TABLE OF SET VALUES
3/1532-BMP 903 050 Uen Rev B 2006-12-11
1(26)
Systems with ACU type BMP 903 050 Contents 1 Tables of set values 3
2 Device Explore 3 2.1 ACU System/Setting 3 2.2 Rect Group/Setting 4 2.3 Batt Group/Setting 5 2.4 LVD 1/Setting 8 2.5 LVD 2/Setting 8 3 Settings 9 3.1 Network configuration 9 3.2 NMS configuration 9 3.3 MC configuration 9 3.4 User information configuration 10 3.5 Time synchronization 10 4 Maintenance/Modify configure online 11 4.1 Modify ACU 11 4.2 Modify device 11 4.3 Modify signal 12
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
2(26)
The contents of this document are subject to revision without notice due to continued progress in methodology, design, and manufacturing.
© Emerson Network Power Energy Systems AB 2006 – All rights reserved
Emerson Network Power Energy Systems AB
SE – 141 82 Stockholm Sweden
Tel. +46 8 721 6000 Fax. +46 8 721 7177 www.emersonenergy.com
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
3(26)
1 Tables of set values These tables are based on the ACU software revision 1.30, for NetSure™ 201, NetSure™ 501 and NetSure™ 701, –48 V.
All settings and choices affect the functions of the power supply system. The values shall therefore not be changed without a consequence analysis.
If a default value is adjusted, the new value shall be entered in the column “Plant-specific setting”. The default settings listed are the factory default settings.
Note: The appearance of some settings will depend on what configuration package file has been downloaded to the ACU.
2 Device Explore Note: When browsing the control and settings of the system devices, some settings
will be blocked (the set button is grey). The reason is that the setting depends on another setting or that the user authority level does not approve a change of the setting.
2.1 ACU System/Setting Index Signal name
Value
(default) Remark Plant-specific
setting Sign. date
1 Auto/Man State Auto
2 Outgoing Alarm Blocked Normal
3 Under-voltage 1 Level 48.50 V Must be set ≥ UV 2 and < U nom.
4 Under-voltage 2 Level 43.50 V Must be set ≤ UV 1
5 Maintenance Time Delay 30 Day Alarm activation time
6 Maintenance Time Limit 360 Day Alarm periodicity
7 High Ambient Temperature Limit
35.00 deg.C Must be set > Low amb. temp.
8 Low Ambient Temperature Limit
5.00 deg.C Must be set < High amb. temp.
9 Over-voltage 1 Level 55.70 V Must be set > U boost charge
10 Over-voltage 2 Level 58.50 V Must be set > Over-voltage 1 Level
11 LCD Alarm Sound Off
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
4(26)
Index Signal name
Value (default)
Remark Plant-specific setting
Sign. date
12 Load Shunt Full Current 1000.0 A
13 Load Shunt Full Voltage 75.0 mV
14 Bat 1 Shunt Full Current 1000.0 A
15 Bat 1 Shunt Full Voltage 75.0 mV
16 Bat 2 Shunt Full Current 1000.0 A
17 Bat 2 Shunt Full Voltage 75.0 mV
18 DI 1 Activation Level 48 V
19 DI 2 Activation Level 48 V
20 DI 3 Activation Level 48 V
21 DI 4 Activation Level 48 V
22 DI 5 Activation Level 48 V
23 DI 6 Activation Level 48 V
2.2 Rect Group/Setting Index Signal name
Value
(default) Remark Plant-specific
setting Sign. date
1 High Voltage limit 59.0 V Must be set 0.5 V > U boost charge
2 Low voltage limit 40.0 V
3 Over-vol restart time 300 s
4 Soft-Startup with load time 8 s
5 WALK-In enabled Disabled
6 Redundancy Enabled Disabled
7 Pre-Currlmt for Redund Enb
Disabled
8 Min Redundancy 100 % Min. accepted re-dundancy. (Must be
set < Max. red. –110%)
9 Max Redundancy 300 % Max. prefered re-dundancy. (Must be
set > Min. red. +110%)
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
5(26)
Index Signal name
Value (default)
Remark Plant-specific setting
Sign. date
10 Switch-off Delay 5 min
11 Cycle Activation Time 1 CLK The time (0-23 o´clock) for cycling
12 Cycle Period 30 Day
13 Rect Start Sequentially Elapse
0 s
14 Rectifier Power Type Double supply
The rect. LC feed-ing
2.3 Batt Group/Setting Index Signal name
Value
(default) Remark Plant-specific
setting Sign. date
1 Battery Type No. 1
2 Nominal Voltage 54.5 V (System voltage) Must be set > Un-dervoltage 1 and <
U boost ch.
