Subproject : Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project VIETNAM ELECTRICITY TRUNGSON HYDROPOWER COMPANY LIMITED ENVIRONMENTAL MANAGEMENT PLAN MAI CHAU 110 KV SUBSTATION AND 35 KV POWER LINE SUPPLY FOR CONSTRUCTION OF TRUNG SON HYDROPOWER PROJECT Ha Noi, January 2013 Environmental Management Plan (EMP) E2248 1

TẬP ĐOÀN ĐIỆN LỰC VIỆT NAM - Documents & …documents.worldbank.org/curated/en/132961468131703481/E... · Web viewConstruction of the subproject “Mai Chau 110 kV substation

Embed Size (px)

Citation preview

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

VIETNAM ELECTRICITY

TRUNGSON HYDROPOWER COMPANY LIMITED

ENVIRONMENTAL MANAGEMENT PLAN

MAI CHAU 110 KV SUBSTATION AND 35 KV POWER LINE SUPPLY FOR CONSTRUCTION OF

TRUNG SON HYDROPOWER PROJECT

Ha Noi, January 2013

Environmental Management Plan (EMP)

E2248 v14

1

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Table of Contents

1. PROJECT DESCRIPTION AND SCOPE OF WORK.................................................................................4

1.1. Construction of Mai Chau 110 kV Substation and its 68 m Connection Line.................................................5

1.2. Construction of 35kV Power Line Supply for Construction of Trung Son HPP ...........................................11

1.3. Supplement of Materials and Equipment for the Subproject..........................................................................14

1.4. Transportation of Construction Materials and Equipment.............................................................................14

1.5. Number of Workers and Workers Camps.......................................................................................................14

1.6. Subproject Schedule.......................................................................................................................................15

1.7. Total of Subproject Investment......................................................................................................................16

1.8. Some Pictures of the Subproject Site..............................................................................................................172. POLICY AND REGULATION FRAMEWOR............................................................................................212.1. Regulations of Vietnamese Government........................................................................................................212.2. The World Bank Safeguard policies..............................................................................................................22

3. ENVIRONMENTAL SCREENING..............................................................................................................223.1. Screening for Eligibility of Subproject Siting................................................................................................22

3.2. Potential Impacts.............................................................................................................................................26

4. MITIGATION MEASURES...........................................................................................................................37

5. EMERGENCY ACTION PLAN....................................................................................................................486. COMMUNITY CONSULTATION AND INFORMATION DISCLOSURE............................................50

7. ENVIRONMENTAL MONITORING PLAN...............................................................................................54

8. ARRANGEMENT FOR EMP IMPLEMENTATION.................................................................................62

9. REPORTING PROCEDURE.........................................................................................................................64

10. CAPACITY BUILDING PLAN..................................................................................................................65

11. ESTIMATED COST FOR IMPLEMENTATION OF EMP.....................................................................66

REFERENCES.....................................................................................................................................................67APPENDIX 1 LIST OF MEMBERS PREPARING THE REPORT..............................................................68APPENDIX 2: TOR for Construction Supervision Consultant (CSC)..........................................................69

Environmental Management Plan (EMP) 2

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

ABBREVIATIONS

DEP Distribution Efficiency Project

ECOPs Environmental Code of Practices

EIA Environmental Impact Assessment

EMP Environmental Management Plan

EG Environmental Guideline

EVN Electricity of Vietnam

HHs Households

HPP Hydropower project

PAHs Project Affected Households

PECC4 Power Engineering and Consulting Company 4

PMU Project Management Unit

PC Power Company

ROW Right of Ways

WB World Bank

Environmental Management Plan (EMP) 3

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

1. PROJECT DESCRIPTION AND SCOPE OF WORK

GENERAL DESCRIPTION

This is a subproject under the Trung Son hydropower project financed by the World Bank. Reasons of Subproject proposals:

Trung Son hydropower plant will be constructed on the Ma River, in the territory of Trung Son commune, Quan Hoa district, Thanh Hoa province. Installed capacity of the hydropower project is 260 MW, annual electricity produced will be 1056 GWh. Trung Son hydropower project will bring benefit in term of power generation and flood control.

Construction of the subproject “Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project” is aimed to meet the local power demand, supply electricity for construction of Trung Son hydropower project and supply electricity for ressettlement sites.

The subproject is consisted of two components:

- Mai Chau 110 kV substation and connections;

- 35kV power line supply for construction of Trung Son hydropower project (19. 427 km).

The construction of Mai Chau 110 kV substation and 19.427 km of 35 kV power line can cause negative impacts on the environment and local communities during pre-construction phase, construction phase and operation phase.

In order to ensure that potential negative impacts are identified and mitigated during subproject implementation and that the subproject complies with the Environmental Assessment policy (OP/BP 4.01) of the WB, an Environmental Management Plan (EMP) of the subproject has been prepared in compliance with the Environmental Guideline (EG) prepared under Trung Son hydropower project. This EMP is prepared with reference to Environmental Management Framework (EMF) of the Distribution Efficiency Project sponsored by the WB. Application of some items of EMF is suitable in this case due to similarities of the Subproject and other subproject under DEP. This EMP includes: the subproject description, legal and policy frameworks, applicable environmental technical standards and regulations, potential negative impacts, proposed mitigation measures to be implemented prior and during construction and operation, and implementation arrangements. The EMP also includes Environmental Codes of Practice (ECOP) that will be integrated into bidding and contractual documents, monitoring and supervision during the implementation.

Environmental Management Plan (EMP) 4

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

EIA of Trung Son hydropower project (including the subproject Mai Chau 110 kV substation and 35 kV power line supply for Trung Son HP) was approved by Ministry of Environment and Natural resource by Decision N0 1257/QD-BTNMT dated 17/6/2008 on approval of EIA for Trung Son hydropower project.

PROJECT DESCRIPTION

1.1. Construction of Mai Chau 110 kV Substation and its 68 m Connection Line1.1.1. Alternatives for subproject location.

General requirements on Subproject’s locations

Selection of location for Mai Chau 110 kV substation is made based on the following technical and financial requirements:

- To comply with Master plan for power development No 6 and comply with Local socio-economic plannings;

- Technical requirement: To ensure to have enough area for the substation and power line connections. The location should be optimized in term of having minimum power loss for power grid;

- Natural condition requirement: Geological pattern is suitable for substation construction, climate is suitable. Topography is preferably to be flat, open to enable access and connections with the power grid.

- Location should be convineinent for construction, transportation of substation’s equipment during operation phase.

- Minimize compensation and ressettlement, avoid impact in cultural and historical valuable sites. Minimize impact on local landscape and views.

- Minimize loads on ground leveling. - Make use of the existing facilities such as road, power source, water source. - Minimize environmental impacts caused by the substation to surrounding

areas.

Substation location alternativesBased on the above-mentioned requirement, technical consultants (PECC4) have investigated and proposed 3 alternatives described bellow:

- Option 1: Mai Chau 110 kV substation will be constructed on rice and dry crop field of Na Quan (Tong and Dau villages), Tong Dau commune, Mai Chau district, Hoa Binh province.

- Option 2: Mai Chau 110 kV substation will be constructed on agricultural alnd of Vang village, Mai Chau township, Mai Chau district, Hoa Binh province.

- Option 3: Mai Chau 110 kV substation will be constructed on the agricultural land next to the existing Mai Chau 35 kV substation in Mai Chau township, Mai Chau district, Hoa Binh province.

Environmental Management Plan (EMP) 5

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Among these three options, the option 3 having connecting 110 kV power line overpassing deeply in center of Mai Chau township. This affect affect development of Mai Chau township so there will be many disadvantages to local development planning. Beside that, the option 3 will not comply with Decision 5638/QDD-BCT dated 22/20/2008 of MOIT on “Decision on amandement of Power Development Planning for Hoa Binh Province in period 2006- 2010 with vision to 2015”. So option 3 is excluded before go to further considerations. Table 1.1. Comparison of alternatives for Mai Chau 110 kV substation location

Aspects to be considered

Option 1(Tong Dau commune)

Option 2(Mai Chau township)

Planning issue This option is not conflict with other local planning.

Near planned residential areas of Mai Chau township.

Natural conditions, work load for ground leveling and substation foundation

- Area is open, quite flat, and dry. At the present time, the area is 1-harvest rice field.

- Area is open, quite flat, and dry. At the present time, the area is 2-harvest rice field.

Connection scale and possibilities for extension

- Convenient for connections with 110 kV, 35 kV with possibility to connect with 22 kV. Extension of the substation is possible.

- Connections are limited because of planned residential area. There is limited possibility of the subproject extension.

Existing infrastructures - Convenient for construction and management during operation phase.

- Convenient for construction and management during operation phase.

Environmental and social impacts

- Limited environmental impacts. Limited resettlement and compensation.

- Larger impacts on rice field in the substation location as well as in connecting power lines.

Financial issue Higher investment costInvestment cost of the option 1 is about 2 billion VND due to:- Length of the access road to the substation is 300 m longer;- Length of 35 kV supply for Trung Son HPP is 1,800 m longer.

Lower investment cost

Comparison of power loss when connects to the power grid

There is no difference between two options.

Consultation with local authorities During site investigations, Consulting company PECC4 has worked and

consulted with relevant authorities in Hoa Binh province. Even the

option 1 having higher investment cost than the option 2 (2.05 billions),

Environmental Management Plan (EMP) 6

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

but this location is more suitable for the socio-economic planning of

Hoa Binh province. Local authorities approve the Option 1.

Selected alternative X1.1.2. Specific description of substations by selected location

Table 1.2 Project Scope and Site Summary – New 110/35kV Substation and Connection lines

1. Name of 110 kV sub-station, other sub-stations and length of ROW:

Location of each sub-station (specify name of commune and district)

ROW width and length List communes where transmission lines come through, by district

Mai Chau 110 kV substation

An acquired area is 8,336.0 m2.

- Width of the ROW of the connection is 4 m. Length is 68 m.

Hoa Binh province, Mai Chau district, Tong Dau commune

3. Total land area acquired for sub-stations construction and existing land use

- Total acquired land for the substation including access road is 8,336.9 m2

- Total land permanently acquired for foundations of towers of the 68 m connection line is 283.40 m2

List by sub-station, total land area include access road

Attach a simplified layout showing existing land use within 50 m from the boundaries of each sub-station

4. Is there any sub-station or ROW located within 3 km from natural reserves or forests...?

Yes______ No_X____

If yes, declare in (6)

5. Is there any sub-station or ROW located within 300m from historical sites, temples, pagodas or other cultural structure?

Yes______ No__X___

If yes, declare in (6)

6. Is there any sub-station or ROW located within 300m from to a commune centre

Yes___X___ No_____

Environmental Management Plan (EMP) 7

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

rung (CPC, school, market, clinic etc) or within 2 km from a residential cluster?

