Upload
others
View
2
Download
1
Embed Size (px)
Citation preview
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 2 of 18
TABLE OF CONTENTS
1.0 INTRODUCTION ............................................................................................................................. 3
2.0 STANDARDS, CODES AND REGULATIONS ................................................................................ 4
3.0 CERTIFICATION .............................................................................................................................. 5
4.0 AREA CLASSIFICATION/ENVIRONMENT ................................................................................... 6
5.0 DRAWINGS AND SPECIFICATIONS ............................................................................................. 7
6.0 DESIGN REQUIREMENTS .............................................................................................................. 8
7.0 FABRICATION ............................................................................................................................... 13
8.0 TERMINATION ............................................................................................................................. 14
9.0 WIRING ......................................................................................................................................... 15
10.0 EARTHING .................................................................................................................................... 16
11.0 INSPECTION AND TESTING ....................................................................................................... 17
12.0 CRATING AND SHIPPING ........................................................................................................... 18
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 3 of 18
1.0 INTRODUCTION
This specification describes the minimum requirements for the assembly of an
electrical/instrumentation cabinet (out or inside room) and the fabrication of the cabinet itself.
Field cable marshalling, system power supplies and related racking, mounting and wiring
supports for installation in a system cabinet are also subject to this specification.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 4 of 18
2.0 STANDARDS, CODES AND REGULATIONS
All equipment specified herein shall conform in design, material and performance with the latest
editions (with amendments) of the following Codes and Standards current at time of order
placement.
2.1 Dutch rules for working environment (ARBO arbeidsomstandigheden wet).
Dutch Mine Regulations 31 October 2002 (Mijnbouw Wet, staatsblad 542).
Directive 94/9/EC (ATEX 95) Equipment and protective systems intended for use in potential
explosive atmospheres.
The latest CENELEC standards.
The Regulations of “Het Nederlandse Normalisatie Instituut“ (NEN) as applicable as such but
not limited to:
NEN 1010 Safety provisions for Low Voltage Installations.
NEN-EN-50110 Operation of electrical installations
EN 50014 Electrical apparatus for potentially explosive atmospheres.
thru
EN 50020 + Exclusive EN 50021 for EExn Equipment
EN 50028 +
EN 50039
IEC 60079-10 Electrical apparatus for explosive atmosphere – part 10: Classification of
hazardous areas
IEC 60079-14 Electrical apparatus for explosive atmosphere – part 14: Electrical installations
in hazardous areas
IEC 60079-17 Electrical apparatus for explosive atmosphere – part 17: Inspection and
maintenance of electrical installations in hazardous areas
IEC 60051 Recommendations for direct acting indicating electrical measuring
instruments and their accessories
IEC 60204-1 Electrical equipment of industrial machines
IEC 60529 Classification of degrees of protection provided by enclosures
VDE 0875 Regulations for the radio interference suppression of Appliances, Machines
and Installations for rated Frequencies from 0 to 20 kc/s
EMC International Electromagnetic Compatibility
EU Certification conform European Rules, including 'CE' marking
2.2 GENERAL SPECIFICATIONS
610 General Specification for General Construction of Electrical, Instrumentation
and Telecommunication installations.
Ж 612 General Specification for Instrument Inspection, Pre-commissioning and
Commissioning
525 General Specification for Painting and Coating.
Latest revision of above referenced specifications can be found on
https://www.neptuneenergy.com/en/about-us/supply-chain/suppliers-to-neptune-energy-
netherlands-bv
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 5 of 18
3.0 CERTIFICATION
Equipment located in hazardous areas shall be certified in accordance with ATEX directive
94/9/EC. Only equipment with certification issued by the notified bodies will be accepted.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 6 of 18
4.0 AREA CLASSIFICATION/ENVIRONMENT
The location of the plant is an offshore platform in the Dutch sector of the North Sea.
The following environmental conditions apply:
Protected area:
Area classification : non-hazard
Maximum temperature : +35 °C
Ж Daily average temperature : +20 °C
Minimum temperature : +10 °C
Relative humidity : up to 100%
Air quality : saline
Ж Degrees of Protection : IP-41
Unprotected area:
Area classification : hazard (Zone 0, 1, or 2)
Maximum temperature : +26 °C
Daily average temperature : +15 °C
Minimum temperature : -20 °C
Relative humidity : up to 100%
Air quality : saline and moist
Ж Degrees of Protection : IP-56
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 7 of 18
5.0 DRAWINGS AND SPECIFICATIONS
5.1 The following drawings shall be supplied by the system cabinet's supplier ('Supplier'), as a
minimum:
general arrangement of the panel(s)
termination diagrams, hook-up drawings, etc.
datasheets of each type of equipment installed on this panel
Bill of Material.
