29
Cooling Filtering Heating Ventilation Technical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery

Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

  • Upload
    dokhanh

  • View
    224

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

Cooling FilteringHeating Ventilation

Technical documentation

ComfoAir XL 800-6000The latest generation of ventilation units with heat recovery

Page 2: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

2

Service and recommendations The latest heat recovery range from Zehnder is called ComfoAir XL. This range provides a healthy and pleasant indoor climate especially for use in commercial buildings and apartment blocks.

There are numerous options with regard to the range of versions, control system technology, options and accessories. You can also arrange your unit combinations yourself. We are pleased to help you achieve your optimal ventilation system.

We would be delighted to support you: ■ Detailed recommendations based on a special operating point/with price details■ Support in the project (draft and implementation)■ Instructions on ventilation systems■ Telephone/personal assistance

People in a perfect indoor climate: for a nicer living area, work area and living environment.We give you our word. Zehnder ‘always around you’.

All rights reserved.Utmost care and attention has been taken to create this document; however, the publisher cannot be held liable for any damage arising from missing or incorrect representation of information in this document. In the case of dispute, the Dutch version of the text shall have priority.

Page 3: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

3

Table of contents1. General ...................................................................................................................................................................... 4

1.1 Important features ............................................................................................................................................... 4

1.2 Passive house certification.................................................................................................................................. 4

1.3 ComfoAir XL series and options ......................................................................................................................... 4

1.4 Block diagram ..................................................................................................................................................... 5

2. Set-up ........................................................................................................................................................................ 6

2.1 Air-tight housing .................................................................................................................................................. 6

2.2 Fans .................................................................................................................................................................... 7

2.3 High-performance plate heat exchanger ............................................................................................................ 7

2.4 Siphon ................................................................................................................................................................ 7

2.5 Bypass ................................................................................................................................................................ 7

2.6 Filter .................................................................................................................................................................... 7

2.7 Batteries .............................................................................................................................................................. 8

2.8 Flaps ................................................................................................................................................................... 8

2.9 Design ................................................................................................................................................................. 9

3 Control unit ............................................................................................................................................................. 10

3.1 Controller .......................................................................................................................................................... 10

3.2 Supply ............................................................................................................................................................... 10

4. Quick selection ....................................................................................................................................................... 11

4.1 Coding ............................................................................................................................................................... 11

4.2 Selection schematic .......................................................................................................................................... 11

4.3 Selection chart .................................................................................................................................................. 12

5. Dimensions and weight .......................................................................................................................................... 14

5.1 Indoor installation .............................................................................................................................................. 14

5.2 Exterior mounting ............................................................................................................................................. 15

6. Technical data ........................................................................................................................................................ 16

6.1 Technical data ComfoAir XL 800 ....................................................................................................................... 16

6.2 Technical data ComfoAir XL 1500 ..................................................................................................................... 18

6.3 Technical data ComfoAir XL 2200 ..................................................................................................................... 20

6.4 Technical data ComfoAir XL 3300 ..................................................................................................................... 22

6.5 Technical data ComfoAir XL 4400 ..................................................................................................................... 24

6.6 Technical data ComfoAir XL 6000 ..................................................................................................................... 26

7. Accessories.............................................................................................................................................................28

Page 4: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

4

1. GeneralThe ComfoAir XL series is a new generation of heat

recovery units, which is suitable for use in commercial

buildings and/or in apartment buildings. The ComfoAir XL

series covers 6 different capacities from 800 to 6000 m³/h.

1.1 Important features■ Heat recovery of approx. 90 %■ Capacity up to 6000 m³/h■ Equipped with 100 % bypass■ Passive house certification■ Renewed controller (ModBus communication)■ Constant volume and pressure control possible■ Unique, air-tight housing■ Renewed filter concept■ Filter monitoring with pressure sensors■ Easily accessible connection PCB■ Unit easy to configure at specific operating point■ Diaphragm siphon installed as standard

1.2 Passive house certificationThe ComfoAir XL units were designed in cooperation with the Passive House Institute (PHI) and in accordance with its directives. The units have passive house certification. This means that they satisfy the stringent requirements applied

by the Passive House Institute, whereby this series achieves greater energy savings (25 %) than the previous generation. The specific SFP value (specific fan output) is less than 0.34 W/(m³/h).

