5
TECHNICAL SPECIFICATIONS Image for guidance purposes. Model: VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE Amperes in the different voltages: STAND-BY POWER: (LTP “Limited Time Power” norma ISO 8528-1) CONTINUOUS POWER: (PRP “Prime Power” norma ISO 8528-1) ENGINE ALTERNATOR MAKE MODEL MODEL These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract. VOLVO TAD 732 GE ECO 38-1SN 180 kVA 200 kVA 415/240 50 3 0,8 180/144 198/158 275,79 400/230 50 3 0,8 180/144 198/158 286,13 380/220 50 3 0,8 180/144 198/158 301,19 240/139 50 3 0,8 180/144 198/158 476,88 230/133 50 3 0,8 180/144 198/158 497,61 220/127 50 3 0,8 180/144 198/158 520,23 IVV180S - VOLVO - TAD 732 GE IVV180S Generator set with manual or automatic control panel.

TECHNICAL SPECIFICATIONS - Generator · 2017. 4. 20. · VOLVO TAD 732 GE ECO 38-1SN 180 kVA 200 kVA 415/240 50 3 0,8 180/144 198/158 275,79 400/230 50 3 0,8 180/144 198/158 286,13

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TECHNICAL SPECIFICATIONS - Generator · 2017. 4. 20. · VOLVO TAD 732 GE ECO 38-1SN 180 kVA 200 kVA 415/240 50 3 0,8 180/144 198/158 275,79 400/230 50 3 0,8 180/144 198/158 286,13

TECHNICAL SPECIFICATIONS

Image for guidance purposes.

Model:

VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE

Amperes in the different voltages:

STAND-BY POWER:(LTP “Limited Time Power” norma ISO 8528-1)

CONTINUOUS POWER:(PRP “Prime Power” norma ISO 8528-1)

ENGINE

ALTERNATOR

MAKE MODEL

MODEL

These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.

VOLVO TAD 732 GE

ECO 38-1SN

180 kVA

200 kVA

415/240 50 3 0,8 180/144 198/158 275,79

400/230 50 3 0,8 180/144 198/158 286,13

380/220 50 3 0,8 180/144 198/158 301,19

240/139 50 3 0,8 180/144 198/158 476,88

230/133 50 3 0,8 180/144 198/158 497,61

220/127 50 3 0,8 180/144 198/158 520,23

IVV180S - VOLVO - TAD 732 GE

IVV180SGenerator set with manualor automatic control panel.

Page 2: TECHNICAL SPECIFICATIONS - Generator · 2017. 4. 20. · VOLVO TAD 732 GE ECO 38-1SN 180 kVA 200 kVA 415/240 50 3 0,8 180/144 198/158 275,79 400/230 50 3 0,8 180/144 198/158 286,13

INMESOL, S.L.

Power PRP (kWm)

Power LTP (kWm)

No. cylinders

Cylinder capacity (L)

Diameter per stroke (mm)

Compression ratio

Cooling system

Injection

Suction

Series regulator

Steering wheel coupling

Oil capacity (L)

Oil consumption (%)

Min. alarm oil pressure (bar)

Aircoolingflow(m3/h)

Combustionairflow(m3/h)

Max. back pressure for fan (mbar)

Exhaustgasflow(m3/h)

Exhaust back pressure (mbar)

Temp. exhaust gases (ºC))

VDC (V)

Battery (Ah)

Engine start-up (kW)

Lubrication system

Ventilation system

Exhaust system

Electrical system

GENERAL DATA

ENGINE CHARACTERISTICS

MAKE MODEL

These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.

VOLVO TAD 732 GE

160

179

6

7.15

108 x 130

18

LIQUID

DIRECT

-

ELECTRONIC

2

34

0.35

2

14040

684

0

1914

50

529

24

120

5.50

IVV180S - VOLVO - TAD 732 GE

Page 3: TECHNICAL SPECIFICATIONS - Generator · 2017. 4. 20. · VOLVO TAD 732 GE ECO 38-1SN 180 kVA 200 kVA 415/240 50 3 0,8 180/144 198/158 275,79 400/230 50 3 0,8 180/144 198/158 286,13

INMESOL, S.L.

GENERAL DATA

ALTERNATOR CHARACTERISTICS

MODEL

%POWERUSED LITRES/HOUR

DIMENSIONS, CAPACITIES AND APPROXIMATE WEIGHT

GENERATOR SET CONSUMPTION

FUEL TANK (LITRES)

WEIGHT(KG)

DIMENSIONS (MM) LENGTH WIDTH HEIGHT

Power PRP (kVA)

Power LTP (kVA)

EfficiencyAlt.3/4%

EfficiencyAlt.4/4%

No. Poles

Voltage regulator

No. wires

Insulation

Xd (%)

X’d (%)

X

Degree of protection

These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.

ECO 38-1SN

180

198

92.60

92.40

4

DSR

12

H

197

9.70

5.50

IP21

50%

75%

100%

21

31

41

3600 1350 2040

360.00

2800.00

IVV180S - VOLVO - TAD 732 GE

Page 4: TECHNICAL SPECIFICATIONS - Generator · 2017. 4. 20. · VOLVO TAD 732 GE ECO 38-1SN 180 kVA 200 kVA 415/240 50 3 0,8 180/144 198/158 275,79 400/230 50 3 0,8 180/144 198/158 286,13

INMESOL, S.L.

GENERAL DESCRIPTION

The “INMESOL” generator set is an electrical energy generating machine which is used in places where there is no mains supply or when there is a MAINS failure.

The mobile elements, distribution belt, fan, etc., and those parts which reach high temperatures during operation, exhaust manifold, etc, include their corresponding protections, in compliance with the requirements of the Machinery Directive 2006/42.

REGULATIONS

The machine holds the “CE” marking, and the corresponding Declaration of Conformity isissuedwitheachofthem,inwhichitspecifiesthatthemachinecomplieswithR.D 842/2002 Low Voltage Regulations and with the European Directives:

2006/42onSafetyinMachinery. ▪

2006/95/CEonElectricalSafety. ▪

2004/108/CEonElectromagneticCompatibility. ▪

2005/88/CE on NOISE EMISSIONS by equipment for outdoor use (for ▪SOUNDPROOF GENERATOR SETS).

INMESOL GENERATOR SET

These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.

IVV180S - VOLVO - TAD 732 GE

Page 5: TECHNICAL SPECIFICATIONS - Generator · 2017. 4. 20. · VOLVO TAD 732 GE ECO 38-1SN 180 kVA 200 kVA 415/240 50 3 0,8 180/144 198/158 275,79 400/230 50 3 0,8 180/144 198/158 286,13

DSE 6020 AUTOMATIC CONTROL PANEL

PROTECTION, DISTRIBUTION AND AUTOMATIC CONTROL panel which starts the generator set when it detects a mains failure and stops it when the mains is restored with the control unit DSE 6020. It also starts and stops the group manually via a pushbutton or remote start-up by contact

DSE 6020 AUTOMATIC CONTROL PANEL

These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.

Image for guidance purposes.

CONTACT US FOR DETAILED DATA SHEETS AND OTHER CONTROL PANEL OPTIONS

SOUNDPROOFED GENERATOR SETS