If yes, declare in (6)

7. List of environmental sensitive structures claimed in (3) – (5)

No. Name of sub-station/ROW location

Environmental sensitive objects (name and brief

Distance

1- Mai Chau 110 kV substation and its connection line

- Tong Dau primary school

The school is about 150 m far from Mai Chau 110 kV substation. The first part of 35 kV supply power line is going along the edge of the school.

Mai Chau 110 kV subsation is proposed to be built in the land used for 1-harvest rice field and dry crop cultivation on Tong Dau commune, Mai Chau dictrict of Hoa Binh province.

- North of the proposed subsation is bordered with field for rice and dry crop cultivation;

- South of the substation is field and about 100 m far from Tong Dau primary school.

- East of the substation is borderd with national road N0 15. - West of the substation is field and is about 100 m far from 110 kV Hoa Binh-

Moc Chau power line and 35 kV Mai Chau- Hoa Binh power line. Total acquired land for the substation is 8,336.0 m2. Of which:

- Land for the substation and access road is: 7,336.0 m2.- Land for resting house of operating team is: 1,000.0 m2.

An access road to the substation

An access road to the substation is 135.0 m in length connecting substation to the

national road 15. This road is made by reinforced concrete, 4 m wide. Slope of the road is

2% in both sides. The pavement is 1.5 m and ROW of the road is 6 m (calculated from

the outest point of the pavement).

Environmental Management Plan (EMP) 8

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

The road is constructed by widening of the existing inter commune road in Tong Dau

commune. At the present time, this inter commune road is also passing Tong Dau

primary school. From the widening point to Tong Dau primary school is about 150 m.

During construction, widening of the road might cause short term environmental impacts

on the traffic in the inter commune road. In long term, subproject’s vehicles will use only

the extended road for transportation so no impact on local traffic will occur.

Water supply system

Water used for living and construction will be purchased from the water supply utility of Mai Chau district. Water supply pipe is available at 100 m far from the substation. Water for construction will be supplied to construction sites by tank truck and plastic water pipes. During operation phase, water will be supplied through zinc-coated steel pipe (34 mm in diameter). Water will be stored in 10m3 reinforced cisterns and will be pumped up to tank fixed in roof of operating house and resting house.

Water drainage system

- Domestic water will be collected to underground cistern and will self soaked to the soil.

- Drainage system for the substation’s surface water run off: rain water will be drained out through designed slope. Collecting holes are designed along road inside the substation. Holes are connected by PVC 150. By this PVC pines, rain water is collected and discharged to the existing water canal outside the substation.

Table 1.3. Main Work Load for Construction of Mai Chau Subsation

No Work Unit Amount

1 Remove vegetation cover (0.1 m thick) m3 855

2 Soil excavation for foundation m3 840

3 Soil leveling m3 7,802.5

Basin for oil collection in emergency will be constructed under each transformer. Basin will be constructed by reinforced concrete. This basin is under grounded and has a volume about 22 m3. This volume is enough to collect oil in the designed transformers

Environmental Management Plan (EMP) 9

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

(including the transformer reserved to install in later phase – from 110 kV - 25MVA to 110 kV - 40 MVA). Walls (0.5 m high) around foundation of transformers are constructed to avoid oil spill. In case, accident of oil spill is occurred, spilled oil will be collected through steel pipe Ф200, 5mm thick.

Fire prevention and protection system

There are 2 water tanks (3 m3 /each tank) and 6 sand containers (1m and 1m in height). Water tanks and sand containers are allocated along road and near inflammable subjects such as transformers, operating house. Beside these, there are fire extinguishers (powder type, CO2 type) and manual tools for fire control are equipped.

Environmental Management Plan (EMP) 10

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Scheme 1. Sketch map of Mai Chau 110 kV Substation

Environmental Management Plan (EMP) 11

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

110 kV connection line

Start point: in between tower N0 187 - 188 (the point is 40.3 m far from tower No 187) of the existing 110kV Hoa Binh - Moc Chau power line.

End point: Gate tower of the proposed Mai Chau 110 kV substation;

Length: 68m.

Topography in the area (that the connection line will overpassing) is quite flat. Land use pattern in the ROW is rice and dry crop field. The connection line will overpass land of Tong Dau commune, Mai Chau district, Hoa Binh province.

Route of the connection line is agreed by People committee of Hoa Binh province by document 285/UBND-CT dated 09/3/2009.

1.2. Construction of 35kV Power Line Supply for Construction of Trung Son HPP (19,427 km).

Table 1.4. Project scope and Site Summary

1. Total length of power lines 19.427 km

2. Name of communes where powerlines come through

Commune in Hoa Binh province, Mai Chau district: Tong Dau, Mai Chau township, Chieng Chau, Mai Ha, Van Mai.

Thanh Hoa province, Quan Hoa district: Phu Thanh

3. Width of ROW

- 3 m

- Total land permanently acquired for foundations of 19.427 km of 35 kV power line is: 3,513.41 m2

4. Is there any ROW located within 3 km from natural reserves or forests...?

Yes X______ No_____

If yes, declare in (7) (Note: the power line will overpass planted bamboo Luong forest of the local people).

5. Is there any ROW located within 300m from historical sites, temples, pagodas or other cultural structure?

Yes ______ No__X___

If yes, declare in (7)

6. Is there any ROW located within 300m from to a commune centre (CPC, school, market, clinic etc) or within 2 km from a residential cluster?

Yes _X_____ No_____

If yes, declare in (7)

Environmental Management Plan (EMP) 12

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

7. List of environmental sensitive structures claimed in (4) – (6)

No Name of ROW locationEnvironmental sensitive objects (name

and brief description)

Distance

1 - Start point to G1 - Tong Dau primary school

The school is about 150 m far from Mai Chau 110 kV substation.

2 - Section G3-G4

- Residential area of Mai Chau township - The power line is about 200 m far from the residential area.

3 - Section G7 – G8 - Centre of Chieng Chau commune - 70m

4 - Section G15 – G16- National road No 15 in Mai Ha commune area

- The power line is about 50 m far from National road No15.

5 - Section G21 – G22 - Admistrative area of Van Mai commune - 70m

6 - Section G25 - The power line will overpass Xia stream- The power line will overpass Xia stream

7- Section G25 to the end point

- Bamboo Luong forest planted by local people for commercial purpose

- The power line will overpass bamboo Luong forest planted by local people for commercial purpose

Route of the 35 kV power line was approved by People committee of Hoa Binh province and Quan Hoa district agreed. The power line will mainly go along national road No 15, along the road used for construction of Trung Son HPP, along inter commune road. The power line will mainly overpass rice field. Main characters of the power line are described in Table 1.4.

Table 1.5. Main Characteristics of the 35 kV Power Line

No Characteristics Information

1 Starting point 35 kV feeder of Mai Chau 110 kV

Environmental Management Plan (EMP) 13

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Characteristics Information

substation

2 Ending pointTower No 59 of 35 kV power line supply

for Ban Uon 110 kV substation

3 Voltage level 35 kV

4 Number of phases 01

5 Length 19,427 m

6 Number of direction changes 38

7 Number of houses within ROW 0

8 Length of part overpassing rice field 11,461 m

9 Length of part overpassing fruit gardens 145 m

10 Length of part overpassing planted eucalyptus 210 m

11Length of part overpassing planted bamboo Luong forest

3,759 m

12 Length of part overpassing dry crop fields 2,403 m

13 Length of part overpassing unused land 1,429 m

14 Number of times overpassing streams 3 times

15 Number of times ovepassing road <10 m 4 times

16 Number of times ovepassing road <5 m 21 times

The 35 kV power line is composed of two main sections as described bellows:

- Section 1: From the starting point to G26 (15,396 m in length).

The power line is started from Mai Chau 110 kV/30 kV substation in Tong Dau commune (Mai Chau district, Hoa Binh province). The power line will overpass Mai Chau- Hoa Binh 35 kV power line and Hoa Binh- Moc Chau 110 kV power line. In this section, the power line will go along national road No 15 (in the right hand side). Distance from the power line to the national road is ranging from 250 m to 500 m. Turnings (change direction of the route) are required to avoid residential areas. Topography of the area is quite plain. Main land use patterns are fruit tree gardens, rice and dry crop fields, hills with bamboo Luong planted forest. The power line will overpass land of Tong Dau commune, Mai Chau Township, Chieng Chau, Mai Ha, Van Mai of Mai Chau district, Hoa Binh province.

Environmental Management Plan (EMP) 14

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

- Section 2: From G26 to tower No 59 of 35 kV power line supply for Ban Uon 110 kV substation (under RE 2 WB loan). This section is 4,031 m long.

From G26, the power line will turn left and go along inter commune road to reach to construction site of Trung Son HPP. Distance of the power line to this inter commune road is ranging from 100 m – 300 m. Topography of this section is quite complex with high hills and deep creeks. Main land use pattern is bamboo Luong forest mixed with dense shrubs. From G37, the power line will connect with 35 kV power line of RE 2 project in Quan Hoa district of Thanh Hoa province. The power line will overpass land of Van Mai commune of Mai Chau district (Hoa Binh province) and Phu Thanh, Trung Son communes of Quan Hoa district (Thanh Hoa province).

1.3. Supplement of Materials and Equipment for the Subproject

Sand, rocks, gravels, cements etc.... are supplied by local suppliers.

Other materials will be provided from warehouse of PMU at Moc Chau and Co Luong communes.

1.4. Transportation of Construction Materials and Equipment

Long-way transportation

Cars will be used for transportation of materials, equipment from ware house of PMU to subproject’s construction sites as well as for transportation within construction sites. Concrete centrifugal towers will be purchased from Hoa Binh province will be separated according to type of towers and provided to each site as required. Loading and unloading materials and equipment will be done manually or by cranes. Local suppliers will directly transport materials to gathering points along the power line.

Transportation within the construction sites

National road, provincial road, inter-district and inter commune roads will be used for transportation of materials and equipment among the construction sites. An average transportation is 15 km.

Short-way transportation

From gathering points, materials and equipment are transported manually or half-manually to construction sites. An average distance for short way transportation is 300 m.

Environmental Management Plan (EMP) 15

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

1.5. Number of Workers and Workers Camps

Mai Chau 110 kV substation and connection line: Warehouse, camp are proposed bo be located in reserve area for the second transformer in the substation area. These structures will be build by assembling steel structures to easily dismount in later phase. Foundations of these warehouse and camp will be build by bricks. Colums, beams will be made by wood or steel. Roof will be made by corrugated iron sheets (or cement sheets). Walls will be made by plywoods. Ground will be montared by cement to ensure cleaness, hygenity.

Camp will consist of living area, office area... Number of workers for construction of the substation and 68 m connection line is as bellows:

▫ Direct worker : 60 people

▫ In-direct worker : 07 people

▫ Site managers : 05 people

35 kV power line: There will be two construction team. Each team will consist of 40 people. These workers will hire houses of local people for their camps.

