Click here to load reader
Upload
wholenumber
View
9
Download
5
Embed Size (px)
DESCRIPTION
This article talks about the importance of Protective relays and cites example
Citation preview
Tech Tidbits, vol. 2 - Potential Electrical Protective
Relay Problems
Every piece of electrical equipment on every rig is installed with a device or devices of some type to
prevent damage, ranging from the simplest, fuses, to complex protective relays. These devices are
used to isolate equipment from the problem when conditions exist that can cause damage, including
under and over voltage, current, frequency, load imbalance and some combinations of the above.
While conducting generator testing on one rig recently, a generator tripped off-line on two occasions
due to differential current. The load imbalance in this case was a difference of 1.65 MW between
transformer phases, which would cause a fire. However, both times, no problem was identified. The
drilling contractor contacted the manufacturer, GE, and learned of potentially defective protective
equipment.
WEST confirmed that differential current tripping problems
have been documented from Multilin SR 489 relays that were loaded with a particular version of
firmware. Only relays with certain serial numbers are affected. Accordingly, those rigs that utilize
these Multilin SR 489 protective relays should review the relay serial numbers to understand
susceptibility to false trips from their installed firmware. Two of the six installed on the referenced rig,
including the one responsible for the false trips, fit the criteria requiring the upgraded firmware. Please
see the GE Multilin Service Bulletin for more information.