74
Technical Committee on Water Additives for Fire Control and Vapor Mitigation (WAB-AAA) Memorandum DATE: April 28, 2016 TO: Principal and Alternate Members of the Technical Committee on Water Additives for Fire Control and Vapor Mitigation (WAB – AAA) FROM: Jacqueline Wilmot, Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AGENDA PACKAGE – NFPA 18/18A/1150 Second Draft Meeting (F2016) Enclosed is the agenda for the NFPA 18/18A/1150 Second Draft meeting of the Technical Committee on Water Additives for Fire Control and Vapor Mitigation, which will be held on Thursday, April 28, via teleconference. Please review the attached public comments in advance, and if you have alternate suggestions, please come prepared with proposed language and respective substantiation. If you have any questions prior to the meeting, please do not hesitate to contact me at: Office: (617) 984-7498 E-mail: [email protected] For administrative questions, please contact Sarah Caldwell at (617) 984 -7950. I look forward to working with everyone.

Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Technical Committee on Water Additives for Fire Control and Vapor

Mitigation (WAB-AAA)

Memorandum

DATE: April 28, 2016 TO: Principal and Alternate Members of the Technical Committee on Water Additives for Fire

Control and Vapor Mitigation (WAB – AAA) FROM: Jacqueline Wilmot, Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AGENDA PACKAGE – NFPA 18/18A/1150 Second Draft Meeting (F2016)

Enclosed is the agenda for the NFPA 18/18A/1150 Second Draft meeting of the Technical

Committee on Water Additives for Fire Control and Vapor Mitigation, which will be held on

Thursday, April 28, via teleconference. Please review the attached public comments in

advance, and if you have alternate suggestions, please come prepared with proposed language

and respective substantiation.

If you have any questions prior to the meeting, please do not hesitate to contact me at: Office: (617) 984-7498 E-mail: [email protected] For administrative questions, please contact Sarah Caldwell at (617) 984 -7950. I look forward to working with everyone.

Page 2: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Technical Committee on Water Additives for Fire Control and Vapor Mitigation (WAB-AAA)

NFPA 18/18A/1150 Second Draft Meeting (Fall 2016)

Thursday, April 28, 2016

Teleconference/Web Meeting

AGENDA

1. Call to Order – 11:00AM EST

2. Introduction and Attendance

3. Chairman Comments

4. Approval of Previous Meeting Minutes

5. Staff Liaison Presentation on NFPA’s new Revision Process and F2016 Cycle

6. Review of Public Comments, and development of Second Revisions for NFPA 18 and NFPA 18A

7. New Business

8. Adjourn Meeting – TBA

Please submit requests for additional agenda items to the chair and staff liaison at least seven days prior to the meeting.

Page 3: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Technical Committee on Water Additives for Fire Control and Vapor Mitigation (WAB-AAA)

NFPA 18/18A/1150 Second Draft Meeting (Fall 2016)

Thursday, April 28, 2016

Teleconference/Web Meeting

Key Dates for the Fall 2016 Revision Cycle

Final Date for First Draft Meeting June 15, 2015 Posting of First Draft and TC Ballot August 3, 2015 Final date for Ballot Return August, 24, 2015 Post First Draft Report for Public Comment September 7, 2015 Public Comment Closing Date November, 16, 2015 Final Date for Second Draft Meeting May 2, 2016 Posting of Second Draft and TC Ballot June 13, 2016 Final Date for Ballot Return July 5, 2016 Final Second Draft Posted July 18, 2016 Closing Date for Notice of Intent to Make a Motion (NITMAM) August 22, 2016 Issuance of Consent Document (No NITMAMs) November 11, 2016 NFPA Annual Meeting June 2016 Issuance of Document with NITMAM August 10, 2017 Technical Committee deadlines are in bold.

Page 4: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Wednesday 3 9, Wednesday

Water Additives for Fire Control and Vapor MitigationWAB-AAAName Representation Class Office

Distribution by %

Company

Armand V. Brandao FM Approvals FM I Chair

Brian R. Foster AEGIS Insurance Services, Inc. I Principal

Walter Groden AIG Property Casualty I Principal

3Voting Number Percent 25%

Michael T. Greiner Hazard Control Technologies, Inc. M Secretary

Alison C. Gude Tyco Fire Suppression & BuildingProducts

TYCO M Principal

Gerald J. Halpin III CET Fire Pumps Manufacturing FAMA M Principal

Robert E. Tinsley, Jr. Pyrocool Technologies, Inc. M Principal

4Voting Number Percent 33%

Cecilia W. Johnson USDA Forest Service RT Principal

Blake M. Shugarman UL LLC UL RT Principal

2Voting Number Percent 17%

John D. Campbell NRG Fire Consulting SE Principal

Qingsheng Wang Oklahoma State University SE Principal

2Voting Number Percent 17%

Tracy Browder XCEL Energy EEI U Principal

1Voting Number Percent 8%

12Total Voting Number

Page 5: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Technical Committee on Water Additives for Fire Control and Vapor Mitigation (WAB-AAA)

NFPA 18/18A/1150 Second Draft Meeting (Fall 2016)

Thursday, April 28, 2016

Teleconference/Web Meeting

Staff Liaison Notice

Note from the Staff Liaison Dear Technical Committee Members: We are very pleased that you will be participating in the processing of the 2017 Edition of NFPA 18, 18A and 1150. Development of this document would not be possible without the participation of volunteers like you. Thank you! Meeting Preparation Committee members should review the published comments prior to the meeting and to be prepared to act on each item. Handout materials should be submitted to the chair and staff liaison at least seven days prior to the meeting. Only one posting of the Public Comments will be made; it will be arranged in section/order and will be pre-numbered. This will be posted to the NFPA 18/18A/1150 Document Information page (www.nfpa.org/18; www.nfpa.org/18A; www.nfpa.org/1150) under the “Next Edition” tab. If you are having trouble accessing the website, please contact Sarah Caldwell at [email protected] Mandatory Materials:

Last edition of the standard Meeting agenda Public Comments Committee Officer’s Guide (Chairs) Roberts’ Rules of Order (Chair; An abbreviated version may be found in the

Committee Officer’s Guide) Optional Materials:

Page 6: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

NFPA Annual Directory NFPA Manual of Style

Regulations and Guiding Documents All committee members are expected to behave in accordance with the Guide for the Conduct of Participants in the NFPA Codes and Standards Development Process. All actions during and following the committee meetings will be governed in accordance with the Regulations Governing the Development of NFPA Standards. Failure to comply with these could result in challenges to the standards-making process. A successful challenge on procedural grounds could prevent or delay publication of the document. The style of the document must comply with the Manual of Style for NFPA Technical Committee Documents.

Page 7: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Technical Committee on Water Additives for Fire and Vapor Mitigation (WAB-AAA)

NFPA 18/18A/1150 Second Draft Meeting (Fall 2016)

Thursday, April 28, 2016

Teleconference/Web Meeting

General Procedures for Meetings

Use of tape recorders or other means capable of producing verbatim transcriptions of any NFPA Committee Meeting is not permitted.

Attendance at all NFPA Committee Meetings is open. All guests must sign in and identify their affiliation.

Participation in NFPA Committee Meetings is generally limited to committee members and NFPA staff. Participation by guests is limited to individuals, who have received prior approval from the chair to address the committee on a particular item, or who wish to speak regarding public proposals or comments that they submitted.

The chairman reserves the right to limit the amount of time available for any presentation.

No interviews will be allowed in the meeting room at any time, including breaks.

All attendees are reminded that formal votes of committee members will be secured by letter ballot. Voting at this meeting is used to establish a sense of agreement, but only the results of the formal letter ballot will determine the official action of the committee.

Note to Special Experts: Particular attention is called to Section 3.3(e ) of the NFPA Guide for Conduct of Participants in the NFPA Codes and Standards Development Process in the NFPA Directory. This section requires committee members to declare any interest they may represent, other than their official designation as shown on the committee roster. This typically occurs when a special expert is trained by and represents another interest category on a particular subject. If such a situation exists on a specific issue or issues, the committee member shall declare those interest to the committee and refrain from voting on any action relating to those issues.

Smoking is not permitted at NFPA Committee Meetings.

Page 8: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

NFPA 18/18A/1150 Technical Committee on Water Additives for Fire Control and Vapor Mitigation

First Draft Meeting - April 28-29, 2015 Four Points Sheraton

Norwood, MA

Minutes of Meeting

Attendees:

See attached attendance.

NFPA Liaison:

Jacqueline R. Wilmot

1. Meeting was called to order to order at 8:05 AM EST, Tuesday, May 28th, 2015.

2. Attendance was completed.

3. Armand Brandao, Chair, reviewed the agenda and provided introductory and procedural information.

4. Staff Liaison Jacqueline Wilmot provided a brief presentation covering committee member responsibilities, actions, revision cycle and the upcoming new process.

5. The meeting minutes of April 27, 2010 were reviewed and accepted.

6. NFPA Research Division provided presentation on how the Research Foundation, One Stop Data Shop and Library can assist the Technical Committee.

7. The committee proceeded to review and act on public inputs.

8. Committee input was created for NFPA 18

9. The Research Foundation Report titled: “Evaluation of Water Additives for Fire Control and Vapor Mitigation – Phase II, Two and Three Dimensional Class B Fire Tests” was reviewed.

10. Following Task Groups Created:

Task Group TG Chair Members

Deep Seated Class A Fires – Finalize FR-13

Brian Foster Walter Groden, Robert Taylor

Class C Fire – Finalize FR-17 Anthony Natale

Test Matrix Armand Brandao

Page 9: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

11. Follow-up Meeting scheduled for June 3, 2015 from 1PM EST – 4PM EST via teleconference

12. New Business

13. Meeting adjourned at 4 PM EST, Tuesday April 29, 2015.

 

Page 10: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

NFPA 18/18A/1150 Technical Committee on Water Additives for Fire Control and Vapor Mitigation

First Draft Meeting Follow-Up - June 3, 2015 Teleconference/Web Meeting

Minutes of Meeting

Attendees:

See attached attendance.

