TABLE OF SET VALUES 3/1532-BMP 903 050 Uen Rev B 2006-12-11 1(26) Systems with ACU type BMP 903 050 Contents 1 Tables of set values 3 2 Device Explore 3 2.1 ACU System/Setting 3 2.2 Rect Group/Setting 4 2.3 Batt Group/Setting 5 2.4 LVD 1/Setting 8 2.5 LVD 2/Setting 8 3 Settings 9 3.1 Network configuration 9 3.2 NMS configuration 9 3.3 MC configuration 9 3.4 User information configuration 10 3.5 Time synchronization 10 4 Maintenance/Modify configure online 11 4.1 Modify ACU 11 4.2 Modify device 11 4.3 Modify signal 12

Table of Set Values ACU RevB

Embed Size (px)

Citation preview

Page 1: Table of Set Values ACU RevB

TABLE OF SET VALUES

3/1532-BMP 903 050 Uen Rev B 2006-12-11

1(26)

Systems with ACU type BMP 903 050 Contents 1 Tables of set values 3

2 Device Explore 3 2.1 ACU System/Setting 3 2.2 Rect Group/Setting 4 2.3 Batt Group/Setting 5 2.4 LVD 1/Setting 8 2.5 LVD 2/Setting 8 3 Settings 9 3.1 Network configuration 9 3.2 NMS configuration 9 3.3 MC configuration 9 3.4 User information configuration 10 3.5 Time synchronization 10 4 Maintenance/Modify configure online 11 4.1 Modify ACU 11 4.2 Modify device 11 4.3 Modify signal 12

Page 2: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

2(26)

The contents of this document are subject to revision without notice due to continued progress in methodology, design, and manufacturing.

© Emerson Network Power Energy Systems AB 2006 – All rights reserved

Emerson Network Power Energy Systems AB

SE – 141 82 Stockholm Sweden

Tel. +46 8 721 6000 Fax. +46 8 721 7177 www.emersonenergy.com

Page 3: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

3(26)

1 Tables of set values These tables are based on the ACU software revision 1.30, for NetSure™ 201, NetSure™ 501 and NetSure™ 701, –48 V.

All settings and choices affect the functions of the power supply system. The values shall therefore not be changed without a consequence analysis.

If a default value is adjusted, the new value shall be entered in the column “Plant-specific setting”. The default settings listed are the factory default settings.

Note: The appearance of some settings will depend on what configuration package file has been downloaded to the ACU.

2 Device Explore Note: When browsing the control and settings of the system devices, some settings

will be blocked (the set button is grey). The reason is that the setting depends on another setting or that the user authority level does not approve a change of the setting.

2.1 ACU System/Setting Index Signal name

Value

(default) Remark Plant-specific

setting Sign. date

1 Auto/Man State Auto

2 Outgoing Alarm Blocked Normal

3 Under-voltage 1 Level 48.50 V Must be set ≥ UV 2 and < U nom.

4 Under-voltage 2 Level 43.50 V Must be set ≤ UV 1

5 Maintenance Time Delay 30 Day Alarm activation time

6 Maintenance Time Limit 360 Day Alarm periodicity

7 High Ambient Temperature Limit

35.00 deg.C Must be set > Low amb. temp.

8 Low Ambient Temperature Limit

5.00 deg.C Must be set < High amb. temp.

9 Over-voltage 1 Level 55.70 V Must be set > U boost charge

10 Over-voltage 2 Level 58.50 V Must be set > Over-voltage 1 Level

11 LCD Alarm Sound Off

Page 4: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

4(26)

Index Signal name

Value (default)

Remark Plant-specific setting

Sign. date

12 Load Shunt Full Current 1000.0 A

13 Load Shunt Full Voltage 75.0 mV

14 Bat 1 Shunt Full Current 1000.0 A

15 Bat 1 Shunt Full Voltage 75.0 mV

16 Bat 2 Shunt Full Current 1000.0 A

17 Bat 2 Shunt Full Voltage 75.0 mV

18 DI 1 Activation Level 48 V

19 DI 2 Activation Level 48 V

20 DI 3 Activation Level 48 V

21 DI 4 Activation Level 48 V

22 DI 5 Activation Level 48 V

23 DI 6 Activation Level 48 V

2.2 Rect Group/Setting Index Signal name

Value

(default) Remark Plant-specific

setting Sign. date

1 High Voltage limit 59.0 V Must be set 0.5 V > U boost charge

2 Low voltage limit 40.0 V

3 Over-vol restart time 300 s

4 Soft-Startup with load time 8 s

5 WALK-In enabled Disabled

6 Redundancy Enabled Disabled

7 Pre-Currlmt for Redund Enb

Disabled

8 Min Redundancy 100 % Min. accepted re-dundancy. (Must be

set < Max. red. –110%)

