Technical Parameters

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

5

42

400

800

8

100

3

C

35

75%

8500

1500

Class A

TUV CE

400

800

8

400

3

D

50

75%

4000

1000

Class A

TUV CE

400

800

8

800

3

D

50

75%

2500

500

Class A

TUV CE

SE Electronic Molded Case Circuit Breaker

Technical Parameters

400

800

8

250

3

C

35

75%

7000

1000

Class A

TUV CE

400

800

8

630

3

D

50

75%

2500

500

Class A

TUV CE

Rated voltage Ue (V)

Rated insulation voltage Ui (V)

Rated impulse withstand voltageUimp (KV)

Rated current In (A)

Number of poles

Rated ultimate short circuit

breaking capacity Icu kA

Rated operating short circuit

breaking capacity Ics kA

Mechanical life

Electrical life

Tripping ways

Installation mode

Product accessories

Use class

50HZ AC 400V

50HZ AC 400V

Mechanical without maintenance

AC 400V

Electronic tripping

Fixed front connection

Fixed rear connection

Undervoltage release

Shunt release

Alarm contact

Auxiliary contacts

Extension terminal

AC Motor

Round extended handle

Square extended handle

Phase partition

SE-100 SE-400 SE-800SE-250 SE-630

: Available(*)

MCcB

FUNCTIONS AND FEATURES

43

SE Electronic Molded Case Circuit Breaker

Trip unit function

SE Electronic Molded Case Circuit Breaker

Intelligent controller funtion

MCcB

FUNCTIONS AND FEATURES

» Flexible setting: offer three section protection function, including long delay, short-time delay, instantaneous

protection, realize the action currents and action time adjustable, the user can set the trip module according

to the load current requirements

» Design patent: current transformer design, it can judge effectively even the current reaches a high value

» Instantaneous trip design: trip the large short circuit current, and also improve the action reliability

» Load monitoring: electronic tripping device configured load indicator lamp, can indicate the actual load

status during operation accurately

» Fault indication: when the hardware of electronic trip fault, the indication light; during the normal operation,

the indicator will flicker as a frequency of 50Hz, every 0.5 seconds for 1 bright

Isolation Function

SE series product has isloation protection function. The operation handle can indicate “OFF”

position only when the contact is really opened.

Tripping Current(A) Ir=In x

Delay time (S) Tr

Tripping Current(A) Isd=Ir x

Delay time Tsd

Tripping Current(A) Ii=In x

Rated Current (A) In Frame 100/250 Frame 400/630/800

Overload Protection (long delay)

Short-Circuit Protection (short delay)

Short-Circuit Protection (instantaneous)

0.4/0.5/0.6/0.7/0.8/0.9/0.95/1

0.5/1/2/4+OFF

0.4/0.5/0.6/0.7/0.75/0.8/0.85/0.9/0.95/1

0.5/1/2/4/8/12/16+OFF

2/2.5/3/3.5/4/5/6/7/8/10

0.1/0.2/0.3/0.4+0/0.1/0.2/0.3/0.4+OFF

2/2.5/3/3.5/4/5/6/7/8/10

0.1/0.2/0.3/0.4+0/0.1/0.2/0.3/0.4+OFF

2/4/6/8/10In+OFF 2/4/6/8/10/12In+OFF

44

SE Electronic Molded Case Circuit Breaker

List of accessories

MCcB

ACCESSORIES

Extension terminal

Interphase barriers

Electric motor

Round handle

Square handle

Shunt release

Under voltage release

Leakage alarm contact

Fixed Rear Connection

Alarm contact

Auxilary contact

7

8

9

10

11

1

2

3

4

5

6

1

8

2

9

6

45

6

3

10

11

7

45

SE Electronic Molded Case Circuit Breaker

Electrical Accessories

MCcB

ACCESSORIES

Auxiliary contact and alarm contact

Auxiliary contact:

An accessory connected in the auxiliary circuit of the switching device to indicate the circuit

breaker status of ON or OFF or Trip.

Alarm contact:

An accessory used to indicate the circuit breaker status of ON or OFF or Trip. When the alarm

contact indicates that the circuit breaker is at Trip status, there are the following five possibilities:

» Overload or short circuit fault

» Residual current fault

» Manual test button trip

» Shunt release action

» Line fault and undervoltage release action

Electrical wiring diagram

Electrical parameters of auxiliary alarm contact

Conventional Thermal Current

Thermal Current Use class (IEC/EN 60947-2)

Working electricity 50Hz / AC 400V

electricty 50HZ / DC 220V

Circuit Breaker

3A

AC 15 / DC 13

0.3A

0.15

ON OFF/Trip

F12

F14

B12

B14

F11

B11 B14 B11

F11F12

F14Auxiliary

Alarm

46

SE Electronic Molded Case Circuit Breaker

Electrical Accessories

MCcB

ACCESSORIES

Shunt release

Electric Motor

» The shunt release shall reliably trip the circuit breaker at the voltage between 70% and 110% of the rated

control power voltage U

» The circuit breaker shall be reset on the spot after tripping through the shunt release.

» Provide on-site and remote distance control circuit breaker to implement switch-on and switch-off

Undervoltage release

» The undervoltage release shall reliably trip the circuit breaker at the voltage between 35% and 70% of

the rated operational voltage

» The undervoltage release shall ensure that the circuit breaker can be switched on at the voltage between

85% and 110% of the rated operational voltage

» The undervoltage release shall prevent the circuit breaker from switching on when voltage is below 35%

of the rated operational voltage

Ue

Undervoltage Release Wiring

47

SE Electronic Molded Case Circuit Breaker

Mechanical Accessories

MCcB

ACCESSORIES

Interphase barriers

The interphase barriers can enhance the insulating performances of the conductors between the phases.

They can be installed from the front slot even after the switch is installed.

