Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
1 of 53
Tank Farm Plant Operating Procedure 242-A Evaporator
USQ # EV-18-0421-S, Rev.1
CHANGE HISTORY ( LAST 5 REV-MODS )
Rev-Mod Release Date Justification: Summary of Changes
O-5 09/26/2018 Periodic review comment
resolution
Formatting changes/updates to comply with standard.
Updated Radiation and Contamination Control statement in 3.2.1.
Modified equipment identification tags in tables.
Updated HV-CP1-1 and HV-CP2-1 in checklist 1 to condensate
drains. Updated records section. Replaced figure 1 with new
updated version from TO-600-160. Replaced signature sheet with
one from standard.
O-4 03/15/2018
Operations Request - It was
noted during a procedure
walkdown by the SOE's that
HV-CW-25 was not inside the
AMU, but was located outside
the pump and cooling pad
The HV-CW-25 row was deleted from table "Valving Inside
AMU" (located in page 33 of TO-620-160 Checklist 1) and added
to table "Valving Outside on Pump and Cooling Pad" (located in
page 33 of TO-620-160 Checklist 1)
Struck out Step 4.2.1
O-3 01/30/2017 Operations Request
Removal of Sahara Air Dryer and Portable Air Compressor from
procedure. The following sections were removed to accommodate
this: 5.5, 5.6, 5.7, and 5.13. Removed figure 3 and 4.
O-2 07/18/2016 Record management request Update the records section.
O-1 03/31/2016 Operations request Page 52 Figure 3 changed "MCC1" to "MCC-1" to match field.
Table of Contents Page
1.0 PURPOSE AND SCOPE ................................................................................................................ 3
1.1 Purpose ................................................................................................................................ 3
1.2 Scope ................................................................................................................................... 3
2.0 INFORMATION............................................................................................................................. 3
2.1 Terms and Definitions......................................................................................................... 3
2.2 General Information ............................................................................................................ 3
3.0 PRECAUTIONS AND LIMITATIONS......................................................................................... 5
3.1 Personnel Safety.................................................................................................................. 5
3.2 Radiation and Contamination Control ................................................................................ 5
4.0 Special Tools, Equipment, and Supplies......................................................................................... 6
4.1 Performance Documents ..................................................................................................... 6
4.2 Field Preparation ................................................................................................................. 7
5.0 PROCEDURE ................................................................................................................................. 8
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
2 of 53
5.1 Glycol Cooling and Air Receiver R-E-1Valve Line-up ..................................................... 8
5.2 Initial Start-Up or Re-Start after Prolonged Outage ........................................................... 9
5.3 Normal Compressor Start-Up ........................................................................................... 16
5.4 Shutdown Air Compressors/Glycol Cooling .................................................................... 21
5.5 CP-E-1/CP-E-2 Setup Maximum Pressure at Sigma V-7 Controller ............................... 22
5.6 Reset P1/P2 Lead/Lag Pressure Configuration ................................................................. 24
5.7 Reset and Synchronize P1/P2 Timers for CP-E-1 and CP-E-2 ......................................... 27
5.8 Air Compressors CP-E-1/CP-E-2 Clock Check/Synchronization .................................... 29
5.9 Activate/Enter the Password for CP-E-1/CP-E-2 ............................................................. 31
5.10 Records ............................................................................................................................. 32
Checklist 1 - Glycol Cooling System Valving - Startup ........................................................................... 33
Checklist 2 - Kaeser Compressor Valve Line-Up - Startup ...................................................................... 34
Checklist 3- Air Receiver R-E-1 Valving - Startup .................................................................................. 35
Checklist 4 - Air Receiver R-E-1 Re-pressurization Valving - Startup .................................................... 36
Figure 1 - Glycol/Water Compressor Cooler Valving .............................................................................. 37
Figure 2 - Process Air System Compressors and Air Receiver R-E-1 ..................................................... 38
Figure 3 - Adding Cooling Oil to Airend.................................................................................................. 39
Figure 4 - Sigma Control Display, Keys/Buttons and Indicators ............................................................. 40
Figure 5 - Sigma Control Main Menu Overview ...................................................................................... 42
Figure 6 - Configuration Menu Tree ......................................................................................................... 43
Signature Sheet 1 ...................................................................................................................................... 44
Attachment 1 – Alarm Messages for Machine Shutdown ........................................................................ 45
Attachment 2 – Warning Messages (Yellow Lights) ................................................................................ 49
Attachment 3 – Other Faults ..................................................................................................................... 53
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
3 of 53
1.0 PURPOSE AND SCOPE
1.1 Purpose
This procedure provides instructions for the start-up, operation, and shutdown of the
242-A Compressed Air System.
1.2 Scope
This procedure applies to the 242-A Compressed Air System and its associated
instrumentation and controls.
2.0 INFORMATION
2.1 Terms and Definitions
AMU - Aqueous Make Up
SM/OE - Shift Manager/Operations Engineer.
2.2 General Information
2.2.1 Refer to Figure 4 for Control Panel, Function Key/Button menu.
2.2.2 The oil level indicator for Compressors CP-E-1 and CP-E-2 is always checked under load, and after running for approximately 20 minutes.
2.2.3 If the Maintenance Warning is flashing (see Figure 4, Item 15) pressing the
Information “ ” key/button will determine the event/cause.
2.2.4 To establish which unit (CP-E-1 or CP-E-2) is acting as the “Lead” compressor at any given time, the following conditions will be the
determining factors:
If “P1” is displayed in the lower left hand corner of Sigma Display, CP-E-1 is the lead and CP-E-2 is the lag compressor
If “P2” is displayed in the lower left hand corner of Sigma Display, CP-E-2 is the lead and CP-E-1 is the lag compressor.
2.2.5 After program information has been input using the SIGMA Control, always press the “Enter” key/button to save the information.
2.2.6 SIGMA display values can only be changed when the value is in the 3rd line
of display and is denoted by the symbol (see Section 5.9 for graphic).
Pressing the “Enter” key/button selects that value for editing.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
4 of 53
2.2 General Information (Cont.)
2.2.7 Editing the selected value(s) is performed by using the “Up” and/or “Down” keys. The “Esc” key can be used to exit the editing process at any time prior
to hitting “Enter”. Edited information will be saved by pressing the “Enter”
key when done. The “Esc” key is used to return to the Main Menu after the
editing process is complete.
2.2.8 If a compressor is stopped underload i.e., pressing E stop, loss of power, improper compresor shut down, etc. oil from the airend may be pushed up
into the air linlet filter and housing.
2.2.9 At Operations’ earliest opportuntity, the air inlet filter housing should be wiped down and filter inspected. If filter is damaged it should be replaced.
2.2.10 If power is lost on a compressor (disconnect opened or experienced loss of power) when power is returned the P1/P2 cycle timer resets. The compressor
will start up in the P2 mode and will continue to run in P2 mode until the
P1/P2 cycle timer sees the hour that has been established for compressors to
switch modes. At that hour the compressor will go to P1 mode and the timer
will reset to 168 hours.
2.2.11 Anytime a compressor(s) has been either de-energized (disconnect opened) or experience loss of power, when reenergized, both CP-E-1 and CP-E-2 will
need to be Reset and Synchronize per Section 5.7.
2.2.12 Section 5.7 must always be performed on both CP-E-1 and CP-E-2 at the same time to keep the compressor switching sequence cycle consistent.
2.2.13 If the LOAD/IDLE key on the compressor Sigma Control Display (refer to Figure 4) is pressed while the compressor is idling, the compressor will
remain in idle mode and will not load until the LOAD/IDLE key is pressed
again.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
5 of 53
3.0 PRECAUTIONS AND LIMITATIONS
3.1 Personnel Safety
WARNING - During compressor starts, rotating equipment may potentially cause
personnel injuries.
3.1.1 Exercise caution when around air compressors. Compressors are rotating equipment and may start up automatically at any time.
3.1.2 Working on or near air compressors may require hearing protection.
3.1.3 If a lock and tag is required during the performance of this procedure, comply with the DOE-0336, Hanford Site Lockout/Tagout Procedure.
3.1.4 Compliance with DOE–0359, Hanford Site Electrical Safety Program is required when working with electrical equipment.
3.2 Radiation and Contamination Control
3.2.1 Work in radiological areas will be performed using a Radiological Work Permit following review by Radiological Control per ALARA work planning
procedure TFC ESHQ RP_RWP C 03.
3.2.2 When work is performed in or when work will result in a high contamination, high radiation, or an airborne radioactivity area, an approved work package
must be developed which is reviewed by Radiological Control per ALARA
work planning procedure TFC-ESHQ-RP_RWP-C-03.
3.2.3 The opening of any system or component within a radiological area requires the presence of a Health Physics Technician to verify contamination control.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
6 of 53
4.0 SPECIAL TOOLS, EQUIPMENT, AND SUPPLIES
The following supplies may be needed at the work place:
Ladder
Bucket
SIGMA Fluid Cooling Oil
Kaeser supplied key to access panels
Other tools, equipment, and supplies as identified by Shift Manager/OE/FWS.