1.3 ComfoAir XL series and options The ComfoAir XL series is available in a variety of versions and with numerous options. The focus was placed on the smallest possible dimensions during development of the units.

Versions:■ ComfoAir XL 800 ■ ComfoAir XL 1500 ■ ComfoAir XL 2200 ■ ComfoAir XL 3300■ ComfoAir XL 4400■ ComfoAir XL 6000

Mounting:■ Indoor installation (I)■ Outdoor installation (A)

Air direction:■ Left (L)■ Right (R)

Air direction for left-side versionThe intake opening for the outside air is located at the top right and the outlet opening for the used air is located at the top left. The extract air is located at the bottom right and the air supply at the bottom left.

Air direction for right-side versionThe intake opening for the outside air is located at the top left and the outlet opening for the used air is located at the top right. The extract air is located at the bottom left and the air supply at the bottom right.

Filter:■ Cellular filter F7/G4 (PF) ■ Bag filter F7/G4 (BF)

Options:■ Bypass:

- Bypass open/closed (B) - Bypass modulating (BM)

■ Pre-heater (PRH)■ Post-heater (POH)■ Cooler (CL)■ Outside air flap (DMP-ODA)■ Exhaust air flap (DMP-EHA)

1 EHA = Exhaust air 2 SUP = Supply air 3 ODA = Outdoor air 4 ETA = Extract air

EHA1

SUP2

EHA1

SUP2

ODA3

ETA4

ODA3

ETA4

Page 5: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

5

1.4 Block diagram

- Filter

- Heater

- Cooler

- Heat exchanger

- Fan

- Temperature sensor

- Bypass

- Flap

ODA - Outside air

EHA - Exhaust air

ETA - Extract air

SUP - Supply air

Page 6: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

6

2. Set-up

2.1 Air-tight housingThe housing of the ComfoAir XL has a unique quality. The double seals on the panels ensure that the housing is perfectly air tight. The housing comprises a self-supporting structure that is made from double-walled panels with internal insulation that is 44 mm thick. The panels are produced from sendzimir sheet with a weatherproof Plastisol coating (Goosewing Grey – RAL 7044) applied to the outside. A special polyester coating (RAL 7035) is applied to the inside. These panels are free from thermal bridges and guarantee excellent insulation of the housing. The draft focusses on compliance with the Passive House Directive (internal and external leaks lower than 3 %). An overview of the specifications is provided below.

Feature Class

Mechanical strength 2A

Internal leak (at 400 Pa) < 3 % of the nominal volume

External leak (at 400 Pa) < 3 % of the nominal volume

Thermal insulation T2 (0,51 Wm2/K)

Thermal bridge factor TB1

Fire resistant B

Angled profile

1. Foam2. Sendzimir sheet 0.7 mm with Plasticol coat

RAL 70443. Sendzimir sheet 1.0 mm with powder coating

RAL 70354. Plastic profile with rubber shaft seal5. Rubber shaft seal6. Plastic tubes7. M8 screw8. M8 nut

Intermediate profile

1. Polyurethane foam. Insulation thickness 40 kg/m3 2. Outer skin: 0.7 mm pre-coated, galvanized sheet steel with Plastisol coating3. Internal coating: 1.0 mm pre-coated, galvanized sheet steel RAL 70354. Plastic profile with rubber sealing lip5. Dual rubber sealing tape6. Plastic connection tube7. M8 screw8. M8 nut9. Aluminium sealing profile10. Thermal PE insulating foam

Page 7: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

7

2.2 FansThe ComfoAir XL series consists of directly driven, energy-saving EC fans with backward-curved blades. These fans achieve an energy saving of more than 25 % compared to conventional AC fans. These fans are mounted vibration-free onto a mounting bracket. This obviates the need for flexible sleeves to ensure a vibration-free connection of the air ducts.

Error messageAn alarm function is included in the control board as standard. This alarm function is activated if a fan fails. The error message can also be activated by measuring the pressure difference via the supply air filter if desired.

2.3 High-performance plate heat exchanger The HR cross-counterflow heat exchanger (HR plate heat exchanger) is made of high-grade aluminium and has a thermal efficiency of approx. 90 % depending on the outside temperature and the air humidity in the rooms. The exchanger is corrosion-free and resistant to seawater and can be fully recycled.