Standard offer 2pcs (3P)

Extension terminals

Easy to install and connect the products in the Rear Connection

Handle operating mechanism

Extended Rotary Handle

» Function: indication of the three positions of switch-on, switch-off and trip

» Residual earth-leakage fault. The circuit breaker cannot switch-on when the switch board door is open

» The door cannot be opened if the circuit breaker is ON

» An extension shaft that can be adjusted to the distance between the back of circuit breaker and door, the

specific distance refers to the dimensions at the rear and the installation part

» The OFF-Position of the circuit breaker can hang 1-3 locks with the diameter of 5mm

48

SE Electronic Molded Case Circuit Breaker

100/250AF Installation Dimension

165

35

107

114.5

89.585.5

48.5

23.5

M8*16

65

47 35.5

127

97112

400AF Installation Dimension

257

54.5

44

140

54.5

M10*45

146114100

97.538.5

105

4326

.521

5MCcB

INSTALLATION DIMENSIONS

Chart of fixed front connectioninstallation hole

Installation dimension of fixed front connection

Chart of fixed front connectioninstallation hole

Remark: X-X, Y-Y is the center of 3-pole circuit breaker

Remark: X-X, Y-Y is the center of 3-pole circuit breaker

49

SE Electronic Molded Case Circuit Breaker

630/800AF Installation Dimension

280

104.

570

.5

70

M12*40

35.5

97.5100114

146

70 70210

55.5

243

Safety Distance

MCcB

INSTALLATION DIMENSIONS

Remark: no matter whether the products have the accessories, the distance between the products must meet the requirements of C distance.

Remark: X-X, Y-Y is the center of 3-pole circuit breaker

Circuit Breaker

SE-100

SE-250

SE-400

SE-630

SE-800

A

60

60

110

110

110

B

60

60

110

110

110

C

30

30

70

70

70

B1

Legnth of

Exposed

Conductor +B

50

SE Electronic Molded Case Circuit Breaker

Extension Rotary Handle Base Dimension*

MCcB

INSTALLATION DIMENSIONS

Remark: the shortest distance of G connecting rod is 50mm and ex-factory standard configuration is 150mm, please contact the factory if the special customization is required

Round

Square

SE-100/SE-250 SE-400/SE-630/SE-800

Circuit Breaker

SE-100

SE-250

SE-400

SE-630

SE-800

C

35

35

44

70

70

D

71.5

71.5

107.5

121.5

121.5

K

20

20

20

20

20

H

56

56

76

76

76

E

71.5

71.5

107.5

121.5

121.5

51

SE Electronic Molded Case Circuit Breaker

Tripping characteristics

SE-100/SE-250

SE-400

1034 68

In

20 30

I tON2

10.30 .4 0.60 .8 1024 68 20

IR

0.4s0.3s0.2s0.1s0s

I tOFF2

0.002

0.005

0.02

0.05

100

1000

10000

20

50

1.5

10

5

200

500

2000

5000

t(s)

0.1

1

0.01

0.2

0.5

0.2

I= 100~ 250 0.4~1.0 InR

T= (0.5~4)sR

Isd=(2~10)Ir

Ii=(2~10)ln

1034 68

In

20 30

T= (0.5~16) sR

I tON2

10.30 .4 0.60 .8 1023 46 8 20

IR

0.4s0.3s0.2s0.1s0s

I tOFF2

Ii=(2~12)ln

0.002

0.005

0.02

0.05

100

1000

10000

20

50

1.5

10

5

200

500

2000

5000

t(s)

0.1

1

0.01

0.2

0.5

0.2

Isd=(2~10)Ir

I= 160~400= 0.4~1.0 InR

MCcB

TRIPPING CURVES

52

SE Electronic Molded Case Circuit Breaker

Tripping characteristics

SE-630/SE-800

1034 68

In

20 30

T= (0.5~16) sR

It ON2

10.30 .4 0.60 .8 1023 46 8 20

IR

0.4s0.3s0.2s0.1s0s

It OFF2

Ii=(2~12)l n

0.002

0.005

0.02

0.05

100

1000

10000

20

50

1.5

10

5

200

500

2000

5000

t(s)

0.1

1

0.01

0.2

0.5

0.2

Isd=(2~10)Ir

I= 320~ 800= 0.4R ~1.0 In

SE Molded Case Circuit Breaker

Ordering codes

100 A

250 A

400 A

630 A

800 A

Frame 100A

Frame 250A

Frame 400A

Frame 630A

Frame 800A

SE100C1003FF

SE250C2503FF

-

-

-

-

SE400D4003FF

SE630D6303FF

SE800D8003FF

Ordering CodesRated CurrentFrame35KA 50KA

MCcB

TRIPPING CURVES

SELECTION GUIDE

53

MCcB

SE 800

CERTIFICATIONSSE 100

SE 630

55

54

ACB,,, Framee 2000A,, Fixed ACBBB, FFramee 3200A, Fixed

SA Air Circuit Breaker

400

800

8

1000--2000

3, 4

T

80

50

50

10000

2500

1000

500

SA Air Circuit Breaker

Technical Parameters

400

800

8

2000--3200

3, 4

T

80

80

65

8000

2500

1000

500

Rated voltage Ue (V)

Rated insulation voltage Ui (V)

Rated impulse withstand voltage Uimp (KV)

Rated current In (A)

Number of poles

Rated ultimate short circuit

breaking capacity Icu kA

Rated operating short circuit

breaking capacity Ics kA

Rated Short-Time withstand

current lcw (kA/1s)

Mechanical life

Electrical life

50/60HZ AC 400V

50/60HZ AC 400V

50/60HZ AC 400V

Mechanical with maintenance

Mechanical without maintenance

Electrical with maintenance

Electrical without maintenance

SA-2000 SA-3200

ACB

RANGE OF PRODUCTS

FUNCTIONS AND FEATURES

55

SA Air Circuit Breaker

Function Information

ECW-L

INTELLIGENT CONTROLLER

Protection

Long time delay

Short time delay

Instantaneous

Earthing

Action current IR

Delay time tL

Action current Isd

Delay time ts

Action current Ii

Action current Ig

Action current tG

Protection Characteristics Setting range

Protection Characteristics for Overload Delay

Protection Characteristics for Short-Delay Short Circuit

Protection Characteristics for Instantaneous Short Circuit

Earthing protection

Use

Protect cable, prevent ageing

Protect equipment, prevent impedance short circuit

Protect equipment, prevent metallicity short circuit

(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0) In+OFF

30s, 60s, 120s, 240s

(3, 4, 5, 6, 7, 8, 10) In+OFF

0.2s, 0.4s

(10, 11, 12, 14, 16, 18, 20) In+OFF (Frame 2000A)