4.1 Performance Documents
The following documents may be needed to perform this procedure:
TF-OR-PWR-03, 242-A Evaporator Stationary Operating Engineer Rounds
TO-230-140, Operate 241-AW Instrument Air System
Procedure 7-SA-790.
The following Sigma Control and Service manuals are located in Shift Office:
SIGMA CONTROL – Quick-reference Operating Inst., Version 72.00 05/03
Service Manual - Screw Compressor ASD T Tri-Voltage 9_5721 06 USE
Service Manual SIGMA CONTROL Index: 7_7000_0-00 10 USE – BUB 80.XX.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
7 of 53
4.2 Field Preparation
4.2.1 REPORT all deviations or discrepancies immediately to the Shift Manager.
4.2.2 REQUEST Shift Manager to identify required equipment and desired configuration for the following:
Required
()
Equipment Description Desired Configuration
(ON/OFF)
Initial*
CP-E-1 Compressor
CP-E-2 Compressor
CP-E-1 Glycol System
CP-E-2 Glycol System
* N/A if not required.
4.2.3 REQUEST Shift Manager to identify which Sections, (5.1 through 5.9) will be worked.
Identified Section(s)
/ /
Signature Print (First & Last) Date
Shift Manager /OE
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
8 of 53
5.0 PROCEDURE
NOTE - See Step 4.2.3 for Sections to be worked. Those Sections identified in Step 4.2.3 must
be worked sequentially unless otherwise granted flexibility by means of notes or
specific work instructions found in work steps.
5.1 Glycol Cooling and Air Receiver R-E-1Valve Line-up
5.1.1 IF directed by Shift Manager, PERFORM glycol cooling system valving per Checklist 1.
5.1.2 CHECK surge tank TK-E-105 to ensure coolant level is approximately one-half full in sight glass.
5.1.2.1 IF coolant is low, ADD coolant per work package and manufacturer’s recommendations.
5.1.3 IF directed by Shift Manager, PERFORM valving for Kaeser compressor(s) per Checklist 2.
5.1.4 IF directed by Shift Manager, PERFORM Air Receiver valving per Checklist 3.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
9 of 53
5.2 Initial Start-Up or Re-Start after Prolonged Outage
Prepare Compressor for Initial Startup
5.2.1 IF this is not the initial Start-Up, or Re-Start after a prolonged outage, (> 3 months) GO TO Section 5.3.
5.2.2 IF this is the initial start-up or re-start after a prolonged outage for CP-E-1, (> 3 months), CONFIRM the following:
CP-E-1 DRY COOLER DISCONNECTS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
Outside by glycol chiller unit DC3-DS-1 OFF (Open)
CP-E-1 COMPRESSOR DISCONNECTS
Compressor No. 1 CPE1-DS-1 OFF (Open)
CP-E-1 COMPRESSOR BREAKERS
MCC-2, Comp. A7 Compressor CP-E-1 OFF (Open)
5.2.3 IF this is the initial start-up or re-start after a prolonged outage for CP-E-2, (> 3 months), CONFIRM the following:
CP-E-2 DRY COOLER DISCONNECTS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
Outside by glycol chiller unit DC4-DS-1 OFF (Open)
CP-E-2 COMPRESSOR DISCONNECTS
Compressor No.2 CPE2-DS-1 OFF (Open)
CP-E-2 COMPRESSOR BREAKERS
MCC-2, Comp. A8 Compressor CP-E-2 OFF (Open)
5.2.4 NOTIFY Maintenance (for each compressor being started) to add SIGMA Fluid cooling oil to the air end inlet valve filling port per procedure 5-SA-789
242-A Kaeser Air Compressor Annual Maintenance.
5.2.5 IF open, CLOSE AND LATCH all access doors on Compressor(s).
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
10 of 53
5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)
NOTE - The Emergency Stop push button (red) is located below the control panel of
the air compressors. If the Emergency Stop push button was used to stop the
compressor while under load, oil from the airend may have been pushed up
into the air inlet filter.
5.2.6 CHECK (for each compressor being started) that the “Emergency Stop” push button(s) are not latched in the “IN” position for each compressor.
5.2.6.1 IF “Emergency Stop” push button(s) is/are latched-in the “IN” position, NOTIFY Shift Manager AND
IF directed, LIGHTLY TWIST the “Emergency Stop” push
button(s) in counter-clockwise direction to unlatch.
5.2.7 IF identified in Step 4.2.2 to run CP-E-1 compressor without the glycol chiller unit, PERFORM lineup as follows:
CP-E-1 DRY COOLER DISCONNECTS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
Outside by glycol chiller unit DC3-DS-1 OFF (Open)
CP-E-1 COMPRESSOR BREAKERS
MCC-2, Comp. A7 Compressor CP-E-1 ON (Closed)
CP-E-1 COMPRESSOR DISCONNECTS
Compressor No. 1 CPE1-DS-1 ON (Closed)
5.2.8 IF identified in Step 4.2.2 to run CP-E-2 compressor without the glycol chiller unit, PERFORM lineup as follows:
CP-E-2 DRY COOLER DISCONNECTS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
Outside by glycol chiller unit DC4-DS-1 OFF (Open)
CP-E-2 COMPRESSOR BREAKERS
MCC-2, Comp. A8 Compressor CP-E-2 ON (Closed)
CP-E-2 COMPRESSOR DISCONNECTS
Compressor No.2 CPE2-DS-1 ON (Closed)
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
11 of 53
5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)
5.2.9 IF identified in Step 4.2.2 to run CP-E-1 compressor with glycol chiller unit, PERFORM the following:
CP-E-1 COMPRESSOR BREAKERS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
MCC-2, Comp. A7 Compressor CP-E-1 ON (Closed)
CP-E-1 COMPRESSOR DISCONNECTS
Compressor No. 1 CPE1-DS-1 ON (Closed)
CP-E-1 DRY COOLER DISCONNECTS
Outside by glycol chiller unit DC3-DS-1 ON (Closed)
Initial Startup or Restart of Air Compressor(s)
5.2.10 IF identified in Step 4.2.2 to run CP-E-2 compressor with glycol chiller unit, PERFORM the following:
CP-E-2 COMPRESSOR BREAKERS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
MCC-2, Comp. A8 Compressor CP-E-2 ON (Closed)
CP-E-2 COMPRESSOR DISCONNECTS
Compressor No.2 CPE2-DS-1 ON (Closed)
CP-E-2 DRY COOLER DISCONNECTS
Outside by glycol chiller unit DC4-DS-1 ON (Closed)
NOTE - When the disconnect switches and breakers are closed, the compressors
automatically performs a self-test before the compressor(s) may be started.
- Refer to Figure 4 for Control Panel, Function Key/button menu.
5.2.11 ALLOW the controller to carry out the self-test, THEN
CHECK the green LED “Controller Power” is illuminated.
5.2.12 IF compressor is in Alarm, NOTIFY Shift Manager of Alarm(s) AND
CLEAR the Alarm(s) by pressing the “Acknowledge/Reset” key/button.
5.2.12.1 IF the Alarm does not clear, NOTIFY Shift Manager AND
REFER to Attachment 1 through Attachment 3 as applicable to
clear the alarm(s).
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
12 of 53
5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)
5.2.13 IF Maintenance Warning is Flashing/Lit NOTIFY Shift Manager AND
PERFORM the following:
5.2.13.1 PRESS the Information “ ” key/button to determine the event/cause.
NOTE - It is common for Condensate chamber to fill due to compressor
cooling after being shut off. This may leave the condensate
chamber full and between blow-down cycles resulting in a warning
on next start-up.
5.2.13.2 IF the event/cause is not condensate drain, NOTIFY Shift Manager/OE for resolution.
NOTE - The Condensate Drain Units are located inside the compressor
enclosure.
5.2.13.3 IF the cause is displayed as “Condensate drain” PRESS AND HOLD “Test” Button for > 2 seconds on applicable condensate
drain unit (flashing red alarm LED on unit) to force drain blow-
down.
5.2.13.4 IF the Condensate Drain unit blow-down was successful, (flashing red alarm LED on condensate Drain unit goes off),
PERFORM one of the following as applicable:
a. IF Maintenance Warning light does not clear, NOTIFY Shift Manager for resolution.
OR
IF Maintenance Warning light clears, GO TO Step 5.2.14.
5.2.13.5 IF the Condensate Drain unit blow-down was not successful; REPEAT the blow-down after the compressor has been started
and is under load at Step 5.2.15.9.
5.2.13.6 IF Maintenance Warning is still flashing, PRESS “Acknowledge/Reset” key/button AND
CONFIRM Maintenance Warning stops flashing and goes solid
yellow.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
13 of 53
5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)
5.2.14 CHECK displayed time and date on CP-E-1 and CP-E-2 are correct AND
IF not, REQUEST maintenance to reset per Procedure 7-SA-790.
5.2.15 PERFORM the following on compressor CP-E-1 and/or CP-E-2:
5.2.15.1 PRESS the “LOAD/IDLE” toggle key/button AND
CONFIRM the green LED “IDLE” is illuminated.
5.2.15.2 IF the compressor shows alarm/warning, NOTIFY Shift Manager.
WARNING
During compressor starts, rotating equipment may potentially
cause personnel injuries.
