41
1 TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin Refer to the QuickLIT Web site for the most up-to-date version of this document. Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 One-to-One Temperature Sensing System Overview. . . . . . . . . . . . . . . . . . . . . . . . . 4 WRS-TTx Series Wireless Room Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . 6 TE-7820 Series Receivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 TE-7830 Series Receivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 RF Interference and Security in One-to-One Applications . . . . . . . . . . . . . . . . . . . . . . 10 Radio Frequency Addresses for One-to-One Applications . . . . . . . . . . . . . . . . . . . . . . 11 Sensor Averaging and High or Low Temperature Selection . . . . . . . . . . . . . . . . . . . . . 12 HVAC PRO Applications That Support a One-to-One System. . . . . . . . . . . . . . . . . . . . 13 Guidelines for Job Sites with 510 or More TE-7800 Series Receivers . . . . . . . . . . . . . 14 Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 One-to-One System Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Commissioning Procedures Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Commissioning Procedures Workflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Planning and Record-Keeping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Setting the TE-7800 Series Receiver RF Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Setting the WRS-TTx Series Sensor RF Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Setting the Sensor Input Mode for Multiple Sensor Applications . . . . . . . . . . . . . . . . . 19 Connecting TE-7800 Series Receivers to Supported Controllers . . . . . . . . . . . . . . . . . 20 Connecting the TE-7820 Receiver to VMA14 Series Controllers . . . . . . . . . . . . . . . . . . . . 20 Connecting the TE-7830 Receiver to Supported Controllers . . . . . . . . . . . . . . . . . . . . . . . . 22 Configuring Supported Controllers for One-to-One Applications . . . . . . . . . . . . . . . . 24 Configuring VMA14 Series Controllers for One-to-One Applications . . . . . . . . . . . . . . . . . . 25 Calculating TE-7830 Series Receiver Analog Output Signal Values . . . . . . . . . . . . . . . . . . 27 TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin TE-7820-0, TE-7830-0, TE-7820-1, TE-7830-1 Code No. LIT-12011097 Issued October 4, 2010 Supersedes October 6, 2008

TE-7800 Series One-to-One Wireless Room Temperature Sensing System

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Refer to the QuickLIT Web site for the most up-to-date version of this document.

TE-7800 Series One-to-One Wireless Room Temperature Sensing SystemTechnical BulletinTE-7820-0, TE-7830-0,TE-7820-1, TE-7830-1

Code No. LIT-12011097Issued October 4, 2010

Supersedes October 6, 2008

Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

One-to-One Temperature Sensing System Overview. . . . . . . . . . . . . . . . . . . . . . . . . 4

WRS-TTx Series Wireless Room Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . 6

TE-7820 Series Receivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

TE-7830 Series Receivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

RF Interference and Security in One-to-One Applications . . . . . . . . . . . . . . . . . . . . . . 10

Radio Frequency Addresses for One-to-One Applications . . . . . . . . . . . . . . . . . . . . . . 11

Sensor Averaging and High or Low Temperature Selection . . . . . . . . . . . . . . . . . . . . . 12

HVAC PRO Applications That Support a One-to-One System. . . . . . . . . . . . . . . . . . . . 13

Guidelines for Job Sites with 510 or More TE-7800 Series Receivers . . . . . . . . . . . . . 14

Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

One-to-One System Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Commissioning Procedures Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Commissioning Procedures Workflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Planning and Record-Keeping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Setting the TE-7800 Series Receiver RF Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Setting the WRS-TTx Series Sensor RF Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Setting the Sensor Input Mode for Multiple Sensor Applications. . . . . . . . . . . . . . . . . 19

Connecting TE-7800 Series Receivers to Supported Controllers . . . . . . . . . . . . . . . . . 20

Connecting the TE-7820 Receiver to VMA14 Series Controllers . . . . . . . . . . . . . . . . . . . . 20

Connecting the TE-7830 Receiver to Supported Controllers. . . . . . . . . . . . . . . . . . . . . . . . 22

Configuring Supported Controllers for One-to-One Applications . . . . . . . . . . . . . . . . 24

Configuring VMA14 Series Controllers for One-to-One Applications. . . . . . . . . . . . . . . . . . 25

Calculating TE-7830 Series Receiver Analog Output Signal Values . . . . . . . . . . . . . . . . . . 27

1TE-7800 Series One-to-One Wireless Room Temperature Sensing SystemTechnical Bulletin

Page 2: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Temperature Values for 0 to 5 VDC Analog Signal Applications . . . . . . . . . . . . . . . . . . . . . . . . . 27

Temperature Values for 0 to 10 VDC Analog Signal Applications . . . . . . . . . . . . . . . . . . . . . . . . 28

Configuring AS-AHU, AS-UNT, and AS-VAV Controllers for One-to-One Applications . . . 28

Commissioning AS-AHU, AS-UNT, or AS-VAV Controllers for One-to-One Applications . . 31

Configuring a DX-9100 Interface for a One-to-One Wireless Application . . . . . . . . . . . . . . 32

Commissioning a DX-9100 Controller for a One-to-One Application. . . . . . . . . . . . . . . . . . 34

Testing for RF Signal Conflicts at Job Sites with Duplicate RF Addresses. . . . . . . . . 35

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Checking a One-to-One Application’s RF Signal Strength . . . . . . . . . . . . . . . . . . . . . . 36

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

WRS-TTx Series Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

TE-7800 Series Receivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin2

Page 3: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

art Number096

244

4-10139-8

4-10126-19

4-10139-16

TE-7800 Series One-to-One Wireless Room Temperature Sensing SystemTechnical Bulletin

Document IntroductionThis document describes how to commission, configure, and troubleshoot WRS-TTx Series Sensors, TE-7800 Series Receivers, and One-to-One wireless room temperature sensing systems. This document also provides some information for configuring supported controllers for One-to-One sensing system applications.

This document does not describe how to locate or install the WRS-TTx Series Sensors and TE-7800 Series Receivers. Nor does it describe how to install, commission, operate, or troubleshoot any of the digital field controllers that support One-to-One temperature sensing system applications.

Related Documentation Table 1: TE-7800 Series One-to-One System Related Documents For Information On See Document LIT or PApplications, Features, and Benefits of the One-to-One Wireless Room Temperature Sensing System

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Product Bulletin

LIT-12011

Applications, Features, and Benefits of Wireless Metasys Systems

Wireless Metasys System Product Bulletin LIT-12011

Locating, Mounting, and Wiring the TE-7800 Series Receivers

TE-7800 Series Receivers for One-to-One Wireless Room Temperature Sensing Systems Installation Instructions

Part No. 2

Locating and Mounting the WRS-TTx Series Wireless Room Temperature Sensors

WRS-TTx Series Wireless Room Temperature Sensors Installation Instructions

Part No. 2

Using the WRS-SST Series Wireless Sensing System Tools to Test Radio Frequency (RF) Signal Strength, Locate Sensors and Receivers, and Troubleshoot One-to-One Wireless Sensing Systems

WRS-SST Series Wireless Sensing System Tools Technical Bulletin

Part No. 2

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 3

Page 4: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

One-to-One Temperature Sensing System OverviewThe TE-7800 Series One-to-One Wireless Room Temperature Sensing System is designed to interface with supported Johnson Controls® controllers to provide wireless temperature control of single-zone, room temperature applications.

A simple One-to-One wireless room temperature sensing system consists of one to four WRS-TTx Series Wireless Room Temperature Sensors communicating single-zone temperature data to an associated TE-7820 Series or TE-7830 Series Receiver (Figure 1).

• A TE-7820 Series Receiver interfaces with a single Johnson Controls VMA14 Series Controller. See TE-7820 Series Receivers for more information.

• A TE-7830 Series Receiver interfaces with a single Johnson Controls AS-AHU, AS-UNT, AS-VAV, DX-9100, or FXxx Series Field Controller. See TE-7830 Series Receivers for more information.

See WRS-TTx Series Wireless Room Temperature Sensors for more information on the WRS-TTx Series Sensors.

Figure 1: One-to-One Wireless Room Temperature Sensing Applications

Internet

Firewall

VMA2(Stand-Alone)

Site Management Portal orReady Access Portal Client

Ethernet

NAE

AS-UNT

AnalogInterface Cable

TE-7820Receiver 3

TE-7830Receiver 2

WRS-TTxSensor 3A

WRS-TTxSensor 3B

WRS-TTxSensor 3C

WRS-TTxSensor 2A

WRS-TTxSensor 2B

VMA1

Zone BusInterface Cable

TE-7820Receiver 1

WRS-TTxSensor 1

FC Bus

Zone BusInterface Cable

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin4

Page 5: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Note: Multiple WRS-TTx Series Sensor models, TE-7800 Series Receiver models, and WRS-SST Series Wireless Sensing System Tools are available. The WRS-TTx0000-0 Series Sensors, TE-78x0-0 Series Receivers, and WRS-SST-100 Tool have a 15 dBm transmission power. The WRS-TTx0000-1 Series Sensors, TE-78x0-1 Series Receivers, and WRS-SST-101 Tool (CE Mark compliant models) have reduced transmission power (10 dBm) and transmission range to comply with the requirements of select countries.

The receiver meets the IEEE 802.15.4 standard for low power, low duty cycle RF transmitting systems and operates on the 2.4 GHz Industrial, Scientific, Medical (ISM) band. The One-to-One wireless room temperature sensing system is designed for indoor applications only, and should not be used for outdoor or inter-building applications.

The WRS-TTx Series Sensors and the TE-7800 Series Receivers operate as transceivers to create a bidirectional association between the sensors and the receivers that allows the temperature sensing system to synchronize and confirm data transmissions between the devices. The sensors and receivers must be located and installed properly to provide adequate RF signal strength to maintain this wireless association.

The maximum transmission range for indoor line-of-sight transmissions between a WRS-TTx0000-0 Series Sensor and an associated TE-78x0-0 Series Receiver is 500 ft (152 m). Taking into consideration RF signal absorption and reflection due to metal obstructions, walls, and furniture found in typical building interiors, the practical average indoor line-of-sight transmission range between a sensor and receiver is 200 ft (61 m). See Related Documentation for references to installation instructions.

The maximum transmission range for indoor line-of-sight transmissions between a WRS-TTx0000-1 Series Sensor and an associated TE-78x0-1 Series Receiver is 375 ft (114 m). Taking into consideration RF signal absorption and reflection due to metal obstructions, walls, and furniture found in typical building interiors, the practical average indoor line-of-sight transmission range between a sensor and receiver is 164 ft (50 m). See Related Documentation for references to installation instructions.

