    TAHX SeriesTopaire Air Cooled Screw Chillers

    Cooling Capacity: 107 to 403 TR (376 to 1419 kW)

  • 01

    Topaire air cooled screw chillers are designed to meet current and future requirements in terms of reliability, energy e�-ciency and intelligent control. We use the best technologies available today: Twin-rotor screw compressors with a variable capacity valve are ideally matched to coolers and condensers optimally con�gured for superior heat transfer and unit e�ciency. It is ideal for schools, hospitals, shopping malls, o�ce buildings as well as factories and manufacturing plants.

    Introduction

  • 02

    Midea air cooled screw chillers are designed to meet current and future requirements in terms of reliability, energy e�-ciency and intelligent control. We use the best technologies available today: Twin-rotor screw compressors with a variable capacity valve are ideally matched to coolers and condensers optimally con�gured for superior heat transfer and unit e�ciency. It is ideal for schools, hospitals, shopping malls, o�ce buildings as well as factories and manufacturing plants.

    Contents

    Specifications Electrical data Water pressure drop Performance table Dimensions Options

    Installation

    20 Typical piping system21 Selection software

    03 Features and bene�ts05 Normal condition

  • 03

    Features and benefitsEnvironmental responsibility

    A more e�cient chiller means less power consumption, which reduces greenhouse gas(CO2) emissions.R134a friendly refrigerant has no ozone-depletion potential.High e�ciency,world class,sustainable and reliable performance.

    Lowest total cost of ownershipReliability, low risk of uncomfortable downtime.

    The best parts, Bitzer Comp. &Danfoss EXV, Shneider electric.

    World-class testing facilities ensure the performance and reliability.

    Each unit was extensively tested to verify its operational reliability and to ensure a smooth startup.

    Serviceability, low maintenance costs.

    Larger dimension impellers reduced speed causing less noise.The lower ambient temperature, the lower fan air �ow, then reduce noise. Intelligent control logic balance the performance and working fan numbers to control the noise and power consumption.Super low noise model is optional.

    Silent operation

  • 04

  • TAHX 110 D3 TAHX 140 D3 TAHX 170 D3TAHX 210 D3

    07

    Specifications

    Normal condition

    TAHX__D3 110 140 170 210

    Cooling capacitykW

    Power input kW

    COP

    IPLV

    kW/kW

    kW/kW

    Semi-hermetic screw compressor

    Circuit A Quantity 1 1 1 1

    Circuit B Quantity -- -- -- --

    Oil recharge Type BSE170 BSE170 BSE170 BSE170

    Circuit A L 30 30 30 32

    Circuit B L -- -- -- --

    Refrigerant Type R134a R134a R134a R134a

    Circuit A kg 76 90 105 140

    Circuit B kg -- -- -- --

    Control Type EXV EXV EXV EXV

    Evaporator Type

    Water content L 222 308 340 520

    Water �ow m³/h

    Pressure drop kPa

    Max. woking pressure (water side) MPa 1 1 1 1

    Pipe connection type

    Water inlet/outlet pipe dim. mm 125 125 125 150

    Condenser Type Fin-coil Fin-coil Fin-coil Fin-coil

    Fan Quantity 6 8 10 10

    Total air �ow m³/h 23000*6 23000*8 23000*10 23000*10

    Fan speed rpm 940 940 940 940

    Unit size(L×W×H) mm

    Shipping weight kg

    Running weight kg

    Shell and tube heat exchanger(DX)

    Victaulic coupling

    Note:1) Nominal cooling capacities are based on the following conditions:Chilled water inlet/outlet temp: 12°C/7°C; Outdoor temp (DB/WB):35°C/24°C,Evaporator fouling factor=0.018 m2.°C/kW2) The applicable ambient temperature range of R134a air-cooled screw units is 15°C ~ 43°C。