NFPA Liaison:

Jacqueline R. Wilmot

1. Meeting was called to order to order at 8:05 AM EST, Wednesday, June 3, 2015.

2. Attendance was completed.

3. Armand Brandao, Chair, reviewed the agenda and provided introductory and procedural information.

4. The Task Groups reported findings to the Technical Committee.

5. First Revisions were created for NFPA 18A

Task Group TG Chair Members

Deep Seated Class A Fires – Finalize FR-13

Brian Foster Walter Groden, Robert Taylor

Class C Fire – Finalize FR-17 Anthony Natale

Test Matrix Armand Brandao

6. Follow-up Meeting scheduled for July 8, 2015 from 1PM EST – 4PM EST via teleconference

7. New Business

8. Meeting adjourned at 4 PM EST, Wednesday, June 3, 2015

 

Page 11: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

NFPA 18/18A/1150 Technical Committee on Water Additives for Fire Control and Vapor Mitigation

First Draft Meeting Follow-Up - July 8, 2015 Teleconference/Web Meeting

Minutes of Meeting

Attendees:

See attached attendance.

NFPA Liaison:

Jacqueline R. Wilmot

1. Meeting was called to order to order at 1PM EST, July 8, 2015.

2. Attendance was completed.

3. Armand Brandao, Chair, reviewed the agenda and provided introductory and procedural information.

4. The Task Group on Class C Fire Test Methods Reported to Technical Committee 5. First Revisions were created for NFPA 18A

Task Group TG Chair Members

Class C Fire – Finalize FR-17 Anthony Natale

6. New Business

7. Meeting adjourned at 2:30 PM EST, Wednesday, July 8, 2015

 

Page 12: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

 

 

 

NFPA 18 Public Comment 

Page 13: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 1-NFPA 18-2015 [ Chapter 2 ]

Chapter 2 Referenced Publications

2.1 General.

The documents or portions thereof listed in this chapter are referenced within this standard andshall be considered part of the requirements of this document.

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2016 edition.

NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2017 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire ProtectionSystems, 2017 edition.

NFPA 1150, Standard on Foam Chemicals for Fires in Class A Fuels, 2017 edition.

NFPA 1901, Standard for Automotive Fire Apparatus, 2016 edition.

2.3 Other Publications.

2.3.1 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM D97, Standard Test Method for Pour Point of Petroleum Products, 2012.

ASTM D323, Standard Test Method for Vapor Pressure of Petroleum Products (Reid Method),2014.

ASTM D1293, Standard Test Methods for pH of Water, 1999 ( 2012) .

ASTM D1331, Standard Test Methods for Surface and Interfacial Tension of Solutions of Surface-Active Agents, 1989, reapproved2014 reapproved 2014 .

ASTM D2196, Standard Test Methods for Rheological Properties of Non-Newtonian Materials byRotational (Brookfield type) Viscometer, 2015.

ASTM E729, Standard Guide for Conducting Acute Toxicity Tests on Test Materials with Fishes,Macroinvertebrates, and Amphibians, 1996 (2014) , reapproved 2011 .

ASTM G1, Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens,2011.

ASTM G31, Standard Practice for Laboratory Immersion Corrosion Testing of Metals, 1972,reapproved 2004 2012A .

2.3.2 ISO Publications.

International Organization for Standardization, 1 rue de Varembe, Case postale 56, CH-1211Geneva 20 ISO Central Secretariat, BIBC II, Chemin de Blandonnet, 8, CP 401, 1214 Vernier,Geneva , Switzerland .

ISO/IEC 17025, General Requirements for the Competence of Testing and CalibrationLaboratories, 2005, Technical Corrigendum 1, 2006 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 3 1/25/2016 1:21 PM

Page 14: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

2.3.3 NACE Publications.

NACE International, 1440 South Creek Drive, Houston, TX 77084-4906.

NACE TM0169, Standard Test Method for Laboratory Corrosion Testing of Metals, Reaffirmed2000 2012A .

2.3.4 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

UL 162, Standard for Foam Equipment and Liquid Concentrates, 1994, revised 1999 2015 .

ANSI/ UL 711 CAN / ULC CAN- S508, Rating and Fire Testing of Fire Extinguishers, 2004,revised 2009 2013 .

2.3.5 U.S. EPA Publications.

U.S. Environmental Protection Agency, National Service Center for Environmental Publications(NSCEP), P.O. Box 42419, Cincinnati, OH 45242.

OPPTS 835.3110, Ready Biodegradability, Section M, CO2 Evolution (Modified Sturm) Test, Fate,

Transport and Transformation Test Guidelines, January 1998.

OPPTS 850.1075, Fish Acute Toxicity Test, Freshwater and Marine, Ecological Effects TestGuidelines, 1996.

OPPTS 870.1100, Acute Oral Toxicity, Health Effects Test Guidelines, 2002.

OPPTS 870.1200, Acute Dermal Toxicity, Health Effects Test Guidelines, 1998.

OPPTS 870.2400, Acute Eye Irritation, Health Effects Test Guidelines, 1998.

OPPTS 870.2500, Acute Dermal Irritation, Health Effects Test Guidelines, 1998.

2.3.6 U.S. Government Publications.

U.S. Government Printing Publishing Office, 732 North Capitol Street, NW, Washington, DC20402 , 20401-0001 .

Title 40, Code of Federal Regulations, Part 160, “Good Laboratory Practice Standards,” 2011.

Title 40, Code of Federal Regulations, Part 792, “Good Laboratory Practice Standards,” 2011.

2.3.7 Other Publications.

Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA,2003.

2.4 References for Extracts in Mandatory Sections.

NFPA 10, Standard for Portable Fire Extinguishers, 2017 edition.

NFPA 30, Flammable and Combustible Liquids Code, 2015 edition.

Statement of Problem and Substantiation for Public Comment

Referenced current SDO addresses, standard names, numbers, and editions.

Related Item

First Revision No. 5-NFPA 18-2015 [Section No. B.1.1]

First Revision No. 6-NFPA 18-2015 [Section No. B.1.2.3]

First Revision No. 18-NFPA 18-2015 [Section No. B.1.2.1]

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 3 1/25/2016 1:21 PM

Page 15: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Submitter NFPA User ID: [email protected]

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Tue Sep 29 02:04:56 EDT 2015

Copyright Assignment

I, Aaron Adamczyk, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights incopyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this PublicComment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Aaron Adamczyk, and I agree to be legally bound by the above Copyright Assignmentand the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronicsignature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 3 1/25/2016 1:21 PM

Page 16: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

 

 

 

NFPA 18A Public Comment 

Page 17: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 20-NFPA 18A-2015 [ Global Input ]

I support the development of Class C Fire test Methods. Test should consider the use of agents in

extinguishers, municipal applications and arc suppression for energized electrical fires.

Statement of Problem and Substantiation for Public Comment

As technology evolves and the demand for power grows; the absence of viable agents for the suppression of class C fires presents an unreasonable risk to life, property and our infrastructure. The lack of safe and effective agents leaves the fire services with no means of an offensive attack for suppression much less a defensive attack to protect exposures. The ability to have agents tested and listed will ensure that fire services and brigades have the best possible solution to these low frequency high hazard incidents. We cannot hope for success; we must prepare for it.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Arthur Hudman

Organization: [ Not Specified ]

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 15:07:21 EST 2015

Copyright Assignment

I, Arthur Hudman, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rightsin copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Arthur Hudman, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 37 1/25/2016 1:23 PM

Page 18: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 1-NFPA 18A-2015 [ Chapter 2 ]

Chapter 2 Referenced Publications

2.1 General.

The documents or portions thereof listed in this chapter are referenced within this standard andshall be considered part of the requirements of this document.

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2016 edition.

NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2017 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based FireProtection Systems, 2017 edition.

NFPA 1901, Standard for Automotive Fire Apparatus, 2016 edition.

2.3 Other Publications.

2.3.1 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428-2959.

ASTM D92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup Tester,2012b.

ASTM D97, Standard Test Method for Pour Point of Petroleum Products, 2012.

ASTM D1293, Standard Test Methods for pH of Water, 1999 ( 2012) .

ASTM D2196, Standard Test Methods for Rheological Properties of Non-Newtonian Materialsby Rotational (Brookfield type) Viscometer, 2015.

ASTM D2240, Standard Test Method for Rubber Property — Durometer Hardness, 2010.

ASTM E729, Standard Guide for Conducting Acute Toxicity Tests on Test Materials with Fishes,Macroinvertebrates, and Amphibians, 2014.

ASTM G1, Standard Practice for Preparing, Cleaning, and Evaluating Corrosion TestSpecimens, 2014.

ASTM G31, Standard Practice for Laboratory Immersion Corrosion Testing of Metals, 1972(2011) 2012a .

2.3.2 ISO Publications.

International Organization for Standardization, 1 rue de Varembé, Case postale 56, CH-1211,Genève 20, ISO Central Secretariat, BIBC II, Chemin de Blandonnet, 8, CP 401, 1214Vernier, Geneva, Switzerland .

ISO/IEC 17025, General requirements for the competence of testing and calibrationlaboratories, 2005, Technical Corrigendum 1, 2006 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 37 1/25/2016 1:23 PM

Page 19: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

2.3.3 NACE Publications.

NACE International, 1440 South Creek Drive, Houston, TX 77084-4906.

NACE/ASTM TM0169 G0031 12A, Standard Test Method — Laboratory Corrosion Testing ofMetals, 2000 2012a .

2.3.4 UL Publications.

Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

UL 162, Foam Equipment and Liquid Concentrates, 1994, revised 1999 2015 .

ANSI/UL 711/ULC CAN /ULC - S508, Rating and Fire Testing of Fire Extinguishers, 2004,revised 2009 2013 .

