Ducted SplitAir ConditionerSERVICE MANUALMODELS: LN-0380CC/AC
LN-0480CC/ACLN-0580CC/AC
WEBSITE http://biz.LGservice.comE-MAIL http://www.LGEservice.com/techsup.html
LN-SM-04
— 2 —
Contents
Model Number Nomenclature...............................................................................................3
General Data ..........................................................................................................................4
Dimensions ............................................................................................................................5
Wiring Diagram......................................................................................................................6
Troubleshooting Guide .........................................................................................................7
Features of Controller .........................................................................................................13
Exploded View and Replacement Parts List .....................................................................14
— 3 —
L N - 0 5 8 0 C CC: ConvertibleH: Horizontal FlowD: Down Flow
C: Cooling OnlyH: Heat Pump
1 : 115/60/15 : 200-220/50/18 : 380-415/50/3B : 220/60/3
2 : 220/60/16 : 220-240/50/19 : 380-415/60/3C : 440-460/50/3
3 : 208-230/60/17 : 100/50(60)/1A : 220/50/3D : 440-460/60/3
03 : 3 ton 08 : 7.5 ton 15 : 15 ton04 : 4 ton 09 : 8.5 ton 18 : 17.5 ton05 : 5 ton 10 : 10 ton 20 : 20 ton06 : 6.25 ton 13 : 12.5 ton 25 : 25 ton
Development Sequence
Nominal cooling capacity
LGDucted Split Air Conditioner
Model Number Nomenclature
— 4 —
General Data
Table-1
1) Test Condition of ARI Rated Cooling Capacity :Ambient:95°F , Air entering temprature : 80°F DB and 67°F WB
2) ARI standard210/240 or 360 for EER270 for Sound
3) Filters are standard supply.
Models LN-0380CC/AC LN-0480CC/AC LN-0580CC/ACCapacity Cooling (Btu/h) 35500 47000 57000
(W) 10402 13771 16701(kcal/h) 8946 11844 14364
Electric Heater (Watt) Option(5/10kW) Option(5/10kW) Option(5/10kW)Electrical Voltage (PH,V,Hz) 3/380-415/50 3/380-415/50 3/380-415/50Data Running Current Cooling (Amps) 7.5 9 11
M.C.A (Amps) 12.8 13.6 14.5Power Input Cooling (Watt) 4100 5150 5800
Performance EER Cooling (Btu/hr.W) 8.7 9.1 9.8Air Circulation (Indoor/Outdoor) (CFM) 1,030/2,470 1,410/3,000 1,770/3,000Moisture Removal ( /hr) 3 3.7 4.7Noise Cooling dB(A) - - -
Outdoor (dB(A),1m) 60 65 65Features Wired Remote Controller -(field supply thermostat) -(field supply thermostat) -(field supply thermostat)
Time Delay Safety Function O O OVertical Air-flow Direction control O O OHorizontal Air-flow Directioon control O O OCooling Operation Mode O O OHeating Operation Mode - - -Air Circulation Mode O O OSoft Dry Operation - - -Fan Speeds (steps) 2 2 2Auto-Operation - - -Sleep Mode - - -Timer Setting (24-Hour on/off) - - -Forced Operation - - -Self-Diagnosis Function - - -