The sensors and receivers are associated with each other with unique RF addresses. The RF addresses are established on the devices by setting the switches on address DIP switch blocks on the devices. After the sensor/receiver associations are created, the sensors transmit (at 60 second intervals) the sensed zone temperature, the setpoint temperature, zone occupancy status, and low battery conditions, depending on the WRS-TTx Series Sensor model, the target controller model, and the controller configuration. See Radio Frequency Addresses for One-to-One Applications on page 11, Setting the TE-7800 Series Receiver RFAddress on page 16, and Setting the WRS-TTx Series Sensor RF Address on page 18 for more information on setting RF addresses in One-to-One sensing system applications.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 5

Page 6: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

In One-to-One applications with two to four sensors, the target receiver can be configured to send temperature control data based on the average temperature, the highest temperature, or the lowest temperature sensed by the WRS-TTx Series Sensors. See Sensor Averaging and High or Low Temperature Selection on page 12.

The WRS-TTx Series Sensors and the TE-7800 Series Receivers also provide signal strength indication and other wireless diagnostic data.

Note: WRS-TTx Series Sensors and TE-7800 Series Receivers are not compatible with TE-7700 Series Sensors and Receivers. TE-7700 Series Sensors and Receivers are discontinued, and replacements are no longer available for order. If a TE-7700 Series Sensor or Receiver fails in a TE-7700 Wireless Sensing System application, you must replace the TE-7700 Series Receiver with a TE-7800 Series Receiver and replace the associated TE-7700 Sensors with WRS-TTx Series Sensors.

WRS-TTx Series Wireless Room Temperature SensorsThe WRS-TTx Series Wireless Room Temperature Sensors (Figure 2) are designed to sense room/zone temperature and transmit wireless temperature and zone status data to TE-7800 Series Receivers.

Depending on the sensor model, the WRS-TTx Series Sensors can transmit the sensed temperature, setpoint temperature, occupancy status, and low battery conditions to an associated receiver. The receiver passes the temperature data to a controller.

IMPORTANT: The One-to-One wireless room temperature sensing system, TE-7800 Series Receivers, and WRS-TTx Series Sensors are not designed or intended for use in mission-critical or life/safety applications.

Figure 2: WRS-TTP Wireless Room Temperature SensorPhysical Features and Dimensions, in./mm

Manual OccupancyOverride Button

Tamper ResistantSet Screw

TemperatureSetpoint

Control Dial

4-23/32120

3-5/3280

1-1/238

Back of Base toFront of Setpoint

Control Dial

Occupancy LED

FIG

:dm

nsns

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin6

Page 7: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

The WRS-TTx Series Sensors also provide manual occupancy override and signal strength diagnostic capabilities. See Table 2 for the available WRS-TTx Series Sensor models.

Note: The WRS-TTx0000-0 Series Sensors have a 15 dBm transmission power, and the WRS-TTx0000-1 Series Sensors (CE Mark compliant models) have a reduced transmission power (10 dBm) and transmission range to comply with the requirements of select countries.

WRS-TTx Series Wireless Room Temperature Sensors are also designed for use in WRS Series Many-to-One Wireless Room Temperature Sensing Systems. Refer to the WRS Series Many-to-One Wireless Room Temperature Sensing System Technical Bulletin (LIT-12011095) for more information.

Note: Do not attempt to set up a WRS-TTx Series Sensor to report to more than one TE-7800 Series Receiver. One-to-One wireless sensing system applications do not support global sharing of a sensor’s data. Attempting to set a single sensor to report to multiple receivers typically results in controller malfunctions and loss of temperature control in the zones.

Table 2: WRS-TTx Series SensorsProduct Code Number

Product Description

WRS-TTP0000-0 Wireless Room Temperature Sensor, Warmer/Cooler (+/-) Setpoint Adjustment, 15 dBm Transmission Power

WRS-TTP0000-1 Wireless Room Temperature Sensor, Warmer/Cooler (+/-) Setpoint Adjustment, 10 dBm Transmission Power (CE Mark)

WRS-TTR0000-0 Wireless Room Temperature Sensor, No Setpoint Adjustment, 15 dBm Transmission Power

WRS-TTR0000-1 Wireless Room Temperature Sensor, No Setpoint Adjustment, 10 dBm Transmission Power (CE Mark)

WRS-TTS0000-0 Wireless Room Temperature Sensor, Setpoint Adjustment Scale:55 to 85°F/13 to 29°C, 15 dBm Transmission Power

WRS-TTS0000-1 Wireless Room Temperature Sensor, Setpoint Adjustment Scale:55 to 85°F/13 to 29°C, 10 dBm Transmission Power (CE Mark)

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 7

Page 8: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

TE-7820 Series ReceiversThe TE-7820 Series Receivers (Figure 3) are designed to receive wireless data messages from WRS-TTx Series Sensors and communicate that data via a hard-wired connection to a Johnson Controls VMA14 Series Field Controller.

The TE-7820 Series Receiver collects wireless data transmissions containing the sensed zone temperature, the zone temperature setpoint, the zone occupancy status, signal strength measurements, and sensor low-battery conditions from one to four associated WRS-TTx Series Wireless Sensors. The receiver then processes the zone data and delivers that data directly to a single VMA14 Series Controller via a hard-wired zone bus interface.

The TE-7820 Series Receiver requires 24 VAC, Class 2 supply power. The receiver has an 8-pin RJ-45 port for the zone bus interface with the VMA14 Series Controller, two Light-Emitting Diodes (LEDs) that indicate RF signal and zone bus status, and two DIP switch blocks for setting the RF address and sensor input mode (Figure 3).

Figure 3: TE-7820 Series ReceiverPhysical Features and Dimensions, in./mm

AVG

HIG

HLO

W

ZON

E B

US

24 V

AC

24 V

AC

CO

M

ZONE BUSto VMA1400

(Tstat)RF ADDRESS

MULTXMTRS

TE-7820-0RECEIVER

RF

SIG

NAL

OFF

ON

OFF

ON

256

128

64 32 16 8 4 2 1

FIG

:te_7

820_

0

OmnidirectionalIndoor Antenna

24 VACPower Supply

Terminals

Zone Bus to VMA14 Port

RF Signal andZone Bus LEDs

RF ADDRESSDIP Switch Block

MULT XMTRS DIP Switch Block for setting the sensor input mode in One-to-One applications with

.multiple sensors

2-1/1652

5-1/2140

5-3/4146

4-13/16122

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin8

Page 9: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

TE-7830 Series ReceiversThe TE-7830 Series Receivers (Figure 4) are designed to receive wireless data messages from WRS-TTx Series Sensors and communicate that data via a hard-wired connection to a single supported digital field controller.

The TE-7830 Series Receiver collects wireless data transmissions containing the sensed zone temperature, the zone temperature setpoint, the occupancy status, signal strength measurements, and low-battery conditions from one to four associated WRS-TTx Series Wireless Sensors. The receiver then processes the zone data and delivers that data directly to a single supported Johnson Controls AS-AHU, AS-UNT, AS-VAV, DX-9100, or FXxx Series Field Controller over a hard-wired analog interface.

Figure 4: TE-7830 Series ReceiverPhysical Features and Dimensions, in./mm

RF ADDRESS

TE-7830-0 RECEIVER

ANALOG INTERFACE

OU

T C

OM

MO

NS

ET P

OIN

T O

UT

ZON

E TE

MP

ERAT

UR

E O

UT

RE

LAY

CO

MM

ON

LOW

BAT

TER

Y R

ELAY

OC

CU

PAN

CY

RE

LAY

24 V

AC C

OM

MO

N

OFF

ON

Tsta

t LO

W B

ATTE

RY

REM

OVE

FO

R A

S-AH

U, D

X-9

100

Jumper J1

RF

SIG

NAL

24 V

AC

OFF

ON

AV

GH

IGH

LOW

OFF

ON

256

128

64 32 16 8 4 2 1

24 VACPower Supply

Terminals

RF Signal and SensorLow Battery LEDs

RF ADDRESSDIP Switch Block

MULT XMTRS DIP Switch Block for setting the sensor input mode in One-to-One applications with

.multiple sensors

OmnidirectionalIndoor Antenna

Binary OutputRelay Terminals

Analog OutputTerminals

FIG

:te_7

830_

0

5-1/2140

5-3/4146

2-1/1652

4-13/16122

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 9

Page 10: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

The TE-7830 Series Receiver requires 24 VAC, Class 2 supply power. The receiver has removable terminal blocks for wiring the analog interface with supported controllers, two Light-Emitting Diodes (LEDs) that indicate RF signal and low sensor battery conditions, and two DIP switch blocks for setting the RF address and sensor input mode (Figure 4).

RF Interference and Security in One-to-One ApplicationsThe WRS-TTx Series Sensors, TE-7800 Series Receivers, and the One-to-One wireless sensing system are designed to virtually eliminate RF interference with other wireless applications. In most commercial environments, the One-to-One system does not encounter or generate significant RF interference, even in environments that are saturated with cell phones and competing Wireless Fidelity (WiFi) applications.

The WRS-TTx Series Sensors and TE-7800 Series Receivers operate on the 2.4 GHz ISM band and use multi-frequency Direct-Sequence, Spread-Spectrum (DSSS) technology.

Cell phones do not operate on the 2.4 GHz ISM band, and cell phone interference is not a problem with One-to-One systems, except when a cell phone is operated within 3 ft (1 m) of a WRS-TTx Series Receiver. When One-to-One systems encounter most other WiFi transmissions in the 2.4 GHz ISM band, the transmissions appear as merely noise and do not significantly impact wireless sensing system communication.

Using DSSS technology, the WRS-TTx Series Sensor is designed to transmit a rapid sequence of high-speed (2 millisecond) redundant data bursts to the associated receiver every 60 seconds. The sensor transmits up to eight redundant data bursts in rapid sequence, each burst is transmitted on a different Zigbee™ frequency. When a single data burst is successful received and acknowledged (or if all eight redundant transmissions fail), the sensor goes dormant for 60 seconds and then repeats the transmission burst sequence.

These multi-frequency, redundant, data-transmission sequences greatly enhance the success of the wireless sensing system data transmissions. Transmitting short, high-speed data bursts at 60-second intervals also reduces RF data-transmission collisions and interference with other WiFi transmissions. The DSSS technology also prevents most malicious RF interference.

RF interference and transmission failures can also be prevented by maintaining an adequate distance between RF transmitting devices. Some examples include:

• WRS-TTx Series Sensor should not be mounted less than 3 ft (1 m) from a TE-7800 Series Receiver.