2.3.5 ULC Publications.

Underwriters’ Laboratories of Canada, 7 Underwriters Road, Toronto ON M1R 3B4.

ULC CAN /ULC - S560, Category 3 Aqueous Film-Forming Foam (AFFF) Liquid Concentrates,2006.

2.3.6 U.S. EPA Publications.

Environmental Protection Agency, William Jefferson Clinton East Building, 1200 PennsylvaniaAvenue, NW, Washington, DC 20460.

OPPTS 835.3110, Ready Biodegradability, Section M, CO 2 Evolution (Modified Sturm) Test,

Fate, Transport and Transformation Test Guidelines, January 1998.

OPPTS 850.1075, Fish Acute Toxicity Test, Freshwater and Marine, Ecological Effects TestGuidelines, 1996.

OPPTS 870.1100, Acute Oral Toxicity, Health Effects Test Guidelines, 1998.

OPPTS 870.1200, Acute Dermal Toxicity, Health Effects Test Guidelines, 1998.

OPPTS 870.2400, Acute Eye Irritation, Health Effects Test Guidelines, 1998.

OPPTS 870.2500, Acute Dermal Irritation, Health Effects Test Guidelines, 1998.

2.3.7 U.S. Government Publications.

U.S. Government Publishing Office, 732 North Capitol Street, NW, Washington, DC20401-0001.

Title 40, Code of Federal Regulations, Part 86.113-94, Air Programs, “Fuel Specifications,”2012.

Title 40, Code of Federal Regulations, Part 160, Pesticide Programs, “Good LaboratoryPractice,” 2011.

Title 40, Code of Federal Regulations, Part 792, Toxic Substances Control Act, “GoodLaboratory Practice,” 2011.

2.3.8 Other Publications.

Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA,2003.

2.4 References for Extracts in Mandatory Sections.

NFPA 10, Standard for Portable Fire Extinguishers, 2017 edition.

NFPA 36, Standard for Solvent Extraction Plants, 2017 edition.

NFPA 1145, Guide for the Use of Class A Foams in Manual Structural Fire Fighting, 2017edition.

NFPA 1150, Standard on Foam Chemicals for Fires in Class A Fuels, 2017 edition.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 37 1/25/2016 1:23 PM

Page 20: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Statement of Problem and Substantiation for Public Comment

Referenced current SDO names, addresses, standard numbers, and editions.

Related Public Comments for This Document

Related Comment Relationship

Public Comment No. 2-NFPA 18A-2015 [Section No. E.1.2.3]

Related Item

First Revision No. 2-NFPA 18A-2015 [Section No. 2.3.1]

First Revision No. 3-NFPA 18A-2015 [Section No. 2.3.3]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Sun Oct 11 19:39:17 EDT 2015

Copyright Assignment

I, Aaron Adamczyk, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rightsin copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Aaron Adamczyk, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 37 1/25/2016 1:23 PM

Page 21: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 12-NFPA 18A-2015 [ Chapter 8 ]

Chapter 8 Class C Fire Test Methods

8.1 General.

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures:

Conductivity test

8.1 General

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures:

(1) Extinguisher test

(2) Manual Operations test

(3) Arcing Conductor test

8.2 Extinguisher Test

8.2.1 The safe use of water additives in extinguishers to mitigate or suppress a Class Cfire shall be evaluated through the following test method. The test and setup has beeninformed by ANSI / UL 711 requiring a test voltage of 100kV AC to be applied at 48” whichis the minimum approach distance for hazard as defined by OSHA 1910.269 Table R-7found below in Exhibit 8.2.1.a

Exhibit 8.2.1.a

Additional Proposed Changes

File Name Description Approved

OSHA_Table_R.pdf

As technology evolves and the demand for power grows, the absence of viable agents for the suppression of Class C fires presents an unreasonable risk to life and property. The lack of safe and effective agents leaves fire and utility services with no means of an offensive attack, not to mention a defensive attack. Further, waiting for utility response ties up fire resources because these volatile incidents cannot be managed without their support. The fire services need the ability to resolve these large volume weather driven events and return to fire duty.

I strongly support the development of Class C Fire test methods. Tests should consider the use of agents in extinguishers,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 37 1/25/2016 1:23 PM

Page 22: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

municipal applications and arc suppression for down wires and manhole fires.

Statement of Problem and Substantiation for Public Comment

As technology evolves and the demand for power grows, the absence of viable agents for the suppression of Class C fires presents an unreasonable risk to life and property. The lack of safe and effective agents leaves fire and utility services with no means of an offensive attack, not to mention a defensive attack. Further, waiting for utility response ties up fire resources because these volatile incidents cannot be managed without their support. The fire services need the ability to resolve these large volume weather driven events and return to fire duty.

I strongly support the development of Class C Fire test methods. Tests should consider the use of agents in extinguishers, municipal applications and arc suppression for down wires and manhole fires.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Bree Goldstein

Organization:

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Thu Nov 05 15:20:04 EST 2015

Copyright Assignment

I, Bree Goldstein, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights incopyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this PublicComment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Bree Goldstein, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 37 1/25/2016 1:23 PM

Page 23: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

TABLE R-7-ALTERNATIVE MINIMUM APPROACH DISTANCES FOR VOLTAGES OF MORE THAN 72.5 KV 1 2 3 Voltage range phase to phase (kV) Phase-to-ground

exposure Phase-to-phase

exposure M Ft M Ft 72.6 to 121.0 ....................................................................... 1.13 3.71 1.42 4.66 121.1 to 145.0 ......................................................................... 1.30 4.27 1.64 5.38 145.1 to 169.0 ......................................................................... 1.46 4.79 1.94 6.36 169.1 to 242.0 ......................................................................... 2.01 6.59 3.08 10.10 242.1 to 362.0 .......................................................................... 3.41 11.19 5.52 18.11 362.1 to 420.0 ......................................................................... 4.25 13.94 6.81 22.34 420.1 to 550.0 ......................................................................... 5.07 16.63 8.24 27.03 550.1 to 800.0 ......................................................................... 6.88 22.57 11.38 37.34 1 Employers may use the minimum approach distances in this table provided the worksite is at an

elevation of 900 meters (3,000 feet) or less. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.

2 Employers may use the phase-to-phase minimum approach distances in this table provided that no insulated tool spans the gap and no large conductive object is in the gap.

3 The clear live-line tool distance shall equal or exceed the values for the indicated voltage ranges. United States Department of Labor Occupational Safety & Health Administration

Page 24: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 28-NFPA 18A-2015 [ Chapter 8 ]

Chapter 8 Class C Fire Test Methods

8.1 General.

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures:

(1) Conductivity test

I support the development of Class C Fire test Methods. Test should consider the use of agentsin extinguishers, municipal applications and arc suppression for energized electrical fires

Statement of Problem and Substantiation for Public Comment

As technology evolves and the demand for power grows; the absence of viable agents for the suppression of class C fires presents an unreasonable risk to life, property and our infrastructure. The lack of safe and effective agents leaves the fire services with no means of an offensive attack for suppression much less a defensive attack to protect exposures. The ability to have agents tested and listed will ensure that fire services and brigades have the best possible solution to these low frequency high hazard incidents. We cannot hope for success; we must prepare for it.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: WALTER GRODEN

Organization: GREENVILLE FIRE DEPT

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Thu Nov 12 09:37:57 EST 2015

Copyright Assignment

I, WALTER GRODEN, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am WALTER GRODEN, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 37 1/25/2016 1:23 PM

Page 25: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 3-NFPA 18A-2015 [ Chapter 8 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 37 1/25/2016 1:23 PM

Page 26: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Chapter 8

Class C Fire Test Methods

8.

1 1 General .

Water additive solutions for Class C fires shall be tested and listed in accordancewith one or more of the following test procedures

:

(1) Conductivity test

.

(1) Extinguisher test

(2) Manual Operations test

(3) Arcing Conductor test

8.2 Extinguisher Test

8.2.1 The safe use of water additives in extinguishers to mitigate or suppress a Class C fireshall be evaluated through the following test method. The test and setup has been informed byANSI / UL 711 requiring a test voltage of 100kV AC to be applied at 36” which is the minimumapproach distance for contact hazard as defined by OSHA 1910.269 Table R-7 found below inExhibit 8.2.1.a

Exhibit 8.2.1.a

8.2.3 The pass/fail criterion shall be a maximum measured leakage current below 500uA at36”. As informed by NFPA 70E Standards for Electrical Safety in the Workplace (effects ofcurrent of the human body - 1 mA is the perception threshold level so a leakage half of thatvalue to pass the test is required)

8.2.4 Water additives shall be evaluated for viscosity and surface tension values to determineif the agent pooling will be sufficiently large enough to expand beyond the standoff distancewhich could pose the risk of electrocution. If it is found the agent cannot spread beyond thestandoff distance as stated in the instructions the agent shall not be subjected to theconductivity test required by NFPA 10.

8.2.5 The water additive solution shall be prepared at the manufacturer’s minimum andmaximum recommended concentrations.

8.2.6 Use of these extinguishers should be limited to trained fire fighters, such as fire servicesmeeting the qualifications of NFPA 1001, private brigades who are NFPA 1081 qualified, andElectrically Qualified Workers 1910.332 (b)(3), as defined by OSHA.

8.3 Manual Operations Test

8.3.1 This section of code addresses the ability of water additive solutions to be evaluated foruse in manual firefighting operations to suppress Class C fires or on fires impinged by “Live”electrical sources.

8.3.2 The agent shall be tested with application and mixing hardware specified by the

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 37 1/25/2016 1:23 PM

Page 27: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

manufacturer and under the worst case application conditions, including consolidated streamand maximum flow rate.

8.3.3 The test apparatus shall be configured and the agent prepared for application per themanufacturers written instructions

8.3.4 Tests shall be conducted using a solution of water additive made with the concentrate,as received, in fresh water and at the concentration specified by the manufacturer. Wateradditive solutions made with synthetic seawater may also be tested, if such usage is specifiedby the manufacturer.