Outdoor Coil Tube Size (mm) 7 7 7Row/FPI 2/18FPI 2/18FPI 2/18FPILength (mm) 818.6 1240.4 1357.4Face Area (m2) 0.62 1.04 1.14
Indoor Coil Tube Size (mm) 9.52 9.52 9.52Row/FPI 2/18FPI 2/18FPI 3/16FPILength (mm) 385 400 400Face Area (m2) 0.33 0.43 0.43
Outdoor Fan Type Propeller Propeller PropellerNo. used/Diameter 1/460 1/556 1/556Drive Type Direct Direct DirectRPM 880 900 900
Dimensions Indoor unit (W x H x D) (mm) 470*1014*480 600*1135*500 600*1135*500Outdoor unit (W x H x D) (mm) 870*800*320 722*855*691 722*855*691
Net Weight Indoor unit kg(Ibs) 59(130) 63(139) 63(139)Outdoor unit kg(Ibs) 65(143) 105(214) 105(214)
Service Liquid (mm) 9.52 12.7 12.7Valve Gas (mm) 15.88 19.05 19.05Stuffing Without S/Parts (20FT/40FT) 35/68 24/51 24/51
— 5 —
Dimensions
LN-0380CC/AC, LN-0480CC/AC, LN-0580CC/AC
1. Indoor unit Unit Dimensions
2. Outdoor unit
27.2"(691)
33.7"(855)
28.4"(722)
31.5"(800)
21.5"(546)12.6"(320)
34.3"(870)
LN-0380CC/AC LN-0480CC/ACLN-0580CC/AC
Filter Provision
M
C
E
D
HG
F
Q
N
L
KI
J
P
BA
Liqid lineLiqid lineLiquid line
R
CondensateDrain-Upflow3/4" NPT-Female
CondensateDrain-Horizontal3/4" NPT-Female
Suction lineSuction lineSuction line
MODEL LN-0380CC/AC LN-0480CC/AC, LN-0580CC/ACA 18.5 (470) 23.6 (600)B 18.9 (480) 19.7 (500)C 39.9 (1014) 44.7 (1135)D 3.3 (84) 5.4 (136)E 11.9 (303) 13.0 (329)F 5.6 (142) 7.1 (181)G 12.0 (304) 12.6 (319)H 0.6 (15) 0.6 (15)I 4.3 (110) 6.7 (170)J 6.3 (160) 9.4 (240)K 1.7 (43) 2.5 (64)L 2.0 (50) 2.8 (71)M 2.0 (52) 2.3 (58)N 1.8 (45) 2.1 (54)P 1.3 (32) 1.5 (38)Q 8.7 (221) 11.2 (285)R 19.1 (485) 23.0 (584)
Unit: inch(mm)
Unit: inch(mm)
FACTORY WIRING
OPTIONAL WIRING
FIELD WIRING
BK : BLACK
BR : BROWN
BL : BLUE
OR : ORANGE
RD : RED
GN/YL : GREEN /YELLOW
YL : YELLOW
WH : WHITE
NOTES
TRANS
OUTDOOR UNIT INDOOR UNIT
GN/YL
WH
BK
OR
BL
T3 T2T1
COMP
CAPACITOR
CAPACITORMOTOR(OUT)
MOTOR(IN)
3Ø 4WIRE 380/415V, 50HzPOWER SUPPLY
GN/YL
WH
BK
BK BL
BL
RD
RDRD YL
1
2
3
4
5
OR
BL
MA
GN
ET
IC C
ON
TAC
T(F
or C
omp)
PO
WE
R R
ELA
Y(F
or I/
Mot
or)
MA
GN
ET
IC C
ON
TAC
T(F
or E
/Hea
ter)
OU
TD
OO
R U
NIT
IND
OO
R U
NIT
PILLARTERMINAL
TIME DELAY P.C.B
FUSE(250V, 10A)
TERMINALBLOCK
PILLARTERMINAL
AC 24V
Fan
L
N
1
2
3
R
G
Y
W
Comp
Heater
AC 24V
Fan
Comp
Heater
ELECTRO-MECHANICALTHERMOSTAT
MECHANICALTHERMOSTAT
TERMINALBLOCK
THERMOSTATFOR EVA
TERMINALBLOCK
TE
RM
INA
LB
LOC
K
TERMINALBLOCK
RDWH
BK
BK
R S T N
WH RD
YL OR
OR
OR
RD
BK
BK BK
RD
A4
6B
BL
BL
OR
BK
BK(HI)
BR
YL
BL(LOW)
BK
OR
3Ø 4WIRE 380/415V, 50HzPOWER SUPPLY
USINGELECTRICHEATER
R S T N
TERMINALBLOCK
ELECTRICHEATEREH
P/NO : 3854A20098A
3
1 2
4
DIAGRAM WIRING
FACTORY WIRING
OPTIONAL WIRING
FIELD WIRING
BK : BLACK
BR : BROWN
BL : BLUE
OR : ORANGE
RD : RED
GN/YL : GREEN /YELLOW
YL : YELLOW
WH : WHITE
NOTES
TRANS
OUTDOOR UNIT INDOOR UNIT
GN/YL
WH
BK
OR
BL
RD
WH
BK
T3 T2T1
COMP
CA
PAC
ITO
R CAPACITORMOTOR(OUT)
MOTOR(IN)
GN/YL
WH
BK
BK BL
BL
RD
RDRD YL BK
1
2
3
4
5
OR
BL
MA
GN
ET
IC C
ON
TAC
T(F
or C
omp)
PO
WE
R R
ELA
Y(F
or I/
Mot
or)
