421 04 5001 00 April 2008 TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product. DANGER - Immediate hazards which will result in severe personal injury or death. WARNING - Hazards or unsafe practices which could result in severe personal injury or death. CAUTION - Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or opera‐ tion. Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: The signal word CAUTION is used throughout this manual in the following manner: Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures on product labels. WARNING Safety Labeling and Signal Words ! ! CAUTION WARNING TABLE OF CONTENTS Wiring Diagrams 2 - 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Charging Chart 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tech Labels (Expanded Data) and Multipying Factors 5 - 11 . . . . . . . . . . . . . . . . . . . . . . Condenser Only Data 12 - 15 . . . . . . . . . . . . . . . . . . . . . . Cooling Multiplying Factors 16 - 20 . . . . . . . . . . . . . . . . . Exploded Drawings 21 - 23 . . . . . . . . . . . . . . . . . . . . . . . . Parts List 24 - 26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Model Number Identification 27 . . . . . . . . . . . . . . . . . . . . ! WARNING DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified per‐ sons could result in equipment malfunction, prop‐ erty damage, personal injury and/or death. The information contained in this manual is inten‐ ded for use by a qualified service technician famili‐ ar with safety procedures and equipped with the proper tools and test instruments. Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.

TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

421 04 5001 00 April 2008

TECHNICAL SUPPORT MANUALSplit System Air Conditioner

N2A3

DANGER, WARNING, CAUTION, andNOTEThe signal words DANGER, WARNING,CAUTION, and NOTE are used to identify levels ofhazard seriousness. The signal word DANGER isonly used on product labels to signify an immediatehazard. The signal words WARNING, CAUTION,and NOTE will be used on product labels andthroughout this manual and other manuals that mayapply to the product.

DANGER - Immediate hazards which will result insevere personal injury or death.

WARNING - Hazards or unsafe practices whichcould result in severe personal injury or death.

CAUTION - Hazards or unsafe practices whichmay result in minor personal injury or product orproperty damage.

NOTE - Used to highlight suggestions which willresult in enhanced installation, reliability, or opera‐tion.

Signal Words in Manuals

The signal word WARNING is used throughout thismanual in the following manner:

The signal word CAUTION is used throughout thismanual in the following manner:

Signal Words on Product Labeling

Signal words are used in combination with colorsand/or pictures on product labels.

WARNING

Safety Labeling and Signal Words

!

! CAUTION

WARNING

TABLE OF CONTENTSWiring Diagrams 2 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Charging Chart 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tech Labels (Expanded Data)and Multipying Factors 5 - 11. . . . . . . . . . . . . . . . . . . . . .

Condenser Only Data 12 - 15. . . . . . . . . . . . . . . . . . . . . .

Cooling Multiplying Factors 16 - 20. . . . . . . . . . . . . . . . .

Exploded Drawings 21 - 23. . . . . . . . . . . . . . . . . . . . . . . .

Parts List 24 - 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Model Number Identification 27. . . . . . . . . . . . . . . . . . . .

! WARNING

DEATH, PERSONAL INJURY, AND/OR PROPERTYDAMAGE HAZARD

Failure to carefully read and follow this warningcould result in equipment malfunction, propertydamage, personal injury and/or death.

Installation or repairs made by unqualified per‐sons could result in equipment malfunction, prop‐erty damage, personal injury and/or death.

The information contained in this manual is inten‐ded for use by a qualified service technician famili‐ar with safety procedures and equipped with theproper tools and test instruments.

Installation must conform with local buildingcodes and with the National Electrical CodeNFPA70 current edition or Canadian ElectricalCode Part 1 CSA C.22.1.

David
Logo on Grey - Title
Page 2: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

2421 04 5001 00

Model Sizes: 18, 24, 30, 36, 42, 48

1. Symbols are electrical representation only.

2. Compressor and fan motor furnished with inherent thermal protection.

3. To be wired in accordance with National Electric N.E.C. and local codes.

4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.

5. Use copper conductors only. Use conductors suitable for at least 75°C (167°F).

6. Connection for typical cooling only thermostat. For other arrangements see installation instructions.

7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead.

8. When start capacitor and relay are installed, start thermistor (PTC) is not used.

9. CH not used on all units.

10. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.

11. Check all electrical connections inside control box for tightness.

12. Do not attempt to operate unit until service valves have been opened.

13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting.

14. Wire not present if HPS, LPS or CTD are used.

Page 3: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

421 04 5001 003

Model Size: 60

1. Symbols are electrical representation only.

2. Compressor and fan motor furnished with inherent thermal protection.

3. To be wired in accordance with National Electric N.E.C. and local codes.

4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.

5. Use copper conductors only. Use conductors suitable for at least 75°C (167°F).

6. Connection for typical cooling only thermostat. For other arrangements see installation instructions.

7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead.

8. When start capacitor and relay are installed, start thermistor (PTC) is not used.

9. CH not used on all units.

10. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.

11. Check all electrical connections inside control box for tightness.

12. Do not attempt to operate unit until service valves have been opened.

13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting.

14. Wire not present if HPS, LPS or CTD are used.

Page 4: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

4 421 04 5001 00

R-22 CHARGING CHART� Find the required Subcooling Temperature on the unit Rating Plate. Use the closest column on the chart below

(5, 10, 15, or 20) .

� Add or remove refrigerant until both the Liquid Line Temperature and Liquid Pressure agree with chart data.

Measured Liquid Pressure (psig)

Rating Plate (required) Subcooling Temperature (°F)

5 10 15 20

R-22 Required Liquid Line Temperature (°F)

163 83 78 73 68

171 86 81 76 71

179 89 84 79 74

187 92 87 82 77

196 95 90 85 80

205 98 93 88 83

214 101 96 91 86

223 104 99 94 89

233 107 102 97 92

243 110 105 100 95

253 113 108 103 98

264 116 111 106 101

274 119 114 109 104

285 122 117 112 107

297 125 120 115 110

309 128 123 118 113

Page 5: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

421 04 5001 005

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 6: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

6421 04 5001 00

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 7: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

421 04 5001 007

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 8: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

8421 04 5001 00

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 9: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

421 04 5001 009

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 10: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

10421 04 5001 00

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 11: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

421 04 5001 0011

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 12: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

12 421 04 5001 00

Data for Condenser Only (Cooling)

Saturated SuctionTemperature °F

Condenser Entering Air Temperature °F

55 65 75 85 95 105 115 125

N2A318AKB, N2A318GKB

30TCG 15.30 14.40 13.60 12.90 12.10 11.40 10.60 9.80SDT 68.80 77.90 87.20 96.60 106.00 115.50 125.00 134.50KW 0.83 0.93 1.03 1.14 1.26 1.40 1.56 1.75

35TCG 17.00 16.00 15.10 14.30 13.50 12.70 11.90 10.90SDT 70.30 79.30 88.50 97.80 107.20 116.60 126.10 135.50KW 0.84 0.94 1.04 1.15 1.27 1.41 1.58 1.77