Ж 5.2 In general Supplier shall produce all new drawings as can be regarded practical to clarify
Installation details. These drawings shall be returned to Company's representative after
completion. All new drawings shall be formatted for AutoCAD 2006.
5.3 Supplier shall supply drawings as specified in the SDR (Supplier Document Requirements) for
the relevant specification. During the project Supplier shall keep an up-to-date record of all
changes in the installation and show these changes on the relevant drawings. Buyer shall have
access to these documents at all times.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 8 of 18
6.0 DESIGN REQUIREMENTS
6.1 The system cabinet shall be configured in accordance with the requirements as specified herein.
However, Supplier shall be responsible for the proper working of the system.
6.2 No deviations from the requirements of this specification are allowed unless itemised in
Supplier's quotation and subsequently approved in writing.
6.3 Should any conflict occur as a result of complying with the specification, the order of
precedence shall be as follows:
this specification;
national standards.
6.4 CABINET REQUIREMENTS
The installation of wiring, piping and tubing, etc. in the cabinet(s) shall be in accordance with
industrial standard's neat and good working practice and shall be arranged such as to allow for
easy removal and/or maintenance of installed equipment and instruments.
The cabinet shall be executed as a complete enclosure and shall be provided with internal iron
angle or channel frame work of sufficient strength to support the internal system.
The cabinet shall be constructed as follows:
Outdoor installation:
The panels shall be made of 316L stainless steel plate, thickness minimum 3 mm.
Ж The carbon steel framing supports and other construction parts shall be anti-corrosion treated
and painted in accordance with Buyer’s Painting and Coating Specification (number 525, latest
edition). The enclosure classification shall be minimum IP-56.
Generally, all material shall be selected suitable for the environment conditions as described in
section 4 of this specification
Ж Indoor installation:
The panels shall be made of mild steel plate, thickness minimum 3 mm for the front plate to
receive panel mounted instruments. The panels shall be reinforced against buckling.
The enclosure classification shall be IP-41 as a minimum.
The cabinet(s) shall be provided with front and/or back access door(s) mounted on hinges. The
door(s) shall have "T" type door handles without locks.
The cabinet(s) shall be furnished with proper mounting assembly suitable for mounting in the
specified area/location. A plinth, minimum 100 mm, shall be provided for free-standing type
cabinet(s). For wall mounting type, the cabinet(s) shall be provided with the suitable mounting
brackets assembly.
The cabinet(s) shall also be provided with lifting eyes on the top of the cabinet for lifting
purposes.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 9 of 18
Cable entries, such as MCT's (multi cable transit), Ex'd' cable glands and bulkhead connectors,
etc. for interfaces with other systems, shall also be part of this system cabinet. Buyer will advise
the size and numbers of the entries which have interfaces with Buyer's systems.
Ж Before shipment all cable entries shall be covered, providing IP-41 degree of protection.
6.5 POWER SUPPLY
Depending on the project specification, the following power supply systems are available on
the platform:
Ж Electrical supply:
a) 24V DC
b) 48V DC
c) 120V DC
d) 220V/230V AC 50 Hz
e) 380V/400V AC 50 Hz
Air supply:
Dry air with minimum/normal/maximum pressure of: 4/6/10 Barg.
Hydraulic supply:
As per project specification.
Ж For electrical services, the cabinet shall be provided with terminals to receive the required power
supplies. This power distribution system shall be furnished with a pad lockable main switch. If
required, sub-distribution by means of circuit breakers shall be incorporated. Buyer will provide
the power supply to the cabinet/panel terminals.
The cabinet shall also be provided with a service lighting fixture and socket outlet connected to
230V AC power supply. Furthermore a drawing pocket shall be installed.
Details of the power consumption of the cabinet shall be provided to enable Buyer to calculate
the required size of the power supply cables and fuses.
Ж 6.6 ELECTROMAGNETIC COMPATIBILITY (EMC)
All equipment and installations shall comply with the electromagnetic compatibility
requirements both in emission and immunity.