3 Temp Compensation Cen-ter
20.0 deg.C
4 Compensation Coefficient 96.0 mv/deg.C
5 Very High Temperature limit
55.00 deg.C Must be set > High Temp limit
6 High Temperature limit 40.00 deg.C Must be set < Very High Temp limit and
> Low temp. limit
7 Low temperature limit 0.00 deg.C Must be set < High Temp limit
8 Number of battery blocks 24
9 Planned Test Enabled Disable
10 AC Fail Test Enabled Disable
11 Test Voltage Level 45.00 V Rect. Voltage (Must be set ≤ Test End Voltage –0.2 V)
12 Test End Time 60 min
13 Test End Voltage 46.40 V Must be set ≥ Test Voltage Level
+0.2 V
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
6(26)
Index Signal name
Value (default)
Remark Plant-specific setting
Sign. date
14 Test End Capacity 30.00 % Remaining batt. capacity
15 Pre-BC Enabled Disable
16 Constant current test en-abled
Disable
17 Constant current test cur-rent
10000.0 A
18 Number of schedule Test per year
0 Opens indexes 19 to 30
19 Planed Test1 -- MM-DD HH
20 Planed Test2 -- MM-DD HH
21 Planed Test3 -- MM-DD HH
22 Planed Test4 -- MM-DD HH
23 Planed Test5 -- MM-DD HH
24 Planed Test6 -- MM-DD HH
25 Planed Test7 -- MM-DD HH
26 Planed Test8 -- MM-DD HH
27 Planed Test9 -- MM-DD HH
28 Planed Test10 -- MM-DD HH
29 Planed Test11 -- MM-DD HH
30 Planed Test12 -- MM-DD HH
31 Record threshold 0.050 V
32 Short Test Enabled Disable Requires ≥2 battery shunts
33 Short Test Cycle 30 days
34 Max Diff Current For Short Test
0.05 C10
35 Short Test Duration 5 min
36 Boost Charge Voltage 56.4 V Must be set > U nom. and < U over-
voltage
37 Maximum Boost Charge Time
5 h
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
7(26)
Index Signal name
Value (default)
Remark Plant-specific setting
Sign. date
38 Stable BC Current 0.010 C10 Limitation of BC current
39 Stable BC Delay 60 min Fixed time for pro-longed BC
40 Automatic Boost Charge Enabled
no
41 FC to BC Current 0.060 C10 BC start condition
42 FC to BC Capacity 80.0 % BC start condition
43 Cyclic BC Enabled No
44 Cyclic BC Interval 180 days
45 Cyclic BC Duration 300 min
46 Rated Capacity 1000.0 Ah Total battery capac-ity connected to
each battery shunt
47 Battery Current Limit 0.70 C10 Max. batt. current (Must be set <
index 48)
48 Over current Setpoint 1.00 C10 Alarm level. (Must be set >
index 47)
49 Capacity Coefficient 96.0 %
50 Low Capacity setting 75%
51 Very High Temp Vol Set-point
48 V The system voltage at very high tem-
perature
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
8(26)
2.4 LVD 1/Setting Index Signal name
Value
(default) Remark Plant-specific
setting Sign. date
1 LVD Enabled Enabled
2 LVD Mode By voltage
3 LVD Voltage 42.00 V Must be set < “Index 5”
4 LVD Time 300 min
5 LVD reconnect voltage 50.00 V
6 LVD reconnect delay 2 min
7 LVD dependency None
2.5 LVD 2/Setting Index Signal name
Value
(default) Remark Plant-specific
setting Sign. date
1 LVD Enabled Enabled
2 LVD Mode By voltage
3 LVD Voltage 42.00 V Must be set < “Index 5”
4 LVD Time 300 min
5 LVD reconnect voltage 50.00 V
6 LVD reconnect delay 2 min
7 LVD dependency LVD 1
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
9(26)
3 Settings
3.1 Network configuration Selection Value
(default) Remark Plant-specific
setting Sign. date
ACU IP: 192.168.0.1 The ACU IP adress
Mask:
Gateway:
3.2 NMS configuration NMS IP Public commu-
nity Private commu-
nity Accept trap level Sign. date
3.3 MC configuration Selection Plant-specific setting Sign. date
Protocol Type
Protocol Media
TCP/IP port number
Callback in use
Report in use
CCID (Range from 1-255)
SOCID (Range from 1-20479)
Max alarm report at-tempts (Range from 0-255)
Call elapse time [s] (Range from 0-600)
Main report phone number
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
10(26)
Selection Plant-specific setting Sign. date
Second report phone number
Callback phone number
Main report IP
Second report IP
Security connection IP 1
Security connection IP 2
Safety level
3.4 User information configuration User name Authority
(Browser, Operator, En-gineer, Administrator)
Password Sign. date
3.5 Time synchronization Selection Plant-specific setting Sign. date
Local zone
Get time automatically from the following time servers: (Yes/No)
Primary server:
Secondary server:
Interval to adjust time: (Minutes)
Specify time (Yes/No)
Date:
Time:
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
11(26)
