2
TC544A / TC244AX / TC344AX Display Specifications Digits 4+4 digits, 7 Segment LED dual display LED Indication 1. Output 1 ON T : Auto tune 2. Output 2 ON S : Dwell timer Input Specifications Inputs Thermocouple (J,K,T,R,S) / RTD (Pt100) o Resolution 0.1 / 1 for TC / RTD inputs o (fixed 1 for R & S type TC input) o Indication Accuracy For J, K & T inputs : 0.25% of F.S. ±1 o For R & S inputs : 0.5% of F.S. ±2 (20 min of warm up time for TC inputs) o For RTD inputs : 0.1% of F.S. ±1 (F.S. = Full Scale) o o Temperature Unit C / F selectable Input Filter (FTC) 0.2 to 10.0sec Sampling time 250 ms Output Specifications Control Output (Relay or SSR user selectable) Relay contact (SPDT) 5A resistive @ 250V AC / 30V DC (TC544A) : SPST RLY) SSR drive (Voltage Pulse) 12V DC, 50 mA Auxiliary Output Relay Contact (SPDT) 5A resistive @ 250V AC / 30V DC (TC544A) : SPST RLY) SSR drive (Voltage Pulse) 12V DC, 50 mA Functional Specifications Control Action 1) PID Control with auto tuning. 2) ON-OFF Control o Proportional Band (P) 1.0 to 400.0 Integral Time (I) 0 to 9999 sec Derivative Time (D) 0 to 9999 sec Cycle Time 0.1 to 99.9 sec o Hysteresis Width 0.1 to 99.9 o Manual Reset Value -19.9 to 19.9 Heat-cool Control Action PID o Proportional Band-Cool 0.0 to 400.0 Cycle Time-Cool 0.1 to 99.9 sec Dead Band Programmable from setpoint low limit to setpoint high limit. Settings for Alarm Output Modes Deviation, Absolute o Hysteresis 0.1 to 99.9 Environmental Specifications o Temperature Operating : 0 to 50 C o Storage : -20 to 75 C Humidity (non-condensing) 95% RH Weight TC544 : 142 gms TC244 : 200 gms TC344 : 252 gms Auxiliary Supply Specifications Supply Voltage 85 to 270V AC / DC (50 / 60Hz) OPTIONAL - 24V AC/DC, ±10% Power Consumption 6 VA max @ 230V AC Features: ! 4+4 digits, 7 segment LED dual display ! TC / RTD Input ! PID, ON / OFF Control ! Two Setpoints ! o o C / F Selectable ! Field selectable Control Output (Relay or SSR) ! Auxiliary Output : Relay / SSR ! Easy to use Certifications: C US ® 1 www.selec.com Temperature Controllers 48 x 48 mm 72 x 72 mm 96 x 96mm

TC544A / TC244AX / TC344AX Temperature Controllers

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TC544A / TC244AX / TC344AX Temperature Controllers

TC544A / TC244AX / TC344AX

Display Specifications

Digits 4+4 digits, 7 Segment LED dual display

LED Indication 1. Output 1 ON T : Auto tune 2. Output 2 ON S : Dwell timer

Input Specifications

Inputs Thermocouple (J,K,T,R,S) / RTD (Pt100)o Resolution 0.1 / 1 for TC / RTD inputs

o (fixed 1 for R & S type TC input) o Indication Accuracy For J, K & T inputs : 0.25% of F.S. ±1

oFor R & S inputs : 0.5% of F.S. ±2 (20 min of warm up time for TC inputs)

o For RTD inputs : 0.1% of F.S. ±1

(F.S. = Full Scale) o o Temperature Unit C / F selectable

Input Filter (FTC) 0.2 to 10.0sec

Sampling time 250 ms

Output Specifications

Control Output (Relay or SSR user selectable)

Relay contact (SPDT) 5A resistive @ 250V AC / 30V DC (TC544A) : SPST RLY)

SSR drive (Voltage Pulse) 12V DC, 50 mA

Auxiliary Output

Relay Contact (SPDT) 5A resistive @ 250V AC / 30V DC (TC544A) : SPST RLY)

SSR drive (Voltage Pulse) 12V DC, 50 mA

Functional Specifications

Control Action 1) PID Control with auto tuning. 2) ON-OFF Control oProportional Band (P) 1.0 to 400.0

Integral Time (I) 0 to 9999 sec

Derivative Time (D) 0 to 9999 sec

Cycle Time 0.1 to 99.9 sec oHysteresis Width 0.1 to 99.9

o Manual Reset Value -19.9 to 19.9 Heat-cool Control Action PID

o Proportional Band-Cool 0.0 to 400.0 Cycle Time-Cool 0.1 to 99.9 sec

Dead Band Programmable from setpoint low limit to setpoint high limit.

