technical data
FAQ-BVV1B
Wall Mounted Unit
air conditioning systems
SplitSky Air
� Split Sky Air � Indoor Units 1
� Indoor Units � R-410A � FAQ-BVV1B
TABLE OF CONTENTSFAQ-BVV1B
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 For indoor units only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 8Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Sound level data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10 Air flow pattern. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
11 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
� Indoor Units � R-410A � FAQ-BVV1B
1
� Split Sky Air � Indoor Units2
1 Features
Indoor Unit Split Sky FAQ-BVV1B R-410A � Lightweight and compact
� Ideal for shops, restaurants or offices requiring maximum floor space for furniture, decorations and fittings
� Fits neatly on a wall
� Nice design and very compact casing
� Both horizontal flaps and front panel can easily be removed and washed
� Auto-swing function ensures efficient air distribution via louvers that close automatically when the unit is switched off
� Extremely quiet in operation
� Easy to install
� Daikin remote controls give you easy control at your fingertips.
� The wired remote control provides you with a schedule timer, enabling to program the air conditioning daily or weekly.
� The optional remote ON/OFF enables you to start/stop the air conditioning from a mobile phone via a telephone remote control (field supply).
� The optional forced OFF enables you to switch off the unit automatically. E.g. when a window is opened, the unit switches off.
� The �home leave� operation button prevents large temperature differences by continuously operating at a minimum (heating mode) or maximum (cooling mode) preset level while you�re out or sleeping. It also allows the indoor temperature to return quickly to your favourite comfort level.
heat pump optional 2 steps optional
optional
2
� Split Sky Air � Indoor Units 3
� Indoor Units � R-410A � FAQ-BVV1B
2 Specifications
2-1 FOR INDOOR UNITS ONLY FAQ71BVV1B FAQ100BVV1B
Nominal Input Cooling kW 0.068 0.101Heating kW 0.068 0.101
2-2 TECHNICAL SPECIFICATIONS FAQ71BVV1B FAQ100BVV1B
Casing Colour WhiteMaterial Resin
Dimensions Packing Height mm 366 483Width mm 1147 1740Depth mm 337 299
Unit Height mm 290 360Width mm 1050 1570Depth mm 230 200
Weight Unit kg 13.0 26.0Packed Unit kg 17.0 34.0
Heat Exchanger
Dimensions Length mm 863 1320Nr of Rows 2 2Fin Pitch mm 1.40 1.40Nr of Passes 4 9Face Area m² 0.289 0.332Nr of Stages 16 12Empty Tubeplate Hole
2
Tube type Hi-XA N-HixFin Type Cross fin coil (Multi louver fins and HI-XA tubes) Cross fin coil (Multi louver fins and N-hix tubes)
Fan Type Cross flow fanQuantity 1 1
Air Flow Rate Cooling High m³/min 19.0 23.0Low m³/min 15.0 19.0
Heating High m³/min 19.0 23.0Low m³/min 15.0 19.0
Fan Motor Quantity 1 1Model QCL9686M QCL1163MA+QCL1163MBNumber of steps 2 2Output (high)
W 43 49
Cooling Sound Power High dBA 59.0 61.0Low dBA 53.0 57.0
Sound Pressure
High dBA 43.0 45.0Low dBA 37.0 41.0
Heating Sound Power High dBA 59.0 61.0Low dBA 53.0 57.0
Sound Pressure
High dBA 43.0 45.0Low dBA 37.0 41.0
Refrigerant Type R-410APiping connections
Liquid (OD) Type Flare connectionDiameter (OD)
mm 9.5 9.5
Gas Type Flare connectionDiameter (OD)
mm 15.9 15.9
Drain Diameter (OD)
mm VP13 (I.D. 13/O.D. 18) VP20 (I.D. 20/O.D. 26)
Heat Insulation Foamed polystyrene/polyethyleneSafety Devices PC board fuse
� Indoor Units � R-410A � FAQ-BVV1B
2
� Split Sky Air � Indoor Units4
2 Specifications
Standard Accessories
Item Installation and operation manualQuantity 1 1Item Paper pattern for installation
Insulation tapeInstallation panel
ScrewsInsulation for fitting
Notes The sound pressure level is measured via a microphone at 1m distance of the unit.Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please
refer to sound level drawings of this chapter.The sound power level is an absolute value indicating the power which a sound source generates.
