53
Operate 242-A Evaporator Compressed Air System Type CONTINUOUS Document No. TO-620-160 Rev/Mod O-5 Release Date 09/26/2018 Page 1 of 53 Tank Farm Plant Operating Procedure 242-A Evaporator USQ # EV-18-0421-S, Rev.1 CHANGE HISTORY ( LAST 5 REV-MODS ) Rev-Mod Release Date Justification: Summary of Changes O-5 09/26/2018 Periodic review comment resolution Formatting changes/updates to comply with standard. Updated Radiation and Contamination Control statement in 3.2.1. Modified equipment identification tags in tables. Updated HV-CP1-1 and HV-CP2-1 in checklist 1 to condensate drains. Updated records section. Replaced figure 1 with new updated version from TO-600-160. Replaced signature sheet with one from standard. O-4 03/15/2018 Operations Request - It was noted during a procedure walkdown by the SOE's that HV-CW-25 was not inside the AMU, but was located outside the pump and cooling pad The HV-CW-25 row was deleted from table "Valving Inside AMU" (located in page 33 of TO-620-160 Checklist 1) and added to table "Valving Outside on Pump and Cooling Pad" (located in page 33 of TO-620-160 Checklist 1) Struck out Step 4.2.1 O-3 01/30/2017 Operations Request Removal of Sahara Air Dryer and Portable Air Compressor from procedure. The following sections were removed to accommodate this: 5.5, 5.6, 5.7, and 5.13. Removed figure 3 and 4. O-2 07/18/2016 Record management request Update the records section. O-1 03/31/2016 Operations request Page 52 Figure 3 changed "MCC1" to "MCC-1" to match field. Table of Contents Page 1.0 PURPOSE AND SCOPE ................................................................................................................ 3 1.1 Purpose................................................................................................................................ 3 1.2 Scope ................................................................................................................................... 3 2.0 INFORMATION............................................................................................................................. 3 2.1 Terms and Definitions......................................................................................................... 3 2.2 General Information ............................................................................................................ 3 3.0 PRECAUTIONS AND LIMITATIONS......................................................................................... 5 3.1 Personnel Safety.................................................................................................................. 5 3.2 Radiation and Contamination Control ................................................................................ 5 4.0 Special Tools, Equipment, and Supplies......................................................................................... 6 4.1 Performance Documents ..................................................................................................... 6 4.2 Field Preparation ................................................................................................................. 7 5.0 PROCEDURE ................................................................................................................................. 8

Tank Farm Plant Operating Procedure 242-A Evaporator USQ # EV … · 2019. 1. 10. · 5.1 Glycol Cooling and Air Receiver R-E-1Valve Line-up 5.1.1 IF directed by Shift Manager, PERFORM

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    1 of 53

    Tank Farm Plant Operating Procedure 242-A Evaporator

    USQ # EV-18-0421-S, Rev.1

    CHANGE HISTORY ( LAST 5 REV-MODS )

    Rev-Mod Release Date Justification: Summary of Changes

    O-5 09/26/2018 Periodic review comment

    resolution

    Formatting changes/updates to comply with standard.

    Updated Radiation and Contamination Control statement in 3.2.1.

    Modified equipment identification tags in tables.

    Updated HV-CP1-1 and HV-CP2-1 in checklist 1 to condensate

    drains. Updated records section. Replaced figure 1 with new

    updated version from TO-600-160. Replaced signature sheet with

    one from standard.

    O-4 03/15/2018

    Operations Request - It was

    noted during a procedure

    walkdown by the SOE's that

    HV-CW-25 was not inside the

    AMU, but was located outside

    the pump and cooling pad

    The HV-CW-25 row was deleted from table "Valving Inside

    AMU" (located in page 33 of TO-620-160 Checklist 1) and added

    to table "Valving Outside on Pump and Cooling Pad" (located in

    page 33 of TO-620-160 Checklist 1)

    Struck out Step 4.2.1

    O-3 01/30/2017 Operations Request

    Removal of Sahara Air Dryer and Portable Air Compressor from

    procedure. The following sections were removed to accommodate

    this: 5.5, 5.6, 5.7, and 5.13. Removed figure 3 and 4.

    O-2 07/18/2016 Record management request Update the records section.

    O-1 03/31/2016 Operations request Page 52 Figure 3 changed "MCC1" to "MCC-1" to match field.

    Table of Contents Page

    1.0 PURPOSE AND SCOPE ................................................................................................................ 3

    1.1 Purpose ................................................................................................................................ 3

    1.2 Scope ................................................................................................................................... 3

    2.0 INFORMATION............................................................................................................................. 3

    2.1 Terms and Definitions......................................................................................................... 3

    2.2 General Information ............................................................................................................ 3

    3.0 PRECAUTIONS AND LIMITATIONS......................................................................................... 5

    3.1 Personnel Safety.................................................................................................................. 5

    3.2 Radiation and Contamination Control ................................................................................ 5

    4.0 Special Tools, Equipment, and Supplies......................................................................................... 6

    4.1 Performance Documents ..................................................................................................... 6

    4.2 Field Preparation ................................................................................................................. 7

    5.0 PROCEDURE ................................................................................................................................. 8

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    2 of 53

    5.1 Glycol Cooling and Air Receiver R-E-1Valve Line-up ..................................................... 8

    5.2 Initial Start-Up or Re-Start after Prolonged Outage ........................................................... 9

    5.3 Normal Compressor Start-Up ........................................................................................... 16

    5.4 Shutdown Air Compressors/Glycol Cooling .................................................................... 21

    5.5 CP-E-1/CP-E-2 Setup Maximum Pressure at Sigma V-7 Controller ............................... 22

    5.6 Reset P1/P2 Lead/Lag Pressure Configuration ................................................................. 24

    5.7 Reset and Synchronize P1/P2 Timers for CP-E-1 and CP-E-2 ......................................... 27

    5.8 Air Compressors CP-E-1/CP-E-2 Clock Check/Synchronization .................................... 29

    5.9 Activate/Enter the Password for CP-E-1/CP-E-2 ............................................................. 31

    5.10 Records ............................................................................................................................. 32

    Checklist 1 - Glycol Cooling System Valving - Startup ........................................................................... 33

    Checklist 2 - Kaeser Compressor Valve Line-Up - Startup ...................................................................... 34

    Checklist 3- Air Receiver R-E-1 Valving - Startup .................................................................................. 35

    Checklist 4 - Air Receiver R-E-1 Re-pressurization Valving - Startup .................................................... 36

    Figure 1 - Glycol/Water Compressor Cooler Valving .............................................................................. 37

    Figure 2 - Process Air System Compressors and Air Receiver R-E-1 ..................................................... 38

    Figure 3 - Adding Cooling Oil to Airend.................................................................................................. 39

    Figure 4 - Sigma Control Display, Keys/Buttons and Indicators ............................................................. 40

    Figure 5 - Sigma Control Main Menu Overview ...................................................................................... 42

    Figure 6 - Configuration Menu Tree ......................................................................................................... 43

    Signature Sheet 1 ...................................................................................................................................... 44

    Attachment 1 – Alarm Messages for Machine Shutdown ........................................................................ 45

    Attachment 2 – Warning Messages (Yellow Lights) ................................................................................ 49

    Attachment 3 – Other Faults ..................................................................................................................... 53

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    3 of 53

    1.0 PURPOSE AND SCOPE

    1.1 Purpose

    This procedure provides instructions for the start-up, operation, and shutdown of the

    242-A Compressed Air System.

    1.2 Scope

    This procedure applies to the 242-A Compressed Air System and its associated

    instrumentation and controls.

    2.0 INFORMATION

    2.1 Terms and Definitions

    AMU - Aqueous Make Up

    SM/OE - Shift Manager/Operations Engineer.

    2.2 General Information

    2.2.1 Refer to Figure 4 for Control Panel, Function Key/Button menu.

    2.2.2 The oil level indicator for Compressors CP-E-1 and CP-E-2 is always checked under load, and after running for approximately 20 minutes.

    2.2.3 If the Maintenance Warning is flashing (see Figure 4, Item 15) pressing the

    Information “ ” key/button will determine the event/cause.

    2.2.4 To establish which unit (CP-E-1 or CP-E-2) is acting as the “Lead” compressor at any given time, the following conditions will be the

    determining factors:

    If “P1” is displayed in the lower left hand corner of Sigma Display, CP-E-1 is the lead and CP-E-2 is the lag compressor

    If “P2” is displayed in the lower left hand corner of Sigma Display, CP-E-2 is the lead and CP-E-1 is the lag compressor.

    2.2.5 After program information has been input using the SIGMA Control, always press the “Enter” key/button to save the information.

    2.2.6 SIGMA display values can only be changed when the value is in the 3rd line

    of display and is denoted by the symbol (see Section 5.9 for graphic).

    Pressing the “Enter” key/button selects that value for editing.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    4 of 53

    2.2 General Information (Cont.)

    2.2.7 Editing the selected value(s) is performed by using the “Up” and/or “Down” keys. The “Esc” key can be used to exit the editing process at any time prior

    to hitting “Enter”. Edited information will be saved by pressing the “Enter”

    key when done. The “Esc” key is used to return to the Main Menu after the

    editing process is complete.

    2.2.8 If a compressor is stopped underload i.e., pressing E stop, loss of power, improper compresor shut down, etc. oil from the airend may be pushed up

    into the air linlet filter and housing.

    2.2.9 At Operations’ earliest opportuntity, the air inlet filter housing should be wiped down and filter inspected. If filter is damaged it should be replaced.

    2.2.10 If power is lost on a compressor (disconnect opened or experienced loss of power) when power is returned the P1/P2 cycle timer resets. The compressor

    will start up in the P2 mode and will continue to run in P2 mode until the

    P1/P2 cycle timer sees the hour that has been established for compressors to

    switch modes. At that hour the compressor will go to P1 mode and the timer

    will reset to 168 hours.