8.3.5 Tests shall be conducted only when the ambient temperature is above 5°C (40°F) andin still air. If tested outdoors, wind speeds shall be less that 5 miles/hour (8 km/hour).

8.3.6 Testing shall be conducted similarly to UL 711, Rating and Fire Testing of FireExtinguishers , section 9,but scaled for manual firefighting operations using AC or DC.

8.3.7 The 12 inch by 12 inch target shall be replaced with a 138 kV disconnect switch such asused in an electrical substation or other appropriate target for the category voltage. Illustrationbelow is a typical electrical substation disconnect switch.

Exhibit 8.3.7.a

138Kv substation Disconnect switch

8.3.8 The disconnect switch shall be located at the top of the bus bar and energized using apower supply that is capable of supplying the desired test voltage while the insulators isolatethe bus bar from ground.

8.3.9 Disconnect switches designed for target voltages above 138kV, such as 345kV and500kV, are ideal since their designs consider insulation from a ground reference via theinsulators.

8.3.10 A wire shall be inserted into the nozzle to ensure contact is made with the stream ofsolution being tested. The wire shall be attached to ground through a circuit containing twomultimeters in series, The two multimeters shall be set, one each, to read current in milliampsand microamps. The current measurements are to be recorded during each test, afterstabilization of the readings.

Exhibit 8.3.10.a

Multi-meter arrangement in the current measuring circuit.

8.3.11 The discharge appliance shall be fixed in place on a test stand for safety. The standshall be initially positioned at the Test Standoff distance for the voltage schedule outlined inexhibit 8.3.11.a rating table.

Exhibit 8.3.11.a

Rating Table

Category VoltageOperating Safe

Standoff Distance, ftTest Standoff Distance,

ft

I < 600 V 107.5

Solid Stream

II < 34 kV 2518.75

Solid Stream

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 37 1/25/2016 1:23 PM

Page 28: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

III < 138 kV 7556.25

Solid Stream

IV < 345 kV 12593.75

Solid Stream

V < 500 kV 135101.25

Solid Stream

VI 110 V – 138kV 1530 Degree Fog

See 8.3.18

VII 139kV – 500kV 3030 Degree Fog

See 8.3.18

8.3.12 The rating table provided as exhibit 8.3.11.a establishes categories to define voltage,the operating safe standoff distance, and test standoff distance (75 percent of the operatingstandoff distance) for common electrical equipment thresholds.

8.3.13 The stream shall then be directed onto the target to ensure the proper trajectory.

8.3.14 The maximum specified flow rate of the equipment shall be used and the nozzle shallbe adjusted to produce the most consolidated (solid) stream possible. Once the flow has beenestablished and all personnel are at a safe distance, the target shall be energized to thespecified ac voltage.

8.3.15 The concentrate shall then be proportioned into the water stream at the manufacturer’sspecified concentration and the solution shall be applied to the target for a minimum period of90 seconds.

8.3.16 Tests shall be repeated while incrementally closing the distance to the target until theleakage current has exceeded the 500uA threshold. Three tests shall be conducted at a givendistance to derive the average leakage current.

8.3.17 Acceptable performance shall be defined as maximum leakage current less than 500uA at 75 percent of the Test Standoff Distance outlined in Rating Table provided as exhibit8.3.11.a

8.3.18 Tests VI & VII outlined in the Rating Table (exhibit 8.3.11.a) shall be completed using a30 degree or greater fixed fog pattern with acceptable performance defined as follows:

.

(1) 110v-138kV: < 500 uA at 15feet

(2) 139kV-765kV: < 500 uA at 30 feet

8.3.19 The Table (exhibit 8.3.11.a) shall be used to assign a Class C rating category to thewater additive solution, based upon the distance at which the maximum leakage currentcriterion was met.

8.3.20 The following data shall be recorded for each test:

(1) Water additive and solution concentration

(2) Application and proportioning devices makes and models

(3) Ambient temperature and wind conditions

(4) Viscosity and conductivity of the concentrate and solution

(5) Leakage currents measured, including the maximum and average leakage

(6) Water pressure and flow

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 37 1/25/2016 1:23 PM

Page 29: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

(7) Breakdown distance for 500 uA leakage current

8.4 Arc Conductor Test

8.4.1 Water additive solutions shall demonstrate the ability to suppress artificially generatedfaults using copper cables. The tests shall be monitored for heat release and products ofcombustion.

8.4.2 Test Set-Up

8.4.2.1 The test set up shall be configured indoors in a conditioned environment.

8.4.2.2 Test Equipment: New 500 kcmil Copper conductor 600V EAM/LSNH installed ina precast concrete distribution box type B-3.6 shall be used to produce a phase to phase faultcreating an arc with a target fault current of 2 kA. The required test voltage is 480v AC.

8.4.2.3 Tests shall be conducted using a solution of water additive made with theconcentrate, as received, in fresh water and at the concentration specified by themanufacturer. Water additive solutions made with synthetic seawater may also be tested, ifsuch usage is specified by the manufacturer.

8.4.2.4 Water additive concentrate viscosity and conductivity shall be measured andreported.

8.4.3 Test Procedures.

8.4.3.1 Number of Tests - Six tests shall be conducted to derive the average arcsuppression results. Three tests will be conducted without the water additive and anotherthree will be conducted with the solution.

8.4.3.2 To limit resistance, the 500 Kcmil cable for the test will be no longer the 25’. The 500 Kcmil cable will be connected to the 480v source and an inductor will be placed inseries between the voltage source at the faulted cable in the test box to control current. Twoinches of insulation will be removed from the inner walls of each cable at the terminal ends.The cables shall be installed at the bottom of the concrete box, with the terminal ends of eachcable positioned in manner that a 1 inch air-gap resides between the stripped portions ofcable. The approximate dimensions of the interior volume of the concrete box shall be: 33 in.wide x in. long x 24 in.18 in. deep. The concrete box drawing is shown in exhibit 8.4.3.2.a

Exhibit 8.4.3.2.a

Concrete Box Drawing

8.4.3.3 One calorimeter shall be installed above the concrete box to measure theincident energy generated by the fault.

8.4.3.4 The configuration for the arc conductor test is shown in exhibit 8.4.3.4.a

Exhibit 8.4.3.4.a

Arc conductor test configuration

8.4.3.5 The Fault duration shall be until the fault self-extinguishes or a steady state isreached.

8.4.3.6 The solution shall be discharged into the concrete service box once the cablehas been faulted so that the height of the agent reaches 6 in. above the burning cable.

8.4.3.7 Combustible gases shall be measured two-minutes prior to the inception ofcable fault through the application of the product in order to record the evolution andproduction of combustible gases created by the burning insulation on the jacket of the cable. Measurements shall continue for five minutes after the solution has risen to the prescribedlevel.

8.4.3.8 The production of combustible gases is the cause of secondary explosions inelectrical fires.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 37 1/25/2016 1:23 PM

Page 30: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.3.9 The results of the test shall be evaluated using arc suppression as the criterionfor success. The arc is considered to have been suppressed through observation and verifiedby the use of calorimetry.

8.4.3.10 The following data shall be recorded for each test:

(1) Arc duration

(2) Current and Voltage waveforms (exhibit 8.4.3.10.a)

(3) Ambient temperature

(4) Calorimeter data

(6) Video (high and normal speed)

Exhibit 8.4.3.10.a

Illustrates test report format.

Additional Proposed Changes

File Name Description Approved

18a-Section_8_Oct-25.docx

Statement of Problem and Substantiation for Public Comment

Problem Statement: Currently, NFPA 18a only considers Class A & B fires while Class C fires remain low frequency high hazard incidents. The NFPA fails to support the fire services & utilities with viable agents capable of being used safely and effectively in an electrical environment. In the absence of formal support from NFPA localized R&D work with Con Edison and the FDNY has yielded the solutions provided to you herein. • Extinguishers: Currently, the extinguishers that have a Class C listing can be used in a Class C environment but cannot extinguish a Class C fire. We need to open the door with testing for agents that can suppress an energized fire. In addition, Class A and Class B listings are scalable while Class C is not. We are proposing a Professional Class C rating for use by the fire services, brigades and electrically qualified OSHA workers. We are looking at the use of extinguishers to manage a problem before it becomes an emergency. This can prove to have significant effect in the aircraft and maritime industry. • Manual Suppression: the municipal fire services are tasked with the preservation of life and property. However they remain white knuckled at electrical fires hoping for a favorable outcome because there is no direction in terms of what agents are safe for mitigation/suppression. Due to the lack of viable agents, the fire services cannot even assume a defensive role safely which places substations and power plants at risk from collateral. These incidents can result in large blackouts compromising public safety and the integrity of the electrical infrastructure. . • Arc Suppression: From burning wires to manhole fires these incidents present a significant risk to the general public. These events are mostly weather driven and exceed the staffing capacity of the utility to provide support in a timely manner. Testing will provide the fire services with agents to mitigate the effects of these situations. These weather driven incidents can quickly consume the resources of even the largest fire departments leaving few members available for fire duty thus putting the public at risk.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 37 1/25/2016 1:23 PM

Page 31: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Submitter Full Name: Anthony Natale

Organization: Consolidated Edison of New York

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Sun Oct 25 19:54:09 EDT 2015

Copyright Assignment

I, Anthony Natale, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rightsin copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Anthony Natale, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 37 1/25/2016 1:23 PM

Page 32: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Chapter 8 Class C Fire Test Methods 8.1 General. Water additive solutions for Class C fires shall be tested and listed in accordance with one or more of the following test procedures.