MA
GN
ET
IC C
ON
TAC
T(F
or E
/Hea
ter)
OU
TD
OO
R U
NIT
IND
OO
R U
NIT
PILLARTERMINAL
TIME DELAY P.C.B
FUSE(250V, 10A)
TERMINALBLOCK
PILLARTERMINAL
AC 24V
Fan
L
N
1
2
3
R
G
Y
W
Comp
Heater
AC 24V
Fan
Comp
Heater
ELECTRO-MECHANICALTHERMOSTAT
MECHANICALTHERMOSTAT
TERMINALBLOCK
THERMOSTATFOR EVA
TERMINALBLOCK
RD WH BK
OR
OR
RD
BK
BK BK
RD
A4
6B
BL
BL
BL(LOW)
BR
YL
BK(HI)
3Ø 4WIRE 380/415V, 50HzPOWER SUPPLY
USINGELECTRICHEATER
R S T N
TERMINALBLOCK
ELECTRICHEATEREH
P/NO : 3854A20101A
3
1 2
4
DIAGRAM WIRING
RS
TN
RS
TN
1(L)
2(N
)3
4
1(L)
2(N
)3
4
3Ø 4
WIR
E 3
80/4
15V
50H
zP
OW
ER
SU
PP
LY
BK BK
OR OR
YL YL
BR BR
TERMINAL BLOCK
— 6 —
Wiring Diagram
LN-0580CC/AC, LN-0480CC/AC
LN-0380CC/AC
Troubleshooting Guide
— 7 —
Ineffective Cooling or Heating
Check of outdoor coil(heat exchanger) & the fanoperation.
Check gas leakage.
Repair gas leak.
Replacement of unit if theunit is beyond repair.
Satisfactory operation withtemperature difference ofinlet & outlet air ;COOLING : 7~10°CHEATING : 15~17°C
Check heat load increase incooling operation.
Unexpected residue
Added electrical utencil
Check of inside gaspressure.
Adjust refrigerantcharge.
Malfunction of compressor.
Replacement ofcompressor
Check of cold (warm) air cir-culation for smooth flow.
Dirty indoor coil(heat exchanger.)
Malfunction of fan.
Clogging of air filter.
Obstruction at air outlet.
Countermeasure againstabove trouble.
Check clogging in refrigera-tion circuit.
Repair clogging in refrigera-tion circuit.
In general, possible trouble is classified in two causes.The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective AirConditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but ineffective cooling
— 8 —
Troubleshooting Guide
Fails to Start
Check of circuit breakerand fuse.
Check control switch.
Fan only fails to start.
Improper wiring.
Defect of fan motorcapacitor.Defect of compressor
capacitor.
Irregular motor resistance( Ω )Irregular motor insulation( Ω )
Replacement of fan motor.
Improper electric heater
Replacement of electric heater.
Regular but fails to start.
Replacement of compressor.
Electric heater is not energized
Loose terminal connection.
Improper wiring
Irregular motor resistance ( Ω )
Irregular motor insulation ( Ω )
Replacement of compressor
Drop of power voltage.
Capacitor check.
Replacement of capacitor.
Compressor only fails to start.
Check power source.
Check control switchsetting.
— 9 —
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
1. No cooling and heating operation performed1) Both the blower and the compressor do not work
NAME PLATE RATING MINIMUM MAXIMUM
380/415 V 323 V 477 V
2) Only Indoor blowers do not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Other parts except theunit
Magnetic switch for com-pressor & fan motor
Operating switch
• Electric supply interrupted• Defective power wiring• Cut off power fuse
Too low voltage
Control point is on condi-tion of "OFF" due to trou-ble.
