20
EASYLIFE Air/water heat pump Electricity (energy supplied to the compressor) Natural renewable energy free of charge HYBRID AIR/WATER CONDENSING/ LOW TEMPERATURE OIL HEAT PUMPS FOR HEATING AND DOMESTIC HOT WATER PRODUCTION AWHP…-EFU C/EFU… Hybrid V200 AWHP…-EFU… Hybrid: heat pump incorporating a floor-standing (non-condensing) oil boiler AWHP…-EFU C… Hybrid: heat pump incorporating a floor-standing condensing oil boiler ALEZIO O HYBRID ALEZIO O Hybrid is a range of air/water Inverter heat pumps, comprising an outdoor unit and a hydraulic indoor module incorporating: - A floor-standing EFU type 22.4 or 29.8 kW oil boiler and a 180 litre hybrid DHW tank. - A floor-standing EFU C type 19.3, 24.3 or 32 kW condensing oil boiler and a 180 litre hybrid DHW tank. - Operates down to -20°C (-15°C for the 4 and 6 kW versions), - Single or three phase power supply, - Start-up current limitation using INVERTER technology. The heat pumps in this range stand out because of their performances: COP of 4.05 to 4.65 at an outside air temperature of +7°C/+35°C (EER of 3.99 to 4.75 at a temperature of +35°C/+18°C). High-tech products fitted with the INVERTER output storage system, they improve set point temperature stability, significantly reduce electricity consumption and run silently. Thanks to their reversibility and the underfloor cooling type cooling option (water at +18°C), by fan coil units when they are fitted with the “Insulation Kit” (water at +7°C), they provide absolute year round comfort. As for the hybrid function, it enables the simultaneous or separate management of the heat pump and the oil boiler according to weather conditions and heating needs: one of the aims of the hybrid function is to meet those needs by always consuming the most efficient energy, whether gas or electricity, i.e.: - Either the cheapest energy (to optimise heating costs), - Or the one that uses the least primary energy or generates the lowest CO 2 emissions as part of an environmentally friendly approach. Heating and cooling for underfloor heating/ cooling or air conditioning by fan coil units. Models incorporating DHW production and management Heat pump: NeOvo Condens condensing boiler: Condensing Domestic fuel oil CE identification No.: 0085CQ0002 NeOvo EcoNox low temperature boiler: Domestic fuel oil CE identification No.: 0085CQ0004

Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

  • Upload
    trinhtu

  • View
    220

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

EASYLIFE

Air/water heat pump

Electricity(energy supplied to the compressor)

Natural renewable energy free of charge

HYBRID AIR/WATER CONDENSING/ LOW TEMPERATURE OIL HEAT PUMPS FOR

HEATING AND DOMESTIC HOT WATER PRODUCTION

AWHP…-EFU C/EFU… Hybrid V200

AWHP…-EFU… Hybrid: heat pump incorporating a

floor-standing (non-condensing) oil boiler

AWHP…-EFU C… Hybrid: heat pump incorporating

a floor-standing condensing oil boiler

ALEZIO O HYBRID

ALEZIO O Hybrid is a range of air/water Inverter heat pumps, comprising an outdoor unit and a hydraulic indoor module incorporating:- A floor-standing EFU type 22.4 or 29.8 kW oil boiler and a 180 litre

hybrid DHW tank. - A floor-standing EFU C type 19.3, 24.3 or 32 kW condensing

oil boiler and a 180 litre hybrid DHW tank. - Operates down to -20°C (-15°C for the 4 and 6 kW versions),- Single or three phase power supply,- Start-up current limitation using INVERTER technology.

The heat pumps in this range stand out because of their performances: COP of 4.05 to 4.65 at an outside air temperature of +7°C/+35°C (EER of 3.99 to 4.75 at a temperature of +35°C/+18°C). High-tech products fitted with the INVERTER output storage system, they improve set point temperature stability, significantly reduce electricity consumption and run silently. Thanks to their reversibility and the underfloor cooling type cooling option (water at +18°C), by fan coil units when they are fitted with the “Insulation Kit” (water at +7°C), they provide absolute year round comfort.

As for the hybrid function, it enables the simultaneous or separate management of the heat pump and the oil boiler according to weather conditions and heating needs: one of the aims of the hybrid function is to meet those needs by always consuming the most efficient energy, whether gas or electricity, i.e.:- Either the cheapest energy (to optimise heating costs),- Or the one that uses the least primary energy or generates the lowest CO2

emissions as part of an environmentally friendly approach.

Heating and cooling for underfloor heating/cooling or air conditioning by fan coil units. Models incorporating DHW production and management

Heat pump:

NeOvo Condens condensing boiler:

Condensing

Domestic fuel oil

CE identification No.:0085CQ0002

NeOvo EcoNox low temperature boiler:

Domestic fuel oil

CE identification No.:0085CQ0004

Page 2: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

2

MODELS AVAILABLE

The ALEZIO O Hybrid comprises a reversible outdoor unit and an indoor unit composed of a NeOvo type floor-standing oil boiler and a hybrid DHW tank that handles domestic hot water production. - The hybrid DHW tank incorporates: the 180-litre tank, the

stainless steel plate condenser, the disconnecting cylinder, the hydrobloc with modulating circulating pump with an EEI < 0.23, the reversal valve, the PCBs for interfacing with the outdoor unit and the NeOvo boiler, 2 DHW temperature sensors and the flow meter.

- The NeOvo Condens type floor-standing condensing oil boiler: for connection to a chimney flue. The boiler comprises a main heating body in eutectic cast iron, an exchanger-condenser on the flue gases in carbon ceramic, a compact burner with low NOx and CO emissions, a heating circulating pump with an EEI < 0.23, a 3-bar safety valve, an expansion vessel, the IniControl 2 control panel with a control system run according to the outside temperature that incorporates the hybrid parameters. The boiler is

positioned on top of the hybrid tank to form a uniform column and can also be placed beside the hybrid tank with the EH525 option (to be ordered separately). Further information on the NeOvo Condens boiler can be found in the dedicated leaflet.

- The NeOvo EcoNox type floor-standing (non-condensing) oil boiler: for connection to a chimney flue. The boiler comprises a heating body in eutectic cast iron, a compact burner with low NOx and CO emissions, a heating circulating pump with an EEI < 0.23, a 3-bar safety valve, an expansion vessel, the IniControl 2 control panel with a control system run according to the outside temperature that incorporates the hybrid parameters. The boiler is positioned on top of the hybrid tank to form a uniform column and can also be placed beside the hybrid tank with the EH525 option (to be ordered separately). Further information on the NeOvo EcoNox boiler can be found in the dedicated leaflet.

ENERGY LABEL Each heat pump comes with its energy label, which incorporates various items of information: energy efficiency, annual energy consumption, manufacturer’s name, noise level…If you combine your heat pump, for instance, with a solar system, a DHW storage tank, a control device or another generator,

you can improve your system’s performance and generate the corresponding «system» label: go to our website « www.dedietrich-heating.com »

Created by De Dietrich, the ECO-SOLUTIONS label guarantees you a range of products compliant with the European Eco-design and Energy Labelling directives. These directives apply from 26 September 2015 to heating and domestic hot water appliances.

With De Dietrich ECO-SOLUTIONS, you can benefit from the latest generation of multi-energy systems, easier to use, with better performance and energy savings, designed to give you greater comfort while caring for the environment. ECO-SOLUTIONS also mean expertise, advice and a wide range of services from the De Dietrich professional network.

