Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
Temperature measuring and monitoring● Stainless steel temperature transmitters and sensors Pt 100/Pt 1000● Thermostats (also in Ex-versions)
Hf
14103_TTS62/4_GB_2000_Temp 06.11.2000 9:08 Uhr Seite 2
CONTENTSPage
General notes on temperature measurement
with resistance sensors 3Stainless steel
temperature
transmitters
and sensors
Stainless steel temperature transmitters 4
Stainless steel temperature sensors 5
Evaluation units Programmable digital displays with
2 limit value switches 6
Mechanical
thermostats(general notes)
The most important technical datas 8/9
Switching units 10
Temperature monitoring in
explosion-endangered areas 10
Mounting and adjustment 11/12
Room thermostats 13
Rod thermostats 14
Capillary tube thermostats 15
Frost protection thermostats 16
Two-phase frost protection 7
Accessories Immersion tubes 17
Wall brackets, plugs 18
Temperature monitors
and limiters –
TÜV component
tested
Temperature monitors and limiters –
component tested according to DIN 3440
(for steam and hot water) 19
3
Temperature
sensors
General notes on temperature measurementwith resistance sensors Pt 100 and Pt 1000
Connection possibilitiesfor Pt sensors
Two-wire connection
Advantage: Only 2 wires
Disadvantage: The line resistance RL
falsifies the measuring
result
Three-wire connection
Advantage: The line resistances are
taken into account
by the evaluation
electronics. The
measuring result is not
falsified
Disadvantage: 3 wires are required.
All 3 wires must have
the same resistance
Four-wire connection
Power supply
Advantage: The line resistances
do not play any role
because of the
evaluation electronics
(current feed and
high-ohmic voltage
interrogation). The
measuring result is
not falsified. The lines
can have different
resistances.
Disadvantage: 4 wires are required.
Connection wires with the same
colours are connected with one
another electrically.
Platinum temperature sensors Pt 00 or Pt 000 make use of the constant change in
resistance of materials with changing temperatures. Because of its good stability and high
reproducibility, a platinum-rhodium alloy specially suited for this is mainly used. The
resistance of the sensor becomes larger as the temperature rises.
The resistance values are stipulated in DIN IEC 75 as follows:
Pt 100 = 100 ohms at 0 hCPt 1000 = 1000 ohms at 0 hC
The resistance values for all temperatures are quoted in the above mentioned standard.The
resistance sensors are divided into 2 classes in accordance with their limiting deviations.
Class A: 0.15 K + 0.002 x t
Class B: 0.30 K + 0.005 x t*
*t is the numerical value of the temperature in hC (without taking the sign into account)
Resistance value of the Pt 00 sensors (excerpt from DIN 43 760, IEC 75)
Tempe- Basic values for Pt 00 (Ohm) Tempe-
rature rature
hC 0 2 3 4 5 6 7 8 9 0 hC
– 50 80.31 79.91 79.51 79.11 78.72 78.32 77.92 77.52 77.13 76.73 76.33 – 50
– 40 84.27 83.88 83.48 83.08 82.69 82.29 81.89 81.50 81.10 80.70 80.31 – 40
– 30 88.22 87.83 87.43 87.04 86.64 86.25 85.85 85.46 85.06 84.67 84.27 – 30
– 20 92.16 91.77 91.37 90.98 90.59 90.19 89.80 89.40 89.01 88.62 88.22 – 20
– 10 96.09 95.69 95.30 94.91 94.52 94.12 93.73 93.34 92.95 92.55 92.16 – 10
0 100.00 99.61 99.22 98.83 98.44 98.04 97.65 97.26 96.87 96.48 96.09 0
0 100.00 100.39 100.78 101.17 101.56 101.95 102.34 102.73 103.12 103.51 103.90 0
10 103.90 104.29 104.68 105.07 105.46 105.85 106.24 106.63 107.02 107.40 107.79 10
20 107.79 108.18 108.57 108.96 109.35 109.73 110.12 110.51 110.90 111.28 111.67 20
30 111.67 112.06 112.45 112.83 113.22 113.61 113.99 114.38 114.77 115.15 115.54 30
40 115.54 115.93 116.31 116.70 117.08 117.47 117.85 118.24 118.62 119.01 119.40 40
50 119.40 119.78 120.16 120.55 120.93 121.32 121.70 122.09 122.47 122.86 123.24 50
60 123.24 123.62 124.01 124.39 124.77 125.16 125.54 125.92 126.31 126.69 127.07 60
70 127.07 127.45 127.84 128.22 128.60 128.98 129.37 129.75 130.13 130.51 130.89 70
80 130.89 131.27 131.66 132.04 132.42 132.80 133.18 133.56 133.94 134.32 134.70 80
90 134.70 135.08 135.46 135.84 136.22 136.60 136.98 137.36 137.74 138.12 138.50 90
100 138.50 138.88 139.26 139.64 140.02 140.39 140.77 141.15 141.53 141.91 142.29 100
110 142.29 142.66 143.04 143.42 143.80 144.17 144.55 144.93 145.31 145.68 146.06 110
120 146.06 146.44 146.81 147.19 147.57 147.94 148.32 148.70 149.07 149.45 149.82 120
130 149.82 150.20 150.57 150.95 151.33 151.70 152.08 152.45 152.83 153.20 153.58 130
140 153.58 153.95 154.32 154.70 155.07 155.45 155.82 156.19 156.57 156.94 157.31 140
150 157.31 157.69 158.06 158.43 158.81 159.18 159.55 159.93 160.30 160.67 161.04 150
160 161.04 161.42 161.79 162.16 162.53 162.90 163.27 163.65 164.02 164.39 164.76 160
170 164.76 165.13 165.50 165.87 166.24 166.61 166.98 167.35 167.72 168.09 168.46 170
180 168.46 168.83 169.20 169.57 169.94 170.31 170.68 171.05 171.42 171.79 172.16 180
190 172.16 172.53 172.90 173.26 173.63 174.00 174.37 174.74 175.10 175.47 175.84 190
200 175.84 176.21 176.57 176.94 177.31 177.68 178.04 178.41 178.78 179.14 179.51 200
The resistance values of the Pt 000 are higher by one power of ten.