Troubled or defectivecontactor
Measure power sypplywith a tester in case thatthe same power source issupplied to other equip-ment except the unit,what and where troubledcan be discovered bychecking the operation ofother equipment.
Measure it with a tester.
Make short-circuit, thenmeasure it with tester.
Check it with the eyes ortester.
• Repair a switch box andrelative instrument.
• Replacement of fuse
• Request a power supplier to repair.
Check the power source.Use a thick cable if nec-essary.
Replace it if necessary.
Repair or replace it.
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Motor
Capacitor
Electric wiring
• Over heated• Wiring short
Defected
• Cut- OFF of wiring• Short circuited on
operation
Check it with tester
Check it with a tester.
Check it with a tester.
Repair or replace it.
Replace it.
Rewiring or Repair.
Troubleshooting Guide
— 10 —
3) Only outdoor fan does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Motor
Electric Wiring
• Over-heated• Wire short
Cut off of wiring
Short circuited on operation
Check how it is insulated.
Check it with a tester.
Repair or replace it.
Rewiring or repair.
4) Only compressor does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Magnetic switch forcompressor motor
Compressor motor
High pressure switch(Option part)
Electric circuit
Defective contact, magnetic coil troubled.
Troubled over-heated (layer short)
Troubled or defective contact or operating
Defective connection ordisconnection of the circuitfor compressor.
Check it with the eyes onwith a tester.
Check how it is insulated.
Check it with a tester.
Check it with a tester.
Repair or replace it.
Replace or repair thecompressor.
Replace it if neces-sary.
Rewiring or push resetbutton.
Troubleshooting Guide
— 11 —
Note: Use an appropriate measuring instrument for readjustment.
*1: High-pressure switch moves.
*2: Low- pressure switch moves.
2. The Units discontinue after the operation started
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Outdoor coil
In-condensable gasblended.
High pressure switch(Option part)
Refrigerant
Outdoor Fan
Coil is dirty *1
Air intruded into the refrigerant pipe line *1
Improper adjustment
A shortage of refrigerantamount. * 2
Check pressure
Reverse rotation of fan Obstacle
Air short circuit *1
Checking
In the event that difference between thesaturating temperaturecorresponding to highpressure and the temperature of air discharged from the outdoor coil is more than15°C, incondensable gasmay be blended.
Check it with a pressuregauge.
Confirm the wind blowingout upward.
Check it with eyes.
Wash it by means ofsomething like chemicalwashing.
Extract air by vacuumpump, then replenish(charge) the refrigerant.
Read just it to normaloperating pressure. (Note)Don't alternate the specified adjusting pressure. If the adjustedpressure exceed thespecified range, it willcause a great accident.
Replenish the refrigerant. Repair thespot where it is leaked.
If reversed, connectinterchanged wires toeach terminal. Power wirings.
Troubleshooting Guide
— 12 —
3. The unit is working, but not cooling and heating sufficiently(Both blower and compressor are working)
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Load
Air flow
Short air volume
Refrigerant
Air passage
Air filter
Much Cooling or Heatingload
Obstacle disturbs Intakeof uniform airflow.
Reverse rotation of blower.
Shortage in the chargedrefrigerant.
Improper or foreign bodies
Clogged with dust
Heat load increased. Window or door has manycracks or gaps.
Checking
Checking
Coil inlet pipe is frosted
Checking
Checking
Do necessary disposalrespectively.
Correct it.
Correct it.
Recharge it. (Repair the leakage spot).
Correct or clear the foreign bodies.
Cleaning
4. All the functions are performed as specified, but very noisy and vibrantWHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Compressor
Blower
Screws
Electric troubles(Magnetic contactor)
Others
• Checking
Checking
Checking
Checking
Improper installation Checking
• Replace the compressor
Repair or replace it.Clear the foreign bodies.
Correct
Repair and clean orreplace it.
Correct it.
Liquid refrigerant floodingback from the evaporator.
Faulty Discharge valveand suction valve.
Fan broken.
Foreign matters intruded.
Looseness or fail-off ofscrews
Defective contact.Defective contact point.Rusting and foreign mat-ters in the iron core con-tact face. Defective con-tact of the operating switch.