    2.2.11 Anytime a compressor(s) has been either de-energized (disconnect opened) or experience loss of power, when reenergized, both CP-E-1 and CP-E-2 will

    need to be Reset and Synchronize per Section 5.7.

    2.2.12 Section 5.7 must always be performed on both CP-E-1 and CP-E-2 at the same time to keep the compressor switching sequence cycle consistent.

    2.2.13 If the LOAD/IDLE key on the compressor Sigma Control Display (refer to Figure 4) is pressed while the compressor is idling, the compressor will

    remain in idle mode and will not load until the LOAD/IDLE key is pressed

    again.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    5 of 53

    3.0 PRECAUTIONS AND LIMITATIONS

    3.1 Personnel Safety

    WARNING - During compressor starts, rotating equipment may potentially cause

    personnel injuries.

    3.1.1 Exercise caution when around air compressors. Compressors are rotating equipment and may start up automatically at any time.

    3.1.2 Working on or near air compressors may require hearing protection.

    3.1.3 If a lock and tag is required during the performance of this procedure, comply with the DOE-0336, Hanford Site Lockout/Tagout Procedure.

    3.1.4 Compliance with DOE–0359, Hanford Site Electrical Safety Program is required when working with electrical equipment.

    3.2 Radiation and Contamination Control

    3.2.1 Work in radiological areas will be performed using a Radiological Work Permit following review by Radiological Control per ALARA work planning

    procedure TFC ESHQ RP_RWP C 03.

    3.2.2 When work is performed in or when work will result in a high contamination, high radiation, or an airborne radioactivity area, an approved work package

    must be developed which is reviewed by Radiological Control per ALARA

    work planning procedure TFC-ESHQ-RP_RWP-C-03.

    3.2.3 The opening of any system or component within a radiological area requires the presence of a Health Physics Technician to verify contamination control.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    6 of 53

    4.0 SPECIAL TOOLS, EQUIPMENT, AND SUPPLIES

    The following supplies may be needed at the work place:

    Ladder

    Bucket

    SIGMA Fluid Cooling Oil

    Kaeser supplied key to access panels

    Other tools, equipment, and supplies as identified by Shift Manager/OE/FWS.

    4.1 Performance Documents

    The following documents may be needed to perform this procedure:

    TF-OR-PWR-03, 242-A Evaporator Stationary Operating Engineer Rounds

    TO-230-140, Operate 241-AW Instrument Air System

    Procedure 7-SA-790.

    The following Sigma Control and Service manuals are located in Shift Office:

    SIGMA CONTROL – Quick-reference Operating Inst., Version 72.00 05/03

    Service Manual - Screw Compressor ASD T Tri-Voltage 9_5721 06 USE

    Service Manual SIGMA CONTROL Index: 7_7000_0-00 10 USE – BUB 80.XX.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    7 of 53

    4.2 Field Preparation

    4.2.1 REPORT all deviations or discrepancies immediately to the Shift Manager.

    4.2.2 REQUEST Shift Manager to identify required equipment and desired configuration for the following:

    Required

    ()

    Equipment Description Desired Configuration

    (ON/OFF)

    Initial*

    CP-E-1 Compressor

    CP-E-2 Compressor

    CP-E-1 Glycol System

    CP-E-2 Glycol System

    * N/A if not required.

    4.2.3 REQUEST Shift Manager to identify which Sections, (5.1 through 5.9) will be worked.

    Identified Section(s)

    / /

    Signature Print (First & Last) Date

    Shift Manager /OE

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    8 of 53

    5.0 PROCEDURE

    NOTE - See Step 4.2.3 for Sections to be worked. Those Sections identified in Step 4.2.3 must

    be worked sequentially unless otherwise granted flexibility by means of notes or

    specific work instructions found in work steps.

    5.1 Glycol Cooling and Air Receiver R-E-1Valve Line-up

    5.1.1 IF directed by Shift Manager, PERFORM glycol cooling system valving per Checklist 1.

    5.1.2 CHECK surge tank TK-E-105 to ensure coolant level is approximately one-half full in sight glass.

    5.1.2.1 IF coolant is low, ADD coolant per work package and manufacturer’s recommendations.

    5.1.3 IF directed by Shift Manager, PERFORM valving for Kaeser compressor(s) per Checklist 2.

    5.1.4 IF directed by Shift Manager, PERFORM Air Receiver valving per Checklist 3.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    9 of 53

    5.2 Initial Start-Up or Re-Start after Prolonged Outage

    Prepare Compressor for Initial Startup

    5.2.1 IF this is not the initial Start-Up, or Re-Start after a prolonged outage, (> 3 months) GO TO Section 5.3.

    5.2.2 IF this is the initial start-up or re-start after a prolonged outage for CP-E-1, (> 3 months), CONFIRM the following:

    CP-E-1 DRY COOLER DISCONNECTS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    Outside by glycol chiller unit DC3-DS-1 OFF (Open)

    CP-E-1 COMPRESSOR DISCONNECTS

    Compressor No. 1 CPE1-DS-1 OFF (Open)

    CP-E-1 COMPRESSOR BREAKERS

    MCC-2, Comp. A7 Compressor CP-E-1 OFF (Open)

    5.2.3 IF this is the initial start-up or re-start after a prolonged outage for CP-E-2, (> 3 months), CONFIRM the following:

    CP-E-2 DRY COOLER DISCONNECTS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    Outside by glycol chiller unit DC4-DS-1 OFF (Open)

    CP-E-2 COMPRESSOR DISCONNECTS

    Compressor No.2 CPE2-DS-1 OFF (Open)

    CP-E-2 COMPRESSOR BREAKERS

    MCC-2, Comp. A8 Compressor CP-E-2 OFF (Open)

    5.2.4 NOTIFY Maintenance (for each compressor being started) to add SIGMA Fluid cooling oil to the air end inlet valve filling port per procedure 5-SA-789

    242-A Kaeser Air Compressor Annual Maintenance.

    5.2.5 IF open, CLOSE AND LATCH all access doors on Compressor(s).

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    10 of 53

    5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)

    NOTE - The Emergency Stop push button (red) is located below the control panel of

    the air compressors. If the Emergency Stop push button was used to stop the

    compressor while under load, oil from the airend may have been pushed up

    into the air inlet filter.

    5.2.6 CHECK (for each compressor being started) that the “Emergency Stop” push button(s) are not latched in the “IN” position for each compressor.

    5.2.6.1 IF “Emergency Stop” push button(s) is/are latched-in the “IN” position, NOTIFY Shift Manager AND

    IF directed, LIGHTLY TWIST the “Emergency Stop” push

    button(s) in counter-clockwise direction to unlatch.

    5.2.7 IF identified in Step 4.2.2 to run CP-E-1 compressor without the glycol chiller unit, PERFORM lineup as follows:

    CP-E-1 DRY COOLER DISCONNECTS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    Outside by glycol chiller unit DC3-DS-1 OFF (Open)

    CP-E-1 COMPRESSOR BREAKERS

    MCC-2, Comp. A7 Compressor CP-E-1 ON (Closed)

    CP-E-1 COMPRESSOR DISCONNECTS

    Compressor No. 1 CPE1-DS-1 ON (Closed)

    5.2.8 IF identified in Step 4.2.2 to run CP-E-2 compressor without the glycol chiller unit, PERFORM lineup as follows:

    CP-E-2 DRY COOLER DISCONNECTS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    Outside by glycol chiller unit DC4-DS-1 OFF (Open)

    CP-E-2 COMPRESSOR BREAKERS

    MCC-2, Comp. A8 Compressor CP-E-2 ON (Closed)

    CP-E-2 COMPRESSOR DISCONNECTS

    Compressor No.2 CPE2-DS-1 ON (Closed)

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    11 of 53

    5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)

    5.2.9 IF identified in Step 4.2.2 to run CP-E-1 compressor with glycol chiller unit, PERFORM the following:

    CP-E-1 COMPRESSOR BREAKERS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    MCC-2, Comp. A7 Compressor CP-E-1 ON (Closed)

    CP-E-1 COMPRESSOR DISCONNECTS

    Compressor No. 1 CPE1-DS-1 ON (Closed)

    CP-E-1 DRY COOLER DISCONNECTS

    Outside by glycol chiller unit DC3-DS-1 ON (Closed)

    Initial Startup or Restart of Air Compressor(s)

    5.2.10 IF identified in Step 4.2.2 to run CP-E-2 compressor with glycol chiller unit, PERFORM the following:

    CP-E-2 COMPRESSOR BREAKERS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    MCC-2, Comp. A8 Compressor CP-E-2 ON (Closed)

    CP-E-2 COMPRESSOR DISCONNECTS

    Compressor No.2 CPE2-DS-1 ON (Closed)

    CP-E-2 DRY COOLER DISCONNECTS

    Outside by glycol chiller unit DC4-DS-1 ON (Closed)

    NOTE - When the disconnect switches and breakers are closed, the compressors

    automatically performs a self-test before the compressor(s) may be started.

    - Refer to Figure 4 for Control Panel, Function Key/button menu.

    5.2.11 ALLOW the controller to carry out the self-test, THEN

    CHECK the green LED “Controller Power” is illuminated.

    5.2.12 IF compressor is in Alarm, NOTIFY Shift Manager of Alarm(s) AND

    CLEAR the Alarm(s) by pressing the “Acknowledge/Reset” key/button.

    5.2.12.1 IF the Alarm does not clear, NOTIFY Shift Manager AND

    REFER to Attachment 1 through Attachment 3 as applicable to

    clear the alarm(s).

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    12 of 53

    5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)

    5.2.13 IF Maintenance Warning is Flashing/Lit NOTIFY Shift Manager AND

    PERFORM the following:

    5.2.13.1 PRESS the Information “ ” key/button to determine the event/cause.

    NOTE - It is common for Condensate chamber to fill due to compressor

    cooling after being shut off. This may leave the condensate

    chamber full and between blow-down cycles resulting in a warning

    on next start-up.

