TEKNOPOOLSwimming Pool
Air Handling Units
Teknopool ....................................................... 3
Components ................................................... 4
Automation ..................................................... 6
Project Designing ........................................... 9
Content Teknogen
As one of the leading manufacturers of Heating,
Ventilation and Air Conditioning market,
TEKNOGEN HVAC stands for innovation, top
quality, leading technology and reliable service.
That’s why our motto is ‘’SIMPLY THE BEST
SOLUTIONS’.
One of the core issues for production is quality
and high-end components for reaching top quality
units. All internal prosesses are being regulated
by ISO9001 quality management system.
We combine the demands from the market
with the new trends for energy savings and
environmental needs. This combination leads
us to create new designs with innovated ideas.
This approach makes us have loyal customers
worldwide.
TEKNOGEN has a large range for Air handling
Units, Fancoils, Heat Recovery Ventilators,
Swimming Pool Air Handling Units, Chillers,
Rooftop Units, Floor Convectors, Unit Heaters.
Our headquarters located in Istanbul and the
factory is in Izmir.
If you are looking for high quality production and
a solution partner, we Teknogen ready.
General Specifications
TEKNOPOOL units are designed by R&D Department in 8 models for pools with water surface between 50m2-500m2. They used for dehumidification process of the pools. They come with automation panel. Thereby, the cost for installation and operation will be minimized thanks to plug and play design. It consist of three sections, Fan, Heat Recovery and Dehumidification.
Fan Section
The return air goes into dehumidification process and comes to Fan section. Fan section blows dehudified air back to pool area. There are three different types of application in this secton; Belt driven, Plug fan and EC Plug fan.
Heat Recovery Section
Two types of heat recovery systems are available with TEKNOPOOL units; Heat Pipe and Plate Type.It is possible to consume less energy while reaching higher dehumidification values by using heat recovery systems in swimming pool air handling units.
Dehumidification section
TEKNOPOOL units have two types of dehumudification systems; In heat recovery systems and with mechanical cooling. R407C refrigerant is used in mechanical cooling systems. The components of the systems are; compressor,condenser, evaporator,expansion valve,dryer,selenoid valve,suction accumulator, liquid tank . High performance scroll compressors are preferred in this system.
Technical specifications
Teknopool
ModelDehumidification Capacity
(with %20 Fresh Air,Total)
AirFlow
Evaporator Capacity(7.2 °C evaporation,
54.4 °C condensation, R407C)
Condensing Capacity(7.2 °C evoporation,
54.4 °C Condensation, R407C)
HeatingCoil
kg/h m3/h kW kW kW
TE
KN
OP
OO
L
5 23,43 3000 24,9 30,6 17
7.5 31,24 4000 33,5 43,4 19,8
10 46,87 6000 50,9 65,4 28,1
15 58,59 7500 60,6 82,5 34,3
20 70,3 9000 75,6 99 45,7
30 85,93 11000 87,7 115,8 58,7
40 113,27 14500 112,4 148,6 78,9
45 148,42 19000 172,8 222,6 77,9
50 187,48 24000 201 260,4 118,8
55 234,36 30000 242,4 330 137,2
3
Components
Body
The body of TEKNOPOOL units consist of eloxal coated corrosion resistant aluminium profiles . The panels are produced with special gasketing to prevent any contact between inner and outer sheet metals. The 50mm panels which has 70kg/m3 rockwool in density . The sheet metal which is 275gr/m2 galvanised coated and RAL9002 coated is used as standard component for all sheet metal applications.Thereby TEKNOPOOL units offer corrosion resistance.
Compressor
High performance Scroll compressors are used in TEKNOPOOL units. Cooling chamber and compressor are designed at the same cell . This design offers easy start up of the unit. R407C refrigerant is used in the system.Pressure sensors at the suction and forcing side saves compressor and the system.
Evaporator
Direct expansion exchangers are used in TEKNOPOOL units for dehumidification of return air. The surface of the evaporators are hydrophilic coated. The body is epoxy painted.
Drain System
Due to high condensation,TEKNOPOOL Units has a safe,easy and fast drain system to discharge water from the system. The drain pan designed by R&d department of TEKNOGEN is made up of stainless steel and it collects water to a single point and discharge water immediately. Syphon is a standard application in all TEKNOPOOL units and it easily removes drain to water network.