40TCG 18.70 17.70 16.70 15.90 15.00 14.10 13.20 12.20SDT 71.80 80.70 89.80 99.10 108.40 117.80 127.20 136.50KW 0.85 0.95 1.05 1.16 1.28 1.43 1.60 1.79

45TCG 20.50 19.40 18.40 17.50 16.50 15.60 14.60 13.50SDT 73.30 82.20 91.20 100.40 109.70 119.00 128.30 137.60KW 0.86 0.96 1.06 1.17 1.30 1.44 1.61 1.81

50TCG 22.40 21.30 20.20 19.20 18.20 17.10 16.10 14.90SDT 75.00 83.70 92.70 101.80 111.00 120.20 129.50 138.80KW 0.87 0.97 1.07 1.18 1.31 1.46 1.63 1.83

55TCG 24.40 23.20 22.10 21.00 19.90 18.80 17.60 16.40SDT 76.70 85.30 94.20 103.20 112.30 121.50 130.70 140.00KW 0.88 0.97 1.08 1.19 1.32 1.47 1.65 1.85

N2A324AKB, N2A324GKB

30TCG 19.60 18.90 18.20 17.30 16.30 15.00 13.60 12.00SDT 71.10 80.30 89.50 98.80 108.10 117.30 126.30 135.20KW 1.14 1.24 1.37 1.51 1.69 1.89 2.12 2.38

35TCG 21.70 20.90 20.10 19.20 18.10 16.90 15.50 13.90SDT 72.80 81.80 91.00 100.20 109.50 118.60 127.70 136.70KW 1.15 1.25 1.38 1.53 1.70 1.90 2.13 2.38

40TCG 24.00 23.10 22.20 21.20 20.10 18.80 17.40 15.90SDT 74.60 83.50 92.50 101.70 110.90 120.00 129.20 138.20KW 1.16 1.27 1.39 1.54 1.71 1.91 2.14 2.39

45TCG 26.50 25.40 24.30 23.30 22.10 20.80 19.40 17.80SDT 76.60 85.30 94.20 103.20 112.30 121.50 130.60 139.60KW 1.17 1.28 1.41 1.56 1.73 1.93 2.15 2.41

50TCG 29.20 27.90 26.70 25.50 24.20 22.90 21.40 19.80SDT 78.60 87.10 95.90 104.80 113.80 122.90 132.00 141.00KW 1.17 1.29 1.42 1.57 1.75 1.95 2.17 2.42

55TCG 32.10 30.60 29.20 27.80 26.40 25.00 23.50 21.90SDT 80.80 89.20 97.70 106.50 115.40 124.40 133.40 142.40KW 1.18 1.30 1.43 1.59 1.77 1.96 2.19 2.44

TCG = Gross Cooling Capacity (x 1000 BTU/hr)SDT = Saturated Temperature Leaving CompressorkW = Outdoor Unit Kilowatts

Page 13: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

421 04 5001 00 13

Data for Condenser Only (Cooling)

Saturated SuctionTemperature °F

Condenser Entering Air Temperature °FSaturated SuctionTemperature °F 1251151059585756555

N2A330AKB, N2A330GKB

30TCG 24.50 23.50 22.50 21.30 20.10 18.90 17.50 16.10SDT 71.20 80.30 89.60 98.80 108.10 117.50 126.80 136.10KW 1.30 1.46 1.63 1.81 2.00 2.21 2.44 2.70

35TCG 27.30 26.10 24.90 23.70 22.30 20.90 19.50 17.90SDT 73.00 82.00 91.10 100.20 109.50 118.70 128.00 137.20KW 1.32 1.48 1.65 1.83 2.03 2.24 2.48 2.75

40TCG 30.20 28.90 27.60 26.20 24.70 23.20 21.60 20.00SDT 74.90 83.70 92.70 101.70 110.90 120.00 129.30 138.50KW 1.35 1.51 1.68 1.86 2.06 2.28 2.52 2.80

45TCG 33.30 31.80 30.30 28.80 27.20 25.60 23.90 22.20SDT 76.80 85.50 94.40 103.30 112.40 121.50 130.60 139.80KW 1.39 1.54 1.71 1.89 2.09 2.31 2.56 2.84

50TCG 36.40 34.90 33.30 31.60 29.90 28.20 26.40 24.60SDT 78.80 87.40 96.10 105.00 113.90 123.00 132.10 141.20KW 1.42 1.57 1.73 1.91 2.11 2.33 2.58 2.86

55TCG 39.70 38.00 36.30 34.60 32.80 31.00 29.10 27.20SDT 80.80 89.30 97.90 106.70 115.60 124.60 133.60 142.70KW 1.43 1.58 1.74 1.92 2.11 2.33 2.58 2.87

N2A336AKB, N2A336GKB

30TCG 30.10 29.00 27.70 26.30 24.80 23.00 21.10 19.00SDT 73.40 82.30 91.20 100.30 109.30 118.40 127.50 136.40KW 1.63 1.81 2.00 2.20 2.43 2.70 3.01 3.37

35TCG 33.50 32.10 30.70 29.20 27.50 25.60 23.60 21.40SDT 75.40 84.10 92.90 101.80 110.80 119.80 128.80 137.70KW 1.67 1.85 2.04 2.24 2.47 2.73 3.04 3.40

40TCG 37.00 35.50 33.90 32.20 30.40 28.40 26.30 24.00SDT 77.60 86.10 94.70 103.50 112.40 121.30 130.20 139.10KW 1.73 1.90 2.09 2.29 2.51 2.78 3.08 3.44

45TCG 40.60 38.90 37.20 35.40 33.40 31.30 29.10 26.70SDT 79.80 88.10 96.60 105.30 114.00 122.90 131.70 140.50KW 1.77 1.95 2.13 2.33 2.56 2.82 3.13 3.49

50TCG 44.30 42.50 40.60 38.60 36.50 34.30 32.00 29.40SDT 82.00 90.10 98.50 107.10 115.70 124.50 133.20 142.00KW 1.81 1.98 2.16 2.37 2.59 2.86 3.17 3.53

55TCG 48.00 46.00 44.00 41.90 39.70 37.40 34.90 32.30SDT 84.10 92.10 100.40 108.80 117.40 126.10 134.70 143.40KW 1.82 1.99 2.18 2.38 2.61 2.87 3.18 3.55

TCG = Gross Cooling Capacity (x 1000 BTU/hr)SDT = Saturated Temperature Leaving CompressorkW = Outdoor Unit Kilowatts

Page 14: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

14 421 04 5001 00

Data for Condenser Only (Cooling)

Saturated SuctionTemperature °F

Condenser Entering Air Temperature °FSaturated SuctionTemperature °F 1251151059585756555

N2A342AKA, N2A342GKA

30TCG 34.10 32.70 31.10 29.60 28.80 26.30 24.70 22.90SDT 72.90 81.90 91.00 100.10 104.80 118.70 128.00 137.40KW 1.96 2.19 2.44 2.72 2.88 3.38 3.75 4.15

35TCG 37.60 36.00 34.30 32.70 31.80 29.20 27.40 25.50SDT 74.60 83.50 92.50 101.60 106.20 120.00 129.30 138.60KW 1.99 2.22 2.47 2.75 2.90 3.41 3.79 4.20

