Vertical Hi-Rise Fan Coil UnitsFor Concealed Application
Double deflectionsupply air grille
Optional quickconnect plug forthermostat
Service accesspanel location,shown with panelremoved
Return air opening
Drain pan
Riser pipesexpanded, couplingsnot required
Optional riser cover
Direct drive blowerPSC motor
Branch piping withmotorized controlvalves, ball valves,manual air vents
Optional connectionfor tandem unit
High capacityCW/HW coil, twoor four pipe
Optional outdoor airduct
1
TEMSPEC INC.
COMPANY PROFILE
Temspec designs and manufactures unit ventilators for school classroomsand vertical stack fan coil units for high-rise hotels and condominiums. Thecompany was established in 1971 and has gained a reputation in theH.V.A.C. industry for on-time delivery of high quality equipment.
We specialize in flexible response to customers’ needs, often customizingthe units to suit specific application requirements. We work closely withEngineers at the design stage to ensure optimum use of the units within theH.V.A.C. system.
Since 1971 Temspec has produced over 250,000 fan coil units and over10,000 unit ventilators. Our market encompasses the whole of the U.S.A.and Canada through a network of experienced sales representatives.
Our client portfolio includes such prestigious companies as Hilton hotels,Marriott, Stouffers, Sheraton, Novotel, Skydome hotel, Royal York hotel,Intercontinental, Red Lion Inns, Fairmont, Tridel, Bally’s, Harvey’s Casino,Omni, Ramada and Belterra Casino Resort.
OTHER PRODUCT CATALOGS FROM TEMSPEC ARE:• Classroom unit ventilators• Hi-rise fan coil units with finished cabinet for exposed application
2
TEMSPEC “FAN COIL”
PARA EL CARIBE Y LAS REGIONES DE AMERICA DEL SUR
Por más de veinte anos Temspec Inc. ha producido unidades de “Fan Coil”. Para la construcción yrenovación de hoteles con multiples pisos, en el mercado de Norte America.
Unidades con alta capacidad de refrigeracion han sido instaladas en muchos hoteles de Florida yCalifornia. Nuestra clientela de hoteles incluyen Marriott, Stouffers, Hilton, Sheraton, Hyatt, Royal Yorky el Hotel Skydome. Todos nuestros equipos son aprovados por C.S.A. y U.L.
Las ventajas de unidades verticales de “Fan Coil” en los cuartos de hotel son:
• Una operación sumamente silenciosa, porque la unidad no es comprímida.
• El mantenimiento es simple, las únicas partes movibles son el motor de ventilación y el motor de la válvula.
• Amplia selección de capacidades en refrigeracion son disponibles.
• Bajo costo de cable eléctrico en la habitación, desde que el equipo usa sólo un servicio de 15amperes.
• La unidad está ocultada detrás de la pared. Los huéspedes sólo ven dos parrillas Y untermostato. El uso de una unidad “Fan Coil” permite un alto grado de libertad en disenoarquitectural.
• La installacion es simple, las unidades se apilan, en una tubería vertical, la cual lleva el aguafría hacia las unidades verticalmente arriba del edificio.
• Un calentador auxiliar eléctrico puede ser incluído, si calefacción es necesaria en los días fríosde invierno.
Las unidades de “Fan Coil” enfrían el cuarto el aíre cruza el radiador, la temperatura en el radiador esde 7˚C. El aíre ya enfriado es distribuido a el cuarto por una parrilla de defleccion doble. Agua fríaes bombeada hacia la unidad de fan coil por un sistema central. Las unidades estan localizadasverticalmente unas encima de las otras en el edificio y son abastecidas por un sistema de tuberias decobre insulado. Este sistema de tuberias tiene, una tuberia de abastecimiento otra de regreso y laultima es la de desague.
Configuraciones especiales para acomodar requerimientos arquitecturales son disponibles, y un sistemade asistencia en diseno se ofrece en nuestra planta de Toronto. Idiomas hablados por nuestrospersonal experimentado, son inglés y espanol.
Por encuestas directas, (favor de) dirigirse a los siguientes.
En Espanol: Sr. Eduardo Sarmiento - Gerente De PlantaEn Inglés: Sr. Brian Partington - Vice Presidente y Gerente General
~
~
~
3
DescriptionDraw-thru unit for a two-pipechange-over system.Hot water or chilled water iscirculated through a single coil.Temperature is controlled by amotorized valve with continuous orcycled fan operation.
Draw-thru unit for a two-pipechange-over system (as TVA), withauxiliary electric heat, or as achilled water cooling unit with totalheating by the electric coil.
Draw-thru unit for a four-pipe yearround heating - cooling option. Hotwater and chilled water arecirculated through a split coil.Temperature is controlled by twomotorized valves with continuous orcycled fan operation.
nom.cfm
350
450
600
800
1000
1200
350
450
600
800
1000
1200
350
450
600
800
1000
1200
single
TVA350
TVA450
TVA600
TVA800
TVA1000
TVA1200
TVE350
TVE450
TVE600
TVE800
TVE1000
TVE1200
TVS350
TVS450
TVS600
TVS800
TVS1000
TVS1200
slave
TVA350S
TVA450S
TVA600S
TVA800S
TVA1000S
TVA1200S
TVE350S
TVE450S
TVE600S
TVE800S
TVE1000S
TVE1200S
TVS350S
TVS450S
TVS600S
TVS800S
TVS1000S
TVS1200S
master
TVA350M
TVA450M
TVA600M
TVA800M
TVA1000M
TVA1200M
TVE350M
TVE450M
TVE600M
TVE800M
TVE1000M
TVE1200M
TVS350M
TVS450M
TVS600M
TVS800M
TVS1000M
TVS1200M
SERIESTVA
SERIESTVE
SERIESTVS
All Temspec products are either UL or CSA / NRTL approved.
4
The fan coil unit shall be a draw through type.The cabinet shall be fabricated from 18ga corrosion resistant steel and lined with1/2” glass fiber insulation which is coated on the air side.The coil shall have corrugated aluminium fins mechanically boned to 1/2” coppertube. The coil shall be factory pressure tested at not less than 350 p.s.i. The drainpan shall be insulated on the underside.The flexible coil branches shall be 1/2” type “L” copper, attached to the riser stubsusing heavy duty compression fittings. Ball type isolating valves shall be provided.A manual air vent shall be located at the high point on the return leg.The supply and return risers shall be “M” copper pipe, expanded at the top end.The riser insulation shall be 1/2” wall closed cell material which complies withASTM E 84 for flame-spread and smoke-developed ratings. The insulation shallbe continuous over the riser length within the height of the cabinet. Provision ofinsulation on pipework extending beyond the ends of the cabinet and riser anchorsshall be by Division 15. Refer to the riser schedule for pipe diameters and locationof expansion compensators. The condensate risers shall be Type “M” copper if3/4 or 1” diameter, type “DWV” if 1 1/4” or larger.The control valve shall be two position, two-way/three-way, with a24V/120V/208V/277V class “F” motor. Cv ratings shall be 3.5 for two way and4.0 for three way valves. Differential pressure rating shall be 20 p.s.i.Note 1: When two-way valves are specified, pump and chiller by pass (or othermeans) must be provided to ensure that the maximium water pressure drop ratingof the valve is not exceeded.Note 2: When the control system uses an aquastat, three-way valves should bespecified so that the aquastat can sense the water temperature in the branchpiping, at all times.The motor shall be a three-speed p.s.c. type 8 pole motor, 120V/208V/277V,single phase. The motor shall have a quick connect plug. The fan shall be a directdrive type, with a galvanized forward curved wheel in a painted housing.The coil shall be single stage with an open wire nickel-chrome element carried infloating ceramic bushings. An auto-reset high limit switch shall be factory installedin the coil frame.A 1” thick disposable glass-fiber media filter shall be fitted inside the return airgrille.A baffle shall be included in units with left and right or front and back supply airopenings.