4
Components
Fan/Motor
Three types of fan applications are possible in TEKNOPOOL units; belt driven,Plug Fan,EC Plug Fan.
Condenser
The refrigerant gas is vaporised during cooling process of air and it condensates(turns to liqid) again in condenser.
Heat recovery
Two types of heat recovery systems are available with TEKNOPOOL units; Heat Pipe and Plate Type. Both systems work on same principle. Thye produce energy efficiency through bringing condenser and evaporator inlet air temperatures to optimum working conditions by using energy coming form dehumidifiated return air.
Filter
G4 Panel filters are standard in TEKNOPOOL units on fresh air and return air directions. M5, M6, F7, F8, F9 bag filters are optional.
5
Automation
TEKNOPOOLunits are produced with full automation control system. All scenarios are defined in automation system which lets the user have plug and play unit. Thereby , start procedure will be very easy after duct,drain and power connections. There are four different scenarios for dehumidification prcess in TEKNOPOOL units;
Winter(Night)-Dehumidification On
This scenario is active during non-common usage of the pool. The unit works with %100 fresh air. The cooling chamber works and dehumidification is on.
Winter(Night)-Dehumidification Off
This scenario is active if pool is not used. The unit works with %100 fresh air. The cooling chamber does not work and dehumidification is off.The heater is on.
Winter(Day)-Dehumidification On
This scenario is active during common usage of the pool. The unit works with %75 fresh air and %25 return air. The cooling chamber Works and dehumidification is on. The heater will start if it is needed. This is the scenario that the unit works with full capacity.
SummerThis scenario is active if outer and inner temperaturs are close to each other.The unit works with %100 fresh air. The cooling chamber does not work . The heater will start if it is needed.
Components Used for Automation
• Humidity and temperature sensors• Differential Pressure sensor• Frequncy converters(In Plug Fan Applications)• Damper Motor(Proportionally Controlled)• Low/High Pressure Controls for Compressor• MCC Board• DDC Board
Automation System
TEKNOPOOL units specially designed automation cards. This card can control ,blowing and suction fans, safety of cooling chamber, damper on the unit,constant flow of the fans. The control panel could be connected till 200m . away from the unit. Weekly programming, filter dirtiness alarm, operation and fault signals are available.
6
Automation
SCENARIOS WITH HEAT PIPE HEAT RECOVERY
WINTER(NIGHT)-DEHUMIDIFICATION ON
30,00
BUAT (ICERDE)
DAM
LA T
UTU
CU
EVAPO
RATÖ
R
KO
ND
EN
SER
Supply Air
HEAT P
IPE
Return Air
ISIT
ICI
Compressor ON
Heat Recovery ON
Suction Fan ON
Supply Fan ON
Fresh Air %0
After Heater If Needed
WINTER(NIGHT)-DEHUMIDIFICATION OFF
30,00
BUAT (ICERDE)
DAM
LA T
UTU
CU
EVAPO
RATÖ
R
KO
ND
EN
SER
Supply Air
HEAT P
IPE
Return Air
ISIT
ICI
Compressor OFF
Heat Recovery OFF
Suction Fan ON
Supply Fan ON
Fresh Air %0
After Heater ON
WINTER(DAY)-DEHUMIDIFICATION ON
BUAT (ICERDE)
DAM
LA T
UTU
CU
EVAPO
RATÖ
R
KO
ND
EN
SER
Supply Air
HEAT P
IPE
Return Air