40TCG 41.20 39.50 37.80 36.00 35.00 32.20 30.30 28.30SDT 76.50 85.20 94.10 103.10 107.60 121.40 130.60 139.80KW 2.02 2.25 2.50 2.78 2.94 3.45 3.83 4.24

45TCG 45.20 43.30 41.40 39.50 38.50 35.40 33.40 31.20SDT 78.40 87.00 95.80 104.70 109.20 122.80 132.00 141.10KW 2.06 2.28 2.53 2.82 2.97 3.48 3.87 4.28

50TCG 49.30 47.30 45.30 43.20 42.10 38.80 36.60 34.30SDT 80.50 89.00 97.60 106.40 110.80 124.30 133.40 142.50KW 2.09 2.32 2.57 2.85 3.01 3.52 3.91 4.33

55TCG 53.80 51.60 49.40 47.10 46.00 42.40 40.00 37.50SDT 82.60 91.00 99.50 108.20 112.60 125.90 134.90 143.90KW 2.13 2.36 2.61 2.89 3.05 3.56 3.95 4.37

N2A348AKA, N2A348GKA

30TCG 43.30 40.70 38.10 35.60 33.10 30.50 28.00 25.60SDT 72.60 81.40 90.20 99.20 108.30 117.40 126.60 135.90KW 2.32 2.53 2.75 3.00 3.26 3.54 3.84 4.15

35TCG 48.10 45.40 42.70 40.00 37.30 34.70 32.00 29.40SDT 74.50 83.10 91.90 100.80 109.80 119.00 128.10 137.30KW 2.36 2.57 2.80 3.06 3.34 3.64 3.96 4.30

40TCG 53.30 50.40 47.50 44.70 41.80 39.00 36.20 33.40SDT 76.50 85.00 93.70 102.50 111.50 120.50 129.60 138.80KW 2.39 2.61 2.85 3.11 3.41 3.73 4.07 4.44

45TCG 58.90 55.80 52.70 49.60 46.60 43.60 40.70 37.70SDT 78.60 87.00 95.60 104.30 113.20 122.20 131.20 140.30KW 2.43 2.65 2.89 3.17 3.47 3.80 4.17 4.56

50TCG 64.80 61.40 58.10 54.80 51.60 48.40 45.30 42.10SDT 80.80 89.10 97.50 106.10 115.00 123.90 132.90 141.90KW 2.47 2.69 2.94 3.22 3.53 3.88 4.26 4.67

55TCG 71.00 67.30 63.80 60.20 56.80 53.40 50.10 46.70SDT 83.00 91.30 99.60 108.10 116.80 125.60 134.60 143.50KW 2.51 2.73 2.99 3.27 3.59 3.95 4.34 4.77

TCG = Gross Cooling Capacity (x 1000 BTU/hr)SDT = Saturated Temperature Leaving CompressorkW = Outdoor Unit Kilowatts

Page 15: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

421 04 5001 00 15

Data for Condenser Only (Cooling)

Saturated SuctionTemperature °F

Condenser Entering Air Temperature °FSaturated SuctionTemperature °F 1251151059585756555

N2A360AKB, N2A360GKB

30TCG 52.00 49.50 47.10 44.60 41.90 39.10 36.10 32.80SDT 75.00 83.90 93.00 102.20 111.30 120.50 129.60 138.60KW 2.71 3.02 3.35 3.71 4.12 4.58 5.10 5.71

35TCG 57.40 54.70 52.00 49.30 46.50 43.50 40.30 37.00SDT 77.00 85.80 94.80 103.90 113.00 122.10 131.10 140.10KW 2.79 3.09 3.41 3.77 4.18 4.65 5.19 5.81

40TCG 63.20 60.20 57.30 54.40 51.30 48.20 44.80 41.30SDT 79.10 87.80 96.70 105.60 114.70 123.70 132.70 141.70KW 2.88 3.17 3.49 3.85 4.26 4.74 5.29 5.93

45TCG 69.30 66.00 62.80 59.60 56.40 53.00 49.50 45.80SDT 81.30 89.90 98.60 107.50 116.40 125.40 134.40 143.30KW 2.98 3.26 3.57 3.93 4.34 4.82 5.39 6.03

50TCG 75.60 72.00 68.50 65.10 61.60 58.00 54.20 50.30SDT 83.50 92.00 100.60 109.40 118.20 127.10 136.00 144.90KW 3.08 3.34 3.65 4.00 4.42 4.90 5.47 6.14

55TCG 82.00 78.10 74.30 70.50 66.80 63.00 59.00 54.90SDT 85.70 94.10 102.60 111.30 120.00 128.90 137.70 146.50KW 3.17 3.42 3.72 4.06 4.48 4.97 5.55 6.22

TCG = Gross Cooling Capacity (x 1000 BTU/hr)SDT = Saturated Temperature Leaving CompressorkW = Outdoor Unit Kilowatts

Page 16: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

16421 04 5001 00

COOLING Multiplying Factors for other Indoor Combinations

IndoorModel

FurnaceModel Capac. (MBh) Power (AMPS)

IndoorModel

FurnaceModel Capac. (MBh) Power (AMPS)

IndoorModel

FurnaceModel Capac. (MBh) Power (AMPS)