The grilles shall be provided by the fan coil unit manufacturer. The grilles shall bedouble deflection type with a balancing damper included on grilles that are on fancoil units which have a top opening (ducted).
Remote supply air grilles shall be provided by the ventilator contractor.
The return air grille shall be provided by the fan coil unit manufacturer. The grilleshall have a hinged access panel for filter replacement. The blades of the grilleshall be fixed, horizontal.Grilles shall be fabricated from light gauge steel, finished in standard metallic grayor white colored baked enamel.The control package shall be as described in the control section of the specification.The fan coil unit shall be UL or CSA/NRTL approved.
UNIT CONFIGURATIONUNIT CASING
COIL
COIL BRANCHES
RISERS
CONTROL VALVE
FAN / MOTOR ASSEMBLY
ELECTRIC COIL
FILTER
LINE OF SIGHT BAFFLE
UNIT MOUNTED SUPPLY AIR GRILLES
REMOTE ( DUCTED MOUNTED )SUPPLY AIR GRILLES
RETURN AIR GRILLE/ACCESS PANEL
GRILLE MATERIAL
CONTROLSAPPROVALS
TYPICAL SPECIFICATION
5
Optional Features1. The riser package supplied separately from the unit to facilitate installation when access is limited.
2. Finished cabinet for exposed installation ( see other catalog )
3. Supply and return risers fabricated using type L copper pipe.
4. Condensate riser insulated.
5. Expansion compensation loop sets fitted to the supply or return risers within the unit casing.
6. Drain cocks and isolating valves fitted to risers.
7. Two pipe C.W. coil split horizontally to allow separate cooling/dehumidification of outdoor aircomponent.
8. Flow control device fitted to coil branch connections.
9. Drain plug fitted to coil.
10. Gypsum firewall fitted within the riser package.
11. Pressure-temperature plugs fitted to branch connections.
12. Riser insulation up to 1” wall thickness.
13. Many control options are available (see following control options page).
14. Energy management system terminals.
15. Damper controlled fresh air inlet.
16. 15A, 20A or 30A disconnect switch (Fused or un-fused).
17. Provision can be made for remote mounting of the thermostat.
18. Top opening in the unit casing for ducting supply air to remote discharge grilles.
19. Unit casing of non-standard height.
20. Extension sleeves for supply air openings, return air openings and thermostat boxes (suppliedseparately).
21. Registers (supply air grilles with dampers) substituted for the standard double-deflection supply airgrilles.
22. Custom paint finish on grilles.
23. Secondary return air openings with grilles having screw holes for wall mounting. Filter media is fittedin the grille.
24. Washable filter media.
6
CONTROL PACKAGES
TYPE TCF No control valve, thermostat cycles the fan, 2 pipe system.
REF.
TCF-1
TCF-10
TCF-11
VOLTAGE
24
120
120
HEAT/COOL CHANGEOVER
MANUAL
MANUAL
AUTO
THERMOSTAT
T87F/Q539J
T6069A
T6169A
FAN OPERATION
CYCLED
CYCLED
CYCLED
TYPE TCDV Thermostat cycles valves, fan is continuous or cycles with valves, 4 pipe system.
REF.
TCDV-10
TCDV-20
VOLTAGE
120
120
HEAT/COOL CHANGEOVER
AUTO
AUTO
THERMOSTAT
T6575C
T6575D
FAN OPERATION
CYCLED OR CONTINUOUS
USER SELECTABLE
TYPE TCVE Thermostat cycles c.w. valve, fan is continuous, 2 pipe c.w. coil with full size electric heater (no hot water available).
REF.
TCVE-20
VOLTAGE
120 TO 277
HEAT/COOL CHANGEOVER
AUTO
THERMOSTAT
T6575D
FAN OPERATION
USER SELECTABLE
TYPE TCV Thermostat cycles valve, fan is continuous or cycles with valve, 2 pipe system without electric heater.
REF.
TCV-1
TCV-2
TCV-3
TCV-10
TCV-11
TCV-12
VOLTAGE
24
24
24
120
120
120
HEAT/COOL CHANGEOVER
MANUAL
AUTO
AUTO
MANUAL
AUTO
AUTO
THERMOSTAT
T8575B
T8575C
T8575D
T6575B
T6575C
T6575D
FAN OPERATION
CYCLED OR CONTINUOUS
CYCLED OR CONTINUOUS
USER SELECTABLE
CYCLED OR CONTINUOUS
CYCLED OR CONTINUOUS
USER SELECTABLE
TYPE TCVAE Thermostat cycles valve, fan is continuous or cycles with valve, 2 pipe H.W./C.W. system with auxiliary electric heater.
IMPORTANT NOTE
The thermostat part numbers shown above are Honeywell. A wide selection of factory installed control packages is available, please call thefactory to discuss options.
REF.
TCVAE-1
TCVAE-2
TCVAE-3
TCVAE-10
TCVAE-11
TCVAE-20
VOLTAGE
24
24
24
120 TO 277
120 TO 277
120 TO 277
HEAT/COOL CHANGEOVER
MANUAL
MANUAL
AUTO
MANUAL
AUTO
AUTO
THERMOSTAT
T8575B
T8575C
T8575D
T6575B
T6575C
T6575D
FAN OPERATION
CYCLED OR CONTINUOUS
CYCLED OR CONTINUOUS
USER SELECTABLE
CYCLED OR CONTINUOUS
CYCLED OR CONTINUOUS
USER SELECTABLE
7
ELECTRICAL DATA
FAN MOTOR DATAAll motors are permanent split capacitor type
Amperage shown is for unit operating at high speed
Unit size
350
450
600
800
1000
1200
amps
1.10
1.47
2.21
2.81
3.9
3.9
h.p.
1/15
1/14
1/12
1/8
1/4
1/4
amps
0.52
0.59
0.9
1.2
1.6
1.6
h.p.
1/20
1/18
1/14
1/8
1/4
1/4
amps
0.5
0.5
0.75
1.3
1.8
1.8
h.p.
1/14
1/14
1/12
1/5
1/4
1/4
120v / 1 / 60 208v / 1 / 60 277v / 1 / 60
ELECTRIC COIL DATA FOR “TVE” SERIES UNITS
All heaters are single stage, single phase supply.
Unit size
350, 450
350, 450
350, 450, 600, 800
350, 450, 600, 800, 1000, 1200
350, 450, 600, 800, 1000, 1200
600, 800, 1000, 1200
1000, 1200
kW
1.0
1.5
2.0
3.0
4.0
5.0
6.0
Btuh
3410
5120
6820
10240
13650
17060
20470
115v
8.7
13.0
17.4
–
–
–
–
277v
3.6
5.4
7.2
10.8
14.4
18.1
21.7
208v
4.8
7.2
9.6
14.4
19.2
24.0
–
AmpsMax.
8
SOUND POWER LEVELS (dB, reference 10-12 Watts)
(Sound tests were conducted in accordance with ARI standard 443.71 by a Nationally recognized test and research center.)