Settings for Alarm Output Modes Deviation, Absolute

o Hysteresis 0.1 to 99.9

Environmental Specifications

oTemperature Operating : 0 to 50 C oStorage : -20 to 75 C

Humidity (non-condensing) 95% RH

Weight TC544 : 142 gms TC244 : 200 gms TC344 : 252 gms

Auxiliary Supply Specifications

Supply Voltage 85 to 270V AC / DC (50 / 60Hz) OPTIONAL - 24V AC/DC, ±10%

Power Consumption 6 VA max @ 230V AC

Features:! 4+4 digits, 7 segment LED dual display! TC / RTD Input ! PID, ON / OFF Control! Two Setpoints!

o o C / F Selectable! Field selectable Control Output (Relay or SSR)! Auxiliary Output : Relay / SSR! Easy to use

Certifications: C US

®

1www.selec.com

Temperature Controllers

48 x 48 mm 72 x 72 mm 96 x 96mm

Page 2: TC544A / TC244AX / TC344AX Temperature Controllers

TC544A / TC244AX / TC344AX

Dimensions

A

52

72

96

MODELS

TC544A

TC344AX

TC244AX

B

52

72

96

C

94

83.7

73

D

45

67

90.5

E

4

4.5

5

F

46

69

92

G

46

69

92

DIM

All dimensions are in mm

Panel Cutout

F

G

B

A C

D

E

2www.selec.com

Temperature Controllers

Input Sensor Ranges

Ranges

Pt100-150 to 850 -150 to 850oC

oF

1 0.1

K

T

R & S

-199 to 400 -199 to 400

J-199 to 750 -199 to 750

oC

oC

oC

oC

oF

oF

oF

oF

-238 to 1562 -199 to 999

-328 to 1382 -199 to 999

-199 to 1350 -199 to 999

-328 to 2462 -199 to 999

-328 to 750 -199 to 750

0 to 1750 N/A

N/A32 to 3182

Resolution

Sensor type

Terminal Connections

2Cable Size (mm ) : 1.5-2.5 ; Stud Hole for Lug (mm) : 3.5 ; Tightening Torque (N-m) : 0.8

Cable Size (AWG) : 16-13 ; Stud Hole for Lug (inch) : 0.137 ; Tightening Torque (Lb-inch) : 7

L (+)

N (-)

1

2

5

4

6

7

8

9

10

11

12

13

14

15

16

17

18

TC+/RTD1

TC-/RTD2

RTD33

NO2

SS

R1+

-

NO1

COM2

NC2

COM1

NC1

TC344AXTC244AXTC544A

L (+)

N (-)

NO2

1

2

3

4

5

6

7

COM2

8

9

10

11

12

13

14

TC+/RTD1

TC-/RTD2

RTD3

SS

R

+

-

NC2

NO1

COM1 NC1

7

8

9

10

COM2

COM1

NO2

2

1

3

4

5

L (+) 6

N ( )

NO1

-

TC+/RTD1

TC /RTD2

RTD3

12

11

SSR1-

SSR1+

SSR

2

+

-

SSR

2

SSR

2

+

+

- -

Compliance

Applicable EMI / EMC Standards

Product Standard : IEC 61326-1

Category Standards Compliance

ESD Immunity Level III

Surge Immunity+/- 2 kV common mode, +/- 1 kV differential mode

Radiated SusceptibilityLevel III, 80 to 1000MHz Level II, 1.4GHz to 2GHz Level I, 2GHz to 2.7GHz

Conducted Susceptibility Level II

IEC 61000-4-2

IEC 61000-4-5

IEC 61000-4-3

IEC 61000-4-6

Voltage Dips andInterruptions

Dips : 0% residual voltage / 1 cycle (Criteria B), 40% residual voltage / 10 cycles 50Hz / 12 cycles 60Hz (Criteria C)70% residual voltage / 25 cycles50Hz / 30 cycles 60Hz (Criteria C) Interruptions : 0% residual voltage /250 cycles 50Hz / 300 cycles 60Hz(Criteria C)

IEC 61000-4-11

Level III

Conducted Emission

Radiated Emission

Electrical Fast Transient

CISPR-11

CISPR-11

IEC 61000-4-4

C US

®

C US

®

C US

®

TC244AX-24V

TC344AX

TC344AX-24V

TC544A --

--

--

--

--

--

--

--

--

--

--

--

--

--

--

----

--

--

TC544A-24V

TC244AX

TC544A-CU

OUTPUT 2

SSR (12V DC)RELAY

SUPPLY VOLTAGE

24V AC/DC

85-270V AC/DC

TC244AX-CU

OUTPUT 1

SSR (12V DC)RELAY

CERTIFICATION

TC344AX-CU

PRODUCT CODE

Ordering Information

For TC544 : 48 X 48 Collar clamp ACL4802 For TC244/TC344 : Clamp side with screw assembled

Mounting Accessories (Supplied with units)

Accessories (Optional)

Adapter plate 1) AP7248 : Plastic adapter plate, used to mount 1 / 16 DIN (cutout size 48 x 48) Instrument into existing (72 x 72) cutout size. 2) AP9648 : Plastic adapter plate, used to mount 1 / 16 DIN (cutout size 48 x 48) Instrument into existing (96 x 96) cutout size.

3) AP9672 : Plastic adapter plate, used to mount 72 x 72mm size instrument into existing (96 x 96) cutout size.

4) AP4896-4848-G-C : Plastic adapter plate, used to mount 1 / 16 DIN (cutout size 48 x 48) Instrument into existing (48 x 96) cutout size.

Standard SELEC accessories that can be used with this product.