• Check for refrigerant over-charge.• Check to see if the intake air temperature is
extremely cold.• Check for insufficient air flow quantity.
Troubleshooting Guide
— 13 —
Features of Controller
12V
12V
L1
L2
L3
12V
R03M220K
R01M47K
R06M1K Q01M
KRC107K
DO1M1N4148
RY01MJQ1a-12V
ZNRINR14D471
TRANSRY01M
JQ1a-12V
MagneticRelay
AC220V60Hz
R02M47K IC01M
KA393
D04D10
D02D
D05D
C02D104
C04D104
IC01D7812
C01D470uF25V
D03D
D02D~D05D1SR139-600
3
8
1+-2
4C01M3.3uF
+
+
IC2C7
IC1 C1CN1
CN2
D1
D2D3
D4
D5
C4
RY1
R5
R8
R9
R6
D6
C6
C8
R7
D7
R3
R2
C2
R4
R1
R10
PCB: 2Q01062A
C3
C5
Q1
Q2
IC3
CN
3
1. Timer PCB Circuit Diagram
2. Timer PCB ASSY
— 14 —
Exploded View and Replacement Parts List
249951
552111
266140
W0CZZ-1
354210-2
354210-1
W6920
261704
268716
330860-1
359012
346810
330860-2
1. Indoor Unit • Exploded View (LN-0580CC/AC, LN-0480CC/AC, LN-0380CC/AC)
— 15 —
Exploded View and Replacement Parts List• Replacement Parts List
LN-0580CC/AC
LN-0480CC/AC
LN-0380CC/AC
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A10044B 4995A10044B261704 TRANSFORMER,POWER 6171AQ2138G 6171AQ2138G266140 CONTROLLER ASSEMBLY(CIRC) 6614A30001J 6614A30001J268716 TIMER 3Q01017B 3Q01017B
330860-1 DRAIN PAN 3086A10006A 3086A10006A330860-2 DRAIN PAN 3086A10007A 3086A10007A346810 MOTOR ASSEMBLY,INDOOR 4681A20022K 4681A20022K
354210-1 EVAPORATOR ASSEMBLY,FIRST 5421A10002J 5421A10002J354210-2 EVAPORATOR ASSEMBLY,FIRST 5421A10002K 5421A10002K359012 FAN ASSEMBLY,BLOWER 2A00578M 2A00578M552111 TUBE ASSY,CAPILLARY 5211A20297D 5211A20297DW6920 RELAY 6920AP3194B 6920AP3194B
W0CZZ-1 CAPACITOR,DRAWING 2A00986C 2A00986C
LOCATIONNo.
DESCRIPTIONLN-0580CC LN-0580AC
PART No.
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A10044C 4995A10044C261704 TRANSFORMER,POWER 6171AQ2138G 6171AQ2138G266140 CONTROLLER ASSEMBLY(CIRC) 6614A30001J 6614A30001J268716 TIMER 3Q01017B 3Q01017B
330860-1 DRAIN PAN 3086A10006A 3086A10006A330860-2 DRAIN PAN 3086A10007A 3086A10007A346810 MOTOR ASSEMBLY,INDOOR 4681A20022F 4681A20022F
354210-1 EVAPORATOR ASSEMBLY,FIRST 5421A10002M 5421A10002M354210-2 EVAPORATOR ASSEMBLY,FIRST 5421A10002N 5421A10002N359012 FAN ASSEMBLY,BLOWER 2A00578M 2A00578M552111 TUBE ASSY,CAPILLARY 5211A20233Z 5211A20233ZW6920 RELAY 6920AP3194B 6920AP3194B
W0CZZ-1 CAPACITOR,DRAWING 0CZZA20001C 0CZZA20001C
LOCATIONNo.
DESCRIPTIONLN-0480CC LN-0480AC
PART No.