4 Maintenance/Modify configure online Note: The modifications will affect the indications on the display and home pages.
4.1 Modify ACU Signal Name Setting Value Sign. date
Site SiteName
Site Site Location
Site Site Description
4.2 Modify device Index Default Device
Name (On home page)
Default Device abbr name (On
display)
New Full Device Name New abbr De-
vice Name Sign. date
1 ACU System ACU System
2 RectifierGroup Rect Group
3 Rectifier1 Rectifier1
4 Rectifier2 Rectifier2
5 Rectifier3 Rectifier3
6 Rectifier4 Rectifier4
7 Rectifier5 Rectifier5
8 Rectifier6 Rectifier6
9 BatteryGroup Batt Group
10 Battery1 Battery1
11 DC Distribution DC
12 DC Fuse DC Fuse
13 Battery Fuse Group Batt Fuse Grp
14 Battery Fuse Battery Fuse
15 LVD Group LVD Group
16 LVD1 LVD1
17 LVD2 LVD2
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
12(26)
4.3 Modify signal
4.3.1 ACU System/Sample signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 System Voltage System Voltage
2 System Load System Load
3 System Power System Power
4 Total System Power Consumption
Power Consump
5 Power Peak In 24 Hours
Power Peak
6 Average Power in 24 Hours
Avg power
7 Total Run Time Total Run Time
8 Maintenance Time Run
Mtn Time Run
9 System Status Signal
System Status
10 ACU Internal Status Internal Status
11 Running Config Type
Config Type
4.3.2 ACU System/Control signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Clear run time Clr run time
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
13(26)
4.3.3 ACU System/Setting signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Auto/Man State Auto/Man State
2 Outgoing Alarm Blocked
Alarm Blocked
3 Under-voltage 1 Level
Low Voltage
4 Under-voltage 2 Level
Under Voltage
5 Maintenance Time Delay
Mtn Time Delay
6 Maintenance Time Limit
Mtn Time Limit
7 High Ambient Tem-perature Limit
High Amb Temp
8 Low Ambient Tem-perature Limit
Low Amb Temp
9 Over-voltage1 Level Over Voltage 1
10 Over-voltage2 Level Over Voltage 2
11 LCD Alarm Sound LCD Alarm Sound
12 Load Shunt Full Current
Load Shunt Curr
13 Load Shunt Full Voltage
Load Shunt Volt
14 Bat 1 Shunt Full Current
Bat 1 Shunt Cur
15 Bat 1 Shunt Full Voltage
Bat 1 Shunt Vol
16 Bat 2 Shunt Full Current
Bat 2 Shunt Cur
17 Bat 2 Shunt Full Voltage
Bat 2 Shunt Vol
18 DI 1 Activation Level DI 1 Act Lvl
19 DI 2 Activation Level DI 2 Act Lvl
20 DI 3 Activation Level DI 3 Act Lvl
21 DI 4 Activation Level DI 4 Act Lvl
22 DI 5 Activation Level DI 5 Act Lvl
23 DI 6 Activation Level DI 6 Act Lvl
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
14(26)
4.3.4 ACU System/Alarm signal In-dex
Default Signal full
name (On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 Supervision Unit Internal Fault
ACU Fault CA
2 CAN communi-cation failure
CAN Comm Fault
CA
3 Mains Failure Mains Failure OA
4 Under-voltage Under Vol MA
5 Very Under-voltage
Very Under Vol CA
6 Over-voltage Over Voltage CA
7 High Ambient Temperature
High Amb Temp NA
8 Low Ambient Temperature
Low Amb Temp NA
9 Ambient Tem-perature Sensor
Fault
T Sensor Fault NA
10 Outgoing Alarms Blocked
Alarm Blocked OA
11 Maintenance Time Limit Alarm
Mainte-nanceAlrm
OA
12 Over Maximum Power Alarm
Over Power OA
13 Config Er-ror(from backup
config)
Config Error 1 OA
14 Config Er-ror(from default
config
Config Error 2 OA
15 Abnormal load current
Ab load curr CA
16 SPD Fault SPD Fault NA
17 Very Over-voltage
Very Over Volt CA
18 Digital Input 1 DI 1 MA
19 Digital Input 2 DI 2 MA
20 Digital Input 3 DI 3 MA
21 Digital Input 4 DI 4 MA