When Pt sensors are connected, the line resistances between the measuring point and
evaluation unit (e. g. transmitter) must be taken into account (see narrow column).
All FEMA evaluation units (transmitters and temperature switches) have an input circuit for
3-wire connection. The sensors must be connected in accordance with the following
diagrams. All 3 wires must be of equal length and have the same wire cross section to
compensate for the line resistances.
Two-wire sensor Three-wire sensor Four-wire sensor
Evaluation unit for
three-wire
connection
Evaluation unit for
three-wire
connection
Evaluation unit for
three-wire
connection
Measured valve
4
Typeseries
PZ 17
Temperature transmitters, output signal 4–20 mAmade of high-grade steel, sensor Pt 100
Technical data
Temperature ranges
Range No.
–50 . . . + 50 hC 55
–50 . . . +100 hC 51
0 . . . 50 hC 50
0 . . . 100 hC 100
0 . . . 200 hC 200
The no. has to be added to the temperature
range, e. g. PZ 171–200/200
Action direction
Rising temperature produces rising output
signal.
Installation position
arbitrary
Protective category
IP 65
Electrical connection
cable entry Pg
Operating voltage
12–36 V DC
Output signal
4–20 mA
Load
500 Ohms at 24 V DC
Response time in liquids
(63 % temperature change)
5 seconds
Linearity error
max. ± 0.1 % FS
Temperature drift
0.01 % FS/hC
Temperature at the transmitter head
–10 . . . 70 hC
Connection diagram
Materials
Sensor: 1.4571
Housing: 1.4301
Immersion tubes
for type PZ 7 see page 5.
Fixing flange R 187
for air duct probe PZ 177–. . . see page 5
171 177
The temperature transmitters consist completely of stainless steel. The transmitter module is
housed for easy access in the housing head and can also be replaced as required. A Pt 00,
Class B to DIN IEC 75 is used as sensor.
Type overview
Immersion depth L (mm) max. perm. pressure Screw-in(bar) thread G 1/2
100 40 PZ 171-100/. . .150 40 PZ 171-150/. . .200 35 PZ 171-200/. . .250 35 PZ 171-250/. . .
The pressure data apply up to a temperature of 250 hC
Immersion depth L (mm) Air duct* probe
100 PZ 177-100/. . .150 PZ 177-150/. . .200 PZ 177-200/. . .250 PZ 177-250/. . .
* Can be used only up to max. 200 hC
Dimensions
171 177
Tendering textTemperature transmitter complete in stainless steel with screw-in tread G 1/2 / union nut / air
duct probe immersion depth . . . mm, temperature range from . . . to . . . hC. Supply voltage
12–36 V DC, output signal 4–20 mA.
R 185–. . .
R 187
5
Typeseries
P 17
Temperature sensors Pt 00 / Pt 000in stainless steel version
The temperature sensors consist completely of stainless steel (tube: .457, terminal
housing: .430).Sensor element: Pt 00,Class B to DIN IEC75, three-wire connection, cable
entry Pg , degree of protection IP 65.
Temperature range –50 . . . 600 hC, for P 177: –50 . . . 220 hC.
Max. temperature at the connection head: 50 hC
Immersion probe with screw-in thread G 1/2, 8 mm l, –50 . . . 400 hC
max. perm. Type TypeImmersion depth L (mm) pressure (bar) Pt 000 Pt 00
100 40 P 271-100 P 171-100150 40 P 271-150 P 171-150200 35 P 271-200 P 171-200250 35 P 271-250 P 171-250
The pressure data apply up to a temperature of 250 hC, at temperatures up to 400 hC the
permissible pressure is reduced by 50 %.
Air duct probe 8 mm l, –50 . . . 220 hC
Type TypeImmersion depth L (mm) Pt 000 Pt 00
100 P 277-100 P 177-100150 P 277-150 P 177-150200 P 277-200 P 177-200250 P 277-250 P 177-250
Dimensions as for temperature transmitter of the same construction. See page 4.
Immersions tubes G1/2 (only for P 7 . . ., P 27 . . . and PZ 7 . . .)
Immersion depth (L) (mm) Type
100 R 85-100150 R 85-150200 R 85-200250 R 85-250
Fixing Flange
Fixing Flange R 187 for air duct probe, stainless steel 1.4571
6
Typeseries
AP
Programmable display,
with 2 limit value switches
Technical data
Input signals
Freely selectable by setting
jumpers (see type summary)
Housing front
48 x 96 mm (DIN)
Dimension display
For APT: hCFor APV: none
Display
3|-digit, LED 12.5 mm, red,
automatic “–”-sign
Display range
See type overview.