1.6. Subproject Schedule

Some of main milestones of Mai Chau 110 kV substation is:

- Preparation of technical design and approval : 01/2011 - 11/2011

- Preparation of Request for Proposal for Bidding : 9/2012 - 10/2012

- Ground breaking : 12/2012

- Completion and commissioning : 3rd quarter 2013

Table 1.6. Estimated Schedule for the 35 kV power line

No Work Days after commencement

20 40 60 80 100 120 140 160 180

1 Preparation of construction site

2 Construction of foundations

3 Tower erections

Environmental Management Plan (EMP) 16

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

4 Cable pulling

5 Commissioning

1.7. Total of Subproject Investment

Table 1.7. Total of Subproject Investment

Unit: VND

Item Substation and connection line

35 kV power line Total

1. Construction cost 16,107,900,270 9,914,755,000 26,022,655,270

2. Equipment cost 21,841,810,937 375,367,000 22,217,177,937

3. Construction investment consulting cost

3,207,180,883 761,720,000 3,968,900,883

4. Other cost 2,008,482,845 122,257,000 2,130,739,845

5. Contingency 3,453,229,995 1,136,115,000 4,589,344,995

Grand total 46,618,604,930

12,310,214,000

58,928,818,930

Environmental Management Plan (EMP) 17

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

1.8. Some Pictures of the Subproject Site

Location of Mai Chau 110 kV substation

The substation is proposed to be build in rice, dry crop field The nearest house is about 200 m far from

the subsation location

There is an access road to the substation area. This road leads to Tong Dau primary school

Tong Dau primary school is in the right handside of the road

This road will be widened to create an access road to the Mai Chau substation.Section from G3- G4 (in Mai Chau township)

The power line will overpass field for rice and dry crop cultivation of Mai Chau township

Environmental Management Plan (EMP) 18

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Small road turning from national road No 15 to near section G3- G4.

Residential area of Mai Chau township us about 100 – 150 m far from the power line

Section from G7- G8 (Lac village - Chieng Chau commune)

The power line will overpass rice field far from residential area.

There is a small stream near rice field. This stream is about 100 m far from the foundations of the power line.

At this section, the power line will overpass inter commune road

Environmental Management Plan (EMP) 19

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Section from G15- G16 (Van Mai commune)

The power line will overpass rice field The power line will in the right hand side and along national road No 15 and is about 50 m far from this road.

Section from G 18 – G19 (Khoe village, Van Mai commune)

The power line will overpass rice field, small stream

The power line will overpass inter commune road, bridges. There are houses scattered in the subproject area (about 50 m- 70 m far from the power line)

Section G21 – G22 (Van Mai commune)

The power line will overpass rice field The power line will overpass inter commune road

Environmental Management Plan (EMP) 20

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

The power line will go near primary school, administrative house of Van Mai commune (about 70 m far)

The power line is about 70 m far from residential area.

Section G25 – G26 (Van Mai commune)

The power line will overpass Xia stream (6 m wide)

A chain bridge above Xia stream (near the power line position).

Section from G26 to end point

The power line will overpass bamboo Luong planted forest of the local people.

Environmental Management Plan (EMP) 21

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

2. POLICY AND REGULATION FRAMEWOR

2.1. Regulations of Vietnamese Government

The following laws and regulations in Vietnam are applied for the subproject:

Environment Protection Law 52/2005/QH11 passed by the National Assembly dated on 29/11/2005 regulating responsibilities of individuals and organizations regarding environmental protection.

Law on Cultural Heritage No. 28/2001/QH10.

Decree no. 29/2011/NÐ-CP dated 18 April 2011 regarding regulations on strategic environmental assessment, environmental impacts assessment and environmental protection commitments.

Circular no. 26/2011/TT-BTNMT dated 18 July 2011 detailing some articles of Decree no. 29/2011/ND-CP dated 18 April 2011 regarding regulations on strategic environmental assessment, environmental impacts assessment and environmental protection commitments.

Decree 106/2005/ND-CP dated 17th August 2005 on detailed regulations and guidance on implementation of some Articles of the Law on Electricity related to safe protection of high voltage networks.

Decree 81/2009/ND-CP dated 12th October 2009 on revision and addition of some Articles of Decree 106/2005/ND-CP dated 17th August 2005 on detailed regulations and guidance on implementation of some Articles of the Law on Electricity related to safe protection of high voltage networks.

Circular no. 12/2011/TT-BTNMT dated 14 April 2011 regarding the management of hazardous wastes.

National Technical Regulations: QCVN01:2009/BYT - National technical regulations on quality of drinking water; QCVN02:2009/BYT - National technical regulations on quality of domestic water; QCVN08:2008/BTNMT - National technical regulations on quality of surface water; QCVN09:2008/BTNMT - National technical regulations on quality of groundwater; QCVN05:2009/BTNMT - Air quality – Standards for ambient air quality; QCVN06:2009/BTNMT - Air quality – Maximum allowable concentration of hazardous substances in the ambient air.

EVN Guidance no. 2623/CV-EVN – KHCN&MT, dated 28 May 2007 regarding the management and pollution prevention and exposure to PCBs.

Environmental Management Plan (EMP) 22

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

2.2. The World Bank Safeguard policies

The environmental screening according to criteria described in the EG for subproject has been carried out and the result shows that the WB policies on Environmental Assessment (OP 4.01) and Involuntary Resettlement (OP 4.12) are triggered for this subproject. The subproject has also to comply with the Bank’s requirement on Public Consultation and Information Disclosure Policy. The implementation of policy on Involuntary Resettlement (OP 4.12) is addressed in a separate safeguard document.

3. ENVIRONMENTAL SCREENING3.1. Screening for Eligibility of Subproject Siting

Subproject name: 110 kV Mai Chau substation and 35 kV power line supply for Trung Son HPP

Province: Hoa Binh, Thanh Hoa

District: Mai Chau (Hoa Binh province); Quan Hoa (Thanh Hoa province).

Commune: Tong Dau, Mai Chau township, Chieng Chau, Mai Ha, Van Mai commune (Mai Chau- Hoa Binh) and Phu Thanh commune (Quan Hoa, Thanh Hoa).

Table 3.1. Environmental Screening for Subproject Eligibility

Screening Question Construction Operation

Yes No Yes No

1. Subproject's sitting:

Is the Subproject site adjacent to or within any of the following environmental sensitive areas?

Cultural heritage site X X

Protected areas such as National Parks, Nature Reserves, Bio-conservation areas, bird yards, mangrove forest etc.

X X

Wetlands X X

Forests X1 X

Estuaries X X

Buffer zone of Protected areas X X

1 Planted bamboo Luong forest

Environmental Management Plan (EMP) 23

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Screening Question Construction Operation

Rivers and reservoirs X X

Canals and irrigation system X X

Agricultural land X X

2. Potential environmental impacts

Will the Subproject cause:

Encroachment on historical/cultural areas X X

Encroachment on critical ecosystem (e.g. sensitive or protected area, national park, nature reserve etc....)

X X

Disfiguration of landscape and increase waste generation

X X

Removal of vegetation cover or cut down of trees resulted from clearance at the sub-station and along ROW?

X X

Change of surface water quality or water flows X X

Increase water turbidity due to run- off and erosion

X X

Waste water from camping sites is directly discharged to the surface water resources or not?

X X

Construction waste is directly discharged to the surface water or not?

X X

Increase the dust level? X X

Increase noise and/or vibration? X X

Permanent land acquisition X X

Temporary land acquisition X X

Resettlement of households? If yes, how many households?

X X

Would the resettlement site is environmentally and/or culturally sensitive

X X

Environmental Management Plan (EMP) 24

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Screening Question Construction Operation

Is there any risk of disease dissemination from construction workers to the local people (and vice versa)?

X X

Is there any potential for conflict between construction workers and local people (and vice versa)?

X X

Are explosive and hazardous chemicals used within the Subproject?

X X

In the past, there was any accident incurred due to landmines or explosive materials remaining from the war?

X X

Will Subproject's construction cause disturbance to the transportation in the Subproject's site?

X X

Subproject's construction will cause any damage to the existing local roads, bridges or other rural infrastructures?

X X

Will soil excavation during Subproject's construction cause soil erosion?

X X

Will Subproject need to open new access roads? X2 X

Will Subproject cause fragmentation of habitat of flora and fauna?

X X

Will Subproject cause impact on air quality? X X

Will Subproject cause accident risks for workers and community during construction phase?

X X

Will Subproject generate hazardous wastes including PCBs from the replacement of transformers?

X X

Will Subproject cause risk to safety and human health (electric and magnetic fields, electric shock etc.)?

X X

2 Access road to the substation. Beside this road there will not be any access road need to create for ROW maintenance

Environmental Management Plan (EMP) 25

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Conclusion:

Since implementation of the subproject would mainly cause land acquisition, increased dust generation, air pollution, and domestic waste production during the construction phase. However, these impacts are not significant, temporary, and localized, and can be mitigated available mitigation measures. During the operational phase the main impacts would be visual, due to the alteration of the previously existing landscape, and potentially on the avifauna, who is at risk of collision and electrocution. However, as the TL follows exiting infrastructure and the height of pylons and wires is moderate; these impacts are anticipated to be low. Therefore, the subproject is assessed as B environmental category according to the World Bank’s operational policy OP4.01 on environmental assessment, requiring an ESIA and an EMP as analytical and mitigation instruments.

Environmental Management Plan (EMP) 26

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

3.2. Potential Impacts

Table 3.2. Potential impact

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

Pre-construction phase

1 Permanent and temporary land acquisition

Medium Short

Long

Total permanent land acquisition of the Subproject is as follows:

- Mai Chau substation: 8,336.0 m2;

- The land acquired for pole foundations of the power line is 169.0 m2.

- Area of land within ROWs is 115,482 m2. This land is not acquired but trees higher than 4 m can not planted.

Total temporary land acquisition is 27,728 m2, of which rice field land is 163.083 m2; land for dry crops is 4,806 m2.

Medium and mitigable

2 Impact on Subproject affected household

Medium Long term - Total number of HHs affected by the Subproject is 306 HHs;

- Affected types: land loss for foundation, substation; having house within ROWs; loss of trees and crops, rice; trees will be damaged during cable pulling.

Medium

3 Loss of vegetation due to land clearance for the substation

Medium Long - In Hoa Binh province, the substation and power line are located and overpassed mainly rice fields. In Thanh Hoa province, the power line will overpass area planted by bamboo Luong forest. Number of Luong trees will need to be cut is 2.504. Some other trees will also need to be cut for land acquisition, they are: 24 fruit trees, 25 eucalyptus trees, etc.

Medium

4 Health risk due to None None - The Subproject would not use chemicals or explosives; None

Environmental Management Plan (EMP) 27

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

explosives, chemical hazard

- Subproject sites were cleared for landmine after war time and used for agriculture for a long time.