N2A318>EB*2X18B** 1.00 1.00 ED*2X18B** MV08B15**B* 1.00 0.93 EHD2X24A** MV08B15**B* 1.04 0.97

EB*2X18B** *8MPV050 1.02 0.95 ED*2X24B** 1.02 1.02 EMA2X24D** 1.02 1.02

EB*2X18B** MV08B15**B* 1.00 0.93 ED*2X24B** *8MPV050 1.05 0.98 FEM2X18**** 1.03 0.96

EB*2X24B** 1.02 1.02 ED*2X24B** MV08B15**B* 1.02 0.96 FEM2X24**** 1.04 0.97

EB*2X24B** *8MPV050 1.05 0.98 ED*2X24F** 1.02 1.02 FS(M,U)2X18*** 1.01 1.01

EB*2X24B** MV08B15**B* 1.02 0.96 EHD2X24A** 1.02 1.02 FS(M,U)2X24*** 0.98 0.98

EB*2X24F** 1.02 1.02 EHD2X24A** *8MPV050 1.05 0.98 FSA2X18**** 0.98 0.98

ED*2X18B** 1.00 1.00 EHD2X24A** *9MPV050 1.05 0.98 FSA2X24**** 1.02 1.02

ED*2X18B** *8MPV050 1.02 0.95 EHD2X24A** *9MPV075 1.05 0.98 FVM2X24**** 0.99 0.93

N2A324>EB*2X24B** 1.00 1.00 ED*2X24F** *9MPV050 1.00 0.93 EHD2X24A** MV12F19**B* 1.02 0.95

EB*2X24B** *8MPV050 1.01 0.97 ED*2X24F** *9MPV075 1.01 0.94 EHD2X30A** 1.01 1.01

EB*2X24B** MV08B15**B* 1.00 0.93 ED*2X24F** MV12F19**B* 1.00 0.93 EHD2X30A** *8MPV050 1.03 0.98

EB*2X24F** 1.00 1.00 ED*2X30B** 1.01 1.01 EHD2X30A** *8MPV075 1.03 0.96

EB*2X24F** *8MPV075 1.02 0.95 ED*2X30B** *8MPV050 1.02 0.97 EHD2X30A** *8MPV100 1.04 0.97

EB*2X24F** *9MPV050 1.00 0.93 ED*2X30B** MV08B15**B* 1.01 0.94 EHD2X30A** *8MPV125 1.04 0.97

EB*2X24F** *9MPV075 1.01 0.94 ED*2X30F** 1.01 1.01 EHD2X30A** *9MPV050 1.01 0.94

EB*2X24F** MV12F19**B* 1.00 0.93 ED*2X30F** *8MPV075 1.03 0.96 EHD2X30A** *9MPV075 1.02 0.95

EB*2X30B** 1.01 1.01 ED*2X30F** *9MPV050 1.01 0.94 EHD2X30A** *9MPV100 1.03 0.96

EB*2X30B** *8MPV050 1.02 0.97 ED*2X30F** *9MPV075 1.02 0.95 EHD2X30A** *9MPV125 1.04 0.97

EB*2X30B** MV08B15**B* 1.01 0.94 ED*2X30F** MV12F19**B* 1.01 0.94 EHD2X30A** MV08B15**B* 1.02 0.95

EB*2X30F** 1.00 1.00 EHD2X24A** 1.00 1.00 EHD2X30A** MV12F19**B* 1.02 0.95

EB*2X30F** *8MPV075 1.03 0.96 EHD2X24A** *8MPV050 1.01 0.97 EMA2X24D** 1.00 1.00

EB*2X30F** *9MPV050 1.01 0.94 EHD2X24A** *8MPV075 1.01 0.94 FEM2X24**** 1.01 0.94

EB*2X30F** *9MPV075 1.02 0.95 EHD2X24A** *8MPV100 1.02 0.95 FEM2X30**** 1.02 0.95

EB*2X30F** MV12F19**B* 1.01 0.94 EHD2X24A** *8MPV125 1.02 0.95 FS(M,U)2X24*** 1.01 1.01

ED*2X24B** 1.00 1.00 EHD2X24A** *9MPV050 1.01 0.94 FS(M,U)2X30*** 1.00 1.00

ED*2X24B** *8MPV050 1.01 0.97 EHD2X24A** *9MPV075 1.01 0.94 FSA2X24**** 0.98 0.98

ED*2X24B** MV08B15**B* 1.00 0.93 EHD2X24A** *9MPV100 1.01 0.94 FSA2X30**** 0.99 0.99

ED*2X24F** 1.00 1.00 EHD2X24A** *9MPV125 1.02 0.95 FVM2X24**** 1.02 0.95

ED*2X24F** *8MPV075 1.02 0.95 EHD2X24A** MV08B15**B* 1.01 0.94 FVM2X36**** 1.01 0.94

> Indicates Tested Indoor Model

- continued on next page -

Page 17: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

421 04 5001 0017

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

N2A330>EB*2X30B** 1.00 1.00 ED*2X30F** *9MPV050 0.99 0.95 EHD2X30A** MV12F19**B* 1.00 0.93

EB*2X30B** *8MPV050 0.99 0.97 ED*2X30F** *9MPV075 0.99 0.95 EHD2X36A** 1.01 1.01

EB*2X30B** MV08B15**B* 1.00 0.93 ED*2X30F** MV12F19**B* 1.00 0.93 EHD2X36A** *8MPV050 1.01 0.96

EB*2X30F** 1.00 1.00 ED*2X36B** 1.00 1.00 EHD2X36A** *8MPV075 1.01 0.95

EB*2X30F** *8MPV075 1.01 0.94 ED*2X36B** *8MPV050 1.00 0.97 EHD2X36A** *8MPV100 1.01 0.95

EB*2X30F** *9MPV050 0.99 0.95 ED*2X36B** MV08B15**B* 1.00 0.93 EHD2X36A** *8MPV125 1.01 0.95

EB*2X30F** *9MPV075 0.99 0.95 ED*2X36F** 1.01 1.01 EHD2X36A** *9MPV050 1.00 0.93

EB*2X30F** MV12F19**B* 0.99 0.93 ED*2X36F** *8MPV075 1.01 0.94 EHD2X36A** *9MPV075 1.00 0.93

EB*2X36B** 1.00 1.00 ED*2X36F** *9MPV050 1.00 0.96 EHD2X36A** *9MPV100 1.01 0.95

EB*2X36B** *8MPV050 1.00 0.97 ED*2X36F** *9MPV075 1.00 0.96 EHD2X36A** *9MPV125 1.01 0.95

EB*2X36B** MV08B15**B* 1.00 0.93 ED*2X36F** MV12F19**B* 1.01 0.94 EHD2X36A** MV08B15**B* 1.01 0.94

EB*2X36F** 1.01 1.01 ED*2X36J** 1.00 1.00 EHD2X36A** MV12F19**B* 1.01 0.94

EB*2X36F** *8MPV075 1.01 0.94 ED*2X36J** *8MPV100 1.02 0.95 EMA2X36D** 1.01 1.01

EB*2X36F** *9MPV050 1.00 0.96 ED*2X36J** *8MPV125 1.02 0.95 FEM2X30**** 1.01 0.94

EB*2X36F** *9MPV075 1.00 0.96 ED*2X36J** *9MPV100 1.01 0.95 FEM2X35**** 1.01 0.97

EB*2X36F** MV12F19**B* 1.01 0.94 EHD2X30A** 1.00 1.00 FEM2X36**** 1.03 0.96

EB*2X36J** 1.00 1.00 EHD2X30A** *8MPV050 0.99 0.97 FS(M,U)2X30*** 0.99 0.99

EB*2X36J** *8MPV100 1.02 0.95 EHD2X30A** *8MPV075 1.00 0.96 FSA2X30**** 0.99 0.99

EB*2X36J** *8MPV125 1.02 0.95 EHD2X30A** *8MPV100 1.00 0.96 FSA2X36**** 1.00 1.00

EB*2X36J** *9MPV100 1.01 0.95 EHD2X30A** *8MPV125 1.00 0.93 FSM2X36**** 1.02 1.02

ED*2X30B** 1.00 1.00 EHD2X30A** *9MPV050 0.99 0.94 FSU2X36**** 0.99 1.01

