2
TELECOM DATACOM MASS TRANSIT POWER UTILITIES 2500 VA OIL & GAS Illustrations are non-binding and may include customized fittings. TSI BRAVO ST 2500 - 110/230 STANDALONE INVERTER SYSTEM POWER 2500 VA INPUT 110 Vdc and 230 Vac OUTPUT 230 Vac DESCRIPTION The TSI Bravo ST solution secures AC loads at 230 Vac from a 110 Vdc infrastructure. Additional AC input is used under normal conditions to achieve an overall conversion efficiency of 96%. In the event of a grid failure, it automatically switches to the DC to secure the loads. In addition to this, this solution includes a bypass that feeds AC loads directly from the grid if there is a problem in the system. The modules included are hot swappable for ease of maintenance and extensibility (from 2.5 to 5kVA). APPLICATIONS All business critical applications and all types of AC loads. The solution is design for highest AC output availability. Both inverter modules and by-pass are hot-swappable which ensures low Mean Time to Repair (MTTR), reduction in service costs. MAIN FEATURES Extra AC input for increased efficiency Integrated bypass Compact solution (2U high) Modularity (from 2.5 to 5 kVA) www.cet-power.com AC Load = ~ DC Load Baery Backup GRID TSI BRAVO ST

TELECOM DATACOM MASS TRANSIT POWER UTILITIES OIL & GAS · TELECOM DATACOM MASS TRANSIT POWER UTILITIES 2500 VA OIL & GAS I TSI BRAVO ST 2500 - 110/230 STANDALONE INVERTER SYSTEM POWER

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TELECOM DATACOM MASS TRANSIT POWER UTILITIES OIL & GAS · TELECOM DATACOM MASS TRANSIT POWER UTILITIES 2500 VA OIL & GAS I TSI BRAVO ST 2500 - 110/230 STANDALONE INVERTER SYSTEM POWER

TELECOM DATACOM MASS TRANSIT POWER UTILITIES

2500VA

OIL & GAS

Illustrations are non-binding and may include customized fittings.

TSI BRAVO ST 2500 - 110/230

STANDALONE INVERTERSYSTEM

POWER 2500 VAINPUT 110 Vdc and 230 Vac

OUTPUT 230 Vac

DESCRIPTIONThe TSI Bravo ST solution secures AC loads at 230 Vac from a 110 Vdc infrastructure.

Additional AC input is used under normal conditions to achieve an overall conversion efficiency of 96%. In the event of a grid failure, it automatically switches to the DC to secure the loads.

In addition to this, this solution includes a bypass that feeds AC loads directly from the grid if there is a problem in the system.

The modules included are hot swappable for ease of maintenance and extensibility (from 2.5 to 5kVA).

APPLICATIONSAll business critical applications and all types of AC loads. The solution is design for highest AC output availability. Both inverter modules and by-pass are hot-swappable which ensures low Mean Time to Repair (MTTR), reduction in service costs.

MAIN FEATURES Extra AC input for increased efficiency Integrated bypass Compact solution (2U high) Modularity (from 2.5 to 5 kVA)

www.cet-power.com

AC Load

= ~ DC

Load

Battery Backup

GRID

TSI BRAVO ST

Page 2: TELECOM DATACOM MASS TRANSIT POWER UTILITIES OIL & GAS · TELECOM DATACOM MASS TRANSIT POWER UTILITIES 2500 VA OIL & GAS I TSI BRAVO ST 2500 - 110/230 STANDALONE INVERTER SYSTEM POWER

Illustrations are non-binding and may include customized fittings.

TSI BRAVO STTSI Bravo ST 2500 - 110 / 230

GENERAL

Part number S32P75E0102S

EMC (immunity) EN 61000-4-2 / EN 61000-4-3 / EN61000-4-4 / EN 61000-4-5 / EN 61000-4-6 / EN 61000-4-8

EMC (emission) (class) EN 55022 (B)

Safety IEC 60950 / EN62040-1 / EN62040-2

Cooling / Isolation Forced / Doubled

MTBF 240 000 hrs (MIL-217-F)

Efficiency (Typical): Enhanced power conversion / on line 96% / 91%

Dielectric strength DC/AC 4300 Vdc

RoHS 6 Compliant

Vibration GR63 office vibration 0 to 100 hz-0.1 g / transport vibration 5-100 Hz 0.5 g 100 to 500 hz-1.5 g / Drop test

Operating conditionsDesigned for installation in an IP20 or IP21 environment.