9 Max Redundancy 300 % Max. prefered re-dundancy. (Must be

set > Min. red. +110%)

Page 5: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

5(26)

Index Signal name

Value (default)

Remark Plant-specific setting

Sign. date

10 Switch-off Delay 5 min

11 Cycle Activation Time 1 CLK The time (0-23 o´clock) for cycling

12 Cycle Period 30 Day

13 Rect Start Sequentially Elapse

0 s

14 Rectifier Power Type Double supply

The rect. LC feed-ing

2.3 Batt Group/Setting Index Signal name

Value

(default) Remark Plant-specific

setting Sign. date

1 Battery Type No. 1

2 Nominal Voltage 54.5 V (System voltage) Must be set > Un-dervoltage 1 and <

U boost ch.

3 Temp Compensation Cen-ter

20.0 deg.C

4 Compensation Coefficient 96.0 mv/deg.C

5 Very High Temperature limit

55.00 deg.C Must be set > High Temp limit

6 High Temperature limit 40.00 deg.C Must be set < Very High Temp limit and

> Low temp. limit

7 Low temperature limit 0.00 deg.C Must be set < High Temp limit

8 Number of battery blocks 24

9 Planned Test Enabled Disable

10 AC Fail Test Enabled Disable

11 Test Voltage Level 45.00 V Rect. Voltage (Must be set ≤ Test End Voltage –0.2 V)

12 Test End Time 60 min

13 Test End Voltage 46.40 V Must be set ≥ Test Voltage Level

+0.2 V

Page 6: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

6(26)

Index Signal name

Value (default)

Remark Plant-specific setting

Sign. date

14 Test End Capacity 30.00 % Remaining batt. capacity

15 Pre-BC Enabled Disable

16 Constant current test en-abled

Disable

17 Constant current test cur-rent

10000.0 A

18 Number of schedule Test per year

0 Opens indexes 19 to 30

19 Planed Test1 -- MM-DD HH

20 Planed Test2 -- MM-DD HH

21 Planed Test3 -- MM-DD HH

22 Planed Test4 -- MM-DD HH

23 Planed Test5 -- MM-DD HH

24 Planed Test6 -- MM-DD HH

25 Planed Test7 -- MM-DD HH

26 Planed Test8 -- MM-DD HH

27 Planed Test9 -- MM-DD HH

28 Planed Test10 -- MM-DD HH

29 Planed Test11 -- MM-DD HH

30 Planed Test12 -- MM-DD HH

31 Record threshold 0.050 V

32 Short Test Enabled Disable Requires ≥2 battery shunts

33 Short Test Cycle 30 days

34 Max Diff Current For Short Test

0.05 C10

35 Short Test Duration 5 min

36 Boost Charge Voltage 56.4 V Must be set > U nom. and < U over-

voltage

37 Maximum Boost Charge Time

5 h

Page 7: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

7(26)

Index Signal name

Value (default)

Remark Plant-specific setting

Sign. date

38 Stable BC Current 0.010 C10 Limitation of BC current

39 Stable BC Delay 60 min Fixed time for pro-longed BC

40 Automatic Boost Charge Enabled

no

41 FC to BC Current 0.060 C10 BC start condition

42 FC to BC Capacity 80.0 % BC start condition

43 Cyclic BC Enabled No

44 Cyclic BC Interval 180 days

45 Cyclic BC Duration 300 min

46 Rated Capacity 1000.0 Ah Total battery capac-ity connected to

each battery shunt

47 Battery Current Limit 0.70 C10 Max. batt. current (Must be set <

index 48)

48 Over current Setpoint 1.00 C10 Alarm level. (Must be set >

index 47)

49 Capacity Coefficient 96.0 %

50 Low Capacity setting 75%

51 Very High Temp Vol Set-point

48 V The system voltage at very high tem-

perature

Page 8: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

8(26)