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
15(26)
Index
Default Signal full
name (On home
page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
Default alarm level
New alarm level
Sign. date
22 Digital Input 5 DI 5 MA
23 Digital Input 6 DI 6 MA
24 Manual Mode Manual Mode OA
4.3.5 Rectifier Group/Sample signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Number of rectifiers Rect Number
2 Communicating Rectifiers
Comm Rect Num
3 Valid Rectifers Valid Rectifers
4 Average voltage Average Voltage
5 Total current Total Current
6 Used capacity Used Capacity
7 Max used capacity Max Used Cap
8 Min used capacity Min Used cap
4.3.6 Rectifier Group/Control signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Voltage Trim Voltage Trim
2 Rectifer Current Limit
Current Limit
3 DC On/Off Control DC On/Off Ctl
4 AC On/Off Control AC On/Off Ctl
5 All LED control LED Ctl
6 Fan speed control Fan Speed Ctl
7 Rectifier On When AC Over-voltag
AC over Voltage
8 Reset Rectifier lost alarm
Reset Rect lost
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
16(26)
4.3.7 Rectifier Group/Setting signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 High Voltage limit Rect Over Volt
2 Low voltage limit Rect Low Volt
3 Over-vol restart time Over Volt Start
4 Soft-Startup with load time
WALKIn Time
5 WALK-In enabled WALKIn Enable
6 Redundancy En-abled
Redundancy Enb
7 Pre-Currlmt for Re-dund Enb
PCL for Redund
8 Min Redundancy Min Rdncy
9 Max Redundancy Max Rdncy
10 Switch-off Delay Switch-offDelay
11 Cycle Activation Time
Cyc Act Time
12 Cycle Period Cyc Period
13 Rect Start Sequen-tially Elapse
Rect Start Seq
14 Rectifier Power type Rect Power type
4.3.8 Rectifier Group/ Alarm signal In-dex
Default Signal full
name (On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 Multi-rectifiers failure
Multi-rect fail CA
2 Rectifier lost Rectifier lost MA
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
17(26)
4.3.9 Rectifier/Sample signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Rectifier SN Rect SN
2 Voltage Rect Voltage
3 Current Value Rect Current
4 AC Status AC Status
5 DC Status DC Status
6 Input AC voltage Rect AC Voltage
7 Current limit Current Limit
8 Derate by AC Derate by AC
9 Derate by Temp Derate by Temp
10 Temperature Rect Temp
11 Used capacity Used Capacity
12 Total Running Time Running Time
13 WALK-In enabled status
Walk-in Enable
4.3.10 Rectifier/Control signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 DC On/Off Control Rect DC Ctl
2 AC On/Off Control Rect AC Ctl
3 Rectifier Reset Rect Reset
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
18(26)
4.3.11 Rectifier/Alarm signal In-dex
Default Signal full
name (On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 AC failure Rect AC Failure OA
2 Over tempera-ture
Rect Over Temp OA
3 Rectifier Failure Rectifier Failure MA
4 Over-voltage Rect Over Volt MA
5 Rectifier pro-tected
Rect Protected OA
6 Fan failure Rect Fan Fail MA
7 Rectifier current limit alarm
Rect Curr limit OA
8 EEPROM failure EEPROM failure OA
9 Rectifier not response
Rect not respon OA
10 Power limited for rect
Power Lmt-Rect OA
11 Rectifier sharing current alarm
Rect Shar Curr OA
4.3.12 Battery Group/Sample signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Battery Current Batt Current
2 Battery Temperature Batt Temp
3 Expected Current Limitation
ExpCurrLmt
4 Total Time of Shal-low Cycles
Shallow CycTime
5 Total Time of Deep Cycles
Deep Cyc Time
6 Total Time of Deep Discharge
Deep Disch Time
