Tele-Protection Signal List for 132 kV Line Protection: 132 kV Line Protection with Distance (21) Relay as Main & Directional Over Current/Earth Fault (67/67N) as Back-up Relay Type Signal Remarks Main (21) 21 Tx (Distance Sent) Generally Under-Reaching 21 Rx (Distance Received) Back-up (67N) 67N Tx (DSEF/DEF Sent) Generally Over-Reaching 67N Rx (DSEF/DEF Received) Breaker Fail DTT-1 (Direct Transfer Trip) Rx Separate Communication Channels should be Used for Each Signal Sent DTT-2 (Direct Transfer Trip) Rx DTT-1 (Direct Transfer Trip) Tx Separate Communication Channels should be Used for Each Signal Received DTT-2 (Direct Transfer Trip) Tx 132 kV Line Protection with Line Differential (87L) Relay as Main & Directional Over Current/Earth Fault (67/67N) as Back-up Main (87L) Inter-Tripping Signal should be Internally Sent/r by the Same Fibre-Optic Channel with Which both End 87L Relays are Communicating. Back-up (67N) 67N Tx (DSEF/DEF Sent) Generally Over-Reaching 67N Rx (DSEF/DEF Received) Breaker Fail DTT-1 (Direct Transfer Trip) Rx Separate Communication Channels should be Used for Each Signal Sent DTT-2 (Direct Transfer Trip) Rx DTT-1 (Direct Transfer Trip) Tx Separate Communication Channels should be Used for Each Signal Received DTT-2 (Direct Transfer Trip) Tx

Tele-Protection Signal List for 132 KV Line Protection

Embed Size (px)

DESCRIPTION

Power System ProtectionLine Protection

Citation preview

  • Tele-Protection Signal List for 132 kV Line Protection:132 kV Line Protection with Distance (21) Relay as Main & Directional Over

    Current/Earth Fault (67/67N) as Back-upRelay Type Signal Remarks

    Main (21) 21 Tx (Distance Sent) Generally Under-Reaching21 Rx (Distance Received)

    Back-up (67N)67N Tx (DSEF/DEF Sent)

    Generally Over-Reaching67N Rx (DSEF/DEFReceived)

    Breaker Fail

    DTT-1 (Direct TransferTrip) Rx Separate Communication Channels should be

    Used for Each Signal SentDTT-2 (Direct TransferTrip) Rx

    DTT-1 (Direct TransferTrip) Tx Separate Communication Channels should be

    Used for Each Signal ReceivedDTT-2 (Direct TransferTrip) Tx

    132 kV Line Protection with Line Differential (87L) Relay as Main & Directional OverCurrent/Earth Fault (67/67N) as Back-up

    Main (87L)Inter-Tripping Signal should be Internally Sent/r

    by the Same Fibre-Optic Channel with Whichboth End 87L Relays are Communicating.

    Back-up (67N)67N Tx (DSEF/DEF Sent)

    Generally Over-Reaching67N Rx (DSEF/DEFReceived)

    Breaker Fail

    DTT-1 (Direct TransferTrip) Rx Separate Communication Channels should be

    Used for Each Signal SentDTT-2 (Direct TransferTrip) Rx

    DTT-1 (Direct TransferTrip) Tx Separate Communication Channels should be

    Used for Each Signal ReceivedDTT-2 (Direct TransferTrip) Tx