ED*2X30B** *8MPV050 0.99 0.97 EHD2X30A** *9MPV075 0.99 0.94 FVM2X24**** 1.01 0.94

ED*2X30B** MV08B15**B* 1.00 0.93 EHD2X30A** *9MPV100 0.99 0.93 FVM2X36**** 1.01 0.94

ED*2X30F** 1.00 1.00 EHD2X30A** *9MPV125 0.99 0.93 FVM2X48**** 1.04 0.97

ED*2X30F** *8MPV075 1.01 0.94 EHD2X30A** MV08B15**B* 1.00 0.93

N2A336>EB*2X36F** 1.00 1.00 ED*2X36F** *9MPV075 0.99 0.97 EHD2X36A** MV12F19**B* 1.00 0.93

EB*2X36B** 0.99 0.99 ED*2X36F** MV12F19**B* 1.01 0.94 EHD2X36A** MV16J22**B* 1.00 0.93

EB*2X36B** MV08B15**B* 1.00 0.93 ED*2X36J** 1.00 1.00 EHD2X36A** MV20L24**B* 1.00 0.93

EB*2X36F** *8MPV075 1.00 0.96 ED*2X36J** *8MPV100 1.02 0.95 EHD2X42A** 1.01 1.01

EB*2X36F** *9MPV050 0.99 0.99 ED*2X36J** *8MPV125 1.02 0.95 EHD2X42A** *8MPV050 0.99 0.95

> Indicates Tested Indoor Model

- continued on next page -

Page 18: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

18421 04 5001 00

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

EB*2X36F** *9MPV075 0.99 0.97 ED*2X36J** *9MPV100 1.01 0.97 EHD2X42A** *8MPV075 1.01 0.97

EB*2X36F** MV12F19**B* 1.01 0.94 ED*2X36J** MV16J22**B* 1.01 0.94 EHD2X42A** *8MPV100 1.02 0.96

EB*2X36J** 1.00 1.00 ED*2X42F** 1.01 1.01 EHD2X42A** *8MPV125 1.02 0.96

EB*2X36J** *8MPV100 1.02 0.95 ED*2X42F** *8MPV075 1.01 0.97 EHD2X42A** *9MPV050 1.00 0.96

EB*2X36J** *8MPV125 1.02 0.95 ED*2X42F** *9MPV050 1.00 0.97 EHD2X42A** *9MPV075 1.01 0.96

EB*2X36J** *9MPV100 1.01 0.97 ED*2X42F** *9MPV075 1.00 0.96 EHD2X42A** *9MPV100 1.02 0.97

EB*2X36J** MV16J22**B* 1.01 0.94 ED*2X42F** MV12F19**B* 1.01 0.94 EHD2X42A** *9MPV125 1.02 0.96

EB*2X42F** 1.01 1.01 ED*2X42J** 1.01 1.01 EHD2X42A** MV08B15**B* 1.01 0.94

EB*2X42F** *8MPV075 1.01 0.96 ED*2X42J** *8MPV100 1.02 0.96 EHD2X42A** MV12F19**B* 1.01 0.94

EB*2X42F** *9MPV050 1.00 0.97 ED*2X42J** *8MPV125 1.02 0.96 EHD2X42A** MV16J22**B* 1.01 0.94

EB*2X42F** *9MPV075 1.00 0.96 ED*2X42J** *9MPV100 1.02 0.98 EHD2X42A** MV20L24**B* 1.01 0.94

EB*2X42F** MV12F19**B* 1.00 0.93 ED*2X42J** MV16J22**B* 1.01 0.94 EMA2X36D** 1.00 1.00

EB*2X42J** 1.01 1.01 ED*2X42L** 1.01 1.01 FEM2X35**** 1.02 0.98

EB*2X42J** *8MPV100 1.02 0.96 ED*2X42L** *9MPV125 1.02 0.96 FEM2X36**** 1.04 0.97

EB*2X42J** *8MPV125 1.02 0.96 ED*2X42L** MV20L24**B* 1.01 0.94 FEM2X42**** 1.04 0.97

EB*2X42J** *9MPV100 1.02 0.98 EHD2X36A** 1.00 1.00 FS(M,U)2X42*** 1.02 1.02

EB*2X42J** MV16J22**B* 1.01 0.94 EHD2X36A** *8MPV050 0.99 0.96 FSA2X36**** 1.00 1.00

EB*2X42L** 1.01 1.01 EHD2X36A** *8MPV075 1.01 0.94 FSM2X36**** 1.02 0.99

EB*2X42L** *9MPV125 1.02 0.96 EHD2X36A** *8MPV100 1.01 0.94 FSU2X36**** 1.01 1.02

EB*2X42L** MV20L24**B* 1.01 0.94 EHD2X36A** *8MPV125 1.01 0.94 FVM2X24**** 1.00 0.96

ED*2X36B** 0.99 0.99 EHD2X36A** *9MPV050 0.99 0.95 FVM2X36**** 1.01 0.94

ED*2X36B** MV08B15**B* 1.00 0.93 EHD2X36A** *9MPV075 0.99 0.95 FVM2X48**** 1.05 0.98

ED*2X36F** 1.00 1.00 EHD2X36A** *9MPV100 1.01 0.96 FVM2X60**** 1.05 0.98

ED*2X36F** *8MPV075 1.00 0.96 EHD2X36A** *9MPV125 1.01 0.94

ED*2X36F** *9MPV050 0.99 0.99 EHD2X36A** MV08B15**B* 0.99 0.93

N2A342>EB*2X42J** 1.00 1.00 ED*2X48J** *8MPV125 1.02 1.01 EP*42J**** 0.95 0.98

EB*2X42J** *8MPV100 1.00 0.98 ED*2X48J** *9MPV100 1.01 0.99 EP*42J**** *8MPV100 0.95 0.98

EB*2X42J** *8MPV125 1.00 0.98 ED*2X48J** MV16J22**** 1.02 0.98 EP*42J**** *8MPV125 0.95 0.98

EB*2X42J** *9MPV100 1.00 1.00 ED*2X48L** 1.01 1.01 EP*42J**** *9MPV100 0.94 0.96

EB*2X42J** MV16J22**** 1.00 0.96 ED*2X48L** *9MPV125 1.02 1.01 EP*42J**** MV16J22**** 0.95 0.95

EB*2X42L** 1.00 1.00 EHD2X42A** 1.00 1.00 EP*48F**** 0.96 0.99

EB*2X42L** *9MPV125 1.00 0.98 EHD2X42A** *8MPV075 1.00 1.00 EP*48F**** *8MPV075 0.96 0.99

> Indicates Tested Indoor Model

- continued on next page -

Page 19: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

421 04 5001 0019

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

EB*2X48F** 1.00 1.00 EHD2X42A** *8MPV100 1.00 0.98 EP*48F**** *9MPV075 0.95 0.98

EB*2X48F** *8MPV075 1.00 1.00 EHD2X42A** *8MPV125 1.00 0.98 EP*48J**** 0.99 1.02

EB*2X48F** *9MPV075 0.99 0.99 EHD2X42A** *9MPV075 1.00 1.00 EP*48J**** *8MPV100 0.99 0.99

EB*2X48J** 1.01 1.01 EHD2X42A** *9MPV100 1.00 0.98 EP*48J**** *8MPV125 0.99 0.99

EB*2X48J** *8MPV100 1.01 0.99 EHD2X42A** *9MPV125 1.00 0.98 EP*48J**** *9MPV100 0.98 0.98

EB*2X48J** *8MPV125 1.01 0.97 EHD2X42A** MV16J22**** 1.00 0.96 EP*48J**** MV16J22**** 0.99 0.94

EB*2X48J** *9MPV100 1.01 0.99 EHD2X42A** MV20N26**** 1.00 0.96 EP*48L**** 0.99 1.02

EB*2X48J** MV16J22**** 1.02 0.98 EHD2X48A** 0.99 0.99 EP*48L**** *9MPV125 0.99 0.99