The energy label, together with the ECO-SOLUTIONS, shows you the performance of your chosen product. More info at www.dedietrich-heating.com

Page 3: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

3

MODELS

A

A ++

A

A ++

HP with NeOvo Condens boiler

HP rated heating power at +7°C/+35°C

(kW)

Cooling power HP

at +35°C/+18°C (kW)

Useful boiler output at 50/30°C

(heating mode) (kW)

Model

HYB

RID

_Q00

03A

Model withfloor-standing condensing oil boiler for heating and DHW production

3.94 3.84 19.3 AWHP 4 MR-EFU C-E19 Hybrid V200

5.79 4.69 19.3 AWHP 6 MR-EFU C-E19 Hybrid V200

7.9 7.9 19.3 AWHP 8 MR-EFU C-E19 Hybrid V200

11 .39 11 .16 19.3 AWHP 11 MR-EFU C-E19 Hybrid V200

11 .39 11 .16 19.3 AWHP 11 TR-EFU C-E19 Hybrid V200

5.79 4.69 24.3 AWHP 6 MR-EFU C-E24 Hybrid V200

7.9 7.9 24.3 AWHP 8 MR-EFU C-E24 Hybrid V200

11 .39 11 .16 24.3 AWHP 11 MR-EFU C-E24 Hybrid V200

11 .39 11 .16 24.3 AWHP 11 TR-EFU C-E24 Hybrid V200

7.9 7.9 32 AWHP 8 MR-EFU C-E32 Hybrid V200

11 .39 11 .16 32 AWHP 11 MR-EFU C-E32 Hybrid V200

11 .39 11 .16 32 AWHP 11 TR-EFU C-E32 Hybrid V200

HP with NeOvo EcoNox boiler

HP rated heating power at +7°C/+35°C

(kW)

Cooling power HP

at +35°C/+18°C (kW)

Useful boiler output at 50/30°C

(heating mode) (kW)

Model

HYB

RID

_Q00

03A

Model withfloor-standing low temperature oil boiler for heating and DHW production

3.94 3.84 19.3 AWHP 4 MR-EFU-E22 Hybrid V200

5.79 4.69 19.3 AWHP 6 MR-EFU-E22 Hybrid V200

7.9 7.9 19.3 AWHP 8 MR-EFU-E22 Hybrid V200

11 .39 11 .16 19.3 AWHP 11 MR-EFU-E22 Hybrid V200

11 .39 11 .16 19.3 AWHP 11 TR-EFU-E22 Hybrid V200

7.9 7.9 24.3 AWHP 8 MR-EFU-E29 Hybrid V200

11 .39 11 .16 24.3 AWHP 11 MR-EFU-E29 Hybrid V200

11 .39 11 .16 24.3 AWHP 11 TR-EFU-E29 Hybrid V200

Page 4: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

4

MAIN DIMENSIONS

Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection)

l

0

A

C

K

275 95

165 138

172

600

46

680 104

69 69

393448

642

735

1038

(1)

520

1964

600

106

1130

834

1260

156

7

1

1011

56

9

436

813 4

110375

738

14

2

3

HYB

RID

_F03

00

Key� Domestic hot water outlet G 3/4” M� Heating circuit flow G 1” M� Heating circuit return G 1” M� Condensates discharge, PVC pipe Ø 24 x 19 mm� Cool. gas connector:

- AWHP 4 and 6 MR: 1/2” flare - AWHP 8 MR and 11 MR/TR: 5/8” flare - Hybrid calorifier: 5/8” flare

� Cool. fluid connector: - AWHP 4 and 6 MR: 1/4” flare

- AWHP 8 MR and 11 MR/TR: 5/8” flare - Hybrid calorifier: 3/8” flare

� Circulating loop return � Flue gas nozzle:

- Ø 80 mm (EFU C...), - Ø 125 mm (EFU...)

Domestic cold water inlet G 3/4” M Heating return mixing valve circuit G 1” M (with

package EH528: internal pipes kit with motorised 3-way valve and pump)

� Heating flow mixing valve circuit G 1” M (with package EH528: internal pipes kit with motorised 3-way valve and pump)

� Drain valve, connection for pipe int. Ø 14 mm Evacuation safety valves, connection for pipe

Ø 18 mm int.

(1) Feet adjustable from 0 to 20 mm

Models: AWHP..-EFU-.. Hybrid V200 (with NeOvo EcoNox boiler with chimney flue connection)

l

0

A

C 300 95

141

600

680 104

69 69

393448

642

735

1038

(1)

520

1964

600

106

1130

834

1588 7

1

1011

56

9

436

8

13

110375

738

14

2

3

HYB

RID

_F03

02A

Outside module for the AWHP..-EFU… Hybrid V200

1350

26

431447

42

65

950

65

66

56

53 28

19600 175175

330 370

3040

54

53 28

19175

330 370

30

175

943

950

23

431447

57 415

65

6

150 500800

300183

365

402318

887

155

600

10

6990

6

5

AWHP 4 MR… e 6 MR… AWHP 8 MR… AWHP 11 MR/TR…

PAC

_F01

70A

PAC

_F00

87C

PAC

_F00

88D

AWHP-EFU C… A (mm) C (mm) K (mm)E19 961 92 136E24 981 92 156E32 1083 218 260

AWHP-EFU… A (mm) C (mm)E22 970 146E29 1097 272

Page 5: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

5

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS OF THE HEAT PUMP WITH NEOVO CONDENS BOILER

Conditions of use: allowable operating temperatures

Models: AWHP…-EFU C-…HYBRID V200 4 MR-E19

6 MR-E19

8 MR-E19

11 MR-E19

11 TR-E19

6 MR-E24

8 MR-E24

11 MR-E24

11 TR-E24

8 MR-E32

11 MR-E32

11 TR-E32

Heating output +7°C/+35°C (1) kW 3.94/4.10 5.79/6.00 7.9/8.00 11 .39/11 .2 11 .39/11 .2 5.79/6.00 7.9/8.00 11 .39/11 .2 11 .39/11 .2 7.9/8.00 11 .39/11 .2 11 .39/11 .2Heating COP +7°C/+35°C (1) 4.53/4.80 4.05/4.42 4.34/4.40 4.65/4.45 4.65/4.45 4.05/4.42 4.34/4.40 4.65/4.45 4.65/4.45 4.34/4.40 4.65/4.45 4.65/4.45Heating output -7°C/+35°C (1) kW 2.83/3.80 4.35/4.40 5.60/7.00 8.09/8.5 8.09/8.5 4.35/4.40 5.60/7.00 8.09/8.5 8.09/8.5 5.60/7.00 8.09/8.5 8.09/8.5Heating COP -7°C/+35°C (1) 2.8/2.79 2.57/2.72 2.71/2.90 2.88/2.89 2.88/2.89 2.57/2.72 2.71/2.90 2.88/2.89 2.88/2.89 2.71/2.90 2.88/2.89 2.88/2.89Absorbed electrical power +7°C/+35°C (1) kWe 0.87 1 .43 1 .82 2.45 2.45 1 .43 1 .82 2.45 2.45 1 .82 2.45 2.45

* Seasonal space heating energy efficiency (5) % 134 132 134 132 132 134 134 132 132 134 132 132

* Seasonal space heating energy efficiency (with outdoor sensor) (6) % 136 134 136 134 134 136 136 134 134 136 134 134

Cooling output +35°C/+18°C (2) kW 3.84 4.69 7.9 11 .16 11 .16 4.69 7.9 11 .16 11 .16 7.9 11 .16 11 .16Cooling COP (EER) +35°C/+18°C (2) 4.83 4.09 3.99 4.75 4.75 4.09 3.99 4.75 4.75 3.99 4.75 4.75

