6
Technical Note 00840-0900-4021, Rev AA Rosemount Flowmeters January 2016 Sealing Requirements for Flow Applications 1.1 Sealing requirements for electrical equipment Sealing is a serious concern for industrial process control due to the nature of the hazardous materials used in the process industry. The considerations for transmitter sealing are outlined below: For explosion-proof/flameproof approved transmitters, seals may be necessary to prevent the propagation of flame through the cable or conduit system. For transmitter sensors with wetted parts, additional sealing may be necessary to prevent the process from entering the electrical system and migrating from hazardous areas to safe or unclassified areas. Most facilities have rules and regulations for sealing. In addition, there are national regulations or standards that address sealing requirements. The most common are listed below: NEC ® 2014 Articles 501.15, 501.17, 502-15, 505.16, 505.26, and 506.16 CEC C22.1-12 Rule 18-072, 18-092, 18-108, 18-154, 18-204, and 18-254 IEC/EN 60079-14:2013 Clauses 5.9, 9.4, and 14.4 ANSI/API RP 14F Section 6.8.2.2 1.2 Flameproof/Explosion-proof seals A flameproof/explosion-proof seal (commonly referred to as a conduit/cable seal) is installed at the entry of electrical equipment to prevent flame propagation from one portion of the electrical system to another. The seal is either a poured seal (potted) or a compression fitting. Flameproof/explosion proof seals are required on all installations where conduit or cable passes from one hazardous location to another or to a safe area. These seals are not designed to contain process fluids and typically hold a maximum pressure of 6 inH 2 O (14.9 mbar) before allowing process fluids to pass. A typical poured seal is shown below: This type of sealing can also be incorporated into the equipment. Explosion-proof enclosures that do not contain arcing, sparking or heat producing components may be approved and marked “factory sealed” or equivalent. This type of enclosure does not require seals at the conduit/cable entries. This is the case with most enclosures used for Rosemount products. Review the product label or installation drawing for sealing requirements.

Technical Note: Sealing Requirements for Flow Applications · 1.4 ANSI/ISA 12.27.01 Standard for process sealing ... 1.5.1 Vortex flowmeters ... Technical Note: Sealing Requirements

  • Upload
    vutram

  • View
    218

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Technical Note: Sealing Requirements for Flow Applications · 1.4 ANSI/ISA 12.27.01 Standard for process sealing ... 1.5.1 Vortex flowmeters ... Technical Note: Sealing Requirements

Technical Note00840-0900-4021, Rev AA

Rosemount FlowmetersJanuary 2016

Sealing Requirements for Flow Applications

1.1 Sealing requirements for electrical equipment

Sealing is a serious concern for industrial process control due to the nature of the hazardous materials used in the process industry. The considerations for transmitter sealing are outlined below:

For explosion-proof/flameproof approved transmitters, seals may be necessary to prevent the propagation of flame through the cable or conduit system.

For transmitter sensors with wetted parts, additional sealing may be necessary to prevent the process from entering the electrical system and migrating from hazardous areas to safe or unclassified areas.

Most facilities have rules and regulations for sealing. In addition, there are national regulations or standards that address sealing requirements. The most common are listed below:

NEC® 2014 Articles 501.15, 501.17, 502-15, 505.16, 505.26, and 506.16

CEC C22.1-12 Rule 18-072, 18-092, 18-108, 18-154, 18-204, and 18-254

IEC/EN 60079-14:2013 Clauses 5.9, 9.4, and 14.4

ANSI/API RP 14F Section 6.8.2.2

1.2 Flameproof/Explosion-proof seals

A flameproof/explosion-proof seal (commonly referred to as a conduit/cable seal) is installed at the entry of electrical equipment to prevent flame propagation from one portion of the electrical system to another. The seal is either a poured seal (potted) or a compression fitting. Flameproof/explosion proof seals are required on all installations where conduit or cable passes from one hazardous location to another or to a safe area. These seals are not designed to contain process fluids and typically hold a maximum pressure of 6 inH2O (14.9 mbar) before allowing process fluids to pass. A typical poured seal is shown below:

This type of sealing can also be incorporated into the equipment. Explosion-proof enclosures that do not contain arcing, sparking or heat producing components may be approved and marked “factory sealed” or equivalent. This type of enclosure does not require seals at the conduit/cable entries. This is the case with most enclosures used for Rosemount™ products. Review the product label or installation drawing for sealing requirements.