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20165A 4995A20165A261704 TRANSFORMER,POWER 6171AQ2138G 6171AQ2138G266140 CONTROLLER ASSEMBLY(CIRC) 6614A30001J 6614A30001J268716 TIMER 3Q01017B 3Q01017B
330860-1 DRAIN PAN 3086A10011A 3086A10011A330860-2 DRAIN PAN 3086A10012A 3086A10012A346810 MOTOR ASSEMBLY,INDOOR 4681A20022F 4681A20022F
354210-1 EVAPORATOR ASSEMBLY,FIRST 5421A20070A 5421A20070A354210-2 EVAPORATOR ASSEMBLY,FIRST 5421A20070B 5421A20070B359012 FAN ASSEMBLY,BLOWER 2A00578U 2A00578U552111 TUBE ASSY,CAPILLARY 5211A20297C 5211A20297CW6920 RELAY 6920AP3194B 6920AP3194B
W0CZZ-1 CAPACITOR,DRAWING 2A00986D 2A00986D
LOCATIONNo.
DESCRIPTIONLN-0380CC LN-0380AC
PART No.
— 16 —
Exploded View and Replacement Parts List
5468
10
5590
10
5522
03-1
W0C
ZZ-2
5541
60
6499
5055
2203
-256
6001
5540
31-2
5540
31-1
2. Outdoor Unit • Exploded View (LN-0580CC/AC, LN-0480CC/AC)
— 17 —
Exploded View and Replacement Parts List
5541
60
5522
03-1
5522
03-2
5590
10
5468
10
4353
01
5540
31
6499
50
5660
01
W0C
ZZ-2
• Exploded View (LN-0380CC/AC)
— 18 —
Exploded View and Replacement Parts List• Replacement Parts List
LN-0580CC/AC
LN-0480CC/AC
LN-0320CC/AC
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995A20157A 4995A20157A546810 MOTOR ASSEMBLY,OUTDOOR 4681A20039A 4681A20039A
552203-1 VALVE,SERVICE 2A00499E 2A00499E552203-2 VALVE,SERVICE 2H01890A 2H01890A554031-1 CONDENSER ASSEMBLY,BENT 5403A10001B 5403A20057F554031-2 CONDENSER ASSEMBLY,BENT 5403A10001D 5403A20057H554160 COMPRESSOR 5417A20008G 5417A20008G559010 FAN ASSEMBLY,PROPELLER 5901A10010A 5901A10010A
W0CZZ-2 CAPACITOR,DRAWING 2A00986D 2A00986D566001 SWITCH,MAGNET 6600B000040 6600B000040
LOCATIONNo.
DESCRIPTIONLN-0580CC LN-0580AC
PART No.
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995A20157A 4995A20157A546810 MOTOR ASSEMBLY,OUTDOOR 4681A20039A 4681A20039A
552203-1 VALVE,SERVICE 2A00499E 2A00499E552203-2 VALVE,SERVICE 2H01890A 2H01890A554031-1 CONDENSER ASSEMBLY,BENT 5403A10001F 5403A20057K554031-2 CONDENSER ASSEMBLY,BENT 5403A10001H 5403A20057M554160 COMPRESSOR ASSEMBLY 5417A30002A 5417A30002A559010 FAN ASSEMBLY,PROPELLER 5901A10010A 5901A10010A
W0CZZ-2 CAPACITOR,DRAWING 2A00986D 2A00986D566001 SWITCH,MAGNET 6600B000040 6600B000040
LOCATIONNo.
DESCRIPTIONLN-0480CC LN-0480AC
PART No.
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995AP2136W 4995AP2136W546810 MOTOR ASSEMBLY,OUTDOOR 4681A20008Z 4681A20008Z
552203-1 VALVE,SERVICE 2A00392F 2A00392F552203-2 VALVE,SERVICE 2A00393A 2A00393A554031 CONDENSER ASSEMBLY,BENT 5403A20022V 5403A20066D554160 COMPRESSOR ASSEMBLY 5417A90001E 5417A90001E559010 FAN ASSEMBLY,PROPELLER 1A00195B 1A00195B566001 SWITCH,MAGNET 6600B000040 6600B000040
W0CZZ-2 CAPACITOR,DRAWING 2A00986D 2A00986D435301 GRILLE,DISCHARGE 3530A20007J 3530A20007J
LOCATIONNo.
DESCRIPTIONLN-0380CC LN-0380AC
PART No.
P/No.: 3828A20134B
January, 2005
Printed in Korea