Absorbed electrical power +35°C/+18°C (2) kWe 0.72 1 .15 2.0 2.35 2.35 1 .15 2.0 2.35 2.35 2.0 2.35 2.35

Nominal water flow rate t = 5 K m3/h 0.68 1 .00 1 .36 1 .96 1 .96 1 .00 1 .36 1 .96 1 .96 1 .36 1 .96 1 .96Manometric height available at nominal flow rate t = 5 K mbar 580 620 480 120 120 620 480 120 120 480 120 120

Nominal air flow rate m3/h 2100 2100 3300 6000 6000 2100 3300 6000 6000 3300 6000 6000

Outdoor unit power supply voltage V

230 V single

230 V single

230 V single

230 V single

400 V three-phase

230 V single

230 V single

230 V single

400 V three-phase

230 V single

230 V single

400 V three-phase

Start-up amperage A 5 5 5 5 3 5 5 5 3 5 5 3Acoustic power of the outdoor/indoor module (3) dB(A) 62.4/48.8 64.8/48.8 66.7/48.8 69.7/47.6 69.7/47.6 64.8/48.8 66.7/48.8 69.7/47.6 69.7/47.6 66.7/48.8 69.7/47.6 69.7/47.6

R 410 A refrigerant kg 2.1 2.1 3.2 4.6 4.6 2.1 3.2 4.6 4.6 3.2 4.6 4.6Max pre-loaded length m 10 10 10 10 10 10 10 10 10 10 10 10DHW calorifier capacity l 177 177 177 177 177 177 177 177 177 177 177 177Maximum usable volume of hot water (Vmax) (4) l 249 247 251 231 231 247 251 231 231 251 231 231

DHW heating time (th) (4) h 1 h 54 2 h 00 1 h 58 1 h 33 1 h 33 2 h 00 1 h 58 1 h 33 1 h 33 1 h 58 1 h 33 1 h 33Absorbed output on primary energy (Pes) (5) W 90.3 90.3 90.3 90.3 90.3 90.3 90.3 90.3 90.3 90.3 90.3 90.3

COP DHW-PE (4) 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07Water heating energy efficiency (6) % 106 106 106 106 106 106 106 106 106 106 106 106Weight of the outdoor unit/weight of the indoor unit empty with boiler

kg 42/334 42/334 75/334 118/334 118/334 42/362 75/362 118/362 118/362 75/362 118/390 118/390

(1) Heating mode: outside air temp. / water temp. at the outlet. Performances according to EN 14511-2 with optimised inverter frequency/Measurement necessary to size the HP.

(2) Cooling mode: outside air temp. / water temp. at the outlet. Performances according to EN 14511-2.(3) Test run according to the NF EN 12102 standard at +7°C/+55°C.(4) Draw-off cycle : L, performances according to EN 13203-5.(5) According to commission regulation (EU) n°813/2013.(6) According to commission regulation (EU) n°811/2013.* At average temperature.

Use limit temp. in heating mode:Water: +18°C/+60°C,Outside air: -20°C/+35°C (-15°C for 4 and 6 kW)

Use limit temp in cooling mode:Water: +18°C/+25°C,Outside air: -5°C/+46°C

Heating circuit:Max operating pressure: 3 barMax operating temp: 95°C

DHW circuit:Max operating pressure: 10 barMax operating temp: 65°C

Page 6: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

6

TECHNICAL SPECIFICATIONS

Models: AWHP…-EFU-…HYBRID V200 4 MR-E22

6 MR-E22

8 MR-E22

11 MR-E22

11 TR-E22

8 MR-E29

11 MR-E29

11 TR-E29

Heating output +7°C/+35°C (1) kW 3.94/4.10 5.79/6.00 7.9/8.00 11 .39/11 .2 11 .39/11 .2 7.9/8.00 11 .39/11 .2 11 .39/11 .2Heating COP +7°C/+35°C (1) 4.53/4.80 4.05/4.42 4.34/4.40 4.65/4.45 4.65/4.45 4.34/4.40 4.65/4.45 4.65/4.45Heating output -7°C/+35°C (1) kW 2.83/3.80 4.35/4.40 5.60/7.00 8.09/8.5 8.09/8.5 5.60/7.00 8.09/8.5 8.09/8.5Heating COP -7°C/+35°C (1) 2.8/2.79 2.57/2.72 2.71/2.90 2.88/2.89 2.88/2.89 2.71/2.90 2.88/2.89 2.88/2.89Absorbed electrical power +7°C/+35°C (1) kWe 0.87 1 .43 1 .82 2.45 2.45 1 .82 2.45 2.45

* Seasonal space heating energy efficiency (5) % 134 131 134 131 131 134 131 131

* Seasonal space heating energy efficiency (with outdoor sensor) (6) % 136 133 136 133 133 136 133 133

Cooling output +35°C/+18°C (2) kW 3.84 4.69 7.9 11 .16 11 .16 7.9 11 .16 11 .16Cooling COP (EER) +35°C/+18°C (2) 4.83 4.09 3.99 4.75 4.75 3.99 4.75 4.75Absorbed electrical power +35°C/+18°C (2) kWe 0.72 1 .15 2.0 2.35 2.35 2.0 2.35 2.35

Nominal water flow rate t = 5 K m3/h 0.68 1 .00 1 .36 1 .96 1 .96 1 .36 1 .96 1 .96Manometric height available at nominal flow rate t = 5 K mbar 580 620 480 120 120 480 120 120

Nominal air flow rate m3/h 2100 2100 3300 6000 6000 3300 6000 6000

Outdoor unit power supply voltage V 230 V single

230 V single

230 V single

230 V single

400 V three-phase

230 V single

230 V single

400 V three-phase

Start-up amperage A 5 5 5 5 3 5 5 3Acoustic power of the outdoor/indoor module (3) dB(A) 62.4/48.8 64.8/48.8 66.7/48.8 69.7/47.6 69.7/47.6 66.7/48.8 69.7/47.6 69.7/47.6

R 410 A refrigerant kg 2.1 2.1 3.2 4.6 4.6 3.2 4.6 4.6Max pre-loaded length m 10 10 10 10 10 10 10 10DHW calorifier capacity l 177 177 177 177 177 177 177 177Maximum usable volume of hot water (Vmax) (4) l 249 247 251 231 231 251 231 231

DHW heating time (th) (4) h 1 h 54 2 h 00 1 h 58 1 h 33 1 h 33 1 h 58 1 h 33 1 h 33Absorbed output on primary energy (Pes) (5) W 90.3 90.3 90.3 90.3 90.3 90.3 90.3 90.3

COP DHW-PE (4) 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07 1 .07Water heating energy efficiency (6) % 106 106 106 106 106 106 106 106Weight of the outdoor unit/weight of the indoor unit empty with boiler kg 42/334 42/334 75/334 118/334 118/334 75/334 118/334 118/334

(1) Heating mode: outside air temp. / water temp. at the outlet. Performances according to EN 14511-2 with optimised inverter frequency/Measurement necessary to size the HP.

(2) Cooling mode: outside air temp. / water temp. at the outlet. Performances according to EN 14511-2.(3) Test run according to the NF EN 12102 standard at +7°C/+55°C.(4) Draw-off cycle : L, performances according to EN 13203-5.(5) According to commission regulation (EU) n°813/2013.(6) According to commission regulation (EU) n°811/2013.* In average temperature.