• Cell phones should not be used within 3 ft (1 m) of a WRS-TTx Series Receiver.

• WiFi access points should be mounted at least 20 ft (6 m) from any WRS-TTx Series Sensor or TE-7800 Series Receiver.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin10

Page 11: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

• Other low-power WiFi transmitting devices should be mounted at least 3 ft (1 m) from any WRS-TTx Series Sensor or TE-7800 Series Receiver.

• WiFi devices that transmit powerful signals should be mounted at least 20 ft (6 m) from any WRS-TTx Series Sensor or TE-7800 Series Receiver.

• 2.4 GHz cordless phones and some older phone headsets can cause interference and should not be used anywhere near a One-to-One sensing system.

To secure One-to-One RF wireless messages, the WRS-TTx Series Sensors and TE-7800 Series Receivers use a custom Johnson Controls message protocol that prevents deciphering any One-to-One data transmissions that are received or intercepted by any other WiFi devices.

Radio Frequency Addresses for One-to-One ApplicationsTo establish wireless RF associations in One-to-One applications, you must assign and configure the same, unique RF address on the TE-7800 Series Receiver and the WRS-TTx Series Sensor or sensors associated with that receiver.

The RF address for a TE-7800 Series Receiver is configured manually by positioning the numbered switches on the RF ADDRESS DIP switch block on the receiver. The address setup procedure is the same for TE-7820 and TE-7830 Series Receivers. See Setting the TE-7800 Series Receiver RFAddress on page 16.

The RF address for each WRS-TTx Series Sensor associated with a TE-7800 Series Receiver must match the receiver RF address. The WRS-TTx Series Sensor’s RF address is configured by positioning the numbered switches on the TRANSMITTER ID DIP switch block on the sensor. See Setting the WRS-TTx Series Sensor RF Address.

The RF ADDRESS DIP switch block on the receiver and the TRANSMITTER ID DIP switch block on the sensor are binary switch blocks. The switches on each switch block are assigned numbers (1, 2, 4, 8, 16, 32, 64, 128, and 256). The RF address is a number between 1 and 511, equal to the sum of the numbers of the switches that are in the ON position. Thus placing Switches 1, 4, 8, and 32 in the ON position establishes an RF address of 45 for the device.

The One-to-One wireless sensing system does not use the PROPERTY CODE DIP switch block. Set all switches on the PROPERTY CODE DIP switch block to OFF on all WRS sensors in One-to-One applications. The PROPERTY CODE DIP switch block is used in Many-to-One wireless sensing systems applications. Refer to the WRS Series Many-to-One Wireless Room Temperature Sensing System Technical Bulletin (LIT-12011095) for more information.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 11

Page 12: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

In multiple-sensor applications, two or more WRS-TTx Series Sensors have the same RF address and the TE-7800 Series Receiver identifies individual sensors by their serial numbers (which is embedded in the sensor’s RF transmissions). In the single sensor applications, the receiver associates with the first WRS-TTx Series Sensor with a matching RF address and rejects all others. If 15 minutes pass with no RF transmission from the associated sensor, the receiver attempts to associate with another matching sensor (if one has been received) or waits for the first matching RF transmission.

If the TE-7800 Series Receiver fails to respond to a WRS-TTx Series Sensor with a matching RF address, the receiver may have already locked onto another sensor with the same RF address. To clear the receiver from an incorrect association, cycle the receiver power off and back on, or momentarily change the receiver’s RF address to a different RF address and then back to the original RF address again.

Never use the same RF address for two receivers that are in the same building or general location unless there are 510 or more receivers at the job site and you have thoroughly tested the duplicate address applications’ signal strengths to ensure that the receivers are well out of the RF signal range of each other’s associated sensors. RF signals can reflect off objects or pass through glass windows, and it is possible for RF signals to travel between buildings or reach receivers several floors away. Installations with 510 or more TE-7800 Series Receivers require special consideration. For large installations, contact a Johnson Controls representative for application support. See Guidelines for Job Sites with 510 or More TE-7800 Series Receivers for more information.

Sensor Averaging and High or Low Temperature SelectionOne to four WRS-TTx Series Sensors can be associated with a TE-7800 Series Receiver in a One-to-One sensing system application.

In One-to-One applications with one WRS-TTx Series Sensor, the single sensor transmits the sensed temperature, setpoint temperature, occupancy status, and low-battery conditions to the receiver.

In One-to-One applications where two to four WRS-TTx Series Sensors are associated with a single receiver, you can choose one of three sensor input modes:

• Temperature Averaging (AVG): The receiver averages the temperature inputs from all of the associated sensors and uses the average as a single control temperature for the temperature control loop.

• High Temperature Selection (HIGH): The receiver uses the highest sensed temperature as the control temperature for the temperature control loop.

• Low Temperature Selection (LOW): The receiver uses the lowest sensed temperature as the control temperature for the temperature control loop.

In multiple sensor applications, the receiver must be set to one of the sensor input modes using the MULT XMTRS DIP switch block on the receiver. See Setting the WRS-TTx Series Sensor RF Address for detailed procedures.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin12

Page 13: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

eceiver0 TE-7830

Series-

Yes

-

Yes

-

-

Yes

Yes

Yes

-

Yes

-

Yes

-

-

Yes

Yes

-

Yes

-

Yes

-

Yes

Yes

-

Yes

If more than one of the switches on the MULT XMTRS DIP switch block are positioned ON, the AVG switch takes priority over the HIGH and LOW switches, and the HIGH switch takes priority over the LOW switch.

In a multiple sensor application, all of the sensor addresses must match the associated TE-7800 Series Receiver RF address. The receiver identifies the individual sensors by the unique serial number that is programmed into each sensor and sent with each data message from the sensor.

Note: In single-sensor and multiple-sensor applications, a One-to-One sensing system interfaces with only one supported controller.

HVAC PRO Applications That Support a One-to-One SystemTable 3 lists the HVAC PRO controller applications that the TE-7800 Series Receivers support.Table 3: Johnson Controls Applications That Support a One-to-One System

(Part 1 of 2)Application Group and Application Name RF R

TE-782Series

Air Handlers 100% OA Dual Path - Dual Duct - Hot/Cold Deck Reset -

Air Handlers 100% OA Dual Path - Dual Duct - Zone Control -

Air Handlers 100% OA Dual Path - Multizone - Hot/Cold Deck Reset -

Air Handlers 100% OA Dual Path - Multizone - Zone Control -

Air Handlers 100% OA Single Path - Constant Discharge Air Temperature -

Air Handlers 100% OA Single Path - Exhaust Air Temp Control -

Air Handlers 100% OA Single Path - Room Control -

Air Handlers 100% OA Single Path - Room Control Cooling/Room Reset Heating -

Air Handlers 100% OA Single Path - Supply Air Reset from Zone Temperature -

Air Handlers MA Dual Path - Dual Duct - Hot/Cold Deck Reset -

Air Handlers MA Dual Path - Dual Duct - Zone Control -

Air Handlers MA Dual Path - Multizone - Hot/Cold Deck Reset -

Air Handlers MA Dual Path - Multizone - Zone Control -

Air Handlers MA Single Path - Constant Discharge Air Temperature -

Air Handlers MA Single Path - Return Air Control -

Air Handlers MA Single Path - Room Control -

Air Handlers MA Single Path - Room Control Cooling/Room Reset Heating -

Air Handlers MA Single Path - Supply Air Reset from Return Temperature -

Air Handlers MA Single Path - Supply Air Reset from Zone Temperature -

Central Plant Applications - Pump Lead/Lag Control -

Commercial Zoning Applications - Damper Assembly (VAV) -

Commercial Zoning Applications - Damper Assembly (VMA) Yes

Commercial Zoning Applications - Rooftop (UNT)1 -

Generic Input/Output - Point Multiplexer2 -

N2 Dial Applications - N2 Dial Module Configuration -

Rooftop Applications - Packaged Rooftop -

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 13

Page 14: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Yes

Yes

-

Yes

Yes

Yes

-

-

e applications.for this

eceiver0 TE-7830

Series

Guidelines for Job Sites with 510 or More TE-7800 Series ReceiversYou can create up to 509 unique RF address settings for One-to-One applications at a job site. Job sites that have 510 or more TE-7800 Series Receivers require duplicate RF address settings. Duplicate RF address settings can create random interference and erratic operation in One-to-One applications. Observe the following guidelines when installing 510 or more receivers at a job site:

• Ensure that One-to-One applications with duplicate RF address setting are located as far from each other as possible to avoid RF signal overlap and conflicts between the applications.

• Typically, the One-to-One applications with duplicate addresses are out of range of each other if the individual applications are:

- two or more floors or building levels apart and not near windows on the same side of the building or near atriums or other open common areas

- more than 1,000 ft (300 m) away from each other

• Test for and verify the absence of RF signal overlap between One-to-One applications with duplicate RF address settings.

Terminal Unit Applications - Fan Coil -

Terminal Unit Applications - Heat Pump -

Terminal Unit Applications - TC Fan Coil -

Terminal Unit Applications - Unit Vent -

VAV Applications - Dual Duct -

VAV Applications - Single Duct -

VAV Applications - VMA Dual Duct Yes

VAV Applications - VMA Single Duct Yes

1. Only the UNT11xx Series has enough binary inputs to support low-battery indication in One-to-On2. The user must define a sideloop with the appropriate ranging to use the TE-7830 Series Receiver

application.

Table 3: Johnson Controls Applications That Support a One-to-One System (Part 2 of 2)

Application Group and Application Name RF RTE-782Series

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin14

Page 15: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Detailed Procedures

One-to-One System Commissioning OverviewThere are a variety of procedures that must be performed to design, install, commission, configure, and troubleshoot a One-to-One wireless room temperature sensing system. Many of these procedures are contained in this section of this document. Some of the required procedures are presented in other documentation.

• See the Related Documentation table for references to the documents with information on locating and installing WRS-TTx Series Sensors and TE-7800 Series Receivers.

• Refer to the supported controller’s documentation for information on installing, commissioning, configuring, and troubleshooting the target controller.