    5.2.13.2 IF the event/cause is not condensate drain, NOTIFY Shift Manager/OE for resolution.

    NOTE - The Condensate Drain Units are located inside the compressor

    enclosure.

    5.2.13.3 IF the cause is displayed as “Condensate drain” PRESS AND HOLD “Test” Button for > 2 seconds on applicable condensate

    drain unit (flashing red alarm LED on unit) to force drain blow-

    down.

    5.2.13.4 IF the Condensate Drain unit blow-down was successful, (flashing red alarm LED on condensate Drain unit goes off),

    PERFORM one of the following as applicable:

    a. IF Maintenance Warning light does not clear, NOTIFY Shift Manager for resolution.

    OR

    IF Maintenance Warning light clears, GO TO Step 5.2.14.

    5.2.13.5 IF the Condensate Drain unit blow-down was not successful; REPEAT the blow-down after the compressor has been started

    and is under load at Step 5.2.15.9.

    5.2.13.6 IF Maintenance Warning is still flashing, PRESS “Acknowledge/Reset” key/button AND

    CONFIRM Maintenance Warning stops flashing and goes solid

    yellow.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    13 of 53

    5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)

    5.2.14 CHECK displayed time and date on CP-E-1 and CP-E-2 are correct AND

    IF not, REQUEST maintenance to reset per Procedure 7-SA-790.

    5.2.15 PERFORM the following on compressor CP-E-1 and/or CP-E-2:

    5.2.15.1 PRESS the “LOAD/IDLE” toggle key/button AND

    CONFIRM the green LED “IDLE” is illuminated.

    5.2.15.2 IF the compressor shows alarm/warning, NOTIFY Shift Manager.

    WARNING

    During compressor starts, rotating equipment may potentially

    cause personnel injuries.

    5.2.15.3 INFORM individuals in the area to stand clear for compressor start.

    5.2.15.4 AFTER green LED “IDLE” is illuminated, PRESS “ON” key/button.

    5.2.15.5 CONFIRM the following:

    “Machine ON” green LED illuminates

    The compressor(s) runs at idle.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    14 of 53

    5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)

    NOTE - If the compressor(s) are being reenergized (disconnect closed) after

    being de-energized (disconnect open) the compressor(s) will start

    up in “P2” mode.

    - Allowing the compressor to idle for 1 minute ensures cooling oil

    is distributed throughout the machine.

    - The compressor may not go to “Load” if system air pressure is

    above low setpoint of compressor. Use the following information

    to evaluate the system pressure.

    If “P1” is displayed CP-E-1 is the lead and CP-E-2 is the lag compressor

    If “P2” is displayed CP-E-2 is the lead and CP-E-1 is the lag compressor

    Lead compressor has a low setpoint of 105 psi and a high set point of 120 psi

    Lag compressor has a low setpoint of 100 psi and a high set point of 115 psi.

    5.2.15.6 AFTER allowing the compressor to idle for a minimum of one minute, PRESS the “LOAD IDLE” key.

    5.2.15.7 CONFIRM the compressor switches to “LOAD” and delivers compressed air.

    OR

    IF the compressor does not go to load immediately, CHECK the

    system pressure on the 1st line of the “Sigma Control Display”,

    and the “P1” and “P2” Operation mode.

    5.2.15.8 IF the system pressure is below the low setpoint for the compressor in the current operating mode and unit does not start,

    NOTIFY Shift Manager/OE.

    5.2.15.9 IF the Condensate drain unit blow-down was not successful in Step 5.2.13.5, PRESS AND HOLD “Test Button” for > 2

    seconds on applicable condensate drain unit to force drain

    blow-down.

    a. IF the Maintenance Warning does not clear, NOTIFY Shift Manager/OE for resolution.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    15 of 53

    5.2 Initial Start-Up or Re-Start after Prolonged Outage (Cont.)

    NOTE - The oil level indicator for Compressors CP-E-1 and CP-E-2 is

    always checked under load, and after a warm-up runtime of

    approximately 20 minutes.

    5.2.15.10 ALLOW the compressor(s) to run up to approximately 20 minutes to come up to running temperature.

    5.2.15.11 CHECK the oil level indicator (mounted on the oil separator tank) reads between Low (Red) and High (orange) level AND

    IF not, NOTIFY Shift Manager for resolution.

    5.2.16 REPEAT Steps 5.2.11 through 5.2.15.11 for each compressor identified in Step 4.2.2.

    5.2.17 RESET AND SYNCHRONIZE P1/P2 Timers for CP-E-1 and CP-E-2 per Section 5.7.

    5.2.18 IF the glycol chiller unit is running by direction of Shift Manager/OE, PERFORM the following:

    5.2.18.1 CHECK that coolant is flowing through sight glass on running compressor.

    Compressor Sight Glass

    CP-E-1 FG-CW-1

    CP-E-2 FG-CW-2

    5.2.18.2 IF coolant is not flowing, NOTIFY Shift Manager/OE.

    5.2.19 ENSURE daily power operator rounds TF-OR-PWR-03 are performed to establish baseline.

    5.2.20 MONITOR the compressor(s) for the first few hours of operation to ensure that it is operating correctly.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    16 of 53

    5.3 Normal Compressor Start-Up

    NOTE - The Emergency Stop push button (red) is located below the control panel of

    the air compressors. If the Emergency Stop push button was used to stop the

    compressor while under load, oil from the air end may have been pushed up

    into the air inlet filter

    5.3.1 CHECK that the “Emergency Stop” push buttons are not latched-in the “IN” position for each compressor.

    5.3.1.1 IF “Emergency Stop” push button(s) is/are latched in the “IN” position, NOTIFY Shift Manager AND

    IF directed, LIGHTLY TWIST the “Emergency Stop” push

    button(s) in counter-clockwise direction to unlatch.

    5.3.2 IF identified in step 4.2.2 to run CP-E-1 compressor without the glycol chiller unit, PERFORM lineup as follows:

    CP-E-1 DRY COOLER DISCONNECTS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    Outside by glycol chiller unit DC3-DS-1 OFF (Open)

    CP-E-1 COMPRESSOR BREAKERS

    MCC-2, Comp. A7 Compressor CP-E-1 ON (Closed)

    CP-E-1 COMPRESSOR DISCONNECTS

    Compressor No. 1 CPE1-DS-1 ON (Closed)

    5.3.3 IF identified in step 4.2.2 to run CP-E-2 compressor without the glycol chiller unit, PERFORM lineup as follows:

    CP-E-2 DRY COOLER DISCONNECTS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    Outside by glycol chiller unit DC4-DS-1 OFF (Open)

    CP-E-2 COMPRESSOR BREAKERS

    MCC-2, Comp. A8 Compressor CP-E-2 ON (Closed)

    CP-E-2 COMPRESSOR DISCONNECTS

    Compressor No.2 CPE2-DS-1 ON (Closed)

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    17 of 53

    5.3 Normal Compressor Start-Up (Cont.)

    5.3.4 IF identified in Step 4.2.2 to run CP-E-1 compressor with glycol chiller unit, PERFORM the following:

    CP-E-1 COMPRESSOR BREAKERS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    MCC-2, Comp. A7 Compressor CP-E-1 ON (Closed)

    CP-E-1 COMPRESSOR DISCONNECTS

    Compressor No. 1 CPE1-DS-1 ON (Closed)

    CP-E-1 DRY COOLER DISCONNECTS

    Outside by glycol chiller unit DC3-DS-1 ON (Closed)

    5.3.5 IF identified in Step 4.2.2 to run CP-E-2 compressor with glycol chiller unit, PERFORM the following:

    CP-E-2 COMPRESSOR BREAKERS

    LOCATION EQUIPMENT I.D. NUMBER POSITION CHECK

    MCC-2, Comp. A8 Compressor CP-E-2 ON (Closed)

    CP-E-2 COMPRESSOR DISCONNECTS

    Compressor No.2 CPE2-DS-1 ON (Closed)

    CP-E-2 DRY COOLER DISCONNECTS

    Outside by glycol chiller unit DC4-DS-1 ON (Closed)

    NOTE - The compressor(s) will carry out a self-test prior to the green light coming on.

    5.3.6 PERFORM Steps 5.3.7 through 5.3.16 for each compressor identified in Step 4.2.2.

    5.3.7 ALLOW the controller to carry out the self-test, THEN

    CHECK the green LED “Controller Power” is illuminated.

    5.3.8 IF compressor is in Alarm, NOTIFY Shift Manager of Alarm(s) AND

    CLEAR the Alarm(s) by pressing the “Acknowledge/Reset” key/button.

    5.3.8.1 IF the Alarm does not clear, NOTIFY Shift Manager AND

    REFER to Attachment 1 through Attachment 3 as applicable to

    clear the alarm(s).

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    18 of 53

    5.3 Normal Compressor Start-Up (Cont.)

    5.3.9 IF Maintenance Warning is Flashing/Lit, NOTIFY Shift Manager AND

    PERFORM the following:

    5.3.9.1 PRESS the Information “ ” key/button to determine the event/cause.

    NOTE - It is common for Condensate chamber to fill due to compressor

    cooling after being shut off. This may leave the condensate

    chamber full and between blow-down cycles resulting in a warning

    on next start-up.

    5.3.9.2 IF the event/cause is not condensate drain, NOTIFY Shift Manager/OE for resolution.

    NOTE- The condenser Drain Units are located inside the compressor

    enclosure.

    5.3.9.3 IF the cause is displayed as “Condensate drain” PRESS AND HOLD “Test” Button for > 2 seconds on applicable condensate

    drain unit (flashing red alarm LED on condensate drain unit) to

    force drain blow-down.

    5.3.9.4 IF the Condensate Drain unit blow-down was successful, (flashing red alarm LED on condensate drain unit goes off),

    PERFORM one of the following as applicable:

    a. IF Maintenance Warning light does not clear, NOTIFY Shift Manager for resolution.

    OR

    IF Maintenance Warning light clears, GO TO Step 5.3.10.