2.4 LVD 1/Setting Index Signal name

Value

(default) Remark Plant-specific

setting Sign. date

1 LVD Enabled Enabled

2 LVD Mode By voltage

3 LVD Voltage 42.00 V Must be set < “Index 5”

4 LVD Time 300 min

5 LVD reconnect voltage 50.00 V

6 LVD reconnect delay 2 min

7 LVD dependency None

2.5 LVD 2/Setting Index Signal name

Value

(default) Remark Plant-specific

setting Sign. date

1 LVD Enabled Enabled

2 LVD Mode By voltage

3 LVD Voltage 42.00 V Must be set < “Index 5”

4 LVD Time 300 min

5 LVD reconnect voltage 50.00 V

6 LVD reconnect delay 2 min

7 LVD dependency LVD 1

Page 9: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

9(26)

3 Settings

3.1 Network configuration Selection Value

(default) Remark Plant-specific

setting Sign. date

ACU IP: 192.168.0.1 The ACU IP adress

Mask:

Gateway:

3.2 NMS configuration NMS IP Public commu-

nity Private commu-

nity Accept trap level Sign. date

3.3 MC configuration Selection Plant-specific setting Sign. date

Protocol Type

Protocol Media

TCP/IP port number

Callback in use

Report in use

CCID (Range from 1-255)

SOCID (Range from 1-20479)

Max alarm report at-tempts (Range from 0-255)

Call elapse time [s] (Range from 0-600)

Main report phone number

Page 10: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

10(26)

Selection Plant-specific setting Sign. date

Second report phone number

Callback phone number

Main report IP

Second report IP

Security connection IP 1

Security connection IP 2

Safety level

3.4 User information configuration User name Authority

(Browser, Operator, En-gineer, Administrator)

Password Sign. date

3.5 Time synchronization Selection Plant-specific setting Sign. date

Local zone

Get time automatically from the following time servers: (Yes/No)

Primary server:

Secondary server:

Interval to adjust time: (Minutes)

Specify time (Yes/No)

Date:

Time:

Page 11: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

11(26)

4 Maintenance/Modify configure online Note: The modifications will affect the indications on the display and home pages.

4.1 Modify ACU Signal Name Setting Value Sign. date

Site SiteName

Site Site Location

Site Site Description

4.2 Modify device Index Default Device

Name (On home page)

Default Device abbr name (On

display)

New Full Device Name New abbr De-

vice Name Sign. date

1 ACU System ACU System

2 RectifierGroup Rect Group

3 Rectifier1 Rectifier1

4 Rectifier2 Rectifier2

5 Rectifier3 Rectifier3

6 Rectifier4 Rectifier4

7 Rectifier5 Rectifier5

8 Rectifier6 Rectifier6

9 BatteryGroup Batt Group

10 Battery1 Battery1

11 DC Distribution DC

12 DC Fuse DC Fuse

13 Battery Fuse Group Batt Fuse Grp

14 Battery Fuse Battery Fuse

15 LVD Group LVD Group

16 LVD1 LVD1

17 LVD2 LVD2

Page 12: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

12(26)

4.3 Modify signal

4.3.1 ACU System/Sample signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 System Voltage System Voltage

2 System Load System Load

3 System Power System Power

4 Total System Power Consumption

Power Consump

5 Power Peak In 24 Hours

Power Peak

6 Average Power in 24 Hours

Avg power

7 Total Run Time Total Run Time

8 Maintenance Time Run

Mtn Time Run

9 System Status Signal

System Status

10 ACU Internal Status Internal Status

11 Running Config Type

Config Type

4.3.2 ACU System/Control signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Clear run time Clr run time

Page 13: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

13(26)

4.3.3 ACU System/Setting signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Auto/Man State Auto/Man State

2 Outgoing Alarm Blocked

Alarm Blocked

3 Under-voltage 1 Level

Low Voltage

4 Under-voltage 2 Level

Under Voltage

5 Maintenance Time Delay

Mtn Time Delay

6 Maintenance Time Limit

Mtn Time Limit

7 High Ambient Tem-perature Limit

High Amb Temp

8 Low Ambient Tem-perature Limit

Low Amb Temp

9 Over-voltage1 Level Over Voltage 1

10 Over-voltage2 Level Over Voltage 2

11 LCD Alarm Sound LCD Alarm Sound

12 Load Shunt Full Current

Load Shunt Curr

13 Load Shunt Full Voltage

Load Shunt Volt

14 Bat 1 Shunt Full Current

Bat 1 Shunt Cur

15 Bat 1 Shunt Full Voltage

Bat 1 Shunt Vol

16 Bat 2 Shunt Full Current

Bat 2 Shunt Cur

17 Bat 2 Shunt Full Voltage

Bat 2 Shunt Vol

18 DI 1 Activation Level DI 1 Act Lvl

19 DI 2 Activation Level DI 2 Act Lvl

20 DI 3 Activation Level DI 3 Act Lvl

21 DI 4 Activation Level DI 4 Act Lvl

22 DI 5 Activation Level DI 5 Act Lvl

23 DI 6 Activation Level DI 6 Act Lvl

Page 14: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

14(26)