Commissioning Procedures Requirements

To commission a One-to-One wireless temperature sensing application, you need:

• one to four WRS-TTx Series Sensors

• one TE-7820 Series or TE-7830 Series Receiver

• a 24 VAC Class 2 power supply for the receiver

• an installed, commissioned, and configured VMA14 Series or supported controller

• a zone bus interface cable for TE-7820 Series Receiver (VMA14 Series Controller) applications or an analog interface cable for TE-7830 Series Receiver (supported digital controller) applications

Note: A 9 ft (2.8 m) interface cable is included with each TE-7800 Series Receiver. Additional cable lengths are available for TE-7820 Series Receiver/zone bus applications. You can fabricate longer cables for TE-7830 Series Receiver/analog interface applications. Refer to the TE-7800 Series Receivers for One-to-One Wireless Room Temperature Sensing System Installation Instructions (Part No. 24-10139-8) for more information on cables and cable length limitations.

Commissioning Procedures WorkflowThe procedures required to commission and configure a One-to-One system can be performed in a variety of sequences. The job site and workflow dictate the order in which these procedures are performed. The procedure order shown below is a typical sequence.

To commission and configure a One-to-One system, you must perform the following procedures:

• Install, commission, and configure the target field controller.

• Install and address the WRS-TTx Series Sensor(s).

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 15

Page 16: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

• Commission/address and install the TE-7800 Series Receiver.

• Test the RF signal strength between the associated devices.

• Connect the TE-7800 Series Receiver to the target controller.

• Test and confirm operation of the complete One-to-One application.

Planning and Record-Keeping

When commissioning and configuring a control system with several One-to-One systems and multiple sensors, receivers, and controllers, we strongly recommend that you obtain a set of the building plans, the Heating, Ventilating, and Air Conditioning (HVAC) plans, and the building specifications.

Use the building plans and specifications to determine the best line-of-sight RF pathways and the potential locations for the sensors and receivers. Test the potential device locations to determine if the RF signal strength is adequate and adjust device locations as necessary.

You should create a sensor/receiver association table to record all of the device addresses and a device map that shows the locations of all sensors, receivers, and supported field controllers for the final as-built control system.

Note: Do not create duplicate RF addresses on any of the receivers at your job site. Duplicate RF addresses can cause a variety of problems in One-to-One applications. If your job site has 510 or more receivers, you must take special precautions to avoid RF signal conflicts between One-to-One applications with the same address. See Guidelines for Job Sites with 510 or More TE-7800 Series Receivers on page 14 and Testing for RF Signal Conflicts at Job Sites with Duplicate RFAddresses on page 35 for more information.

Setting the TE-7800 Series Receiver RF AddressThe TE-7800 Series Receiver requires a unique RF address to communicate with associated WRS-TTx Series Sensors. Set the RF address for the receiver by positioning the numbered switches on the RF ADDRESS DIP switch block. See Radio Frequency Addresses for One-to-One Applications for more information.

To manually set the TE-7800 Series Receiver RF address:

1. Disconnect power to the TE-7800 Series Receiver.

2. Set the numbered switches on the RF ADDRESS DIP switch block to the desired RF address (Figure 5).

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin16

Page 17: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Note: The TE-7800 Series Receivers ship from the factory with all DIP switches set in the OFF position. When the DIP switches are all set in the OFF position (address 0) or all set in the ON position (address 511), the TE-7820 Series Receiver automatically uses the N2 network address assigned to the connected VMA14 Series Controller for its RF address. If your application uses an automatically assigned RF address, you must determine the TE-7820 Series Receiver’s RF address and set the RF address on the associated WRS Series Sensor or sensors to match the receiver’s assigned RF address.

Do not use the 510 RF address setting for a permanent receiver address. Reserve the 510 RF address setting for testing and troubleshooting One-to-One applications.

3. Check the TRANSMITTER ID DIP switch block on the back of the associated sensor and make certain that the POWER switch is set in the OFF position (Figure 7). See Setting the WRS-TTx Series Sensor RF Address for more information.

4. Apply 24 VAC power to the TE-7800 Series Receiver.

5. Repeat this procedure for each receiver in your application.

Note: Do not create duplicate addresses on any of the receivers at your job site. Duplicate addresses can cause a variety of problems in One-to-One applications. If your job site has more than 509 receivers, you have to take special precautions to avoid RF signal conflicts between applications with the same address. See Guidelines for Job Sites with 510 or More TE-7800 Series Receivers on page 14 and Testing for RF Signal Conflicts at Job Sites with Duplicate RFAddresses on page 35 for more information.

Figure 5: RF ADDRESS and MULT XMTRS DIP Switch Blocks on a TE-7800 Series Receiver

AVG

HIG

HLO

W

RF ADDRESSMULT

XMTRS

OFF

ON

OFF

ON

256

128

64 32 16 8 4 2 1

RF Address DIP switch block withDIP switches positioned to create an RF Address value of 45.

Multiple Transmitter Input Mode DIP Switch Block with DIP switches positioned for a single sensor application.

FIG

:rf_a

ddrs

s

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 17

Page 18: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Setting the WRS-TTx Series Sensor RF AddressAssociate the WRS Series Sensors to a TE-7800 Series Receiver by setting the TRANSMITTER ID DIP switches on the sensors to the same positions as the RF ADDRESS DIP switches on the target TE-7800 Series Receiver so that the RF address setting on both devices match. See Radio Frequency Addresses for One-to-One Applications for more information.

If more than one sensor is used in your One-to-One application, the RF address (TRANSMITTER ID) for each sensor must match the RF address (RF ADDRESS) for the associated TE-7800 Series Receiver. The receiver identifies the individual sensors by their serial numbers, which are sent with each sensor transmission.

To set the WRS-TTx Series Sensor RF address (TRANSMITTER ID):

1. Remove the WRS-TTx Series Sensor housing from the sensor mounting base as shown in Figure 6.

2. Move the WRS-TTx Series Sensor power switch on the TRANSMITTER ID DIP switch block to the OFF position (Figure 7).

3. Set all of the switches on the PROPERTY CODE DIP switch block to the OFF position (Figure 7). (One-to-One sensing system applications do not use PROPERTY CODE settings for their RF addresses. PROPERTY CODE settings are used in Many-to-One sensing system applications only.)

Figure 6: Removing the WRS-TTx Series Sensor Housingfrom its Mounting Base

Tabs

1. Loosen (but do not remove)the tamper-resistant set screwon the locking tab of themounting base.

2. Insert a coin into the sloton the top of the sensor housing, and depress thelocking tab on the mountingbase to release the housing.

FIG

:cvr

_rm

vl

4. Pull the bottom of the sensor housingdown and off the tabs on the mounting base.

3. Swing thesensor housing offthe mounting base.

MountingBase

SensorHousing

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin18

Page 19: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

4. Match the receiver RF address by setting the numbered switches on the TRANSMITTER ID DIP switch block to the same positions as the numbered switches on the RF ADDRESS DIP switch block on the associated receiver (Figure 7).

5. Ensure the batteries are installed correctly and move the sensor POWER switch to the ON position (if you are putting the sensor into operation).

6. Reinstall the sensor housing to the wall mount base.

7. If the associated receiver is configured and powered on, you can press the sensor occupancy button to determine if the sensor and receiver are communicating.

Setting the Sensor Input Mode for Multiple Sensor ApplicationsUp to four WRS-TTx Series Sensors can be associated with a single TE-7800 Series Receiver. In multiple-sensor One-to-One applications, you must select a sensor input mode for the application by setting the switches on the MULT XMTERS DIP switch block. See Sensor Averaging and High or Low Temperature Selection for more information.

In multiple sensor applications requiring setpoint adjustment, the setpoints of each sensor are averaged. If only one sensor is to control the setpoint, the other sensors should not include setpoint adjustment capability.

To set the sensor input mode on a TE-7800 Series Receiver for multiple sensor applications:

1. Set the MULT XMTRS DIP switches on the receiver to the required positions.

• In single-sensor applications, set all three MULT XMTRS DIP switches to the OFF position.

• In multiple-sensor applications, set the MULT XMTRS DIP switches according to the desired application input mode.

Figure 7: PROPERTY CODE and TRANSMITTER ID DIP Switch Blocks on the Back of the WRS-TTx Series Sensor Housing

WRS-TTx Series SensorSwitchON/OFF

16 8 4 2 1

PROPERTY CODE

OFF

ON

OFF

TRANSMITTER IDO

NPO

WER

256

128

64 32 16 8 4 2 1

Set all five switches on the DIP switch-block to the

position.

PROPERTY CODE

OFF

Set the numbered switches on the DIP switch block to

the same position as the DIP switcheson the associated TE-7800 SeriesReceiver. (In this illustration, the totalvalue of the switches equals 45.)

TRANSMITTER ID

ON

FIG

:wrs

_dp_

swtc

h_12

1

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 19

Page 20: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

- If the sensor temperature readings are averaged, set only the AVG DIP switch to the ON position.

- If the highest sensor temperature reading is used, set only the HIGH DIP switch to the ON position.

- If the lowest sensor temperature reading is used, set only the LOW DIP switch to the ON position.

Note: In multiple-sensor applications requiring setpoint adjustment, the setpoints of each sensor are averaged. If only one sensor is to control the setpoint, the other sensors should not include setpoint adjustment capability.

If more than one of the switches on the MULT XMTRS DIP switch block are positioned ON, the AVG switch takes priority over the HIGH and LOW switches, and the HIGH switch takes priority over the LOW switch.

In single-sensor and multiple-sensor One-to-One applications, the TE-7800 Series Receiver interfaces with only one supported controller.

Connecting TE-7800 Series Receivers to Supported ControllersThe TE-7820 Series Receiver connects to VMA14 Series Controllers only (Figure 8). The TE-7830 Series Receiver connects to Johnson Controls AS-AHU, AS-UNT, AS-VAV, DX-9100, and FXxx Series Field Controllers (Figure 9).

Note: The TE-7800 Series Receivers are sensitive RF devices. To avoid degrading this sensitivity, do not run the interface cable near high voltage power wiring, phase controlled lighting, and/or phase controlled electric motors.

Connecting the TE-7820 Receiver to VMA14 Series Controllers

To connect the power and zone bus between the TE-7820 Series Receiver and the VMA14 Series Controller using the 6 ft (1.8 m) interface cable provided, see Figure 8 and follow these instructions:

1. Connect the interface cable between the Tstat modular socket on the side of the VMA14 Series Controller and the ZONE BUS to VMA1400 (Tstat) modular socket on the receiver (Figure 8).

Note: Additional zone bus interface cables, with lengths up to 100 ft (30.5 m), are available. See the TE-7800 Series One-to-One Wireless Room Temperature Sensing System Product Bulletin (LIT-12011096) for zone bus interface cable ordering information.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin20

Page 21: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

2. Connect the power cable between the 24 VAC spade terminal connections on the side of the VMA14 Series Controller and the 24 VAC spade terminal connections on the receiver (Figure 8).