TECHNICAL SPECIFICATIONS OF THE HEAT PUMP WITH NEOVO ECONOX BOILER

Conditions of use: allowable operating temperatures

Use limit temp. in heating mode:Water: +18°C/+60°C,Outside air: -20°C/+35°C (-15°C for 4 and 6 kW)

Use limit temp in cooling mode:Water: +18°C/+25°C,Outside air: -5°C/+46°C

Heating circuit:Max operating pressure: 3 barMax operating temp: 90°C

DHW circuit:Max operating pressure: 10 barMax operating temp: 65°C

Page 7: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

7

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS OF THE NEOVO CONDENS BOILERGenerator type:

- EFU C…E: heating onlyBoiler type: condensingBurner: integrated forced draught (unit)

Energy used: oilCE identification No.: CE-0085CQ0002Combustion discharge: chimney flue

Models EFU C 19 E 24 E 32 ENominal output at flow/return t° at 50/30°C kW 19.3 24.3 32.0

Efficiency as a % PCI, load … % and water temp. …°C

- 100 % Pn, ave. temp. 70°C % 96.4 96.3 95.8- 30% Pn, return temp. 30°C % 101 .5 100.9 99.9

Seasonal space heating energy efficiency (1) % 88 89 88Seasonal space heating energy efficiency (with outdoor sensor) (2) % 90 91 90Nominal water output at Pn t = 20 K m3/h 0.783 0.994 1 .319Stand-by losses at t = 30 K W 84 84 100

Electrical power- of the auxiliaries (without pump) at Pn W 172 143 143- of the auxiliaries on standby W 4 4 4- of the circulating pump at Pn W 33 33 33

Water content l 24 29.5 35Water resistance at t = 20 K mbar 36 57 101Flue gas mass flow rate kg/h 31 39 51Available pressure at the nozzle Pa 20 30 45Manometric height available heating circuit mbar 594 517 390Weight empty kg 205 233 261

(1) According to commission regulation (EU) n°813/2013.(2) According to commission regulation (EU) n°811/2013.

TECHNICAL SPECIFICATIONS OF THE NEOVO ECONOX BOILERGenerator type:

- EFU E…: heating onlyBoiler type: low temperatureBurner: integrated forced draught (unit)

Energy used: oilCE identification No.: 0085CQ0004Combustion discharge: chimney flue

Models EFU 22 E 29 ENominal output kW 22.4 29.8

Efficiency as a % PCI, load … % and water temp. …°C

- 100 % Pn, ave. temp. 70°C % 93.3 93.1- 30 % Pn, ave. temp. 40°C % 97.3 96.6

Seasonal space heating energy efficiency (1) % 86 86Nominal water output at Pn t = 20 K m3/h 0.964 1 .282Stand-by losses at t = 30 K W 83 95

Electrical power- of the auxiliaries (without pump) at Pn W 143 144- of the auxiliaries on standby W 4 4- of the circulating pump at Pn W 33 33

Water content l 24.5 30.0Water resistance at t = 20 K mbar 5 9Flue gas mass flow rate kg/h 36 48Vacuum necessary at the nozzle Pa 5 5Manometric height available heating circuit mbar 573 483Weight empty kg 210 228

(1) According to commission regulation (EU) n°813/2013.

Page 8: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

8

TECHNICAL SPECIFICATIONS

DATA TABLES FOR SIZING

Water flow temperature (°C)25 35 40 45 50 55 60

Output kW COP Output

kW COP Output kW COP Output

kW COP Output kW COP Output

kW COP Output kW COP

Out

side

air

tem

pera

ture

(°C) -20 - - - - - - - - - - - - - -

-15 - - 3.05 2.06 2.95 1 .78 2.84 1 .50 2.74 1 .29 - - - --10 3.80 3.03 3.80 2.48 3.68 2.14 3.55 1 .83 3.39 1 .59 3.22 1 .35 - --7 3.80 3.39 3.80 2.79 3.80 2.44 3.8 2.08 3.78 1 .85 3.58 1 .60 - -2 4.00 3.81 4.00 3.24 4.00 2.95 4.00 2.67 4.00 2.31 4.00 1 .90 4.00 1 .497 4.10 5.73 4.10 4.80 4.10 4.21 4.10 3.63 4.10 3.05 4.10 2.42 4.10 1 .8512 4.86 7.08 4.86 5.59 4.86 4.77 4.86 3.95 4.86 3.45 4.86 2.91 4.86 2.3315 5.19 7.82 5.19 6.03 5.19 5.14 5.19 4.25 5.19 3.71 5.19 3.15 5.19 2.5320 5.62 8.66 5.62 6.69 5.62 5.71 5.62 4.72 5.62 4.12 5.62 3.49 5.62 2.80

AWHP 4 MR-…HYBRID V200

AWHP 6 MR-…HYBRID V200Water flow temperature (°C)

25 35 40 45 50 55 60Output

kW COP Output kW COP Output

kW COP Output kW COP Output

kW COP Output kW COP Output

kW COP

Out

side

air

tem

pera

ture

(°C) -20 - - - - - - - - - - - - - -

-15 - - 3.46 1 .97 3.32 1 .71 3.18 1 .46 3.02 1 .22 - - - --10 4.40 2.70 4.22 2.40 4.11 2.08 4.00 1 .77 3.81 1 .53 3.61 1 .28 - --7 4.40 3.29 4.40 2.72 4.40 2.35 4.40 1 .98 4.40 1 .76 4.40 1 .54 - -2 5.00 3.47 5.00 2.97 5.00 2.72 5.00 2.47 5.00 2.13 5.00 1 .76 5.00 1 .387 6.00 5.51 6.00 4.42 6.00 3.87 6.00 3.32 6.00 2.84 6.00 2.32 6.00 1 .7712 7.07 6.47 7.07 5.05 7.07 4.34 7.07 3.63 7.07 3.19 7.07 2.73 7.07 2.2315 7.54 7.04 7.54 5.46 7.54 4.68 7.54 3.89 7.54 3.43 7.54 2.92 7.54 2.3820 8.04 7.55 8.04 5.87 8.04 5.03 8.04 4.19 8.04 3.68 8.04 3.14 8.04 2.56

AWHP 8 MR-…HYBRID V200Water flow temperature (°C)

25 35 40 45 50 55 60Output

kW COP Output kW COP Output

kW COP Output kW COP Output

kW COP Output kW COP Output

kW COP

Out

side

air

tem

pera

ture

(°C) -20 - - 6.09 1 .62 6.07 1 .49 6.04 1 .37 - - - - - -

-15 - - 7.00 1 .97 7.00 1 .76 7.00 1 .56 6.62 1 .51 - - - --10 7.00 2.91 7.00 2.47 7.00 2.20 7.00 1 .92 7.00 1 .76 6.69 1 .56 - --7 7.00 3.51 7.00 2.90 7.00 2.55 7.00 2.20 7.00 1 .96 7.00 1 .71 - -2 7.50 3.97 7.50 3.40 7.50 3.11 7.50 2.83 7.50 2.37 7.14 1 .91 6.57 1 .657 8.00 5.24 8.00 4.40 8.00 3.90 8.00 3.40 8.00 3.10 8.00 2.77 8.00 2.3312 9.00 6.16 9.00 5.26 9.00 4.54 9.00 3.83 9.00 3.42 9.00 2.97 9.00 2.5015 9.65 6.63 9.65 5.70 9.65 4.87 9.65 4.04 9.65 3.59 9.65 3.11 9.65 2.5820 10.15 7.03 10.15 6.03 10.15 5.14 10.15 4.25 10.15 3.76 10.15 3.25 10.15 2.68