As a consequence the two main aspects of EMC arise:
Electromagnetic emission (Radiated or Conducted Emission)
Devices have to be designed in a way that emitting electromagnetic disturbances do not
interfere with the process control systems, operation of radio, telecommunication and other
devices in accordance with their purpose.
Electromagnetic immunity/interference (Radiated or Conducted Susceptibility)
Devices have to be designed in a way that they have adequate immunity to electromagnetic
interferences and operation in accordance with their purpose is possible.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 10 of 18
To comply with EMC the above mentioned aspects have to be observed during the construction
of electrical, instrumentation and telecommunication installations.
Attention shall be given to:
Devices designed and constructed to fulfil the demands of EMC. No changes shall be made at
the construction these devices. As example variable speed drives.
Cables connected to these devices shall be suitable (screening) to fulfil the Electro Magnetic
Compatibility.
Connection of cables to these devices. Prescription of manufacturer has to be followed. When
cables are connected wrongly the device will no longer be Electro Magnetic Compatible.
When cables enter a device through a multi cable transit, this multi cable transit shall be
suitable to fulfil the demands of MCT.
Neptune Energy standard is Roxtec EMC sealing system.
The modules (blocks) contain a conductive foil which establishes a full 360o low transfer
impedance contact with the cable screen.
The frames shall be constructed of stainless steel to make contact with the conductive foil of
the modules.
6.7 COOLING
Cooling shall be adequate for the environment as detailed in Section 4.0. It is Supplier's
responsibility to provide heat dissipation calculations showing that the temperature inside the
cabinet does not exceed 40°C under the maximum load conditions at maximum ambient
temperature. When applicable, Supplier shall supply a forced cooling ventilation system to be
installed in the system.
6.8 SPARAGE
Wire and cable trunking and/or supporting shall have a minimum of 25% spare capacity on
completion, including known future installations.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 11 of 18
Ж 6.9 TUBING AND FITTINGS
For all tubing and fitting connections and supporting see general specification 610 section 8.3.
All incoming and outgoing tubing shall be connected to bulkhead couplings. The bulkhead
coupling shall be tagged with tube number and service/function.
All tubing shall be of 904-L stainless steel, imperial sized (inch), and shall be selected for the
applicable pressure ratings specified and sized adequately for the required capacity and duty.
Tubing shall be in compliance with the following:
Material : ASTM B 677 Grade TP 904-L.
Execution : Seamless, Bright annealed.
Hardness : HRB-80 max.
Marking : Material grade, heat number, O.D. and W.T.
: Marking to be free of chlorides, zinc, lead or copper.
Thickness : As a minimum 0.049” W.T. shall be used.
Certification : According to EN 10204/3.1.B.
Manufacturer : As per preferred Suppliers list of general specification 610.
Installation : For installation of tubing refer to chapter 8.3 of general specification 610.
All fittings shall be of 316-L stainless steel, imperial sized (inch/NPT), and shall be selected for
the applicable pressure ratings specified and sized adequately for the tubing described above.
Contractor shall insure that all instrument fitters are certified for “Swagelok” twin ferrule fittings.
All tube connections shall be inspected by a third party invited by Company.
Fittings shall be manufactured by Swagelok.
All bolts, nuts and washers shall be stainless steel A4
As sealant material, Teflon tape or SWAK shall be used.
The tubing shall be secured to the tray with "STAUFF" type PP-ACHV (black) fastening blocks at
(maximum) 0.6 metres intervals. Blocks with stainless steel cover plates, bolts and nuts shall be
delivered and supplied by the Contractor. To prevent corrosion between the “Stauff” blocs and
the SS tubing Molykote 111 shall be applied on top and bottom “Stauff” bloc before the
installation of the top “Stauff” bloc .After fastening the bulging should be removed.
This shall be done on all “Stauff” blocs (e.g. process, instrument air and hydraulic tubing).
The contractor shall ensure that all “Stauff” blocks (incl. Neptune Energy supplied items) shall
be kept clean and free of dirt, dust and blasting grid during fabrication, Neptune Energy shall
have the right to supervise the preventive measures and precautions carried out by contractor
In case of any doubt “Stauff” blocks shall be reinstated by contractor.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 12 of 18
6.10 PAINTING
The cabinet shall have standard finish and painted 'grey' in accordance with RAL 7035. Painting
shall be in accordance with Manufacturer's Standard.
Supplier shall include in his supply sufficient primer and finish paint to repair approximately 5
percent of the surface of the equipment, at site, in case of damage (minimum quantity 1 kg).
