Saia-Burgess Group 2
InternationalDivisionsRange
Timers 13
Electromechanical KKH 14
KOE 17
Electronic KOP.F 20
KOL 24
KOP.J 28
KOP.K 32
Hour meter 37
Electromechanical CMC 38
CMT 42
CMU 44
Electronic CXR 46
CXG 23, 28 48
CXE 51
Counters 55
Electromechanical
Totalising CMB / CMA / CBG / CMM 56 + 59 + 62 + 64
Preset CMM 66
Electronics
Totalising CXB / CXG 20, 26 69 + 72
Differential CXG 21 / CXR 74 + 77
Preset CXP / CXE / CXD 80 + 82 + 85
Digital tachometers CXG 22, 25 / CXD / CXE 88 + 91 + 94
Control Relays 99
Analog KFE 100/101/301, 300, 302 100 + 103 + 106
Digital KFE 102/103 109
Thermidor KFT 100, 200 112
Energy Meter 117
Single phase AAD1 118
www.saia-burgess.com saia-burgess Control Devices2 | 3
Saia-Burgess GroupInternational
Close to the customer worldwide
Our production locations, wholly-owned sales
companies, tech centres and agents place us on
hand, wherever our customers are situated.
www.saia-burgess.comsaia-burgess Control Devices 2 | 3
Saia-Burgess Group
Austria SalzburgVienna
Belgium VilvoordeFrance Paris
Germany DreieichDresdenHalverOldenburgVelbert
Hungary BudaörsÓzd
Italy MilanNetherlands GoudaSwitzerland Murten
United Kingdom GatesheadNuneaton
Tunisia MonastirCanada Scarborogh
USA TroyVandaliaVernon Hills
China Hong KongDongguan*Shenzhen*
*Joint Venture
Sale
s Co
mpa
nies
Prod
uctio
n Si
tes
Auto
mot
ive
Tech
Cen
tre
Saia-Burgess Group
Agents
www.saia-burgess.com saia-burgess Control Devices4 | 5
The structure of our company, with its threedivisions, is market led.
Automotive Division
Supplies mechanical and electromechanical com-
ponents in large volumes worldwide (switches,
motors, solenoids, sensors) together with sub-
systems as innovative solutions for clearly defined
applications in the comfort and safety areas of
automotive design.
Industry Division
Supplies OEM customers worldwide with a broad
product range comprising electromechanical and
electronic components and subsystems. These
cover increased demands for comfort and safety
features, mainly in domestic appliances, heating,
ventilation and air-conditioning applications, and
in the general industrial sector.
Controls Division
Supplies customers in Europe with control tech-
nology based on programmable logic controllers
for use mainly in the areas of building automa-
tion and general industrial automation.
Our research and development is focused to-
tally on market need and customer requirements.
Substantial investment is made in the develop-
ment not only of innovative, new products, but also
of customised solutions. Our products are manu-
factured, according to type and technical re-
quirements, on either highly automated, partially
automated or manual production equipment.
Market led structure Innovative Products
Saia-Burgess DivisionsCompany Structure
www.saia-burgess.comsaia-burgess Control Devices 4 | 5
The Industry Division offers a broad range
of standard and customised products: switches,
motors, solenoids, door locking systems, sensors,
electronic control devices and subsystems. The
Division has worldwide presence with its own
sales network and tech centre organisation.
Combining the electromechanical with
electronics
The fusion of electronic and electromechanical
subassemblies has made new, innovative solutions
possible for a variety of industrial applications.
Highly flexible production
The Division is involved with design and engi-
neering, tool manufacture, electronics, plastic
and metal parts production, assembly employing
its own extensive quality procedures and test
equipment. The options of partially automated or
manual production for medium to small volumes
offer a high level of manufacturing flexibility.
Solutions for comfort and safety
Saia-Burgess Industry Division
Domestic appliances are safer and more
convenient
The use of control switches, microswitches, sole-
noids, sensors and subsystems in coffee machines,
extractor hoods, microwave ovens, washing ma-
chines, dishwashers, tumble dryers, mixers, etc.
has brought greater safety and comfort to the user.
Improved energy efficiency in heating,
ventilation and air-conditioning
The level of energy efficiency in buildings has been
increased by the use of solenoids, motors, micro-
switches, sensors and subsystems in gas and water
valves, and in air valves for heating, ventilation,
air-conditioning and fuel-cell applications.
More comfort and safety in very diverse
applications
Comfort and safety have been improved by using
microswitches, control switches, motors, sole-
noids and subsystems in office machinery, postal
sorting equipment and other very varied applica-
tions in vending machines, gaming machines, spe-
cialist vehicles, telecommunications and medical
equipment.
Heating/Ventilation /Air Conditioning Domestic AppliancesKitchen Appliances
Vending and Gaming Machines Special Vehicles Office Equipment
www.saia-burgess.com saia-burgess Control Devices6 | 7
KKH KOEType
Characteristics
Mounting
Dimensions (mm)
Functions*
Time ranges
Outputs
Supply voltage
Page
TimersElectromechanical
Control Components
open, manual start timer manual time setting elapsed time indicator
flush mounting front or side mounting
55 x 73 x 65
no
1, 5, 15, 30 min1, 2, 3, 12, 24 h
2 snap-action as change-over, 250 VAC, 16 A
230 VAC, 50 Hz
14
additional functions elapsed time indicator
surface mounting snap on or screws flush mounting with clip
surface: 45 x 70 x 99 flush: 45 x 45 x 93
11, 12, 21, 22, 23 by external wiring
6 time ranges, selected 0.1s...60 h
1 timed and 1 instantaneouschange-over contact, 250 VAC, 2/5 A
230 VAC, 50 Hz
17
KOP.F KOL KOP.J KOP.KType
Characteristics
Mounting
Dimensions (mm)
Functions*
Time ranges
Outputs
Supply voltage
Page
TimersElectronic
large rotary dial DIN dimensions multifunction multi time range multi voltage
flush mounting plug-in on 11 pin socket
45 x 45 x 95
211, 212, 217, 221, 223, 247 by external wiring
12 time ranges, selected 0.01s...10 h
1 relay with two contacts aschange-over, 250 VAC, 5 A
24...230 VDC/VAC, 50/60 Hz
20
17.5 mm multifunction multi time range multi voltage
surface mounting snap-on DIN rail 35 mm
17.5 x 80 x 70
11, 12, 21, 42, 51, 60
6 time ranges, 0.05 s up to 10 h
1 relay NO, KOL1..1 relay as change-over, KOL3..250 VAC, 5 A
24...48 VDC or 24...240 VAC, 50/60 Hz
24
22.5 mm mono or multifunction high immunity to interference
surface mounting snap-on DIN rail 35 mm
22.5 x 75 x 109
11, 12, 16, 19, 21, 22, 23, 24, 28, 31, 32, 33, 34, 41, 42, 51
12 time ranges, 0.05 s up to 60 h
1 relay as change-over, 250 VAC, 8 A
24...48 VDC or 24...240 VAC, 50/60 Hz
28
wide range of capabilities LED
surface mounting snap-on DIN rail 35 mm
22.5 x 75 x 109
11, 12, 16, 21, 22, 23, 24, 42, 19
10 time ranges, 0.05 s up to 60 hmulti time 0.05 up to 60 h
2 relays as change-over, instantaneous and/or timer, 250 VAC, 8 A
24...48 VDC or 24...240 VAC, 50/60 Hz
32
* 11: delayed operation; 12: delayed release; 16: delayed operation and release; 21: fleeting-on delay timer; 22: fleeting-off delay timer; 23: impulseconverter; 24: impulse generator; 42: flasher relay; 28: watchdog; 31/70: asymmetrical timer; 51: star-delta timer; 19: power off delayed release
www.saia-burgess.comsaia-burgess Control Devices 6 | 7
CMC CMT CMUType
Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Page
Hour MetersElectromechanical
micro counter minimal power consumption
flush mounting with clip
30 x 13 x 33
99.999.99 h
mechanical, 4 mm high digit decimal places in red
5 VDC and 12 VDC
38
DIN dimension
flush mounting with clip or 2 screws M3
45 x 22 x 49
DC: 999.999.99 hAC: 99.999.99 h
mechanical, 4 mm high digit decimal places in red
12...24 VDC and 230 VAC
42
cut-out 46 x 46 mm or 50.5 mm
flush mounting with clip
48 x 48
99.999.99 h
mechanical, 4 mm high digit
12...24 VDC24 or 230 VAC 50 Hz
44
large display standard DIN housing
flush mounting with clip
90 x 42 x 105
999.999, time units: h:min:s, s, 0.01h or 0.01s
LED, 13 mm high digit
11...30 VDC and 90...250 VAC
46
single, double or combined meter
programmable
flush mounting with clip
45 x 22 x 59
999.999, time units: h:min:s or s:min:h
LED, 8 mm high digit
10...30 VDC
48
LCD display preset value programmable resolution
flush mounting with clip
45 x 45 x 86
999.999, time units: h:min:s or s, min, h
LCD, backlight 9 mm high digit – counting 8 mm high digit – preset
11...30 VDC and 90...250 VAC
51
Type
Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Page
Hour MetersElectronic
CXR CXG 23, 28 CXE
www.saia-burgess.com saia-burgess Control Devices8 | 9
Type
Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Page
micro size for PCB machine solder washable
surface or PCB mounting flush mounting with clip snap-on DIN rail 35 mm
29 x 14 x 3527 x 35 x 1230 x 58 x 53
9.999.999
mechanical, 4 mm high digit optical
12 VDC, 24 VDC and 230 VAC
56
small size low current consumption
surface mounting with nut flush mounting with clamping
spring
31 x 20 x 55 (50)
999.999 without reset 99.999 with reset
mechanical, 4 mm high digit
24 VDC and 230 VAC
59
robust totalising counter, proven over many years
flush mounting with clampingspring
37 x 24 x 57
9.999.999 without reset 99.999 with reset
mechanical, 4 mm high digit
6, 12, 24, 110, 220 VDC 24, 115, 230 VAC
62
robust totalising counter with no,manual or electrical reset
surface mounting flush mounting with clamping
spring
28 x 52 x 72
99.999.999 without reset999.999 with reset
mechanical, 4 mm high digit
12, 24 VDC and 24, 115, 230 VAC
64
CMM CXB CXG 20, 26 CXG 21Type
Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Page
CountersElectromechanical, Preset Electronic, Totalising Electronic, Differential
battery operated (lithium)
flush mounting with clampingspring
screw mounting on front
45 x 22 x 40
99.999.999
LCD, 7 mm high digit
independent
69
up counting, manual reset down counting, manual and
electrical reset
flush mounting with clip
52 x 52 x 72
99.999 CMM152999.999 CMM362CMM152 counting up with permanent display of the preset valueCMM362 counting down
mechanical, 4 mm high digit
24 VDC and 24, 115, 230 VAC
66
single, double or combi counter programmable
flush mounting with clip
45 x 22 x 59
999.999
LED, 8 mm high digit
10...30 VDC
72
differential counter programmable
flush mounting with clip
45 x 22 x 59
–199.999...999.999
LED, 8 mm high digit
10...30 VDC
74
CountersElectromechanical, Totalising
CMB CMA CBG CMM
www.saia-burgess.comsaia-burgess Control Devices 8 | 9
1 preset value stationary display battery operated (lithium)
flush mounting with clip
45 x 45 x 86
–19.999...99.999
LCD, 7.5 mm high digit
independent
80
1 or 2 preset values or batch function
multifunction
flush mounting with clip
45 x 45 x 86
–999.999...999.999
LCD backlite, 9 mm high digit
12.5...30 VDC, 230 VAC
82
large display standard DIN housing
flush mounting with clip
90 x 42 x 105
999.999 h, min, s0.01 h or 0.01 s
LED, 13 mm high digit
11...30 VDC and 90...250 VAC
77
CXR CXP CXE CXDType
Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Page
counting up and down reset to zero or preset value
flush mounting with clip
45 x 45 x 86
–19.999...99.999
7-segment LED
24 VDC, 230 VAC
85
CountersElectronic, Preset
CXG 22, 25 CXD CXEType
Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Page
CXG22: tachometer/frequencycounter
CXG25: totalising counter andtachometer
flush mounting with clip
45 x 22 x 59
999.999 h, min, s0.01 h or 0.01 s
LED, 8 mm high digit
10...30 VDC
88
monitors revolutions/velocity flow rate control 1 limit value
surface mounting flush mounting with
clamping spring
45 x 45 x 86
0...99.999
LED, 7.5 mm high digit
12.5...30 VDC and 230 VAC
91
multifunction 1 or 2 limit values
flush mounting with clip
45 x 45 x 86
999.999 h, min, s0.01 h or 0.01 s
LCD backlight, 9 mm high digit
11...30 VDC and 90...250 VAC
94
CountersDigital, Tachometers
www.saia-burgess.com saia-burgess Control Devices10 | 11
KFE 100/101/301 KFE 300 KFE 302 KFE 102/103Type
Characteristics
Mounting
Dimensions (mm)
Setting
Time range
Outputs
Supply voltage
Function control
Page
Control RelaysAnalog Digital
monitors over/under voltage mono fixed/adjustable mono/three phase: 5 or 10 min
snap-on DIN rail 35 mm
35 x 85 x 58
KFE 100: Umin 0.75 UN; Umax 1.2 UN (fix)KFE 101/301: Umin 0.8 UN; Umax 1.2 UN
5 or 10 min, selection bywire bridge or switch
1 relay (change-over contact); 8 A, 250 VAC
KFE 100/101: 230 VAC; 50/60 Hz; KFE 301: 400 VAC; 50/60 Hz; P ≤ 4 VA
fault and power supply LED
100
monitors loss of phase control,phase order, phase asymmetryand under voltage
snap-on DIN rail 35 mm
35 x 85 x 58
control asymmetry 5 to 20% under voltage phase order (fixed) loss of phase (fixed)
300 ms (fixed)
1 relay (change-over contact); 8 A, 250 VAC
400 VAC; 50/60 Hz; P ≤ 4 VA
phase fault, fault asymmetryand power supply LED
103
three phase surveillance of AC voltage
snap-on DIN rail 35 mm
35 x 85 x 58
Umin 0.8 UN Umax 1.15 UN (fix) memory option over voltage fix 1.15 UN
0.1 to 12 sec
1 relay (change-over contact); 8 A, 250 VAC
400 VAC; 50/60 Hz; P ≤ 4 VA
fault and power supply LED
106
KFE 102 measures voltage AC/DC KFE 103 measures current AC/DC
snap-on DIN rail 35 mm
35 x 85 x 58
hysteresis 5 to 50% memory option KFE 102: Umin 15 V;
Umax 700 VDC/480 VAC KFE 103: Imin 0.1 A; Imax 10 A AC/DC
KFE 102: 0.1 to 12 sec KFE 103: 0.1 to 12 (20) sec
1 relay (change-over contact); 8 A, 250 VAC
230 VAC; 50/60 Hz; P ≤ 4 VA
display
109
AAD1KFT 100 KFT 200Type
Characteristics
Mounting
Dimensions (mm)
Setting
Outputs
Supply voltage
Function control
Page
Control Relays CounterThermistor Energy Meter
temperature monitor PTC short circuit detection PTC broken wire detection reset by supply interruption
surface mounting snap on DIN rail 35 mm
22.5 x 75 x 96
automatic reset
1 relay (NO contact)10 A, 250 VAC
230 VAC; 50/60 Hz; P ≤ 3 VA
red LED for faultgreen LED for power supply
112
temperature monitor memory fonction PTC short circuit detection PTC broken wire detection reset by supply interruption
surface mounting snap on DIN rail 35 mm
22.5 x 75 x 96
manual or automatic reset
1 relay (change-over contact)10 A, 250 VAC
230 VAC; 50/60 Hz; P ≤ 3 VA
red LED for faultgreen LED for power supply
112
single phase direct measurement class 1 precision PTB approval S0+/S0- output 1000 imp/kWh nominal current IN = 5 A,
Imax 25 A according EN61036
surface mounting snap on DIN rail 35 mm
17.5 x 85 x 59
999.999.9
mechanical, 4 mm high digit decimal places in red
230 VAC, 50/60 Hz; P ≤ 8 VA
flashing red LED
118
Type
Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Function control
Page
Saia-Burgess is active in thedevelopment and manufactureof Switches, Sensors, Motors,Control Components as well asrelated sub-systems.