    5.3.9.5 IF the Condenser Drain unit blow-down was not successful, REPEAT this action after the compressor has been under load at

    Step 5.3.13.1.

    5.3.9.6 IF Maintenance Warning is still flashing, PRESS “Acknowledge/Reset” key/button AND

    CONFIRM Maintenance Warning stops flashing and goes solid

    yellow.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    19 of 53

    5.3 Normal Compressor Start-Up (Cont.)

    WARNING

    During compressor starts, rotating equipment may potentially cause

    personnel injuries.

    5.3.10 INFORM individuals in the area to stand clear for compressor start.

    5.3.11 PRESS the “ON” key/button (Refer to Figure 4 as necessary).

    5.3.12 CONFIRM the “Machine ON” green LED illuminates.

    5.3.12.1 IF the compressor shows alarm/warning, NOTIFY Shift Manager.

    NOTE - If the compressor(s) is being started form either being de-energized (disconnect

    open) or loss of power the compressor(s) will start up in “P2” mode.

    - The compressor may not go to load if system air pressure is within normal

    range. Use the following information to evaluate the system pressure.

    If “P1” is displayed CP-E-1 is the lead and CP-E-2 is the lag compressor

    If “P2” is displayed CP-E-2 is the lead and CP-E-1 is the lag compressor

    Lead compressor has a low setpoint of 105 psi and a high set point of 120 psi

    Lag compressor has a low setpoint of 100 psi and a high set point of 115 psi.

    5.3.12.2 CONFIRM the compressor switches to “LOAD” and delivers compressed air

    OR

    IF the compressor does not go to load immediately, CHECK the

    system pressure on the 1st line of the “Sigma Control Display”

    and the “P1” and “P2” Operation mode.

    5.3.12.3 IF the system pressure is below the low setpoint for the compressor in the current operating mode and unit does not start,

    NOTIFY Shift Manager/OE.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    20 of 53

    5.3 Normal Compressor Start-Up (Cont.)

    5.3.13 ALLOW Compressor(s) to charge system, THEN

    CHECK air pressure is 100 to 120 psi as read from 1st line of Sigma Control

    display.

    5.3.13.1 IF the Condenser Drain unit blow-down was not successful in Step 5.3.9.5, PRESS AND HOLD the “Test Button” for > 2

    seconds on applicable condensate drain unit to force drain blow-

    down.

    a. IF the Maintenance Warning does not clear, NOTIFY Shift Manager/OE for resolution, otherwise continue.

    5.3.13.2 ALLOW the compressor(s) to run approximately 20 minutes to come-up to normal operating temperature.

    5.3.13.3 CHECK the oil level indicator (mounted on the oil separator tank) reads between Low and High level AND

    IF not, NOTIFY Shift Manager for resolution.

    5.3.14 IF the glycol chiller unit is running by direction of Shift Manager/OE, PERFORM the following:

    5.3.14.1 CHECK that coolant is flowing through sight glass on running compressor.

    Compressor Sight Glass

    CP-E-1 FG-CW-1

    CP-E-2 FG-CW-2

    5.3.14.2 IF coolant is not flowing, NOTIFY Shift Manager/OE.

    5.3.15 REPEAT Steps 5.3.7 through 5.3.14.2 for each compressor identified in Steps 4.2.2.

    5.3.16 IF the compressor(s) being started has been either de-energized (disconnect opened) during shutdown or was shut-down due to a loss of power,

    RESET AND SYNCHRONIZE P1/P2 Timers for CP-E-1 and CP-E-2 per

    Section 5.7.

    5.3.17 ENSURE daily power operator rounds TF-OR-PWR-03 are performed to establish baseline.

    5.3.18 MONITOR the compressor(s) for the first few hours of operation to ensure that it is operating correctly.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    21 of 53

    5.4 Shutdown Air Compressors/Glycol Cooling

    NOTE - Refer to Figure 4 for this Section.

    5.4.1 PRESS the “LOAD IDLE” key/button.

    5.4.2 CONFIRM machine switches to “IDLE” and IDLE LED flashes.

    5.4.3 IF the compressor does not shift to “IDLE”, NOTIFY Shift Manager.

    5.4.4 ALLOW the compressor to idle for at least five (5) minutes, PRESS the “OFF” key/button AND

    CONFIRM the following:

    “ON” LED extinguishes

    Compressor(s) shuts down.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    22 of 53

    5.5 CP-E-1/CP-E-2 Setup Maximum Pressure at Sigma V-7 Controller

    NOTE - This Section will only be used if one of the compressors has failed and if

    directed by the Shift Manager/OE.

    - This Section is used to set the running compressor’s pressure settings to 120 psi with a System Differential (SD) of -15 psi with no lead/lag

    relationship with the other compressor.

    5.5.1 AT the direction of the Shift Manager/OE, PERFORM the following steps 5.5.2 through 5.5.15 on either CP-E-1 or CP-E-2.

    5.5.2 ENTER level 4 Password by referring to Section 5.9 as applicable.

    NOTE - SIGMA display values can only be changed when the value is in the 3rd line of

    display and is denoted by the symbol (refer to Section 5.9 for graphic).

    Pressing the “Enter” key/button selects that value for editing.

    - Editing the selected value(s) is performed by using the “Up” and/or “Down” keys. The “Esc” key can be used to exit the editing process at any time prior

    to hitting “Enter”. Edited information will be saved by pressing the “Enter”

    key when done. The “Esc” key is used to return to the Main Menu after the

    editing process is complete.

    5.5.3 PRESS the “Up” key/button until “CONFIGURATION” appears in third (3rd) line of display AND

    PRESS the “Enter” key/button.

    5.5.4 IF “PRESS SETTINGS” is not visible, PRESS the “Down” key/button until “PRESS SETTINGS” appears AND

    PRESS “Enter” key/button.

    5.5.5 PRESS “Down” key/button until “LOAD CONTROL” appears AND

    PRESS “Enter” key/button.

    5.5.6 SCROLL past “LOCAL MODE” to “P1/P2 cycle” AND

    PRESS “Enter” key/button.

    5.5.7 SET to P1 using the down keys/button AND

    CONFIRM by pressing “Enter”.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    23 of 53

    5.5 CP-E-1/CP-E-2 Setup Maximum Pressure at Sigma V-7 Controller

    (Cont.)

    5.5.8 SCROLL down to “SETTINGS” AND

    CONTINUE down to one line past “P1/P2 cycle”.

    5.5.9 SET the number of hours for P1 and P2 to 168 hours by placing these values in the 3rd line and using the up/down keys/buttons (normal value is 168 hours

    for plant operations).

    5.5.10 SCROLL down to “START” AND

    SET to “START P1” (confirm by pressing “enter” key/button).

    5.5.11 SCROLL down one line AND

    SET “Start cycle time” for CP-E-1 to approximately 30 minutes in the future

    (will start this time today).

    5.5.12 SCROLL back up to “LOCAL MODE” AND GO TO P1.

    5.5.13 CHANGE “P1” to “P1/P2 cycle”.

    5.5.13.1 PRESS “Enter” key/button THEN

    PRESS “esc”.

    5.5.14 SCROLL up to “COMPRESSOR” AND

    PRESS “Enter” key/button.

    5.5.14.1 SET P1 SP (setpoint) to 120 psi.

    5.5.14.2 ENSURE SD is -15 psi.

    5.5.14.3 SET P2 SP (setpoint) to 115 psi.

    5.5.14.4 ENSURE SD is -15 psi.

    5.5.15 PRESS “esc” repeatedly to return to Main Menu [top level].

    5.5.16 NOTIFY Shift Manager/OE that air compressor has been programmed at maximum facility pressure for Operating mode.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    24 of 53

    5.6 Reset P1/P2 Lead/Lag Pressure Configuration

    Reset CP-E-1 Pressure

    5.6.1 IF CP-E-1 does not need its P1/P2 pressure settings to be reset to lead/lag configuration, GO TO Step 5.6.14.

    5.6.2 ENTER level 4 Password by referring Section 5.9 as applicable.

    NOTE - SIGMA display values can only be changed when the value is in the 3rd line of

    display and is denoted by the symbol (refer to Section 5.9 for graphic).

    Pressing the “Enter” key/button selects that value for editing.

    - Editing the selected value(s) is performed by using the “Up” and/or “Down” keys. The “Esc” key can be used to exit the editing process at any time prior

    to hitting “Enter”. Edited information will be saved by pressing the “Enter”

    key when done. The “Esc” key is used to return to the Main Menu after the

    editing process is complete.

    5.6.3 PRESS the “Up” key/button until “CONFIGURATION” appears in third (3rd) line of display AND

    PRESS the “Enter” key/button.

    5.6.4 IF “PRESS SETTINGS” is not visible, PRESS the “Down” key/button until “PRESS SETTINGS” appears AND

    PRESS “Enter” key/button.

    5.6.5 PRESS “Down” key/button until “LOAD CONTROL” appears AND

    PRESS “Enter” key/button.

    5.6.6 SCROLL past “LOCAL MODE” to “P1/P2 cycle”, PRESS “Enter” key/button.

    5.6.7 SET to P1 using the up/down keys/buttons AND

    CONFIRM by pressing “enter”.

    5.6.8 SCROLL down to “SETTINGS” AND

    CONTINUE down to one line past “P1/P2 cycle”.

    5.6.9 ENSURE the number of hours for P1 and P2 to 168 hours (normal value is 168 hours for plant operations).

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    25 of 53

    5.6 Reset P1/P2 Lead/Lag Pressure Configuration (Cont.)

    Reset CP-E-1 Pressure (Cont.)

    5.6.10 SCROLL back up to “LOCAL MODE” AND

    CHANGE “P1” to “P1/P2 cycle”.

    5.6.10.1 PRESS “Enter” key/button THEN

    PRESS “esc”.

    5.6.11 SCROLL up to “COMPRESSOR” AND

    PRESS “Enter” key/button.