Unit size
350
450
600
800
Speedhighmed.lowhighmed.lowhighmed.lowhighmed.low
575553605855626059646260
454341494744545249555247
403836434138494745504845
373431383532464239474237
322826363028443734453734
242117272420373330393430
191817302928312927
Octave band
Center frequency (CPS)
2
125
3
250
4
500
6
2000
7
4000
8
8000
5
1000
TYPICAL ROOM EFFECT
Subtract the appropriate room effect value from the unit sound power level, by octave band. The resulting soundpressure values can then be plotted on an octave band analysis chart.
Hard room (Hospital)Medium room (Hotel)Soft room (Office)
03.03.3
0.86.97.2
2.57.510.3
3.58.511.0
4.08.510.5
4.88.6
10.5
5.88.510.7
Octave band
Center frequency (CPS)
2
125
3
250
4
500
6
2000
7
4000
8
8000
5
1000
EXTERNAL STATIC PRESSURE DATA
Fan coil model Fan speed
TVA / TVE / TVS 350
TVA / TVE / TVS 450
TVA / TVE / TVS 600
TVA / TVE / TVS 800
TVA / TVE / TVS 1000
TVA / TVE / TVS 1200
LowMed.HighLowMed.HighLowMed.HighLowMed.HighLowMed.HighLowMed.High
0.00270315350350410450460545600615720800780920100092010801200
0.0526031033534040044044553059060070078576090098090010601170
0.1025030032032038542042551056557567075073086094086010201120
0.152402853003053704004104905405506407207008209008259801080
0.202202652802803453753804605005106006706507708407709201000
E.S.P. (inches of water)
1
8
2
10
9
4
5
SIDESECTION
FRONTVIEW
TOPVIEW
6
7
3
81
"2
C
D
4"
48"
86"
6"
A
6"
33"
B
21
"1
9
VERTICAL FAN COIL UNIT – “TVA” SERIES
TWO PIPE CHANGEOVER, C.W./H.W., WITHOUT AUXILIARY ELECTRIC HEATER
For details of factory mounted riserpackage refer to drawing TVR2 on page 14.
1. Double deflection supply air grille. Left, right, backor front locations. Dimension “D” varies withc.f.m., 5”, 8”, 10”, 12”, 14” or 16”.
2. Return air grille with hinged panel and disposablefilter.
3. Centerline of coil branch connections,location at left, right or back.
4. Copper drain stub, flexible hose to condensate riser.5. Insulated drain pan.
6. C.W./H.W. two pipe coil.7. Direct drive centrifugal fan.8. Optional top supply air opening.9. Electrical box used for a unit mounted
line voltage thermostat or fan speedswitch.
10. Service panel.
MODELTVA 350TVA 450TVA 600TVA 800TVA 1000TVA 1200
A17”17”20”20”20”20”
B17”17”20”20”24”24”
C14”14”14”14”16”16”
10
SIDESECTION
FRONTVIEW
TOPVIEW
4
6
2
3
1
8
10
9
7
11
5
86"
48"
6"6"
4"
D
C B
33"
81
"221
"1
A
VERTICAL FAN COIL UNIT – “TVE” SERIES
TWO PIPE CHANGEOVER, C.W./H.W., WITH AUXILIARY OR FULL SIZE ELECTRIC HEATER
For details of factory mounted riserpackage refer to drawing TVR2 on page 14.
1. Double deflection supply air grille.Left, right, back or front locations.Dimension “D” varies with c.f.m., 5”, 8”,10”, 12”, 14” or 16”.
2. Return air grille with hinged panel anddisposable filter.
3. Centerline of coil branch connections,location at left, right or back.
4. Copper drain stub, flexible hose tocondensate riser.
5. Insulated drain pan.6. C.W./H.W. two pipe coil.7. Direct drive centrifugal fan.8. Optional top supply air opening.9. Electrical box used for a unit mounted line
voltage thermostat or fan speed switch.10. Service panel.11. Electric heating coil.
MODELTVE 350TVE 450TVE 600TVE 800TVE 1000TVE 1200
A17”17”20”20”20”20”
B17”17”20”20”24”24”
C14”14”14”14”16”16”
11
1
2
4
5
6
73
9
10
8
D
4"
48"
86"
33"
6"
A
6"
C B
81
"221
"1
SIDESECTION
FRONTVIEW
TOPVIEW
VERTICAL FAN COIL UNIT – “TVS” SERIES
FOUR PIPE C.W./H.W.
For details of factory mounted riserpackage refer to drawing TVR4 on page 15.
1. Double deflection supply air grille.Left, right, back or front locations.Dimension “D” varies with c.f.m., 5”, 8”,10”, 12”, 14” or 16”.
2. Return air grille with hinged panel anddisposable filter.
3. Centerline of coil branch connections,location at left, right or back.
4. Copper drain stub, flexible hose tocondensate riser.
5. Insulated drain pan.6. C.W./H.W. coils in a common frame.7. Direct drive centrifugal fan.8. Optional top supply air opening.9. Electrical box used for a unit mounted
line voltage thermostat or fan speedswitch.
10. Service panel.
MODELTVS 350TVS 450TVS 600TVS 800TVS 1000TVS 1200
A17”17”20”20”20”20”
B17”17”20”20”24”24”
C14”14”14”14”16”16”
12
1
811
2
10
9
5
3
4
76
D
W A
C B
[2A + W]
81
"221
"1
FRONT VIEWSIDE SECTION
MASTERSLAVE
4"
48"
86"
6"
TANDEM VERTICAL FAN COIL SYSTEM - “TV” SERIESBACK TO BACK ARRANGEMENT
For details of factory mounted riser dimensions referto drawings TVR2 and TVR4.NOTE: Dimension “W” is variable.
1. Double deflection supply air grille.Left, right, back or front locations.Dimension “D” varies with c.f.m., 5”, 8”,10”, 12”, 14” or 16”.
2. Return air grille with hinged panel anddisposable filter.
3. Factory mounted riser package.4. Copper drain stub, flexible hose to
condensate riser.5. Insulated drain pan.
6. C.W./H.W. two pipe or four pipe coil.7. Direct drive centrifugal fan.8. Optional top supply air opening.9. Electrical box used for a unit mounted
line voltage thermostat or fan speedswitch.
10. Service panel.11. 5/8” gypsum board.
MODELTVA TVE TVS 350TVA TVE TVS 450TVA TVE TVS 600TVA TVE TVS 800TVA TVE TVS 1000TVA TVE TVS 1200
A17”17”20”20”20”20”
B17”17”20”20”24”24”
C14”14”14”14”16”16”
13
W BC
[2B + W]
MASTERSLAVE 8
1
2
7 6
5
34
9
10
11
D
4"
6"
48"
86"
81
"221
"1
SIDE SECTION
FRONT VIEWBACK VIEW
A
TANDEM VERTICAL FAN COIL SYSTEM - “TV” SERIESSIDE TO SIDE ARRANGEMENT
For details of factory mounted riser dimensions referto drawings TVR2 and TVR4.NOTE: Dimension “W” is variable.
1. Double deflection supply air grille.Left, right, back or front locations.Dimension “D” varies with c.f.m., 5”, 8”,10”, 12”, 14” or 16”.
2. Return air grille with hinged panel anddisposable filter.
3. Factory mounted riser package.4. Copper drain stub, flexible hose to
condensate riser.5. Insulated drain pan.