Benefits of a high-performance plate heat exchanger:■ No wear■ Easy to maintain■ 100 % separate air streams ■ Low risk of contamination

Extractair

Supply air

Exhaust air

Outside air

Frost protectionUnder certain circumstances, condensate can freeze. To prevent this, frost protection is incorporated. This shuts down the supply fan when there is a risk of frost and can deactivate it for a short period.

2.4 Siphon A siphon is installed to remove condensate that forms in the plate heat exchanger. An external diaphragm siphon must be connected to remove the condensate that forms on the cooler. The siphon can be kept frost-free by using an insulated ribbon heating element. The contact for supply and control can be set in the software.

2.5 BypassComfoAir XL is equipped with a 100 % bypass. The control unit of the ComfoAir XL automatically brings the bypass valve to the closed and open positions. This bypass is located near the heat exchanger and is controlled by a counter-rotating bypass valve, which is controlled automatically by a servo motor. When the bypass valve opens, the extract air flows around the high-performance plate heat exchanger and no thermal transfer takes place. The filter system continues to work, however. In this way, it is possible to use what is referred to as 'free cooling' or night ventilation in the evening and during the night.

Please also refer to the block diagram in chapter 1, section 4 for details of bypass operation.

Open/closed or modulating bypassComfoAir XL can be equipped with an open/closed or modulating bypass. The servomotor regulates the modulating bypass and ensures that the temperature of the supply air is constant. This is particularly important when the unit has a cooling battery.

2.6 FilterTwo types of filters are available for filtering the supply and exhaust air flows: one cellular filter and a bag filter. The supply air flow is equipped with a F7 filter as standard, the exhaust air flow is equipped with a G4 filter. With the newly developed filter clamps, the filters are mounted onto the filter frame, which minimises leaks. The units are equipped with a filter monitor as standard. This is achieved with pressure sensors that measure the resistance via a filter to issue dirt notification.

Page 8: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

8

2.7 BatteriesThe ComfoAir XL series can optionally be equipped with a pre-heater and post-heater or cooler. The battery connections are attached outside the unit. The control unit for these batteries is set up to be equipped with several power relays (230 V) and 0-10-volt outputs via the connection board of the unit. The connection board issues a 0-10 V signal to control the two-way valve. The power relay (230 V) is used to supply the circulation pump. The batteries must be connected to an externally fed cold and/or hot water supply. All batteries must be selected on a project-related basis.

Pre-heater A pre-heater can be attached to pre-heat the cold outside air in winter. This heating battery is positioned in front of the heat exchanger and can be used as a frost protection system. The preheater is calculated on the basis of the water/glycol medium to prevent the battery from freezing.

Post-heaterThe post-heater increases the temperature of the supply air. In this way, air can be blown in at a higher comfort temperature. The post-heater is located behind the heat exchanger in the direction of the air flow.

Cooling battery A cooling battery is used to cool the supply air. This battery is positioned behind the heat exchanger like the post-heater. The cooling battery is mounted on the drain plate to collect condensate. A polypropylene droplet catcher that runs to the drain plate is positioned behind the cooling battery in the direction of air flow.

2.8 FlapsFlaps can be used to protect the unit against outside influences when it is not in operation. The intake can be equipped with a lockable flap either for the outside air or the exhaust air.

Page 9: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

9

2.9 Design

AB C

C

D

E F

G

H II

J

Q QKL

M N OP

J

ComfoAir XL is equipped with the following components as standard:■ A: Plate heat exchanger with high-performance heat recovery■ B: Drain plate below the plate heat exchanger with siphon ■ C: Two EC fans with backward-curved blades■ D: Main board■ E: Connection PCB■ F: Operating switch

ComfoAir XL is equipped with the following components as standard for mounting indoors:■ G: Metal support frame

ComfoAir XL is equipped with the following components as standard for mounting outdoors: ■ G: Support frame made of galvanised metal ■ H: Coated metallic cover ■ I: Two droplet catchers

Options:■ J: Panel or bag filter, filter class 7 for outside air and G4 for extract air■ K: Bypass valve open/closed or equipped with modulating servomotor■ L: Pre-heater to ensure controlled ventilation■ M: Post-heater for enhanced comfort■ N: Chiller for dehumidifying and cooling the supply air - O: Droplet catcher behind the cooler to collect moisture - P: Drain plate with condensate drain below the chiller■ Q: Flap with servomotor

Page 10: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

10

3 Control unit3.1 Controller

ComfoAir XL is equipped with a multifunctional controller. The control unit comprises two different PCBs. The main board, to which all internal components can be connected, is located inside the unit. All external functions are bundled at the connection PCB. This is located behind the designer front panel and is easily accessible to implement numerous connections. The units have an automatic frost-protection.

