Insulation Second Issue June 2016 Low Energy – Low Carbon Buildings Routes to Compliance: Fire Safety FOR FAÇADES INCORPORATING KINGSPAN KOOLTHERM ® K15 RAINSCREEN BOARD ON BUILDINGS WITH A HABITABLE STOREY 18 M, OR GREATER, ABOVE GROUND LEVEL

Technical Bulletin: Routes to Compliance: Fire Safety

Embed Size (px)

Citation preview

Page 1: Technical Bulletin: Routes to Compliance: Fire Safety

Insulat ion

Second Issue June 2016

Low Energy – Low Carbon Buildings

Routes to Compliance: Fire SafetyFOR FAÇADES INCORPORATING KINGSPAN KOOLTHERM® K15 RAINSCREEN BOARD ON BUILDINGS WITH A HABITABLE STOREY 18 M, OR GREATER, ABOVE GROUND LEVEL

Page 2: Technical Bulletin: Routes to Compliance: Fire Safety

Contents

2

Page

Introduction 3 About this Document 3

Routes to Compliance 4 Approved Documents B Volume 2 & Technical Handbooks Section 2 4 Building Control Alliance (BCA) 5

Compliance Route forKingspan Kooltherm® K15 Rainscreen Board 6 Step–by–step Guide to Compliance 6 Linear Route 6 Performance–based Route 6 Fire Safety Engineering Route 6 Kingspan Insulation’s Commitment 6

Other Design Considerations 7 Factors to Consider 7 Kingspan Kooltherm® K15 Rainscreen Board Benefits 7

Case Studies 8 Woodberry Down, Residential & Commercial Regeneration, Hackney 8 Notre Dame Catholic College, Liverpool 10 Queen Elizabeth University Hospital, Glasgow, Scotland 12 Unite, Student Accommodation, Portsmouth 14

Appendix A 16 Step–by–step Guide to Compliance 16

Appendix B 17 Exact System Test Data 17

Appendix C 18 Desktop Study Reports 18

Page 3: Technical Bulletin: Routes to Compliance: Fire Safety

Introduction

Barnsley College, Old Mill Lane Campus, South Yorkshire.

3

About this DocumentRainscreen and masonry façades are popular building envelope specifications, particularly in high–rise applications. They allow architectural freedom, whilst providing suitable protection against the elements.

However, choosing the best route to compliance, with fire safety regulatory requirements in Great Britain, necessitates a clear understanding of the complexities and the common misconceptions that surround the use of insulation in these constructions. The route that best serves the purpose of the building and the needs of stakeholders, whilst producing a well–balanced result, may not always be the most obvious option.

This technical bulletin examines the use of insulation in the façades of buildings with a habitable storey 18 metres, or greater, above ground level. It also advises on how to interpret the guidance given in Approved Documents B Volume 2, Technical Handbooks Section 2 and Building Control Alliance Technical Guidance Note 18, for meeting the fire safety requirements of the Building Regulations / Standards for external fire spread.

Page 4: Technical Bulletin: Routes to Compliance: Fire Safety

Approved Documents B Volume 2 & Technical Handbooks Section 2There are three routes to compliance with the fire safety requirements of the Building Regulations / Standards regarding the insulation in façades on buildings with a habitable storey 18 metres, or greater, above ground level.

Linear RouteFirstly, a linear route to compliance is offered by the technical guidance given in Approved Documents B Volume 2: Fire Safety – Buildings other than Dwellinghouses (separate editions for England and Wales), and Technical Handbooks Section 2: Fire – Domestic & Non–domestic (Scotland).

This route requires the insulation to be of limited combustibility (England & Wales) or non–combustible (Scotland), which, in this context, is defined by being a material that either is ‘listed’ or has met the required performance criteria after having been subjected to specific small scale fire tests. Unlike in large scale fire tests, testing is performed on the insulation in isolation from all other materials comprising the façade system. As such, material performance determined via this route is not wholly representative of that for the complete system build–up.

Notwithstanding the classification of the insulation in terms of combustibility, there are separate provisions for the external surfaces of the façade system in relation to the building height, use and boundary. For instance, where the boundary of a building is no greater than one metre, the façade should be Class 0 / Low Risk / Euroclass B–s3d2 or better, regardless of whether the insulation is of limited combustibility or non–combustible.NB Approved Documents B Volume 1: Fire Safety – Dwellinghouses (separate editions for England and Wales) refers to Approved Documents B Volume 2 for supplementary guidance in relation to unusual or very large buildings i.e. those greater than 18 metres in height.

Routes to Compliance

4

Performance–based RouteSecondly, a performance–based route is also offered. The guidance requires that the complete façade build–up meets the acceptance criteria set out in BR 135 (Fire performance of external thermal insulation for walls of multi–storey buildings), using large scale test data from:

l BS 8414–1: 2002 (Fire performance of external cladding systems. Test methods for non–loadbearing external cladding systems applied to the face of a building); or

l BS 8414–2: 2005 (Fire performance of external cladding systems. Test method for non–loadbearing external cladding systems fixed to and supported by a structural steel frame).

Fire Safety Engineering RouteThirdly, compliance with the functional fire safety standards may also be demonstrated by alternative means i.e. the adoption of a Fire Safety Engineering approach.

Based upon scientific principles from an integrated or a ‘whole building’ perspective, Fire Safety Engineering not only considers the performance of structures, systems, products and materials when exposed to fire, it also includes human behavioural aspects, fire prevention and active and passive fire protection measures e.g. effective means of egress and adequate measures for alarm, detection, control and extinguishment.