5.2.15.3 INFORM individuals in the area to stand clear for compressor start.
5.2.15.4 AFTER green LED “IDLE” is illuminated, PRESS “ON” key/button.
5.2.15.5 CONFIRM the following:
“Machine ON” green LED illuminates
The compressor(s) runs at idle.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
14 of 53
5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)
NOTE - If the compressor(s) are being reenergized (disconnect closed) after
being de-energized (disconnect open) the compressor(s) will start
up in “P2” mode.
- Allowing the compressor to idle for 1 minute ensures cooling oil
is distributed throughout the machine.
- The compressor may not go to “Load” if system air pressure is
above low setpoint of compressor. Use the following information
to evaluate the system pressure.
If “P1” is displayed CP-E-1 is the lead and CP-E-2 is the lag compressor
If “P2” is displayed CP-E-2 is the lead and CP-E-1 is the lag compressor
Lead compressor has a low setpoint of 105 psi and a high set point of 120 psi
Lag compressor has a low setpoint of 100 psi and a high set point of 115 psi.
5.2.15.6 AFTER allowing the compressor to idle for a minimum of one minute, PRESS the “LOAD IDLE” key.
5.2.15.7 CONFIRM the compressor switches to “LOAD” and delivers compressed air.
OR
IF the compressor does not go to load immediately, CHECK the
system pressure on the 1st line of the “Sigma Control Display”,
and the “P1” and “P2” Operation mode.
5.2.15.8 IF the system pressure is below the low setpoint for the compressor in the current operating mode and unit does not start,
NOTIFY Shift Manager/OE.
5.2.15.9 IF the Condensate drain unit blow-down was not successful in Step 5.2.13.5, PRESS AND HOLD “Test Button” for > 2
seconds on applicable condensate drain unit to force drain
blow-down.
a. IF the Maintenance Warning does not clear, NOTIFY Shift Manager/OE for resolution.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
15 of 53
5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)
NOTE - The oil level indicator for Compressors CP-E-1 and CP-E-2 is
always checked under load, and after a warm-up runtime of
approximately 20 minutes.
5.2.15.10 ALLOW the compressor(s) to run up to approximately 20 minutes to come up to running temperature.
5.2.15.11 CHECK the oil level indicator (mounted on the oil separator tank) reads between Low (Red) and High (orange) level AND
IF not, NOTIFY Shift Manager for resolution.
5.2.16 REPEAT Steps 5.2.11 through 5.2.15.11 for each compressor identified in Step 4.2.2.
5.2.17 RESET AND SYNCHRONIZE P1/P2 Timers for CP-E-1 and CP-E-2 per Section 5.7.
5.2.18 IF the glycol chiller unit is running by direction of Shift Manager/OE, PERFORM the following:
5.2.18.1 CHECK that coolant is flowing through sight glass on running compressor.
Compressor Sight Glass
CP-E-1 FG-CW-1
CP-E-2 FG-CW-2
5.2.18.2 IF coolant is not flowing, NOTIFY Shift Manager/OE.
5.2.19 ENSURE daily power operator rounds TF-OR-PWR-03 are performed to establish baseline.
5.2.20 MONITOR the compressor(s) for the first few hours of operation to ensure that it is operating correctly.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
16 of 53
5.3 Normal Compressor Start-Up
NOTE - The Emergency Stop push button (red) is located below the control panel of
the air compressors. If the Emergency Stop push button was used to stop the
compressor while under load, oil from the air end may have been pushed up
into the air inlet filter
5.3.1 CHECK that the “Emergency Stop” push buttons are not latched-in the “IN” position for each compressor.
5.3.1.1 IF “Emergency Stop” push button(s) is/are latched in the “IN” position, NOTIFY Shift Manager AND
IF directed, LIGHTLY TWIST the “Emergency Stop” push
button(s) in counter-clockwise direction to unlatch.
5.3.2 IF identified in step 4.2.2 to run CP-E-1 compressor without the glycol chiller unit, PERFORM lineup as follows:
CP-E-1 DRY COOLER DISCONNECTS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
Outside by glycol chiller unit DC3-DS-1 OFF (Open)
CP-E-1 COMPRESSOR BREAKERS
MCC-2, Comp. A7 Compressor CP-E-1 ON (Closed)
CP-E-1 COMPRESSOR DISCONNECTS
Compressor No. 1 CPE1-DS-1 ON (Closed)
5.3.3 IF identified in step 4.2.2 to run CP-E-2 compressor without the glycol chiller unit, PERFORM lineup as follows:
CP-E-2 DRY COOLER DISCONNECTS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
Outside by glycol chiller unit DC4-DS-1 OFF (Open)
CP-E-2 COMPRESSOR BREAKERS
MCC-2, Comp. A8 Compressor CP-E-2 ON (Closed)
CP-E-2 COMPRESSOR DISCONNECTS
Compressor No.2 CPE2-DS-1 ON (Closed)
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
17 of 53
5.3 Normal Compressor Start-Up (Cont.)
5.3.4 IF identified in Step 4.2.2 to run CP-E-1 compressor with glycol chiller unit, PERFORM the following:
CP-E-1 COMPRESSOR BREAKERS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
MCC-2, Comp. A7 Compressor CP-E-1 ON (Closed)
CP-E-1 COMPRESSOR DISCONNECTS
Compressor No. 1 CPE1-DS-1 ON (Closed)
CP-E-1 DRY COOLER DISCONNECTS
Outside by glycol chiller unit DC3-DS-1 ON (Closed)
5.3.5 IF identified in Step 4.2.2 to run CP-E-2 compressor with glycol chiller unit, PERFORM the following:
CP-E-2 COMPRESSOR BREAKERS
LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK
MCC-2, Comp. A8 Compressor CP-E-2 ON (Closed)
CP-E-2 COMPRESSOR DISCONNECTS
Compressor No.2 CPE2-DS-1 ON (Closed)
CP-E-2 DRY COOLER DISCONNECTS
Outside by glycol chiller unit DC4-DS-1 ON (Closed)
NOTE - The compressor(s) will carry out a self-test prior to the green light coming on.
5.3.6 PERFORM Steps 5.3.7 through 5.3.16 for each compressor identified in Step 4.2.2.
5.3.7 ALLOW the controller to carry out the self-test, THEN
CHECK the green LED “Controller Power” is illuminated.
5.3.8 IF compressor is in Alarm, NOTIFY Shift Manager of Alarm(s) AND
CLEAR the Alarm(s) by pressing the “Acknowledge/Reset” key/button.
5.3.8.1 IF the Alarm does not clear, NOTIFY Shift Manager AND
REFER to Attachment 1 through Attachment 3 as applicable to
clear the alarm(s).
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
18 of 53
5.3 Normal Compressor Start-Up (Cont.)
5.3.9 IF Maintenance Warning is Flashing/Lit, NOTIFY Shift Manager AND
PERFORM the following:
5.3.9.1 PRESS the Information “ ” key/button to determine the event/cause.
NOTE - It is common for Condensate chamber to fill due to compressor
cooling after being shut off. This may leave the condensate
chamber full and between blow-down cycles resulting in a warning
on next start-up.
5.3.9.2 IF the event/cause is not condensate drain, NOTIFY Shift Manager/OE for resolution.
NOTE- The condenser Drain Units are located inside the compressor
enclosure.
5.3.9.3 IF the cause is displayed as “Condensate drain” PRESS AND HOLD “Test” Button for > 2 seconds on applicable condensate
drain unit (flashing red alarm LED on condensate drain unit) to
force drain blow-down.
5.3.9.4 IF the Condensate Drain unit blow-down was successful, (flashing red alarm LED on condensate drain unit goes off),
PERFORM one of the following as applicable:
a. IF Maintenance Warning light does not clear, NOTIFY Shift Manager for resolution.
OR
IF Maintenance Warning light clears, GO TO Step 5.3.10.
5.3.9.5 IF the Condenser Drain unit blow-down was not successful, REPEAT this action after the compressor has been under load at
Step 5.3.13.1.
5.3.9.6 IF Maintenance Warning is still flashing, PRESS “Acknowledge/Reset” key/button AND
CONFIRM Maintenance Warning stops flashing and goes solid
yellow.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
19 of 53
5.3 Normal Compressor Start-Up (Cont.)
WARNING
During compressor starts, rotating equipment may potentially cause
personnel injuries.
5.3.10 INFORM individuals in the area to stand clear for compressor start.
5.3.11 PRESS the “ON” key/button (Refer to Figure 4 as necessary).
5.3.12 CONFIRM the “Machine ON” green LED illuminates.
5.3.12.1 IF the compressor shows alarm/warning, NOTIFY Shift Manager.
NOTE - If the compressor(s) is being started form either being de-energized (disconnect
open) or loss of power the compressor(s) will start up in “P2” mode.
- The compressor may not go to load if system air pressure is within normal
range. Use the following information to evaluate the system pressure.
If “P1” is displayed CP-E-1 is the lead and CP-E-2 is the lag compressor
If “P2” is displayed CP-E-2 is the lead and CP-E-1 is the lag compressor
Lead compressor has a low setpoint of 105 psi and a high set point of 120 psi
Lag compressor has a low setpoint of 100 psi and a high set point of 115 psi.