4.3.4 ACU System/Alarm signal In-dex

Default Signal full

name (On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 Supervision Unit Internal Fault

ACU Fault CA

2 CAN communi-cation failure

CAN Comm Fault

CA

3 Mains Failure Mains Failure OA

4 Under-voltage Under Vol MA

5 Very Under-voltage

Very Under Vol CA

6 Over-voltage Over Voltage CA

7 High Ambient Temperature

High Amb Temp NA

8 Low Ambient Temperature

Low Amb Temp NA

9 Ambient Tem-perature Sensor

Fault

T Sensor Fault NA

10 Outgoing Alarms Blocked

Alarm Blocked OA

11 Maintenance Time Limit Alarm

Mainte-nanceAlrm

OA

12 Over Maximum Power Alarm

Over Power OA

13 Config Er-ror(from backup

config)

Config Error 1 OA

14 Config Er-ror(from default

config

Config Error 2 OA

15 Abnormal load current

Ab load curr CA

16 SPD Fault SPD Fault NA

17 Very Over-voltage

Very Over Volt CA

18 Digital Input 1 DI 1 MA

19 Digital Input 2 DI 2 MA

20 Digital Input 3 DI 3 MA

21 Digital Input 4 DI 4 MA

Page 15: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

15(26)

Index

Default Signal full

name (On home

page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

Default alarm level

New alarm level

Sign. date

22 Digital Input 5 DI 5 MA

23 Digital Input 6 DI 6 MA

24 Manual Mode Manual Mode OA

4.3.5 Rectifier Group/Sample signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Number of rectifiers Rect Number

2 Communicating Rectifiers

Comm Rect Num

3 Valid Rectifers Valid Rectifers

4 Average voltage Average Voltage

5 Total current Total Current

6 Used capacity Used Capacity

7 Max used capacity Max Used Cap

8 Min used capacity Min Used cap

4.3.6 Rectifier Group/Control signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Voltage Trim Voltage Trim

2 Rectifer Current Limit

Current Limit

3 DC On/Off Control DC On/Off Ctl

4 AC On/Off Control AC On/Off Ctl

5 All LED control LED Ctl

6 Fan speed control Fan Speed Ctl

7 Rectifier On When AC Over-voltag

AC over Voltage

8 Reset Rectifier lost alarm

Reset Rect lost

Page 16: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

16(26)

4.3.7 Rectifier Group/Setting signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 High Voltage limit Rect Over Volt

2 Low voltage limit Rect Low Volt

3 Over-vol restart time Over Volt Start

4 Soft-Startup with load time

WALKIn Time

5 WALK-In enabled WALKIn Enable

6 Redundancy En-abled

Redundancy Enb

7 Pre-Currlmt for Re-dund Enb

PCL for Redund

8 Min Redundancy Min Rdncy

9 Max Redundancy Max Rdncy

10 Switch-off Delay Switch-offDelay

11 Cycle Activation Time

Cyc Act Time

12 Cycle Period Cyc Period

13 Rect Start Sequen-tially Elapse

Rect Start Seq

14 Rectifier Power type Rect Power type

4.3.8 Rectifier Group/ Alarm signal In-dex

Default Signal full

name (On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 Multi-rectifiers failure

Multi-rect fail CA

2 Rectifier lost Rectifier lost MA

Page 17: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

17(26)

4.3.9 Rectifier/Sample signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Rectifier SN Rect SN

2 Voltage Rect Voltage

3 Current Value Rect Current

4 AC Status AC Status

5 DC Status DC Status

6 Input AC voltage Rect AC Voltage

7 Current limit Current Limit

8 Derate by AC Derate by AC

9 Derate by Temp Derate by Temp

10 Temperature Rect Temp

11 Used capacity Used Capacity

12 Total Running Time Running Time

13 WALK-In enabled status

Walk-in Enable

4.3.10 Rectifier/Control signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 DC On/Off Control Rect DC Ctl

2 AC On/Off Control Rect AC Ctl

3 Rectifier Reset Rect Reset

Page 18: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

18(26)

4.3.11 Rectifier/Alarm signal In-dex

Default Signal full

name (On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 AC failure Rect AC Failure OA