Furthermore, it can facilitate innovation in building design without compromising fire safety, particularly in some large and complex buildings, as well as multi–purpose buildings, where it may be the only practical way to achieve a satisfactory level of fire safety.

If taking this advanced route to compliance, the guidance given in a number of supporting published documents can be followed. However, Approved Documents B Volume 2 (both England and Wales) refer directly to BS 7974: 2001 (Application of fire safety engineering principles to the design of buildings. Code of practice), while Technical Handbooks Section 2 refers directly to IFEG: 2005 (International Fire Engineering Guidelines).

Queen Elizabeth University Hospital, Glasgow, Scotland.

Page 5: Technical Bulletin: Routes to Compliance: Fire Safety

Kingswood Academy, Hull.5

Bauhaus Rossetti Place, Mixed–use Development, Manchester.

Building Control Alliance (BCA) With the aim of addressing common misconceptions as regards to the use of combustible materials within the façade system of residential buildings containing a storey 18 metres, or greater, above ground level, industry group, BCA, operating in England and Wales, issued its Technical Guidance Note 18: Use of Combustible Cladding Materials on Residential Buildings (Issue 1: June 2015).

Whilst it reiterates the guidance given in Approved Document B Volume 2 (England) for the Fire Safety Engineering route, it, however, expands in an advisory manner, upon the guidance given for the linear and performance–based routes and in addition, categorises each method into ‘Options’.

The guidance given for the linear route differs in that it explicitly states that for the entire façade area, both above and below 18 metres, all major elements comprising the façade system, including the internal lining board and the external facing material, should be of limited combustibility.

BCA Technical Guidance Note 18 advises that the preferred method of demonstrating compliance is to submit evidence to the Building Control Body (BCB), showing that the complete proposed façade system has been assessed in accordance with the acceptance criteria (i.e. external fire spread, internal fire spread and mechanical performance), set out in BR 135, using data from large scale tests carried out by an independent United Kingdom Accreditation Service (UKAS) accredited testing body, to BS 8414–1: 2002 and BS 8414–2: 2005.

However, given the sheer number of possible façade build–ups combined with increasingly elaborate and innovative materials, fire test data may not exist for every possible build–up. In circumstances where such empirical data is absent, another option for demonstrating compliance is offered.

This option allows the submission of a Desktop Study Report from a suitably qualified fire specialist, which states whether, in their professional opinion, the acceptance criteria of BR 135 would be met with the proposed system. It requires the report to be supported by the results of testing by a suitable UKAS accredited testing body, and to specifically reference any tests that have been carried out on the product.

Since it was first outlined in the June 2014 edition of BCA Technical Guidance Note 18, this option has become a commonly adopted method of demonstrating compliance with an increasing number of private and local authority Building Control Bodies (BCB’s), as well as structural warranty and insurance providers, upholding the guidance contained within. This includes:

l Local Authority Building Control (LABC);

l the building control and warranty functions of National House Building Council (NHBC);

l LABC Warranty, new home and structural warranty provider for LABC; and

l building control, insurance service and structural warranty provider, Premier Guarantee.

Page 6: Technical Bulletin: Routes to Compliance: Fire Safety

6

Ebbw Fawr, Learning Community School, Blaenau Gwent, Wales.

Compliance Routes for Kingspan Kooltherm® K15 Rainscreen Board

Kingspan Kooltherm® K15 Rainscreen Board is designed for use in façade systems with either a proprietary or non–proprietary external finish and in both masonry and steel frame system (SFS) constructions. Kingspan Kooltherm® K15 Rainscreen Board is ideal for both new build and refurbishment.

Step–by–step Guide to ComplianceTo assist designers in identifying the most appropriate route to take for compliance with the fire safety requirements of the Building Regulations / Standards, when using Kingspan Kooltherm® K15 Rainscreen Board in the façades of buildings with a habitable storey 18 metres, or greater, above ground level, Kingspan Insulation has developed a step–by–step guide. The guide draws upon the guidance given in Approved Documents B Volume 2, Technical Handbooks Section 2 and BCA Technical Guidance Note 18.

It is important to note that firstly, there is no requirement to have to consider the routes in a particular order and that secondly, it is possible to adopt a hybrid approach to demonstrate compliance by combining, in whole, or in part, different elements of each method.

Furthermore, the specified construction may already meet the requirements for a number of applications. As such, Kingspan Insulation recommends consulting the warranty provider, or other authorising body, in the first instance.

Refer to Appendix A for details of the step–by–step guide to compliance.

Linear RouteBCA Option 1Although Kingspan Kooltherm® K15 Rainscreen Board is Class 0, as defined by the Building Regulations, the linear route to compliance is not open.

Kingspan Kooltherm® Rainscreen Board can however, be deemed compliant for use in the façades of buildings not exceeding 18 metres in height.

Performance–based RouteBCA Option 2Kingspan Kooltherm® K15 Rainscreen Board has been tested in differing thicknesses with a range of cladding materials to BS 8414–1: 2002 and BS 8414–2: 2005, in accordance with the performance criteria set out in BR 135.

Refer to Appendix B for details of the build–ups that have been successfully tested.

BCA Option 3A cohort of qualified fire specialists have carried out a large number of project specific desktop studies assessing the suitability of Kingspan Kooltherm® K15 Rainscreen Board, in differing façade build–ups, for use in buildings with a habitable storey 18 metres, or greater, above ground level.

Refer to Appendix C for examples of build–ups that have undergone an assessment.

Fire Safety Engineering RouteBCA Option 4This route requires every factor of the design, construction, use and management of the building to be fully considered. Whilst it does not rely solely on the standalone fire performance of individual products, the data that is available for Kingspan Kooltherm® K15 Rainscreen Board can form an essential part of the information that would be needed if adopting this approach.