Note: One end of the spade terminal connector portion of the interface cable features two Y-spade terminal connectors that tap into the 24 VAC power source provided by the VMA14 Series Controller. The other end of the spade terminal connector portion of the interface cable features a removable screw terminal block that is pushed onto the 24 VAC spade terminal connectors on the receiver.

Figure 8: TE-7820 Series Receiver Wired to a VMA14 Series Controller

AVG

HIG

HLO

W

ZON

E B

US

24 V

AC

24 V

AC

CO

M

ZONE BUSto VMA1400

(Tstat)RF ADDRESS

MULTXMTRS

TE-7820-0RECEIVER

24 VAC COM

Power and Zone Bus Interface withJohnson Controls VMA14 Series Digital Controller,

6 ft (1.8 m) Interface Cable included with TE-7820-x Series RF Receiver

To SupplyTransformer

Tstat

24VAC: 2

24 VAC

24VAC: 1

TE-7820-x Series RF Receiverwith Zone Bus Interface

Johnson ControlsVMA14 Series

Digital Controller

RF

SIG

NA

L

OFF

ON

OFF

ON

256

128

64 32 16 8 4 2 1

FIG

:te78

20_w

rng

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 21

Page 22: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

r

Connecting the TE-7830 Receiver to Supported ControllersTo connect the power and analog interface cables between a TE-7830 Series Receiver and a supported controller using the 1.8 m (6 ft) cable provided, see Figure 9 and follow these instructions:

1. Connect the three-position screw terminal block with the white, orange, and brown wires to the three spade terminal connections on the receiver labeled:

a. ZONE TEMPERATURE OUT

b. SETPOINT OUT

c. OUT COMMON

Note: Position the screw terminal block so that the three screw heads are facing outward (Figure 9).

2. Connect the other end of the interface cable with the spade terminal connectors to the appropriate Analog Input (AI) terminations on the controller. If the controller does not accommodate 1/4 in. (6 mm) spade terminal connectors, the wire ends should be clipped and stripped before making the connections.

• Connect the white wire to the analog input AI-1 of the controller (zone temperature).

• Connect the orange wire to the analog input selected for setpoint.

Figure 9: TE-7830 Series Receiver Wired to a Supported Controller

* Relay Common (green wire) should be connected to either Binary In COM or Binary In SRC, depending on the field controller.

24 VAC

Johnson ControlsAS-AHU, AS-UNT, AS-VAV, DX-9100, o

FXxx Series Controller

RF ADDRESS

TE-7830-0 RECEIVER

ANALOG INTERFACE

OU

T C

OM

MO

NS

ET

PO

INT

OU

TZO

NE

TE

MPE

RAT

UR

E O

UT

RE

LAY

CO

MM

ON

LOW

BAT

TER

Y R

ELAY

OC

CU

PAN

CY

RE

LAY

24 V

AC C

OM

MO

N

OFF

ON

Tsta

t LO

W B

ATTE

RY

REM

OV

E F

OR

AS

-AH

U, D

X-9

100

24 VAC COM

24 V

AC C

OM

OC

C B

I

BI C

OM

*TE

MP

AI-1

**S

ET P

T A

I

AI C

OM

24 V

AC

RE

D

BLK

BLU

YE

LG

RN

WH

T

OR

NB

RN

RED

BLK BLU

YEL

GR

N

WH

T

OR

N

BR

N

Note: Remove Jumper J1 for Johnson Controls AS-AHU,DX-9100, and FXxx Series Controller applications that requiredisabling the manual override status via the zone temperature.Do not remove Jumper J1 for Johnson Controls AS-UNT orAS-VAV Controller applications.

Jumper J1

RF

SIG

NA

L

TE-7830-x Series RF Receiverwith Analog Interface

LOW

BAT

BI

To SupplyTransformer

Power and Analog Interface withJohnson Controls AS-AHU, AS-UNT, AS-VAV,

DX-9100, or FXxx Series Controller,6 ft (1.8 m) Interface Cable Included with

TE-7830-x Series RF Receiver

24 V

AC

OFF

ON

AVG

HIG

HLO

W

OFF

ON

256

128

64 32 16 8 4 2 1

** Zone Temperature Out (white wire) should be connected to analog input AI-1 of the field controller (zone temperature).

FIG

:te78

30_w

rng

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin22

Page 23: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Note: If a WRS-TTR0000-x Series Sensor is used in the installation, the orange wire should be insulated, taped back, and not connected at the controller end, since there is no setpoint adjustment available on this sensor model.

• Connect the brown wire to the analog input common.

3. Connect the three-position screw terminal block with the blue, yellow, and green wires to the three spade terminal connections on the receiver labeled:

a. OCCUPANCY RELAY

b. LOW BATTERY RELAY

c. RELAY COMMON

Note: Position the screw terminal block so that the three screw heads are facing outward (Figure 9).

4. Connect the other end of the interface cable with the spade terminal connectors to the appropriate Binary Input (BI) terminations on the controller. If the controller does not accommodate 1/4 in. (6 mm) spade terminal connectors, the wire ends should be clipped and stripped before making the connections.

5. Connect the blue wire to the occupancy binary input of the controller. In applications where a binary input is not used for this function, the blue wire should be insulated, taped back, and not connected at the controller end.

Note: Remove jumper J1 in AS-AHU, DX-9100, and FXxx Series applications to prevent the zone temperature from being driven low if the manual occupancy override button on the WRS-TTx Series Sensor is pressed. AS-AHU, DX-9100, and FXxx Series Controllers do not use the occupancy override option. See Figure 9 for J1 jumper location.

Note: Install jumper J1 in AS-UNT and AS-VAV applications to allow the receiver to drive the zone temperature low if the manual occupancy override button on the WRS-TTx Series Sensor is pressed. AS-UNT and AS-VAV Controllers do not require a separate binary input for occupancy status, since these controllers detect occupancy override when the zone temperature signal goes to 0 V. See Figure 9 for J1 jumper location.

6. Connect the yellow wire to the low-battery binary input terminal on the controller. In applications where a binary input is not available for low-battery conditions, the yellow wire should be insulated, taped back, but not connected at the controller end.

7. Connect the green wire to the controller as follows:

• For AS-AHU Series Controllers, connect the green wire to BICM or BI COM (24 VAC common).

• For AS-UNT100 Series Controllers, connect the green wire to 24 VAC.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 23

Page 24: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

• For AS-UNT1100 Series Controllers, connect the green wire to BI SRC (24 VAC).

• For AS-VAV100 Series Controllers, connect the green wire to BINARY COM (24 VAC common).

• For DX-9100 Series Controllers, connect the green wire to DI COM (24 VAC common).

• For FXxx Series Controllers, connect the green wire to terminal D01 & D02 COM.

8. Connect the two-position screw terminal block containing the red and black wires to the two spade terminal connections on the receiver identified as 24 VAC and 24 VAC COMMON.

Note: Position the terminal block so that the screw heads are facing outward (Figure 9).

9. Connect the other end of the interface cable with the two Y-spade terminal connectors to the appropriate 24 VAC terminations on the controller. If the controller does not accommodate 6 mm (1/4 in.) spade terminal connectors, clip and strip the wire ends before making the connections.

Configuring Supported Controllers for One-to-One ApplicationsVMA14 Series Controllers and supported digital field controllers must be properly configured to operate with TE-7800 Series Receivers and One-to-One sensing system applications.

You must use the HVAC PRO software tool (Release 8.04B or later) to configure the VMA14, AS-AHU, AS-UNT, and AS-VAV Series Controllers.

You must use the GX-9100 Commissioning Tool (Release 8.04 or later) to configure the DX-9100 Controllers.

You must use FX Builder to configure the FXxx Series Controllers; refer to the FX Builder literature for more details.

Note: It is assumed that the user of this document has a working knowledge of and experience with the HVAC PRO software tool and GX-9100 Commissioning Tool. See Related Documentation on page 3 for references to relevant Johnson Controls user documentation.

The procedures that follow describe how to configure only those values in the controller UI that are required for a One-to-One application to interface and operate with VMA14, AS-AHU, AS-UNT, AS-VAV, or DX-9100 Series Controllers. Refer to the controller documentation and the relevant software tool documentation for complete information on configuring the controller.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin24

Page 25: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Configuring VMA14 Series Controllers for One-to-One ApplicationsThe VMA14 Series Controller is easily configured using the HVAC PRO software tool. HVAC PRO is part of the M-Tool suite of tools. The software also runs on a Metasys® Operator Workstation (OWS) connected to the N2 Bus to configure, download, and commission the controller.

You configure the VMA14 Series Controller using HVAC PRO software (Release 8.04B or later) by answering a series of yes/no and multiple choice questions, specifying setpoints and other parameters. HVAC PRO software has a library of applications, control sequences, and algorithms that automatically configure the controller in response to the answers.

To commission the VMA14 Series Controller:

1. Launch the HVAC PRO software tool.

2. On the File menu, click New.

3. Select Application Group: VAV Applications.

4. Select Applications: VMA Single Duct.

5. Click OK.

6. Answer the questions, up to Thermostat Type.

7. Select the appropriate RF wireless sensor option (Figure 10).

Figure 10: Choosing the RF Wireless Sensor Option

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 25

Page 26: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

8. Select the appropriate occupancy mode for the sensor (Figure 11).

Note: The third selection for occupancy mode is not recommended since the WRS-TTx Series Sensor LED does not indicate an occupancy mode.

9. Complete the question/answer session. The thermostat type and occupancy button are the only two questions relevant to wireless One-to-One applications.

10. Click the Parameters button.

11. Scroll down in the Parameters list box to the RF wireless thermostat parameter group. Powerfail Diag is TRUE when the RF wireless battery should be replaced. Read the PRN file to determine the point location (look under the VAV Box - RF Wireless Thermost heading), when mapping the point to a supervisory system.

AI 1 Zone Temp and AI 2 (either Remote Adjust or Remote Set Point) are configurable similar to other VMA single duct applications; however, these two inputs are fixed at AI 1 and AI 2 when selecting an RF Wireless Thermostat in the VMASingle Duct application. Zero is the default offset for the Zone Temperature.

12. Save the application for a VMA14 Series Controller, then download and commission.

Note: The receiver reports to the control system that the zone temperature and setpoint are out of range if an RF transmission is not received from its associated sensor for a period of 15 minutes or more.