Outside Air
Exhaust Air
ISIT
ICI
Compressor ON
Heat Recovery ON
Suction Fan ON
Supply Fan ON
Fresh Air (%)25
After Heater If Needed
SUMMER
ISIT
ICI
BUAT (ICERDE)
DAM
LA T
UTU
CU
EVAPO
RATÖ
R
KO
ND
EN
SER
Supply Air
HEAT P
IPE
Return Air
Outdoor Air
Exhaust Air
Compressor OFF
Heat Recovery ON
Suction Fan ON
Supply Fan ON
Fresh Air (%)100
After Heater If Needed
7
Automation
SCENARIOS WITH PLATE TYPE HEAT RECOVERY
WINTER(NIGHT)-DEHUMIDIFICATION ON
Supply Air
BUAT (ICERDE)
ISIT
ICI
Return Air
EVAPO
RATÖ
R
DAM
LA T
UTU
CU
KO
ND
EN
SER
Compressor OFF
Heat Recovery OFF
Suction Fan OFF
Supply Fan ON
Fresh Air %0
After Heater ON
WINTER(NIGHT)-DEHUMIDIFICATION ON
Supply Air
BUAT (ICERDE)
ISIT
ICI
ORTAMA
EVAPO
RATÖ
R
DAM
LA T
UTU
CU
KO
ND
EN
SER
Compressor OFF
Heat Recovery OFF
Suction Fan ON
Supply Fan ON
Fresh Air (%)0
After Heater ON
WINTER(DAY)-DEHUMIDIFICATION ON
Outside Air
Exhaust Air
Supply Air
BUAT (ICERDE)
ISIT
ICI
Return Air
EVAPO
RATÖ
R
DAM
LA T
UTU
CU
KO
ND
EN
SER
Compressor ON
Heat Recovery ON
Suction Fan ON
Supply Fan ON
Fresh Air (%)25
After Heater If Needed
SUMMER – DEHUMIDIFICATION OFF
Outside Air
Exhaust Air
Supply Air
BUAT (ICERDE)
ISIT
ICI
Return Air
KO
ND
EN
SER
EVAPO
RATÖ
R
DAM
LA T
UTU
CU
Compressor OFF
Heat Recovery ON
Suction Fan ON
Supply Fan ON
Fresh Air (%)100
After Heater If Needed
8
Project Designing
W = е х S х (P Max
- Р Set
) g/h;
S- Pool surface in m2
Pmax-Pressure of the air at pool water temperature in mbar
Pset-Pressure of the pool indoor air on humidity and temperature at design conditions
e- Pool usage coefficient;it can be obtained from below table
Pool usage coefficient Pool type g / (m2 х h х mbar)
0.5 P1 Indoor pools
5 P2 Non-used pools
15 P3 Pools with number of users low to medium
20 P4 Pools with number of users medium to high
28 P5 Recreation pools or waterparks
35 P6 Pools with artificial waves and water-slides
Calculation for a Residence Pool project design
Pool Surface: 100 (m2)By using Mollier diagram;
28C ,%100 RH , vapor pressure of the air 37,78mbar30C ,%60 RH , vapor pressure of the air 25,45mbar
Can be calculated.
The e number will be 15 since it is a residence pool.
The quantitiy of the evaporation from the pool surface,W
W = 15 x 100 x (37,78 - 25,45) = 18.495 g/h ≈ 18,5 l/h
Water Temperature: 28 (°C)
Indoor Temperature: 30 (°C)
Relative Humidity of Pool Area: 60 (% RH)
Pool type
P1 P2
XP3 P4 P5 P6
TEKNOPOOL units are designed according to VDI 2089 :Part1 and dehumdification values are calculated in compliance with pool surface. The dehumdifications are calculated with below formula;
9
WWW.TEKNOGENHVAC.COM
Notes
Notes
HEADQUARTERSBY ISITMA SOGUTMA KLIMA HAVALANDIRMA SAN TIC. A.S.ATATURK MAH. DUDULLU CAD. SEREF SOKAK. NO 46 34758 ATASEHIR - ISTANBUL / TURKEYTEL + 90 216 324 51 59 • FAX + 90 216 324 99 [email protected] • WWW.TEKNOGENHVAC.COM
FACTORYKAZIM KARABEKIR MAHALLESI BEKIR SAYDAM CAD.NO:104 IS KAPI NO: 25 PANCAR, AYRANCILAR, TORBALI - IZMIR / TURKEYTEL + 90 232 864 11 11 • FAX + 90 232 864 10 11
AP
RIL
20
16
BY
HV
AC
SY
ST
EM
S I
NC
.R
ES
ER
VE
S T
HE
RIG
HT
TO
MA
KE
ALT
ER
AT
ION
SD
UE
TO
TE
CH
NIC
AL
DE
VE
LO
PM
EN
TS
WIT
HO
UT
PR
IOR
NO
TIC
E.