(7, 8, 9, 10, 11, 12, 14) In+OFF (Frame 3200A)

(0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8) In+OFF

0.1s, 0.2s, 0.3s, 0.4s

L

S

I

G

ACB

56

SA Air Circuit Breaker

Function Information

ECW-M

INTELLIGENT CONTROLLER

Protection

Long time delay

Short time delay

Instantaneous

Earthing

Fault current Delay time

tR 15 30 60 120 240 480

1.5xIR 15 30 60 120 240 480

2xIR 8.4 16.9 33.8 67.5 135 270

7.2xIR 0.65 1.3 2.6 5.2 10.4 20.8

t=(1.5/N)2xtR

N=Fault current divided by the setting current I/IR

t=Delay Time of Failure ActiontR=Setting Value of Long-Delay Time

Action current IR

Delay time tL

Protection Characteristics

Measure

Miscellaneous function

Setting range

Protection Characteristics for Overload Delay

Use

Protect cable, prevent ageing

Protect equipment, prevent impedance short circuit

Protect equipment, prevent metallicity short circuit

Current measurement

Voltage measurement

Pre-alarm

Self-diagnosis function

Fault log

Test function

(0.4~1.0) In + OFF (>>100A)

L

S

I

G

ACB

57

SA Air Circuit Breaker

Function Information

ECW-M

INTELLIGENT CONTROLLER

Fault current Delay time

ts(s) 60 120 240 480

I2T: OFF Min.delay(ms) 60 120 240 480

Max.delay 33.8 67.5 135 270

I2T: ON Min.delay 2.6 5.2 10.4 20.8

I>8IR Max.delay 140 240 345 460

I2T: ON Inverse time limit delay t=(8IR)2/I2×ts

R

SA-2000 SA-3200

Action current Isd

Action time tS

Action current Ii

Protection Characteristics for Short-Delay Short Circuit

Protection Characteristics for Instantaneous Short Circuit

Inverse time Limit I2T

2.0In~50kA+OFF 2.0In~75kA+OFF

Measure

Action current Ig (0.2~1.0)In+OFF

Action current tG 0.1s, 0.2s, 0.3s, 0.4s, OFF

ACB

58

SA Air Circuit Breaker

Function Information

ECW-H

Protection

Long time delay

Short time delay

Instantaneous

Earthing

Action current IR

Protection curve

Type selection

Setting delay time

Protection Characteristics

Measure

Miscellaneous function

Setting range

Protection Characteristics for Overload long time delay

Use

Protect cable, prevent ageing

Protect equipment, prevent impedance short circuit

Protect equipment, prevent metallicity short circuit

Current measurement

Voltage measurement

Power measurement

Harmonic wave measurement

Pre-alarm

Self-diagnosis function

Communication function

Fault log

Test function

OFF+0.4~1.0In

SI: Standard inverse time limit

VI: Rapid inverse time limit

EI(G): Express inverse time limit (distribution)

EI(M): Express inverse time limit (electromotor)

HV: High-Pressure Welding Fuse Compatibility

I2t: Universal inverse time limit protection

C01~C16

L

S

I

G

INTELLIGENT CONTROLLERACB

59

SA Air Circuit Breaker

Function Information

ECW-H

SA-2000 SA-3200

Action Current of Inverse Time Limit Is

Action Current of Fixed Time Limit Isd

Delay Time of Fixed Time Limit tsd

Action current Ii

Protection Characteristics for Short Delay

Instantaneous protection Characteristics

OFF+(0.4~15)In

OFF+(0.4~15)In

(0.1~0.4s)

2.0In~50kA+OFF 2.0In~75kA+OFF

Earthing protection Characteristics

Action current Ig (0.2~1.0)In+OFF

Inverse time limit 1.5~6, +OFF

Delay time tg (0.1~0.4)s

INTELLIGENT CONTROLLER ACB

60

SA Air Circuit Breaker

List of accessories

ACB

ACCESSORIES

Veil

Door frame

Key lock

Power supply module

Relay module

DC power supply module

N-phased transformer

Cable mechanical interlock

Mechanical interlock rod

Phase barrier

Undervoltage delayrelease

Auxiliary contact

Motor mechanism

Undervoltage release

Shunt close release

Shunt open release

6

7

8

9

10

11

12

13

14

15

16

1

2

3

4

5

1

12

13

14

15

16

11

9

10

2

4

5

6

7

8

3

61

SA Air Circuit Breaker

List of accessories

ACB

ACCESSORIES

Shunt open release

When the breaker is stored, under prescriptive voltage, through long-distance remote

control operation, let the breaker break

Shunt close release

When the breaker is stored, under prescriptive voltage, through long-distance remote

control operation, let the breaker close

Undervoltage release and undervoltage delay release

The undervoltage release automatically opens a circuit breaker when voltage drops

to a value ranging between 35% to 70% of the line voltage. after tripping,the

circuit breaker cannot be re-closed again when the voltage lowers than 35% or until

returns to 85% of line voltage. Undervoltage relay release lets the breaker break in

1s-5s(adjustable)

Accessory parameter

Rated operational voltage V 230VAC 400VAC 220VDC

Operation voltage (0.7-1.1)Us

Consumption 300VA(AC) 40W(DC)

Breaking time <30ms

Accessory parameter

Rated operational voltage V 230VAC 400VAC 220VDC

Operation voltage (0.85-1.1)Us

Consumption 300VA(AC) 40W(DC)

Breaking time <70ms

Accessory parameter

Rated operational voltage V 230VAC 400VAC 220VDC

Operation voltage (0.7-1.1)Us

Consumption 300VA(AC) 40W(DC)