Kingspan Insulation’s CommitmentKingspan Insulation is committed to a continuing program of testing, both independently and collaboratively, to increase the breadth of BS 8414 fire test data for Kingspan Kooltherm® K15 Rainscreen Board in common façade build–ups. The results of these tests will also provide valuable additional data to help those engaged in desktop studies or fire safety engineering.

Furthermore, Kingspan Insulation has a dedicated technical advisory service for those seeking assistance on projects where Kingspan Kooltherm® K15 Rainscreen Board is specified for use in high–rise buildings.

Kingspan Insulation will endeavour to assist those seeking:

l practical guidance on how to satisfy the requirements of the fire safety engineer;

l collaboration on large scale testing programs; or

l evidence of performance e.g. official reports and certification.

Email [email protected] for further information.

Page 7: Technical Bulletin: Routes to Compliance: Fire Safety

Other Design Considerations

Factors to ConsiderIrrespective of the chosen route to compliance, there are other fundamental aspects of the building design that must be considered. For example, use of compartmentalisation to limit internal fire spread or the separation distance between buildings so as to limit the risk of fire spreading from one building to another.

Whilst the fire performance of the building envelope is a vital element of good construction, it is just one of a number of factors that should influence the façade insulation specification. Since the primary role of the insulation is to conserve energy, thermal performance must also be a key consideration. Other considerations include:

l BBA Certification;

l LABC Registered Detail status;

l environmental impact and responsible sourcing;

l moisture resistance, air–infiltration and durability;

l insulant thickness and weight, thus associated load implications;

l cost and Return on Investment (ROI);

l ease of installation;

l availability and logistics; and

l access to technical support from specification through installation to maintenance.

None of these elements should be regarded in isolation. They should be considered in the context of the building as a whole – its overall design, its intended use, and any associated risks or benefits arising from selected materials in situ.

7

Kingspan Kooltherm® K15 Rainscreen Board BenefitsKingspan Kooltherm® K15 Rainscreen Board comprises a premium performance rigid thermoset fibre–free phenolic insulation core faced on both sides with a low emissivity composite foil. The core is manufactured with a blowing agent that has zero Ozone Depletion Potential (ODP) and low Global Warming Potential (GWP).

Kingspan Kooltherm® K15 Rainscreen Board, produced at Kingspan Insulation’s Pembridge, UK, manufacturing facility offers the following benefits:

l thermally efficient – a thermal conductivity as low as 0.020 W/m·K makes it the most thermally efficient insulation product commonly used in façade systems;

l thin insulation – the thinnest commonly used rainscreen insulation product for any specific U–value;

l BBA certified – its use is covered by BBA Certificate 14/5134;

l LABC Registered Detail – certified as Registered Detail EWWS165, it is the first insulation board to achieve LABC Registered Detail status as a thermal insulation layer in a rainscreen cladding system;

l ‘A+’ Green Guide Rating – an Ecoprofile, certified by BRE Certification to the 2008 BRE Environmental Profiles Methodology has been created for the product and BRE has assigned the boards a Green Guide Summary Rating of A+;

l BES 6001 certified – certified ‘Excellent’ to BES 6001 (Responsible Sourcing of Construction Products);

l manufactured to the highest standards – under a management system certified to ISO 9001: 2008 (Quality management systems. Requirements), ISO 14001: 2004 (Environmental Management Systems. Requirements) and BS OHSAS 18001: 2007 (Health & Safety Management Systems. Requirements);

l closed cell structure – resists moisture and water vapour ingress – a problem which can be associated with open cell materials such as mineral fibre and which can result in reduced thermal performance;

l unaffected by air infiltration – a problem that can be experienced with mineral fibre and which can reduce thermal performance;

l safe and easy to install – fibre–free insulation core; and

l Return on Investment (ROI) up to 4250% – when compared with common insulation solutions, its use in new commercial buildings can provide an ROI of over 4000% on the additional cost of the insulation by creating greater marketable internal floor area, without compromising the designed building footprint, for details go to www.kingspaninsulation.co.uk/RealValueofSpace.Kingswood Academy, Hull.

Page 8: Technical Bulletin: Routes to Compliance: Fire Safety

Case Studies

The Woodberry Down regeneration is an ambitious project – the result of a collaborative partnership between Berkeley Homes, Hackney Council, Genesis Housing Association and the residents’ group, Woodberry Down Community Organisation. Once completed it will include three new public parks; a community centre and library; a children’s centre; and

retail and commercial opportunities.

“Kingspan Kooltherm® K15 Rainscreen Board was installed as part of the anodised rainscreen cladding used on the top storeys of many of the blocks. These sections extend beyond 18 metres and it was, therefore, essential that the product offered excellent fire performance.”

8

Woodberry Down, Residential & Commercial Regeneration, HackneyPremium performance products from Kingspan Insulation have been used to insulate new high and low rise buildings as part of one of London’s largest and most ambitious regeneration programmes.

Woodberry Down was once heralded as the ‘estate of the future’ but in recent years had suffered from an increasing number of issues including: subsidence, asbestos, damp, and poor insulation. An eight phase regeneration plan will replace outdated concrete tower blocks with more than 5,500 brand new homes over the next 20 years.

Architect Hawkins\Brown specified Kingspan Kooltherm® K12 Framing Board and Kingspan Kooltherm® K15 Rainscreen Board for Kick Start Sites 2 and 5 within the master plan, comprising 710 residential units and over 1500 sq.m of commercial space, spread across a number of blocks.

Kingspan Kooltherm® K12 Framing Board was also installed within a steel framing system behind the main brickwork façade elements.