5.3.12.2 CONFIRM the compressor switches to “LOAD” and delivers compressed air
OR
IF the compressor does not go to load immediately, CHECK the
system pressure on the 1st line of the “Sigma Control Display”
and the “P1” and “P2” Operation mode.
5.3.12.3 IF the system pressure is below the low setpoint for the compressor in the current operating mode and unit does not start,
NOTIFY Shift Manager/OE.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
20 of 53
5.3 Normal Compressor Start-Up (Cont.)
5.3.13 ALLOW Compressor(s) to charge system, THEN
CHECK air pressure is 100 to 120 psi as read from 1st line of Sigma Control
display.
5.3.13.1 IF the Condenser Drain unit blow-down was not successful in Step 5.3.9.5, PRESS AND HOLD the “Test Button” for > 2
seconds on applicable condensate drain unit to force drain blow-
down.
a. IF the Maintenance Warning does not clear, NOTIFY Shift Manager/OE for resolution, otherwise continue.
5.3.13.2 ALLOW the compressor(s) to run approximately 20 minutes to come-up to normal operating temperature.
5.3.13.3 CHECK the oil level indicator (mounted on the oil separator tank) reads between Low and High level AND
IF not, NOTIFY Shift Manager for resolution.
5.3.14 IF the glycol chiller unit is running by direction of Shift Manager/OE, PERFORM the following:
5.3.14.1 CHECK that coolant is flowing through sight glass on running compressor.
Compressor Sight Glass
CP-E-1 FG-CW-1
CP-E-2 FG-CW-2
5.3.14.2 IF coolant is not flowing, NOTIFY Shift Manager/OE.
5.3.15 REPEAT Steps 5.3.7 through 5.3.14.2 for each compressor identified in Steps 4.2.2.
5.3.16 IF the compressor(s) being started has been either de-energized (disconnect opened) during shutdown or was shut-down due to a loss of power,
RESET AND SYNCHRONIZE P1/P2 Timers for CP-E-1 and CP-E-2 per
Section 5.7.
5.3.17 ENSURE daily power operator rounds TF-OR-PWR-03 are performed to establish baseline.
5.3.18 MONITOR the compressor(s) for the first few hours of operation to ensure that it is operating correctly.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
21 of 53
5.4 Shutdown Air Compressors/Glycol Cooling
NOTE - Refer to Figure 4 for this Section.
5.4.1 PRESS the “LOAD IDLE” key/button.
5.4.2 CONFIRM machine switches to “IDLE” and IDLE LED flashes.
5.4.3 IF the compressor does not shift to “IDLE”, NOTIFY Shift Manager.
5.4.4 ALLOW the compressor to idle for at least five (5) minutes, PRESS the “OFF” key/button AND
CONFIRM the following:
“ON” LED extinguishes
Compressor(s) shuts down.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
22 of 53
5.5 CP-E-1/CP-E-2 Setup Maximum Pressure at Sigma V-7 Controller
NOTE - This Section will only be used if one of the compressors has failed and if
directed by the Shift Manager/OE.
- This Section is used to set the running compressor’s pressure settings to 120 psi with a System Differential (SD) of -15 psi with no lead/lag
relationship with the other compressor.
5.5.1 AT the direction of the Shift Manager/OE, PERFORM the following steps 5.5.2 through 5.5.15 on either CP-E-1 or CP-E-2.
5.5.2 ENTER level 4 Password by referring to Section 5.9 as applicable.
NOTE - SIGMA display values can only be changed when the value is in the 3rd line of
display and is denoted by the symbol (refer to Section 5.9 for graphic).
Pressing the “Enter” key/button selects that value for editing.
- Editing the selected value(s) is performed by using the “Up” and/or “Down” keys. The “Esc” key can be used to exit the editing process at any time prior
to hitting “Enter”. Edited information will be saved by pressing the “Enter”
key when done. The “Esc” key is used to return to the Main Menu after the
editing process is complete.
5.5.3 PRESS the “Up” key/button until “CONFIGURATION” appears in third (3rd) line of display AND
PRESS the “Enter” key/button.
5.5.4 IF “PRESS SETTINGS” is not visible, PRESS the “Down” key/button until “PRESS SETTINGS” appears AND
PRESS “Enter” key/button.
5.5.5 PRESS “Down” key/button until “LOAD CONTROL” appears AND
PRESS “Enter” key/button.
5.5.6 SCROLL past “LOCAL MODE” to “P1/P2 cycle” AND
PRESS “Enter” key/button.
5.5.7 SET to P1 using the down keys/button AND
CONFIRM by pressing “Enter”.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
23 of 53
5.5 CP-E-1/CP-E-2 Setup Maximum Pressure at Sigma V-7 Controller
(Cont.)
5.5.8 SCROLL down to “SETTINGS” AND
CONTINUE down to one line past “P1/P2 cycle”.
5.5.9 SET the number of hours for P1 and P2 to 168 hours by placing these values in the 3rd line and using the up/down keys/buttons (normal value is 168 hours
for plant operations).
5.5.10 SCROLL down to “START” AND
SET to “START P1” (confirm by pressing “enter” key/button).
5.5.11 SCROLL down one line AND
SET “Start cycle time” for CP-E-1 to approximately 30 minutes in the future
(will start this time today).
5.5.12 SCROLL back up to “LOCAL MODE” AND GO TO P1.
5.5.13 CHANGE “P1” to “P1/P2 cycle”.
5.5.13.1 PRESS “Enter” key/button THEN
PRESS “esc”.
5.5.14 SCROLL up to “COMPRESSOR” AND
PRESS “Enter” key/button.
5.5.14.1 SET P1 SP (setpoint) to 120 psi.
5.5.14.2 ENSURE SD is -15 psi.
5.5.14.3 SET P2 SP (setpoint) to 115 psi.
5.5.14.4 ENSURE SD is -15 psi.
5.5.15 PRESS “esc” repeatedly to return to Main Menu [top level].
5.5.16 NOTIFY Shift Manager/OE that air compressor has been programmed at maximum facility pressure for Operating mode.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
24 of 53
5.6 Reset P1/P2 Lead/Lag Pressure Configuration
Reset CP-E-1 Pressure
5.6.1 IF CP-E-1 does not need its P1/P2 pressure settings to be reset to lead/lag configuration, GO TO Step 5.6.14.
5.6.2 ENTER level 4 Password by referring Section 5.9 as applicable.
NOTE - SIGMA display values can only be changed when the value is in the 3rd line of
display and is denoted by the symbol (refer to Section 5.9 for graphic).
Pressing the “Enter” key/button selects that value for editing.
- Editing the selected value(s) is performed by using the “Up” and/or “Down” keys. The “Esc” key can be used to exit the editing process at any time prior
to hitting “Enter”. Edited information will be saved by pressing the “Enter”
key when done. The “Esc” key is used to return to the Main Menu after the
editing process is complete.
5.6.3 PRESS the “Up” key/button until “CONFIGURATION” appears in third (3rd) line of display AND
PRESS the “Enter” key/button.
5.6.4 IF “PRESS SETTINGS” is not visible, PRESS the “Down” key/button until “PRESS SETTINGS” appears AND
PRESS “Enter” key/button.
5.6.5 PRESS “Down” key/button until “LOAD CONTROL” appears AND
PRESS “Enter” key/button.
5.6.6 SCROLL past “LOCAL MODE” to “P1/P2 cycle”, PRESS “Enter” key/button.
5.6.7 SET to P1 using the up/down keys/buttons AND
CONFIRM by pressing “enter”.
5.6.8 SCROLL down to “SETTINGS” AND
CONTINUE down to one line past “P1/P2 cycle”.
5.6.9 ENSURE the number of hours for P1 and P2 to 168 hours (normal value is 168 hours for plant operations).
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
25 of 53
5.6 Reset P1/P2 Lead/Lag Pressure Configuration (Cont.)
Reset CP-E-1 Pressure (Cont.)
5.6.10 SCROLL back up to “LOCAL MODE” AND
CHANGE “P1” to “P1/P2 cycle”.
5.6.10.1 PRESS “Enter” key/button THEN
PRESS “esc”.
5.6.11 SCROLL up to “COMPRESSOR” AND
PRESS “Enter” key/button.
5.6.11.1 SET P1 SP (setpoint) to 120 psi.
5.6.11.2 ENSURE SD is -15 psi.
5.6.11.3 SET P2 SP (setpoint) to 115 psi.
5.6.11.4 ENSURE SD is -15 psi.
5.6.12 PRESS “esc” repeatedly to return to Main Menu [top level].
5.6.13 GO TO Section 5.7.
Reset CP-E-2 Pressure
5.6.14 ENTER level 4 Password by referring to Section 5.9 as applicable.
5.6.15 PRESS the “Up” key/button until “CONFIGURATION” appears in third (3rd) line of display AND
PRESS the “Enter” key/button.
5.6.16 IF “PRESS SETTINGS” is not visible, PRESS the “Down” key/button until “PRESS SETTINGS” appears AND
PRESS “Enter” key/button.
5.6.17 PRESS “Down” key/button until “LOAD CONTROL” appears AND
PRESS “Enter” key/button.