Other ranges can be set.
Decimal point
Programmable
Measuring rate
2.5 measurements/second
Keyboard
lockable with jumper
Programmable switching
outputs
2 changeover switches
Output relay switching
capacity
2 x 230 V, 5 A AC
Supply voltage
230 V, 50–60 Hz, 3 VA
Degree of protection (front)
IP 60. DIN 40.050
Working temperature
–0 to +50 hC
Type of connection
Lift terminals
Front cut-out
H x B: 44.5 x 90.5 mm
Installation depth
15 mm
Dimensions
Various routines for setting the following parameters are integrated in the digital display
which is controlled by microprocessor:
y Measuring range (starting and end point)
y Display range (starting and end point)
y Position of the decimal point
y 2 limit values (relays) and their hysteresis
y Drop-down or pull-in delay of the relays
y Enquiry of the minimum and maximum measured value
y Rounding up and down the last digit
y Average formation
y Serial port (RS 232)
All routines and parameters can be set by keys on the front. The switching status of the
relays is displayed by LEDs.
The setting is buffered. On interruption of the supply voltage the set parameters are retai-
ned.
A galvanically isolated supply voltage of 24 V DC (max. 30 mA) is available for supplying
transmitters.
Type summary
Type Input signal Display range Suitable for
(programmable) (programmable) sensor
APV 630 0–1 V DC Pressure and
0–0 V DC –999 to +999 temperature
0–20 mA DC transmitter
APT 650 Pt 00 / Pt 000 –150 hC . . . +199.9 hC Temperature
–200 hC . . . +800 hC sensors
Pt 00 / Pt 000Cutting
90 x 44 mm
7
MODUFLEX
Typeseries
FTS
Two-phase frost protectionwith limiter contact and integrated priority selection
FTS
Technical data
Supply voltage
24 V AC ± 20 % or
24–36 V DC
Output signal
0–10 V ± 1 mA (with falling temperature)
+ floating limiter contact
Power consumption
max. 1 W
Cable entry
2 x Pg 11 for output signal 0–10 V
Plug connection to DIN 43650
for limit value switch
Protective category
IP 65
Installation
With 2 size 4 mm screws directly on the
duct wall.
5 capillary tube holders, Type H 3, are
included in the supply.
Ambient temperature
12–50 hCCaution: at ambient temperatures below
10 hC, the unit reacts and signals
“Risk of frost”.
Tendering text
Two-phase frost protection with limiter
contact and integrated maximum selection
for surface monitoring of the air heater, with
self-monitoring sensor
Input signal: 0–10 V
Output signal: 0–10 V ± 1 mA
+ single-pole changeover switch.
Capillary tube length 3/6 m.
Wiring diagram (plug connector)
Switching capacity
8 A, 250 V AC
The frost protection generates with
falling temperature a constant out-
put signal of 0–10 V. If the tempera-
ture drops further, a limiter contact
(single-pole changeover contact)
is actuated.
If the output signal of the controller
(Y signal) is looped through the
frost protection, a maximum selec-
tion of the two signals takes place. If
the Y signal from the controller is
larger than the output signal of the
frost protection, the controller
determines the position of the hea-
ting valve (normal operation). If the
output signal of the frost protection
is larger than theYsignal of the con-
troller (risk of frost), then the frost
protection determines the position
of the heating valve as long a “Risk
of frost” is signaled by the sensor.
Once the risk of frost is removed,
the controller automatically takes
over control of the heating valve
again.
External priority selection is thus
not required. The sensor acting
over the entire length is self-moni-
toring, i. e. in the case of breakage
of damage of the capillary tube,
“Risk of frost” is signaled.
If the signal of the controller is not
looped through, then the FTS out-
puts the frost control signal.
Range of action Capillary tube Type
10 . . . 3 hC 6 m FTS 015
10 . . . 3 hC 3 m FTSB 015
Characteristic Block circuit diagram
Please refer to page 16 for frost protection
thermostats.
Connection diagram
Limiter Comparator
8
Mechanical thermostats
Fields of Application FEMA thermostats are suitable for regulating and monitoring temperatures in industrial pre-
mises, vessels, boiler plant, pipelines, air heating and conditioning systems. Many other
applications over and above these are conceivable owing to the variety of designs and the
extensive range of accessories.
Types TRM Room thermostats
TAM Capillary tube thermostats
TX Rod thermostats
FT Frost-protection thermostats
Sensor systems
Room- Capillary Rod Air duct Frost-
sensor tube sensor sensor sensor protection
TRM TAM TX + R 10 sensor
Operation of theTemperature Sensors(effect on switchingdifference)
The temperature sensors may be regarded as temperature-dependent pressure sensors.
As the temperature rises the pressure in the sensor system also increases. The change in
pressure is transmitted to the microswitch by a bellows system or a diaphragm. A
compression spring, the initial tension of which can be varied by means of the set-
point spindle, acts as the reacting force. The switching temperatures are adjustable in
this way. A distinction can be made between adsorption and tension systems according
to the mode of operation of the sensors.
In the case of adsorption systems (range up to 50 hC) largely linear scales are produced
and the switching difference is almost constant over the whole range of adjustment.