Breaking time <30ms

62

SA Air Circuit Breaker

List of accessories

Motor mechanism

When the breaker is under breaking and power supply, motor mechanism is automatic

stored. So under shunt release, undervoltage and closing release, let the breaker break

and close

Auxiliary contact

It is used for keeping watch on the breaker’s status, connecting position signal light

and breaking indicator light

Accessory parameter

Rated control voltage V 230VAC 400VAC 220VDC

Action voltage (0.85-1.1)Us

Consumption 192VA(AC) 192W(DC)

Energy storage time <5s

Accessory parameter

Utilization category AC-15 DC13

Auxiliary contact default type 5NO 5NC (4NO 4NC for 1000AF)

Conventional thermal current Ith 6A

Auxiliary contact’s energized Equal to circuit breaker operation

operational performance performance

Making & Under I/Ie making 10 1

breaking normal I/Ie breaking 1 1

capacity conditions U/Ue 1 1

cosø or T0.95 0.3 6Pe*

Under U/Ue 10 1.1

abnormal I/Ie 1 1.1

conditions cosø or T0.95 1 1

Operation cycles 10 10

ACB

ACCESSORIES

63

SA Air Circuit Breaker

List of accessories

Keylock

When the breaker is breaking, it could be lock in.

It is divided into three types: one lock and one key, two locks and one key, three

locks and two keys

Cable Mechanical Interlock

It could connect two or three breakers to be linkage.

*Note: The Max Horizonal installation distance is 2M.

Mechanical interlock rod

It could connect two breakers to be linkage,one of the breakers is closing,

the other is breaking

*Note: Only for Vertical intallation, and the Max installation distance is 0.9M

Phase Barrier

Install in the middle of the breaker busbar, increase creepage distance, prevent to

engender electric arc

ACB

ACCESSORIES

64

SA Air Circuit Breaker

L - Type and M - Type intelligent controller

WIRING DIAGRAM

Maincurrent

UV SO SC

Auxiliarycontact

Undervoltage Shuntopen

Energystorage

Shuntclose

Energy stored

indicationMotor Auxiliary contactIntelligent controller

Pin function:» #1 and #2: auxiliary supply input terminal (#1 for positive terminal when being DC)» #3, #4 and #5: contact output of tripping fault (#4 refers to shared terminal); contact capacity: 16A @380VAC» #6, #7, #8 and #9: two groups of auxiliary terminals with circuit breaker status;contact capacity: 16A @380VAC» #20 PE wire, protection earthing wire» #25, #26: output for circumscribed transformer

Remarks» #27 and #28 of undervoltage release UV connect to main circuit.» UV, SO, SC and Motor can be connected with different control voltage, Auxiliary contact is 5a5b, Shunt

open and close have been tandem connected with NO & NC auxiliary contact in the factory.» #35 can be connected to the power supply directly (automatic pre-storing energy), also to the power

supply after adopting tandem connection with normal open button (manual pre-storing energy).» #6 & #7 can output normal close contacts, if the users put forward.» Power module 1 is DC Power module, and there is no such module when the power AC power supply. The

input & output terminals cannot be connected reversely.» The auxiliary contact is 5 open and 5 close, #25 & #26 are circumscribed transformer, applied for (3P+N)

T type earthing failure protection.

Components:UV: undervoltage, SO: Shunt open, SC: Shunt closes, AUX: auxiliary contact, M: Motor, SB1: Make button, SB2: Shunt button

ACB

65

SA Air Circuit Breaker

2000AF Overall dimensions

INSTALLATION DIMENSIONS ACB

66

SA Air Circuit Breaker

3200AF Overall dimensions

INSTALLATION DIMENSIONSACB

S Molded Case Circuit Breaker

Ordering codes

1000 A

1250 A

1600 A

2000 A

Frame 2000 SA02KT10K3FH

SA02KT12K3FH

SA02KT16K3FH

SA02KT02K3FH

Ordering CodesRated CurrentFrame Icu

80 KA

80 KA

80 KA

80 KA

Frame 3200 2000 A

2250 A

3200 A

SA32KT02K3FH

SA32KT25K3FH

SA32KT32K3FH

80 KA

80 KA

80 KA

SELECTION GUIDE

67

ACB

68

ACB SA

CERTIFICATIONSACB

69

SC 9A~95A Contactor

IEC 60947-4-1

With the new generation of technical platform and automated production and testing equipment, the brand new SC9~95

convenient use and international leading quality. The series include three major categories, namely SC9~95 contactor, SO-93 thermal overload relay and their accessories.

Installation position:

• Pollution class: Class 3

Ambient temperature:

• In normal operation, the ambient temperature ranges between -5 ºC and +40 ºC

Altitude:

• Altitude at normal installation position does not exceed 2000m

Humidity:

Product protection grade: IP20

Contactors

PRODUCT DETAILS

NORMAL INSTTTALLAATION ANDD OPERATION CONDITIONS

SC contactor: 9-95A

SO thermal overload relay

SCHPCs transparent dust cover, AXF top auxiliary contact, AXS side

auxiliary contact, TD6 air delayed head and L4 mechanical in

CB,CE, SEMKO

independent mounting base CB,CE, SEMKO

70

SC 9A-95A Contactor

Main Technical Parameters of SC

FUNCTIONS AND FEATURES

Contactors

Contactor Model

Main Circuit Characteristics

Rated Insulation Voltage (Ui)

Coil

Main circuit terminal wiring capability

Certificates CB, CE, SEMKO

Rated Operational Voltage (Ue)

Conventional Thermal Current

ConventionalOperationalCurrent (Ie)

ConventionalOperatingPower (Pe)

Mechanical Durabilities

ElectricalDurabilities

Rated controlcircuit voltage (Us)

Flexible wire

without terminal

Coil Power

OperationFrequency

Allowable Control circuit voltage (Us)