www.saia-burgess.comsaia-burgess Control Devices 12 | 13
Timers
Type Preferred Products Page
Electromechanical KKH KKH10200B3E1N00 14KKH10200Q3E1N00KKH10200E4E1N00KKH10200B5E1N00KKH10200R5E1N00
KOE KOE511A0MVD5N00 17KOE511E0MVD5N00KOE512A0MVD5N00KOE512E0MVD5N00
Electronic KOP.F KOP260F0MWVAN00 20
Electronic KOL KOL360H7MRVPN00 24KOL311H7MRVPN00KOL312H7MRVPN00KOL321H7MRVPN00KOL342H7MRVPN00KOL251H7MKVPN00
Electronic KOP.J KOP111J7MWVPN00 28KOP112J7MWVPN00KOP160J7MWVPN00KOP170J7MWVPN00
Electronic KOP.K KOP511K7MWVPN00 32KOP512K7MWVPN00KOP560K7MWVPN00KOP119K7MWVPN00KOP219K7MWVPN00
KKH
Characteristics
Mounting
Dimensions (mm)
Functions*
Time ranges
Outputs
Supply voltage
www.saia-burgess.com saia-burgess Control Devices14 | 15
KKHCam programmer
Electromechanical
open, manual start timer manual time setting elapsed time indicator
flush mounting front or side mounting
55 x 73 x 65
no
1, 5, 15, 30 min1, 2, 3, 12, 24 h
2 snap-action as change-over, 250 VAC, 16 A
230 VAC, 50 Hz
Preferred Range
Ordering Reference Characteristics
Without limit stop of 5 mm milled shaft Mounted in self tapping screws 2 channels Supply voltage 220...240 V, 50 Hz
KKH10200B3E1N00 Time range 1 min
KKH10200Q3E1N00 Time range 5 min
KKH10200E4E1N00 Time range 15 min
KKH10200B5E1N00 Time range 1 h
KKH10200R5E1N00 Time range 6 h
www.saia-burgess.comsaia-burgess Control Devices 14 | 15
Technical dataTime ranges 1 min 1 h
5 min 2 h15 min 3 h30 min 6 h
12 h24 h
Max. setting time 95% of the time rangeMin. setting time 5% of the time rangeSetting accuracy 2% of the time rangeElapsed time indicator by the rotating shaftSupply voltage 187…264 VAC, 50 HzPower consumption 3.5 VAOutputs snap-action switches with pure silver contacts (change-over)Switching capacity 250 VAC, 16 AInsulation voltage 2 kV/50 HzDegree of protection protection class II between plate shaft switch and motorApprovals UL on requestAmbient temperature –15°C to +50°CConnections motor: multistrand, 150mm length, with plug-on connectors 6.3 x 0.8mm
snap-action switches: plug-on connectors 6.3 x 0.8mm (with hole for soldering)Mounting flush mounting
on the front: mounting with 2 self-tapping screws Ø 3.5mmon the side: mounting with 2 screws M3any mounting position
Circuit diagrams
x = period for setting the timet = set timez = differential between channel a and b
(1% of the time range final value)
KKH
www.saia-burgess.com saia-burgess Control Devices16 | 17
KKH
Technical dataDimensions
Type KKH
Shaft 0 Shaft for setting knob with 5 mm flat, and limit stop1 Shaft for setting knob with 5 mm flat, without limit stop2 Shaft for setting knob without flat, and limit stop3 Shaft for setting knob without flat, and without limit stop6 Shaft for setting knob with 4.6 mm flat, and limit stop7 Shaft for setting knob with 4.6 mm flat, without limit stop
Type 0 Self tapping screws, ø 30 mm 4 Screws M4, ø 30 mmof mounting 1 Self tapping screws, ø 28.5 mm 5 Screws M3, ø 28.5 mm
3 Screws M3, ø 30 mm 6 Screws M4, ø 28.5 mm
Number 1 One channelof channels 2 Two channels
3 Three channels
Program cams OO Standard milled camO1 Adjustable (s) camO2 Adjustable (r) cam
Time ranges E2 15 s B3 1 min B5 1 hJ2 30 s Q3 5 min F5 2 hN2 45 s (only for 50 Hz) B4 10 min J5 3 h
E4 15 min R5 6 hJ4 30 min C6 12 h
G6 24 h
Supply voltage B1 12 V, 50 Hz G1 12 V, 60 HzB4 24 V, 50 Hz G4 24 V, 60 HzD1 110–120 V, 50 Hz J1 110–120 V, 60 HzE1 220–240 V, 50 Hz K1 220–240 V, 60 Hz
NOO
Ordering Reference
KOECharacteristics
Mounting
Dimensions (mm)
Functions*
Time ranges
Outputs
Supply voltage
www.saia-burgess.comsaia-burgess Control Devices 16 | 17
KOETimer
Electromechanical
additional functions elapsed time indicator
surface mounting snap on or screws flush mounting with clip
surface: 45 x 70 x 99 flush: 45 x 45 x 93
11, 12, 21, 22, 23 by external wiring
6 time ranges, selected 0.1s...60 h
1 timed and 1 instantaneous change-over contact, 250 VAC, 2/5 A
230 VAC, 50 Hz
Preferred Range
Ordering Reference Characteristics
Output 1 timed and 1 instantaneous contact Time range Multi time (selected) 0.1 s...60 h Supply voltage 230 V, 50 Hz
KOE511A0MVD5N00 Delayed operation Surface mounting
KOE511E0MVD5N00 Delayed operation Flush mounting
KOE512A0MVD5N00 Delayed release Surface mounting
KOE512E0MVD5N00 Delayed release Flush mounting
* 11: delayed operation; 12: delayed release; 16: delayed operation and release; 21: fleeting-on delay timer;22: fleeting-off delay timer; 23: impulse converter; 24: impulse generator; 42: flasher relay; 28: watchdog;31/70: asymmetrical timer; 51: star-delta timer; 19: power off delayed release
www.saia-burgess.com saia-burgess Control Devices18 | 19
Technical dataMulti time ranges 0.1…6s, 1…60s, 0.1…6min, 1…60min, 0.1…6h, 1…60h (by selection)Min. setting time 2% of the time range final value (tmax.)Setting accuracy 1.5% of the time range final value (tmax.)Repeat accuracy ±1.5% of the time range final value (tmax.)Reset time KOE511: 200 msElapsed time indicator by rotating time indicatorSupply voltage 207…253 VAC, 50 HzPower consumption < 6 VA over allDuty cycle 100%Outputs 1 timed and 1 instantaneous contact as potential-free change-overSwitching capacity timed contact: 250 VAC/5 A
instantaneous contact: 250 VAC/2 AInsulation voltage 2 kV/50 HzProtection class surface mounting: front IP 50, terminals IP 30
flush mounting: front IP 50, terminals IP10Approvals UL, C-ULAmbient temperature –10°C to +60°CConnections screw terminals for 2 x 2.5 mm2 (single wire) or 2 x 1.5 mm2 (multistrand with end sleeve)Mounting surface mounting: snap-on mounting on DIN rail 35 mm or mounting with 2 screws M4
flush mounting: mounting by plastic spring clip any mounting position
Circuit diagrams
KOE
KOE 511: delayed operation, resetting on supply failure(fleeting-on delay timer and pulse lengthening by external wiring)
KOE 512: delayed release, standstill at zero voltage(fleeting-off delay timer by external wiring)
Voltage interruption for a reset >200ms
Duration of the control pulse >200ms
www.saia-burgess.comsaia-burgess Control Devices 18 | 19
Technical dataDimensions
KOE
Type KOE
Function 511 1 instantaneous contact, 1 contact with delayed operationstandstill at zero voltage
512 1 instantaneous contact, 1 contact with delayed release
Housing A0 Surface mounting (screw-type)E0 Flush mounting (screw-type)F0 Flush or plug-in type mounting (11 poles)
Supply voltage MVB4 24 V, 50 HzMVD1 110–120 V, 50 HzMVD5 230 V, 50 HzMVG4 24 V, 60 HzMVJ1 110–120 V, 60 HzMVJ5 230 V, 60 Hz
NOO
Accessories CJ 211 11-pin socket (47 x 47 x 20 mm) for flush mounting, connections with screw terminalsCJ 250 11-pin socket (68 x 68 x 24 mm) for mounting with screws or snap-on mounting on DIN rail 35 mm
connections with screw terminals
Ordering Reference
Surface mounting
Flush mounting
KOP.FCharacteristics
Mounting
Dimensions (mm)
Functions*
Time ranges
Outputs
Supply voltage
www.saia-burgess.com saia-burgess Control Devices20 | 21
KOP.FTimer
Electronic
large rotary dial DIN dimensions multifunction multi time range multi voltage
flush mounting plug-in on 11 pin socket
45 x 45 x 95
211, 212, 217, 221, 223, 247 by external wiring
12 time ranges, selected 0.01s...10 h
1 relay with two contacts as change-over, 250 VAC, 5 A
24...230 VDC/VAC, 50/60 Hz
Preferred Range
Ordering Reference Characteristics
KOP260F0MWVAN00 Panel cut out 48 x 48 mm Multi time range 0.01 s...10 h Supply voltage 24...230 V AC/DC Multi functions: Delayed, Fleeting, Impulse converter, Flasher relay
* 11: delayed operation; 12: delayed release; 16: delayed operation and release; 21: fleeting-on delay timer;22: fleeting-off delay timer; 23: impulse converter; 24: impulse generator; 42: flasher relay; 28: watchdog;31/70: asymmetrical timer; 51: star-delta timer; 19: power off delayed release
www.saia-burgess.comsaia-burgess Control Devices 20 | 21
Technical dataMulti time ranges 0.01…0.5s 0.01…0.5min 0.01…0.5h
0.02… .1s 0.02… .1min 0.02… .1h0.1… .5s 0.1… .5min 0.1… .5h0.2….10s 0.2….10min 0.2….10h
time range, unit of time and function are all selected from front panel with screwdriverSetting accuracy ±3% of the time range final value (tmax.)Repeat accuracy ±1% of the time range final value (tmax.)Reset time 100 ms with pulse control
300 ms with supply controlSupply voltage 24…230 VDC/VAC, ±15%, 50/60 HzPower consumption 3 W at VDC, 3.5 VA at VACDuty cycle 100%Pulse control supply voltage range, duration of the control pulse >50 ms Outputs 1 relay with two contacts as change-over, green LED remains lit during timingSwitching capacity U = 250 VAC, Ith = 5 A, P = 1250 VA
2.5 A/250 VAC (AC14), 5A/24 VDCInsulation characteristics 2 kVAC/50 Hz test voltage according to VDE 0435 and 4kV 1.2/50ms surge voltage according to
EN 60947-5-1 between all inputs and outputsEMC/Interference immunity surge capacity according to IEC 1000-4-5, level 3; Burst according to IEC1000-4-4, level 3;
ESD according to IEC 1000-4-2, level 3EMC/Emissions electromagnetic fields according to EN 55022, class BProtection class front IP 40Approvals UL, C-ULAmbient temperature –10°C to +55°CMounting flush mounting with plastic spring clip or surface mounting with plug-in socket (accessory) for mounting
with 2 screws M3 or snap-on mounting on DIN rail 35mm, any mounting position
KOP.F
www.saia-burgess.com saia-burgess Control Devices22 | 23
Technical dataCircuit diagrams
U
Outputs 1⁄2
green LED
yellow LED
U
S1)
Outputs 1⁄2
green LED
yellow LED
U
S2)
Outputs 1⁄2
green LED
yellow LED
U
S
Outputs 1⁄2
green LED
yellow LED
U
S3)
Outputs 1⁄2
green LED
yellow LED
U
S
Outputs 1⁄2
green LED
yellow LED
1) The falling edge of S starts the sequence of t; the rising edge of S leads to a reset of t.2) Function 221 requires a jumper between terminals 2 and 7.