Tension systems (range 40–90 and 80–130 hC) are based on the interdependence of
temperature and pressure of a medium (vapour pressure diagram). The vapour pressure
curves are non-linear in shape, the result of which is a non-linear temperature scale.
The switching difference is variable and is determined by the switching temperature set in
each case.
The graph in the margin shows the typical dependence of the switching difference on the
range of adjustment in tension systems. The switching differences are as a rule larger in
the lower range of adjustment and smaller in the upper range of adjustment than the
specified values.
The mid-range switching difference is specified in the data sheets in each case.
A complete thermostat consists of a sensor system and switching unit. Sensors and swit-
ching units of different types can be combined with each other owing to the modular
system of construction which is adhered to throughout.
Sw
itchin
gdiffe
rence
Switching temperature
(Desired value)
9
The most important technical datafor thermostats
Normal version -version
. . . 200 . . . 700
Switch housing Aluminium diecast GD Al Si 12 Aluminium diecast GD Al Si 12
Switching function and
connection drawing
(applies only for version
with microswitch)
Floating change-over contact. Floating change-over contact.
With rising pressure switching over With rising pressure switching over
single-pole from 3–1 to 3–2 single-pole from 3–1 to 3–2
Switching capacity
(applies only for version
with microswitch)
8 A at 250 VAC 3 A at 250 VAC
5 A at 250 VAC inductive 2 A at 250 VAC inductive
8 A at 24 V DC 3 A at 24 V DC
0.3 A at 250 V DC 0.03 A at 250 V DC
Installaton position arbitrary, preferably vertical vertical
Degree of protection
(in vertical position)
IP 54 (on request IP 65 by ZF 351) IP 65
Ex degree of protection – EEx de IIC T6 tested
to EN 50014/50018/500/19 (CENELEC)
PTB approval – Ex-90.C. 1059
Electrical connection Plug connection to DIN 43650 Terminal connection
Cable entry Pg 11 Pg 11
Ambient temperature –15 to +70 hC –15 to +60 hC
Switching point Adjustable on the spindle. Adjustable on the spindle after the
terminal box lid is removed.
Switching difference Adjustable or not adjustable Not adjustable
(see type overview)
Medium temperature Max. 70 hC, briefly 85 hC Max. 60 hC
Vibration strength Up to 4 g no noteworthy deviations. The switching difference is reduced slightly at higher
accelerations. Use able 25 g not permissible.
Insulations values Overvoltage category III, contamination class 3, reference surge voltage 4000 V. The
conformity to DIN VDE 01 10 (01.89) is confirmed.
0
ThermostateSwitch units / connection diagrams
Plug connection
series 200
Description Connection diagrams
Normal version
microswitch, single pole changeover
ZFT 206 Minimum limiter
(for frost protection thermostates)
With manual lock for reconnection.
Interlocking with increasing temperature
ZFT 213 Gilded contacts with little transition
resistance (e. g. for low tension)
Cannot be supplied with adjustable
switching differential
ST 218 Plug connector with position indication
12 V – 240 V AC/DC
ZFT 351 Protection type IP 65 and switch housing with
surface protection
(terminal connection housing)
ZFT 513 EExi-version
Housing 300, cable entry and terminals
blue. Gold plated contacts,
Protection type IP 65
(terminal connection housing)
ZFT 5971 Setting and sealing according to specification
Example for ordering:
TX 150–513
Code for additional function (Minimum limiter)
Code of temperature range
Type
Temperature monitoring inexplosion-endangered areas
Temperature switches with special equipment can also be used in the
Ex area ≥ Zone 1.
The following alternatives are possible:
1. Thermostat with pressure-proof encapsulated switchingdevice, degree of protection EEx de IIC T6The thermostat in pressure-proof encapsulation can be used directly in the Ex area
≥ Zone 1). Maximum switching voltage, switching capacity and ambient temperature
must be taken into account and the rules for the installation in the Ex area must be obser-
ved.
All thermostats can be equipped with Ex switching mechanisms. Nevertheless, special
circuits as well as versions with adjustable switching differences are not possible.
2. Thermostats in EExi versionAll thermostats in normal version can be used in the Ex area ≥ Zone 1 if they are incorpo-
rated in an “intrinsically safe circuit”. In principle the intrinsic safety is based on that fact
that the control circuit run in the Ex area carries onlya small amount of energywhich is not
able to generate ignitable sparks.
Isolating switching amplifiers, e. g. Type EX 01 must be tested by the PTB and approved
for Ex-installations.
Isolating switching amplifiers must in any event be installed outside the Ex zone.
Thermostats which are intended for EEx-ia installations can be equipped with blue termi-
nals and cable entries.Because of the low voltages and currents which are carried by the
contacts of the microswitch, gold plated contacts are recommended (additional function
ZF 513).
1
ThermostatsGeneral technical information
Adjustment of the thermostats Adjustment to the lower switching point
The desired value xs corresponds to the lower switching point (on falling temperature), the
upper switching point xo (on rising temperature) is higher by the switching difference xd.
Setting the switchingtemperature(Desired value setting)
The grub screw located above the scale is to be slackened off approx. 2 turns before making
an adjustment and tightened up again after setting.
The switching temperature is set by the spindle. The set switching temperature can be read
off on the scale.