Flexible wire

with terminal

Fixed wire

without terminal

Number of Poles

SC95

110

95

49.0

44.0

21.3

45.0

45.0

22.0

18.5

SC80

110

80

49.0

37.0

17.3

37.0

45.0

18.5

15.0

SC65

80

65

42.0

28.0

14.0

30.0

37.0

15.0

11.0

SC50

60

50

39.0

24.0

12.0

22.0

33.0

11.0

11.0

SC40

50

40

34.0

18.5

9.0

18.5

30.0

7.5

7.5

SC38

40

38

22.0

14.0

8.9

18.5

18.5

7.5

7.5

SC32

40

32

22.0

12.0

7.5

15.0

18.5

7.5

5.5

SC25

32

25

18.0

8.5

4.4

11.0

15.0

5.5

4.0

SC18

25

18

12.0

7.7

3.8

7.5

10.0

4.0

3.7

SC12

20

12

8.9

5.0

2.0

5.5

7.5

3.0

1.5

SC09

20

9

6.6

3.5

1.5

4.0

5.5

2.2

1.1

V

V

A

A

A

A

KW

KW

KW

KW

10,000 times

10,000 times

10,000 times

Time/Hour

Time/Hour

V

V

V

V

VA

VA

W

mm

mm

mm

mm

mm

mm

AC-3, 380/400V

AC-3, 660/690V

AC-4, 380/400V

AC-4, 660/690V

AC-3, 380/400V

AC-3, 660/690V

AC-4, 380/400V

AC-4, 660/690V

AC-3

AC-4

AC-3

AC-4

50 Hz

50/60 Hz

Operation

Drop out

Inrush

Sealed

Heat Dissipation

1 Wire

2 Wire

1 Wire

2 Wire

1 Wire

2 Wire

600

300

1200

24, 36, 48, 110, 127, 220/230, 240, 380/400, 415, 440

85% ~ 110% Us

24, 36, 48, 110, 127, 220/230, 240, 380/400, 415, 440

20% ~ 75% Us

1000

90 65

1122

900

17

650

110

22

1200

300

60

6~9.5

1~3

1...4

1...4

1...4

1...2.5

70

6~9.5

1~3

1.5...6

1.5...6

1...6

1...4

200

15~20

6~10

2.5...25

2.5...16

2.5...25

2.5...10

2.5...25

2.5...10

4...50

4...25

4...50

4...16

4...50

4...25

1.5...10

1.5...6

1.5...6

1.5...6

1...4

1...4

3

690

690

71

Wiring Diagram

SC09 ~SC95

SC40 ~ SC95

Wiring digram for star-delta starter

SC09 ~ SC38

FUNCTIONS AND FEATURES

Contactors

72

SC Schematic diagram of accessories

SC09~SC38

FUNCTIONS AND FEATURES

Contactors

73

SC Contactors

Ratings & References

SELECTION GUIDE

Contactors

9 A

12 A

18 A

25A

32 A

38 A

40 A

50 A

65 A

80 A

95 A

4 KW

5.5 KW

7.5 KW

11 KW

15 KW

18.5 KW

18.5 KW

22 KW

30 KW

37 KW

45 KW

1

0

1

0

1

0

1

0

1

0

1

1

1

1

1

1

0

1

0

1

0

1

0

1

0

1

0

1

1

1

1

1

SC009M5310

SC009M5301

SC012M5310

SC012M5301

SC018M5310

SC018M5301

SC025M5310

SC025M5301

SC032M5310

SC032M5301

SC038M5310

SC040M5311

SC050M5311

SC065M5311

SC080M5311

SC095M5311

Ordering Codes

Auxiliary Contacts

Rated Current

Rated Current

Auxiliary Contacts

Coil Voltage Coil Frequency Poles

Motor Power Pe

Product Name

KW, AC-3, 380V

SC

Ie (A)

09

09 : 09 A...

95 : 95 A

NO

M

B : 24 V...

M : 220V/230V...

Q : 380V/400V

NC

5

5 : 50 Hz...

7: 50/60 Hz

3

3

Note: Only 3 Poles are available

10

10 : 1NO+0NC01 : 0NO+1NC11 : 1NO+1NC

74

INSTALLATION DIMENSION

Contactors

Amax

a

B2max

d

Bmax

b

Cmax

e

B1max

c

C1max

f

C2maxModel

Model

SC 09, 12, 18SC 25, 32, 38SC 40, 50, 65SC 80, 95

SC 09, 12, 18SC 25, 32, 38SC 40, 50, 65SC 80, 95

74.583

127.5127.5

3540--

7182

101112

--

4040

45.556.574.585.5

50/6050/60

--

82.597

117125.5

--

100/110100/110

58698899

--

105105

114.5129

148.5157

--

5967

139.5154

173.5182

75

SC 115A~630A Contactor

Main Technical Parameters of SC

FUNCTIONS AND FEATURES

Contactors

Contactor Model

Main Circuit Characteristics

Rated Insulation Voltage (Ui)

Coil

Main circuit terminal wiring capability

Certificates CB, CE, SEMKO

Rated Operational Voltage (Ue)

ConventionalOperationalCurrent (Ie)

ConventionalOperatingPower (Pe)

Mechanical Durabilities

Electrical Durabilities

Rated controlcircuit voltage (Us)

Flexible wire

without terminal

Coil Power

Operation Frequency

Allowable Control circuit voltage (Us)

Copper Bar

Number of Poles 3

SC630

360

188

800

200

335

375

450

600

80

300

1650

22

20

-

-

60*5

SC500

500

147

630

147

250

280

335

600

80

300

1250

24

18

-

240

40*5

SC400

400

138

500

110

200

220

280

600

80

300

1200

20

14

-

150

30*5

SC330

330

117

400

100

160

180

220

600

80

600

240

-

30*5

SC265

265

105

350

75

132

140

160

600

80

600

1200

13

12

240

-

32*3

SC225

225

85

315

63

110

110

129

600

100

600

185

-

32*4

SC185

185

79

275

55

90

100

110

600

100

600

800

55

24

150

-

25*3

SC150

150

60

250

40

75

80

100

1000

120

600

120

-

25*3

SC115

115

52

200

30

55

59

80

1000

120

600

550

45

16

95

-

20*3

V

V

A

A

A

KW

KW

KW

KW

10,000 times

10,000 times

Time/Hour

VA

VA

W

mm

mm

mm

AC-3, 380/400V

AC-4, 380/400V

AC-1, 380/400V

AC-3, 220/240V

AC-3, 380/400V

AC-4, 415/440V

AC-4, 660/690V

50 Hz

50/60 Hz

Operation

Drop out

Inrush

Sealed

Heat Dissipation

1 pc section

2 pc section

2 pc section

110V, 127V, 220V, 230V, 240V, 380V, 400V, 440V

110V, 220V, 380V (115-225 AF)