Water flow temperature (°C)25 35 40 45 50 55 60

Output kW COP Output

kW COP Output kW COP Output

kW COP Output kW COP Output

kW COP Output kW COP

Out

side

air

tem

pera

ture

(°C) -20 - - 6.87 1 .79 6.71 1 .64 6.55 1 .49 - - - - - -

-15 - - 8.17 2.16 8.07 1 .93 7.96 1 .69 7.87 1 .52 7.77 1 .34 - --10 8.50 3.02 8.50 2.52 8.50 2.27 8.50 2.02 8.50 1 .78 8.50 1 .54 - --7 8.50 3.45 8.50 2.89 8.50 2.55 8.50 2.22 8.50 1 .94 8.50 1 .65 - -2 10.00 3.86 10.00 3.32 10.00 2.99 10.00 2.66 10.00 2.28 10.00 1 .89 9.36 1 .497 11 .20 4.89 11 .20 4.45 11 .20 3.94 11 .20 3.42 11 .20 3.02 11 .20 2.60 11 .20 2.1312 12.85 5.60 12.85 5.16 12.85 4.54 12.85 3.92 12.85 3.48 12.85 2.99 12.85 2.4815 13.62 6.00 13.62 5.49 13.62 4.83 13.62 4.18 13.62 3.71 13.62 3.21 13.62 2.6520 14.67 6.62 14.67 5.96 14.67 5.27 14.67 4.57 14.67 4.06 14.67 3.52 14.67 3.10

AWHP 11 MR/TR-…HYBRID V200

These performance are not certified. They are only to be used for sizing the HP.

Page 9: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

9

TECHNICAL SPECIFICATIONS

DESCRIPTION

Indoor module: components Outdoor module: components

Note: Further information on NeOvo Condens and NeOvo EcoNox boilers to be incorporated in the hybrid heat pump: see relevant leaflets.

AWHP 8 MR…

PAC

_Q01

21

AWHP 4 MR… and 6 MR…3-bar safety valve

Automatic air ventPressure gauge

Heating generator control system PCBDHW temperature sensor(top - not shown)Magnesium anode

Reversal valve motor

DHW temperature sensor(bottom)

Condenser (stainless steel plate exchanger)

Outside unit interface PCB

Air vent

Temperature sensor

Flow meter

Circulating pumpHydrobloc with

reversal valveSafety valve

Floor standing oil boiler

• NeOvo Condens (condensing)

• NeOvo EcoNox (non-condensing)

Electronic PCB

Ventilator

Evaporator

“Inverter“ compressor

with power receiver

AWHP 11 MR/TR…

HYB

RID

_Q00

17

HPI

_Q00

20“Inverter“

compressorwith power receiver

4-way valve for cycle inversion

Stop valve on the refrigeration connections

with outdoor unit

Evaporator

Electronic PCB

HPI

_Q00

21

“Inverter“ compressor

with power receiver

4-way valve for cycle inversion

Stop valve on the refrigeration connections

with outdoor unit

Evaporator

Electronic PCB

Expansion vessel and heating pump

(not shown)

Page 10: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

10

CONTROL PANEL

Additional functions on the IniControl 2 control panel dedicated to AWHP…HYBRID heat pumps

This enables the management of one direct circuit, one integrable optional 3-way valve circuit and DHW production. Access to the various menus enables the configuration of the parameters for the HP’s various operating modes (heating, heating + DHW,

DHW only, cooling/air conditioning, cooling/air conditioning and DHW). A large screen displays the HP’s operating status in the various operating modes: operation of the compressor, boiler back-up, heating mode, cooling/air conditioning mode...

EF_Q

0026

Large digital display

Keys:- for accessing the various

menus and parameters,- for setting and manual

reset, variable as and when selections are made

CONTROL PANEL

Programmable wire room thermostat - Package AD137Programmable wireless room thermostat - Package AD200Non-programmable room thermostat - Package AD140

AD140

AD200 The programmable thermostats handle heating control and weekly programming according to various operating modes: “Automatic” according to the programme, “Permanent” at a set temperature or “Holidays”. The “wireless” version is delivered with

a receiver box to be affixed to the wall close to the boiler. The non-programmable thermostat can only be used to control the room temperature according to the instruction given.

8801

Q00

386

66Q

120A

Underfloor heating connection kit - Package HA255This cable harness is inserted into the heating pump and comprises the wires used to connect a safety

thermostat for an underfloor heating system.

HA

255_

Q00

01

2-circuit control system kit - Package EH527Kit used to run a circuit with mixing valve.

PAC

_Q00

39

Hygro sensor kit - cooling (On/Off) - Package HK27Sensor that measures the hygrometry level. It must be installed on the flow for the underfloor heating/cooling system. In „cooling“ mode, it is used to shut

down the HP (On/Off) when the hygrometry level becomes too high to prevent the formation of condensation.H

PI_Q

0017

CONTROL PANEL OPTIONS

Humidity sensor (0 - 10 V) - Package HZ64Sensor that measures the hygrometry level. It must be installed on the flow for the underfloor heating/cooling system. In “cooling” mode, it is used to adapt

the temperature of the flow water to prevent the formation of condensation.

HYB

RID

_Q00

50

Page 11: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

11

COMPLEMENTARY CONTROL SYSTEM FUNCTIONS

THE “HYBRID” FUNCTION

The hybrid function in the inside module control system is used to manage solutions that combine an HP (using a proportion of renewable energy) and a condensing boiler (oil or gas) running alone or simultaneously, depending on weather conditions and heating needs.

The aim of the hybrid function is to meet the system's needs by always consuming the most efficient energy, be it gas, oil or electricity, i.e.:- Either the cheapest energy (to optimise heating costs),- Or the one that uses the least primary energy as part of an

environmentally friendly approach.The values corresponding to the "energy price" or the "primary energy factor" can be modified in the control system parameters.

The advantages of this method of management are also:- Reduction in HP output for a low-cost electricity contract (no

surcharge for an electrical back-up system)- 100% cover of heating and DHW needs by the HP + boiler

system- In an existing home, energy savings compared with running a

boiler only, reduction in CO2 emissions from the boiler already in place, connection possible without having to replace any existing heat-emitting devices or having to resort to very high temperature devices.

To heat and light our homes and produce domestic hot water, we consume energy (oil, wood, gas, electricity). The final energy used by the consumer is not always available in the natural state (e.g. electricity) and sometimes requires processing. The primary energy represents the energy used to carry out such processing. The primary energy is quantified by "the primary energy factor",

which expresses the amount of primary energy required to obtain one unit of energy. For electricity, the factor is 2.5, which means that it is necessary to consume 2.5 kWh of primary energy to obtain 1 kWh of electrical energy. For natural gas and oil, this factor is 1 (gas and oil are primary energies).

Primary energy

Performances of a hybrid solutionThe graph below presents a performance comparison (COP) for heating and DHW production in the primary energy used for various solutions:- The hybrid solution: combination of an HP and a condensing

boiler (renewable energy, electrical energy and gas or oil energy),

- The solution with an HP only (renewable energy with electrical back-up),

- The solution with a condensing boiler only (oil or gas energy).

For an outside air temperature lower than the switch-over point, the hybrid solution improves system performances (COP on primary energy) compared with an HP used on its own. Likewise for an air temperature higher than the switch-over point, the hybrid solution shows better performances that those of a condensing boiler used on its own.