6. C.W./H.W. two pipe or four pipe coil.7. Direct drive centrifugal fan.8. Optional top supply air opening.9. Electrical box used for a unit mounted
line voltage thermostat or fan speedswitch.
10. Service panel.11. 5/8” gypsum board.
MODELTVA TVE TVS 350TVA TVE TVS 450TVA TVE TVS 600TVA TVE TVS 800TVA TVE TVS 1000TVA TVE TVS 1200
A17”17”20”20”20”20”
B17”17”20”20”24”24”
C14”14”14”14”16”16”
14
1
3
2
41
33"
R C S
RCS
21
"3 21
"3
TOPVIEW
LEFT RISERS BACK RISERS RIGHT RISERS
E
F.F.L.
6"
SIDE VIEW
R C S
CL
RISER PACKAGE – TWO PIPE SYSTEM
FAN COIL SERIES “TVA” AND “TVE”
1. Flange around return air opening on front of unit.2. Insulated copper risers, type “M” or type “L”.3. Top end expanded to allow a 2” insertion of the riser from above.4. Optional 1/2” hard copper stub-out to tandem fan coil unit.
• The supply and return positionscan be reversed to cater for suitelayout variations on the riserstack.
• Dimension “E” is to suit the floorto floor height.
• If the floor to floor height exceeds9ft., separate extension piecesbetween floors are required.
S = Supply riserR = Return riserC = Condensate riser
DRAWING # TVR2
15
1
3 HW
SH
WR
C CW
RC
WS
HW
SH
WR C
CW
RC
WSHWS
HWRCCWRCWS
43
"3 85
"2 85
"2 43
"3
TOPVIEW
LEFT RISERS BACK RISERS RIGHT RISERS
6"
2
41
33"
E
F.F.L.
SIDE VIEW
CL
RISER PACKAGE – FOUR PIPE SYSTEM
FAN COIL SERIES “TVS”
1. Flange around return air opening on front of unit.2. Insulated copper risers, type “M” or type “L”.3. Top end expanded to allow a 2” insertion of the riser from above.4. Optional 1/2” hard copper stub-out to tandem fan coil unit.
• The supply and return positionscan be reversed to cater for suitelayout variations on the riserstack.
• Dimension “E” is to suit the floorto floor height.
• If the floor to floor height exceeds9ft., separate extension piecesbetween floors are required.
HWS = Hot water supply riserHWR = Hot water return riserCWS = Chilled water supply riserCWR = Chilled water return riserC = Condensate riser
DRAWING # TVR4
16
5
2
5
4
4 1
35
PLAN VIEW
SIDESECTION
W
L
43
"
CL
LOCATION OF FLOOR OPENING FOR RISERS
When the project has riserpipe diameters 2” or largerplus 1” thickness insulation,dimension “W” should beincreased to 6”.
1. Floor slab.2. Opening in floor slab.3. Insulated risers.4. Return air opening flange on front of unit.5. Alternative positions for return air opening.
FAN COIL SERIESTVATVETVS
W5”5”5”
L14”14”17”
17
5
2
1
3 4
L
L = F + 2"
92"F
TYPICAL FAN COIL UNIT INSTALLATION - NEW CONSTRUCTION
RISER PACKAGE FACTORY ATTACHED TO THE FAN COIL UNIT
Important notes:
• The 92” dimension for riser height must bemaintained during installation for all unitson all floors.If this is not done the riser stub-out to thecoil will not be centered in the slot in thefan coil body.
• If dimension “F” exceeds 9ft., separateextension pipes between floors are required,field installed.
• Firestopping in the floor opening is by thecontractor.
1. Fan coil unit.2. Riser package, factory attached to side
or back of fan coil unit.3. Rectangular opening in cast floor slab.4. Floor slab.5. Top of riser pipe expanded.
2” insertion of pipe from above.
INSTALLATION SEQUENCE:
A. Core-drill the floor slab. It might be necessaryto x-ray the slab to avoid re-bar.
B. Install risers using the template provided forlocating the riser stubs vertically and at thecorrect horizontal centerlines. Anchor the risersand make good the insulation. Fit fire-stop into the hole in the floor slab. The risers can bepressure tested at this stage.
Note: The risers are in two pieces so that theywill fit into the elevator.
C. Bring the fan coil into the room using a two-wheel hand truck. Remove and discard thetemporary branch loop support bracket. Push thefan coil into position so that the riser stubs and ball valves penetrate the back or side of the fancoil. Push the coil branch loops into the male coupling on the stub and tighten the ferrule/nutprovided. Attach the flexible drain hose to thecondensate stub. Shim the unit so that it isvertical.
18
3
1
4
2
5
L
L = F + 2"
92"F
33"
21
"2
TYPICAL FAN COIL UNIT INSTALLATION - RETROFIT
RISERS INSTALLED SEPARATELY
1. Fan coil unit.2. Insulated copper riser assembly.3. Core-drilled holes in floor slab.
4. Supply and return riser stubs with ballvalves and compression fittings.
5. Condensate riser stub.
19
1
2 3 4
2"
7"5"
14"
21
"1
CL
LOCATION OF OPTIONAL SECONDARY RETURN AIR OPENING
ALL “TV” SERIES FAN COIL UNITS
Notes:
• The opening can be in the back panel or in either side.
• The fan coil unit is a draw-through type and the drain pan is low in theunit. This restricts the height of the opening to the 1 1/2” dimensionshown above.
1. Fan coil cabinet.2. Secondary return air opening.3. Secondary return air grille with filter media.4. Sleeving collar.
20
21
"2
21
"2 21
"2
21
"2
LEFT RISERS
BACK RISERS
SIDEPANEL
BACKPANEL
RIGHT RISERS
A B
LOCATION OF OPTIONAL OUTDOOR AIR INTAKE DUCT
ALL “TV” SERIES FAN COIL UNITS
Duct inlet in cabinetis 3” diameter
MODEL35045060080010001200
A17”17”20”20”20”20”
B17”17”20”20”24”24”
21
2
6
5
3
4 8
1 4
6
7
PART NUMBERS:
14" x 48" - FSM 131 16" x 48" - FSM 132
Approximately1/16" clearance
Section through collar and grille frame
INSTALLATION OF THE RETURN AIR GRILLE
Sequence of installation by the contractor:
A. If the drywall has not been installed flush with the outer edge of the collar on the unit and if the gapbetween the inner surface of the drywall and the outer edge of the collar exceeds 1/2”, the openingwill have to be sleeved.
B. Insert the grille into the collar in the fan coil unit so that the grille frame is against the drywall.
C. Lift the hinged panel in the grille and secure the grille by fitting two sheet metal screws as shownabove. Do not overtighten the screws as this might distort the grille frame and cause the hinged panelto be a loose fit in the retaining clips.