2-3 ELECTRICAL SPECIFICATIONS FAQ71BVV1B FAQ100BVV1B
Power Supply Phase V1 V1Frequency Hz 50 50Voltage V 220-240
Power Supply Intake Outdoor unit only
2-2 TECHNICAL SPECIFICATIONS FAQ71BVV1B FAQ100BVV1B
3
3
� Split Sky Air � Indoor Units 5
� Indoor Units � R-410A � FAQ-BVV1B
3 Safety device settings
FAQ71-100B
Model Safety devices FAQ71B FAQ100B
FAQ∼B
Fuse − −Fan motor thermal fuse (°C) − −
Fan motor thermal protector (°C) − OFF: 130±5ON: 83±20
DU423-9101L
� Indoor Units � R-410A � FAQ-BVV1B
4
� Split Sky Air � Indoor Units6
4 Options
Optional accessories FAQ71B FAQ100B
Remote control Wired BRC1D528
Infrared type Heat pump BRC7EA618 BRC7CA510W
Cooling only BRC7EA619 BRC7CA511W
Wiring adapter for electrical appendices (2)* *KRP4AA51
Installation box for adapter PCB KRP4AA93 -
Central remote control DCS302CA51
Electrical box with earth terminal (3 blocks) KJB311AA
Unified ON/OFF control DCS301BA51
Electrical box with earth terminal (2 blocks) KJB212AA
Noise filter (for electromagnetic interface use only) KEK26-1A -
Schedule timer DST301BA51
Interface adapter for Sky Air series - DTA112BA51
Remote sensor KRCS01-1A -
Drain up kit K-KDU572CVE -
Connector for forced on, forced off - EKROROA
3D044482A
Note:
1. Installation box (KRP4AA93) is necessary for each adapter marked*
3
5
� Split Sky Air � Indoor Units 7
� Indoor Units � R-410A � FAQ-BVV1B
5 Control systems
3TW23651-2
6.5 x 9 (Round end slit)
Cover open
Cover closed
5 x 7 (Round end slit) HoleJ5
5 x 10 (Round end slit)
BRC1D527
� Indoor Units � R-410A � FAQ-BVV1B
6
� Split Sky Air � Indoor Units8
6 Dimensional drawing & centre of gravity6 - 1 Dimensional drawing
3D038540C
unit (mm)
50or
mor
e30
orm
ore
(Req
uire
dsp
ace)
J80 hole
approx. 345
approx. 475
FAQ71B
approx. 400
Mounting location
approx. 390
Piping direction
(Required space)
50 or more
Dimensions forfull open frontpanel
Outside line
J80 hole
(piping and wiringintake)
2500 or moreFor installation in high
spaces
(Req
uire
dsp
ace)
120 or less
1 Front panel2 Front grille3 Air outlet4 Gas pipe (J15.9 Flare connection)5 Liquid pipe (J9.5 Flare connection)6 Drain hose VP13 (External dia J18)7 Grounding terminal (M4)8 Right side piping connection hole9 Left side drain piping connection hole
Notes:1 Location of general rated name plate
Right side plate outside surface2 In case of using infrared remote control,
this position will be a signal receiver.Refer to the drawing of infrared remotecontrol in detail.
Name plate
50 or more
Piping directionNote) 2
Piping direction
(Required space)
3D044897A
unit (mm)
50or
mor
e
250 or more
(Req
uire
dsp
ace)
J80 hole
approx. 450
approx. 600
FAQ100B
8-5x20 Oval hole (for wood screw)
Mounting locationDetailjA (Mounting hole for installation plate)
approx. 580
Piping direction
(Required space)
50 or more50 or more
(Required space)
5-6x20 Oval hole (for wood screw)
13-J5 Hole (for wood screw)
2-J12 Hole (for bolt)(piping and wiringintake)
Note 2. (service space for air filter)
Direction for air filter draw out
1 Front grille2 Air filter3 Discharge outlet4 Gas piping connection (J15.9 flare)5 Gas piping connection (J9.5 flare)6 Drain pipe connection (VP20 O.D. J26)7 Earth terminal(M4) (inside cover)8 Slit hole for right side piping connection9 Slit hole for left side piping connection
Notes:1 Location of general rated name plate
Right side plate outside surface2 In case of using infrared remote control, this
position will be a signal receiver. Refer to thedrawing of infrared remote control in detail.