Comparison of primary energy performances of an electric HP, a condensing boiler and a hybrid solution

COP (on primary energy)

Outside air temperature in °CSource CETIAT

Electric HPHybrid solution Condensing boiler

0-1-2-3-4-5-6 1 2 3 4 5 6 7 8 9 10 11 12

HP_

F097

4A

Page 12: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

12

COMPLEMENTARY CONTROL SYSTEM FUNCTIONS

EXAMPLES OF HYBRID SOLUTIONSExample of a hybrid solution according to the primary energy factor

Example of a hybrid solution according to energy cost

The graph opposite illustrates the various hybrid solutions according to outside air temperature and energy cost.When the COP of the HP > 2.5 and the Tair > Teq alone, the HP will be called upon. For Toff < Tair < Teq, the control system runs the HP in combination with the boiler. When the COP of the HP < 2.5 the control system runs the boiler only.For each configuration, it is therefore the control system that decides which generator or combination of generators will be used to meet heating and DHW needs.The principle of management according to primary energy is especially valid in new homes.

The graph below illustrates the operating principle of the hybrid solution according to outside air temperature and energy cost.Calculating the energy price ratio R:

R = electricity price (€/kWh)

= 0.15/0.07 = 2.1 Gas price (€/kWh)(the energy price factors in the annual contract) It is factor R (calculated energy price ratio) and the outside air temperature which are used as parameters by the control system to define the various operating modes. In the example opposite:- The HP is an AWHP 8 MR-EFU…HYBRID model- The generators are installed in an existing house of 130 m2.When the COP of the HP > 2.1 and T air > +2°C, the control system runs the HP only to meet heating needs and DHW production.When the COP of the HP > 2.1 and -5°C < T air < +2°C, the control system runs the HP in combination with the boiler. When the COP of the HP < 2.1, the control system runs the boiler only.For each configuration, it is therefore the control system that decides which generator or combination of generators will be used to meet heating and DHW needs.

Condensingboileronly

Condensingboiler

HP

HPonly

HP COP < 2,5

Outputfrom the

HP

HP COP > 2,5

+

Toff Teq Outside air temperature in °C

Heat losses

Condensingboileronly

Condensingboiler

HP

HPonly

HP COP < R

Outputfrom the

HP

HP COP > R

+

+2°C-5°C Outside air temperature in °C

Heat losses

HP_

F030

0H

P_F0

301

Comment:Operation of the hybrid function is activated:- If the outside temperature is higher than the HP shut-down temperature (-20°C,

-15°C for 4 and 6 MR), the HP is always started up first and the boiler back-up is called upon only if heating needs are higher than the HP can provide.

- If the outside temperature is lower than the HP shut-down temperature, the boiler will handle heating needs on its own.

Page 13: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

13

OPTIONS FOR THE ALEZIO O Hybrid HEAT PUMP

OUTDOOR MODULE OPTIONS

INDOOR MODULE OPTIONSHybrid DHW tank

PAC

_Q00

32

Wall mounting bracket + anti-vibration studs for AWHP 4/6 and 8 MR… - Package EH95Wall mounting bracket + anti-vibration studs for AWHP 11 MR/TR… - Package EH250This kit is used to mount the outdoor unit of the AWHP to the wall.

It comes with anti-vibration studs to limit the transmission of vibrations into the ground.

PAC

_Q01

00

Condensate tray tank for wall bracket - Package EH111In solid plastic, this kit is used to recuperate condensates from the outdoor unit. It can be fitted to the wall mounting bracket package EH95.

PAC

_Q00

98

Floor support - Package EH112Support in hard wearing PVC, for mounting the outside unit on the ground. The screws, washers and nuts are provided for quick and easy mounting.

HIB

RID

_Q00

11

Silencer kit for outdoor module - Package EH572After installation, helps to reduce the level of noise emitted by the outdoor unit by the order of 2 to 3 dB(A).

PAC

_Q00

43

Kit for 3-way valve circuit (internal) - Package EH528Used to connect a circuit with mixing valve. This kit is incorporated inside the casing of the hybrid hydraulics kit. It contains the reversal valve, the high

energy efficiency pump (EEI < 0.23) and the flow sensor for the valve circuit.

PAC

_F02

18

Insulation kit for cooling mode with fan coil unit (water at + 7°C)- Package EH567Used to insulate the hydraulic part of the hybrid tank.

GSH

P_Q

009

Kit for mounting the boiler to the right or left of the hybrid tank - Package EH525Contains the kit to connect the hydraulics in the NeOvo… boiler to the hybrid tank and the cover for the hybrid tank.

Page 14: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

14

OPTIONS FOR THE ALEZIO O Hybrid HEAT PUMP

For the accessories for NeOvo Condens and NeOvo EcoNox boilers, see Product Catalogue 2016

BOILER OPTIONS

INSTALLATION OPTIONS PA

C_Q

0097

Refrigerant connection kit 5/8” - 3/8”:- Length 5 m - Package EH114- Length 10 m - Package EH115- Length 20 m - Package EH116

Refrigerant connection kit 1/2” - 1/4”: - Length 10 m - Package EH142

Insulated, high quality copper pipe restricting heat losses and condensation.

PAC

_Q00

99

Electric tracing kit - Package EH113This kit prevents the condensates from freezing.

Storage tank: B 80 T - Package EH85 or B 150 T - Package EH60These 80- and 150-litre tanks help to limit short cycle running of the compressor and provide a reserve for the defrosting phase in reversible Air/Water heat pumps.

They are also recommended for all HPs connected to installations in which the water volume is less than 5 l/kW heating power.Example: HP output = 10 kWMin. volume in the installation: 50 litresDimensions: B 80 T: H 850 x W 440 x D 450 mm

B 150 T: H 1003 x Ø 601 mmPAC

_Q00

21

8962

Q02

4

EH85 EH60

PAC

_Q00

09B

Screen filter 400 μm + isolating valve - Package EH61This filter protects the water exchanger in the heat pump from impurities.

SIZING AN ALEZIO O Hybrid SYSTEM

SIZING RULESThe sizing of the HP and the boiler is done in relation to the heat losses calculation. The heat losses are calculated according to the NF EN 12831 standard. The losses are calculated for the rooms heated by the HP and are broken down into: - Surface losses through walls and partitions,- Unit length losses via links between the different surfaces,- Losses by air renewal and infiltration.

For optimum sizing, the following rules should be observed:- 50% of losses � HP output � 60% of losses - Boiler output = 120% of losses

Losses in [kW] at Tbase 7 8 9 10 11 12 13 14 15 16 17 18 19 20

ALEZIO O HYBRID AWHP 4MR

AWHP 4MR

AWHP 6MR

AWHP 6MR

AWHP 6MR

AWHP 8MR

AWHP 8MR

AWHP 8MR

AWHP 8MR

AWHP 11MR

or AWHP 11TR

AWHP 11MR

or AWHP 11TR

AWHP 11MR

or AWHP 11TR

AWHP 11MR

or AWHP 11TR

AWHP 11MR

or AWHP 11TR

Page 15: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

15

INFORMATION REQUIRED FOR INSTALLATION

POSITIONING THE OUTDOOR UNIT

- The outdoor units for ALEZIO O Hybrid heat pumps should be installed close to the house, on a terrace, on the façade or in a garden. They are designed to operate in the rain but can also be installed under cover as long as there is sufficient ventilation.

- The outdoor unit must be installed protected from prevailing winds that may influence the installation’s performance.

- We recommend positioning the unit above the average depth of snowfall in the region in which it is installed.

- The emplacement of the outdoor unit should be carefully chosen in order for it to be compatible with environmental requirements: integration in the site, compliance with planning rules or co-ownership agreements.

- No obstacles must hinder the free circulation of air around the exchanger on intake and output. It is therefore necessary to allow clearance all around the appliance that will also facilitate connection, commissioning and maintenance operations (see installation diagrams below).