    5.6.11.1 SET P1 SP (setpoint) to 120 psi.

    5.6.11.2 ENSURE SD is -15 psi.

    5.6.11.3 SET P2 SP (setpoint) to 115 psi.

    5.6.11.4 ENSURE SD is -15 psi.

    5.6.12 PRESS “esc” repeatedly to return to Main Menu [top level].

    5.6.13 GO TO Section 5.7.

    Reset CP-E-2 Pressure

    5.6.14 ENTER level 4 Password by referring to Section 5.9 as applicable.

    5.6.15 PRESS the “Up” key/button until “CONFIGURATION” appears in third (3rd) line of display AND

    PRESS the “Enter” key/button.

    5.6.16 IF “PRESS SETTINGS” is not visible, PRESS the “Down” key/button until “PRESS SETTINGS” appears AND

    PRESS “Enter” key/button.

    5.6.17 PRESS “Down” key/button until “LOAD CONTROL” appears AND

    PRESS “Enter” key/button.

    5.6.18 SCROLL past “LOCAL MODE” to “P1/P2” cycle, PRESS “Enter” key/button.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    26 of 53

    5.6 Reset P1/P2 Lead/Lag Pressure Configuration (Cont.)

    Reset CP-E-2 Pressure (Cont.)

    5.6.19 SET to P1 using the down keys/buttons AND

    CONFIRM by pressing “enter”.

    5.6.20 SCROLL down to “SETTINGS”, THEN

    CONTINUE down to one line past “P1/P2 cycle”.

    5.6.21 ENSURE the number of hours for P1 and P2 is 168 hours (normal value is 168 hours for plant operations).

    5.6.22 SCROLL back up to “LOCAL MODE” AND

    CHANGE “P1” to “P1/P2” cycle.

    5.6.22.1 PRESS “Enter” key/button THEN

    PRESS “esc”.

    5.6.23 SCROLL up to “COMPRESSOR” AND

    PRESS “Enter” key/button.

    5.6.23.1 SET P1 SP (setpoint) to 115 psi.

    5.6.23.2 ENSURE SD is -15 psi.

    5.6.23.3 SET P2 SP (setpoint) to 120 psi.

    5.6.23.4 ENSURE SD is -15 psi.

    5.6.24 PRESS “esc” repeatedly to return to Main Menu [top level].

    5.6.25 PERFORM Section 5.7 (to re-establish the lead/lag function of air compressors CE-P-1 and CE-P-2).

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    27 of 53

    5.7 Reset and Synchronize P1/P2 Timers for CP-E-1 and CP-E-2

    5.7.1 DO NOT START this section if all work cannot be performed prior to 12:00 pm.

    5.7.1.1 IF work on both compressors cannot be completed prior to 12:00 pm, WAIT until after 12:00 pm to start work.

    5.7.2 PERFORM Steps 5.7.2 through 5.7.14 on CP-E-1 and CP-E-2 concurrently to set and synchronized time to current hour and minutes.

    5.7.3 IF necessary, ENTER the level 4 Password by referring to Section 5.9.

    NOTE - SIGMA display values can only be changed when the value is in the 3rd line of

    display and is denoted by the symbol (refer to Section 5.9 for graphic).

    Pressing the “Enter” key/button selects that value for editing.

    - Editing the selected value(s) is performed by using the “Up” and/or “Down” keys. The “Esc” key can be used to exit the editing process at any time prior

    to hitting “Enter”. Edited information will be saved by pressing the “Enter”

    key when done. The “Esc” key is used to return to the Main Menu after the

    editing process is complete.

    5.7.4 PRESS the “Up” key/button until “CONFIGURATION” appears in third (3rd) line of display AND

    PRESS “Enter” key/button.

    5.7.5 IF “PRESS SETTINGS” is not visible, PRESS the “Down” key/button until “PRESS SETTINGS” appears AND

    PRESS “Enter” key/button.

    5.7.6 PRESS “Down” key/button until “LOAD CONTROL” appears AND

    PRESS “Enter” key/button.

    5.7.7 SCROLL past “LOCAL MODE” to “P1/P2” cycle, PRESS “Enter” key/button.

    5.7.8 SET to P1 using the up/down keys/buttons AND

    CONFIRM by pressing “Enter”.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    28 of 53

    5.7 Reset and Synchronize P1/P2 Timers for CP-E-1 and CP-E-2 (Cont.)

    5.7.9 SCROLL down to “SETTINGS” AND

    CONTINUE down to “START”.

    5.7.10 SET to “START P1”.

    5.7.11 SCROLL down one line AND

    SET the “start cycle time” to 12:00 pm.

    5.7.12 SCROLL back up to “Local Mode” AND

    CHANGE “P1” to “P1/P2 Cycle”.

    5.7.12.1 PRESS “Enter” key/button, THEN

    PRESS “esc”.

    5.7.13 RECORD the synchronized time in the “As-Left” column on each compressor’s Data Sheet.

    5.7.14 PRESS “Esc” repeatedly to return to Main Menu [top level].

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    29 of 53

    5.8 Air Compressors CP-E-1/CP-E-2 Clock Check/Synchronization

    NOTE - During Clock Check/Synchronization, the units must be powered up, but

    should not be at Idle or under Load while synchronizing the two units.

    - Section 5.8 may be performed independently as plant conditions dictate.

    5.8.1 IF either unit is running; DETERMINE if unit is at “Idle” or if unit is under “Load”.

    5.8.1.1 IF the unit is at “Idle”, PRESS the “OFF” key.

    5.8.1.2 IF the unit is under “Load”, PRESS the “Load/Idle” key AND

    AFTER unit switches to “Idle” PRESS the “OFF” key.

    5.8.2 ENSURE the following valves from system air are positioned as indicated:

    Valve # Position Check

    HV-CPE1-5 CLOSED

    HV-CPE2-5 CLOSED

    Checking/Setting Date

    5.8.3 CHECK the Date on both CP-E-1/CP-E-2 display.

    5.8.4 IF the Date(s) are correct, GO TO Step 5.8.6.

    5.8.5 IF the Date(s) are not correct, SET the Date(s) by performing Steps 5.8.5.1 through 5.8.5.8 on CP-E-1 and/or CP-E-2 as applicable.

    5.8.5.1 ENTER the password by referring to Section 5.9.

    5.8.5.2 FROM the Main Menu, SCROLL up to “CONFIGURATION,” AND

    PRESS “Enter” key (refer to Figure 4 through Figure 6 as

    necessary).

    5.8.5.3 PRESS the “Down” key to “GENERAL” AND

    PRESS “Enter” key.

    5.8.5.4 PRESS the “Down” key repeatedly until the Date is displayed in the 3rd line of the display.

    5.8.5.5 PRESS the “Enter” key and the cursor appears under the first numeral of the Date.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    30 of 53

    5.8 Air Compressors CP-E-1/CP-E-2 Clock Check/Synchronization (Cont.)

    Checking/Setting Date (Cont.)

    5.8.5.6 CHANGE the Date with the “Down” or “Up” key AND

    SAVE the Date with the “Enter” key.

    5.8.5.7 REPEAT for month and year as applicable.

    5.8.5.8 PRESS the “Escape” key repeatedly to return to Main Menu.

    Checking/Setting Time

    5.8.6 PERFORM Steps 5.8.7 through 5.8.9 on CP-E-1 and CP-E-2 concurrently to obtain synchronized time and to prevent display(s) from timing out.

    5.8.7 FROM the Main Menu, SCROLL up to “CONFIGURATION” AND

    PRESS “Enter” key (refer to Figure 4 through Figure 6 as necessary).

    5.8.8 PRESS the “Down” key to “GENERAL” and PRESS “Enter” key.

    5.8.9 PRESS the “Down” key until the Time is displayed in the 3rd line of the display.

    5.8.10 IF the As-Found times of both units are synchronized to within one (1) minute, EXIT this Section.

    5.8.11 IF the units are not synchronized, ENTER the level 4 password by referring to Section 5.9.

    5.8.12 DETERMINE the following:

    Which clock (CP-E-1 or CP-E-2) is closest to the actual time

    Is this time accurate to within 5 minutes of actual time?

    5.8.13 IF not within 5 minutes of actual time, SET one of the clocks to actual time.

    5.8.14 SYNCHRONIZE the two clocks to 1 minute per Data Sheet by using the “Up” and “Down” keys to change the Time and the “Enter” key to save the

    hour/minutes as required.

    5.8.15 PRESS “Esc” repeatedly to return to Main Menu [top level].

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    31 of 53

    5.9 Activate/Enter the Password for CP-E-1/CP-E-2

    NOTE - The following passwords have been entered in the controller at the factory:

    Password for Level Zero (0): 00000

    Password for Level Four (4): 12EXP.

    5.9.1 AT the Main Menu PRESS the “UP” key/button repeatedly UNTIL “PASSWORD” appears in the third (3rd) line of display THEN

    PRESS the “Enter” key/button.

    5.9.2 PRESS the “Enter” key/button and the cursor appears under the first character of the password (e.g. XXXXX).

    5.9.3 PRESS the “Down” key/button or the “Up” key/button repeatedly until the required character appears.

    5.9.4 PRESS the “Enter” key/button and the cursor jumps to the next character of the password.

    NOTE - After entering the last character the activated “password level” is displayed (in

    this case Level Four (4).

    5.9.5 SET the remaining characters of the password until password is complete as shown below.

    5.9.6 PRESS the “Escape” key/button repeatedly to return to Main Menu [top level].

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    32 of 53

    5.10 Records

    5.10.1 PERFORM the following for records identified within this procedure.

    5.10.1.1 RECORD the number of times the record was generated in applicable column

    OR

    PLACE a check mark () in the N/A column.

    5.10.1.2 SUBMIT the package for verification of completed records.

    Records Submittal Checklist

    Number

    of times

    completed

    N/A

    ()

    4.2 Field Preparation Step 4.2.2

    Step 4.2.3

    Checklists Checklist 1 - Glycol Cooling System Valving - Startup

    Checklist 2 - Kaeser Compressor Valve Line-Up - Startup

    Checklist 3- Air Receiver R-E-1 Valving - Startup

    Checklist 4 - Air Receiver R-E-1 Re-pressurization Valving - Startup

    Signature Sheets

    Signature Sheet 1

    FWS/OE/Shift Manager SEND the completed records to the Central Shift Office for records

    retention.