Slight variations between the set value and the switching point are inevitable due to toleran-
ces and spreads in the characteristics of the sensors and springs, also to friction in the
moving parts of the switch.The thermostats are as a rule set in such a way the desired value
setting and the actual switching temperature coincide best in the middle range. Any possi-
ble divergences are uniformly distributed to either side.
Turning to right: Low switching temperature
Turning to left: High switching temperature
Changing theswitching difference(only on switching units TRMV . . .)
The switching difference is changed by turning the threaded rod inside the setting spindle.
The lower switching point is not changed by adjusting the difference, only the upper
switching point is shifted by the amount of the difference. One revolution of the difference
screw varies the switching difference by approximately [ of the total differential range.
Bear in mind when making the adjustment:
Switching temperature:
Turning to the right – lower switching point. Turning to the left – higher switching point.
Switching difference:
Turning to the right – larger difference. Turning to the left – smaller difference.
Electrical connection Plug connection according DIN 43 650. Cable entry Pg 11. Max. cable diameter: 10 mm.
Cable outlet possible in 4 directions – spaced 90h apart.
Connection diagrams see page 0.
Switching
temperature
Switching
difference
2
ThermostatsGeneral technical information
Temperature limiter
with manual reconnection block
(Frost protection thermostats)
The frost protection thermostats can be made with mechanical latching.When the value set
on the scale is reached, the microswitch changes over and stays in this position. The blok-
king device can be released again by pressing the unlatching button (identified by a red dot
on the scale side of the switching unit).According to the type, the latch mayoperate when the
value rises orwhen the value falls.Unlatching can take place onlywhen the temperature has
been lowered or, in the case of latching at the lower switching point, raised again by a certain
amount.
Caution: Press unlatching button before putting into operation.
Connection diagrams see ZFT 206 (page 0).
Sealing the setting spindle The setting spindles for desired value and switching difference can be covered and sealed
with the sealing parts which are available accessories (type designation P2) consisting of a
sealing plate and cross-head screw.
The sealing parts can also be fitted later.The varnished adjusting screws are also covered by
them.
Repetitive accuracy Extensive testing on our premises and endurance tests by authorised testing bodies have
shown that the repetitive accuracy of the FEMA thermostats lies within the limits of ± 5 % of
the smalles switching differential specified in the lists over a working period of approx.
100.000 switching cycles, provided, of course, that the units are not stressed beyond the
maximum permissible temperatures at any time. The repetitive accuracy is independent of
the desired value set at any one time.
Mounting position Preference is to be given, if possible, to the vertical mounting position.
Type of protection IP 54 is guaranteed in accordance with the conditions of
DIN 40 050 for vertical mounting. The type of protection may be changed by a different
mounting position.
Installation of thethermostat in the open
The FEMA thermostats can also be installed in the open, if they are mounted in a vertical
position.
On temperatures below 0 hC please take care that there can form no condensation at the
sensor and inside the switching unit.
3
Typeseries
TR
Room Thermostatsfor industrial premises
Technical data
(not for Ex-versions)
Casing
Die-cast metal GD AI Si 12 to DIN 1725.
Resistant to ammonian steam and
seawater.
Mounting Position
Optional.
Max. Ambient temperature
70 hC60 hC on Ex-versions.
Max. Temperature at the sensor
70 hC
Contact complement
Single-pole changeover.
Switching capacity
8 (5) A 250 V AC.
Type of protection
IP 54 to DIN 40 050
(in the case of vertical mounting).
Installation
With H 1 support bracket or with
2 screws (l 4) bulk-head
mounting.
Adjustment
Scale value corresponds with the lower
switching point (with falling temperature),
the upper switching point is higher by the
switching differential.
Plug connection
By means of obliquely angled plug to DIN
43 650 (3-pole +earth contact), cable entry
Pg 11, max. cable diameter 10 mm. Cable
outlet possible in 4 directions – spaced
90h apart.
Switching temperature
Adjustable from outside with screw-driver.
Switching difference
Not adjustable on TRM, adjustable on
TRMV.
For values see summary of types.
Dimensions
FEMA room thermostats are suitable for industrial plant, for greenhouses, cowsheds and
warehouses, also for monitoring the maximum temperature in switchgear cabinets and relay
stations.
Room thermostats are supplied complete with H 1 wall bracket.
Type Range of Switching differenceadjustment (mean value)
Switching difference not adjustable
TRM 022 –20 bis +20 hC 1.0 K
TRM 40 0 bis +40 hC 1.0 K
TRM 150 +10 bis +50 hC 1.0 K
Switching difference adjustable
TRMV 40 0 bis +40 hC 3–10 K
TRMV 150 +10 bis +50 hC 3–10 K
Ex-proof · Design EEx de IIC T6(technical data see page 10)
Type Range of adjustment Switching difference Max. permissible(mean value) temperature on sensor
Switching difference not adjustable
Ex-TRM 022 –20/+20 hC 1.0 K 70 hCEx-TRM 40 0/+40 hC 1.0 K 70 hCEx-TRM 150 +10/+50 hC 1.0 K 70 hC
Tendering Text
Room thermostat for industrial premises, Type TRM,
range of adjustment . . . to . . . hC.
Switching difference not adjustable/adjustable.
Die-cast metal with plug connection to DIN 43 650.