400

100

B

100

1001000

1000

A

PAC

_F01

02A

100(150)500(1000)

100(150)

100(200)

100(200)

200(300)

150(250)

150(250)

300(500)

1000(1500)

Max. 500

500(1000)

100(150)

PAC

_F01

01PA

C_F

0102

Minimum installation distances to be observed (mm)

200(300)

1000

Max. 500

AWHP…Hybrid 4/6 MR 8 MR 11 MR/TRA (mm) 600 943 1350B (mm) 800 950 950

dimensions without brackets: AWHP 4, 6, 8-EFU… Hybrid V200 dimensions in brackets: AWHP 11 MR/TR-EFU… Hybrid V200

(300))

500

(150

0)Max. 300

(1500)

(1500)

(1000)

(600)

(2000)

(150)

(1500)

(500)

Dimensions = minimum distances

Page 16: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

16

INFORMATION REQUIRED FOR INSTALLATION

Acoustic integration

The acoustic performances of the outside units are defined by the following two values:- The acoustic power Lw expressed in dB(A): this

characterises the sound emission capacity of the source independent of its environment. It is used to compare appliances with each other.

- The acoustic pressure Lp expressed in dB(A): this is the value perceived by the human ear. It depends on parameters such as the distance from the source, and the size and nature of the walls of the premises. The regulations are based on this value.

Definitions

The regulation on neighbourhood noise can be found in the Decree of 31/08/2006 and in the NF S 31-010 standard. Noise is defined by emergence, which is the difference between the level of acoustic pressure measured when the appliance is off compared with the level measured when the appliance is running in the same place.

The maximum difference permitted is:- Day time (7 a.m. - 10 p.m.): 5 dB(A)- Night time (10 p.m. - 7 a.m.): 3 dB(A)

Noise

- Do not place it in the vicinity of sleeping areas,- Avoid proximity with a terrace, do not install the module

opposite a wall. The increase in noise level caused by the installation configuration is shown in the diagrams below:

- The various set-ups below should be avoided:

- In order to limit noise and the transmission of vibrations, we recommend:• Installing the outdoor module on a metal frame or an inertia

base frame. The mass of such a base frame must be at least

twice the mass of the module and it must be independent of the building. In all cases, anti-vibration studs must be fitted to reduce the transmission of vibrations.

• To pass refrigerant connections through walls, use appropriate sleeves,

• For the fittings, use flexible, vibration-proof materials,• Install vibration reduction devices on refrigerant connections,

such a loops, brackets and elbows.- We also recommend installing a noise reduction device in the

form of:• A wall damper to be fitted to the wall behind the module,• An acoustic screen: the surface area of the screen must

greater than the dimensions of the outdoor module and it must be positioned as close to it as possible while allowing air to circulate freely. The screen must be made of an appropriate material such as acoustic bricks, concrete blocks coated with absorbent materials. It is also possible to use natural screens such as embankments of earth.

Recommendations on the acoustic integration of the outdoor module

Module placed against a wall: +3 dB(A)

Module placed in a corner: +6 dB(A)

Module placed in an interior courtyard: +9 dB(A)

Ventilation directed towards the neighbouring property

Module positioned on the property boundary

Module placed beneath a window

HPI

_F00

29

POSITIONING THE INDOOR UNITThe installation and servicing of the appliance, whether in a residential building or in a building open to the general public, must be carried out by a qualified professional pursuant to the prevailing regulatory texts and codes of practice.The indoor unit of the ALEZIO O Hybrid must be installed in a frost-free room with adequate ventilation.

B: 500 mm for the AWHP…- E… HYBRID V200 versions (versions for connection to a chimney flue)

500

500

1970

min. 250

1130

600B

min.

1000

827

HYB

RID

_F02

12A

Page 17: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

17

INFORMATION REQUIRED FOR INSTALLATION

Maximum connection distances (see below) MAXIMUM DISTANCES AND QUANTITY OF REFRIGERANT FLUID TO BE LOADED

LB

1 C

l

0

2

No additional load of refrigerant fluid is necessary if the length of the refrigerant pipe is less than 10 m. For lengths in excess of 10 m, the following additional loading is necessary:

Pre-loaded quantity of refrigerant

HYB

RID

_F02

10

REFRIGERATION CONNECTIONInstallation of ALEZIO O Hybrid heat pumps includes work on the refrigerant circuit.The appliances must be installed, commissioned, maintained and repaired by duly authorised qualified personnel, pursuant to the

requirements of prevailing directives, laws and regulations and in accordance with the codes of practice of the profession. See also the leaflet, “General Information”.

ELECTRICAL CONNECTIONThe electrical installation of HPs must be done according to the Codes of Practice and in accordance with prevailing standards, decrees and texts arising therefrom.

Recommended cable cross-sections and circuit breakers to be installed

Comment:The hybrid boiler should be connected separately at 230 V/50 Hz.

AWHP…-EFU… 4 MR 6 MR 8 MR 11 MR/TRØ cooling gas pipe 1/2" 1/2" 5/8" 5/8"Ø cooling fluid pipe 1/4" 1/4" 3/8" 3/8"L (m) 40 40 40 75B (m) 10 10 30 30

L: maximum connection distance between outdoor and indoor unit.B: maximum height difference permitted between the inside module and the outside unit

ModelAdditional load of refrigerant fluid (in kg)

for a distance > 10 m11 to 20 m 21 to 30 m 31 to 40 m 41 to 50 m 51 to 60 m 61 to 75 m

AWHP 4 MR 0.2 0.4 0.6 - - -AWHP 6 MR 0.2 0.4 0.6 - - -AWHP 8 MR 0.15 0.3 0.6 - - -AWHP 11 MR/TR 0.2 0.4 1 .0 1 .6 2.2 2.8

Outdoor unit Indoor unitHP Type Output

electrical absorbed

at + 7/35°C

Nominalintensity

at + 7/35°C

Start-up intensity

at+ 7/35°C

Maximalintensity

Power supplyoutdoor unit

Power supplyindoor module

CableBUS

…-phase kW A A ASC

(mm2)Curve C*

DJSC

(mm2)Curve C

DJSC

(mm2)AWHP 4 MR… Single 0.87 4.11 5 13 3 x 2.5 16 A 3 x 1 .5 10 A 3 x 1 .5

6 MR… Single 1 .43 6.57 5 13 3 x 2.5 16 A 3 x 1 .5 10 A 3 x 1 .58 MR… Single 1 .82 8.99 5 19 3 x 4 25 A 3 x 1 .5 10 A 3 x 1 .511 MR… Single 2.45 11 .41 5 29.5 3 x 6 32 A 3 x 1 .5 10 A 3 x 1 .511 TR… Three- 2.45 3.8 3 13 5 x 2.5 16 A 3 x 1 .5 10 A 3 x 1 .5

B: max height differenceL: maximum connection distanceC: 15 elbows max.

� Outdoor unit� Indoor unit

SC = cable cross-section in mm2

DJ = circuit breaker* differential protection motor

Page 18: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

18

INFORMATION REQUIRED FOR INSTALLATION

HYDRAULIC CONNECTIONThe indoor modules of ALEZIO O Hybrid heat pumps are fully fitted out for the connection of a direct circuit (radiators or underfloor heating): circulating pump with energy efficiency index EEI < 0.23, expansion vessel, heating safety valve, pressure gauge, air vent…The connection of a second circuit (underfloor heating) is possible by incorporating an optional “3-way valve kit - Package EH528“.