D. Install the filter and close the access panel.
1. Hinged access panel2. Access panel retaining clip3. Throw-away 1” filter4. Grille frame
5. Filter channel6. Sheet metal screw by installing contractor7. Collar around return air opening in fan coil unit8. Drywall
22
Heating Capacities - 2 Pipe Coils
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
Btuh
25970
27480
28430
29100
29580
29950
WTD
35.5
28.2
24.0
19.9
17.4
15.4
WPD
0.5
0.9
1.2
1.7
2.2
2.8
Btuh
29600
31220
32220
32900
33380
33750
WTD
40.4
32.0
26.4
22.5
19.6
17.3
WPD
0.7
1.2
1.7
2.3
3.0
3.8
3 ROW COIL 4 ROW COIL
TVA 350 TVE 350
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
Btuh
32430
34650
36070
37050
37760
38310
WTD
44.2
35.5
29.6
25.3
22.1
19.7
WPD
0.7
1.2
1.7
2.3
3.0
3.8
Btuh
36810
39290
40810
41840
42570
43120
WTD
50.1
40.2
33.4
28.6
25.0
22.1
WPD
0.9
1.5
2.3
3.1
4.1
5.1
3 ROW COIL 4 ROW COIL
TVA 450 TVE 450
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
Btuh
41200
44720
46990
48560
49710
50590
WTD
56.0
45.7
38.5
33.2
29.1
25.9
WPD
0.9
1.4
2.1
2.8
3.6
4.6
Btuh
46420
50510
53040
54740
55950
56860
WTD
63.0
51.5
43.4
37.3
32.7
29.1
WPD
1.2
1.9
2.7
3.8
4.9
6.2
3 ROW COIL 4 ROW COIL
TVA 600 TVE 600
g.p.m.
2.0
2.5
3.0
3.5
4.0
5.0
Btuh
55240
58850
61380
63240
64670
66710
WTD
56.3
48.1
41.8
37.0
33.1
27.4
WPD
1.8
2.6
3.6
4.6
5.8
8.5
Btuh
62230
66430
69300
71370
72920
75080
WTD
63.4
54.2
47.2
41.7
37.3
30.8
WPD
2.4
3.5
4.8
6.2
7.8
11
3 ROW COIL 4 ROW COIL
TVA 800 TVE 800
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
Btuh
74170
79020
82030
84070
85550
86660
WTD
50.5
40.4
33.6
28.7
25.1
22.2
WPD
4.2
6.8
10
14
18
23
Btuh
83460
88950
92240
94400
95930
97070
WTD
56.7
45.4
37.8
32.2
28.1
24.9
WPD
5.6
9.2
13
18
24
30
3 ROW COIL 4 ROW COIL
TVA 1000 TVE 1000
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
Btuh
83770
90300
94400
97220
99250
100800
WTD
56.9
46.1
38.6
33.2
29.1
25.8
WPD
4.6
7.6
11
15
20
25
Btuh
94230
101850
106500
109600
111700
113400
WTD
63.9
52.0
43.5
37.4
32.7
29.1
WPD
6.2
10
15
20
26
33
3 ROW COIL 4 ROW COIL
TVA 1200 TVE 1200
• WTD = water temperature drop in ˚FWPD = water pressure drop across coil in ft. of water.
• Capacities are for high fan speed.• Capacities are for 70˚F E.A.T.• Capacities are for 180˚F E.W.T.
For other water temperatures, multiply the heating capacity by thecorrection factor in table H1.
• L.A.T = E.A.T. + Btuh x 0.926c.f.m.
• For capacities different to those shown on this page, call the factory.• Lower W.P.D. can be achieved by using coils with multiple circuits,
call the factory for details.
E.W.T.
120
140
160
180
200
Correction Factor
0.45
0.63
0.81
1.00
1.18
TABLE H1
23
Heating Capacities - 4 Pipe Coils
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
Btuh
13940
14540
14930
15200
15400
15570
WTD
19.1
14.9
12.3
10.4
9.1
8.0
WPD
1.1
1.8
2.7
3.7
4.9
6.2
Btuh
20800
22020
22820
23390
23820
24150
WTD
28.4
22.6
18.8
16.0
14.0
12.4
WPD
0.3
0.6
0.8
1.1
1.5
1.8
1 ROW COIL 2 ROW COIL
TVS 350
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
Btuh
17730
18600
19160
19560
19853
20100
WTD
24.3
19.1
15.8
13.4
11.7
10.3
WPD
1.5
2.5
3.7
5.0
6.6
8.4
Btuh
26150
27900
29100
29890
30500
30970
WTD
35.7
28.6
23.9
20.5
17.9
15.9
WPD
0.5
0.8
1.1
1.5
2.0
2.5
1 ROW COIL 2 ROW COIL
TVS 450
1 ROW COIL 2 ROW COIL
TVS 6001 ROW COIL 2 ROW COIL
TVS 800
1 ROW COIL 2 ROW COIL
TVS 10001 ROW COIL 2 ROW COIL
TVS 1200
• WTD = water temperature drop in ˚FWPD = water pressure drop across coil in ft. of water.
• Capacities are for high fan speed.• Capacities are for 70˚F E.A.T.• Capacities are for 180˚F E.W.T.
For other water temperatures, multiply the heating capacity by thecorrection factor in table H1.
• L.A.T = E.A.T. + Btuh x 0.926c.f.m.
• For capacities different to those shown on this page, call the factory.• Lower W.P.D. can be achieved by using coils with multiple circuits,
call the factory for details.
E.W.T.
120
140
160
180
200
Correction Factor
0.45
0.63
0.81
1.00
1.18
TABLE H1
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
Btuh
23190
24530
25400
26020
26480
26840
WTD
31.7
25.2
20.9
17.8
15.6
13.8
WPD
1.8
3.0
4.5
6.1
8.0
10
Btuh
33620
36330
38110
39380
40330
41060
WTD
45.8
37.2
31.2
26.9
23.6
21.1
WPD
0.6
0.9
1.3
1.8
2.4
3.0
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
Btuh
40780
42580
43720
44520
–
–
WTD
27.9
21.9
18.0
15.3
–
–
WPD
9.1
15
22
30
–
–
Btuh
60600
64340
66730
68400
69620
70560
WTD
41.3
32.9
27.4
23.4
20.4
18.1
WPD
2.7
4.5
6.6
9.1
12
15
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
Btuh
46440
48760
50260
51300
–
–
WTD
31.7
25.0
20.6
17.6
–
–
WPD
10
17
24
33
–
–
Btuh
68570
73470
76630
78840
80470
81720
WTD
46.7
37.6
31.4
26.9
23.6
21.0
WPD
3.0
5.0
7.3
10
13
16
g.p.m.
2.0
2.5
3.0
3.5
4.0
4.5
Btuh
30860
32190
33130
33830
34830
35180
WTD
31.6
26.4
22.7
19.9
17.7
14.5
WPD
3.8
5.6
7.7
10
13
19
Btuh
45130
47860
49810
51280
52420
54090
WTD
46.1
39.2
34.0
30.0
26.9
22.2
WPD
1.2
1.7
2.3
3.0
3.8
5.6
24
Cooling Capacities - TVA350, TVE350, TVS350
• WTR = water temperature rise in ˚FWPD = water pressure drop across coil in ft. of water.
• Capacities are for high fan speed.• For capacities different to those shown on this page, call the factory.• Total and sensible cooling capacities are in Btuh.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
0.7
1.2
1.8
2.4
3.2
4.0
TOTAL
6150
7360
8180
8230
9370
9800
SENS.
5570
6050
6380
6640
6870
7050
WTR
8.2
7.4
6.5
5.9
5.4
4.9
TOTAL
6780
8100
9000
9710
10300
10780
SENS.
6210
6720
7080
7360
7600
7800
WTR
9.0
8.1
7.2
6.5
5.9
5.4
WTR
10.2
9.1
8.1
7.3
6.6
6.1
TOTAL
7650
9130
10140
10940
11600
12130
SENS.
6740
7290
7680
8000
8250
8460
TOTAL
8570
10210
11340
12220
12970
13540
SENS.