Essential features:■ Connection to the building technology via ModBus communication ■ Constant Air Flow: to set fixed capacities ■ Filter monitoring: Pressure sensors measure the resistance via the filter■ The unit software is equipped with a timeswitch as standard ■ Control via external sensor: CO2, pressure, relative air humidity■ Various connections: 230 V, power relay ■ Generation of summer night cooling via digital input ■ Compatible with fire alarm system via digital input■ Summer night cooling: activation via an external signal■ Frost protection for the high-performance plate heat exchanger:

the supply fan is shut down when there is a risk of frost

ComfoAir XL is easy to change over from constant air volume control to pressure control. This type of control requires a pressure sensor to measure the pressure in the supply air or extract air duct.

3.2 SupplyAn integrated operating switch is located at the operating side of the ComfoAir XL unit. The connection terminals and connection board are located behind the designer front panel. The board is equipped with a display as standard, which can be used easily to set the desired operating point. The power supply is connected to the operating switch. All versions, except for ComfoAir XL 6000, are equipped with a 230 V/50 Hz/1~ power supply. ComfoAir XL 6000 must be equipped with a 400 V/50 Hz/3~ power supply.

Page 11: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

11

4. Quick selection4.1 Coding

ComfoAir XL 800 CFE R B I PF CL PRH POH DMP-ODA

DMP ODA = Outside air flap DMP EHA = Exhaust air flap

POH = Post-heater

PRH = Pre-heater

CL = Cooler

PF = Cellular filterBF = Bag filter

I = Indoor installationO = Outdoor installation

B = Bypass open/closedBM = Bypass modulating

R = Right-handed versionL = Left-handed version

CFE = Counterflow plate heat exchanger

Product type designation (air volume in m³/h)

Product family name

4.2 Selection schematicOverview of air capacityType

: Capacity according to Passive House Directive : Total capacity, reported at least 200 Pa.

Page 12: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

12

4.3 Selection chart

Type

Air volume m³/s m³/s

Air volume m³/h m³/h

External static pressure (in connection with cooler, pre-heater and post-heater) Pa

Max. consumed power (excluding cooler, pre-heater and post-heater) kW

Voltage VAC

Max. consumed power (excluding cooler, pre-heater and post-heater) A

Frequency Hz

Cos π -

Protection system Fuse

HEAT RECOVERY  

- Outside air conditions °C/RH

- Extract air conditions °C/RH

- Total heat recovery performance: %

- Total heat recovery performance according to NEN 5138:2004 %

COLD RECOVERY  

- Outside air conditions °C/RH

- Extract air conditions °C/RH

- Temperature efficiency (perceptible performance) %

PREHEATER  

Air volume m³/s

Air volume m³/h

- Temperature distribution water/glycol °C/°C

- Temperature distribution air °C/°C

- Heat output kW

- Pressure loss of water side kPa

- Water-side connection DN

POST-HEATER  

Air volume m³/s

Air volume m³/h

- Temperature distribution water °C/°C

- Supply air temperature °C/°C

- Heat output kW

- Pressure loss of water side kPa

- Water-side connection DN

COOLER  

Air volume m³/s

Air volume m³/h

- Temperature distribution water °C/°C

- Supply air temperature °C

- Cooling power kW

- Pressure loss of water side kPa

- Water-side connection DN

Page 13: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

13

ComfoAir XL 800 ComfoAir XL 1500 ComfoAir XL 2200 ComfoAir XL 3300 ComfoAir XL 4400 ComfoAir XL 6000

0.22 0.42 0.56 0.92 1.22 1.67

800 1500 2200 3300 4400 6000

430 650 340 450 350 230

0.9 1.7 1.6 2.7 2.8 4.1

1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 3~ 400

5.4 6.9 6.8 11.5 12.2 6.4

50/60 50/60 50/60 50/60 50/60 50/60

0.67 0.98 0.99 1.00 1.00 1.00

C (10 A) C (10 A) C (10 A) C (16 A) C (16 A) C (10 A)