Figure 11: Choosing the Occupancy Mode

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin26

Page 27: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

FIG

:te_7

830_

sgnl

_scl

s

°F/29°C

Calculating TE-7830 Series Receiver Analog Output Signal ValuesThe TE-7830 Series Receiver generates and sends analog signals (0 to 5 VDC) to the target field controller based on data messages from the WRS-TTx Series Sensors. The field controller interprets these analog signals to determine the sensed zone temperature and the zone setpoint.

The configuration procedures in this document provide the values required to configure the zone temperature range and the zone setpoint range for AS-AHU, AS-UNT, AS-VAV, and DX-9100 Controllers. In most application scenarios, you should use the values provided in those procedures to configure the zone temperature and zone setpoint ranges for these controllers.

Temperature Values for 0 to 5 VDC Analog Signal Applications

The 0 to 5 VDC analog signals from the TE-7830 Series Receiver are scaled to zone temperature and zone setpoint values as illustrated in the scales in Figure 12. Use these scaled values in the sections that follow to configure the analog inputs of the AS-AHU, AS-UNT, AS-VAV, or DX-9100 Controller.

The scaled values in Figure 12 provide the proper linearization for the specific controller selected for the installation. The setpoint adjustment dial can be adjusted from 55 to 85°F or 13 to 29°C on the WRS-TTS0000-x Series Sensor, or it can be adjusted for warmer/cooler (+/-) on the WRS-TTP0000-x Series Sensor.

Note: The Zone Setpoint Scale shown in Figure 12 is for -5 to 5° setpoint range applications.

Figure 12: 0 to 5 VDC/Zone Temperature and Zone Setpoint Scale

2.0 V

3.5 V

0.5 V = Sensor Adjustment DialPositioned Counterclockwise to or - 55°F/13°C

85

0.5 V

3.5 V = Sensor Adjustment DialPositioned Clockwise to or

+85°F/29°C

Warmer/Cooler (+/-) Adjustor

Remote Setpoint

Zone Setpoint Scale(For 0 to 5 VDC Analog Signal)

2.0 V

4.0 V

0.0 V = -20°F/-29°C

5.0 V =

5.0 V

Zone Temperature Scale(For 0 to 5 VDC Analog Signal)

115°F/46°C

-20°F/-29°C

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 27

Page 28: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Temperature Values for 0 to 10 VDC Analog Signal Applications

The TE-7830 Series Receiver’s 0 to 5 VDC analog output signal can be applied to certain controllers that accept only 0 to 10 VDC analog signals. Use the following information to configure controllers that accept only 0 to 10 VDC signals.

Note: The calculations and values are the same if the field controller is set up for °F or °C.

In warmer/cooler applications, the range of adjustment can be changed to match the requirements of the application. Table 4 includes setpoint values calculated using the following equations:

• Setpoint at 0 V = Lower Setpoint – (0.5 x K)

• Setpoint at 10 V = Upper Setpoint + (6.5 x K)

where:

Note: In the procedures that follow, the warmer/cooler setpoint adjustment range is assumed to be ±5 (F° or C°).

Configuring AS-AHU, AS-UNT, and AS-VAV Controllers for One-to-One Applications

AS-AHU, AS-UNT, and AS-VAV Controllers are easily configured using the HVAC PRO software tool. HVAC PRO software is part of the M-Tool suite of tools. The software also runs on a Metasys Operator Workstation (OWS) connected to the N2 Bus to configure, download, and commission the controller.

A user can configure the controller using HVAC PRO software (Release 8.04B or later) by simply responding to a series of yes/no and multiple choice questions, specifying setpoints and other parameters. HVAC PRO software has a library of applications, control sequences, and algorithms that automatically configure the controller in response to the answers.

To configure an AS-AHU, AS-UNT, or AS-VAV Controller, proceed as follows:

1. Launch the HVAC PRO software tool.

2. Skip to Step 3 to open an existing file and modify it. To create a new application, proceed as follows:

a. On the File menu, click New.

Table 4: Setpoint Values for Warmer/Cooler Setpoint Adjustment RangesSetpoint Adjustment Range (F° or C°)

Setpoint Value at 0 V(°F or °C)

Setpoint Value at 10 V(°F or °C)

±5° -6.7° 26.7°

±3° -4.0° 16.0°

±1° -1.3° 5.3°

Setpoint Adjustment Range3

K =

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin28

Page 29: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

b. Select the application group and the specific application.

c. Answer the questions as required by the application. See Step 3 for specific applications that can support the RF receiver with analog outputs (applications not listed are not supported).

3. To modify an existing application, proceed as follows:

a. On the File menu, click Open.

b. Select the appropriate file and click OK.

c. If necessary, answer the questions and modify the parameters as follows:

(1) VAV Applications (Single or Dual Duct)

- If no remote setpoint is required, first answer Define setpoint type: with As appropriate to your application, then answer Define Remote AI points with None (Unused).

- If a remote setpoint is required, first answer Define setpoint type: with Single setpoint with bias, then answer Define Remote AI points with Warmer/Cooler adjust.

- If the temporary occupancy needs to be active, answer Do you want the Temporary Occupied feature? with Yes.

- Define a user-defined binary input for battery status. Define the units (State0:Normal,State1:Low).

(2) Rooftop Applications (Packaged Rooftop) and Terminal Unit Applications (Unit Vent, Fan Coil, and Heat Pump)

- If no remote setpoint is required, answer Define Remote AI points with None (Unused).

- If a remote setpoint is required, answer Define Remote AI points with Warmer/Cooler adjust.

- If the temporary occupancy needs to be active, answer Do you want the Temporary Occupied feature? with Yes.

- Define a user-defined binary input for battery status. Define the units (State0:Normal,State1:Low).

(3) Air Handlers MA Single Path (Room Control, Room Control Cooling/Room Reset, and Supply Air Reset from Zone Temperature) and Air Handlers 100% OA Single Path (Room Control, Room Control Cooling/Room Reset, and Supply Air Reset from Zone Temperature)

- If a remote setpoint is required, first answer Select the setpoint type: with Single zone setpoint (this question is not presented for Air Handlers MA Single Path or Supply Air Reset from Zone Temperature), then answer Is a remote zone setpoint needed? with Remote setpoint slider.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 29

Page 30: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

- Define a user-defined binary input for battery status. Define the units (State0:Normal,State1:Low).

d. Modify the zone temperature analog input as follows:

- Zone Temp: Change the Sensor Type to Voltage (V), change the Input Range Low to 0.74 and High to 4.44, and change the Output Range Low to 0°F (-17.8°C) and High to 100°F (37.8°C).

e. Modify the remote setpoint analog input as follows.

(1) VAV Applications (Single or Dual Duct)

- Remote Setpoint: Change the Sensor Type to Voltage (V), change the Input Range Low to 0 and High to 4.0, and change the Output Range Low to 50°F or 10.0°C and High to 90°F or 32.2°C.

- Warmer/Cooler Adjust: Change the Sensor Type to Voltage (V), change the Input Range Low to 0 and High to 4.0, and change the Output Range Low to -6.7°F (-21.5°C) and High to 26.7°F (-2.9°C) (for ±5F° range).

(2) Rooftop Applications (Packaged Rooftop) and Terminal Unit Applications (Unit Vent, Fan Coil, and Heat Pump)

- Warmer/Cooler Adjust: Change the Sensor Type to Voltage (V), change the Input Range Low to 0 and High to 4.0, and change the Output Range Low to -6.7°F (-21.5°C) and High to 26.7°F (-2.9°C) (for ±5F° range).

- Remote Setpoint: Previously the application was configured to operate with a warmer/cooler adjustment. Make the following modifications to obtain an application that supports remote setpoint with bias.

Note: If the remote setpoint analog input goes unreliable, the controller defaults this to a setpoint of 0°F or 0°C. The actual setpoints become the values of the biases as follows:

- Analog Input Configuration: Change the Long name to Remote SetPoint, change the Sensor Type to Voltage(V), change the Input Range Low to 0 and High to 4.0, and change the Output Range Low to 50°F or 10.0°C and High to 90°F or 32.2°C.

- Parameter Configuration, Zone Heating Setpoint: Change the OccHtg Setpt to -2°F or -1°C and the name to Occ Htg Bias, change the Stby Htg Setpt to -4°F or -2°C and the name to Stby Htg Bias, and change the Unocc Htg Setpt to -9°F or -5°C and the name to Unocc Htg Bias.

- Parameter Configuration, Zone Cooling Setpoint: Change the OccClg Setpt to 2°F or 1°C and the name to Occ Clg Bias, change the Stby Clg Setpt to 4°F or 2°C and the name to Stby Clg Bias, and change the Unocc Clg Setpt to 9°F or 5°C and the name to Unocc Clg Bias.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin30

Page 31: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

(3) Air Handlers MA Single Path (Room Control, Room Control Cooling/Room Reset, and Supply Air Reset from Zone Temperature) and Air Handlers 100% OA Single Path (Room Control, Room Control Cooling/Room Reset, and Supply Air Reset from Zone Temperature)

- Rem Zone Setpnt: Change the Sensor Type to Voltage (V), change the Input Range Low to 0 and High to 4.0, and change the Output Range Low to 50°F or 10.0°C and High to 90°F or 32.2°C.

f. Save the application for the appropriate controller type.

g. Download the application to the controller.

Commissioning AS-AHU, AS-UNT, or AS-VAV Controllers for One-to-One Applications

AS-AHU, AS-UNT, and AS-VAV Controllers are easily commissioned using the HVAC PRO software tool (Release 8.04B or later).

For AS-UNT and AS-VAV Controllers, do not remove Jumper J1 (identified in Figure 2 on the TE-7830 Series Receiver). With Jumper J1 not removed, occupancy override status is enabled via the zone temperature. Set the AS-UNT or AS-VAV analog input switches for 0 to 10 VDC.

For AS-AHU Controllers, set the analog input switches for voltage and remove Jumper J1.

To ensure proper operation of the TE-7830 Series Receiver and the AS-AHU, AS-UNT, or AS-VAV Controller, verify the following features (if chosen):

1. Validate communication from the zone sensor to the controller as follows:

a. Monitor the zone setpoint analog input and rotate the setpoint adjustment dial the entire range.

Note: For multiple sensor installations, move the adjustment dials to low end of the setpoint range on all of the sensors. Test each sensor individually by moving the adjustment dial on each sensor (one at a time) through the entire range to verify the response to that sensor. Remember to return the dial to the low end of the setpoint range before testing the next sensor.

You can wait for a sensor to report the adjustment to the receiver or simply press the occupancy override button to initiate an immediate sensor transmission to the receiver.

b. Press the manual occupancy override button and verify that the Temp Occ status momentarily becomes Closed.