Kingspan Kooltherm® K15 Rainscreen Board was installed as part of the anodised rainscreen cladding used on the top storeys of many of the blocks. These sections extend beyond 18 metres and it was, therefore, essential that the product offered excellent fire performance.

Page 9: Technical Bulletin: Routes to Compliance: Fire Safety

9

Page 10: Technical Bulletin: Routes to Compliance: Fire Safety

Will Griffiths from Cull & Griffiths Ltd. commented on the installation:

“We were extremely pleased to be able to support the local community as part of this special project. The Kingspan Kooltherm® K15 Rainscreen Board is both lightweight and easy to cut to size onsite. This made the installation process straightforward for our installers.”

Now complete, Notre Dame Catholic College complements the Great Homer Street regeneration scheme on the outskirts of Liverpool city centre.

10

Case Studies

Notre Dame Catholic College, LiverpoolKingspan Kooltherm® K15 Rainscreen Board has been used to insulate an ambitious open–plan school in Liverpool, designed to provide engaging architecture on a limited budget.

Designed by Sheppard Robson, Notre Dame Catholic College uses an innovative model, developed with Liverpool City Council, which combines a standardised clear–span outer shell with modular internal spaces. These spaces can be developed to meet the specific needs and requirements of each school and can even be adapted over time. The internal area combines large break–out areas with multi–storey education and study spaces including an amphitheatre, chapel, and demountable classrooms.

The school’s outer shell is clad in a pearlescent metal façade and to maximise building fabric performance, Sheppard Robson specified over 3000 sq.m of Kingspan Kooltherm® K15 Rainscreen Board.

To help strengthen the local economy, Willmott Dixon Construction ensured 70% of the project work force was sourced from the surrounding area. As part of this approach, the rainscreen cladding system and 60 mm Kingspan Kooltherm® K15 Rainscreen Board were installed by local SFS experts, Cull & Griffiths Ltd.

Page 11: Technical Bulletin: Routes to Compliance: Fire Safety

11

Page 12: Technical Bulletin: Routes to Compliance: Fire Safety

Queen Elizabeth University Hospital, Glasgow, ScotlandGlasgow’s £842million ‘super hospital’ is on course to achieve a BREEAM ‘Excellent’ rating with the help of premium performance Kingspan Kooltherm® K15 Rainscreen Board.

Queen Elizabeth University Hospital combines cutting–edge laboratory facilities with a 166,000 sq.m adult and children’s hospital designed to manage 110,000 A&E patients every year. The 14 storey central hospital building has been designed by IBI Group with an extended quadrangular star layout which ensures all patient rooms not only have external windows, but grand views over the city. The project was delivered under budget and five weeks ahead of schedule by Brookfield Multiplex.

Kingspan Kooltherm® K15 Rainscreen Board was specified to insulate a range of façade systems on the external walls of the project. The product delivers outstanding performance with thermal conductivities as low as 0.020 W/m.K. This contributed towards an overall U–value of just 0.15 W/m2.K, helping to minimise heating demand and assisting in the award of credits in the Energy section of the BREEAM assessment.

12

Case Studies

Kingspan Kooltherm® K15 Rainscreen Board has also been assigned a highest possible 2008 Green Guide Summary Rating of A+ and is certified ‘Very Good’ under BES 6001: Responsible Sourcing of Construction Products standard, meeting the requirements of the ‘Embodied Impact’ and ‘Responsible Sourcing’ BREEAM credits.

The hospital’s unusual design created additional challenges for specialist contractor, Prater. Operations manager, William Morrison, discussed how the Kingspan Kooltherm® K15 Rainscreen Board helped them to meet the requirements:

“The shape of the building with many curves, angles and land locked areas made the need for lightweight, flexible and robust material imperative. Kingspan Kooltherm® K15 Rainscreen Board provided the necessary thermal performance, ease of site installation and most importantly, resilience to the West of Scotland weather until such time the overcladding was completed.”

Page 13: Technical Bulletin: Routes to Compliance: Fire Safety

13

Page 14: Technical Bulletin: Routes to Compliance: Fire Safety

14

Unite, Student Accommodation, PortsmouthKingspan Kooltherm® K15 Rainscreen Board has been specified as part of a new £42 million purpose built student accommodation project in Portsmouth, due to its outstanding thermal performance and ability to meet the stringent fire performance requirements for the project.

Once completed, the Unite Students development will provide high quality and safe accommodation for 836 students. Cooley Architects’ design uses coloured Alpolic ACM cladding to form an eye–catching cube at the top of the 240 ft building. Kingspan Kooltherm® K15 Rainscreen Board was installed as part of the rainscreen façade system as Marvin Village, Managing Director of Metclad Contracts Ltd, explained:

“We chose to take the Desktop Study route to compliance as this would allow us to use a premium performing insulation, a fundamental component in achieving the energy efficient design requirements, whilst also demonstrating compliance with fire safety regulations.

It was therefore clear that we were seeking, not only a superior rigid phenolic insulant, but one that was backed up by a professional technical support service with a high level of expertise. Kingspan Insulation was the only rigid insulation manufacturer that offered this, helping simplify matters whilst guiding us through the routes to compliance from start to finish.”

Under the Desktop Study route to compliance, a fully qualified fire specialist was asked to draw up a report, specific to this project, on the façade system. The specialist was supplied with specifically referenced test data for the rainscreen components and planning documents including cross–sections, elevations and fire–stop details. Based on this information, they gave their approval that the entire rainscreen solution would meet the performance requirements of BR 135.