5.6.18 SCROLL past “LOCAL MODE” to “P1/P2” cycle, PRESS “Enter” key/button.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
26 of 53
5.6 Reset P1/P2 Lead/Lag Pressure Configuration (Cont.)
Reset CP-E-2 Pressure (Cont.)
5.6.19 SET to P1 using the down keys/buttons AND
CONFIRM by pressing “enter”.
5.6.20 SCROLL down to “SETTINGS”, THEN
CONTINUE down to one line past “P1/P2 cycle”.
5.6.21 ENSURE the number of hours for P1 and P2 is 168 hours (normal value is 168 hours for plant operations).
5.6.22 SCROLL back up to “LOCAL MODE” AND
CHANGE “P1” to “P1/P2” cycle.
5.6.22.1 PRESS “Enter” key/button THEN
PRESS “esc”.
5.6.23 SCROLL up to “COMPRESSOR” AND
PRESS “Enter” key/button.
5.6.23.1 SET P1 SP (setpoint) to 115 psi.
5.6.23.2 ENSURE SD is -15 psi.
5.6.23.3 SET P2 SP (setpoint) to 120 psi.
5.6.23.4 ENSURE SD is -15 psi.
5.6.24 PRESS “esc” repeatedly to return to Main Menu [top level].
5.6.25 PERFORM Section 5.7 (to re-establish the lead/lag function of air compressors CE-P-1 and CE-P-2).
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
27 of 53
5.7 Reset and Synchronize P1/P2 Timers for CP-E-1 and CP-E-2
5.7.1 DO NOT START this section if all work cannot be performed prior to 12:00 pm.
5.7.1.1 IF work on both compressors cannot be completed prior to 12:00 pm, WAIT until after 12:00 pm to start work.
5.7.2 PERFORM Steps 5.7.2 through 5.7.14 on CP-E-1 and CP-E-2 concurrently to set and synchronized time to current hour and minutes.
5.7.3 IF necessary, ENTER the level 4 Password by referring to Section 5.9.
NOTE - SIGMA display values can only be changed when the value is in the 3rd line of
display and is denoted by the symbol (refer to Section 5.9 for graphic).
Pressing the “Enter” key/button selects that value for editing.
- Editing the selected value(s) is performed by using the “Up” and/or “Down” keys. The “Esc” key can be used to exit the editing process at any time prior
to hitting “Enter”. Edited information will be saved by pressing the “Enter”
key when done. The “Esc” key is used to return to the Main Menu after the
editing process is complete.
5.7.4 PRESS the “Up” key/button until “CONFIGURATION” appears in third (3rd) line of display AND
PRESS “Enter” key/button.
5.7.5 IF “PRESS SETTINGS” is not visible, PRESS the “Down” key/button until “PRESS SETTINGS” appears AND
PRESS “Enter” key/button.
5.7.6 PRESS “Down” key/button until “LOAD CONTROL” appears AND
PRESS “Enter” key/button.
5.7.7 SCROLL past “LOCAL MODE” to “P1/P2” cycle, PRESS “Enter” key/button.
5.7.8 SET to P1 using the up/down keys/buttons AND
CONFIRM by pressing “Enter”.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
28 of 53
5.7 Reset and Synchronize P1/P2 Timers for CP-E-1 and CP-E-2 (Cont.)
5.7.9 SCROLL down to “SETTINGS” AND
CONTINUE down to “START”.
5.7.10 SET to “START P1”.
5.7.11 SCROLL down one line AND
SET the “start cycle time” to 12:00 pm.
5.7.12 SCROLL back up to “Local Mode” AND
CHANGE “P1” to “P1/P2 Cycle”.
5.7.12.1 PRESS “Enter” key/button, THEN
PRESS “esc”.
5.7.13 RECORD the synchronized time in the “As-Left” column on each compressor’s Data Sheet.
5.7.14 PRESS “Esc” repeatedly to return to Main Menu [top level].
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
29 of 53
5.8 Air Compressors CP-E-1/CP-E-2 Clock Check/Synchronization
NOTE - During Clock Check/Synchronization, the units must be powered up, but
should not be at Idle or under Load while synchronizing the two units.
- Section 5.8 may be performed independently as plant conditions dictate.
5.8.1 IF either unit is running; DETERMINE if unit is at “Idle” or if unit is under “Load”.
5.8.1.1 IF the unit is at “Idle”, PRESS the “OFF” key.
5.8.1.2 IF the unit is under “Load”, PRESS the “Load/Idle” key AND
AFTER unit switches to “Idle” PRESS the “OFF” key.
5.8.2 ENSURE the following valves from system air are positioned as indicated:
Valve # Position Check
HV-CPE1-5 CLOSED
HV-CPE2-5 CLOSED
Checking/Setting Date
5.8.3 CHECK the Date on both CP-E-1/CP-E-2 display.
5.8.4 IF the Date(s) are correct, GO TO Step 5.8.6.
5.8.5 IF the Date(s) are not correct, SET the Date(s) by performing Steps 5.8.5.1 through 5.8.5.8 on CP-E-1 and/or CP-E-2 as applicable.
5.8.5.1 ENTER the password by referring to Section 5.9.
5.8.5.2 FROM the Main Menu, SCROLL up to “CONFIGURATION,” AND
PRESS “Enter” key (refer to Figure 4 through Figure 6 as
necessary).
5.8.5.3 PRESS the “Down” key to “GENERAL” AND
PRESS “Enter” key.
5.8.5.4 PRESS the “Down” key repeatedly until the Date is displayed in the 3rd line of the display.
5.8.5.5 PRESS the “Enter” key and the cursor appears under the first numeral of the Date.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
30 of 53
5.8 Air Compressors CP-E-1/CP-E-2 Clock Check/Synchronization (Cont.)
Checking/Setting Date (Cont.)
5.8.5.6 CHANGE the Date with the “Down” or “Up” key AND
SAVE the Date with the “Enter” key.
5.8.5.7 REPEAT for month and year as applicable.
5.8.5.8 PRESS the “Escape” key repeatedly to return to Main Menu.
Checking/Setting Time
5.8.6 PERFORM Steps 5.8.7 through 5.8.9 on CP-E-1 and CP-E-2 concurrently to obtain synchronized time and to prevent display(s) from timing out.
5.8.7 FROM the Main Menu, SCROLL up to “CONFIGURATION” AND
PRESS “Enter” key (refer to Figure 4 through Figure 6 as necessary).
5.8.8 PRESS the “Down” key to “GENERAL” and PRESS “Enter” key.
5.8.9 PRESS the “Down” key until the Time is displayed in the 3rd line of the display.
5.8.10 IF the As-Found times of both units are synchronized to within one (1) minute, EXIT this Section.
5.8.11 IF the units are not synchronized, ENTER the level 4 password by referring to Section 5.9.
5.8.12 DETERMINE the following:
Which clock (CP-E-1 or CP-E-2) is closest to the actual time
Is this time accurate to within 5 minutes of actual time?
5.8.13 IF not within 5 minutes of actual time, SET one of the clocks to actual time.
5.8.14 SYNCHRONIZE the two clocks to 1 minute per Data Sheet by using the “Up” and “Down” keys to change the Time and the “Enter” key to save the
hour/minutes as required.
5.8.15 PRESS “Esc” repeatedly to return to Main Menu [top level].
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
31 of 53
5.9 Activate/Enter the Password for CP-E-1/CP-E-2
NOTE - The following passwords have been entered in the controller at the factory:
Password for Level Zero (0): 00000
Password for Level Four (4): 12EXP.
5.9.1 AT the Main Menu PRESS the “UP” key/button repeatedly UNTIL “PASSWORD” appears in the third (3rd) line of display THEN
PRESS the “Enter” key/button.
5.9.2 PRESS the “Enter” key/button and the cursor appears under the first character of the password (e.g. XXXXX).
5.9.3 PRESS the “Down” key/button or the “Up” key/button repeatedly until the required character appears.
5.9.4 PRESS the “Enter” key/button and the cursor jumps to the next character of the password.
NOTE - After entering the last character the activated “password level” is displayed (in
this case Level Four (4).
5.9.5 SET the remaining characters of the password until password is complete as shown below.
5.9.6 PRESS the “Escape” key/button repeatedly to return to Main Menu [top level].
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
32 of 53
5.10 Records
5.10.1 PERFORM the following for records identified within this procedure.
5.10.1.1 RECORD the number of times the record was generated in applicable column
OR
PLACE a check mark () in the N/A column.
5.10.1.2 SUBMIT the package for verification of completed records.
Records Submittal Checklist
Number
of times
completed
N/A
()
4.2 Field Preparation Step 4.2.2
Step 4.2.3
Checklists Checklist 1 - Glycol Cooling System Valving - Startup
Checklist 2 - Kaeser Compressor Valve Line-Up - Startup
Checklist 3- Air Receiver R-E-1 Valving - Startup
Checklist 4 - Air Receiver R-E-1 Re-pressurization Valving - Startup
Signature Sheets
Signature Sheet 1
FWS/OE/Shift Manager SEND the completed records to the Central Shift Office for records
retention.