Note: For multiple sensor applications, repeat Steps 1a and 1b for each sensor.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 31

Page 32: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

2. Validate wiring for zone temperature and battery status as follows:

a. Loosen the screw for ZONE TEMPERATURE OUT and remove the white wire from the terminal block.

b. Verify that the zone temperature went unreliable at the controller.

c. Reconnect the white wire to the screw terminal pluggable block.

d. Use a jumper to short the RELAY COMMON terminal and the LOW BATTERY RELAY terminal on the receiver.

e. Verify that a low battery status was read by the controller.

Configuring a DX-9100 Interface for a One-to-One Wireless Application

DX-9100 Controllers are easily configured using the GX-9100 Programming Tool, which is part of the M-Tool suite of tools. The software also runs on a Metasys Operator Workstation (OWS) connected to the Metasys network to configure, download, and commission the controller.

Note: It is assumed that the user of this document has basic knowledge of and experience using the GX-9100 Programming Tool.

A user can configure the controller using the GX-9100 Programming Tool (Release 8.02 or later) by specifying data for the analog and binary input points.

To configure a DX-9100 Controller, proceed as follows:

1. Launch the GX-9100 Programming Tool.

2. Either create a new application or open an existing file and modify it.

3. If the analog input has already been set to Active, proceed directly to Step 4b. If the analog input has been defined as Passive, proceed as follows:

a. Note which program module connections the analog input has.

b. Right-click the analog input and select Delete.

c. Confirm the Delete by clicking Yes.

4. Modify the zone temperature analog input as follows:

a. Right-click on the analog input to be configured as zone temperature and select Active.

b. Right-click the analog input and select Data.

c. Change the User Name to ZN-T.

d. Change the Type of Active Input to the number 0 which represents 0 to 10 VDC.

e. Change the High Range to 250°F (121.1°C).

f. Change the Low Range to -20°F (-28.9°C).

g. Modify the other defaults as required by the application.

h. Click OK.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin32

Page 33: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

i. Reestablish the analog input connections to the appropriate program modules if they had been previously defined.

5. If required, modify the remote setpoint analog input as follows:

a. Right-click the analog input to be configured as remote setpoint and select Active.

b. Right-click the analog input and select Data.

c. Change the User Name to ZN-SP.

d. Change the Type of Active Input to the number 0, which represents 0 to 10 VDC.

e. Change the High Range to 150°F (65.6°C).

f. Change the Low Range to 50°F (10°C).

g. Modify the other defaults as required by the application.

h. Click OK.

6. If required, modify the warmer/cooler adjust analog input as follows:

a. Right-click on the analog input to be configured as warmer/cooler adjust and select Active.

b. Right-click the analog input and select Data.

c. Change the User Name to ZN-WC.

d. Change the Type of Active Input to the number 0 which represents 0 to 10 VDC.

e. Change the High Range to 26.7°F (-2.9°C).

f. Change the Low Range to -6.7°F (-21.5°C).

g. Modify the other defaults as required by the application.

h. Click OK.

7. Modify the occupancy override digital input as follows:

a. Enter a timer module for the desired occupancy override. Do not invert the timer module.

b. Connect the digital input to the Input Connection #x (non-inverted) of the timer module.

c. Right-click the timer module to be configured and select Data.

d. Change the appropriate Timer #x Type to 5 (OFFdelay).

e. Change the Time Units #x to 1 (minutes).

f. Change the Time Period #x to the desired occupancy override time in minutes.

g. Click OK.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 33

Page 34: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

h. Connect the output of the timer (PMnTDOx, where n is the module number and x is the timer number) to the occupancy override logic.

8. Map the battery status digital input to the supervisory system to provide an alarm when the sensor battery is low (State 0: Normal, State1: Low).

9. Save the application for the appropriate controller firmware version.

10. Download the application to the DX9100 Controller.

Commissioning a DX-9100 Controller for a One-to-One ApplicationDX-9100 Controllers are easily commissioned using the GX-9100 Commissioning Tool (Release 8.04 or later).

Remove Jumper J1 (Figure 4 on page 9) to disable occupancy override status via the zone temperature. To ensure proper operation of the TE-7830 Series Receiver and the DX-9100 Controller, verify the following features (if chosen):

1. Validate communication from the zone transmitter to the controller as follows:

a. Monitor the zone setpoint analog input and move the setpoint adjustment dial the full range. For multiple transmitter installations, move all but one adjustment dial to the bottom end of the setpoint range and then move the remaining adjustment dial to verify its response.

b. Press the manual occupancy override button and verify the occupancy override status.

c. For multiple transmitter installations, repeat Steps 1a and 1b for each transmitter.

2. Validate wiring for zone temperature and battery status as follows:

a. Loosen the screw for ZONE TEMPERATURE OUT and remove the white wire from the screw terminal pluggable block.

b. Verify that the zone temperature reading drops below 32°F (0°C).

c. Reconnect the white wire to the screw terminal pluggable block.

d. Use a jumper to short the RELAY COMMON terminal and the LOW BATTERY RELAY terminal on the receiver.

e. Verify that a low battery status was read by the controller.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin34

Page 35: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Testing for RF Signal Conflicts at Job Sites with Duplicate RF Addresses

Job sites with 510 or more TE-7800 Series Receivers require duplicate RF addresses on some of the receivers and sensors. See Guidelines for Job Sites with 510 or More TE-7800 Series Receivers on page 14 for more information on locating receivers and sensors at job sites with duplicate RF addresses.

After you have determined the locations for the receivers and sensors with duplicate RF addresses, you should test the RF communication between the devices and ensure there are no RF conflicts between the applications with duplicate RF addresses before permanently mounting the sensors and receivers.

To test for RF signal conflicts at job sites with duplicate RF addresses:

1. Set the RF addresses on the receivers that have duplicate addresses (Receiver A and Receiver B) to the test RF address setting of 510, temporarily position the receivers at their intended locations, and then power only Receiver A on.

Note: You can monitor WRS-TTx Series Sensors and TE-7800 Series Receivers in One-to-One wireless sensing systems via a wireless connection using the WRS-SST Series Wireless Sensing System Tools. Refer to the WRS-SST Series Wireless Sensing System Tools Technical Bulletin (Part No. 24-10139-16) for more information on using the WRS-SST Series Tool to monitor One-to-One applications over a wireless connection.

2. Create a temporary, movable test sensor by setting the RF address (on the TRANSMITTER ID DIP switch) to 510 on an unmounted WRS-TTx Series Sensor and power the sensor on.

3. Temporarily locate the test sensor at the intended location for Sensor A (that associates with Receiver A), and press the manual occupancy override button to ensure that the test sensor does communicate with Receiver A.

Note: If Receiver A associates with more than one sensor, repeat Step 3 for each Sensor A location to ensure that all of the A sensors do communicate with Receiver A.

4. Next, temporarily locate the test sensor at the intended location for Sensor B (that associates with Receiver B) and press the manual occupancy override button to ensure that the test sensor does not communicate with Receiver A.

Note: If Receiver B associates with more than one sensor, repeat Step 4 for each Sensor B location to ensure that all of the B sensors do not communicate with Receiver A.

5. Power Receiver A off and power Receiver B on. Repeat the procedures above to test both the A and B sensor locations and ensure that the:

• B sensors do communicate with Receiver B

• A sensors do not communicate with Receiver B

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 35

Page 36: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Troubleshooting

Checking a One-to-One Application’s RF Signal StrengthYou should verify adequate RF signal strength between sensors and receivers, especially in applications with excessive distances or metal barriers (such as ductwork, concrete with metal reinforcements, equipment rooms, or elevator shafts). The RF signal strength in One-to-One wireless sensing system applications can be checked ahead of time as follows:

1. Set the DIP switches on the sensor and receiver (or the wireless sensing system tool) to the same RF address. Make sure that the switches on the PROPERTY CODE DIP switch block on the sensor are all set to the OFF position.

2. Provide temporary 24 VAC power to the TE-7800 Series Receiver and hold the receiver in the desired mounting location. (As an alternative, use the optional battery-powered WRS-SST Series Wireless Sensing System Tools).

3. Hold the WRS-TTx Series Sensor near its desired mounting location in the zone, with the battery installed and the power switch set to ON.

4. Observe the Wireless LED on the receiver. Approximately every 60 seconds, an RF transmission occurs and the LED blinks. You can force the sensor into Rapid Transmit Mode by pressing the WRS-TTx Series Sensor’s manual occupancy override button for 3 seconds or more.

In Rapid Transmit Mode, the sensor transmits a signal every 10 seconds for 30 minutes. After each transmission, the occupancy override LED on the sensor flashes (one, two, or three times) on to indicate the signal strength between the sensor and the receiver. Also, the signal strength LED on the receiver blinks off to indicate the relative signal strength between the sensor and receiver.

• Three consecutive flashes (of the sensor LED) or blinks (of the receiver LED) every 10 seconds indicate an excellent signal strength.

• Two consecutive flashes (of the sensor LED) or blinks (of the receiver LED) every 10 seconds indicate a good signal strength.

• One flash (of the sensor LED) or blink (of the receiver LED) every 10 seconds indicates a weak signal strength. A weak signal strength may result in sporadic loss of data; therefore, reconsider the sensor and/or receiver mounting locations.

If relocating the sensor fails to improve the RF signal reception at the receiver, try rotating the antenna in 45-degree increments, selecting a different mounting plane where at least 2 in. (102 mm) of the antenna are below metal structures, or selecting a new mounting location.

Note: The TE-7820 Series Receiver may be wired up to 300 ft (91 m) from a VMA14 Series Controller, and the TE-7830 Series Receiver may be wired up to 100 ft (30 m) from a supported Johnson Controls controller.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin36

Page 37: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

s ries.

ciated ss on s on

ere may

nd m Tools.

iver

5. Check the receiver for adequate RF signal strength after the building occupant moves into the space. Checking a second time ensures that none of the occupant furnishings or equipment interferes with RF signal reception.

See Table 5 for troubleshooting additional problems or symptoms, possible causes, and suggested course of action. Table 5: Troubleshooting One-to-One Wireless Sensing Applications

(Part 1 of 2)Problem or Symptom Cause/ActionWRS-TTx Series Sensor is not associated with the target receiver. (This is indicated by pressing the manual occupancy override button on the sensor and the occupancy override LED does not light.)