6940
7540
7950
8290
8580
8800
WTR
11.4
10.2
9.1
8.2
7.4
6.8
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 43˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
0.7
1.2
1.8
2.4
3.2
4.0
TOTAL
5480
6620
7370
7960
8460
8830
SENS.
5480
5760
6050
6290
6490
6650
WTR
7.3
6.6
5.9
5.3
4.8
4.4
TOTAL
6100
7350
8180
8840
9390
9800
SENS.
6100
6430
6750
7010
7230
7400
WTR
8.1
7.4
6.5
5.9
5.4
4.9
WTR
9.4
8.4
7.4
6.7
6.1
5.6
TOTAL
7010
8370
9300
10050
10690
11140
SENS.
6500
7000
7350
7640
7890
8070
TOTAL
7920
9440
10450
11330
12040
12540
SENS.
6710
7250
7640
7950
8220
8410
WTR
10.6
9.4
8.4
7.6
6.9
6.3
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 45˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.0
1.6
2.4
3.3
4.3
5.4
TOTAL
7300
8670
9610
10330
10930
11390
SENS.
6310
6870
7260
7560
7810
8010
WTR
9.7
8.7
7.7
6.9
6.2
5.7
TOTAL
8040
9550
10580
11370
12020
12520
SENS.
7020
7620
8040
8370
8640
8850
WTR
10.7
9.6
8.5
7.6
6.9
6.3
WTR
12.1
10.8
9.5
8.5
7.7
7.0
TOTAL
9080
10770
11920
12800
13540
14090
SENS.
7630
8280
8730
9100
9400
9630
TOTAL
10180
12050
13320
14310
15120
15730
SENS.
7880
8580
9080
9470
9800
10050
WTR
13.6
12.1
10.7
9.5
8.6
7.9
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 43˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.0
1.6
2.4
3.3
4.3
5.4
TOTAL
6550
7800
8650
9310
9870
10260
SENS.
6020
6510
6860
7130
7360
7530
WTR
8.7
7.8
6.9
6.2
5.6
5.1
TOTAL
7290
8660
9600
10340
10750
11390
SENS.
6730
7270
7640
7940
8190
8370
WTR
9.7
8.7
7.7
6.9
6.3
5.7
WTR
11.1
9.9
8.7
7.8
7.1
6.5
TOTAL
8310
9860
10930
11760
12450
12940
SENS.
7340
7920
8340
8670
8950
9150
TOTAL
9390
11120
12320
13260
14030
14560
SENS.
7590
8230
8680
9050
9360
9570
WTR
12.5
11.1
9.9
8.8
8.0
7.3
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 45˚F E.W.T.
25
Cooling Capacities - TVA450, TVE450, TVS450
• WTR = water temperature rise in ˚FWPD = water pressure drop across coil in ft. of water.
• Capacities are for high fan speed.• For capacities different to those shown on this page, call the factory.• Total and sensible cooling capacities are in Btuh.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.0
1.6
2.4
3.3
4.3
5.4
TOTAL
7600
9160
10250
11110
11840
12410
SENS.
7070
7680
8110
8460
8760
9000
WTR
10.1
9.2
8.2
7.4
6.8
6.2
TOTAL
8390
10090
11280
12220
13020
13640
SENS.
7880
8530
9000
9380
9700
9950
WTR
11.2
10.1
9.0
8.2
7.4
6.8
WTR
12.6
11.4
10.2
9.2
8.4
7.7
TOTAL
9470
11370
12710
13770
14670
15360
SENS.
8550
9250
9760
10180
10530
10800
TOTAL
10620
12720
14210
15400
16400
17150
SENS.
8800
9567
10110
10560
10940
11240
WTR
14.2
12.7
11.4
10.3
9.4
8.6
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 43˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.0
1.6
2.4
3.3
4.3
5.4
TOTAL
6930
8220
9210
10000
10680
11170
SENS.
6930
7300
7700
8010
8290
8490
WTR
9.2
8.2
7.4
6.7
6.1
5.6
TOTAL
7710
9130
10230
11110
11850
12390
SENS.
7710
8160
8590
8930
9230
9440
WTR
10.3
9.1
8.2
7.4
6.8
6.2
WTR
11.3
10.4
9.3
8.4
7.7
7.0
TOTAL
8500
10400
11640
12640
13480
14080
SENS.
8500
8890
9360
9740
10060
10300
TOTAL
9780
11730
13120
14250
15200
15850
SENS.
8500
9200
9700
10120
10480
10730
WTR
13.1
11.7
10.5
9.5
8.7
7.9
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 45˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.3
2.1
3.1
4.3
5.7
7.2
TOTAL
8900
10680
11940
12920
13730
14350
SENS.
7930
8650
9170
9580
9920
10190
WTR
11.9
10.7
9.6
8.6
7.9
7.2
TOTAL
9800
11760
13140
14220
15110
15780
SENS.
8840
9600
10160
10610
10980
11260
WTR
13.1
11.8
10.5
9.5
8.6
7.9
WTR
14.8
13.3
11.9
10.7
9.7
8.9
TOTAL
11070
13260
14800
16020
17020
17760
SENS.
9600
10430
11040
11530
11940
12240
TOTAL
12410
14840
16550
17910
19020
19820
SENS.
9900
10800
11460
11990
12440
12770
WTR
16.6
14.8
13.3
11.9
10.9
9.9
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 43˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.3
2.1
3.1
4.3
5.7
7.2
TOTAL
8060
9570
10720
11630
12380
12920
SENS.
8060
8200
8660
9040
9350
9580
WTR
10.8
9.6
8.6
7.8
7.1
6.5
TOTAL
8970
10630
11900
12910
13740
14330
SENS.
8970
9160
9660
10070
10410
10650
WTR
12.0
10.6
9.5
8.6
7.9
7.2
WTR
13.5
12.1
10.8
9.8
8.9
8.1
TOTAL
10100
12110
13550
14700
15630
16290
SENS.
9230
9980
10540
10990
11370
11630
TOTAL
11410
13660
15280
16560
17620
18330
SENS.
9530
10350
10960
11460
11880
12160
WTR
15.2
13.7
12.2
11.0
10.1
9.2
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 45˚F E.W.T.
26
Cooling Capacities - TVA600, TVE600, TVS600
• WTR = water temperature rise in ˚FWPD = water pressure drop across coil in ft. of water.
• Capacities are for high fan speed.• For capacities different to those shown on this page, call the factory.• Total and sensible cooling capacities are in Btuh.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.2
1.9
2.8
3.9
5.1
6.4
TOTAL
9580
11540
13050
14270
15300
16100
SENS.
9580
10000
10600
11090
11500
11840
WTR
12.8
11.5
10.4
9.5
8.7
8.0
TOTAL
10600
12700
14360
15700
16830
17700
SENS.
10600
11100
11770
12300
12750
13100
WTR
14.1
12.7
11.5
10.5
9.6
8.8
WTR
15.8
14.3
13.0
11.8
10.8
10.0
TOTAL
11810
14330
16190
17700
18960
19910
SENS.
11140
12060
12770
13350
13840
14220
TOTAL
13240
16030
18100
19790
21200
22230
SENS.
11450
12440
13200
13830
14380
14770
WTR
17.7
16.0
14.5
13.2
12.1
11.1
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 43˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.2
1.9
2.8
3.9
5.1
6.4
TOTAL
8970
10320
11700
12800
13760
14460
SENS.