Stainless steel cabinet for outdoor use shall be painted in compliance with Buyer’s Painting and
Coating specification (525, latest revision).
6.11 IDENTIFICATION
Supplier shall furnish one white nameplate, fixed to the cabinet, in black letters, stating the tag
number of the cabinet, description, manufacturer, year, power supply, order number, name
Supplier.
Instrument nameplates shall be made of corrosion resistant weatherproof material with black
letters with a minimum height of 5 mm on a white background. Inscription shall be in the English
language.
Permanent nameplates shall also be provided identifying each instrument, instrument switch,
meter, relays, control switch, indication lights, etc. in accordance with IEC regulations.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 13 of 18
7.0 FABRICATION
7.1 Conventional industry standards shall be followed in the assembly and a good workmanship
used in fabricating this cabinet. Supplier shall use a quality control method to assure that the
cabinet is assembled and wired in accordance with the drawings.
7.2 A connection function check shall be made on a 100% basis before the cabinet is
energised/pressurised. The unit shall be cleared of all defects before presenting it to Buyer for
acceptance.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 14 of 18
8.0 TERMINATION
Ж 8.1 Input/output terminals shall preferably be Phoenix-Contact of the Clip line series and shall be
fitted to terminal rails located on a mounting plate in the cabinet. I.S. terminals shall be coloured
blue. There shall be a physical segregation between the I.S. circuits and the non-I.S. circuits in
the cabinet in accordance with the applicable standards. All terminals shall be elevated at least
30 mm from the terminal rails.
8.2 Terminals for voltage levels >50V AC or 120V AC shall be physically segregated from all other
terminals and shall be fitted with a personnel protection cover clearly labelled.
8.3 Terminals shall be of the non-self loosening type, shall be nickel plated and only accept one
wire. Terminals to accommodate wiring by others shall be sized to accept 1.5 mm² wires for
signal cables and wires of a minimum 4 mm² for power cables. The terminals shall be of a
separation type whereby the input circuit can be separated from the other circuit without
shutdown the system.
8.4 Sockets and terminals for input/output connections shall be arranged and labelled according
to the documents and drawings provided by Buyer with Purchase Order. Each shall be identified
by a securely fixed label which is clearly visible after site cabling is complete.
8.5 Cable screens of instrument cables are to be connected to the instrument earth bar which shall
be supplied and installed by the cabinet Supplier. All earth connections within Supplier's scope
of responsibility shall be made and shall be suitable and in accordance with the system
requirements. Note that earth bars for I.S. and non-I.S. earth connections shall be separately
installed within the cabinet, as detailed in section 10.
8.6 All powered outputs to solenoid valves, indicating lamps and the like shall be fused on the
positive side of the power supply.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 15 of 18
9.0 WIRING
Ж 9.1 All wires within the panel that are connected to terminal strips used for convenience in internal
wiring, or wires terminating on device terminals not otherwise marked, and wires terminating
on terminal strips for external connections shall be marked with permanent type wire markers
bearing the number of the terminal row and/or the device terminal to which it is connected.
Wire markers shall be of the interlockable type. Thermal Transfer Technology can be used to
print on heat shrinkable sleeves or ribbons.
Wires connected to terminal rows shall be marked with terminal row/terminal number.
Wires connected to relays, plc’s, circuit breakers, etc. shall be marked with the numbers of the
relevant devices.
9.2 All control wiring within the panel shall be of stranded wire 0.5 mm² with an insulation rating of
500V and a minimum of 2.5 mm² for power busses.
9.3 Wire pins make AMP-pidg or bootlace ferrules shall be used.
9.4 Systems operating at different voltage levels are to be fully segregated.
9.5 Wiring to the swing-out rack(s) and door(s) shall be properly secured in wire looms by using
spiral lacing or equal.
9.6 All intrinsically safe equipment and wiring shall be segregated. Overall insulating sheath of
intrinsically safe wiring shall be blue. Trunking shall also be segregated and coloured blue.
9.7 Internal wiring shall be by single core, insulated wires, with the following colours:
black colour - AC/DC wiring, power supplies
grey colour - electronic signal, incoming and outgoing contacts
blue colour - intrinsically safe wiring
9.8 Wiring shall be housed in a system of plastic wireducts. A separate duct is required for the
following:
AC wiring, power supply, incoming and outgoing contacts (grey colour)
Electronics signal wiring (grey colour)
Intrinsically safe wiring (blue colour)
A 50 mm distance is required between the intrinsically safe wiring and the other wiring types.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 16 of 18
10.0 EARTHING
10.1 Where a number of electrical components are to be earthed, parallel earthing shall be employed
and not series looping of equipment.