    05

    RT 106 140 168 204

    492.6 590.6 716.1

    158.6 186.7 233.5

    3.10 3.16 3.06

    4.195 4.292 4.167

    373.4

    123.7

    3.01

    4.086

    77.30 92.90 111.4

    44.2 46.7 47.8

    58.80

    32.1

    4865x2280x2400 5800x2280x2400 5800x2280x2400

    4280 4980 5400

    3810x2280x2400

    3300

    3520 4590 5320 5920

  • TAHX 260 D3 TAHX 400 D3TAHX 285 D3TAHX 345 D3

    08

    Note:1) Nominal cooling capacities are based on the following conditions:Chilled water inlet/outlet temp: 12°C/7°C; Outdoor temp (DB/WB):35°C/24°C,Evaporator fouling factor=0.018 m2.°C/kW.2) The applicable ambient temperature range of R134a air-cooled screw units is 15°C ~ 43°C。

    TAHX__D3

    Cooling capacity

    Power input

    COP

    IPLV

    Semi-hermetic screw compressor

    Circuit A

    Circuit B

    Oil recharge

    Circuit A

    Circuit B

    Refrigerant

    Circuit A

    Circuit B

    Control Type

    Evaporator

    Water content

    Water �ow

    Pressure drop

    Max. woking pressure (water side)

    Pipe connection type

    Water inlet/outlet pipe dim.

    Condenser

    Fan

    Total air �ow

    Fan speed

    Unit size(L×W×H)

    Shipping weight

    Running weight

    kW

    kW

    kW/kW

    Quantity

    Quantity

    Type

    L

    L

    Type

    kg

    kg

    Type

    L

    m³/h

    kPa

    MPa

    mm

    Type

    Quantity

    m³/h

    rpm

    mm

    kg

    kg

    285

    1

    1

    BSE170

    30

    30

    R134a

    90

    90

    EXV

    600

    1

    150

    Fin-coil

    16

    23000*16

    940

    345

    1

    1

    BSE170

    30

    30

    R134a

    105

    105

    EXV

    770

    1

    200

    Fin-coil

    16

    23000*16

    940

    Shell and tube heat exchanger(DX)

    Victaulic coupling

    400

    1

    1

    BSE170

    32

    32

    R134a

    140

    140

    EXV

    910

    1

    200

    Fin-coil

    20

    23000*20

    940

    260

    kW/kW

    1

    1

    BSE170

    30

    30

    R134a

    76

    90

    EXV

    620

    1

    150

    Fin-coil

    14

    23000*14

    940

    06

    RT 281 340 401253

    989.5

    317.3

    3.11

    1196

    380.1

    3.14

    1411

    464.9

    3.03

    890.9

    284.4

    3.13

    4.253 4.289 4.1534.268

    154.7

    60.8

    185.9

    58.2

    219.8

    56.4

    138.5

    60.1

    9640x2280x2400

    8800

    9400

    9640x2280x2400

    9060

    9830

    11700x2280x2400

    10900

    11810

    8800x2280x2400

    7680

    8300

  • 09

    Electrical data Water pressure drop

    LSBLGW380/C

    LSBLGW500/C

    LSBLGW600/C

    LSBLGW720/C

    LSBLGW900/C

    LSBLGW1000/C

    LSBLGW1200/C

    LSBLGW1420/C

    Unit Model

    120

    100

    80

    60

    40

    20

    0Evap

    orat

    or W

    ater

    Pre

    ssur

    e D

    rop/

    kpa

    Evap

    orat

    or W

    ater

    Pre

    ssur

    e D

    rop/

    kpa

    120

    100

    80

    60

    40

    20

    0

    1. Customer to specify the exact nominal power supply available on site so that electrical components are selected accurately.2. Main power must be supplied from a single �eld supplied and mounted fused circuit breaker.3. The compressor crankcase heaters must be energized for hours before the unit is initially started or after a prolonged power disconnection.4. All �eld wiring must be in accordance with local standards.5. Neutral line required on 400V-3Ph-50Hz(5 wires) power supply.6. Rated load Amps values are on nominal conditions.7. The ±10% voltage variation from the nominal is allowed for a short time only,not permanently.