4
Typeseries
TX
Rod ThermostatsDepth of immersion: 135 and 220 mm
Technical data(not for Ex-versions)
Casing
Die-cast metal GD Al Si 12 to
DIN 1725.
Mounting position
Optional.
Max. ambient temperature at the
switching unit
70 hC.
60 hC on Ex-versions.
Max. permissible temperature at the
sensor
See summary of types.
Contact Complement
Single-pole changeover.
Switching capacity
8 (5) A 250 V AC.
Type of protection
IP 54 to DIN 40 050
(in the case of vertical mounting).
Adjustment
Scale value corresponds with the lower
switching point (with falling temperature),
the upper switching point is higher by the
switching differential.
Plug connection
By means of obliquely angled plug to DIN
43 650 (3-pole +earth contact), cable entry
Pg 11, max. cable diameter 10 mm, cable
outlet possible in 4 directions – spaced
90h apart.
Plug is included.
Switching temperature
Adjustable from outside with screw-driver.
Switching difference
Not adjustable, for values see summary of
types.
Accessories
Immersion tubes
see page 17.
Dimensions
Rod thermostats can be installed as immersion thermostats in pipelines and containers and
for monitoring temperature in air ducts. The suitable immersion tube has to be chosen
according to the application.
Type Range of Switching difference Max. permissibleadjustment (mean value) temperature
at sensor
Depth of immersion 135 mm
TX 023 –20 bis + 30 hC 1.5 K 110 hCTX 150 +10 bis + 50 hC 1.5 K 110 hCTX 490 +40 bis + 90 hC 2.5 K 125 hCTX 813 +80 bis +130 hC 4.0 K 150 hC
Depht of immersion 220 mm
TXB 023 –20 bis + 30 hC 1.5 K 110 hCTXB 150 +10 bis + 50 hC 1.5 K 110 hCTXB 490 +40 bis + 90 hC 2.5 K 125 hCTXB 813 +80 bis +130 hC 4.0 K 150 hC
Ex-Proof · Design EEx de IIC T6(technical data see page 10)
Type Range of Switching difference Max. permissibleadjustment (mean value) temperature
at sensor
Immersion depth 135 mm
Ex-TX 023 –20 bis + 30 hC 1.5 K 110 hCEx-TX 150 +10 bis + 50 hC 1.5 K 110 hCEx-TX 490 +40 bis + 90 hC 2.5 K 125 hC
Immersion depth 220 mm
Ex-TXB 023 –20 bis + 30 hC 1.5 K 110 hCEx-TXB 150 +10 bis + 50 hC 1.5 K 110 hCEx-TXB 490 +40 bis + 90 hC 2.5 K 125 hC
Tendering Text
Rod thermostat, Type TX . . . , range of adjustment . . . to . . . hC dept of immersion 135 mm /
220 mm, die-cast metal with plug connection to DIN 43 650.
Accessories
Immersion tube, type . . .
5
Typeseries
TA
Capillary tube thermostatswith 1.5 m capillary tube
Technical data(not for Ex-versions)
Casing
Die-cast metal GD Al Si 12 to DIN 1725.
Mounting position
Optional.
Max. ambient temperature at the
switching unit
70 hC.
60 hC on Ex-versions.
Capillary tube
Cu capillary tube, 1.5 m long.
Sensor cartridge
8 mm l, 100 mm long, material: Cu.
Contact complement
Single-pole changeover.
Switching capacity
8 (5) A 250 V AC.
Type of protection
IP 54 to DIN 40 050
(in the case of vertical mounting).
Installation
Temperature sensor with or without immer-
sion tube in vessels, air ducts, etc.
Switching unit with 2 srews (l 4) bulkhead
mounting.
Adjustment
Scale value corresponds with the lower
switching point (with falling temperature),
the upper switching point is higher by the
switching differential.
Plug connection
3-pole + earth conductor, accessible after
removing terminal box cover.
Cable entry Pg 11, max. cable diameter
10 mm.
Switching temperature
Adjustable by means of screwdriver on set-
ting spindle (accessible after removing ter-
minal box cover).
Switching difference
Not adjustable.
Immersion tubes see page 17
Dimensions
The sensor cartridge at the end of the capillary tube is the actual active (temperature-sensi-
tive) part of the sensor. Changes in temperature on the capillary tube have no effect on the
switching point.
Pressuretight installation of the sensor in pressure vessels of all kinds is possible with the aid
of immersion tubes.
Type Range of Switching difference Max. permissibleadjustment (mean value) temperature
at sensor
TAM 022 –20 bis + 20 hC 1.5 K 110 hCTAM 150 +10 bis + 50 hC 1.5 K 110 hCTAM 490 +40 bis + 90 hC 2.0 K 125 hCTAM 813 +80 bis +130 hC 2.0 K 150 hC
Ex-proof · Design EEx de IIC T6(technical data see page 10)
Type Range of Switching difference Max. permissibleadjustment (mean value) temperature
at sensor
Ex-TAM 022 –20 bis + 20 hC 1.5 K 110 hCEx-TAM 150 +10 bis + 50 hC 1.5 K 110 hCEx-TAM 490 +40 bis + 90 hC 2.0 K 125 hCEx-TAM 813 +80 bis +130 hC 2.0 K 150 hC
Tendering Text
Capillary tube thermostat, Type TAM . . .