-10°/90 % -10°/90 % -10°/90 % -10°/90 % -10°/90 % -10°/90 %

21°/55 % 21°/55 % 21°/55 % 21°/55 % 21°/55 % 21°/55 %

90.0 90.2 89.9 89.8 89.9 89.8

79.8 80.1 79.8 79.6 79.8 79.6

28 °/60 % 28 °/60 % 28 °/60 % 28 °/60 % 28 °/60 % 28 °/60 %

24 °/55 % 24 °/55 % 24 °/55 % 24 °/55 % 24 °/55 % 24 °/55 %

79.3 79.6 79.2 79.2 78.9 79.2

0.22 0.42 0.56 0.92 1.22 1.67

800 1500 2200 3300 4400 6000

60/40 60/40 60/40 60/40 60/40 60/40

-20/0 -20/0 -20/0 -20/0 -20/0 -20/0

5.39 10.1 13.46 22.22 29.62 40.39

4.7 10.4 19.3 14.7 16.2 18.4

25 25 25 25 25 25

0.22 0.42 0.56 0.92 1.22 1.67

800 1500 2200 3300 4400 6000

60/40 60/40 60/40 60/40 60/40 60/40

22 22 22 22 22 22

1.4 2.57 3.5 5.78 7.7 10.5

2.0 9.2 15.9 8.1 6.2 6.1

15 15 15 25 25 25

0.22 0.42 0.56 0.92 1.22 1.67

800 1500 2200 3300 4400 6000

6/12 6/12 6/12 6/12 6/12 6/12

16 16 16 16 16 16

4.8 9.1 12.1 20.5 26.6 36.3

13.8 13.2 19 23.8 23.3 23

25 25 25 25 32 40

Page 14: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

14

5. Dimensions and weight5.1 Indoor installation

The dimensions refer to the above-mentioned standard unit, version with cellular filter (PF). For these dimensions, a post-heater (POH) can be used as standard.

Type L

[mm]B

[mm]H

[mm]Air connection

[mm]Weight

[kg]

ComfoAir XL 800 1750 700 1168 525 x 395 235-275

ComfoAir XL 1500 1750 1050 1168 875 x 395 310-340

ComfoAir XL 2200 2514 700 1500 612 x 612 450-600

ComfoAir XL 3300 2514 1050 1500 962 x 612 600-750

ComfoAir XL 4400 2514 1400 1500 1312 x 612 750-900

ComfoAir XL 6000 2514 1750 1500 1662 x 612 900-1050

The following dimensions refer to the additional length of the optional components.

Option Additional length

[mm]

Bag filter (BF) or pre-heater (PRH)* or empty section 350

Cooler (CL) or empty section 350

* ComfoAir XL 800 and ComfoAir XL 1500 do not require an additional length; a pre-heater (PRH) fits as standard here.

Page 15: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

15

5.2 Exterior mounting

The dimensions refer to the above-mentioned standard unit, version with cellular filter (PF). For these dimensions, a post-heater (POH) can be used as standard.

Type L

[mm]B

[mm]H

[mm]Air connection

[mm]Weight

[kg]

ComfoAir XL 800 1750 700 1168 525 x 395 335-385

ComfoAir XL 1500 1750 1050 1168 875 x 395 420-460

ComfoAir XL 2200 2514 700 1500 612 x 612 560-750

ComfoAir XL 3300 2514 1050 1500 962 x 612 730-920

ComfoAir XL 4400 2514 1400 1500 1312 x 612 900-1090

ComfoAir XL 6000 2514 1750 1500 1662 x 612 1070-1280

The following dimensions refer to the additional length of the optional components.

Option Additional length

[mm]

Bag filter (BF) or pre-heater (PRH)* or empty section 350

Cooler (CL) or empty section 350

* ComfoAir XL 800 and ComfoAir XL 1500 do not require an additional length for the PRH; a pre-heater (PRH) fits as standard here.