    07

    TAHX_D3 110 140 170 210

    Standard voltage

    Voltage range V

    Max. running current A

    Max. power consumption kW

    Rated current A

    Compressor A

    Locked rotor Amps. A

    Max. allowed current A

    Rated current A

    Rated power kW

    Compressor B

    Locked rotor Amps. A -- -- -- --

    Max. allowed current A -- -- -- --

    Rated current A -- -- -- --

    Rated power kW -- -- -- --

    Fan

    Full load Amps.(each) A 4.9 4.9 4.9 4.9

    Power input(each) kW 2.4 2.4 2.4 2.4

    Total input kW 14.4 19.2 24 24

    Crankcase heater

    Voltage V 220 220 220 220

    Total input kW 0.3 0.3 0.3 0.3

    Total Amps. A 1.36 1.36 1.36 1.36

    415V 3Ph 50Hz

    380~415

    TAHX_D3 260 285 345 400

    Standard voltage

    Voltage range V

    Max. running current A

    Max. power consumption kW

    Rated current A

    Compressor A

    Locked rotor Amps. A

    Max. allowed current A

    Rated current A

    Rated power kW

    Compressor B

    Locked rotor Amps. A

    Max. allowed current A

    Rated current A

    Rated power kW

    Fan

    Full load Amps.(each) A 4.9 4.9 4.9 4.9

    Power input(each) kW 2.4 2.4 2.4 2.4

    Total input kW 33.6 38.4 38.4 48

    Crankcase heater

    Voltage V 220 220 220 220

    Total input kW 0.6 0.6 0.6 0.6

    Total Amps. A 2.72 2.72 2.72 2.72

    415V 3Ph 50Hz

    380~415

    299.8 384.4 430.1 546.7

    123.7 158.6 186.7 233.5

    220.5 281.7 331.9 414.5

    615.0 845.0 845.0 965.0

    389.0 473.0 473.0 480.0

    191.1 242.5 282.9 365.5

    109.3 139.4 162.7 209.5

    684.3 768.6 840.4 1094

    284.4 317.2 380.1 464.9

    504.4 563.4 676.7 825.6

    615.0 845.0 845.0 965.0

    389.0 473.0 473.0 480.0

    193.7 242.5 299.2 363.8

    111.5 139.4 170.9 208.4

    845.0 845.0 845.0 965.0

    473.0 473.0 473.0 480.0

    242.1 242.5 299.2 363.8

    139.3 139.4 170.9 208.4

  • TAHX 140 D3TAHX 170 D3

    TAHX 110 D3TAHX 210 D3

    TAHX 260 D3TAHX 345 D3

    TAHX 285 D3TAHX 400 D3

    08

    TAHX 110 D3TAHX 140 D3TAHX 170 D3TAHX 210 D3TAHX 260 D3TAHX 285 D3TAHX 345 D3TAHX 400 D3

  • TAHX 110 D3

    TAHX 140 D3

    9

  • TAHX 170 D3

    TAHX 210 D3

    10

  • TAH

    X26

    0D

    3

    11

  • TAH

    X28

    5D

    3

    12

  • TAH

    X34

    5D

    3

    13

  • TAH

    X40

    0D

    3

    14

  • 15

  • Mounting location

    Note: All dimensions are in mm

    2

    2

    2

    2

    2

    2

    16

    Foundation

    Unit bottomFoundationbolt M14

    Control boxA B C D E

    L

    G

    H I J

    F

    K

    150200 2000 1800 1800 1800 1800

    11700

    2180

    2280

    150

    M N

    1800

    7720

    2180

    2280

    180017001500150

    150

    1300

    Control box FoundationUnit bottom Foundation bolt M14

    A B

    FE

    C

    G

    D

    H

    TAHX 110D3 TAHX 140D3 TAHX 170D3

    TAHX 210D3

    TAHX 260D3

    TAHX 285D3 TAHX 345D3

    FoundationUnit bottom

    Foundationbolt M14

    Control box

    1503810

    2180

    2280

    150

    8931600

    B

    C D

    A B

    ED

    C

    F

    A

    20701504865

    2180

    2280

    150

    1630 530

    FoundationUnit bottomFoundation bolt M14

    Control box FoundationUnit bottom

    Control box

    Foundationbolt M14

    E F

    A B C

    D

    100020001500150

    2180

    150

    2280

    5800

    Unit bottom

    Foundation Foundation