In addition, a further 75 mm thickness of Kingspan Kooltherm® K3 Floorboard was fitted on the ground floor. Both products feature a fibre–free insulation core and have been assigned a highest possible BRE Green Guide summary rating of A+. To complete the building envelope, a layer of high performance Kingspan Thermaroof® TR27 LPC/FM was also installed on the roof of the building.

Case Studies

Page 15: Technical Bulletin: Routes to Compliance: Fire Safety

15

Page 16: Technical Bulletin: Routes to Compliance: Fire Safety

Appoint a suitably qualifi ed fi re specialist to assess the suitability of the proposed

façade system.

Do they, in their professional opinion,

confi rm in a Desktop Study Report that the build–up is suitable for the designated

project, i.e. that the acceptance criteria of BR

135 would be met?

FIRE SAFETYENGINEERING ROUTE

Refer to Appendix B. Does the proposed façade system build–up match one that

has been successfully tested toBS 8414-1: 2002 or BS 8414-2: 2005, by an independent UKAS accredited testing

body, and subsequently confi rmed as having met the acceptance criteria

set out in BR 135?

LINEAR ROUTE GET IN [email protected]

01544 387 382

COMPLIANCEACHIEVED

COMPLIANCEACHIEVED

COMPLIANCEACHIEVED

COMPLIANCEACHIEVED

COMPLIANCEACHIEVED

NO YES YES YES YES

YES NO NO NO NO

COMPLIANCE ACHIEVED

PERFORMANCE BASED ROUTE

BCA OPTION 1SOLE MATERIAL PERFORMANCE

BCA OPTION 2EXACT SYSTEM TEST DATA

BCA OPTION 3DESKTOP STUDY REPORT

BCA OPTION 4SCIENTIFIC APPROACH

In accordance with Approved Documents Volume 2, Technical Handbooks Section 2 and BCA

Technical Guidance Note 18 Option 1.

For buildings with a habitable storey ≥ 18 m above ground level,

the insulant must be of limited combustibility (England & Wales),

non–combustible (Scotland),if following BCA guidance, of limited

combustibility in conjunction with the internal lining board

and external cladding materials (England & Wales).

In accordance with Approved Documents Volume 2, Technical Handbooks Section 2 and BCA

Technical Guidance Note 18 Option 2.

The assessment uses large scale fi re test data demonstrating the

performance of the complete façade assembly.

BCA Technical Guidance Note 18 requires testing to be carried out

by an independent UKAS accredited testing body.

In accordance with BCA Technical Guidance Note 18 Option 3.

Requires suffi cient, accurate and detailed information from the outset

including, but not limited to:façade build–up and fi re test data for

each component; design plans; fi re stop / barrier confi guration; material specifi cation, performance data and

relevant certifi cation.

In accordance with Approved Documents Volume 2, Technical Handbooks Section 2 and BCA

Technical Guidance Note 18 Option 4.

A sophisticated holistic approach based on scientifi c principles from

an integrated or a‘Whole Building’ perspective.

Considered the only practical way to achieve fi re safety requirements,

particularly for large, complex or multi–purpose buildings.

Kingspan Insulation’s dedicated technical advisory service will endeavour to assist those engaged in desktop studies or fi re safety engineering and those seeking:

• practical guidance on how to satisfy the requirements of the fi re safety engineer;

• collaboration on large scale testing programs;

• evidence of performance by way of offi cial reports and certifi cation; or

• anything else.

� � � � �

The proposed façade system build–up,

incorporating Kingspan Kooltherm® K15 Rainscreen

Board, meets the acceptance criteria set out in BR 135 and can thus be deemed compliant for all storeys of the building.

The proposed façade system build–up,

incorporating Kingspan Kooltherm® K15 Rainscreen

Board would meet the acceptance criteria set out in BR 135 and can thus be deemed compliant for all storeys of the building.

The proposed façade system build–up,

incorporating Kingspan Kooltherm® K15

Rainscreen Board, meets the acceptance criteria set out in BR 135 and can thus be deemed

compliant for all storeys of the building.

Compliance is not contingent upon

the standalone fi re performance of the

proposed façade system or Kingspan Kooltherm® K15 Rainscreen Board. Compliance can only

be determined after all factors that affect the building are considered

holistically.

Kingspan Kooltherm® K15 Rainscreen Board is Class 0, as defi ned by

the Building Regulations and can thus be deemed

compliant.

Does the building have a habitable storey 18 metres, or greater, above

ground level?

Has the the proposed façade system build–up

undergone an assessment and been subsequently confi rmed, in a Desktop Study Report and in the professional opinion of a suitably qualifi ed fi re specialist, suitable for the designated project i.e. that the acceptance criteria of BR 135 would

be met?

Is the available data for the proposed façade system, including that for

Kingspan Kooltherm® K15 Rainscreen Board in isolation, suffi cient to

form part of the information that is required to undertake a detailed

analysis of relevant, specifi c aspects of fi re safety engineering in buildings?

16

Appendix A

Compliance Routes for Kingspan Kooltherm® K15 Rainscreen BoardStep–by–step guide to compliance with the fire safety requirements of the Building Regulations / Standards when using Kingspan Kooltherm® K15 Rainscreen Board in the façades of buildings. This guide draws upon the guidance given in Approved Documents B Volume 2, Technical Handbooks Section 2 and BCA Technical Guidance Note 18.

Page 17: Technical Bulletin: Routes to Compliance: Fire Safety

Appoint a suitably qualifi ed fi re specialist to assess the suitability of the proposed

façade system.

Do they, in their professional opinion,

confi rm in a Desktop Study Report that the build–up is suitable for the designated

project, i.e. that the acceptance criteria of BR

135 would be met?