(1) Extinguisher test (2) Manual Operations test (3) Arcing Conductor test

8.2 Extinguisher Test 8.2.1 The safe use of water additives in extinguishers to mitigate or suppress a Class C fire shall be evaluated through the following test method. The test and setup has been informed by ANSI / UL 711 requiring a test voltage of 100kV AC to be applied at 36” which is the minimum approach distance for contact hazard as defined by OSHA 1910.269 Table R-7 found below in Exhibit 8.2.1.a Exhibit 8.2.1.a

8.2.3 The pass/fail criterion shall be a maximum measured leakage current below 500uA at 36”. As informed by NFPA 70E Standards for Electrical Safety in the Workplace (effects of current of the human body - 1 mA is the perception threshold level so a leakage half of that value to pass the test is required) 8.2.4 Water additives shall be evaluated for viscosity and surface tension values to determine if the agent pooling will be sufficiently large enough to expand beyond the standoff distance which could pose the risk of electrocution. If it is found the agent cannot spread beyond the standoff distance as stated in the instructions the agent shall not be subjected to the conductivity test required by NFPA 10.

Page 33: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.2.5 The water additive solution shall be prepared at the manufacturer’s minimum and maximum recommended concentrations. 8.2.6 Use of these extinguishers should be limited to trained fire fighters, such as fire services meeting the qualifications of NFPA 1001, private brigades who are NFPA 1081 qualified, and Electrically Qualified Workers 1910.332 (b)(3), as defined by OSHA. 8.3 Manual Operations Test 8.3.1 This section of code addresses the ability of water additive solutions to be evaluated for use in manual firefighting operations to suppress Class C fires or on fires impinged by “Live” electrical sources. 8.3.2 The agent shall be tested with application and mixing hardware specified by the manufacturer and under the worst case application conditions, including consolidated stream and maximum flow rate. 8.3.3 The test apparatus shall be configured and the agent prepared for application per the manufacturers written instructions 8.3.4 Tests shall be conducted using a solution of water additive made with the concentrate, as received, in fresh water and at the concentration specified by the manufacturer. Water additive solutions made with synthetic seawater may also be tested, if such usage is specified by the manufacturer. 8.3.5 Tests shall be conducted only when the ambient temperature is above 5°C (40°F) and in still air. If tested outdoors, wind speeds shall be less that 5 miles/hour (8 km/hour). 8.3.6 Testing shall be conducted similarly to UL 711, Rating and Fire Testing of Fire Extinguishers, section 9,but scaled for manual firefighting operations using AC or DC. 8.3.7 The 12 inch by 12 inch target shall be replaced with a 138 kV disconnect switch such as used in an electrical substation or other appropriate target for the category voltage. Illustration below is a typical electrical substation disconnect switch. Exhibit 8.3.7.a 138Kv substation Disconnect switch

Page 34: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.3.8 The disconnect switch shall be located at the top of the bus bar and energized using a power supply that is capable of supplying the desired test voltage while the insulators isolate the bus bar from ground. 8.3.9 Disconnect switches designed for target voltages above 138kV, such as 345kV and 500kV, are ideal since their designs consider insulation from a ground reference via the insulators. 8.3.10 A wire shall be inserted into the nozzle to ensure contact is made with the stream of solution being tested. The wire shall be attached to ground through a circuit containing two multimeters in series, The two multimeters shall be set, one each, to read current in milliamps and microamps. The current measurements are to be recorded during each test, after stabilization of the readings. Exhibit 8.3.10.a Multi-meter arrangement in the current measuring circuit.

Page 35: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.3.11 The discharge appliance shall be fixed in place on a test stand for safety. The stand shall be initially positioned at the Test Standoff distance for the voltage schedule outlined in exhibit 8.3.11.a rating table. Exhibit 8.3.11.a Rating Table

Category Voltage Operating Safe Standoff

Distance, ft

Test Standoff Distance, ft

I < 600 V 10 7.5

Solid Stream

II < 34 kV 25 18.75

Solid Stream

III < 138 kV 75 56.25

Solid Stream

IV < 345 kV 125 93.75

Solid Stream

V < 500 kV 135 101.25

Solid Stream

VI 110 V – 138kV 15 30 Degree Fog

See 8.3.18

VII 139kV – 500kV 30 30 Degree Fog

See 8.3.18

8.3.12 The rating table provided as exhibit 8.3.11.a establishes categories to define voltage, the operating safe standoff distance, and test standoff distance (75 percent of the operating standoff distance) for common electrical equipment thresholds. 8.3.13 The stream shall then be directed onto the target to ensure the proper trajectory. 8.3.14 The maximum specified flow rate of the equipment shall be used and the nozzle shall be adjusted to produce the most consolidated (solid) stream possible. Once the flow has been established and all personnel are at a safe distance, the target shall be energized to the specified ac voltage.

Page 36: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.3.15 The concentrate shall then be proportioned into the water stream at the manufacturer’s specified concentration and the solution shall be applied to the target for a minimum period of 90 seconds. 8.3.16 Tests shall be repeated while incrementally closing the distance to the target until the leakage current has exceeded the 500uA threshold. Three tests shall be conducted at a given distance to derive the average leakage current. 8.3.17 Acceptable performance shall be defined as maximum leakage current less than 500 uA at 75 percent of the Test Standoff Distance outlined in Rating Table provided as exhibit 8.3.11.a 8.3.18 Tests VI & VII outlined in the Rating Table (exhibit 8.3.11.a) shall be completed using a 30 degree or greater fixed fog pattern with acceptable performance defined as follows: .

(1) 110v-138kV: < 500 uA at 15feet (2) 139kV-765kV: < 500 uA at 30 feet

8.3.19 The Table (exhibit 8.3.11.a) shall be used to assign a Class C rating category to the water additive solution, based upon the distance at which the maximum leakage current criterion was met. 8.3.20 The following data shall be recorded for each test:

(1) Water additive and solution concentration (2) Application and proportioning devices makes and models (3) Ambient temperature and wind conditions (4) Viscosity and conductivity of the concentrate and solution (5) Leakage currents measured, including the maximum and average leakage (6) Water pressure and flow (7) Breakdown distance for 500 uA leakage current

8.4 Arc Conductor Test 8.4.1 Water additive solutions shall demonstrate the ability to suppress artificially generated faults using copper cables. The tests shall be monitored for heat release and products of combustion. 8.4.2 Test Set-Up 8.4.2.1 The test set up shall be configured indoors in a conditioned environment.

Page 37: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.2.2 Test Equipment: New 500 kcmil Copper conductor 600V EAM/LSNH installed in a precast concrete distribution box type B-3.6 shall be used to produce a phase to phase fault creating an arc with a target fault current of 2 kA. The required test voltage is 480v AC. 8.4.2.3 Tests shall be conducted using a solution of water additive made with the concentrate, as received, in fresh water and at the concentration specified by the manufacturer. Water additive solutions made with synthetic seawater may also be tested, if such usage is specified by the manufacturer. 8.4.2.4 Water additive concentrate viscosity and conductivity shall be measured and reported. 8.4.3 Test Procedures. 8.4.3.1 Number of Tests - Six tests shall be conducted to derive the average arc suppression results. Three tests will be conducted without the water additive and another three will be conducted with the solution. 8.4.3.2 To limit resistance, the 500 Kcmil cable for the test will be no longer the 25’. The 500 Kcmil cable will be connected to the 480v source and an inductor will be placed in series between the voltage source at the faulted cable in the test box to control current. Two inches of insulation will be removed from the inner walls of each cable at the terminal ends. The cables shall be installed at the bottom of the concrete box, with the terminal ends of each cable positioned in manner that a 1 inch air-gap resides between the stripped portions of cable. The approximate dimensions of the interior volume of the concrete box shall be: 33 in. wide x in. long x 24 in.18 in. deep. The concrete box drawing is shown in exhibit 8.4.3.2.a

Page 38: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Exhibit 8.4.3.2.a Concrete Box Drawing

Page 39: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.3.3 One calorimeter shall be installed above the concrete box to measure the incident energy generated by the fault. 8.4.3.4 The configuration for the arc conductor test is shown in exhibit 8.4.3.4.a Exhibit 8.4.3.4.a Arc conductor test configuration

8.4.3.5 The Fault duration shall be until the fault self-extinguishes or a steady state is reached. 8.4.3.6 The solution shall be discharged into the concrete service box once the cable has been faulted so that the height of the agent reaches 6 in. above the burning cable. 8.4.3.7 Combustible gases shall be measured two-minutes prior to the inception of cable fault through the application of the product in order to record the evolution and production of combustible gases created by the burning insulation on the jacket of the cable. Measurements shall continue for five minutes after the solution has risen to the prescribed level.

Page 40: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.3.8 The production of combustible gases is the cause of secondary explosions in electrical fires. 8.4.3.9 The results of the test shall be evaluated using arc suppression as the criterion for success. The arc is considered to have been suppressed through observation and verified by the use of calorimetry. 8.4.3.10 The following data shall be recorded for each test:

(1) Arc duration (2) Current and Voltage waveforms (exhibit 8.4.3.10.a) (3) Ambient temperature (4) Calorimeter data (6) Video (high and normal speed)

Exhibit 8.4.3.10.a Illustrates test report format.