/ /
Signature Print (First & Last) Date
FWS/OE/Shift Manager
The record custodian identified in the company-level Records Inventory and Disposition
Schedule (RIDS) is responsible for record retention in accordance with TFC-BSM-
IRM_DC-C-02.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
33 of 53
Checklist 1 - Glycol Cooling System Valving - Startup
Valve
Number Description Valve Position Operator Initials
Valving Outside on Pump and Cooling Pad
HV-CW-1 P-3 Supply Isolation Valve OPEN
HV-CW-2 P-4 Supply Isolation Valve OPEN
HV-CW-3 P-3/P-4 Supply Line Isolation Valve OPEN
HV-CW-4 P-3/P-4 Supply Line Isolation Valve OPEN
HV-CW-5 DC-3 Supply Isolation Valve OPEN
HV-CW-6 DC-3 Return Isolation Valve OPEN
HV-CW-7 DC-4 Supply Isolation Valve OPEN
HV-CW-8 DC-4 Return Isolation Valve OPEN
HV-CW-13 PI-CW-1 and Glycol Fill Port Isolation Valve OPEN
HV-CW-14 Glycol Fill Port CLOSED
HV-CW-20 P-3/P-4 Return Line Isolation Valve OPEN
HV-CW-21 P-3 Return Line Isolation Valve OPEN
HV-CW-22 P-4 Return Line Isolation Valve OPEN
HV-CW-25 P-3/P-4 Inlet Drain Valve CLOSED
Valving Inside AMU
HV-CW-9 CP-E-1 Return Isolation Valve OPEN
HV-CW-10 CP-E-2 Return Isolation Valve OPEN
HV-CW-11 CP-E-1 Supply Isolation Valve OPEN
HV-CW-12 CP-E-2 Supply Isolation Valve OPEN
HV-CW-17 CP-E-1/2 Supply Isolation Valve OPEN
HV-CW-18 TK-E-105 Sight Glass Isolation Valve OPEN
HV-CW-19 TK-E-105 Sight Glass Isolation Valve OPEN
HV-CW-23 CP-E-1 Supply Drain Valve CLOSED
HV-CW-24 CP-E-2 Supply Drain Valve CLOSED
HV-CP1-1 CP-E-1 Condensate Drain Valve OPEN
HV-CP2-1 CP-E-2 Condensate Drain Valve OPEN
* Green seal on valve indicates CLOSED; Red seal indicates OPEN.
Shift Manager Review: / / ________________
Signature Print (First & Last) Date
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
34 of 53
Checklist 2 - Kaeser Compressor Valve Line-Up - Startup
Valve Number Description Valve Position Operator
Initials
CPE1/CPE2 Valves
HV-CPE1-7 CPE1 Outlet Air Vent to Atmosphere CLOSED
HV-CPE1-5 Outlet Air Isolation Valve (to Air Receiver) OPEN
HV-CPE2-7 CPE2 Outlet Air Vent to Atmosphere CLOSED
HV-CPE2-5 Outlet Air Isolation Valve (to Air Receiver) OPEN
* Green seal on valve indicates CLOSED; Red seal indicates OPEN.
Shift Manager Review: / / ________________
Signature Print (First & Last) Date
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
35 of 53
Checklist 3- Air Receiver R-E-1 Valving - Startup
Valve Number Description Valve Position Operator Initials
HV-RE1-4 R-E-1 strainer CLOSED
HV-RE1-12 Hose Connection supply valve CLOSED
HV-RE1-10 Process air connect (capped) CLOSED*
HV-IA-RE1-2 PCV-RE1-1 strainer CLOSED
HV-IA-RE1-3 Hose connection supply valve CLOSED
HV-IA-RE1-4 PCV-RE1-1 bypass CLOSED
HV-RE1-9 Hose connection isolation valve OPEN*
HV-RE1-1 Supply air to HV-CPE1-2/CPE2-2 OPEN*
HV-RE1-3 R-E-1 drain trap bypass CLOSED
HV-RE1-2 R-E-1 drain trap inlet OPEN
HV-RE1-5 R-E-1 drain trap outlet OPEN
HV-RE1-6 FI-RE1-1 inlet OPEN*
HV-RE1-7 FI-RE1-1 outlet OPEN*
HV-RE1-13 FI-RE1-1 bypass CLOSED
HV-RE1-8 Process air supply to AW Tank Farm OPEN*
HV-RE1-8A R-E-1 air outlet OPEN*
HV-RE1-21 PSLL-RE1-2 Isolation OPEN
HV-RE1-22 PI-RE1-1 Isolation OPEN
HV-IA-RE1-1 PCV-RE1-1 inlet OPEN
HV-IA-RE1-5 PCV-RE1-1 outlet OPEN
HV-PA-AW-1 AW Farm Isolation valve CLOSED
HV-PA-AW-2 AW Farm Isolation valve CLOSED
HV-PA-AW-3 AW Farm Isolation valve CLOSED
HV-PA-POR-1 Portable Air Compressor Isolation valve CLOSED
HV-PA-POR-2 Portable Air Compressor Isolation valve CLOSED
* Green seal on valve indicates CLOSED; Red seal indicates OPEN.
Shift Manager Review: / / ________________
Signature Print (First & Last) Date
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
36 of 53
Checklist 4 - Air Receiver R-E-1 Re-pressurization Valving - Startup
Valve Number Description Valve Position Operator Initials
HV-RE1-3 R-E-1 drain trap bypass CLOSED
HV-RE1-4 R-E-1 strainer CLOSED
HV-RE1-10 Process air connect (capped) CLOSED
HV-RE1-13 FI-RE1-1 bypass CLOSED
HV-RE1-8 Process air supply to AW Tank Farm CLOSED
HV-RE1-8A R-E-1 air outlet CLOSED
HV-IA-RE1-3 Hose connection supply valve CLOSED
HV-IA-RE1-4 PCV-RE1-1 bypass CLOSED
HV-RE1-1 Supply air to HV-CPE1-2/CPE2-2 OPEN
HV-RE1-2 R-E-1 drain trap inlet OPEN
HV-RE1-5 R-E-1 drain trap outlet OPEN
HV-RE1-6 FI-RE1-1 inlet OPEN
HV-RE1-7 FI-RE1-1 outlet OPEN
HV-IA-RE1-1 PCV-RE1-1 inlet OPEN
HV-IA-RE1-5 PCV-RE1-1 outlet OPEN
HV-IA-RE1-6 PI-IA-1 supply OPEN
HV-IA-RE1-7 PI-RE1-1 supply OPEN
* Green seal on valve indicates CLOSED; Red seal indicates OPEN.
Shift Manager Review: / / ________________
Signature Print (First & Last) Date
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
37 of 53
Figure 1 - Glycol/Water Compressor Cooler Valving
TK-C-100
1-8
P-C-100
2-33
FV-C100-5
2-242-26
2-28
1-12
2-30
2-2
9
1-10
Floor
Drain
1-9
PI-FC1-1
F-C-1
Filter
Floor Drain
½"
Vent
Line
½"
Sludge
Drain
Line
1-11
HV-RC3-3
1-17
1-16
1-13
2-25
1-13A 1-15
PI-FC1-2
To LERF
TK-241-AW-102
To TK-C-100
FIT
C1
00
-5
Check
Valve
1-15A1-12A
To
PT
-FC
1-4
-1A
Valve Key
Check
Gate
Pressure Regulated
2-Way Ball
3 Way
Ball Valve
PCV-RC3-1
1-211-18
1-19
1-20
PIPC-2
1-55
PIPC-1
1-54
1-28
PIPC-3
1-56
2-35 2-36
1-29
1-27FE-RC3-1
For accuracy and detail,
See Drawing H-2-98990
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
38 of 53
Figure 2 - Process Air System Compressors and Air Receiver R-E-1
T
Drain
HV-RE1-5 HV-RE1-2
COMPRESSED AIR SYSTEM
HV-RE1-3
HV-RE1-4
Glycol Out
Glycol In
Oil
Cooler
HV-RE1-1
R-E-1
FIRE-1-1
HC
HV
-RE
1-2
1
HV-RE1-8A
HV-RE1-9
H
PSVRE1-1
ATM
Glycol Out
Glycol In
Oil
Cooler
HV-RE1-13
CP-E-1CP-E-2
Air
Receiver
AW
Farm
HV
-PA
-AW
-1
HV-RE1-7HV-RE1-6
ProcessAir
PI
RE1-1
PSLL
RE1-2
H2
V-R
E1-2
HV
-RE
1-1
0
HC
HV-RE1-8
HV-RE1-12
HV-PA-POR-2
F-CPE1-1
F-CPE2-1F F
HV-CPE2-5
HV-CPE2-7 HV-CPE1-7
HV-CPE1-5
V-P
A-A
W-2
HV-PA-AW-3HV-PA-POR-1
Porta
ble
Air
Com
press
or 1
HV-CP2-1 HV-CP1-1
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
39 of 53
Figure 3 - Adding Cooling Oil to Airend
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
40 of 53
Figure 4 - Sigma Control Display, Keys/Buttons and Indicators
Item Description Function
1 «ON» Switches on the machine.
The programmed operating mode is active.
2 «OFF» Switches the machine off.