FIRE SAFETYENGINEERING ROUTE

Refer to Appendix B. Does the proposed façade system build–up match one that

has been successfully tested toBS 8414-1: 2002 or BS 8414-2: 2005, by an independent UKAS accredited testing

body, and subsequently confi rmed as having met the acceptance criteria

set out in BR 135?

LINEAR ROUTE GET IN [email protected]

01544 387 382

COMPLIANCEACHIEVED

COMPLIANCEACHIEVED

COMPLIANCEACHIEVED

COMPLIANCEACHIEVED

COMPLIANCEACHIEVED

NO YES YES YES YES

YES NO NO NO NO

COMPLIANCE ACHIEVED

PERFORMANCE BASED ROUTE

BCA OPTION 1SOLE MATERIAL PERFORMANCE

BCA OPTION 2EXACT SYSTEM TEST DATA

BCA OPTION 3DESKTOP STUDY REPORT

BCA OPTION 4SCIENTIFIC APPROACH

In accordance with Approved Documents Volume 2, Technical Handbooks Section 2 and BCA

Technical Guidance Note 18 Option 1.

For buildings with a habitable storey ≥ 18 m above ground level,

the insulant must be of limited combustibility (England & Wales),

non–combustible (Scotland),if following BCA guidance, of limited

combustibility in conjunction with the internal lining board

and external cladding materials (England & Wales).

In accordance with Approved Documents Volume 2, Technical Handbooks Section 2 and BCA

Technical Guidance Note 18 Option 2.

The assessment uses large scale fi re test data demonstrating the

performance of the complete façade assembly.

BCA Technical Guidance Note 18 requires testing to be carried out

by an independent UKAS accredited testing body.

In accordance with BCA Technical Guidance Note 18 Option 3.

Requires suffi cient, accurate and detailed information from the outset

including, but not limited to:façade build–up and fi re test data for

each component; design plans; fi re stop / barrier confi guration; material specifi cation, performance data and

relevant certifi cation.

In accordance with Approved Documents Volume 2, Technical Handbooks Section 2 and BCA

Technical Guidance Note 18 Option 4.

A sophisticated holistic approach based on scientifi c principles from

an integrated or a‘Whole Building’ perspective.

Considered the only practical way to achieve fi re safety requirements,

particularly for large, complex or multi–purpose buildings.

Kingspan Insulation’s dedicated technical advisory service will endeavour to assist those engaged in desktop studies or fi re safety engineering and those seeking:

• practical guidance on how to satisfy the requirements of the fi re safety engineer;

• collaboration on large scale testing programs;

• evidence of performance by way of offi cial reports and certifi cation; or

• anything else.

� � � � �

The proposed façade system build–up,

incorporating Kingspan Kooltherm® K15 Rainscreen

Board, meets the acceptance criteria set out in BR 135 and can thus be deemed compliant for all storeys of the building.

The proposed façade system build–up,

incorporating Kingspan Kooltherm® K15 Rainscreen

Board would meet the acceptance criteria set out in BR 135 and can thus be deemed compliant for all storeys of the building.

The proposed façade system build–up,

incorporating Kingspan Kooltherm® K15

Rainscreen Board, meets the acceptance criteria set out in BR 135 and can thus be deemed

compliant for all storeys of the building.

Compliance is not contingent upon

the standalone fi re performance of the

proposed façade system or Kingspan Kooltherm® K15 Rainscreen Board. Compliance can only

be determined after all factors that affect the building are considered

holistically.

Kingspan Kooltherm® K15 Rainscreen Board is Class 0, as defi ned by

the Building Regulations and can thus be deemed

compliant.

Does the building have a habitable storey 18 metres, or greater, above

ground level?

Has the the proposed façade system build–up

undergone an assessment and been subsequently confi rmed, in a Desktop Study Report and in the professional opinion of a suitably qualifi ed fi re specialist, suitable for the designated project i.e. that the acceptance criteria of BR 135 would

be met?

Is the available data for the proposed façade system, including that for

Kingspan Kooltherm® K15 Rainscreen Board in isolation, suffi cient to

form part of the information that is required to undertake a detailed

analysis of relevant, specifi c aspects of fi re safety engineering in buildings?

17

Page 18: Technical Bulletin: Routes to Compliance: Fire Safety

18

Appendix B

Exact System Test DataBuild–ups incorporating Kingspan Kooltherm® K15 Rainscreen Board successfully tested to BS 8414–1: 2002 and BS 8414–2: 2005, in accordance with the performance criteria set out in BR 135. In all cases shown, fire stopping was provided by intumescent fire breaks positioned at floor level and around all openings, in accordance with the guidance given in Approved Documents B Volume 2 and Technical Handbooks Section 2.

ArGeTon 30 mm non–combustible terracotta tile cladding fixed to an aluminium vertical support railing system on helping hand brackets.

80 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm cement based calcium sheathing board.

Two layers of 12.5 mm plasterboard fixed to 150 mm SFS.

Build–up: ArGeTon terracotta tile cladding & SFS

Report No.: 291642

6 mm non–combustible cement board cladding fixed to an aluminium vertical support railing system at600 mm centres.

Stofix ventilated brick cladding system on horizontal rails secured to a Stofix vertical railing system using Stofix right angle brackets.

60 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to 100 mm blockwork substrate.

Two layers of 60 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to 12 mm cement particle sheathing board.

Build–up: Cement board cladding & masonry blockwork

Report No.: P101812–1000

Build–up: Stofix ventilated brick slip cladding & SFS

Report No.: P100576–1000

BS 8414–1: 2002

*Report prepared for CAREA® Façade, ZA Bel Air, 49520, Combrée, France (UK Office: CAREA® Ltd, 85 Fleet Street, 7th Floor, London EC4Y 1AE).