Page 41: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 33-NFPA 18A-2015 [ Chapter 8 ]

Chapter 8 Class C Fire Test Methods

8.1 General.

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures:

(1) Conductivity test

I support the development of Class C Fire test Methods. Test should consider the use ofagents in extinguishers, municipal applications and arc suppression for energized electricalfires. (give more detail if possible)

Statement of Problem and Substantiation for Public Comment

As technology evolves and the demand for power grows; the absence of viable agents for the suppression of class C fires presents an unreasonable risk to life, property and our infrastructure. The lack of safe and effective agents leaves the fire services with no means of an offensive attack for suppression much less a defensive attack to protect exposures. The ability to have agents tested and listed will ensure that fire services and brigades have the best possible solution to these low frequency high hazard incidents. We cannot hope for success; we must prepare for it.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Paul Kies

Organization: Con Edison

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 13 10:05:34 EST 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 37 1/25/2016 1:23 PM

Page 42: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Copyright Assignment

I, Paul Kies, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights incopyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this PublicComment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Paul Kies, and I agree to be legally bound by the above Copyright Assignmentand the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwrittensignature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 37 1/25/2016 1:23 PM

Page 43: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 7-NFPA 18A-2015 [ Chapter 8 ]

Chapter 8 Class C Fire Test Methods

8.1 General.

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures:

(1) Conductivity test

Statement of Problem and Substantiation for Public Comment

I support the development of Class C Fire test Methods. Test should consider the use of agents in extinguishers, municipal applications and arc suppression for down wires and manhole fires and other class “C” fires as well .As technology evolves and the demand for power grows; the absence of viable agents for the suppression of Class C fires presents an unreasonable risk to life and property. The lack of safe and effective agents leaves the fire services with no means of an offensive attack much less a defensive attack. Waiting for utility response ties up fires resources because these volatile incidents cannot be managed without their support. The fire services need the ability to resolve these large volume weather driven events and return to fire duty.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Anthony M Tricarico

Organization: FDNY

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Mon Oct 26 15:22:01 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 37 1/25/2016 1:23 PM

Page 44: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Copyright Assignment

I, Anthony M Tricarico, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Anthony M Tricarico, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 37 1/25/2016 1:23 PM

Page 45: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 8-NFPA 18A-2015 [ Chapter 8 ]

Chapter 8 Class C Fire Test Methods

8.1 General.

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures:

(1) Conductivity test

Statement of Problem and Substantiation for Public Comment

I support the development of Class C Fire test Methods. Test should consider the use of agents in extinguishers, municipal applications and arc suppression for down wires and manhole fires as well as other types class “C” fires. As technology evolves and the demand for power grows; the absence of viable agents for the suppression of Class C fires presents an unreasonable risk to life and property. The lack of safe and effective agents leaves the fire services with no means of an offensive attack much less a defensive attack. Waiting for utility response ties up fires resources because these volatile incidents cannot be managed without their support. The fire services need the ability to resolve these large volume weather driven events and return to fire duty.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Anthony M Tricarico

Organization: FDNY

Affilliation: Suffolk County Fire Department

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Mon Oct 26 15:29:02 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 37 1/25/2016 1:23 PM

Page 46: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Copyright Assignment

I, Anthony M Tricarico, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Anthony M Tricarico, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 37 1/25/2016 1:23 PM

Page 47: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 16-NFPA 18A-2015 [ Chapter 8 [Title Only] ]

Class C Fire Test Methods

Class C fire test methods need to be developed. These test methods should consider the use ofagents in extinguishers, applications for municipal operations such as manhole fires, transformerfires (both underground and pole transformers, and arc suppression for these energized electricalfires.

Statement of Problem and Substantiation for Public Comment

Changes in technology and the demand for power demonstrates the need for viable agents for the suppression of class C fires. Without these new Class C suppression agents there is an increased risk to the first responder, utility worker and the public. This is an unreasonable risk to life, property and our infrastructure. The lack of safe and effective agents inhibits the fire services from initiating an offensive attack for suppression on the source as well as protecting exposures. It is vital to have these new agents tested and listed so the municipal fire services and fire brigades can have the best possible tools to mitigate these hazardous incidents.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Stephen Raynis

Organization: Fire Department City of New Yo

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 10:40:05 EST 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 37 1/25/2016 1:23 PM

Page 48: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Copyright Assignment

I, Stephen Raynis, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rightsin copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Stephen Raynis, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 37 1/25/2016 1:23 PM

Page 49: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 19-NFPA 18A-2015 [ Chapter 8 [Title Only] ]

Class C Fire Test Methods

I support the development of Class C Fire test Methods. Test should consider the use of agents inextinguishers, municipal applications and arc suppression for energized electrical fires.

Statement of Problem and Substantiation for Public Comment

As technology evolves and the demand for power grows; the absence of viable agents for the suppression of class C fires presents an unreasonable risk to life, property and our infrastructure. The lack of safe and effective agents leaves the fire services with no means of an offensive attack for suppression much less a defensive attack to protect exposures. The ability to have agents tested and listed will ensure that fire services and brigades have the best possible solution to these low frequency high hazard incidents. We cannot hope for success; we must prepare for it.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Jeremy Burkhart

Organization: Consolidated Edison of NY

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 13:33:36 EST 2015

Copyright Assignment

I, Jeremy Burkhart, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rightsin copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Jeremy Burkhart, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 37 1/25/2016 1:23 PM

Page 50: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 13-NFPA 18A-2015 [ Section No. 8.1 ]

8. 1

1 General

.

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures:

Conductivity test

(1) Extinguisher test

(2) Manual Operations test

(3) Arcing Conductor test

8.2 Extinguisher Test

8.2.1 The safe use of water additives in extinguishers to mitigate or suppress a Class C fireshall be evaluated through the following test method. The test and setup has been informedby ANSI / UL 711 requiring a test voltage of 100kV AC to be applied at 48” which is theminimum approach distance for hazard as defined by OSHA 1910.269 Table R-7 found belowin Exhibit 8.2.1.a

Exhibit 8.2.1.a

Statement of Problem and Substantiation for Public Comment

As technology evolves and the demand for power grows, the absence of viable agents for the suppression of Class C fires presents an unreasonable risk to life and property. The lack of safe and effective agents leaves fire and utility services with no means of an offensive attack, not to mention a defensive attack. Further, waiting for utility response ties up fire resources because these volatile incidents cannot be managed without their support. The fire services need the ability to resolve these large volume weather driven events and return to fire duty.

I strongly support the development of Class C Fire test methods. Tests should consider the use of agents in extinguishers, municipal applications and arc suppression for down wires and manhole fires.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 37 1/25/2016 1:23 PM

Page 51: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Bruce Stone

Organization: FireIce Solutions

Affilliation: Tactical Team

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Thu Nov 05 22:43:03 EST 2015

Copyright Assignment

I, Bruce Stone, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights incopyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this PublicComment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Bruce Stone, and I agree to be legally bound by the above Copyright Assignmentand the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwrittensignature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 37 1/25/2016 1:23 PM

Page 52: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 38-NFPA 18A-2015 [ Section No. 8.1 ]

8.1 General.

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures:

(1) Conductivity test

I support the development of Class C Fire test Methods. Test should consider the use of agentsin extinguishers, municipal applications and arc suppression for energized electrical fires

Statement of Problem and Substantiation for Public Comment

As technology evolves and the demand for power grows; the absence of viable agents for the suppression of class C fires presents an unreasonable risk to life, property and our infrastructure. The lack of safe and effective agents leaves the fire services with no means of an offensive attack for suppression much less a defensive attack to protect exposures. The ability to have agents tested and listed will ensure that fire services and brigades have the best possible solution to these low frequency high hazard incidents. We cannot hope for success; we must prepare for it.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Edward Kleiman

Organization: GelTech

Affilliation: FireIce

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 13 15:36:17 EST 2015

Copyright Assignment

I, Edward Kleiman, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rightsin copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Edward Kleiman, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 37 1/25/2016 1:23 PM

Page 53: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 5-NFPA 18A-2015 [ Section No. 8.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 37 1/25/2016 1:23 PM

Page 54: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Chapter 8

.1 Class C Fire Test Methods

8.1 General .

Water additive solutions for Class C fires shall be tested and listed in accordance with one ormore of the following test procedures

:

(1) Conductivity test

.

(1) Extinguisher test

(2) Manual Operations test

(3) Arcing Conductor test

8.2 Extinguisher Test

8.2.1 The safe use of water additives in extinguishers to mitigate or suppress a Class C fireshall be evaluated through the following test method. The test and setup has been informed byANSI / UL 711 requiring a test voltage of 100kV AC to be applied at 36” which is the minimumapproach distance for contact hazard as defined by OSHA 1910.269 Table R-7 found below inExhibit 8.2.1.a

Exhibit 8.2.1.a

8.2.3 The pass/fail criterion shall be a maximum measured leakage current below 500uA at36”. As informed by NFPA 70E Standards for Electrical Safety in the Workplace (effects ofcurrent of the human body - 1 mA is the perception threshold level so a leakage half of thatvalue to pass the test is required)

8.2.4 Water additives shall be evaluated for viscosity and surface tension values to determine ifthe agent pooling will be sufficiently large enough to expand beyond the standoff distancewhich could pose the risk of electrocution. If it is found the agent cannot spread beyond thestandoff distance as stated in the instructions the agent shall not be subjected to theconductivity test required by NFPA 10.

8.2.5 The water additive solution shall be prepared at the manufacturer’s minimum andmaximum recommended concentrations.

8.2.6 Use of these extinguishers should be limited to trained fire fighters, such as fire servicesmeeting the qualifications of NFPA 1001, private brigades who are NFPA 1081 qualified, andElectrically Qualified Workers 1910.332 (b)(3), as defined by OSHA.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 37 1/25/2016 1:23 PM

Page 55: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.3 Manual Operations Test

8.3.1 This section of code addresses the ability of water additive solutions to be evaluated foruse in manual firefighting operations to suppress Class C fires or on fires impinged by “Live”electrical sources.

8.3.2 The agent shall be tested with application and mixing hardware specified by themanufacturer and under the worst case application conditions, including consolidated streamand maximum flow rate.

8.3.3 The test apparatus shall be configured and the agent prepared for application per themanufacturers written instructions

8.3.4 Tests shall be conducted using a solution of water additive made with the concentrate,as received, in fresh water and at the concentration specified by the manufacturer. Wateradditive solutions made with synthetic seawater may also be tested, if such usage is specifiedby the manufacturer.

8.3.5 Tests shall be conducted only when the ambient temperature is above 5°C (40°F) and instill air. If tested outdoors, wind speeds shall be less that 5 miles/hour (8 km/hour).

8.3.6 Testing shall be conducted similarly to UL 711, Rating and Fire Testing of FireExtinguishers , section 9,but scaled for manual firefighting operations using AC or DC.