5 Impact on historical and cultural properties

None None - There are no historical and cultural resources near and inside the Subproject area

None

Construction phase

6 Impact in Tong Dau primary school

Medium Short - Tong Dau primary school is about 150 m far from the proposed substation. Therefore, the school might be affected by noise, dust, vibration during construction time. However, these impacts will last only in a short period of time (about 3 months, when ground leveling and civil work are occurred). These impacts can be mitigated by application of mitigation measures as specified in Chapter 4.

- An access road to the substation is created by widening an inter commune road of Tong Dau commune. This inter commune road is also passing Tong Dau primary school. So transportation of pupils and teachers might be affected during construction time. This impact will mostly occur during ground leveling, road construction, civil work for substation construction. When the access road is completed, subproject’s vehicles will use only the new road. So impact on local traffic will not be considerably affected.

Medium and Mitigable

7 Surface water contamination.

Medium Short - Ground leveling, construction of foundation, substation and substation’s access road might washout soil, rock to the surface water system of region;

Medium and Mitigable

Environmental Management Plan (EMP) 28

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

- Mai Chau 110 kV substation is about 50 m far from a small stream. This stream is going along national road No15. This is the only one surface water source near the substation.

- The 35 kV power line will 2 times overpass Xia stream and one time overpass other small stream in Chieng Chau commune. Width of these steams at the over passing point is from 4-7 m. Beside these, the power line will not overpass other surface water such as river, stream, and reservoir.

- Construction of foundations near the streams might cause risk on water contamination due to debris, construction materials washed out to the water bodies.

- The Subproject area is quite flat; therefore, the risks of erosion, soil and construction materials runoff are not high.

- Excavation is planned to do in dry season. Excess soil will be reused to fill in the poles’ foundations. Thus there will be no soil, rock left after the Subproject implementation.

- No tower will be constructed in the above mentioned streams.

- Thus the impact on surface water pollution in the Subproject area is medium and can be mitigated.

8 Noise and vibration Medium Short - Noise and vibration are caused by: equipment, material transportation, Subproject's vehicles, pole's erection and cable's pulling, generators (if there are any);

Medium and mitigable

Environmental Management Plan (EMP) 29

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

- About 100 m far from the substation is Tong Dau primary school. Few houses are about 200 m far from the substation location. These are the nearest areas with human living in the substation location. The nearest residential area of the substation is center of Chieng Chau commune (2 km far from the substation).

- The 35 kV power line will mainly overpass rice fields, bamboo Luong forest. Sections of the power line going near residential area is G3-G4 (Mai Chau township), G21-G22 (Van Mai commune). These residential areas are about 70 m far from the power line. Main part of the power line are far from residential areas so construction activities of the subproject will not impact to normal life of local people.

- Construction materials will be supplied by local supplier within medium distance to construction sites.

- Equipment, cables, materials transported from Ha Noi and from Mai Chau district to the sites through national road 15 and provincial roads system. After that these materials will be transported manually or half-manually to construction sites.

- Due to the above reasons, the noise and vibration impact caused by the Subproject is considered as medium, happening in a short period of time and can be mitigated.

9 Soil erosion Small Short - The topography of the substation area and the power line is quite flat. Vegetation cover is quite good. From G26 to the end point (about 4,031

Mitigable

Environmental Management Plan (EMP) 30

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

m), the power line will overpass hills with high slopes. However, in this area is bamboo Luong forest. Luong trees are very well grown. Vegetation cover is quite thick so risk of soil erosion is low.

- Excavation, backfill and ground leveling are prioritized to be done in dry season;

- Regarding soil erosion, the impact is assessed as small according to small scale of the sub-station site, short construction time. Furthermore, these impacts can be reduced to even smaller when implementing mitigation measures.

10 Air pollution Medium Short -Dust generated from soil excavation, ground leveling especially during dry seasons. The subjects to be affected by dust are people living, working near roads used for transportation of the constriction materials such as national, provincial, district, inter commune roads.

- The Subproject site is away from residential and urban areas therefore air pollution (dust) would not affect much on people living in the Subproject area; The most affected area by air pollution will be substation location, center of Chieng Chau commune, center of Van Mai commune. These areas will be sprayed by water during dry and strong wind times.

- There are 3 residential areas about 70 m far from the Subproject sites. Construction activities at these sites are just construction of foundations. Size of the foundations is 2 m x 2.3 m x 2 m (depth) so impact can be

Medium and Mitigable

Environmental Management Plan (EMP) 31

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

assessed as medium and can be mitigated as described in Table 4.1. Other residential areas are far from the subproject sites.

11 Ecological impact Small Short - Proposed substation is located in very intensively used by human activities.

- The main land use pattern in the substation area and ROWs are rice fields and dry crops. There are 2.504 km from 19.427 km of the power line overpassing bamboo Luong forest. This forest is planted and periodically exploited for commercial purpose.

- Except rice field, Luong forest, there are few other trees, fruit trees, eucalyptus are impacted. These trees mainly have economic but not ecological value.

- There is also no special impact caused by Subproject on fauna since the Subproject sites are mainly rice fields, planted Luong forests, gardens, land along roads. These are very common patterns in the area. Beside these, there is no special habitat observed.

Small and mitigable

12 Traffic disturbance including water-way transportation

Small Short - Transportation of materials and equipment will disturb the normal traffic in the areas during short period of time.

- The substation is located in an open area; the transportation of construction materials is generally easy due to relatively developed traffic system in the subproject area.

- The power line will 4 times overpassing roads having width from 5- 10 m; 21 times overpassing roads having width less than 5 m. When

Medium and Mitigable

Environmental Management Plan (EMP) 32

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

pulling wires across these roads, scaffolds will be constructed to enable normal transportation on this road. These roads are quite small with low density of transportation so traffic in these areas will not be seriously affected.

13 Degradation of the existing rural roads, rice fields and path at edges of rice fields.

Medium Short - Transportation of construction materials with high frequency may cause damage to the inter-commune roads;

- Currently local authorities and people supervise the management of rural road quite well. Large load transportations are not allowed to run through roads whose quality is not good enough. This is also an issue that the contractors have to comply and thoroughly calculate transporting options to avoid rural road degradation.

- Manually or half-manually transportation material to construction sites might also cause damages to the rice fields, path at edges of the rice fields.

- The road section that most potentially be damaged by subproject activities is the inter commune road that will be widened for an access road of the Mai Chau substation. Other roads used by subproject’s vehicles are potentially less affected.

Medium and Mitigable

14 Solid waste generated from soil excavation

Minor Short Excessive soil and materials will be used for poles’ foundations filling. The volume of excessive soil is often not enough for foundations, sometimes it has to purchase and transport from other places. Therefore it could be said that impact is in minor level.

Minor

Environmental Management Plan (EMP) 33

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

15 Environmental impacts caused by construction workers

Medium Short - The subproject implementation is expected to be completed in 9 months, from that construction period will last for 5-6 months. High construction time is last from 5 to 6 months. The remaining time is mainly reserved for the installation of equipments;

- It is expected to be 72 workers involving with construction of the substation. These worker will create their camps in substation's area, where is reserved for the second phase (installation of another transformer). Number of workers involving with construction of the power line is about 80; they will be divided into two groups and will stay in houses rent from local people. Workers will be chosen from the skilled ones in the region so in this camp number of worker will be also about 30-40 workers/each site.

- In the camp for substation, other ancillary’s constructions such as bathrooms, toilets will be built for workers to use.

- Camp sites will dispose domestic solid wastes that can cause environmental pollution. However these wastes are mainly package materials, leftover food... with small amount.

Medium and mitigable

16 Conflict between construction worker and local people

Small Short - Conflict might cause because of: Difference in incomes, cultures, behaviors; However worker are come from the region so these differences are not considerable.

- The subproject will be implemented in well developed area with high population density; the number of workers is not considerable in

Minor

Environmental Management Plan (EMP) 34

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

comparison with local people.

- Stay duration of workers in each site is short (6-9 months), so the impact therefore considered as minor.

17 Health and safety Medium Short - Accidents might happen during construction if the safety issues are not well considered.

- Accidents might happen to the workers or local people living around the subproject area.

Medium and mitigable

18 Flooding of an area surrounding the substation

Small Long - An area used for substation is land used for rice field. This area will be leveled to 0.3 m higher than the existing level.

- By leveling up the ground for the substation, rice field in surrounding area might be flooded;

- Water level in rice field is controllable by farmers with support of irrigation system. In case water is increased, farmer will regulate water level accordingly. Flooding will not occur.

- Experiences from other similar projects show that this impact was not happened. However subproject owner will work with farmers during construction phase and operation phase to check the problem. In case flooding would occur, Project owner will design proper drainage system to keep water regime as closed as the existing conditions.

The impact is assessed as small and can be mitigated.

Small

19 Interruption of utility Small Short - Installation of power line requires power interruption to some areas. Small

Environmental Management Plan (EMP) 35

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

services -Due to power interruption some services which' operation depend on power supply would be interrupted.

Operation phase

20 Supplying electricity for construction of Trung Son HPP

Large Long - Subproject is primary aimed to supply for construction of Trung Son HPP. In later phase, the power line and substation will supply electricity for resettlement sites of trung Son HPP.

- The subproject actively supports for development of the area; handcraft and traditional work and services can be developed.

- Increase the quality of life for local residents due to sufficiency and stability of power supply.

Positive

21 Impact on Tong Dau primary school.

None None - During operation phase, the substation will not cause noise, dust, vibration ... so Mai Chau substation will not cause impact on activities of the school.

- The substation protected by walls, guards so pupils can not access, therefore accidents related to electricity could not occurred to pupils as well as to local people.

No impact

22 Health and safety Minor Long - There are no habitants in the substation area. The number of employments in the substation is small (about 10-15 people divided into shifts). The safety regulations in the substation are guaranteed so there will be no impact on health and safety of workers;

- If safety regulations are not complied, it might affect on heath

Minor and mitigable

Environmental Management Plan (EMP) 36

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

workers, however this case is extremely rare.

- According to Vietnam Government regulations, houses are allowed to be existed in the ROW of 110 kV and 220 kV power line. However these houses are required to meet certain requirements as described in Table 4.1 of the EMP.

- 35 kV power line will not cause impact to people living within and near ROW.

23 Electromagnetic field None None - The power line is designed according to existing technical regulations; electromagnetic field will not exceed permissible value (5kV/m). 5 kV/m is safe electromagnetic field level for human health.

- When the power line is designed according to technical standards, the electromagnetic field in the ROW is always lower than 5 kV/m for power line with voltage under 220 kV.

- At this electromagnetic field level, there will not be effect of electromagnetic field on human health.

None

24 Oil, hazardous waste contamination

Minor Long - No PCBs containing oil will be used during the subproject’s construction and operation;

- During the subproject operation, some chemical will be used such as accumulators, batteries, dielectric oil, lubricants etc. These equipment and chemicals will be registered and managed as regulated by Circular 12/2011/TT-BTNMT dated 14/4/2011 on Management of hazardous wastes. These practices are applied for all other substations of EVN and

Minor and mitigable

Environmental Management Plan (EMP) 37

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Magnitude Duration Description of the impacts Evaluation of impacts

will apply for Mai Chau substation as well.

