation (Levi)
Instrument transformer VT (voltage) (USA:
potential transformer PT) Disconnector
Circuit breaker
Instrument transformer CT
(current) Disconnector
Disconnector
(Bypass) Main transformer
(31,5 MVA, 110 kV)
https://noppa.aalto.fi/noppa/kurssi/s-18.3150 57
Electropedia: The World’s Online Electrotechnical Vocabulary www.electropedia.org
switching device a device designed to make or break the current in one or more electric circuits
switchgear a general term covering switching devices and their combination with associated control, measuring,
protective and regulating equipment, also assemblies of such devices and equipment with associated
interconnections, accessories, enclosures and supporting structures, intended in principle for use in
connection with generation, transmission, distribution and conversion of electric energy
(mechanical) switch a mechanical switching device capable of making, carrying and breaking currents under normal circuit
conditions which may include specified operating overload conditions and also carrying for a specified time
currents under specified abnormal circuit conditions such as those of short circuit.
Note – A switch may be capable of making but not breaking short-circuit currents.
disconnector (isolator) a mechanical switching device which provides, in the open position, an isolating distance in accordance with
specified requirements.
Note – A disconnector is capable of opening and closing a circuit only when either negligible current is
broken or made, or when no significant change in the voltage across the terminals of each of the poles of the
disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a
specified time currents under abnormal conditions such as those of short circuit.
circuit-breaker a mechanical switching device, capable of making, carrying and breaking currents under normal circuit
conditions and also making, carrying for a specified time and breaking currents under specified abnormal
circuit conditions such as those of short circuit.
instrument transformer a transformer intended to transmit an information signal to measuring instruments, meters and
protective or control devices Note – The term "instrument transformer" encompasses both
current transformers and voltage transformers.