CAREA® Acantha grooved panel cladding fixed to a horizontal support railing system on helping hand brackets.

140 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm cement based calcium sheathing board.

Two layers of 12.5 mm plasterboard mechanically fixed to 150 mm SFS.

Build–up: CAREA® Acantha grooved panel cladding & SFS*

Report No.: P100769–1000

BS 8414–2: 2005

Two layers of 12.5 mm plasterboard fixed to 100 mm SFS.

*Report prepared for Stofix Oy, Lentokatu 2, 90460 Oulu, Finland. (UK Office: Stofix UK Ltd, St. James House, 13 Kensington Square, London W8 5HD).

Page 19: Technical Bulletin: Routes to Compliance: Fire Safety

19

ArGeTon 30 mm non–combustible terracotta tile cladding fixed to a steel vertical support railing system on helping hand brackets.

ArGeTon 30 mm non–combustibleterracotta tile claddingfixed to an aluminiumvertical support railingsystem on helping handbrackets.

140 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm cement based calcium sheathing board

140 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm cement bonded particle board

Build–up: ArGeTon terracotta tile cladding & SFS

Report No.: 297211

Build–up: ArGeTon terracotta tile cladding & SFS

Report No.: P100184–1000

*Report prepared for Aquarian Cladding Systems, Eversea Business Centre, 13 Gardens Road, Clevedon, North Somerset BS21 7QQ, UK & Isosystems, Malmedyer Weg 62, B–4770, AMEL–Schoppen, Belgium.

120 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm sheathing board.

60 mm Gebrik cladding panels comprising 43 mm rigid polyurethane foam behind 17 mm brick slips fixed to the inner sheathing board.

Build–up: Gebrik insulated brick cladding system on Kingspan Kingframe SFS

Report No.: P100838–1001

Two layers of 12.5 mm plasterboard fixed to 150 mm SFS

Two layers of 12.5 mm plasterboard fixed to 150 mm SFS

Two layers of 12.5 mmplasterboard fixed to150 mm Kingspan Kingframe®

SFS filled with rock mineral fibre

Page 20: Technical Bulletin: Routes to Compliance: Fire Safety

Appendix C

Desktop Study ReportsExamples of façade system build–ups incorporating Kingspan Kooltherm® K15 Rainscreen Board successfully assessed by qualified fire specialists for use in buildings with a habitable storey 18 metres, or greater, above ground level. Each assessment is specific to the project for which the build–up is specified. Whilst the build–ups shown have been confirmed as being suitable for the designated application, it should not be assumed that they are automatically suitable for others.NB Where a breathable membrane is specified, advice should be sought from the cladding manufacturer as regards to where it should be located within the façade system.

Glass panel on polished 190 mm pre–cast concrete cladding. 100 mm

Kingspan Kooltherm® K15 Rainscreen Board.

Two layers of 15 mm plasterboard fixed to SFS filled with acoustic mineral fibre.

Build–up: Glass panel on pre–cast concrete cladding & SFS

Report No.: CC302787

20

Two layers of 12.5 mm plasterboard on 100 mm SFS partially filled with 50 mm rock mineral fibre.

80 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12.5 mm sheathing board with a breathable membrane e.g. Kingspan nilvent ®, between.

Brickworkfacing.

Build–up: Brickwork facing & SFS

Report No.: 351838

Build–up: Copper cladding panel on plywood & SFS

Report No.: 351838

Build–up: CAREA® Aquila Cladding & SFS

Report No.: 351838

Two layers of 12.5 mm plasterboard on 100 mm SFS filled with 100 mm rock mineral fibre.

110 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12.5 mm sheathing board with a breathable membrane e.g. Kingspan nilvent ®, between.

Pre–oxidised coppercladding on 18 mmplywood fixed to avertical support railingsystem on helping hand brackets.

110 mm Kingspan Kooltherm® Rainscreen Board fixed to a 12.5 mm weather defence board with gypsum core.

Two layers of 12.5 mm plasterboard fixed to SFS filled with rock mineral fibre.

CAREA® Aquila cladding fixed using vertical rails on helping hand brackets.

Page 21: Technical Bulletin: Routes to Compliance: Fire Safety

Aluminium cladding fixed to an aluminium vertical support railing system on helping hand brackets.

100 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm sheathing board with a breathable membrane between.

Two layers of 15 mm plasterboard fixed to SFS filled with rock mineral fibre.

Build–up: Aluminium honeycomb cladding panel & SFS

Report No.: 351839

21

Marble composite cladding fixed to an aluminium vertical support railing system on helping hand brackets.

100 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm sheathing board with a breathable membrane between.

Two layers of 15 mm plasterboard fixed to SFS filledwith rock mineral fibre.

Build–up: Marble composite cladding panel & SFS

Report No.: 351839

Natural stone cladding fixed to an aluminium vertical support railing system on helping hand brackets.

100 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm sheathing board with a breathable membrane between.

Two layers of 15 mm plasterboard fixed to SFS filled with rock mineralfibre.

Build–up: Natural stone cladding panel & SFS

Report No.: 351839

Two layers of 12.5 mm plasterboard to 150 mm SFS partially filled with 50 mm rock mineral fibre.

150 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm calcium silicate cement building board with Kingspan nilvent ® breathable membrane between.

Ceramic tile cladding fixed to a horizontal railing system on helping hand brackets.