A Delayed operation with pulse control (217)
B Fleeting-on delay timer (221)
B Impulse converter (223)
C Flasher relay starting with pause and reset (247)
D Delayed release (212)
A Delayed operation with pulse control (211)
KOP.F
www.saia-burgess.comsaia-burgess Control Devices 22 | 23
KOP.F
Type KOP
Function 260 Multi function with 2 contacts
Housing F0 Flush or plug-in type mounting (11 poles)
Time ranges MW 0.01 s...10 h, multi time range
Supply voltage BA 12 VAC/DCBK 24 VAC/DCCA 48 VAC/DCCW 110 VAC/DCR1 110...240 VACVA 24...230 VAC/DC
NOO
Accessories CJ 211 11-pin socket (47 x 47 x 20 mm) for flush mounting, connections with screw terminalsCJ 250 11-pin socket (68 x 68 x 24 mm) for mounting with screws or snap-on mounting on DIN rail 35 mm
connections with screw terminals
Ordering Reference
Dimensions
Panel cut out:45 x 45 mm
Technical data
KOLCharacteristics
Mounting
Dimensions (mm)
Functions*
Time ranges
Outputs
Supply voltage
www.saia-burgess.com saia-burgess Control Devices24 | 25
KOLTimer
Electronic 17.5 mm
17.5 mm multifunction multi time range multi voltage
surface mounting snap-on DIN rail 35 mm
17.5 x 80 x 70
11, 12, 21, 42, 51, 60
6 time ranges, 0.05 s up to 10 h
1 relay NO, KOL1..1 relay as change-over, KOL3..250 VAC, 5 A
24...48 VDC or 24...240 VAC, 50/60 Hz
Preferred Range
Ordering Reference Characteristics
Multi time range 0.05 s...10 h Multi voltage 24...48 VDC and 24...240 VAC
KOL360H7MRVPN00 Multi functions timer 311/12/21/42
KOL311H7MRVPN00 Delayed operation timer
KOL312H7MRVPN00 Delayed release timer
KOL321H7MRVPN00 Fleeting-on delay timer
KOL342H7MRVPN00 Flasher relay timer
KOL251H7MKVPN00 Star/delta timer
* 11: delayed operation; 12: delayed release; 16: delayed operation and release; 21: fleeting-on delay timer;22: fleeting-off delay timer; 23: impulse converter; 24: impulse generator; 42: flasher relay; 28: watchdog;31/70: asymmetrical timer; 51: star-delta timer; 19: power off delayed release
www.saia-burgess.comsaia-burgess Control Devices 24 | 25
KOL
Technical dataMulti time ranges 0.05…1 s 0.05…1 min 0.05…1 h
0.5…10 s 0.5…10 min 0.5…10 htime range and function selected from front with screwdriver
Setting accuracy ±5% of the time range final value (tmax.)Repeat accuracy 1% of the time range final value (tmax.)Reset time 100 msSupply voltage 24…48 VDC or 24…240 VAC, 50/60 Hz (dual voltage)Voltage tolerance –15%/+20% (DC), –15%/+10% (AC)Power consumption 0.5 W at 24 VDC, 5 VA at 240 VACDuty cycle 100%Pulse control supply voltage range, current 1 mA, duration of the control pulse >250 msOutput 1 relay as change-over, LED display of output statusSwitching capacity U = 250 VAC, Ith = 5 A, P = 1000 VA
1 A/250 VAC (AC 14) or 1 A/24 VDC (DC 13) according to IECInsulation characteristics 2 kVAC/50 Hz test voltage according to VDE 0435
and 4 kV 1.2/50ms surge voltage according to EN 60947-5-1 between all inputs and outputs
EMC/Interference immunity surge capacity according to IEC 1000-4-5, level 3;Burst according to IEC1000-4-4, level 3;ESD according to IEC 1000-4-2, level 3
EMC/Emissions electromagnetic fields according to EN 55022, class BApprovals UL, C-ULAmbient temperature –20°C to +50°CConnections screw terminals for 1x 0.5mm2 up to 2 x 2.5mm2, for Pozidrive no.1 (max.1Nm) or screwdriver, finger safe
according to VDE 0106Mounting surface mounting; snap-on mounting on DIN rail 35 mm or screw mounting by adapter (accessory) and
2 screws M4, any mounting position
www.saia-burgess.com saia-burgess Control Devices26 | 27
Technical dataCircuit diagrams
KOL
Delayed operation (11)
Delayed release (12)
Flasher relay (42)
Star-delta relay (251)
Fleeting-on delay timer (21)
= green LED: power on= orange LED: output in operating position
= green LED: output in operating position
www.saia-burgess.comsaia-burgess Control Devices 26 | 27
KOL
Type KOL
Function 111 Mono function, 4 time range, delayed operation311 Mono function, 6 time range, delayed operation112 Mono function, 4 time range, delayed release312 Mono function, 6 time range, delayed release121 Mono function, 4 time range, fleeting-on delay timer321 Mono function, 6 time range, fleeting-on delay timer142 Mono function, 4 time range, flasher relay342 Mono function, 6 time range, flasher relay160 Multi function, 4 time range360 Multi function, 6 time range 251 Dual Voltage, 4 time range, star-delta relay
Housing H7 6 Terminals
Time ranges MN Multi time 0.5 s...1 h, for KOL 112, 160MN Multi time 0.75 s...1 h, for KOL 111, 121, 142MR Multi time 0.05 s...10 h, for KOL3...MK Multi time 0.15 s...10 min, for KOL251 only
Supply voltage VP 24...240 VAC & 24...48 VDC, for KOL3...M1 12 VDCVM 230–240 VAC for KOL1...
NOO
Accessories CJ260 Adapter for screw mounting
Ordering Reference
Technical dataDimensions Timer Adapter for screw mounting
KOP.JCharacteristics
Mounting
Dimensions (mm)
Functions*
Time ranges
Outputs
Supply voltage
www.saia-burgess.com saia-burgess Control Devices28 | 29
KOP.JTimer
Electronic 22.5 mm
Preferred Range
Ordering Reference Characteristics
Multi time range 1 s...60 h Supply voltage 24...48 VDC & 24...240 VAC
KOP111J7MWVPN00 Delayed operation
KOP112J7MWVPN00 Delayed release
KOP160J7MWVPN00 Universial 8 functions 111/112/116/121/122/123/124/142+on/off
KOP170J7MWVPN00 Asymmetrical impulser
* 11: delayed operation; 12: delayed release; 16: delayed operation and release; 21: fleeting-on delay timer;22: fleeting-off delay timer; 23: impulse converter; 24: impulse generator; 42: flasher relay; 28: watchdog;31/70: asymmetrical timer; 51: star-delta timer; 19: power off delayed release
22.5 mm mono or multifunction high immunity to interference
surface mounting snap-on DIN rail 35 mm
22.5 x 75 x 109
11, 12, 16, 19, 21, 22, 23, 24, 28, 31, 32, 33, 34, 41, 42, 51
12 time ranges, 0.05 s up to 60 h
1 relay as change-over, 250 VAC, 8 A
24...48 VDC or 24...240 VAC, 50/60 Hz
www.saia-burgess.comsaia-burgess Control Devices 28 | 29
Technical dataTime ranges 0.05…1 s 0.05…1 min 0.05…1 h
0.15…3 s 0.15…3 min 0.15…3 h0.5…10 s 0.5…10 min 0.5…10 h1.5…30 s 1.5…30 min 3…60 h(multi-versions: time range and function selected from front with screwdriver)
Setting accuracy ±5% of the time range final value (tmax.)Repeat accuracy ±0.2% of preset valueReset time 50 msSupply voltage 24…48 VDC or 24…240 VAC, 50/60 Hz (dual voltage)Voltage tolerance ±20% (DC), –15%/+10% (AC)Power consumption 1.5 W (DC) or 1.5 VA (AC)Duty cycle 100%Pulse control supply voltage range, current 1 mA, duration of the control pulse >50 ms (AC), >30 ms (DC),
pause >55 ms (DC)Output 1 relay as change-over, LED display of output statusSwitching capacity U = 440 VAC, Ith = 8 A, P = 2000 VA
3A/250 VAC (AC 15), 3A/440 VAC (AC 14) or 1 A/24 VDC (DC 13) according to IECInsulation characteristics 2 kVAC/50Hz test voltage according to VDE0435 and 6 kV 1.2/50 ms surge voltage according to
EN 60947-5-1 between all inputs and outputsEMC/Interference immunity surge capacity of the power supply according to IEC 1000-4-5: 4kV 1.2/50 ms
burst according to IEC 1000-4-4: 6 kV 6/50 ns ESD according to IEC 1000-4-2: at contact 8kV, in air 8 kVelectromagnetic HF field according to IEC 801-3 and electromagnetic HF signal from wiring arrangementaccording to IEC 801-6: level 3
EMC/Emissions electromagnetic fields according to EN 55022, class BSecure isolation according to VDE 106, part 101Protection class case IP 40, terminals IP 20Approvals UL, C-ULAmbient temperature open –20°C to +60°C
enclosed –20°C to +45°CConnections screw terminals for 1 x 0.5 mm2 up to 2 x 2.5 mm2 (single wire) or 2 x 1.5 mm2 (multistrand with end sleeve),
AWG 14…20, with dual chamber system, screws M3.5 for Pozidrive no.2 (Philips) and no.2 slot, suitable forpower screwdrivers (max. 1.2 Nm), finger safe according to VDE 0106
Mounting surface mounting; snap-on mounting on DIN rail 35mm or screw mounting by adapter (accessory) and2 screws M4, any mounting position
KOP.J
www.saia-burgess.com saia-burgess Control Devices30 | 31
Technical dataCircuit diagrams
KOP.J
– output in rest position, no timing
– output in rest position, time running
– output in operating position, no timing
– output in operating position, time running
LED status display
Delayed operation (111)
Delayed release (112)
Fleeting-off delay timer (122)
Impulse converter (123)
Impulse generator (124)
Flasher relay starting with pulse (142)
Star-delta relay (251)
Fleeting-on delay timer (121)
Delayed operation and release (116)
Flasher relay starting with pause (141)Delayed operation with pulse control (118)
Fleeting-on delay timer with pulse control (128) “watchdog”
With supply voltage control and starting with pause (131) With supply voltage control and starting with pulse (132)
With pulse control and starting with pause (133) With pulse control and starting with pulse (134)
1) Another voltage than the supply voltage can also be used for pulse control, for example A1–A2 = 230VAC and B1–A2 = 24 VDC.
KOP160: universal timerwith 10 time ranges and 8 functions (111, 112, 116, 121, 122, 123, 124, 142)plus on/off function for commissioning and maintenance
On function Off function
www.saia-burgess.comsaia-burgess Control Devices 30 | 31
KOP.J
Type KOP
Function 111 Delayed operation112 Delayed release116 Delayed operation and release118 Delayed operation with pulse control121 Fleeting-on delay timer122 Fleeting-off delay timer123 Impulse converter124 Impulse generator128 Fleeting-on delay timer with pulse control "watchdog"141 Flasher relay starting with pause142 Flasher relay starting with pulse160 Universal timer170 Asymmetrical impulser251 Star-delta relay
Housing J7 6 Terminals
Time ranges BA 0.05...1 s GA 0.05...1 min NA 0.05...1 hCA 0.15...3 s HA 0.15...3 min PA 0.15...3 hEA 0.5...10 s KA 0.5...10 min RA 0.5...10 hFA 1.5...30 s LA 1.5...30 min WA 3...60 h
MW Multi time 0.05 s...60 h
Supply voltage VP 24...240 VAC & 24...48 VDCM1 12 VDCE9 346...440 VAC, (without UL approval)VA 24...240 VAC / VDC
NOO
Accessories CJ260 Adapter for screw mounting
Ordering Reference
DimensionsTimer Adapter for screw mounting
Technical data
www.saia-burgess.com saia-burgess Control Devices32 | 33
KOP.KTimer
Electronic 22.5 mm
KOP.KCharacteristics
Mounting
Dimensions (mm)
Functions*
Time ranges
Outputs
Supply voltage
Preferred Range
Ordering Reference Characteristics
Function Time range Supply voltage
KOP511K7MWVPN00 Delayed operation 1 s...60 h 24...48 VDC and 24...240 VAC
KOP512K7MWVPN00 Delayed release 1 s...60 h 24...48 VDC and 24...240 VAC
KOP560K7MWVPN00 Multi function 1 s...60 h 24...48 VDC and 24...240 VAC
KOP119K7MWVPN00 True off delay after power off 1 outp. 0.15 s...10 min 24...240 VAC/DC
KOP219K7MWVPN00 True off delay after power off 2 outp. 0.15 s...10 min 24...240 VAC/DC
* 11: delayed operation; 12: delayed release; 16: delayed operation and release; 21: fleeting-on delay timer;22: fleeting-off delay timer; 23: impulse converter; 24: impulse generator; 42: flasher relay; 28: watchdog;31/70: asymmetrical timer; 51: star-delta timer; 19: power off delayed release
wide range of capabilities LED
surface mounting snap-on DIN rail 35 mm
22.5 x 75 x 109
11, 12, 16, 21, 22, 23, 24, 42, 19
10 time ranges, 0.05 s up to 60 h multi time 0.05 up to 60 h
2 relays as change-over, instantaneous and/or timer, 250 VAC, 8 A
24...48 VDC or 24...240 VAC, 50/60 Hz
www.saia-burgess.comsaia-burgess Control Devices 32 | 33
Technical dataMulti time ranges 0.05…1 s 0.05…1 min 0.05…1 h
0.15…3 s 0.15…3 min 0.15…3 h0.5…10 s 0.5…10 min 0.5…10 h
3…60 h(time range and function selected from front with screwdriver)
Setting accuracy ±5% of the time range final value (tmax.)Repeat accuracy ±0.2% of preset valueReset time 50 msSupply voltage 24…48VDC or 24…240VAC, 50/60Hz (dual voltage)Voltage tolerance ±20% (DC), –15%/+10% (AC)Power consumption 1.5 W (DC) or 1.5 VA (AC)Duty cycle 100%Pulse control supply voltage range, current 1mA, duration of the control pulse >50ms (AC), >30ms (DC), pause >55ms (DC)Outputs 2 relays as change-over, LED display of output statusSwitching capacity U = 440 VAC, Ith = 8 A, P = 2000 VA
3 A/250 VAC (AC 15), 3 A/440 VAC (AC 14) or 1 A/24 VDC (DC 13) according to IECInsulation characteristics 2 kVAC/50 Hz test voltage according to VDE0435 and 6 kV 1.2/50 ms surge voltage according
to EN 60947-5-1 between all inputs and outputsEMC/Interference immunity surge capacity of the power supply according to IEC 1000-4-5: 4kV 1.2/50ms
burst according to IEC 1000-4-4: 6kV 6/50 nsESD according to IEC 1000-4-2: at contact 8 kV, in air 8kVelectromagnetic HF field according to IEC 801-3 and electromagnetic HF signal from wiring arrangementaccording to IEC 801-6: level 3
EMC/Emissions electromagnetic fields according to EN 55022, class BSecure isolation according to VDE 106, part 101Protection class case IP 40, terminals IP 20Approvals UL, C-ULAmbient temperature open –20°C to +60°C
enclosed –20°C to +45°CConnections screw terminals for 1 x 0.5mm2 up to 2 x 2.5mm2 (single wire) or 2 x 1.5mm2 (multistrand with end sleeve),
AWG 14…20, with dual chamber system, screws M3.5 for Pozidrive no.2 (Philips) and no.2 slot, suitable forpower screwdrivers (max. 1.2 Nm), finger safe according to VDE 0106
Mounting surface mounting; snap-on mounting on DIN rail 35mm or screw mounting by adapter (accessory) and2 screws M4, any mounting position
KOP.K
www.saia-burgess.com saia-burgess Control Devices34 | 35
KOP.K
– output in rest position, no timing
– output in rest position, time running
– output in operating position, no timing
– output in operating position, time running
LED status display
Delayed operation (511/11)
Delayed release (512/12)
Fleeting-off delay timer (22)
Impulse converter (23)
Impulse generator (24)
Flasher relay starting with pulse (42)
KOP560: universal timerwith 10 time ranges and 8 functions (11 to 42) plus on/off function for com-missioning and maintenance
Fleeting-on delay timer (21)
Delayed operation and release (16)
1) For pulse control, another voltage than the supply voltage can also be used, for example A1–A2 =230VAC and B1–A2 = 24VDC.