Environmental Management Plan (EMP) 38

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

4. MITIGATION MEASURESTable 4.1. Mitigation measures

The subproject is very similar to the subprojects of Distribuion Efficiency Project (DEP), which is also supported by loan from the WB. The environmental code of practices (ECOPs) was developed for DEP. During preparation of this EMP, consultant has reffered to these ECOPs and recommended to apply for the subproject.

Table 4.1. Mitigation Measures Applied for Impact

No Impact Mitigation measures applied for the impact Responsible for Implementation

General mitigation measures according to ECOP in Construction phase

1 Impacts to vegetation cover and ecological resources

The Contractor shall prepare a Clearance, Revegetation and Restoration Management Plan for prior approval by the Construction Engineer, following relevant regulations. The Clearance Plan shall be approved by Construction Supervision Consultant and followed strictly by contractor. Areas to be cleared should be minimized as much as possible.

Site clearance in a forested area is subject to permission from Department of Agriculture and Rural Development.

The Contractor shall remove topsoil from all areas where topsoil will be impacted on by rehabilitation activities, including temporary activities such as storage and stockpiling, etc; the stripped topsoil shall be stockpiled in areas agreed with the Construction Supervision Consultant for later use in re-vegetation and shall be adequately protected.

The application of chemicals for vegetation clearing is not permitted. When needed, erect temporary protective fencing to efficiently protect the preserved trees

before commencement of any works within the site. No area of potential importance as an ecological resource should be disturbed unless there is

prior authorization from CSC, who should consult with PMUs, and the relevant local authorities. This could include areas of breeding or feeding of birds or animals, fish spawning areas, or any area that is protected as a green space.

Contractor

Environmental Management Plan (EMP) 39

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

2. Impacts of dust The Contractor is responsible for compliance with relevant Vietnamese legislation with respect to ambient air quality.

The Contractor shall implement dust suppression measures (e.g. water sprays vehicles, covering of material stockpiles, etc.) as required. Spray water in construction sites for the substation and its access road during dry and windy weather. Construction vehicles shall comply with speed limits and haul distances shall be minimized.

Material loads shall be suitably covered and secured during transportation to prevent the scattering of soil, sand, materials or dust.

The Contractor shall be responsible for any clean-up resulting from the failure by his employees or suppliers to property secure transported materials.

Exposed soil and material stockpiles shall be protected against wind erosion and the location of stockpiles shall take into consideration the prevailing wind directions and locations of sensitive receptors.

Dust masks should be used where dust levels are excessive.

Contractor

3 Air pollution All vehicles must comply with Vietnamese regulations controlling allowable emission limits of exhaust gases.

Vehicles in Vietnam must undergo a regular emissions check and get certified named: “Certificate of conformity from inspection of quality, technical safety and environmental protection” following Decision No. 35/2005/QD-BGTVT.

There should be no burning of waste or construction materials or cleared vegetation on site. Cement processing plants should be far from residential areas.

Contractor

4 Noise and vibration The contractor is responsible for compliance with the relevant Vietnamese legislation with respect to noise and vibration.

All vehicles must have appropriate “Certificate of conformity from inspection of quality, technical safety and environmental protection” following Decision No. 35/2005/QD-BGTVT; to avoid exceeding noise emission from poorly maintained machines.

When needed, measures to reduce noise to acceptable levels must be implemented and could

Contractor

Environmental Management Plan (EMP) 40

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

include silencers, mufflers, acoustically dampened panels or placement of noisy machines in acoustically protected areas.

Avoiding or minimizing transportation though or material processing near community areas.

5 Water pollution The Contractor must be responsible for compliance with the relevant Vietnamese legislation relevant to wastewater discharges into watercourses.

Portable or constructed hygienic toilets must be provided on site for construction workers. Wastewater from toilets as well as kitchens, showers, sinks, etc. shall be discharged into a conservancy tank for removal from the site or discharged into municipal sewerage systems; there should be no direct discharges to any water body.

Wastewater over standards set by relevant Vietnam technical standards/regulations must be collected in a conservancy tank and removed from site by licensed waste collectors.

Using techniques as berms, silt barriers, settlement ponds, drainage channels, minimization of the time soil is left open and unprotected, immediate landscaping an seeding after completion of works, during construction to limit the exposure of disturbed sediments to moving water.

Before construction, all necessary wastewater disposal permits/licenses and/or wastewater disposal contract have been obtained.

At completion of construction works, wastewater collection tanks and septic tanks shall be safely disposed or effectively sealed off.

Contractor

6 Solid waste Before construction, a solid waste control procedure (storage, provision of bins, site clean-up schedule, bin clean-out schedule, etc.) must be prepared by Contractors and it must be carefully followed during construction activities.

Before construction, all necessary waste disposal permits or licenses must be obtained or hire local environmental services (such as environmental service team of Mai Chau district. which is under management of Mai Chau environmental management division of Mai Chau district) for collection of house hould waste from camp sites and construction waste (if there is any).

Measures shall be taken to reduce the potential for litter and negligent behavior with regard

Contractor

Environmental Management Plan (EMP) 41

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

to the disposal of all refuse. At all places of work, the Contractor shall provide litter bins, containers and refuse collection facilities.

Solid waste may be temporarily stored on site in a designated area approved by the Construction Supervision Consultant and relevant local authorities prior to collection and disposal through a licensed waste collector, such as environmental service team of Mai Chau district which is under management of Mai Chau environmental management division of Mai Chau district.

Waste storage containers shall be covered, tip-proof, weatherproof and scavenger proof. No burning, on-site burying or dumping of solid waste shall occur. Recyclable materials such as wooden plates for trench works, steel, scaffolding material, site

holding, packaging material, etc shall be collected and separated on-site from other waste sources for reuse, for use as fill, or for sale.

If not removed off site, solid waste or construction debris shall be disposed of only at sites identified and approved by the Construction Supervision Consultant and included in the site specific measures. Under no circumstances shall the contractor dispose of any material in environmentally sensitive areas, such as in areas of natural habitat or in or close to watercourses.

7 Chemicals or hazardous wastes

Chemical waste of any kind shall be disposed of at an approved appropriate landfill site and in accordance with local legislative requirements. The Contractor shall obtain needed disposal certificates.

The removal of asbestos-containing materials or other toxic substances shall be performed and disposed of by specially trained and certified workers.

Used oil and grease shall be removed from site and sold to an approved used oil recycling company.

Used oil, lubricants, cleaning materials, etc. from the maintenance of vehicles and machinery shall be collected in holding tanks and removed from site by a specialized oil recycling company for disposal at an approved hazardous waste site.

Used oil or oil-contaminated materials that could potentially contain PCBs shall follow procedures provided in the EMF to avoid any leakage or affecting workers. The local

Contractor

Environmental Management Plan (EMP) 42

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

DONRE must be contacted for further guidance. Unused or rejected tar or bituminous products shall be returned to the supplier’s production

plant. Relevant agencies shall be promptly informed of any accidental spill or incident. Store chemicals appropriately and with appropriate labeling. Appropriate communication and training programs should be put in place to prepare workers

to recognize and respond to workplace chemical hazards. Prepare and initiate a remedial action following any spill or incident. In this case, the

contractor shall provide a report explaining the reasons for the spill or incident, remedial action taken, consequences/damage from the spill, and proposed corrective actions.

8 Traffic management Before construction, carry out consultations with local government and community and with traffic police.

Significant increases in number of vehicle trips must be covered in a construction plan previously approved. Routing, especially of heavy vehicles, needs to take into account sensitive sites such as schools, hospitals, and markets.

Installation of lighting at night must be done if this is necessary to ensure safe traffic circulation.

Place signs around the construction areas to facilitate traffic movement, provide directions to various components of the works, and provide safety advice and warning.

Employing safe traffic control measures, including road/rivers/canal signs and flag persons to warn of dangerous conditions.

Avoid material transportation for construction during rush hour. Passageways for pedestrians and vehicles within and outside construction areas should be

segregated and provide for easy, safe, and appropriate access. Signpost shall be installed appropriately in both water-ways and roads where necessary.

Contractor

Environmental Management Plan (EMP) 43

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

9 Interruption to utilitiy services

Planned and unplanned interruptions to water, gas, power, internet services: the Contractor must undertake prior consultation and contingency planning with local authorities about the consequences of a particular service failure or disconnection.

Coordinate with relevant utility providers to establish appropriate construction schedules. Provide information to affected households on working schedules as well as planned

disruptions (at least 5 days in advance). Interruptions of water supply to agricultural areas must also be avoided. The contractor should ensure alternative water supply to affected residents in the event of

disruptions lasting more than one day. Any damages to existing utility systems of cable shall be reported to authorities and repaired.

Contractor

10 Restoration of affected areas

Cleared areas such as borrow pits which are no longer in use, disposal areas, site facilities, workers’ camps, stockpiles areas, working platforms and any areas temporarily occupied during construction of the project works shall be restored using landscaping, adequate drainage and revegetation.

Start revegetation at the earliest opportunity. Appropriate local native species of vegetation shall be selected for the planting and restoration of the natural landforms.

Spoil heaps and excavated slopes shall be re-profiled to stable batters, and grassed to prevent erosion.

All affected areas shall be landscaped and any necessary remedial works shall be undertaken without delay, including green-spacing, roads, bridges and other existing works.

Trees shall be planted at exposed land and on slopes to prevent or reduce land collapse and keep stability of slopes.

Soil contaminated with chemicals or hazardous substances shall be removed and transported and buried in waste disposal areas.

Restore all damaged road and bridges caused by project activities.

Contractor

11 Worker and public Contractor shall comply with all Vietnamese regulations regarding worker safety. Contractor

Environmental Management Plan (EMP) 44

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

Safety Prepare and implement action plan to cope with risk and emergency. Preparation of emergency aid service at construction site. Training workers on occupational safety regulations. If blasting is to be used, additional mitigation measures and safety precautions must be

outlined in the EMP. Ensure that ear pieces are provided to and used by workers who must use noisy machines

such as piling, explosion, mixing, etc., for noise control and workers protection. During demolition of existing infrastructure, workers and the general public must be

protected from falling debris by measures such as chutes, traffic control, and use of restricted access zones.

Install fences, barriers, dangerous warning/prohibition site around the construction area which showing potential danger to public people (such as unfinished power pole foundation, high risk electrical shock areas, etc.).

The contractor shall provide safety measures as installation of fences, barriers warning signs, lighting system against traffic accidents as well as other risk to people and sensitive areas.

If previous assessments indicate there could be unexploded ordnance (UXO), clearance must be done by a relevant army unit.

12 Communication with local communities about Subproject environmental issues

Maintain open communications with the local government and concerned communities; the contractor shall coordinate with local authorities (leaders of local wards or communes, leader of villages) for agreed schedules of construction activities at areas nearby sensitive places or at sensitive times (e.g., religious festival days).