2 Over tempera-ture

Rect Over Temp OA

3 Rectifier Failure Rectifier Failure MA

4 Over-voltage Rect Over Volt MA

5 Rectifier pro-tected

Rect Protected OA

6 Fan failure Rect Fan Fail MA

7 Rectifier current limit alarm

Rect Curr limit OA

8 EEPROM failure EEPROM failure OA

9 Rectifier not response

Rect not respon OA

10 Power limited for rect

Power Lmt-Rect OA

11 Rectifier sharing current alarm

Rect Shar Curr OA

4.3.12 Battery Group/Sample signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Battery Current Batt Current

2 Battery Temperature Batt Temp

3 Expected Current Limitation

ExpCurrLmt

4 Total Time of Shal-low Cycles

Shallow CycTime

5 Total Time of Deep Cycles

Deep Cyc Time

6 Total Time of Deep Discharge

Deep Disch Time

7 Total times of Shal-low Cycles

Shal Cyc Times

8 Total times of Deep Cycles

Deep Cyc Times

Page 19: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

19(26)

Index Default Signal full name (On

home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

9 Total times of Deep Discharge

Deep DischTimes

10 Temperature Com-pensation Active

Temp Comp Activ

11 Battery Current Limit Active

Bat Curr Lmtd

12 Predict discharge time

Pre Disch Time

13 Battery management state

BM State

4.3.13 Battery Group/Control signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Boost/Float charge control

BC/FC Control

2 Reset Battery Ca-pacity

Reset Capacity

3 Reset abnormal batt curr alarm

Reset AbCur alm

4 Reset discharge curr imbalance

Reset ImCur alm

5 Start Battery test Start Batt Test

6 Stop battery test Stop Batt Test

7 Reset Bad Battery Alarm

Reset Bad Batt

4.3.14 Battery Group/Setting signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Battery Type No. Batt Type No.

2 Nominal Voltage FC Voltage

3 Temp Compensation Center

TempComp Center

4 Compensation Coef-ficient

TempComp Coeff

5 Very High Tempera-ture limit

Very high Temp

Page 20: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

20(26)

Index Default Signal full name (On

home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

6 High Temperature limit

High Temp Limit

7 Low temperature limit

Low Temp Limit

8 Number of battery blocks

Battery Blocks

9 Planned Test En-abled

PlanBT Enabled

10 AC Fail Test En-abled

AcFail Test Enb

11 Test Voltage Level Test Volt

12 Test End Time Test End Time

13 Test End Voltage Test End Volt

14 Test End Capacity Test End Cap

15 Pre-BC Enabled Pre-BC Enabled

16 Constant current test enabled

ConstCurrT Enb

17 Constant current test current

ConstCurrT Curr

18 Number of schedule Test per year

Paned Test Num

19 Planed Test1 Planed Test1

20 Planed Test2 Planed Test2

21 Planed Test3 Planed Test3

22 Planed Test4 Planed Test4

23 Planed Test5 Planed Test5

24 Planed Test6 Planed Test6

25 Planed Test7 Planed Test7

26 Planed Test8 Planed Test8

27 Planed Test9 Planed Test9

28 Planed Test10 Planed Test10

29 Planed Test11 Planed Test11

30 Planed Test12 Planed Test12

Page 21: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

21(26)

Index Default Signal full name (On

home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

31 Record threshold RecordThreshold

32 Short Test Enabled ShortTestEnable

33 Short Test Cycle ShortTest Cycle

34 Max Diff Current For Short Test

Max Diff Cur

35 Short Test Duration ShortTest Time

36 Boost Charge Volt-age

BC Voltage

37 Maximum Boost Charge Time

BC Protect Time

38 Stable BC Current Stable BC Curr

39 Stable BC Delay Stable BC Delay

40 Automatic Boost Charge Enabled

Auto BC Enabled

41 FC to BC Current To BC Current

42 FC to BC Capacity To BC Capacity

43 Cyclic BC Enabled CycBC Enabled

44 Cyclic BC Interval CyclBC Interval

45 Cyclic BC Duration CyclBC Duration

46 Rated Capacity Rated Capacity

47 Battery Current Limit Batt Curr Lmt

48 Over current Set-point

Over Current

49 Capacity Coefficient Capacity Coef

50 Low Capacity setting Low Cap setting

51 Very High Temp Vol Setpoint

Hi-Hi Temp Vol

Page 22: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

22(26)

4.3.15 Battery Group/Alarm signal In-dex

Default Signal full

name (On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 Temperature sensor failure