Build–up: Ceramic tile cladding & SFS

Report No.: 354601

Page 22: Technical Bulletin: Routes to Compliance: Fire Safety

Appendix C

Stofix ventilated brick cladding system on horizontal rails secured to a vertical railing system using mild steel helping hand brackets and an aluminium top hat channel.

Two layers of 12.5 mm plasterboard fixed to 150 mm SFS partiallyfilled with 50 mmrock mineral fibre.

150 mm Kingspan Kooltherm® K15 Rainscreen Boardfixed to a 12 mmcalcium silicate cement sheathing board with Kingspan nilvent ® breathable membrane between.

Build–up: Stofix ventilated brick cladding system & SFS

Report No.: 354601

Fibre cement cladding fixed to a vertical support railing system on helping hand brackets.

Two layers of 15 mm plasterboard fixed to 100 mm SFS filled with rock mineral fibre.

Build–up: Fibre cement cladding panel & SFS

Report No.: P100573–1006

22

Build–up: A2 Grade ACM cladding panel & SFS

Report No.: P100573–1003

Two layers of 15 mm plasterboard on fixed to 100 mm SFS

90 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm calcium silicate sheathing board

130 mm Kingspan Kooltherm® K15 Rainscreen Board mechanically fixed to 12 mm sheathing board with integrated breathable membrane.

Aluminium cladding fixed to an aluminium vertical support railing system on helping hand brackets

130 mm Kingspan Kooltherm® K15 Rainscreen Board fixed to a 12 mm cement particle board.

Grade FR Grade ACM cladding on a bracketing system comprising helping hand brackets and top hat systems fixed to horizontal carrier rails to back of SFS.

Two layers of 15 mm plasterboard fixed to 100 mm SFS filled with glass mineral fibre.

Build–up: FR Grade ACM cladding panel & SFS

Report No.: 361241

Page 23: Technical Bulletin: Routes to Compliance: Fire Safety

23

Page 24: Technical Bulletin: Routes to Compliance: Fire Safety

® CAREA is a Registered Trademark. ® Kingspan, Kooltherm and the Lion Device are Registered Trademarks of the Kingspan Group plc in the UK and other countries. All rights reserved.

Registered in England & Wales, No. 01882722. Registered Office: Pembridge, Leominster, Herefordshire HR6 9LA UK. VAT GB428602456.

Technical Advisory ServiceKingspan Insulation supports all of its products with a comprehensive Technical Advisory Service for designers, specifiers, stockists and contractors.

This includes a computer–aided service designed to give fast, accurate technical advice. upon receipt of your project specification. Calculations can be carried out to provide U–values, condensation / dew point risk, required insulation thicknesses etc… Thereafter any number of permutations can be provided to help you achieve your desired targets.

The Kingspan Insulation online U–value Calculator is also available for pitched and flat roofs, walls and floors. It contains calculations carried out by persons approved under the Scheme for Calculation Competency Part 1 – U–value and condensation risk. The tool is free, easy to use and requires no registration.

The Kingspan Insulation Technical Service Department can also give general application advice and advice on design detailing and fixing etc... Site surveys are also undertaken as appropriate.

The Kingspan Insulation British Technical Service Department operates under a management system certified to the BBA Scheme for Assessing the Competency of Persons to Undertake U–value and Condensation Risk Calculations.

For U–value calculations, go to the Kingspan Insulation website or contact the Kingspan Insulation Technical Service Department:

Tel: +44 (0) 1544 387 382 Fax: +44 (0) 1544 387 482email: [email protected]–calculator.co.uk

General EnquiriesFor all other enquiries:

Tel: +44 (0) 1544 388 601Fax: +44 (0) 1544 388 888email: [email protected]

Kingspan Insulation Ltd. reserves the right to amend product specifications without prior notice. Product thicknesses shown in this document should not be taken as being available ex–stock and reference should be made to the current Kingspan Insulation price–list or advice sought from Kingspan Insulation’s Customer Service Department (see above left). The information, technical details and fixing instructions etc. included in this literature are given in good faith and apply to uses described. Recommendations for use should be verified for suitability and compliance with actual requirements, specifications and any applicable laws and regulations. For other applications or conditions of use, Kingspan Insulation offers a Technical Advisory Service (see above), the advice of which should be sought for uses of Kingspan Insulation products that are not specifically described herein. Please check that your copy of this literature is current by contacting the Kingspan Insulation Marketing Department (see left).

Kingspan Insulation Ltd is a member of:

The National Insulation Association (NIA)

Contact Details

Customer ServiceFor quotations, order placement and details of despatches, contact the Kingspan Insulation Customer Service Department:

Tel: +44 (0) 1544 388 601Fax: +44 (0) 1544 388 888email: [email protected]

Literature & SamplesKingspan Insulation produces a comprehensive range of technical literature for designers, specifiers, contractors, stockists and end users. The literature contains clear ‘user friendly’ advice on typical design; design considerations; thermal properties; sitework and product data.

Available as a complete Design Manual or as individual product brochures, Kingspan Insulation technical literature is an essential specification tool. For copies, go to the Kingspan Insulation website or contact the Kingspan Insulation Marketing Department:

Tel: +44 (0) 1544 387 384Fax: +44 (0) 1544 387 484email: [email protected] www.kingspaninsulation.co.uk/literature

Tapered RoofingFor technical guidance, quotations, order placement and details of despatches contact the Kingspan Insulation Tapered Roofing Department:

Tel: +44 (0) 1544 387 383Fax: +44 (0) 1544 387 483email: [email protected]

Kingspan Insulation LtdPembridge, Leominster, Herefordshire HR6 9LA, UK

www.kingspaninsulation.co.uk

U Value Competency Scheme

CERTIFICATE CS/1004-2