Page 16: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

16

6. Technical data6.1 Technical data, ComfoAir XL 800

Specific fan power, pressure loss and sound level

■ Supply air max. line ■ Extract air max. line■ Cooler supply air, pre-heater and post-heater ● Sound level

Page 17: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

17

Operating point Sound, supply air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 363 52 72.6 66.7 58.3 58.9 59.2 50.3 65

2 625 150 73.5 72.1 63.4 63.1 63.6 55.9 70

3 818 260 74.4 78.3 69.2 67.9 68.6 62.3 75

Operating point Sound, extract air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 363 52 56.8 46.2 37.5 38.0 31.8 22.4 45

2 625 150 60.6 52.4 43.0 42.6 36.1 27.8 49

3 818 260 64.9 59.3 49.2 47.9 40.9 33.9 55

Operating point Housing radiation

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 363 52 46.0 50.3 41.3 39.6 44.3 18.8 48

2 625 150 46.8 55.7 46.5 43.8 48.7 24.4 53

3 818 260 47.8 61.8 52.3 48.6 53.7 30.8 58

* ref Lw,0 = 10-12 W; 0 m distance.

Page 18: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

18

6.2 Technical data, ComfoAir XL 1500Specific fan power, pressure loss and sound level

■ Supply air max. line ■ Extract air max. line■ Cooler supply air, pre-heater and post-heater ● Sound level

Page 19: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

19

Operating point Sound, supply air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 881 86 68.4 76.5 66.3 64.9 66.1 60.7 73

2 1119 139 69.3 76.9 68.7 67.0 68.1 63.0 74

3 1528 260 71.3 77.7 74.0 71.8 72.7 68.2 78

Operating point Sound, extract air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 881 86 61.0 59.5 55.2 49.6 45.9 37.6 57

2 1119 139 61.8 61.7 57.4 51.5 47.6 39.6 59

3 1528 260 63.7 66.6 62.3 55.8 51.4 44.2 63

Operating point Housing radiation

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 881 86 53.5 62.0 49.3 45.2 52.3 30.1 57

2 1119 139 54.3 62.3 51.6 47.3 54.3 32.3 59

3 1528 260 56.3 63.2 57.0 52.0 58.8 37.5 62

* ref Lw,0 = 10-12 W; 0 m distance.

Page 20: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

20

6.3 Technical data, ComfoAir XL 2200Specific fan power, pressure loss and sound level

■ Supply air max. line ■ Extract air max. line■ Cooler supply air, pre-heater and post-heater ● Sound level

Page 21: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

21

Operating point Sound, supply air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 986 50 69.3 72.5 59.2 62.6 63.0 56.0 69

2 1498 116 72.0 76.8 69.8 71.0 71.0 65.2 77

3 2187 247 75.7 82.6 84.2 82.3 81.7 77.6 88

Operating point Sound, extract air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 986 50 60.1 63.6 49.5 49.3 41.4 33.8 57

2 1498 116 65.3 66.0 59.7 58.0 49.4 42.2 63

3 2187 247 72.4 69.3 73.4 69.6 60.2 53.6 74

Operating point Housing radiation

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 986 50 54.6 63.4 47.3 46.3 50.7 29.1 57

2 1498 116 57.3 67.7 57.9 54.7 58.6 38.3 64

3 2187 247 60.9 73.5 72.3 66.0 69.3 50.8 74

* ref Lw,0 = 10-12 W; 0 m distance.

Page 22: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

22

6.4 Technical data, ComfoAir XL 3300Specific fan power, pressure loss and sound level

■ Supply air max. line ■ Extract air max. line■ Cooler supply air, pre-heater and post-heater ● Sound level

Page 23: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

23

Operating point Sound, supply air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 1788 73 72.6 82.1 72.0 74.0 72.7 67.6 79

2 2623 158 77.0 87.5 79.1 81.0 79.5 74.7 86

3 3334 255 80.7 92.2 85.1 86.9 85.2 80.8 92

Operating point Sound, extract air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 1788 73 64.5 64.6 59.3 49.2 46.6 38.3 60

2 2623 158 66.4 72.4 67.4 56.5 53.0 45.4 68

3 3334 255 68.0 79.1 74.4 62.7 58.4 51.4 74

Operating point Housing radiation

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 1788 73 55.3 57.9 50.2 52.7 49.6 34.5 57

2 2623 158 59.7 63.3 57.2 59.6 56.3 41.6 63

3 3334 255 63.4 68.0 63.2 65.6 62.0 47.6 69

* ref Lw,0 = 10-12 W; 0 m distance.