Page 2: Technical Note: Sealing Requirements for Flow Applications · 1.4 ANSI/ISA 12.27.01 Standard for process sealing ... 1.5.1 Vortex flowmeters ... Technical Note: Sealing Requirements

Technical Note00840-0900-4021, Rev AA

Rosemount FlowmetersJanuary 2016

1.3 Process seals

A process seal prevents flammable process fluids from getting into the electrical system and moving from a hazardous area to a non-hazardous area, such as a control room. Process seals must be robust to withstand the pressure, temperature, corrosion and cyclic effects associated with industrial processes. They must be considered for any installation where a flammable process fluid is present. Thermowells and welded diaphragms are examples of process seals.

1.4 ANSI/ISA 12.27.01 Standard for process sealing

In 2000, user members of the ISA (International Society of Automation) SP12 committee pushed for the development of a standard for process sealing of electrical equipment used in hazardous locations that would allow the equipment to be exempted from the NEC process sealing requirements. ANSI/ISA 12.27.01 was the result of this effort. This standard identifies two sealing methods.

The first sealing method is to test and certify a single high integrity seal, referred to as single seal. Testing includes temperature and fatigue testing of the seal, where it is subjected to 100,000 pressure cycles at worst case temperatures. Following this testing, the seal is subjected to leakage and burst overpressure tests.

The second sealing method is to test and certify a multiple seal configuration, referred to as dual seal. Refer to ANSI/ISA 12.27.01 for dual seal testing of devices with annunciation of the primary seal failure.

Both methods provide adequate measures to prevent process fluid from entering into the electrical system.

1.5 Flow process sealing compliance

1.5.1 Vortex flowmeters

All Rosemount 8800 Vortex Flowmeter meterbody designs incorporate high integrity seals integral to the design. The following illustration identifies these components within the meter body where the Vortex sensor is mounted.

2 Rosemount Flowmeters

Page 3: Technical Note: Sealing Requirements for Flow Applications · 1.4 ANSI/ISA 12.27.01 Standard for process sealing ... 1.5.1 Vortex flowmeters ... Technical Note: Sealing Requirements

Technical Note 00840-0900-4021, Rev AA

Rosemount FlowmetersJanuary 2016

Figure 1-1. Vortex Sensor Mounting

As shown above the primary seal is cast into the Vortex meterbody. The secondary seal is a metal O-ring compressed onto the meterbody when the Vortex sensor is seated. The primary seal is pressure rated to the process pressure of the meterbody.

Rosemount 8800 Vortex Flowmeters with FM or CSA approval are labeled “Factory Sealed” or “Seal not required” for users in the United States and Canada. This is an indicator to installers that separate process seals and explosion-proof seals (conduit seals) are not required. As is true for all interpretations of the NEC and CEC, the final acceptance of the installation must be obtained from the local authority having jurisdiction.

CSA International has certified the Rosemount 8800 Vortex Flowmeter to ANSI/ISA 12.27.01-2003. The associated markings are included on any CSA approved product.

1.5.2 Magnetic flowmeters

Magnetic flowmeters are used in applications with conductive process fluids. These fluids are typically non-flammable and consequently do not require process sealing. For those situations where the process does contain flammable fluids, the primary seal consists of the electrodes and the liner material. If appropriate materials are selected that are compatible with the process, this primary seal should not fail. However, if a secondary seal is required, the Rosemount 8705 Magnetic Flowmeter Sensor offers coil housing configuration options where the electrodes are housed in separate compartments, providing process containment should the primary seal fail. An Alternate construction shown in Figure 1-2 and Figure 1-3 displays the Rosemount 8705 Magnetic Flowmeter Sensor where a secondary seal is provided, if required, at the flow tube adapter. In the alternate method the secondary seal would provide process containment if the primary seal failed.