EB*2X48L** 1.01 1.01 EHD2X48A** *8MPV075 0.99 0.99 EP*48N**** 0.99 1.02

EB*2X48L** *9MPV125 1.02 1.01 EHD2X48A** *8MPV100 0.99 0.97 EP*48N**** MV20N26**** 0.99 0.97

EBP42**** 0.98 1.00 EHD2X48A** *8MPV125 0.99 0.97 EX*42F**** 0.98 0.98

EBP48**** 1.00 1.03 EHD2X48A** *9MPV075 0.99 0.99 EX*42F**** *8MPV075 0.99 0.99

EBV36**** 0.98 0.96 EHD2X48A** *9MPV100 0.99 0.97 EX*42F**** *9MPV075 0.98 0.98

EBV48**** 1.04 0.99 EHD2X48A** *9MPV125 0.99 0.97 EX*42J**** 0.98 0.98

EBV60**** 1.06 1.02 EHD2X48A** MV16J22**** 0.99 0.94 EX*42J**** *8MPV100 1.00 1.00

EBX48**** 1.01 1.01 EHD2X48A** MV20N26**** 0.99 0.94 EX*42J**** *8MPV125 1.00 0.98

ED*2X42J** 1.00 1.00 EL*42F**** 0.94 0.96 EX*42J**** *9MPV100 0.99 0.99

ED*2X42J** *8MPV100 1.00 0.98 EL*42F**** *8MPV075 0.95 0.98 EX*42J**** MV16J22**** 1.01 0.99

ED*2X42J** *8MPV125 1.00 0.98 EL*42F**** *9MPV075 0.94 0.96 EX*48J**** 1.00 1.00

ED*2X42J** *9MPV100 1.00 1.00 EL*48F**** 0.96 0.99 EX*48J**** *9MPV125 1.00 0.98

ED*2X42J** MV16J22**** 1.00 0.96 EL*48F**** *8MPV075 0.96 0.99 EX*48L**** 1.00 1.00

ED*2X42L** 1.00 1.00 EL*48F**** *9MPV075 0.95 0.98 EX*48L**** *9MPV125 1.00 1.00

ED*2X42L** *9MPV125 1.00 0.98 EMA2X48D** 0.99 0.99 EX*48N**** 1.00 1.00

ED*2X48F** 1.00 1.00 EMH42F**** 0.94 0.96 EX*48N**** MV20N26**** 1.00 0.96

ED*2X48F** *8MPV075 1.00 1.00 EMH48F**** 0.98 1.00 FEM2X42**** 1.02 1.01

ED*2X48F** *9MPV075 0.99 0.99 EP*42F**** 0.94 0.96 FEM2X48**** 1.04 0.99

ED*2X48J** 1.01 1.01 EP*42F**** *8MPV075 0.95 0.98 FS(M,U)2X42*** 1.00 1.00

ED*2X48J** *8MPV100 1.01 0.99 EP*42F**** *9MPV075 0.94 0.96 FS(M,U)2X48*** 1.01 1.01

N2A348>EB*2X48J** 1.00 1.00 ED*2X48L** 1.00 1.00 EMH48F**** 0.95 0.97

EB*2X48F** 0.98 0.98 ED*2X48L** *9MPV125 1.00 1.00 EP*48F**** 0.93 0.96

EB*2X48J** *8MPV100 1.00 1.00 ED*2X60J** 1.03 1.03 EP*48J**** 0.96 0.98

EB*2X48J** *8MPV125 1.01 1.01 ED*2X60J** *8MPV100 1.04 1.04 EP*48L**** 0.96 0.98

> Indicates Tested Indoor Model

- continued on next page -

Page 20: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: N2A

3

20421 04 5001 00

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

EB*2X48J** *9MPV100 0.98 0.98 ED*2X60J** *8MPV125 1.04 1.04 EP*48N**** 0.96 0.98

EB*2X48J** MV16J22**** 1.02 1.00 ED*2X60J** *9MPV100 1.03 1.03 EP*48N**** MV20N26**** 0.98 0.98

EB*2X48L** 1.00 1.00 ED*2X60J** MV16J22**** 1.05 1.01 EP*60J**** 0.99 1.02

EB*2X48L** *9MPV125 1.00 1.00 ED*2X60L** 1.03 1.03 EP*60J**** MV16J22**** 1.00 0.98

EB*2X60J** 1.03 1.03 ED*2X60L** *9MPV125 1.03 1.01 EP*60L**** 0.99 1.02

EB*2X60J** *8MPV100 1.04 1.04 EHD2X48A** 1.00 1.00 EP*60N**** 0.99 1.02

EB*2X60J** *8MPV125 1.04 1.02 EHD2X48A** *8MPV100 0.99 0.97 EP*60N**** MV20N26**** 1.00 0.98

EB*2X60J** *9MPV100 1.03 1.03 EHD2X48A** *8MPV125 0.99 0.99 EX*48J**** 0.98 1.01

EB*2X60J** MV16J22**** 1.05 1.01 EHD2X48A** *9MPV100 0.99 0.99 EX*48L**** 0.98 1.01

EB*2X60L** 1.03 1.03 EHD2X48A** *9MPV125 0.99 0.99 EX*48N**** 0.98 1.01

EB*2X60L** *9MPV125 1.03 1.01 EHD2X48A** MV16J22**** 0.99 0.97 EX*48N**** MV20N26**** 1.00 0.98

EBP48**** 1.00 1.03 EHD2X48A** MV20N26**** 0.99 0.97 EX*60L**** 1.04 1.04

EBP60**** 1.02 1.05 EHD2X60A** 1.03 1.03 EX*60L**** *9MPV125 1.03 1.01

EBV48**** 1.03 1.01 EHD2X60A** *8MPV100 1.02 1.00 EX*60N**** 1.04 1.04

EBV60**** 1.05 1.01 EHD2X60A** *8MPV125 1.02 1.00 EX*60N**** MV20N26**** 1.05 1.01

EBX48**** 1.02 1.05 EHD2X60A** *9MPV100 1.02 1.02 FEM2X48**** 1.03 1.01

EBX60**** 1.04 1.07 EHD2X60A** *9MPV125 1.02 1.00 FEM2X60**** 1.05 1.01

ED*2X48F** 0.98 0.98 EHD2X60A** MV16J22**** 1.02 0.98 FS(M,U)2X48*** 1.02 1.02

ED*2X48J** 1.00 1.00 EHD2X60A** MV20N26**** 1.02 0.98 FS(M,U)2X60*** 1.04 1.04

ED*2X48J** *8MPV100 1.00 1.00 EL*48F**** 0.93 0.96 FVM2X48**** 1.02 0.94

ED*2X48J** *8MPV125 1.01 1.01 EL*60J**** 0.99 1.02 FVM2X60**** 1.03 0.95

ED*2X48J** *9MPV100 0.98 0.98 EL*60J**** MV16J22**** 1.00 0.98

ED*2X48J** MV16J22**** 1.02 1.00 EMA2X48D** 0.98 0.98

N2A360>EB*2X60L** 1.00 1.00 ED*2X60J** MV16J22**B* 1.00 0.96 EHD2X60A** MV20L24**B* 1.00 0.96

EB*2X60J** 1.00 1.00 ED*2X60L** 1.00 1.00 FEM2X60**** 1.00 0.96

EB*2X60J** MV16J22**B* 1.00 0.96 ED*2X60L** MV20L24**B* 1.00 0.96 FS(M,U)2X60*** 1.00 1.00

EB*2X60L** MV20L24**B* 1.00 0.96 EHD2X60A** 1.00 1.00 FVM2X60**** 1.01 0.95

ED*2X60J** 1.00 1.00 EHD2X60A** MV16J22**B* 1.00 0.96

> Indicates Tested Indoor Model

Page 21: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

421 04 5001 00 21

A

G

2

L

B

32

3

C

E

F

D

Nut, AcornGuardFan