2) Output 2 selected as instantaneous contact with sliding switch on front panel (output switches withsupply voltage U or with control pulse S).
3) Bridge or potentiometer 10kW, min. 0.25W (low voltage) for external time setting.
True off delay after power off (119/219)
On function Off function
Technical dataCircuit diagrams
www.saia-burgess.comsaia-burgess Control Devices 34 | 35
KOP.K
Type KOP
Function 119 Delayed operation219 Delayed release511 Delayed operation and release512 Delayed operation with pulse control560 Fleeting-on delay timer
Connection K7 12 screw mounting
Time ranges BA 0.05...1 s GA 0.05...1 min NA 0.05...1 hCA 0.15...3 s HA 0.15...3 min PA 0.15...3 hEA 0.5...10 s KA 0.5...10 min RA 0.5...10 h
WA 3...60 hMW Multi time 0.05 s...60 h
Supply voltage VP 24...240 VAC & 24...48 VDCM1 12 VDCE9 346...440 VAC, (without UL approval)VA 24...240 VAC/VDC
NOO
Accessories CJ260 Adapter for screw mounting
Ordering Reference
Dimensions
www.saia-burgess.comsaia-burgess Control Devices 36 | 37
Hour meter
Type Preferred Products Page
Electromechanical CMC CMC072L7N0L0N00 38
Electromechanical CMT CMT072E1N0L0N00 42
Electromechanical CMU CMU072E1N0L0N00 44
Electronic CXR CXR262VKN0N0N00 46
Electronic CXG CXG231M4N 48CXG281M4N
Electronic CXE CXE312M4L 51CXE322M4L
www.saia-burgess.com saia-burgess Control Devices38 | 39
CMCHour meter
Electromechanical
CMCCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting fixed by spring clip Supply voltage: 12 VDC Time base: quartz
CMC072L7N0L0N00 Capacity: 99.999.9 h
micro counter minimal power consumption
flush mounting with clip
30 x 13 x 33
99.999.99 h
mechanical, 4 mm high digit decimal places in red
5 VDC and 12 VDC
www.saia-burgess.comsaia-burgess Control Devices 38 | 39
Technical dataCounting capacity 99.999.99 hTime base quartz (switch-on times of <36s, about 0.01 h, are not counted)Reset noneDisplay dials; white figures on black background, decimal places in red, 1.2 x 4mm (optical)Supply voltage details see under ordering numbers, AC 50/60 Hz, voltage tolerance DC/AC ±10% residual ripple DC max. 48% Power consumption 10…55 mW at 5 VDC
48…250 mW at 24 VDC0.7 VA at 230 VAC
EMC/Interference immunity according to EN 50082-1EMC/Emission according to EN 55014Protection class front IP65 (flush mounting)Ambient temperature –10°C to +60°CMounting details see under dimensions, any mounting positionConnections details see under dimensions
CMC
www.saia-burgess.com saia-burgess Control Devices40 | 41
CMC970: Surface mounting, plug-in on printed circuit board, machine solderable andwashable
CMC976: Surface mounting, plug-in on printed circuit board, machine solderable andwashable
CMC072: Flush mounting, mounting by plastic spring clip, connection with flexible leads of150mm length
CMC
Dimensions
Technical data
www.saia-burgess.comsaia-burgess Control Devices 40 | 41
CMC
Type CMC
Housing 970 Surface mounting on printed circuit board, solderable and washableO72 Flush mountingO79 Surface mounting, snap-on mounting on DIN rail 35mm
Supply voltage L7 5 VDCM1 12 VDCM4 24 VDCE1 220...240 VAC
N0L0 N00
Ordering Reference
CMC079: Surface mounting, snap-on mounting on DIN rail 35mm or mounting with 1 screwM4, connection with screw terminals for 2 x 2.5mm2 single wire
Dimensions
Technical data
www.saia-burgess.com saia-burgess Control Devices42 | 43
CMTHour meter
Electromechanical
CMTCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting fixed by spring clip Supply Voltage: 230 V, 50 Hz Time base: main frequency
CMT072E1N0L0N00 99.999,99h without reset
DIN dimension
flush mounting with clip or 2 screws M3
45 x 22 x 49
DC: 999.999.99 hAC: 99.999.99 h
mechanical, 4 mm high digit decimal places in red
12...24 VDC and 230 VAC
www.saia-burgess.comsaia-burgess Control Devices 42 | 43
Technical dataCounting capacity DC: 999.999.99h
AC: 99.999.99hTime base DC: quartz, AC: mains frequencyReset withoutDisplay dials; white figures on black background, decimal places in red, 1.8 x 4mmSupply voltage 10…27 VDC
198…264 VAC, 50HzPower consumption 180 mW at 12 VDC, 2VA at 220 VACEMC/Interference immunity according to EN 50082-1EMC/Emission according to EN 55014Protection class front IP52Ambient temperature –15°C to +50°CMounting flush mountingConnections screw for single wire
Dimensions
CMT
Flush mounting, mounting by plastic spring clip, connection with screwterminals for 2 x 2.5mm2 single wire
Mounting with 2 screws M3 and front frame CJ405 (accessory)
Type CMT
Function 072 99.999.99 h, Clip-on mounting
Supply voltage T5 12...24 VDC G4 24 VAC, 60 HzB4 24 VAC, 50 Hz J1 110...120 VAC, 60 HzD1 110...120 VAC, 50 Hz K1 220...240 VAC, 60 HzE1 220...240 VAC, 50 Hz VC 36...80 VDC
Connection N Screw only for CMT072
N0L0 N00
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices44 | 45
CMUHour meter
Electromechanical
CMUCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting fixed by spring clip Supply voltage, 230 V, 50 Hz Time base: main frequency
CMU072E1N0L0N00 Display: 99.999.99 h
cut-out 46 x 46 mm or 50.5 mm
flush mounting with clip
48 x 48
99.999.99 h
mechanical, 4 mm high digit
12...24 VDC24 or 230 VAC 50 Hz
www.saia-burgess.comsaia-burgess Control Devices 44 | 45
Technical dataCounting capacity 99.999.99hTime base DC: quartz, AC: mains frequencyReset noneDisplay dials; white figures on black background, decimal places in red, 1.8 x 4mmSupply voltage 12…24 VDC
24…400 VAC, 50 Hz or 60 HzPower consumption 180 mW at 12 VDC, 2 VA at 220 VACEMC/Interference immunity according to EN 50082-1EMC/Emission according to EN 55014Protection class front IP52Approvals UL, CSAAmbient temperature –15°C to +50°CMounting flush mounting, mounting by plastic spring clip, any mounting positionConnections screw terminals for 2 x 2.5mm2 single wire
Dimensions
CMU
Type CMU
Function 072 99.999.99 h, Clip-on mounting
Supply voltage T5 12...24 VDC G4 24 VAC, 60 Hz E5 400 VAC, 50 HzB4 24 VAC, 50 Hz J1 110...120 VAC, 60 Hz K5 400 VAC, 60 HzD1 110...120 VAC, 50 Hz K1 220...240 VAC, 60 HzE1 220...240 VAC, 50 Hz
N0L0 N00
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices46 | 47
CXRHour meter
Electronic
CXRCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting with spring clip Supply voltage: 115...230 VAC Time base: quarz (s, 0.01 s or 0.01 h)
CXR262VKN0N0N00 Capacity: 999.999 or 99:59:59
large display standard DIN housing
flush mounting with clip
90 x 42 x 105
999.999, time units: h:min:s, s, 0.01h or 0.01s
LED, 13 mm high digit
11...30 VDC and 90...250 VAC
www.saia-burgess.comsaia-burgess Control Devices 46 | 47
Technical dataCounting capacity 999.999, time unit (h/min/s, s, 0.01h or 0.01s) selected by DIL switchesTime base quartzReset to zero; none, manual and/or electrical, selected by DIL switches (reset impulse: min. length 5 ms)Display 7-segment LED, 13 mm highSupply voltage 11…30 VDC (Uin), residual ripple max. 5%
90…250 VAC, 50/60 HzPower consumption 14W (24 VDC) or 15 VA (AC)Types of sensor contacts, voltage impulses, electronic sensors NPN/PNP
(pull-up or pull-down input mode selected by DIL switches)Input voltage DC: Low 0…0.2 x Uin, High 0.6 x Uin…30V
AC: Low 0…4V, High 8…30VSensor supply AC: Vs = 24 VDC, ±10%, max.150 mAEMC/Interference immunity according to EN 50082-2EMC/Emission class B according to EN 55011Data protection min.10 years (EEPROM)Protection class front IP40Ambient temperature 0°C to +50°CMounting flush mounting, mounting by plastic spring clip, any mounting positionConnections 2 x plug-in screw terminal connection, block X1 (main supply) for wires 0.2…2.5mm2,
block X2 (inputs) for wires 0.14…1.5mm2
Connection diagram
Dimensions
CXR
Detailed information on programming and electrical connection isenclosed with the counter.
Type CXR
Function 262 scaling factor 0.0001 ... 999.999 via keyboard, Screw terminal
Supply voltage VK 115...230 VACVB 10...30 VDC
N0N0 N00
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices48 | 49
CXG 23, 28Hour meter
Electronic
CXG 23, 28Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting Time base, sec. min. h Capacity: 999.999 or 99:59:59 Supply voltage, 24 VDC
CXG231M4N Hour meter
CXG281M4N Duplicate hour meter
single, double or combined meter programmable
flush mounting with clip
45 x 22 x 59
999.999, time units: h:min:s or s:min:h
LED, 8 mm high digit
10...30 VDC
www.saia-burgess.comsaia-burgess Control Devices 48 | 49
Technical dataCounting frequency max. 30 i/s (counting pulse min.5 ms) or 10000 i/sReset none, manual and/or electrical (reset pulse min. 5 ms)Display 7-segment LED, 8mm high suppression of preceding zeros with or without fixed decimal pointSupply voltage 10…30 VDC (Uin)Power consumption max. 50 mATypes of pulse generator contacts, voltage pulses, electronic transmitters NPN/PNP (pull-up or pull-down)Input voltage low 0…0.2 x Uin, high 0.6 x Uin…30VDCInput resistance approx 10 kWOutput optocoupler, max. 30 V/10 mAEMC/interference immunity class B according to EN 55011 or EN 50082-2EMC emission according to EN 55081-2Data protection EEPROM, min.10 years or 1 million memory cyclesProtection class front IP65Ambient temperature operation: –10°C to +50°C
storage: –25°C to +70°CMounting flush mounting, mounting by plastic spring clip or 2 x M4 screws, any mounting positionConnections screw terminals for 0.2…2.5mm2
Connectiondiagrams
Dimensions
CXG 23, 28
Detailed information on programming and electrical connection isenclosed with counters.1) With optocoupler output
Collector Output1)
Emitter
Reset/Set Reset
INP B Input B
INP A Input A
0V (GND)
Supply voltage 10…30VDC
CXG23/...27/...28
Mounting with front frame for screw mounting (delivered with counter)
www.saia-burgess.com saia-burgess Control Devices50 | 51
CXG 23, 28
Type CXG
Function 231 Time meter/short time meter, counting capacity 0...999.999232 Time meter with optocoupler output (NPN)281 Double time meter
Supply voltage M4 10...30 VDC
N
Ordering Reference
www.saia-burgess.comsaia-burgess Control Devices 50 | 51
CXEPreset hour meter
Electronic
CXECharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting Time base, quartz s. min. h Capacity, 999.999, or h:min:s programmable 99:99:99 Supply voltage, 11...30 VDC
CXE312M4L 1 preset value
CXE322M4L 2 preset value
LCD display preset value programmable resolution
flush mounting with clip
45 x 45 x 86
999.999, time units: h:min:s or s, min, h
LCD, backlight 9 mm high digit – counting 8 mm high digit – preset
11...30 VDC and 90...250 VAC
www.saia-burgess.com saia-burgess Control Devices52 | 53
Technical dataCounting capacity –999.999…999.999Preset 1 or 2 preset values (or batch counter), keyboard entry, output signal at zero or preset valueReset to zero or preset value; manual and/or electrical or automatic (reset impulse: min. length 5 ms)Display 7-segment LCD, backlight; counting value 9mm high, preset value 7mm high; status of the outputs;
with or without fixed decimal pointSupply voltage DC: 11…30V (Uin), residual ripple max. 2%
AC: 90…250V, ±10%, 50/60HzPower consumption max. 0.1A (DC) or 4VA (AC)Types of sensor contacts, voltage impulses, electronic sensors NPN/PNP (pull-up/pull-down input mode)Input voltage DC: Low 0…0.2 x Uin, High 0.6 x Uin…30V
AC: Low 0…4V, High 12…30VSensor supply AC: VS = 24VDC, –40%/+15%, max. 80mA, unregulatedOutputs relay, max. 3A/250VAC, or transistor (optocoupler), max. 15mA/30VDC, permanent signal or impulse signal
0.01…99.99sEMC/Interference immunity class B according EN 55011 or EN 50082-2Data protection min.10 yearsProtection class front IP 65Ambient temperature 0°C to +50°CMounting flush mounting, mounting by plastic spring clip or by front frame for 2 x M4 screws, any mounting positionConnections 2 x plug-in screw terminal connection for wires 0.2…2.5mm2
Connection diagram
Dimensions
CXE
Detailed information on programming and electrical connection isenclosed with the counter.