    / /

    Signature Print (First & Last) Date

    FWS/OE/Shift Manager

    The record custodian identified in the company-level Records Inventory and Disposition

    Schedule (RIDS) is responsible for record retention in accordance with TFC-BSM-

    IRM_DC-C-02.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    33 of 53

    Checklist 1 - Glycol Cooling System Valving - Startup

    Valve

    Number Description Valve Position Operator Initials

    Valving Outside on Pump and Cooling Pad

    HV-CW-1 P-3 Supply Isolation Valve OPEN

    HV-CW-2 P-4 Supply Isolation Valve OPEN

    HV-CW-3 P-3/P-4 Supply Line Isolation Valve OPEN

    HV-CW-4 P-3/P-4 Supply Line Isolation Valve OPEN

    HV-CW-5 DC-3 Supply Isolation Valve OPEN

    HV-CW-6 DC-3 Return Isolation Valve OPEN

    HV-CW-7 DC-4 Supply Isolation Valve OPEN

    HV-CW-8 DC-4 Return Isolation Valve OPEN

    HV-CW-13 PI-CW-1 and Glycol Fill Port Isolation Valve OPEN

    HV-CW-14 Glycol Fill Port CLOSED

    HV-CW-20 P-3/P-4 Return Line Isolation Valve OPEN

    HV-CW-21 P-3 Return Line Isolation Valve OPEN

    HV-CW-22 P-4 Return Line Isolation Valve OPEN

    HV-CW-25 P-3/P-4 Inlet Drain Valve CLOSED

    Valving Inside AMU

    HV-CW-9 CP-E-1 Return Isolation Valve OPEN

    HV-CW-10 CP-E-2 Return Isolation Valve OPEN

    HV-CW-11 CP-E-1 Supply Isolation Valve OPEN

    HV-CW-12 CP-E-2 Supply Isolation Valve OPEN

    HV-CW-17 CP-E-1/2 Supply Isolation Valve OPEN

    HV-CW-18 TK-E-105 Sight Glass Isolation Valve OPEN

    HV-CW-19 TK-E-105 Sight Glass Isolation Valve OPEN

    HV-CW-23 CP-E-1 Supply Drain Valve CLOSED

    HV-CW-24 CP-E-2 Supply Drain Valve CLOSED

    HV-CP1-1 CP-E-1 Condensate Drain Valve OPEN

    HV-CP2-1 CP-E-2 Condensate Drain Valve OPEN

    * Green seal on valve indicates CLOSED; Red seal indicates OPEN.

    Shift Manager Review: / / ________________

    Signature Print (First & Last) Date

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    34 of 53

    Checklist 2 - Kaeser Compressor Valve Line-Up - Startup

    Valve Number Description Valve Position Operator

    Initials

    CPE1/CPE2 Valves

    HV-CPE1-7 CPE1 Outlet Air Vent to Atmosphere CLOSED

    HV-CPE1-5 Outlet Air Isolation Valve (to Air Receiver) OPEN

    HV-CPE2-7 CPE2 Outlet Air Vent to Atmosphere CLOSED

    HV-CPE2-5 Outlet Air Isolation Valve (to Air Receiver) OPEN

    * Green seal on valve indicates CLOSED; Red seal indicates OPEN.

    Shift Manager Review: / / ________________

    Signature Print (First & Last) Date

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    35 of 53

    Checklist 3- Air Receiver R-E-1 Valving - Startup

    Valve Number Description Valve Position Operator Initials

    HV-RE1-4 R-E-1 strainer CLOSED

    HV-RE1-12 Hose Connection supply valve CLOSED

    HV-RE1-10 Process air connect (capped) CLOSED*

    HV-IA-RE1-2 PCV-RE1-1 strainer CLOSED

    HV-IA-RE1-3 Hose connection supply valve CLOSED

    HV-IA-RE1-4 PCV-RE1-1 bypass CLOSED

    HV-RE1-9 Hose connection isolation valve OPEN*

    HV-RE1-1 Supply air to HV-CPE1-2/CPE2-2 OPEN*

    HV-RE1-3 R-E-1 drain trap bypass CLOSED

    HV-RE1-2 R-E-1 drain trap inlet OPEN

    HV-RE1-5 R-E-1 drain trap outlet OPEN

    HV-RE1-6 FI-RE1-1 inlet OPEN*

    HV-RE1-7 FI-RE1-1 outlet OPEN*

    HV-RE1-13 FI-RE1-1 bypass CLOSED

    HV-RE1-8 Process air supply to AW Tank Farm OPEN*

    HV-RE1-8A R-E-1 air outlet OPEN*

    HV-RE1-21 PSLL-RE1-2 Isolation OPEN

    HV-RE1-22 PI-RE1-1 Isolation OPEN

    HV-IA-RE1-1 PCV-RE1-1 inlet OPEN

    HV-IA-RE1-5 PCV-RE1-1 outlet OPEN

    HV-PA-AW-1 AW Farm Isolation valve CLOSED

    HV-PA-AW-2 AW Farm Isolation valve CLOSED

    HV-PA-AW-3 AW Farm Isolation valve CLOSED

    HV-PA-POR-1 Portable Air Compressor Isolation valve CLOSED

    HV-PA-POR-2 Portable Air Compressor Isolation valve CLOSED

    * Green seal on valve indicates CLOSED; Red seal indicates OPEN.

    Shift Manager Review: / / ________________

    Signature Print (First & Last) Date

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    36 of 53

    Checklist 4 - Air Receiver R-E-1 Re-pressurization Valving - Startup

    Valve Number Description Valve Position Operator Initials

    HV-RE1-3 R-E-1 drain trap bypass CLOSED

    HV-RE1-4 R-E-1 strainer CLOSED

    HV-RE1-10 Process air connect (capped) CLOSED

    HV-RE1-13 FI-RE1-1 bypass CLOSED

    HV-RE1-8 Process air supply to AW Tank Farm CLOSED

    HV-RE1-8A R-E-1 air outlet CLOSED

    HV-IA-RE1-3 Hose connection supply valve CLOSED

    HV-IA-RE1-4 PCV-RE1-1 bypass CLOSED

    HV-RE1-1 Supply air to HV-CPE1-2/CPE2-2 OPEN

    HV-RE1-2 R-E-1 drain trap inlet OPEN

    HV-RE1-5 R-E-1 drain trap outlet OPEN

    HV-RE1-6 FI-RE1-1 inlet OPEN

    HV-RE1-7 FI-RE1-1 outlet OPEN

    HV-IA-RE1-1 PCV-RE1-1 inlet OPEN

    HV-IA-RE1-5 PCV-RE1-1 outlet OPEN

    HV-IA-RE1-6 PI-IA-1 supply OPEN

    HV-IA-RE1-7 PI-RE1-1 supply OPEN

    * Green seal on valve indicates CLOSED; Red seal indicates OPEN.

    Shift Manager Review: / / ________________

    Signature Print (First & Last) Date

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    37 of 53

    Figure 1 - Glycol/Water Compressor Cooler Valving

    TK-C-100

    1-8

    P-C-100

    2-33

    FV-C100-5

    2-242-26

    2-28

    1-12

    2-30

    2-2

    9

    1-10

    Floor

    Drain

    1-9

    PI-FC1-1

    F-C-1

    Filter

    Floor Drain

    ½"

    Vent

    Line

    ½"

    Sludge

    Drain

    Line

    1-11

    HV-RC3-3

    1-17

    1-16

    1-13

    2-25

    1-13A 1-15

    PI-FC1-2

    To LERF

    TK-241-AW-102

    To TK-C-100

    FIT

    C1

    00

    -5

    Check

    Valve

    1-15A1-12A

    To

    PT

    -FC

    1-4

    -1A

    Valve Key

    Check

    Gate

    Pressure Regulated

    2-Way Ball

    3 Way

    Ball Valve

    PCV-RC3-1

    1-211-18

    1-19

    1-20

    PIPC-2

    1-55

    PIPC-1

    1-54

    1-28

    PIPC-3

    1-56

    2-35 2-36

    1-29

    1-27FE-RC3-1

    For accuracy and detail,

    See Drawing H-2-98990

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    38 of 53

    Figure 2 - Process Air System Compressors and Air Receiver R-E-1

    T

    Drain

    HV-RE1-5 HV-RE1-2

    COMPRESSED AIR SYSTEM

    HV-RE1-3

    HV-RE1-4

    Glycol Out

    Glycol In

    Oil

    Cooler

    HV-RE1-1

    R-E-1

    FIRE-1-1

    HC

    HV

    -RE

    1-2

    1

    HV-RE1-8A

    HV-RE1-9

    H

    PSVRE1-1

    ATM

    Glycol Out

    Glycol In

    Oil

    Cooler

    HV-RE1-13

    CP-E-1CP-E-2

    Air

    Receiver

    AW

    Farm

    HV

    -PA

    -AW

    -1

    HV-RE1-7HV-RE1-6

    ProcessAir

    PI

    RE1-1

    PSLL

    RE1-2

    H2

    V-R

    E1-2

    HV

    -RE

    1-1

    0

    HC

    HV-RE1-8

    HV-RE1-12

    HV-PA-POR-2

    F-CPE1-1

    F-CPE2-1F F

    HV-CPE2-5

    HV-CPE2-7 HV-CPE1-7

    HV-CPE1-5

    V-P

    A-A

    W-2

    HV-PA-AW-3HV-PA-POR-1

    Porta

    ble

    Air

    Com

    press

    or 1

    HV-CP2-1 HV-CP1-1

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    39 of 53

    Figure 3 - Adding Cooling Oil to Airend

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    40 of 53

    Figure 4 - Sigma Control Display, Keys/Buttons and Indicators

    Item Description Function

    1 «ON» Switches on the machine.