8.3.7 The 12 inch by 12 inch target shall be replaced with a 138 kV disconnect switch such asused in an electrical substation or other appropriate target for the category voltage. Illustrationbelow is a typical electrical substation disconnect switch.

Exhibit 8.3.7.a

138Kv substation Disconnect switch

8.3.8 The disconnect switch shall be located at the top of thebus bar and energized using a power supply that is capable ofsupplying the desired test voltage while the insulators isolatethe bus bar from ground.

8.3.9 Disconnect switches designed for target voltages above138kV, such as 345kV and 500kV, are ideal since their

designs consider insulation from a ground reference via the insulators.

8.3.10 A wire shall be inserted into the nozzle to ensure contact is made with the stream ofsolution being tested. The wire shall be attached to ground through a circuit containing twomultimeters in series, The two multimeters shall be set, one each, to read current in milliampsand microamps. The current measurements are to be recorded during each test, afterstabilization of the readings.

Exhibit 8.3.10.a

Multi-meter arrangement in the current measuring circuit.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 37 1/25/2016 1:23 PM

Page 56: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.3.11 The discharge appliance shall be fixed in place on a test stand for safety. The standshall be initially positioned at the Test Standoff distance for the voltage schedule outlined inexhibit 8.3.11.a rating table.

Exhibit 8.3.11.a

Rating Table

Category VoltageOperating Safe

Standoff Distance, ftTest Standoff Distance, ft

I < 600 V 107.5

Solid Stream

II < 34 kV 2518.75

Solid Stream

III < 138 kV 7556.25

Solid Stream

IV < 345 kV 12593.75

Solid Stream

V < 500 kV 135101.25

Solid Stream

VI 110 V – 138kV 1530 Degree Fog

See 8.3.18

VII 139kV – 500kV 3030 Degree Fog

See 8.3.18

8.3.12 The rating table provided as exhibit 8.3.11.a establishes categories to define voltage,the operating safe standoff distance, and test standoff distance (75 percent of the operatingstandoff distance) for common electrical equipment thresholds.

8.3.13 The stream shall then be directed onto the target to ensure the proper trajectory.

8.3.14 The maximum specified flow rate of the equipment shall be used and the nozzle shallbe adjusted to produce the most consolidated (solid) stream possible. Once the flow has beenestablished and all personnel are at a safe distance, the target shall be energized to the

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 37 1/25/2016 1:23 PM

Page 57: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

specified ac voltage.

8.3.15 The concentrate shall then be proportioned into the water stream at the manufacturer’sspecified concentration and the solution shall be applied to the target for a minimum period of90 seconds.

8.3.16 Tests shall be repeated while incrementally closing the distance to the target until theleakage current has exceeded the 500uA threshold. Three tests shall be conducted at a givendistance to derive the average leakage current.

8.3.17 Acceptable performance shall be defined as maximum leakage current less than 500uA at 75 percent of the Test Standoff Distance outlined in Rating Table provided as exhibit8.3.11.a

8.3.18 Tests VI & VII outlined in the Rating Table (exhibit 8.3.11.a) shall be completed using a30 degree or greater fixed fog pattern with acceptable performance defined as follows:

.

(1) 110v-138kV: < 500 uA at 15feet

(2) 139kV-765kV: < 500 uA at 30 feet

8.3.19 The Table (exhibit 8.3.11.a) shall be used to assign a Class C rating category to thewater additive solution, based upon the distance at which the maximum leakage currentcriterion was met.

8.3.20 The following data shall be recorded for each test:

(1) Water additive and solution concentration

(2) Application and proportioning devices makes and models

(3) Ambient temperature and wind conditions

(4) Viscosity and conductivity of the concentrate and solution

(5) Leakage currents measured, including the maximum and average leakage

(6) Water pressure and flow

(7) Breakdown distance for 500 uA leakage current

8.4 Arc Conductor Test

8.4.1 Water additive solutions shall demonstrate the ability to suppress artificially generatedfaults using copper cables. The tests shall be monitored for heat release and products ofcombustion.

8.4.2 Test Set-Up

8.4.2.1 The test set up shall be configured indoors in a conditioned environment.

8.4.2.2 Test Equipment: New 500 kcmil Copper conductor 600V EAM/LSNH installed ina precast concrete distribution box type B-3.6 shall be used to produce a phase to phase faultcreating an arc with a target fault current of 2 kA. The required test voltage is 480v AC.

8.4.2.3 Tests shall be conducted using a solution of water additive made with theconcentrate, as received, in fresh water and at the concentration specified by themanufacturer. Water additive solutions made with synthetic seawater may also be tested, ifsuch usage is specified by the manufacturer.

8.4.2.4 Water additive concentrate viscosity and conductivity shall be measured andreported.

8.4.3 Test Procedures.

8.4.3.1 Number of Tests - Six tests shall be conducted to derive the average arcsuppression results. Three tests will be conducted without the water additive and anotherthree will be conducted with the solution.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 37 1/25/2016 1:23 PM

Page 58: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.3.2 To limit resistance, the 500 Kcmil cable for the test will be no longer the 25’. The 500 Kcmil cable will be connected to the 480v source and an inductor will be placed inseries between the voltage source at the faulted cable in the test box to control current. Twoinches of insulation will be removed from the inner walls of each cable at the terminal ends.The cables shall be installed at the bottom of the concrete box, with the terminal ends of eachcable positioned in manner that a 1 inch air-gap resides between the stripped portions ofcable. The approximate dimensions of the interior volume of the concrete box shall be: 33 in.wide x 33 in. long x 24 in. deep. The concrete box drawing is shown in exhibit 8.4.3.2.a

Exhibit 8.4.3.2.a

Concrete Box Drawing

8.4.3.3 One calorimeter shall be installed above the concrete box to measure theincident energy generated by the fault.

8.4.3.4 The configuration for the arc conductor test is shown in exhibit 8.4.3.4.a

Exhibit 8.4.3.4.a

Arc conductor test configuration

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 37 1/25/2016 1:23 PM

Page 59: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.3.5 The Fault duration shall be until the fault self-extinguishes or a steady state isreached.

8.4.3.6 The solution shall be discharged into the concrete service box once the cablehas been faulted so that the height of the agent reaches 6 in. above the burning cable.

8.4.3.7 Combustible gases shall be measured two-minutes prior to the inception ofcable fault through the application of the product in order to record the evolution andproduction of combustible gases created by the burning insulation on the jacket of the cable. Measurements shall continue for five minutes after the solution has risen to the prescribedlevel.

8.4.3.8 The production of combustible gases is the cause of secondary explosions inelectrical fires.

8.4.3.9 The results of the test shall be evaluated using arc suppression as the criterionfor success. The arc is considered to have been suppressed through observation and verifiedby the use of calorimetry.

8.4.3.10 The following data shall be recorded for each test:

(1) Arc duration

(2) Current and Voltage waveforms (exhibit 8.4.3.10.a)

(3) Ambient temperature

(4) Calorimeter data

(6) Video (high and normal speed)

Exhibit 8.4.3.10.a

Illustrates test report format.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 37 1/25/2016 1:23 PM

Page 60: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Additional Proposed Changes

File Name Description Approved

18a-Section_8_Oct-25.docx Text with images and tables

Statement of Problem and Substantiation for Public Comment

The development of Class C Fire test Methods need to be expanded on beyond NFPA 10. Class A and B fires range in size, type and procedure to suit applications however class C is currently only applicable to extinguishers for all to use. Test should consider the use of agents in extinguishers, fixed system applications, and manual operation for both municipal applications, utility personal who face arc suppression for down wires, transformer fires, manhole fires and the protection of other electrical systems. As technology evolves and the demand for power grows; the absence of testing and certification for viable agents for the suppression of Class C fires presents an unreasonable risk to life and property. Without the standardized testing process, certification and recognition by NFPA will make it difficult for professionals to determine a suitable agent. The lack of safe and effective agents leaves the fire services with no means of an offensive attack much less a defensive attack. Waiting for utility response ties up fires resources because these volatile incidents cannot be managed without their support. The fire services need the ability to resolve these large volume weather driven events and return to fire duty.

Related Item

First Revision No. 18-NFPA 18A-2015 [New Section after 7.7]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: James Lynch

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 37 1/25/2016 1:23 PM

Page 61: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Organization: Amped I Research & Development

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Mon Oct 26 11:53:29 EDT 2015

Copyright Assignment

I, James Lynch, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights incopyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this PublicComment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am James Lynch, and I agree to be legally bound by the above Copyright Assignmentand the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwrittensignature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 37 1/25/2016 1:23 PM

Page 62: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Chapter 8 Class C Fire Test Methods 8.1 General. Water additive solutions for Class C fires shall be tested and listed in accordance with one or more of the following test procedures.

(1) Extinguisher test (2) Manual Operations test (3) Arcing Conductor test

8.2 Extinguisher Test 8.2.1 The safe use of water additives in extinguishers to mitigate or suppress a Class C fire shall be evaluated through the following test method. The test and setup has been informed by ANSI / UL 711 requiring a test voltage of 100kV AC to be applied at 36” which is the minimum approach distance for contact hazard as defined by OSHA 1910.269 Table R-7 found below in Exhibit 8.2.1.a Exhibit 8.2.1.a

8.2.3 The pass/fail criterion shall be a maximum measured leakage current below 500uA at 36”. As informed by NFPA 70E Standards for Electrical Safety in the Workplace (effects of current of the human body - 1 mA is the perception threshold level so a leakage half of that value to pass the test is required) 8.2.4 Water additives shall be evaluated for viscosity and surface tension values to determine if the agent pooling will be sufficiently large enough to expand beyond the standoff distance which could pose the risk of electrocution. If it is found the agent cannot spread beyond the standoff distance as stated in the instructions the agent shall not be subjected to the conductivity test required by NFPA 10.