7 Total times of Shal-low Cycles
Shal Cyc Times
8 Total times of Deep Cycles
Deep Cyc Times
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
19(26)
Index Default Signal full name (On
home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
9 Total times of Deep Discharge
Deep DischTimes
10 Temperature Com-pensation Active
Temp Comp Activ
11 Battery Current Limit Active
Bat Curr Lmtd
12 Predict discharge time
Pre Disch Time
13 Battery management state
BM State
4.3.13 Battery Group/Control signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Boost/Float charge control
BC/FC Control
2 Reset Battery Ca-pacity
Reset Capacity
3 Reset abnormal batt curr alarm
Reset AbCur alm
4 Reset discharge curr imbalance
Reset ImCur alm
5 Start Battery test Start Batt Test
6 Stop battery test Stop Batt Test
7 Reset Bad Battery Alarm
Reset Bad Batt
4.3.14 Battery Group/Setting signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Battery Type No. Batt Type No.
2 Nominal Voltage FC Voltage
3 Temp Compensation Center
TempComp Center
4 Compensation Coef-ficient
TempComp Coeff
5 Very High Tempera-ture limit
Very high Temp
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
20(26)
Index Default Signal full name (On
home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
6 High Temperature limit
High Temp Limit
7 Low temperature limit
Low Temp Limit
8 Number of battery blocks
Battery Blocks
9 Planned Test En-abled
PlanBT Enabled
10 AC Fail Test En-abled
AcFail Test Enb
11 Test Voltage Level Test Volt
12 Test End Time Test End Time
13 Test End Voltage Test End Volt
14 Test End Capacity Test End Cap
15 Pre-BC Enabled Pre-BC Enabled
16 Constant current test enabled
ConstCurrT Enb
17 Constant current test current
ConstCurrT Curr
18 Number of schedule Test per year
Paned Test Num
19 Planed Test1 Planed Test1
20 Planed Test2 Planed Test2
21 Planed Test3 Planed Test3
22 Planed Test4 Planed Test4
23 Planed Test5 Planed Test5
24 Planed Test6 Planed Test6
25 Planed Test7 Planed Test7
26 Planed Test8 Planed Test8
27 Planed Test9 Planed Test9
28 Planed Test10 Planed Test10
29 Planed Test11 Planed Test11
30 Planed Test12 Planed Test12
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
21(26)
Index Default Signal full name (On
home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
31 Record threshold RecordThreshold
32 Short Test Enabled ShortTestEnable
33 Short Test Cycle ShortTest Cycle
34 Max Diff Current For Short Test
Max Diff Cur
35 Short Test Duration ShortTest Time
36 Boost Charge Volt-age
BC Voltage
37 Maximum Boost Charge Time
BC Protect Time
38 Stable BC Current Stable BC Curr
39 Stable BC Delay Stable BC Delay
40 Automatic Boost Charge Enabled
Auto BC Enabled
41 FC to BC Current To BC Current
42 FC to BC Capacity To BC Capacity
43 Cyclic BC Enabled CycBC Enabled
44 Cyclic BC Interval CyclBC Interval
45 Cyclic BC Duration CyclBC Duration
46 Rated Capacity Rated Capacity
47 Battery Current Limit Batt Curr Lmt
48 Over current Set-point
Over Current
49 Capacity Coefficient Capacity Coef
50 Low Capacity setting Low Cap setting
51 Very High Temp Vol Setpoint
Hi-Hi Temp Vol
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
22(26)
4.3.15 Battery Group/Alarm signal In-dex
Default Signal full
name (On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 Temperature sensor failure
Temp sensor fai OA
2 High Tempera-ture
High Temp OA
3 Very high tem-perature
Very hi-Temp OA
4 Low Tempera-ture
Low Temp OA
5 Plan Battery test in progress
Plan BT OA
6 AC failure Batt test in Progress