Range of adjustment . . . to hCLength of capillary tube 1.5 m, die-cast metal with plug connection to DIN 43 650.
Accessories
Immersion tube type . . .
See also page 18 for further accessories (Wall bracket H 2, Capillary tube bushing R 4
and R 5).
6
Typeseries
FT
Frost protection thermostatsfor air heating and conditioning systems
Technical data(not for Ex-versions)
Casing
Die-cast metal GD Al Si 12 to
DIN 1725.
Sensor
Cu capillary tube
Max. ambient temperature
at the switching unit
70 hC.
60 hC on Ex-versions.
Contact complement
Single-pole changeover.
Switching capacity
8 (5) A 250 V AC.
Type of protection
IP 54 to DIN 40 050
(in the case of vertical mounting).
Switching difference
Permanently set in the factory to approx.4 K.
Adjustment
Scale value corresponds with the lower
switching point (with falling temperature),
the upper switching point is higher by the
switching differential.
Plug connection
Obliquely angled plug, 3-pole with earth
contact to DIN 43 650
Cable entry Pg 11.
Max. cable diameter 10 mm.
Cable outlet possible in 4 directions-
spaced 90h apart.
Plug is included.
Dimensions
Accessories
5 capillary tube holders (included in
delivery).
See also page 18 (capillary tube bushings
R 4 and R 5).
FEMA frost protection thermostats reliably monitor the temperature in hot water-heated air
heaters. If the temperature falls below the set value, the thermostat switches off. A visual or
audible “frost hazar” alarm can be switched on at the same time. A fixed stop on the setting
spindle at 3 hC prevents the thermostat from being set below the freezing point due to inex-
pert adjustment.
If the capillary tube is damaged or broken, the FEMA frost protection thermostats reliably
switch off towards the safe side (e. g. fan off) irrespective of the temperature at the sensor.
Mode of operationThe FT types with 3 m or 6 m capillary tube detect the temperature over the whole length of
the capillary tube and are therefore used to monitor the surface of the whole air heater. If the
capillary tube is undercooled at any point, the thermostat switches off.
The frost protection thermostats with reclose prevention (switching units 206) break
the circuit at the set value as the temperature falls. The switching state adopted is mechani-
cally latched against automatically switching on again. The latch can only be released again
by actuating the unlatching button after the temperature has risen again by approx. 8 hC.
Note:In the case of the FT types care is to be taken to ensure that the ambient temperature at the
switching unit does not fall below the set switching point. Also, parts of the capillary tube out-
side the air heater are not to be laid in areas the temperature of which can fall below the set
switching point. Both can lead to premature switch-off.
Standard Type Type with reclose Range of Max. Versionprevention adjustment temperature
at sensor
FT 015 FT 015-206 4–15 hC 200 hC 6 m capillary tube
FTB 015 FTB 015-206 4–15 hC 200 hC 3 m capillary tube
Ex-Proof · Design EEx de IIC T6(technical data see page 10)
Type Range of Max. Versionadjustment temperature
at sensor
Ex-FT 015 4–15 hC 130 hC 6 m capillary tube
Ex-FTB 015 4–15 hC 130 hC 3 m capillary tube
Two-phase frost protection control with output signal 0–10 V and limit
switch. See separate data sheet, FTS, page 7.
Tendering Text
Frost protection thermostat, Type . . . with 3 m/6 m capillary tube. Range of adjustment
3–15 hC with/without internal reclose prevention, die-cast metal housing with plug-connec-
tion to DIN 43 650.
7
AccessoriesImmersion tubesfor thermostats and temperature transmitter
Type Depth of immersion Overall length Suitable for
L (mm) L2 (mm)
Nickel-plated brass type, G 1/2, max. permissible pressure: 25 bar
R 1 / Ms 135 151
R 2 / Ms 220 236 TAM . . .
R 3 / Ms 500 516
R 10 / Ms 135 151TX . . . /TP
R 20 / Ms 220 236
Stainless steel type (1.4571 + 1.4401) G 1/2, max. permissible pressure: 63 bar
R 1 / Nst 135 151
R 2 / Nst 220 236 TAM . . .
R 10 / Nst 135 151TX . . . /TP
R 20 / Nst 220 236
Nickel-plated brass type, 1/2 NPT, max. permissible pressure: 25 bar
RN 1 / Ms 135 151
RN 2 / Ms 220 236 TAM . . .
RN 10 / Ms 135 151TX . . . /TP
RN 20 / Ms 220 236
Stainless steel type (1.4571 + 1.4401) 1/2 NPT, max. permissible pressure: 63 bar
RN 1 / Nst 135 151
RN 2 / Nst 220 236 TAM . . .
RN 10 / Nst 135 151TX . . . /TP
RN 20 / Nst 220 236
Immersion tubes with fixing flange for air ductsmaterial: steel, chromated
R 6 Depth of immersion 135 mmTX . . .