Copies in Vietnamese of relevant parts of these ECOPS should contain in contractor documents and of other relevant environmental safeguard documents shall be made available to local communities and to workers at the site.

Reduced playground space, loss of playing fields and car parking: The loss of amenities during the construction process is often an unavoidable source of inconvenience to users in sensitive areas. However, early consultation with those affected, provides the opportunity to investigate and implement alternatives. In all cases damages shall be compensated.

Contractor

Environmental Management Plan (EMP) 45

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

Disseminate project information to affected parties (for example local authority, enterprises and affected households, etc) through community meetings before construction commencement.

Provide a community relations contact from whom interested parties can receive information on site activities, project status and project implementation results.

Provide all information, especially technical findings, in a language that is understandable to the general public and in a form of useful to interested citizens and elected officials through the preparation of fact sheets and news release, when major findings become available during project phase.

Monitor community concerns and information requirements as the project progresses; Respond to telephone inquiries and written correspondence in a timely and accurate manner. Inform local residents about construction and work schedules, interruption of services,

traffic detour routes and provisional bus routes, blasting and demolition, as appropriate. Provide technical documents and drawings to PC’s community, especially a sketch of the

construction area and the EMP of the construction site. Notification boards shall be erected at all construction sites providing information about the

project, as well as contact information about the site managers, environmental staff, health and safety staff, telephone numbers and other contact information so that any affected people can have the channel to voice their concerns and suggestions.

13 Workforce, camp and site management

Workers‘camps will be located at least 100 m away from schools and health care centres and not be located on steep slopes. The workforce shall be provided with safe, suitable and comfortable accommodations and safe portable water. They have to be maintained in clean and sanitary conditions.

Site offices, worker camps, mixing stations, and workshops shall be located NOT within 100m from any water courses, 500 meters of existing residential area.

Engineers and workers shall register their temporary residence with the local authority. Contractor should sign committeemen with local authorities on keeping of security and

social safety on subproject’s areas. Allocate officer to be the Contractor‘s Workplace Safety and Environment Officer

Contractor

Environmental Management Plan (EMP) 46

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

responsible for environmental and safety issues including training for workers. Septic tank toilets must be provided at all construction camp areas where there will be

concentration of labor. First aid boxes shall be provided in each construction camp site.

14 Chance finding procedures in case of founding objects with historical or cultural values

See Table 4.2. Contractor in coordination with

Project owner and relevant local authorities

Specific Mitigation Measures Applied for the sub-project in Construction Phase

15 Impact on land acquisition to the local HHs, vegetation covers

Careful site survey for substation location, power line routes, consult with local authorities for optimal selection of Subproject construction sites ;

Disclose detail information on temporarily and permanently acquired land to affected households;

Proper compensation for affected households. It is estimated that compensation cost for land acquisition of substation is 624 millions VND; and power line is 12,851 millions VND

Schedule land acquisition after rice or crop harvesting seasons to avoid harvest losses to people as well as avoid other high activities time in agricultural cultivation.

The subproject owner shall prepare and carry out the compensation plan according to Vietnamese and the WB’ Regulations in accordance with RPF for the DEP Project and RP of the subproject.

Select pole’s foundation locations properly to minimize impacts on land, rice field, or garden losses of local people; Pole locations should be arranged properly in local people’ land so that affected households can still use the remaining part of their land comfortably.

Simple scaffolds will be created when pulling cables overpassing rice fields, gardens to

-Design Consultant;- Sub-project owner coordinates with local authorities

Environmental Management Plan (EMP) 47

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

avoid damages to the rice fields and trees.Specific Measures Applied during Operation Phase

16 ROW protection Comply with Decree 106/2005/ND-CP dated 17/8/2011 on the protection of high-voltage power grid corridor; Decree 81/2009/ND-CP dated 12/10/2009 on safety protection for high voltage power network;

Carry out regular supervision of ROWs protection.

- Southern High Voltage Power Network Company operation)

17 Oil, hazardous chemical contamination

Oil containing PCB is not allowed to use for the subproject; Oil refilling (if required) of transformers shall be done in the Workshop. Ussually, after

certain time of operation (5 year in average) the oil inside the transformer might be degraded in term of lower dielectric quality, high content of moisture so the oil must be retrofilled to phase out moisture and other contaminats. After retrofilling, the oil will be reused.

After use, the transformer will be handled to agency that is lisenced to transport and treat used oil as regulated by Cicular 12/2011/TT-BTNMT dated 14/4/2011 on management of hazardous waste.

Design and construct basin under transformers for spill oil collection and central larger basin for oil collection for whole substation as they were described in the approved Subproject technical design report.

Use oil collectors during maintenance services for unexpected oil spills into environment. Carry out regular check and maintenance the transformers so as any leakage and/or failure

risks can be detected timely; Replace or repair transformer as soon as possible after leakage from transformers detected.

Isolate the leakage and fix the problem to ensure that the leakage does not cause pollution in water sources nearby;

Maintain and regularly check the fire protection devices at the Thoai Son substation; Comply with regulation of Vietnam Government as required by Circular 12/2011/TT-

BTNMT dated 14/4/2011 on management of hazardous waste.

- Southern Hịgh Voltage Power Network CompanyDesigned consultant

Environmental Management Plan (EMP) 48

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Impact Mitigation measures applied for the impact Responsible for Implementation

18 Fire prevention and protection system

Designed system for Fire prevention and protection of the substation was certified and approved by Fire prevention and protection system from authorized agency (PC66) by Document No 78/TD-PCCC (PC66) dated 26/5/2010.

Designed consultantHigh Voltage Power Network Company

Environmental Management Plan (EMP) 49

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

5. EMERGENCY ACTION PLANTable 5.1. Chance finding procedures and Emergency action plan

No. Risk Action Responsibility

1 Artifacts found during excavation works

Contractor shall protect the site and report to the Construction Supervisor/PMUs and local museum/ cultural management authority. Deliver the object found to local museum/ cultural management authority. Determine whether construction can be continued or halted for further investigation

The Directors of the provincial Department of Cultural and Information and local Museum shall be responsible for the subsequent handling of the objects found in accordance with Article 21 of the Decree no. 92/2002 guiding the Implementation of the Law on Cultural Heritage.

Contractor, construction supervisor to coordinate Contractor

Contract

2 Remains found during excavation works

Protect the site and report to local authority

Determine who/where/how to address and propose next actions

Implement the proposed actions

Contractor

All relevant authorities

Those who are assigned to3 There are complaints

from community about environmental problems related to construction

Fix the problem immediately if possible

Take note in log book

Discuss with the Employer/local authority where conflicts occur

Contractor

Contractor, PMUs and local authority

4 Worker accidents Carry out first aid where possible and transfer the victim the nearest hospital as soon as possible and if necessary

Protect the site and place warning site

Prepare incident notes

Worker/people at the site

Environmental Management Plan (EMP) 50

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No. Risk Action Responsibility

5 Unexploded ordinances is found

Protect the site

Report to local authority

Contact the most relevant local army base and ask for help

Contractor

Contractor/local authority

Environmental Management Plan (EMP) 51

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

6. COMMUNITY CONSULTATION AND INFORMATION DISCLOSURE

During subproject preparation stage (2011-2012), the following activities were carried out:

Activity 1: Investigate and discussion with local authorities about the substation location and power line routing.

Activity 2: Site investigation, preparation of Environmental Management Plan for the Subproject

Activity 3: Organizing public consultation. The subproject will overpass 6 communes and town of Mai Chau district (hoa Binh province) and Phu Thanh commune of Quan Hoa district (Thanh Hoa province). Public consultation in 6 communes of Mai Chau district:Subproject Management Unit and Consultants organized 6 consultation meetings at 6 subproject’s communes. Details of the meetings are described in Table 6.1. Project owner and consultant held public consultation for Environmental management plan of 110 kV Xuan Mai substation and 35 kV power line Subproject. The representatives of Subproject Owner and Consulting Company presented to the public on the following main issues:

Subproject description: route of power line, the substation location, the necessity of construction of the above-mentioned Subprojects;

The potential environmental impacts might be caused by the Subproject; Measures to mitigate the impact.

Participants of the meetings are: representatives of affected HHs, representatives of local authorities and representatives of local power company. Table 6.1. Summary of comments at public consultation meetings in Mai Chau district

No Comments received Response of Project owner and consultant

At office of people committee of Chieng Chau commune - 8h30- 12/9/2012Number of participants: 40 people1 - It is required to spray water in intensive construction sites such

as substation and its access road.- This comments will be integrated in Chapter for mitigation measures (Table 4.1. Item 2)

2 - Subproject’s construction work might cause damage to the local existing roads. Contractors are required to repair road if there are some damages during construction, transportation of materials.

- This measure was already described in Table 4.1. Item 10 on Restoration of affected areas

3 - Contractors are required to arrange proper construction schedule to avoid cultivation and harvest activities of local people.

- This measure will be added on Table 4.1. Item 15 on Impact on land

Environmental Management Plan (EMP) 52

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Comments received Response of Project owner and consultant

acquisition to the local HHs, vegetation covers

At office of people committee of Mai Ha commune - 8h30- 13/9/2012Number of participants: 26 people4 - Contractors are required to strictly follow EMP and inform in

advance construction schedule to local people for cooperation and avoid damages to agricultural cultivation of local people.

- Comments are recorded and PMU will cooperate with Contractor to early inform construction schedule.

5 - PMU should early inform local people on compensation plan, land acquired from affected HHs.

-Comments are recorded and PMU will early inform acquired land and compensation plan for affected HHs.

At Cultural house of Mai Hoang Son village – Mai Hich commune. 13h30 - 13/9/2012.Number of participants: 15 people (details of participants are listed in Annex 5).6 - Environmental impacts of the subproject are minor. However

Project owner and Contractors should pay attention on management of worker as described in EMP to avoid impact on normal life of local people.

-Comments are recorded and PMU will pay attention on supervision of implementation of EMP and management of worker as well.

7 - Contractors are required to commit with local authorities on keeping security and social safety in the subproject’s areas.

- This comment will be added in mitigation measure in Table 4.1. Item 13 on Workforce, camp and site management

At office of people committee of Tong Dau commune - 10h30- 12/9/2012Number of participants: 56 people8 - PMU and Contractors are required to strictly follow this EMP

to minimize environmental impact on health of local people-Comments are recorded and PMU will pay attention on supervision of implementation of EMP.

9 - Transportation of materials might cause impact on traffic in the subproject’s site, so PMU and Contractor are required to implement mitigation measures as described in EMP to minimize this impact.

-Comments are recorded and PMU will pay attention on supervision of implementation of EMP.

10 - Common experiences showed that after construction Contractors are not pay attention on implementation of advanced committeemen, so PMU should have measure to require Contractor to implement rehabilitation of affected areas during construction.

-Comments are recorded and PMU will pay attention on supervision of Contractors on implementation of EMP.