MotorFan

Raceway

Fan

Top, Cover

Grille, Inlet

Base, Pan

ServicePanel

ControlBox

ControlBoxCover

NOTE: This illustration is forreference only. Your unit maydiffer in appearance or may notinclude all components shown.Please refer to Parts List forexact parts listing.

Page 22: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

22 421 04 5001 00

6

9

27

35

7

17

1

11

10

N

G

19

8

36

Condenser, CoilAssembly

Blanket ,Sound( When Used )

Compressor

Bolt, SHLDR (4)

Heater, CRKC( When Used )

Switch, LowPressure

Valve ServiceSuction

GrommetCompressor

SupportCoil

BasePan

Switch Temp.CC Heater(When Used)

Valve Service,Liquid

Switch, HighPressure

Plug, Compressor

,

,24Filter Drier

NOTE: This illustration is forreference only. Your unit maydiffer in appearance or may notinclude all components shown.Please refer to Parts List forexact parts listing.

Page 23: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

421 04 5001 00 23

25

D

21

5

P

433

34

Box, Control

HarnessAssembly

Lug, Ground

Contactor

Strap,Capacitor

Capacitor

CTL, 2 SPD Fan

Module,Comfort Alert

NOTE: This illustration is forreference only. Your unit maydiffer in appearance or may notinclude all components shown.Please refer to Parts List forexact parts listing.

Page 24: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

24 421 04 5001 00

N2A3 PARTS LIST

KEYNO. DESCRIPTION PART NO. N

2A31

8AK

B20

0

N2A

318G

KB

200

N2A

324A

KB

200

N2A

324G

KB

200

N2A

330A

KB

200

N2A

330G

KB

200

N2A

336A

KB

200

N2A

336G

KB

200

N2A

342A

KA

100

N2A

342G

KA

100

N2A

348A

KA

200

N2A

348A

KA

200

N2A

360A

KB

200

N2A

360G

KB

200

01 COMPRESSOR ZR16KA-PFV-130 ZR16KAPFV130 1 1 - - - - - - - - - - - -01 ZR21KA-PFV-130 ZR21KAPFV130 - - 1 1 - - - - - - - - - -01 ZR26KA-PFV-130 ZR26KAPFV130 - - - - 1 1 - - - - - - - -01 ZR32KA-PFV-130 ZR32KAPFV130 - - - - - - 1 1 - - - - - -01 ZR38KA-PFV-130 ZR38KAPFV130 - - - - - - - - 1 1 - - - -01 ZR44KA-PFV-130 ZR44KAPFV130 - - - - - - - - - - 1 1 - -01 ZR54KA-PFV-130 ZR54KAPFV130 - - - - - - - - - - - - 1 102 MOTOR CONDENSER FAN 1172706 1 1 - - - - - - - - - - - -02 1172707 - - 1 1 - - - - - - - - - -02 1172708 - - - - 1 1 - - - - - - - -02 1172709 - - - - - - - - 1 1 - - - -02 1172775 - - - - - - 1 1 - - - - - -02 1173665 - - - - - - - - - - 1 1 1 103 FAN BLADE 1172711 1 1 - - - - - - - - - - - -03 1172712 - - 1 1 - - - - - - - - - -03 1173853 - - - - 1 1 - - - - - - - -03 1173854 - - - - - - - - 1 1 - - - -03 1172713 - - - - - - 1 1 - - - - - -03 1172716 - - - - - - - - - - 1 1 1 104 CONTACTOR 30 AMP 1172472 1 1 1 1 1 1 1 1 1 1 1 1 - -04 40 AMP 1172786 - - - - - - - - - - - - 1 105 CAPACITOR 370V 30+5 MFD 1172109 1 1 - - - - - - - - - - - -05 370V 35+5 MFD 1172110 - - 1 1 - - - - - - - - - -05 370V 45+5 MFD 1172124 - - - - 1 1 - - - - - - - -05 370V 50+5 MFD 1172111 - - - - - - 1 1 - - - - - -05 370V 55+5 MFD 1172123 - - - - - - - - 1 1 - - - -05 370V 60+7.5 MFD 1172294 - - - - - - - - - - 1 1 - -05 370V 80+5 MFD 1172296 - - - - - - - - - - - - 1 106 CONDENSER COIL 1172720 1 1 1 1 - - - - - - - - - -06 1176538 - - - - 1 1 - - - - - - - -06 1172788 - - - - - - 1 1 - - - - - -06 1172789 - - - - - - - - 1 1 - - - -06 1174078 - - - - - - - - - - 1 1 - -06 1176539 - - - - - - - - - - - - 1 107 SERVICE VALVE SUCTION 1172726 1 1 1 1 1 1 - - - - - - - -07 1172727 - - - - - - 1 1 1 1 1 1 1 108 SERVICE VALVE LIQUID 1172792 1 1 1 1 1 1 1 1 1 1 1 1 1 109 PLUG COMPRESSOR HARNESS 1172729 1 1 1 1 - - - - - - - - - -09 1172730 - - - - 1 1 1 1 - - - - - -09 1172731 - - - - - - - - 1 1 - - - -09 1172732 - - - - - - - - - - - - 1 109 1172793 - - - - - - - - - - 1 1 - -10 GROMMET COMPRESSOR 1171270 4 4 4 4 4 4 4 4 4 4 4 4 4 4

- continued on next page -

Page 25: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

421 04 5001 00 25

N2A3 PARTS LIST (continued)

KEYNO. N

2A36

0GK

B20

0

N2A

360A

KB

200

N2A

348A

KA

200

N2A

348A

KA

200

N2A

342G

KA

100

N2A

342A

KA

100

N2A

336G

KB

200

N2A

336A

KB

200

N2A

330G

KB

200

N2A

330A

KB

200

N2A

324G

KB

200

N2A

324A

KB

200

N2A

318G

KB

200

N2A

318A

KB

200

PART NO.DESCRIPTION11 BOLT COMPRESSOR MOUNTING 1173630 4 4 4 4 4 4 4 4 4 4 4 4 4 420 DISTRUBITOR 1173667 - - - - - - - - - - - - 1 120 1172021 - - - - - - - - 1 1 - - - -20 1172022 - - - - - - - - - - 1 1 - -24 DRIER 1172794 - 1 - 1 - 1 - 1 1 1 1 1 - 132 RACEWAY 1173642 1 1 1 1 1 1 - - - - - - - -