3 «Clock» Switches clock control on and off.
4 «Remote control» Switches remote control on and off.
5 «LOAD/IDLE» Toggles compressor between LOAD and IDLE operating modes.
6 «DOWN» Scrolls down the menu options.
Reduces a parameter value.
7 «UP» Scrolls up the menu options.
Increases a parameter value.
8 «escape» Returns to the next higher menu option level.
Exits the edit mode without Saving.
Returns to the main menu when held down at least 10 seconds.
9 «enter» Only affects the value in the third line of the display.
Enters the selected menu option.
Exits the edit mode and saves.
10 «Events & Information» Displays the event memory.
Selection is possible from every menu.
Return with “esc” key/button.
11 «Acknowledge/Reset» Signifies recognition of alarms and warning messages.
Resets the event memory (When Permitted).
Figure 4 continued on next page.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
41 of 53
Figure 4 - Sigma Control Display, Keys/Buttons and Indicators (Cont.)
Item Description Function
12 Display field Alphanumeric display with 4 lines.
13 Alarm Flashes red when an alarm occurs.
Lights continuously when acknowledged.
14 Communication Lights red if communication via the profibus interface is interrupted.
15 Warning
and
Maintenance
Flashes yellow for:
● maintenance work due,
● warning messages.
Lights continuously when acknowledged.
16 Controller power Lights green when the power supply to the controller is switched on.
17 LOAD Lights green when the compressor is running under LOAD.
18 IDLE Lights green when the compressor is running in IDLE.
Flashes when the «LOAD/IDLE» toggle key/button is pressed.
19 Machine ON Lights green when the machine switched on.
20 Clock The LED lights when the machine is in clock control.
21 Remote control The LED lights when the machine is in remote control.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
42 of 53
Figure 5 - Sigma Control Main Menu Overview
100 psi 80 ºF
key -OFF ¦ p1 – off total 13000 h load 12034 h ↕
100 psi 80 ºF ------------------------- off
------------------------- ↕
PASSWORD
CLOCK
CONFIGURATION
COMPONENTS
PACKAGE TEST
COMMUNICATION
LANGUAGE
STATUS
ANALOG DATA
OPERATING DATA
MAINTENANCE
MESSAGES
STATISTICS
esc
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
43 of 53
Figure 6 - Configuration Menu Tree
Configuration
- general
version
model:
PN:
SN:
weekday: ……
date: ……
time: ……
summer/winter
date format:
time format:
unit of pressure:
unit of temperature:
- pressure settings
● compressor
pRV
pressure increase
nominal pressure
setpoint pressure p1
setpoint pressure p2
system pressure low
cut-in pressure minimum
● vacuum package
system pressure high
setpoint pressure p2
setpoint pressure p1
pressure fall
● load control
- load control
local mode
remote mode
remote key: y/n
- settings
p1/p2 clock, p1/p2
cycle, p1/p2 RC,
idle load,
local-load RC
venting mode
- idle key active: y/n
esc
To “COMPONENTS” Menu
To “CLOCK” Menu
- control mode
control mode :> …...
settings:
Dual
Quadro
Vario
unload period
refrigeration dryer
modulating valve
- compressor start
compressor ON
local mode:
key, key+clock
clock key: y/n
remote mode:
key+clock, RC
remote key: y/n
clock key: y/n
remote contact:
input
compressor OFF
venting: y/n
holidays
holiday period
- reset
remote mode
remote key: y/n
input
- I/O periphery
- binary output function
- show quantities
- external messages
- switch
- analog output parameter
- timer
OFF
ON
output
= ENTER/RETURN key: initiates move to the next sub menu and enters parameters and passwords.
= ESCAPE key: returns to the next higher level or to the main menu.
esc
= UP ARROW key: scrolls text display downwards.
= DOWN ARROW key: scrolls text display upwards.
i = INFORMATION key: calls up additional information or the event memory.
Bold Text: can be changed by pressing ENTER key Normal Text: can be read only
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
44 of 53
Signature Sheet 1
Participating personnel enter their signature, printed name (first & last), and initials below.
Signature Printed Name (First & Last) Initials
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
45 of 53
Attachment 1 – Alarm Messages for Machine Shutdown
Basic Information
There are three types of fault:
● Alarm: Red LED flashes – See chapter vendor manual chapter 9.2.
● Warning: Yellow LED flashes - See chapter vendor manual chapter 9.3.
● Other faults: No indication - See chapter vendor manual chapter 9.4.
Sheet 1 of 4
Message Possible cause Remedy
blowoff prot.
The activating pressure of the safety relief valve on
the oil separator tank has been exceeded.
Change the oil separator cartridge.
Open the shut-off valve in the venting line.
sh.cct.AI1
sh.cct.AI2
The connection between the sensor and the analog
input is shorted.
Check line and connections.
AI3/AI4 error Line-break between analog input and the sensor.
Short circuit to earth.
Check line and connections.
sh.cct.AI5
sh.cct.AI6
The connection between the sensor and the analog
input is shorted.
Check line and connections.
AI7/AI8 error Line-break between the analog input and the sensor.
Short circuit to earth.
Check line and connections.
Model Machine model uncertain. Call authorized KAESER Service representative.
bus alarm The bus link from the Profibus DP interface is
defective.
Check line and settings.
PD
Package discharge temperature too low. Call authorized KAESER Service representative.
PD-
Package discharge temperature too high. Check the cooling oil level.
Clean the cooler.
Check the fan motor.
DO0.6/DO0.7 I
Short circuit in the line between the digital output and
the consumer. Check line and connections.
DO1.6/DO1.7 I
Short circuit in the line between the digital output and
the consumer. Check line and connections.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
46 of 53
Attachment 1 – Alarm Messages for Machine Shutdown (Cont.)
Sheet 2 of 4
Message Possible cause Remedy
Airend rotation The motor is turning in the wrong direction. Change over phase lines L1 and L2.
error: RS-485-USS SFC machine with USS protocol:
RS485 transmission
SIGMA CONTROL frequency converter fault
Check the connection between the frequency
converter and SIGMA CONTROL.
Check configuration of the RS485.
Call authorized KAESER Service representative.
ext. message 0
ext. message 1
ext. message 2
ext. message 3
ext. message 4
ext. message 5
Customer specific:
No adjustments possible.
-
back pressure Back pressure in the oil separator tank caused by
defective venting.
Check venting line.
HT cell Fault in the high tension cell. Call authorized KAESER Service representative.
V-belts ruptured The drive belts have parted during machine operation Replace drive belts.
no press. buildup Machine produces no compressed air.
The setpoint pressure does not rise above 50 psig for a
preset period
Check machine for leaks.
Check coupling/V-belts
Call authorized KAESER Service representative.
Condensate drain The condensate drain is defective. Check the condensate drain.
coolingwater low Cooling water pressure too low. Check cooling water supply.
Cooling water throttling valve: check setting.
RD p
Pressure switch for the refrigerant compressor has
activated. Keep ambient conditions within specified limits.
Clean the refrigerant condenser.
Clean the cooler.
RD T
Temperature in the refrigeration dryer too high. Ensure adequate ventilation.
Clean the refrigerant condenser.
Clean the cooler.
Install an extractor fan.
Fan M2 I
Overload shutdown of the first fan motor Investigate cause of shutdown.
Reset overload trip.
Call authorized KAESER Service representative.
Fan M3 I
Overload shutdown of the second fan motor Investigate cause of shutdown.
Reset overload trip.
Call authorized KAESER Service representative.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
47 of 53
Attachment 1 – Alarm Messages for Machine Shutdown (Cont.)
Sheet 3 of 4
Message Possible cause Remedy
fan M4 I
Overload shutdown of the third fan motor Investigate cause of shutdown.
Reset overload trip.
Call authorized KAESER Service representative.
fan M7 I
Overload shutdown of the control cabinet fan motor Investigate cause of shutdown.
Call authorized KAESER Service representative.
motor I
Overload shutdown of the compressor drive motor. Investigate cause of shutdown.
Change the oil separator cartridge.
Call authorized KAESER Service representative.
motor T
Drive motor overheated. Clean the motor.
Keep ambient conditions within specified limits.
motor bearings Drive motor bearings overheated. Grease the motor bearings.
Call authorized KAESER Service representative.
mains cont. on? Mains contactor not pulling in. Check mains contactor and wiring.
mains cont. off? Mains contactor not dropping out. Check mains contactor and wiring.
mains voltage
2nd power failure. Check power supply voltage.
Check door interlock switch.
mains monitor Fault in mains power supply. Have the mains power supply checked.
Emergency stop EMERGENCY STOP button pressed. Unlatch the pushbutton.
OST dp
Oil separator cartridge clogged. Change the oil separator cartridge.
OST T
Maximum air temperature at the oil separator tank
outlet is exceeded. Check the line to the trip relay.
Oil p
No changeover to LOAD as long as the minimum oil
pressure is not reached.
Check the oil circuit.
Check pressure switch, line, and connection.
p-switch Customer specific:
no adjustments possible. -
pRV
The activating pressure of the oil separator tank safety
relief valve has been exceeded. Change the pressure relief valve.
FC Frequency converter fault Call authorized KAESER Service representative.