8970
9520
10060
10500
10880
11160
WTR
12.0
10.3
9.4
8.5
7.9
7.2
TOTAL
9990
11460
12990
14230
15280
16030
SENS.
9990
10650
11230
11720
12130
12430
WTR
13.3
11.5
10.4
9.5
8.7
8.0
WTR
14.7
13.1
11.8
10.8
9.9
9.1
TOTAL
11000
13060
14790
16200
17390
18220
SENS.
11000
11600
12230
12770
13230
13550
TOTAL
12150
14730
16670
18270
19600
20510
SENS.
11070
11980
12680
13260
13760
14110
WTR
16.2
14.7
13.3
12.2
11.2
10.3
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 45˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.5
2.5
3.8
5.2
6.8
8.6
TOTAL
11050
13220
15000
16420
17600
18480
SENS.
11050
11140
11860
12450
12940
13320
WTR
14.7
13.2
12.0
11.0
10.1
9.2
TOTAL
12220
14560
16500
18070
19360
20320
SENS.
12220
12390
13160
13800
14330
14740
WTR
16.3
14.6
13.2
12.1
11.1
10.2
WTR
18.0
16.4
14.9
13.6
12.5
11.4
TOTAL
13480
16400
18600
20360
21810
22860
SENS.
12340
13440
14290
14990
15580
16010
TOTAL
15100
18360
20800
22770
24380
25520
SENS.
12700
13890
14810
15570
16210
16680
WTR
20.2
18.4
16.7
15.2
13.9
12.8
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 43˚F E.W.T.
g.p.m.
1.5
2.0
2.5
3.0
3.5
4.0
WPD
1.5
2.5
3.8
5.2
6.8
8.6
TOTAL
10340
11800
13420
14730
15820
16600
SENS.
10340
10580
11220
11750
12200
12520
WTR
13.8
11.8
10.7
9.8
9.0
8.3
TOTAL
11500
13110
14910
16360
17560
18410
SENS.
11500
11820
12530
13104
13590
13940
WTR
15.4
13.1
11.9
10.9
10.0
9.2
WTR
16.9
14.8
13.6
12.4
11.4
10.5
TOTAL
12690
14930
16970
18620
19980
20920
SENS.
12690
12880
13660
14300
14840
15220
TOTAL
13820
16850
19140
21000
22520
23550
SENS.
12240
13330
14180
14890
15480
15880
WTR
18.4
16.9
15.3
14.0
12.9
11.8
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 45˚F E.W.T.
27
Cooling Capacities - TVA800, TVE800, TVS800
• WTR = water temperature rise in ˚FWPD = water pressure drop across coil in ft. of water.
• Capacities are for high fan speed.• For capacities different to those shown on this page, call the factory.• Total and sensible cooling capacities are in Btuh.
g.p.m.
2.0
2.5
3.0
3.5
4.0
4.5
WPD
2.4
3.5
4.9
6.4
8.1
11.9
TOTAL
13570
15580
17260
18690
19790
21240
SENS.
12570
13350
14020
14600
15040
15640
WTR
13.6
12.5
11.5
10.7
9.9
8.5
TOTAL
14940
17150
18990
20570
21760
23350
SENS.
14010
14850
15570
16190
16660
17310
WTR
15.0
13.7
12.7
11.8
10.9
9.3
WTR
16.9
15.5
14.3
13.3
12.2
10.5
TOTAL
16850
19340
21410
23180
24490
26290
SENS.
15190
16110
16890
17570
18080
18790
TOTAL
18860
21630
23950
25920
27330
29362
SENS.
15620
16620
17470
18200
18740
19520
WTR
18.9
17.3
16.0
14.8
13.7
11.8
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 43˚F E.W.T.
g.p.m.
2.0
2.5
3.0
3.5
4.0
5.0
WPD
2.4
3.5
4.9
6.4
8.1
11.9
TOTAL
12480
13920
15460
16770
17730
19090
SENS.
12480
12710
13300
13820
14210
14760
WTR
12.5
11.1
10.3
9.6
8.9
7.6
TOTAL
13880
15470
17170
18620
19670
21190
SENS.
13880
14210
14860
15420
15830
16430
WTR
13.9
12.4
11.5
10.6
9.8
8.5
WTR
15.3
14.1
13.0
12.1
11.2
9.6
TOTAL
15290
17610
19550
21200
22350
24090
SENS.
15290
15470
16190
16810
17250
17920
TOTAL
17280
19860
22050
23900
25160
27130
SENS.
15070
15980
16770
17450
17920
18660
WTR
17.3
15.9
14.7
13.7
12.6
10.9
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 45˚F E.W.T.
g.p.m.
2.0
2.5
3.0
3.5
4.0
5.0
WPD
2.4
3.5
4.8
6.3
8.0
11.9
TOTAL
15280
17680
19660
21340
22620
24360
SENS.
13890
14840
15640
16330
16870
17600
WTR
15.3
14.1
13.1
12.2
11.3
9.7
TOTAL
16820
19460
21640
23490
24860
26780
SENS.
15470
16490
17360
18110
18680
19470
WTR
16.8
15.6
14.4
13.4
12.4
10.7
WTR
19.0
17.6
16.3
15.1
14.0
12.1
TOTAL
18970
21930
24400
26470
27980
30150
SENS.
16770
17890
18850
19670
20280
21160
TOTAL
21220
24530
27290
29590
31230
33670
SENS.
17270
18490
19530
20420
21060
22040
WTR
21.2
19.6
18.2
16.9
15.6
13.5
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 43˚F E.W.T.
g.p.m.
2.0
2.5
3.0
3.5
4.0
5.0
WPD
2.4
3.5
4.8
6.3
8.0
11.9
TOTAL
14280
15760
17590
19120
20250
21890
SENS.
14280
14080
14800
15420
15880
16560
WTR
14.3
12.6
11.7
10.9
10.1
8.8
TOTAL
15890
17510
19530
21240
22460
24290
SENS.
15890
15730
16520
17200
17690
18440
WTR
15.9
14.0
13.0
12.1
11.2
9.7
WTR
17.2
16.0
14.8
13.8
12.8
11.1
TOTAL
17190
19930
22240
24170
25530
27620
SENS.
16120
17140
18010
18760
19290
20130
TOTAL
19390
22480
25080
27240
28730
31100
SENS.
16620
17730
18690
19510
20080
21010
WTR
19.4
18.0
16.7
15.6
14.4
12.4
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 45˚F E.W.T.
28
Cooling Capacities - TVA1000, TVE1000, TVS1000
• WTR = water temperature rise in ˚FWPD = water pressure drop across coil in ft. of water.
• Capacities are for high fan speed.• For capacities different to those shown on this page, call the factory.• Total and sensible cooling capacities are in Btuh.
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
WPD
5.7
9.4
14
19
25
32
TOTAL
20140
23450
25490
27150
28440
29470
SENS.
16980
18310
19140
19830
20370
20800
WTR
13.4
11.7
10.2
9.1
8.1
7.4
TOTAL
22170
25780
28040
29860
31270
32400
SENS.
18880
20300
21200
21940
22520
23000
WTR
14.8
12.9
11.2
10.0
8.9
8.1
WTR
16.7
14.5
12.6
11.2
10.1
9.1
TOTAL
24990
29000
31560
33610
35190
36460
SENS.
20480
22010
23010
23820
24460
24980
TOTAL
27960
32370
35260
37540
39300
40700
SENS.