85%~110% Us

20%~75% Us

1000

690

76

SC 115A~630A Contactor

Wiring Diagram for Star-Delta Starter

WIRING DIAGRAM

Contactors

77

SC Schematic diagram of accessories

SC 115A-630A Contactor

FUNCTIONS AND FEATURES

Contactors

78

SC accessories

SC 115A-630A Contactor

TD6 Air Delayed Head

Auxiliary Contact

FUNCTIONS AND FEATURES

Contactors

0

1

2

0

1

2

3

4

0

1

2

2

4

2

Top

Side

2

1

0

4

3

2

1

0

2

1

0

AXF6 02

AXF6 11

AXF6 20

AXF6 04

AXF6 13

AXF6 22

AXF6 31

AXF6 40

AXF6 02

AXF6 11

AXF6 20

Ordering CodesComposition Contact Point LayoutPolesInstallation Position

NO NC

Making

type delay

Breaking

type delay

Top

0.1-3s

0.1-30s

10-180s

0.1-3s

0.1-30s

10-180s

TD6 20

TD6 22

TD6 24

TD6 30

TD6 32

TD6 34

Ordering CodesDealy Type Delay RangeWiring DiagramInstallation Position

79

SC accessories

SC 115A-630A ContactorMechanical Interlock

* Note: For vertical interlock contact supplier

Mechanical Interlock

Without electrical interlock

SC-115~150

SC-185~225

SC-265~330

SC-400~500

SC-630

L6 FFH

L6 GGH

L6 HHH

L6 KKH

L6 LL H

Ordering CodesInterlock Type Contactor Type

Coils

220V

380V

220V

380V

220V

380V

220V

380V

220V

380V

220V

380V

SC-115~150

SC-185~225

SC-265~330

SC-400

SC-500

SC-630

X6 150 M

X6 150 Q

X6 250 M

X6 250 Q

X6 330 M

X6 330 Q

X6 400 M

X6 400 Q

X6 500 M

X6 500 Q

X6 630 M

X6 630 Q

Ordering CodesCoil VoltageContactor Type

FUNCTIONS AND FEATURES

Contactors

80

SC 115A~630A Contactor

Overall dimensions

Amax PBmax SCmax Ø f M H L X1 X1 Ga HaModel

SC-400SC-500SC-630

213223309

485580

206233304

253040

220233256

M10M10M12

146150181

181208264

158172202

145146155

151520

202030

8080

180

170~180170~180180~190

(200-550V) (200-550V)

SC-115~SC330

SC-400~SC500

SC-630

* Note: 'f' reserved space to ensure draw-out coil can take out easily

Amax PBmax SCmax Ø f M H L X1 X1 Ga HaModel

SC-115SC-150SC-185SC-225SC-265SC-330

167167171171202213

374040484848

163171174197203206

202020252525

172172183183215220

M6M8M8

M10M10M10

131131131131147147

147150154172178181

124124127127147158

107107

113.5113.5141145

101010101010

151515151515

808080809696

110~120110~120110~120110~120110~120110~120

(200-550V) (200-550V)

INSTALLATION DIMENSION

Contactors

81

SO Thermal Overloads Relays

Main technical parameters

Temperature compensation

Trip level 10A

10

Rated insulation voltage (Ui) V

Product features

Overload protection

Phase failure protection

Manual reset

Automatic reset

Stop button

Test button

Trip indication

Tolerance on slope in any direction

Auxiliary circuit

Utilization category

Rated frequency Hz

Rated insulation voltage (Ui) V

Rated operational voltage (Ue) V

Rated operational current (Ie) A

Conventional thermal current (Ith) A NO

NC

Product certification

Base

-5 C ~ +40 C

SO-25, SO-36

SO-93

660V

YES

YES

YES

YES

YES

YES

YES

±5

AC-15 DC-13

50 50

500 500 500

230 230 230

1.57 0.90 0.14

5 5 5

5 5 5

CB, CE, SEMKO

Name Reference

SO-25 SO25J

SO-36 SO36J

SO-93 SO93J

FUNCTIONS AND FEATURES

OVERLOAD RELAY

82

SO Thermal Overloads Relays

Trip Characteristics

Trip Characteristics for current balance

Trip Characteristics for current imbalance

Trip Characteristics for Average Value (Environment temperature 20 C)

Ambient Temp.Tripping Time Initial ConditionMultiples of

Trip class 10ASetting current

Non-tripping within 2hTripping within 2h

1.01.15

Trip class 10

Non-tripping within 2hTripping within 2h

Without previous loadAfter No.1 Test

+20 C

Ambient Temp.Tripping Time Initial ConditionMultiples of

Trip class 10ASetting current

Non-tripping within 2hTripping within 2h<2 min

1.051.21.57.2

Trip class 10

Non-tripping within 2hTripping within 2h<4 min

Without previous loadAfter No.1 TestAfter No.1 Test

Without Previous load

+20 C

+20

FUNCTIONS AND FEATURES

OVERLOAD RELAY

83

SO Thermal Overloads Relays

Installation wiring diagram

Fu-fuse.KM-Contactor.Fr-Thermal overload relay.SB1-Stop button.SB2-Start button.