At office of people committee of Mai Chau township - 13h30- 12/9/2012Number of participants: 19 people.11 - PMU should pay attention on supervision of Contractor on -Comments are recorded

Environmental Management Plan (EMP) 53

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Comments received Response of Project owner and consultant

cleaning of construction materials when the construction work is completed.

and PMU will pay attention on supervision of Contractors on implementation of EMP.

At office of people committee of Van Mai commune - 8h30- 14/9/2012Number of participants: 70 people.12 - Solid wastes of worker should be collected and treated to ensure

hygenity of subproject’s areas.-Comments are recorded and PMU will pay attention on supervision of Contractors on implementation of EMP in general and on measures applied for solid wastes of worker camp in particular.

13 - Contractors are required to commit with local authorities on keeping security and social safety in the subproject’s areas.

- This comment will be added in mitigation measure in Table 4.1. Item 13 on Workforce, camp and site management

Public consultation in Phu Thanh commune- Quan Hoa district In Phu Thanh commune, number of affceted HHs are limited (6 HHs are directly affected in term of land and properties, other are living far from the subproject’s site so they are likely not affected in term of environmental impacts). Therefore, public consultation are implemented by giving in advace the summary EMP and interveiw for comments of the affected HHs. Summary of comments are given in Table 6.2.

Table 6.2. Summary of comments at public consultation meetings in Phu Thanh commune, Quan Hoa district

No Name of interviewed HHs Comments for EMP1 Luong Xuan Thao - Agree on the given EMP2 Kha Văn Tha - PMU should pay attention on request

Contractors to keep securiry and social safety for people in houses rent by worker.

3 Luong Van Kham - Agree on the given EMP4 Be Xuan Tinh - PMU should inform in advance compensation

paln and construction plan so local people can arrange harvesting of bamboo Luong in proper time.

5 Luong Thi Tho - Agree on the given EMP6 Ha Van Minh - If contractors damages local roads during

construction, they should repair the roads.

Environmental Management Plan (EMP) 54

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

The comments received in Phu Thanh commune are similar to comments received through public consultation meetings in Mai Chau districts. The Project owner and Consultant received comments and integrated them during updating of the EMP report.

Activity 4: Review and edit the EMP according to collected ideas. Continue to receive feedback for affected households.

Activities 5: Disclosure of the EMP (Supposed to disclose in October, 2012)

- The Vietnamese version of EMP report will be disclosure at People’s Committee of Tong Dau commune, at People’s Committee of Mai Chau district and at People’s Committee of Phu Thanh commune, so interested public and organizations can access and monitor EMP compliance

- The English and Vietnamese versions of the EMP will be sent to the Vietnam Development Information Center, 63 Ly Thai To, Hanoi for information disclosure.

- The English version of the EMP will be sent to Infoshop of the WB at Washington to be disclosed.

Environmental Management Plan (EMP) 55

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

7. ENVIRONMENTAL MONITORING PLANTable 7.1. Environmental monitoring plan

No. Environmental Issues

Parameter is to be monitored LocationWhere is the

parameter to be monitored?

MethodHow

Are the parameter to be monitored/ type of

monitoring equipment?

Frequency Responsibility

CONSTRUCTION PHASE1 Surface water

turbidity and soil erosion

1) Visual observation to assess whether the excavation and other construction activities cause any pollution to the surface water as in irrigation system, in rivers where power line is crossing.2) The measures applied by Contractor to avoid the pollution of water;3) Measures applied to strengthen the canal’s shores at locations where the construction of pole foundation is near canal?4) If there is some complaints from local people about the pollution of water source caused by Subproject activity the measurement of water quality parameters should be taken.

Section from G26 to end point (part over passing hills in Van Mai commune (Mai Chau district) and in Phu Thanh (Quan Hoa district).

- By observation - Daily observation will be recorded and Monthly report will be prepared and submitted during whole construction period

- Contractor- PMU (Technical supervisors or so called Technical supervisors of PMU is responsible to carry out )

Environmental Management Plan (EMP) 56

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No. Environmental Issues

Parameter is to be monitored LocationWhere is the

parameter to be monitored?

MethodHow

Are the parameter to be monitored/ type of

monitoring equipment?

Frequency Responsibility

2 Noise level around Subproject’s construction sites and in adjacent areas

1) Assess by observation whether (i) the noise level from Subproject’s construction site is acceptable for surrounding residential areas (ii) The construction machines, or equipment make noise that annoy local people.2) The mitigation measures of noise applied by the Contractor.3) In case of some complaints from local people, Consultant should carry out measurements.

- The residential area nearest to the substation; road along transportation route of the subproject vehicles.

- By observation As above As above

3 Dust 1) Assess by visual observation whether (i) the dust caused by construction is serious; (ii) the measures taken by Contractor to control the dust level2) The mitigation measures applied by the Contractor if dust level increases in the area3) Measurement should be taken if there are some complaints from local peopleRecommended areas with emphasis to be monitored: Subproject construction sites; residential areas near construction site.

- Subproject’s sites along national road no 15, centre of Chieng Chau and Van Mai communes.

- By observation As above As above

Environmental Management Plan (EMP) 57

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No. Environmental Issues

Parameter is to be monitored LocationWhere is the

parameter to be monitored?

MethodHow

Are the parameter to be monitored/ type of

monitoring equipment?

Frequency Responsibility

4 Solid waste and site cleaning after the construction

Assess observe whether:1) Construction residues are clean up after the construction2) The way that Contractor disposes solid wastes from construction site.Special attention should be paid on the time after construction work.

- Construction site for the substation and sites for completed or ongoing construction of foundations

- By observation As above As above

5 Transportation disturbance

Assess, observe:(1) Whether the construction and other Subproject's activities such as pole's erection, cable pulling cause any serious disturbance to the local traffic;(2) Necessary measures taken to avoid the disturbance to local traffic such as: warning signs of construction site, transportation is avoiding heavy traffic hours etc. (see more details in section Mitigation measures).

- Access road to the substation, sites along national road No 15.

- By observation and interview local people.

As above As above

6 Transportation disturbance

Assess, observe:(1) Whether the construction and other Subproject's activities such as pole's erection, cable pulling cause any serious disturbance to the local traffic;(2) Necessary measures taken to avoid the disturbance to local traffic such as: warning signs of construction site, transportation is avoiding heavy traffic hours etc.(see more details in section

- Along national road No 15;- Along inter commune road used for transportation of the materials and equipment

- By observation As above As above

Environmental Management Plan (EMP) 58

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No. Environmental Issues

Parameter is to be monitored LocationWhere is the

parameter to be monitored?

MethodHow

Are the parameter to be monitored/ type of

monitoring equipment?

Frequency Responsibility

Mitigation measures);(3) Contractor did repair roads, paths in rice fields damaged by construction activities?(4) Is there any complaint of the local people on the issue?

7 Sanitation facilities at worker camp

Assess and observe whether:- Camps are keeping clean? Toilets area is keep in hygienic condition or not?- Solid waste container is properly located?- Municipal waste water is collected and properly discharged?- Interview workers and local people living near site that there is any disease dissemination between workers and local people and via versa or not?

- Camp sites in the substation and rent houses of workers constructing the power line

- By observation and interview local people.

As above As above

8 Conflict between worker and local people

Interview authority staffs, workers and local people on:- Whether staying of workers seriously affect life, living habits of local people?- There is any conflict occurred during stay of worker or not? If there is any, how it was resolved? The Contractor and Subproject owner are taken on solving this conflict actively?

- Subproject’s communes

- Interview local people.

As above As above

9 Current situation of safety and

Assess safety level during construction works:

- Construction sites in the substation and

- By observation and interview staffs of

As above As above

Environmental Management Plan (EMP) 59

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No. Environmental Issues

Parameter is to be monitored LocationWhere is the

parameter to be monitored?

MethodHow

Are the parameter to be monitored/ type of

monitoring equipment?

Frequency Responsibility

health protection measures

- The Contractor has provides personnel safety protection to worker or does not?- Regulations, standards on electrical technique and safety to avoid electricity shock, accidents.

along the power line PMU

10 Construction material management

Assess and observe:(1) The management of construction material in the warehouses, stockpiles(2) The management of construction material in the construction site

- Ware houses for construction materials of the subproject.

- By observation As above As above

11 Affect on agriculture activities

Interview the Contractor, local people and assess whether:- The working schedule is properly arranged; avoid harvesting season and the weeks with high agricultural activities.

- Agricultural land near by the subproject sites.

- By observation and interview Contractor, local people.

As above As above

12 Emergency action plan

1) There is a case of founding artifact with cultural, historical, spiritual values during operation or not?2) The Constructor, Subproject owner, and relevant parties are carrying out the procedures as required in the Table 4.1 and Table 4.2 or not?

- Subproject sites - By interview local people, Contractor and staffs of PMU

As above As above

OPERATION PHASE13 Health and

safetyOperation agency should make report on the following issues:- Summary of accidents occurring during power line operation;

- The substation and the power line areas.

- Operating unit collects data

Annually - Northern High Voltage Power Network Company

Environmental Management Plan (EMP) 60

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No. Environmental Issues

Parameter is to be monitored LocationWhere is the

parameter to be monitored?

MethodHow

Are the parameter to be monitored/ type of

monitoring equipment?

Frequency Responsibility

- Situation on provisions of safety protection equipment.

(manages the substation) and Hoa Binh power company (manages the power line).

14 Management of ROW and electric and magnetic field intensity

Operation agency should make report on the following issues:- Situation on implementation of the power line’s ROW protection;- Mitigation measures to prevent ROW violation event (if there is)- The Electromagnetic field intensity inside ROW meet required standard or not?- There is any complain of local people related to ROW and Electromagnetic field or not? If is, the measurement should be made.

- The substation and the power line areas.

- Operating unit collects data

Annually - As above

15 Use and evidence oil pollution and other hazardous chemical at Mai Chau 110 kV substation

Assessment by visual observation:(1) There is leakage of oil, chemicals from electrical equipments to the environment or not?(2) Where are the maintenance and reparation of electrical equipments implanted? Are these activities safe to health and environment?(3) To comply with the regulation on

- The substation area. - Operating unit collects data

Annually Northern High Voltage Power Network Company

Environmental Management Plan (EMP) 61

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No. Environmental Issues

Parameter is to be monitored LocationWhere is the

parameter to be monitored?

MethodHow

Are the parameter to be monitored/ type of

monitoring equipment?

Frequency Responsibility

environmental management or not (Submit periodic reports to the Department of Natural Resources and Environment; Register ownership for hazardous waste, and other regulations of as required by Circular 12/2009/TT-BTNMT on management of HZW)

Environmental Management Plan (EMP) 62

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

Scheme illustrates environmental monitoring

Environmental Management Plan (EMP)

The WB

Local authorities and people

PMU

Contractor

TSHP Co.