SIGMA CONTROL T
Keep ambient conditions within specified limits.
Control cabinet: check filter mat and fan.
Softstart Fault in the soft start equipment Call authorized KAESER Service representative.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
48 of 53
Attachment 1 – Alarm Messages for Machine Shutdown (Cont.)
Sheet 4 of 4
Message Possible cause Remedy
start T
Airend discharge temperature (ADT) too low.
Ambient temperature: < +36 F Keep ambient conditions within specified limits.
T switch Customer specific:
no adjustments possible. -
ADT
The airend discharge temperature (ADT) did not reach
the minimum required level within the specified time.
Call authorized KAESER Service representative.
ADT
Maximum permissible airend discharge temperature
exceeded.
Keep ambient conditions within specified limits.
Clean the cooler.
Check the cooling oil level.
ADT dT/dt Airend discharge temperature rising too quickly. Check the cooling oil level.
Call authorized KAESER Service representative.
access doors Door opened/panel removed while the machine is
running.
Fit and secure all panels and close access doors.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
49 of 53
Attachment 2 – Warning Messages (Yellow Lights)
Sheet 1 of 4 Message Possible cause Remedy
blowoff prot.
The blowoff pressure of the safety relief valve
will soon be reached.
Change the oil separator cartridge.
Open the shut-off valve in the vent-ing line.
bus alarm The bus link from the Profibus DP in-terface is
interrupted.
Check bus highway and plug.
PD temperature
Package discharge temperature too low. Call authorized KAESER Service
representative.
PD temperature
Package discharge temperature too high. Clean the cooler.
Check the cooling oil level.
elect. equip. h
The maintenance interval for checking electrical
equipment and wiring has expired.
Carry out the check and reset the maintenance
interval counter.
error: FEPROM Internal controller memory error. Call authorized KAESER Service
representative.
error: RS 485-PP Wrong configuration or transmission error. Check the link/interface connections between
the two controllers.
Check maximum cable length and screening.
1 master and 1 slave configured.
error SMS SMS can not be sent. Call authorized KAESER Service
representative.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
50 of 53
Attachment 2 – Warning Messages (Yellow Lights) (Cont.)
Sheet 2 of 4
Message Possible cause Remedy
ext. message 0
ext. message 1
ext. message 2
ext. message 3
ext. message 4
ext. message 5
Customer specific:
No adjustments possible.
-
FC AI1 fault SCF machine:
Network pressure sensor on AI1 defective. Call authorized KAESER Service representative.
FC MM Service SCF machine:
Service mode for frequency converter.
Deactivate the service mode as soon as setting of
the frequency converter is complete.
FC mains SCF machine:
Failure of power supply to the frequency
converter.
Check power supply
annual maint Last maintenance was one year ago. Carry out the necessary maintenance and reset the
corresponding maintenance interval counter.
no press. buildup The compressor cannot build-up to working
pressure.
Check for air leaks
Check the value for internal pressure given in the
menu against the reading on the oil
separator tank pressure gauge.
condensate drain. The condensate drain is defective. Check the condensate drain and drain line.
RD T
Refrigeration dryer:
Compressed air temperature too low.
Call authorized KAESER Service representative.
RD p
Refrigeration dryer:
Pressure in the refrigerant circuit too low.
Inlet pressure switch tripped.
Call authorized KAESER Service representative.
RD p
Refrigeration dryer:
Pressure in the refrigerant circuit too high.
Safety pressure switch tripped.
Keep ambient conditions within specified limits.
Clean the refrigerant condenser.
Check the fan motor.
Call authorized KAESER Service representative.
bearing.maint. h
The maintenance interval for greasing the
bearings has expired. Grease the motor bearings.
ext.load signal? External load signal indistinct:
Increased cut-out pressure exceeded.
The external load control has not switched to idle
(off load)
Check settings of the external controller. Take into
account pressure drops across filters and dryers.
air filter dp
Air filter clogged. Air filter maintenance.
air filter dp
Air filter clogged. Air filter maintenance.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
51 of 53
Attachment 2 – Warning Messages (Yellow Lights) (Cont.)
Sheet 3 of 4
Message Possible cause Remedy
air filter h
Maintenance interval for air filter cleaning has
elapsed.
Check the air filter.
modem problem SIGMA CONTROL does not recognize the
modem.
Check the link between SIGMA CONTROL
and the modem.
motor T
Drive motor overheating. Clean the motor.
Keep ambient conditions within specified
limits.
motor starts /h
The permissible number of motor starts was
exceeded in the last 60 minutes.
Extend the idle period.
Increase capacity of air receiver.
Increase cross-section of piping between
compressor and air receiver.
motor starts /d
The permissible number of motor starts was
exceeded in the last 24 hours.
Extend the idle period.
Increase capacity of air receiver.
Increase cross-section of piping between
compressor and air receiver.
bearingchange h
The maintenance interval for checking the
bearings has expired.
Have the motor bearings checked by an
authorized KAESER Service representative.
system press.
Network pressure has fallen below the ‘low’
value.
Air consumption too high.
Check air demand.
Check transducer connections and wiring.
Check the ‘systpress. low’ warning setting.
system press.
Network pressure is above the ‘sys,press. high’
value.
Check for air leaks.
Check the ‘systpress. high’ warning setting.
Check if the machine switches to LOAD.
mains voltage
1. Power failure:
machine was re-started automatically.
Check power supply.
Check the door interlock switch.
separator dp
The pressure drop across the oil separator
cartridge has risen.
Oil separator cartridge clogged.
Change the oil separator cartridge.
separator h
The interval for the next oil separator cartridge
check has expired.
Change the oil separator cartridge.
oil filter dp
The pressure drop across the oil filter has risen.
Oil filter clogged.
Change the oil filter.
oil filter h
The interval for the next oil filter check has
expired.
Change the oil filter.
oil level
Cooling oil level too low. Top up the cooling oil.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
52 of 53
Attachment 2 – Warning Messages (Yellow Lights) (Cont.)
Sheet 4 of 4
Message Possible cause Remedy
oilT
Cooling oil temperature too low. Check temperature switch, line and connection.
Check the oil circuit.
Increase room temperature.
oil change h
The interval for the oil change has expired. Change the cooling oil
p-switch Customer specific:
no adjustments possible.
-
buffer battery Data retention battery id insufficient.. Change the battery.
error: RAM Internal RAM defective. Call authorized KAESER Service
representative.
oil content
The compressed air oil content limit will soon be
reached.
Check the scavenge tube in the oil separator
cartridge.
Check the dirt trap strainer in the scavenge line.
Check air treatment upstream of the measuring
point.
V-belt tension Belt tension is too low. Re-tension drive belts.
bit.coup.insp.h
The maintenance interval for V-belt
tension/coupling inspection has expired.
Carry out visual check.
Re-tension drive belts.
start T
The airend temperature is too low (< +14 F) for
the machine to be operated.
Keep ambient conditions within specified
limits.
start T
The airend temperature is too low (< +36 F) Keep ambient conditions within specified
limits.
set output The ‘set output’ test function is activated. Stop the ‘set output’ mode.
T switch Customer specific:
No adjustments possible.
-
TRAP interrupt System message:
TRAP interrupt
Call authorized KAESER Service
representative.
ADT
Airend discharge temperature has almost reached
maximum.
Clean the cooler.
Check the cooling oil level.
Replace oil filter.
Ensure adequate ventilation.
Keep surrounding temperature within
recommended limits.
access doors Door opened with the machine stopped. Close access doors.
Operate 242-A Evaporator Compressed Air System
Type
CONTINUOUS Document No.
TO-620-160 Rev/Mod
O-5 Release Date
09/26/2018 Page
53 of 53
Attachment 3 – Other Faults
Message Possible cause Remedy
Machine runs but produces
no compressed air
Inlet valve not opening or only opening partially. Call authorized KAESER Service
representative.
Venting valve not closing. Call authorized KAESER Service
representative.
Leaks in the pressure system. Check pipework and connections for leaks and
tighten any loose fittings.
Air consumption is greater than the capacity of
the compressor.
Check the air system for leaks.
Shut down the consumer(s).
Hose coupling or maintenance hose still plugged
into the quick-release coupling on the oil
separator tank
Remove coupling or maintenance hose.
Cooling oil runs out of the
air filter.
Oil level in the oil separator tank too high. Drain off oil until the correct level is reached.
Inlet valve defective. Call authorized KAESER Service
representative.
Compressor switches
between LOAD and IDLE
more than twice per
minute.
Air receiver too small. Increase size of air receiver.
Airflow into the compressed air network
restricted.
Increase air pipe diameters.
Check filter elements.
The differential between cut-in and cut-out
pressure is too small. Check switching differential.
Cooling oil leaking into the
floor pan.
Hose coupling or maintenance hose still plugged
into the quick-release coupling on the oil
separator tank
Remove coupling or maintenance hose.
Oil cooler leaking. Call authorized KAESER Service
representative.
Leaking joints. Tighten joints.
Replace seals.
Cooling oil consumption
too high.
Unsuitable oil is being used. Use SIGMA FLUID cooling oil.
Oil separator cartridge split. Change the oil separator cartridge
Oil level i