The WRS-TTx Series Sensor batteries may be low.Replace the sensor batteries. Refer to the WRS-TTx Series Wireless Room Temperature Sensors Installation Instruction(Part No. 24-10126-19) for information on replacing the batte

The sensor and receiver RF addresses may not match.Check/reconfigure the RF addresses on the sensor and assoreceiver. See Setting the TE-7800 Series Receiver RF Addrepage 16 and Setting the WRS-TTx Series Sensor RF Addrespage 18 for more information.

The sensor and receiver may be out of RF signal range or thbe a RF signal obstruction between them.Check the RF signal strength and path between the sensor areceiver using the WRS-SST Series Wireless Sensing Syste

The receiver antenna may be positioned poorly.Reposition the receiver antenna and recheck the sensor/receassociation at the sensor.

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 37

Page 38: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

s ries.

igured

Receiver

receiver

g the

n the

or and

e

rces of

pping

nal idelines

be

r.

the h the

stment

5°F/13 to 29°C

Sensor);

dresses and for

Technical Specifications

Zone temperature control and/or zone setpoint is incorrect, unreliable, or erratic.

The WRS-TTx Series Sensor batteries may be low.Replace the sensor batteries. Refer to the WRS-TTx Series Wireless Room Temperature Sensors Installation Instruction(Part No. 24-10126-19) for information on replacing the batte

The zone temperature or setpoint values/range may be confincorrectly in the field controller.Check analog signal set up. See Calculating TE-7830 SeriesAnalog Output Signal Values on page 27.

More than one sensor may have the same RF address as theand the receiver is not set for multiple sensors.Check sensor and receiver addresses. See Setting the TE-7800 Series Receiver RF Address on page 16 and SettinWRS-TTx Series Sensor RF Address on page 18 for more information.

An obstruction may have been placed in the RF path betweesensor and the receiver.Check the RF path and the signal strength between the sensthe receiver.

New RF/WiFi interference may have been introduced into thOne-to-One environment.Check for changes to the RF/WiFi environment and new souRF interference.

Two receivers may have duplicate RF addresses and overlasignal coverage with associated sensors.Check for duplicate RF addresses and ensure there is no sigoverlap in applications with duplicate RF addresses. See Gufor Job Sites with 510 or More TE-7800 Series Receivers.

The wiring between the receiver and the field controller may incorrect or damaged.Check the wiring between the receiver and the field controlle

The sensor may be defective or damaged.Turn off the suspect sensor and configure a new sensor withreceiver address. Check the operation of the new sensor witreceiver.

WRS-TTx Series Sensors (Part 1 of 2)Product Codes WRS-TTP0000-x Series Sensors: Warmer/Cooler (+/-) Setpoint Adju

WRS-TTR0000-x Series Sensors: No Setpoint AdjustmentWRS-TTS0000-x Series Sensors: Setpoint Adjustment Scale 55 to 8

Power Requirements 3 VDC Supplied by Two 1.5 VDC AA Alkaline Batteries (Included withTypical Battery Life: 60 Months (48 Months Minimum)

Addressing DIP Switches, Field Adjustable for up to 511 Unique Transmitter ID AdUp to 31 Unique Property Code Addresses

Ambient Operating Temperature Limits

-0 to 122°F (18 to 50°C)

Ambient Operating Humidity Limits

5 to 95% RH, Noncondensing

Ambient Storage Temperature Limits

-40 to 160°F (-40 to 71°C)

Table 5: Troubleshooting One-to-One Wireless Sensing Applications (Part 2 of 2)

Problem or Symptom Cause/Action

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin38

Page 39: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

ne-of-Sight;

ne-of-Sight;

(29 to 43°C)

tions for Low

ick Mark)

t is in ons of the

licationsrface Applications

n

e between , and FXxx Series

pply

o 510 Unique Matches the Addresso 510 Unique

Ambient Storage Humidity Limits

5 to 95% RH, Noncondensing

RF Band Direct-Sequence, Spread-Spectrum, 2.4 GHz ISM Bands

Transmission Power WRS-TTx0000-0 Series Sensors: 15 dBm MaximumWRS-TTx0000-1 Series Sensors: 10 dBm Maximum

Transmission Range WRS-TTx0000-0 Series Sensors: 500 ft (152 m) Maximum Indoor Li200 ft (61 m) Practical Average IndoorWRS-TTx0000-1 Series Sensors: 375 ft (114 m) Maximum Indoor Li165 ft (50 m) Practical Average Indoor

Transmissions Every 60 Seconds (+20 Seconds); Every 10 Seconds (+2 Seconds) in Rapid Transmit Mode

Temperature System Accuracy 1F° (0.6C°) Over the Range of 55 to 85°F (13 to 29°C); 1.5F° (0.9C°) Over a Range of 32 to 55°F (0 to 13°C) and 85 to 110°F

Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor

Materials NEMA 1 White Plastic Housing

Mounting Double-Sided Adhesive Foam Tape Mount; Double-Sided Adhesive Foam Tape Included with Sensor

Compliance (WRS-TTx0000-0 Series Sensors)

United States: Transmission Complies with FCC Part 15.247 RegulaPower Unlicensed TransmittersTransmitter FCC Identification: CB2-TMPSENS2400A

Canada: Industry Canada IC: 279A-TSENS24A

Australia and New Zealand: Australia/NZ Emissions Compliant (C-TCompliance (WRS-TTx0000-1 Series Sensors)

Europe: CE Mark – Johnson Controls, Inc., declares that this produccompliance with the essential requirements and other relevant provisiR&TTE Directive 1999/05/EC.South Africa: Accepts Directives for Europe

Shipping Weight 0.3 lb (0.14 kg)

TE-7800 Series Receivers (Part 1 of 2)Product Codes TE-7820-x Series Receivers for One-to-One Zone Bus Interface App

TE-7830-x Series Receivers for One-to-One 0 to 5 VDC Analog Inte

Field Controller Interface TE-7820-x Series Receivers: Power and Zone Bus Interface betweeTE-7820-x Series Receiver and VMA14 Series ControllerTE-7830-x Series Receivers: Power and 0 to 5 VDC Analog InterfacTE-7830-x Series Receiver and AS-AHU, AS-UNT, AS-VAV, DX-9100Controller

Power Requirements 24 VAC (+10%/-15%), 50/60 Hz, 4.5 VA (Minimum) Class 2 Power Su

Addressing TE-7820-x Series Receivers: DIP Switches, Field Adjustable for up tAddresses; for Addresses 0 and 511, the TE-7820-x Series Receiver N2 Address of the Associated VMA14 Series Controller for Its Actual TE-7830-x Series Receivers: DIP Switches, Field Adjustable for up tAddresses; Addresses 0 and 511 are Invalid

Ambient Operating Temperature Limits

32 to 122°F (0 to 50°C)

Ambient Operating Humidity Limits

5 to 95% RH, Noncondensing

Ambient Storage Temperature Limits

-40 to 160°F (-40 to 71°C)

Ambient Storage Humidity Limits

5 to 90% RH, Noncondensing

WRS-TTx Series Sensors (Part 2 of 2)

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 39

Page 40: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

f-Sight;

f-Sight;

, Setpoint,

ture and Setpoint: Low Battery: Dry

(29 to 43°C)

4 VAC Class 2

4 VAC Class 2 Low Battery e Temperature

wer Unlicensed

ick Mark)

t is in ons of the

ns beyond these ing from

RF Band Direct-Sequence, Spread-Spectrum, 2.4 GHz ISM Bands

Transmission Power TE-78x0-0 Series Receivers: 15 dBm MaximumTE-78x0-1 Series Receivers: 10 dBm Maximum

Transmission Range TE-78x0-0 Series Receivers: 500 ft (152 m) Maximum Indoor Line-o200 ft (61 m) Practical Average IndoorTE-78x0-1 Series Receivers: 375 ft (114 m) Maximum Indoor Line-o165 ft (50 m) Practical Average Indoor

Transmissions Every 60 Seconds (±20 Seconds)

Receiver Outputs TE-7820-x Series Receivers: One Zone Bus Output for TemperatureField Strength Measurements, and Low Battery IndicationTE-7830-x Series Receivers: Two Analog Outputs for Zone Tempera0 to 5 VDC, 2 mA Maximum; Two Binary Outputs for Occupancy and Contacts Rated for 24 VAC, 50 mA Maximum

Temperature System Accuracy 1F° (0.6C°) Over the Range of 55 to 85°F (13 to 29°C); 1.5F° (0.9C°) Over a Range of 32 to 55°F (0 to 13°C) and 85 to 110°F

Sensor Type Internal 10k ohm Negative Temperature Coefficient (NTC) Thermistor

Wiring Terminations and Network Interfaces

TE-7820-x Series Receivers: One Two-Position Terminal Block for 2Supply Power and One Zone Bus PortTE-7830-x Series Receivers: One Two-Position Terminal Block for 2Supply Power, One Three-Position Terminal Block for Occupancy andBinary Output Relays, and One Three-Position Terminal Block for Zonand Setpoint Temperature Outputs

Materials Gray Plastic Housing with UL94-5VB Flammability Rating

Mounting Screw Mount; Four No. 6 Pan-Head, Sheet-Metal Screws Included

Compliance (TE-78x0-0 Series Receivers)

United States: Intended for NEC Class 2 Connection

UL Listed, File E107041, CCN PAZX

UL 94-5VB Flammability Rating

FCC Compliant to CFR 47, Part 15, Subpart B, Class A

Transmission Complies with FCC Part 15.247 Regulations for Low PoTransmittersReceiver Radio Module FCC Identification: CB2-RFMOD2400A

Canada: Intended for CEC Class 2 Connection

UL Listed, File E107041, CCN PAZX7

UL 94-5VB Flammability Rating

Industry Canada IC: 279A-RFMOD24A

Australia and New Zealand: Australia/NZ Emissions Compliant (C-TCompliance (TE-78x0-1 Series Receivers)

Europe: CE Mark – Johnson Controls, Inc., declares that this produccompliance with the essential requirements and other relevant provisiR&TTE Directive 1999/05/EC.South Africa: Accepts Directives for Europe

Shipping Weight 1.0 lb (0.45 kg)

The performance specifications are nominal and conform to acceptable industry standard. For application at conditiospecifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resultmisapplication or misuse of its products.

TE-7800 Series Receivers (Part 2 of 2)

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin40

Page 41: TE-7800 Series One-to-One Wireless Room Temperature Sensing System

Published in U.S.A. www.johnsoncontrols.com

TE-7800 Series One-to-One Wireless Room Temperature Sensing System Technical Bulletin 41

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.

Building Efficiency507 E. Michigan Street, Milwaukee, WI 53202