AC failure BT OA
7 Manual Battery test in progress
Manual BT OA
8 Short Test in progress
Short Test OA
9 Discharge Cur-rent Imbalance
Dis Curr Im OA
10 Cyclic Boost Charge
Cyclic BC OA
11 Automatic Boost Charge
Auto BC OA
12 Manual Boost Charge
Manual BC OA
13 Abnormal Bat-tery Current
Abnorm Bat Curr OA
14 Temperature Compensation
Active
Temp Comp Activ
NA
15 Battery Current Limit Active
Batt Curr Lmt NA
16 Battery Charge Prohibited Alarm
Charge Prohibit OA
17 Boost charge for test alarm
Pre-BC Alarm OA
18 Master Battery Test in progress
Master BT OA
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
23(26)
In-dex
Default Signal full
name (On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
19 Master Boost Charge in pro-
gress
Master BC OA
20 Bad Battery Bad Batt OA
21 Battery Test Failure
Test Failure OA
4.3.16 Battery/Sample signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 Battery Current Batt Current
2 Battery Capacity (Ah)
Batt Cap (Ah)
3 Battery Capacity (%) Batt Cap (%)
4.3.17 Battery/Alarm signal Inde
x Default
Signal full name
(On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 Exceed Current Limit
Exceed Curr Lmt OA
2 Over Battery current
Over Current NA
3 Low capacity Low capacity OA
4.3.18 Battery Fuse Unit/Alarm signal Inde
x Default
Signal full name
(On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 Fuse alarm Fuse Alarm OA
2 Fuse 1 alarm Fuse 1 Alarm OA
3 Fuse 2 alarm Fuse 2 Alarm OA
4 Fuse 3 alarm Fuse 3 Alarm OA
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
24(26)
4.3.19 DC Distribution/Sample signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 DC Voltage DC Voltage
4.3.20 DC Fuse Unit/Alarm signal In-dex
Default Signal full
name (On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 Fuse alarm Fuse Alarm OA
2 Prio Fuse 1 alarm
P Fuse 1 alarm OA
3 Prio Fuse 2 alarm
P Fuse 2 alarm OA
4 Prio Fuse 3 alarm
P Fuse 3 alarm OA
5 Normal Fuse 1 alarm
N Fuse 1 alarm OA
6 Normal Fuse 2 alarm
N Fuse 2 alarm OA
7 Normal Fuse 3 alarm
N Fuse 3 alarm OA
8 Normal Fuse 4 alarm
N Fuse 4 alarm OA
9 Normal Fuse 5 alarm
N Fuse 5 alarm OA
10 Normal Fuse 6 alarm
N Fuse 6 alarm OA
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
25(26)
4.3.21 LVD 1 unit/Control signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 LVD Control LVD Ctrl
4.3.22 LVD 1 unit/Setting signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 LVD Enabled LVD Enabled
2 LVD Mode LVD Mode
3 LVD Voltage LVD Voltage
4 LVD Time LVD Time
5 LVD reconnect volt-age
LVD Recon Volt
6 LVD reconnect delay LVD Recon Delay
7 LVD dependency LVD depend
4.3.23 LVD 2 unit/Setting signal Index Default Signal
full name (On home page)
Default Signal abbr name (On
display)
New Signal full Name New Signal
abbr Name Sign. date
1 LVD Enabled LVD Enabled
2 LVD Mode LVD Mode
3 LVD Voltage LVD Voltage
4 LVD Time LVD Time
5 LVD reconnect volt-age
LVD Recon Volt
6 LVD reconnect delay LVD Recon Delay
7 LVD dependency LVD depend
TABLE OF SET VALUES – BMP 903 050
3/1532-BMP 903 051 Uen Rev B 2006-12-11
26(26)
4.3.24 LVD 1 Unit/Alarm signal In-dex
Default Signal full
name (On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 Disconnected Disconnected OA
2 Contactor Fault Contactor Fault CA
4.3.25 LVD 2 Unit/Alarm signal In-dex
Default Signal full
name (On home page)
Default Signal abbr
name (On display)
New Signal full Name
New Signal abbr Name
De-fault alarm level
New alarm level
Sign. date
1 Disconnected Disconnected OA
2 Contactor Fault Contactor Fault CA