Notes: Supervision work flow

Reporting work flow

63

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

8. ARRANGEMENT FOR EMP IMPLEMENTATION

8.1. Responsibilities for Implementing the Environmental Management PlanNon-compliance by the contractor could result in suspension of works, financial penalties, or other penalties, as must be clearly spelled out in the EMP and in the contract.

Contractors are responsible for implementation of EMP. The responsibilities for monitoring EMP implementation are typically shared between the contractor, the PMU, and the Construction Supervision Consultant (CSC). The Contractor’s Work Plan should incorporate the guidelines provided in the EMP created for the subproject. The designated Technical Officer(s) and Safeguards Officer(s) of the PMU are responsible for supervising the adherence to the agreed EMP by the selected contractor(s). The World Bank may periodically supervise implementation activities of the subproject.

At a minimum, the contractor should prepare a monthly report on adherence to EMP which should be submitted to the CSC and to the PMU. Subproject-specific or contract-specific reporting requirements are described in the EMP. CSC is responsible for monitoring overall environmental performance of the project and submit to PMUs quarterly monitoring reports.

To ensure effective implementation of the EMP, the following actions will be carried out during the implementation of the subproject:

8.1.1  During Detailed Design and Preparation of Bidding Contract Documents

During the detailed design and bidding invitation preparation, the project management unit will be responsible for incorporate the EMP (mitigation measures, responsibilities of the contractor) into the attached annexes in the bidding invitation and contract signed with the contractor. Engineers taking charge of the detailed design will also refer to findings in the EIA and EMP to ensure environmental issues will be looked at in the final design.

During the bidding invitation preparation and the contract, it is necessary to ensure the contractor is fully informed of its responsibilities in implementing environmental mitigation measures and its commitment to compliance.

8.1.2  During Construction Phase

PMU will assign the Construction Supervising Consultant (CSC) and/or field engineer to be responsible for supervision of safeguard performance of contractor on a daily basis. A generic Terms of Reference (TOR) is provided in Annex 2. CSC and/or field engineers will carry out, but not limited to, the following tasks:

-  Before the commencement of the construction, confirm that all compensation for land and facilities are provided and relocation and/or land acquisition/donation has been completed. 

Environmental Management Plan (EMP) 64

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

-  Closely supervise the implementation of safeguard measures throughout the construction period. 

-   Confirm the compliance with the EMP and inspect for any damages caused by the contractor.

- If necessary, prepare a minutes to ask the contractor to compensate or rehabilitate as provisions of the contract. Contractor safeguard performance will be included in the subproject progress report.

Role and responsibilities of parties in implementing EMP are summarized in the below table:

Table 8.1. Institutional Arrangements for EMP implementation Role R

esponsibilities

Organization

Project Owner - Ultimately responsible for overall project management, including environmental management.

Trung Son Hydropower One Member Limited Liability Company

EnvironmentalOfficer

- Specific responsibility and point of contact for environmental issues.

PMU of the Project owner

Project Implementation and management Agency (PMU)

- Responsible for coordination and management of overall project implementation, including guiding and supervising implementation of the EMP.

- Prepare bidding document including environmental requirements for mitigation of potential impacts as specified in this EMP;

- Planning and implementation of environmental management activities during construction.

- Coordinating with other parties in relation to environmental management activities.

- Carrying out internal monitoring and supervising.- Supervising and providing budget for monitoring

activities.- Reporting on environmental information to concerned

parties.

PMU of the Project owner

Project Operator - Responsible for operation of the project including operation stage environmental management and monitoring activities.

Hoa Binh power Company and Northern Grid Company

Consultant - Responsible for preparation of EMP documentation.ConstructionSupervision consultant

- Responsible for supervision of civil works contractors during construction, including implementation of environmental management activities under the EMP

ConstructionSupervision consultant paid by PMU

ConstructionContractor

Responsible for construction works and following contractor specifications outlined in the EMP. This includes:

- Preparing proposal for bid including mitigation measures applied for potential environmental impacts including estimated budget to carry out these measures.

Contractor chosen byPMU

Environmental Management Plan (EMP) 65

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

- Assign at least one staff working for self supervision of EMP compliance and implementation of environmental mitigation measures during the preconstruction and construction periods.

- Take actions to mitigate all potential negative impacts in line with the objective described in the ECOP.

- Actively communicate with local residents and take actions to prevent disturbance during construction.

- Ensure all the construction activities having sufficient documents from the related organization.

- Ensure that all staff and workers understand the procedure and their tasks in the environmental management program.

- Report to the PMU on any difficulties and their solutions- Report to local authority and PMU if environmental

accidents occur and coordinate with agencies and keys stakeholders to resolve these issues

9. REPORTING PROCEDURETable 9.1. Reporting Procedure

Report Prepared by Submitted to Frequency of Reporting

1 Contractor to the Employer PMU Once before construction commences and monthly thereafter

2 Construction Supervision consultant

PMU Monthly

4 Community Monitoring PMU When the community has any complaint about the subproject safeguards implementation

5 PMU Trung Son Hydropower One Member Limited Liability Company

Six-monthly

6 Trung Son Hydropower One Member Limited Liability Company

WB, EVN Six-monthly

10. CAPACITY BUILDING PLANTable 10.1. Proposed Program and Time for Training Activities in Environmental Protection

Environmental Management Plan (EMP) 66

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

No Trainings Time

1 Training on safety and mitigation measures applied for construction workers

- Before construction start.

2 Training on environmental management and supervision of EMP for staffs of PMU

- Annually in training program of Trung Son HPP

3 Training for local authorities and people on co-supervision of the EMP

- Before construction start.

4 EVN training on environmental management in general

- Annually

Table 10.2. The Estimating Cost for Future Trainings

No Training Cost (VND)

1 Training on safety and mitigation measures applied for construction workers

- Cost will be included in Contractor cost

2 Training on environmental management and supervision of EMP for staffs of PMU

- Annually in training program of Trung Son HPP

3 Training for local authorities and people on co-supervision of the EMP (Organize meeting 7 subproject communes and inform, instruct local authorities, people on EMP and right to supervise the EMP)

(6,000,000 VND/commune x 7 commune) + 8,000,000 VND for printing materials for these meetings = 50,000,000 VND

50,000,000 VND

4 EVN training on environmental management in general (cost for sending staffs to attend the training)

2 staffs 2,000,000 VND/year x 20 years = 80,000,000 VND

TOTAL 130,000,000 VND

Environmental Management Plan (EMP) 67

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

11. ESTIMATED COST FOR IMPLEMENTATION OF EMPTable 11.1. Estimated costs for implementation of EMP (VND)

No Item Construction Operation (20 years of life cycle)

1 Mitigation measures The costs are covered in Contract with Construction Contractors

The cost is covered in production cost of the Northern High Voltage Power Network Company and Hoa Binh Power Company

2 Monitoring costs for technical supervisor of PMU

The cost is covered in running cost of PMU

The cost is covered in running cost of Subproject operating units: Northern High Voltage Power Network Company and Hoa Binh Power Company

4 Capacity building 130,000,000 Included in training cost of Trung Son HPP

TOTAL 130,000,000 Included in training cost of Trung Son HPP

TOTAL 130,000,000 VND

Environmental Management Plan (EMP) 68

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

REFERENCES

1 Resettlement Plan of the Subproject

2 World Bank Environmental Assessment Source Book

3 Subproject investment report

4 Environmental guideline of the subproject (EG)

5 Environment Management Framework for DEP Project.

Environmental Management Plan (EMP) 69

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

APPENDIX 1LIST OF MEMBERS PREPARING THE

REPORT

Name of Consultants

Position Roles

Tran Minh Team leader

MSc. on Environmental Management

Environmental expert

Prepare Inception report

Prepare EMP

Review and approve information collection tools and content of community consultation.

Nguyen Thi Thuc

MSc. on Environmental Management

Environmental expert

Support team leader in site investigation

Support team leader on data processing for preparation of EMP

Supporting team

Bachelors on social science

Support on community consultation and data processing

Environmental Management Plan (EMP) 70

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

APPENDIX 2:

TOR for Construction Supervision Consultant

(CSC)General

The Construction Supervision Consultant (CSC)) is to provide professional technical services (“the Services”) to help ensure effective implementation of the ECOP and subproject EMPs.

Scope of Services:

The general services to be provided by the CSC are to inspect, monitor the construction activities to ensure that mitigation measures adopted in the ECOPs/EMP are properly implemented, and that the negative environmental impacts of the project are minimized.

On behalf of the PMU, the CSC will conduct the following tasks:

- Conduct regular site inspections;

- Review the status of implementation of environmental protection measures against the EMP and contract documents;

- Review the effectiveness of environmental mitigation measures and project environmental performance;

- As needed, review the environmental acceptability of the construction methodology (both temporary and permanent works), relevant design plans and submissions. Where necessary, the CSC shall seek and recommend the least environmental impact alternative in consultation with the designer, the Contractor(s), and PMU;

- Verify the investigation results of any non-compliance of the environmental quality performance and the effectiveness of corrective measures; and

- Provide regular feedback audit results to the contractor’s Chief Engineer according to the ECOP and site-specific mitigation measures;

- Instruct the Contractor(s) to take remedial actions within a specified timeframe, and carry out additional monitoring, if required, according to the contractual requirements and procedures in the event of non-compliances or complaints;

- Instruct the Contractor(s) to take actions to reduce impacts and follow the required EMP procedures in case of non-compliance / discrepancies identified;

- Instruct the Contractor(s) to stop activities which generate adverse impacts, and/or when the Contractor(s) fails to implement the EMP requirements / remedial actions.

- For contracts that Site Environmental Management Plan (SEMP) are required, the CSC shall provide the final review and recommend clearance of all Site Environmental plans which may affect the environment. These include, but are not limited to: dredging areas, borrow pits and disposal sites, worker’s camp plans. The CSC will review and approve the SEMP presented by the Contractors. Where these plans are found not to comply with the EMP, EIA or RAP, the CSC shall work with the PMU and Contractor to establish suitable measures or remediation.

Environmental Management Plan (EMP) 71

Subproject: Mai Chau 110 kV substation and 35 kV power line supply for construction of Trung Son hydropower project

- Addressing Complaints: Complaints will be received by the Contractor’s Site Office from local residents with regard to environmental infractions such as noise, dust, traffic safety, etc. The Contractor’s Chief Engineer or his deputy, and the CSC shall be responsible for processing, addressing or reaching solutions for complaints brought to them. The CSC shall be provided with a copy of these complaints and shall confirm that they are properly addressed by the Contractors in the same manner as incidents identified during site inspections.

- Certification for Monthly Payments: The CSC shall confirm the monthly payments for environmentally related activities implemented by the Contractor.

- Reporting: the CSC shall prepare the following written reports:

o Bi-weekly report of non-compliance issues

o Summary monthly report covering key issues and findings from reviewing and supervision activities

o At the end of the project the CSC shall prepare a final report summarizing the key findings from their work, the number of infringements, resolutions, etc. as well as advice and guidance for how such assignments should be conducted in the future.