A. Sensor nutB. SensorC. Metal O-ring

D. Secondary seal (silver plated alloy C-ring)E. MeterF. Primary seal (casting)

A

B

CD

E

F

B

3Rosemount Flowmeters

Page 4: Technical Note: Sealing Requirements for Flow Applications · 1.4 ANSI/ISA 12.27.01 Standard for process sealing ... 1.5.1 Vortex flowmeters ... Technical Note: Sealing Requirements

Technical Note00840-0900-4021, Rev AA

Rosemount FlowmetersJanuary 2016

Figure 1-2. M3 and M4 Coil Housing Configuration

A. Primary seal (electrode/liner)B. Secondary seal (isolated electrode compartment)C. 2 � fused glass sealD. 2 � M6 pressure relief port with removable cap screwE. Optional: use relief port to plumb to safe area (supplied area)

As shown above, the Rosemount 8705 Magnetic Flowmeter Sensor with the isolated electrode compartment incorporates multiple components to produce high integrity seals that eliminate the need for an additional seal as identified in the regulations and standards listed previously. The installation of a tube approved for the environment where the sensor is located can safely announce a primary seal breech.

A B

C

D

E

4 Rosemount Flowmeters

Page 5: Technical Note: Sealing Requirements for Flow Applications · 1.4 ANSI/ISA 12.27.01 Standard for process sealing ... 1.5.1 Vortex flowmeters ... Technical Note: Sealing Requirements

Technical Note 00840-0900-4021, Rev AA

Rosemount FlowmetersJanuary 2016

Figure 1-3. M1 Coil Housing Configuration

A. Primary seal (electrode/liner)B. Secondary seal (isolated electrode compartment)C. M6 pressure relief port with removable cap screwD. Optional: use relief port to plumb to safe area (supplied by user)

As shown above, the Rosemount 8705 Magnetic Flowmeter Sensor with the isolated transmitter incorporates multiple components to produce high integrity seals that eliminate the need for an additional seal as identified in the regulations and standards listed previously. The installation of a tube approved for the environment where the sensor is located can safely announce a primary seal breech.

1.6 Summary

The majority of Rosemount transmitters can be installed without the need for additional sealing. This information has been provided as reference only. Users should seek guidance of the local authority having jurisdiction (AHJ) for final approval of all electrical installations.

B

A

C

D

5Rosemount Flowmeters

Page 6: Technical Note: Sealing Requirements for Flow Applications · 1.4 ANSI/ISA 12.27.01 Standard for process sealing ... 1.5.1 Vortex flowmeters ... Technical Note: Sealing Requirements

Technical Note00840-0900-4021, Rev AA

January 2016

Global HeadquartersEmerson Process Management 6021 Innovation Blvd.Shakopee, MN 55379, USA

+1 800 522 6277 or +1 303 527 5200+1 303 530 8459 [email protected]

North America Regional OfficeEmerson Process Management 7070 Winchester CircleBoulder, CO 80301, USA

+1 800 522 6277 or +1 303 527 5200+1 303 530 8459 [email protected]

Latin America Regional OfficeEmerson Process Management Multipark Office Center Turrubares Building, 3rd & 4th floorGuachipelin de Escazu, Costa Rica

+1 506 2505 6962+1 954 846 [email protected]

Europe Regional OfficeEmerson Process Management Flow B.V.Neonstraat 16718 WX EdeThe Netherlands

+31 (0) 318 495555+31 (0) 318 495556 [email protected]

Asia Pacific Regional OfficeEmerson Process Management Asia Pacific Pte Ltd1 Pandan CrescentSingapore 128461

+65 6777 8211+65 6777 0947 [email protected]

Middle East and Africa Regional OfficeEmerson Process Management Emerson FZE P.O. Box 17033,Jebel Ali Free Zone - South 2Dubai, United Arab Emirates

+971 4 8118100+971 4 8865465 [email protected]

Linkedin.com/company/Emerson-Process-Management

Twitter.com/Rosemount_News

Facebook.com/Rosemount

Youtube.com/user/RosemountMeasurement

Google.com/+RosemountMeasurement

Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/pages/Terms-of-Use.aspxThe Emerson logo is a trademark and service mark of Emerson Electric Co.Rosemount and Rosemount logotype are trademarks of Emerson Process Management.National Electrical Code is a registered trademark of National Fire Protection Association, Inc.All other marks are the property of their respective owners.© 2016 Emerson Process Management. All rights reserved.