32 1171428 - - - - - - 1 1 - - - - - -

32 1175919 - - - - - - - - - - - - 1 1

32 1173651 - - - - - - - - 1 1 - - - -

32 1173664 - - - - - - - - - - 1 1 - -

33 LUG GROUND 1172300 1 1 1 1 1 1 1 1 1 1 1 1 1 134 HARNESS WIRE ASSY 1172736 1 1 1 1 1 1 1 1 1 1 1 1 1 135 HEATER CRANKCASE 1173944 - - - - - - - - - - - - 1 136 SWITCH TEMP CC HTR 1173669 - - - - - - - - - - - - 1 1)( CAP SERVICE KIT 11/16-20 1175650 1 1 1 1 1 1 1 1 - - - - 1 1)( CAP SERVICE KIT 15/16-20 1175651 1 1 1 1 1 1 1 1 - - - - - -)( CAP SERVICE KIT 1-1/16-20 1175652 - - - - - - - - - - - - 1 1A PANEL TOP 1176497 1 1 1 1 1 1 - - - - - - - -A 1176407 - - - - - - 1 1 - - - - - -A 1176412 - - - - - - - - - - - - 1 1A 1174075 - - - - - - - - 1 1 - - - -A 1174079 - - - - - - - - - - 1 1 - -B NUT HEX 1172740 4 4 4 4 4 4 4 4 4 4 4 4 4 4C GRILLE INLET 1172745 - - - - - - - - 1 - - - - -C 1172751 - - - - - - - - - 1 - - - -C 1173674 - - - - - - - - - - 1 - - -C 1173675 - - - - - - - - - - - 1 - -C 1176509 1 - 1 - - - - - - - - - - -C 1176542 - 1 - 1 - - - - - - - - - -C 1176499 - - - - 1 - - - - - - - - -C 1176543 - - - - - 1 - - - - - - - -C 1176515 - - - - - - 1 - - - - - - -C 1176544 - - - - - - - 1 - - - - - -C 1176507 - - - - - - - - - - - - 1 -C 1176545 - - - - - - - - - - - - - 1D BOX CONTROL 1172753 1 1 1 1 1 1 1 1 1 1 1 1 1 1E COVER CONTROL BOX 1176491 1 1 - - - - - - - - - - - -E 1176492 - - 1 1 - - - - - - - - - -E 1175004 - - - - 1 1 - - - - - - - -E 1176493 - - - - - - 1 1 - - - - - -E 1175005 - - - - - - - - - - - - 1 1E 1174065 - - - - - - - - 1 1 1 1 - -F PANEL SERVICE 1172755 1 1 1 1 - - 1 1 - - - - - -

- continued on next page -

Page 26: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

26 421 04 5001 00

N2A3 PARTS LIST (continued)

KEYNO. N

2A36

0GK

B20

0

N2A

360A

KB

200

N2A

348A

KA

200

N2A

348A

KA

200

N2A

342G

KA

100

N2A

342A

KA

100

N2A

336G

KB

200

N2A

336A

KB

200

N2A

330G

KB

200

N2A

330A

KB

200

N2A

324G

KB

200

N2A

324A

KB

200

N2A

318G

KB

200

N2A

318A

KB

200

PART NO.DESCRIPTIONF 1174066 - - - - 1 1 - - - - - - - -F 1174077 - - - - - - - - 1 1 - - 1 1F 1174780 - - - - - - - - - - 1 1 - -G PAN BASE 1176496 1 1 1 1 1 1 - - - - - - - -G 1176406 - - - - - - 1 1 - - - - - -G 1176411 - - - - - - - - - - - - 1 1G 1174076 - - - - - - - - 1 1 - - - -G 1174081 - - - - - - - - - - 1 1 - -L GUARD FAN 1176498 1 1 1 1 1 1 - - - - - - - -L 1172764 - - - - - - 1 1 1 1 - - - -L 1172765 - - - - - - - - - - 1 1 1 1N SUPPORT COIL 1174068 3 3 3 3 3 3 5 5 5 5 5 5 5 5P STRAP CAPACITOR 1172734 1 1 1 1 1 1 1 1 - - - - - -P 1172735 - - - - - - - - 1 1 1 1 1 1)( PAINT 1174415 1 1 1 1 1 1 1 1 1 1 1 1 1 1)( SCREW HEX HEAD #10 X 1/2” 1174677 12 12 12 12 12 12 12 12 12 12 12 12 12 12

)( SCREW HEX HEAD #10 X 3/8” 1174676 14 14 14 14 14 14 14 14 14 14 14 14 14 14

)( SCREW HEX HEAD #10 X 5/8” 1174678 4 4 4 4 4 4 4 4 4 4 4 4 4 4)( Manual, Installation 42101500101 1 1 1 1 1 1 1 1 1 1 1 1 1 1)( Manual, Owners 42102500000 1 1 1 1 1 1 1 1 1 1 1 1 1 1)( Warranty 40106401003 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Page 27: TECHNICAL SUPPORT MANUAL Split System Air Conditioner N2A3 - Alpine Home … Series... · 2016. 8. 11. · TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3 2 421 04 5001

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: N2A3

421 04 5001 00 27

OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE (single phase)Digit Position: 1 2 3 4 5, 6 7 8 9 10 11 12

Example Part Number: N 2 A 3 18 A K B 2 0 0Product Family

2 = R-224 = R-410A REFRIGERANTA = Air ConditionerH = Heat Pump TYPE3 = 13 SEER4 = 14 SEER5 = 15 SEER6 = 16 SEER7 = 17 SEER8 = 18 SEER NOMINAL EFFICIENCY18 = 18,000 BTUH = 1½ tons24 = 24,000 BTUH = 2 tons30 = 30,000 BTUH = 2½ tons36 = 36,000 BTUH = 3 tons42 = 42,000 BTUH = 3½ tons48 = 48,000 BTUH = 4 tons60 = 60,000 BTUH = 5 tons NOMINAL CAPACITYA = Standard GrilleG = Coil Guard GrilleC = Coastal FEATURES

K = 208/230-1-60 VOLTAGE

Sales Code

Engineering Revision

Extra Digit

Extra Digit

ACCESSORIES PART NUMBER IDENTIFICATION GUIDEDigit Position: 1 2 3 4 5 6, 7 8, 9 10, 11

Example Part Number: N A S A 0 0 1 01 C H

N = Non-Branded BRANDING

A = Accessory PRODUCT GROUP

S = Split System (AC & HP) KIT USAGEA = OriginalB = 2nd Generation MAJOR SERIES0 = Generic or Not Applicable

2 = R-22

4 = R-410A REFRIGERANTProduct Identifier Number

Package Quantity

Type of Kit(Example: CH = Crankcase Heater)

International Comfort Products, LLC

Lewisburg, Tennessee 37091