2) This output is only present in the version with 2 presets and can also beprogrammed as a break contact.
with front frame for screw mounting
www.saia-burgess.comsaia-burgess Control Devices 52 | 53
CXE
Type CXE
Function 321 1 preset value/output322 2 preset values/outputs323 relais output328 static output
Supply voltage M4 10...30 VDCB4 24 VAC, 50/60 HzC1 48 VAC, 50/60 HzV3 110...230 VAC, 50/60 Hz
Display N 7-segment LCDL 7-segment LCD with backlight
Ordering Reference
www.saia-burgess.comsaia-burgess Control Devices 54 | 55
Counters
Type Preferred Products Page
Electromechanical
Totalising CMB CMB072M4N2N0N00 56CMB072M1N2N0N00CMB062M4N1N0N46CMB062M1N1N0N46
Totalising CMA CMA152M4N0N0N00 59CMA152E1N0N0N00CMA062M4N0N0N00CMA062E1N0N0N00
Totalising CBG CBG072M4L0N0N00 62CBG052M4L0N0N00CBG152M4L0N0N00CBG156M4L0N0N00CBG072E1L0N0N00CBG052E1L0N0N00CBG152E1L0N0N00CBG156E1L0N0N00
Totalising CMM CMM081M4N2N0S00 64CMM161M4N2N0S00CMM361M4N2N0S00CMM081E1N4N0S00CMM161E1N4N0S00CMM361E1N4N0S00
Preset CMM CMM152M4S2N0V00 66CMM152E1S4N0V00CMM362M4S2N0V00CMM362E1S4N0V00
Electronic
Totalising CXB CXB382VGN2N0N00 69
Totalising CXG CXG201M4N 72CXG261M4N
Differential CXG CXG211M4N 74
Differential CXR CXR262VKN0N0N00 77
Preset CXP CXP326VGN0N0N00 80
Preset CXE CXE312V3L 82CXE322V3L
Preset CXD CXD212D5N0N0N00 85CXD212M4N0N0N00
Digital tachometers CXG CXG222M4N 88CXG251M4N
Digital tachometers CXD CXD212D5N0N0N00 91CXD212M4N0N0N00
Digital tachometers CXE CXE312V3L 94CXE322V3L
www.saia-burgess.com saia-burgess Control Devices56 | 57
CMBCounters
Electromechanical, totalising
CMBCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting with spring clip No reset Counting frequency 25 i/s
CMB072M1N2N0N00 7 digits 12V DC
CMB072M4N2N0N00 7 digits 24V DC
CMB062M1N1N0N46 6 digits 12V DC Shock resistant
CMB062M4N1N0N46 6 digits 24V DC Shock resistant
micro size for PCB machine solder washable
surface or PCB mounting flush mounting with clip snap-on DIN rail 35 mm
29 x 14 x 3527 x 35 x 1230 x 58 x 53
9.999.999
mechanical, 4 mm high digit optical
12 VDC, 24 VDC and 230 VAC
www.saia-burgess.comsaia-burgess Control Devices 56 | 57
Technical dataCounting capacity 9.999.999Counting direction counting upCounting frequency max. 25 i/s (counting impulse: min. length20 ms)
max. 10 i/s for CMB 079 E1 (counting impulse: min. length50 ms)Reset noneDisplay dials; white figures on black background, 1.2 x 4mm (optical)Supply voltage 12 VDC and 24 VDC, ±10%, residual ripple max. 48%
198…264 VAC, 50/60 HzPower consumption 250 mW (DC) or 0.8 VA (AC)Duty cycle 100%Types of sensor contacts, electronic sensors NPN/PNPLife expectancy min. 50 million impulsesEMC/Interference immunity according to EN 50082-2EMC/Emissions according to EN 55014Protection class front IP65 (flush mounting)Ambient temperature –10°C to +60°CMounting details see under dimensions, any mounting positionConnections details see under dimensions
CMB
www.saia-burgess.com saia-burgess Control Devices58 | 59
Dimensions
CMB 976: Surface mounting, plug-in on printed circuit board, machine solderable and washable
CMB 072: Flush mounting, mounting by plastic spring clip, connection with flexible leads of 150 mm length
CMB 079: Surface mounting, snap-on mounting on DIN rail 35 mm or mounting with 1 screwM4, connection with screw terminals for 2 x 2.5mm2 single wire
CMB 970: Surface mounting, plug-in on printed circuit board, machine solderable and washable
CMB
Technical data
Type CMB
Version 970 Machine solderable and washable, 7 Digit numbers, mounting on printed circuit board062 Standard, 6 Digit numbers, flush mounting072 Standard, 7 Digit numbers, flush mounting
Supply voltage M1 12 VDCM4 25 VDCE1 220...240 VAC
Counting N1 DC 10 i/sec or AC (all voltages)frequency N2 DC 25 i/sec (only 12 and 24 VDC)
NON00
Ordering Reference
www.saia-burgess.comsaia-burgess Control Devices 58 | 59
CMACounters
Electromechanical, totalising
CMACharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting with spring clip Counting frequency 10i/s
CMA152M4N0N0N00 5 digits, manual reset 24 VDC
CMA152E1N0N0N00 5 digits, manual reset 230 VAC
CMA062M4N0N0N00 6 digits, no reset 24 VDC
CMA062E1N0N0N00 6 digits, no reset 230 VAC
small size low current consumption
surface mounting with nut flush mounting with clamping spring
31 x 20 x 55 (50)
999.999 without reset 99.999 with reset
mechanical, 4 mm high digit
24 VDC and 230 VAC
www.saia-burgess.com saia-burgess Control Devices60 | 61
Technical dataCounting capacity 999.999 without reset
99.999 with resetCounting direction counting upCounting frequency max.10 i/s (counting impulse: min. length 50 ms)Reset to zero; none or manualDisplay dials; white figures on black background, 1.7 x 4 mmSupply voltage 24 VDC, ±10%, residual ripple max. 48%
198…264 VAC, 50/60 HzPower consumption 500 mW (DC) or 1.5 VA (AC)Duty cycle 100%Types of sensor contacts, electronic sensors NPN/PNPLife expectancy min. 50 million impulsesEMC/Interference immunity according to EN 50082-2EMC/Emissions according to EN 55014Protection class front IP 40Ambient temperature –10°C to +50°CMounting details see under dimensions, any mounting positionConnections flexible leads, length 150 mm
CMA
www.saia-burgess.comsaia-burgess Control Devices 60 | 61
Dimensions
CMA 062: Without reset, flush mounting, mounting with clamping spring
CMA 151: Manual reset, surface mounting, mounting with nut
CMA 152: Manual reset, flush mounting, mounting with clamping spring
CMA 061: Without reset, surface mounting, mounting with nut
CMA
Technical data
Type CMA
Function 061 Without reset, 6 digit numbers, surface mounting062 Without reset, 6 digit numbers, flush mounting152 With manual reset, 5 digit numbers, flush mounting
Supply voltage M4 24 VDCE1 220...240 VAC
NONO NOO
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices62 | 63
CBGCounters
Electromechanical, totalising
CBGCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting with spring clip
CBG072M4L0N0N00 7 digits no reset 24 VDC Grey housing
CBG052M4L0N0N00 5 digits no reset 24 VDC Grey housing
CBG152M4L0N0N00 5 digits manual reset 24 VDC Grey housing
CBG156M4L0N0N00 5 digits manual reset 24 VDC Black housing
CBG072E1L0N0N00 7 digits no reset 230 VAC Grey housing
CBG052E1L0N0N00 5 digits no reset 230 VAC Grey housing
CBG152E1L0N0N00 5 digits manual reset 230 VAC Grey housing
CBG156E1L0N0N00 5 digits manual reset 230 VAC Black housing
robust totalising counter, proven over many years
flush mounting with clamping spring
37 x 24 x 57
9.999.999 without reset 99.999 with reset
mechanical, 4 mm high digit
6, 12, 24, 110, 220 VDC 24, 115, 230 VAC
www.saia-burgess.comsaia-burgess Control Devices 62 | 63
Technical dataCounting capacity 9 999 999 without reset
99 999 with resetCounting direction counting upCounting frequency max. 15 i/s (DC supply)
max. 10 i/s (AC supply)Reset none, or ManualDisplay dials: white figures on black background, 4 mm high.Supply Voltage 6, 12, 24, 48, 110 and 220 VDC +/-10% residual ripple max 48%
24, 48, 115, 198…264VAC, 50/60 HzPower consumption 2,5W (DC) or 3,5VA(AC)Duty cycle 100%Type of sensors contacts, and NPN or PNP sensorsLife expectancy 40 x 106 impulsesProtection class front IP 40Ambient temperature –0°C to +50°CMounting any positionConnections 2.8 x 0.8 mm tags for push-on connectors
Dimensions
CBG
Type CBG
Function 05 no reset, 5 digits07 no reset, 7 digits15 with manual reset, 5 digits,
Mounting 1 surface mounting with mounting nut, grey housing2 flush mounting with clamping spring, grey housing3 flush mounting with 2 screws, black housing5 surface mounting with mounting nut, black housing6 flush mounting with clamping spring, black housing
Supply voltage L6 6 VDCM1 12 VDCM4 24 VDCN1 48 VDCN8 110 VDCP4 220 VDCB4 24 VACC1 48 VACD1 110…115 VACE1 220…240 VAC
Connection L tags K flexible leads
NONOO
Ordering Reference
1) with manual reset2) 1...4.5 mm clamping spring in position 1
4.5...6 mm clamping spring in position 2
www.saia-burgess.com saia-burgess Control Devices64 | 65
CMMCounter
Electromechanical, totalising
CMMCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting with spring clip
CMM081M4N2N0S00 8 digits no reset 24 VDC
CMM161M4N2N0S00 6 digits manual reset 24 VDC
CMM361M4N2N0S00 6 digits electrical reset 24 VDC
CMM081E1N4N0S00 8 digits no reset 230 VAC
CMM161E1N4N0S00 6 digits manual reset 230 VAC
CMM361E1N4N0S00 6 digits electrical reset 230 VAC
robust totalising counter with no, manual or electrical reset
surface mounting flush mounting with clamping spring
28 x 52 x 72
99.999.999 without reset999.999 with reset
mechanical, 4 mm high digit
12, 24 VDC and 24, 115, 230 VAC
www.saia-burgess.comsaia-burgess Control Devices 64 | 65
Technical dataCounting capacity 99 999 999 without reset
999 999 with resetCounting direction counting upCounting frequency max. 25 i/s (DC supply)
max. 18 i/s (AC supply)Reset none, manual, or manual and electricalDisplay dials: white figures on black background, 4mm high.Supply Voltage 12VDC and 24 VDC +/-10% residual ripple max 48%
198…264VAC, 50/60 HzPower consumption counting: 2W (DC) or 3VA(AC)
electrical reset: 9W (DC) or 12VA(AC)Duty cycle counting: 100%
electrical reset: 20%, max 1 minType of sensors contactsLife expectancy 200 x 106 impulsesEMC/ interference immunity according to EN 50082-2EMC/emissions according to EN 55014Protection class front IP 40Ambient temperature –10°C to +45°CMounting any positionConnections 2.8 x 0.8 mm tags for push-on connectors
Dimensions
CMM
Type CMM
Function 081 without reset, 8 digits, flush mounting161 with manual reset, 6 digits, flush mounting361 with electric and manual reset, 6 digits, flush mounting
Supply voltage M1 12 VDCM4 24 VDCB4 24 VACD1 110…115 VACE1 220…240 VAC
Count N2 max. 25 i/s (DC supply)frequency N4 max. 18 i/s (AC supply)
NONOO
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices66 | 67
CMMCounter
Electromechanical, Preset
CMMCharacteristics
Mounting
Dimensions (mm)
counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting with spring clip
CMM152M4S2N0V00 5 digits counting up, manual reset 24 VDC
CMM152E1S4N0V00 5 digits counting up, manual reset 230 VAC
CMM362M4S2N0V00 6 digits counting down, electrical reset 24 VDC
CMM362E1S4N0V00 6 digits counting down, electrical reset 230 VAC
up counting, manual reset down counting, manual and electrical reset
flush mounting with clip
52 x 52 x 72
99.999 CMM152999.999 CMM362CMM152 counting up with permanent display of the preset valueCMM362 counting down
mechanical, 4 mm high digit
24 VDC and 24, 115, 230 VAC
www.saia-burgess.comsaia-burgess Control Devices 66 | 67
Technical dataCounting capacity 99 999 CMM152
999 999 CMM362Counting direction counting up CMM152
counting down CMM362Counting frequency max. 25 i/s (DC supply)
max. 18 i/s (AC supply)Reset manual, (CMM152) or manual and electrical (CMM362)Display dials: white figures on black background, 4 mm high.Supply Voltage 24 VDC +/–10% residual ripple max 48%
198…264VAC, 50/60 HzPower consumption counting: 3W (DC) or 3VA(AC) CMM152
3W (DC) or 3VA(AC) CMM362electrical reset: 10W (DC) or 12VA(AC) CMM362
Duty cycle counting: 100%electrical reset: 20%, max 1 min
Type of sensors contactsLife expectancy 200 x 106 impulsesEMC/ interference immunity according to EN 50082-2EMC/emissions according to EN 55014Protection class front IP 40Ambient temperature -10°C to +45°CMounting any positionConnections pins dia 1,6 mm (CMM152)
or 2.8 x 0.8 mm tags (CMM362)
Dimensions
CMM
CMM 152
CMM 362
Type CMM
Function 152 counting up, with manual reset, 5 digits, flush mountingwith permanent display of the preset value
362 counting Down with electric and manual reset, 6 digitsflush mounting
Supply voltage M4 24 VDCB4 24 VACD1 110…115 VACE1 220…240 VAC
Count N2 max. 25 i/s (DC supply)frequency N4 max. 18 i/s (AC supply)
NONO NOO
Ordering Reference
CMM
www.saia-burgess.com saia-burgess Control Devices68 | 69