Temp sensor fai OA

2 High Tempera-ture

High Temp OA

3 Very high tem-perature

Very hi-Temp OA

4 Low Tempera-ture

Low Temp OA

5 Plan Battery test in progress

Plan BT OA

6 AC failure Batt test in Progress

AC failure BT OA

7 Manual Battery test in progress

Manual BT OA

8 Short Test in progress

Short Test OA

9 Discharge Cur-rent Imbalance

Dis Curr Im OA

10 Cyclic Boost Charge

Cyclic BC OA

11 Automatic Boost Charge

Auto BC OA

12 Manual Boost Charge

Manual BC OA

13 Abnormal Bat-tery Current

Abnorm Bat Curr OA

14 Temperature Compensation

Active

Temp Comp Activ

NA

15 Battery Current Limit Active

Batt Curr Lmt NA

16 Battery Charge Prohibited Alarm

Charge Prohibit OA

17 Boost charge for test alarm

Pre-BC Alarm OA

18 Master Battery Test in progress

Master BT OA

Page 23: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

23(26)

In-dex

Default Signal full

name (On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

19 Master Boost Charge in pro-

gress

Master BC OA

20 Bad Battery Bad Batt OA

21 Battery Test Failure

Test Failure OA

4.3.16 Battery/Sample signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 Battery Current Batt Current

2 Battery Capacity (Ah)

Batt Cap (Ah)

3 Battery Capacity (%) Batt Cap (%)

4.3.17 Battery/Alarm signal Inde

x Default

Signal full name

(On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 Exceed Current Limit

Exceed Curr Lmt OA

2 Over Battery current

Over Current NA

3 Low capacity Low capacity OA

4.3.18 Battery Fuse Unit/Alarm signal Inde

x Default

Signal full name

(On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 Fuse alarm Fuse Alarm OA

2 Fuse 1 alarm Fuse 1 Alarm OA

3 Fuse 2 alarm Fuse 2 Alarm OA

4 Fuse 3 alarm Fuse 3 Alarm OA

Page 24: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

24(26)

4.3.19 DC Distribution/Sample signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 DC Voltage DC Voltage

4.3.20 DC Fuse Unit/Alarm signal In-dex

Default Signal full

name (On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 Fuse alarm Fuse Alarm OA

2 Prio Fuse 1 alarm

P Fuse 1 alarm OA

3 Prio Fuse 2 alarm

P Fuse 2 alarm OA

4 Prio Fuse 3 alarm

P Fuse 3 alarm OA

5 Normal Fuse 1 alarm

N Fuse 1 alarm OA

6 Normal Fuse 2 alarm

N Fuse 2 alarm OA

7 Normal Fuse 3 alarm

N Fuse 3 alarm OA

8 Normal Fuse 4 alarm

N Fuse 4 alarm OA

9 Normal Fuse 5 alarm

N Fuse 5 alarm OA

10 Normal Fuse 6 alarm

N Fuse 6 alarm OA

Page 25: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

25(26)

4.3.21 LVD 1 unit/Control signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 LVD Control LVD Ctrl

4.3.22 LVD 1 unit/Setting signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 LVD Enabled LVD Enabled

2 LVD Mode LVD Mode

3 LVD Voltage LVD Voltage

4 LVD Time LVD Time

5 LVD reconnect volt-age

LVD Recon Volt

6 LVD reconnect delay LVD Recon Delay

7 LVD dependency LVD depend

4.3.23 LVD 2 unit/Setting signal Index Default Signal

full name (On home page)

Default Signal abbr name (On

display)

New Signal full Name New Signal

abbr Name Sign. date

1 LVD Enabled LVD Enabled

2 LVD Mode LVD Mode

3 LVD Voltage LVD Voltage

4 LVD Time LVD Time

5 LVD reconnect volt-age

LVD Recon Volt

6 LVD reconnect delay LVD Recon Delay

7 LVD dependency LVD depend

Page 26: Table of Set Values ACU RevB

TABLE OF SET VALUES – BMP 903 050

3/1532-BMP 903 051 Uen Rev B 2006-12-11

26(26)

4.3.24 LVD 1 Unit/Alarm signal In-dex

Default Signal full

name (On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 Disconnected Disconnected OA

2 Contactor Fault Contactor Fault CA

4.3.25 LVD 2 Unit/Alarm signal In-dex

Default Signal full

name (On home page)

Default Signal abbr

name (On display)

New Signal full Name

New Signal abbr Name

De-fault alarm level

New alarm level

Sign. date

1 Disconnected Disconnected OA

2 Contactor Fault Contactor Fault CA