    The programmed operating mode is active.

    2 «OFF» Switches the machine off.

    3 «Clock» Switches clock control on and off.

    4 «Remote control» Switches remote control on and off.

    5 «LOAD/IDLE» Toggles compressor between LOAD and IDLE operating modes.

    6 «DOWN» Scrolls down the menu options.

    Reduces a parameter value.

    7 «UP» Scrolls up the menu options.

    Increases a parameter value.

    8 «escape» Returns to the next higher menu option level.

    Exits the edit mode without Saving.

    Returns to the main menu when held down at least 10 seconds.

    9 «enter» Only affects the value in the third line of the display.

    Enters the selected menu option.

    Exits the edit mode and saves.

    10 «Events & Information» Displays the event memory.

    Selection is possible from every menu.

    Return with “esc” key/button.

    11 «Acknowledge/Reset» Signifies recognition of alarms and warning messages.

    Resets the event memory (When Permitted).

    Figure 4 continued on next page.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    41 of 53

    Figure 4 - Sigma Control Display, Keys/Buttons and Indicators (Cont.)

    Item Description Function

    12 Display field Alphanumeric display with 4 lines.

    13 Alarm Flashes red when an alarm occurs.

    Lights continuously when acknowledged.

    14 Communication Lights red if communication via the profibus interface is interrupted.

    15 Warning

    and

    Maintenance

    Flashes yellow for:

    ● maintenance work due,

    ● warning messages.

    Lights continuously when acknowledged.

    16 Controller power Lights green when the power supply to the controller is switched on.

    17 LOAD Lights green when the compressor is running under LOAD.

    18 IDLE Lights green when the compressor is running in IDLE.

    Flashes when the «LOAD/IDLE» toggle key/button is pressed.

    19 Machine ON Lights green when the machine switched on.

    20 Clock The LED lights when the machine is in clock control.

    21 Remote control The LED lights when the machine is in remote control.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    42 of 53

    Figure 5 - Sigma Control Main Menu Overview

    100 psi 80 ºF

    key -OFF ¦ p1 – off total 13000 h load 12034 h ↕

    100 psi 80 ºF ------------------------- off

    ------------------------- ↕

    PASSWORD

    CLOCK

    CONFIGURATION

    COMPONENTS

    PACKAGE TEST

    COMMUNICATION

    LANGUAGE

    STATUS

    ANALOG DATA

    OPERATING DATA

    MAINTENANCE

    MESSAGES

    STATISTICS

    PRINT

    esc

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    43 of 53

    Figure 6 - Configuration Menu Tree

    Configuration

    - general

    version

    model:

    PN:

    SN:

    weekday: ……

    date: ……

    time: ……

    summer/winter

    date format:

    time format:

    unit of pressure:

    unit of temperature:

    - pressure settings

    ● compressor

    pRV

    pressure increase

    nominal pressure

    setpoint pressure p1

    setpoint pressure p2

    system pressure low

    cut-in pressure minimum

    ● vacuum package

    system pressure high

    setpoint pressure p2

    setpoint pressure p1

    pressure fall

    ● load control

    - load control

    local mode

    remote mode

    remote key: y/n

    - settings

    p1/p2 clock, p1/p2

    cycle, p1/p2 RC,

    idle load,

    local-load RC

    venting mode

    - idle key active: y/n

    esc

    To “COMPONENTS” Menu

    To “CLOCK” Menu

    - control mode

    control mode :> …...

    settings:

    Dual

    Quadro

    Vario

    unload period

    refrigeration dryer

    modulating valve

    - compressor start

    compressor ON

    local mode:

    key, key+clock

    clock key: y/n

    remote mode:

    key+clock, RC

    remote key: y/n

    clock key: y/n

    remote contact:

    input

    compressor OFF

    venting: y/n

    holidays

    holiday period

    - reset

    remote mode

    remote key: y/n

    input

    - I/O periphery

    - binary output function

    - show quantities

    - external messages

    - switch

    - analog output parameter

    - timer

    OFF

    ON

    output

    = ENTER/RETURN key: initiates move to the next sub menu and enters parameters and passwords.

    = ESCAPE key: returns to the next higher level or to the main menu.

    esc

    = UP ARROW key: scrolls text display downwards.

    = DOWN ARROW key: scrolls text display upwards.

    i = INFORMATION key: calls up additional information or the event memory.

    Bold Text: can be changed by pressing ENTER key Normal Text: can be read only

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    44 of 53

    Signature Sheet 1

    Participating personnel enter their signature, printed name (first & last), and initials below.

    Signature Printed Name (First & Last) Initials

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    45 of 53

    Attachment 1 – Alarm Messages for Machine Shutdown

    Basic Information

    There are three types of fault:

    ● Alarm: Red LED flashes – See chapter vendor manual chapter 9.2.

    ● Warning: Yellow LED flashes - See chapter vendor manual chapter 9.3.

    ● Other faults: No indication - See chapter vendor manual chapter 9.4.

    Sheet 1 of 4

    Message Possible cause Remedy

    blowoff prot.

    The activating pressure of the safety relief valve on

    the oil separator tank has been exceeded.

    Change the oil separator cartridge.

    Open the shut-off valve in the venting line.

    sh.cct.AI1

    sh.cct.AI2

    The connection between the sensor and the analog

    input is shorted.

    Check line and connections.

    AI3/AI4 error Line-break between analog input and the sensor.

    Short circuit to earth.

    Check line and connections.

    sh.cct.AI5

    sh.cct.AI6

    The connection between the sensor and the analog

    input is shorted.

    Check line and connections.

    AI7/AI8 error Line-break between the analog input and the sensor.

    Short circuit to earth.

    Check line and connections.

    Model Machine model uncertain. Call authorized KAESER Service representative.

    bus alarm The bus link from the Profibus DP interface is

    defective.

    Check line and settings.

    PD

    Package discharge temperature too low. Call authorized KAESER Service representative.

    PD-

    Package discharge temperature too high. Check the cooling oil level.

    Clean the cooler.

    Check the fan motor.

    DO0.6/DO0.7 I

    Short circuit in the line between the digital output and

    the consumer. Check line and connections.

    DO1.6/DO1.7 I

    Short circuit in the line between the digital output and

    the consumer. Check line and connections.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    46 of 53

    Attachment 1 – Alarm Messages for Machine Shutdown (Cont.)

    Sheet 2 of 4

    Message Possible cause Remedy

    Airend rotation The motor is turning in the wrong direction. Change over phase lines L1 and L2.

    error: RS-485-USS SFC machine with USS protocol:

    RS485 transmission

    SIGMA CONTROL frequency converter fault

    Check the connection between the frequency

    converter and SIGMA CONTROL.

    Check configuration of the RS485.

    Call authorized KAESER Service representative.

    ext. message 0

    ext. message 1

    ext. message 2

    ext. message 3

    ext. message 4

    ext. message 5

    Customer specific:

    No adjustments possible.

    -

    back pressure Back pressure in the oil separator tank caused by

    defective venting.

    Check venting line.

    HT cell Fault in the high tension cell. Call authorized KAESER Service representative.

    V-belts ruptured The drive belts have parted during machine operation Replace drive belts.

    no press. buildup Machine produces no compressed air.

    The setpoint pressure does not rise above 50 psig for a

    preset period

    Check machine for leaks.

    Check coupling/V-belts

    Call authorized KAESER Service representative.

    Condensate drain The condensate drain is defective. Check the condensate drain.

    coolingwater low Cooling water pressure too low. Check cooling water supply.

    Cooling water throttling valve: check setting.

    RD p

    Pressure switch for the refrigerant compressor has

    activated. Keep ambient conditions within specified limits.

    Clean the refrigerant condenser.

    Clean the cooler.

    RD T

    Temperature in the refrigeration dryer too high. Ensure adequate ventilation.

    Clean the refrigerant condenser.

    Clean the cooler.

    Install an extractor fan.

    Fan M2 I

    Overload shutdown of the first fan motor Investigate cause of shutdown.

    Reset overload trip.

    Call authorized KAESER Service representative.

    Fan M3 I

    Overload shutdown of the second fan motor Investigate cause of shutdown.

    Reset overload trip.

    Call authorized KAESER Service representative.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    47 of 53

    Attachment 1 – Alarm Messages for Machine Shutdown (Cont.)

    Sheet 3 of 4

    Message Possible cause Remedy

    fan M4 I

    Overload shutdown of the third fan motor Investigate cause of shutdown.

    Reset overload trip.

    Call authorized KAESER Service representative.

    fan M7 I

    Overload shutdown of the control cabinet fan motor Investigate cause of shutdown.

    Call authorized KAESER Service representative.

    motor I

    Overload shutdown of the compressor drive motor. Investigate cause of shutdown.

    Change the oil separator cartridge.

    Call authorized KAESER Service representative.

    motor T

    Drive motor overheated. Clean the motor.

    Keep ambient conditions within specified limits.

    motor bearings Drive motor bearings overheated. Grease the motor bearings.

    Call authorized KAESER Service representative.

    mains cont. on? Mains contactor not pulling in. Check mains contactor and wiring.

    mains cont. off? Mains contactor not dropping out. Check mains contactor and wiring.

    mains voltage

    2nd power failure. Check power supply voltage.

    Check door interlock switch.

    mains monitor Fault in mains power supply. Have the mains power supply checked.

    Emergency stop EMERGENCY STOP button pressed. Unlatch the pushbutton.

    OST dp

    Oil separator cartridge clogged. Change the oil separator cartridge.

    OST T

    Maximum air temperature at the oil separator tank

    outlet is exceeded. Check the line to the trip relay.

    Oil p

    No changeover to LOAD as long as the minimum oil

    pressure is not reached.

    Check the oil circuit.

    Check pressure switch, line, and connection.

    p-switch Customer specific:

    no adjustments possible. -

    pRV

    The activating pressure of the oil separator tank safety

    relief valve has been exceeded. Change the pressure relief valve.