10.2 On equipment, earth conductor connections, which are regularly disconnected for maintenance
of the equipment, shall be made with screw type solderless connectors. Other connections shall
be made with crimp type connectors.
10.3 Bolted earth connections shall be made with corrosion-proof materials with spring washers
and/or locknuts fitted.
10.4 When equipment earthing or bonding jumpers are not bare copper but insulated, the colour of
the insulation shall be yellow/green.
10.5 Minimum size of earth conductors shall be 2.5 mm² (for safety grounding).
10.6 An isolated earthbar (clean or instrument earth) and a non-isolated earthbar (dirty or plant
earth) to which equipment earthing is connected shall be supplied. The earthbars shall be
supplied with bolts and washers size M10 to accommodate Buyer's external earth connections.
Screens, armouring and earth wires of instrument cables shall be connected to an isolated earth
bar, cabinets and power cable armouring shall be connected to a non-isolated earth bar.
10.7 All electrical joints made for earthing shall be accessible and checked for tightness and electrical
contact (clean, not corroded).
10.8 Instrument earth wire and sleeving shall be coloured yellow/black and dirty earth wire and
sleeving shall be coloured yellow/green.
10.9 Removable parts (e.g. links to doors) shall be earthed by means of a flexible earth wire with
yellow/green insulation.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 17 of 18
11.0 INSPECTION AND TESTING
11.1 Buyer's representative and/or Certifying Authorities representatives shall have the right of
access to the units at any time during fabrication, to ensure that the materials and workmanship
are in accordance with this specification, the applicable drawings and design codes, and that
fabrication is being performed to the required standard.
11.2 The responsibility for inspection and testing rests with Supplier. Supplier shall notify Buyer in
writing with a minimum of ten (10) days before any testing, enabling Buyer's representative to
be present to witness such tests.
Buyer reserves the right to witness such inspections and testing, which are necessary to achieve
certification/documentation requirements.
Inspection and/or witnessing of tests and release of units for shipment shall in no way relieve
Supplier of any responsibilities and guarantees as to the provisions of this specification.
Written permission must be obtained for any phase of inspection or testing to be waived.
11.3 Supplier shall provide a detailed test procedure for Buyer's review and approval at least four(4)
weeks prior to Supplier's test programme. The test programme shall ensure that all the testing
required is identified, performed and documented. The tests to be carried out shall include, but
not be limited to, the following:
Mechanical check on proper installation, nameplates engraving for insulation, damage,
accessibility of installed equipment, compliance to the specification.
Electrical circuits shall be checked for continuity, insulation testing within the voltage extremes
and earth fault.
A full functional test of the complete system using approved simulating devices. Supplier
shall provide all temporary wiring, required to perform a complete functional test.
11.4 Factory Acceptance Test
Supplier shall present a fault free system for the Factory Acceptance Test (FAT) to Buyer or
Buyer's representative. The FAT procedure shall include the handing over of all records made
during the construction period such as test results, list of changes, 'as-built' drawings,
calibration certificates and any other relevant documentation. The tests shall be fully
documented and recorded including any equipment failures, repairs or replacement, in the
Manufacturer's Record Book.
Any malfunctions of equipment shall be rectified and retested, at Supplier's expense and to the
satisfaction of Buyer, as part of the testing.
Sufficient time, ample space and necessary assistance shall be provided by Supplier to ensure
inspection and testing to the satisfaction of Buyer or his representative.
Neptune Energy Netherlands B.V.
Specification 611 rev. 7 Page 18 of 18
12.0 CRATING AND SHIPPING
After the cabinet has been checked in Supplier's workshop and is found to be to Buyer's
satisfaction, Supplier shall prepare the cabinet for shipment.
Ж Packing and protection shall be sufficient to protect the cabinet and its contents for a period of
3 months when stored in an unheated warehouse following delivery.
Special attention shall be taken when equipment is shipped to an offshore location, the package
shall than be seaworthy as per requisition.
In general, the mounted instruments can remain in the cabinet if shipping instructions by the
instrument manufacturer are followed and moving parts are secured and kept from vibrating
during transit.
Fragile parts shall be packaged separately in sturdy boxes with suitable shock absorbing
material to prevent these items from being crushed or jarred during transit.