Page 24: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

24

6.5 Technical data, ComfoAir XL 4400Specific fan power, pressure loss and sound level

■ Supply air max. line ■ Extract air max. line■ Cooler supply air, pre-heater and post-heater ● Sound level

Page 25: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

25

Operating point Sound, supply air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 2228 64 79.9 61.2 62.1 64.6 60.5 51.6 69

2 3261 137 82.3 87.0 81.5 83.5 80.4 74.8 87

3 4453 256 79.6 91.8 85.5 86.9 84.6 79.7 91

Operating point Sound, extract air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 2228 64 65.4 59.1 53.4 49.9 47.3 37.2 57

2 3261 137 74.2 77.7 67.8 64.8 63.1 55.9 73

3 4453 256 75.3 83.7 72.6 69.9 69.1 63.2 78

Operating point Housing radiation

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 2228 64 72.6 47.5 45.5 46.8 44.8 20.4 57

2 3261 137 74.9 73.3 64.9 65.7 64.7 43.6 71

3 4453 256 72.3 78.1 68.8 69.1 68.8 48.5 75

* ref Lw,0 = 10-12 W; 0 m distance.

Page 26: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

26

6.6 Technical data, ComfoAir XL 6000Specific fan power, pressure loss and sound level

■ Supply air max. line ■ Extract air max. line■ Cooler supply air, pre-heater and post-heater ● Sound level

Page 27: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

27

Operating point Sound, supply air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 3105 67 83.4 75.0 70.8 72.4 68.3 61.7 76

2 4592 146 83.8 85.1 79.3 80.8 76.4 70.5 85

3 5899 242 83.6 94.1 87.0 88.4 83.7 78.3 92

Operating point Sound, extract air

Qv

[m3/h]P

[Pa]125 Hz

[dB]250 Hz

[dB]500 Hz

[dB]1000 Hz

[dB]2000 Hz

[dB]4000 Hz

[dB]LwA*

dB(A)

1 3105 67 70.6 72.0 60.4 56.6 52.5 42.2 66

2 4592 146 75.4 78.8 68.2 65.1 61.2 51.9 73

3 5899 242 79.6 85.4 75.1 72.8 69.2 60.9 80

Operating point Housing radiation

Qv

[m3/h]P

[Pa]125Hz[dB]

250 Hz[dB]

500 Hz[dB]

1000 Hz[dB]

2000 Hz[dB]

4000 Hz[dB]

LwA*dB(A)

1 3105 67 78.1 65.5 57.5 57.6 56.7 30.4 65

2 4592 146 78.5 75.6 65.9 66.0 64.8 39.2 72

3 5899 242 78.3 84.6 73.6 73.6 72.1 47.0 80

* ref Lw,0 = 10-12 W; 0 m distance.

Page 28: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

28

7. AccessoriesSAG 0-3 VComfoAir XL keeps the air volume constant. Output can be programmed in three air volume stages via a display. The SAG 0-3 CV switch can then be used to select the stages high, medium and low.The housing is white (RAL 9010) and ideal for installation in a fitted housing with a depth of 40 mm. A surface-mounted housing is available for mounting.

CO2/ssensorComfoAir XL can also be controlled using a CO2

sensor. A CO2 sensor measures the CO2 concentration in the ambient air at the position to which it is attached. The CO2 sensor selects the air vent stage on the basis of the ventilation requirement in the room. If the CO2 concentration is high, the ventilation stage is increased automatically. If the CO2 concentration is low, the ventilation stage is reduced automatically.

Diaphragm siphonA diaphragm siphon does not have a gooseneck; instead it comprises a non-return valve made of silicone rubber, which opens as soon as water presses against the membrane and closes again due to the vacuum in the unit. The siphon can be equipped on request with a heating cable to protect against frost or the formation of ice.

Siphon heaterSiphons are sensitive to frost. Siphon heating reduces the risk of frost damage.

Joining pieceAll units are delivered with rectangular connections and tubtaras. They can be used to connect a drain from rectangular to round.

Page 29: Technical documentation ComfoAir XL 800-6000 The · PDF fileTechnical documentation ComfoAir XL 800-6000 The latest generation of ventilation units with heat recovery. 2 ... 2.3 High-performance

Zehnder Group Deutschland GmbH · Sales International · Almweg 34 · 77933 Lahr · Germany T +49 7821 586-392 · F +49 7821 586-406 [email protected] · www.international.zehnder-systems.com

Z_S

I_V

0414

_CS

Y_D

AS

_Com

foA

irXL,

en,

sub

ject

to

chan

ge w

ithou

t no

tice