Brand name plate
Ceiling surface
7
� Split Sky Air � Indoor Units 9
� Indoor Units � R-410A � FAQ-BVV1B
7 Piping diagram
4D037995B
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
Indoor heat exchanger
Field piping J9. 5C1220T-0
FAQ71-100B
Field piping J15.9C1220T-0
Refrigerant pipe connection port diameters
Model A BFAQ71, 100B J 9.5 J 15.9
To outdoor unit
Indoor unit
� Indoor Units � R-410A � FAQ-BVV1B
8
� Split Sky Air � Indoor Units10
8 Wiring diagram8 - 1 Wiring diagram
3D043881A
FAQ71B
A1P Printed circuit boardHAP Light emitting diode (service monitor green)M1S Motor (swing flap)M1F Motor (indoor fan)R1T Thermistor (air)R2T Thermistor (coil)SS1 Selector switch (emergency)X1M Terminal blockX2M Terminal block
Power supply? Signal receiver circuit. Signal transmission circuit
Infrared remote controlReceiver / display unitA2P Printed circuit boardA3P Printed circuit boardBS1 Push button (on/off)H1P Light emitting diode (on-red)H2P Light emitting diode (timer-green)H3P Light emitting diode (filter sign-red)H4P Light emitting diode (defrost-orange)SS1 Selector switch (main/sub)SS2 Selector switch (wireless address set)
Connector for optional partsX15A Connector (float switch)X35A Connector (group control adapter)Wired remote controlR1T Thermistor (air)SS1 Selector switch (main/sub)
To outdoorunit
Note) 4
In case of simultaneousoperation system.
Toou
tdoo
runi
t
Notes
1. D : Terminal, F : Connector, : Field wiring2. In case using central remote control, connect it to the
unit in accordance with the attached instructionmanual.
3. Remote control model varies according to thecombination system, confirm technical materials andcatalogs, etc. before connecting.
4. X24A is connected when the infrared remote controlkit is being used.
5. Shows short circuit connector6. Symbols show as follows Red:red, Blk:black, Ylw:yellow,
Org:orange, Gry:gray, Prp:purple, Blu:blue7. Confirm the method of setting the selector switch (SS1,
SS2) by installation manual and engeneering materials,etc.
Receiver / display unit (attached to infrared remote control)
Note) 4
Indoor unit(master)
Indoor unit(slave)
Remote control
Norm. Emerg.
Note) 2
Transmission wiringcentral remote control
Wired remote control
Control box
SIDE FRONT
ON/OFF input from outside
3D044228A
FAQ100B
A1P Printed circuit boardA2P Printed circuit board
(Transformer) 230V/16V)C1R Capacitor (M1F)HAP Light emitting diode (service monitor green)KAR Magnetic relay (M1S)KPR Magnetic relay (M1P)M1F Motor (indoor fan)M1S Motor (swing flap)Q1M Thermo switch (M1F embedded)R1T Thermistor (air)R2T Thermistor (coil)
S1Q Limit switch (swing flap)SS1 Selector switch (emergency)V1TR Phase control circuitX1M Terminal blockX2M Terminal block? Signal receiver circuit. Signal transmission circuitWired remote controlR1T Thermistor (air)SS1 Selector switch (main/sub)
Infrared remote controlReceiver / display unitA3P Printed circuit boardA4P Printed circuit boardBS1 Push button (on/off)H1P Light emitting diode (on-red)H2P Light emitting diode (timer-green)H3P Light emitting diode (filter sign-red)H4P Light emitting diode (defrost-orange)SS1 Selector switch (main/sub)SS2 Selector switch (wireless address set)
Connector for optional partsX15A Connector (float switch)X25A Connector (drain pump)X35A Connector (group control adapter)X16AX61A
Connector (interface adapter for sky air series)
To outdoorunit
Note) 4
Wired remotecontrol
Control box
In case of simultaneousoperation system.
Toou
tdoo
runi
t
Notes
1. D : Terminal F, : Connector2. : Field wiring3. In case using central remote control, connect it to
the unit in accordance with the attachedinstruction manual.
4. X24A is connected when the infrared remotecontrol kit is being used.
5. Remote control model varies according to thecombination system, confirm technical materialsand catalogs, etc. before connecting.
6. Symbols show as follows Red:red, Blk:black,Ylw:yellow, Org:orange, Gry:gray, Prp:purple,Blu:blue
7. Confirm the method of setting the selectorswitch (SS1, SS2) by installation manual andengeneering materials, etc.
8. x15A, x25A are connected when the drain up kitis being used. Connect it to the kit in accordancewith the attached installation manual.
Receiver / display unit
Note) 4
Indoor unit(master)
Indoor unit(slave)
Infrared remotecontrol
Emerg.Norm.