R 7 Depth of immersion 220 mm
Fastening flange for Pt 100-/Pt 1000 sensor, l = 5 mm
Type R 8 TP, PF, PS
Use of the immersion tubes
for pressure prooffor air ducts
for
installation (up to 100 bar) exhaust
pipesR 1 R 2 R 10 R 20
RN 1 RN 2 R 3 RN 10 RN 20 R 6 R 7 R 8 R 15 R 18
TAM . . . x x x
TX . . . x x
TXB . . . x x
Temperature xTransmitter
TP . . . x xSensors
PF . . ., PS . . .
only
together
with re-
taining
spring
FF 135
Transmitter
PZ 17
Sensors
P 17 x
Immersion tubes G 1/2, internal l 8 mm
Immersion tubes 1/2 NPT,
internal l 8 mm
R 6 R 7
R 8 R 8 (example for mounting)
8
AccessoriesAccessoriesfor thermostats
Wall bracket Type H 1
including fixing screws and plugs (6 mm l).
included as standard with Type TRM thermostats. Suitable for all switching units.
Wall bracket Type H 2
for fixing the sensor cartridges of capillary tube thermostats. Suitable for all Type TAM
capillary tube thermostats.
Capillary tube holder Type H 3
to attach the capillary tube of frost protection thermostats to the frame of the air heater
(5 off packed in bag).
Suitable for FT frost protection thermostats and frost protection FTS.
Sealing, type P 2
consisting of cover plate and screw for covering and sealing the adjustment screws.
Heat conducting compound Type WLP 1
to improve the transfer of heat, e. g. in the case of contact thermostats.
Approx. 0.5 cm3 in handy dispenser.
Capillary tube bushing, type R 4
with 3 mm capillary tube screw in thread G 1/2HH suitable for all types TAM, FT and FTS.
Capillary tube bushing, type R 5
Rubber plug for 3 mm capillary tube, bore diameter 0 mm.Not pressure-tight (5 pcs. packed
in bag). Suitable for all TAM, FT and FTS.
Plug ST 5 to DIN 43050
for switching units of series 200, with seal and fastening screw, 3-pole + earth contact.
Plug ST 3 to DIN 43050
(replacement for large plug of frost protection thermostats).
Plug connectors with position indication ST 218
Operating voltage: 12–240 V AC/DC
Operating current: max. 2 A
LED current drain: max. 10 mA
LED indication: green if voltage present at contact
pin 1
red if voltage present at contact
pin 2
Connection rotatable 270h engaging at increments of 45hType of protection: IP 65
Ambient temperature: 0–60 hCSuitable for pressure and temperature switches with plug connection
(series 200) with are equipped with a mikro switch (standard version).
19
Technical dataHousingAluminium diecastingwith plastic cover
Immersion tube(included in supply): brassScrew-in thread: G ½Immersion depth: see type overview
Stainless steel immersion tubeoptional, see table below
Max. ambient temperature80 °C at the switching head
Switching point accuracy(in upper third of scale)for TW, STW, STB: � 5 %for TR: � 1.5 %(in % of scale range)
Switching difference(in % of scale range)for TR, TW: 3–4 %for STW, STB: 4–6 %
Lead sealThe cover of the switch can be leadsealed so that the internal settings ofthe limiter switching points are no longeraccessible after sealing.
Switching capacity10 (2) A, 250 V AC
Type of protectionIP 54
The temperature monitors and temperature limiters correspond to the requirements ofDIN 3440 and can thus be used for heating systems according to DIN 4751, for steamand hot water systems and for district heating systems. The devices with safetyfunction (STW, STB) are self-monitoring, i.e. in the case of breakage or leaks in themeasuring system the circuit is opened and the system is switched off to the safe side.
TW, STW, TR STB
Type STW 1F STW + TRF STB + TWF STB + TRF STB 1F TWP 1F
Function Safetytemperature
monitor
Safetytemperaturemonitor and
controller
Safetytemperaturelimiter and
monitor
Safetytemperaturelimiter andcontroller
Safetytemperature
limiter
Temperaturemonitor
Setting range 20–150 °C 20–150 °C 30–110 °C 30–110 °C 60–130 °C 20–150 °C
TÜV-test certificate STW (STB)89496S
TR / STW (STB)89996S
TW / STB90496
TR / STB90096
STB89596
TW89296
Setting internal STW internalTR external
STB internalTW external
STB internalTR external
internal internal
Controls accessiblefrom outside
none Setting wheelfor TR
Reclosingbutton
Reclosingbutton and
setting wheelfor TR
Reclosingbutton
none
Contact Changeover 2 x changeover NC (STB) andchangeover
(TW)
NC (STB) andchangeover
(TR)
NC Changeover
Reclosing lockout(internal)
no no yes yes yes no
Max. temperatureat the probe
175 °C 175 °C 130 °C 130 °C 150 °C 175 °C
Immersion depth 150 mm 150 mm 150 mm 150 mm 150 mm 100 mm
Stainless steelimmersion tube
T4 NST F T5 NST F T5 NST F T5 NST F T4 NST F T4 NST F
Typeseries
STBTemperature monitors, temperature limitersComponent tested according to DIN 3440
STB + TWF
STB 1F
Connection diagrams:In devices with doublefunction there are2 switching elements.Observe the function ofthe relevant switch onconnection.
Fema Controls · Honeywell AGP. O. box 1254 · 71099 Schönaich/GermanyPhone ++49(0)7031/637-828 · Fax ++49(0)7031/[email protected] · www.honeywell.de/femaTechnical data and pictures not obligatory
for delivery. Subject to change.
EN3B-0259GE51 R0700 Printed in Germany
H
f
Monitoring and control of pressure, temperature and flow
14103_TTS62/4_GB_2000_Temp 06.11.2000 9:08 Uhr Seite 1