CXBCounter
Electronic, totalising
CXBCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
CXB382VGN2N0N00 Flush mounting with spring clip Counting capacity 99.999.999 Manual or electrical reset Counting frequency 18 i/s
www.saia-burgess.comsaia-burgess Control Devices 68 | 69
battery operated (lithium)
flush mounting with clamping spring screw mounting on front
45 x 22 x 40
99.999.999
LCD, 7 mm high digit
independent
www.saia-burgess.com saia-burgess Control Devices70 | 71
Technical dataCounting capacity 99.999.999Counting direction counting upCounting frequency type VH: max.30 i/s (counting impulse: min. length16ms) or max. 2500 i/s
(counting impulse: min. length 0.2 ms) selected by wiringtype VG: max. 18 i/s (counting impulse: min. length 28ms)
Reset to zero; manual and/or electrical (reset impulse: min. length 25 ms)Display 7-segment LCD, 7 mm highSupply and data protection independent by lithium batterie, life cycle up to 10 years at 20°CTypes of sensor type VH: contacts, electronic sensors NPN, voltage impulses
type VG: contacts, voltage impulsesInput voltage type VH: Low 0…0.7 VDC, High 3…30 VDC
type VG: Low <1 VDC/VAC High 5…240 VDC/VACEMC/Interference immunity according to EN 50081-1EMC/Emissions class B according to EN 55022Protection class front IP 65Ambient temperature –10°C to +60°CMounting flush mounting, mounting with clamping spring or by 2 screws and front frame, any mounting positionConnections type VH: flexible leads of 250mm length
type VG: screw terminals for wires 0.2…2.5mm2
Connection diagrams
CXB
Type VG
Type VH
www.saia-burgess.comsaia-burgess Control Devices 70 | 71
Dimensions
CXB
Type CXB382
Input voltage VG Voltage inputs 5...240 VDC/VACVH NPN-inputs 3...30 VDC
Couter N2 30 Hz and 2.5 kHzfrequency N6 18 Hz
NONOO
Ordering Reference
Type
VH
Type
VG
Technical data
www.saia-burgess.com saia-burgess Control Devices72 | 73
CXG 20, 26Counter
Electronic, totalising
CXG 20, 26Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting with spring clip Counting capacity 0...999.999 Counting direction upwards Reset to zero is selected Without output Supply voltage 24 VDC
CXG201M4N Totalising counter
CXG261M4N* Double totalising counter
*function switching with right-hand button
single, double or combi counter programmable
flush mounting with clip
45 x 22 x 59
999.999
LED, 8 mm high digit
10...30 VDC
www.saia-burgess.comsaia-burgess Control Devices 72 | 73
Type CXG
Function 201 Totalising counter261 Double totalising counter
Supply Voltage M4 10...30 VDC
N
Ordering Reference
CXG 20, 26
Technical dataCounting frequency max. 30 i/s (counting pulse min.5 ms) or 10000 i/sReset none, manual and/or electrical (reset pulse min. 5 ms)Display 7-segment LED, 8mm high suppression of preceding zeros with or without fixed decimal pointSupply voltage 10…30 VDC (Uin)Power consumption max. 50 mATypes of pulse generator contacts, voltage pulses, electronic transmitters NPN/PNP (pull-up or pull-down)Input voltage low 0…0.2 x Uin, high 0.6 x Uin…30 VDCInput resistance approx 10 kWOutput optocoupler, max. 30V/10 mAEMC/Interference immunity class B according to EN 55011 or EN 50082-2EMC/Emissions according to EN 55081-2Data protection EEPROM, min.10 years or 1 million memory cyclesProtection class front IP65Ambient temperature operation: –10°C to +50°C
storage: –25°C to +70°CMounting flush mounting, mounting by plastic spring clip or 2 x M4 screws, any mounting positionConnections screw terminals for 0.2…2.5mm2
Connection diagrams
Detailed information on programming and electrical connection is enclosed with counter.1) With optocoupler output
Reset Reset
INP Count input0V (GND) Supply voltage10…30VDC
CXG20/...26
Dimensions
Mounting with front frame for screw mounting (delivered with counter)
www.saia-burgess.com saia-burgess Control Devices74 | 75
CXG 21Counter
Electronic, differential
CXG 21Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
CXG211M4N Counting frequency 30 i/s Reset: none, manual or electrical Capacity 999.999 Without output
differential counter programmable
flush mounting with clip
45 x 22 x 59
–199.999...999.999
LED, 8 mm high digit
10...30 VDC
www.saia-burgess.comsaia-burgess Control Devices 74 | 75
CXG 21
Technical dataCounting frequency max. 30 i/s (counting pulse min.5 ms) or 10000 i/sReset none, manual and/or electrical (reset pulse min. 5 ms)Display 7-segment LED, 8mm high suppression of preceding zeros with or without fixed decimal pointSupply voltage 10…30 VDC (Uin)Power consumption max. 50 mATypes of pulse generator contacts, voltage pulses, electronic transmitters NPN/PNP (pull-up or pull-down)Input voltage low 0…0.2 x Uin, high 0.6 x Uin…30 VDCInput resistance approx 10 kWOutput optocoupler, max. 30V/10 mAEMC/Interference immunity class B according to EN 55011 or EN 50082-2EMC/Emissions according to EN 55081-2Data protection EEPROM, min.10 years or 1 million memory cyclesProtection class front IP65Ambient temperature operation: –10°C to +50°C
storage: –25°C to +70°CMounting flush mounting, mounting by plastic spring clip or 2 x M4 screws, any mounting positionConnections screw terminals for 0.2…2.5mm2
Connection diagrams
Detailed information on programming and electrical connection is enclosed with counter.1) With optocoupler output
Collector Output1)
EmitterReset/Set ResetINP B Input BINP A Input A0V (GND) Supply voltage10…30VDC
CXG21
www.saia-burgess.com saia-burgess Control Devices76 | 77
CXG 21
Dimensions
Type CXG
Function 211 Differential counter (with sign)212 Differential counter (with sign), with optocoupler output
Supply Voltage M4 10...30 VDC
N
Ordering Reference
Mounting with front frame for screw mounting (delivered with counter)
Technical data
www.saia-burgess.comsaia-burgess Control Devices 76 | 77
CXRCounter
Electronic, differential
CXRCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
CXR262VKN0N0N00 Flush mounting with spring clip Counting direction: up and down Capacity: -99.999...999.999 Manual or electrical reset (by selection) Counting frequency 30 i/s Supply voltage: 115...230 VAC
large display standard DIN housing
flush mounting with clip
90 x 42 x 105
999.999 h, min, s0.01 h or 0.01 s
LED, 13 mm high digit
11...30 VDC and 90...250 VAC
www.saia-burgess.com saia-burgess Control Devices78 | 79
Technical dataCounting capacity –99.999…999.999Counting direction counting up and down; counting input functions selected by DIL switches:
Counting frequency max. 30 i/s (counting impulse: min. length10 ms), 1000 i/s or 100000 i/s selected by DIL switches;programmable scaling factor 0.0001…99.9999
Reset to zero; manual and/or electrical selected by DIL switches (reset impulse: min. length5 ms)Display 7-segment LED, 13 mm high; selected with or without fixed decimal point by DIL switchesSupply voltage 11…30 VDC (Uin), residual ripple max. 5%
90…250 VAC, 50/60 HzPower consumption 14 W (24 VDC) or 15 VA (AC)Types of sensor contacts, voltage impulses, electronic sensors NPN/PNP
(pull-up or pull-down input mode selected by DIL switches)Input voltage DC: Low 0…0.2 x Uin, High 0.6 x Uin…30 V
AC: Low 0…4 V, High 8…30 VSensor supply AC: Vs = 24 VDC, ±10%, max.150 mAEMC/Interference immunity according to EN 50082-2EMC/Emissions class B according to EN 55011Data protection min.10 years (EEPROM)Protection class front IP 40Ambient temperature 0°C to +50°CMounting flush mounting, mounting by plastic spring clip, any mounting positionConnections 2 x plug-in screw terminal connection,
block X1 (main supply) for wires 0.2…2.5mm2, block X2 (inputs) for wires 0.14…1.5mm2
Connection diagrams
Dimensions
CXR
Change of counting direction
Differential counting
Rotational direction detector (phase sensing)single evaluation
Detailed information on programming and electrical connection is enclosed with the counter.
www.saia-burgess.comsaia-burgess Control Devices 78 | 79
CXR
Type CXR
Function 262 scaling factor 0.0001...99.9999 via keyboard, screw terminal
Supply voltage VK 115...230 VACVB 10...30 VDC
N0N0 N00
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices80 | 81
CXPCounter
Electronic, preset
CXPCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
CXP362VGN0N0N00 Capacity 999...999 Frequency 25 i/s 1 preset Supply voltage independent, 2 lithium batteries
1 preset value stationary display battery operated (lithium)
flush mounting with clip
45 x 45 x 86
–19.999...99.999
LCD, 7.5 mm high digit
independent
www.saia-burgess.comsaia-burgess Control Devices 80 | 81
Technical dataCounting capacity 999.999Counting direction counting up or counting down, programmableCounting frequency max. 25 i/s (counting impulse: min. length 20 ms)Preset 1 preset value, keyboard entryReset to zero or preset value; manual and/or electrical or automatic programmable
(reset impulse: min. length 50ms)Display 7-segment LCD, counting value 7 mm high, preset value 4mm high; status of the output; programmable
with or without fixed decimal pointSupply voltage independent, 2 lithium batteriesTypes of sensor voltage impulsesInput voltage 12…250 VDC/VACOutput max. 0.5A/230 VAC, relay, programmable as make or break contactEMC/Interference immunity according to EN 50082-2EMC/Emissions class B according to EN 55011Data protection 8 years lithium batteries, including voltage monitoringProtection class front IP54Ambient temperature –10°C to +60°CMounting flush mounting, mounting by plastic spring clip or by front frame CJ406 (accessory) for 2 x M4 screws, any
mounting positionConnections 1 x plug-in screw terminal connection for wires 0.2…2.5mm2
Connection diagram
Dimensions
CXP
1) Output programmable as make or break contactDetailed information on programming and electricalconnection is enclosed with the counter.
with front frame CJ406 for screw mounting
Type CXP
Function 362 1 preset value
Supply voltage VG Independent by lithium batteries
N0N0 N00
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices82 | 83
CXECounter
Electronic, preset
CXECharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Capacity 999.999 Supply voltage 110...240 VAC LCD with backlight Reset: manual, electrical or automatic Relay output Scaling factor 0.0001...9.9999 and gate time 0.01...99.99 s
CXE312V3L 1 preset
CXE322V3L 2 preset
1 or 2 preset values or batch function multifunction
flush mounting with clip
45 x 45 x 86
–999.999...999.999
LCD backlite, 9 mm high digit
12.5...30 VDC, 230 VAC
www.saia-burgess.comsaia-burgess Control Devices 82 | 83
Technical dataCounting capacity –999.999…999.999Preset 1 or 2 preset values (or batch counter), keyboard entry, output signal at zero or preset valueReset to zero or preset value; manual and/or electrical or automatic (reset impulse: min. length 5 ms)Display 7-segment LCD, back-lit; counting value 9mm high, preset value 7mm high; status of the outputs; with or
without fixed decimal pointSupply voltage DC: 11…30 V (Uin), residual ripple max. 2%
AC: 90…250 V, ±10%, 50/60 HzPower consumption max. 0.1 A (DC) or 4 VA (AC)Types of sensor contacts, voltage impulses, electronic sensors NPN/PNP (pull-up/pull-down input mode)Input voltage DC: Low 0…0.2 x Uin, High 0.6 x Uin…30V
AC: Low 0…4 V, High 12…30 VSensor supply AC: VS = 24 VDC, –40%/+15%, max. 80 mA, unregulatedOutputs relay, max. 3A/250VAC, or transistor (optocoupler), max. 15 mA/30 VDC, permanent signal or impulse signal
0.01…99.99 sEMC/Interference immunity class B according EN 55011 or EN 50082-2Data protection min.10 yearsProtection class front IP65Ambient temperature 0°C to +50°CMounting flush mounting, mounting by plastic spring clip or by front frame for 2 x M4 screws, any mounting positionConnections 2 x plug-in screw terminal connection for wires 0.2…2.5mm2
Connection diagram
Dimensions
CXE
Detailed information on programming and electrical connection is enclosed with the counter.2) This output is only available in the version with 2 presets and can also be programmed as a break contact.