Note) 8
8
� Split Sky Air � Indoor Units 11
� Indoor Units � R-410A � FAQ-BVV1B
8 Wiring diagram8 - 2 External connection diagram
4D044475
V1, ModelPower supply1∼50Hz220V-240V
Main switch
Fuse Fuse
NOTES1 Line voltage wiring
Control circuit wiring2 All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.3 Use copper conductors only.4 See wiring diagrams for details.5 Install fuse and mainswitch for safety.6 All field wiring and components must be provided by a licensed electrician.7 The unit shall be grounded in compilance with the applicable local and national codes.8 Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific
installation.9 Never share a common power supply with other equipment.
V3, ModelPower supply1∼50Hz230V
Main switch
� Indoor Units � R-410A � FAQ-BVV1B
9
� Split Sky Air � Indoor Units12
9 Sound data9 - 1 Sound level data
Microphone
Model
Sound pressure level
Sound power level230V
Measuring location50Hz
CoolingH/L
HeatingH/L
CoolingH/L
HeatingH/L
FAQ71B 43/37 43/37 45/41 45/41
FAQ100B 59/53 59/53 61/57 61/57
9
� Split Sky Air � Indoor Units 13
� Indoor Units � R-410A � FAQ-BVV1B
9 Sound data9 - 2 Sound pressure spectrum
4D038512C
Oct
ave
band
soun
dpr
essu
rele
vel
Octave band center frequency (Hz)
FAQ71B (Cooling/Heating)
approximatethreshold hearingfor continuousnoise
H (230V)
L (230V)
Note:1. Sound pressure levels are measured in an anechoic room.2. Data are valid at nominal operation conditions.3. Operation sound level differs with operation and ambient conditions.
4D027787B
FAQ100B (Cooling)
Oct
ave
band
soun
dpr
essu
rele
vel
Octave band center frequency (Hz)
approximatethreshold hearingfor continuousnoise
H (230V)
L (230V)
Note:1. Sound pressure levels are measured in an anechoic room.2. Data are valid at nominal operation conditions.3. Operation sound level differs with operation and ambient conditions.
4D027790B
FAQ100B (Heating)
Oct
ave
band
soun
dpr
essu
rele
vel
Octave band center frequency (Hz)
approximatethreshold hearingfor continuousnoise
H (230V)
L (230V)
Note:1. Sound pressure levels are measured in an anechoic room.2. Data are valid at nominal operation conditions.3. Operation sound level differs with operation and ambient
conditions.
� Indoor Units � R-410A � FAQ-BVV1B
10
� Split Sky Air � Indoor Units14
10 Air flow pattern
4D039573B
FAQ71B
Cooling - air velocity distribution
Air flow direction: 10° (downward)
FAQ71B
Cooling - air temperature distribution
Air flow direction: 10° (downward)
3
10
� Split Sky Air � Indoor Units 15
� Indoor Units � R-410A � FAQ-BVV1B
10 Air flow pattern
4D028547B
FAQ100B
Cooling - air velocity distribution
Air flow direction: 10° (downward)
FAQ100B
Cooling - air temperature distribution
Air flow direction: 10° (downward)
� Indoor Units � R-410A � FAQ-BVV1B
10
� Split Sky Air � Indoor Units16
10 Air flow pattern
4D039574B
FAQ71B
Heating - air velocity distribution
Air flow direction: 65°C (downward)
FAQ71B
Heating - air temperature distribution
Air flow direction: 65°C (downward)
10
� Split Sky Air � Indoor Units 17
� Indoor Units � R-410A � FAQ-BVV1B
10 Air flow pattern
4D028548B
FAQ100B
Heating - air velocity distribution
Air flow direction: 65°C (downward)
FAQ100B
Heating - air temperature distribution
Air flow direction: 65°C (downward)
� Indoor Units � R-410A � FAQ-BVV1B
11
� Split Sky Air � Indoor Units18
11 Installation11 - 1 Installation method
Names and functions of partsja Indoor unitjb Outdoor unitjc Infrared remote controljd Inlet airje Discharged airjf Air outletjg Air flow flap (at air outlet)jh Refrigerant piping, connection electric wireji Drain pipejj Air inlet
The built-in air filter removes dust and dirt.jk Ground wire
Wire to ground from the outdoor unit to prevent electrical shocks.
ISO14001 assures an effective environmental management system in order to help protect human•health•and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the•environment.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin units comply with the Europeanregulations that guarantee the safety ofthe product.
Zandvoordestraat 300B-8400 Ostend - Belgiumwww.daikineurope.com EE
DE0
6-1/
3 •
05/2
006
Prep
ared
in B
elgi
um b
y La
nnoo
The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..
ÉEEDE06-1/3ÇËÍ
Split - Sky Air
Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products.