Page 63: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.2.5 The water additive solution shall be prepared at the manufacturer’s minimum and maximum recommended concentrations. 8.2.6 Use of these extinguishers should be limited to trained fire fighters, such as fire services meeting the qualifications of NFPA 1001, private brigades who are NFPA 1081 qualified, and Electrically Qualified Workers 1910.332 (b)(3), as defined by OSHA. 8.3 Manual Operations Test 8.3.1 This section of code addresses the ability of water additive solutions to be evaluated for use in manual firefighting operations to suppress Class C fires or on fires impinged by “Live” electrical sources. 8.3.2 The agent shall be tested with application and mixing hardware specified by the manufacturer and under the worst case application conditions, including consolidated stream and maximum flow rate. 8.3.3 The test apparatus shall be configured and the agent prepared for application per the manufacturers written instructions 8.3.4 Tests shall be conducted using a solution of water additive made with the concentrate, as received, in fresh water and at the concentration specified by the manufacturer. Water additive solutions made with synthetic seawater may also be tested, if such usage is specified by the manufacturer. 8.3.5 Tests shall be conducted only when the ambient temperature is above 5°C (40°F) and in still air. If tested outdoors, wind speeds shall be less that 5 miles/hour (8 km/hour). 8.3.6 Testing shall be conducted similarly to UL 711, Rating and Fire Testing of Fire Extinguishers, section 9,but scaled for manual firefighting operations using AC or DC. 8.3.7 The 12 inch by 12 inch target shall be replaced with a 138 kV disconnect switch such as used in an electrical substation or other appropriate target for the category voltage. Illustration below is a typical electrical substation disconnect switch. Exhibit 8.3.7.a 138Kv substation Disconnect switch

Page 64: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.3.8 The disconnect switch shall be located at the top of the bus bar and energized using a power supply that is capable of supplying the desired test voltage while the insulators isolate the bus bar from ground. 8.3.9 Disconnect switches designed for target voltages above 138kV, such as 345kV and 500kV, are ideal since their designs consider insulation from a ground reference via the insulators. 8.3.10 A wire shall be inserted into the nozzle to ensure contact is made with the stream of solution being tested. The wire shall be attached to ground through a circuit containing two multimeters in series, The two multimeters shall be set, one each, to read current in milliamps and microamps. The current measurements are to be recorded during each test, after stabilization of the readings. Exhibit 8.3.10.a Multi-meter arrangement in the current measuring circuit.

Page 65: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.3.11 The discharge appliance shall be fixed in place on a test stand for safety. The stand shall be initially positioned at the Test Standoff distance for the voltage schedule outlined in exhibit 8.3.11.a rating table. Exhibit 8.3.11.a Rating Table

Category Voltage Operating Safe Standoff

Distance, ft

Test Standoff Distance, ft

I < 600 V 10 7.5

Solid Stream

II < 34 kV 25 18.75

Solid Stream

III < 138 kV 75 56.25

Solid Stream

IV < 345 kV 125 93.75

Solid Stream

V < 500 kV 135 101.25

Solid Stream

VI 110 V – 138kV 15 30 Degree Fog

See 8.3.18

VII 139kV – 500kV 30 30 Degree Fog

See 8.3.18

8.3.12 The rating table provided as exhibit 8.3.11.a establishes categories to define voltage, the operating safe standoff distance, and test standoff distance (75 percent of the operating standoff distance) for common electrical equipment thresholds. 8.3.13 The stream shall then be directed onto the target to ensure the proper trajectory. 8.3.14 The maximum specified flow rate of the equipment shall be used and the nozzle shall be adjusted to produce the most consolidated (solid) stream possible. Once the flow has been established and all personnel are at a safe distance, the target shall be energized to the specified ac voltage.

Page 66: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.3.15 The concentrate shall then be proportioned into the water stream at the manufacturer’s specified concentration and the solution shall be applied to the target for a minimum period of 90 seconds. 8.3.16 Tests shall be repeated while incrementally closing the distance to the target until the leakage current has exceeded the 500uA threshold. Three tests shall be conducted at a given distance to derive the average leakage current. 8.3.17 Acceptable performance shall be defined as maximum leakage current less than 500 uA at 75 percent of the Test Standoff Distance outlined in Rating Table provided as exhibit 8.3.11.a 8.3.18 Tests VI & VII outlined in the Rating Table (exhibit 8.3.11.a) shall be completed using a 30 degree or greater fixed fog pattern with acceptable performance defined as follows: .

(1) 110v-138kV: < 500 uA at 15feet (2) 139kV-765kV: < 500 uA at 30 feet

8.3.19 The Table (exhibit 8.3.11.a) shall be used to assign a Class C rating category to the water additive solution, based upon the distance at which the maximum leakage current criterion was met. 8.3.20 The following data shall be recorded for each test:

(1) Water additive and solution concentration (2) Application and proportioning devices makes and models (3) Ambient temperature and wind conditions (4) Viscosity and conductivity of the concentrate and solution (5) Leakage currents measured, including the maximum and average leakage (6) Water pressure and flow (7) Breakdown distance for 500 uA leakage current

8.4 Arc Conductor Test 8.4.1 Water additive solutions shall demonstrate the ability to suppress artificially generated faults using copper cables. The tests shall be monitored for heat release and products of combustion. 8.4.2 Test Set-Up 8.4.2.1 The test set up shall be configured indoors in a conditioned environment.

Page 67: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.2.2 Test Equipment: New 500 kcmil Copper conductor 600V EAM/LSNH installed in a precast concrete distribution box type B-3.6 shall be used to produce a phase to phase fault creating an arc with a target fault current of 2 kA. The required test voltage is 480v AC. 8.4.2.3 Tests shall be conducted using a solution of water additive made with the concentrate, as received, in fresh water and at the concentration specified by the manufacturer. Water additive solutions made with synthetic seawater may also be tested, if such usage is specified by the manufacturer. 8.4.2.4 Water additive concentrate viscosity and conductivity shall be measured and reported. 8.4.3 Test Procedures. 8.4.3.1 Number of Tests - Six tests shall be conducted to derive the average arc suppression results. Three tests will be conducted without the water additive and another three will be conducted with the solution. 8.4.3.2 To limit resistance, the 500 Kcmil cable for the test will be no longer the 25’. The 500 Kcmil cable will be connected to the 480v source and an inductor will be placed in series between the voltage source at the faulted cable in the test box to control current. Two inches of insulation will be removed from the inner walls of each cable at the terminal ends. The cables shall be installed at the bottom of the concrete box, with the terminal ends of each cable positioned in manner that a 1 inch air-gap resides between the stripped portions of cable. The approximate dimensions of the interior volume of the concrete box shall be: 33 in. wide x in. long x 24 in. deep. The concrete box drawing is shown in exhibit 8.4.3.2.a

Page 68: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Exhibit 8.4.3.2.a Concrete Box Drawing

Page 69: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.3.3 One calorimeter shall be installed above the concrete box to measure the incident energy generated by the fault. 8.4.3.4 The configuration for the arc conductor test is shown in exhibit 8.4.3.4.a Exhibit 8.4.3.4.a Arc conductor test configuration

8.4.3.5 The Fault duration shall be until the fault self-extinguishes or a steady state is reached. 8.4.3.6 The solution shall be discharged into the concrete service box once the cable has been faulted so that the height of the agent reaches 6 in. above the burning cable. 8.4.3.7 Combustible gases shall be measured two-minutes prior to the inception of cable fault through the application of the product in order to record the evolution and production of combustible gases created by the burning insulation on the jacket of the cable. Measurements shall continue for five minutes after the solution has risen to the prescribed level.

Page 70: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

8.4.3.8 The production of combustible gases is the cause of secondary explosions in electrical fires. 8.4.3.9 The results of the test shall be evaluated using arc suppression as the criterion for success. The arc is considered to have been suppressed through observation and verified by the use of calorimetry. 8.4.3.10 The following data shall be recorded for each test:

(1) Arc duration (2) Current and Voltage waveforms (exhibit 8.4.3.10.a) (3) Ambient temperature (4) Calorimeter data (6) Video (high and normal speed)

Exhibit 8.4.3.10.a Illustrates test report format.

Page 71: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale
Page 72: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Public Comment No. 2-NFPA 18A-2015 [ Section No. E.1.2.3 ]

E.1.2.3 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

UL 162, Foam Equipment and Liquid Concentrates, 1994, revised 1999 2015 .

ANSI/UL 300, Fire Testing of Fire Extinguishing Systems for Protection of Commercial CookingEquipment, 2005, revised 2014 .

ANSI/UL711/ULC CAN /ULC - S508, Rating and Fire Testing of Fire Extinguishers, 2004,revised 2009 2013 .

Statement of Problem and Substantiation for Public Comment

Referenced current SDO standard numbers, and editions.

Related Public Comments for This Document

Related Comment Relationship

Public Comment No. 1-NFPA18A-2015 [Chapter 2]

Referenced current SDO names, addresses, standardnumbers, and editions.

Related Item

First Revision No. 7-NFPA 18A-2015 [Section No. E.1.2.1]

Submitter Information Verification

Submitter NFPA User ID: [email protected]

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Telephone:

Street Address:

City:

State:

Zip:

Submittal Date: Sun Oct 11 20:35:15 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 37 1/25/2016 1:23 PM

Page 73: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

Copyright Assignment

I, Aaron Adamczyk, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rightsin copyright in this Public Comment (including both the Proposed Change and the Statement of Problem andSubstantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of theNFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am theauthor of this Public Comment and that I have full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am Aaron Adamczyk, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I amcreating an electronic signature that will, upon my submission of this form, have the same legal force and effect as ahandwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 37 1/25/2016 1:23 PM

Page 74: Technical Committee on Water Additives for Fire Control and ......5. First Revisions were created for NFPA 18A Task Group TG Chair Members Class C Fire – Finalize FR-17 Anthony Natale

 

 

 

NFPA 1150 – No Public Comments 

Received