When installed in a dusty or corrosive environment, appropriate measures (air filtering, …) must be taken.Altitude above sea without de-rating < 1500 m / derating > 1500 m – 0.8 % per 100 m

Ambient / storage temperature / relative humidity -20 to 50 ° C / -40 to 70 ° C / 95 %, non-condensing

Material (casing) Coated steel-ALU ZINC

AC OUTPUT POWER

Nominal Output power (VA) 2500

Nominal Output power (W) 2000

Short time overload capacity 150 % (15 seconds) 110 % permanent within T° range

Admissible load power factor Full power rating from 0 inductive to 0 capacitive

Internal temperature management and switch off Above 50°C ambiant T° derating up to 65°C. Automatic restart with hyteresis +/- 5°C

DC INPUT SPECIFICATIONS

Nominal voltage (DC) 110 V

Voltage range (DC) 90 - 160 V

Nominal current at nominal DC voltage and max power W 20.2 A (at 110 Vdc and 2000 W output), 41 A (at 110 Vdc and 4000 W output)

Maximum input current (for 15 second) / voltage ripple 29 A / < 200 mV rms

Input voltage boundaries User selectable with T2S interface min and max value

AC INPUT SPECIFICATIONS

Nominal voltage (AC) 220 Vac / 230 Vac / 240 Vac

Voltage range (AC) 150-265 V

Brownout 150 to 185 V linear derating 150 VA/120 W per 10 Vac for 2500 VA model and 300 VA/240 W for 5000 VA model

AC input range min and max value Adjustable between 150 Vac and 265 Vac (fixed hysteresis 10 Vac)

AC input power factor (EPC operation mode) > 99%

Frequency range (selectable) / synchronization range 50 – 60 Hz / range 47 – 53 Hz / 57 – 63 Hz

AC OUTPUT SPECIFICATIONS

Nominal voltage (AC) 230 V / 220V / 240 Vac adjustable (default 230 Vac - 50 Hz)

Frequency / frequency accuracy 50 - 60 Hz / 0.03 %

Total harmonic distortion (resistive load) < 1.5 %

Load impact recovery time 0.4 ms

Turn on delay 20 s to 40 s depending on the number of module installed

Nominal current. Protected against reverse current 10.9 A

Crest factor at nominal power3 : 1

With short circuit management and protection

Short circuit clear up capacity10 x In for 20 msec - Available while Mains is available at AC input port

With magnitude control and managementShort circuit current after clear up capacity 2.1 In during 15 s and 1.5 In after 15 s

IN TRANSFER PERFORMANCE

Max. voltage interruption AC to DC module - Module to bypass 0 ms between DC to AC and AC to DC / <10 ms between BRAVO mode and automatic bypass

SIGNALING & SUPERVISION

Display Synoptic LED

Alarms output / supervision Dry contacts on shelf / Standard USB port and MODBUS on T2S, optional : Candis Display / Candis TCP-IP

Remote on / off on rear terminal of the shelf via T2S

www.cet-power.com

carm

elde

sign

.be

04/2

014

TSI BRAVO ST 2500 - 110/230 - Datasheet v1.0 Specifications can change without notice. New data will be updated on our Web site: www.cet-power.com. The present equipment is protected by several international patents, trademarks and copyrights.

485 mm / 19"

515 mm / 20.28"

5.8 kg / 12.8 lbs2 U

435 mm / 17.13"

2 U

103 mm / 4.05"

4.3 kg / 9.5 lbs

421.3 mm / 16.65"

2 U

204.7 mm / 8.05"

2.4 kg / 5.3 lbs