21140
22780
23880
24770
25460
26020
WTR
18.7
16.2
14.1
12.5
11.2
10.2
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 43˚F E.W.T.
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
WPD
5.7
9.4
14
19
25
32
TOTAL
17990
20960
22880
24410
25600
26550
SENS.
16140
17310
18080
18700
19190
19580
WTR
12.0
10.5
9.2
8.1
7.3
6.6
TOTAL
19980
23250
25390
27090
28400
29460
SENS.
18040
19300
20140
20820
21350
21780
WTR
13.3
11.6
10.2
9.0
8.1
7.4
WTR
15.2
13.2
11.6
10.3
9.2
8.4
TOTAL
22750
26420
28870
30800
32300
33500
SENS.
19640
21020
21960
22710
23300
23780
TOTAL
25660
29730
32520
34680
36360
37700
SENS.
20310
21790
22830
23660
24310
24830
WTR
17.1
14.9
13.0
11.6
10.4
9.4
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 45˚F E.W.T.
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
WPD
7.6
12
18
26
34
42
TOTAL
22590
26510
29020
30970
32460
33620
SENS.
18760
20370
21420
22250
22890
23400
WTR
15.1
13.3
11.6
10.3
9.3
8.4
TOTAL
24860
29140
31910
34050
35680
36960
SENS.
20850
22570
23710
24610
25300
25850
WTR
16.6
14.6
12.8
11.4
10.2
9.2
WTR
18.7
16.4
14.4
12.8
11.5
10.4
TOTAL
28020
32780
35920
38330
40160
41600
SENS.
22630
24490
25760
26750
27510
28120
TOTAL
31340
36590
40130
42810
44850
46440
SENS.
23390
25390
26790
27870
28710
29370
WTR
20.9
18.3
16.1
14.3
12.8
11.6
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 43˚F E.W.T.
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
WPD
7.6
12
18
26
34
42
TOTAL
20130
23670
26020
27830
29210
30300
SENS.
17780
19200
20160
20920
21500
21960
WTR
13.4
11.8
10.4
9.3
8.4
7.6
TOTAL
22360
26260
28870
30880
32410
33610
SENS.
19870
21400
22460
23280
23920
24420
WTR
14.9
13.1
11.6
10.3
9.3
8.4
WTR
17.0
14.9
13.1
11.7
10.5
9.6
TOTAL
25450
29830
32830
35110
36840
38200
SENS.
21650
23330
24510
25430
26130
26700
TOTAL
28700
33570
36980
39540
41490
43010
SENS.
22410
24230
25540
26550
27330
27950
WTR
19.2
16.8
14.8
13.2
11.7
10.8
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 45˚F E.W.T.
29
Cooling Capacities - TVA1200, TVE1200, TVS1200
• WTR = water temperature rise in ˚FWPD = water pressure drop across coil in ft. of water.
• Capacities are for high fan speed.• For capacities different to those shown on this page, call the factory.• Total and sensible cooling capacities are in Btuh.
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
WPD
6.2
10
15
21
28
35
TOTAL
21830
25800
28380
30490
32140
33470
SENS.
19360
20920
21960
22820
23500
24060
WTR
14.6
12.9
11.4
10.2
9.2
8.4
TOTAL
24040
28360
31220
33530
35340
36800
SENS.
21550
23220
24340
25270
26010
26600
WTR
16.0
14.2
12.5
11.2
10.1
9.2
WTR
18.1
16.0
14.1
12.6
11.4
10.4
TOTAL
27100
31900
35150
37740
39780
41410
SENS.
23360
25160
26410
27430
28230
28890
TOTAL
30320
35610
39270
42160
44430
46250
SENS.
24070
25990
27360
28470
29340
30060
WTR
20.2
17.8
15.7
14.1
12.7
11.6
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 43˚F E.W.T.
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
WPD
6.2
10
15
21
28
35
TOTAL
19550
23020
25430
27370
28890
30120
SENS.
19550
19820
20770
21550
22170
22670
WTR
13.0
11.5
10.2
9.1
8.3
7.5
TOTAL
21750
25530
28220
30370
32060
33420
SENS.
21750
22120
23160
24000
24680
25230
WTR
14.5
12.8
11.3
10.1
9.2
8.4
WTR
16.4
14.5
12.8
11.5
10.4
9.5
TOTAL
24610
29010
32100
34350
36450
37990
SENS.
22450
24070
25230
26170
26917
27520
TOTAL
27760
32640
36150
38890
41050
42780
SENS.
23160
24910
26190
27220
28040
28700
WTR
18.5
16.3
14.5
13.0
11.7
10.7
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
3 ROW COIL 45˚F E.W.T.
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
WPD
8.2
14
20
28
37
46
TOTAL
24240
28980
32190
34720
36670
38220
SENS.
21300
23200
24520
25580
26410
27070
WTR
16.2
14.5
12.9
11.6
10.5
9.6
TOTAL
26680
31850
35400
38180
40320
42020
SENS.
23700
25730
27170
28320
29220
29940
WTR
17.8
15.9
14.2
12.7
11.5
10.5
WTR
20.1
17.9
16.0
14.3
13.0
11.8
TOTAL
30070
35830
39860
42980
45390
47290
SENS.
25700
27910
29500
30760
31750
32540
TOTAL
33630
39990
44530
48000
50690
52810
SENS.
26500
28870
30620
31990
33070
33940
WTR
22.4
20.0
17.8
16.0
14.5
13.2
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 43˚F E.W.T.
g.p.m.
3.0
4.0
5.0
6.0
7.0
8.0
WPD
8.2
14
20
28
37
46
TOTAL
21550
25810
28800
31140
32950
34390
SENS.
20240
21920
23130
24080
24840
25440
WTR
14.4
12.9
11.5
10.4
9.4
8.6
TOTAL
23930
28630
31960
34550
36560
38150
SENS.
22640
24460
25780
26820
27650
28300
WTR
16.0
14.3
12.8
11.5
10.5
9.5
WTR
18.2
16.3
14.6
13.1
11.9
10.9
TOTAL
27240
32530
36350
39290
41570
43380
SENS.
24650
26630
28110
29270
30190
30920
TOTAL
30720
36610
40940
44250
46810
48840
SENS.
25440
27600
29230
30510
31510
32320
WTR
20.5
18.3
16.4
14.8
13.4
12.2
72DB/61.5 WB 75DB/63WB 78DB/65WB 80DB/67WB
▲
E.A.T. ˚F
4 ROW COIL 45˚F E.W.T.
30
Notes
31
Notes
32
Notes
TEMSPEC HVAC PRODUCTS
Vertical classroom unit ventilators. A full line of split system units and unitswith self-contained air conditioning, upto 5 tons of cooling. Exceptionallyquiet operation, competitive prices.
Temspec manufactures equipment to precisely meet specifications. Our technical staff work with the customer to provide the bestpossible HVAC solutions for specific applications.
PLANT LOCATION:
6720 Columbus Road
Mississauga, Ontario
Canada L5T 2G1
Tel: 1-888-TEMSPEC(1-888-836-7732)
Fax: 905-670-3592www.temspec.comEstablished 1971
• CLASSROOM UNITVENTILATORSChilled water and split system DX unitsplus units with self-contained airconditioning.
• VERTICAL STACK FAN COILUNITSFor concealed and exposed applications.
• CUSTOM FAN COIL UNITSVertical fan coil units for differentretrofit applications.
0702