Comment: As ALEZIO O Hybrid heat pumps are “SPLIT INVERTER” models with a refrigerant link between the outdoor unit and the indoor module, it is not necessary to add glycol to the installation.

At the outlet of AWHP 4, 6 and 8 MR…

Manometric height available for the heating circuit

0 0.5 1.0 1.5 2.0 2.5

1

2

3

4

5

6

7

HYB

RID

_F00

17

Avai

labl

e pr

essu

re in

mH

2O

Flow rate in m3/h

ALEZIO O Hybrid 4 MR 6 MR 8 MR 11 MR/TRStorage tank capacity (litres) 20 30 40 55

At the outlet of AWHP 11 MR/TR…

0 0.5 1.0 1.5 2.0 2.5

1

2

3

4

5

6

7

Avai

labl

e pr

essu

re in

mH

2O

Flow rate in m3/h

Important comments on:The various emitters

The heat pumps’ water outlet temperature is limited: max. 65°C. It is therefore imperative to work on low temperature emitters, i.e. underfloor heating/cooling or radiators sized for low temperature. For cooling mode, underfloor heating with compatible slab and covering only is suitable. It is also necessary to observe minimum underfloor cooling flow temperatures in line with the geographical area of installation to prevent any condensation (between 18°C and 22°C).

Refrigerant fluids The refrigerant fluid, R 410 A, has properties suitable for heat pumps. It belongs to the HFC family (hydrofluorocarbons), composed of chemical molecules containing carbon, fluorine and hydrogen. They do not contain chlorine and are therefore not damaging to the ozone layer.

Cooling or air conditioning modeSo-called reversible heat pumps can be use for cooling in the summer. A 4-way valve, called a cycle reversal valve, switches the cycle from heating mode to cooling mode.The compressor intake is connected to the internal exchanger and thus becomes an evaporator. The compressor backflow is connected to the external exchanger and thus becomes a condenser.Note: For Air/Water type HPs, this 4-way valve is also used for the evaporator defrosting phase.In the case of an installation with underfloor heating/cooling (flow/return water temp.: +18°C/+23°C), the refrigerant output is limited, but sufficient, to keep conditions pleasantly comfortable inside the home. This allows an average reduction in room temperature of 3 to 4°C. In the case of an installation with fan coil units (flow/return water temp.: +7°C/+12°C), it is necessary to order the optional “insulation kit for air conditioning mode - Package EH567”.

SIZING THE BUFFER TANKThe volume of water in the heating installation must be able to store all of the energy provided by the HP during its minimum operating time. The storage volume therefore corresponds to the minimum volume of water required, the capacity of which is drawn from the mains. - Installation of a storage tank is advisable for installations with a

water volume of fewer than 5 l/kW HP heating power (factor in the volume of water in the indoor module).

- Increasing the volume in an installation limits short cycle running of the compressor (the greater the water volume, the fewer the number of compressor start-ups and the longer its lifespan).

- As an initial approach, below is an estimated storage volume for a minimum operating time of 6 minutes, a regulation differential of 5 K and factoring in a negligible mains volume (factor in the water volume in the indoor module).

Page 19: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

19

EXAMPLES OF INSTALLATIONS

The examples presented below cannot cover the full range of installation scenarios that may be encountered. Their purpose is to draw the attention to the basic rules to be followed. A certain number of control and safety devices are shown but it is ultimately up to experts, consultant engineers and design departments to take the final decision on the safety and control devices to be used in the boiler room according to its specificities. In all cases, it is necessary to abide by the codes of practice and prevailing regulations.

Attention: for the connection of domestic hot water, a sleeve made of steel, cast iron or any other insulating material must be interposed between the hot water outlet and these pipes to prevent any corrosion to the connections, if the distribution pipes are made of copper.

17

1146

27

35a

HA 255230V 50Hz

230V 50Hz

347

BU

SB

US

AD 200

230V ou 400V 50Hz

17 30 92928

9 950

EH 61

9

147

4465

21

l

0

BUS

AD200

AWHP...-EFU-...Hybride

1611

EH528

EH 527

EH 525

230V 50Hz

EH 61

230V 50Hz

9147

347

BU

S BU

S

EH 528

AD 137 AD 137

230V ou 400V 50Hz

64

17309 2928

9 950

52

51

EH 61

9147

23

4465

21

AWHP...-EFU C-...Hybride

0

l

17

1146

2711 10

35a

16

11

HYB

RID

_F00

14H

YBRI

D_F

0013

ALEZIO O Hybrid V200 (with non-condensing NeOvo EcoNox boiler)- 1 direct underfloor heating circuit- DHW production

ALEZIO O Hybrid V200 (with NeOvo Condens condensing boiler) with hybrid DHW tank placed beside the boiler- 1 direct (radiator) circuit - 1 circuit with mixing valve- DHW production

A

A ++

A

A ++

Keys 3 3-bar safety valve 4 Pressure gauge 5a Flow rate controller 7 Automatic air vent 9 Block valve 10 3-way mixing valve 11 Heating accelerator

16 Expansion vessel 17 Drain valve 21 Outside sensor 23 Flow sensor downstream of mixing

valve 27 Non-return valve 28 Domestic cold water inlet

29 Pressure reducer 30 Domestic safety unit calibrated and

sealed at 7 bar 44 65°C safety thermostat with

manual reset for underfloor heating

46 Heating/DHW reversal valve

50 Disconnector 51 Thermostatic valve 52 Differential valve 65 Direct heating circuit:

underfloor heating 147 Filter + isolating valves

Page 20: Technical leaflet ALEZIO O Hybrid 4 MAIN DIMENSIONS ¸ Models: AWHP..-EFU C-.. HYBRID V200 (with NeOvo Condens boiler with chimney flue connection) l 0 A C K 275 95 165 138 172 600

DE DIETRICH THERMIQUES.A.S. with corporate capital of 22 487 610 €57, rue de la Gare - F-67580 MERTZWILLERTel. +33 3 88 80 27 00 - Fax +33 3 88 80 27 99www.dedietrich-heating.com

09/2

016

– 30

0030

895

– 34

7.555

.559

Stra

sbou

rg C

ompa

nies

Reg

ister

– D

ocum

ent n

ot c

ontra

ctua

lly b

indi

ng -

Prin

ted

in F

ranc

e - O

TT Im

prim

eurs

673

10 W

asse

lonn

e - 1

6030

9

AIR/FLUE GAS CONNECTION

Important RecommendationsIn order to make the most of the performances of heat pumps for optimal comfort and to maximise their useful life, we recommend that you pay particular attention to their installation, commissioning and maintenance ; to do this, abide by the various instructions that come with the appliances. In addition, the De Dietrich catalogue offers a commissioning service for heat pumps ; we also strongly recommend that you take out a maintenance contract.

For the installation of the air/flue gas connection flues and the rules on installation, in addition to details of the various configurations,

you can refer to the document, “Flue System” or the current Product Catalogue.

TABLE OF MAXIMUM AIR/FLUE GAS CONDUIT LENGTHS PERMITTED ACCORDING TO BOILER TYPE

Lmax (1)

B23P

� Configuration B23P: Connection to a chimney flue (combustion air taken from the boiler room).

Type of air/flue gas connectionLmax of the connecting pipes in m

AWHP…- EFU C… Hybrid

Single flues in chimney (rigid or flex) (combustion air taken from the premises) (PPS) B23P

Ø 80 mm (rigid) 15

Ø 80 mm (flex) 15

HP with NeOvo Condens as back-up

EF_F

0075

(1) For each additional metre of horizontal pipe, remove 1 .2 m from the vertical lengh Lmax show in the table below.