    bolt M14

    Control boxA B C D E

    F G H I J

    564 1570 1180 1800 2570150 8800

    2180

    2280

    150

    A B C D E

    L G H I J

    Foundation

    Unit bottom

    Foundation bolt M14

    Control box F

    K

    150

    400 1800 1500 1500 1800 1800

    9640

    2180

    150

    2280

    TAHX 400D3

    Foundation

    Unit bottom

    Foundation bolt M14

    Control boxA B C D E

    L

    G

    H I J

    F

    K

    150

    200 2000 1800 1800 1800 1800

    11700

    2180

    2280

    150

    M N

    1800

  • 17

    Unit bottom

    Foundation

    Sping isolator

    Unit bottom

    Steel Plate (thickness ≥ 5mm)

    Rubber pad

    Foundation

    Installation requirements:1. Be sure to take the base preparation and structure into consideration seriously during installation,particularly on rooftop

    installa tions in order to avoid noise and vibration. Consulting the building designer before conducting installation is recom-

    mended.

    2. A drainage ditch should surround the base to ensure dewatering occurs.

    3. Anti-vibration pad is to be placed between the base frame and foundation in order to avoid vibrations and unnecessary

    noise, and make sure the unit is horizontal during installation.

    Load distribution Unit:KG- - - - - - - - - -

    - - - - - - - -

    - - - - - - - -

    - - - - - -

    - - - -

    - -

    - -

    Model A B C D E F G H I J K L M N

    TAHX 110 D3 869 901 869 901

    TAHX 140 D3 633 855 832 633 855 832

    TAHX 170 D3 815 934 921 815 934 921

    TAHX 210 D3 687 765 800 758 687 765 800 758

    TAHX 260 D3 814 944 947 747 733 814 944 947 747 733

    TAHX 285 D3 726 912 917 732 731 732 726 912 917 732 731 732

    TAHX 345 D3 789 912 905 779 777 773 789 912 905 779 777 773

    TAHX 400 D3 794 925 954 936 800 798 798 794 925 954 936 800 798 798

    TAHX 110D3 TAHX 140D3 TAHX 170D3 TAHX 210D3 TAHX 260D3

    TAHX 285D3 TAHX 345D3 TAHX 400D3

    B

    C D

    A B

    ED

    C

    F

    A

    E F

    A B C

    D E F

    A B C D

    HG

    A B C D E

    F G H I J

    A B C D E

    L G H I J

    F

    K

    A B C D E

    L G H I J

    F

    K

    A B C D E

    L

    G

    H I J

    F

    K M N

  • 18

  • 21

    Selection softwareProfessional selection software makes the product selection process much easier and more e�cient than conventional

    manual selection. Simple operating interface and smart arithmetic greatly improves selection e�ciency. The user simply

    needs to provide several basic parameters, such as cooling capacity, fouling factor, power supply, etc. The program will

    then display all suitable models for easy selection. This software can be conveniently updated online. If you have any

    questions please feel free to contact us.

    19

  • 2016

    Air cooled screw chiller 50Hz

    www.topaire.com.my

    Manufacturer

    Manufacturer

    Manufacturer

    Kota BharuLot 1848, Jalan Hospital, Kg. Cherang, Taman Kenangan, 15200 Kota Bharu, Kelantan. Tel: +609-748 9295 Fax: +609-748 9297

    TOPAIRE SALES & SERVICES SDN BHDNo.A7-2-2, Block A, Megan Salak Park, Jalan 2/125E,

    Taman Desa Petaling, 57100 Kuala Lumpur.

    Tel

    Email

    : +603-90563228 (Hunting line) : +603-90562800 : [email protected]

    Melaka

    DT 3662, Jalan Angkasa Nuri 21, Taman Angkasa Nuri, 76100 Durian Tunggal, Melaka. Tel: +606-332 1027 Fax: +606-337 2360

    TAHX/0618