    FC Frequency converter fault Call authorized KAESER Service representative.

    SIGMA CONTROL T

    Keep ambient conditions within specified limits.

    Control cabinet: check filter mat and fan.

    Softstart Fault in the soft start equipment Call authorized KAESER Service representative.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    48 of 53

    Attachment 1 – Alarm Messages for Machine Shutdown (Cont.)

    Sheet 4 of 4

    Message Possible cause Remedy

    start T

    Airend discharge temperature (ADT) too low.

    Ambient temperature: < +36 F Keep ambient conditions within specified limits.

    T switch Customer specific:

    no adjustments possible. -

    ADT

    The airend discharge temperature (ADT) did not reach

    the minimum required level within the specified time.

    Call authorized KAESER Service representative.

    ADT

    Maximum permissible airend discharge temperature

    exceeded.

    Keep ambient conditions within specified limits.

    Clean the cooler.

    Check the cooling oil level.

    ADT dT/dt Airend discharge temperature rising too quickly. Check the cooling oil level.

    Call authorized KAESER Service representative.

    access doors Door opened/panel removed while the machine is

    running.

    Fit and secure all panels and close access doors.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    49 of 53

    Attachment 2 – Warning Messages (Yellow Lights)

    Sheet 1 of 4 Message Possible cause Remedy

    blowoff prot.

    The blowoff pressure of the safety relief valve

    will soon be reached.

    Change the oil separator cartridge.

    Open the shut-off valve in the vent-ing line.

    bus alarm The bus link from the Profibus DP in-terface is

    interrupted.

    Check bus highway and plug.

    PD temperature

    Package discharge temperature too low. Call authorized KAESER Service

    representative.

    PD temperature

    Package discharge temperature too high. Clean the cooler.

    Check the cooling oil level.

    elect. equip. h

    The maintenance interval for checking electrical

    equipment and wiring has expired.

    Carry out the check and reset the maintenance

    interval counter.

    error: FEPROM Internal controller memory error. Call authorized KAESER Service

    representative.

    error: RS 485-PP Wrong configuration or transmission error. Check the link/interface connections between

    the two controllers.

    Check maximum cable length and screening.

    1 master and 1 slave configured.

    error SMS SMS can not be sent. Call authorized KAESER Service

    representative.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    50 of 53

    Attachment 2 – Warning Messages (Yellow Lights) (Cont.)

    Sheet 2 of 4

    Message Possible cause Remedy

    ext. message 0

    ext. message 1

    ext. message 2

    ext. message 3

    ext. message 4

    ext. message 5

    Customer specific:

    No adjustments possible.

    -

    FC AI1 fault SCF machine:

    Network pressure sensor on AI1 defective. Call authorized KAESER Service representative.

    FC MM Service SCF machine:

    Service mode for frequency converter.

    Deactivate the service mode as soon as setting of

    the frequency converter is complete.

    FC mains SCF machine:

    Failure of power supply to the frequency

    converter.

    Check power supply

    annual maint Last maintenance was one year ago. Carry out the necessary maintenance and reset the

    corresponding maintenance interval counter.

    no press. buildup The compressor cannot build-up to working

    pressure.

    Check for air leaks

    Check the value for internal pressure given in the

    menu against the reading on the oil

    separator tank pressure gauge.

    condensate drain. The condensate drain is defective. Check the condensate drain and drain line.

    RD T

    Refrigeration dryer:

    Compressed air temperature too low.

    Call authorized KAESER Service representative.

    RD p

    Refrigeration dryer:

    Pressure in the refrigerant circuit too low.

    Inlet pressure switch tripped.

    Call authorized KAESER Service representative.

    RD p

    Refrigeration dryer:

    Pressure in the refrigerant circuit too high.

    Safety pressure switch tripped.

    Keep ambient conditions within specified limits.

    Clean the refrigerant condenser.

    Check the fan motor.

    Call authorized KAESER Service representative.

    bearing.maint. h

    The maintenance interval for greasing the

    bearings has expired. Grease the motor bearings.

    ext.load signal? External load signal indistinct:

    Increased cut-out pressure exceeded.

    The external load control has not switched to idle

    (off load)

    Check settings of the external controller. Take into

    account pressure drops across filters and dryers.

    air filter dp

    Air filter clogged. Air filter maintenance.

    air filter dp

    Air filter clogged. Air filter maintenance.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    51 of 53

    Attachment 2 – Warning Messages (Yellow Lights) (Cont.)

    Sheet 3 of 4

    Message Possible cause Remedy

    air filter h

    Maintenance interval for air filter cleaning has

    elapsed.

    Check the air filter.

    modem problem SIGMA CONTROL does not recognize the

    modem.

    Check the link between SIGMA CONTROL

    and the modem.

    motor T

    Drive motor overheating. Clean the motor.

    Keep ambient conditions within specified

    limits.

    motor starts /h

    The permissible number of motor starts was

    exceeded in the last 60 minutes.

    Extend the idle period.

    Increase capacity of air receiver.

    Increase cross-section of piping between

    compressor and air receiver.

    motor starts /d

    The permissible number of motor starts was

    exceeded in the last 24 hours.

    Extend the idle period.

    Increase capacity of air receiver.

    Increase cross-section of piping between

    compressor and air receiver.

    bearingchange h

    The maintenance interval for checking the

    bearings has expired.

    Have the motor bearings checked by an

    authorized KAESER Service representative.

    system press.

    Network pressure has fallen below the ‘low’

    value.

    Air consumption too high.

    Check air demand.

    Check transducer connections and wiring.

    Check the ‘systpress. low’ warning setting.

    system press.

    Network pressure is above the ‘sys,press. high’

    value.

    Check for air leaks.

    Check the ‘systpress. high’ warning setting.

    Check if the machine switches to LOAD.

    mains voltage

    1. Power failure:

    machine was re-started automatically.

    Check power supply.

    Check the door interlock switch.

    separator dp

    The pressure drop across the oil separator

    cartridge has risen.

    Oil separator cartridge clogged.

    Change the oil separator cartridge.

    separator h

    The interval for the next oil separator cartridge

    check has expired.

    Change the oil separator cartridge.

    oil filter dp

    The pressure drop across the oil filter has risen.

    Oil filter clogged.

    Change the oil filter.

    oil filter h

    The interval for the next oil filter check has

    expired.

    Change the oil filter.

    oil level

    Cooling oil level too low. Top up the cooling oil.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    52 of 53

    Attachment 2 – Warning Messages (Yellow Lights) (Cont.)

    Sheet 4 of 4

    Message Possible cause Remedy

    oilT

    Cooling oil temperature too low. Check temperature switch, line and connection.

    Check the oil circuit.

    Increase room temperature.

    oil change h

    The interval for the oil change has expired. Change the cooling oil

    p-switch Customer specific:

    no adjustments possible.

    -

    buffer battery Data retention battery id insufficient.. Change the battery.

    error: RAM Internal RAM defective. Call authorized KAESER Service

    representative.

    oil content

    The compressed air oil content limit will soon be

    reached.

    Check the scavenge tube in the oil separator

    cartridge.

    Check the dirt trap strainer in the scavenge line.

    Check air treatment upstream of the measuring

    point.

    V-belt tension Belt tension is too low. Re-tension drive belts.

    bit.coup.insp.h

    The maintenance interval for V-belt

    tension/coupling inspection has expired.

    Carry out visual check.

    Re-tension drive belts.

    start T

    The airend temperature is too low (< +14 F) for

    the machine to be operated.

    Keep ambient conditions within specified

    limits.

    start T

    The airend temperature is too low (< +36 F) Keep ambient conditions within specified

    limits.

    set output The ‘set output’ test function is activated. Stop the ‘set output’ mode.

    T switch Customer specific:

    No adjustments possible.

    -

    TRAP interrupt System message:

    TRAP interrupt

    Call authorized KAESER Service

    representative.

    ADT

    Airend discharge temperature has almost reached

    maximum.

    Clean the cooler.

    Check the cooling oil level.

    Replace oil filter.

    Ensure adequate ventilation.

    Keep surrounding temperature within

    recommended limits.

    access doors Door opened with the machine stopped. Close access doors.

  • Operate 242-A Evaporator Compressed Air System

    Type

    CONTINUOUS Document No.

    TO-620-160 Rev/Mod

    O-5 Release Date

    09/26/2018 Page

    53 of 53

    Attachment 3 – Other Faults

    Message Possible cause Remedy

    Machine runs but produces

    no compressed air

    Inlet valve not opening or only opening partially. Call authorized KAESER Service

    representative.

    Venting valve not closing. Call authorized KAESER Service

    representative.

    Leaks in the pressure system. Check pipework and connections for leaks and

    tighten any loose fittings.

    Air consumption is greater than the capacity of

    the compressor.

    Check the air system for leaks.

    Shut down the consumer(s).

    Hose coupling or maintenance hose still plugged

    into the quick-release coupling on the oil

    separator tank

    Remove coupling or maintenance hose.

    Cooling oil runs out of the

    air filter.

    Oil level in the oil separator tank too high. Drain off oil until the correct level is reached.

    Inlet valve defective. Call authorized KAESER Service

    representative.

    Compressor switches

    between LOAD and IDLE

    more than twice per

    minute.

    Air receiver too small. Increase size of air receiver.

    Airflow into the compressed air network

    restricted.

    Increase air pipe diameters.

    Check filter elements.

    The differential between cut-in and cut-out

    pressure is too small. Check switching differential.

    Cooling oil leaking into the

    floor pan.

    Hose coupling or maintenance hose still plugged

    into the quick-release coupling on the oil

    separator tank

    Remove coupling or maintenance hose.

    Oil cooler leaking. Call authorized KAESER Service

    representative.

    Leaking joints. Tighten joints.

    Replace seals.

    Cooling oil consumption

    too high.

    Unsuitable oil is being used. Use SIGMA FLUID cooling oil.

    Oil separator cartridge split. Change the oil separator cartridge

    Oil level i