with front frame for screw mounting
2)
www.saia-burgess.com saia-burgess Control Devices84 | 85
CXE
Type CXE
Function 312 1 preset value/output322 2 preset values/outputs
Supply voltage M4 10...30 VDCB4 24 VAC, 50/60 HzC1 48 VAC, 50/60 HzV3 110...230 VAC, 50/60 Hz
Display N 7-segment LCDL 7-segment LCD with backlight
Ordering Reference
www.saia-burgess.comsaia-burgess Control Devices 84 | 85
CXDCounter
Electronic, preset
CXDCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Function Tachometer Counting capacity 0...999.999 Output Relay Time unit 1 second Scaling factor 0.0001...99.999 Delay time 01...99.9 sec Counting frequency 10 kHz
CXD212D5N0N0N00 230 VAC, 50/60 Hz
CXD212M4N0N0N00 24 VDC
counting up and down reset to zero or preset value
flush mounting with clip
45 x 45 x 86
–19.999...99.999
7-segment LED
24 VDC, 230 VAC
www.saia-burgess.com saia-burgess Control Devices86 | 87
Technical dataCounting capacity –19.999…99.9992)
Preset 1 preset value, keyboard entry, output signal programmable at zero or preset valueReset to zero or preset value; manual and/or electrical or automatic programmable (reset impulse: min. length 5ms)Display 7-segment LED, 7.5mm high; programmable with or without fixed decimal pointSupply voltage 12.5…30 VDC (Uin), residual ripple max. 2%
207…253 VAC, 50/60HzPower consumption 2.5W (24VDC) or 4 VA (AC)Types of sensor contacts, voltage impulses, electronic sensors NPN/PNP (programmable pull-up/pull-down input mode)Input voltage DC: Low 0…0.2 x Uin, High 0.6 x Uin…30V
AC: Low 0…4 V, High 12…30 VSensor supply AC: Vs = 24 VDC, –40%/+15%, max. 80 mA, unregulatedOutput relay, max. 8A/250VAC (ohmic load), permanent signal or impulse signal programmable 0.01…99.98sEMC/Interference immunity according to EN 50082-2EMC/Emissions class B according to EN 55011Data protection min.10 years (EEPROM)Protection class front IP 54Approvals UL, C-ULAmbient temperature 0°C to +50°CMounting flush mounting, mounting by plastic spring clip or by front frame CJ406 for 2 x M4 screws, any mounting positionConnections 2 x plug-in screw terminal connection for wires 0.2…2.5mm2
2) Overrun or underrun by up to 1 decade without loss of counting impulses.
Connection diagram
Dimensions
CXD
Detailed information on programming and electrical connection is enclosed with the counter.
with front frame for screw mounting
www.saia-burgess.comsaia-burgess Control Devices 86 | 87
CXD
Type CXD
Function 212 1 preset value/output
Supply voltage M4 12.5...30 VDCD5 230 VAC
NONO NOO
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices88 | 89
CXG 22, 25Counter
Digital tachometers
CXG 22, 25Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Flush mounting with spring clip Counting capacity 0...999.999 Unit of time s or min Delay time 01.1...99.9 s None reset Supply voltage 24 VDC Output optocoupler
CXG222M4N Tachometer output optocoupler
CXG251M4N Totalising counter and tachometer* without output
*function switching with right-hand button
CXG22: tachometer/frequency counter CXG25: totalising counter and tachometer
flush mounting with clip
45 x 22 x 59
999.999 h, min, s0.01 h or 0.01 s
LED, 8 mm high digit
10...30 VDC
www.saia-burgess.comsaia-burgess Control Devices 88 | 89
Technical dataCounting frequency max. 30 i/s (counting pulse min.5 ms) or 10000 i/sReset none, manual and/or electrical (reset pulse min. 5 ms)Display 7-segment LED, 8 mm high, suppression of preceding zeros, with or without fixed decimal pointSupply voltage 10…30 VDC (Uin)Power consumption max. 50 mATypes of pulse generator contacts, voltage pulses, electronic transmitters NPN/PNP (pull-up or pull-down)Input voltage low 0…0.2 x Uin, high 0.6 x Uin…30 VDCInput resistance approx 10 kWOutput optocoupler, max. 30 V/10 mAEMC/Interference immunity class B according to EN 55011 or EN 50082-2EMC/Emissions according to EN 55081-2Data protection EEPROM, min.10 years or 1 million memory cyclesProtection class front IP65Ambient temperature operation: –10°C to +50°C
storage: –25°C to +70°CMounting flush mounting, mounting by plastic spring clip or 2 x M4 screws, any mounting positionConnections screw terminals for 0.2…2.5mm2
Connection diagrams
Dimensions
CXG 22, 25
Detailed information on programming and electrical connection is enclosed with counters.1) With optocoupler output
CollectorOutput for CXG221)
Emitter
INP Count input
0V (GND)Supply voltage
10…30VDC
CXG22/CXG25
Mounting with front frame for screw mounting (delivered with counter)
www.saia-burgess.com saia-burgess Control Devices90 | 91
CXG 22, 25
Type CXG
Function 221 Totalising counter222 Totalising counter with optocoupler output251 Totalising counter and tachometer
Supply Voltage M4 10...30 VDC
N
Ordering Reference
www.saia-burgess.comsaia-burgess Control Devices 90 | 91
CXDCounter
Digital tachometers
CXDCharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Preferred Range
Ordering Reference Characteristics
Function Tachometer Counting capacity 0...99.999 Output Relay Time unit 1 second Scaling factor 0.0001...99.999 Delay time 01...99.9 s Counting frequency 10 kHz
CXD212D5N0N0N00 230 VAC, 50/60Hz
CXD212M4N0N0N00 24 VDC
monitors revolutions/velocity flow rate control 1 limit value
surface mounting flush mounting with clamping spring
45 x 45 x 86
0...99.999
LED, 7.5 mm high digit
12.5...30 VDC and 230 VAC
www.saia-burgess.com saia-burgess Control Devices92 | 93
Technical dataCounting capacity 0…99.999Frequency range 0.01…10000 Hz max. 7500 Hz with dual evaluationScaling factor 0.001…9.999 and gate time 0.01…99.99 s programmableInput function counting up and down, programmable counting input functions:
Preset 1 limit value, keyboard entryReset to zero; none, manual and/or electrical programmable (reset impulse: min. length 5 ms)Display 7-segment LED, 7.5mm high; programmable with or without fixed decimal pointSupply voltage 11…30 VDC (Uin), residual ripple max. 2%
207…253 VAC, 50/60 HzPower consumption 2.5W (24 VDC) or 4 VA (AC)Types of sensor contacts, voltage impulses, electronic sensors NPN/PNP (programmable pull-up/pull-down input mode)Input voltage DC: Low 0…0.2 x Uin, High 0.6 x Uin…30V
AC: Low 0…4 V, High 12…30 VSensor supply AC: Vs = 24 VDC, –40%/+15%, max. 80 mA, unregulatedOutput relay, max. 3A/250VAC, permanent signal or impulse signal programmable 0.01…99.98sEMC/Interference immunity according to EN 50082-2EMC/Emissions class B according to EN 55011Data protection min.10 years (EEPROM)Protection class front IP 54Approvals UL, C-ULAmbient temperature 0°C to +50°CMounting flush mounting, mounting by plastic spring clip or by front frame CJ406 for 2 x M4 screws, any mounting
positionConnections 2 x plug-in screw-terminal connection for wires 0.2…2.5mm2
Connection diagram
CXD
Change of counting direction
Differential counting
Rotational direction detector (phase sensing) single or dual evaluation2)
Detailed information on programming and electrical connection is enclosed with the counter.
www.saia-burgess.comsaia-burgess Control Devices 92 | 93
Dimensions
CXD
Type CXD
Function 212 1 preset value/output
Supply voltage M4 12.5...30 VDCD5 230 VAC
NONO NOO
Ordering Reference
with front frame for screw mounting
Technical data
www.saia-burgess.com saia-burgess Control Devices94 | 95
CXECounter
Digital tachometers
CXECharacteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltages
Preferred Range
Ordering Reference Characteristics
Capacity 999.999 Supply voltage 110...240 VAC LCD with backlight Reset: manual, electrical or automatic Relay output Scaling factor 0.0001...9.9999 and gate time 0.01...99.99 s
CXE312V3L 1 preset
CXE322V3L 2 preset
multifunction 1 or 2 limit values
flush mounting with clip
45 x 45 x 86
999.999 h, min, s0.01 h or 0.01 s
LCD backlight, 9 mm high digit
11...30 VDC and 90...250 VAC
www.saia-burgess.comsaia-burgess Control Devices 94 | 95
Technical dataCounting capacity –999.999…999.999Frequency range 0.01…10000 Hz max. 7000 i/s with phase sensing, max.900 i/s with automatic reset max. 500 i/s with dual
evaluation and automatic resetScaling factor 0.0001…9.9999 and gate time 0.01…99.99 s Counting direction counting up and down, programmable counting input functions:
Preset 1 or 2 preset values (or batch counter), keyboard entry, output signal at zero or preset valueReset to zero or preset value; manual and/or electrical or automatic (reset impulse: min. length 5 ms)Display 7-segment LCD, backlight; counting value 9 mm high, preset value 7mm high; status of the outputs; with or
without fixed decimal pointSupply voltage DC: 11…30 V (Uin), residual ripple max. 2%
AC: 90…250 V, ±10%, 50/60 HzPower consumption max. 0.1 A (DC) or 4 VA (AC)Types of sensor contacts, voltage impulses, electronic sensors NPN/PNP (pull-up/pull-down input mode)Input voltage DC: Low 0…0.2 x Uin, High 0.6 x Uin…30 V
AC: Low 0…4 V, High 12…30 VSensor supply AC: VS = 24 VDC, –40%/+15%, max. 80 mA, unregulatedOutputs relay, max. 3A/250 VAC, or transistor (optocoupler), max. 15mA/30 VDC,
permanent signal or impulse signal 0.01…99.99 sEMC/Interference immunity class B according EN 55011 or EN 50082-2Data protection min.10 yearsProtection class front IP65Ambient temperature 0°C to +50°CMounting flush mounting, mounting by plastic spring clip or by front frame for 2 x M4 screws, any mounting positionConnections 2 x plug-in screw terminal connection for wires 0.2…2.5mm2
Connection diagram
CXE
Detailed information on programming and electrical connection is enclosed with the counter.1) This output is only available in the version with 2 presets and can also be programmed as a break contact.