WIRING DIAGRAM

OVERLOAD RELAY

84

SO Thermal Overloads Relays

Ratings & References

SELECTION GUIDE

OVERLOAD RELAY

0. 1-0.16

0.16-0.25

0.25-0.4

0.4-0.63

0.63-1

1-63-1

1.6-2.5

2.5-4

4-6

5.5-8

7-10

9-13

12-18

17-25

23-32

30-40

23-32

30-40

37-50

48-65

55-70

63-80

80-93

25

36

93

09-38

09-38

09-38

09-38

09-38

09-38

09-38

09-38

09-38

09-38

09-38

12-38

18-38

25-38

25-32

32-38

40-95

40-95

50-95

50-95

65-95

80-95

95

SOD16009T032

SOD25009T032

SO0D4009T032

SOD63009T032

SO001009T032

SO1D6009T032

SO2D5009T032

SO004009T032

SO006009T032

SO008009T032

SO010009T032

SO013012T032

SO018018T032

SO025025T032

SO032025T032

SO040032T032

SO032040T095

SO040040T095

SO050050T095

SO065050T095

SO070065T095

SO080080T095

SO093095T095

Ordering CodesSetting Current Suitable ContactorFrame Rating

(A) (A) SC

85

SO Thermal Overloads Relays

Overall dimensions

SO-25

SO-36

SO-93

INSTALLATION DIMENSION

OVERLOAD RELAY

86

SO Thetrmal Overloads Relays

Ratings & References

SELECTION GUIDE

OVERLOAD RELAY

48-65

55-70

63-80

75-95

90-115

105-135

120-150

130-160

150-185

145-200

180-250

230-320

290-400

350-480

460-630

65

70

80

95

115

135

150

160

185

200

250

320

400

480

630

SC 115~185

SC 115~185

SC 115~185

SC 115~185

SC 115~185

SC 115~185

SC 115~185

SC 115~185

SC 115~185

SC 225~630

SC 225~630

SC 225~630

SC 225~630

SC 225~630

SC 225~630

SO 065115T185

SO 070115T185

SO 080115T185

SO 095115T185

SO 115115T185

SO 135115T185

SO 150115T185

SO 160115T185

SO 185115T185

SO 200115T630

SO 250115T630

SO 320115T630

SO 400115T630

SO 480115T630

SO 630115T630

Ordering CodesSetting Current Suitable ContactorFrame Rating

(A) (A) SC

87

SO Thermal Overloads Relays

Trip Characteristics

Trip Characteristics

Trip Characteristics for Current Imbalance

Ambient Temp.

Ambient Temp.

Tripping Time

Tripping Time

Initial Condition

Initial Condition

Multiples of

Multiples of

Trip class 10A

Trip class 10A

Setting current

Setting current

Non-tripping within 2hTripping within 2h< 2 min

Non-tripping within 2hTripping within 2h

1.051.21.57.2

1.0 0.91.15 0

any 2 phase 3rd phase

Trip class 10

Trip class 10

Non-tripping within 2hTripping within 2h< 4 min

Non-tripping within 2hTripping within 2h

Without previous loadAfter No.1 TestAfter No.1 Test

Without previous load

Without previous loadAfter No.1 Test

+20 C

+20 C

+20 C

Temperature Compensation -10 C~+55 C

Trip Class

Frame Current

Rates impulse withstand voltage (Uimp)

Installation Method

10A10SO185SO630/F

SO 630/FSO18548~185A145~630A6kVOverload ProtectionPhase Failure ProtectionManual and Automatic ResetTripping IndicationStop ButtonTest ButtonAssembly/Independent: SO185Independent: SO630/F

FUNCTIONS AND FEATURES

OVERLOAD RELAY

88

SO Thermal Overloads Relays

Trip Characteristics

Trip Characteristics for Average Value (Environment temperature 20 C)

FUNCTIONS AND FEATURES

OVERLOAD RELAY

89

SO Thermal Overloads Relays

Overall Dimensions

A B CModel

SC-115SC-150SC-185

248253257

167167171

172172183

INSTALLATION DIMENSION

OVERLOAD RELAY

90

SK Capacitor Switching Contactor

Standard: IEC 60947-4-1 IEC 60947-5-1

Function: SK capacitor switching contactor provide:

Switch three-phase unipolar or multipolar capacitor group,to improve their power factor

Reduce the current closing of the impact of capacitor

SELECTION GUIDE

CAPACITOR CONTACTOR

1

2

0

1

2

0

1

2

0

1

2

1

2

25

32

43

63

95

1

0

2

1

0

2

1

0

2

2

1

2

1

SK12M 25300

SK12M 25300

SK12M 25300

SK18M 32300

SK18M 32300

SK18M 32300

SK20M 43300

SK20M 43300

SK20M 43300

SK30M 63300

SK30M 63300

SK45M 95300

SK45M 95300

Ordering CodesAuxiliary ContactRate Conventional Thermal Current

(A) NO NC

91

FUNCTION AND FEATURES

CAPACITOR CONTACTOR

SK Capacitor Contactors

Main technical parameters

Contactor Model

Main Circuit Characteristics

Rated Insulation Voltage (Ui)

Coil

Auxiliary Contact

Rated Operational Voltage (Ue)

Controlled capacitor rate capacity

Rate Conventional thermal currentControl inrush current capacity

Mechanical Life

Electrical Life

Coil Voltage

Operational Voltage

Drop-out Voltage

Rated conventional thermal current

Operation Frequency

Cable connection cross section of copper conductor

Minimum load can be connected

Number of Poles 3

SK45M-95

63

22.5

45

95

100

10

120

4

SK30M-63

43

15

30

63

100

10

300

4

SK20M-43

29

10

20

43

100

10

300

4

SK18M-32

23

9

18

32

100

10

300

4

SK12M-25

17

6

12

25

100

10

300

4

10

6V x 10mA

V

V

A

Kvar

Kvar

A

10,000 times

10,000 times

Operations/h

mm

V

V

V

A

AC-6b, 400V

AC-6b, 230V

AC-6b, 400V

AC-6b, 400V

AC36, 110V, 127V, 220V, 380V, 400V

85%~110% Us

20%~75% Us

500

400

92

CAPACITOR CONTACTOR

Ambient temperature:

• In normal operation, the ambient temperature ranges between -5 ºC and +40 ºC

Altitude: 2000m

Humidity:

WORKING COOONNDIITIONS

• Pollution class: Class 3

• Installation type: III

93

MANUAL MOTOR STARTER

SS Motor Starter

Introduction for Functions

FUNCTION AND FEATURES

94

MANUAL MOTOR STARTER

SS Motor Starter

Main technical parameters

FUNCTION AND FEATURES

Operation mode

Frame current

Rated impulse withstand voltage

Rated operational voltage

Rated isolation voltage

Rated operational frequency

Trip class

Fastening torque

Mechanical durabilities

Electrical durabilities AC-3 400V

Overload protection category

Short circuit protection

Isolation function

Temperature compensation function

Button operated

32A

6000 V

690 V

690 V

50/60 Hz

10 A

1.7 N.m

100000

100000

Phase failure, thermal overload

Yes

Yes

Yes

100kA

100kA

100kA

100kA

100kA

100kA

2.25kA

2.25kA

2.25kA

2.25kA

2.25kA

2.25kA

2.25kA

2.25kA

2.25kA

100kA

100kA

100kA

100kA

100kA

100kA

3kA

3kA

3kA

3kA

3kA

3kA

3kA

3kA

3kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

50kA

10kA

4.5kA

4.5kA

3kA

3kA

3kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

50kA

10kA

6kA

6kA

4kA

4kA

4kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

50kA

15kA

4kA

4kA

3kA

3kA

3kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

50kA

15kA

8kA

8kA

6kA

6kA

6kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

7.5kA

7.5kA

6kA

6kA

5kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

15kA

15kA

15kA

15kA

10kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

50kA

50kA

50kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

100kA

50kA

50kA

50kA

0.1 - 0.16 A

0.16 - 0.25 A

0.25 - 0.4 A

0.4 - 0.63 A

0.63 - 1 A

1 - 1.6 A

1.6 - 2.5 A

2.5 - 4 A

4 - 6.3 A

6 - 10 A

9 - 14 A

13 - 18 A

17 - 23 A

20 - 25 A

24 - 32 A

Ue: 230/240 VSetting Current Ue: 400/415 V Ue: 440 V Ue: 500 V Ue: 690 V

Icu Icu Icu Icu IcuIcs Ics Ics Ics Ics

95

SS Motor Starter

Main technical parameters

The temperature compensation performance

Trip Characteristics for phase load unbalance (Phase failure)

Trip Characteristics for phase load balance

Ambient Temp.Tripping Time Initial ConditionMultiples of Setting current

Non-tripping within 2hTripping within 2h< 2 min

Non-tripping within 2hTripping within 2hNon-tripping within 2hTripping within 2h

Non-tripping within 2hTripping within 2h

1.051.21.57.2

1.01.2

1.051.3

1.0 0.91.15 0

any 2 phase 3rd phase

Without previous loadImmediately after No.1 TestImmediately after No.1 TestWithout previous load

Without previous loadImmediately after No.1 TestWithout previous loadImmediately after No.3 Test

Without previous loadImmediately after No.1 Test

+20 C+20 C+20 C+20 C

+40 C+40 C-5 C-5 C

+20 C+20 C

-

-

-

0.37kW

0.55kW

1.1kW

1.5kW

3kW

4kW

7.5kW

9kW

11kW

15kW

18.5kW

22kW

-

0.06kW

0.09kW

0.12kW

0.25kW

0.37kW

0.75kW

1.5kW

2.2kW

4kW

5.5kW

7.5kW

9kW

11kW

15kW

-

-

-

-

-

-

0.37kW

0.75kW

1.1kW

2.2kW

3kW

4kW

5.5kW

5.5kW

7.5kW

0.1 - 0.16 A

0.16 - 0.25 A

0.25 - 0.4 A

0.4 - 0.63 A

0.63 - 1 A

1 - 1.6 A

1.6 - 2.5 A

2.5 - 4 A

4 - 6.3 A

6 - 10 A

9 - 14 A

13 - 18 A

17 - 23 A

20 - 25 A

24 - 32 A

Ue: 230/240 VSetting Current Ue: 400/415 V Ue: 690 V

3 Phase motor rated power, 50/60 Hz, AC-3

FUNCTION AND FEATURES

MANUAL MOTOR STARTER

96

SS Motor Starter

Main technical parameters

Wiring diagram

FUNCTION AND FEATURES

MANUAL MOTOR STARTER

97

SS Motor Starter

Standard: IEC 60947-1 IEC 60947-2 IEC 60947-4-1

SELECTION GUIDE

MANUAL MOTOR STARTER

1.5

2.4

5

8

13

22.5

33.5

51

78

138

170

223

327

327

416

0.1 - 0.16

0.16 - 0.25

0.25 - 0.4

0.4 - 0.63

0.63 - 1

1 - 1.6

1.6 - 2.5

2.5 - 4

4 - 6.3

6 - 10

9 - 14

13 - 18

17 - 23

20 - 25

24 - 32

-

0.06

0.09

0.12

0.25

0.37

0.75

1.5

2.2

4

5.5

7.5

9

11

15

SSD16100K

SSD25100K

SS0D4100K

SSD63100K

SS001100K

SS1D6100K

SS2D5100K

SS004100K

SS6D3100K

SS010100K

SS014015K

SS018015K

SS023015K

SS025015K

SS032010K

SC-0911

SC-0911

SC-0911

SC-0911

SC-0911

SC-0911

SC-0911

SC-0911

SC-0911

SC-0911

SC-1211

SC-1811

SC-2511

SC-2511

SC-3211

Ordering CodesRecommendedRated Operating PowerMagnetic ReleaseThermal Release

Current Id (A)Setting Current (KW) Contactor

98

SS Motor Starter

Accessories

1- Pry the top auxiliary protective cover up;

contact close to the circuit breaker

3- Align the installation position and insert it

Installation of SS-HAE11 or SS-HAE20

SELECTION GUIDE

MANUAL MOTOR STARTER

Undervoltage Release

Shunt Release

Auxiliary Contact Top

Side

Waterproof Cover

HUV

HAS

AE

AN

MC

SS-HAU110

SS-HAU220

SS-HAU380

SS-HAU415

SS-HAS110

SS-HAS220

SS-HAS380

SS-HAS415

SS-HAE20

SS-HAE11

SS-HAN20

SS-HAN11

SS-HDP632MC

110~127V

220~240V

380~400V

415V

110~127V

220~240V

380~400V

415V

2NO

1NC+1NO

2NO

1NC+1NO

IP55

Ordering CodesSpecsTypeName

99

Control Products

Extra High Voltage Research Center

CERTIFICATIONS

MANUAL MOTOR STARTER