TMCOMPACT DEHUMIDIFIER - VICTORY PLUS SERIES SPECIFICATION
*Note:- Other voltage options available are 200/220/240/380/440/460 VAC, 1Ph/3Ph, 50/60 Hz
MODEL
TM VICTORY PLUS 200TM VICTORY PLUS 420TM VICTORY PLUS 700TM VICTORY PLUS 1000TM VICTORY PLUS 1500TM VICTORY PLUS 2000
PROCESS
AIR FLOW
(CMH)
200
420
700
1000
1500
2000
PROCESS
ESP
(Pa.)
200
200
200
200
200
200
PROCESS
MOTOR
(KW)
0.24
0.24
0.3
0.3
1.6
1.6
REACT.
AIR FLOW
(CMH )
39
83
138
197
295
393
REACT.
ESP
(Pa.)
200
200
200
200
200
200
REACT.
MOTOR
(KW)
0.12
0.12
0.15
0.15
0.3
0.3
REACT.
HEATER
(KW)
1.4
2.8
4.8
7.2
10.8
13.9
POWER *
REQD.
(v/Ø/Hz.)
230 /1/ 50
230 /1/ 50
415 /3/ 50
415 /3/ 50
415 /3/ 50
415 /3/ 50
APPROX.
WEIGHT
(Kg.)
60
70
130
135
290
290
NOISELEVEL
AT 3 METRE
dB(A)
66
66
66
66
66
66
High Efficiency and Reliability
§ A totally self contained unit with compatibility for both 100 mm and 200 mm deep rotors
§ Rotor media consisting of high performance metal silicates
§ Rotor incorporating robust internal structure with stainless steel (SS 304) perimeter flange for industrial quality, durability and easy serviceability
§ Extended media and seal life by rotor perimeter flange
§ Edge hard face coating on rotor ensuring longer life and good sealing for media and seals
§ Non-flammable rotor with organic < 2%
§ Insulated process and reactivation air flow sectors
§ Unique teflon coating with silicon seal design for minimum air leakage
§ Speed controlled brushless/EC fans
§TM Process fan with brushless DC motors for Victory Plus 200,
420, 700 and 1000 models on sliding plate for easy access
§TMProcess fan with EC motors in Victory Plus 1500 and 2000
models on sliding plate for easy access
§ CNC fabricated unit(s) with stainless steel (SS 304) construction
§TMPTC heaters for Victory Plus 200 and 420 models
§ Fully automated operation using PLC
§ Access and maintenance to components from operation side only
§ Integrated bypass purge air
Necessary Controls and Safety
§ Differential air pressure switch for providing react air flow for TMVictory Plus 700 and above models
§ Thermostat cutout for safety from high temperature present in TMVictory Plus 700 and above models
§ Microprocessor based controller for easy operation and multiple options
§ Electrical interlocking of fan motors, heaters and rotor drive for better synchronization
Options
§ Humidity control through digital humidistat
§ Measuring and display differential pressure or air flow
§ Touch screen panel for smooth and quick operation
§ Weatherproof design
§ Pre and post cooling modules
§ Temperature display for process inlet/outlet & react outlet
§ Airflow % display
§ Output: 3 x 0.10V (extra;control valve, SCR)
§ PID regulator for variable process air flow
§ PID regulator for control valves and heaters
§ Modbus communication
Easy to Install
§ Several mounting and installation options
§ Small footprints: low volume/weight per CMH
Easy to Operate
§ Specially designed for longer and uninterrupted operations
Easy to Maintain
§ Quick and easily serviceable
§ Water washable rotor
FEATURE HIGHLIGHTS
www.bryair.com
Technical Data Sheet
TM
series
Compact Dehumidifier
Note : All dimensions in mm.
MODELUNIT DIMENSIONAL DATA
Inlet Outlet
Process DuctConnection
Reactivation DuctConnection
F
125
150
250
250
352
352
G
125
150
250
250
352
352
Inlet
H
75
125
150
150
200
200
Outlet
I
75
125
150
150
200
200
A
665
665
774
774
1118
1118
B
630
670
878
878
1180
1180
C
400
460
664
664
911
911
D
410
450
654
654
500
500
E
150
150
150
150
600
600
TM VICTORY PLUS 200TM VICTORY PLUS 420TM VICTORY PLUS 700TM VICTORY PLUS 1000TM VICTORY PLUS 1500TM VICTORY PLUS 2000
Due to constant upgradation, data subject to change without notice
DATA & DUCT CONNECTION DIMENSIONS (mm)
1. Process Air Inlet2. Process Air Outlet3. Reactivation Air Inlet4. Reactivation Air Outlet
Victory Plus 1500 & 2000TM
1
3
2
4
B
F
H
G
A C
D
E
Victory Plus 200 to 1000TM
Technical Data Sheet
TM
series
Compact Dehumidifier
* The performance chart shown is for 100 mm deep rotor
Performance charts are for nominal process airflow within the TMoperating range each Victory Plus series with the assumption
WPI = WRI. Please consult Bry-Air for other specific condition.
PERFORMANCE CHART
Example :-
Conditions:Process inlet w PI = 12g/kgProcess inlet T PI. = 20 °C
Chart Data :-Process outlet w PO = 4.4g/kgProcess outlet T PO. = 42 °C
PR
OC
ES
S O
UT
LE
T A
IR M
OIS
TU
RE
CO
NT
EN
T w
PO
(g/k
g)
PROCESS INLET AIR MOISTURE CONTENT wPI(g/kg)
0P
RO
CE
SS
OU
TL
ET
AIR
DB
TE
MP
ER
AT
UR
E T
PO
(C
)
Due to constant upgradation, data subject to change without notice
TECHNICALDATA SHEET
Bulletin: BAA : D0060Effective: SEP. 13, 2016Supercedes: BAA : D0060 Dated: MAR. 30, 2016
Reach us at:Contact: +91 8130237917
Email: [email protected]
www.bryair.com
©, ® & ‘TM’ of Bry-Air (Asia) Pvt. Ltd.TM
Corporate Office & Plant II 21C, Sector-18, Gurgaon 122015, INDIAPhone: +91-124-4091111Fax: +91-124-4091100E-mail: [email protected]
Int’l. Sales Office & Plant I419-420, Udyog Vihar, Phase-III, Gurgaon 122016, INDIAPhone: +91-124-4184444Fax: +91-124-4184400E-mail: [email protected].: www.bryair.com
BRY-AIR (USA)E-mail: [email protected] (MALAYSIA)Email: [email protected] (CHINA)E-mail: [email protected] PROKON GmbH (EUROPE) E-mail: [email protected] (BRAZIL)E-mail: [email protected] (NIGERIA)E-mail: [email protected]