PostScript Bild
D:\KUNDEN\SAIA\Katalog\IZ\CXE_e2.eps
Change of counting direction
Differential counting
Rotational direction detector (phase sensing)single or dual evaluation
www.saia-burgess.com saia-burgess Control Devices96 | 97
Dimensions
CXE
Type CXE
Function 312 1 preset value/output322 2 preset values/outputs
Supply voltage M4 10...30 VDCD5 90...250 VAC
Display N 7-segment LCDL 7-segment LCD with backlight
Ordering Reference
with front frame for screw mounting
Technical data
www.saia-burgess.comsaia-burgess Control Devices 98 | 99
Control Relays
Type Preferred Products Page
Analog KFE KFE 100NE1N 100KFE 101NE1NKFE 301NE9N
KFE 300NE9N 103
KFE 302NE9N 106
LCD KFE KFE 102NE1N 109KFE 103NE1N
Thermistor KFT100 KFT100JE1N 112KFT200 KFT200KE1N
www.saia-burgess.com saia-burgess Control Devices100 | 101
KFE 100/101/301Control Relays
Analog
KFE 100/101/301Characteristics
Mounting
Dimensions (mm)
Setting
Time range
Outputs
Supply voltage
Function control
Preferred Range
Ordering Reference Characteristics
Monitors/Control Supply voltage Setting Time range
KFE100NE1N over/under voltage 230 VAC, 50/60 Hz Umin 0.75 Un; Umax 1.2 Un 5 or 10 min
KFE101NE1N over/under voltage 230 VAC, 50/60 Hz Umin 0.8 Un; Umax 1.2 Un 5 or 10 min
KFE301NE9N over/under voltage 400 VAC, 50/60 Hz Umin 0.8 Un; Umax 1.2 Un 5 or 10 min
monitors over/under voltage mono fixed/adjustable mono/three phase: 5 or 10 min
snap-on DIN rail 35 mm
35 x 85 x 58
KFE 100: Umin 0.75 UN; Umax 1.2 UN (fix)KFE 101/301: Umin 0.8 UN; Umax 1.2 UN
5 or 10 min, selection by wire bridge or switch
1 relay (change-over contact); 8 A, 250 VAC
KFE 100/101: 230 VAC; 50/60 Hz; KFE 301: 400 VAC; 50/60 Hz; P ≤ 4 VA
fault and power supply LED
www.saia-burgess.comsaia-burgess Control Devices 100 | 101
Voltage: UnTolerancesDuty cycleConsumptionMax. length of supply cable:(capacity of cable10 nF/100 m)Display of available voltageMonitoring level of input signalsDelay time of output relay
Error display «def»Error storageRelay output, change-over
Circuit diagram
Dimensions
KFE 100/101/301
Monitoring air-conditioninginstallation, simple, 1-phaseKFE 100
230 VAC, 50/60 Hz0,75...1.2 Uncontinuous duty4 VA150 m
1 LED greenpermanentmin. 0.75 Un, max. 1.2 Un5 min or 10 min with externalbridge1 LED redno8 A, 250 VAC
Monitoring air-conditioninginstallation, 1-phaseKFE 101
230 VAC, 50/60 Hz0.8...1.2 Uncontinuous duty4 VA150 m
1 LED greenadjustable by potentiometermin. ±5% Un, max. ±20% Un5 min. or 10 min. with switch
1 LED redno8 A, 250 VAC
Monitoring air-conditioninginstallation, 3-phaseKFE 301
400 VAC, 50/60 Hz0.8...1.2 Uncontinuous duty4 VA150 m
1 LED greenadjustable by potentiometermin. ±5% Un, max ±20% Un5 min. or 10 min. with switch
1 LED redno8 A, 250 VAC
Technical data
www.saia-burgess.com saia-burgess Control Devices102 | 103
KFE 100/101/301
Type KFE 100/101/301
Functions 100 Single phase over/under voltage control relay for climate control compressors101 Single phase adjustable voltage control relay for climate control compressors301 Three phases adjustable voltage control relay for climate control compressors
Housing N 35 mm DIN
Supply voltage D1 115 VACE1 230 VACE9 400 VAC for KFE 301 only
Ordering Reference
www.saia-burgess.comsaia-burgess Control Devices 102 | 103
KFE 300Control Relays
Analog
KFE 300Characteristics
Mounting
Dimensions (mm)
Setting
Time ranges
Outputs
Supply voltage
Function control
Preferred Range
Ordering Reference Characteristics
Monitors/Control Supply voltage Setting Time range
KFE300NE9N Phase conrol 400 VAC, 50/60 Hz asymetry 5 to 20% 300 ms fix
monitors loss of phase control, phase order, phaseasymmetry and under voltage
snap-on DIN rail 35 mm
35 x 85 x 58
control asymmetry 5 to 20% under voltage phase order (fixed) loss of phase (fixed)
300 ms (fixed)
1 relay (change-over contact); 8 A, 250 VAC
400 VAC; 50/60 Hz; P ≤ 4 VA
phase fault, fault asymmetry and power supply LED
Voltage: UnTolerancesDuty cycleConsumptionMax. length of supply cable:(capacity of cable10 nF/100 m)Display of available voltageMonitoring level of input signals
Delay time of output relay
Error display «def»Display of error «Asymmetry»Error storageRelay output, change-over
Circuit diagram
Dimensions
KFE 300
Monitoring air-conditioninginstallation, 1-phaseKFE 300
400 VAC, 50/60 Hz0.8...1.15 Uncontinuous duty4 VA150 m
1 LED greenasymmetry by potentiometer–5% to –20%over voltage permanently 1.11 Unperm. T1 = 200 ms (at opening)perm. T2 = 300 ms (at closing)1 LED red1 LED yellow asyno8 A, 250 VAC
Technical data
www.saia-burgess.com saia-burgess Control Devices104 | 105
KFE 300
Type KFE
Functions 300 Three phase full control relay for motors
Housing N 35 mm DIN
Supply voltage E9 400 VAC, 50/60 Hz
Ordering Reference
www.saia-burgess.comsaia-burgess Control Devices 104 | 105
KFE 302Control Relays
Analog
KFE 302Characteristics
Mounting
Dimensions (mm)
Setting
Time ranges
Outputs
Supply voltage
Function control
Preferred Range
Ordering Reference Characteristics
Monitors/Control Supply voltage Setting Time range
KFE302NE9N Over/under voltage 400 VAC, 50/60 Hz Umin 0.8 Un; Umax 1.2 Un 0.1 to 12 s
www.saia-burgess.com saia-burgess Control Devices106 | 107
three phase surveillance of AC voltage
snap-on DIN rail 35 mm
35 x 85 x 58
Umin 0.8 UN Umax 1.15 UN (fix) memory option over voltage fix 1.15 UN
0.1 to 12 sec
1 relay (change-over contact); 8 A, 250 VAC
400 VAC; 50/60 Hz; P ≤ 4 VA
fault and power supply LED
Voltage: UnTolerancesDuty cycleConsumptionMax. length of supply cable:(capacity of cable10 nF/100 m)Display of available voltageMonitoring level of input signals
Delay time of output relay
Error display «def»Error storageRelay output, change-over
Circuit diagram
Dimensions
KFE 302
Voltage monitoring, 3-phaseKFE 302
400 VAC, 50/60 Hz0.8...1.15 Uncontinuous duty4 VA150 m
1 LED greenadjustable by potentiometer forlow voltage 5% to 20% Unover voltage permanently 1.15 Unadjustable by potentiometer0.1 s to 12 s1 LED redswitch selected8 A, 250 VAC
Technical data
www.saia-burgess.comsaia-burgess Control Devices 106 | 107
KFE 302
Type KFE
Functions 302 Three phase voltage control relay with memory
Housing N 35 mm DIN
Supply voltage E9 400 VAC, 50/60 Hz
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices108 | 109
KFE 102/103Control Relays
Digital
KFE 102/103Characteristics
Mounting
Dimensions (mm)
Setting
Time ranges
Outputs
Supply voltage
Function control
Preferred Range
Ordering Reference Characteristics
Monitors/Control Setting Time range Supply voltage
KFE102NE1N Voltage Umin 15 V; Umax 700 VDC / 480 VAC 0.1 to 12 s 230 VAC, 50/60 Hz– Hysteresis 5 to 50 %– Memory option
KFE103NE1N Current Imin 0,1 A; Imax 10 A AC/DC / 230 VAC, 50/60 Hz– Hysteresis 5 to 50 %– Memory option 0.1 to 12 (20) sec– Current transformer 50 / 5 to 600 / 5
www.saia-burgess.comsaia-burgess Control Devices 108 | 109
KFE 102 measures voltage AC/DC KFE 103 measures current AC/DC
snap-on DIN rail 35 mm
35 x 85 x 58
hysteresis 5 to 50% memory option KFE 102: Umin 15 V; Umax 700 VDC/480 VAC KFE 103: Imin 0.1 A; Imax 10 A AC/DC
KFE 102: 0.1 to 12 sec KFE 103: 0.1 to 12 (20) sec
1 relay (change-over contact); 8 A, 250 VAC
230 VAC; 50/60 Hz; P ≤ 4 VA
display
Voltage: UnTolerances: ACDuty cycleConsumptionMinimum reaction timeMaximum length of supply cable:(capacity of cable 10 nF/100 m)Max. cable length of inputsignal measurement cableImmunity to micro lossesof supply voltageMax. range of inputmeasurementsLevel of value to be measuredProgrammable hysteresisTime delay (t1)Time delay inhibition (t2)Error storageProgramming of parametersVisual display of parameters
Circuit diagram
Dimensions
KFE 102/103
Voltage monitoringKFE 102
230 VAC, 50/60 Hz0.85...1.15 Uncontinuous duty4 VA200 ms150 m
50 m
200 ms minimum
15 to 700 VDC15 to 484 VACas programmed in maximum input rangemax. 5 to 50% of defined level value0.1 to 12 snot applicableyes, with software programming, menu «Prog»with software menu via 2 buttons (set, select)with software menu View, by pressing «select» button
Current monitoringKFE 103
230 VAC, 50/60 Hz0.85...1.15 Uncontinuous duty4 VA200 ms150 m
50 m
200 ms minimum
0.1 to 10 ADC0.1 to 600 AAC (current converter)as programmed in maximum input rangemax. 5 to 50% of defined level value0.1 to 12 s0.1 to 20 syes, with software programming, menu «Prog»with software menu via 2 buttons (set, select)with software menu View, by pressing «select» button
Technical data
www.saia-burgess.com saia-burgess Control Devices110 | 111
KFE 102/103
KFE
Functions 102 Digital AC (single phase) or DC voltage control relay general purpose103 Digital AC (single phase) or DC current control relay general purpose
Housing N 35 mm DIN
Supply voltage D1 115 VACE1 230 VAC
Ordering Reference
www.saia-burgess.comsaia-burgess Control Devices 110 | 111
KFT 100/200Control Relays
Thermistor
KFT 100 200Characteristics
Mounting
Dimensions (mm)
Setting
Outputs
Supply voltage
Function control
Preferred Range
Ordering Reference Characteristics
Monitors/Control Supply voltage Setting Outputs
KFT100JE1N temperature 230 VAC, 50/60Hz automatic reset 1 relay (NO contact), 10A 250VAC
KFT200KE1N temperature/memory function 230 VAC, 50/60Hz manual/automatic reset 1 relay (changeover contact), 10A 250VAC
www.saia-burgess.com saia-burgess Control Devices112 | 113
temperature monitor PTC short circuit detection PTC broken wire detection reset by supply interruption
surface mounting snap on DIN rail 35 mm
22.5 x 75 x 96
automatic reset
1 relay (NO contact)10 A, 250 VAC
230 VAC; 50/60 Hz; P ≤ 3 VA
red LED for faultgreen LED for power supply
temperature monitor memory fonction PTC short circuit detection PTC broken wire detection reset by supply interruption
surface mounting snap on DIN rail 35 mm
22.5 x 75 x 96
manual or automatic reset
1 relay (change-over contact)10 A, 250 VAC
230 VAC; 50/60 Hz; P ≤ 3 VA
red LED for faultgreen LED for power supply
KFT100 KFT200temperature monitor temperature monitor, memory function
Voltage: Un 230 VAC, 50/60Hz 230 VAC, 50/60HzTolerances 0.85…1,15Un 0.85…1,15UnDuty cycle continuous cycle continuous cycleConsumption ≤ 3 VA ≤ 3 VAMinimum reaction time 100 ms 100 msMax. length of supply cable(capacity of cable 10nF/100m): 100 m 100 mMax. length of signal and reset cable: 40 m 40 mImmunity to micro losses of supply voltage: 200 ms minimum 200 ms minimumMemory function no yes, by memory slide switchInsulation characteristics 2.5kV AC/50Hz test voltage according VDE part 200 and 6kV surge voltage
according to IEC 60947-5-1EMC/Interface immunity surge capability of the power supply according to IEC 61000-4-5: 4kV
burst according to IEC 61000-4-4: 4kVESD according to IEC 61000-4-2: 8kVElectromagnetic HF field according to IEC 61000-4-3: 3V/m 80-1000MHZ and electromecanical HF signal fromwiring arrangement according to IEC 61000-4-6: 3V 0.15-80MHz
EMC/Emissions electromagnetic fields according to EN 55022, class BProtection class terminals IP 20
case IP 40Ambient temperature operation (enclosed) –20°C…+55°C
storage –40°C…+70°CMounting surface mounting: snap-on mounting on DIN rail 35 mm or screw mounting by adapter (accessory) and
2 screws M4, any mounting positionConnections screw terminals for 1 x 0.5 mm2 up to 2 x 2.5 mm2 (single wire )or 2 x 1.5 mm2 (multistrand with end sleeve),
AWG...20, with dual chamber system, screws M3.5 for Pozidrive no.2 (Philips) and no. 2 slot, suitable for power screwdrivers (max. 1.2 Nm), finger safe according to VDE 0106
Function control red LED for faultgreen LED for power supply
Circuit diagram
KFT 100/200
Technical data
KFT 100 KFT 200
www.saia-burgess.comsaia-burgess Control Devices 112 | 113
KFT 100/200
KFT
Functions 100 Thermistor relay 100200 Thermistor relay 200 with fault memory
Housing J 22.5mm, 6 screw mountingK 22.5mm, 12 screw mounting
Supply voltage D1 115 VACE1 230 VAC
N00
Accessories CJ260 Adapter for screw mounting
Ordering Reference
www.saia-burgess.com saia-burgess Control Devices114 | 115
Dimensions Timer Adapter for screw mounting
Energy Meter
Type Preferred Products Page
Single phase AAD1 AAD1D5E10KR2A00 118
www.saia-burgess.comsaia-burgess Control Devices 116 | 117
AAD1Energy Meter
Single phase
AAD1Characteristics
Mounting
Dimensions (mm)
Counting capacity
Display
Supply voltage
Function control
Preferred Range
Ordering Reference Characteristics
AAD1D5E10KR2A00 Single phase energy meter Class 1 25 A/230 VAC direct measuring SO+/SO– output 1000 imp/kWh
www.saia-burgess.com saia-burgess Control Devices118 | 119
single phase direct measurement class 1 precision PTB approval S0+/S0- output 1000 imp/kWh nominal current IN = 5 A, Imax 25 A according EN61036
surface mounting snap on DIN rail 35 mm
17.5 x 85 x 59
999.999.9
mechanical, 4 mm high digit decimal places in red
230 VAC, 50/60 Hz; P ≤ 8 VA
flashing red LED
Technical dataRated voltage (V) 230 VAC, single phase, 2 wire 50 Hz,tolerance –20%/+15%Approvals PTB Class 1 (1%)Rated current In (IMAX) 5 (25) AMinimum load current 20 mA according to precision class 1Ambient temperature –10°C...+45 (according to EN 61036, class 1)Open collector output (SO) optocoupler 30 V/20 mA max. and 5 V min.
impedance 100 Ωpulse duration 50 msoutput pulses 1000i/kWh
LED flashing red 2000i/kWhConsumption 8 VAInsulation characteristics 4 kV/50 Hz test according to VDE 0435
6 kV 1.2/50 ms surge voltage according to IEC 255-4Protection class II
EMC/Interference immunity 4 kV 1.2/50 ms surge voltage according to IEC 1000-4-5 on the mains1 kV 1.2/50 ms surge voltage according to IEC 1000-4-5 on the output SOBurst according to IEC 1000-4-4, level 4 (4 kV)ESD according to IEC 1000-4-2, level 3 (8 kV)
Protection class IP 50, connections IP 20Connections mains cable max. 6 mm2, output cable max. 2.5 mm2
Terminal screws mains M 4, output (SO) M3 pozidrive philips, flat no. 1Mounting DIN rail 35 mmOrder number AAD1D5E10KR2A00 (non calibrated)
AAD1D5E10KR1A00 (calibrated)Lead cover 4 104 7420 0
Connection diagram
AAD1
NEUTRAL
LOAD
www.saia-burgess.comsaia-burgess Control Devices 118 | 119
AAD1
Type AAD Energy Meter 25 A, class 1
Phases 1 1 phases/2 leaders
Rated voltage D5 230 V, 50 Hz
Rated current E 5(25)A
Output 1 SO+/– max. 30 V, 20 mA
Stream 0 1 : 1transformers
relationship
Impulse K 1000 imp/kWhinstallment /
S0 +/–
(fix) R
Precision 1 calibrated2 non calibrated
Ordering Reference
Dimensions
Technical data
www.saia-burgess.com saia-burgess Control Devices120 | 121